2
Fire CRFF
1. Introduction to VdS 3
2. Product description 11Introduction 11Performance range 11Product range 12Type keys 12
3. Construction 13CR 5, 10, 15 and 20 13CRI 5, 10, 15 and 20 13CR 32, 45 and 64 14CRN 32, 45 and 64 14Test pressure 15Installation 15How to read the curve charts 23Curve conditions 23Performance tests 24Certificate 24
4. Performance curves 25CRFF 5- (1-29) 25CRFF 10- (1-20) 26CRFF 15- (1-14) 27CRFF 20- (1-14) 28CRFF 32- (1-11) 29CRFF 45- (1-7) 30CRFF 64- (1-8-1) 31
5. Further fire pumps 32End-suction pumps 32
6. Further product documentation 34WebCAPS 34WinCAPS 35
Intr
od
uc
tio
n t
o V
dS
Fire CRFF 1
1. Introduction to VdS
VdS Schadenverhütung GmbH is an independent, international, accredited and notified testing and certification institution for fire prevention and safety technology as well as for physical and electronic protection against intrusion. ("Schadenverhütung" is the German word for "loss prevention").
VdS Schadenverhütung is accredited according to the EN 45000 series of European standards and is a member of the European Fire and Security Group (EFSG). VdS experts are represented in all relevant German and international committees.
The concept behind VdS recognition is to ensure that only tested and certified products and services are offered to the safety and security markets. This is equally advantageous for user and supplier.
For further information on VdS, see www.vds.de.
VdS standardsThe products in this data booklet have been built to comply with VdS standards on water-based firefighting systems, described in the following documents:
• VdS CEA 4001-S:2003-11: Planning and installation.
• VdS 2100-07: Guidelines for water-based firefighting systems.
• VdS 2344: Procedures for testing and approval of equipment, components and systems used in fire protection and security control.
Standards approval processGrundfos is to test the pumps and fill in the application forms for each individual pump size. The following documentation should to submitted to the VdS:
• complete drawings with list of parts and materials of the major components
• a statement regarding quality and production (ISO 9001 + Annex A & D)
• data sheet with technical information
• installation and operating instructions.
If the application forms are accepted, VdS will attend the final test at the Grundfos premises. If the evaluation of the test results is positive, the VdS will issue a certificate on the approval of the pump.
3
Intro
du
ctio
n to
Vd
S
4
Fire CRFF1
VdS certificateThe following pages show the VdS certificate for the CRFF pumps.
TM
05
39
97
19
12
Intr
od
uc
tio
n t
o V
dS
Fire CRFF 1
Fire pumpsGrundfos centrifugal pumps approved by the VdS are designed for the distribution of water in stationary sprinkler systems using either foam or water spray. They are operated in case of fire and during tests.
Materials
VdS-approved pumps must comply with these requirements:
• impeller, wear rings and wet parts such as shaft, washers and nuts must be made of non-corrosive iron.
• castings must be made of EN-GJL-250 cast iron.
VdS requirements for EN-GJL-250 do not allow heads (H) above 110 m and flow rates (Q) above 600 m3/h. Above 110 m ductile iron is required.
Pump characteristic
The VdS focuses strongly on the instabilities which may be present in sprinkler systems consisting of long and different pipe circuits. Two instable pumps may cause vibrations or breakdown.
If the characteristic is instable, the instability must not exceed 5 %. See examples of instable (fig. 1) and stable (fig. 2) characteristics below.
Fig. 1 Instable characteristics
Fig. 2 Stable characteristics
Duty rangeThe VdS operates with a concept known as Qzul ("zul" is an abbreviation of "zulässig" which means permissible). See fig. 3. The duty point of the pump must not be to the right of this limit.
Qzul is defined on the basis of the pump NPSH curves. The following calculation must be made for the largest and smallest pump impeller diameter.
TM
03
27
95
49
05
0 20 40 60 80 100 120 140 160 180 Q [m³/h]
14
16
18
20
22
24
26
28
30
32
34
36
38
40
[m]H
NK 80-315
ISO 9906 Annex A
50 Hz, n = 1450 min-1
ø275
ø290
ø305
ø320
ø334
73.3 %
72.5 %
72.1 %
74.8 %
74.2 %74 %
72 %
70 %
68 %
68 %70 %
72 %
74 %
TM
05
21
64
05
12
Find the flow rate at 4.5 m and 5.5 m NPSH
Multiply the value Q4.5 m NPSH by 1.2
Does the result exceed the value of Q5.5 m NPSH?
YesQzul = Q5.5 m NPSH / 1.2
No
Qzul = Q4.5 m NPSH
0 200 400 600 800 1000 1200 1400 1600 1800 2000 Q [l/min]
0
5
10
15
20
25
30
35
40
45
50
55
60
65
[m]H
0 20 40 60 80 100 120 Q [m³/h]
NKF 50-200
ISO 9906 Annex A
EN12845/prEN12259-12
2950 rpm
ø170
ø194
ø207
ø219
15 kW
22 kW
18.5 kW
11 kW
9
Intro
du
ctio
n to
Vd
S
10
Fire CRFF1
Fig. 3 Exampel of Qzul and duty range
Motor power ratingTo ensure that the motor is capable of operating the pump at any time to supply water, the VdS stipulates an excess capacity of motor power.
Overloading power curves
Motor power is found at 16 m NPSH.
Non-overloading power curves
Motor power is found at the power peak +5 %.
TM
05
28
06
26
12
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 Q [m³/h]
0
20
40
60
80
100
120
140
160
180
200
220
H[m]
0 1 2 3 4 5 6 7 8 Q [l/s]
0
400
800
1200
1600
2000
p[kPa]
CRFF 202-pole, 50 Hz
ISO 9906/2 Annex A
-1, ø104.8 (3 kW)
-12, ø104.8 (15 kW)
-14, ø104.8 (18.5 kW)
-2, ø104.8 (4 kW)
-4, ø104.8 (5.5 kW)
-5, ø104.8 (7.5 kW)
-8, ø104.8 (11 kW)
VdS Zulassungsgrenze / VdS Rated capacity
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 Q [m³/h]
0
4
8
12
P2[kW]
-1, ø104.8
-12, ø104.8
-14, ø104.8
-2, ø104.8-4, ø104.8-5, ø104.8
-8, ø104.8
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 Q [m³/h]
0
2
4
6
NPSH[m]
NPSH
Qzul
5.54.5
23.5
27.3 28.5
Pro
du
ct
de
sc
rip
tio
n
Fire CRFF 2
2. Product description
IntroductionGrundfos Fire CRFF pump units are typically used in firefighting applications for supplying water to fire hose reels, fire hydrants or sprinkler systems.
This data booklet covers the range of electrically powered CRFF centrifugal pumps, designed and approved by the VdS for use in fire systems.
Performance range
TM
05
40
32
19
123 4 5 6 7 8 9 10 15 20 30 40 50 60 70 80 90
Q [m³/h]
20
40
60
80
100
120
140
160
180
200
220
240
H[m]
11 2 3 4 5 6 7 8 9 1010 Q [l/s]
0.4
0.8
1.2
1.6
2.0
2.4
[MPa]p
CRFF2-pole, 50 Hz
ISO 9906/2 Annex A
CR
FF
45
CR
FF
32
CR
FF
20
CR
FF
15
CR
FF
10
CR
FF
5
CR
FF
64
11
Pro
du
ct d
es
crip
tion
12
Fire CRFF2
Product range
Standard range
2-pole
Other stages are available on request.
Type keys
CR, CRI, CRN
Codes
Pump sizeNumber of
stages
VdS approval Number
Motor, P2 [kW]
Product number
CRFF 5
1
P412003
0.55 98156624
3 0.75 98156599
6 1.1 98156598
9 1.5 98156595
14 2.2 98156594
20 3 98156593
28 4 98156622
29 5.5 98156589
CRFF 10
1
P412003
1.1 98156655
3 1.5 98156653
4 2.2 98156651
7 3 98156649
10 4 98156645
15 5.5 98156647
20 7.5 98156641
CRFF 15
1
P412003
2.2 98156692
2 3 98156680
3 4 98156678
5 5.5 98156677
8 7.5 98156676
12 11 98156674
14 15 98156658
CRFF 20
1
P412003
3 98156748
2 4 98156730
4 5.5 98156729
5 7.5 98156728
9 11 98156727
13 15 98156722
14 18.5 98156721
CRFF 32
1
P412003
2.2 98158475
2 4 98158473
3 5.5 98158471
4 7.5 98158470
6 11 98158569
8 15 98158468
10 18.5 98158464
11 22 98158461
CRFF 45
1
P412003
5.5 98158498
2 11 98158497
3 15 98158496
4 18.5 98158595
5 22 98158480
7 30 98158479
CRFF 64
1
P412003
5.5 98158960
2 11 98158959
3 18.5 98158958
4 22 98158523
5 30 98158522
6 37 98158521
8-1 45 98158524
Example CR FF 32 (s) -4 -2 -A -F -G -E -HQQE
Type range:CR, CRI, CRN
Pump approved for firefighting
Flow rate [m3/h]
All impellers with reduced diameter
Number of impellers
Number of reduced-diameter impellers
Code for pump version
Code for pipe connection
Code for materials
Code for rubber parts
Code for shaft seal
Example A -F -A -E -H QQ E
Pump version
A Basic version
B Oversize motor
Pipe connection
F DIN flange
G ANSI flange
J JIS flange
Materials
I Wetted parts of EN 1.4301/AISI 304
Code for rubber parts
E EPDM
F FXM
K FFKM
V FKM
Shaft seal
H Balanced cartridge seal
Q Silicon carbide
U Tungsten carbide
B Carbon
E EPDM
F FXM
K FFKM
V FKM
Co
ns
tru
cti
on
Fire CRFF 3
3. Construction
CR 5, 10, 15 and 20
Sectional drawing
Materials, CR
1) CR 5.2) CR 10, 15, 20.
CRI 5, 10, 15 and 20
Sectional drawing
Materials, CRI
1) Stainless steel available on request.2) CRI 5.3) CRI 10, 15, 20.
TM
02
11
98
06
01
- G
R7
37
7 -
GR
73
79
TM
02
11
94
14
03
Pos. Designation Materials EN/DIN AISI/ASTM
1 Pump headCast ironEN-GJL-200
EN-JL1030 ASTM 25B
3 Shaft Stainless steel 1.4401 1)
1.4057 2)AISI 316AISI 431
4 Impeller Stainless steel 1.4301 AISI 304
5 Chamber Stainless steel 1.4301 AISI 304
6 Sleeve Stainless steel 1.4301 AISI 304
7O-ring for sleeve
EPDM or FKM
8 BaseCast ironEN-GJL-200
EN-JL1030 ASTM 25B
9 Neck ring PTFE
10 Shaft seal
Rubber parts EPDM or FKM
1
3
10
4
5
9
8
67
TM
02
18
08
20
01
- G
R7
37
3 -
GR
73
75
TM
02
11
95
14
03
Pos. Designation Materials EN/DIN AISI/ASTM
1 Pump headCast ironEN-GJL-200 1) EN-JL1030 ASTM 25B
2Pump head cover
Stainless steel 1.4408CF 8M equal to
AISI 316
3 Shaft Stainless steel 1.4401 2)
1.4460 3)AISI 316AISI 329
4 Impeller Stainless steel 1.4301 AISI 304
5 Chamber Stainless steel 1.4301 AISI 304
6 Sleeve Stainless steel 1.4301 AISI 304
7O-ring for sleeve
EPDM or FKM
8 Base Stainless steel 1.4408CF 8M equal to
AISI 316
9 Neck ring PTFE
10 Shaft seal Cartridge type
11 Base plateCast ironEN-GJL-200 1) EN-JL1030 ASTM 25B
Rubber parts EPDM or FKM
1
2 10
4
5
9
8
6
3
11
7
13
Co
ns
truc
tion
14
Fire CRFF3
CR 32, 45 and 64
Sectional drawing
Materials, CR
CRN 32, 45 and 64
Sectional drawing
Materials, CRN
1) Stainless steel available on request.
TM
01
21
50
12
98
TM
01
18
36
14
03
Pos. Designation Materials EN/DIN AISI/ASTM
1 Pump headCast ironEN-GJS-500-7
EN-JS1050ASTM
80-55-06
2 Motor stoolCast ironEN-GJL-200
EN-JL1030 ASTM 25B
3 Shaft Stainless steel 1.4057 AISI 431
4 Impeller Stainless steel 1.4301 AISI 304
5 Chamber Stainless steel 1.4301 AISI 304
6 Sleeve Stainless steel 1.4301 AISI 304
7O-ring for sleeve
EPDM or FKM
8 BaseCast ironEN-GJS-500-7
EN-JS1050ASTM
80-55-06
9 Neck ringCarbon-graphite filled PTFE
10 Shaft seal
11 Bearing ring Bronze
12Bottom bearing ring
Tungsten carbide/tungsten carbide
Rubber parts EPDM or FKM
2
3
1
5
9
4
6
11
8
12
10
7
TM
02
73
99
34
03
TM
01
18
37
14
03
Pos. Designation Materials EN/DIN AISI/ASTM
1 Pump head Stainless steel 1.4408CF 8M equal to
AISI 316
2 Motor stoolCast ironEN-GJL-200 1) EN-JL1030 ASTM 25B
3 Shaft Stainless steel 1.4462
4 Impeller Stainless steel 1.4401 AISI 316
5 Chamber Stainless steel 1.4401 AISI 316
6 Sleeve Stainless steel 1.4401 AISI 316
7O-ring for sleeve
EPDM or FKM
8 Base Stainless steel 1.4408CF 8M equal to
AISI 316
9 Neck ringCarbon-graphite filled PTFE
10 Shaft seal
11 Bearing ringCarbon-graphite filled PTFE
12Bottom bearing ring
Tungsten carbide/tungsten carbide
13 Base plateCast ironEN-GJS-500-7 1) EN-JS1050
ASTM 88-55-06
Rubber parts EPDM or FKM
2
1
5
9
4
6
11
8
12
7
13
3
10
2
1
5
9
4
6
11
8
12
7
13
3
10
Co
ns
tru
cti
on
Fire CRFF 3
Test pressurePressure testing has been made with +20 °C water containing corrosion inhibitor.
Installation
Pipe connectionWhen installing the pipes, make sure that the pump housing is not stressed by the pipework.
The suction and discharge pipes must be of an adequate size, taking the pump inlet pressure into account.
Install the pipes so that air locks are avoided, especially on the suction side of the pump. See fig. 4.
Fig. 4 Pipelines
Fit isolating valves on either side of the pump to avoid having to drain the system if the pump needs to be cleaned or repaired.
Make sure the pipes are adequately supported as close to the pump as possible, both on the suction and the discharge side. The counter flanges should lie true against the pump flanges without being stressed; otherwise, the pump will be damaged.
Pressure stage
Operating pressure Test pressure
bar MPa bar MPa
PN 10 10 1.0 15 1.5
PN 16 16 1.6 24 2.4
TM
00
22
63
33
93
15
Co
ns
truc
tion
16
Fire CRFF3
Dimensional sketch CR, CRI 5
Dimensions and weights
TM
03
17
23
28
05
ø35
ø14
0
75
20
B1
B2
141100
250
ø10
0ø
89
180220
4 x ø13.5
19 x 24.5G 1/2
D2
D1
G 1/2 G 1/2
FGJ (DIN-ANSI-JIS)PN 25 / DN 25/32
D3
Pump typeMotor
P2 [kW]
CR CRI
Dimensions [mm] Net weight [kg] Dimensions [mm] Net weight [kg]
DIN flangeD1 D2 D3 DIN flange
DIN flangeD1 D2 D3 DIN flange
B1 B1+B2 B1 B1+B2
CR 5-1 0.55 279 470 141 109 - 24 - - - - - -
CR 5-3 0.75 306 497 141 109 - 26 - - - - - -
CR 5-6 1.1 393 644 141 109 - 30 - - - - - -
CR 5-9 1.5 490 771 178 110 - 38 - - - - - -
CR 5-14 2.2 625 946 178 110 - 42 - - - - - -
CRI 5-20 3 - - - - - - 795 1130 198 120 - 49
CRI 5-28 4 - - - - - - 1038 1410 220 134 - 64
CRI 5-29 5.5 - - - - - - 1038 1429 220 134 - 78.5
Co
ns
tru
cti
on
Fire CRFF 3
Dimensional sketch CR, CRI 10
Dimensions and weights
TM
03
17
25
28
03
B2
D2D1
4 x ø13.5130178
80
G 1/2
280
B1
G 1/2G 1/2
256
18 x 20.2
ø39
20
FJ (DIN-JIS)
ø11
4ø
150
215ø110
D3
PN 16-25 / DN 40
Pump typeMotor
P2 [kW]
CR CRI
Dimensions [mm] Net weight [kg] Dimensions [mm] Net weight [kg]
DIN flange D1 D2 D3DIN flange
DIN flange D1 D2 D3DIN flange
B1 B1+B2 B1 B1+B2
CR 10-1 1.1 343 534 141 109 - 34 - - - - - -
CR 10-3 1.5 377 628 141 109 - 39 - - - - - -
CR 10-4 2.2 423 704 178 110 - 47 - - - - - -
CR 10-7 3 518 853 198 120 - 57 - - - - - -
CR 10-10 4 608 980 220 134 - 69 - - - - - -
CRI 10-15 5.5 - - - - - - 760 1151 220 134 300 94
CRI 10-20 7.5 - - - - - - 940 1319 260 159 300 112
17
Co
ns
truc
tion
18
Fire CRFF3
Dimensional sketch CR, CRI 15
Dimensions and weights
TM
03
17
27
28
05
B2
D2D1
G 1/2
G 1/2 D3
130176
90
G 1/2
300215256
ø6520
PN 16-25 / DN 50
ø12
5ø
165
B1
F (DIN)
4 x ø13.5 ø18.1
Pump typeMotor
P2 [kW]
CR CRI
Dimensions [mm] Net weight [kg] Dimensions [mm] Net weight [kg]
DIN flange D1 D2 D3DIN flange
DIN flange D1 D2 D3DIN flange
B1 B1+B2 B1 B1+B2
CR 15-1 2.2 400 651 141 109 - 42 - - - - - -
CR 15-2 3 415 736 178 110 - 50 - - - - - -
CR 15-3 4 465 800 198 120 - 57 - - - - - -
CR 15-5 5.5 555 927 220 134 - 69 - - - - - -
CRI 15-8 7.5 - - - - - - 720 1099 260 159 300 104
CRI 15-12 11 - - - - - - 977 1448 314 204 350 151
CRI 15-14 15 - - - - - - 1067 1538 314 204 350 165
Co
ns
tru
cti
on
Fire CRFF 3
Dimensional sketch CR, CRI 20
Dimensions and weights
TM
03
17
27
28
05
B2
D2D1
G 1/2
G 1/2 D3
130176
90G 1/2
300215256
ø6520
PN 16-25 / DN 50
ø12
5ø
165
B1
F (DIN)
4 x ø13.5 ø18.1
Pump typeMotor
P2 [kW]
CR CRI
Dimensions [mm] Net weight [kg] Dimensions [mm] Net weight [kg]
DIN flange D1 D2 D3DIN flange
DIN flange D1 D2 D3DIN flange
B1 B1+B2 B1 B1+B2
CR 20-1 3 400 651 141 109 - 42 - - - - - -
CR 20-2 4 415 736 178 110 - 50 - - - - - -
CR 20-4 5.5 542 933 220 134 300 88 - - - - - -
CR 20-5 7.5 587 978 220 134 300 90 - - - - - -
CRI 20-9 11 - - - - - - 797 1268 314 204 350 144
CRI 20-13 15 - - - - - - 977 1448 314 204 350 163
CRI 20-14 18.5 - - - - - - 1067 1538 314 204 350 178
19
Co
ns
truc
tion
20
Fire CRFF3
Dimensional sketch CR, CRN 32
Dimensions and weights
TM
01
17
49
32
98
Pump typeMotor
P2 [kW]
CR CRN
Dimensions [mm]Net weight [kg]
Dimensions [mm]Net weight [kg]
B1 B1+B2 D1 D2 D3 B1 B1+B2 D1 D2 D3
CR 32-1 2.2 505 826 178 110 270 64 - - - - - -
CR 32-2 4 575 947 220 134 270 82 - - - - - -
CR 32-3 5.5 645 1036 220 134 300 96 - - - - - -
CR 32-4 7.5 715 1094 260 159 300 111 - - - - - -
CRN 32-6 11 - - - - - - 965 1436 314 204 350 163
CRN 32-8 15 - - - - - - 1105 1576 314 204 350 185
CRN 32-10 18.5 - - - - - - 1245 1760 314 204 350 205
CRN 32-11 22 - - - - - - 1315 1856 314 204 350 222
Co
ns
tru
cti
on
Fire CRFF 3
Dimensional sketch CR, CRN 45
Dimensions and weights
TM
01
17
51
32
03
8 x ø18
G 1/2
ø80266331
ø120
ø160
ø200
D2D1
190248365
B1
B2
G 1/2
G 1/2
4 x ø14
140
D3
45
PN16-25-40/DN80
Pump typeMotor
P2 [kW]
CR CR
Dimensions [mm]Net weight [kg]
Dimensions [mm]Net weight [kg]
B1 B1+B2 D1 D2 D3 B1 B1+B2 D1 D2 D3
CR 45-1 5.5 559 950 220 134 270 100 - - - - - -
CR 45-2 11 639 1100 314 204 350 160 - - - - - -
CR 45-3 15 829 1300 314 204 350 176 - - - - - -
CR 45-4 18.5 909 1424 314 204 350 193 - - - - - -
CRN 45-5 22 - - - - - - 989 1530 314 204 350 211
CRN 45-7 30 - - - - - - 1149 1759 407 315 400 324
21
Co
ns
truc
tion
22
Fire CRFF3
Dimensional sketch CR, CRN 64
Dimensions and weights
TM
01
17
53
51
97
ø100266331
ø150
ø180
ø220
D2D1
190248365
B1
B2
G 1/2 8 x ø18
G 1/2
G 1/2
4 x ø14
140
D3
45
PN16/DN100
PN25-40/DN100
45
4 x ø14
G 1/2
8 x ø22
ø235
ø190
ø150
331266ø100
F (DIN)
F (DIN)
Pump typeMotor
P2 [kW]
CR CR
Dimensions [mm]Net weight [kg]
Dimensions [mm]Net weight [kg]
B1 B1+B2 D1 D2 D3 B1 B1+B2 D1 D2 D3
CR 64-1 5.5 561 952 220 134 300 102 - - - - - -
CR 64-2 11 754 1225 314 204 350 162 - - - - - -
CR 64-3 18.5 836 1351 314 204 350 193 - - - - - -
CR 64-4 22 919 1460 314 204 350 211 - - - - - -
CRN 64-5 30 - - - - - - 1001 1611 407 315 400 318
CRN 64-6 37 - - - - - - 1084 1751 407 315 400 355
CRN 64-8-1 45 - - - - - - 1249 1957 439 338 450 448
Co
ns
tru
cti
on
Fire CRFF 3
How to read the curve charts
Curve conditions
Selection of pumps
The guidelines below apply to the curves shown in the performance charts, pages 25 to 31.
• Tolerances according to ISO 9906 and VdS 2100-07.
• The curves show pump performance with different number of impellers at the nominal speed.
• The bold part of the curves shows the recommended operating range.
• The thin parts are not allowed according to the VdS.
• Do not use the pumps at minimum flow rates below 0.1 x Q at optimum efficiency because of the danger of overheating of the pump.
• The curves apply to of water at a temperature of +20 °C and a kinematic viscosity of 1 mm2/s (1 cSt).
• NPSH: The curves are according to the minimum and maximum number of impellers.
• In case of other densities than 1000 kg/m3 the discharge pressure is proportional to the density.
• When pumping water with a density higher than 1000 kg/m3, motors with correspondingly higher outputs must be used.
Calculation of total head
The total pump head consists of the height difference between the measuring points + the differential head + the dynamic head.
TM
05
28
07
26
12
0 4 8 12 16 20 24 28 32 36 40 Q [m³/h]
0
20
40
60
80
100
120
140
160
180
200
220
H[m]
0 2 4 6 8 10 12 Q [l/s]
0.0
0.4
0.8
1.2
1.6
2.0
[MPa]p
CRFF 322-pole, 50 Hz
ISO 9906/2 Annex A
-11, ø118.3 (22 kW)
-1, ø118.3 (2.2 kW)
-10, ø118.3 (18.5 kW)
-2, ø118.3 (4 kW)
-3, ø118.3 (5.5 kW)
-4, ø118.3 (7.5 kW)
-6, ø118.3 (11 kW)
-8, ø118.3 (15 kW)
VdS Zulassungsgrenze / VdS Rated capacity
0 4 8 12 16 20 24 28 32 36 40 Q [m³/h]
0
5
10
15
20
P2[kW]
-1, ø118.3
-10, ø118.3-11, ø118.3
-2, ø118.3-3, ø118.3-4, ø118.3
-6, ø118.3
-8, ø118.3
0 4 8 12 16 20 24 28 32 36 40 Q [m³/h]
0
2
4
6
[m]NPSH
NPSH
Pump type and motor speed
Number of stages
Total pump headH = Htotal
The power curve indicates pump input power, P2.
The NPSH curve is according to the minimum and maximum impeller diameter.
Qzul indicates the limit of the individual pump performance range according to the VdS.
QH curve for the individual pump
Hgeo: Height difference between measuring points.Hstat: Differential head between the suction and the
discharge side of the pump.Hdyn: Calculated values based on the velocity of the
pumped water on the suction and the discharge side of the pump.
Htotal Hgeo Hstat Hdyn+ +=
23
Co
ns
truc
tion
24
Fire CRFF3
Performance testsThe requested duty point for every pump is tested according to ISO 9906 and VdS 2100-07.
If the customer requires a specific number of impellers (not a specific duty point), the pump will be tested at a duty point which is 2/3 of the maximum flow rate of the published performance curve related to the ordered number of impellers (according to ISO 9906).
If the customer requires either more points on the curve to be checked or certain minimum performances or certificates, individual measurements must be made.
CertificateThe pump order includes a test certificate confirming the required QH performance.
Pe
rfo
rma
nc
e c
urv
es
4
4. Performance curves
CRFF 5- (1-29)
TM
05
28
03
26
12
0 1 2 3 4 5 6 7 8 Q [m³/h]
0
20
40
60
80
100
120
140
160
180
200
H[m]
0.0 0.5 1.0 1.5 2.0 2.5 Q [l/s]
0
400
800
1200
1600
p[kPa]
CRFF 52-pole, 50 Hz
ISO 9906/2 Annex A
-1, ø73.2 (0.55 kW)
-14, ø73.2 (2.2 kW)
-20, ø73.2 (3 kW)
-29, ø73.2 (5.5 kW)
-3, ø73.2 (0.75 kW)
-6, ø73.2 (1.1 kW)
-9, ø73.2 (1.5 kW)
-28, ø73.2 (4 kW)
VdS Zulassungsgrenze / VdS Rated capacity
0 1 2 3 4 5 6 7 8 Q [m³/h]
0
1
2
3
4
P2[kW]
-14, ø73.2
-20, ø73.2
-28, ø73.2-29, ø73.2
-3, ø73.2-6, ø73.2-9, ø73.2
-1, ø73.2
0 1 2 3 4 5 6 7 8 Q [m³/h]
0
1
2
3
NPSH[m]
NPSH
25
Pe
rform
an
ce
cu
rve
s
26
4
CRFF 10- (1-20)
TM
05
28
04
26
12
0 1 2 3 4 5 6 7 8 9 10 11 12 13 Q [m³/h]
0
20
40
60
80
100
120
140
160
180
200
220
240
H[m]
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 Q [l/s]
0
400
800
1200
1600
2000
p[kPa]
CRFF 102-pole, 50 Hz
ISO 9906/2 Annex A
-1, ø92.9 (1.1 kW)
-10, ø92.9 (4 kW)
-14, ø92.9 (5.5 kW)
-20, ø92.9 (7.5 kW)
-3, ø92.9 (1.5 kW)
-4, ø92.9 (2.2 kW)
-7, ø92.9 (3 kW)
VdS Zulassungsgrenze / VdS Rated capacity
0 1 2 3 4 5 6 7 8 9 10 11 12 13 Q [m³/h]
0
2
4
6
P2[kW]
-1, ø92.9
-10, ø92.9
-14, ø92.9
-20, ø92.9
-3, ø92.9-4, ø92.9-7, ø92.9
0 1 2 3 4 5 6 7 8 9 10 11 12 13 Q [m³/h]
1
2
3
4
NPSH[m]
NPSH
Pe
rfo
rma
nc
e c
urv
es
4
CRFF 15- (1-14)
TM
05
28
05
26
12
0 2 4 6 8 10 12 14 16 18 20 22 24 Q [m³/h]
0
20
40
60
80
100
120
140
160
180
200
220
H[m]
0 1 2 3 4 5 6 7 Q [l/s]
0
400
800
1200
1600
2000
p[kPa]
CRFF 152-pole, 50 Hz
ISO 9906/2 Annex A
-1, ø104.8 (2.2 kW)
-12, ø104.8 (11 kW)
-14, ø104.8 (15 kW)
-2, ø104.8 (3 kW)
-3, ø104.8 (4 kW)
-5, ø104.8 (5.5 kW)
-8, ø104.8 (7.5 kW)
VdS Zulassungsgrenze / VdS Rated capacity
0 2 4 6 8 10 12 14 16 18 20 22 24 Q [m³/h]
0
2
4
6
8
10
P2[kW]
-1, ø104.8
-12, ø104.8
-14, ø104.8
-2, ø104.8-3, ø104.8-5, ø104.8
-8, ø104.8
0 2 4 6 8 10 12 14 16 18 20 22 24 Q [m³/h]
0
1
2
3
4
NPSH[m]
NPSH
27
Pe
rform
an
ce
cu
rve
s
28
4
CRFF 20- (1-14)
TM
05
28
06
26
12
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 Q [m³/h]
0
20
40
60
80
100
120
140
160
180
200
220
H[m]
0 1 2 3 4 5 6 7 8 Q [l/s]
0
400
800
1200
1600
2000
p[kPa]
CRFF 202-pole, 50 Hz
ISO 9906/2 Annex A
-1, ø104.8 (3 kW)
-12, ø104.8 (15 kW)
-14, ø104.8 (18.5 kW)
-2, ø104.8 (4 kW)
-4, ø104.8 (5.5 kW)
-5, ø104.8 (7.5 kW)
-8, ø104.8 (11 kW)
VdS Zulassungsgrenze / VdS Rated capacity
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 Q [m³/h]
0
4
8
12
P2[kW]
-1, ø104.8
-12, ø104.8
-14, ø104.8
-2, ø104.8-4, ø104.8-5, ø104.8
-8, ø104.8
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 Q [m³/h]
0
2
4
6
NPSH[m]
NPSH
Pe
rfo
rma
nc
e c
urv
es
4
CRFF 32- (1-11)
TM
05
28
07
26
12
0 4 8 12 16 20 24 28 32 36 40 Q [m³/h]
0
20
40
60
80
100
120
140
160
180
200
220
H[m]
0 2 4 6 8 10 12 Q [l/s]
0.0
0.4
0.8
1.2
1.6
2.0
[MPa]p
CRFF 322-pole, 50 Hz
ISO 9906/2 Annex A
-11, ø118.3 (22 kW)
-1, ø118.3 (2.2 kW)
-10, ø118.3 (18.5 kW)
-2, ø118.3 (4 kW)
-3, ø118.3 (5.5 kW)
-4, ø118.3 (7.5 kW)
-6, ø118.3 (11 kW)
-8, ø118.3 (15 kW)
VdS Zulassungsgrenze / VdS Rated capacity
0 4 8 12 16 20 24 28 32 36 40 Q [m³/h]
0
5
10
15
20
P2[kW]
-1, ø118.3
-10, ø118.3-11, ø118.3
-2, ø118.3-3, ø118.3-4, ø118.3
-6, ø118.3
-8, ø118.3
0 4 8 12 16 20 24 28 32 36 40 Q [m³/h]
0
2
4
6
[m]NPSH
NPSH
29
Pe
rform
an
ce
cu
rve
s
30
4
CRFF 45- (1-7)
TM
05
28
08
26
12
0 5 10 15 20 25 30 35 40 45 50 55 Q [m³/h]
0
20
40
60
80
100
120
140
160
180
200
H[m]
0 2 4 6 8 10 12 14 16 Q [l/s]
0.0
0.4
0.8
1.2
1.6
[MPa]p
CRFF 452-pole, 50 Hz
ISO 9906/2 Annex A
-7, ø136.3 (30 kW)
-2, ø136.3 (11 kW)
-3, ø136.3 (15 kW)
-4, ø136.3 (18.5 kW)
-5, ø136.3 (22 kW)
-1, ø136.3 (5.5 kW)
VdS Zulassungsgrenze / VdS Rated capacity
0 5 10 15 20 25 30 35 40 45 50 55 Q [m³/h]
0
5
10
15
20
25
P2[kW]
-7, ø136.3
-1, ø136.3
-2, ø136.3-3, ø136.3
-4, ø136.3
-5, ø136.3
0 5 10 15 20 25 30 35 40 45 50 55 Q [m³/h]
0
1
2
3
4
[m]NPSH
NPSH
Pe
rfo
rma
nc
e c
urv
es
4
CRFF 64- (1-8-1)
TM
05
28
09
26
12
0 10 20 30 40 50 60 70 80 90Q [m³/h]
0
20
40
60
80
100
120
140
160
180
200
220
240
H[m]
0 5 10 15 20 25 Q [l/s]
0.0
0.4
0.8
1.2
1.6
2.0
[MPa]p
CRFF 642-pole, 50 Hz
ISO 9906/2 Annex A
-8-1, ø142.9 (45 kW)
-1, ø142.9 (5.5 kW)
-2, ø142.9 (11 kW)
-3, ø142.9 (18.5 kW)
-4, ø142.9 (22 kW)
-5, ø142.9 (30 kW)
-6, ø142.9 (37 kW)
VdS Zulassungsgrenze / VdS Rated capacity
0 10 20 30 40 50 60 70 80 90Q [m³/h]
0
10
20
30
40
P2[kW]
-1, ø142.9-2, ø142.9
-3, ø142.9-4, ø142.9
-5, ø142.9-6, ø142.9
-8-1, ø142.9
0 10 20 30 40 50 60 70 80 90Q [m³/h]
0
2
4
6
[m]NPSH
NPSH
31
Fu
rthe
r fire p
um
ps
32
Fire CRFF5
5. Further fire pumps
Grundfos can also provide end-suction and split case pumps, controllers and drivers according to standards such as VdS, LPCB, EN, FM, OKF and NFPA.
Please contact your local Grundfos sales company for options of fire pump sets and other products with standards suitable for your requirements.
End-suction pumps
VdS diesel range
TM
03
84
73
26
11
20 30 40 50 60 80 100 150 200 300 400 500 600 800Q [m³/h]
20
30
40
50
60
70
80
90
100
120
[m]H
NKFDiesel
125-315
125-250.1
125-250
100-200
150-400
150-400
150-400
150-500
150-40080-250
65-200
80-20050-2002960 min-1
2960 min-1
2960 min-1
2960 min-1
1800 min-1
1800 min-1
1480 min-1
1700 min-1
1600 min-1
2960 min-1
2960 min-1
2990 min-1
2980 min-1
Fu
rth
er
fire
pu
mp
s
Fire CRFF 5
VdS electrical range
TM
02
93
54
26
11
20 30 40 50 60 80 100 150 200 300 400 500 600Q [m³/h]
20
30
40
50
60
70
80
90
100
120
150[m]H
NKF50 Hz
125-315/2
125-250.1/2
100-200/2
125-250/2
150-400/4
150-500/4
80-250/2
65-200/2 80-200/250-200/2
33
Fu
rthe
r pro
du
ct d
oc
um
en
tatio
n
34
Fire CRFF6
6. Further product documentation
WebCAPSWebCAPS is a Web-based Computer Aided Product Selection program available on www.grundfos.com.
WebCAPS contains detailed information on more than 220,000 Grundfos products in more than 30 languages.
Information in WebCAPS is divided into six sections:
• Catalogue
• Literature
• Service
• Sizing
• Replacement
• CAD drawings.
Catalogue
Based on fields of application and pump types, this section contains the following:• technical data• curves (QH, Eta, P1, P2, etc.) which can be adapted to the
density and viscosity of the pumped liquid and show the number of pumps in operation
• product photos• dimensional drawings• wiring diagrams• quotation texts, etc.
Literature
This section contains all the latest documents of a given pump, such as• data booklets• installation and operating instructions• service documentation, such as Service kit catalogue and
Service kit instructions• quick guides• product brochures.
Service
This section contains an easy-to-use interactive service catalogue. Here you can find and identify service parts of both existing and discontinued Grundfos pumps.Furthermore, the section contains service videos showing you how to replace service parts.
Fu
rth
er
pro
du
ct
do
cu
me
nta
tio
n
Fire CRFF 6
WinCAPS
Fig. 5 WinCAPS DVD
WinCAPS is a Windows-based Computer Aided Product Selection program containing detailed information on more than 220,000 Grundfos products in more than 30 languages.
The program contains the same features and functions as WebCAPS, but is an ideal solution if no internet connection is available.
WinCAPS is available on DVD and updated once a year.
Sizing
This section is based on different fields of application and installation examples and gives easy step-by-step instructions in how to size a product:• Select the most suitable and efficient pump for your
installation.• Carry out advanced calculations based on energy,
consumption, payback periods, load profiles, life cycle costs, etc.
• Analyse your selected pump via the built-in life cycle cost tool.• Determine the flow velocity in wastewater applications, etc.
Replacement
In this section you find a guide to selecting and comparing replacement data of an installed pump in order to replace the pump with a more efficient Grundfos pump. The section contains replacement data of a wide range of pumps produced by other manufacturers than Grundfos.
Based on an easy step-by-step guide, you can compare Grundfos pumps with the one you have installed on your site. When you have specified the installed pump, the guide will suggest a number of Grundfos pumps which can improve both comfort and efficiency.
CAD drawings
In this section, it is possible to download 2-dimensional (2D) and 3-dimensional (3D) CAD drawings of most Grundfos pumps.
These formats are available in WebCAPS:
2-dimensional drawings:• .dxf, wireframe drawings• .dwg, wireframe drawings.
3-dimensional drawings:• .dwg, wireframe drawings (without surfaces)• .stp, solid drawings (with surfaces)• .eprt, E-drawings.
0 1
Subject to alterations.
35
GRUNDFOS A/S . DK-8850 Bjerringbro . DenmarkTelephone: +45 87 50 14 00www.grundfos.com
The name Grundfos, the Grundfos logo, and the payoff Be–Think–Innovate are registrated trademarks owned by Grundfos Management A/S or Grundfos A/S, Denmark. All rights reserved worldwide.
Being responsible is our foundationThinking ahead makes it possible
Innovation is the essence