    1NOVEMBER, 2007 HD103PAGE OF 14

    TECHNICAL DATA :

    Deluge Valve is known as a s yst em cont rol valve in a delugesyst em, used for fast applicat ion of wat er in a spray syst em.To prot ect areas such as power t ransformer inst allat ion,

    st orage t ank, conveyor prot ect ion and ot her indust r ialapplicat ion et c. Wit h t he addit ion of foaming agent t hey do

    prot ect Aircr aft hangar and inflammable liquid fire.

    VALVE OPERATIONHD Deluge valve is a quick r elease, hydraulically operat eddiaphragm valve. It has t hree chambers, isolat ed fromeach ot her by t he diaphragm operat ed clapper and seatseal. While in SET posit ion, wat er press ure is t r ansmit t edt hrough an ext ernal bypass check valve and rest rict ionorifice from t he syst em supply side t o t he t op chamber,so t hat supply pressure in t he t op chamber act acrosst he diaphragm operat ed clapper which holds t he seat

    against t he inlet supply pr ess ur e because of t hedifferent ial pressure design. On det ect ion of fire t het op chamber is vent ed t o at mosphere t hrough t he out letpor t via opened act uat ion devices. The t op chamberpressure cannot be replenished thr ough t he rest rict edinlet por t , and t he upward force of t he supply pressur elift s t he clapper allowing t he wat er flow t o t he syst em

    piping net work and alarm devices.

    TRIM DESCRIPTION

    a) BASIC TRIM

    The basic t r im is r equir ed on all HD Deluge valver egard less o f r e lease syst em. I t cont a in t hosecom ponent s whic h ar e r equir ed in al l t ypes ofinst allat ion, suc h as t he M ain dr ain valve, Primingconnect ion, Drip check valve, Emergency r elease valve

    and pressure gauges.

    MODEL H

    NOM INAL SIZE 2 00 , 1 50 , 1 00 and 8 0 NB

    MAXIMUM SERVICE 12 Bar ( 175 psi )

    PRESSURE

    THREADED OPENING BSPT

    M OUN TIN G Ver t ical or Hor izont al

    mount ing

    FACTORY HYDROSTATIC 25 Kg./sq.cm. ( 35 5 psi )

    TEST PRESSURE

    FLANGE CONNECTION ANSI B 16.5 # 150

    RECOM MENDED 2 00 NB- 3 00 t o 1 15 0 m3/hr

    FLOW RATE 150NB - 170 t o 650 m3/hr

    1 00 NB - 50 t o 225 m3/hr

    8 0 NB - 30 t o 110 m3/hr

    FRICTIONAL LOSS IN 200NB - 44 .00met res

    TERMS OF 150NB - 35 .00 met r es

    EQUIVALENT LENGTH 100NB - 15.00met res

    OF PIPE (C-1 20 ) 8 0NB - 1 0.5 0 met r es

    WET PILOT SPRINKLER As per gr aph in t he

    HEIGHT LIMITATION cat alogue.

    NET WEIGHT 200NB - 172 Kg.

    WITHOUT TRIM 150NB - 101 Kg.

    1 00 NB - 6 9 Kg.

    8 0NB - 4 6 Kg.

    FINISH Fir e r ed epoxy paint ed

    APPROVAL Except 2 0 0NB all ot her s izes

    are UL list ed.

    ORDERING 1 . Size of valve.IN FORM ATION 2 . Flange s pec if icat i on.

    3. Valve tr im vert ical orhor izont al.

    4. Trim t ype - Dry pilot,Wet pilot , Electr ic,Test and alarm.

    LISTED

    9P76

    DELUGE VALVEM ODEL-H

    DESCRIPTION

  • 8/7/2019 HD103 - DV - H

    2/14

    2NOVEMBER, 2007 HD103PAGE OF 14

    c) W ET PILOT TRIM( HYDRAULIC RELEASE )

    Wet pilot operat ion uses a pilot line of closed sprinklerscont aining pressurized wat er, supplied t hrough t heupst r eam side of t he Deluge valve, t hrough a rest r ict edorifice. All t he release lines are connect ed t o a commonrelease line. Due t o release fo any one of t he releasedevice, t he wat er presure in t he t op chamber of t he

    Deluge valve drops, and t he Deluge valve opens.

    d) ELECTRIC RELEASE TRIMTo act uat e a Deluge valve elect r ically, a s olenoid valve is

    provided t o drain t he wat er from t he t op chamber oft he Deluge valve. A pr ess ur e s wit ch is pr ovided t oact ivat e an elect ric alarm, t o shut down t he desiredequipement or t o give "Tr ipped" indicat ion t o t he Delugevalve. In addit ion t o t his a pr ess ure s wit ch can alsomonit or "Low air pressur e" and "Fire condit ion" when usedin dry pilot air line.

    e) TEST AND ALARM TRIM W ITHSPRINKLER ALARM

    This t rim is s upplied wit h t he spr inkler alarm bell, whichbells on act uat ion of t he Deluge valve. A t est valve isprovided t o t est t he normal oper at ion of t he sprinkleralarm bell.

    RESETTING PROCEDURE FOR THE

    DELUGE VALVE(i) Close t he upst ream side st op valve pr ovided below

    t he deluge valve.

    ii) Open bot h t he drain valves and close when t he flowof wat er has ceased.

    (iii) Close t he r elease device/replace t he S pr inkler ifr elease was t hrough Sprinkler /Q.B.Det ect or.

    iv) Inspect and r elease if required, or close t he sect ionof t he det ect ion syst em subject ed t o "Fire condit ion".

    (v) In case of dry pilot det ect ion syst em, open t he airsupply valve t o build-up air pr ess ur e. Open t he

    b) DRY PILOT TRIM (PNEUMATIC RELEASE)Dry pilot operat ion uses a pilot line of closed Spr inkler/QB det ect or cont aining air under pr essure, locat ed int he area t o be prot ect ed. It requires regulat ed dry airsupply wit h main supply point t hrough rest rict ed or ifice.

    The air press ure t o be maint ained as spec ified in t hecat alogue of Dry Pilot Act uat or, Model-H. The pilot lineis connect ed t o air inlet side of act uat or. The t opchamber of t he deluge valve is connect ed t o wat er inletside of act uat or.

    When t here is an air pr essure dr op, or due t o releaseof any of t he r elease device on det ect ion of fir e, t hediaphragm of act uat or is lift ed and allows t he wat er t odrain. This r eleases t he wat er pres sur e in t he t opchamber of t he deluge valve, allowing t he deluge valvet o open and wat er t o flow int o t he syst em piping & alarmdevices. Recommended air supply pressur e for dry pilott rim syst em is 3 t o 4 kg/sq.cm.

    priming valve fully. Open t he upst ream side of t hest op valve provided below t he Deluge valve. No wat ershould flow int o t he sys t em.

    Not e : The valve can be reset wit hout undergoing aboveprocedur e, by just closing / replacing t he release deviceas valve is aut o reset t ype. The reset t ime may be longor cause vibr at ion while c losing depending on backpressur e at t he out let of t he valve.

    CAUTION(a) Do not close t he pr iming valve, down s t r eam

    and upst ream st op valves, while t he syst em isin service.

    (b) The releasing device must be maint ained in t heopen posit ion, when act uat ed, t o prevent t hedeluge valve from closure.

    (c) While using a Deluge valve in t he wet pilot syst emt he height and t he lengt h of t he wet pilotdet ect ion line is t o be limit ed as shown in t hewet pilot spr ionkler height limit at ion graph.

    (d) Do not connect t he Spr inkler Alarm out letdr ainline t o c lose a common drain as it maycr eat e back pressur e and Sprinkler Alarm maynot funct ion.

    (e) Deluge valve mus t have s uppor t t o absor bsudden opening or closing vibrat ion shock t o t hepiping.

    (f ) The r espons ibi l i t y of maint enance of t hepr ot ect ion sys t em and devices in pr operoperat ing condit ion lies wit h t he owner of t hesyst em.

    SYSTEM TESTING PROCEDURE

    (i) Keep t he upst r eam side of t he st op valve part iallyopen. To avoid wat er f low t o syst em side close t hesyst em side st op valve. This valve is t o be kept inopen posit ion aft er t he t est ing is complet ed.

    (ii) Let any of t he release devices t o t r ip. This will r esultin a sudden drop of wat er pr essure in t he deluge

    valve t op chamber r esult ing t he deluge valve t o open.Close t he upst ream side st op valve immediat ely.

    (iii) Reset t he valve as per t he procedure given underheading "RESETTING PROCEDURE FOR THE DELUGEVALVE".

    INSPECTION AND M AINTENANCEInst alled syst em piping net work must be flushed pr operlybefor e placing t he Deluge valve in ser vice.

    A qualified and t r ained per son mus t commiss ion t hesyst em. Aft er few init ial successful t est an aut horizedpers on must be t r ained t o perf orm inspect ion and

    t est ing of t he syst em. It is recommended t o have regularinspect ion and t est run of t he syst em as per NFPA

  • 8/7/2019 HD103 - DV - H

    3/14

    3NOVEMBER, 2007 HD103PAGE OF 14

    guideline or in accor dance t o t he organisat ion having

    local jurisdict ion.

    (i) W ARNINGInspect ion and t est ing is t o be carr ied out only by

    aut hor ised and t rained per sonnel. DO NOT TURN OFFt he wat er supply or close any valve t o make repair(s)or t est t he valve, wit hout placing a roving fire pat r olin t he area covered by t he syst em. Also infor m t helocal securit y personnel and cent r al alarm st at ion,so t hat t here is no false alar m signal.

    It is r ecommended t o carr y out physical inspect ionof t he syst em at least t wice in a week. The inspect ionshould ver ify t hat all t he cont rol valves are in pr operposit ion as per t he syst em r equirement and nodamage has t aken place t o any component .

    (ii) NORMAL CONDITION(a) All main valves ar e open and are s ealed wit h

    t amper pr oof seal.

    (b) Drain valves must be kept closed.

    (c) No leak or drip is det ect ed from t he drip valve.

    (d) All t he gauges except t he sys t em side wat erpres sur e gauge, should show t he r equiredpressure.

    (e) There should be no leakage in t he syst em.

    (iii) NORM AL CONDITION TEST

    (a) The sys t em s hould be chec ked for nor malcondit ion at least once in a week.

    (b) Test t he s pr inkler alarm bell or elect r ic alarmby t urning t he alarm t est valve t o t he t estposit ion. The alar m should sound. This t estshould be carr ied out at least once in a week.

    (c) Depress t he drip valve knob. Significant wat eraccumulat ion indicat es a possible seat leakage.

    (d) Conduct t he wat er f low t est as per t heprocedure of syst em t est ing at least once amont h.

    (iv) PERIODIC CHECKConduct t he wat er flow t est by actuat ing few of t her elease devices pr ovided in t he s yst em.Clean allst r ainer (s) and priming line r est r ict ion.This t est ist o be carried out at least once in t hree mont hs.

    ABN ORM AL CONDITION

    (i) ALARM FAILS TO SOUND(a) Check for any obst ruct ion in t he alarm t est line,

    make cert ain t hat t he sprinkler alarm is free t ooper at e.

    (b) If an elect r ic alarm is pr ovided, check t he

    elect rical circuit ry t o t he alarm.

    (ii) FALSE TRIPS(a) Check for clogging in priming line, r est r ict ion

    orifice c heck valve, pr iming valve & s t rainer.

    (b) Leakage in t he release syst em.

    (c) The deluge air panel orifice clogged or low supplypressure.

    (iii) LEAKAGE THROUGH THE DELUGE VALVE(a) Damaged deluge valve seat or obst r uct ion on

    t he seat face by foreign object .

    (b) Leakage in release syst em.

    (c) Part ly clogged pr iming line r est r ict ion or ifice

    check valve.

    (d) Low air pres sur e on release syst em line or

    leakage in release syst em.

  • 8/7/2019 HD103 - DV - H

    4/14

    4NOVEMBER, 2007 HD103PAGE OF 14

    VALVENOMINAL 'A' 'B'

    SIZE

    200 NB 552 360

    150 NB 462 321

    100 NB 412 290

    80 NB 372 272

    DELUGE VALVE MODEL - H SIZE 200/ 150 / 100 / 80 NB

    DIM ENSION in millimet er ( Approximat e )

    20

    18

    1

    3

    3

    A

    B

    7

    5

    4

    2

    3

    17

    16

    21

    10

    9

    6

    19

    15

    14

    13

    8

    12

    PART NO. ITEM 200 150 100 80 DESCRIPTION 200 150 100 80 M ATERIAL SPECIFICATION

    NB NB NB NB NB NB NB NB

    1 3641 2421 2501 2781 HOUSING 1 1 1 1 CAST STEEL /ASTM A216 WCB

    2 9147 9147 9147 9147 LOCK NUT 1 1 1 1 STAINLESS STEEL 304

    3 9135 9135 9135 9135 HEX NUT 1 1 1 1 STAINLESS STEEL 304

    4 3646 2426 2506 2785 SEAT 1 1 1 1 BRONZE IS:318 LTB-II/ASTM B62

    5 8537 9783 9784 9791 "O" RING 1 1 1 1 NEOPRENE RUBBER

    6 9112 9112 9112 - HEX HEAD BOLT 6 4 4 - STAINLESS STEEL 304

    7 3645 2425 2505 2789 RUBBER CLAMP 1 1 1 1 BRONZE IS:318 LTB-II/STM B 62

    8 3648 2428 2508 2787 RUBBER SEAT 1 1 1 1 NEOPRENE RUBBER

    9 9986 9986 9986 9986 "O" RING 1 1 1 1 NEOPRENE RUBBER

    10 3650 2432 2511 2791 SPINDLE 1 1 1 1 S.S. 304/ASTM A276 TYPE-30411 3643 2423 2503 2784 CLAPPER 1 1 1 1 BRONZE IS:318 LTB-II/ASTM B62

    12 3647 2427 2507 2786 DIAPHRAGM 1 1 1 1 NEOPRENE RUBBER

    13 3644 2424 2504 2788 CLAMP RING 1 1 1 1 BRONZE IS:318 LTB-II/ASTM B62

    14 8806 9151 9151 9151 HEX HEAD BOLT 8 8 8 8 STAINLESS STEEL 304

    15 3651 2433 2512 2792 SPRING 1 1 1 1 STAINLESS STEEL 316

    16 9047 9047 9047 9058 HEX HEAD BOLT 12 12 12 12 IS:1 36 3/STEEL ISO 4 01 8 (GALVANISED)

    17 3655 2431 2510 2793 SPINDLE ADAPTOR 1 1 1 1 BRASS IS:319-I/ASTM B16

    18 9982 9787 9788 9982 "O" RING 1 1 1 1 NEOPRNE RUBBER

    19 3649 2429 2509 2783 COVER 1 1 1 1 CAST STEEL / ASTM A216 GR WCB

    20 2514 2514 2514 2514 PLUG 1 1 1 1 STEEL PLATED

    21 9019 9019 9019 9018 HEX NUT 12 12 12 12 IS:1363/STEEL IS 4018 (GALVANISED)

    PART LIST

  • 8/7/2019 HD103 - DV - H

    5/14

  • 8/7/2019 HD103 - DV - H

    6/14

    6NOVEMBER, 2007 HD103PAGE OF 14

    1 8627 UNION 2 2 2 2

    2 9365 HEX NIPPLE 8 8 8 83 9423 BALL VALVE 1 1 1 1

    4 8616 ELBOW 2 2 2 2

    5 9381 Y TYPE STRAINER 1 1 1 1

    6 1906 RESTRICTION CHECK VALVE HD MAKE MODEL-A 2 2 2 2

    7 8619 TEE 4 4 4 4

    8 9480 PIPE NIPPLE X 80 MM 1 1 1 1

    9 9397 PIPE NIPPLE X 100 MM 1 1 1 1

    10 1921 EMERGENCY RELEASE STATION HD MAKE MODEL-MR 1 1 1 1

    11 1561 DRY PILOT ACTUATOR HD MAKE MODEL-DPA 1 1 1 1

    12 9413 REDUCING HEX NIPPLE X 1 1 1 1

    13 9477 GAUGE VALVE 3 3 3 3

    14 9374 ELBOW 2 2 2 215 9526 PRESSURE GAUGE 3 3 3 3

    16 9363 HEX NIPPLE 1 1 1 1

    17 1911 DRIP VALVE HD MAKE MODEL-A 1 1 1 1

    18 9367 HEX NIPPLE 1 2 2 2 2

    19 8950 PIPE NIPPLE 2 X 80 MM 1 1 1 -

    19 8952 PIPE NIPPLE 1 -1 /4 X 80 MM - - - 1

    20 9394 ANGLE VALVE 2 1 1 1 -

    20 9392 ANGLE VALVE 1-1/4 - - - 1

    21 9552 REDUCING NIPPLE X1 /2 X65 MM 1 1 1 1

    22 8621 TEE 1 1 1 1 1

    23 9486 REDUCING HEX NIPPLE 1 X 1 1 1 1

    24 9391 ANGLE VALVE 1 1 1 1 1

    25 9413 REDUCING HEX NIPPLE X 1 1 - -

    25 9552 REDUCING NIPPLE X X65 MM - - 1 1

    26 8629 PLUG 1 1 1 1

    27 8630 PLUG 1 1 1 1

    28 8629 PLUG 1 1 1 1

    29 8629 PLUG

    TEST AND A LARM TRIM ( OPTIONAL)

    30 8617 ELBOW 1 1 1 1

    31 9366 HEX NIPPLE 2 2 2 2

    32 9421 SWING CHECK VALVE 1 1 1 1

    33 8620 TEE 1 1 1 1

    34 9553 REDUCING HEX NIPPLE X 1 1 1 1

    35 3653 COPPER TUBE ASSY 1 - - -

    35 2438 COPPER TUBE ASSY - 1 - -

    35 2518 COPPER TUBE ASSY - - 1 -

    35 2796 COPPER TUBE ASSY - - - 1

    36 9423 BALL VALVE. 1 1 1 1

    37 9441 PIPE NIPPLE X 80 MM - - 1 1

    37 9406 PIPE NIPPLE X 100 MM 1 1 - -

    38 9382 Y TYPE STRAINER 1 1 1 1

    ELECTRIC TRIM FOR SOLENOID VALVE ( OPTIONA L)

    39 9365 HEX NIPPLE 1 1 1 1

    40 - SOLENOID VALVE TWO WAY 1 1 1 1

    ELECTRIC TRIM FOR PRESSURE SWI TCH ( OPTION AL)

    41 9365 HEX NIPPLE 1 1 1 1

    42 8619 TEE 1 1 1 1

    43 - PRESSURE SWITCH 1 1 1 1

    NO CODE DESCRIPTION SIZE

    PNEUMATIC & ELECTRIC RELEASE TRIM FOR HORIZONTAL M OUNTINGDELUGE VALVE M ODEL - H, 20 0 / 1 5 0 / 1 00 / 8 0 N B

  • 8/7/2019 HD103 - DV - H

    7/14

  • 8/7/2019 HD103 - DV - H

    8/14

    8NOVEMBER, 2007 HD103PAGE OF 14

    1 8627 UNION 1 1 1 1

    2 9365 HEX NIPPLE 4 4 4 4

    3 9423 BALL VALVE 1 1 1 1

    4 8616 ELBOW 4 4 4 4

    5 9381 Y TYPE STRAINER 1 1 1 1

    6 1906 RESTRICTION CHECK VALVE HD MAKE MODEL A 1 1 1 1

    7 8619 TEE 2 2 2 2

    8 9480 PIPE NIPPLE X 80 MM 1 1 1 1

    9 9 397 PIPE NIPPLE x 100 MM 2 2 2 2

    10 1921 EMERGENCY RELEASE STATION HD MAKE MODEL MR 1 1 1 1

    11 9477 GAUGE VALVE 2 2 2 2

    12 9374 ELBOW 1 1 1 1

    13 9526 PRESSURE GAUGE 2 2 2 2

    14 9363 HEX NIPPLE 1 1 1 1

    15 1911 DRIP VALVE HD MAKE MODEL-A 1 1 1 1

    16 9367 HEX NIPPLE 1 2 2 2 2

    17 8850 PIPE NIPPLE 2 X 80 MM 1 1 1 -

    17 8952 PIPE NIPPLE 1 X 80 MM - - - 1

    18 9394 ANGLE VALVE 2 1 1 1 -

    18 9392 ANGLE VALVE 1 - - - 1

    19 9552 REDUCING NIPPLE X X65 MM 1 1 1 1

    20 8621 TEE 1 1 1 1 1

    21 9486 REDUCING NIPPLE 1 X 1 1 1 1

    22 9391 ANGLE VALVE 1 1 1 1 1

    23 9413 REDUCING HEX NIPPLE X 1 1 - -

    23 9552 REDUCING NIPPLE X X65 MM - - 1 1

    24 8629 PLUG 1 1 1 1

    25 8629 PLUG 1 1 1 1

    26 8630 PLUG 1 1 1 1

    27 8629 PLUG 1 1 1 1

    TEST AND ALARM TRIM ( OPTIONAL)

    28 8617 ELBOW 1 1 1 1

    29 9366 HEX NIPPLE 2 2 2 2

    30 9421 SWING CHECK VALVE 1 1 1 1

    31 8620 TEE 1 1 1 1

    32 9553 REDUCING HEX NIPPLE X 1 1 1 1

    33 3653 COPPER TUBE ASSY 1 1 1 1

    33 2438 COPPER TUBE ASSY 1 1 1 1

    33 2518 COPPER TUBE ASSY 1 1 1 1

    33 2796 COPPER TUBE ASSY 1 1 1 1

    34 9423 BALL VALVE. 1 1 1 1

    35 9441 PIPE NIPPLE X 80 MM - - 1 1

    35 9406 PIPE NIPPLE X 100 MM 1 1 - -

    36 9382 Y TYPE STRAINER 1 1 1 1

    ELECTRIC TRIM FOR SOLEN OID VALVE ( OPTIONA L)

    37 9365 HEXNIPPLE 1 1 1 1

    38 - SOLENOID VALVE X TWO WAY 1 1 1 1

    HYDRAULIC & ELECTRIC RELEASE TRIM FOR HORIZONTAL M OUNTING

    DELUGE VALVE MODEL - H, 200/ 150/ 100/ 80 NB

    N O. CODE DESCRI PTI ON SI ZE

  • 8/7/2019 HD103 - DV - H

    9/14

  • 8/7/2019 HD103 - DV - H

    10/14

    10NOVEMBER, 2007 HD103PAGE OF 14

    1 8627 UNION 3 3 3 3

    2 9365 HEX NIPPLE 9 9 9 9

    3 9561 PIPE NIPPLE X 60 MM - 1 1 1

    3 9569 PIPE NIPPLE X 90 MM 1 - - -

    4 9568 PIPE NIPPLE X 90 MM 1 1 1 1

    5 9423 BALL VALVE 1 1 1 1

    6 8616 ELBOW 1 1 1 1

    7 9381 Y TYPE STRAINER 1 1 1 1

    8 1906 RESTRICTION CHECK VALVE HD MAKE MODEL A 2 2 2 2

    9 8619 TEE 5 5 5 5

    10 9480 PIPE NIPPLE X 80 MM 1 1 1 1

    11 1921 EMERGENCY RELEASE STATION HD MAKE MODEL MR 1 1 1 1

    12 1561 DRY PILOT ACTUATOR HD MAKE MODEL DPA 1 1 1 1

    13 9413 REDUCING HEX NIPPLE X 2 2 2 2

    14 9477 GAUGE VALVE 3 3 3 3

    15 9526 PRESSURE GAUGE 3 3 3 3

    16 9363 HEX NIPPLE 1 1 1 1

    17 9374 ELBOW 2 2 2 2

    18 9552 REDUCING NIPPLE X X 65MM 1 1 1 1

    19 1911 DRIP VALVE HD MAKE MODEL-A 1 1 1 1

    20 9486 REDUCING HEX NIPPLE 1 X 1 1 1 1

    21 8621 TEE 1 1 1 1 1

    22 9367 HEX NIPPLE 1 2 2 2 2

    23 9391 ANGLE VALVE 1 1 1 1 1

    24 8950 PIPE NIPPLE 2 X 80 MM 1 1 1 -

    24 8952 PIPE NIPPLE 1 X 80 MM - - - 125 9394 ANGLE VALVE 2 1 1 1 -

    25 9392 ANGLE VALVE 1 - - - 1

    26 8629 PLUG 3 3 3 3

    27 8630 PLUG 1 1 1 1

    28 8629 PLUG 1 1 1 1

    TEST AND ALARM TRIM ( OPTIONAL)

    29 8616 ELBOW 1 1 1 1

    30 3654 COPPER TUBE ASSY. 1 - - -

    30 2411 COPPER TUBE ASSY. - 1 - -

    30 2519 COPPER TUBE ASSY. - - 1 -

    30 2797 COPPER TUBE ASSY. - - - 1

    31 8619 TEE 1 1 1 132 9365 HEX NIPPLE 1 1 1 1

    33 9423 BALL VALVE 1 1 1 1

    34 9553 REDUCING HEX NIPPLE X 1 1 1 1

    35 8620 TEE 1 1 1 1

    36 9366 HEX NIPPLE 2 2 2 2

    37 9421 SWING CHECK VALVE 1 1 1 1

    38 9382 Y TYPE STRAINER 1 1 1 1

    39 9365 HEX NIPPLE 1 1 1 1

    ELECTRIC TRIM FOR SOLEN OID VALVE ( OPOTIONAL)

    40 9365 HEX NIPPLE 1 1 1 1

    41 - SOLENOID VALVE TWO WAY 1 1 1 1

    ELCTRIC TRIM FOR PRESSURE SWITCH ( OPTIONA L)

    42 9365 HEX NIPPLE 1 1 1 1

    43 8619 TEE 1 1 1 1

    44 - PRESSURE SWITCH 1 1 1 1

    NO CODE DESCRIPTION SIZE

    PNEUM ATIC & ELECTRIC RELEASE TRIM FOR VERTICAL M OUNTING

    DELUGE VALVE MODEL - H, 200/ 150/ 100/ 80 NB

  • 8/7/2019 HD103 - DV - H

    11/14

  • 8/7/2019 HD103 - DV - H

    12/14

  • 8/7/2019 HD103 - DV - H

    13/14

    13NOVEMBER, 2007 HD103PAGE OF 14

    ELECTRIC & PNEUM ATIC RELEASE TRIM - SCHEMATIC DELUGE VALVE - 20 0 / 1 5 0 / 1 00 / 8 0 NB

    ELECTRIC & HYDRAULIC RELEASE TRIM - SCHEMATIC DELUGE VALVE - 2 00 / 1 50 / 1 00 / 8 0 NB

    HORIZONTAL M OUNTING VERTICAL M OUNTING

    HORIZONTAL M OUNTING VERTICAL M OUNTING

    OPTIONAL

    ANGLE VALVE

    NON RETURN VALVEVALVE

    GAUGE VALVE

    STRAINER

    ER - EMERGENCY RELESE BOX

    DV - DELUGE VALVE

    OD - OPEN DRAIN

    M - SIX WAY MANIFOLD

    CD - COMMON DRAIN

    RCV - RESTRECTION CHECK VALVE

    PG - PRESSUER GAUGE

    DR.V - DRIP VALVE

    SV - SOLONOID VALVE F - FUNNEL

    PS - PRESSURE SWITCH

    BY USER

    STOP VALVE

    DV

    PS

    M

    INLET

    DPA

    OD

    PV

    TO DRAIN

    TO DETECTION

    RCV

    PGLINE

    RCV

    PG

    FROM

    SUPPLYOUTLET

    OD

    OD

    CD

    ~

    OD

    ~

    G

    *

    *

    SV

    DR.V

    PG

    CD

    FROMCOMPRESSOR

    RCVPG

    TO DETECTIONLINE

    DPA

    TO

    PV

    RCV

    OD

    *

    G

    PG

    INLET

    SUPPLY

    FROM

    OD

    OUTLET

    M

    SV

    *OD

    PG

    OD

    DR.V

    DV

    DRAIN

    DV

    M

    INLET

    OD

    PV

    TO DETECTIONLINE

    RCV

    PG

    FROM

    SUPPLY OUTLET

    OD

    OD

    CD

    ~

    OD

    ~

    G

    *

    *

    SV

    DR.V

    PG

    CD

    TO DETECTIONLINE

    PV

    RCV

    OD

    *

    G

    PG

    INLET

    SUPPLY

    FROM

    OD

    OUTLE

    M

    SV

    *OD

    PG

    OD

    DR.V

    DV

  • 8/7/2019 HD103 - DV - H

    14/14

    14NOVEMBER, 2007 HD103PAGE OF 14

    W ET PILOT SPRINKLER

    HEIGHT LIM ITATION OF 15 0 NB

    W ET PILOT SPRINKLER

    HEIGHT LIMITATION OF 1 0 0 NB

    W ET PILOT SPRINKLER

    HEIGHT LIM ITATION OF 80 NB

    LIMITED W ARRANTYProduct s m anufact ur ed by HD FIRE PROTECT PVT.LTD.. are war rant ed againstdefects in mater ial and workmanship for a period of Two (2) years fr om the dat e

    of shipment .

    HD's obligation under t his warrant y is limit ed to r eplace or repair t he products

    or it s part s, which are shown to HD's examinat ion to be in a defect ive condition

    att ributable to HD. No warr anty is given for products or components which havebeen subject , t o mis use, improper inst allat ion, cor rosion, wear and t ear, im-

    pr oper st orag e, modificat ion or r epaired. If t he defect at t ribut able t o HDcannot be rect ified by repair or replacement , t hen HD may elect t o refund t he

    pur chase pric e of t he equipment in complet e disc harg e of it s obligat ion undert his Limited Warr anty.

    IN NO EVENT SHALL HD FIRE PROTECT PVT. LTD. BE LIABLE IN CONTRACT, STRICT

    LIABILITY OR ANY OTHER LEGAL THEORY, FOR INCIDENTAL, IN-DIRECT, SPECIAL OR

    CONSEQUENTIAL DAMAGES, INCLUDING DAMAGES. FOR INJURY TO PERSON ORDEATH OR DAMAGE TO PROPERTY AND OR PENALTIES RESULTING FROM ANYPRODUCTS OR COMPONENT MANUFACTURED OR ASSEMBLED BY HD. THIS IS

    LIMITED WARRANTY ONLY. HD DISCLAIMS WITH RESPECT TO THE PRODUCTS ALLIMPLIED WARRANTIES OF MERCHANTABILITY AND ALL IMPLIED WARRANTIES OF

    FITNESS FOR A PARTICULAR PURPOSE. THERE IS NO WARRANTY OF ANY NATURE

    MADE BY HD BEYOND AS STATED ABOVE.

    NOTICE :

    The equipment pres ent ed in t his bullet in is t o be inst alled in accor dance wit h t he lat est publicat ion s t andar ds of N FPA or ot her similar organis at ions and alsowit h t he pr ovision of government codes or ordinances wherever applicable.

    The informat ion provided by us are t o t he best of our knowledge and belief, and are general guidelines only. Sit e handling and inst allation cont rol is beyond our r each.Hence we give no guar ant ee for res ult and t ake no liabilit y for damages, loss or penalt ies w hat soever, res ult ing fr om our suggest ion, infor mat ion, r ecommendat ion

    or damages due t o our product .

    Product development is a cont inuous pr ogramme of HD FIRE PROTECT PVT. LTD. and hence t he right t o modify any specification wit hout prior not ice is r eserved wit ht he com pany.

    C-3/6, THE NANDANVAN IND. ESTATE, L.B.S. MARG, THANE 400 604., INDIA. PHONES : + (91) 22 25 83 5 434 2582 6958 2582 6793FAX : + (91) 22 2 581 2524 679 6 90 49EMAIL : [email protected] W EBSITE : www.hdfir e.com