2020 High Wall SplitProduct Training
Haier Air Conditioning
Training Objectives
By the end of this training, you will:
• Have been introduced to the Haier Flexis Series.
• Be able to interpret and identify a Haier Aircon Flexis by their model number.
• Be able to interpret a Haier Aircon serial number and know where the serial plate is located.
• Be able to locate, understand and translate dimension and installation information.
• Have a basic understanding of system functions and specifications.
• Have a basic understanding of the error codes.
• Have a basic understanding of the electrical layout and specifics of sensors and type of compressors F&P Haier models use.
• Have an understanding of common repairs.
3
1• Flexis / MRVs
2• Application
3.
• Installation Easy Install/Maintenance4
• Remote Control & Functions
5• DRC & Wi-Fi
6• Technical Hints
7 • MRVs Installation
8• Questions
F Series
Flexis
Flexis AC High Wall
Indoor AS35FBBHRAAS53FEBHRAAS71FEBHRAAS82FFAHRA
Outdoor 1U35JACFRA1U53RABFRA1U71FEBHRA1U82SAAFRA
Remote Control YR-HQ Flexis
1. ECO SENSOR button (Flexis) Eco Pilot button (Dawn)
2. DRY button - Used to set DRY operation.
3. COOL button - Used to set COOL operation.
4. TEMP button - used to change setting Temperature
5. ON / OFF button
6. Display of each function status
7. Operation mode display
8. WIFI and CLOCK display
9. TEMP display
10. Humidity display
11. FAN SPEED display
12. SWING display - Swing up/down display, swing left/right display
13. TIMER ON display TIMER OFF display CLOCK display
14. FAN button
15. QUIET button
16. HEAT button
17. SELF CLEAN button
Flexis Controls
Remote Control YR-HQ
18. TIMER button
19. CLOCK button
20. 10 ºC button special heating set function: 10 degree heating maintaining (valuable for RS)
21. HEALTH button
22. SMART button Used to set SMART operation. (This function is unavailable on some models)
23. SWING up/down button
24. SWING left/right button
25. SLEEP button
26. HEALTH AIRFLOW button
27. LIGHT button Control off & on lightening of the indoor LED display board.
28. CODE button A-b yard
29. APPLY button
30. TURBO button
Flexis Controls
Domestic Air ConditionerBasics
• Air conditioning is the process whereby the condition of air, its temperature and moisture content, is changed.
• Comfort is subjective, however most people (90%), are comfortable when the air temperature is between 18-22°C and the humidity is between 40-65%.
• This known as the comfort zone or zone of human comfort
Temperature Comfort
Understand your location
• Good air circulation is imperative to good unit performance and energy efficiency
• Correct Outdoor unit air clearances improve performance and reduce noise
• Units need to be mounted where they can be accessed for service
• Correct wall brackets for the unit size need to fitted or ventilation and safety can be compromised
Haier AC Installation Dimensions
Installation Dimensions
IndoorOutdoor
Minimum Requirements
R32 Refrigerant
Now used in Flexis Models, R32 has similar working pressure to R410A around 12-26 Bar (174-377 Psi)
R32 has better capability to exchange heat-load than R410A , it produces a higher capacity than R410A therefore is more efficient.
Due to these efficiencies,R32 use 30% less refrigerant charge to produce an equal load capacity.
Flexis Installation
Modern type of flaring tool
• Flare joint must be made using the
correct tooling
• Modern flaring kit allows the flare ring to
be formed at a set “torque”
• The tightness is pre-set & does not over
stress the pipe work
• Be careful to remove the burrs by using a
deburring tool from the edges of the
pipes before flaring
Installation
Deburring Tool
• Flare joint tightened with a torque spanner
• Avoid over stressing the joint( double spanner)
Avoid stress
Installation
Correct torque must be applied
COPPER
PIPE OD
(mm)
FLARE
SIZE (mm)
FLARE
NUT OD
(mm)
TORQUE
N/m
6.35 ¼’ 8.7 – 9.1 17 14 – 18
9.52 3/8’ 12.8 – 13.2 22 34 – 42
12.7 ½’ 16.2 – 16.6 26 34 – 42
15.88 5/8’ 19.3 – 19.7 36 69 - 82
HVAC TOOLS
Equipment Model Number Please Circle
Recovery Unit Yes No
Nitrogen Regulator Yes No
Vac Pump Yes No
Vacustat/ Torr Gauge Yes No
Data Logger Yes No
Oxy & Acetylene Yes No
Anemometer and Air hood Yes No
Recovery Bottle Yes No
Refrigeration Gauges 410A/R32 Yes No
Bottle of Clean 410A/R32 Yes No
Amp/Tong Tester Yes No
Multi Meter Digital & Analogue Yes No
Digital Thermometer Yes No
Does your company have the following equipment in each Service Vehicle?
Electronic Hand-held leak detectorthat detects a wide range of refrigerants, such as CFC, HFC,HCFC and HFO refrigerants 1234yf and R32.
It is most important that Oxygen Free Nitrogen (OFN) is
continually purged through the pipework when welding
• Purged = 3-5psig above atmospheric pressure
During brazing process, the inside of the copper
produces “Carbon deposits”
Installation
• Pressure test with nitrogen to establish basic system seal
• Release pressure and connect vacuum pump
• System must hold a vacuum to at least 500 microns (equivalent to
99.9% vacuum)
• Always use a quality vacuum pump
• Check and change oil on a regular basis
• Check vacuum with Torr gauge or vacustat positioned as far from
vacuum pump as possible
Installation
Before Putting system into service the unit must undergo the following tests
Strength test
Leakage test
note: only use dry nitrogen
3.0 Bar - Minimum 3 min
15.0 Bar - Minimum 3 min
32.0 Bar - Minimum 3 min
41.5 Bar - Strength test for a period of time acceptable to show any signs of deformation of pipe work
33.0 Bar - Minimum 5 minutes
Installation (MRV)
0
10
20
30
40
50
60
-20 -10 0 10 20 30 40
evaporative temp
To
rr
In ambient conditions of 10°c moisture will not boil off until 10 Torr is achieved
0
10
20
30
40
50
60
-20 -10 0 10 20 30 40
evaporative temp
To
rr
Or below 500 micron with vacustat
Installation
Flexis Easy Installation
18
Time saved on Installation
With the help of 1. Improved mounting plate ,2. L-shaped Easy Support Clip design,3. Snap-in design 4. Left/right optional drainage pipe design,
Designed with easier installing in mind
Flexis Easy Maintenance
19
With the help of 5. External emergency button design,6. The pluggable computer board design 7. Easy & quick removal motor design
Easier maintenance.
Time saved on Maintenance
Flexis Easy Installation .
20
Advanced technology of mounting plate improvement to make AC easier installing.
Mounting Plate Improvement
Measurements and space for tape line on mounting plate, it is more convenient for quick positioning to save installation time.
It is easier to fix the tape.
21
Flexis L-shaped Easy Support Clip design
Advanced technology of L-shaped easy support clip, larger operating space expanded by 48% , easier pipe connection without auxiliary tools to support the machine.
2 L-shaped Easy Support Clip
It is more convenient for installation by extending space(nearly 168mm) with additional support clip.
Expanded 48%
22
Flexis Snap-in design
4.With the Snap-in design , remove pinch plate without screwdriver to make AC easier installing.
Snap-in design
Removing the Snap-On decoration plate will allow installers to easier connectpiping and wires.
Step2: pull down the slot with
finger
23
Flexis Left/right optional drainage pipe design
2-Way Drain Pipe Design
The indoor unit offers the possibility of left or right pipingdirection, easy for installation.
With 2-way piping design, there is no worry about the position where the AC is installed. You can change the drain pipe position by one screw
3.Advanced technology of 2-Way Drain, getting rid of some of the installation environment restrictions, to make AC easier installing.
24
Flexis the pluggable computer board design
Step 1: Open the fascia and remove the screw from the electrical cover.
Step 2:Remove the PCB through the panel
Quick & Easy Repair PCB
PCB removal and maintenance just 2 steps without disassembling evaporator.
Haier AC Installation Electrical
Choose your interconnecting cables carefully
1.5mm Orange Four Core or Flat Four Core TPS: Active and Comms wires side by side and twist creating magnetic interference down the CommsLine. ***Please do not use these cables***
Only use 2.5mm 3 Wire TPS and Separate 1.5mm Single 1.5mm Double Insulated Comms Wire
Secure your Outer Insulation
All units Interconnection Wiring
• All Haier A/C Wiring is the same for the interconnection at both indoor and outdoor units
• 1 = Neutral 2=Active (Live) 3= Comms 4= Earth
Haier AC Installation Electrical
27
Flexis easy &quick required motor design
6 Quick & Easy Repair Motor
Normal :9 Tedious stepsa. Pump system down. b. Release the connecting pipe
and remove the indoor unit.c. Open the panel and remove
the coverd. Remove electrical cabinet. e. Remove the evaporator. f. Disassemble the screw of fan
and motor. g. Remove the motor bracket. h. Take out the motor.
Motor removal just 5 steps without disassembling evaporator.
Step 1: Open the faccia and remove the cover
Step2: Disassemble the electrical box, remove the fixed screw of the motor and fan
Step3:Remove the 2 screws of the motor bracket.
Step4:Remove the two brackets on the right side of the motor.
Step 5: Remove the motor
Promotion 44%
F Series Serial Number and Model
Indoor under the Front cover, Outdoor the same as other models
Model & Serial Number locations
Technical Service Hints
F Series Indoor PCB ServiceAccess to PCB without removing outer cover of outdoor unit.Earth terminal screw on indoor coil.
Technical Install Hints
• The indoor unit is shipped from the factory with a small nitrogen
charge in it. The pressure will release when the transport caps
are removed from the flare connections.
• Both of the brass flare nuts for the indoor connections are in the
same packaging as the remote control.
• Remove the foam stripes around the blower wheel before
starting 5.3kW & 7.1kW indoor units.
• Follow the electrical connection labels. Haier terminal blocks are
labelled 1 Neutral, 2 Line, 3 Comms, and 4 Earth. You may be used to
seeing Line, Neutral, Comms, and Earth.
Technical Install Hints
• Flexis series the hole is already drilled out.
• Rubber feet for condensor are in packaging under
condenser.
• All models are DRED enabled. Connection cable is a
data cable with RJ45 connector and is accessible at
condensor terminal blocks.
Technical Install Hints
• All Flexis indoor PCBs are the same part number
for that series of product. The units capacity is set
via the Dip Switches
• F Series H0011800593B.
• SW2 on the PCB needs to be set to the correct
indoor capacity when changing from original part.
• First indication they are incorrectly set may be
reverse operation of the louvre or you may get a
communications fault (E7)
Indoor Dipswitch settings for 26 Indoor Dipswitch settings for 35
3 OFF 3 OFF
4 OFF 4 ON
Indoor Dipswitch settings for 53 Indoor Dipswitch settings for 71
3 ON 3 ON
4 OFF 4 ON
Technical Service Hints
• Cut only J2 on Flexis series units ,only when
replacing a faulty indoor PCB.
Display Bridges
Demand Response Control
DEMAND RESPONSE CONTROL (DRC)
For models fitted with Demand Response Control
Demand response Control provides a method by which a controlling authority, most likely a power supply company, can limit the amount of power that an air conditioner can consume in comparison to its nominal full load power consumption. The aim is to reduce overall power consumption to the supply network at critical peak load times. A command is passed down the power supply which triggers a response. Not dissimilar to what some power companies do when controlling peak demand for electric water heaters in some countries.
DRC is capable of demanding three different levels of response from the air conditioner, identified as DRM1, DRM2 and DRM3.DRM1 which is 'compressor off' is the minimum required to meet the Australian New Zealand standard AS4755.3.1.DRM2 must not exceed 50% of Capacity kWDRM3 must not exceed 75% of Capacity kW
If DRC is being used by your power supplier your product will show one of the three responses in the LED display as follows
d1: Indicates that your supplier has switched off your unit due to high power demand on the local net workd2: Indicates that your supplier has reduced the capacity of your unit to 50% due to high power demand on the local net workd3: Indicates that your supplier has reduced the capacity of your product to 75% due to high power demand on the local net work
Important please note if any one of the LED indicators shown above are displayed on your products LED display DO NOT call Haier Customer Service until you have checked with your power supplier to confirm if they have activated their DRC device.
DREDS device is connected to the RJ485 plug to control
If after conferring with your power supplier you believe your product requires service please call Haier Customer Service on New Zealand 0800 424 372
Product Identification
Serial Number
Louvres
F Series – Vertical and Horizontal Movement
Haier DAC Functions
Wi-Fi Functions
WiFi
Wi-Fi Functions
WiFi
Basic control and monitoring – Turn on/off, Mode, Setting temperature , Room temperature , Fan speed and Louver swing.
STATUS of AC –Turn on /Turn off
MODE –Auto Cool Heat Fan Dry
SETTING TEMP. –Operating range from 16-30℃/60-86℉
FAN SPEED–High Mid Low Auto
ROOM TEMP. –Display range from 0-55℃/32-130℉
Wi-Fi Functions
Wi-Fi
9. ECO - SENSOR
Two technologies 1. Follow and avoid2. Occupied/unoccupied.
Human Sensor Energy-saving Tech.
1. Forget to turn off the AC when no one is in the room, cause energy waste;2. Airflow directly to people when cooling, which is uncomfortable and may cause disease;3. Airflow may direct to no-people area, cause energy waist.
User’s
Point’s
Info1. Two-area Human Sensor Integrated module;2. Sensed angle – 120°3. Sensed distance – 5m4. Two sensed zones (1 & 2)
Benefits
for
Users:
Enables energy saving operations
when the room is unoccupied for 20
minutes:
Two-area sensor, avoid human when cooling
and direct to human when heating. More
comfortable & energy-saving
Heathy Airflow Mode
F Human Sensor Technologies——Angle: 140° within 2 meters(120° out of 2 meters);Distance should be 8 meters(5 meters tested)
Flexis Sensor
Self-clean
41
With regular use of self-clean technology, there is minimal need to clean the AC evaporator
Time saved on Cleaning
Self-clean
42
Self Clean (evaporator self-cleaning) is applicable for both NSV/NFV Series inverter models
Conclusion: Self Clean is the patent technology for Haier which can clean the evaporator.
This function can help end-user to save the cleaning cost with 99.9% anti-bacteria rate.
Pains of end-user
If cleaning .
If not cleaning .
It takes twice cleaning a year and cost
Major benefits to end-user
1) saving the cleaning fee
Bacterial, virus will spread into the airflow .
For reference: The cooling performance will reduce approximately by 10%~15% because of dirty evaporator .
3) Cooling performance not affected by dirty evaporator 2) Healthy air, 99.9% anti-bacteria rate
After periodic use, dust will be accumulated on the surface of evaporator, which is easily breeding bacteria and virus.
43
Self-clean
Press the Self Clean Button on remote controller
CL (short for clean) will display on the front panel
The evaporator will freeze After time the unit will cause ice to melt and wash away dirt covered on the surface of the evaporator
Whole process 21 Minutes
Self Clean Process
Bacteria killing at the same time
Nano silver anti-virus material on the surface of aluminum can effectively kill 99.9% bacteria and virus at the same time
Recommended Frequency
Recommend to use Self Clean once a week to keep evaporator clean
Note: During the Self Clean process, the unit stops cooling performance and the customer will not feel cold air blowing from the system.
Technical Functions
Emergency Button
Operation under emergency mode
Room temp Mode Set temp Fan mode
Higher than 23℃ Cooling 26℃ Auto
Lower than 23℃ Heating 23℃ Auto
1. When remote controller is lost, it is possible to use this button.2. Press the button, hear “Pi” sound, then the unit will start.3. In this condition, the unit will choose appropriate mode automatically
4. Press this button and hold down for 5 seconds, until hear two “Pi” “Pi” sound.5. In this condition, the unit running at cooling mode with high fan speed.6. Keep pressing the emergency button for 15 seconds and then release. There will
be “Pi” sound 3 times. The display on the indoor unit will then show the last error.
External emergency button run the machine without opening the
cover panel.
MRV S” 9kW Cooling / 10kW Heating
MRV S” 9kW Cooling 10kW Heating
High Wall Model AS302MNERA
Remote Control YR-HD
Wi-Fi
MRV S “ Outdoor Unit
MRV S” Outdoor / Indoor Electrical Connection
Power (240V) Connections
Control (P & Q) connections to indoor units
3=P4=Q
Power (240V) Connections
Outdoor Unit: Diagnostic PCB
Status LED
Manual function and mode selection switches
Connection for laptop analyzer
Start Up
1. Confirm the number of ID units, OD unit type, and supply voltage are correct
2. The compressor has a 5-minute delay feature
3. ID units cannot run in both cooling and heating at the same time
4. Automatic defrost usually lasts from 2-10 minutes; indoor fans slow or stop
5. Only operate the system within the prescribed temperature range
6. If the humidity exceeds 80%, the indoor units may blow moisture into the room
7. If the “restart” function is enabled, the system will resume the last state following a power failure
8. Add labels in the disconnect boxes to identify connected ID and OD units when multiple units are installed
Start Up
Looking for ID units Discovered ID units
Once indoor is found set BM1 to on
Questions?
53