EDUS041820A
Split TypeAir Conditioners
FTXR-T Series
1. Power Supply ..............................................................................................32. Functions.....................................................................................................43. Specifications ..............................................................................................54. Dimensions .................................................................................................8
4.1 Indoor Unit.................................................................................................... 84.2 Outdoor Unit ................................................................................................. 9
5. Wiring Diagrams........................................................................................105.1 Indoor Unit.................................................................................................. 105.2 Outdoor Unit ............................................................................................... 11
6. Piping Diagrams........................................................................................126.1 Indoor Unit.................................................................................................. 126.2 Outdoor Unit ............................................................................................... 13
7. Capacity Tables ........................................................................................147.1 Capacity Correction Factor by the Length of Refrigerant Piping
(Reference) ................................................................................................ 23
8. Operation Limit..........................................................................................249. Sound Level ..............................................................................................25
9.1 Measuring Location .................................................................................... 259.2 Indoor Unit.................................................................................................. 269.3 Outdoor Unit ............................................................................................... 28
10.Electric Characteristics..............................................................................3011.Installation Manual ....................................................................................31
11.1 Indoor Unit.................................................................................................. 3111.2 Outdoor Unit ............................................................................................... 45
12.Operation Manual......................................................................................6913.Optional Accessories ..............................................................................104
13.1 Option List ................................................................................................ 10413.2 <BRC944B2> Wired Remote Controller................................................... 105
Heat Pump
FTXR09TVJUWFTXR09TVJUSFTXR12TVJUWFTXR12TVJUSFTXR18TVJUWFTXR18TVJUS
RX09RMVJU9RX12RMVJU9RX18RMVJU9A
Split Type Air Conditioners FTXR-T Series 1
EDUS041820A
13.3 <BRCW901A03/08> Wired Remote Controller Cord ............................... 11913.4 <BRP072A43> Wireless LAN Connection Adaptor.................................. 12013.5 <KRP413BB1S> Wiring Adaptor for Timer Clock /
Remote Controller .................................................................................... 12813.6 <DCS302C71> Central Remote Controller .............................................. 13213.7 <DCS301C71> Unified ON/OFF Controller.............................................. 16313.8 <DST301BA61> Schedule Timer Controller ............................................ 17013.9 <KRP928BB2S> Interface Adaptor for DIII-NET
(Residential Air Conditioner) .................................................................... 18913.10<KPW937E4> Air Direction Adjustment Grille ......................................... 19213.11<KPW063A4> Air Direction Adjustment Grille ......................................... 19413.12<KKG067A41> Back Protection Wire Net ............................................... 19613.13<KKG063A42> Back Protection Wire Net ............................................... 19713.14<FTDBHMS, FTDBHML, KEH067A41E, KEH063A4E>
Drain Pan Heater...................................................................................... 19813.15<KPS067A41> Snow Hood (Intake Side Plate)....................................... 20413.16<KPS067A42> Snow Hood (Intake Rear Plate) ...................................... 20613.17<KPS067A44> Snow Hood (Outlet) ........................................................ 20813.18<KPS063A41> Snow Hood (Intake Side Plate)....................................... 21013.19<KPS063A44> Snow Hood (Intake Rear Plate) ...................................... 21213.20<KPS063A47> Snow Hood (Outlet) ........................................................ 214
2 Split Type Air Conditioners FTXR-T Series
EDUS041820A Power Supply
1. Power Supply
Note: Power Supply Intake; Outdoor Unit
Indoor Unit Outdoor Unit Power Supply
FTXR09TVJUWRX09RMVJU9
1 phase, 208 - 230 V, 60 Hz
FTXR09TVJUS
FTXR12TVJUWRX12RMVJU9
FTXR12TVJUS
FTXR18TVJUWRX18RMVJU9A
FTXR18TVJUS
Split Type Air Conditioners FTXR-T Series 3
Functions EDUS041820A
2. Functions
Category Functions
FT
XR
09/1
2/18
TV
JUW
(S)
RX
09/1
2RM
VJU
9R
X18
RM
VJU
9A Category Functions
FT
XR
09/1
2/18
TV
JUW
(S)
RX
09/1
2RM
VJU
9R
X18
RM
VJU
9A
Basic Functions
Inverter (with inverter power control) Health & Cleanliness
Titanium apatite deodorizing filter
Operation limit for cooling Refer toP. 24
Mold proof air filter
Operation limit for heating Wipe-clean flat panel
PAM control Washable grille —
Standby electricity saving — MOLD PROOF operation —
Compressor Oval scroll compressor — Good-sleep cooling operation —
Swing compressor Timer WEEKLY TIMER operation
Rotary compressor — Count up-down ON/OFF timer —
Reluctance DC motor 24-hour ON/OFF TIMER
Comfortable Airflow
Power-airflow flap — NIGHT SET mode
Power-airflow dual flaps Worry Free (Reliability & Durability)
Auto-restart (after power failure)
Power-airflow diffuser — Self-diagnosis (R/C)
Wide-angle louvers Anti-corrosion treatment of outdoor heat exchanger
Auto-swing (up and down)
Auto-swing (right and left) Flexibility Multi-split/split type compatible indoor unit
3-D airflow Chargeless 32.8 ft
(10 m)COMFORT AIRFLOW operation
Comfort Control
Auto fan speed Either side drain (right or left)
Indoor unit quiet operation Power selection —
NIGHT QUIET mode (automatic) — Low outdoor temperature cooling operation (–15°C) (5°F)
OUTDOOR UNIT QUIET operation (manual)
INTELLIGENT EYE operation (auto energy saving) Low outdoor temperature cooling operation
(–20°C) (–4°F)
2-area INTELLIGENT EYE operation (comfort) °F/°C changeover R/C temperature display (factory setting: °F)
Quick warming function (preheating operation)
Hot-start function Remote Control
Wireless LAN connection (option)
Automatic defrosting Remote control adaptor(normal open pulse contact) (option)
Fan stop when thermo-off in cooling
Operation Automatic cooling/heating changeover Remote control adaptor (normal open contact) (option)
Program dry function
Fan only DIII-NET compatible (adaptor) (option)
Lifestyle Convenience
POWERFUL operation (inverter) Remote Controller
Wireless
HOME LEAVE operation — Wired (option)
ECONO operation
Indoor unit ON/OFF button
Multi-colored indicator lamp
Multi-colored lamp brightness setting
Signal receiving sign
R/C with back light
Temperature display —
Note: : Available— : Not available
Requires wind baffle and field settings
4 Split Type Air Conditioners FTXR-T Series
EDUS041820A Specifications
3. Specifications60 Hz, 208 - 230 V
Notes: 1. SL: The Quiet fan level of the airflow rate setting.2. When connected with multi-system outdoor unit, refer to the specifications of the multi outdoor unit to be
connected.3. The data are based on the conditions shown in the table below.
ModelIndoor Unit FTXR09TVJUW FTXR09TVJUS
Outdoor UnitRX09RMVJU9 RX09RMVJU9
Cooling Heating Cooling HeatingCapacity Rated (Min. ~ Max.) Btu/h 9,000 (4,500 ~ 10,600) 10,000 (4,100 ~ 14,600) 9,000 (4,500 ~ 10,600) 10,000 (4,100 ~ 14,600)
Running current A 4.28 - 3.87 3.83 - 3.46 4.28 - 3.87 3.83 - 3.46Power Consumption (Rated) W 819 733 819 733Power Factor (Rated) % 92.0 - 92.0 92.0 - 92.1 92.0 - 92.0 92.0 - 92.1EER (Rated) Btu/h·W 11.00 — 11.00 —COP (Rated) W/W — 4.00 — 4.00SEER / HSPF 18.00 9.30 18.00 9.30
Piping ConnectionsLiquid in. (mm) 1/4 (6.4) 1/4 (6.4)Gas in. (mm) 3/8 (9.5) 3/8 (9.5)Drain in. (mm) 11/16 (18) 11/16 (18)
No. of Wiring Connection 3 for Power Supply, 4 for Interunit Wiring (Including Ground Wiring)
3 for Power Supply, 4 for Interunit Wiring (Including Ground Wiring)
Max. Interunit Piping Length ft (m) 65.6 (20) 65.6 (20) Max. Interunit Height Difference ft (m) 49.2 (15) 49.2 (15)Chargeless ft (m) 32.8 (10) 32.8 (10)Amount of Additional Charge of Refrigerant
oz/ft(g/m) 0.21 (20) 0.21 (20)
Indoor Unit FTXR09TVJUW FTXR09TVJUSFront Panel Color White Silver
Airflow Rate
H
cfm (m³/min)
272 (7.7) 346 (9.8) 272 (7.7) 346 (9.8)M 208 (5.9) 258 (7.3) 208 (5.9) 258 (7.3)L 162 (4.6) 201 (5.7) 162 (4.6) 201 (5.7)SL 134 (3.8) 117 (3.3) 134 (3.8) 117 (3.3)
Fan Motor
H
rpm
1,410 1,720 1,410 1,720M 1,140 1,340 1,140 1,340L 940 1,100 940 1,100SL 820 760 820 760
FanType Cross Flow Fan Cross Flow FanSpeed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Heat ExchangerType Multi Slit Fin Multi Slit FinRows × Stages, Fin per Inch 2 × 18, 21 2 × 18, 21
Remote Controller ARC466A36 ARC466A36Dimensions (H × W × D) in. (mm) 11-15/16 × 39-5/16 × 8-3/8 (303 × 998 × 212) 11-15/16 × 39-5/16 × 8-3/8 (303 × 998 × 212)Packaged Dimensions (H × W × D) in. (mm) 12-11/16 × 43-3/8 × 15-5/16 (322 × 1,101 × 389) 12-11/16 × 43-3/8 × 15-5/16 (322 × 1,101 × 389)Weight (Mass) Lbs (kg) 27 (12) 27 (12)Gross Weight (Gross Mass) Lbs (kg) 36 (16) 36 (16)Sound Pressure Level H / M / L / SL dB(A) 38 / 32 / 25 / 19 41 / 34 / 28 / 19 38 / 32 / 25 / 19 41 / 34 / 28 / 19Outdoor Unit RX09RMVJU9 RX09RMVJU9Casing Color Ivory White Ivory White
CompressorType Hermetically Sealed Swing Type Hermetically Sealed Swing TypeModel 1YC23AUXD 1YC23AUXD
Refrigerant OilType FVC50K FVC50KCharge oz (L) 12.68 (0.375) 12.68 (0.375)
RefrigerantType R-410A R-410ACharge Lbs (kg) 2.09 (0.95) 2.09 (0.95)
Airflow Rate cfm (m³/min) 985 (27.9) 1,130 (32) 985 (27.9) 1,130 (32)
Fan Motor H rpm 800 910 800 910Fan Type Propeller Propeller
Heat ExchangerType Waffle Fin Waffle FinRows × Stages, Fin per Inch 2 × 24, 17 2 × 24, 17
Dimensions (H × W × D) in. (mm) 21-5/8 × 26-9/16 × 11-3/16 (550 × 675 × 284) 21-5/8 × 26-9/16 × 11-3/16 (550 × 675 × 284)Packaged Dimensions (H × W × D) in. (mm) 24-3/4 × 32-11/16 × 16 (629 × 830 × 407) 24-3/4 × 32-11/16 × 16 (629 × 830 × 407)Weight (Mass) Lbs (kg) 60 (27) 60 (27)Gross Weight (Gross Mass) Lbs (kg) 71 (32) 71 (32)Sound Pressure Level dB(A) 46 50 46 50Drawing No. 3D120044 3D120044
Conversion Formulae
kcal/h = kW × 860Btu/h = kW × 3412
cfm = m³/min × 35.3Cooling Indoor ; 80°FDB (26.7°CDB) / 67°FWB (19.4°CWB)
Outdoor ; 95°FDB (35°CDB) / 75°FWB (23.9°CWB)
HeatingIndoor ; 70°FDB (21.1°CDB) / 60°FWB (15.6°CWB)Outdoor ; 47°FDB (8.33°CDB) / 43°FWB (6.11°CWB)
Piping Length 25 ft (7.5 m)
Split Type Air Conditioners FTXR-T Series 5
Specifications EDUS041820A
60 Hz, 208 - 230 V
Notes: 1. SL: The Quiet fan level of the airflow rate setting.2. When connected with multi-system outdoor unit, refer to the specifications of the multi outdoor unit to be
connected.3. The data are based on the conditions shown in the table below.
ModelIndoor Unit FTXR12TVJUW FTXR12TVJUS
Outdoor UnitRX12RMVJU9 RX12RMVJU9
Cooling Heating Cooling HeatingCapacityRated (Min. ~ Max.) Btu/h 12,000 (4,500 ~ 12,800) 13,500 (4,100 ~ 15,800) 12,000 (4,500 ~ 12,800) 13,500 (4,100 ~ 15,800)
Running current A 5.46 - 4.94 5.60 - 5.06 5.46 - 4.94 5.60 - 5.06Power Consumption (Rated) W 1,091 1,106 1,091 1,106Power Factor (Rated) % 96.1 - 96.0 95.0 - 95.0 96.1 - 96.0 95.0 - 95.0EER (Rated) Btu/h·W 11.00 — 11.00 —COP (Rated) W/W — 3.58 — 3.58SEER / HSPF 17.00 10.00 17.00 10.00
Piping ConnectionsLiquid in. (mm) 1/4 (6.4) 1/4 (6.4)Gas in. (mm) 3/8 (9.5) 3/8 (9.5)Drain in. (mm) 11/16 (18) 11/16 (18)
No. of Wiring Connection 3 for Power Supply, 4 for Interunit Wiring (Including Ground Wiring)
3 for Power Supply, 4 for Interunit Wiring (Including Ground Wiring)
Max. Interunit Piping Length ft (m) 65.6 (20) 65.6 (20)Max. Interunit Height Difference ft (m) 49.2 (15) 49.2 (15)Chargeless ft (m) 32.8 (10) 32.8 (10)Amount of Additional Charge of Refrigerant
oz/ft(g/m) 0.21 (20) 0.21 (20)
Indoor Unit FTXR12TVJUW FTXR12TVJUSFront Panel Color White Silver
Airflow Rate
H
cfm (m³/min)
335 (9.5) 395 (11.2) 335 (9.5) 395 (11.2)M 219 (6.2) 290 (8.2) 219 (6.2) 290 (8.2)L 169 (4.8) 226 (6.4) 169 (4.8) 226 (6.4)SL 131 (3.7) 131 (3.7) 131 (3.7) 131 (3.7)
Fan Motor
H
rpm
1,710 1,930 1,710 1,930M 1,210 1,470 1,210 1,470L 990 1,200 990 1,200SL 820 800 820 800
FanType Cross Flow Fan Cross Flow FanSpeed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Heat ExchangerType Multi Slit Fin Multi Slit FinRows × Stages, Fin per Inch 2 × 18, 21 2 × 18, 21
Remote Controller ARC466A36 ARC466A36Dimensions (H × W × D) in. (mm) 11-15/16 × 39-5/16 × 8-3/8 (303 × 998 × 212) 11-15/16 × 39-5/16 × 8-3/8 (303 × 998 × 212)Packaged Dimensions (H × W × D) in. (mm) 12-11/16 × 43-3/8 × 15-5/16 (322 × 1,101 × 389) 12-11/16 × 43-3/8 × 15-5/16 (322 × 1,101 × 389)Weight (Mass) Lbs (kg) 27 (12) 27 (12)Gross Weight (Gross Mass) Lbs (kg) 36 (16) 36 (16)Sound Pressure Level H / M / L / SL dB(A) 45 / 34 / 26 / 20 45 / 37 / 29 / 20 45 / 34 / 26 / 20 45 / 37 / 29 / 20Outdoor Unit RX12RMVJU9 RX12RMVJU9Casing Color Ivory White Ivory White
CompressorType Hermetically Sealed Swing Type Hermetically Sealed Swing TypeModel 1YC23AUXD 1YC23AUXD
Refrigerant OilType FVC50K FVC50KCharge oz (L) 12.68 (0.375) 12.68 (0.375)
RefrigerantType R-410A R-410ACharge Lbs (kg) 2.09 (0.95) 2.09 (0.95)
Airflow Rate cfm (m³/min) 1,105 (31.3) 1,130 (32) 1,105 (31.3) 1,130 (32)
Fan Motor H rpm 890 910 890 910Fan Type Propeller Propeller
Heat ExchangerType Waffle Fin Waffle FinRows × Stages, Fin per Inch 2 × 24, 17 2 × 24, 17
Dimensions (H × W × D) in. (mm) 21-5/8 × 26-9/16 × 11-3/16 (550 × 675 × 284) 21-5/8 × 26-9/16 × 11-3/16 (550 × 675 × 284)Packaged Dimensions (H × W × D) in. (mm) 24-3/4 × 32-11/16 × 16 (629 × 830 × 407) 24-3/4 × 32-11/16 × 16 (629 × 830 × 407)Weight (Mass) Lbs (kg) 60 (27) 60 (27)Gross Weight (Gross Mass) Lbs (kg) 71 (32) 71 (32)Sound Pressure Level dB(A) 49 51 49 51Drawing No. 3D120044 3D120044
Conversion Formulae
kcal/h = kW × 860Btu/h = kW × 3412
cfm = m³/min × 35.3Cooling Indoor ; 80°FDB (26.7°CDB) / 67°FWB (19.4°CWB)
Outdoor ; 95°FDB (35°CDB) / 75°FWB (23.9°CWB)
HeatingIndoor ; 70°FDB (21.1°CDB) / 60°FWB (15.6°CWB)Outdoor ; 47°FDB (8.33°CDB) / 43°FWB (6.11°CWB)
Piping Length 25 ft (7.5 m)
6 Split Type Air Conditioners FTXR-T Series
EDUS041820A Specifications
60 Hz, 208 - 230V
Notes: 1. SL: The Quiet fan level of the airflow rate setting.2. When connected with multi-system outdoor unit, refer to the specifications of the multi outdoor unit to be
connected.3. The data are based on the conditions shown in the table below.
ModelIndoor Unit FTXR18TVJUW FTXR18TVJUS
Outdoor UnitRX18RMVJU9A RX18RMVJU9A
Cooling Heating Cooling HeatingCapacityRated (Min. ~ Max.) Btu/h 18,000 (5,100 ~ 18,500) 20,000 (5,800 ~ 21,200) 18,000 (5,100 ~ 18,500) 20,000 (5,800 ~ 21,200)
Running current A 9.29 - 8.40 8.70 - 7.87 9.29 - 8.40 8.70 - 7.87Power Consumption (Rated) W 1,875 1,755 1,875 1,755Power Factor (Rated) % 97.0 - 97.0 97.0 - 97.0 97.0 - 97.0 97.0 - 97.0EER (Rated) Btu/h·W 9.60 — 9.60 —COP (Rated) W/W — 3.34 — 3.34SEER / HSPF 14.50 9.80 14.50 9.80
Piping ConnectionsLiquid in. (mm) 1/4 (6.4) 1/4 (6.4)Gas in. (mm) 1/2 (12.7) 1/2 (12.7)Drain in. (mm) 11/16 (18) 11/16 (18)
No. of Wiring Connection 3 for Power Supply, 4 for Interunit Wiring (Including Ground Wiring)
3 for Power Supply, 4 for Interunit Wiring (Including Ground Wiring)
Max. Interunit Piping Length ft (m) 98.4 (30) 98.4 (30)Max. Interunit Height Difference ft (m) 65.6 (20) 65.6 (20)Chargeless ft (m) 32.8 (10) 32.8 (10)Amount of Additional Charge of Refrigerant
oz/ft(g/m) 0.21 (20) 0.21 (20)
Indoor Unit FTXR18TVJUW FTXR18TVJUSFront Panel Color White Silver
Airflow Rate
H
cfm (m³/min)
350 (9.9) 413 (11.7) 350 (9.9) 413 (11.7)M 275 (7.8) 332 (9.4) 275 (7.8) 332 (9.4)L 226 (6.4) 275 (7.8) 226 (6.4) 275 (7.8)SL 208 (5.9) 208 (5.9) 208 (5.9) 208 (5.9)
Fan Motor
H
rpm
1,760 2,000 1,760 2,000M 1,440 1,660 1,440 1,660L 1,230 1,420 1,230 1,420SL 1,160 1,130 1,160 1,130
FanType Cross Flow Fan Cross Flow FanSpeed Steps 5 Steps, Quiet, Auto 5 Steps, Quiet, Auto
Heat ExchangerType Multi Slit Fin Multi Slit FinRows × Stages, Fin per Inch 2 × 18, 21 2 × 18, 21
Remote Controller ARC466A36 ARC466A36Dimensions (H × W × D) in. (mm) 11-15/16 × 39-5/16 × 8-3/8 (303 × 998 × 212) 11-15/16 × 39-5/16 × 8-3/8 (303 × 998 × 212)Packaged Dimensions (H × W × D) in. (mm) 12-11/16 × 43-3/8 × 15-5/16 (322 × 1,101 × 389) 12-11/16 × 43-3/8 × 15-5/16 (322 × 1,101 × 389)Weight (Mass) Lbs (kg) 27 (12) 27 (12)Gross Weight (Gross Mass) Lbs (kg) 36 (16) 36 (16)Sound Pressure Level H / M / L / SL dB(A) 46 / 40 / 35 / 30 47 / 41 / 35 / 30 46 / 40 / 35 / 30 47 / 41 / 35 / 30Outdoor Unit RX18RMVJU9A RX18RMVJU9ACasing Color Ivory White Ivory White
CompressorType Hermetically Sealed Swing Type Hermetically Sealed Swing TypeModel 2YC36PXD 2YC36PXD
Refrigerant OilType FVC50K FVC50KCharge oz (L) 21.98 (0.650) 21.98 (0.650)
RefrigerantType R-410A R-410ACharge Lbs (kg) 2.49 (1.13) 2.49 (1.13)
Airflow Rate cfm (m³/min) 2,461 (69.7) 2,553 (72.3) 2,461 (69.7) 2,553 (72.3)
Fan Motor H rpm 850 880 850 880Fan Type Propeller Propeller
Heat ExchangerType Waffle Fin Waffle FinRows × Stages, Fin per Inch 1 × 32, 18 1 × 32, 18
Dimensions (H × W × D) in. (mm) 28-15/16 × 34-1/4 × 12-5/8 (735 × 870 × 320) 28-15/16 × 34-1/4 × 12-5/8 (735 × 870 × 320)Packaged Dimensions (H × W × D) in. (mm) 31-7/8 × 41-9/16 × 17-1/2 (810 × 1,056 × 464) 31-7/8 × 41-9/16 × 17-1/2 (810 × 1,056 × 464)Weight (Mass) Lbs (kg) 97 (44) 97 (44)Gross Weight (Gross Mass) Lbs (kg) 115 (52) 115 (52)Sound Pressure Level dB(A) 54 55 54 55Drawing No. 3D127164 3D127164
Conversion Formulae
kcal/h = kW × 860Btu/h = kW × 3412
cfm = m³/min × 35.3Cooling Indoor ; 80°FDB (26.7°CDB) / 67°FWB (19.4°CWB)
Outdoor ; 95°FDB (35°CDB) / 75°FWB (23.9°CWB)
HeatingIndoor ; 70°FDB (21.1°CDB) / 60°FWB (15.6°CWB)Outdoor ; 47°FDB (8.33°CDB) / 43°FWB (6.11°CWB)
Piping Length 25 ft (7.5 m)
Split Type Air Conditioners FTXR-T Series 7
Dimensions EDUS041820A
4. Dimensions4.1 Indoor Unit
FTXR09/12TVJUW(S)
FTXR18TVJUW(S)
8 Split Type Air Conditioners FTXR-T Series
EDUS041820A Dimensions
4.2 Outdoor Unit
RX09/12RMVJU9
RX18RMVJU9A
3D092206E
C: 3D092224C
Split Type Air Conditioners FTXR-T Series 9
Wiring Diagrams EDUS041820A
5. Wiring Diagrams5.1 Indoor Unit
FTXR09/12/18TVJUW(S)
10 Split Type Air Conditioners FTXR-T Series
EDUS041820A Wiring Diagrams
5.2 Outdoor Unit
RX09/12RMVJU9
RX18RMVJU9A
Split Type Air Conditioners FTXR-T Series 11
Piping Diagrams EDUS041820A
6. Piping Diagrams6.1 Indoor Unit
FTXR09/12TVJUW(S)
FTXR18TVJUW(S)
12 Split Type Air Conditioners FTXR-T Series
EDUS041820A Piping Diagrams
6.2 Outdoor Unit
RX09/12RMVJU9
RX18RMVJU9A
Split Type Air Conditioners FTXR-T Series 13
Capacity Tables EDUS041820A
7. Capacity Tables
FTXR09TVJUW + RX09RMVJU9 FTXR09TVJUS + RX09RMVJU9
60 Hz, 208 VCooling
Heating
AFR 7.7
BF 0.16
Temp: CelsiusTC, SHC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CDB)
EWB EDB 10 20 30 35 40 46
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 2.53 1.90 0.34 2.53 1.90 0.53 2.46 1.86 0.75 2.34 1.80 0.81 2.21 1.74 0.87 2.07 1.67 0.94
16.0 22.0 3.07 2.07 0.51 2.83 1.95 0.63 2.58 1.83 0.75 2.46 1.78 0.81 2.33 1.72 0.87 2.19 1.66 0.95
18.0 25.0 3.19 2.15 0.51 2.95 2.04 0.64 2.70 1.93 0.76 2.58 1.88 0.82 2.46 1.83 0.88 2.31 1.76 0.95
19.4 26.7 3.25 2.26 0.52 3.01 2.15 0.64 2.76 2.04 0.76 2.64 1.99 0.82 2.52 1.94 0.88 2.37 1.88 0.95
22.0 30.0 3.44 2.16 0.52 3.19 2.07 0.64 2.95 1.98 0.76 2.82 1.93 0.82 2.70 1.89 0.88 2.55 1.84 0.96
24.0 32.0 3.56 2.10 0.53 3.31 2.01 0.65 3.07 1.93 0.77 2.94 1.89 0.83 2.82 1.85 0.89 2.67 1.80 0.96
Temp: FahrenheitTC, SHC: kBtu/hPI: kW
INDOOR OUTDOOR TEMPERATURE (°FDB)
EWB EDB 50 68 86 95 104 115
°F °F TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
57.2 68.0 8.62 6.47 0.34 8.62 6.47 0.53 8.39 6.35 0.75 7.97 6.15 0.81 7.55 5.94 0.87 7.05 5.70 0.94
60.8 71.6 10.48 7.06 0.51 9.64 6.66 0.63 8.80 6.26 0.75 8.39 6.07 0.81 7.97 5.87 0.87 7.46 5.65 0.95
64.4 77.0 10.90 7.34 0.51 10.06 6.96 0.64 9.22 6.59 0.76 8.80 6.41 0.82 8.38 6.23 0.88 7.88 6.02 0.95
67.0 80.0 11.10 7.69 0.52 10.27 7.33 0.64 9.43 6.97 0.76 9.00 6.80 0.82 8.59 6.63 0.88 8.08 6.42 0.95
71.6 86.0 11.73 7.39 0.52 10.89 7.06 0.64 10.05 6.75 0.76 9.63 6.60 0.82 9.21 6.44 0.88 8.71 6.26 0.96
75.2 89.6 12.14 7.17 0.53 11.30 6.87 0.65 10.46 6.59 0.77 10.05 6.45 0.83 9.63 6.31 0.89 9.12 6.14 0.96
AFR 9.8
Temp: CelsiusTC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CWB)
EDB –15 –10 –5 0 6 10 18
°C TC PI TC PI TC PI TC PI TC PI TC PI TC PI
15.0 1.40 0.53 1.68 0.56 1.96 0.59 2.25 0.61 3.04 0.72 3.31 0.74 3.84 0.79
21.1 1.31 0.55 1.60 0.57 1.88 0.60 2.16 0.63 2.94 0.73 3.21 0.76 3.74 0.81
22.0 1.28 0.55 1.56 0.58 1.84 0.61 2.13 0.63 2.90 0.74 3.16 0.76 3.70 0.81
24.0 1.24 0.56 1.53 0.58 1.81 0.61 2.09 0.64 2.86 0.75 3.12 0.77 3.66 0.82
25.0 1.23 0.56 1.51 0.59 1.79 0.61 2.07 0.64 2.84 0.75 3.10 0.77 3.64 0.82
27.0 1.19 0.57 1.48 0.59 1.76 0.62 2.04 0.65 2.80 0.76 3.06 0.78 3.59 0.83
Temp: FahrenheitTC: kBtu/hPI: kW
INDOOR OUTDOOR TEMPERATURE (°FWB)
EDB 5 14 23 32 43 50 64
°F TC PI TC PI TC PI TC PI TC PI TC PI TC PI
59.0 4.78 0.53 5.74 0.56 6.70 0.59 7.67 0.61 10.38 0.72 11.28 0.74 13.10 0.79
70.0 4.48 0.55 5.45 0.57 6.41 0.60 7.37 0.63 10.00 0.73 10.94 0.76 12.75 0.81
71.6 4.37 0.55 5.33 0.58 6.29 0.61 7.25 0.63 9.89 0.74 10.80 0.76 12.61 0.81
75.2 4.25 0.56 5.21 0.58 6.17 0.61 7.14 0.64 9.75 0.75 10.66 0.77 12.47 0.82
77.0 4.19 0.56 5.15 0.59 6.11 0.61 7.08 0.64 9.69 0.75 10.59 0.77 12.40 0.82
80.6 4.07 0.57 5.03 0.59 6.00 0.62 6.96 0.65 9.55 0.76 10.45 0.78 12.27 0.83
14 Split Type Air Conditioners FTXR-T Series
EDUS041820A Capacity Tables
60 Hz, 230 VCooling
Heating
AFR 7.7
BF 0.16
Temp: CelsiusTC, SHC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CDB)
EWB EDB 10 20 30 35 40 46
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 2.53 1.90 0.34 2.53 1.90 0.53 2.46 1.86 0.75 2.34 1.80 0.81 2.21 1.74 0.87 2.07 1.67 0.94
16.0 22.0 3.07 2.07 0.51 2.83 1.95 0.63 2.58 1.83 0.75 2.46 1.78 0.81 2.33 1.72 0.87 2.19 1.66 0.95
18.0 25.0 3.19 2.15 0.51 2.95 2.04 0.64 2.70 1.93 0.76 2.58 1.88 0.82 2.46 1.83 0.88 2.31 1.76 0.95
19.4 26.7 3.25 2.26 0.52 3.01 2.15 0.64 2.76 2.04 0.76 2.64 1.99 0.82 2.52 1.94 0.88 2.37 1.88 0.95
22.0 30.0 3.44 2.16 0.52 3.19 2.07 0.64 2.95 1.98 0.76 2.82 1.93 0.82 2.70 1.89 0.88 2.55 1.84 0.96
24.0 32.0 3.56 2.10 0.53 3.31 2.01 0.65 3.07 1.93 0.77 2.94 1.89 0.83 2.82 1.85 0.89 2.67 1.80 0.96
Temp: FahrenheitTC, SHC: kBtu/hPI: kW
INDOOR OUTDOOR TEMPERATURE (°FDB)
EWB EDB 50 68 86 95 104 115
°F °F TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
57.2 68.0 8.62 6.47 0.34 8.62 6.47 0.53 8.39 6.35 0.75 7.97 6.15 0.81 7.55 5.94 0.87 7.05 5.70 0.94
60.8 71.6 10.48 7.06 0.51 9.64 6.66 0.63 8.80 6.26 0.75 8.39 6.07 0.81 7.97 5.87 0.87 7.46 5.65 0.95
64.4 77.0 10.90 7.34 0.51 10.06 6.96 0.64 9.22 6.59 0.76 8.80 6.41 0.82 8.38 6.23 0.88 7.88 6.02 0.95
67.0 80.0 11.10 7.69 0.52 10.27 7.33 0.64 9.43 6.97 0.76 9.00 6.80 0.82 8.59 6.63 0.88 8.08 6.42 0.95
71.6 86.0 11.73 7.39 0.52 10.89 7.06 0.64 10.05 6.75 0.76 9.63 6.60 0.82 9.21 6.44 0.88 8.71 6.26 0.96
75.2 89.6 12.14 7.17 0.53 11.30 6.87 0.65 10.46 6.59 0.77 10.05 6.45 0.83 9.63 6.31 0.89 9.12 6.14 0.96
AFR 9.8
Temp: CelsiusTC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CWB)
EDB –15 –10 –5 0 6 10 18
°C TC PI TC PI TC PI TC PI TC PI TC PI TC PI
15.0 1.40 0.53 1.68 0.56 1.96 0.59 2.25 0.61 3.04 0.72 3.31 0.74 3.84 0.79
21.1 1.31 0.55 1.60 0.57 1.88 0.60 2.16 0.63 2.94 0.73 3.21 0.76 3.74 0.81
22.0 1.28 0.55 1.56 0.58 1.84 0.61 2.13 0.63 2.90 0.74 3.16 0.76 3.70 0.81
24.0 1.24 0.56 1.53 0.58 1.81 0.61 2.09 0.64 2.86 0.75 3.12 0.77 3.66 0.82
25.0 1.23 0.56 1.51 0.59 1.79 0.61 2.07 0.64 2.84 0.75 3.10 0.77 3.64 0.82
27.0 1.19 0.57 1.48 0.59 1.76 0.62 2.04 0.65 2.80 0.76 3.06 0.78 3.59 0.83
Temp: FahrenheitTC: kBtu/hPI: kW
INDOOR OUTDOOR TEMPERATURE (°FWB)
EDB 5 14 23 32 43 50 64
°F TC PI TC PI TC PI TC PI TC PI TC PI TC PI
59.0 4.78 0.53 5.74 0.56 6.70 0.59 7.67 0.61 10.38 0.72 11.28 0.74 13.10 0.79
70.0 4.48 0.55 5.45 0.57 6.41 0.60 7.37 0.63 10.00 0.73 10.94 0.76 12.75 0.81
71.6 4.37 0.55 5.33 0.58 6.29 0.61 7.25 0.63 9.89 0.74 10.80 0.76 12.61 0.81
75.2 4.25 0.56 5.21 0.58 6.17 0.61 7.14 0.64 9.75 0.75 10.66 0.77 12.47 0.82
77.0 4.19 0.56 5.15 0.59 6.11 0.61 7.08 0.64 9.69 0.75 10.59 0.77 12.40 0.82
80.6 4.07 0.57 5.03 0.59 6.00 0.62 6.96 0.65 9.55 0.76 10.45 0.78 12.27 0.83
Split Type Air Conditioners FTXR-T Series 15
Capacity Tables EDUS041820A
C: 3D120261
Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.2. TC, PI and SHC must be calculated by interpolation using the figures in the
above tables. (Figures out of the tables should not be used for calculation.)3. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 25 ft (7.5 m)Level difference : 0 ft (0 m)
4. Airflow rate (AFR) and Bypass factor (BF) are tabulated above table.
BF : Bypass factor
EWB : Entering wet bulb temp. (°C) / (°F)
EDB : Entering dry bulb temp. (°C) / (°F)
TC : Total capacity (kW) / (kBtu/h)
SHC : Sensible heat capacity (kW) / (kBtu/h)
PI : Power input (kW)
16 Split Type Air Conditioners FTXR-T Series
EDUS041820A Capacity Tables
FTXR12TVJUW + RX12RMVJU9 FTXR12TVJUS + RX12RMVJU9
60 Hz, 208 VCooling
Heating
AFR 9.5
BF 0.19
Temp: CelsiusTC, SHC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CDB)
EWB EDB 10 20 30 35 40 46
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 3.01 2.26 0.32 3.01 2.26 0.52 3.01 2.26 0.82 3.01 2.26 1.00 2.97 2.24 1.16 2.67 2.09 1.17
16.0 22.0 3.86 2.56 0.55 3.79 2.53 0.84 3.46 2.37 1.00 3.30 2.29 1.08 3.13 2.21 1.16 2.82 2.07 1.17
18.0 25.0 4.28 2.79 0.69 3.95 2.63 0.85 3.62 2.48 1.01 3.46 2.41 1.09 3.29 2.33 1.17 2.96 2.19 1.17
19.4 26.7 4.36 2.90 0.69 4.03 2.76 0.85 3.70 2.61 1.01 3.54 2.54 1.09 3.38 2.47 1.17 3.04 2.33 1.17
22.0 30.0 4.61 2.78 0.69 4.28 2.65 0.86 3.95 2.52 1.02 3.78 2.46 1.10 3.62 2.40 1.18 3.25 2.26 1.17
24.0 32.0 4.77 2.70 0.70 4.44 2.57 0.86 4.11 2.46 1.02 3.95 2.40 1.10 3.78 2.34 1.18 3.39 2.21 1.17
Temp: FahrenheitTC, SHC: kBtu/hPI: kW
INDOOR OUTDOOR TEMPERATURE (°FDB)
EWB EDB 50 68 86 95 104 115
°F °F TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
57.2 68.0 10.26 7.70 0.32 10.26 7.70 0.52 10.26 7.70 0.82 10.26 7.70 1.00 10.12 7.63 1.16 9.11 7.13 1.17
60.8 71.6 13.17 8.75 0.55 12.93 8.63 0.84 11.81 8.08 1.00 11.24 7.81 1.08 10.68 7.54 1.16 9.61 7.05 1.17
64.4 77.0 14.61 9.50 0.69 13.49 8.97 0.85 12.36 8.46 1.01 11.80 8.21 1.09 11.24 7.96 1.17 10.11 7.47 1.17
67.0 80.0 14.89 9.91 0.69 13.77 9.40 0.85 12.64 8.90 1.01 12.00 8.66 1.09 11.52 8.42 1.17 10.36 7.94 1.17
71.6 86.0 15.73 9.50 0.69 14.60 9.04 0.86 13.48 8.60 1.02 12.91 8.39 1.10 12.35 8.18 1.18 11.09 7.71 1.17
75.2 89.6 16.28 9.20 0.70 15.16 8.78 0.86 14.03 8.38 1.02 13.47 8.19 1.10 12.91 7.99 1.18 11.58 7.55 1.17
AFR 11.2
Temp: CelsiusTC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CWB)
EDB –15 –10 –5 0 6 10 18
°C TC PI TC PI TC PI TC PI TC PI TC PI TC PI
15.0 1.89 0.80 2.27 0.84 2.65 0.88 3.03 0.92 4.10 1.08 4.45 1.12 5.17 1.19
21.1 1.77 0.82 2.15 0.86 2.53 0.91 2.91 0.95 3.96 1.11 4.32 1.14 5.03 1.22
22.0 1.72 0.83 2.10 0.87 2.48 0.91 2.86 0.96 3.91 1.12 4.26 1.15 4.98 1.23
24.0 1.68 0.84 2.06 0.88 2.44 0.92 2.82 0.96 3.85 1.13 4.21 1.16 4.92 1.24
25.0 1.65 0.85 2.03 0.89 2.41 0.93 2.79 0.97 3.82 1.13 4.18 1.17 4.90 1.24
27.0 1.61 0.85 1.99 0.90 2.37 0.94 2.75 0.98 3.77 1.14 4.13 1.18 4.84 1.25
Temp: FahrenheitTC: kBtu/hPI: kW
INDOOR OUTDOOR TEMPERATURE (°FWB)
EDB 5 14 23 32 43 50 64
°F TC PI TC PI TC PI TC PI TC PI TC PI TC PI
59.0 6.43 0.80 7.73 0.84 9.03 0.88 10.33 0.92 13.98 1.08 15.20 1.12 17.64 1.19
70.0 6.04 0.82 7.33 0.86 8.63 0.91 9.93 0.95 13.50 1.11 14.73 1.14 17.17 1.22
71.6 5.88 0.83 7.18 0.87 8.47 0.91 9.77 0.96 13.32 1.12 14.55 1.15 16.99 1.23
75.2 5.72 0.84 7.02 0.88 8.31 0.92 9.61 0.96 13.14 1.13 14.36 1.16 16.80 1.24
77.0 5.64 0.85 6.94 0.89 8.24 0.93 9.53 0.97 13.05 1.13 14.27 1.17 16.71 1.24
80.6 5.48 0.85 6.78 0.90 8.08 0.94 9.37 0.98 12.86 1.14 14.08 1.18 16.52 1.25
Split Type Air Conditioners FTXR-T Series 17
Capacity Tables EDUS041820A
60 Hz, 230 VCooling
Heating
AFR 9.5
BF 0.19
Temp: CelsiusTC, SHC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CDB)
EWB EDB 10 20 30 35 40 46
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 3.01 2.26 0.32 3.01 2.26 0.52 3.01 2.26 0.82 3.01 2.26 1.00 2.97 2.24 1.16 2.77 2.14 1.26
16.0 22.0 3.86 2.56 0.55 3.79 2.53 0.84 3.46 2.37 1.00 3.30 2.29 1.08 3.13 2.21 1.16 2.93 2.12 1.26
18.0 25.0 4.28 2.79 0.69 3.95 2.63 0.85 3.62 2.48 1.01 3.46 2.41 1.09 3.29 2.33 1.17 3.10 2.25 1.27
19.4 26.7 4.36 2.90 0.69 4.03 2.76 0.85 3.70 2.61 1.01 3.54 2.54 1.09 3.38 2.47 1.17 3.18 2.39 1.27
22.0 30.0 4.61 2.78 0.69 4.28 2.65 0.86 3.95 2.52 1.02 3.78 2.46 1.10 3.62 2.40 1.18 3.42 2.32 1.28
24.0 32.0 4.77 2.70 0.70 4.44 2.57 0.86 4.11 2.46 1.02 3.95 2.40 1.10 3.78 2.34 1.18 3.59 2.28 1.28
Temp: FahrenheitTC, SHC: kBtu/hPI: kW
INDOOR OUTDOOR TEMPERATURE (°FDB)
EWB EDB 50 68 86 95 104 115
°F °F TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
57.2 68.0 10.26 7.70 0.32 10.26 7.70 0.52 10.26 7.70 0.82 10.26 7.70 1.00 10.12 7.63 1.16 9.45 7.30 1.26
60.8 71.6 13.17 8.75 0.55 12.93 8.63 0.84 11.81 8.08 1.00 11.24 7.81 1.08 10.68 7.54 1.16 10.01 7.23 1.26
64.4 77.0 14.61 9.50 0.69 13.49 8.97 0.85 12.36 8.46 1.01 11.80 8.21 1.09 11.24 7.96 1.17 10.56 7.67 1.27
67.0 80.0 14.89 9.91 0.69 13.77 9.40 0.85 12.64 8.90 1.01 12.00 8.66 1.09 11.52 8.42 1.17 10.84 8.14 1.27
71.6 86.0 15.73 9.50 0.69 14.60 9.04 0.86 13.48 8.60 1.02 12.91 8.39 1.10 12.35 8.18 1.18 11.68 7.93 1.28
75.2 89.6 16.28 9.20 0.70 15.16 8.78 0.86 14.03 8.38 1.02 13.47 8.19 1.10 12.91 7.99 1.18 12.23 7.76 1.28
AFR 11.2
Temp: CelsiusTC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CWB)
EDB –15 –10 –5 0 6 10 18
°C TC PI TC PI TC PI TC PI TC PI TC PI TC PI
15.0 1.89 0.80 2.27 0.84 2.65 0.88 3.03 0.92 4.10 1.08 4.45 1.12 5.17 1.19
21.1 1.77 0.82 2.15 0.86 2.53 0.91 2.91 0.95 3.96 1.11 4.32 1.14 5.03 1.22
22.0 1.72 0.83 2.10 0.87 2.48 0.91 2.86 0.96 3.91 1.12 4.26 1.15 4.98 1.23
24.0 1.68 0.84 2.06 0.88 2.44 0.92 2.82 0.96 3.85 1.13 4.21 1.16 4.92 1.24
25.0 1.65 0.85 2.03 0.89 2.41 0.93 2.79 0.97 3.82 1.13 4.18 1.17 4.90 1.24
27.0 1.61 0.85 1.99 0.90 2.37 0.94 2.75 0.98 3.77 1.14 4.13 1.18 4.84 1.25
Temp: FahrenheitTC: kBtu/hPI: kW
INDOOR OUTDOOR TEMPERATURE (°FWB)
EDB 5 14 23 32 43 50 64
°F TC PI TC PI TC PI TC PI TC PI TC PI TC PI
59.0 6.43 0.80 7.73 0.84 9.03 0.88 10.33 0.92 13.98 1.08 15.20 1.12 17.64 1.19
70.0 6.04 0.82 7.33 0.86 8.63 0.91 9.93 0.95 13.50 1.11 14.73 1.14 17.17 1.22
71.6 5.88 0.83 7.18 0.87 8.47 0.91 9.77 0.96 13.32 1.12 14.55 1.15 16.99 1.23
75.2 5.72 0.84 7.02 0.88 8.31 0.92 9.61 0.96 13.14 1.13 14.36 1.16 16.80 1.24
77.0 5.64 0.85 6.94 0.89 8.24 0.93 9.53 0.97 13.05 1.13 14.27 1.17 16.71 1.24
80.6 5.48 0.85 6.78 0.90 8.08 0.94 9.37 0.98 12.86 1.14 14.08 1.18 16.52 1.25
18 Split Type Air Conditioners FTXR-T Series
EDUS041820A Capacity Tables
C: 3D120262
Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.2. TC, PI and SHC must be calculated by interpolation using the figures in the
above tables. (Figures out of the tables should not be used for calculation.)3. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 25 ft (7.5 m)Level difference : 0 ft (0 m)
4. Airflow rate (AFR) and Bypass factor (BF) are tabulated above table.
BF : Bypass factor
EWB : Entering wet bulb temp. (°C) / (°F)
EDB : Entering dry bulb temp. (°C) / (°F)
TC : Total capacity (kW) / (kBtu/h)
SHC : Sensible heat capacity (kW) / (kBtu/h)
PI : Power input (kW)
Split Type Air Conditioners FTXR-T Series 19
Capacity Tables EDUS041820A
FTXR18TVJUW + RX18RMVJU9A FTXR18TVJUS + RX18RMVJU9A
60 Hz, 208 VCooling
Heating
AFR 9.9
BF 0.17
Temp: CelsiusTC, SHC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CDB)
EWB EDB 10 20 30 35 40 46
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 3.21 2.41 0.23 3.21 2.41 0.38 3.21 2.41 0.67 3.21 2.41 0.89 3.21 2.41 1.16 3.19 2.40 1.41
16.0 22.0 4.12 2.74 0.34 4.12 2.74 0.58 4.12 2.74 0.99 4.12 2.74 1.28 4.12 2.74 1.60 3.34 2.36 1.41
18.0 25.0 5.10 3.23 0.53 5.10 3.23 0.90 5.10 3.23 1.48 5.10 3.23 1.82 4.91 3.14 2.01 3.49 2.48 1.41
19.4 26.7 5.62 3.56 0.66 5.62 3.56 1.14 5.53 3.52 1.74 5.28 3.40 1.88 5.03 3.28 2.01 3.57 2.62 1.41
22.0 30.0 6.87 3.84 1.19 6.38 3.61 1.47 5.89 3.38 1.75 5.64 3.28 1.89 5.39 3.17 2.02 3.79 2.53 1.41
24.0 32.0 7.12 3.70 1.20 6.63 3.49 1.48 6.13 3.28 1.76 5.89 3.18 1.90 5.62 3.08 2.02 3.94 2.47 1.41
Temp: FahrenheitTC, SHC: kBtu/hPI: kW
INDOOR OUTDOOR TEMPERATURE (°FDB)
EWB EDB 50 68 86 95 104 115
°F °F TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
57.2 68.0 10.95 8.22 0.23 10.95 8.22 0.38 10.95 8.22 0.67 10.95 8.22 0.89 10.95 8.22 1.16 10.87 8.18 1.41
60.8 71.6 14.07 9.34 0.34 14.07 9.34 0.58 14.07 9.34 0.99 14.07 9.34 1.28 14.07 9.34 1.60 11.40 8.05 1.41
64.4 77.0 17.42 11.03 0.53 17.42 11.03 0.90 17.42 11.03 1.48 17.42 11.03 1.82 16.76 10.71 2.01 11.92 8.46 1.41
67.0 80.0 19.18 12.16 0.66 19.18 12.16 1.14 18.85 12.00 1.74 18.00 11.59 1.88 17.18 11.18 2.01 12.18 8.94 1.41
71.6 86.0 23.45 13.10 1.19 21.78 12.31 1.47 20.10 11.55 1.75 19.26 11.18 1.89 18.38 10.80 2.02 12.95 8.64 1.41
75.2 89.6 24.28 12.62 1.20 22.61 11.90 1.48 20.93 11.20 1.76 20.09 10.86 1.90 19.16 10.50 2.02 13.45 8.42 1.41
AFR 11.7
Temp: CelsiusTC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CWB)
EDB –15 –10 –5 0 6 10 18
°C TC PI TC PI TC PI TC PI TC PI TC PI TC PI
15.0 2.80 1.27 3.36 1.34 3.93 1.40 4.49 1.47 6.08 1.72 6.61 1.77 7.68 1.89
21.1 2.63 1.31 3.19 1.37 3.76 1.44 4.32 1.50 5.88 1.76 6.41 1.81 7.47 1.93
22.0 2.56 1.32 3.12 1.39 3.69 1.45 4.25 1.52 5.80 1.77 6.33 1.83 7.29 1.90
24.0 2.49 1.33 3.05 1.40 3.62 1.46 4.18 1.53 5.72 1.79 6.25 1.84 6.85 1.74
25.0 2.46 1.34 3.02 1.41 3.58 1.47 4.15 1.54 5.68 1.79 6.21 1.85 6.63 1.67
27.0 2.39 1.36 2.95 1.42 3.51 1.49 4.08 1.55 5.60 1.81 6.13 1.87 6.19 1.53
Temp: FahrenheitTC: kBtu/hPI: kW
INDOOR OUTDOOR TEMPERATURE (°FWB)
EDB 5 14 23 32 43 50 64
°F TC PI TC PI TC PI TC PI TC PI TC PI TC PI
59.0 9.55 1.27 11.48 1.34 13.41 1.40 15.33 1.47 20.76 1.72 22.57 1.77 26.19 1.89
70.0 8.97 1.31 10.89 1.37 12.82 1.44 14.74 1.50 20.00 1.76 21.87 1.81 25.50 1.93
71.6 8.73 1.32 10.66 1.39 12.58 1.45 14.51 1.52 19.79 1.77 21.60 1.83 24.88 1.90
75.2 8.49 1.33 10.42 1.40 12.35 1.46 14.27 1.53 19.51 1.79 21.32 1.84 23.37 1.74
77.0 8.38 1.34 10.30 1.41 12.23 1.47 14.15 1.54 19.37 1.79 21.18 1.85 22.62 1.67
80.6 8.14 1.36 10.07 1.42 11.99 1.49 13.92 1.55 19.09 1.81 20.91 1.87 21.11 1.53
20 Split Type Air Conditioners FTXR-T Series
EDUS041820A Capacity Tables
60 Hz, 230 VCooling
Heating
AFR 9.9
BF 0.17
Temp: CelsiusTC, SHC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CDB)
EWB EDB 10 20 30 35 40 46
°C °C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14.0 20.0 3.21 2.41 0.23 3.21 2.41 0.38 3.21 2.41 0.67 3.21 2.41 0.89 3.21 2.41 1.16 3.21 2.41 1.55
16.0 22.0 4.12 2.74 0.34 4.12 2.74 0.58 4.12 2.74 0.99 4.12 2.74 1.28 4.12 2.74 1.60 3.59 2.48 1.56
18.0 25.0 5.10 3.23 0.53 5.10 3.23 0.90 5.10 3.23 1.48 5.10 3.23 1.82 4.91 3.14 2.01 3.75 2.60 1.56
19.4 26.7 5.62 3.56 0.66 5.62 3.56 1.14 5.53 3.52 1.74 5.28 3.40 1.88 5.03 3.28 2.01 3.84 2.74 1.56
22.0 30.0 6.87 3.84 1.19 6.38 3.61 1.47 5.89 3.38 1.75 5.64 3.28 1.89 5.40 3.17 2.03 4.09 2.64 1.56
24.0 32.0 7.12 3.70 1.20 6.63 3.49 1.48 6.13 3.28 1.76 5.89 3.18 1.90 5.64 3.09 2.03 4.25 2.58 1.56
Temp: FahrenheitTC, SHC: kBtu/hPI: kW
INDOOR OUTDOOR TEMPERATURE (°FDB)
EWB EDB 50 68 86 95 104 115
°F °F TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
57.2 68.0 10.95 8.22 0.23 10.95 8.22 0.38 10.95 8.22 0.67 10.95 8.22 0.89 10.95 8.22 1.16 10.95 8.22 1.55
60.8 71.6 14.07 9.34 0.34 14.07 9.34 0.58 14.07 9.34 0.99 14.07 9.34 1.28 14.07 9.34 1.60 12.24 8.45 1.56
64.4 77.0 17.42 11.03 0.53 17.42 11.03 0.90 17.42 11.03 1.48 17.42 11.03 1.82 16.76 10.71 2.01 12.81 8.86 1.56
67.0 80.0 19.18 12.16 0.66 19.18 12.16 1.14 18.85 12.00 1.74 18.00 11.59 1.88 17.18 11.18 2.01 13.10 9.34 1.56
71.6 86.0 23.45 13.10 1.19 21.78 12.31 1.47 20.10 11.55 1.75 19.26 11.18 1.89 18.42 10.82 2.03 13.95 9.02 1.56
75.2 89.6 24.28 12.62 1.20 22.61 11.90 1.48 20.93 11.20 1.76 20.09 10.86 1.90 19.25 10.53 2.03 14.51 8.79 1.56
AFR 11.7
Temp: CelsiusTC, PI: kW
INDOOR OUTDOOR TEMPERATURE (°CWB)
EDB –15 –10 –5 0 6 10 18
°C TC PI TC PI TC PI TC PI TC PI TC PI TC PI
15.0 2.80 1.27 3.36 1.34 3.93 1.40 4.49 1.47 6.08 1.72 6.61 1.77 7.68 1.89
21.1 2.63 1.31 3.19 1.37 3.76 1.44 4.32 1.50 5.88 1.76 6.41 1.81 7.47 1.93
22.0 2.56 1.32 3.12 1.39 3.69 1.45 4.25 1.52 5.80 1.77 6.33 1.83 7.29 1.90
24.0 2.49 1.33 3.05 1.40 3.62 1.46 4.18 1.53 5.72 1.79 6.25 1.84 6.85 1.74
25.0 2.46 1.34 3.02 1.41 3.58 1.47 4.15 1.54 5.68 1.79 6.21 1.85 6.63 1.67
27.0 2.39 1.36 2.95 1.42 3.51 1.49 4.08 1.55 5.60 1.81 6.13 1.87 6.19 1.53
Temp: FahrenheitTC: kBtu/hPI: kW
INDOOR OUTDOOR TEMPERATURE (°FWB)
EDB 5 14 23 32 43 50 64
°F TC PI TC PI TC PI TC PI TC PI TC PI TC PI
59.0 9.55 1.27 11.48 1.34 13.41 1.40 15.33 1.47 20.76 1.72 22.57 1.77 26.19 1.89
70.0 8.97 1.31 10.89 1.37 12.82 1.44 14.74 1.50 20.00 1.76 21.87 1.81 25.50 1.93
71.6 8.73 1.32 10.66 1.39 12.58 1.45 14.51 1.52 19.79 1.77 21.60 1.83 24.88 1.90
75.2 8.49 1.33 10.42 1.40 12.35 1.46 14.27 1.53 19.51 1.79 21.32 1.84 23.37 1.74
77.0 8.38 1.34 10.30 1.41 12.23 1.47 14.15 1.54 19.37 1.79 21.18 1.85 22.62 1.67
80.6 8.14 1.36 10.07 1.42 11.99 1.49 13.92 1.55 19.09 1.81 20.91 1.87 21.11 1.53
Split Type Air Conditioners FTXR-T Series 21
Capacity Tables EDUS041820A
C: 3D120263A
Symbols: Notes:
AFR : Airflow rate (m³/min.) 1. shows nominal (rated) capacities and power input.2. TC, PI and SHC must be calculated by interpolation using the figures in the
above tables. (Figures out of the tables should not be used for calculation.)3. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 25 ft (7.5 m)Level difference : 0 ft (0 m)
4. Airflow rate (AFR) and Bypass factor (BF) are tabulated above table.
BF : Bypass factor
EWB : Entering wet bulb temp. (°C) / (°F)
EDB : Entering dry bulb temp. (°C) / (°F)
TC : Total capacity (kW) / (kBtu/h)
SHC : Sensible heat capacity (kW) / (kBtu/h)
PI : Power input (kW)
22 Split Type Air Conditioners FTXR-T Series
EDUS041820A Capacity Tables
7.1 Capacity Correction Factor by the Length of Refrigerant Piping (Reference)The cooling capacity and the heating capacity of the unit have to be corrected in accordance with the length of refrigerant piping — the distance between the indoor unit and the outdoor unit.
<— line : cooling capacity><--- line : heating capacity>
7.1.1 09/12 Class
7.1.2 18 Class
Range of the refrigerant additional charge
Cap
acity
cor
rect
ion
fact
or
16.4 32.8 49.2 65.6 (ft)5 10 15 20 (m)
(R-410A)
Piping length
80
90
100
(%)
Range of the refrigerant additional chargeCap
acity
cor
rect
ion
fact
or
16.4 32.8 49.2 65.6 82.0 (ft)5 10 15 20 25
98.430 (m)
(R-410A)
Piping length
80
90
100
(%)
Split Type Air Conditioners FTXR-T Series 23
Operation Limit EDUS041820A
8. Operation Limit
RX09/12RMVJU9, RX18RMVJU9A
24 Split Type Air Conditioners FTXR-T Series
EDUS041820A Sound Level
9. Sound Level9.1 Measuring Location
Notes: 1. Operation sound is measured in an anechoic chamber.2. The operation sound measuring method is based on JIS standard.
Indoor Unit Outdoor Unit
(1 m)3.3 ft
2.6
ft(0
.8 m
)
MICROPHONE
(1 m)3.3 ft
MICROPHONE
Split Type Air Conditioners FTXR-T Series 25
Sound Level EDUS041820A
9.2 Indoor Unit
FTXR09TVJUW(S)
FTXR12TVJUW(S)
26 Split Type Air Conditioners FTXR-T Series
Sound Level EDUS041820A
9.3 Outdoor Unit
RX09RMVJU9
RX12RMVJU9
28 Split Type Air Conditioners FTXR-T Series
Electric Characteristics EDUS041820A
10.Electric Characteristics
C: 3D120260
Unit Combination Power Supply Compressor OFM IFM
Indoor Unit Outdoor Unit Hz - Volts Voltage Range MCA MFA RLA W FLA W FLA
FTXR09TVJUWFTXR09TVJUS RX09RMVJU9
60 - 208 Max. 60 Hz 253 VMin. 60 Hz 187 V 9.0 15 7.5 39 0.13 29 0.13
60 - 230
FTXR12TVJUWFTXR12TVJUS RX12RMVJU9
60 - 208 Max. 60 Hz 253 VMin. 60 Hz 187 V 9.1 15 7.5 39 0.15 29 0.19
60 - 230
FTXR18TVJUWFTXR18TVJUS RX18RMVJU9A
60 - 208 Max. 60 Hz 253 VMin. 60 Hz 187 V 12.8 15 10.75 110 0.38 29 0.21
60 - 230
Symbols: Notes:1. RLA is the max current that comes in cooling operation and heating
operation.2. Maximum allowable voltage variation between phases is 2%.3. Select wire size based on the larger value of MCA.4. Instead of a fuse, use a circuit breaker.5. Be sure to install a ground leak detector.
(This unit uses an inverter, which means that a ground leak detector capable of handling high harmonics must be used in order to prevent malfunctioning of the ground leak detector.)
MCA : Min. circuit amps (A)
MFA : Max. fuse amps (A)
RLA : Rated load amps (A)
OFM : Outdoor fan motor
IFM : Indoor fan motor
W : Fan motor rated output (W)
FLA : Full load amps (A)
30 Split Type Air Conditioners FTXR-T Series
EDUS041820A Installation Manual
11. Installation Manual11.1 Indoor Unit
Split Type Air Conditioners FTXR-T Series 31
Installation Manual EDUS041820A
Note: Recommend using AWG14, stranded and insulated wire for connections between indoor and outdoor units.
38 Split Type Air Conditioners FTXR-T Series
EDUS041820A Installation Manual
11.2 Outdoor Unit11.2.1 09/12 Class
Split Type Air Conditioners FTXR-T Series 45
Optional Accessories EDUS041820A
13.Optional Accessories13.1 Option List13.1.1 Indoor Unit
Notes: 1 3 m (BRCW901A03) or 8 m (BRCW901A08) length wired remote controller cord is necessary.2 Timer clock and other devices ; obtained locally.3 An interface adaptor (KRP928BB2S) is also required for each indoor unit.4 Standard accessory
13.1.2 Outdoor Unit
Note: Standard accessory
Option Name Model Name
1 Wired remote controller 1 BRC944B2
2 Wired remote controller cord (shielded wire)
Length 9.8 ft (3 m) BRCW901A03
Length 26.3 ft (8 m) BRCW901A08
3 Wireless LAN connection adaptor BRP072A43
4 Wiring adaptor for timer clock / remote controller 2(normal open pulse contact / normal open contact) KRP413BB1S
5 Central remote controller 3 DCS302C71
6 Unified ON/OFF controller 3 DCS301C71
7 Schedule timer controller 3 DST301BA61
8 Interface adaptor for DIII-NET (residential air conditioner) KRP928BB2S
9 Titanium apatite deodorizing filter (without frame) 4 KAF970A46
10 Remote controller loss prevention with chain KKF910A4
Option Name 09/12 Class 18 Class
1 Air direction adjustment grille KPW937E4 KPW063A4
2 Back protection wire net KKG067A41 KKG063A42
3 Drain plug KKP937A4
4 Drain pan heater FTDBHMS, KEH067A41E
FTDBHML, KEH063A4E
5 Snow hood (intake side plate) KPS067A41 KPS063A41
6 Snow hood (intake rear plate) KPS067A42 KPS063A44
7 Snow hood (outlet) KPS067A44 KPS063A47
104 Split Type Air Conditioners FTXR-T Series
EDUS041820A Optional Accessories
13.2 <BRC944B2> Wired Remote Controller13.2.1 Installation Manual
Switch box (Field supplied parts)
Machine screws (M4 x 16)
For the field supplied switch box,use optional accessoriesKJB1111A or KJB2121A.
KJB2121A
CAUTION1. No switch box or staple is supplied. Prepare them locally.2. No remote controller cord is supplied. Prepare the optional remote controller cord 4 wire.3. Be sure to turn off the power to any apparatus connected prior to mounting.4. Prior to mounting equipment, touch something metallic such as a doorknob to remove static
electricity from your body. Never touch the remote controller board or the adapter board.5. Keep the wiring away from any other power source lines to avoid electric noise (external noise).6. Select a flat surface, wherever possible, to mount the remote controller. To prevent deformation
of the cases, do not overtighten the mounting screws.
Insert a bladed screwdriver into the concave ( ) in the remote controller lower case to remove the upper case assembly (two locations).
(1) Exposed mountingSecure the remote controller lower case with the two supplied wood screws.
(2) Embedded mountingSecure the remote controller lower case with the two supplied machine screws.
The remote controller board is located on the upper case. Take care not to scratch the board with the screwdriver.
1. Securing the remote controller lower case
Upper case
Lower caseScrewdriver
To remove, insert and twistthe screwdriver slightly.
Wood screws (φ3.5mm x 16mm)
KJB1111A
Split Type Air Conditioners FTXR-T Series 105
Optional Accessories EDUS041820A
Remove the upper case of the remote control adapterand secure the lower case assembly.
During mounting of the remote controller cord, be careful not to pinch or otherwise damage the wires.(Remote controller cord 4 wire)
2. Securing the remote control adapter
3. Wiring
4. Placing the upper case assembly of the remote controller and the upper case of the remote controller adapter back into their original positions
5. Temperature indication change
Wood screws (φ3.5mm x 16mm)
(Mounting with supplied wood screws)
Remote control adapter (attached)
(Mounting with supplied double-face adhesive tape)
Double-faceadhesive tape
Attached five-wire cord
Remote controller cord (Note 1)
Connector
ConnectorConnector
Tie-band(to secure the cord)
Tie-band (to secure the cord)
Tie-band(to secure the cord)
Upper caseassembly
Lower case
(Cord drawn out on the back)
Catch the lower hook first.
(Cord drawn out on the top)To remote control adapter
Remote controllerboard
Remote controllerboard
Note 1) Ground the both ends of the shielded wire.
Using wire cutters, make a notch for wiring and then seal the notch to ensure it is waterproof.
To indoor unit S21-HA connector
Remote controller cord 4 wire
Item No.
BRCW901A03
BRCW901A08
Length
Approx. 3m (10ft)
Approx. 8m (26ft)
To change from Celsius temperature indication to Fahrenheit one
Press and hold down at the
same time for 5 seconds while the Celsius temperature is indicated. ← See Operation Manual
3P202923-2B
106 Split Type Air Conditioners FTXR-T Series
EDUS041820A Optional Accessories
13.2.2 Operation Manual
4
Controller Commands and their Corresponding FunctionsRun indicator lamp (green)
ON/OFF buttonPress to start the system.Press again to stop the system.
Mode select button
Swing button
Timer setting buttonSets the current time and timer.
Temperature adjustmentbuttonAdjusts the temperature setting.
Airflow rate buttonAdjusts the airflow rate.
Time setting buttonfor the timer
Display
Timer select button
Displays the operatingconditions.
Clock setting button
( page 9)
( page 7)
( page 5)
Selects an operation mode.
Displays the operatingconditions.
Selects one of the following:ONE TIME timer ON DAILY timer ONTIMER OFF
CAUTION•This remote controller cannot be used together with a standard wireless remote controller.Otherwise, what appears on this remote controller's display may fail to correspond to actual operating conditions.
Split Type Air Conditioners FTXR-T Series 107
Optional Accessories EDUS041820A
5
Preparation before Operation Checking the power
If nothing appears on the remote controller's display, turn on the circuit breaker.
Setting the current time
1 Press .
The current time starts blinking.
lights up.
2 Press and set the current time. Hold the button down to rapidly advance the time.
3 Press .
(This completes the current time setting) The clock's accuracy is ±30 seconds per month.
blinks.
2
1·3
Avoid overcooling or overheating. Moderate room temperature settingcontributes to power saving.
Hang a blind or a curtain on the window. This will enhance the cooling/heating effectby intercepting direct sunlight and drafts.
A clogged air filter reduces the cooling/heating effect and wastesenergy. Clean the air filter monthly (everytwo weeks as required) or so.
Please take note of the following points
Electric power is consumed even when the airconditioner is not in operation.
When the unit is not used for a long period oftime such as during off-season, turn off the breaker.
Operating conditions If the operation is continued under any
conditions other than the following, the safetydevice may work to stop the operation. Also, dew may form on the indoor unit and dripfrom it. (Cooling/DRY)
Operation limit differ according to the model.
Notes
To use the unit efficiently
Recommendedtemperature setting
For cooling ·············· 26~28˚C (79˚F~82˚F)For heating ············· 20~22˚C (68˚F~72˚F)
Cooling
DRY
Heating
Outdoor temp.Room temp.Indoor humidityOutdoor temp.Room temp.Indoor humidity
Outdoor temp.Room temp.
-10 to 46˚C (14˚F to 115˚F)18 to 32˚C (64˚F to 90˚F)
Less than 80%-10 to 46˚C (14˚F to 115˚F)18 to 32˚C (64˚F to 90˚F)
Less than 80%
-15 to 20˚C (5˚F to 68˚F)Less than 27˚C
108 Split Type Air Conditioners FTXR-T Series
EDUS041820A Optional Accessories
6
1 Press and hold down at the same time for 5 seconds while the Celsius temperature is indicated.
Preparation before Operation
2 Press and hold down at the same time for 5 seconds while the Fahrenheit temperature is indicated.
Setting Temperature Indication changeTemperature indication can be changed between Celsius and Fahrenheit before use.
1·2
Notes
Temperature indication change between Celsius and Fahrenheit on the remote controller Change the temperature indication in the modes other than the DRY mode.
In the DRY mode, temperature indication setting cannot be changed because the temperature is not indicated. When the Fahrenheit temperature indication is changed to Celsius one, the temperature value
(0.5˚C) will be rounded up. Thus, the preset temperature may be changed.Example:
A preset temperature of 65˚F (equivalent to 18.5˚C) will be changed to 19˚C (66˚F) b y changing the temperature indication.In this case, if you change the Celsius temperature indication again to the Fahrenheit one, the preset temperature is shown not as 65˚F but as 66˚F (equivalent to 19˚C). If the preset temperature is 66˚F (equivalent to 19˚C) and is changed to the Celsius temperature indication, the indication becomes 19˚C (66˚F). In this case, no change by the temperature indication change is observed.
When the temperature indication change is set, the preset temperature is transmitted to the indoor unit so that the reception sound will be heard from the indoor unit.
To change from Celsius temperature indication to Fahrenheit one
To change from Fahrenheit temperature indication to Celsius one
Split Type Air Conditioners FTXR-T Series 109
Optional Accessories EDUS041820A
7
1 Press to select your desired
operation mode.
Each time the button is pressed, the mode changes as follows.
The system does not have the FAN mode.
Automatic · DRY · Cooling · Heating Operation
2 Press .
The run indicator lamp lights up.
Select your desired operation mode.Once preset, the system can get restarted in the same operation mode.
1
2
Run indicator lamp (green)
(Automatic) (DRY)
(Heating) (Cooling)
(DRY) (Cooling) Cooling onlymodel
Heat pumpmodel
To stop the operation:
Press again.
The run indicator lamp goes out.
In Automatic, the temperature setting and operation mode (DRY, Cooling or Heating) are automatically selected according to the room temperature and outdoor temperature at the time of starting operation.
DRY operation In this mode, humidity is removed from the air.
Note
While running in the DRY mode, you may feel cool or warm air from the air outlet. In this case, readjust the airflow direction with the vertical airflow direction louvers. (except Duct Connected type)
Automatic operation
110 Split Type Air Conditioners FTXR-T Series
EDUS041820A Optional Accessories
8
Heating operation Since the heating operation is performed by
taking the heat from outdoor into the room, the heating capacity decreases as the outdoor temperature lowers. If the room is not heated sufficiently, it is recommended to use other heating appliance at the same time.
Since the air conditioner heats the whole room by circulating hot air, it takes some time to heat the entire room completely.
If the outdoor unit gets frosted during heating operation, the heating capacity is decreased. In this case, the unit starts defrosting operation.
No hot air comes out of the indoor unit during defrosting operation.
To adjust the temperature and airflow rate:
To adjust the airflow direction: ( page 9)
OperationmodeSetting
to be adjustedAutomatic DRYCooling Heating
(Temperature)
(Airflow rate)
Temperature cannot be adjusted.
Airflow rate cannot be adjusted.
Temperature is adjustable.
Recommended temperature
Cooling : 26˚C-28˚C (79˚F~82˚F)
Five levels of airflow rate settingfrom " " to " " plus " " are available.
Heating : 20˚C-22˚C (68˚F~72˚F)
When the unit runs in the cooling or heating mode at a low airflow rate, the cooling or heating effect may be insufficient.
Split Type Air Conditioners FTXR-T Series 111
Optional Accessories EDUS041820A
9
Notes
In fixing the horizontal airflow direction, keep the horizontal airflow direction louvers tilted downward in the heating mode, and keep them nearly horizontal level in the cooling or DRY mode. This will enhance the cooling and heating effect.
On the air conditioners with vertical and horizontal swing function, be sure to adjust the airflow directions using the remote controller. Do not forcibly adjust louvers by hand or a malfunction may occur.
Adjusting Airflow Direction
1 Press during operation.
Each time the button is pressed, the airflow direction louvers change their movement.
Adjust the airflow direction for maximum comfort.
To adjust the Airflow Direction
1
Wall Mounted Types (without horizontal swing function)
The horizontal airflow direction louversmove up and down.
The louvers stop just when the button is pressed.
Swing
Airflow directionlouvers stop
Adjustment of horizontal airflow direction The automatic moving range of the horizontal airflow direction louvers varies depending on the
operation mode.
112 Split Type Air Conditioners FTXR-T Series
EDUS041820A Optional Accessories
10
Wall Mounted Type (with horizontal swing function)
The horizontal airflow direction louversmove up and down.
The horizontal airflow direction louversstop just when the button is pressed.Then the vertical ones start moving right and left.
The vertical airflow direction louvers stop just when the button is pressed.
Swing horizontally
Swing vertically
Airflow directionlouvers stop
The vertical and horizontal louvers cannot move at the same time.
Note
The operating procedure and remote controller display are different depending on the indoor unit being connected.
Read How to Adjust the Airflow Direction in the air conditioner’s Operation Manual.
Duct Connected Type (without swing function)This function cannot be used.
Split Type Air Conditioners FTXR-T Series 113
Optional Accessories EDUS041820A
11
Timer Operation
To select the ONE TIME timer mode:
1 Press to select the ONE TIMEtimer mode.
Each time the button is pressed,the modes change as follows.
The Timer Operation feature automatically turns off operation when you go to sleep and turns it back on when you wake up.Use the DAILY Timer mode on weekdays, and the ONE TIME timer mode on weekends.
To cancel the timer settings:
1 Press to clear the timer settings.
Precautions in setting the timer Before starting the timer operation, make sure
the current time is correct. If not, set the clock correctly. ( page 5)
In making time settings, is displayed to make it easy to disable the timer too.
If one minute has passed before making any timer setting, the previous timer settings are reintroduced and the timer is on standby.
In this case, use the (time setting) button and make your desired timer settings.
ONE TIME timer
DAILY timer
TIMER OFF
ON time
OFF time
(Timer settings displayed)
1
2·4·6
3·5
The timer lamp lights up.
The ONE TIME or DAILY TIMER disappears from the display, and the timer lamp goes out too.
Notes
Even when the timer has been off, its programmed settings are still in memory.
If the system has the timer control ON but you start and stop it manually using the ON/OFF button before the designated ON time, the system will restart again at the programmed ON time.
Timer operation When the ON timer is programmed, the
system starts one hour (maximum) earlier so that the temperature set by the remote controller is reached just in time.
When the ONE TIME timer is programmed, the current time is no longer displayed.
114 Split Type Air Conditioners FTXR-T Series
EDUS041820A Optional Accessories
12
1 Press to select the ONE TIME timer.
2 Press .
3 Press to make the ON timer setting.
Example of display with the ONE TIME timer programmed
ONE TIME timerOnce the timer has been activated and then deactivated, it is in the OFF mode.The ON or OFF timers can be programmed.
light up.
ONE TIME
blinks.
Each time the button is pressed, the setting changes in a 10-minute increment or decrement. Hold the button down to advancequickly.
When the ON timer is not used, save the setting as
4 Press .
5 Press to make the OFF timer setting.
6 Press .(The ONE TIME timer is now programmed.)
Both of the ON and OFF timecannot be set as
blinks.
When the OFF timer is not used, save the setting as .
ONE TIME timer programmed.The set time is displayed.
ON timer activated and system starts.The ON timer setting no longer displays.
OFF timer activated, and system stops. The timer setting no longer displays.
Notes
In the following cases, reset the clock (the time setting is kept in the
memory). The circuit breaker has been
activated. The power fails.
Split Type Air Conditioners FTXR-T Series 115
Optional Accessories EDUS041820A
13
Timer Operation To select the DAILY timer mode:
1 Press to select the DAILY timer mode.
Each time the button is pressed, the modes change as follows.
To cancel the timer settings:
1 Press to clear the timer settings.
Example of display with DAILY timer programmed
ONE TIME timer
DAILY timer
TIMER OFF
The timer lamp lights up.
1 2
1 2
ON time
24-hour timer display
OFF time
Timers
The settings of timers and can be seen at a glance.
Two pairs of ON and OFF time settings can be programmed.
(Timer settings displayed)
1
2·3
2
The ONE TIME or DAILY TIMER , and the timer lamp are no longer displayed.
Timers and programmed.
Timer alone programmed.
1 12
Note
The system starts and stops repeatedly until the DAILY timer is set off. Before you leave home for a long time, set the DAILY timer off.
116 Split Type Air Conditioners FTXR-T Series
EDUS041820A Optional Accessories
14
1 Press to select the DAILY timer.
2 Make the ON and OFF time settings. Take the steps from � to �.
Program example: 8:00 ~ 10:00, and 18:00 ~ 23:00
DAILY timerAfter programming, the system starts and stops each day at the preset times. Two pairs of time settings can be programmed.(Example: 8:00 ~ 10:00, and 18:00 ~ 23:00)
DAILY timer indication appears.
lights up.
3 Press . The DAILY timer is now programmed.
Note
If the following appears on the display, the timer must be reprogrammed.
The 24-hour timer display is blinking.
The 24-hour timer display is blinking.
This means that Timers � and � are programmed for the same time settings. New time settings must be made.
This means that the timer has not been programmed yet.
When the timer is not used, save the setting as
Press Pressto make the timer setting.
1
Procedure
Settings
ON time setting
OFF time setting
OFF time setting
2
ON time setting
2
1
� �
� �
� �
�
Tim
erT
imer
When the timer is not used, save the setting as
Split Type Air Conditioners FTXR-T Series 117
Optional Accessories EDUS041820A
15
CleaningCleaning the remote controller
Wipe it clean with soft, dry cloth.Do not use any water hotter than 40˚C (104˚F), or volatile liquids such as benzine, gasoline and thinner, polishing powder, or anything hard such as a scrub brush.
When the unit is not used for a long time1 On a sunny day, keep the system running for
half a day in the FAN mode to dry it up inside.
3
12
FAN mode
1 Press to select the cooling mode.
2 Press to adjust the set
temperature to 32˚C (90˚F).
3 Press .
The airflow rate remains the same, and is not adjustable.
Run the system when the room temperature is below 28˚C (82˚F).
2 Finally turn off the circuit breaker dedicated for the room air conditioner.
3 Clean the air filter and place it back into position.
3P202922-2B
118 Split Type Air Conditioners FTXR-T Series
EDUS041820A Optional Accessories
13.3 <BRCW901A03/08> Wired Remote Controller Cord
3P201487-1
Split Type Air Conditioners FTXR-T Series 119
Optional Accessories EDUS041820A
13.4 <BRP072A43> Wireless LAN Connection Adaptor
120 Split Type Air Conditioners FTXR-T Series
Optional Accessories EDUS041820A
13.5 <KRP413BB1S> Wiring Adaptor for Timer Clock / Remote Controller
128 Split Type Air Conditioners FTXR-T Series
Optional Accessories EDUS041820A
13.6 <DCS302C71> Central Remote Controller13.6.1 Installation Manual
132 Split Type Air Conditioners FTXR-T Series
EDUS041820A Optional Accessories
13.6.2 Operation Manual
Split Type Air Conditioners FTXR-T Series 137
EDUS041820A Optional Accessories
13.7 <DCS301C71> Unified ON/OFF Controller13.7.1 Installation Manual
Split Type Air Conditioners FTXR-T Series 163
Optional Accessories EDUS041820A
13.7.2 Operation Manual
168 Split Type Air Conditioners FTXR-T Series
Optional Accessories EDUS041820A
13.8 <DST301BA61> Schedule Timer ControllerEnables you to connect and control weekly schedule for up to 128 indoor units all together.
13.8.1 Specifications / Dimensions
Simultaneous control of up to 128 indoor units is managed by a week schedule.
The start and stop time for twice a day can be set for the week in increments of 1 minute.
By combining with a central remote controller and schedule timer, you can construct a system that matches the size and use of the building.
If used together with a central remote controller, you can set up to 8 schedule patterns which can be distributed among zones as desired using the central remote controller.
Is equipped with a compensation function for power failure up to 48 hours.
Features thin design of a mere 16 mm in thickness. (Uses JIS recessed box for 2.)
Wiring can be up to 1 km in length. Applicable wiring methods include bus and star in addition to crossover type.
Can be used in combination with other D-BACS equipment.
SPECIFICATIONSSpecifications
Outline drawings
Specifications and appearance subject to change without notice.
Display of time 12-hour digital display
Clock cycle type Quartz clock type
Clock accuracy Within ±30 sec./month (environmental temperature from 15˚C to 35˚C)
Timer programmingTwo pairs of programmed time for both system start and system off can be set in units of minute for each day of the week
Power failure compensation time Approximately 48 hours for a single occurrence of power failure (clock with No. of programmed time)
Size 120 (W) × 120 (H) × 53 (D) mm(Width/Height/Depth)
Weight Approximately 210g
120 16 37
71120
170 Split Type Air Conditioners FTXR-T Series
EDUS041820A Optional Accessories
13.8.2 Installation Manual
Split Type Air Conditioners FTXR-T Series 171
Optional Accessories EDUS041820A
13.8.3 Operation Manual
176 Split Type Air Conditioners FTXR-T Series
EDUS041820A Optional Accessories
13.9 <KRP928BB2S> Interface Adaptor for DIII-NET (Residential Air Conditioner)
Split Type Air Conditioners FTXR-T Series 189
Optional Accessories EDUS041820A
13.10 <KPW937E4> Air Direction Adjustment Grille
192 Split Type Air Conditioners FTXR-T Series
Optional Accessories EDUS041820A
13.11 <KPW063A4> Air Direction Adjustment Grille
194 Split Type Air Conditioners FTXR-T Series
Optional Accessories EDUS041820A
13.12 <KKG067A41> Back Protection Wire Net
3P397444-1
196 Split Type Air Conditioners FTXR-T Series
EDUS041820A Optional Accessories
13.13 <KKG063A42> Back Protection Wire Net
2P403095-1
Split Type Air Conditioners FTXR-T Series 197
Optional Accessories EDUS041820A
13.14 <FTDBHMS, FTDBHML, KEH067A41E, KEH063A4E> Drain Pan Heater
198 Split Type Air Conditioners FTXR-T Series
Optional Accessories EDUS041820A
13.15 <KPS067A41> Snow Hood (Intake Side Plate)
204 Split Type Air Conditioners FTXR-T Series
Optional Accessories EDUS041820A
13.16 <KPS067A42> Snow Hood (Intake Rear Plate)
206 Split Type Air Conditioners FTXR-T Series
Optional Accessories EDUS041820A
13.17 <KPS067A44> Snow Hood (Outlet)
208 Split Type Air Conditioners FTXR-T Series
Optional Accessories EDUS041820A
13.18 <KPS063A41> Snow Hood (Intake Side Plate)
210 Split Type Air Conditioners FTXR-T Series
Optional Accessories EDUS041820A
13.19 <KPS063A44> Snow Hood (Intake Rear Plate)
212 Split Type Air Conditioners FTXR-T Series
Optional Accessories EDUS041820A
13.20 <KPS063A47> Snow Hood (Outlet)
214 Split Type Air Conditioners FTXR-T Series
All rights reservedc
1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor.
Cautions on product corrosion
Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorized parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.
Read the user's manual carefully before using this product. The user's manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
Specifications, designs and other content appearing in this brochure are current as of February 2020 but subject to change without notice.
AK