26
105 CARLYLE SEMI-HERMETIC COMPRESSORS GUIDE TO 06D PART NUMBERING SYSTEM: NOTES: 1. SPECIAL ORDER SERVICE COMPRESSORS FOR BRYANT MAY BE PROCESSED AS “9” NAMEPLATED “6” (8TH DIGIT). 2. SERVICE MODELS WITH “C” IN THE 10th DIGIT REPLACE ALL “A”, “C” AND “E” ORIGINAL EQUIPMENT MODELS AND “D” SERVICE MODELS REPLACE “8” & “F” MODELS. TERMINAL BOXES AND OVERLOADS ARE TO BE RE-USED OR REPLACED IF DAMAGED. 3. “09” IN THE 11TH & 12TH DIGITS HAS BEEN USED IN THE PAST FOR 400-3-50 MOTORS AND IS NO LONGER USED, SO AS TO AVOID CONFUSION IN SERVICE THESE DIGITS ARE TO BE LEFT ON THIS CHART BUT ARE NOT TO BE RE-USED. PRODUCT SERIES UNLOADER VARIATIONS MOTOR SIZE CFM DISPLACEMENT KEY NUMBER VARIABLES ELECTRICAL CHARACTERISTIC VARIATIONS FUTURE DESIGN VARIABLES PACKAGING VARIATIONS SUCTION VALUE & M.E. COVER ORIENTATION VORELOADS & INTERNAL THERMOSTAT MODEL 0 6 D A 3 1 6 0 0 A 3 2 0 0 VARIABLE DIGIT I 2 3 4 5 6 7 8 9 10 11 12 13 14 13TH DIGIT FUTURE DESIGN VARIABLES 0 ORIGINAL DESIGN A/C & REFRIG. 1 2ND GENERATION REFRIG, CPRSR. W/NEW VALVE PLATE 2 MED. RANGE A/C CPRSR. WITH REFRIG. CHARACTERISTICS 3 LOW CLEARANCE VOLUME 4 SUCTION CUT-OFF ELECTRIC UNLOADERS 1 STEP 5 OILLESS 6 7 14TH DIGIT PACKAGING VARIATIONS 0 SERVICE UNIT SINGLE PACK - BASE UNIT UNPACKAGES I SINGLE PACK - DOMESTIC LESS SERVICE VALVE 2 MULTI-PACK - DOMESTIC 3 EXPORT - I UNIT 4 MULTI-PACK 5 PALLETIZED 6 GOVERNMENT PACK 7 SINGLE PACK - DOMESTIC WITH SERVICE VALVE 8 MATCHED COMPONENTS - CONSISTS OF SEPARATE EXPORT PACKAGE PIECES 9 DOMESTIC MULTI-PACK & MCMINNVILLE 1ST, 2ND, 3RD DIGITS SIGNIFY 06D HERMETIC RECIP. COMPRESSOR 4TH DIGIT UNLOADER VARIABLE L E T T E R S T A N D A R D S E R V I C E B O T H DESCRIPTION A X NO HOT GAS BY-PASS UNLOADERS B X ELECTRIC UNLOADERS 1 STEP C X 2 STEP D X PRESSURE UNLOADERS 1 STEP E X 2 STEP F X SUCTION CUT-OFF ELECTRIC UNLOADERS 1 STEP G X 2STEP M X MED. TEMPERATURE, REPLACES ALL “A’s” IN SERVICE N X 2 SHAVED HDS. - SPECIAL ORDER R X REFRIGERATION W X AIC - 2 PLUGGED HDS. REPLACES ALL C&E SERVICE SPEC. ORDERS X X 1 PLUGGED HEAD - REPLACES ALL B, C, D & E PROD. MODELS IN SERVICE Y X REFR. - 2 PLUGGED HDS. SERVICE SPEC. ORDER S X HI-EFF SERVICE MOD. w/I BLOCKED UNLD’R HD - REPLACES F, G, H & J H X SUCTON CUT-OFF PRES- SURE UNLOADERS! 1 STEP J X 2 STEP 5TH DIGIT VARIABLE MOTOR SIZES 2 CYL 4 CYL 6 CYL 0 3 HP 1 2 HP 5 HP 2 24 LBFT 3 5 HP 27 LBFT 4 3 1 / 2 HP 5 5 1 / 2 HP 38 LBFT 6 7 5 HP 20 LBFT 8 3 HP 20 LBFT 24 LBFT 9 10TH DIGIT OVERLOAD & T’STAT. VARIABLE SEE NOTE 2 EXTL. OVLDS. INTL. T’RAT. DESCRIPTION A YES YES B YES NO C NO YES D NO NO E YES YES 1ST OVERLOAD VARIATION F YES NO 1ST OVERLOAD VARIATION G YES YES MANUAL RESET OVERLOADS T NO YES TECUMSEH SERVICE MODELS 9TH DIGIT SUCTION SERVICE VALVE VARIABLES LOC. OF VALVE M.E.COV. DESC. VALVE ORIENTATION A MOTOR END 2 BOLT 30° B MOTOR END 4 BOLT 30° C MOTOR END 2 BOLT 90° D MOTOR END 4 BOLT 90° OR 180° E MOTOR END 2 BOLT 150° F PUMP END PLAIN 270° G PUMP END PLAIN 225° 270° 90° 180° 8TH DIGIT KEY NO. SIGNIFICANCE 0 PROD. MOD. W/T-BOX 1 PKG. CPRSR. & CONTROL BOX 2 OEM A/C CPRSR. 3 TYLER MODELS 4 TECUMSEH OEM MODELS 5 FUTURE USE 6 REMAN. SERVICE CPRSR. 7 NEWMAN SERVICE GPRSR. 6 SPECIAL ORDER ONLY 9 SERV. SPEC. OR SEE NOTE 1 6TH & 7TH DIGITS CRANKCASE ASSEMBLY NO. CYL BORE CFM 07 6D20-249 1- 13 / 16 08 6D23-249 2 09 6D23-249 2 13 6D48-249 2 16 6D48-249 2 18 6D48-249 2 20 6D48-249 2 24 6D68-259 2 28 6D75-249 2 37 6D75-249 2 11TH & 12TH DIGITS ELECTRICAL CHARACTERISTICS VOLTS-PHASE- HERTZ START 00 XL 01 575 - 3 - 60 XL 02 200 - 1 - 60 XL 03 230 - 1 - 60 XL 04 200 - 3 - 60 XL 05 230 - 3 - 60 XL 06 400/460 - 3 - 50/60 XL 07 230 - 1 - 50 XL 08 220 - 3 - 50 XL 09 SEE NOTE 3 XL 10 230 - 2 - 60 XL 11 480 - 3 - 60 XL 12 2081230 - 3 - 60 XL 13 380 - 3 - 60 XL 14 200 - 3 - 60 P/W 15 230 - 3 - 60 P/W 18 220 - 3 - 50 P/W 19 230/460 - 3 - 60 XL 21 575 - 3 - 60 XL 26 400/460 - 3 - 50/60 XL 31 575 - 3 - 60 XL 32 208/230 - 3 - 60 XL 36 400/460 - 3 - 50/60 XL 38 415 - 3 - 50 P/W 39 415 - 3 - 50 XL 33 208/230 - 1 - 60 XL 34 220 - 3 - 50 XL

GUIDE TO 06D PART NUMBERING SYSTEM105 CARLYLE SEMI-HERMETIC COMPRESSORS GUIDE TO 06D PART NUMBERING SYSTEM: NOTES: 1. SPECIAL ORDER SERVICE COMPRESSORS FORBRYANT …

  • Upload
    others

  • View
    10

  • Download
    0

Embed Size (px)

Citation preview

  • 105

    CARLYLE SEMI-HERMETIC COMPRESSORS

    GUIDE TO 06D PART NUMBERING SYSTEM:NOTES:1. SPECIAL ORDER SERVICE COMPRESSORS FOR BRYANT

    MAY BE PROCESSED AS “9” NAMEPLATED “6” (8THDIGIT).

    2. SERVICE MODELS WITH “C” IN THE 10th DIGIT REPLACEALL “A”, “C” AND “E” ORIGINAL EQUIPMENT MODELS AND“D” SERVICE MODELS REPLACE “8” & “F” MODELS.TERMINAL BOXES AND OVERLOADS ARE TO BERE-USED OR REPLACED IF DAMAGED.

    3. “09” IN THE 11TH & 12TH DIGITS HAS BEEN USED IN THEPAST FOR 400-3-50 MOTORS AND IS NO LONGER USED,SO AS TO AVOID CONFUSION IN SERVICE THESE DIGITSARE TO BE LEFT ON THIS CHART BUT ARE NOT TO BERE-USED.

    PRODUCTSERIES

    UN

    LO

    AD

    ER

    VA

    RIA

    TIO

    NS

    MO

    TOR

    SIZ

    E

    CF

    MD

    ISP

    LA

    CE

    ME

    NT

    KE

    YN

    UM

    BE

    R

    VARIABLES

    EL

    EC

    TR

    ICA

    LC

    HA

    RA

    CT

    ER

    IST

    ICV

    AR

    IAT

    ION

    S

    FU

    TU

    RE

    DE

    SIG

    NV

    AR

    IAB

    LE

    S

    PAC

    KA

    GIN

    GV

    AR

    IAT

    ION

    S

    SU

    CT

    ION

    VA

    LU

    E&

    M.E

    .

    CO

    VE

    RO

    RIE

    NTA

    TIO

    N

    VO

    RE

    LO

    AD

    S&

    INT

    ER

    NA

    L

    TH

    ER

    MO

    STA

    T

    MODEL 0 6 D A 3 1 6 0 0 A 3 2 0 0

    VARIABLE DIGIT I 2 3 4 5 6 7 8 9 10 11 12 13 14

    13THDIGIT

    FUTURE DESIGNVARIABLES

    0 ORIGINAL DESIGN A/C & REFRIG.1 2ND GENERATION REFRIG,

    CPRSR. W/NEW VALVE PLATE2 MED. RANGE A/C CPRSR. WITH

    REFRIG. CHARACTERISTICS3 LOW CLEARANCE VOLUME4 SUCTION CUT-OFF

    ELECTRIC UNLOADERS1 STEP

    5 OILLESS67

    14THDIGIT

    PACKAGING VARIATIONS

    0SERVICE UNIT SINGLE PACK -BASE UNIT UNPACKAGES

    ISINGLE PACK - DOMESTICLESS SERVICE VALVE

    2 MULTI-PACK - DOMESTIC3 EXPORT - I UNIT4 MULTI-PACK5 PALLETIZED6 GOVERNMENT PACK

    7SINGLE PACK - DOMESTICWITH SERVICE VALVE

    8MATCHED COMPONENTS -CONSISTS OF SEPARATEEXPORT PACKAGE PIECES

    9DOMESTIC MULTI-PACK &MCMINNVILLE

    1ST, 2ND, 3RD DIGITSSIGNIFY 06D HERMETICRECIP. COMPRESSOR

    4TH DIGIT UNLOADER VARIABLE

    LETTER

    STANDARD

    SERVICE

    BOTH

    DESCRIPTION

    A X NO HOT GAS BY-PASS UNLOADERSB X ELECTRIC UNLOADERS 1 STEPC X 2 STEPD X PRESSURE UNLOADERS 1 STEPE X 2 STEPF X SUCTION CUT-OFF

    ELECTRIC UNLOADERS1 STEP

    G X 2STEPM X MED. TEMPERATURE, REPLACES

    ALL “A’s” IN SERVICEN X 2 SHAVED HDS. - SPECIAL ORDERR X REFRIGERATIONW X AIC - 2 PLUGGED HDS. REPLACES

    ALL C&E SERVICE SPEC. ORDERSX X 1 PLUGGED HEAD - REPLACES ALL

    B, C, D & E PROD. MODELS INSERVICE

    Y X REFR. - 2 PLUGGED HDS. SERVICESPEC. ORDER

    S X HI-EFF SERVICE MOD. w/I BLOCKEDUNLD’R HD - REPLACES F, G, H & J

    H X SUCTON CUT-OFF PRES-SURE UNLOADERS!

    1 STEPJ X 2 STEP

    5TH DIGITVARIABLE

    MOTOR SIZES2 CYL 4 CYL 6 CYL

    0 3 HP1 2 HP 5 HP2 24 LBFT3 5 HP 27 LBFT4 31/2 HP5 51/2 HP 38 LBFT67 5 HP 20 LBFT8 3 HP 20 LBFT 24 LBFT9

    10THDIGIT

    OVERLOAD & T’STAT. VARIABLE SEE NOTE 2EXTL.

    OVLDS.INTL.

    T’RAT.DESCRIPTION

    A YES YESB YES NOC NO YESD NO NOE YES YES 1ST OVERLOAD VARIATIONF YES NO 1ST OVERLOAD VARIATIONG YES YES MANUAL RESET OVERLOADST NO YES TECUMSEH SERVICE MODELS

    9THDIGIT

    SUCTION SERVICE VALVE VARIABLESLOC. OF VALVE M.E.COV. DESC. VALVE ORIENTATION

    A MOTOR END 2 BOLT 30°B MOTOR END 4 BOLT 30°C MOTOR END 2 BOLT 90°D MOTOR END 4 BOLT 90° OR 180°E MOTOR END 2 BOLT 150°F PUMP END PLAIN 270°G PUMP END PLAIN 225°

    270° 90°

    180°

    8THDIGIT

    KEY NO. SIGNIFICANCE

    0 PROD. MOD. W/T-BOX1 PKG. CPRSR. & CONTROL BOX2 OEM A/C CPRSR.3 TYLER MODELS4 TECUMSEH OEM MODELS5 FUTURE USE6 REMAN. SERVICE CPRSR.7 NEWMAN SERVICE GPRSR.6 SPECIAL ORDER ONLY9 SERV. SPEC. OR SEE NOTE 1

    6TH & 7THDIGITS

    CRANKCASEASSEMBLY

    NO.

    CYLBORE

    CFM07 6D20-249 1-13/1608 6D23-249 209 6D23-249 213 6D48-249 216 6D48-249 218 6D48-249 220 6D48-249 224 6D68-259 228 6D75-249 237 6D75-249 2

    11TH& 12THDIGITS

    ELECTRICALCHARACTERISTICS

    VOLTS-PHASE-HERTZ

    START

    00 XL01 575 - 3 - 60 XL02 200 - 1 - 60 XL03 230 - 1 - 60 XL04 200 - 3 - 60 XL05 230 - 3 - 60 XL06 400/460 - 3 - 50/60 XL07 230 - 1 - 50 XL08 220 - 3 - 50 XL09 SEE NOTE 3 XL10 230 - 2 - 60 XL11 480 - 3 - 60 XL12 2081230 - 3 - 60 XL13 380 - 3 - 60 XL14 200 - 3 - 60 P/W15 230 - 3 - 60 P/W18 220 - 3 - 50 P/W19 230/460 - 3 - 60 XL21 575 - 3 - 60 XL26 400/460 - 3 - 50/60 XL31 575 - 3 - 60 XL32 208/230 - 3 - 60 XL36 400/460 - 3 - 50/60 XL38 415 - 3 - 50 P/W39 415 - 3 - 50 XL33 208/230 - 1 - 60 XL34 220 - 3 - 50 XL

  • 106

    CARLYLE SEMI-HERMETIC COMPRESSORS

    06DAIR CONDITIONING DUTY COMPRESSOR APPLICATION DATA

    06ECOMPRESSOR APPLICATION DATA

    R-22

    MODEL NO. NOMINALHPNO. OF

    CYL.CFM @

    1750 RPM

    SUCTIONTEMP. RANGE

    (°F)

    CAPACITY (000 BTUH)AIR COOLED WATER COOLED

    45° SST130° SCT

    0° SC

    40° SST105° SCT

    0° SC06DM808 3 2 8.0 -10 to 50 36.7 39.806D( )313 5 4 13.1 -10 to 50 56.9 62.706D( )818 6.5 4 18.3 -10 to 50 83.3 91.006D( )724 6.5 6 23.9 -10 to 50 - 122.606D( )824 7.5 6 23.9 -10 to 50 106.5 117.306D( )328 10 6 28.0 -10 to 50 128.7 140.006D( )337 10 6 37.1 -10 to 50 - 185.606D( )537 15 6 37.1 -10 to 50 175.4 191.3

    R-22

    MODEL NO. NOMINALHPNO. OF

    CYL.CFM @

    1750 RPM

    SUCTIONTEMP. RANGE

    (°F)

    CAPACITY (000 BTUH)AIR COOLED WATER COOLED

    45° SST130° SCT

    0° SC

    40° SST105° SCT

    0° SC06E( )150 15 4 50.0 -10 to 50 - 245.806E( )250 20 4 50.0 -10 to 50 223.3 247.006E( )265 25 6 65.0 -10 to 50 300.3 334.706E( )266 25 4 66.0 -10 to 50 290.0 302.606E( )175 25 6 75.0 -10 to 50 - 364.306E( )275 30 6 75.0 -10 to 50 332.8 363.006E( )199 35 6 99.0 -10 to 50 - 469.706E( )299 40 6 99.0 -10 to 50 437.9 476.3

    CFM = Cubic Feet Per MinuteSST = Saturated Suction TemperatureSCT = Saturated Condensing TemperatureSC = Sub Cooling

    For mounting configuration,dimensions and weight refer tooutline drawings on followingpages.

    P59N

    For mounting configuration,dimensions and weight refer tooutline drawings on followingpages..

    P51

    Generally, for a compressor changeout in a Carrier/BDP unit the use of existing circuit breaker(s) is acceptable.

  • 107

    CARLYLE SEMI-HERMETIC COMPRESSORS

    06D OUTLINE DRAWINGSNOTE: COMPRESSORS SHOWN WITH OPTIONAL ACCESSORIES - CONTACT YOUR DISTRIBUTOR FOR DETAILS.

    06D COMPRESSOR

    8 CFM 9 CFMNO. OF CYLINDERS 2 2

    BORE AND STROKE (in.) 2.0 x 1.25 2.0 x 1.366DISPLACEMENT CFM AT 1750 RPM 7.95 8.69OIL, CHARGE, PINTS CPP33-2 3.5 3.5

    DRY WEIGHT LESS SERVICE VALVES 150 LBS 140 LBS

    NOTES:1. OIL PUMP IS AUTOMATICALLY REVERSIBLE

    FOR EITHER DIRECTION OF ROTATION.2. CRANKCASE HEATERS (ACCESSORY) WHEN

    REQUIRED ARE STRAPPED TO BASE OF OILRESERVOIR.

  • 108

    CARLYLE SEMI-HERMETIC COMPRESSORS

    06D OUTLINE DRAWINGSNOTE: COMPRESSORS SHOWN WITH OPTIONAL ACCESSORIES - CONTACT YOUR DISTRIBUTOR FOR DETAILS.

    06D COMPRESSOR

    13 CFM 16 CFMNO. OF CYLINDERS 4 4

    BORE AND STROKE (in.) 2.0 x 1.0 2.0 x 1.25DISPLACEMENT CFM AT 1750 RPM 13.00 15.90OIL CHARGE, PINTS CPP33-2 5.0 5.0

    DRY WEIGHT LESS SERVICE VALVES 182 LBS 182 LBS

    NOTE: SUCTION SERVICE VALVE MAY ALSO BE MOUNTED ON OIL PUMP END OF COMPRESSOR.

    06D COMPRESSOR

    18 CFM 20 CFM

    NO. OF CYLINDERS 4 4

    BORE AND STROKE (in.) 2.0 x 1.435 2.0 x 1.559

    DISPLACEMENT CFM AT 1750 RPM 18.26 19.59

    OIL CHARGE, PINTS CPP33-2 7.0 7.0

    DRY WEIGHT LESS SERVICE VALVES 221 LBS 221 LBSNOTE: OIL PUMP IS AUTOMATI-CALLY REVERSIBLE FOR EITHERDIRECTION OF ROTATION.

    Generally, for a compressor changeout in a Carrier/BDP unit the use of existing circuit breaker(s) is acceptable.

  • 109

    CARLYLE SEMI-HERMETIC COMPRESSORS

    06D OUTLINE DRAWINGSNOTE: COMPRESSORS SHOWN WITH OPTIONAL ACCESSORIES - CONTACT YOUR DISTRIBUTOR FOR DETAILS.

    06D COMPRESSOR

    24 CFMNO. OF CYLINDERS 6

    BORE AND STROKE (in.) 2.0 x 1.25DISPLACEMENT CFM AT 1750 RPM 23.66OIL, CHARGE, PINTS CPP33-2 9.5

    DRY WEIGHT LESS SERVICE VALVES 275 LBS

    NOTE: OIL PUMP IS AUTOMATICALLYREVERSIBLE FOR EITHER DIRECTIONOF ROTATION.

    06D COMPRESSOR

    28 CFM 37 CFMNO. OF CYLINDERS 6 6BORE AND STROKE (in.) 2.0 x 1.469 2.0 x 1.983

    DISPLACEMENT CFM AT 1750 RPM 28.04 37.00OIL, CHARGE, PINTS CPP33-2 9.5 9.5DRY WEIGHT LESS SERVICE VALVES 305 LBS 305 LBS

    NOTE: OIL PUMP IS AUTO-MATICALLY REVERSIBLEFOR EITHER DIRECTION OFROTATION.

  • 110

    CARLYLE SEMI-HERMETIC COMPRESSORS

    CARLYLE SEMI-HERMETIC COMPRESSORSDATA AND ACCESSORY LISTING

    To use this chart, first select the compressor suitable for the application. Consider capacity, refrigerant, voltage, wire size, spacelimitations, etc.

    Next, use the compressor model number to enter the accessory tables and find the necessary accessories. These include CircuitBreakers, Service Valve Kits, Terminal Box Kits, Crankcase Heaters. You can also select any optional accessories needed for theinstallation.

    06D COMPRESSOR DATASTANDARD EFFICIENCY MODELS WITH ONE PLUGGED HOT GAS BYPASS UNLOADER HEAD

    COMPRESSORMODEL NO.

    VOLT HP CFMOIL

    CHG.PINTS

    MAX.WATTS

    MAX.RLA*

    *This is the maximum rated load amp rating for the compressor motor. The overcurrent protection (circuit breaker) in the unit may result in much lowerRLA values.

    MTA LRA

    4 CYLINDER ... AIR CONDITIONING ... UNLOADING ... 60 HZ06DX8186-0600 460 6.5 18.3 7 10,800 17.6 22.0 62.006DX8186-1200 208/230 6.5 18.3 7 10,800 39.0 48.8 137.04 CYLINDER ... AIR CONDITIONING ... UNLOADING ... 50 HZ06DX8186-0600 400 6.5 15 7 9,000 17.6 22.0 62.06 CYLINDER ... AIR CONDITIONING ... UNLOADING ... 60 HZ06DX7246-0100 575 6.5 23.9 10 10,800 14.1 17.6 50.006DX7246-0600 460 6.5 23.9 10 10,800 17.6 22.0 62.006DX7246-1200 208/230 6.5 23.9 10 10,800 39.0 48.8 137.006DX8246-0100 575 7.5 23.9 10 14,100 17.8 22.2 62.006DX8246-0600 460 7.5 23.9 10 14,100 22.2 27.8 77.006DX8246-1200 208/230 7.5 23.9 10 14,100 49.3 61.5 170.006DX3286-0100 575 10 28 10 15,900 20.0 25.0 69.006DX3286-0600 460 10 28 10 15,900 24.8 31.0 86.006DX3286-1200 208/230 10 28 10 15,900 55.2 69.0 191.006DX3376-0100 575 10 37.1 10 15,900 20.0 25.0 69.006DX3376-0600 460 10 37.1 10 15,900 24.8 31.0 86.006DX3376-1200 208/230 10 37.1 10 15,900 55.2 69.0 191.06 CYLINDER ... AIR CONDITIONING ... UNLOADING ... 50 HZ06DX7246-0600 400 6.5 20 10 9,000 17.6 22.0 62.006DX8246-0600 400 7.5 20 10 11,700 22.2 27.8 77.006DX3286-0600 400 10 23.3 10 13,200 24.8 31.0 86.006DX3376-0600 400 10 31 10 13,200 24.8 31.0 86.006DX5376-0600 400 15 31 10 17,200 32.0 40.0 120.06 CYLINDER ... AIR CONDITIONING ... UNLOADING ... PART WIND START ... 60 HZ06DX3376-1400 200 10 37.1 10 15,900 27.6/27.6 34.5/34.5 115/9206DX3376-1500 230 10 37.1 10 15,900 24.8/24.8 31.0/31.0 103/866 CYLINDER ... AIR CONDITIONING ... UNLOADING ... 60 HZ06DX5376-0100 575 15 37.1 10 20,700 25.6 32.0 96.006DX5376-0600 460 15 37.1 10 20,700 32.0 40.0 120.006DX5376-1200 208/230 15 37.1 10 20,700 71.2 89.0 266.06 CYLINDER ... AIR CONDITIONING ... UNLOADING ... PART WIND START ... 60 HZ06DX5376-1400 200 15 37.1 10 20,700 35.6/35.6 44.5/44.5 160/13306DX5376-1500 230 15 37.1 10 20,700 32.0/32.0 40.0/40.0 144/1206 CYLINDER ... AIR CONDITIONING ... UNLOADING ... PART WIND START ... 50 HZ06DR3286-1800 220 10 23.3 10 13,200 41.6 52.0 14306DX3376-1800 220 10 31 10 13,200 41.6 52.0 14306DX537-1800 220 15 31 10 17,200 46.9 67.0 200

    Generally, for a compressor changeout in a Carrier/BDP unit the use of existing circuit breaker(s) is acceptable.

  • 111

    CARLYLE SEMI-HERMETIC COMPRESSORS

    06D COMPRESSOR DATA - SINGLE PHASESTANDARD EFFICIENCY - NO UNLOADING

    06D COMPRESSOR DATA - THREE PHASEMEDIUM TEMPERATURE - NO UNLOADING

    06D COMPRESSOR DATA - THREE PHASEHIGH EFFICIENCY - NO UNLOADING

    COMPRESSORMODEL NO.

    VOLT HP CFMOIL

    CHG.PINTS

    MAX.WATTS

    MAX.RLA

    MTA LRA

    2 CYLINDER... AIR CONDITIONING & MEDIUM TEMPERATURE ... 60 HZ06DM8086-0300 230 3 8 3.5 2800 17.0 22.0 70.006DM1096-0300 230 2 8.7 3.5 2800 12.5 15.6 50.04 CYLINDER... AIR CONDITIONING & MEDIUM TEMPERATURE ... 60 HZ06DM3136-0300 230 5 13.1 5 6600 28.0 35.0 100.006DM3166-0300 230 5 15.9 5 6600 28.0 35.0 100.006DM3186-0300 230 5 18.3 7 6600 28.0 35.0 100.006DM5186-0300 230 5.5 18.3 7 7700 36.8 46.0 148.006DM7186-0300 230 5 18.3 7 6600 28.0 35.0 100.0

    COMPRESSORMODEL NO.

    VOLT HP CFMOIL

    CHG.PINTS

    MAX.WATTS

    MAX.RLA*

    *This is the maximum rated load amp rating for the compressor motor. The overcurrent protection (circuit breaker) in the unit may result in muchlower RLA values.

    MTA LRA

    2 CYLINDER... AIR CONDITIONING & MEDIUM TEMPERATURE ... 60 HZ06DM8086-3100 575 3 8 3.5 4100 5.6 7.0 28.406DM8086-3200 208/230 3 8 3.5 4100 14.0 17.4 71.006DM8086-3600 460 3 8 3.5 4100 7.0 8.7 35.52 CYLINDER... AIR CONDITIONING & MEDIUM TEMPERATURE ... 50 HZ06DM8086-3600 400 3 6.7 3.5 3400 7.0 8.7 35.54 CYLINDER... AIR CONDITIONING & MEDIUM TEMPERATURE ... 60 HZ06DM3136-3100 575 5 13.1 5 6250 8.6 10.8 40.006DM3136-3200 208/230 5 13.1 5 6250 21.5 27.0 100.006DM3136-3600 460 5 13.1 5 6250 10.8 13.5 50.006DM3166-3100 575 5 15.9 5 6250 8.6 10.8 40.006DM3166-3200 208/230 5 15.9 5 6250 21.5 27.0 100.006DM3166-3600 460 5 15.9 5 6250 10.8 13.5 50.0

    COMPRESSORMODEL NO.

    VOLT HP CFMOIL

    CHG.PINTS

    MAX.WATTS

    MAX.RLA*

    *This is the maximum rated load amp rating for the compressor motor. The overcurrent protection (circuit breaker) in the unit may result in muchlower RLA values.

    MTA LRA

    4 CYLINDER... AIR CONDITIONING & MEDIUM TEMPERATURE ... 50 HZ06DM3136-3600 400 5 11 5 5,200 10.8 13.5 50.006DM3166-3600 400 5 13 5 5,200 10.8 13.5 50.06 CYLINDER... AIR CONDITIONING & MEDIUM TEMPERATURE ... 60 HZ06DM3376-3100 575 10 37.1 10 16,500 17.9 25.0 91.006DM3376-3600 460 10 37.1 10 16,500 22.1 31.0 114.006DM3376-3200 208/230 10 37.1 10 16,500 44.3 62.0 228.06 CYLINDER... AIR CONDITIONING & MEDIUM TEMPERATURE ... 50 HZ06DM3376-3600 400 10 31 10 13,700 22.1 31.0 114.0

  • 112

    CARLYLE SEMI-HERMETIC COMPRESSORS

    06D COMPRESSOR DATA - THREE PHASEHIGH EFFICIENCY A/C DUTY - SUCTION CUTOFF UNLOADING

    COMPRESSORMODEL NO.

    VOLT HP CFMOIL

    CHG.PINTS

    MAX.WATTS

    MAX.RLA*

    *This is the maximum rated load amp rating for the compressor motor. The overcurrent protection (circuit breaker) in the unit may result in muchlower RLA values.

    MTA LRA

    4 CYLINDER ... AIR CONDITIONING ... UNLOADING ... 60 HZ06DS3136-3100 575 5 13.1 5 6,250 8.6 10.8 40.006DS3136-3600 460 5 13.1 5 6,250 10.8 13.5 50.006DS3136-3200 208/230 5 13.1 5 6,250 21.5 27.0 100.006DS8166-3600 460 6.5 15.9 5 10,800 15.7 22.0 80.006DS8186-3100 575 6.5 18.3 7 10,800 12.6 17.6 64.006DS8186-3600 460 6.5 18.3 7 10,800 15.7 22.0 80.006DS8186-3200 208/230 6.5 18.3 7 10,800 31.5 44.0 160.04 CYLINDER ... AIR CONDITIONING ... UNLOADING ... 50 HZ06DS3136-3600 400 5 11 5 5,200 10.8 13.5 50.006DS8166-3600 400 6.5 13 5 9,000 15.7 22.0 80.006DS8186-3600 400 6.5 15 7 9,000 15.7 22.0 80.06 CYLINDER ... AIR CONDITIONING ... UNLOADING ... 60 HZ06DS8246-3100 575 7.5 239 10 12,800 15.9 22.0 79.006DS8246-3600 460 7.5 23.9 10 12,800 19.9 27.8 99.006DS8246-3200 208/230 7.5 23.9 10 12,800 39.7 55.5 198.006DS3286-3100 575 10 28 10 16,500 17.9 25.0 91.006DS3286-3600 460 10 28 10 16,500 22.1 31.0 114.006DS3286-3200 208/230 10 28 10 16,500 44.3 62.0 228.006DS5376-0100 575 15 37.1 10 20,700 25.6 32.0 96.006DS5376-0600 460 15 37.1 10 20,700 32.0 40.0 120.006DS5376-1200 208/230 15 37.1 10 20,700 71.2 89.0 266.06 CYLINDER ... AIR CONDITIONING ... UNLOADING ... 50 HZ06DS8246-3600 400 7.5 20 10 10,700 19.9 27.8 99.006DS3286-3600 400 10 23 10 13,700 22.1 31.0 114.006DS5376-0600 400 15 37.1 10 17,200 32.0 40.0 120.0

    Generally, for a compressor changeout in a Carrier/BDP unit the use of existing circuit breaker(s) is acceptable.

  • 113

    CARLYLE SEMI-HERMETIC COMPRESSORS

    REQUIRED CIRCUIT BREAKERS: 06D ... 60 HZ (AC DUTY)

    REQUIRED CIRCUIT BREAKERS: 06D ... 50 HZ

    COMPRESSORMODEL NO.

    CIRCUITBREAKERS

    P/N06DM8086-0300 HH83XB48006DM1096-0300 HH83XB48106DM8096-0300 HH32XB48006DM3136-0300 HH83XB48306DM3166-0300 HH83XB48306DM3186-0300 HH83XB48306DM5186-0300 HH83XB48406DM7186-0300 HH83XB48306DM8086-3200 HH83XB49006DM8086-3600 HH83XB49406DM3136-3100 HH83XB49706DM3136-3200 HH83XB31606DM3136-3600 HH83XB44306DM3166-3100 HH83XB49706DM3166-3200 HH83XB31606DM3166-3600 HH83XB44306DM8186-0100 HH83XB45006DM8186-0600 HH83XB41906DM8186-1200 HH83XB30606DM8246-0100 HH83XB41906DM8246-0600 HH83XB40006DM8246-1200 HH83XB42306DM3376-3100 HH83XB45106DM3376-3600 HH83XB452

    COMPRESSORMODEL NO.

    CIRCUITBREAKERS

    P/N06DM3376-3200 HH83XB30506DM3376-1400 HH83XE63006DM3376-1500 HH83XE60406DM5376-0100 HH83XB44006DM5376-0600 HH83XB42206DM5376-1200 HH83XB31106DM5376-1400 HH83XE63306DM5376-1500 HH83XE64306DS3136-3100 HH83XB49706DS3136-3200 HH83XB31606DS3136-3600 HH83XB44306DS8166-3600 HH83XB41606DS8186-3100 HH83XB45006DS8186-3200 HH83XB36806DS8186-3600 HH83XB41606DS8246-3100 HH83XB41606DS8246-3200 HH83XB36406DS8246-3600 HH83XB41506DS3286-3100 HH83XB45106DS3286-3200 HH83XB30506DS3286-3600 HH83XB45206DS5376-0100 HH83XB42006DS5376-0600 HH83XB401

    COMPRESSORMODEL NO.

    CIRCUITBREAKERS

    P/N06DS5376-1200 HH83XB31106DX8186-0100 HH83XB45006DX8186-0600 HH83XB44506DX8186-1200 HH83XB30606DX7246-0100 HH83XB45006DX7246-0600 HH83XB41906DX7246-1200 HH83XB42906DX8246-0100 HH83XB41906DX8246-0600 HH83XB40006DX8246-1200 HH83XB30706DX3286-0100 HH83XB45106DX3286-0600 HH83XB45206DX3286-1200 HH83XB30506DX3376-0100 HH83XB45106DX3376-0600 HH83XB45206DX3376-1200 HH83XB30506DX3376-1400 HH83XE63006DX3376-1500 HH83XE60406DX5376-0100 HH83XB42006DX5376-0600 HH83XB40106DX5376-1200 HH83XB31106DX5376-1400 HH83XE63306DX5376-1500 HH83XE643

    COMPRESSORMODEL NO.

    CIRCUITBREAKERS

    P/N06DM808-3600 HH83XB49406DM313-3600 HH83XB44306DM316-3600 HH83XB44306DM818-0600 HH83XB41906DM824-0600 HH83XB40006DM337-3600 HH83XB45206DM537-0600 HH83XB42206DS3136-3600 HH83XB443

    COMPRESSORMODEL NO.

    CIRCUITBREAKERS

    P/N06DX824-0600 HH83XB40006DX328-0600 HH83XB45206DX328-1800 HH83XB36506DX337-0600 HH83XB45206DX337-1800 HH83XB36506DX537-0600 HH83XB40106DX537-1800 HH83XB314

    COMPRESSORMODEL NO.

    CIRCUITBREAKERS

    P/N06DS8166-3600 HH83XB41606DS8186-3600 HH83XB41606DS8246-3600 HH83XB41506DS3286-3600 HH83XB45206DS5376-3600 HH83XB40106DX818-0600 HH83XB44506DX724-0600 HH83XB419

  • 114

    CARLYLE SEMI-HERMETIC COMPRESSORS

    REQUIRED ACCESSORIES - 06DOPTIONAL ACCESSORIES

    COMPRESSORMODEL NO.

    TERMINALBOX KIT

    SUCTIONSERVICE

    VALVE KIT

    ALTERNATESUCTIONSERVICE

    VALVE KIT

    DISCHARGESERVICE

    VALVE KIT

    ALTERNATEDISCHARGE

    SERVICEVALVE KIT

    SUSPENSIONKIT

    MOUNTINGPLATE KIT

    06DR109 06DA660075 06DA660061 - 06DA660060 06DA660059 06DA660058 06EA660096- - 06DA660061

    013 06DA660078 06DA660064 - 06DA660056316 06DA660064 - 06DA660056718 06DA660065 06EA660090 06DA660056820 06DA660065 06EA660090 06DA660056724 06DA660065 06EA660090 06DA660062 06DA660064 06DA660057228 06EA660090 - 06DA660062 06DA660064 06DA660057337 06EA660090 - 06DA660062 06DA660064 06DA660057

    06DM808 06DA660075 06DA660061 - 06DA660060 06DA660059 06DA660058- - 06DA660061

    809 06DA660061 - 06DA660058( )313 06DA660078 06DA660064 - 06DA660056( )316 06DA660078 06DA660062 06DA660064 06DA660056

    518 06DA660078 06DA660064 - 06DA660061 - 06DA660056 06EA660096( )818 06DA660064 - 06DA660061 - 06DA660056

    06D( )72406DA660063*

    *06DA660065*

    *06DA660062 06DA660064 06DA660057

    -06EA660090*

    *- -

    06DA660064* - - -

    ( )82406DA660063*

    *06DA660065*

    *06DA660062 06DA660064

    -06EA660090*

    *- -

    06DA660064* - - -( )328 06EA660065 06EA660090 06DA660064 -( )337 06DA660065 06EA660090 06DA660064 -( )537 06DA660065 06EA660090 06DA660064 -

    * -- 2 BOLT ** -- 4 BOLT

  • 115

    CARLYLE SEMI-HERMETIC COMPRESSORS

    GUIDE TO 06E PART NUMBERING SYSTEM

    PRODUCTSERIES

    DE

    SIG

    NVA

    RIA

    BL

    ES

    US

    AG

    E

    SIZE

    EL

    EC

    TR

    ICA

    LC

    HA

    RA

    CT

    ER

    IST

    ICS

    FU

    TU

    RE

    DE

    SIG

    N

    MO

    DE

    LA

    ND

    PAC

    KA

    GIN

    GCFMCPRSRS

    HOM.H.P.CPRSRUNITS

    MODEL 0 6 E A 1 5 0 3 4 0DIGIT 1 2 3 4 5 6 7 8 9 10

    1ST, 2HD, 3RD DIGITSO6E HERMETIC COMPRESSOR

    9TH DIGIT SERVICE DESIGN VARIABLE1 THERMOTECTOR PROTECTION OLD

    STYLE CRANKCASE2 NEW MANUFACTURE SERVICE

    COMPRESSOR3 FUTURE USE4 REMANUFACTURED SERVICE

    COMPRESSOR LOW TEMP5 OLD STYLE CRANKCASE ROBERTSHAW

    SENSORS & TAPPED CYL. HDS. MOTORPROTECTION KIT REQ’D. FOR THERMO-TECTOR APPLICATION

    6 REMANUFACTURED SERVICECOMPRESSOR

    7 REMANUFACTUREO SERVICE COMPRES-SOR MED. TEMP.

    9TH DIGIT PROD. DESIGN VARIABLE0 OEM MODEL1 ELECTRICAL REDESIGN23 FIRST REDESIGN

    LONG STROKE CRANKCASE4 SECOND DESIGN

    ROBERTSHAW MOTOR PROTECTION56 CPRSR. MODEL LESS MOTOR

    PROTECTION7 MEDIUM TEMP. ROBERTSHAW MOTOR

    PROTECTION89 CEMAK MODEL

    10TH DIGIT PACKAGING0 MODEL

    NO.4

    MULTI PACK EXP

    1SINGLE PACK

    LESSVALVE

    5PALLETIZED LESS VALVE

    2 MULTI PACK DOM 7 PALLETIZED WITH VALVE3

    SINGLE PACKWITHVALVE

    9 MULTI PACK MC MINN

    SYMBOLS:

    = SAMPLE PART NO. 06E215O36ONOTES:3. 220-3-60 UNIT DESIGNED FOR USE ON 198 to 242 V

    380-3-60 342418 V575-3-60 518660 V460-3-60 414529 V230-3-60 198264 V230-3-50 198264 V400-3-50 342457 V200-3-60 180229 V

    4. RVS HD CPRSR -- ORIGINAL DESIGN NO. 4TH DIGIT A, B, C, D, CRF9TH DIGIT

    REDESIGNNO. 4TH DIGIT F, J, K. L OR N9TH DIGIT SAME AS STANDARD

    5TH DIGIT USAGE0 LIGHT DUTY CPRSR. OR

    CPRSR. UNIT TONNAGE56

    1 MEDIUM DUTY CPRSR. 72 HEAVY DUTY CPRSR. 8 SPECIAL ORDER3 OILLESS 94

    6TH & 7TH DIGIT COMPRESSOR SIZENO. STD. LONG STROKE LONG STROKE SHORTCYL. PROD. STD. CLEARANCE HI CLEARANCE STROKE

    4 50 CFM 66 CFM 60 CFM --6 75 CFM 99 CFM -- 65 CFM

    COMPRESSOR UNITS (CAC USAGE)NO

    CYL.STD. PROD. CPRSR. LONG STROKE CPRSR.

    4 22 (NOM TONS) --6 33 (NOM TONS) 44 (NOM TONS)

    8TH DIGIT ELECT1 575 - 3 - 602 200 - 1 - 603 208/230/460 - 3 - 604 200 - 3 - 605 230 - 3 - 606 400 - 3 - 50

    460 -3 - 607 230 - 1 - 508 230 - 3 - 509 220/380 - 3 - 600 208/230 - 3 - 60A 415 - 3 - 50

    4TH DIGIT 4TH DIGIT UHLDADER VARIABLESUCTIONCUTOFF

    UNLOADINGLETTER

    STANDARD

    SERVICE

    BOTH

    DESCRIPTION

    A X NO UNLOADERS

    2 B X ONE UNLOADER - ELECTRIC

    3 C X TWO UNLOADERS - ELECTRIC

    4 D X ONE UNLOADER - PRESSURE

    5 E X TWO UNLOADERS - PRESSURE

    F X NO UNLOADERS

    RE

    VE

    RS

    ED

    HE

    AD

    6C

    YL

    .

    SE

    EN

    OT

    E2

    6 J X ONE UNLOADER - ELECTRIC

    7 K X TWO UNLOADERS - ELECTRIC

    8 L X ONE UNLOADER - PRESSURE

    9 N X TWO UNLOADERS - PRESSURE

    G X NO UNLOADERS - PRESSURE

    CP

    RS

    RW

    ITH

    CO

    NT

    BO

    X

    US

    ED

    BY

    CA

    CF

    OR

    UN

    ITSP X ONE UNLOADER - ELECTRIC

    U X TWO UNLOADERS - ELECTRIC

    V X ONE UNLOADER - PRESSURE

    W X TWO UNLOADERS - PRESSURE

    M X MEDIUM TEMP. - NO UNLOADERS

    R X REFRIGERATION - NO UNLOADERS

    T XSERVICE CMPRSR. w/(1) BLOCKED SUCTION CUT-OFF UNLOADER HEAD

    REPLACES 2,3,4, 5, 6, 7, 8 & 9

    X XSERVICE COMPRESSOR -AIR CONDITION.

    REPLACES A,B,C, D, E, F J, K,L & N

    Y X SVC. CPRSR. - REFRIG. REPLACES R

  • 116

    CARLYLE SEMI-HERMETIC COMPRESSORS

    06E OUTLINE DRAWINGSNOTE: COMPRESSORS SHOWN WITH OPTIONAL ACCESSORIES - CONTACT YOUR DISTRIBUTOR FOR DETAILS.

    06E COMPRESSOR

    06E( )150 06E( )250 06E( )266

    MOTOR HORSEPOWER 15 20 25NO. OF CYLINDERS 4 4 4

    BORE AND STROKE (in.) 2.688 x 2.188 2.688 x 2.188 2.688 x 2.874DISPLACEMENT CFM AT 1750 RPM 50 50 66OIL, CHARGE, PINTS CPP33-2 14 14 14

    NAMEPLATE TEST PRESSURE - HIGH 450 PSI 450 PSI 450 PSINAMEPLATE TEST PRESSURE - LOW 315 PSI 315 PSI 315 PSIDRY WEIGHT LESS SERVICE VALVES 390 LBS 400 LBS 416 LBS

    MAX. OPERATING CONDITIONS R-22 50/120° F 50/145° F 50/130° F

    06E COMPRESSORS

    06E( )265 06E( )175 06E( )275

    MOTOR HORSEPOWER 25 25 30NO. OF CYLINDERS 6 6 6

    BORE AND STROKE (in.) 2.688 x 1.980 2.688 x 2.188 2.688 x 2.188DISPLACEMENT CFM AT 1750 RPM 65 75 75OIL, CHARGE, PINTS CPP33-2 19 19 19

    NAMEPLATE TEST PRESSURE - HIGH 450 PSI 450 PSI 450 PSINAMEPLATE TEST PRESSURE - LOW 315 PSI 315 PSI 315 PSIDRY WEIGHT LESS SERVICE VALVES 460 LBS 435 LBS 460 LBS

    MAX. OPERATING CONDITIONS R-22 50/145° F 50/120° F 50/145° F

  • 117

    CARLYLE SEMI-HERMETIC COMPRESSORS

    06E OUTLINE DRAWINGSNOTE: COMPRESSORS SHOWN WITH OPTIONAL ACCESSORIES - CONTACT YOUR DISTRIBUTOR FOR DETAILS06E COMPRESSORS

    06E( )099 06E( )199 06E( )299MOTOR HORSEPOWER 30 35 40NO. OF CYLINDERS 6 6 6

    BORE AND STROKE (in.) 2.688 x 2.874 2.688 x 2.874 2.688 x 2.874DISPLACEMENT CFM AT 1750 RPM 65 99 99

    OIL, CHARGE, PINTS CPP33-2 19 19 19NAMEPLATE TEST PRESSURE - HIGH 450 PSI 450 PSI 450 PSINAMEPLATE TEST PRESSURE - LOW 315 PSI 315 PSI 315 PSI

    DRY WEIGHT LESS SERVICE VALVES 495 LBS 495 LBS 519 LBSMAX. OPERATING CONDITIONS R-22 50°/120° F 50°/145° F

  • 118

    CARLYLE SEMI-HERMETIC COMPRESSORS

    06E COMPRESSOR DATA - THREE PHASESTANDARD EFFICIENCY MODELS WITH ONE PLUGGED HOT GAS BYBASS UNLOADER HEAD

    COMPRESSORMODEL NO. VOLT HP CFM

    OILCHG.PINTS

    MAX.WATTS

    MAX.RLA*

    *This is the maximum rated load amp rating for the compressor motor. The overcurrent protection (circuit breaker) in the unit may result in muchlower RLA values.

    MTA LRA4 CYLINDER ... AIR CONDITIONING ... 60 HZ06EX150-160 575 15 50 14 22,000 31 38 9806EX150-360 208-230/460 15 50 14 22,000 72/36 90/45 283/14206EX150-660 ** 460 15 50 14 22,000 36 45 14206EX250-160 575 20 50 14 25,300 36 45 12006EX250-360 208-230/460 20 50 14 25,300 87/44 108/54 345/17306EX250-660 **

    **Order the discrete 400/460-3-50/60 volt compressor for part wind start applications only. When ordering, place the letters PW after the model num-ber, (i.e., 06EX299660PW).

    460 20 50 14 25,300 45 56 15006EX266-160 575 25 66 14 33,600 46 57 16406EX266-360 208-230/460 25 66 14 33,600 112/56 140/70 446/22306EX266-660 ** 460 25 66 14 33,600 57 71 205

    4 CYLINDER ... AIR CONDITIONING ... 50 HZ06EX150-360 200/400 15 41.7 14 18,300 72/36 90/45 283/14206EX150-660 ** 400 15 41.7 14 18,300 36 45 14206EX250-360 200/400 20 41.7 14 21,100 87/44 108/54 345/17306EX250-660 ** 400 20 41.7 14 21,100 45 56 15006EX266-360 200/400 25 55 14 28,000 112/56 140/70 446/22306EX266-660 ** 400 25 55 14 28,000 57 71 205

    6 CYLINDER ... AIR CONDITIONING ... 60 HZ06EX265-160 575 25 68 19 33,600 46 57 16406EX265-360 208-230/460 25 68 19 33,600 112/56 140/70 446/22306EX265-660 ** 460 25 68 19 33,600 57 71 20506EX175-160 575 25 75 19 33,600 46 57 16406EX175-360 208-230/460 25 75 19 33,600 112/56 140/70 446/22306EX175-660 ** 460 25 75 19 33,600 57 71 20506EX275-160 575 30 75 19 39,100 52 65 17606EX275-360 208-230/460 30 75 19 39,100 135/68 168/84 506/25306EX275-660 ** 460 30 75 19 39,100 65 81 22006EX299-160 575 40 99 19 54,000 77 97 24006EX299-360 208-230/460 40 99 19 54,000 189/95 236/118 690/34506EX299-660 ** 460 40 99 19 54,000 97 121 300

    6 CYLINDER ... AIR CONDITIONING ... 50 HZ06EX265-360 200/400 20 54 19 28,000 112/56 140/70 446/22306EX265-660 ** 400 20 54 19 28,000 57 71 20506EX175-360 200/400 25 62.5 19 28,000 112/56 140/70 446/22306EX175-660 ** 400 25 62.5 19 28,000 57 71 20506EX275-360 200/400 30 62.5 19 32,600 135/68 168/84 506/25306EX275-660 ** 400 30 62.5 19 32,600 65 81 22006EX299-360 200/400 40 82.5 19 45,000 189/95 236/118 690/34506EX299-660 ** 400 40 82.5 19 45,000 97 121 300

  • 119

    CARLYLE SEMI-HERMETIC COMPRESSORS

    06E COMPRESSOR DATA - THREE PHASEHIGH EFFICIENCY MODELS - ONE PLUGGED HEAD SUCTION CUTOFF UNLOADING

    COMPRESSORMODEL NO.

    VOLT HP CFMOIL

    CHG.PINTS

    MAX.WATTS

    MAX.RLA*

    *This is the maximum rated load amp rating for the compressor motor. The overcurrent protection (circuit breaker) in the unit may result in muchlower RLA values.

    MTA LRA

    4 CYLINDER ... AIR CONDITIONING ... 60 HZ06ET150-1( )0 † 575 15 50 14 22,000 31 38 9806ET150-3( )006ET150-6( )0

    †**†

    208-230/460460

    1515

    5050

    1414

    22,00022,000

    72/3636

    90/4545

    283/142142

    06ET250-1( )0 † 575 20 50 14 25,300 36 45 12006ET250-3( )0 † 208-230/460 20 50 14 25,300 87/44 108/54 345/17306ET250-6( )0 **†

    **Order the discrete 400/460-3-50/60 volt compressor for part wind start applications only. When ordering, place the letters PW after the model num-ber, (i.e., 06EX299660PW).

    †Digit indicated by ( ) may be a 6 or a 2.

    460 20 50 14 25,300 44 54 1734 CYLINDER ... AIR CONDITIONING ... 50 HZ

    06ET150-320 200/400 15 41.7 14 18,300 72/36 90/45 283/14206ET150-36006ET150-62006ET150-660

    ****

    200/400400400

    151515

    41.741.741.7

    141414

    18,30018,30018,300

    72/363636

    90/454545

    283/142142142

    06ET250-320 200/400 20 41.7 14 21,100 87/44 108/54 345/17306ET250-360 200/400 20 41.7 14 21,100 87/44 108/54 345/17306ET250-620 ** 400 20 41.7 14 21,100 44 54 17306ET250-660 ** 400 20 41.7 14 21,100 44 54 173

    6 CYLINDER ... AIR CONDITIONING ... 60 HZ06ET265-1( )0 † 575 25 65 19 33,600 46 57 16406ET265-3( )0 † 208-230/460 25 65 19 33,600 112/56 140/70 446/22306ET265-6( )0 **† 460 25 65 19 33,600 56 70 22306ET175-1( )0 † 575 25 75 19 33,600 46 57 16406ET175-3( )0 † 208-230/460 25 75 19 33,600 112/56 140/70 446/22306ET175-6( )0 **† 460 25 75 19 33,600 56 70 22306ET275-1( )0 † 575 30 75 19 39,100 52 65 17606ET275-3( )0 † 208-230/460 30 75 19 39,100 135/68 168/84 506/25306ET275-6( )0 **† 460 30 75 19 39,100 68 84 25306ET299-1( )0 † 575 40 99 19 54,000 78 97 24006ET299-3( )0 † 208-230/460 40 99 19 54,000 189/95 236/118 690/34506ET299-6( )0 **† 460 40 99 19 54,000 95 118 345

    6 CYLINDER ... AIR CONDITIONING ... 50 HZ06ET265-320 200/400 25 54 19 28,000 112/56 140/70 446/22306ET265-360 200/400 25 54 19 28,000 112/56 140/70 446/22306ET265-620 ** 400 25 54 19 28,000 56 70 22306ET265-660 ** 400 25 54 19 28,000 56 70 22306ET175-320 200/400 25 62.5 19 28,000 112/56 140/70 446/22306ET175-360 200/400 25 62.5 19 28,000 112/56 140/70 446/22306ET175-620 ** 400 25 62.5 19 28,000 56 70 22306ET175-660 ** 400 25 62.5 19 28,000 56 70 22306ET275-320 200/400 30 62.5 19 32,600 135/68 168/84 506/25306ET275-360 200/400 30 62.5 19 32,600 135/68 168/54 506/25306ET275-620 ** 400 30 62.5 19 32,600 68 84 25306ET275-660 ** 400 30 62.5 19 32,600 68 84 25306ET299-320 200/400 40 82.5 19 45,000 189/95 236/118 690/34506ET299-360 200/400 40 82.5 19 45,000 189/95 236/118 690/34506ET299-620 ** 400 40 82.5 19 45,000 95 118 34506ET299-660 ** 400 40 82.5 19 45,000 95 118 345

  • 120

    CARLYLE SEMI-HERMETIC COMPRESSORS

    REQUIRED CIRCUIT BREAKERS: 06E ... 60 HZ (AC DUTY)

    COMPRESSORMODEL NO.

    CIRCUITBREAKERS

    P/N06EX150-160 HH83XB447

    06EX150-360HH83XE612†

    HH83XB360††HH83XB446†††

    06EX150-660 HH83XB44606EX250-160 HH83XB446

    06EX250-360HH83XE622†

    HH83XB336††HH83XB437†††

    06EX250-660 HH83XE62606EX266-160 HH83XB436

    06EX266-360HH83XE664†

    HH83XC409††HH83XB455†††

    06EX266-660 HH83XE63006EX265-160 HH83XB436

    06EX265-360HH83XE627†

    HH83XC409††HH83XB417†††

    06EX265-660 HH83XE63006EX175-160 HH83XB436

    COMPRESSORMODEL NO.

    CIRCUITBREAKERS

    P/N06ET175-620,-660 HH83XE62506ET250-120,-160 HH83XB446

    06ET250-320,-360HH83XE622†

    HH83XB336††HH83XB437†††

    06ET250-620,-660 HH83XE62606ET265-120,-160 HH83XB433

    06ET265-320,-360HH83XE664†

    HH83XC409††HH83XB455†††

    06ET265-620,-660 HH83XE62506ET275-120,-160 HH83XB424

    06ET275-320,-360HH83XE615†

    HH83XC439††HH83XB471†††

    06ET275-620,-660 HH83XE64306ET299-120,-160 HH83XB425

    06ET299-320,-360HH83XE660†

    HH83XC437††HH83XE662†††

    06ET299-620,-660 HH83XE662

    COMPRESSORMODEL NO.

    CIRCUITBREAKERS

    P/N

    06EX175-360HH83XE664†

    HH83XC409††HH83XB455†††

    06EX175-660 HH83XE63006EX275-160 HH83XB424

    06EX275-360HH83XE615†

    HH83XC439††HH83XB471†††

    06EX275-660 HH83XE64206EX299-160 HH83XB425

    06EX299-360HH83XE660†

    HH83XC437††HH83XE662†††

    06EX299-660 HH83XE66206ET150-120 HH83XB447

    06ET150-360HH83XE612†

    HH83XB360††HH83XB446†††

    06ET150-620,-660 HH83XB44606ET175-120,-160 HH83XB436

    06ET175-320,-360HH83XE664†

    HH83XC409††HH83XB455†††

    REQUIRED CIRCUIT BREAKERS: 06E ... 50 HZ

    COMPRESSORMODEL NO.

    CIRCUITBREAKERS

    P/N

    06EX150-360HH83XE612†

    HH83XB360††HH83XB446†††

    06EX250-360HH83XE622†

    HH83XB336††HH83XB437†††

    06EX250-660 HH83XE626

    06EX266-360HH83XE664†

    HH83XC409††HH83XB455†††

    06EX266-660 HH83XE630

    06EX265-360HH83XE627†

    HH83XC409††HH83XB417†††

    06EX265-660 HH83XE630

    06EX175-360HH83XE664†

    HH83XC409††HH83XB455†††

    06EX175-660 HH83XE630

    COMPRESSORMODEL NO.

    CIRCUITBREAKERS

    P/N

    06EX275-360HH83XE615†

    HH83XC439††HH83XB471†††

    06EX275-660 HH83XE642

    06EX299-360HH83XE660†

    HH83XC437††HH83XE662†††

    06EX299-660 HH83XE662

    06ET150-32006ET150-360

    HH83XE612†HH83XB360††HH83XB446†††

    06ET250-32006ET250-360

    HH83XE622†HH83XB336††HH83XB437†††

    06ET250-620HH83XE626

    06ET250-660

    06ET265-32006ET265-660

    HH83XE664†HH83XC409††HH83XB455†††

    COMPRESSORMODEL NO.

    CIRCUITBREAKERS

    P/N06ET265-620

    HH83XE62506ET265-660

    06ET175-32006ET175-360

    HH83XE664†HH83XC409††HH83XB455†††

    06ET175-620HH83XE625

    06ET175-660

    06ET275-32006ET275-360

    HH83XE615†HH83XC439††HH83XB471†††

    06ET275-620HH83XE643

    06ET275-660

    06ET299-32006ET299-360

    HH83XE660†HH83XC437††HH83XE662†††

    06ET299-620HH83XE662

    06ET299-660

    NOTE: Circuit breakers listed for Discrete 460V Compressors are sized for part wind start.†This circuit breaker is used when Multi-Volt Compressor is connected for 208/230V PWS operation.

    ††This circuit breaker is used when Multi-Volt Compressor is connected for 208/230V XL operation.†††This circuit breaker is used when Multi-Volt Compressor is connected for 460V XL operation.Accessory Screw Package for Circuit Breakers (Required) - P/N 06EA660102 (not used with HH83XA4_- Series Breakers).

    Generally, for a compressor changeout in a Carrier/BDP unit the use of existing circuit breaker(s) is acceptable.

  • 121

    CARLYLE SEMI-HERMETIC COMPRESSORS

    REQUIRED ACCESSORIES - 06EOPTIONAL ACCESSORIES

    COMPRESSORMODEL NO.

    TERMINALBOX KIT

    SUCTIONSERVICE

    VALVE KIT

    ALTERNATESUCTIONSERVICE

    VALVE KIT

    DISCHARGESERVICE

    VALVE KIT

    ALTERNATEDISCHARGE

    SERVICEVALVE KIT

    SUSPENSIONKIT

    MOUNTINGPLATE KIT

    06ET150 06EA660095 06EA660090 - 06DA660064 - 06EA660089 06EA660096250 - 06DA660064 -265 - 06DA660065 06EA660090175 06EA660091 - 06DA660065 06EA660090275 - 06DA660065 06EA660090199 - 06EA660090 -299 - 06EA660090 -

    06EX150 06EA660095 06EA660090 - 06DA660064 -250 - 06DA660064 -166 - 06DA660064 -266 - 06DA660064 -265 - 06DA660065 06EA660090175 06EA660091 - 06DA660065 06EA660090275 - 06DA660065 06DA660090199 - 06EA660090 -299 - 06EA660090 -

    06EY150 06EA660095 06EA660091 - 06DA660064 - 06EA660089 06EA660096166 - 06DA660064 -175 - 06DA660065 06EA660090099 - 06DA660065 06EA660090

    06EZ150 - 06DA660064 -266 - 06DA660064 -175 - 06DA660065 06EA660090199 - 06DA660065 06EA660090

  • 122

    CARLYLE SEMI-HERMETIC COMPRESSORS/ACCESSORIES

    SUCTION CUTOFF UNLOADING VS. HOT GAS BYPASS UNLOADINGSince 1981 many of the Commercial Products Carrier produced with 06E compressors utilized “Suction Cutoff Unloading” in place of Hot GasBypass Unloading.

    It is easy to identify a suction cutoff unloading compressor from a hot gas bypass unloading compressor. This can be done in one of two ways:

    #1) The Finished Goods (new) compressor model number is different than the hot gas bypass model number.

    #2) The unloading heads themselves physically look different.

    compressorfamily

    compressorsize

    voltage

    2 - one electric unloader

    3 - two electric unloaders

    4 - one pressure unloader

    5 - two pressure unloaders

    6 - one electric unloader

    7 - two electric unloaders Reversed Center Head8 - one pressure unloader (6 cylinder)9 - two pressure unloaders

    SUCTION CUTOFF06E 2 275 660

    compressorfamily

    compressorsize

    voltage

    B - one electric unloader

    C - two electric unloaders

    D - one pressure unloader

    E - two pressure unloaders

    J - one electric unloader

    K - two electric unloaders Reversed Center HeadL - one pressure unloader (6 cylinder)N - two pressure unloaders

    HOT GAS BYPASS06E B 275 660

    Suction Cutoff Hot Gas Bypass

    P66 P67

    The parts used in Hot Gas Bypass are different from those used in Suc-tion Cutoff Unloading. These differences are:

    The valve plate gasket for both Hot Gas Bypass and Suction Cutoff is06EA504884.

    Both hot gas bypass and suction cutoff use the same Control ValvePackages:

    These control valves are similar to those you used in the past except thatthe bypass piston is now separate from the valve and the pressure controlvalve has had internal modifications that allow it to operate on suction cut-off applications.

    PART NUMBERSHOT GASBYPASS

    SUCTIONCUTOFF

    Valve Plate Package 06EA660105 06EA660137Cylinder Head Gasket 06EA503314 06EA503334

    Cylinder Head - 06EA503524

    Pressure Control Valve P/N 06EA660100

    Electric Control Valve P/N 06EA660135P68

    Suction CutoffValve Plate

    Suction Cutoff Cylinder Head Gasket

  • 123

    CARLYLE SEMI-HERMETIC COMPRESSORS/ACCESSORIES

    06D SUCTION CUTOFF UNLOADING KITS

    ELECTRICALLYOPERATED

    P/N: 06DA660089

    PRESSURE OPERATED

    (Not recommended forrefrigeration application.)

    P/N: 06DA660090

    ELECTRIC CAPACITY CONTROLMODIFICATION PACKAGE PART NO.: 06DA660089

    The capacity control valve in this package is actuated by an electricsole-noid. The solenoid is either energized or de-energized by theaction of an external controller. The solenoid coil is not supplied withthis package.

    This package can be used to (1) convert an 06D compressor with hotgas bypass unloading to electrically operated suction cutoff unloading,(2) add unloading or (3) add a second bank of unloading to an 06Dcompressor.

    The kit consist of the following:

    Cylinder Head Assembly (incl. capacity control valve)Valve Plate GasketCylinder Head GasketCylinder Head BoltsInstructions

    Solenoid Coils for electric unloader valve.

    PRESSURE CAPACITY CONTROLMODIFICATION PACKAGE PART NO.: 06DA660090

    NOT RECOMMENDED FOR REFRIGERATION APPLICATIONS

    The capacity control valve in this package is controlled by suctionpressure and actuated by discharge pressure.

    This package can be used to (1) convert an 06D compressor with hotgas bypass unloading to suction cutoff unloading, (2) add unloading, or(3) add a second bank of unloading to an 06D compressor. The kit con-sists of the following:

    Cylinder Head Assembly (incl. capacity control valve)Valve Plate GasketCylinder Head GasketCylinder Head BoltsInstructions

    SUCTION CUTOFF UNLOADINGREPAIR KIT PART NO.: 06DA660111

    This kit contains the parts used internally for the suction cutoff unload-ing head. It is used for both electric and pressure operated suction cut-off unloading applications. The kit does not contain the capacitycontrol valve. The kit contains the following:

    Piston and RingValve BodySpringCapacity Control Valve GasketCover GasketStrainerInstructions

    PART NO. VOLTAGEEF19ZE024 24EF19ZE120 120EF19ZE240 208-240

    Suction cutoff unloading is the “state of the art” unload-ing method for the 06E/06D compressors. There aresubstantial energy savings and improved compressorreliability when a hot gas bypass unloading system isreplaced with suction cutoff unloading.

    06DA660089

    06DA660090

    P64

    P65

  • 124

    CARLYLE SEMI-HERMETIC COMPRESSORS/ACCESSORIES

    06E SUCTION CUTOFF UNLOADING KITELECTRIC CAPACITY CONTROLMODIFICATION PACKAGE PART NO.: 06EA660138

    The capacity control valve in this package is actuated by an electric sole-noid. The solenoid is either energized or de-energized by the action of anexternal controller. The solenoid coil is not supplied with this package.

    This package can be used to (1) convert an 06E compressor with hot gasbypass unloading to electrically operated suction cutoff unloading, (2) addunloading, or (3) add a second bank of unloading to an 06E compressor.

    The kit contains the following:

    Cylinder Head Assembly (incl. capacity control valve)

    Valve Plate Gaskets (AC & Ref.)Suction ValvesCylinder Head GasketCapscrewsWashersInstructions

    Solenoid coils for electric unloader valve:

    PRESSURE CAPACITY CONTROLMODIFICATION PACKAGE PART NO.: 06EA660139NOT RECOMMENDED FOR REFRIGERATION APPLICATIONS

    The capacity control valve in this package is controlled by suction pressureand actuated by discharge pressure.

    This package can be used to (1) convert an 06E compressor with hot gasbypass unloading to pressure operated suction cutoff unloading, (2) addunloading, or (3) add a second bank of unloading to an 06E compressor.

    The kit contains the following:

    Cylinder Head Assembly (incl. capacity control valve)

    Valve Plate Gaskets (AC & Ref.)Suction ValvesCylinder Head GasketCapscrewsWashersWrenchInstructions

    SUCTION CUTOFF UNLOADINGREPAIR KIT PART NO.: 06EA660079

    This kit contains the parts used internally for the suction cutoff unloadinghead. It is used for both electric and pressure operated suction cutoffunloading applications.

    The kit does not contain the capacity control valve. The kit contains thefollowing:

    Piston and Ring

    Valve BodySpringCapacity Control Valve GasketCover GasketStrainerInstructions

    PART NO VOLTAGEEF19ZE024 24EF19ZE120 120EF19ZE240 208-240

    Suction cutoff unloading is the “state of the art” unloading methodfor the 06E/06D compressors. There are substantial energy sav-ings and improved compressor reliability when a hot gas bypassunloading system is replaced with suction cutoff unloading.

    CONTROL VALVE KITSThese kits contain the capacity control valve. The 06D and 06E com-pressors use the same capacity control valve. (The piston assembly isused with hot gas bypass unloading only.)

    06EA660100 Pressure operated kit contains thefollowing:Pressure Operated Capacity Control ValveCapacity Control Valve GasketPiston Assembly (for HGBP)WrenchInstructions

    06EA660135 Electrically operated kit contains thefollowing:Electrically Operated Capacity Control Valve (Selectappropriate solenoid coil: 24, 120, or 208-240V)Capacity Control Valve GasketPiston Assembly (for HGBP)Instructions

  • 125

    CARLYLE SEMI-HERMETIC COMPRESSORS/ACCESSORIES

    CRANKCASE HEATERSBAR/STRIP STYLE06D, 2 CYL. AND 4 CYL. 8, 9, 13, 16 CFM MODELS

    CRANKCASE HEATERS06D, 06E, 06CC, 06CY

    Dimensions: 71/2″ Long, 1″ Wide, 1/2″ Thick

    WATTS VOLTSLEAD

    LENGTH(in.)

    CONDUITLENGTH

    (in.)P/N

    50 115 39 24 06DA66009150 230 39 24 06DA660092

    P73

    • NEW STRAIGHT TUBE HEATER DESIGN

    • KIT CONTAINS CRANKCASE HEATER, RETAINER CLIP ANDANTI-SHORT BUSHING, HEAT CONDUCTING GREASE(P/N: 38AQ680001)

    CRANKCASEHEATER

    PACKAGE

    HEATERNUMBER

    VOLTS WATTSCONDUITLENGTH

    (in.)

    WIRELENGTH

    (in.)06EA660165 HT36DM132 115 180 19″ 24″06EA660167 HT36DM134 115 180 52″ 73″06EA660166 HT36DM432 230 180 19″ 24″06EA660168 HT36DM434 230 180 52″ 73″06DA660076 HT36DL480 480 125 NONE 24″06EA660107 HT36FL379 120 125 52″ 73″06EA660108 HT36FL479 240 125 52″ 73″

    P74

  • 126

    CARLYLE SEMI-HERMETIC COMPRESSORS/ACCESSORIES

    OPTIONAL ACCESSORIES - 06D AND 06E

    06E TERMINAL LUGS

    CYLINDER HEAD COOLING FAN PACKAGE

    06D TERMINAL LUG PACKAGE (6 TERMINAL LUGSAND SET SCREWS PER PKG.)

    P/N

    06DR 06DR660014 208/230-1-60/1550 RPM

    06EY 06ER660011 208/230-1-60/1550 RPM

    P/N: 06DA660095

    P54

    06E ACCESSORY ACROSS-THE-LINE JUMPERBAR KIT WITH JAM NUTS

    P/N: 06EA660141

    06D Replacement Terminal Plate KitP/N: 06DA660-134

    Replacement Gasket OnlyP/N: 6 D 40 1061

    P56

    Terminal Lug Socket Tool

    P/N: P920-0009

    P/N: HY85TB004, -008

    NOTE: For some 200/230 volt across the line installations, the connection of 3 power wires to thecompressor may not be possible because the wire diameter may be too large to fit the below listedlugs. In these instances we recommend that 6 motor leads and 6 terminal lugs be used to connect tothe compressor terminal plate. The use of 6 leads (instead of 3) allows for a wire size reduction. Con-sult the National Electric Code or your local electric code for the appropriate wire sizing information.

    FITS WIRE SIZE P/N

    #8 to #4 HY85TB008 *

    * 6 per package

    #4 to #1 HY85TB004P55

  • 127

    CARLYLE SEMI-HERMETIC COMPRESSORS/ACCESSORIES

    06D TERMINAL BOX KITS

    This kit consists of the terminal box and cover plus all screws, wash-ers, and terminals.

    NOTE: Separate terminal lug package is available. Part No.06DA660095 (contains 6 terminal lugs and set screws per pkg.)

    06DA660075 can be used in place of 06DA660078 Terminal Box andCover Package if overloads are to be used with the compressor. How-ever, it may be necessary to field fabricate a mounting box spacer toallow the 06DA660075 box to mount on the compressor body withoutinterfering with the Compressor Terminal Insulator.

    The 06DA660078 Terminal Box and Cover Package mounts directlyto the Terminal Plate.

    P/N: 06DA660075

    P/N: 06DA660078

    P69N

    P70

    P71

    06E TERMINAL BOX KITS

    This kit consists of the terminal box, cover, gasket and 3 cover plates(one blank, one with 3 knockouts, one with concentric knockouts).Screws are included.

    P/N: 06EA660095

    P72

  • 128

    CARLYLE SEMI-HERMETIC COMPRESSORS/ACCESSORIES

    06D, 06E LUBE OIL CONTROL

    06D, 06E COMPRESSORMOUNTING PLATE KIT

    This universal mounting plate kit will accommodate any size 06D or 06Ecompressor offered by RCD. The kit includes the predrilled mountingplate, spacers and template.

    P/N: 06EA660096

    06D, 06E ELECTRONIC LUBE OILCONTROL

    • Solid State• LED’S continuously display

    status of the compressorlubrication system.

    • When control is connected to06E bearing head or6D68-952A (new 06D bearinghead) external tubing is elimi-nated.

    • Timing is not cumulative as incontrols using a thermal tim-ing circuit. Each time a low oilpressure condition is sensedthe time delay will be of fullduration.

    • Short cycle protection - select either 35, 65 or 100 secondtime delay periods to prevent rapid cycling (feature can alsobe bypassed)

    • Manual Reset

    P/N: 06DA660115

    P/N: 060B2008

    P59N

    P60

    P57

    SPECIAL GASKET FORTRANSDUCER & BEARING HEADCONNECTION

    P/N: 06DA680-063

    06D, 06E SUSPENSION KIT

    Suspension kit consists of mounting springs, studs, rubber snubbers,spring retainers, nuts and washers.

    P58

    COMPRESSORMODEL NO.

    SUSPENSIONKIT PART NO.

    06ET15006EA660089250

    265175275299

    06EX150250166266265175275199299

    06EY15006EA660089

    166175099

    06EZ150266175199

    06DX8186 06DA6600567246 06DA6600578246328633765376

    06DR1096 06DA6600580136 06DA6600563166 06DA6600567186 06DA6600568206 06DA6600567246 06DA6600572286 06DA6600573376 06DA660057

    06DM8086 06DA6600583136 06DA6600563166 06DA6600568186 06DA6600563376 06DA6600575376 06DA6600577246 06DA6600578246 06DA660057

    06CC016 06DA660057018 06DA660057124 06DA660057228 06DA660057337 06DA660057550 06EA660089665 06EA660089675 06EA660089899 06EA660089

    COMPRESSORMODEL NO.

    SUSPENSIONKIT PART NO.

  • 129

    CARLYLE SEMI-HERMETIC COMPRESSORS/ACCESSORIES

    SHIPPING PAD INFORMATION

    06DA501032 - Blank-off for both 06D & 06E unloader heads.

    MODELSUCTION VALVEBLANK OFF PAD

    SUCTION VALVEPAD GASKET

    DISCHARGE VALVEBLANK OFF PAD

    DISCHARGE VALVEPAD GASKET

    06DR109 - 6D23-1421 - 6D23-142106DR013, -316 6D43-2473 6D40-1131 - 6D23-142106DR718, -820 5F30-5012 6D68-1131 - 6D23-142106DR724, -228, -337 5F30-5012 6D68-1131 6D43-2473 6D40-1131

    06DM808 - 6D23-1421 - 6D23-142106DM313, -316, -818 6D43-2473 6D40-1131 - 6D23-1421

    06DM724, -824:2 BOLT SUCTION VALVE 6D43-2473 6D40-1131 6D43-2473 6D40-11314 BOLT SUCTION VALVE 5F30-5012 6D68-1131 6D43-2473 6D40-1131

    06DM337, -537 5F30-5012 6D68-1131 6D43-2473 6D40-1131

    06DX818 6D43-2473 6D40-1131 - 6D23-142106DX724, -824:2 BOLT SUCTION VALVE 6D43-2473 6D40-1131 6D43-2473 6D40-11314 BOLT SUCTION VALVE 5F30-5012 6D68-1131 6D43-2473 6D40-1131

    06DX328, -337, -537 5F30-5012 6D68-1131 6D43-2473 6D40-1131

    06ET150, -250 5F30-5012 6D68-1131 6D43-2473 6D40-113106ET265 5F30-5012 6D68-1131 5F30-5012 6D68-113106ET175, -275, -199, -299 06EA402653 06EA500181 5F30-5012 6D68-1131

    06EX150, -250 5F30-5012 6D68-1131 6D43-2473 6D40-113106EX265 5F30-5012 6D68-1131 5F30-5012 6D68-113106EX166 5F30-5012 6D68-1131 6D43-2473 6D40-113106EX175, -275, -199, -299 06EA402653 06EA500181 5F30-5012 6D68-1131

    06EY150, -165 06EA402653 06EA500181 6D43-2473 6D40-113106EY166, -175, -099 06EA402653 06EA500181 5F30-5012 6D68-1131

    06EZ150, -266 06EA402653 06EA500181 6D43-2473 6D40-113106EZ175, -199 06EA402653 06EA500181 5F30-5012 6D68-1131

  • 130

    CARLYLE SEMI-HERMETIC COMPRESSORS/ACCESSORIES

    06D,E CONTROL PANELSThe 06D & E Control Panels include:

    * 120 v Control Circuits* High, Low and Oil Pressure Switches* Time Guard* Compressor Contactor(s)* Control, Pump Out, and Timer Relays* Time Delay and Crankcase Heater Relay (06E panels only)* Fuse* Terminal Block

    * On-Off Switch* Compatible with other manufacturer’s compressors (with

    similar electrical characteristics)

    NOTE: The panels listed for the 06D compressors do not haveoverload protection in the panel; it is on the compressor. The06E panels contain circuit breakers. Also, the pressure switchesfor the 06D panel are attached to a bracket for field installation.The 06E panels have the pressure switches wired and mountedto the back of the panel.

    COMPRESSORMODEL

    VOLTAGEMAXRLA

    X/L ORP/W

    CONTROL BOXMODEL

    06DR1090GA3150 575 2.8 X/L 06DP14006DR1090GA3250 208/230 8.6 X/L 06DP14006DR1090GA3650 208/230 3.9 X/L 06DP140

    06DR0130CA3150 575 5 X/L 06DP14006DR0130CA3250 208/230 12.4 X/L 06DP14006DR0130CA3650 460 6.2 X/L 06DP140

    06DR3160CA3150 575 7.7 X/L 06DP14006DR3160CA3250 208/230 19.3 X/L 06DP14006DR3160CA3650 460 9.6 X/L 06DP140

    06DR7180DA3150 575 7.7 X/L 06DP14006DR7180DA3250 208/230 19.3 X/L 06DP14006DR7180DA3650 460 9.6 X/L 06DP140

    06DR8200DA3150 575 12.6 X/L 06DP14006DR8200DA3250 208/230 31.4 X/L 06DP14006DR8200DA3650 460 15.7 X/L 06DP140

    06DR7240DA3150 575 12.6 X/L 06DP14006DR7240DA3250 208/230 31.4 X/L 06DP14006DR7240DA3650 460 15.7 X/L 06DP140

    06DR2280DA3150 575 15.9 X/L 06DP14006DR2280DA3250 208/230 39.5 X/L 06DP14006DR2280DA3650 460 19.8 X/L 06DP140

    06DR3370DA3150 575 17.9 X/L 06DP14006DR3370DA3250 208/230 44.3 X/L 06DP16006DR3370DA3650 460 22.1 X/L 06DP140

    06DM8080GA3150 575 5 X/L 06DP14006DM8080GA3250 208/230 12.4 X/L 06DP14006DM8080GA3650 460 6.2 X/L 06DP140

    06DM3130CA3150 575 7.7 X/L 06DP14006DM3130CA3250 208/230 19.3 X/L 06DP14006DM3130CA3650 460 9.6 X/L 06DP140

    06DM3160CA3150 575 7.7 X/L 06DP14006DM3160CA3250 208/230 19.3 X/L 06DP14006DM3160CA3650 460 9.6 X/L 06DP140

    06DM3370DA3150 575 17.9 X/L 06DP14006DM3370DA3250 208/230 44.3 X/L 06DP16006DM3370DA3650 460 22.1 X/L 06DP140

    06DA8182AA3150 575 12.6 X/L 06DP14006DA8182AA3250 208/230 31.4 X/L 06DP14006DA8282AA3650 460 15.7 X/L 06DP140

    06DA8242BA3150 575 15.9 X/L 06DP14006DA8242BA3250 208/230 39.6 X/L 06DP14006DA8242BA3650 460 19.8 X/L 06DP140

    06DA3282BA3150 575 17.9 X/L 06DP14006DA3282BA3250 208/230 44.3 X/L 06DP16006DA3282BA3650 460 22.1 X/L 06DP140

    06DA5372BA0150 575 22.9 X/L 06DP14006DA5372BA1250 208/230 63.6 X/L 06DP17506DA5372BA0650 460 28.6 X/L 06DP140

    COMPRESSORMODEL

    VOLTAGEMAXRLA

    X/L ORP/W

    CONTROL BOXMODEL

    06ER150000 208/230 72 X/L 06PF175-1PWS 06PF240-1

    05ER150100 575 31 X/L 06PF140-106ER150600 460 36 X/L 06PF140-2

    06ER165000 208/230 87 X/L 06PF190-1PWS 06PF250-1

    06ER165100 575 36 X/L 06PF140-306ER165600 460 44 X/L 06PF150-1

    PWS 06PF240-2

    06ER175000 208/230 87 X/L 06PF190-1PWS 06PF250-1

    06ER175100 575 36 X/L 06PF140-306ER175600 460 44 X/L 06PF150-2

    PWS 06PF240-2

    06ER099000 208/230 135 X/L 06PF275-1PWS 06PF280-1

    06ER099100 575 42 X/L 06PF160-106ER099600 460 68 X/L 06PF175-2

    PWS 06PF240-3

    06EM150000 208/230 72 X/L 06PF175-1PWS 06PF240-1

    06EM150100 575 31 X/L 06PF140-106EM150600 460 36 X/L 06PF140-2

    06EM175000 208/230 112 X/L 06PF120-1PWS 06PF260-1

    06EM175100 575 46 X/L 06PF150-306EM175600 460 56 X/L 06PF160-2

    PWS 06PF240-4

    06EM199000 208/230 155 X/L 06PF290-1PWS 06PF295-1

    06EM199100 575 62 X/L 06PF175-306EM199600 460 77 X/L 06PF190-2

    PWS 06PF250-2

    06EA250000 208/230 87 X/L 06PF190-1PWS 06PF250-3

    06EA250100 575 36 X/L 06PF140-306EA250600 460 44 X/L 06PF150-2

    PWS 06PF240-2

    06EA265000 208/230 112 X/L 06PF120-1PWS 06PF260-1

    06EA265100 575 46 X/L 06PF150-306EA265600 460 56 X/L 06PF160-2

    PWS 06PF240-5

    06EA275000 208/230 135 X/L 06PF275-1PWS 06PF280-2

    06EA275100 575 52 X/L 06PF160-106EA275600 460 68 X/L 06PF175-4

    PWS 06PF240-6

    06EA299000 208/230 189 X/L 06PF220-1PWS 06PF225-1

    06EA299100 575 75 X/L 06PF175-206EA299600 460 95 X/L 06PF120-2

    PWS 06PF250-1