Prepared For:Sanford LabAttn: Mike Johnson
Date: December 02, 2013
Sold To: Job Name:Sanford Lab - Lead - Preconditioning AHU
Trane U.S. Inc. dba Trane is pleased to provide the enclosed submittal for your review and approval.
Product Summary
Qty Product1 Performance Climate Changer
Matthew DavelaarTrane3500 S. First Ave.Suite 150Sioux Falls, SD 57105-5804Phone: (605) 336-8500Cell:Fax: (605) 336-0824
The attached information describes the equipment we propose tofurnish for this project, and is submitted for your approval.
Submittal
J:\JOBS\97\23318\4\Final Submittal.doc
Table Of Contents
Product Summary..................................................................................................................... 1
Performance Climate Changer (Item A1) ................................................................................. 3Tag Data .................................................................................................................................................. 3Product Data ............................................................................................................................................ 3Performance Data.................................................................................................................................... 5Mechanical Specifications........................................................................................................................ 8As-Built................................................................................................................................................... 12Fan Curve .............................................................................................................................................. 20Accessory .............................................................................................................................................. 23Field Wiring ............................................................................................................................................ 28
Field Installed Options - Part/Order Number Summary ........................................................ 29Performance Climate Changer............................................................................................................... 29
Sanford Lab - Lead - Preconditioning AHU December 02, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /Installed by Others
Equipment Submittal Page 3 of 29
Tag Data - Performance Climate Changer (Qty: 1)
Item Tag(s) Qty Description Model Number
A1 AHU-1 1 Performance Climate Changer ( CSAA ) CSAA014UA
Product Data - Performance Climate Changer
Item: A1 Qty: 1 Tag(s): AHU-1Unit level options
Indoor unitUnit size 14
2.5in. integral base frameUL listed unitMultiple composite handles/latches174 Unit length142.25 Second level lengthNo seismic certification required
Controls and VFD/starterUnwired end devices
WarrantyStandard warranty only
Pipe cabinet sectionNo pipe cabinet
Coil section (Pos #1)Horizontal coilMediumNo drain panRight side - coil supplyStandard panelsUnit coil heightHeating coilSingle use coilType "UW" coil6 rows143 fins per foot nominal fin spacingAluminum finsDelta flo H (Hi efficient).016" (0.406mm) copper tubes1/2in. tube diameter (12.7 mm)Galvanized steel coil casingTurbulators
Diffuser section (Pos #2)Diffuser section
Fan section (Pos #3)Fan sectionExhaust fanDoor- right side18in. diameter AF, M pressBack-top dischargeRight side driveNEMA premium compliant ODPVoltage 460/37.5 hp1800 RPMInverter balance with SGRNo conduitField provided VFD
Coil section (Pos #4)Horizontal coilMediumNo drain panRight side - coil supplyStandard panels
Sanford Lab - Lead - Preconditioning AHU December 02, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /Installed by Others
Equipment Submittal Page 4 of 29
Unit coil heightHeating coilSingle use coilType "5W" coil1 row121 fins per foot nominal fin spacingAluminum finsPrima flo H (Hi efficient).020" (0.508mm) copper tubes5/8in. tube diameter (15.875 mm)Stainless steel coil casing
Filter section (Pos #5)FilterAngled filterDoor- right side
Fan section (Pos #6)Fan sectionSupply fanDoor- right side18in. diameter AF, M pressFront-top dischargeRight side driveNEMA premium compliant ODPVoltage 460/35 hp1800 RPMInverter balance with SGRNo conduitField provided VFD
Diffuser section (Pos #7)Diffuser section
Coil section (Pos #8)Horizontal coilExtended mediumStainless steel drain panRight side - drain connectionRight side - coil supplyStandard panelsUnit coil heightCooling coilSingle use coilType "UW" coil6 rows147 fins per foot nominal fin spacingAluminum finsDelta flo H (Hi efficient).016" (0.406mm) copper tubes1/2in. tube diameter (12.7 mm)Stainless steel coil casingTurbulators
Wheel (Pos #9)CDQ wheelDual path application7000 nominal CFM wheelRegeneration air bypass damperVoltage 115/1Right side driveDoors - right sideStarter
Access section (Pos #10)Access/blank/turning sectionMedium
Sanford Lab - Lead - Preconditioning AHU December 02, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /Installed by Others
Equipment Submittal Page 5 of 29
Performance Data - Performance Climate Changer
Tags AHU-1
Unit level options
Position
Length (in) 174.000
Width (in) 72.000
Rigging weight (lb) 4387.4
Installed weight (lb) 4552.9
Roof curb weight (lb) 0.0
Actual airflow (cfm) 4650
Unit elevation (ft) 0.00
Shipping split 1 weight (lb) 540.8
Shipping split 2 weight (lb) 803.0
Shipping split 3 weight (lb) 220.8
Shipping split 4 weight (lb) 257.2
Shipping split 5 weight (lb) 863.0
Shipping split 6 weight (lb) 468.3
Shipping split 7 weight (lb) 1294.8
Shipping split 8 weight (lb) 105.0Diffuser section
Position #2 #7
Section length (in) 14.000 14.000
Section weight (lb) 102.0 102.0
Diffuser airflow (cfm) 7168 4818
Diffuser area (sq ft) 4.32 4.32
Diffuser pressure drop (in H2O) 0.127 0.057Fan section
Position #3 #6
Section length (in) 42.500 42.500
Section weight (lb) 803.0 761.0
Fan airflow (cfm) 7168 4818
Elevation (ft) 0.00 0.00
Overall ESP (in H2O) 1.000 1.500
Total static pressure (in H2O) 3.438 3.138
Fan discharge loss pressure drop (in H2O) 0.000 0.000
Fan pressure drop (in H2O) 1.000 1.500
Fan outlet velocity (ft/min) 2486 1671
Speed (rpm) 1933 1658
Total brake horsepower (hp) 6.456 3.750
Unit static efficiency (%) 60.05 63.44
Outlet area (sq ft) 2.88 2.88
Motor hertz (Hz) 60 60Access section
Position #10
Section length (in) 14.000
Section weight (lb) 105.0Coil section
Position #1 #4 #8
Section length (in) 14.000 14.000 19.000
Section weight (lb) 438.8 220.8 468.3
Coil performance airflow (cfm) 7168 7000 4818
Unit airflow (cfm) 7168 7000 4818
Coil face area (sq ft) 13.65 12.50 13.65
Coil face velocity (ft/min) 525 560 353
Air pressure drop (in H2O) 0.686 0.128 0.526
Coil section pressure drop (in H2O) 0.686 0.128 0.526
Coil rigging weight (lb) 231.5 68.1 232.8
Sanford Lab - Lead - Preconditioning AHU December 02, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /Installed by Others
Equipment Submittal Page 6 of 29
Tags AHU-1
Coil installed weight (lb) 304.8 86.8 306.3
Top or single coil dry weight (lb) 231.5 68.1 232.8
Leaving dry bulb (F) 123.72 85.00 49.00
Leaving wet bulb (F) - - 48.90
Entering dry bulb (F) 85.00 70.00 70.00
Entering wet bulb (F) - - 69.40
Fluid type Water Water Water
Coil fluid percentage (%) 100.00 100.00 100.00
Entering fluid temperature (F) 130.00 130.00 42.00
Leaving fluid temperature (F) 115.00 115.00 56.00
Fluid temperature rise (F) - - 14.00
Fluid temperature drop (F) 15.00 15.00 -
Standard fluid flow rate (gpm) 40.22 15.22 42.65
Fluid pressure drop (ft H2O) 9.56 0.78 12.18
Fluid velocity (ft/s) 2.76 1.68 2.93
Fluid volume (gal) 8.79 2.25 8.79
Sensible capacity (MBh) - - 112.37
Total capacity (MBh) 301.00 113.87 299.65Filter section
Position #5
Section length (in) 26.500
Section weight (lb) 257.2
Filter airflow (cfm) 4818
Filter area (sq ft) 18.06
Filter condition Mid-life
Filter pressure drop (in H2O) 0.562
Filter section pressure drop (in H2O) 0.562
Filter face velocity (ft/min) 267Wheel
Position #9
Section length (in) 57.500
Section weight (lb) 1294.8
Leaving supply airflow (cfm) 4650
Regeneration airflow (cfm) 7000
Mixed regeneration airflow (cfm) 7168
Cross Leakage Airflow (cfm) 168
Supply air wheel PD (in H2O) 0.493
Greatest wheel exhaust PD (in H2O) 0.000
Regeneration air wheel PD (in H2O) 0.854
Max supply level module PD (in H2O) 0.493
Max exhaust module PD (in H2O) 1.497
Max regeneration air module PD (in H2O) 1.497
Regeneration air bypass damper area (sq ft) 3.05
Entering regeneration ESP (in H2O) 0.500
Leaving supply ESP (in H2O) 0.500
Mixed regeneration air DB (F) 84.16
Mixed regeneration air RH (%) 60.60
Regeneration LDB (F) 85.00
Regeneration EDB (F) 85.00
Regeneration leaving RH (%) 59.70
Regeneration entering RH (%) 59.70
Regeneration leaving HR (gr/lb) 108
Leaving supply air DB (F) 56.83
Leaving supply air RH (%) 59.93
Leaving supply air HR (gr/lb) 41
Filter area (sq ft) 14.44
Sanford Lab - Lead - Preconditioning AHU December 02, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /Installed by Others
Equipment Submittal Page 7 of 29
Tags AHU-1
Filter condition Mid-life
Filter pressure drop (in H2O) 0.643
Total filter pressure drop (in H2O) 0.643
Filter face velocity (ft/min) 485
Sensible energy saved - CDQ (MBh) 0.00
Sanford Lab - Lead - Preconditioning AHU December 02, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /Installed by Others
Equipment Submittal Page 8 of 29
Mechanical Specifications - Performance Climate ChangerItem: A1 Qty: 1 Tag(s): AHU-1
GENERAL
Lifting InstructionsThe air handling units must be rigged, lifted, and installed in strict accordance with the Installation, Operation, andMaintenance manual (CLCH-SVX07B-EN). The units are also to be installed in strict accordance with the specifications.Units may be shipped fully assembled or disassembled to the minimum functional section size in accordance withshipping and job site requirements.
Indoor units shall be shipped on an integral base frame (variable from the standard 2.5" to 8" height) for the purpose ofmounting units to a housekeeping pad and providing additional height to properly trap condensate from the unit. Theintegral base frame may be used for ceiling suspension, external isolation, or as a housekeeping pad. Indoor sizes 3 to30 will also be shipped with a shipping skid designed for forklift transport. Refer to the unit As-Built or Product Datasection of the submittal for the base frame height of each unit.
All units will be shipped with an integral base frame designed with the necessary number of lift points for safeinstallation. All lifting lugs are to be utilized during lift. The lift points will be designed to accept standard rigging devicesand be removable after installation. Units shipped in sections will have a minimum of four points of lift.
Per ASHRAE 62.1 recommendation, indoor air handling units will be shipped stretch-wrapped to protect unit fromin-transit rain and debris.
Installing contractor is responsible for long term storage in accordance with the Installation, Operation, and Maintenancemanual (CLCH-SVX07B-EN).
Unit shall be UL and C-UL Listed.
Air-handling performance data shall be certified in accordance with AHRI Standard 430.
Unit sound performance data shall be provided using AHRI Standard 260 test methods and reported as sound power.Trane, in providing this program and data, does not certify or warrant NC levels. These levels are affected by factorsspecific to each application and/or installation and therefore unable to be predicted or certified by Trane.
Unit Construction
All unit panels shall be 2" solid, double-wall construction to facilitate cleaning of unit interior. Unit panels shall beprovided with a mid-span, no-through-metal, internal thermal break. Casing thermal performance shall be such thatunder 55°F supply air temperature and design conditions on the exterior of the unit of 81°F dry bulb and 73°F wet bulb,condensation shall not form on the casing exterior.
All exterior and interior indoor AHU panels will be made of galvanized steel.
Unit Paint
Unit to ship unpainted from factory. Unit to be painted by 3rd party finisher, or by painting contractor at job site.
Casing DeflectionThe casing shall not exceed 0.0042 inch deflection per inch of panel span at 8 inch static pressure. Total maximumstatic shall not exceed +8 inches w.g. in all positive pressure sections and -8 inches w.g. in all negative pressuresections.
Floor ConstructionThe unit floor shall be of sufficient strength to support a 300.0 lb load during maintenance activities and shall deflect nomore than 0.0042 inch per inch of panel span.
InsulationPanel insulation shall provide a minimum thermal resistance (R) value of 13 ft²-h-ºF/Btu throughout the entire unit.Insulation shall completely fill the panel cavities in all directions so that no voids exist and settling of insulation isprevented. Panel insulation shall comply with NFPA 90A.
Drain Pan
Sanford Lab - Lead - Preconditioning AHU December 02, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /Installed by Others
Equipment Submittal Page 9 of 29
All cooling coil sections shall be provided with an insulated, double-wall, galvanized or stainless steel drain pan. Toaddress indoor air quality (IAQ), the drain pan shall be designed in accordance with ASHRAE 62.1 being of sufficientsize to collect all condensation produced from the coil and sloped in two planes promoting positive drainage to eliminatestagnant water conditions. The outlet shall be located at the lowest point of the pan and shall be sufficient diameter topreclude drain pan overflow under any normally expected operating condition. All drain pan threaded connections shallbe visible external to the unit. Drain connections shall be of the same material as the primary drain pan and shall extenda minimum of 2-1/2" beyond the base to ensure adequate room for field piping of condensate drain traps.Refer to Product Data for specific information on which sections are supplied with a drain pan, the drain pan materialand connection location.
FILTER SECTIONA section shall be provided to support the filter rack as indicated throughout the unit. Refer to Product Data and As-Builtsections of the submittal for specific locations within each unit.
Primary Filters
2-inch pleated media filters made with 100% synthetic fibers that are continuously laminated to a supported steel-wiregrid with water repellent adhesive shall be provided. Filters shall be capable of operating up to 625 fpm face velocitywithout loss of filter efficiency and holding capacity. The filters shall have a MERV 8 rating when tested in accordancewith the ANSI/ASHRAE Standard 52.2.
COIL SECTIONThe coil section shall be provided complete with coil and coil holding frame. The coils shall be installed such thatheaders and return bends are enclosed by unit casings. If two or more cooling coils are stacked in the unit, anintermediate drain pan shall be installed between each coil and be of the same material as the primary drain pan. Likethe primary drain pan, the intermediate drain pan shall be designed being of sufficient size to collect all condensationproduced from the coil and sloped to promote positive drainage to eliminate stagnant water conditions. Theintermediate pan shall begin at the leading face of the water-producing device and be of sufficient length extendingdownstream to prevent condensate from passing through the air stream of the lower coil. Intermediate drain pan shallinclude downspouts to direct condensate to the primary drain pan. The outlet shall be located at the lowest point of thepan and shall be sufficient diameter to preclude drain pan overflow under any normally expected operating condition.
Hydronic coils shall be supplied with factory installed drain and vent piping to unit casing exterior. Piping is to facilitatefield installation of automatic venting or drain valves on coils, which are not supplied with unit. Refer to the Product Datasection of the submittal for the units and/or coils supplied with drain and vent piping.
No casing penetrations supplied for hydronic drain and vents. If required, piping contractor will need to drill drain andvent penetrations using factory located features provided in coil panel.
Water Coils (UW, UU, UA, W, 5W, 5A, WD, 5D, D1, D2, P, or TT)The coils shall have aluminum fins and seamless copper tubes. Copper fins may be applied to coils with 5/8-inch tubes.Fins shall have collars drawn, belled, and firmly bonded to tubes by mechanical expansion of the tubes. The coil casingmay be galvanized or stainless steel. Refer to the Product Data section of the submittal for the coil casing material.The coils shall be proof-tested to 300 psig and leak-tested under water to 200 psig. Coils containing water or ethyleneglycol are certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils CertificationProgram which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of theStandard. Certified units may be found in the AHRI Directory at www.ahridirectory.org. Propylene glycol and calciumchloride, or mixtures thereof, are outside the scope of AHRI Standard 410 and, therefore, do not require AHRI 410 ratingor certification.
Coil header connections are constructed of cast iron with female connections, steel block with female connections orsteel pipe with male connections.
Tubes are 1/2" [13mm] OD 0.016" [0.406mm] thick copper.
Tubes are 5/8" [16mm] OD 0.020" [0.508 mm] thick copper.
ACCESS/INSPECTION / TURNING SECTIONA section shall be provided to allow additional access/inspection of unit components and space for field-installedcomponents as needed. An access door shall be provided for easy access. All access sections shall be complete witha double-wall, removable door downstream for inspection, cleaning, and maintenance. Interior and exterior door panels
Sanford Lab - Lead - Preconditioning AHU December 02, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /Installed by Others
Equipment Submittal Page 10 of 29
shall be of the same construction as the interior and exterior wall panels, respectively. All doors downstream of coolingcoils shall be provided with a thermal break construction of door panel and door frame.
Fans that are selected with inverter balancing shall first be dynamically balanced at design RPM. The fans then will bechecked in the factory from 25% to 100% of design RPM to insure they are operating within vibration tolerancespecifications, and that there are no resonant frequency issues throughout this operating range. Inverter balancing thatrequires lockout frequencies inputted into a variable frequency drive to in order to bypass resonant frequencies shall notbe acceptable. If supplied in this manner by the unit manufacturer, the contractor will be responsible for rebalancing inthe field after unit installation. Fans selected with inverter balancing shall have a maintenance free, circumferentialconductive micro fiber shaft grounding ring installed on the fan motor to discharge shaft currents to ground.
AF FAN SECTIONThe fan type shall be provided as required for stable operation and optimum energy efficiency. The fan shall be adouble-width, double-inlet, multiblade-type, airfoil (AF) fan. The fan shall be equipped with self-aligning, antifrictionbearings with an L-50 life of 200,000 hours, as calculated per ANSI/AFBMA Standard 9. For any bearing requiringrelubrication, the grease line shall be extended to the fan support bracket on the drive side. The fan shall be staticallyand dynamically balanced at the factory as a complete fan assembly (fan wheel, motor, drive, and belts). The fan shaftshall not exceed 75 percent of its first critical speed at any cataloged speed. Fan wheels shall be keyed to the fan shaftto prevent slipping. The fan shafts shall be solid steel. The fan section shall be provided with an access door on the driveside of the fan. Fan performance shall be certified as complying with AHRI Standard 430.
Drive Service Factor
The drives shall be constant speed with fixed-pitch sheaves. The drives shall be selected at a minimum 50 percentlarger than the motor brake horsepower (1.5 service factor).
Motor FrameThe motor shall be mounted integral to the isolated fan assembly and furnished by the unit manufacturer. The motor ismounted inside the unit casing on an adjustable base to permit adjustment of drive belt tension (not applicable for directdrive plenum fans). The motor shall meet or exceed all NEMA Standards Publication MG 1 requirements and complywith NEMA Premium efficiency levels when applicable except for fractional horsepower motors which are not coveredby the NEMA classification. The motor shall be T-frame, squirrel cage with size, type, and electrical characteristics asshown on the equipment schedule. Refer to the Product Data section for selected fan motors within each unit.
Two-Inch Spring IsolatorsThe fan and motor assembly (on sizes 10 to 120) shall be internally isolated from the unit casing with 2-inch (50.8 mm)deflection spring isolators, furnished and installed by the unit manufacturer. The isolation system shall be designed toresist loads produced by external forces, such as earthquakes, and conform to the current IBC seismic requirements.
DIFFUSER SECTIONA diffuser section shall be provided immediately downstream of the fan section. The diffuser shall provide equal airdistribution to blow-thru components immediately downstream of the diffuser. Diffusers attached directly to the fandischarge are not acceptable.
Field Wired Control SystemFactory-mounted direct-digital control (DDC) control points shall be engineered, and mounted by the air handlermanufacturer to reduce installed costs, improve reliability, and save time at unit startup. The control points as selectedby section will require field wiring at the job site. Review unit submittal drawings to verify there is sufficient space foraccess to control points for field wiring. All factory-mounted controls points shall be covered by the air handlermanufacturer's standard warranty.
COOL DRY QUIET (CDQ(TM)) DESICCANT WHEEL SECTIONThe air handling unit shall be provided with a CDQ desiccant wheel to control space humidity based on the specifiedrequirements. The wheel media shall meet the flammability requirements governing this class of products and shall be aUL-recognized component in accordance with UL 1812 and UL1995. The CDQ desiccant wheel speed is not modulatedfor temperature control nor recommended. The CDQ wheel is for humidity control and should be turned off during winterheating. Supply temperature is controlled by the cooling coil or a reheat coil.
Wheel ConstructionThe CDQ desiccant wheel shall be constructed of a synthetic matrix with a type III desiccant. The wheel shall bestructurally reinforced with a spoke system to minimize wheel deflection. All diameter and perimeter seals shall beprovided as part of the cassette assembly. The drive system shall consist of a heavy-duty fractional horsepower A/Cgear motor mounted in the cassette.
Sanford Lab - Lead - Preconditioning AHU December 02, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /Installed by Others
Equipment Submittal Page 11 of 29
CDQ Wheel Drive SystemThe motor shall have permanently lubricated bearings. The bearings, which support rotation of the wheel around acenter shaft, shall be provided with grease fittings for periodic lubrication.
Maintenance and Access DoorsThe wheel matrix shall be cleanable. The desiccant shall not dissolve in the presence of water or high humidity. Accessdoors shall be provided immediately upstream and downstream of the CDQ wheel cassette. Adequate space shall beprovided for cleaning, service, and maintenance of the wheel, motor, bearing, and belt.
Primary Filters
2 inch pleated media filters made with 100% synthetic fibers that are continuously laminated to a supportedsteel wire grid with water repellent adhesive shall be provided. Filters shall be capable of operating up to 625fpm face velocity without loss of filter efficiency and holding capacity. The filters shall have a MERV 8 ratingwhen tested in accordance with the ANSI/ASHRAE Standard 52.2.
Sanford Lab - Lead - Preconditioning AHU December 02, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /Installed by Others
Equipment Submittal Page 12 of 29
As-Built - Performance Climate ChangerItem: A1 Qty: 1 Tag(s): AHU-1
Sanford Lab - Lead - Preconditioning AHU December 02, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /Installed by Others
Equipment Submittal Page 13 of 29
As-Built - Performance Climate ChangerItem: A1 Qty: 1 Tag(s): AHU-1
Sanford Lab - Lead - Preconditioning AHU December 02, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /Installed by Others
Equipment Submittal Page 14 of 29
As-Built - Performance Climate ChangerItem: A1 Qty: 1 Tag(s): AHU-1
OPENING AND DIMENSIONS MAY VARY FROM CONTRACT DOCUMENTS / RETURN OF APPROVED DRAWINGS CONSTITUTES ACCEPTANCE OF THESE VARIANCES / NOT TO SCALE
Unit size: 14
Product group: Indoor unitIntegral base frame: 2.5in. integral base frame
Paint: Unpainted/field painted outdoor
Job Name:Actual airflow: 4650 cfmSales Office:
Unit Casing: 2in Double Wall
Proposal Number:
Rigging/Installed Weight: 4387.4 lb/ 4552.9 lb
Performance Climate ChangerAir Handlers
Pos #12345678910
ModuleCoil sectionDiffuser sectionFan sectionCoil sectionFilter sectionFan sectionDiffuser sectionCoil sectionWheelAccess section
Length141442 1/21426 1/242 1/2141957 1/214
Weight438.80102.00803.00220.80257.20761.00102.00468.301294.80105.00
Installed Unit Weight 4552.90 lbs
1234 59
72
Basic Overall Plan View: Top - Measurements in inches
S1S2S3
S4S5S6
S7
S8
2 1/2
2 1/2
1234
5678
9
10
174 1/8
83
1/4
Overall Elevation View: Right - Shipping splits indicated by bold outline. - Measurements in inches
For maneuvering purposes, include 1.125 inches to each ship split length for overlapping panel flange. Flange will not add to overall installed unit length shown.
Sanford Lab - Lead - Preconditioning AHU December 02, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /Installed by Others
Equipment Submittal Page 15 of 29
As-Built - Performance Climate ChangerItem: A1 Qty: 1 Tag(s): AHU-1
OPENING AND DIMENSIONS MAY VARY FROM CONTRACT DOCUMENTS / RETURN OF APPROVED DRAWINGS CONSTITUTES ACCEPTANCE OF THESE VARIANCES / NOT TO SCALE
Unit size: 14
Product group: Indoor unitIntegral base frame: 2.5in. integral base frame
Paint: Unpainted/field painted outdoor
Job Name:Actual airflow: 4650 cfmSales Office:
Unit Casing: 2in Double Wall
Proposal Number:
Rigging/Installed Weight: 4387.4 lb/ 4552.9 lb
Performance Climate ChangerAir Handlers
1234 59
30 1/217 3/4
11
1/2
141442 1/2
14 26 1/2
42 1/2141957 1/2
1.378 dia elec con(NEMA)
25/8
6
5 5/8
72
Right Side of Unit Detailed Plan View: Top - Measurements in inches
5678910
1414
42 1/214 26 1/2
42 1/21419
57 1/2
Left Side of Unit Detailed Plan View: Bottom - Measurements in inches
Sanford Lab - Lead - Preconditioning AHU December 02, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /Installed by Others
Equipment Submittal Page 16 of 29
As-Built - Performance Climate ChangerItem: A1 Qty: 1 Tag(s): AHU-1
OPENING AND DIMENSIONS MAY VARY FROM CONTRACT DOCUMENTS / RETURN OF APPROVED DRAWINGS CONSTITUTES ACCEPTANCE OF THESE VARIANCES / NOT TO SCALE
Unit size: 14
Product group: Indoor unitIntegral base frame: 2.5in. integral base frame
Paint: Unpainted/field painted outdoor
Job Name:Actual airflow: 4650 cfmSales Office:
Unit Casing: 2in Double Wall
Proposal Number:
Rigging/Installed Weight: 4387.4 lb/ 4552.9 lb
Performance Climate ChangerAir Handlers
1 2 3 4
5 6 7 8
9
10
1414
42 1/2 1426 1/2
42 1/214 19
57 1/22 1/2
2 1/2
41
1/2
Detailed Elevation View: Left - Measurements in inches
2 1/2 33
/8
4 1/44 1/4 4 1/4
19
2 1/2 4 1/4
34
3/4
34
3/4
14
1/4
76
1/2
76
1/2
1234
5678
9
10
3 1/8 2 1/822 1/89 1/2
17 3/42
40 5/8
17"
22"17"
11
1/2
15"
15"
1" N.P.T.E
174 1/8
83
1/4
Detailed Elevation View: Right - Measurements in inches
Sanford Lab - Lead - Preconditioning AHU December 02, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /Installed by Others
Equipment Submittal Page 17 of 29
As-Built - Performance Climate ChangerItem: A1 Qty: 1 Tag(s): AHU-1
OPENING AND DIMENSIONS MAY VARY FROM CONTRACT DOCUMENTS / RETURN OF APPROVED DRAWINGS CONSTITUTES ACCEPTANCE OF THESE VARIANCES / NOT TO SCALE
Unit size: 14
Product group: Indoor unitIntegral base frame: 2.5in. integral base frame
Paint: Unpainted/field painted outdoor
Job Name:Actual airflow: 4650 cfmSales Office:
Unit Casing: 2in Double Wall
Proposal Number:
Rigging/Installed Weight: 4387.4 lb/ 4552.9 lb
Performance Climate ChangerAir Handlers
1
5
68
68
35
35
22
72
2 1/24 1/2
2 1/24 1/2
41
1/2
Detailed Elevation View: Back - Measurements in inches
83
1/4
4
10
2 1/2
2 1/2
Detailed Elevation View: Front - Measurements in inches
Sanford Lab - Lead - Preconditioning AHU December 02, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /Installed by Others
Equipment Submittal Page 18 of 29
As-Built - Performance Climate ChangerItem: A1 Qty: 1 Tag(s): AHU-1
Sanford Lab - Lead - Preconditioning AHU December 02, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /Installed by Others
Equipment Submittal Page 19 of 29
As-Built - Performance Climate ChangerItem: A1 Qty: 1 Tag(s): AHU-1
Sanford Lab - Lead - Preconditioning AHU December 02, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /Installed by Others
Equipment Submittal Page 20 of 29
Fan Curve - Performance Climate ChangerItem: A1 Qty: 1 Tag(s): AHU-1
Overall Unit Acoustics
63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Discharge 86 72 67 64 58 60 56 50Casing 85 81 68 76 72 53 39 32
Ducted Inlet 94 89 79 79 72 70 67 59
Sanford Lab - Lead - Preconditioning AHU December 02, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /Installed by Others
Equipment Submittal Page 21 of 29
Fan Curve - Performance Climate ChangerItem: A1 Qty: 1 Tag(s): AHU-1
5.0
0h
p
7.5
0h
p
10
.00
hp
15
.0
0h
p
1000 RPM
1200 RPM
1400 RPM
1600 RPM
1800 RPM
2000 RPM
2200 RPM
2400 RPM
2450 RPM
45 %WO
50 %WO
60 %WO
70 %WO
80 %WO
90 %WO
BHP adjusted 5% for approximate drive lossUnitSize: 18AA
Motor Frequency: 60.00HzOperating Airflow: 7168.00 cfm
Operating Static Pressure: 3.44 in H2OOperating RPM: 1933.00
Operating Brake Power: 6.46 hpAltitude: 0.00 ft
Design Temp: 70.00 FMax BHP: 6.84 hpEfficiency: 60.05 %
Date: 12/2/13Datafile: C:\Program Files\Trane Company\TOPSS\CSAA\Csaa_fans.ran
3536
0
1
2
3
4
5
6
7
8
9
0 2500 5000 7500 10000 12500 15000
ExhaustSize 14Horizontal Draw-Thru 18inchAF MPress - Single Fan
To
tal
Sta
tic
Pre
ss
ur
e(
inH
2O
)
Airflow(cfm)
Size 14Horizontal Draw-Thru 18inchAF MPress
63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Discharge 87 74 72 73 69 69 67 60Inlet + Casing 90 87 77 77 70 68 63 55
Casing 81 79 67 76 72 53 38 31DuctedInlet 90 86 77 77 70 68 63 55
Sanford Lab - Lead - Preconditioning AHU December 02, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /Installed by Others
Equipment Submittal Page 22 of 29
Fan Curve - Performance Climate ChangerItem: A1 Qty: 1 Tag(s): AHU-1
5.0
0h
p
7.5
0h
p
10
.0
0h
p
15
.00
hp
1000 RPM
1200 RPM
1400 RPM
1600 RPM
1800 RPM
2000 RPM
2200 RPM
2400 RPM
2450 RPM
45 %WO
50 %WO
60 %WO
70 %WO
80 %WO
90 %WO
BHP adjusted 5% for approximate drive lossUnitSize: 18AA
Motor Frequency: 60.00HzOperating Airflow: 4818.00 cfm
Operating Static Pressure: 3.14 in H2OOperating RPM: 1658.00
Operating Brake Power: 3.75 hpAltitude: 0.00 ft
Design Temp: 70.00 FMax BHP: 3.98 hpEfficiency: 63.44 %
Date: 12/2/13Datafile: C:\Program Files\Trane Company\TOPSS\CSAA\Csaa_fans.ran
3536
0
1
2
3
4
5
6
7
8
9
0 2500 5000 7500 10000 12500 15000
SupplySize 14Horizontal Draw-Thru 18inchAF MPress - Single Fan
To
tal
Sta
tic
Pre
ss
ur
e(
inH
2O
)
Airflow(cfm)
Size 14Horizontal Draw-Thru 18inchAF MPress
63Hz 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz
Discharge 86 72 67 64 58 60 56 50Inlet + Casing 94 88 77 76 69 66 66 58
Casing 83 78 64 70 66 47 35 26Ducted Inlet 93 87 76 76 69 66 66 58
Sanford Lab - Lead - Preconditioning AHU December 02, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /Installed by Others
Equipment Submittal Page 23 of 29
Accessory - Performance Climate ChangerItem: A1 Qty: 1 Tag(s): AHU-1
Base Detail
2 1/2"
Sanford Lab - Lead - Preconditioning AHU December 02, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /Installed by Others
Equipment Submittal Page 24 of 29
Accessory - Performance Climate ChangerItem: A1 Qty: 1 Tag(s): AHU-1
D(I
nte
rnal
6 48
59
61
A(f
ilter,
gas
heat)
Cle
ara
nce
item
s
VF
D-
show
n)
B(c
oil,
hum
idifi
er)
D(E
xte
rnal
Sta
rter
or
C(U
VLig
hts
)
483
484
48
61
59
61
8 48
10
48
12
48
66
61
77
82
61
61
17
48
14
48
21
48
87
61
87
61
95
64
66
52
156
64
48
128
25
48
30
48
35
48
95
109
64
64
11
5
64
40
50
48
57
48
141
64
64
141
64
80
56
100
58
120
58
156
64
170
197
64
64
48
89
48
56
ExtV
estible
)
IntV
estib
le)
F(G
as
Heat
Sta
rter
or
E(f
an)
F(G
as
Heat
VF
D)
48
N/A
48
48
48
N/A
N/A
N/A
100
48
48 90
48
51
48
54
108
63
74
79
48
105
61
48
58
10
0
48
60
115
84
84
92
48
170
93
15
3
140
125
48
66
48
66
115
118
48
66
136
92
106
112
48
70
48
77
156
48
77
156
138
138
N/A
48 93
179
48
101
48
101
180
153
167
194
VF
D
59
C(T
CA
C)
43
59
63
75
81
83
83
58
83
58
83
75
83
83
83
83
75
83
52
56
58
58
57
48
110
64
48
66
N/A
N/A83
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
50
48
110
64
48
66
N/A
N/A83
48
48
96
40 64
N/A
N/A
48 60
8348
48
9635 64
N/A
N/A48
60
59
48
30
48
87
64
48
58
N/A
N/A83
48
25
48
77
64
48 51
N/A
N/A75
48
21
48
77
64
48
51
N/A
N/A
75
48
TA
LL
TA
LL
TA
LL
TA
LL
TA
LL
TA
LL
TA
LL
Ga
sh
ea
t
Acce
ss
do
or
F
E
Filt
er
mix
ing
box
Note
:A
ta
min
imum
,th
ebelo
wcl
eara
nce
dim
ensi
ons
are
reco
mm
end
ed
on
one
sid
eofth
eunit
for
regula
rserv
ice
an
dm
ain
ten
ance.
Refe
rto
as-
built
subm
itta
lfo
rlo
cations
of
item
ssu
chas
filte
raccess
doors
,coil,
pip
ing
connectio
ns,
moto
rlo
catio
ns,etc
.S
uffic
ien
tcl
eara
nce
mu
stb
ep
rovid
ed
on
all
sid
es
of
unit
for
rem
ovalo
fpane
lsor
sect
ion-t
o-s
ect
ion
atta
chm
ent.
Cle
ara
nce
for
sta
rters
,V
FD
s,or
oth
er
hig
h-v
oltage
de
vice
sm
ust
be
pro
vid
ed
pe
rN
EC
require
ments
.
D
CB
A
Coil
UV
Lig
hts
or
TC
AC
Fa
n
EX
AM
PL
EU
NIT
-N
OT
CO
NF
IGU
RE
DA
SS
ELE
CT
ED
.
Sanford Lab - Lead - Preconditioning AHU December 02, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /Installed by Others
Equipment Submittal Page 25 of 29
Accessory - Performance Climate ChangerItem: A1 Qty: 1 Tag(s): AHU-1
2B
1B
OF
F
AT
TA
CH
EA
RT
HG
RO
UN
D
L1
L2
W10
9A
,B
14A
10B
13A
11A
1S
10
1K
40
1K
40
1K
40
1T
B1
3-4
1T
B13
-31
OL
1K
40
1T
B13
-1
1T
B13
-2
9A
9B
12
A
AU
TO
HA
ND
W11
1C
B11
1A
,B
2A
,B
1O
L
1O
L
1O
L
2A
1A
T1
T2
1P
7-3
1J7-3
1P
7-2
1J7-2
1P
7-1
1J7-1
GR
D
WH
T
BLK
GR
N
1K
38
TO
CO
OL
DR
Y
QU
IET
MO
TO
RC
US
TO
ME
RS
UP
PL
IED
PO
WE
R
NO
TE
(S):
1
DA
SH
ED
LIN
ES
IND
ICA
TE
RE
CO
MM
EN
DE
DF
IELD
WIR
ING
BY
OT
HE
RS
.
PH
AN
TO
MLIN
ES
IND
ICA
TE
CO
NT
RO
LO
PT
ION
.R
EF
.C
ON
TR
OL
PA
NE
LS
CH
EM
AT
ICF
OR
SP
EC
IFIC
DE
TA
IL.
2
ALL
FIE
LD
WIR
ING
MU
ST
BE
INA
CC
OR
DA
NC
EW
ITH
TH
EN
AT
ION
AL
ELE
CT
ICA
LC
OD
E,S
TA
TE
,A
ND
LO
CA
LR
EQ
UIR
EM
EN
TS
.O
TH
ER
CO
UN
TR
IES
AP
PL
ICA
BLE
NA
TIO
NA
LA
ND
/OR
LO
CA
LR
EQ
UIR
EM
EN
TS
SH
ALL
AP
PL
Y.
FIE
LD
CO
ND
UC
TO
RS
SH
ALL
HA
VE
INS
ULA
TIO
N
RA
TIN
GN
OT
LE
SS
TH
AN
60
0V
CO
PP
ER
CO
ND
UC
TO
RS
ON
LY
.
3
MIN
IMU
MC
IRC
UIT
AM
PA
CIT
Y,
MA
XIM
UM
FU
SE
SIZ
E,A
ND
DIS
CO
NN
EC
T
SIZ
EA
RE
CA
LC
ULA
TE
DB
AS
ED
ON
TH
EIN
VE
RT
ER
INP
UT
LIN
E
CU
RR
EN
TS
PE
RA
RT
ICLE
430-2
OF
TH
EN
AT
ION
AL
EL
EC
TR
ICA
L
CO
DE
.
6
CLO
SE
ST
OR
UN
AU
TO
MO
DE
OR
BY
PA
SS
AU
TO
FO
RO
PT
ION
VF
DO
R
ST
AR
TE
R.
9
RE
MO
VE
JUM
PE
RA
ND
INS
TA
LL
FIE
LD
SA
FE
TY
CO
NT
AC
T.
10 F
IEL
DS
UP
PLIE
DC
ON
TA
CT
S.
16 O
VE
RL
OA
DR
ELA
YT
RIP
SE
TT
ING
MU
ST
BE
AD
JUS
TE
DT
O
CO
RR
ES
PO
ND
WIT
HT
HE
MO
TO
RF
ULL
LO
AD
CU
RR
EN
TA
SS
HO
WN
ON
TH
EM
OT
OR
NA
ME
PLA
TE
.
27 A
TT
AC
HG
RO
UN
DO
RE
QU
IPM
EN
TG
RO
UN
D.C
ON
TA
CT
AU
XIL
LA
RY
TE
RM
INA
LS
TR
IPC
ON
TR
OL
CIR
CU
IT
HA
ND
/OF
F/A
UT
OS
WIT
CH
OV
ER
LO
AD
RE
LA
Y
ST
AR
TE
RC
ON
TA
CT
OR
ST
AR
T/S
TO
PR
ELA
Y
CIR
CU
ITB
RE
AK
ER
1T
B13
1S
10
1O
L
DE
VIC
E
DE
SIG
NA
TIO
N
1K
40
1K
38
1C
B11
DE
SC
RIP
TIO
N
LE
GE
ND
DE
VIC
EP
RE
FIX
LO
CA
TIO
NC
OD
E
LO
CA
TIO
N
AIR
HA
ND
LE
RS
EC
TIO
N
LO
WV
OL
TA
GE
PA
NE
L(U
NIT
SC
HE
MA
TIC
)H
IGH
VO
LT
AG
EP
AN
EL
321
AR
EA
96
95
A2
A1
33
9
10
1K
40
AU
X
13
14
16
27
6
INC
LU
DIN
GR
EM
OT
ED
ISC
ON
NE
CT
SA
ND
AV
ER
TIS
SE
ME
NT
AD
VE
RT
EN
CIA
NE
PA
SR
ES
PE
CT
ER
CE
SM
ES
UR
ES
DE
FO
LL
OW
LO
CK
OU
TA
ND
TA
GP
RO
CE
DU
RE
S
BE
FO
RE
SE
RV
ICIN
G.
INS
UR
ET
HA
TA
LL
MO
TO
RC
AP
AC
ITO
RS
HA
VE
DIS
CH
AR
GE
D
ST
OR
ED
VO
LT
AG
E.
UN
ITS
WIT
HV
AR
IAB
LE
INS
TR
UC
TIO
NS
FO
RC
AP
AC
ITO
RD
ISC
HA
RG
E.
SE
RV
ICIN
GC
OU
LD
RE
SU
LT
IND
EA
TH
OR
INS
TR
UC
TIO
NS
DE
L'E
NT
RA
ÎNE
ME
NT
PO
UR
VIT
ES
SE
VA
RIA
BLE
,S
ER
EP
OR
TE
RA
UX
DÉ
CH
AR
GÉ
S.
DA
NS
LE
CA
SD
'UN
ITÉ
S
LE
SC
ON
DE
NS
AT
EU
RS
DE
SM
OT
EU
RS
SO
NT
TO
UT
EIN
TE
RV
EN
TIO
N.
VÉ
RIF
IER
QU
ET
OU
S
VE
RR
OU
ILLA
GE
ET
DE
SÉ
TIQ
UE
TT
ES
AV
AN
T
OU
VR
IRLE
SS
EC
TIO
NN
EU
RS
ÀD
IST
AN
CE
,
PR
ÉC
AU
TIO
NP
EU
TE
NT
RA
ÎNE
RD
ES
BL
ES
SU
RE
SG
RA
VE
SP
OU
VA
NT
ÊT
RE
DÉ
CH
AR
GE
RLE
SC
ON
DE
NS
AT
EU
RS
.
MO
RT
ELLE
S.
TE
NS
ION
DA
NG
ER
EU
SE
!
SP
EE
DD
RIV
E,R
EF
ER
TO
DR
IVE
FA
ILU
RE
TO
DO
TH
EA
BO
VE
BE
FO
RE
CO
MP
OR
TA
NT
DE
SE
NT
RA
ÎNE
ME
NT
SÀ
PU
ISS
UIV
RE
LE
SP
RO
CÉ
DU
RE
SD
E
CO
UP
ER
TO
UT
ES
LE
ST
EN
SIO
NS
ET
SE
RIO
US
INJU
RY
.WA
RN
ING
DIS
CO
NN
EC
TA
LL
EL
EC
TR
ICP
OW
ER
HA
ZA
RD
OU
SV
OLT
AG
E!
CO
NS
ULT
EL
AS
INS
TR
UC
CIO
NE
SP
AR
ALA
DIR
EC
CIÓ
ND
EV
EL
OC
IDA
DV
AR
IAB
LE
,
PA
RA
LA
SU
NID
AD
ES
CO
NE
JE
DE
SE
RV
ICIO
.A
SE
GÚ
RE
SE
DE
QU
ET
OD
OS
ET
IQU
ET
AD
OA
NT
ES
DE
PR
OC
ED
ER
AL
SIG
ALO
SP
RO
CE
DIM
IEN
TO
SD
EC
IER
RE
Y
INC
LU
SO
LA
SD
ES
CO
NE
XIO
NE
SR
EM
OT
AS
Y
OS
ER
IAS
LE
SIO
NE
SP
ER
SO
NA
LE
S.
IND
ICA
DO
,P
OD
RÍA
OC
AS
ION
AR
LA
MU
ER
TE
EL
NO
RE
ALIZ
AR
LO
AN
TE
RIO
RM
EN
TE
DE
SC
AR
GA
DE
LC
ON
DE
NS
AD
OR
.
LO
SC
AP
AC
ITO
RE
SD
EL
MO
TO
RH
AY
AN
iVO
LT
AJE
PE
LIG
RO
SO
!
DE
SC
AR
GA
DO
EL
VO
LT
AJE
ALM
AC
EN
AD
O.
DE
SC
ON
EC
TE
TO
DA
LA
EN
ER
GÍA
ELÉ
CT
RIC
A,
FA
ILU
RE
TO
DO
SO
MA
YC
AU
SE
DA
MA
GE
TO
TH
E
UN
ITT
ER
MIN
ALS
AR
EN
OT
DE
SIG
NE
DT
OA
CC
EP
T
N'U
TIL
ISE
RQ
UE
DE
SC
ON
DU
CT
EU
RS
EN
CU
IVR
E!
LE
SB
OR
NE
SD
EL'U
NIT
ÉN
ES
ON
TP
AS
CO
NÇ
UE
S
PO
UR
RE
CE
VO
IRD
'AU
TR
ES
TY
PE
SD
EC
ON
DU
CT
EU
RS
.
L'U
TIL
ISA
TIO
ND
ET
OU
TA
UT
RE
CO
ND
UC
TE
UR
PE
UT
SIN
OLO
HA
CE
,P
UE
DE
OC
AS
ION
AR
DA
ÑO
AL
EQ
UIP
O.
PA
RA
AC
EP
TA
RO
TR
OS
TIP
OS
DE
CO
ND
UC
TO
RE
S.
LA
ST
ER
MIN
ALE
SD
ELA
UN
IDA
DN
OE
ST
ÁN
DIS
EÑ
AD
AS
¡UT
ILIC
EÚ
NIC
AM
EN
TE
CO
ND
UC
TO
RE
SD
EC
OB
RE
!
EN
DO
MM
AG
ER
L'É
QU
IPE
ME
NT
.
PR
EC
AU
CIÓ
N
OT
HE
RT
YP
ES
OF
CO
ND
UC
TO
RS
.
EQ
UIP
ME
NT
.
AT
TE
NT
ION
US
EC
OP
PE
RC
ON
DU
CT
OR
SO
NLY
!
CA
UT
ION
200
29
Sanford Lab - Lead - Preconditioning AHU December 02, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /Installed by Others
Equipment Submittal Page 26 of 29
Accessory - Performance Climate ChangerTrap ScheduleItem: A1 Qty: 1 Tag(s): AHU-1
UnitTag(s)
UnitSize
EnteringExt. StaticPressure(in H2O)
DischargeExt. StaticPressure(in H2O)
Drain panSectionLocation
Recommended Trap Dimensions1
SelectedBaserail
Height (in)1
H(in)
J(in)
L(in)
AHU-12
Unit size 14 0.750 0.750Coil section
[8]0.500 1.743 3.243 2.500
1Trap height and selected baserail heights should be reviewed to determine appropriate housekeeping pad height.
2The external static pressure used for fan selection was assumed to be divided 50% to entering duct external static
pressure and 50% discharge external static pressure.
H
J
L
Drain pan trapping for sectionunder negative pressure
L = H + J + pipe diameter where:H = 1 inch for each inch of negativepressure (loaded filters) plus 1 inch
J = 12 H
Drain pan trapping for sectionunder positive pressure
L = H + J + pipe diameter where:H = 1/2 inch (minimum)
J = 12 inch plus the unit positive static
pressure at coil discharge (loadedfilters)
Sanford Lab - Lead - Preconditioning AHU December 02, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /Installed by Others
Equipment Submittal Page 27 of 29
Accessory - Performance Climate ChangerFilter ScheduleItem: A1 Qty: 1 Tag(s): AHU-1
UnitTag(s)
UnitSize
FilterLocation
FilterArrangement
FilterDepth
FilterType
MERVRating
FilterQuantity
FilterSize
AHU-1 Unit size 14Filter section
[5]Angled filter
2in. filterframe
No prefilterCustomersupplied
- -
Pleated media- run set
MERV 842
20in.x20in.20in.x25in.
Sanford Lab - Lead - Preconditioning AHU December 02, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /Installed by Others
Equipment Submittal Page 28 of 29
Field Wiring - Performance Climate ChangerMCA MOP ScheduleItem: A1 Qty: 1 Tag(s): AHU-1
Unit Tag(s) Circuit Circuit Description Voltage/Phase/Hz MCA (A) MOP (A)
AHU-1
1Supply fanmotor(s)
460/3/60 8.38 15.07
2Exhaust fan
motor(s)460/3/60 11.75 21.15
3 Cool-dry quiet 115/1/60 0.41 0.74
Sanford Lab - Lead - Preconditioning AHU December 02, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /Installed by Others
Equipment Submittal Page 29 of 29
Field Installed Options - Part/Order Number Summary
This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or ordernumbers for each field installed option, and references it to a specific product tag. It is NOT intended as a bill ofmaterial for the job.
Product Family - Performance Climate Changer
Item Tag(s) Qty Description Model Number
A1 AHU-1 1 Performance Climate Changer ( CSAA ) CSAA014UA
Field Installed Option Description Part/Ordering Number
1 extra set
Pleated media - run set
1 extra set filters - run set
Pleated media - run set