Upload
others
View
1
Download
0
Embed Size (px)
Citation preview
Enabling Wellbeing
Halton – Vario Design Guide
2
Table of contents
1. Halton Vario - ventilation and air conditioning system overview 3
1.1 Room level, Zonal level and central level 4
1.2 Flexible design and adaptable HVAC systems reduce churn costs 6
2. Room level 8
2.1 Requirements for design of indoor environment and cooling demand 9
2.2 Air water system 12
2.2.1 Operation (demand based ventilation and VAV beam principle) 12
2.2.2 Layout and control zone considerations 15
2.2.3 System & component overview 16
• Halton Rex chilled beams 16
- Integration of controls into chilled beams 16
• Controls 16
2.3 All air system 18
2.3.1 Operation (demand based ventilation and VAV beam principle) 18
2.3.2 Layout and control zone considerations 21
2.3.3 System & component overview ??
• Active diffusers and controls ??
- Integration of controls into room units ??
• Controls ??
3. Zonal level 24
3.1 Operation based on constant pressure ductwork 24
3.1.1 Principle Design of constant pressure ductwork 28
3.1.2 System & component overview 32
• Ductwork components 32
• Controls 32
3.1.3 design examples 33
4. Central level
4.1 Operation ??
4.2 System and component overview ??
4.3 Design examples ??
5. Communication
5.1 Lon, Backnet, Modbus ??
5.2 Network structure ??
5.3 Communication with slave units ??
2 3
In Halton Vario system, energy and environmental
efficiency is implemented together with good
indoor environment quality and wellbeing of users.
Indoors conditions are maintained by demand-
based and only when the spaces are occupied the
indoor conditions are actively controlled.
Halton Vario system's adaptable indoor conditions
impact on:•Usershealth•Userscomfort•Energyefficientoftherealestate•Carbonfootprintoftheenergyuse•Adaptabilityforfutureusers’needs•Reliabilityandsafetyforoperation•Assetvalue
Thoseitemsgivebenefitsfordevelopers,tenantsand
ownerstoruntheiroperationmoreeffectivewayand
improvetheirprofitable.Thebenefitsfordifferent
stake-holdersaresummarizedinthetable1.
1.HaltonVario-ventilationandairconditioningsystemoverview
Halton Vario overview
Table 1. Halton Vario system's benefits for developer, tenants and owners.
Developer Tenants Owners
Higher return of investment (ROI) Health and comfort of employees Lower risk
Lower risk of investment Productivity of workers Lower life-cycle costs
Easier to get financing Better brand Easier to rent
Easier to sell Can employ better people Lower churn costs of continuous changes
Easier to adapt changes during construction phase
Fast and easy layout changes for alteration use of space
Less IEQ complains
4
Fig. 1. Halton Vario system air-water concept.
Halton Vario air-water system
The system is based on smart controls and Halton Vario system’s chilled beams. Halton Vario is a total system for ventilation, cooling and heating in rooms together with the required controls at room, zonal and system level.
Halton Vario air- water system provides solution for room, zonal and central levels:
RoomsHaltonVariosystem'schilledbeamsareusedinofficerooms,openplanofficeandmeetingrooms.Inoffices,unoccupiedoroccupiedspace,theairflowisadjustedaccordingly.Inmeetingrooms,airflowisadjustedfromminimumtomaximum.ControlofconditionsisbasedonCO2,temperatureandoccupancy.Theroomcontrollerensuresperfectconditionsinoccupiedworkplacesandsavesenergywhenspacesareunoccupied.Intheroomcontrolsystem,thereshouldbeintegratede.g.windowswitchandcondensationsencortopreventcondensation.
ZonesHaltonVariosystemdividesthesystemintoventilationzonestoensureflexibilityandcontrollabilityofairflowratechangesindifferentspaces,thatenableslinearoperationofcontroldamperofchilledbeamandmakespossibletointegrateconstantairflow(CAV)andvariableairflowrate(VAV)roomunitsintosameductbranch.Constantstaticpressurezonesenablelayoutflexibilityandminimizethechurncostwhilemakingtheadjustmentsimple.
System levelHaltonVariosystem'sOptimizermonitorstheperformanceoftheventilationsystem.Itminimisesenergyconsumptionbykeepingthelowestpossiblepressureintheductworkthatisrequiredforoperation.Thepositionsofzonedampersaremonitoredandthesystemoptimizesthepressurelosssothatunnecessaryhighpressuredropdoesnothappeninzonedampers.
HaltonVarioair-watersystemisonethemostenergyefficientsolutionresultinginupto50%energysavingscompared to typical non-demand based controlled air-watersystem.TheschemeofthewholeHaltonVarioair-watersystemispresentedinFig.1
Halton Vario overview
1.1HaltonVariosystemofferssolutionsforbothair-waterandall-airwaterventilationandair-conditioningsystems
4 5
Fig. 2. A schematic of the whole Halton Vario all-air system.
Halton Vario overview
HaltonVariosystemislowtemperatureheatingandhightemperaturecoolingsystem.Thus,coolingenergycouldbeprovidere.g.fromchiller,freecoolingorgroundcoupledsystems.Lowtemperatureheatingcanbeprovidedfrome.g.districtheating,boilerorheatpumpsystems.Intheair-handlingunit,thesupplyairtemperatureandairflowratesarecontrolled.Atair-handlingunit,thesupplyairisdehumidifiedtopreventcondensationduringsummerconditions.
Halton Vario all-air system
The Halton Vario system is based on smart controls and active diffusers. Halton Vario all-air system is for ventilation and cooling in rooms with controls at room, zonal and system levels.
HaltonVariosystem’sall-airsystemprovidessolutionforroom,zonalandcentrallevels:•Rooms:HaltonVarioactivediffusersforofficerooms,openplanofficesandmeetingrooms.Inofficesandmeetingrooms,unoccupiedoroccupiedspace,theairflowisadjustedaccordingly.ControlofconditionsisbasedonCO2,temperatureandoccupancysensor.Theroomcontrollerensuresperfectconditionsandsavesenergywhenspacesareunoccupied.
ZonesHaltonVariodividesthesystemintoventilationzonestoensureflexibilityandcontrollabilityofairflowratechangesindifferentspaces.Constantstaticpressureismaintainedinzonalductworks.Zonesallowregulatingtheventilationsystemthemostefficientwaybyreducingunnecessarypressureinthesystem.Constantstaticpressurezonesenablelayoutflexibilityandminimizethechurncostwhilemakingtheadjustmentsimple.•System level:HaltonVariosystem'sOptimizermonitorstheperformanceoftheventilationsystem.Itminimisesenergyconsumptionbykeepingthelowestpossiblepressureintheductworkthatisrequiredforoperation.Thepositionsofzonedampersaremonitoredandthesystemoptimizesthepressurelosssothatunnecessaryhighpressuredropdoesnothappeninzonedampers.
TheschemeofthewholeHaltonVarioall-airsystemispresentedinFig.2.
Intheair-handlingunit,thesupplyairtemperatureiscontrolled.Supplyairflowrateisthemasterthatexhaust(slave)follows.Thefanpoweriscontrolledtoproviderequiredoperationconditionsofthebranchcontroldampers.
6
Halton Vario overview
Table 2. Adapting space types and business processes in office buildings.
Space Interaction Autonomy Operation Example
Hive low low customer service
call centre
Cell low high support tasks
financial administration
Den high low team work media
Club high high expert work
consultancy
The adaptability of office space is one of the main
issue in designing a system for sustainable
buildings. In a modern office environment, balance
is sought between work performed by individuals
and in interaction between employees. The systems
must adapt to changed loads and partition wall
locations. For a room system, adaptability means
taking changes in the supply air flow, cooling effect
and throw pattern of the supply air device into
consideration. All this makes possible to change
office to meeting room quicly and cost-effectively.
The functionality of the workspace significantly affects
the productivity of employees. Often a compromise
must be made among the needs of the employee,
team and organisation when arranging workspaces.
Addressing the interaction and privacy needs of
employees, both of which are important considerations
in organisations, is particularly challenging. In general, it
can be stated that, from the perspective of dispersing
silent information (views, experiences, intuitions), fully
autonomous workspaces do not support the business
models of most companies. On the other hand,
reducing the autonomy afforded by individual
workspaces reduces acoustic privacy, which disturbs
concentration.
Organisational changes in most companies are
continuous and require flexible changes in work
methods and workspaces. The traditional oneperson
office areas, or cells, and open offices, or hives, seen in
traditional offices are today changing into spaces that
are more suited to team work, referred to as dens or
clubs (Table 2).
1.2FlexibledesignandadaptableHVACsystemsreducechurncosts
6 7
Table 3. Churn costs of traditional system.
Costs of traditional system Cost
Design work 30 - 40 €/m2
Changes in automation systems 10 - 20 €/m2
Changes in mechanical systems 40 - 100 €/m2
Changes in electrical systems 30 - 40 €/m2
TOTAL 110 - 200 €/m2
Movingpeopleisexpensive.Thecostofamove
dependsontheextenttowhichthefacilitymustbe
modifiedtoaccommodatethechanges.Oftennew
walls,neworadditionalwiring,new
telecommunicationssystems,orotherconstruction
areneededtocompletethemove.
Whenthenumberofoccupantsortheuseofthe
spacechanges,theindoorenvironmentqualityand
thesystemperformanceshouldalwaysbechecked.
Dependingontheselectedsystems,thecostof
modifyingaspaceandvariesalot.Withtraditional
system,thecostsareeasilyover100€/floor-m2 and
thetotalrequiredtimeincludingdesignandretrofitting
is1…3months.
InTable3,presentstypicalcostswhentheoffice
spaceismodifiedtomeetingroomwithtraditional
system.
Butchangecanbeeasy-churncostsandtherequired
timeforthechangecanbeminimizedifthesystemis
adaptable.Halton’sVariosystemprovidesminimized
churncostsandtimeforthechange.Thechangeof
officetomeetingroomhappenswithin15minutes.
Halton Vario overview
8
Room level
2.Roomlevel
8 9
For the selection of room units, the required
ventilation rate must be specified based on
national requirements or using the recommended
methods in the standard. As a minimum, space
must be ventilated to dilute the bio effluents from
the occupants. In addition, the air flow rate is
increased to take into account the emissions from
the building materials. Recommended airflow rates
for diluting emissions are categorized. Typically
good and excellent level of air quality requires 1.5
– 2.0 l/s per floor-m2 in offices and 4- 6 l/s per
floor-m2 in meeting rooms in standards.
Forachievinghealthy,comfortableandenergyefficient
buildings,itisimportanttoconsidertherequired
airflowratestakenintoaccountthematerial
emissions.Indoorclimateclassificationsand
ventilationratesarespecifiedinEuropeanStandard
EN15251.Whenmaterialemissionsarelow,the
airflowratesinofficeroomsare1.5–2.0l/sper
floor-m2andinmeetingroom4-6l/sperfloor-m2.
Usingnon-lowpollutingmaterialinofficesincreases
significantlytherequiredairflowrates.Table4
presentsairflowratesaccordingtoEN15251.
Table 4. Ventilation rates in offices according European Standard EN 15251.
Ventilation rate of Occupancy Ventilation rate of Building Materials
Very low polluting Low polluting Non-low polluting
Building typeFloor aream2/p
Occupancyl/s/m2
Materiall/s/m2
Total Materiall/s/m2
Total Materiall/s/m2
Total
Cellular office I 10 1.0 0.5 1.5 1.0 2.0 2.0 3.0
II 10 0.7 0.3 1.0 0.7 1.4 1.4 2.1
III 10 0.4 0.2 0.6 0.4 0.8 0.8 1.2
Landscape office I 15 0.7 0.5 1.2 1.0 1.7 2.0 2.7
II 15 0.5 0.3 0.8 0.7 1.2 1.4 1.9
III 15 0.3 0.2 0.5 0.4 0.7 0.8 1.1
Conference room I 2 5 0.5 5.5 1.0 6.0 2.0 7.0
II 2 3.5 0.3 3.8 0.7 4.2 1.4 4.9
III 2 2 0.2 2.2 0.4 2.4 0.8 2.8
Room level
InEuropeEN15251isnowusedbymanycountries
butseveralcountriesdohavetheirownstandardsand
buildingcodes.Also,buildingclassificationschemes
requireshigherairflowratesthanstandardspecifyto
reachmaximumscoresintheevaluation.
EN15251andISOEN7730givestargetvaluesfor
thermalcomfortforboththewholebodythermal
sensationandlocalthermaldiscomforte.g.draught.
Table5onpage10showsthreecategoriesofthermal
environment.
Inheatingmode,thetemperaturegradientbetween
floorandceilingcan’tbetoohigh.Table6shows(see
page10),thereisshownthecategoriesoflocal
thermaldiscomfortparameters(verticaltemperature
gradient,floortemperatureandradianttemperature
asymmetry).
Duetoindividualvariationofthephysiologicaland
psychologicalconditions,itisdifficulttoensurean
environmentsatisfyingalloccupantsexposedtothe
samethermalenvironment.Experimentaldatashow
thatacertainamountofpersonsisalwaysdissatisfied
withthethermalconditions.
2.1Requirementsfordesignofindoorenvironmentandcoolingdemand
10
Duringdesignphase,itisimportanttoanalyzeair
velocitiesintheoccupiedzonesandthusmakesure
thattheselectedsolutiondoesnotcausedraught.
WithHaltonHIT,itiseasytocarryouttherequiredair
velocitycalculations.
Indemandingcases,itisrecommendedtouseCFD-
analysisandmock-upstoguaranteetheperformance.
HaltonprovidesCFDandmock-upservicestoanalyze
theperformance.
Cooling demand
The actual cooling demands should be computed
with dynamic energy simulation program. When
the room units are selected, it is important to make
a difference beintween sensible cooling and total
cooling loads. Chilled beams are sized by sensible
cooling demand. Windows are playing a significant
role in cooling demand. It is profitable to use solar
shading or window with low g-values. Nowadays
with good solar shading and energy efficient lights,
it is possible to reach 60-80 W/floor-m2 also on
perimeter spaces.
Theenergyconsumptionofabuildingdependsonthe
qualitiesofbuildingenvelopeandtheenergyefficiency
oftheselectedHVAC-system.Thepropertiesofthe
windowsarethemostsignificantfactoroncooling
demandinmodernoffices,whereenergyefficient
lightfittingsandlaptopcomputersareenabled.
Withgoodsolarshading,thecoolingrequirementcan
besignificantlyreduced.Thereductionofcoolingloads
alsoexpandsthevarietyofHVAC-systems,whichcan
beusedinbuildings.Lowtemperatureheatingand
hightemperaturecoolingair-watersystemscanbe
moreeasilyintroducedinsuchbuildingswhere
efficientsolarshadingisintroduced.
Duringthedesignphase,itisimportanttomakea
differencebetweensensiblecoolingandtotalcooling
loads,whenair-watersystemsareconsidered.Inair-
waterroomairconditioningsystems,onlysensible
coolingloadiscoveredwithroomunits.Thelatent
loadiscompensatedinair-handlingunitby
dehumidifyingthesupplyairflowtorequiredlevelto
avoidcondensationintheroomspace.Thus,the
coolingcapacityismuchlowercomparedtoe.g.
condensingfan-coilunits,wherethemajorpartof
dehumidificationoccursinthefan-coilunitintheroom
spaces.
Room level
CategoryThermal state of the body as a whole
Operative temperature °C Max. mean air velocity m/s
PPD % PMVSummer (0,5 clo) Cooling
Winter (1 clo) Heating
Summer (0,5 clo) Cooling
Winter (1 clo) Heating
A < 6 -0.2 < PMV < + 0.2 23,5 – 25,5 21,0 – 23,0 0,18 0,15
B < 10 -0.5 < PMV < + 0.5 23,0 – 26,0 20,0 – 24,0 0,22 0,18
C < 15 0.7 < PMV < + 0.7 22,0 – 27,0 19,0 – 25,0 0,25 0,21
CategoryVertical air temperature difference K
Floor surface temperature °C
Radiant temperature asymmetry K
Warm ceiling Cool ceiling Cool wall Warm wall
A < 2 19 - 29 < 5 < 14 < 10 < 23
B < 3 19 - 29 < 5 < 14 < 10 < 23
C < 4 17 - 31 < 7 < 18 < 13 < 35
Table 5. Three categories of thermal environment.
Table 6. Recommended categories for local thermal discomfort parameters.
10 11
Room level
Whenanairconditioningsystemissized,itis
importanttocalculatetheactualcoolingdemandby
usingdynamicenergysimulationprogram.Iftheeffect
ofthethermalmassisnottakenintoaccount,the
wholesystemisover-sized.Inthecoolingdemand,
windowpropertiesareplayingasignificantrole.If
thereisnosolarshadingorwindowwithbadsolar
heatgaincoefficient(gvalue),therequiredcooling
capacitycaneasilybe1.4-1.6timeshigherthanwith
lowsolartransferwindows.
Thecoolinganalysisoftheeffectofwindowstructure
wascarriedoutindifferentclimatezonesinEurope.
Case-study: envelope and windowThesimulatedofficeroomareawas10.8m2 (4.0x2.7x3m,LxWxH).U-valueofthewindowwas1.1W/m2Kandgvaluewas0.4.Fourdifferentheightsofwindow.U-valueoftheexternalwallwas0.3W/m2K.Theexteriorwallwasaconcretewall(heavy)andinteriorwallswereplasterboardstructures(light).
Case-study: heat gains and schedulesTwooccupants,lighting10W/floor-m2 and appliance load10W/floor-m2werefrom9.00a.m.to6.00p.mFansoperatefrom7.00a.m.to8.00p.m.providingaconstantoutdoorairflowrateof2l/s,floor-m2
Roomairtemperaturesetpointwas24°Candsupplyairtemperaturewas14°C.
Inthecase-study,thecoilcapacitywasthemostsignificantportioninthecoolingcapacitiesoftheofficerooms.Thesensiblecoolingofthechilledbeam
Fig 3. Office building module with four different window heights.
Fig.4. A case study of the required sensible cooling capacity of south and west offices in some European cities with different window heights.
coilwas60-75%oftheofficeroom.Themaximumsensiblecoolingpowerinsouthroomsvariedbetween80to120W/floor-m2.Byreducingthewindowheightto1.6m,itispossiblemaintainthesetroomairtemperatureusingthecoolingpowerof80W/floor-m2.Intotheeastandwestfacingofficerooms,themaximumcoolingcapacitywas120W/floor-m2.Whenthewindowheightwas1.6mand1.2m,therequiredcoolingcapacityreducedto90W/floor-m2 and 80W/floor-m2
1,2m 1,6m 2m 2,8m 1,2m 1,6m 2m 2,8m 1,2m 1,6m 2m 2,8mHelsinki Paris Rome
0,0
20,0
40,0
60,0
80,0
100,0
120,0
140,0
160,0
180,0
200,0
West Office Cooling load from air flowsCooling load from beams
Coo
ling
pow
er (W
/m2)
1,2m 1,6m 2m 2,8m 1,2m 1,6m 2m 2,8m 1,2m 1,6m 2m 2,8mHelsinki Paris Rome
0,0
20,0
40,0
60,0
80,0
100,0
120,0
140,0
160,0
180,0
South Office Cooling load from air flowsCooling load from beams
Coo
ling
pow
er (W
/m2)
12
2.2Air-watersystem
2.2.1 Operation
In Halton Vario, air temperature for a beam system is
normally room air by varying the water flow rate. The
control of air quality is based on variable airflow rate.
The delivered outdoor air flow rate is adjusted to
maintain the required zone CO2 concentration. Air
flow rate adjustment could happen in three modes:
unoccupied, occupied and boost. Thanks to the
constant pressure ductwork and linearized
performance of Halton Vario control damper, airflow
rate is easy to adjust and measure. Halton Vario
makes possible to control outdoor airflow rate within
wide range and also guarantee ideal throw pattern
and draught-free operation.
Room air temperature
Thecontrolofspaceairtemperatureforabeamsystem
isnormallyaccomplishedbyvaryingthewaterflowrate
whilemaintainingaconstantoutdoorairflowrate
temperatureorsetaccordingtotheseason.Traditionally,
outdoorairflowratehasbeenconstant,butnowwith
HaltonVariosystem,airflowrateisalsopossibleto
controldemand-based.Intradionalsystemswhenthe
constantsupplyairtemperatureisusede.g.inmeeting
roomsandoffices,unoccupiedspacescouldbeover
cooledwithoutdoorairevenwhenwatervalveisclosed.
WithHaltonVarion,overcoolingisnothappening
becauseairflowrateisdemand-basedcontrolled.
InFig.5,thereisillustratedroomairtemperaturecontrol
basedon4-pipeconnectionchilledbeams.Controlofthe
watersideisaclosedloopcontrolsysteminwhichthe
roomtemperatureisthecontrolledvariable,andthechilled
orwarmwaterflowisadjustedbythecontrolvalve
installedaspartofthewaterpipingtothebeamsinthe
space.Betweenheatingandcoolingmodes,thecontroller
operatesonzero-energybandandbothheatingand
coolingvalvesareclosed.
Thecontrolvalvecanoperateeitherastwo-position
(on-off)ormodulating.On-offcontrolmaycause
significantfluctuationsinthedeliveredairtemperatureof
activebeams,leadingtoswingsinroomconditions.
Whenapplyingconventionalmodulatingcontrolvalves
caremustbetakentoadequatelyselectthevalvesso
thattheyhaveenoughauthorityinthehydrauliccircuit.
Whenmodulatingpressureindependentcontrolvalves
areappliedthevalvesalwayshavefullauthority,the
selectionofthecontrolvalvebecomesmoresimple,not
Room level
12 13
Fig.5. Room air temperature control sequences with Halton 4-pipe Vario system's chilled beam.
Room level
requiringauthorityverificationandanexcellentqualityof
theroomtemperaturecontrolcanmoreeasilybe
achieved.
Roomairtemperaturesetpointcanbedifferentfor
heatingandcoolingmodesandcanbevariedalsobased
ontheroomoccupancymode.Thisadaptsroomair
temperatureaccordingtooutdoorconditionsandsaves
energyonstand-byandunoccupiedmodes.
Table 7. Examples of room air temperature set points.
Space mode Heating mode Cooling mode
Occupied 20 °C 25 °C
Stand-by 19 °C 26 °C
Unoccupied 18 °C 28 °C
InTable7,thereispresentedtypicalroomairtemperature
setpoints.Allpresentedvaluesareparametersthatuser
canchange.
Usercanchangetheroomairtemperaturesetpointwith
wallmountedorremoteuserpanel.Thesetpointshift
rangeisdefinedasparameter.Thedefaultvalueofthe
shiftis±3°C.
Severaldifferentroomairtemperaturecontrolsequences
canbechosenbycontrollerconfiguration(Fig.6):
•2-pipeapplicationforcoolingonly
•2pipeapplicationusingchange-overcontrolforcooling
orheating
•4-pipeapplicationforcoolingandheating
•2pipeapplicationforcoolingandelectricheating
•2pipeapplicationusingchange-overforcoolingand
heatingandadditionalelectricheatingelementfor
reheat
Fig.6. Control sequences of heating and cooling.
• 2-pipe with electric heating, water heating or cooling change over
• 2-pipe, heating or cooling change over
• 4-pipe, heating and cooling
• 2-pipe with electric heating, water cooling
• 2-pipe, heating sequence only
• 2-pipe, cooling only
14
Room level
Fig.8. Airflow rate is controlled based on occupancy and air quality sensors.
Theairqualitycontrolsequencecanbeusedalsoas
extracoolingbyprovidingextraoutdoorairintothe
space.Theincreasedoutdoorairflow
ratecanbeusedasaprimaryofsecondarycooling
sequence(Fig.7).
Air quality
Airqualityiscontrolledbasedonroomoccupancy
modeandroomconditions.Thecontrolofairqualityis
basedonvariableairflowrate.Inoffices,airflowrateis
typicallyadjustedaccordingtooccupancyofthe
space.Inmeetingrooms,additionalairflowrateis
providedbasedonoccupancyandairquality.
ControlofairqualityisbasedonCO2sensor.Demand
controlventilationinvolvesvaryingtheoutdoorairflow
rateinresponsetothequantityofoccupantsinthe
space.Typically,sensorsmonitortheCO2levelsanda
roomspacecontrollermeasuresthedeliveredoutdoor
airflowratetomaintaintherequiredzoneCO2
concentration.Intheroomcontrolsystem,therecould
beintegratede.g.windowswitchandcondensation
sensortopreventcondensation.Thoseswitchesand
sensorsstopstopwaterflowratewhenthereisarisk
ofcondensation.
Inmeetingrooms,airflowisadjustedfromminimum
tomaximum(e.g.from10to100%).Inmeetingroom,
therearethreemodes:unoccupied,occupiedand
boost.Inofficestheairflowisadjustedaccordingto
occupancyofthespace.Inoffices,therearetwo
Fig 7. Air flow rate configured as second or first control sequence.
Air flow rate configured as second cooling sequence. Air flow rate configured as first cooling sequence.
14 15
Room level
modes:unoccupiedandoccupied.Fig.8illustrates
demandcontrolventilationwithHaltonVariosystem's
beams.
BMSsystemadjuststothesystemeithernightorday
operationmode.Inunoccupiedspaces,there
couldbedifferentairflowratesettingfornightandday
times.
InTable8,thereareshownoperationmodesand
airflowcontrolfunctionsinunoccupiedandoccupied
spacesduringdayandnighttimes.
TheactualHaltonVariosystem'schilledbeamairflow
ratedependsontheselectedbeamtype(lengthand
Table 8. Operation modes and the control of airflow rate.
BMS Room CO2 Operation modes and airflow rate control
> 400 ppm Boost Increased airflow Increased airflow based on room conditions
Occupied Normal airflow Normal Halton Rex beam airflow
Stand-by Reduced airflow Adjustable by parameter
Unoccupied Eco settings Adjustable by parameter, or off
Occupied Normal settings Normal Halton Rex beam airflow
nozzlesize),levelofstaticpressureinductworkand
controllerparametersettings.Thenormaland
maximumairflowcanbeselectedfromHaltonHIT.
Intheunoccupiedandstand-bymodes,theHalton
Rexbeamairflowisreducedandthereforeheatingor
coolingcapacityoftheroomunitisdecreased.To
preventspacetemperatureexceedingtemperature
setting,thecontrollerwillresettheunitairflowrateto
normalairflowvalueuntilroomconditionsareagainon
thedesiredlevel.Whentheroomairtemperaturehas
reachedthesetpoint,theairflowrateisthen
readjustedtotheunoccupiedandstand-bysettings.
16
Room level
Throw pattern
InHaltonVariosystem,airflowrateiscontrolledin3
steps.Inunoccupiedmode(step1),airflowrateis
minimale.g.0.3l/sperm2.Whentheoccupancy
sensorrealizesthatthespaceisoccupied,airflowrate
settovaluebasedonthestandarde.g.1.5–2l/sper
m2(step2).Airflowrateisboostedandmodulated
whenairqualitysensordemandsmoreoutdoorair
(step3).InFig.9,thereispresentedthethrown
patterninthreedifferentoperationmodes.
InHaltonRexchilledbeamdual-chamberstructure,
airflowrateisreleasedtoroomspacefromtwonozzle
rows(Fig.10).Thisconceptmakespossibletocontrol
outdoorairflowratewithinwiderangeandalso
guaranteeidealthrowpatternanddraught-freeoperation.
Thankstotheconstantpressureductworkand
linearizedperformanceofHaltonVariosystem's
controldamper,airflowrateiseasytoadjustand
measureusingproductdata.Aprincipleofthecontrol
strategyisshowninFig.11:inunoccupiedmode,the
minimumairflow5l/srateisadjustedwiththecontrol
signalof0.7V.Withthecontrolsignalof5V,the
airflowrateissettobe20l/sthatisrequiredinthe
occupiedmode.Bythechangingthecontrolsignal
from5Vto10V,airflowrateismodulatedfrom20l/s
to75l/s.
Fig.9. Thrown pattern in unoccupied, occupied and boosts modes.
Fig.10. Air is released from two nozzle rows in Halton Vario concept.
Fig.11. A principle of the correlation between control signal and the outdoor airflow rate in Halton Vario system.
Itshouldbenotedthatwhentheoutdoorairflowrate
isincreased,theamountoftheinducedairthrough
thewatercoilalsoincreased.Thuswithhighoutdoor
airflowrates,thereispossible,ifneeded,toincrease
coolingcapacityfromwaterside.
0 1 2 3 4 5 6 7 8 9 100
10
20
30
40
50
60
70
80
90
Control signal V (DC)
l/s l/s
Control signal V (DC)
16 17
2.2.2 Layout and control zone considerations
Chilled beam layout selection takes into account room module dimensions, intended use of the space and flexibility requirements. Beams installation could be in parallel or perpendicular to the façade. Zone control covers room air temperature, outdoor airflow rate and exhaust airflow rate control schemes. The floor area of the single control zone should not be more than 50 m2. This means that the space controller is the master for 1-4 room units.
Thelayouthassomeinfluenceonthehorizontalairdischargeinthespaceandshouldthusbetakenintoaccountatthedesignstage.Asthrownpatterndependsontheroomormoduledimensions,intendeduse,andflexibilityrequired.
Oneofthefirstconsiderationsisarchitecturalrequirementsandowner’swishesforflexibility,Whetheractivebeamscanbearrangedinparallelorperpendiculartothefaçadeprimarilydependsontheapplication.
Itisrecommendedtouseperpendicularinstallation(Fig.12).Inperpendicularinstallation,thermalplumeofwindowhaslowerinfluenceonairdistributionthanwithparallelinstallation(Fig.13).Whenactivebeamsareinstalledparalleltothefaçadetheirairdischargestowardstheexteriorwallandtheinternalzone.Duringwintertime,thedischargetowardsthecoldfaçadeleadshigherdraughtrisk.Withgoodqualitywindowsand solar protection difference between two types of installationsbecomesneglectable.
Room level
Fig.12. Installation of active beams perpendicular to the façade.
Fig.13. Installation of active beams parallel to the façade.
18
Room level
Inperpendicularinstallationtypically,thelengthofthebeamisfrom2.7mto4m.Tosuitarchitecturalrequirements,thelengthofthebeamcasingcanbeselectedlongerthantheactualcapacityrequires(e.g.aslongastheroom).Inthiscasethecoilissizedaccordingtotherequiredcoolingload.Thedistancebetweenthebeamrowsareselectedbasedontheselectedmodulesizeandtoguaranteedraught-freeairdistribution.Typicaldistancebetweentherowsisfrom2.5mto4m.
Inparallelinstallation,thebeamlengthisselectedtofitwiththeroommodulesandflexibledemands.Typically,thelengthofthebeamisbetween1.2m-4.0m.Dependingonthemodulesize,therecouldbeoneortwobeamrowsinthemodule.
Selectionofcontrolzone,itisalwaysbalancingofflexibility(futurechurncosts)andfirstcost.Naturally,smallcontrolzoneenableshighflexibilityandonthecontraryincreasesfirstcosts.
Somecasesitmakessensetoutilizedifferentbeamlengthsandtobuilddemand-basedsizeofthecontrolzones.InFig.15,thereisshownanexampleof
differentsizesofthecontrolzonesinanopenlayoutoffice.In7.5mx16mmodule,5differentzonesaredesigned(redlines).Themarkedredlinesarepre-designedlocationsofwalls.Thatisaccomplishedwith2beamlengths(1.2mand2.4m)installedin5rows.
Zonecontrolcoversroomairtemperature,outdoorairflowrateandexhaustairflowratecontrolschemes.Controlzonecouldbearoomorseveralroomunitscouldbecontrolledparallel.Inpractice,theareaofthecontrolzoneshouldnotbemorethan50m2 to maintaingoodcontrollabilityofinternalconditionsinopenlayoutoffice.
InFig.16,thereisshownofanexampleofthecontrolzoneselectionswhereone(~10m2)andfive(~50m2)roomunitsconsistsacontrolzone.Inthecontrolzoneoffiveroomunitsandacommonroomcontroller,theroomairtemperaturehappenswithacommonvalveorallbeamsareequippedwithvalvesandthosevalvesareparallelcontrolled.
Infiveroomunitszone,indoorairqualityiscontrolledwiththeroomunitspecificcontroldampers.Thosedampersarecontrolledindividuallyorparallelusingoneorseveraloccupancysensor.
2.2.3 System & component overviewTheHaltonVariosystemcontrollerisaroomcontrollerdedicatedtocompleteroomapplicationsprovidingthecontrolofcooling,heating,demandcontrolledventilation.TheHaltonVariosystem'sroomcontrollermanageschilledbeamoperationbycontrollingchilledwaterandhotwatercontrolvalvesin2-or4-pipeapplications.Alsoelectricheatingcanbeused.
Thesystemcanoperateasstandaloneorconnectedtoabussystem.
InHaltonVariosystem,theroomcontrolpackagecoversallrequiredsensor,actuators,valvesanddampersthatmakespossibletocontrolroomairtemperatureandindoorairquality.InFig.17,thereisdescribedthepossibleoptionstointegrateforroomcontrolscheme.RoomcontrollerandsensorcouldbefactoryinstalledintoHaltonRexchilledbeamunit.
Fig.15. Utilization of two beam lengths makes it possible to build different sizes of the control zones. All read lines are the boundaries of the control zones. Control zones are equipped with enough number of occupancy sensors. Typically one occupancy sensor cover ~15 m2.
needsamodifiedimage*nowtoo
unclear
18 19
Fig.16. An example of the selection of control zones where the dotted lines indicate the boundaries of the selected zones.
Fig.17. Components for the room controller.
Room level
11
Wall control panel
Cooling valve
Heating valve
Unit integrated temperature sensor
Window switch
Condense sensor
Room controller
Multi-sensor
CO2 sensor
Remote control panel
Halton Rex Vario 600 with airflow control damper
•HaltonRexintegratedroomcontroller
•Roomairtemperaturemeasurementto
controlspacetemperature
•Occupancysensorfordemandbased
operationwithairflowratecontrol
damper
•Airqualitycontrolwithcarbondioxide
sensor,CO2
•Coolingwithchilledwatercontrolvalve
•Heatingwithhotwatercontrolvalveor
electricalheatingasanoption
•Severaluserinterfaceoptions,either
wallmountedorhand-heldremote
controller
•Condenseprevention
•Energysavingwindowswitch
operation
newclearerimageneededhere'
20
Room level
System components1)HaltonRexchilledbeamswithventilation,coolingandheating(waterorelectric),•Valvesandactuator•Damperandactuator
2)Roomcontroller,userinterfaceandsensors•Userinterfacepanel•Roomairtemperaturesensor•Occupancysensor•Carbondioxidesensor•Windowswitch•Condensationsensor•Lightandsunblindscontrol
Occupancysensorisafundamentalelementof
demandbasedroomconditioncontrol.Itdetects
presenceofpeopleandthereforeadjuststhespace
eithertounoccupiedoroccupiedmode.Theremote
controlleriscommunicatingwithHaltonmulti-sensor.
Themulti-sensorincludesoccupancysensor,light
sensorandremotecontrollerinterface(Fig.18).
Whenapersonenterstheroom,theoccupancy
sensorsendsasignaltotheHaltonVariosystem's
controllertoinformthatthespaceisoccupied().The
controllersetautomaticallyairflowrateandroomair
temperaturesetpointtoacomfortlevel.Whenleaving
thespacetheoccupancysensorsendsanoffsignalto
theHaltonVariosystem'scontrollerthatthespaceis
empty.Afterachosentimedelaythecontrollerwill
usethesetpointsforunoccupiedspace()sensor
coversofthespaceareaof38m2(7x5.5m).Thus,an
occupancysensorcanserve1or2chilledbeamsin
openlayoutoffice.
Thebuildingmanagementsystem(BMS)may
participateinoperatingmodedefinitionbysendingday
andnightinformation.Inthisdocumenttheday()
representsnormalofficehoursandnight()referto
timewhenmostpeopleareoutofoffice.The
combinationofoccupancysensorandBMS
informationdefinestheactualroommode(Table9)
whereallmodeshaveindividualroomairtemperature
andairflowratesettings.
Table 9. Occupancy based space operation modes.
BMS Room Operation modes and airflow rate control
Occupied Comfort settings
Stand-by Be ready for comfort, while saving energy
Unoccupied Eco settings
Occupied Comfort settings
Roomairtemperaturecanbemeasuredeitherbywall
mounteduserpanelorHaltonRexchilledbeamunit
integratedtemperaturesensor(Fig.19).Wallmounted
userpanelisthemostbeneficial,whenfeasibleceiling
structureisavailable.
Thecontrolunitintegratedtemperaturesensor
ensuresmostflexiblelayoutstructureoffloorspace.
TheHaltonRexchilledbeamcanbelocatedeitherin
openfloorspaceoratdedicatedroom.The
temperaturesensorismeasuringthetemperatureof
thespace,andcontrolstheheatingandcoolingvalves
accordingtoroomairtemperaturesetpoint.
Fig. 18. Occupancy sensor and remote controller interface.
Fig. 19. Room temperature control panel and integrated temperature sensor.
20 21
Room level
Condensesensorpreventswatercoilcondensation.In
caseofcondensationthecoolingvalvewillbeclosed
and airflow control damper is set to predefined
position(configurable:remaininnormalcontrol,closed
orfullyopen).Normalcoolingoperationwillbe
re-activatedafteradelay,whencondensationhas
vanished.
Fig. 21. Window switch to detect open window.
Fig. 20. Condense sensor.
Windowswitchisusedtodetectopenwindow.If
windowisopened,bothheatingandcoolingwillbe
closeddown(watervalvesandoptionalelectrical
heating).TheairflowcontroldamperofHaltonRex
chilledbeamissettopredefinedairflowrateposition
(configurable:previousvalue,min,medornormal).In
allcasesthefreezeprotectionmodestaysactive.The
freezeprotectionmodeisactivated,ifroomair
temperaturefallsbelow+8°C.Atfreezeprotection
theheatingvalveorelectricalheatingisactivatedto
preventwatercoilicing.Normalcontroloperation
startsafterpredefineddelaywhenthewindowis
re-closed.
Fordemandbasedventilation,CO2- concentration is
usedasanindicatorofindoorairquality.Supply
airflowrateiscontrolledtomaintainthesettarget
valueofCO2whentheoccupancyratioofpersonis
changed.ThesetvalueofCO2- sensor is typically
600-900ppm(Fig.22).
Fig. 22. Control principle of indoor air quality with CO2- sensor.
22
2.3All-airsystem
2.3.1 Operation
TheHaltonVariosystemisbasedonactivediffusers
andconstantstaticpressure.Roomairconditionsare
controlledbymodulatingsupplyairflowrate.The
controllingsensorcanbeatemperaturesensor,aCO2
sensor,apresencesensororacombinationofthese.
Thethrowpatternisconstantinalloperation
conditionsandthusdraughtriskisminimized.
Dependingonhowthechangeinthepressureofthe
zoneductismanaged,theall-airterminalunitsare
classifiedaspressureindependentorpressure
dependentunits.ApressureindependentVAV-unit
canbedefinedasadevicewheretheairflowcontrolis
notdisturbedbythefluctuationsofthestaticpressure
attheinletofthedevice.Keepingtherequiredstatic
pressureinthemainductsafter
thefansystemcancontrolterminalunits.InFig.23,
thereisshownaconceptofpressureindependent
VAV-system.
Theflowisdeterminedbasedonthedevice'sopening
(between0to100%)andtheunderlyingconstant
staticpressure.Therefore,inordertoassureproper
workofthevariableVAVdiffusers,thelevelofa
pressureintheinletsideshouldbestrictlycontrolled.
Thisisassuredwithinstallingactivecontroldampers
ontheductsservingdifferentzonesformaintaining
constantpressure.
ApressuredependentVAV-unitisadevicewherethe
airflowcontrolisdependingonthestaticpressureat
theinletsideofthedevice.Theairflowwillvarywith
thefluctuationsinstaticpressurebeforethedeviceif
thestaticpressureinthezoneductisnotmaintained
constant.HaltonVariosystem'sall-airsystemisbased
ontheconstantpressureductworkandpressure
dependingactivediffusers.InFig.24,thereisshown
aconceptofpressuredependentVAV-system.
Room level
22 23
Fig.23. A traditional VAV system with pressure independent space supply air terminal units.
Fig.24. Halton Vario all-sir system based on the constant static ductwork.
Room level
24
Room level
IntraditionalVAVsystemwithpressureindependent
supplyairterminalunits,thepressuresensorSPset
pointvalueiskeptonalevelthatcanassureaproper
workofapressureindependentVAVterminalunitatthe
designairflowrate.Inpressureindependentairterminal
unit,thepressuredropsoverthedeviceistypically30
-50Pa.
Room air temperature
Roomairconditionsarecontrolledbymodulating
supplyairflowrate.Incoolingmode,during
unoccupiedmodethesupplyairflowrateatminimum
value.Inthesequence,thesystemisstandbymode.
Whenloads/pollutionsincrease,theairflowrateis
increasedtoreachthesettargetvalue.Exhaust
followsasaslavesupplyside.Inheatingmode,the
operationisasincoolingexceptseparatesetof
parameters
Theparametersthatcontroltheamountofairsupplied
totheroomcanbetemperature,CO2 or presence in
theroom.Usercouldboostbyhandswitchtheairflow
andifwindowisopenventilationisstopped.InFig.
25,thereisshownaprincipleofthesequencesforair
temperaturecontrol.
Usercanchangetheroomairtemperaturesetpoint
withwallmountedorremoteuserpanel.Thesetpoint
shiftrangeisdefinedasparameter.Thedefaultvalue
oftheshiftis±3°C.
Air quality
Airqualityiscontrolledbasedonroomoccupancy
mod,temperatureandindoorairquality.Inoffices,
airflowrateistypicallyadjustedaccordingtoroomair
temperatureandoccupancyofthespace.Inmeeting
roomstogetherwithroomairtemperatureand
occupancy,indoorairqualityiscontrolled.
ControlofairqualityisbasedonCO2sensor.Demand
controlventilationinvolvesvaryingtheoutdoorairflow
rateinresponsetothequantityofoccupantsinthe
space.HaltondiffuserJazincreasedautomatically
supplyairflowrateandmaintainthesetCO2-level,
WhenbothroomairtemperatureandCO2- sensors
areused,thehigherdemandcontrolsthesupply
airflowrate.Fig.26illustratesdemandcontrol
ventilationwithHaltonJazactivediffuserconcept.
BMSsystemadjuststothesystemeithernightorday
operationmode.Inunoccupiedspaces,therecouldbe
differentairflowratesettingfornightanddaytimes.
InTable11,thereareshownoperationmodesand
airflowcontrolfunctionsinunoccupiedandoccupied
spacesduringdayandnighttimes.
TheactualHaltondiffuserJazairflowratesdependon
selectedactivediffusersize,levelofstaticpressurein
ductworkandcontrollerparametersettings.The
airflowrangeforthespecificconditioncanbefound
fromHaltonHIT.
Intheunoccupiedandstand-bymodes,theHalton
diffuserJazairflowisreducedandthereforeheatingor
coolingcapacityoftheroomunitisdecreased.To
preventspacetemperatureexceedingtemperature
setting,thecontrollerwillresettheunitairflowrateto
normalairflowvalueuntilroomconditionsareagainon
thedesiredlevel.Whentheroomairtemperaturehas
reachedthesetpoint,theairflowrateisthen
readjustedtotheunoccupiedandstand-bysettings.
Fig.25. Halton Vario Room air temperature control sequences with Halton Vario air terminal unit.
InTable10,thereispresentedtypicalroomair
temperaturesetpoints.Allpresentedvaluesare
parametersthatusercanchange.
Table 10. Examples of room air temperature set points.
Space mode Cooling mode
Occupied 25 °C
Stand-by 26 °C
Unoccupied 28 °C
24 25
Room level
Office room, typical airflow operation Meeting room, typical airflow operation
Fig. 26 Airflow rate is controlled based on occupancy, room air temperature and air quality.
Table 11. Operation modes and the control of airflow rate.
BMS Room CO2 Operation modes and airflow rate control
600-900 ppm Boost Increased airflow Increased airflow based on room conditions
Occupied Normal airflow Adjusted by parameter
Stand-by Reduced airflow Adjustable by parameter
Unoccupied Eco settings Adjustable by parameter, or off
Occupied Normal settings Normal diffuser airflow
Throw pattern
ThedraughtriskmayoccurwhenusingVAVterminal
unitstogetherwithsupplyairdiffuserswithconstant
dischargearea,suchasCAVsupplyairdevices.The
airflowpatternissuingfromthediffuser,which
dischargestheairhorizontallyacrosstheceiling,hasa
naturaltendencytoattachtothesurface.Ifthe
dischargeareaofthediffuserremainsconstant,the
velocityofthesupplyairstreamfallsindirect
proportiontothereducedairflowrate,resultingarisk
ofthesupplyairjetfallingawayfromtheceiling.
HaltonJazall-airactivediffusercontrolsthrowpattern
andthuspreventdraughtrisk.Draughtriskhasbeen
avoidedwithactivediffuserwork,whichcontrolsthe
diffuseropeningsinawaythatrelativelyconstantair
velocityrangeismaintainedanddumpingwillbe
avoided.ThethrowpatternofHaltonJazactive
diffuserwithmaximumandminimumairflowrateis
illustratedinFig.27.
Fig.27. A scheme of the thrown patter of Halton Vario active diffuser.
Halton Jaz Vario maintains thermal conditions
•Withlowairflowrates,thethrowpatternisdetached
fromceiling:Coanda-effectisutilizedevenwhen
airflowratesareattheminimumlevel
•Demand-basedairflowratesavesenergy.
InHaltonactivediffuser,theairflowcontrolandroom
airdistributioncomponentsareintegratedintothe
sameterminalunit.Thenumberofrequiredsystem
componentsisreducedcomparedstandardVAV-
system.
Min. flow 10%
Max. flow 100%
Min. flow 10%
Max. flow 100%
26
Fig. 28. A principle of the operation of Halton Jaz active diffuser.
Activediffuserchangesitsoutletconfiguration
automaticallywhencontrollingthesuppliedairflow
rate.Theairissuppliedbetweenacontrollingplate
withadistancethatvariesaccordingtotheairflow
rateneeded(Fig.28).Thepositionoftheplateis
controlledbyatraversingmotor,whichgetsimpulses
fromthecontrollingsensorlocatingintheroom.The
controllingsensorcanbeatemperaturesensor,aCO2
sensor,apresencesensororacombinationofthese.
Theflowisdeterminedbasedonthediffuser's
opening,whichisbetween0to100%andthe
underlyingconstantstaticpressure.
Thebasicideabehindthevariablesupplyairdiffuseris
tomaintainaconstantvelocityofthesupplyair
streamdischargedfromthediffuserwithadecreasing
supplyairflowrate.
Room level
2.3.2 Layout and control zone considerations
Zonecontrolcoversroomairtemperature,outdoor
airflowrateandexhaustairflowratecontrolschemes.
Thefloorareaofthecontrolzoneshouldnotbemore
than50m2.Thenumberofparallelcontrolledunits
shouldnotbemorethanfive.
Abalancebetweenthesupplyandexhaustairshould
beassuredinalloperationconditions.Thebalance
betweensupplyandexhaustsideiscontrolledatzone
level.Basedonthesupplyairflowratemeasurement,
theexhaustairflowrateissettomaintaintherequired
pressurizationorequalflowsinsupplyandexhaust
sides.Balancedcontrolzonecouldbearoomor
severalroomunitscouldformacontrolzone.
Inzoneswhereisseveralsupplyunits,theairflowrate
oftheeachunitsarecontrolledparallel.Thenumberof
theparallelcontrolunitshouldnotbehigherthan4
andthemaximumsizeofthecontrolzoneshouldnot
belargerthan50m2.
Exhaustairflowratecouldbeductedineachzone.
Exhaustductworkispossiblesimplifiedbyonly
providingsupplyairflowrateinthespaces.Becauseof
over-pressuretosurroundings,exhaustisleadedto
corridorandfurthertowardscentralizedexhaust
system.Inrooms,thereareinstalledtransfergrilles.
Thetransfergrillesshouldhaverequiredattenuation
propertytomaintainacousticsprivacyInthespaces.
InFig.29,thereisshownanexampleofHaltonJaz
all-airconceptwherethesupplyandexhaustairflow
ratesarebalancedatzonelevel.InFig.30,thereisan
exampleofonefloorofopenlayoutofficewherethe
exhaustiscentralized.
Itshouldbenotedthatinthecentralizedexhaust
conceptairflowratebalanceisnotreallyfulfilledin
eachrooms.Thebalancebetweensupplyandexhaust
airflowratesisvalidonlyatzonelevel.
Tomaintainexactspacelevelairflowratebalance
betweensupplyandexhaustairflowrates,exhaust
sideshouldbeprovidedcontroldamper.Supplyair
flowrateisthemasterandexhaustairflowrateisthe
slavethatfollowssupplyairflowrateandmaintainthe
setpressurization.Toprovideinbothsupplyand
exhaustdemand-basedcontrol,theinvestmentcosts
ishigherthanwithcentralizedexhaustsystem.
26 27
Fig.29 An example of the selection of control zones with Halton Jaz system.
Room level
Fig.30. An example of installation in open layout office with Halton Jaz diffuser.
'needanewclearerimagewithout
theredtext*
28
Room level
System & component overview
TheHaltonVariosystem'sJazcontrollerisaroom
controller dedicated to complete room applications
providingthecontrolofcoolinganddemandcontrolled
ventilation.InFig.31,thereisdescribedthepossible
optionstointegrateforroomcontrolscheme.Room
controllerandsensorcouldbefactoryinstalledinto
HaltonJazactivediffuser.
Thesystemcanoperateasstandaloneorconnected
toabussystem.
InHaltonVariosystemJazdiffuser,theroomcontrol
packagecoversallrequiredsensor,actuatorsand
dampersthatmakespossibletocontrolroomair
temperatureincoolingmodeandindoorairquality.
System components
1)HaltonVariosystemJazactivediffuserforcooling
andventilation,
•embeddedtravelsingactuarandcontrolplate
2)Roomcontroller,userinterfaceandsensors
•Userinterfacepanel
•Roomairtemperaturesensor
•Occupancysensor
•Carbondioxidesensor
•Windowswitch
•Lightandsunblindscontrol
Occupancysensorisafundamentalelementof
demandbasedroomconditioncontrol.Itdetects
presenceofpeopleandthereforeadjuststhespace
eithertocomfortorenergysavingmode.Theremote
controlleriscommunicatingwithHaltonmulti-sensor.
Themulti-sensorincludesoccupancysensor,light
sensorandremotecontrollerinterface(Fig.32).One
sensorcouldcoverof15m2floorarea.
Whenapersonenterstheroom,theoccupancysensorsendsasignaltotheHaltonVariosystem's
Fig. 31. Components for the room controller. 15
Wall control panel
Room controller
Multi-sensor
CO2 sensor
Remote control panel
Unit integrated temperature sensor
Window switch
Halton Jaz Vario active diffuser with airflow control damper
•HaltonJazdiffuserintegratedroom
controller
•Roomairtemperaturemeasurementto
controlspacetemperature
•Occupancysensorfordemandbased
operationwithJazairflowcontrol,
installedonsuspendedceiling
•Airqualitycontrolwithcarbondioxide
sensor,CO2
•CoolingwithJazairflowcontrol
•Severaluserinterfaceoptions,either
wallmountedorhand-heldremote
controller
•Energysavingwindowswitch
operation
Fig. 32. Occupancy sensor and remote controller interface.
28 29
Room level
controllertoinformthatthespaceisoccupied().Thecontrollersetautomaticallyairflowrateandroomairtemperaturesetpointtoacomfortlevel.WhenleavingthespacetheoccupancysensorsendsanoffsignaltotheHaltonVariosystem'scontrollerthatthespaceisempty.Afterachosentimedelaythecontrollerwillusethesetpointsforunoccupiedspace()andadjustthespaceintoecomode.Theoccupancysensorcoversofthespaceareaof38m2(7x5.5m).Thus,anoccupancysensorcanserve1or2Jazactivediffusersinopenlayoutoffice.
Thebuildingmanagementsystem(BMS)mayparticipateinoperatingmodedefinitionbysendingdayandnightinformation.Inthisdocumenttheday()representsnormalofficehoursandnight()refertotimewhenmostpeopleareoutofoffice.ThecombinationofoccupancysensorandBMSinformationdefinestheactualroommode(Table12)whereallmodeshaveindividualroomairtemperatureandairflowratesettings.
Fig. 33. Room temperature control panel and integrated temperature sensor.
Fig. 35. Window switch to detect open window.
Table 12. Occupancy based space operation modes.
BMS Room Operation modes and airflow rate control
Occupied Comfort settings
Stand-by Be ready for comfort, while saving energy
Unoccupied Eco settings
Occupied Comfort settings
Fig. 36. Control principle of indoor air quality with CO2- sensor.
Windowswitchisusedtodetectopenwindow(Fig.35).Ifwindowisopened,coolingwithsupplyairwillbestopped.ThetraversingmotorofHaltonVariosystem'sJazdiffuserissettopredefinedairflowrateposition).
Fordemandbasedventilation,CO2- concentration is usedasanindicatorofindoorairquality.SupplyairflowrateiscontrolledtomaintainthesettargetvalueofCO2whentheoccupancyratioofpersonischanged.ThesetvalueofCO2-sensoristypically400-500ppm(Fig.36).
Fig. 34. Perforated and solid bottom plate option for Halton Jaz Halton Vario system's units.
RoomairtemperaturecanbemeasuredeitherbywallmounteduserpanelorHaltonJazdiffuserunitintegratedtemperaturesensor(Fig.33).Wallmounteduserpanelisthemostbeneficial,whenfeasibleceilingstructureisavailable.
Thecontrolunitintegratedtemperaturesensorensuresmostflexiblelayoutstructureoffloorspace.TheHaltonJazdiffusercanbelocatedeitherinopenfloorspaceoratdedicatedroom.Thetemperaturesensorismeasuringthetemperatureofthespace,andcontrolstheheatingandcoolingvalvesaccordingtoroomairtemperaturesetpoint.
TemperatureandCO2-sensorscanbeintegratedintoperforatedsupplyofHaltonJazdiffuserunits.Sensorintegrationisavailableforsolidandperforatebottomplateexhaustunits.Alternativelywallmounteduserpanelwhereroomtemperaturesensorisinstalledcouldbeused.InFig.34,thereispresentedtwoavailablebottomplatesoption.
30
Zonal level
The constant static pressure ductwork guarantees the performance of the demand- based room terminals. Balancing and monitoring of space airflow rate is simple thanks the linear function of the space damper. In the same zone, it is possible to integrate constant and variable airflow rate terminal units.
Thepurposeofsupplyductworkistodeliverairfromthefantotheroomterminalswhichdistributeairtotheroom.Therequiredpressuredifferentialrequiredbythefanisafunctionofductdesign.Theobjectiveofductdesignistosizetheductsuchthat: •Enableeasychangeofairflowratesofspaces •Minimizepressuredrop •Minimizenoise •Minimizedcost •SimplifyBalancing
Properductdesignrequiredknowledgeofthefactorsthataffectpressuredropandvelocityintheduct.
3.Zonallevel
Pressureinaductsystemisthesumoftwocomponents,staticpressureandvelocitypressure.Staticpressureisequalinalldirections.Velocitypressure(dynamicpressure)isduetothemomentumoftheair.Velocitypressureisdirectional.DynamicpressurecanbecalculatedusingEquation1wherevisairvelocityandρ=densityofair(1.2kg/m3).
Pdyn = ½*ρ*v2 (1)D
Dynamicpressureplusstaticpressure(Ps)isequaltototalpressureasshowninEquation2.
Pt=Pdyn+Ps (2)
Iftheoutletareaislargerthantheinletarea,thevelocitypressureattheoutletmustdecrease.Withafrictionlesssystemwheretotalpressureremainsconstant(Pt),staticpressure(Ps)mustincreaseatthesameratethatvelocitypressure(Pdyn)decreases.Thisphenomenonisknownasstaticregain.Inconstantpressureductworkconceptthisstaticregainisutilized.
3.1Operationbasedonconstantpressureductwork
30 31
Fig. 37. Development of the static, dynamic and total pressure in a ductwork.
Zonal level
However,bothductworkandfittingsintroducefriction.Instraightduct,frictionlossesareduetofluidviscosity.Frictionlossesoffittingsarecausedbyturbulencebetweenthemainandbranchductswhentheairflowpathdirectionchange.Frictionlossesareirreversibleandaretheconversionofmechanicalenergyintoheat.
Generallyspeaking,frictionlossesperunitlengthofstraightductarelessseverethanfrictionlossesinfittings.Frictionallossesoccurattheexpenseofstaticpressure.Frictionallossesdonotimpactvelocitypressure.InFig.37,thereisshowndevelopmentofthetotal,dynamicandstaticpressureinaductworkfromtheairintaketotheterminalunit.
Thesumofthestaticpressureplusdynamicpressureatanypointequalsthetotalpressureintheductsystem.Thelossintotalpressureisadirectresultofthelossinstaticpressureduetofrictionalandturbulencelosses.
Mostengineersusetheequalfrictionlossmethodinductworkdesign.Typicaldesignvalueofthefrictionlossis0.5-1Paperlinearmeter.Withtheequalfrictionlossmethod,thisleadstoairvelocityof4...6m/s.Thismethodisforcingthedesignertoconstantlydecreasethefreeareaoftheduct.InFig.38,thereisdescribedthetotal,dynamicandstaticpressureswhentheconstantpressurelossmethodisused.
Withtheconstantstaticpressuremethod,thepressurelossofductbranchisregainedbydecreasingtheairvelocityafterthebranch.Thishappenswhentheductisnotreduced.Thesamesizeofductworkandrelativelylowvelocity(<max3..5m/s)guaranteesinpracticethatthestaticpressureoverthezoneisconstant.
32
Zonal level
Fig. 38. The change of the total, dynamic and static pressures with constant friction loss method.
Fig. 39. The change of the total, dynamic and static pressures with constant static pressure method.
Thebenefitsofthestaticpressureductworkare:•Giveflexibilitytocontrolspaceairflowrateswith
linear control dampers•Toensureoptimalpressurelevelinallductbranches•Possibletointegrateconstantairflowrate(CAV)and
variableairflowrate(VAV)unitsinthesameductwork
•Easybalancing:onlystaticpressureshouldbechecked
•Reducednoisegenerationinductworkbecauseoflowvelocities
•Lowerfanpowercomparedequalfrictiondesignbecauseoflowvelocities
•Enablesfanoptimizationbyoptimizationdamperpositionsfortherequiredzonalstaticpressure
Inasimplifiedcase-ductwork(Fig.40),thereisdemonstratedthedifferenceofthepressurelevelsbetweentheequalfrictionlossandconstantstaticpressuremethods.Bymaintainingtheconstantfrictionloss(constantairvelocity),thestaticpressurereducesalotovertheductzone.Inthiscase-duct,thestaticpressureisatthefirstterminalunit110Paandreducedto30Paattheendeventhesetvalueofthezoneis150Pa.Thetotalpressurelevelofthemainductis300Paandhighvelocityrequiressoundattenuatorinallbranches.
Usinglowvelocitiesandconstantductsizeinzoneducts,thestaticpressuremaintainconstant.Thereisnoneedofzonalsoundattenuators.Thetotalpressurelevelofthesystemislow(110Pa)andthustheperformanceisenergyefficient.ConstantstaticpressuremakespossibletointroducelinearcontrolofzonedampersandintegrateCAVandVAVterminalsinthesamezoneduct.Linearizationgivesalsoadvantageforcommissioningandairflowratemonitoring.Byknowingthestaticpressureandthepositionofthedamper,itmakeseasilytochecktheactualairflowrateofthespace.
32 33
Zonal level
Fig. 40. The difference of pressure levels between the equal friction loss (panel above) and constant static pressure methods (panel below) (by courtesy of Skanska).
34
Inthezonallevel,thesupplyandexhaustairflowrates
shouldbebalanced.Inthesupplyside,theconstant
pressuredamperisequippedwiththemeasurement
unitthatgivesthesetvalueforexhaustside.Exhaust
airflowratesfollowsasaslavethesupplyside.InFig.
41,thereispresentedinHaltonVariochilledbeam
systemacentralizedexhaustconceptwhereexhaust
airflowsaretransferredthroughwallorceilinginstalled
transfergrillestowardstocentralizedexhaustpoint.
Thesupplyzonalductstaticpressureiskeptconstant
toensuretheoptimumoperationoftheHaltonRex
chilledbeamandtheHaltonJazactivediffuser.
TheMSSpressuresensorunitmeasurestheduct
staticpressureandsendsthevaluetotheHFS
pressurecontroller(0-10Vdc).TheHFScontrolsthe
ductstaticpressurelevelaccordingtothesetpointby
changingdamperbladeposition.
Zonal level
Fig. 41. Constant static pressure supply zone with centralized zone exhaust in Halton Rex chilled beam.
Fig. 44. In large ductworks, the airflow rates should also balancing in the main air conduit.
TheHFSmeasurestheactualairflowrateonsupply
ductandsendsit(networkvariableand/or0-10Vdc)to
theexhaustairflowcontroldamper,HFB.The
measuredsupplyairflowrateisthesetpointtothe
exhaustairflowdampertoensurebalancedventilation
ineachzone.TheexhaustHFBsetpointcanbeshifted
relatedtothesupplyairflowtomaintainthedesigned
over-pressureorunder-pressurebalanceofspace.
(Fig.42).
Theexhaustunitcanbeeitheracommonexhaust
grilleorJazdiffusersinstalledthespaces.
Largerfloorspacecanbedividedtoseveralduct
zonesandsupplyductpressureleveliscontrolled
individuallyoneachzone.Thismakesitpossibleto
havedifferentductpressurelevelsondifferentzones
andenablesuseofdifferentproductslikeHaltonRex
beamandHaltonJazdiffuseratsamefloorspace
(Fig.43).
Inthemainsupplyandexhaustducts,thereare
installedstaticpressuremeasurementunits.Those
unitsgivethesetstaticpressurethatthefanatair-
handlingunitcontrol(Fig.44).
34 35
Zonal level
The MSS pressure sensor unit measures the duct static pressure and sends the value to the HFS pressure controller (0-10 Vdc). The HFS controls the duct static pressure level according to the set point by changing damper blade position.
The HFS measures the actual airflow rate on supply duct and sends it (network variable and/or 0-10 Vdc) to the exhaust airflow control damper, HFB. The measured supply airflow rate is the setpoint to the exhaust airflow damper to ensure balanced ventilation in each zone. The exhaust HFB setpoint can be shifted related to the supply airflow to maintain the designed over-pressure or under-pressure balance of space. (Fig.42).
The exhaust unit can be either a common exhaust grille or Jaz diffusers installed the spaces.
Room units: Room units:
Supply: Vario Rex chilled beam with integrated room controller
Supply: Vario Jax active diffuser with integrated room controller
Supply: Vario Jax active diffuser with integrated room controller
Exhaust: Common exhaust grille.
Exhaust: Vario Jaz exhaust unit with equal outlook with supply unit
Fig. 42. Constant static pressure supply zone with the combination of space and centralized exhaust. Larger floor space can be divided to several duct zones and supply duct pressure level is controlled individually on each zone. This makes it possible to have different duct pressure levels on different zones and enables use of different products like Vario Rex and Vario Jaz at same floor space (Fig.43).
Fig. 43. Office floor plan with compbination of Vario Jaz and Rex units and with Vario Jaz units.
In the main supply and exhaust ducts, there are installed static pressure measurement units. Those units give the set static pressure that the fan at air-handling unit control (Fig. 44).
Fig. 44. In large ductworks, the airflow rates should also balancing in the main air conduit.
Fig. 43. Office floor plan with combination of Halton Jaz diffuser and Halton Rex units and with Halton Jaz units.
Fig. 42. Constant static pressure supply zone with the combination of space and centralized exhaust.
Room units Room unitsSupply:Halton Rex chilled beam with integrated room controller
Supply:Halton Jaz active diffuser with integrated room controller
Exhaust:Common exhaust grille.
Supply:Halton Jaz active diffuser with integrated room controller
Exhaust:Halton Jaz exhaust unit with equal outlook with supply unit
36
Zonal level
IntheTable13,thereisshownestimatedfloorareas
ofthezonethatarepossibletocoverwith10%and
30%ratioofthemeetingrooms(4l/sperm2)and
officerooms(1-2l/sperm2).Thisdepictsthatwith
thefollowingassumptionthezoneareaisfrom300..
900m2.Itshouldbenotedthatactualzonesshouldbe
specifiedwiththeductworkcalculationswherethe
staticpressurelevelsovertheductworkareanalyzed
indifferentoperationconditions.
Withtheusedductworktopologyandductsize,the
changesinthestaticpressureoverthezoneshouldbe
analyzed.Largervariationinthestaticpressureleads
higherinaccuracywiththeairflowrateoftheterminal
units.
Chilledbeamsoperatetypicallyatlevelof80..100Pa.
Inordertoachieveairflowrateinaccuracyoflessthan
10%atroomterminallevel,thedeviationofthestatic
pressurelevelcan’tbehigherthan10...20Pa.
Designofthestaticpressureductworkhappensinthe
followingsteps:
• Airflow rate
Calculatemaximumzoneairflowrateincludingthe
needofmeetingroomsandboostedoffices.
• Size of zone ducts
Airvelocitymax3..5m/sinsupplyduct
Airvelocityof5m/sinexhaustduct
Wholezonesupplyductasequalsize
Exhaustductsizedbyconstantairvelocity
• Connection ducts of terminal units
Thelengthofconnectionductisrecommendedto
beshort<3m.
• Number of units
Typically10-20unitsinductbranch(withringduct
numberofunitsmuchhigher)
• Static pressure sensor
Locatethepressuresensorat1/2--2/3ofthebranch
lengthinsupplyduct
Exhaustductsensorat1/2–1/1ofthebranch
length
• Static pressure set point
DesignroomunitswithHaltonHITandincrease
5-10Patothesetpoint.
• Selection of the zone control damper
5-7m/swithmaximumairflowrate
1-2m/swithminimumairflowrate
Ventilation rate Duct size 400 Duct size 500
Offices Meeting rooms
Percentage of meeting rooms
Percentage of meeting rooms
l/s/m3 l/s/m3 10% 30% 10% 30%
1 4 590 400 905 620
1.5 4 430 335 675 525
2 4 340 290 535 455
Table 13. Zone estimation according to ventilation rates.
3.1.1. Design of constant pressure ductwork
The maximum variation of the static pressure
could be 10-20 Pa to achieve inaccuracy of airflow
rate less than 10 % at terminal units. By using low
air velocity of 3.. 5 m/s and the constant duct size,
it is possible to maintain constant static pressure in
zone duct. Depending on the design airflow rates
and duct topology, 10-20 terminal units could be
installed in a zone.
Constantpressureductdesignisbasedonthestatic
regainafterductsection.Thesamesizeofzoneduct
andrelativelylowvelocityguaranteesthatthe
pressureconversationfromdynamicpressuretostatic
pressurehappensafterthejunctionandthestatic
pressureisalmostconstantoverthewholezoneduct.
Itshouldbenotedinexhaustductisnotpossibleto
utllizestaticregainprinciple.Ductsaresizedbasedon
constantvelocity.Theairvelocitycouldbehigherin
exhaustductthaninsupplyairduct.Theairvelocityof
5m/scouldbeusedinexhaustducts.
Designstartswithdeterminationofthezones.Thezone
couldbethewholefloorareaorpartofthefloor.The
totalrequiredairflowrateisdeterminedforthespecified
zone.Theairflowrateiscomputedtakenintoaccountof
thefutureneedstochangespaceprogram.Inthis
phase,itisimportanttoconsiderwhatisthereserved
ratioofthemeeting(4l/sperm2)andofficeroom(2l/s
per m2).Also,thepossiblelocation(beginningorendof
duct)ofmeetingsroomshouldbeconsidered.
Byusinginthestartingpointairvelocityof3..5m/s,
theductsizeisdetermined.Inpractice,thespace
constraingivesthelimitforpossibleductsize.Forthe
roundducts,themaximumsizeistypically400or
500mm.Withwiderectangularducts,itispossibleto
increasetothesupplyairflowratewiththesame
heightofthespaceconstrain.
36 37
Examples of ductwork topology
The final ductwork topology and duct size
determination is a project specific issue. Many
cases trade-offs are required e.g. because of the
space constrains and possible locations of air
conduit. It is recommended to use symmetric
ductwork. In large ductworks, ring ducts assist to
maintain the constant static pressure.
InFig.45,thereisanexampleofthevariationofthe
staticpressureinaductworkwherethemaximumair
velocityandthetotalairflowrateare5m/sand258l/s
.Theconstantsizeofroundductis315mmandthe
lengthoftheductis50m.Thestaticpressuresensor
isinstalledinthemiddleofthezone.Thepressure
dropoftheroomunitsissetto80Pa.Intheduct
zone,thereare9officeswiththeairflowrateof20l/s.
Attheendoftheductwork,thereismeetingarea
withtwo40l/sroomunits.Inthiscase,thestatic
pressurevariedonly10Painthemainductfromthe
setvalueleadinginaccuracyof5%intheroomunit.
Thefinalductworktopologyandductsize
determinationisaprojectspecificissue.Manycases
trade-offsarerequired.HaltonHITBalanceassiststhe
designoftheductworks.Itmakespossibletoanalyze
differentductworktopologies,thelocationofthe
staticpressuresensorandductsizes.HitBalance
makespossibletooptimizesolutionforthesetdesign
Zonal level
demandsandtoguaranteetheperformance.InFig.
46,thereisanexampleoffloorductworkdesign
wherethestaticpressurelevelsareanalyzedina
complicateductwork.
Itisrecommendedtousesymmetricductwork.Also
inlargeductworks,itisrecommendedtointroduce
ringductstomaintaintheconstantstaticpressure.In
Fig.47,thereisanexampleofthefloorlevelwhere
theringductconceptisintroduced.
Fig. 45. The static pressure and air flow rates in a case-study constant pressure duct.
Fig. 47. An example of ring duct design (by courtesy of Skanska).
needsanewfiguresothatcansee
thefigures'
38
Zonal level
Fig. 46. An example of complicate ductwork where the performance is optimized with Hit Balance.
38 39
3.1.2 System & component overview
Theconstantstaticpressurelevelismaintainedinthe
ductworkwithHFS-controldamper(Fig.48)andthe
staticmeasurementunitMSS(Fig.49).ForHFS-
controldamper,thereisintegratedwithflow
measurementunit(0-10Voutputsignal)asan
accessory.Theoperationrangeofthemeasurement
deviceisfrom1-7m/s.Soundattenuatorwith
differentlengths(600and100mm)isalsoavailableas
anaccessory.TheMSSunitincludesstatictype
pressuremeasurementsensorwithdigitaldisplay.
Adjustablepressuremeasurementranges
correspondingto0-10VDCoutputsignal.The
measurementinaccuracyofMSSlessthan±10%in
typicalapplications.
Intheexhaustsideasaslaveforsupply,HFBcontrol
damperisused(Fig.50).Thevariableairflowdamper
HFBcontainsanaveragingairflowmeasurement
probe,airflowcontrollerandactuator.Airflowis
controlledbasedonactualflowmeasurementby
changingthedamperbladeposition.Theoperation
rangeofthemeasurementdeviceisfrom1-7m/s.
Soundattenuatorwithdifferentlengths(600and100
mm)isalsoavailableasanaccessory.
Intherectangularducts,controldamperUKVisused
tomaintainconstantstaticpressureorthesetairflow
rate(Fig.51).UKVissuitableforlargeairflowrates
fromfacevelocityof1m/sup-to11m/sinsome
applications.UKVwidthisfrom200mmto1600and
heightfrom200mmto1000withtheincrementsof
50mm.
Zonal level
Fig. 48. Zone damper HFS.
Fig. 49. Measurement unit MSS.
Fig. 50. Zone damper HFB.
Fig. 51. Zone damper UKV for rectangular ducts.
40
Zonal level
3.1.3 Example of the specification of zone airflow
rates
Application of Halton Rex Chilled Beam with
Centralized Exhaust
InHaltonRexchilledbeamsolution,airflowrateis
variedinresponsetospaceandzoneoccupancy.In
unoccupiedspaces,outdoorairflowratesaresetto
minimumlevele.g.at0.3l/sperm2.Whentheroom
isoccupied,airflowratesareincreased(e.g.1.2-2l/s
per m2)tomeetairqualitytargets.Inmeetingrooms
whenoccupancyrateincreasedorthereisaneedto
boostairflowrate,theairflowratesaremodulating
e.g.upto4l/sperm2.Thusinthezoneductlevel,the
airflowratevariedalot.
InFig.52,thereisshownaHaltonRexchilledbeam
conceptforzonelevelairflowbalancing.Insupply
duct,constantstaticpressureismaintainedinsupply
ductandthemeasuredsupplyairflowrategivesthe
setvalueforexhaustdamper.
Selection of control dampers is based on the duct
size and the minimum and maximum airflow rate of
zone damper. When the maximum airflow rate is
determined, there is need to specify what is the
ration between meeting and office rooms. Typically
15- 50 % of space area is reserved for meeting
rooms.
Asanexampleofthezonedesign,thereistheareaof
240m2whereare24piecesof10m2roommodules.
Asabreakdownoftheroomunits,thereare18
offices(15l/spermodule)and6piecesofmeeting
rooms(40l/spermodule).Thus,thetotalairflowrate
is510l/s.Withtheselectionof400mmroundduct,
thisleadstothemaximumvelocityof~4m/s.The
minimumairflowrateis0.5l/sperm2means120l/s
and1m/svelocityintheductwork.
Fig. 52. Airflow rate control at zonal level with a Halton Rex chilled beam concept.
40 41
Zonal level
Halton Vario Optimizer (HVO)
Byoptimizingfanpower,itispossibletoreacha
significantenergysavings.Proportionalitylawsseta
correlationwherethepowerconsumptionofthefan
changestothirdpowerwithvolumetricflowratio.
HaltonVariosystem'sOptimizermaintainsduct
pressureaslowaspossibleandcommunicateswith
zonalpressurecontroldampers.
System solution
Byoptimizingfanpower,itispossibletoreacha
significantenergysavings.Proportionalitylawsseta
correlationwherethepowerconsumptionofthefan
changestothirdpowerwithvolumetricflowratio.In
demand-basedsystem,roomairflowrateiscontrolledin
roomunits.Constantpressureductworkismaintained
withzonecontroldampers.Ifthestaticduckpressureis
notoptimized,thepressureisunnecessaryhigh.
HaltonVariosystem'sOptimizerconsiststhree
hierarchiclevelsoperations:masterlevel,zonallevel
HVO-slaveunitsandzonaldamperswhosefunctions
are described below:
Fig. 53. The system architecture of Halton Vario fan optimizator (HVO).
HaltonVarioOptimizer(HVO)mastermodule:
•CommunicationtoAHU
•Network–analog(0-10V)(4-20mA)
•Monitorsallslavemodules
•AHUminimumandmaximumairflow
TheHVOslave
•CommunicationtoHVOmaster
•Network
•Upto6constantpressuredamper
•Damperposition
•Individualairflowmeasurement
•4inputsforfiredampers
Zonedamper
•CommunicationwithHVOslave
•Network
•Damperposition
•Airflow
InFig.53,thereispresentedthesystemarchitecture
ofHVO-concept.
The HVO slave
• Communication to HVO master • Network • Up to 6 constant pressure damper • Damper position • Individual airflow measurement • 4 inputs for fire damper
Zone damper
• Communication with HVO slave • Network • Damper position • Airflow
In Fig. 53, there is presented the system architecture of HVO- concept.
Fig. 53. The system architecture of Halton Vario fan optimizator (HVO).
42
Zonal level
Operation
Thetargetistomaintainaductpressurelevelthatis
aslowaspossibleinordertosaveonfanpower
consumption.TheHaltonVariosystem'sOptimizer
HVOmonitorstheopeningofeachzonedamperand
detectsthemostopendamper.Ifthismost
demandingandopendamperhasunnecessaryhigh
pressuredroplosslevel,theHVOadjuststheAir
HandlingUnit´spressureattheoptimallevel.Thisis
conductedwiththeTrimandResponseLogicleading
toalowerpressurelevelintheentirewholesystem.
TheHVO-slavemonitorsallthedamperspositionof
Fig. 54. Optimization of the static pressure level with Halton Vario Optimizator.
Communication
Halton Vario offers a total solution from management to room conditions, zone static pressure and the pressure optimization of air-handling unit. Halton Vario supports the most common communication protocols: LON, BACnet and MODbus. Halton Vario Rex and Jaz control systems covers the operation at room, zone and central level (Fig. 55). Halton Vario Master- unit is integrated to building management system (BMS) where operation of the system is monitored and the collected information is utilized in facility management.
eachdamperinthezone.Ineachzone,apressure
sensorisinstalled(MSS)tothezonedamperthat
registersthepressureineachzone.Inthezone
damper,theairflowrateisalsomeasuredwiththe
measurementdevice.
Informationoftheopeningofthedamperandairflow
rateissenttotheHVOslave.HVOslave-units
maintaintheadjustedstaticpressureandairflowrate
inthezoneandthusguaranteeexcellentthermal
comfortineachworkplace.
Ifthedamperpositionisaccordingtotheactualneed
forflowandstaticpressure,thereisnoneedfor
Fig. 54. Optimization of the static pressure level with Halton Vario system's Optimizator.
thisisaBelimoimage*.Canwe
useit?shouldweputbelow
Belimosname?
42 43
Zonal level
Fig. 55. Halton Vario control platform and integration with BMS.
adjustment.Butifthedamperopeningisabovethe
specifiedposition,theHVO-slavewillsendamessage
theHVOmasterthatmoreairflowisrequired.The
HVO-mastersendsalsoamessagetotheAHUto
increasethestaticpressuretogetmoreairflowtothe
spaces.
Ifthedamperopeningisbelowacertainpointe.g.
60%,theHVO-mastersendsasignaltotheAHUto
decreasethepressure.Thisensuresthatthemost
opendamperpositionwillbeincreased.
Thevaluesaresentevery2minutes(adjustable)to
adjustthestaticpressure.TheHVOmastermaintains
thesetminimumstaticattheair-handling.Also,the
HVOcomputersthesumofthezoneairflowratesand
guaranteesthatthezonalairflowrateisovertheset
minimumairflowrate.
HVOfanoptimizationhappenwithfollowingthree
steps(Fig.54):
1.Zonecontroldampersmaintainthesetstatic
pressure
2.Airflowratereducesandzonedampersareclosing
tomaintainthesetstaticpressure
3.HVOreducesthetotalstaticpressurelevelatair-
handlingunitandzonedampersopenstooptimal
positionthatmaintainthesetstaticpressureinzone
levels.
Communication
HaltonVariosystemoffersatotalsolutionfrom
managementtoroomconditions,zonestaticpressure
andthepressureoptimizationofair-handlingunit.
HaltonVariosystemsupportsthemostcommon
communicationprotocols:LON,BACnetandModbus.
HaltonRexbeamandJazdiffusercontrolsystems
coverstheoperationatroom,zoneandcentrallevel
(Fig.55).HaltonVariosystem'sMaster-unitis
integratedtobuildingmanagementsystem(BMS)
whereoperationofthesystemismonitoredandthe
collectedinformationisutilizedinfacilitymanagement.
Fig. 55. Halton Vario system control platform and integration with BMS.
Enabling Wellbeing
Halton OyEsterinportti 200240 HELSINKI, FinlandTel. +358 (0)9 221 2121www.halton.com