Product Part Number Guide

July 2008

Page 2: Guia Especificacion Portafolio Medidores
Page 3: Guia Especificacion Portafolio Medidores

Product Part Number Guide

Rev date: July 2008 Page 3 of 28 70052-0188-41

How to print single pages

1. Place your mouse cursor on the page you want to print out.

2. From the menu File, select Print. In the Print dialog box under Page range, select Current page. Click OK.

(do not use the Print icon on the toolbar, otherwise all the pages in the entire document will be printed)

How to determine your meter part number

1. Select one Order Code from each of the ordering categories.

2. Combine these order codes to form the part number for your particular meter configuration.

3. Use that part number when you fill out your purchase order.

Brand Model Form

Factor Current inputs

Voltage inputs

Power supply

System Freq

Comm I/O Security Special Order

Example part number S 7 6 5 0 A 0 C 0 B 6 A 0 A 0 A

In the above example, the part number P7650A0C0B6E0A0A corresponds to:

Brand: S Square D brand

Model: 7650 ION7650 power meter

Form Factor: A0 Integrated display with front optical port, 5 MB logging memory, and 512 samples/cycle resolution.

Current Inputs: C 5A nominal, 20A full scale current inputs

Voltage Inputs: 0 57 to 347 VAC line-to-neutral / 100 to 600 VAC line-to-line

Power Supply: B 85-240 VAC, ±10%/47-63 Hz/110-330 VDC, ±10%

System Frequency: 6 Calibrated for 60 Hz systems

Communications: A0 1 RS-232/RS-485 port, 1 RS-485 port, infrared optical port.

Onboard I/O: A 8 digital inputs, 3 Form C relays, 4 Form A solid-state outputs

Security: 0 Password protected, no hardware lock

Special Order: A None

Page 4: Guia Especificacion Portafolio Medidores

Product Part Number Guide

Rev date: July 2008 Page 4 of 28 70052-0188-41

Revision History

Rev Date Description of change

20 September 7, 2005 Added PQDIF Exporter add-on part numbers to ION Enterprise 5.5 section.

Added RS-485/Modbus communications option to ION6300. Modified ION Wireless Repeater part number and ION6100 & ION6300 options code scheme (combined last three option code characters into one field).

Replaced ION8300/8400/8500 technical documentation/user guide part numbers with ION8600 part numbers.

21 September 19, 2005 Part number corrections for accessories.

22 October 12, 2005 Removed “power cord” from –UNI option for the COM128 and COM32 products.

23 December 2, 2005 Removed ION8600 “future release” options (C5, M5).

24 December 22, 2005 Modified ION6300 meter type description. Corrected description for CBL-8X00-IOE15FT.

25 January 12, 2006 Added RMICAN options for ION8600. Removed 8300/8400/8500 sections.

26 April 19, 2006 Description for ION8600 current input option "E" corrected to 10A.

Added ION6200 RMD without cable option.

27 May 2006 Added ION8800 product

28 June 2006 Schneider Electric rebranding. Added new brand labels for Square D and Merlin Gerin meters.

Removed MGT options from ION7700 product, per MGT Obsolescence Bulletin.

Fixed ION8600 description for Ethernet Fiber and onboard I/O options.

29 July 2006 Add OFGEM option to ION7550 and ION7650

30 August 2006 Schneider Electric rebranding. Added new brand labels for Square D and Merlin Gerin meters.

31 September 2006 New comm card for ION8600 (supports 56k modem)

32 October 2006 Removed 3000 series meters

33 November 2006 Added RMICAN options to ION7550 / ION7650

Removed DOC-UGUIDE-204 and DOC-UGUIDE-205 from ION Enterprise Documentation section

34 February 2007 Added note to OPTICAL-PROBE-USB part description

35 April 2007 Added ION8800 IRIG-B options. Updated ION Enterprise part numbers (version 5.6). Improved description of cable options for 8600 I/O Expander.

36 July 2007 Corrected description of ION8600 current input option “E”. (upper limit on accuracy should be 10A RMS)

37 November 2007 New communications card options for ION7550/ION7650. Minor textual changes for ION Enterprise product. Removed all DOC-BINDER and DOC-UGUIDE part numbers.

38 December 2007 Added "IEC 61000-4-30 Class A measurements" description to ION7650 Special Options "E" and "F".

39 March 2008 Add new communications card options to ION7550 RTU (same change as for the ION7550/ION7650).

40 May 2008 Removed CTs, VTs and terminal blocks. Removed ION7700 product line (obsolete).

41 July 2008 Changed description of brand code “M” from “Merlin Gerin” to “Schneider Electric”.

Page 5: Guia Especificacion Portafolio Medidores

Product Part Number Guide

Rev date: July 2008 Page 5 of 28 70052-0188-41

Contents

HARDWARE ....................................................................................................................................7

ION8800 ..................................................................................................................................................7 ION8800 Comm & I/O module ................................................................................................................................8 ION8800 Related Items...........................................................................................................................................8

ION8600 ..................................................................................................................................................9 ION8600 I/O Expander* ........................................................................................................................................10 ION8600 Related Items* .......................................................................................................................................10

ION7650 ................................................................................................................................................11 ION7550 ................................................................................................................................................12 ION7550 RTU ........................................................................................................................................13

ION7550 / 7650 Comm Card* ...............................................................................................................................14 ION7500 / 7600 Comm Card* ...............................................................................................................................14 ION7550/7650 Expansion I/O*..............................................................................................................................14 ION7550 and ION7650 Related Items*.................................................................................................................15

ION7350 ................................................................................................................................................16 ION7330 ................................................................................................................................................17 ION7300 ................................................................................................................................................18

ION7300 Remote Display .....................................................................................................................................19 ION7300 Series External I/O Cards (REB) ...........................................................................................................19 Output Modules For Optional External I/O Card (REB).........................................................................................19 ION7300 Series Related Items .............................................................................................................................19

ION6200 ................................................................................................................................................20 ION6200 Remote Display .....................................................................................................................................20 Cable for ION6200 Remote Display......................................................................................................................20

ION6200 Stocking Orders ......................................................................................................................21 ION6200 Meter Base ............................................................................................................................................21 ION6200 Option Card ...........................................................................................................................................21

ION6200 Power Supply..........................................................................................................................21 Communications Converters ..................................................................................................................22

COM128................................................................................................................................................................22 COM32..................................................................................................................................................................22

SOFTWARE...................................................................................................................................23

PowerLogic ION Enterprise 5.6 ..............................................................................................................23 PowerLogic ION Enterprise 5.6 Server Licensing .................................................................................................23 PowerLogic ION Enterprise 5.6 Client Licensing ..................................................................................................23 SQL Server 2005 Products ...................................................................................................................................23 New Purchases.....................................................................................................................................................23 Options..................................................................................................................................................................23 Upgrades for ION Enterprise.................................................................................................................................23 PowerLogic ION Enterprise documentation ..........................................................................................................23

Appendix A: ION8600 Custom Nameplate .................................................................................25

Page 6: Guia Especificacion Portafolio Medidores
Page 7: Guia Especificacion Portafolio Medidores

Product Part Number Guide

Rev date: July 2008 Page 7 of 28 70052-0188-41

HARDWARE

Select one code from each ordering category and fill in the boxes below. Use this group of codes when you order your ION8800.

Brand

Model Feature Set

Form Factor

Current inputs

Voltage inputs

Power supply

System Freq

Comm module

Onboard I/O & Comm

Security Special Order

8800 0 B

ION8800 Order Code

Description

M Schneider Electric Branded Brand

P Power Measurement Branded

Model 8800 ION8800 IEC/DIN 43862 19” rack mount series meter with integrated display, U1-U3 wide-range voltage inputs (57-288 VAC L-N or 99-500 VAC L-L). I1-I3 current inputs with additional I4. Supports ION, Modbus-RTU, DNP 3.0 and DLMS protocols. English and French documentation ships with every meter. For onboard I/O see comments below.

A Feature Set B + power quality analysis (waveforms and transient capture with 1024 samples/cycle resolution)

B Feature Set C + EN50160 compliant power quality monitoring

Feature Set

C Basic Tariff/Energy meter

1 10 MB logging memory, Essailec connectors Memory / Form Factor 2 5 MB logging memory, Essailec connectors

C (I1-I3): Configured for 5A nominal, 10A full scale, 14 Amp fault capture, 0.005A starting current Current Inputs

E (I1-I3): Configured for 1A nominal, 10A full scale, 14 Amp fault capture, 0.001A starting current

Voltage Inputs 0 (U1-U3): Autoranging (57-288 VAC L-N or 99-500 VAC L-L)

Power Supply B Single phase power supply: 85-240 VAC ±10% (47-63 Hz) or 110-270 ±10% VDC

5 Calibrated for 50 Hz systems System Frequency

6 Calibrated for 60 Hz systems

Z0 No Comm Module – Meter includes Base Onboard I/O and Comms (see below for details)

A0 Std. comms: 1 RS-232/RS-485 port, **1 RS-485 port (COM2)

C1 Std. comms AND 10BASE-T Ethernet (RJ-45), 56k universal internal modem (RJ-11)

D1 Std. comms AND 10BASE-T Ethernet (RJ-45) / 10BASE-FL Ethernet Fiber, 56k universal internal modem (RJ-11)

E0 Std. comms AND 10BASE-T Ethernet (RJ-45)

F0 Std. comms AND 10BASE-T Ethernet (RJ-45) / 10BASE-FL (ST fiber optic connection)

Comm Module (field serviceable)

M1 Std. comms AND 56k universal internal modem (RJ-11)

A *Base Option AND 8 Form A digital outputs, **1 RS-485 port (COM2)

B *Base Option AND 8 Form A digital outputs, 3 digital inputs (20-56 VDC/AC)

C *Base Option AND 8 Form A digital outputs, 3 digital inputs (80-280 VDC/AC)

D *Base Option AND 1 IRIG-B time sync port, **1 RS-485 port (COM2),3 digital inputs (20-56 VDC/AC)

Onboard I/O and Comms (not field serviceable, part of base unit)

E *Base Option AND 1 IRIG-B time sync port, **1 RS-485 port (COM2), 3 digital inputs (80-280 VDC/AC)

0 Password protected, no security lock Security

1 Password protected with security lock enabled

A None Special Order

C Tropicalization treatment applied

*All Onboard I/O and Comms Base Option includes: 4 Form C solid-state digital outputs, 1 Form C mechanical relay output, one IEC1107 optical communications port, two IEC1107 style optical pulsing ports.

**Channel COM2 is available on the port at the back of the meter OR on the Comm Module (if installed). You must select which terminals your communications wiring is connected to during meter setup.

Page 8: Guia Especificacion Portafolio Medidores

Product Part Number Guide

Rev date: July 2008 Page 8 of 28 70052-0188-41

Select one code from each ordering category and fill in the boxes below. Use this group of codes when you order your ION8800 Communications module.

Comm Module Type Special Order

P880C

ION8800 Comm & I/O module

Order Code

Description

Comm Module 880C ION8800 Communications module for field retrofit installations

A0 Std. comms: 1 RS-232/RS-485 port, **1 RS-485 port (COM2)

C1 Std. comms AND 10BASE-T Ethernet (RJ-45), 56k universal internal modem (RJ-11).

D1 Std. comms AND 10BASE-T Ethernet (RJ-45) / 10BASE-FL Ethernet Fiber, 56k universal internal modem (RJ-11).

E0 Std. comms AND 10BASE-T Ethernet (RJ-45).

F0 Std. comms AND 10BASE-T Ethernet (RJ-45) / 10BASE-FL (ST fiber optic connection).

M1 Std. comms AND 56k universal internal modem (RJ-11)

A None Special Order

C Tropicalization treatment applied

**Channel COM2 is available on the port at the back of the meter OR on the Comm Module (if installed). You must select which terminals your communications wiring is connected to during meter setup.

ION8800 Related Items

BATT-REPLACE-8XXX Replacement batteries for the ION8600 or ION8800, quantity 10

RACK-8800-RAW IEC/DIN 34862 19” Rack with female mating voltage/current and I/O blocks unassembled.

IEC-OPTICAL-PROBE IEC 61107 compliant Optical Probe (DB-9) for use with ION8800 meters

CD-TECHDOC Compact disc containing the latest version of technical documentation for ION hardware and software products.

Page 9: Guia Especificacion Portafolio Medidores

Product Part Number Guide

Rev date: July 2008 Page 9 of 28 70052-0188-41

Select one code from each ordering category and fill in the boxes below. Use this group of codes when you order your ION8600.

Brand Model Feature set Form Factor Current inputs Voltage inputs Power supply System Freq Comm I/O Security Special Order

8600 0

ION8600 Order Code

Description

S Square D branded

P Power Measurement branded

Brand

M Schneider Electric branded

Model 8600 ION8600 Advanced Revenue Meter

A 10MB memory, 50 data recorders (800 channels), waveform recorders, transient detection, flicker, interharmonics

B 4MB memory, 20 data recorders (320 channels), MODBUS Mastering, additional serial port

Feature Set

C 2MB memory, 2 data recorders (32 channels), sag/swell detection

0 * Form 9S Base: 57-277 V (autoranging) 3-Element, 4-Wire

1 Form 35S Base: 120-480 V (autoranging) 2-Element, 3-Wire

2 * Form 36S Base: 57-277 V (autoranging) 2 1/2-Element, 4-Wire

3 * Form 39S with neutral current input (15 Terminal Base): 57-277 V (autoranging) 3-Element, 4-Wire

N * Form 76S with neutral current input (15 Terminal Base): 57-277 V (autoranging) 2 1/2-Element, 4-Wire

4 Form 9 FT21 Switchboard (meter + case) with break out panel

5 Form 35 FT21 Switchboard (meter + case) with break out panel

6 Form 36 FT21 Switchboard (meter + case) with break out panel

7 Form 9 FT21 Switchboard (meter + case) with break out cable

8 Form 35 FT21 Switchboard (meter + case) with break out cable

Form Factor

9 Form 36 FT21 Switchboard (meter + case) with break out cable

C 5 Amp nominal, 20 Amp full scale (50 Amp fault capture, start at 0.005A, accurate from 0.05 - 20A RMS) Current Inputs E 1 Amp nominal, 10 Amp full scale (24 Amp fault capture, start at 0.001A, accurate from 0.01 - 10A RMS)

Voltage Inputs 0 Standard (see Form Factor above)

E Form 9S, 36S, 39S, 76S (socket) and Form 9, 36 (FT21 switchboard): 120-277 VAC. Form 35S (socket) and Form 35 (FT21 switchboard): 120-480 VAC. Powered from the meter's voltage connections.

G Form 9S, 36S (socket) and Form 9, 36 (FT21 switchboard): 57-70 VAC. Powered from the meter's voltage connections. NOT AVAILABLE on Form 35S and Form 35 - you must select the auxiliary power pigtail.

H Auxiliary Power Pigtail: 65-120 VAC or 80-160 VDC (power from external source)

Power Supply

J Auxiliary Power Pigtail: 160-277 VAC or 200-350 VDC (power from external source)

5 Calibrated for 50 Hz systems - NOT AVAILABLE with RMICAN or RMICAN-SEAL options System Frequency 6 Calibrated for 60 Hz systems

A0 Infrared port, RS-232/RS-485 port, RS-485 port

C1 Infrared Optical port, Ethernet (10BASE-T), 56k universal internal modem (RJ-11), RS-232/485 port (note this port is not available with Feature Set C).

C2 Same as C1, but with RJ-31 connector for the modem

E0 Infrared Optical port, Ethernet (10BASE-T), RS-232/485 port, RS-485 port (note this port is not available with Feature Set C)

F0 Infrared Optical port, Ethernet (10BASE-FL), RS-232/485 port, RS-485 port (note this port is not available with Feature Set C) This option is not available with FT21 switchboard form factors (Form Factor options 4 through 9). This option is not available with the onboard I/O option.

Communications

M1 Infrared Optical port, 56k universal internal modem (RJ-11), RS-232/485 port, RS-485 port (note this port is not available with Feature Set C)

A None Onboard I/O

B 4 Form C (KYZ) digital outputs and 3 Form A digital inputs This option is not available with Ethernet Fiber (10BASE-FL) communications option.

0 Password protected, no security lock - NOT AVAILABLE in Canada

1 Password protected with security lock enabled (requires removal of outer cover to configure billing parameters) - NOT AVAILABLE in Canada

3 RMICAN (Measurement Canada approved, security lock enabled)

Security

4 ** RMICAN-SEAL (Measurement Canada approved, factory sealed, and security lock enabled)

A None

B IRIG-B GPS time synchronization port

K *** Customer supplied template (frameworks) installed at the factory

Special Order

L *** Customer supplied template (frameworks) and IRIG-B GPS time synchronization port

To add custom text to your meter's nameplate label, fill out the ION8600 Custom Nameplate form and submit it with your order. * For Measurement Canada approved meters, allowable voltage input range is 69-277 VAC. ** A filled-out ION8600 RMICAN-SEAL Checklist must accompany each RMICAN-SEAL meter order. *** For Special Order “K” and “L”, you must also order the part number CUST-TEMP-SETUP (see ION8600 Related Items section). When the template (framework) is received, the factory will issue a 5-digit code that will be appended to the ION8600 part number.

Page 10: Guia Especificacion Portafolio Medidores

Product Part Number Guide

Rev date: July 2008 Page 10 of 28 70052-0188-41

Select one code from each ordering category and fill in the boxes below. Use this group of codes when you order your I/O Expander.

Brand I/O Expander I/O Option Cable Length

P 850E

ION8600 I/O Expander*

Order Code

Description

Brand P Schneider Electric brand

Digital/Analog I/O 850E I/O Expander for ION8600 meters: Inputs and Outputs for energy pulsing, control, energy counting, status

monitoring, and analog interface to SCADA.

A External I/O box with 8 digital inputs and 8 digital outputs (4 Form A, 4 Form C)

B External I/O box with 8 digital inputs and 4 digital outputs (4 Form C) and 4 analog outputs (0 to 20mA)

C External I/O box with 8 digital inputs and 4 digital outputs (4 Form C) and 4 analog outputs (-1mA to 1mA)

I/O Option

D External I/O box with 8 digital inputs and 4 digital outputs (4 Form C) and 4 analog outputs (two -1 to 1 mA, and two 0 to 20 mA outputs)

0 No cable

1 5ft extension cable, 24-pin male to 24-pin female Molex connector (do not use on meters with the breakout panel form factor option)

2 15ft extension cable, 24-pin male to 24-pin female Molex connector (do not use on meters with the breakout panel form factor option)

Cable Option

3 6ft connector cable, 24-pin male to 14-pin male Molex connector (use only on meters with the breakout panel form factor option)

* The I/O Expander is also supported on legacy meters ION8300, ION8400 and ION8500

ION8600 Related Items*

A-BASE-ADAPTER-9 Form 9S to Form 9A adapter (http://www.pwrm.com/products/socket_adapters/)

A-BASE-ADAPTER-35 Form 35S to Form 35A adapter (http://www.pwrm.com/products/socket_adapters/)

A-BASE-ADAPTER-39 Form 39S to Form 39A adapter (http://www.pwrm.com/products/socket_adapters/)

A-BASE-ADAPTER-76 Form 76S to Form 76A adapter (http://www.pwrm.com/products/socket_adapters/)

OPTICAL-PROBE Serial Optical Probe (DB-9) via IR port

OPTICAL-PROBE-USB Serial Optical Probe (USB) via IR port. Note: This probe supports all ION meters with ANSI optical ports except

ION8600 meters manufactured before November 2006.

CBL-8X00BRKOUT 5ft Breakout Cable: 24-pin female Molex connector to one DB9 female connector for RS-232, and 2 sets of twisted pair wires for two RS-485 port connections

CBL-8X00IOE5FT 5ft extension cable, mates with 24-pin male Molex connector from the meter to the 24-pin female Molex connector on the I/O Expander box (not for use with breakout panel E8, F8 & G8 form factors)

CBL-8X00IOE15FT 15ft extension cable, mates with 24-pin male Molex connector from the meter to the 24-pin female Molex connector on the I/O Expander box (not for use with breakout panel E8, F8 & G8 form factors)

CBL-8XX0-BOP-IOBOX 6ft connector cable, 24-pin male to 14-pin male Molex connector for connecting an ION8000 series meter with breakout panel to an I/O Expander Box

CUST-TEMP-SETUP Set up (or modification) charge for customer supplied template (framework) at time of shipment

BATT-REPLACE-8XXX Replacement batteries for the ION8600, quantity 10

ION-SETUP Configuration software for ION8600 meters. Ships on a CD.

CD-TECHDOC Compact disc containing the latest version of technical documentation for ION hardware and software products.

* ION8600 related items are also supported on legacy meters ION8300, ION8400 and ION8500

Page 11: Guia Especificacion Portafolio Medidores

Product Part Number Guide

Rev date: July 2008 Page 11 of 28 70052-0188-41

Select one code from each ordering category and fill in the boxes below. Use this group of codes when you order your ION7650.

Brand Model Form Factor Current inputs Voltage inputs Power supply System Freq Comm I/O Security Special Order

7650 0

ION7650 Order Code

Description

S Square D branded

P Power Measurement branded

Brand

M Schneider Electric branded

Model 7650 ION7650: Advanced meter with wide-range voltage inputs (57-347V line-neutral or 100-600V line-line),

transient detection, data and waveform recording. Supports ION, Modbus-RTU, and DNP 3.0 protocols.

A0 Integrated display with front optical port, 5 MB logging memory, and 512 samples/cycle resolution.

A1 Integrated display with front optical port, 5 MB logging memory, and 1024 samples/cycle resolution.

B0 Integrated display with front optical port, 10 MB logging memory, and 512 samples/cycle resolution.

B1 Integrated display with front optical port, 10 MB logging memory, and 1024 samples/cycle resolution.

T0 Transducer (no display) version, with 5 MB logging memory, and 512 samples/cycle resolution.

T1 Transducer (no display) version, with 5 MB logging memory, and 1024 samples/cycle resolution.

U0 Transducer (no display) version, with 10 MB logging memory, and 512 samples/cycle resolution.

Form Factor

U1 Transducer (no display) version, with 10 MB logging memory, and 1024 samples/cycle resolution.

C 5 Amp nominal, 20 Amp full scale current input

E 1 Amp nominal, 10 Amp full scale current input

F Current Probe Inputs (for use with 0-1 VAC current probes; probes sold separately) - NOT AVAILABLE with OFGEM option

Current Inputs

G Current Probe Inputs with three Universal Technic 10A clamp on CTs; meets IEC 1036 accuracy - NOT AVAILABLE with OFGEM option

Voltage Inputs 0 57 to 347 VAC line-to-neutral / 100 to 600 VAC line-to-line

B Standard power supply (85-240 VAC, ±10%/47-63 Hz / 110-330 VDC, ±10%) Power Supply

C Low voltage DC power supply (20-60 VDC)

5 Calibrated for 50 Hz systems System Frequency

6 Calibrated for 60 Hz systems. NOT AVAILABLE with OFGEM option

A0 Standard communications (1 RS-232/RS-485 port, 1 RS-485 port). Integrated display models also include 1 ANSI Type 2 optical communications port.

C1 Standard communications plus 10BASE-T/100BASE-TX Ethernet (RJ-45), 56k universal internal modem (RJ-11). Ethernet and modem gateway functions each use a serial communications port.

D1 Standard communications plus 10BASE-T Ethernet (RJ-45) and 10BASE-FL Ethernet Fiber, 33.6k universal internal modem (RJ-11). Ethernet and modem gateway functions each use a serial communications port.

D7 Standard communications plus 10BASE-T/100BASE-TX Ethernet (RJ-45) and 100BASE-FX Ethernet Fiber, 56k universal internal modem (RJ-11). Ethernet and modem gateway functions each use a serial communications port.

E0 Standard communications plus 10BASE-T/100BASE-TX Ethernet (RJ-45). Ethernet gateway function uses a serial communications port.

F0 Standard communications plus 10BASE-T Ethernet (RJ-45) and 10BASE-FL (ST fiber optic connection). Ethernet gateway function uses a serial communications port.

F1 Standard communications plus 10BASE-T/100BASE-TX Ethernet (RJ-45) and 100BASE-FX (SC fiber optic connection). Ethernet gateway function uses a serial communications port.

Communications

M1 Standard communications plus 56k universal internal modem (RJ-11). Modem gateway function uses a serial communications port.

A Standard I/O (8 digital inputs, 3 Form C relays, 4 Form A solid-state outputs)

D Standard I/O plus Expansion I/O card (8 additional digital inputs & four 0 to 1 mA analog inputs)

E Standard I/O plus Expansion I/O card (8 additional digital inputs & four 0 to 20 mA analog inputs)

H Standard I/O plus Expansion I/O card (8 additional digital inputs & four -1 to 1 mA analog outputs)

K Standard I/O plus Expansion I/O card (8 additional digital inputs & four 0 to 20 mA analog outputs)

N Standard I/O plus Expansion I/O card (8 additional Digital In & four 0 to 20 mA analog inputs & four 0 to 20 mA outputs)

I/O

P Standard I/O plus Expansion I/O card (8 additional Digital In & four 0 to 1 Analog Inputs & four -1 to 1 mA analog outputs)

0 Password protected, no hardware lock

1 Password protected and hardware lockable (lock enabled/disabled via jumper on comm card)

3 *RMICAN Measurement Canada approved, security lock enabled

4 *RMICAN-SEAL Measurement Canada approved, factory sealed, security lock enabled

Security

6 Password protected with security lock enabled, terminal cover and UK OFGEM labels

A None

C Tropicalization treatment applied

E EN50160 compliance monitoring and IEC 61000 4-30 Class A measurements, no tropicalization treatment

Special Order

F EN50160 compliance monitoring and IEC 61000 4-30 Class A measurements, with tropicalization treatment

* RMICAN approval for Delta mode sealing is not yet available. Please contact factory for details.

Page 12: Guia Especificacion Portafolio Medidores

Product Part Number Guide

Rev date: July 2008 Page 12 of 28 70052-0188-41

Select one code from each ordering category and fill in the boxes below. Use this group of codes when you order your ION7550.

Brand Model Form Factor Current inputs Voltage inputs Power supply System Freq Comm I/O Security Special Order

7550 0

ION7550 Order Code

Description

S Square D branded

P Power Measurement branded

Brand

M Schneider Electric branded

Model 7550 ION7550: Advanced meter with wide-range voltage inputs (57-347 line-neutral or 100-600V line-line), sag/swell detection, data and waveform recording, and 256 samples/cycle resolution. Supports ION, Modbus RTU and DNP 3.0 protocols.

A0 Integrated display with front optical port and 5 MB logging memory

B0 Integrated display with front optical port and 10 MB logging memory.

T0 Transducer (no display) version, with 5 MB logging memory.

Form Factor

U0 Transducer (no display) version, with 10 MB logging memory.

C 5 Amp nominal, 20 Amp full scale current input

E 1 Amp nominal, 10 Amp full scale current input

F Current Probe Inputs (for use with 0-1 VAC current probes; probes sold separately) - NOT AVAILABLE with OFGEM option

Current Inputs

G Current Probe Inputs with three Universal Technic 10A clamp on CTs; meets IEC 1036 accuracy - NOT AVAILABLE with OFGEM option

Voltage Inputs 0 57 to 347 VAC line-to-neutral / 100 to 600 VAC line-to-line

B Standard power supply (85-240 VAC, ±10%/47-63 Hz / 110-330 VDC, ±10%) Power Supply

C Low voltage DC power supply (20-60 VDC)

5 Calibrated for 50 Hz systems System Frequency

6 Calibrated for 60 Hz systems. NOT AVAILABLE with OFGEM option

A0 Standard communications (1 RS-232/RS-485 port, 1 RS-485 port). Integrated display models also include 1 ANSI Type 2 optical communications port.

C1 Standard communications plus 10BASE-T/100BASE-TX Ethernet (RJ-45), 56k universal internal modem (RJ-11). Ethernet and modem gateway functions each use a serial communications port.

D1 Standard communications plus 10BASE-T Ethernet (RJ-45) and 10BASE-FL Ethernet Fiber, 33.6k universal internal modem (RJ-11). Ethernet and modem gateway functions each use a serial communications port.

D7 Standard communications plus 10BASE-T/100BASE-TX Ethernet (RJ-45) and 100BASE-FX Ethernet Fiber, 56k universal internal modem (RJ-11). Ethernet and modem gateway functions each use a serial communications port.

E0 Standard communications plus 10BASE-T/100BASE-TX Ethernet (RJ-45). Ethernet gateway function uses a serial communications port.

F0 Standard communications plus 10BASE-T Ethernet (RJ-45) and 10BASE-FL (ST fiber optic connection). Ethernet gateway function uses a serial communications port.

F1 Standard communications plus 10BASE-T/100BASE-TX Ethernet (RJ-45) and 100BASE-FX (SC fiber optic connection). Ethernet gateway function uses a serial communications port.

Communications

M1 Standard communications plus 56k universal internal modem (RJ-11). Modem gateway function uses a serial communications port.

A Standard I/O (8 digital inputs, 3 Form C relays, 4 Form A solid-state outputs)

D Standard I/O plus Expansion I/O card (8 additional digital inputs & four 0 to 1 mA analog inputs)

E Standard I/O plus Expansion I/O card (8 additional digital inputs & four 0 to 20 mA analog inputs)

H Standard I/O plus Expansion I/O card (8 additional digital inputs & four -1 to 1 mA analog outputs)

K Standard I/O plus Expansion I/O card (8 additional digital inputs & four 0 to 20 mA analog outputs)

N Standard I/O plus Expansion I/O card (8 additional digital inputs & four 0 to 20 mA analog inputs and four 0 to 20 mA outputs)

I/O

P Standard I/O plus Expansion I/O card (8 additional digital inputs & four 0 to 1 analog inputs & four -1 to 1 mA analog outputs)

0 Password protected, no hardware lock

1 Password protected and hardware lockable (lock enabled/disabled via jumper on comm card)

3 *RMICAN Measurement Canada approved, security lock enabled

4 *RMICAN-SEAL Measurement Canada approved, factory sealed, security lock enabled

Security

6 Password protected with security lock enabled, terminal cover and UK OFGEM labels

A None Special Order

C Tropicalization treatment applied

* RMICAN approval for Delta mode sealing is not yet available. Please contact factory for details.

ION7550 / ION7650 Comm Cards, Expansion I/O Cards, OpenDAC racks, modules and accessories, and related items are listed on

pages 14-15.

Page 13: Guia Especificacion Portafolio Medidores

Product Part Number Guide

Rev date: July 2008 Page 13 of 28 70052-0188-41

Select one code from each ordering category and fill in the boxes below. Use this group of codes when you order your ION7550 RTU.

Brand Model Form Factor RTU Option Power supply Internal Use Comm I/O Security Special Order

7550 N9 9 0

ION7550 RTU Order Code

Description

S Square D branded

P Power Measurement branded

Brand

M Schneider Electric branded

Model 7550 ION7550 device

A0 Integrated display with front optical port and 5 MB logging memory

B0 Integrated display with front optical port and 10 MB logging memory.

T0 Transducer (no display) version, with 5 MB logging memory.

Form Factor

U0 Transducer (no display) version, with 10 MB logging memory.

RTU Option N9 RTU option

B Standard power supply (85-240 VAC, ±10%/47-63 Hz / 110-330 VDC, ±10%) Power Supply

C Low voltage DC power supply (18-75 VDC)

Internal Use 9 This field for internal use only

A0 Standard communications (1 RS-232/RS-485 port, 1 RS-485 port). Integrated display models also include 1 ANSI Type 2 optical communications port.

C1 Standard communications plus 10BASE-T/100BASE-TX Ethernet (RJ-45), 56k universal internal modem (RJ-11). Ethernet and modem gateway functions each use a serial communications port.

D1 Standard communications plus 10BASE-T Ethernet (RJ-45) and 10BASE-FL Ethernet Fiber, 33.6k universal internal modem (RJ-11). Ethernet and modem gateway functions each use a serial communications port.

D7 Standard communications plus 10BASE-T/100BASE-TX Ethernet (RJ-45) and 100BASE-FX Ethernet Fiber, 56k universal internal modem (RJ-11). Ethernet and modem gateway functions each use a serial communications port.

E0 Standard communications plus 10BASE-T/100BASE-TX Ethernet (RJ-45). Ethernet gateway function uses a serial communications port.

F0 Standard communications plus 10BASE-T Ethernet (RJ-45) and 10BASE-FL (ST fiber optic connection). Ethernet gateway function uses a serial communications port.

F1 Standard communications plus 10BASE-T/100BASE-TX Ethernet (RJ-45) and 100BASE-FX (SC fiber optic connection). Ethernet gateway function uses a serial communications port.

Communications

M1 Standard communications plus 56k universal internal modem (RJ-11). Modem gateway function uses a serial communications port.

A Standard I/O (8 digital inputs, 3 Form C relays, 4 Form A solid-state outputs)

D Standard I/O plus Expansion I/O card (8 additional digital inputs & four 0 to 1 mA analog inputs)

E Standard I/O plus Expansion I/O card (8 additional digital inputs & four 0 to 20 mA analog inputs)

H Standard I/O plus Expansion I/O card (8 additional digital inputs & four -1 to 1 mA analog outputs)

K Standard I/O plus Expansion I/O card (8 additional digital inputs & four 0 to 20 mA analog outputs)

N Standard I/O plus Expansion I/O card (8 additional digital inputs & four 0 to 20 mA analog inputs and four 0 to 20 mA outputs)

I/O

P Standard I/O plus Expansion I/O card (8 additional digital inputs & four 0 to 1 analog inputs & four -1 to 1 mA analog outputs)

Security 0 Password protected

A None Special Order

C Tropicalization treatment applied

Page 14: Guia Especificacion Portafolio Medidores

Product Part Number Guide

Rev date: July 2008 Page 14 of 28 70052-0188-41

Select one code from each ordering category and fill in the boxes below. Use this group of codes when you order your ION7550/7650 Comm Card.

Comm Card Type Special Order

P765C

ION7550 / 7650 Comm Card*

Order Code

Description

Comm Card P765C ION7550 / ION7650 Communications card for field retrofit installations

A0 Standard communications (1 RS-232/RS-485 port, 1 RS-485 port). Front optical port support for meters with integrated display.

C1 Standard communications plus 10BASE-T/100BASE-TX Ethernet (RJ-45), 56k universal internal modem (RJ-11; the modem port is shared with the front optical port). Ethernet and modem gateway functions each use a serial communications port.

D7 Standard communications plus 10BASE-T/100BASE-TX Ethernet, 100BASE-FX Ethernet Fiber, 56k universal internal modem (RJ-11; the modem port is shared with the front optical port). Ethernet and modem gateway functions each use a serial communications port.

E0 Standard communications plus 10BASE-T/100BASE-TX Ethernet. Ethernet gateway function uses a serial communications port.

F1 Standard communications plus 10BASE-T/100BASE-TX Ethernet, 100BASE-FX Ethernet Fiber (SC fiber optic connection). Ethernet gateway function uses a serial communications port.

Type

M1 Standard communications plus 56k universal internal modem (RJ-11; the modem port is shared with the front optical port). Modem gateway function uses a serial communications port.

A None Special Order

C Tropicalization treatment applied

* Firmware v350 or higher required. The 7550/7650 communications card is not supported on legacy meters ION7500 and ION7600. Select one code from each ordering category and fill in the boxes below. Use this group of codes when you order your ION7500/7600 Comm Card.

Comm Card Type Special Order

P760C

ION7500 / 7600 Comm Card*

Order Code

Description

Comm Card P760C ION7500 / ION7600 Communications card for field retrofit installations

A0 Standard communications (1 RS-232/RS-485 port, 1 RS-485 port). Front optical port support for meters with integrated display.

C1 Standard communications plus 10BASE-T Ethernet (RJ-45), 33.6k universal internal modem (RJ-11; the modem port is shared with the front optical port). Ethernet and modem gateway functions each use a serial communications port.

D1 Standard communications plus 10BASE-T Ethernet, 10BASE-FL Ethernet Fiber, 33.6k universal internal modem (RJ-11; the modem port is shared with the front optical port). Ethernet and modem gateway functions each use a serial communications port.

E0 Standard communications plus 10BASE-T Ethernet. Ethernet gateway function uses a serial communications port.

F0 Standard communications plus 10BASE-T Ethernet, 10BASE-FL Ethernet Fiber. Ethernet gateway function uses a serial communications port.

Type

M1 Standard communications plus 33.6k universal internal modem (RJ-11; the modem port is shared with the front optical port). Modem gateway function uses a serial communications port.

A None Special Order

C Tropicalization treatment applied

Select one code from each ordering category and fill in the boxes below. Use this group of codes when you order your ION7550/7650 I/O Card.

Expansion I/O Type Special Order

P760A

ION7550/7650 Expansion I/O*

Order Code

Description

I/O Card P760A ION7550 / ION7650 Expansion I/O card for field retrofit installations

D Expansion I/O card with eight digital inputs, four 0 to 1 mA analog inputs

E Expansion I/O card with eight digital inputs, four 0 to 20 mA analog inputs

H Expansion I/O card with eight digital inputs, four -1 to 1 mA analog outputs

K Expansion I/O card with eight digital inputs, four 0 to 20 mA analog outputs

N Expansion I/O card with eight digital inputs, four 0 to 20 mA analog inputs & four 0 to 20 mA outputs

Type

P Expansion I/O card with eight digital inputs, four 0 to 1 analog inputs and four -1 to 1 mA analog outputs

A None Special Order

C Tropicalization treatment applied

* The 7550/7650 expansion I/O card is also supported on legacy meters ION7500 and ION7600

Page 15: Guia Especificacion Portafolio Medidores

Product Part Number Guide

Rev date: July 2008 Page 15 of 28 70052-0188-41

ION7550 and ION7650 Related Items*

ADPT-37XX-7500 Adapter plate enabling the 7550 or 7650 to fit into a 3710 or 3720 ACM panel cutout

TERMCVR-7500 Terminal strip cover for the 7550 or 7650

M1UB10A1V-10A 10 A / 1 VAC Universal Technic Clamp On Current Probe

P32UEP813-1000A 1000 A / 1 VAC Universal Technic Clamp On Current Probe

P32UEP815-3000A 3000 A / 1 VAC Universal Technic Clamp On Current Probe

SCT0750-005-5A 5 A / 0.333 VAC Magnelabs Split Core Current Probe

SCT1250-300-300A 300 A / 0.333 VAC Magnelabs Split Core Current Probe

CD-TECHDOC Compact disc containing the latest version of technical documentation for ION hardware and software products.

* 7550/7650 accessories and related items are also supported on legacy meters ION7500 and ION7600

Page 16: Guia Especificacion Portafolio Medidores

Product Part Number Guide

Rev date: July 2008 Page 16 of 28 70052-0188-41

Select one code from each ordering category and fill in the boxes below. Use this group of codes when you order your ION7350.

Brand Model Form Factor Current inputs Voltage inputs Power supply System Freq Comm I/O Security Special Order

7350 B 0 0

ION7350 Order Code

Description

S Square D branded

P Power Measurement branded

Brand

M Schneider Electric branded

Model 7350 ION7350: Advanced power meter with basic sag/swell detection, waveform recording, harmonics (up to the

31st), high-speed data logging and automatic modem dial-out, multiport communications, 4 digital inputs and 4 digital outputs.

A0 Integrated display, with front optical port

A2 Same as A0, but with CWC (captured wire connector); max 277VAC on voltage inputs

A6 Same as A0, but meter installed in S1 switchboard retrofit cage (with cover and casing)

A7 Same as A0, but meter installed in FT21 (D4B-7F, D4B-3F) switchboard retrofit cage (with cover and casing)

A8 Same as A0, but meter installed in S1 switchboard retrofit cage (with cover, but no casing)

A9 Same as A0, but meter installed in FT21 (D4B-7F, D4B-3F) switchboard retrofit cage (with cover, but no casing)

R0 Transducer with RMD (remote display), with front optical port. DOES NOT support Analog Input and/or Analog Output options.

R1 Same as R0, but with DIN rail mounts on the transducer. DOES NOT support Analog Input and/or Analog Output options.

R2 Same as R0, but with CWC (captured wire connector) inputs on the transducer; maximum 277VAC on voltage inputs. DOES NOT support Analog Input and/or Analog Output options.

R3 Same as R0, but with DIN rail mounts and CWC (captured wire connector) inputs on the transducer; maximum 277VAC on voltage inputs. DOES NOT support Analog Input and/or Analog Output options.

T0 Transducer (no display). Note you cannot use an RMD on this meter if you order the Analog Input and/or Analog Output options.

T1 Transducer (no display) with DIN rail mount. Note you cannot use an RMD on this meter if you order the Analog Input and/or Analog Output options.

T2 Transducer (no display) with CWC (captured wire connector) inputs; maximum 277VAC on voltage inputs. Note you cannot use an RMD on this meter if you order the Analog Input and/or Analog Output options.

Form Factor

T3 Transducer (no display) with DIN rail mount and CWC (captured wire connector) inputs; maximum 277VAC on voltage inputs. Note you cannot use an RMD on this meter if you order the Analog Input and/or Analog Output options.

Current Inputs B 5 Amp nominal, 10 Amp full scale current input

Voltage Inputs 0 Autoranging (50 to 347 VAC +25%) Warning: Maximum 277 VAC for CWC connector type.

B P240 power supply (95-240VAC/47-440Hz/120-310 VDC) Power Supply

C P24 power supply (20 to 65 VDC)

System Frequency 0 Autoranging (50 and 60 Hz)

A0 Two RS-485 ports.

C1 One RS-485 EtherGate port, one RS-485 ModemGate port, 10BASE-T Ethernet (RJ-45), 33.6k universal internal modem (RJ-11). DOES NOT support Analog Input and/or Analog Output options.

C3 Same as C1, but with CWC (captured wire connectors) for the modem. DOES NOT support Analog Input and/or Analog Output options.

E0 One 10BASE-T Ethernet (RJ-45) port, one RS-485 port, one RS-485 EtherGate port.. DOES NOT support Analog Input and/or Analog Output options.

M1 One 33.6k universal internal modem (RJ-11) port, one RS-485 port, one RS-485 ModemGate port.

Communications

M3 Same as M1, but with CWC (captured wire connectors) for the modem.

A No analog inputs/outputs. You must choose this option if ordering RMD remote display options (Form Factor types "R") or Ethernet port options (Communications types "C" or "E").

D Four 0 to 1 mA analog inputs. NOT AVAILABLE with RMD or Ethernet options

E Four 0 to 20 mA analog inputs. NOT AVAILABLE with RMD or Ethernet options

J Four 0 to 1 mA analog outputs. NOT AVAILABLE with RMD or Ethernet options

K Four 0 to 20 mA analog outputs. NOT AVAILABLE with RMD or Ethernet options

M Four 0 to 1 mA analog inputs & four 0 to 1 mA analog outputs. NOT AVAILABLE with RMD or Ethernet options

I/O

N Four 0 to 20 mA analog inputs & four 0 to 20 mA analog outputs. NOT AVAILABLE with RMD or Ethernet options

0 Password protected, no hardware lock

2 Password protected with hardware lock enabled

Security

6 Password protected with security lock enabled, terminal cover and UK OFGEM labels

A None

B Pre-set to MODBUS (available for Form Factor T0, T1, T2 and T3 only)

C Tropicalization treatment applied

Special Order

D Tropicalization treatment applied and pre-set to MODBUS (available for Form Factor T0, T1, T2 and T3 only)

Page 17: Guia Especificacion Portafolio Medidores

Product Part Number Guide

Rev date: July 2008 Page 17 of 28 70052-0188-41

Select one code from each ordering category and fill in the boxes below. Use this group of codes when you order your ION7330.

Brand Model Form Factor Current inputs Voltage inputs Power supply System Freq Comm I/O Security Special Order

7330 B 0 0

ION7330 Order Code

Description

S Square D branded

P Power Measurement branded

Brand

M Schneider Electric branded

Model 7330 ION7330: Advanced power meter with over 200 high accuracy, 3-phase measurements, data logging, multiport communications, 4 digital inputs and 4 outputs.

A0 Integrated display, with front optical port

A2 Same as A0, but with CWC (captured wire connector) inputs; maximum 277VAC on voltage inputs.

A6 Same as A0, but meter installed in S1 switchboard retrofit cage (with cover and casing). Not available with Security options RMICAN or RMICAN-SEAL.

A7 Same as A0, but meter installed in FT21 (D4B-7F, D4B-3F) switchboard retrofit cage (with cover and casing). Not available with Security options RMICAN or RMICAN-SEAL.

A8 Same as A0, but meter installed in S1 switchboard retrofit cage (with cover, but no casing). Not available with Security options RMICAN or RMICAN-SEAL.

A9 Same as A0, but meter installed in FT21 (D4B-7F, D4B-3F) switchboard retrofit cage (with cover, but no casing). Not available with Security options RMICAN or RMICAN-SEAL.

R0 Transducer with RMD (remote display), with front optical port. DOES NOT support Analog Input and/or Analog Output options. Not available with Security options RMICAN or RMICAN-SEAL.

R1 Same as R0, but with DIN rail mounts on the transducer. DOES NOT support Analog Input and/or Analog Output options. Not available with Security options RMICAN or RMICAN-SEAL.

R2 Same as R0, but with CWC (captured wire connector) inputs on the transducer; maximum 277VAC on voltage inputs. DOES NOT support Analog Input and/or Analog Output options. Not available with Security options RMICAN or RMICAN-SEAL.

R3 Same as R0, but with DIN rail mounts and CWC (captured wire connector) inputs on the transducer; maximum 277VAC on voltage inputs. DOES NOT support Analog Input and/or Analog Output options. Not available with Security options RMICAN or RMICAN-SEAL.

T0 Transducer (no display). Note you cannot use an RMD on this meter if you order the Analog Input and/or Analog Output options. Not available with Security options RMICAN or RMICAN-SEAL.

T1 Transducer (no display) with DIN rail mount. Note you cannot use an RMD on this meter if you order the Analog Input and/or Analog Output options. Not available with Security options RMICAN or RMICAN-SEAL.

T2 Transducer (no display) with CWC (captured wire connector) inputs; maximum 277VAC on voltage inputs. Note you cannot use an RMD on this meter if you order the Analog Input and/or Analog Output options. Not available with Security options RMICAN or RMICAN-SEAL.

Form Factor

T3 Transducer (no display) with DIN rail mount and CWC (captured wire connector) inputs; maximum 277VAC on voltage inputs. Note you cannot use an RMD on this meter if you order the Analog Input and/or Analog Output options. Not available with Security options RMICAN or RMICAN-SEAL.

Current Inputs B 5 Amp nominal, 10 Amp full scale current input

Voltage Inputs 0 Autoranging (50 to 347 VAC +25%) Warning: Maximum 277 VAC for CWC connector type.

B P240 power supply (95-240VAC/47-440Hz/120-310 VDC) Power Supply

C P24 power supply (20 to 65 VDC)

System Frequency

0 Autoranging (50 and 60 Hz)

A0 Two RS-485 ports.

C1 One RS-485 EtherGate port, one RS-485 ModemGate port, 10BASE-T Ethernet (RJ-45), 33.6k universal internal modem. DOES NOT support Analog Input and/or Analog Output options.

C3 Same as C1, but with CWC (captured wire connectors) for the modem. DOES NOT support Analog Input and/or Analog Output options.

E0 One 10BASE-T Ethernet (RJ-45) port, one RS-485 port, one RS-485 EtherGate port. DOES NOT support Analog Input and/or Analog Output options.

M1 One 33.6k universal internal modem (RJ-11) port, one RS-485 port, one RS-485 ModemGate port.

Communications

M3 Same as M1, but with CWC (captured wire connectors) for the modem.

A No analog inputs/outputs. You must choose this option if ordering RMD remote display options (Form Factor types "R") or Ethernet port options (Communications types "C" or "E").

D Four 0 to 1 mA analog inputs. NOT AVAILABLE with RMD or Ethernet options

E Four 0 to 20 mA analog inputs. NOT AVAILABLE with RMD or Ethernet options

J Four 0 to 1 mA analog outputs. NOT AVAILABLE with RMD or Ethernet options

K Four 0 to 20 mA analog outputs. NOT AVAILABLE with RMD or Ethernet options

M Four 0 to 1 mA analog inputs & four 0 to 1 mA analog outputs. NOT AVAILABLE with RMD or Ethernet options

I/O

N Four 0 to 20 mA analog inputs & four 0 to 20 mA analog outputs. NOT AVAILABLE with RMD or Ethernet options

0 Password protected, no hardware lock

2 Password protected with hardware lock enabled

3 RMICAN Measurement Canada approved

4 **RMICAN-SEAL Measurement Canada approved, factory sealed

Security

6 Password protected with security lock enabled, terminal cover and UK OFGEM labels

A None

B Pre-set to MODBUS (available for Form Factor T0, T1, T2 and T3 only). Not available with Security options RMICAN or RMICAN-SEAL.

C Tropicalization treatment applied

Special Order

D Tropicalization treatment applied and pre-set to MODBUS (available for Form Factor T0, T1, T2 and T3 only). Not available with Security options RMICAN or RMICAN-SEAL.

** A filled-out ION7300 Series RMICAN-SEAL Checklist must accompany each RMICAN-SEAL meter order.

Page 18: Guia Especificacion Portafolio Medidores

Product Part Number Guide

Rev date: July 2008 Page 18 of 28 70052-0188-41

Select one code from each ordering category and fill in the boxes below. Use this group of codes when you order your ION7300.

Brand Model Form Factor Current inputs Voltage inputs Power supply System Freq Comm I/O Security Special Order

7300 B 0 0

ION7300 Order Code Description

S Square D branded

P Power Measurement branded

Brand

M Schneider Electric branded

Model 7300 ION7300: Advanced power meter with over 100 high accuracy, 3-phase measurements, 1 RS-485 communication port and 4 digital outputs. Supports ION and Modbus-RTU protocols.

A0 Integrated display, with front optical port

A2 Same as A0, but with CWC (captured wire connector) inputs; maximum 277VAC on voltage inputs.

A6 Same as A0, but meter installed in S1 switchboard retrofit cage (with cover and casing). Not available with Security options RMICAN or RMICAN-SEAL.

A7 Same as A0, but meter installed in FT21 (D4B-7F, D4B-3F) switchboard retrofit cage (with cover and casing). Not available with Security options RMICAN or RMICAN-SEAL.

A8 Same as A0, but meter installed in S1 switchboard retrofit cage (with cover, but no casing). Not available with Security options RMICAN or RMICAN-SEAL.

A9 Same as A0, but meter installed in FT21 (D4B-7F, D4B-3F) switchboard retrofit cage (with cover, but no casing). Not available with Security options RMICAN or RMICAN-SEAL.

D0 Display-only model (Integrated display only. No communications. No digital outputs, no analog inputs or outputs). Not available with Security options RMICAN or RMICAN-SEAL.

D2 Same as D0, but with CWC (captured wire connector) inputs. Not available with Security options RMICAN or RMICAN-SEAL.

R0 Transducer with RMD (remote display), with front optical port. DOES NOT support Analog Input and/or Analog Output options. Not available with Security options RMICAN or RMICAN-SEAL.

R1 Same as R0, but with DIN rail mounts on the transducer. DOES NOT support Analog Input and/or Analog Output options. Not available with Security options RMICAN or RMICAN-SEAL.

R2 Same as R0, but with CWC (captured wire connector) inputs on the transducer; maximum 277VAC on voltage inputs. DOES NOT support Analog Input and/or Analog Output options. Not available with Security options RMICAN or RMICAN-SEAL.

R3 Same as R0, but with DIN rail mounts and CWC (captured wire connector) inputs on the transducer; maximum 277VAC on voltage inputs. DOES NOT support Analog Input and/or Analog Output options. Not available with Security options RMICAN or RMICAN-SEAL.

T0 Transducer (no display). Note you cannot use an RMD on this meter if you order the Analog Input and/or Analog Output options. Not available with Security options RMICAN or RMICAN-SEAL.

T1 Transducer (no display) with DIN rail mount. Note you cannot use an RMD on this meter if you order the Analog Input and/or Analog Output options. Not available with Security options RMICAN or RMICAN-SEAL.

T2 Transducer (no display) with CWC (captured wire connector) inputs; maximum 277VAC on voltage inputs. Note you cannot use an RMD on this meter if you order the Analog Input and/or Analog Output options. Not available with Security options RMICAN or RMICAN-SEAL.

Form Factor

T3 Transducer (no display) with DIN rail mount and CWC (captured wire connector) inputs; maximum 277VAC on voltage inputs. Note you cannot use an RMD on this meter if you order the Analog Input and/or Analog Output options. Not available with Security options RMICAN or RMICAN-SEAL.

Current Inputs B 5 Amp nominal, 10 Amp full scale current input

Voltage Inputs 0 Autoranging (50 to 347 VAC +25%) Warning: Maximum 277 VAC for CWC connector type.

B P240 power supply (95-240VAC/47-440Hz/120-310 VDC) Power Supply

C P24 power supply (20 to 65 VDC)

System Freq 0 Autoranging (50 and 60 Hz)

Z0 No communications. You must choose this option if you selected Display model (Form Factor D0 or D2 above).

A0 One RS 485 port

E0 One RS 485 port, one 10BASE-T Ethernet (RJ-45)

Communications

P0 One RS 485 port, one Profibus communications. Available only on Integrated Display models (Form Factor type "A" only).

A No analog inputs/outputs. You must choose this option if ordering Display-only or RMD remote display options (Form Factor types “D” or "R"), or Ethernet or Profibus port options (Communications options "E0", or “P0”).

D Four 0 to 1 mA analog inputs. NOT AVAILABLE with RMD or Ethernet options

E Four 0 to 20 mA analog inputs. NOT AVAILABLE with RMD or Ethernet options

J Four 0 to 1 mA analog outputs. NOT AVAILABLE with RMD or Ethernet options

K Four 0 to 20 mA analog outputs. NOT AVAILABLE with RMD or Ethernet options

M Four 0 to 1 mA analog inputs & four 0 to 1 mA analog outputs. NOT AVAILABLE with RMD or Ethernet options

I/O

N Four 0 to 20 mA analog inputs & four 0 to 20 mA analog outputs. NOT AVAILABLE with RMD or Ethernet options

0 Password protected, no hardware lock

2 Password protected with hardware lock enabled

3 RMICAN Measurement Canada approved

4 **RMICAN-SEAL Measurement Canada approved, factory sealed

Security

6 Password protected with security lock enabled, terminal cover and UK OFGEM labels

A None

B Pre-set to MODBUS (available for Form Factor T0, T1, T2 and T3 only). Not available with Security options RMICAN or RMICAN-SEAL.

C Tropicalization treatment applied

Special Order

D Tropicalization treatment applied and pre-set to MODBUS (available for Form Factor T0, T1, T2 and T3 only). Not available with Security options RMICAN or RMICAN-SEAL.

** A filled-out ION7300 Series RMICAN-SEAL Checklist must accompany each RMICAN-SEAL meter order.

Page 19: Guia Especificacion Portafolio Medidores

Product Part Number Guide

Rev date: July 2008 Page 19 of 28 70052-0188-41

Select one code from each ordering category and fill in the boxes below. Use this group of codes when you order your ION7300/ION7330/ION7350 Remote Modular Display.

Brand Display Type

ION7300 Remote Display

Order Code

Description

S Square D branded

P Power Measurement branded

Brand

M Schneider Electric branded

RMD-7300 ION7300 Remote Modular Display with 6 ft. DB25 cable

RMD-7330 ION7330 Remote Modular Display with 6 ft. DB25 cable

Display Type*

RMD-7350 ION7350 Remote Modular Display with 6 ft. DB25 cable

* Remote Modular Display cannot be used with TRAN units that contain an analog I/O card

ION7300 Series External I/O Cards (REB)

REB Relay Expansion Board: 4-position Grayhill I/O Board and external P240 power supply

REB-P24/48 Same as REB, but comes with 20-60VDC power supply instead

Output Modules For Optional External I/O Card (REB)

GDOAC120 120 VAC, 3.5A, N.O. solid state relay digital output module

GDOAC120MO 120 VAC, 3.5A, N.O. solid state relay digital output module with manual override

GDOAC240 240 VAC, 3.5A, N.O. solid state relay digital output module

GDOAC240MO 240 VAC, 3.5A, N.O. solid state relay digital output module with manual override

GDODC60 60 VDC, 3.5A, N.O. solid state relay digital output module

GDODC60MO 60 VDC, 3.5A, N.O. solid state relay digital output module with manual override

GDODC60L 60 VDC, 1.0A, low leakage, N.O. solid state relay digital output module

GDODC200 200 VDC, 1.0A, N.O. solid state relay digital output module

GDODC100M 100 VDC, 0.5A, N.O. mechanical relay digital output module

ION7300 Series Related Items

GSKT Water resistant gasket

OPTICAL-PROBE Serial Optical Probe (DB-9) via IR port

OPTICAL-PROBE-USB Serial Optical Probe (USB62H) via IR port

ADPT-37XX-73XX Adapter plate enabling an ION73xx to fit a 3710/3720 panel cutout

RAP Adapter plate to mount an ION73xx in an ANSI C39.1 (round hole) cutout

ACCUREPORT Factory generated accuracy graph

TERMCVR-73XX Terminal strip cover

73XXCS-S1 S1 switchboard meter casing

73XXCS-FT21 FT21 switchboard meter casing

CD-TECHDOC Compact disc containing the latest version of technical documentation for ION hardware and software products.

Page 20: Guia Especificacion Portafolio Medidores

Product Part Number Guide

Rev date: July 2008 Page 20 of 28 70052-0188-41

Select one code from each ordering category and fill in the boxes below. Use this group of codes when you order your ION6200.

Brand Model Form Factor Current inputs Voltage inputs Power supply System Freq Comm I/O Security Measurements

6200 A 0 0

ION6200 Order Code

Description

S Square D branded

P Power Measurement branded

Brand

M Schneider Electric branded

Model 6200 ION6200 Meter Kit: ION6200 Meter base, Options Card and Power Supply.

A0 Integrated display model

R1 Transducer model with DIN rail mount, Remote Display and 14-ft cable (RJ-11, 6 conductor, 26 gauge).

R2 Transducer model with DIN rail mount, Remote Display and 6-ft cable (RJ-11, 6 conductor, 26 gauge).

R3 Transducer model DIN rail mount, Remote Display and 30-ft cable (RJ-11, 6 conductor, 26 gauge).

T1 Transducer model with DIN rail mount (requires Comms or pulse outputs)

M0 MegaWatt option on Integrated Display model. Not available with Security options RMICAN or RMICAN-SEAL.

N1 MegaWatt option on Transducer model with DIN rail mount, Remote Display and 14-ft cable (RJ-11, 6 conductor, 26 gauge). Not available with Security options RMICAN or RMICAN-SEAL.

N2 MegaWatt option on Transducer model with DIN rail mount, Remote Display and 6-ft cable (RJ-11, 6 conductor, 26 gauge). Not available with Security options RMICAN or RMICAN-SEAL.

Form Factor

N3 MegaWatt option on Transducer model with DIN rail mount, Remote Display and 30-ft cable (RJ-11, 6 conductor, 26 gauge). Not available with Security options RMICAN or RMICAN-SEAL.

Current Inputs A 10 Amp current inputs (12 Amp max)

Voltage Inputs 0 Autoranging (57-400 VAC L-N / 99-690 VAC L-L)

B P620PB: Standard Plug-in Power Supply (100-240 VAC / 50-60 Hz or 110-300 VDC)

C P620PC: Low voltage DC Plug-in Power Supply (20-60 VDC)

Power Supply

D P620PD: 480 V power supply (480 VAC, 60Hz)

System Frequency 0 Calibrated for use with 50 Hz or 60 Hz systems

Z0 No communications Communications

A0 Single RS-485 port (supports Modbus RTU protocol and ION-compatible PML protocol)

A No I/O I/O

B This option activates the two Form A digital outputs for kWh, kVARh or kVARh energy pulsing

0 No hardware lock (setup is password protected)

2 RMANSI: Revenue Meter approved for use in the United States (ANSI C12.16 approved; meets ANSI C12.20 class 0.5 accuracy at 23°C; 10A current inputs only)

3 RMICAN: Measurement Canada approved revenue meter for use in Canada (10A current inputs only)

Security

4 **RMICAN-SEAL: Factory-sealed and Measurement Canada approved revenue meter

N Standard Measurements (Volts/Amps per phase and avg)

P Enhanced Package #1 (Standard Measurements plus Energy/Power total, Frequency, Power Factor total, Neutral Current

Measurement Package

R Enhanced Package #2 (all measurements)

** A filled-out ION6200 RMICAN-SEAL Checklist must accompany each RMICAN-SEAL meter order.

Select one code from each ordering category and fill in the boxes below. Use this group of codes when you order your ION6200 Remote Display.

Brand Model Display Type Cable Length

620D

ION6200 Remote Display

Order Code

Description

S Square D branded

P Power Measurement branded

Brand

M Schneider Electric branded

Model 620D Remote Display Unit for the ION6200 Transducer meter base

R Standard display Display Type

N MegaWatt option — for use with Transducer meter base with MegaWatt option. - NOT AVAILABLE for RMICAN or RMICAN-SEAL meters

0 No cable Cable Length

1 14-ft cable for connecting Remote Display Unit to the ION6200 Transducer meter base.

Cable for ION6200 Remote Display

P620C1 14-ft cable for connecting Remote Display Unit to the ION6200 Transducer meter base.

P620C2 6-ft cable for connecting Remote Display Unit to the ION6200 Transducer meter base.

P620C3 30-ft cable for connecting Remote Display Unit to the ION6200 Transducer meter base.

Page 21: Guia Especificacion Portafolio Medidores

Product Part Number Guide

Rev date: July 2008 Page 21 of 28 70052-0188-41

ION6200 Stocking Orders

The ION6200 is made up of three separate components: the Meter Base, Option Card and Power Supply. Each of these components are required to create one complete ION6200.

The following order scheme is intended for customers who purchase for stocking purposes. For stocking orders, customers have the option of purchasing quantities of the separate components (i.e. meter base, option card & power supply) and then mixing and matching them as required to serve their needs.

Select one code from each ordering category and fill in the boxes below. Use this group of codes when you order your ION6200 Meter Base.

Brand Model Form Factor Current inputs Voltage inputs System Freq

620B A 0 0

ION6200 Meter Base

Order Code

Description

S Square D branded

P Power Measurement branded

Brand

M Schneider Electric branded

Model 620B ION6200 meter base

A0 Integrated Display on meter base

M0 MegaWatt option on meter base with Integrated Display - NOT AVAILABLE for RMICAN or RMICAN-SEAL meters

Form Factor

T1 Transducer meter base with DIN rail mounts - NOT AVAILABLE for RMICAN or RMICAN-SEAL meters

Current Inputs A 10 Amp current inputs (12 Amp max)

Voltage Inputs 0 Auto-ranging (57-400 VAC L-N / 99-690 VAC L-L)

System Freq 0 Calibrated for use with 50 Hz or 60 Hz systems

Select one code from each ordering category and fill in the boxes below. Use this group of codes when you order your ION6200 Option Card.

Model Comm I/O Security Measurements

P620K

ION6200 Option Card

Order Code

Description

Model P620K Option Card to activate basic and advanced features on the ION6200.

Z0 No communications Communications

A0 Single RS-485 port (supports Modbus RTU protocol and PML protocol)

A No I/O I/O

B This option activates the two Form A digital outputs for kWh, kVARh or kVARh energy pulsing

0 No hardware lock (setup is password protected)

2 RMANSI: Revenue Meter approved for use in the United States (ANSI C12.16 approved; meets ANSI C12.20 class 0.5 accuracy at 23°C; 10A current inputs only)

3 RMICAN: Measurement Canada approved revenue meter for use in Canada (10A current inputs only)

Security

4 RMICAN-SEAL: Factory-sealed and Measurement Canada approved revenue meter

N Standard Measurements (Volts/Amps per phase and avg)

P Enhanced Package #1 (Standard Measurements plus Energy/Power total, Frequency, Power Factor total, Neutral Current)

Measurement Options

R Enhanced Package #2 (all measurements)

ION6200 Power Supply

P620PB Standard Plug-in Power Supply (100-240 VAC / 50-60 Hz or 110-300 VDC) for the ION6200.

P620PC Low voltage DC Plug-in Power Supply (20-60 VDC) for the ION6200.

P620PD 480V power supply (480VAC, 60Hz) for the ION6200.

Page 22: Guia Especificacion Portafolio Medidores

Product Part Number Guide

Rev date: July 2008 Page 22 of 28 70052-0188-41

Communications Converters

COM128 Multiport RS-232 to RS-485 converter; handles four loops of 32 devices. Includes 120VAC to 9-30VDC adapter.

COM128-UNI COM128 with universal power supply (90-264VAC @ 47-63 Hz).

COM128-IND COM128 with mountable universal power supply (85-264VAC @ 47-440Hz / 110-340VDC) with terminal strip connector.

COM32 Single RS-232 to RS-485 converter; handles one loop of 32 devices. Includes 120VAC to 9VDC adapter.

COM32-UNI COM32 with universal power supply (90-264VAC @ 47-63 Hz).

COM32-IND COM32 with mountable universal power supply (85-264VAC @ 47-440Hz / 110-340VDC) with terminal strip connector.

COM32-NOPWR COM32 with no power supply included. Comes with 12” pigtail with spade lug connectors. Requires power source of 9VDC @ 500 mA.

Page 23: Guia Especificacion Portafolio Medidores

Product Part Number Guide

Rev date: July 2008 Page 23 of 28 70052-0188-41

SOFTWARE

PowerLogic ION Enterprise 5.6

PowerLogic ION Enterprise 5.6 Server Licensing

Every new system must be ordered with one (1) IONE56-BASE software and a minimum of five (5) IONE56-DL device licenses. The IONE56-BASE software includes all PowerLogic ION Enterprise applications (Communications, database components, Vista, Reporter, WebReach, Virtual Processor, OPC Client), for installation and use on a single PC (server or workstation).

Beyond the first 5 devices, the customer has the ability to order the exact number of devices required for the system. As the customer adds devices, additional device licenses can be ordered (minimum 5 devices).

PowerLogic ION Enterprise 5.6 Client Licensing

A client license is required for all PCs running PowerLogic ION Enterprise applications (e.g. Vista, Reporter, Management Console, or any combination of these), or PCs that use Terminal Services or Remote Desktop to access the ION Enterprise Server. Previous licenses are non-transferable.

SQL Server 2005 Products

We now have the option to bundle Microsoft SQL Server 2005 in conjunction with ION software. The IONE-SQL-2005 product is a 1 CPU license for SQL Server 2005 Standard Edition. For each additional CPU used by SQL Server, an additional IONE-SQL-2005-CPU is required. These products are for use only with licensed copies of ION Enterprise or ION EEM.

New Purchases

IONE56-BASE PowerLogic ION Enterprise base software

IONE56-DL PowerLogic ION Enterprise device license1

IONE56-CL PowerLogic ION Enterprise client license2

Options

IONE-SQL-2005 SQL Server 2005 bundle option (CD and 1 CPU license)

IONE-SQL-2005-CPU SQL Server 2005 additional CPU license

IONE-OPC-V1 OPC Server support for ION Enterprise

IONE-PQDIF-V1 PQDIF Exporter Module

1 A device license (IONE56-DL) is required for each meter or device connected to your PowerLogic ION Enterprise system. Minimum order quantity

for IONE56-DL is five (5). After you have purchased your IONE56-BASE product, you can order more device licenses as you need them. For 100+ devices, please call the factory for volume pricing. 2 A client license (IONE56-CL) is required for each workstation that is used to connect to your primary PowerLogic ION Enterprise system. After you

have purchased your IONE56-BASE product, you can order more client licenses as you need them.

Upgrades for ION Enterprise3

IONE56-UPGRADE PowerLogic ION Enterprise base upgrade4

IONE56-DLUPG PowerLogic ION Enterprise device license upgrade5

IONE56-CLUPG PowerLogic ION Enterprise client license upgrade4

3 Upgrades only apply to ION Enterprise 5.0 SP5 or later versions.

4 To order the optional OPC Server license with your upgrade, add the IONE-OPC-V1 part number to your purchase order. To order the optional

PQDIF Exporter license with your upgrade, add the IONE-PQDIF-V1 part number to your purchase order. 5 Licenses purchased for previous versions of ION Enterprise systems are non-transferrable.

PowerLogic ION Enterprise documentation

CD-TECHDOC Compact disc containing the latest version of technical documentation for ION hardware and software products.

Page 24: Guia Especificacion Portafolio Medidores

Product Part Number Guide

Rev date: July 2008 Page 24 of 28 70052-0188-41

Page 25: Guia Especificacion Portafolio Medidores

Product Part Number Guide

Rev date: July 2008 Page 25 of 28 70052-0188-41

Appendix A: ION8600 Custom Nameplate

If you would like to add custom text to your meter's nameplate label, fill out this form and submit it with your P.O.

Customer: P.O.#: P.O. line#:

Quantity:

TESTMODE

SHIFTUP

SHIFTDOWN

ALT/ENTER

Mult by

FM 35S

V~

W

FM

DEMANDRESET

3WD

120-480

35S

ABC Electric Co.

PQ-9903A000-00

M 8 G 1 2 3 4 5 6 7 8 9 0 0 0 0 0

*Meter Tag Number (required): 17 characters

maximum

Bar Code 39:

Bar Code Interpretation Line: 17 characters

maximum

PQ9903A000-00

Buyer Specified (Positions 13 to 17)

Manufacturer Serial Number (positions 4 to 12)

Manufacturer Data Code (Position 3) These fields are set to the

Manufacturer’s serial number unless

specified by the customer.

Meter Specification Data Code (Position 1 & 2)

ZY Form 9S 0.0V TA2.5 Kt: 0.0 3Ф4W 3EL

M8 Form 35S 0.0V TA2.5 Kt: 0.0 3Ф3W 2EL

M9 Form 36S 0.0V TA2.5 Kt: 0.0 3Ф4W 2½EL

2C Form 39S 0.0V TA2.5 Kt: 0.0 3Ф4W 3EL

2D Form 76S 0.0V TA2.5 Kt: 0.0 3Ф4W 2½EL

*The METER TAG number is a mandatory requirement for this checklist; each meter to be sealed must have a unique tag number.

Notes: