Upload
miguel-angel
View
118
Download
0
Tags:
Embed Size (px)
Citation preview
Grounding and Cabling of the Drive System
Variable Speed Drives
L1
L2L3
Concentric Cu-shield
A B
Frequency converterPE U V W
PE
Factory main
Trans-former
Frequency converterPE U V W
PE
Factory main
Trans-former
Frequency converterPE U V W
PE
Factory main
Trans-former
L1
L2L3PE L1
L2L3
Fe-armour
Separate protective conductor
C
PE
PE
Concentric Al/Cu-shield
Separate
groundingprotective
wire
W
M 3~
VPEU W
M 3~
VPEUW
M 3~
VPEU
grounding bus grounding busgrounding bus
Variable Speed Drives
Grounding and Cabling of the Drive System
3AFY61201998 REV B
EFFECTIVE: 23.6.2005SUPERSEDES: 11.3.1998
© 2005 ABB Oy. All rights reserved.
Grounding and cabling of the drive system i
Table of contents
Table of contents ................................................................................................................................................. i
Chapter 1 Introduction..................................................................................................................................1-1 What this manual contains.......................................................................................................................1-1 Target audience .......................................................................................................................................1-1 General ....................................................................................................................................................1-1 Objectives of grounding ...........................................................................................................................1-1 Availability ................................................................................................................................................1-2
Bearing currents................................................................................................................1-2 The grounding structure...........................................................................................................................1-3
Chapter 2 Grounding of drive modules ......................................................................................................2-1 General ....................................................................................................................................................2-1
Chapter 3 Cabling of variable speed drives ...............................................................................................3-1 General ....................................................................................................................................................3-1 Supply ......................................................................................................................................................3-1
Transformer ...................................................................................................................................3-1 Grounded secondary (TN, TN-S)......................................................................................3-1 Floating secondary (IT) ....................................................................................................3-1
Cabling...........................................................................................................................................3-1 Low-power supply .............................................................................................................3-1 High-power supply ............................................................................................................3-3
Motor cables ............................................................................................................................................3-5 Recommended AC drive cable types for general applications ......................................................3-5 Availability ......................................................................................................................................3-6 AC drive cable types for limited use ..............................................................................................3-6 Cable routes ..................................................................................................................................3-6 Cabling of high-power frequency converter drives ........................................................................3-7 Additional grounding of motors ......................................................................................................3-8 Cable connections to be avoided.................................................................................................3-10 DC drives .....................................................................................................................................3-12
Signal cables..........................................................................................................................................3-13 PE (protective ground) vs. FE (functional ground) .....................................................................3-13 Interfacing problem of systems with dissimilar grounding ...........................................................3-14 Control cable shielding ................................................................................................................3-15
Analogue and low- voltage (SELV) digital I/O signals.....................................................3-15 Serial communication .....................................................................................................3-16 115/230 VAC digital signals ............................................................................................3-16 Shield connection............................................................................................................3-16
Cabling and insulation of tachometers, pulse encoders ..............................................................3-17 Examples of cabling system drives .............................................................................................3-18 Galvanic isolation.........................................................................................................................3-20 Cable routes ................................................................................................................................3-20 Common mode inductor ..............................................................................................................3-20
Chapter 4 Interference coupling, informative annex .................................................................................4-1 Common impedance coupling .................................................................................................................4-1 Capacitive coupling..................................................................................................................................4-2 Inductive coupling ....................................................................................................................................4-3
Grounding of drive modules
Electromagnetic coupling.........................................................................................................................4-4
Chapter 5 Terms and literature ....................................................................................................................5-1 Terms.......................................................................................................................................................5-1
Armour ...........................................................................................................................................5-1 Availability ......................................................................................................................................5-1 GND...............................................................................................................................................5-1 EMI ................................................................................................................................................5-1 FB ..................................................................................................................................................5-1 FE ..................................................................................................................................................5-1 PE ..................................................................................................................................................5-1 Shield.............................................................................................................................................5-1 TE ..................................................................................................................................................5-1
Literature..................................................................................................................................................5-2 EMC...............................................................................................................................................5-2 Bearing currents ............................................................................................................................5-2
ii Grounding and cabling of the drive system
Chapter 1 Introduction
What this manual contains
This manual describes the grounding and cabling principles of variable speed drive systems. The system may be composed of parts such as a transformer, mains cable, converter, motor cable and motor. The converter may be a single drive or system drive a.c. frequency converter or a d.c. converter. Examples of proper cabling and grounding practices for low voltage systems are given.
A short description of interference phenomena, terms and literature references are included at the end of the manual.
Target audience The manual is intended for persons involved in drive system installations and assembly.
General When the principles given in this manual are followed, the installation will fulfil the appropriate personal safety, electromagnetic compatibility (EMC) and availability requirements concerning grounding and cabling. Product specific instructions are given in the product manuals.
The installation must always be designed and made according to applicable local laws and regulations. ABB does not assume any liability whatsoever for any installation which breaches the local laws and/or other regulations. Furthermore, if the recommendations given by ABB are not followed, the drive may experience problems that the warranty does not cover.
Objectives of grounding
Traditional grounding is based on electrical safety. It ensures personal safety in all circumstances and limits material damages due to electrical faults. For interference-free operation and long-term availability of the drive, more profound methods are needed: high-frequency grounding and equipotential ground planes on building floor, equipment enclosure and circuit board levels.
Grounding and cabling of the drive system 1-1
Grounding of drive modules
Proper cabling and grounding strongly attenuates motor shaft and frame voltages that may cause high-frequency bearing currents and lead to premature bearing replacements.
Availability
Bearing currents
Two types of bearing currents are shown schematically below: high-frequency circulating current (5) and shaft grounding current (7).
INVERTER
MOTOR CABLE MOTOR GEAR LOAD
4
7
3 6 Shaft groundingcurrent
2 4High frequencyshaft voltage
High frequencyframe voltage
7
Common modevoltage pulse
2
1
3
5 6
5High frequencycirculating current
-DC
+DC1
1
High frequencycommon modecurrent
PE-current
1-2 Grounding and cabling of the drive system
Introduction
The grounding structure
Interference-free operation of electronics is facilitated by establishing equipotential areas on all structural levels. Building floors, equipment enclosures and circuit boards are using local ground planes on each level. The ground planes can also be mesh structures.
The best result is achieved by means of a well structured grounding. It begins with ground electrodes connected to each other reliably to form a network. The electrical equipment is connected to the network of electrodes through a short wiring to minimise the impedance (Figure 1-1).
~~ ~~ ~~ ~~ ~~ ~~ ~~ ~~
2
3
1
Figure 1 - 1. Recommended configuration for ground electrodes and grounding networks. 1 Power and communications ground, as needed 2 Soil 3 Multiple, bonded ground electrodes
In buildings where the ground plane model is not carried out, a radial conductor system is used for potential equalization. This is the practice in many old buildings.
A cabinet PE busbar shall be connected to factory ground only at one point if the ground electrode system is of a single electrode type and not well structured (Figure 1-2).
Grounding and cabling of the drive system 1-3
Grounding of drive modules
M M M
Figure 1 - 2. Grounding of the single-electrode drive system.
1-4 Grounding and cabling of the drive system
Chapter 2 Grounding of drive modules
General When assembling drive modules into a cabinet, they must be grounded for personal safety to prevent dangerous voltages under any circumstances. Connection to ground through fixing screws and the cabinet chassis is not always good enough. To ensure the continuity of the protective bonding circuit, modules must be connected to the cabinet PE busbar by a copper busbar or cable. The cross-sections must be in accordance with local regulations. From the EMC standpoint, low impedance high-frequency grounding (0.1 Ω, 25 A) is recommended. The best result can be achieved with a flat copper braid.
Grounding and cabling of the drive system 2-1
Grounding of drive modules
2-2 Grounding and cabling of the drive system
Chapter 3 Cabling of variable speed drives
General Cables are dimensioned on a case-by-case basis in accordance with the local regulations concerning short-circuit protection, operating voltage, permissible touch voltage appearing under fault conditions and current-carrying capacity of the cable. In addition, the cable type must support the EMC protection and availability of installed equipment.
This chapter describes examples of proper cabling and grounding practices. It is necessary to follow the instructions when selecting cables with the local vendor and implementing the grounding of the system.
Supply
Transformer A variable speed drive-dedicated transformer with static shielding between the primary and secondary is recommended.
Grounded secondary (TN, TN-S)
If no frequency converter input filter is used, the grounding impedance of the transformer secondary must be especially low: a at least 70 mm x 0.75 mm copper plate or at least two separate 50 mm2 cables. The distance between the cables must be at least 150 mm. If the installation specific drawings specify larger cross- sections for grounding, they must be followed. The length of the grounding conductor should be as short as possible.
Floating secondary
(IT)
All frequency converter input filters are not suitable for use on IT (ungrounded) systems. With unsuitable EMC filters, the system will be connected to earth potential through the EMC filter capacitors of the drive. This may cause danger or damage the unit.
Cabling
Low-power supply
At low currents (< 300 A) when one cable is sufficient, a shielded symmetrical multicore cable is recommended. The shield is connected to PE at both ends. When the converter incorporates an input filter, also unshielded cable can be used.
Grounding and cabling of the drive system 3-1
Cabling of variable speed drives
Trans-formerPE
L1L2L3
L1L2L3
PE
Converter
N N L1
L2 L3
N
ShortLow inductance
Factory main grounding bus
L1 L2 L3
Figure 3 - 1. Low-power supply with cable.
The reactance of a multicore cable is low enabling the longest supply cabling. With parallel multicore cables, also high currents are possible.
3-2 Grounding and cabling of the drive system
Cabling of variable speed drives
High-current (> 300 A) variable speed drives can be supplied either with a busbar or cable bus system. The metal conduit (shield) of the busbar system shall be connected to PE (Figure 3-2) at either one or both ends.
High-power supply
Trans-former
PE
L1L2L3
N
L1L2L3
PE
Converter
Metal conduit (shield)
N
L1 L2 L3 N
Factory main grounding bus
Figure 3 - 2. Power supply with busbars.
A cable bus system consists of parallel single-core cables for phase leads. Compared to a corresponding busbar system, a cable bus system has:
• better cooling due to separe conductors -> less concuctor material is needed
• lower reactance -> longer distances are allowed.
Trans-former
PE
L1L2L3
N
L1L2L3
PE
Converter
N
Factory main grounding bus
Figure 3 - 3. Power supply with cable bus system.
Grounding and cabling of the drive system 3-3
Cabling of variable speed drives
It is recommended to arrange the cables as shown in Figure 3-4 to achieve as equal a current distribution as possible.
L1 L2 L3 N L1 L2 L3 N L1 L2 L3 N
Figure 3 - 4. Cable bus arrangement.
In single-core cables equipped with concentric protective shield (armour), the phase current induces voltage to the cable shield. If the shields are connected to each other at both ends of the cable, current will flow in the cable shield. In order to prevent this current and to ensure personal safety, the cable shield must be connected to PE at the feeder side only and insulated at the converter side (Figure 3-5).
Trans-former
PE
L1L2L3
N
L1L2L3
PE
Converter
N
Concentric shield
Factory main grounding bus
Figure 3 - 5. Shield connection of single-core cables.
3-4 Grounding and cabling of the drive system
Cabling of variable speed drives
Motor cables Recommended AC drive cable types for general applications
To meet the EMC and availability requirements, only shielded, symmetrical, multicore cables shall be used. Exceptions to this rule are given in the product specific manuals.
To be effective at high frequencies, the shield conductivity shall be at least 1/10 of the phase conductor conductivity. The effectiveness of the shield can be evaluated based on the shield inductance, which must be low and only slightly dependent on frequency. The requirements are easily met with a copper or aluminium shield/armour. The cross-section of a steel shield has to be ample and the shield helix low gradient. Galvanizing increases the high-frequency conductivity.
Aluminium and copper shields are connected to PE at both ends. 360° bonding of the shield utilizes the full high-frequency capability to comply with the EMC and availability requirements. To operate as a protective conductor, the shield conductivity must be at least 50% of the phase lead conductivity.
Three alternative cable types can be recommended. The first cable type is a three-core cable equipped with concentric protective copper shield. The phase wires are at an equal distance from each other and the shield, and the shield is used as a protective conductor. The cross-section of the protective copper braid or strand must be sufficient according to safety regulations. Figure 3-6. A.
Figure 3 - 6. Approved motor cable connections (A, B and C for general use. D for limited use.).
Grounding and cabling of the drive system 3-5
Cabling of variable speed drives
An equally suitable cable type, 3+3+Cu/Al-shield + possible armour, has three symmetrical conductors for protective grounding. The shield is typically a solid corrugated aluminium armour. The shield is connected to the PE bar on the frequency converter side and to the PE terminal on the motor side. Figure 3-6. B.
The third cable type has a galvanized iron, coarse-pitch, stranded armour shield. The shield is connected to PE at both ends. However, a separate high-conductivity PE conductor is needed unless sufficient cross-section of copper is incorporated in the strand, as in some cables from some manufacturers. Figure 3-6. C.
The length of the unshielded part of the cable should be as short as possible on the frequency converter side and at the motor junction box as specified in the drive and motor specific documentation.
Availability The bearing current risk depends on voltages affecting across the motor bearings. Three basic types of voltages can be measured in AC drive applications: shaft end-to-end voltage, shaft voltage to ground or motor frame voltage to ground.
On medium and high power motors, improper motor cabling strongly increases these voltages, thus reducing the lifetime of the motor, gearbox and driven machine bearings. On the other hand, proper cabling and 360° termination of the cable shield at both ends effectively reduce these voltages. Symmetrical, shielded cables reduce the motor frame voltage, the effect being more significant at high motor currents.
AC drive cable types for limited use
Cable sizes up to 10 mm2 and motor powers up to 30 kW
Unsymmetrical cables can be used up to 10 mm2 cable size and up to 30 kW motor power, but a shielded cable is always recommended. Foil shield is common in this power range.
Note: Using a non-shielded cable even in this motor power range may cause interference of other equipment.
Motor power up to 100 kW
Well-shielded (copper or aluminium shield) 4-core or 3+1 core cables can be used for up to 100 kW motor power rating (Figure 3-6. D) with potential equalization according to Figure 3-8a.
Cable routes Cable trays shall have good electrical bonding to each other and to the grounding electrodes. Aluminium tray systems can be used to improve local equalization of potential.
3-6 Grounding and cabling of the drive system
Cabling of variable speed drives
When cabling a high-power frequency converter and motor, several conductor elements have to be used in parallel. In this case, the cabling shall be done according to Figure 3-7.
Cabling of high-power frequency converter drives
Always use symmetrical cabling.
=
~U V W
1 2 3
UV
W
M3 ~
DC bus
1 2 3 1 2 3
1 2 3 1 2 3 1 2 3
Figure 3 - 7. Symmetrical cabling of the high-power frequency converter and motor.
Grounding and cabling of the drive system 3-7
Cabling of variable speed drives
With motors from 100 kW upwards, a potential equalization connection between the motor frame and the machinery is sometimes needed due to the grounding conditions of the driven machinery. Potential equalization is typically needed in applications such as pumps (grounded by water) and gearboxes with central lubrication (grounded by oil pipes). As low inductance is the objective, a copper plate or strip with a cross-section of at least 70 mm x 0,75 mm is required between the motor frame and the gearbox/pump frame. Alternatively, at least two separate 50 mm2 cables can be used. The distance between the cables must be at least 150 mm. Install the potential equalization through the shortest possible route. If protection from dirt is needed, use a plastic tube, not a metal conduit.
Additional grounding of motors
Potential equalization has no electrical safety function. The purpose of it is purely to equalize the potentials. When the motor and the gearbox are mounted on a common steel fundament, no potential equalization is needed.
Potential equalization
U1V1
W1PE
3 ~ M
Driven machinery
0.75 mm
70 mm
> 150 mm
min 50 mm2
Cables/wiresPlate/strip
Figure 3-8a. Potential equalization between the motor frame and the machinery. The purpose of this connection is to equalize the potentials. It has no electrical safety function. When the motor and the gearbox are mounted on a common steel fundament, there is no need to make the connection.
3-8 Grounding and cabling of the drive system
Cabling of variable speed drives
Large motors may have additional grounding terminals outside the terminal box. Connect them to the PE on the motor frame (Figure 3-8b) to ensure a proper connection between the terminal box and the frame.
Cu-cable50 mm2
Figure 3 - 8b. Equalization of the potential of the motor frame and the terminal box of large motors.
Grounding and cabling of the drive system 3-9
Cabling of variable speed drives
If other than the recommended cable types are used, the following rules are mostly useful. Complying with them does, however, not exclude effects of improper cabling and may void warranty.
Cable connections to be avoided
In four-core cables (one is ground), three cores are not at an equal distance from the ground wire. The ground wire must not be used as a protective conductor. The ground wire shall be connected to PE only on the frequency converter side, and it shall be isolated at the motor end. Use a separate protective conductor with a cross-sectional area of at least half of the phase conductor cross-section. The power cable and the protective conductor shall be placed at least 300 mm apart (not on the same cable tray) in order to prevent inductive disturbance currents in the protective conductor (Figure 3-9A). This lay-out can in some countries violate the regulations. In this case, use other cable types.
When a fine-pitch interlaced steel plate armour is provided, the high-frequency capability of the armour is insufficient. The armour can be terminated to PE at both ends if its conductivity is at least 1/10 of the conductivity of the phase conductor. If the conductivity is less than 1/10, leave the motor end open. Do not use the internal unsymmetrical ground wire (fourth conductor) as a protective conductor (figures 3-9.B and 3-9.C). Apply the same rules also to three-core cables. Make the potential equalization connection between the motor frame and the machinery as described on page 3-8.
Single-core cables are not suitable for motor cables!
3-10 Grounding and cabling of the drive system
Cabling of variable speed drives
A B
Frequency converterPE U V W
PE
Factory main
Trans-former
Frequency converterPE U V W
PE
Factory main
Trans-former
L1
L2L3
PE
Separate protective conductor
L1
L2L3PE
Tape Fe-armour
Separate protective conductor
W
M 3~
VPEU W
M 3~
VPEU
Separate
groundingprotective
wire
Frequency converterPE U V W
PE
Factory main
Trans-former
L1
L2L3PE
Tape Fe-armour
Separate protective conductor
W
M 3~
VPEU
Separate
groundingprotective
wire
C
Low armour conductivity <10% High armour conductivity >10%
Separate
groundingprotective
wire
grounding bus grounding bus grounding bus
Figure 3 - 9. Motor cable connections to be avoided.
Grounding and cabling of the drive system 3-11
Cabling of variable speed drives
The same basic rules apply as for AC motors. The most economical power cable has an even number of conductors. Also three-core cables with shield can be used. For larger motors, where several cables are needed, power sharing of three-core cables is made based on the 2+1 / 1+2 principle (Figure 3-10).
DC drives
The excitation cable is a heavy source of interference because of the abrupt commutation. Therefore, always use shielded excitation cables.
Single-core cables shall be rejected for DC drives.
Motors with stator serial winding must have a grounding brush on the shaft to avoid bearing problems.
+ -
1 2 3
+ -
M-
AC bus
1 2 3
1 2 3 1 2 3
1 2 3
1 2 3
+ -
Figure 3 - 10. Symmetrical cabling between the DC converter and the motor
3-12 Grounding and cabling of the drive system
Cabling of variable speed drives
Signal cables PE (protective ground) vs. FE (functional ground)
The ABB policy is to use uniform, equipotential PE grounding with drive systems. The principle is extended to all structural levels of installations in large buildings containing electrical equipment. Example levels are floor, equipment cubicle and circuit board levels.
It is not possible to keep all levels of a large system at the same high-frequency potential, but applying uniform PE grounding at all levels will ensure electromagnetic compatibility.
The end users also apply other installation philosophies, for example, systems with PE and FE (former TE). This is usual in electronic equipment of other manufactures and several previous ABB products.
The FE system of co-operating equipment can be either general or partial (only part of the equipment is built using FE ground, Figure 3-11).
In the sense that the PE and FE grounds are connected together at one point only, the PE/FE structure resembles a one ground-level uniform PE system. Therefore, a large FE system may also need an effective local figh-frequency ground and becomes more like the uniform PE system (Figure 3-12).
Figure 3 - 11. PE and FE system
Grounding and cabling of the drive system 3-13
Cabling of variable speed drives
Figure 3 - 12. Uniform PE system
Interfacing problem of systems with dissimilar grounding
Many existing installations today have been made by applying other grounding principles than those given in this manual, specially concerning low-frequency EMC, even starting from the ground electrodes.
New deliveries, which employ the uniform PE system, are usually additions which have to operate together with the old equipment. Existing systems, implemented with a different philosophy, usually operate well, and making changes in them is out of the question. The mismatching may create problems, which have to be solved case by case. Physically large installations (dimensions, power) normally need some kind of matching.
The matching is done to obtain sufficient compatibility. Sometimes, it is reasonable to accept a lower immunity level. The legal requirements concerning emissions and immunity must, however, be fulfilled.
Matching elements between the systems are usually transformers, optocouplers, optical fibre links, galvanic analogue isolation and common mode interference filters and inductors. All these methods can improve signal transmission. Isolation transformers are used for power supply.
This guide will not go deep into the interfacing practice. It is, however, important to be aware of the interfacing problem areas before implementing signal cables.
3-14 Grounding and cabling of the drive system
Cabling of variable speed drives
It is very important to use correct cable types to meet the EMC compatibility. A wrong cable type can cause severe interference problems. A shielded control cable will reduce disturbances.
Control cable shielding
Always use a shielded cable for safety low-voltage (SELV) control signals.
Analogue and low-
voltage (SELV)
digital I/O signals
Twisting the signal wire with its return wire reduces disturbances caused by inductive coupling. Pairs should be twisted as close to terminals as possible.
A double-shielded twisted pair cable shall be used for analogue signals. Employ one individually shielded pair for each signal. Do not use common return for different analogue signals (Figure 3-13).
A double-shielded cable is the best alternative for low-voltage digital signals but single-shielded twisted pair cable is also possible (Figure 3-14).
Never mix 24 VDC and 115/230 VAC signals in the same cable.
Figure 3 - 13. Double-shielded twisted pair cable
Figure 3 - 14. Single-shielded twisted pair cable
Grounding and cabling of the drive system 3-15
Cabling of variable speed drives
There are several alternatives depending on the type of communication. The communication systems employ either double-shielded (Figure 3-13) or coaxial cables in internal communication. A part of the serial communication is implemented with optical cables (figures 3-17 and 3-18).
Serial communication
A communication system may also have its own cable specification.
Note that serial communications will operate properly only with correct terminating resistors. See the system-specific instructions.
115/230 VAC digital signals
A shielded cable with proper voltage rating is the best alternative but an unshielded multi-core cable can also be used. (Figure 3-15).
Figure 3 - 15. Unshielded multi-core cable
Shield connection
Always connect the shield of a control cable to a ground terminal on the converter side. A ground terminal can be a special clamp, screw or terminal block marked with PE, FE, GND or one of the following symbols:
The unshielded part of the cable shall be minimized. The ground connection of the shield shall be kept as short as possible.
3-16 Grounding and cabling of the drive system
Cabling of variable speed drives
A signal cable shield left unconnected (ungrounded) at both ends does not suppress disturbances.
Grounding a signal cable shield at one end only suppresses the electromagnetic field and inductive disturbances enough in most cases.
Grounding a signal cable shield at both ends improves disturbance suppression above a certain frequency, but forms also a loop where low-frequency current will flow if the ends of the cable shield are at different potentials. Therefore, if high-frequency grounding is needed, the other end of the shield should be grounded via a capacitor. In some equipment the capacitor is incorporated. (Figure 3-16).
Figure 3 - 16. Grounding of signal cables
Cabling and insulation of tachometers, pulse encoders
A tachometer shall be insulated electrically from the motor stator or rotor to prevent the forming of a current path through the tachometer.
The usual coupling-type encoder must have an electrically insulating coupling. When a hollow-shaft type tachometer is used, the insulation can be implemented by insulating the ball joints of the engaging arm, or insulating the bar of the engaging arm. The shield of the tachometer cable should be insulated from the tachometer frame. The other end of the shield should be grounded at the converter PE, see figures 3-17 and 3-18.
Always use a double-shielded cable for the pulse encoder. In case of high-frequency interference problems, the cable shield can be grounded at the encoder end via a capacitor. Single-shielded cables can be used with analogue tachometers.
In hollow-shaft encoders with electrical insulation between the hollow-shaft and the tachometer frame, the cable shield can be connected to the tachometer frame also.
Grounding and cabling of the drive system 3-17
Cabling of variable speed drives
Typical examples of cabling in AC and DC drive systems are shown in figures 3-17 and 3-18.
Examples of cabling system drives
TE
TE
TAITERMINALBLOCK
CONTROLLER (APC)
ADVANCED, COMPACTOPERATOR STATION
+5VP 0VPGND
24V
0V+24V
GND
A
B
A B1)
TE
TEBLOCKTERMINALTAI
TE
(110V)
EXTENDEDI/O
B = Negative signal conductorA = Positive signal conductor
1)
1)
PE
24V
230V
B
A
This wire is connected to boardrack housing in the first drive section only
pair cableFibre-optic
Fibre-optic pair cable
BUTORDISTRI-OPTICAL
APPLICATIONCONTROLLER(APC)
APPLICATION
(APC)CONTROLLERAPPLICATION
SERIAL
UNITLINK
ADMINISTATORMB90 BUS
1X32
1X2
1X32
1X2
INVERTERINVERTERINVERTER
INCOMER SECTION DRIVE SECTIONDRIVE SECTIONDRIVE SECTION
BLOCKTERMINALAPC
INTERFACEMB90 BUS
X2 1 2
MB90 BUSMB90 BUSINTERFACE
X3
MEB
24V
=~
24V
PE
M3~
PEPE
3~M
TE
TE
FREQUENCE
GND0VP
+5VP
TE0
1
TE
PE
3~M
2)
2) Boardrack
2)
2)
RED BLUELINE 1 LINE 2
0VP
0VP0V+24V
24V
EXTENDEDI/O
0V+24V
COMPACTOPERATOR STATION(AOS,COS)
GND
GND
A
B
A
B
B
A
GND
+24V0V
EXTENDEDI/O
CHA2CHA124V
TE
TAI TERMINAL BLOCK
ADVANCED,
(AOS,COS)
CONVERTER INTERFACE
+24V0V
TETE
Figure 3 - 17. Typical example of AC drive system grounding
3-18 Grounding and cabling of the drive system
Cabling of variable speed drives
TE
TE
(110V)
EXTENDEDI/O
B = Negative signal conductorA = Positive signal conductor
1)
1)
PE
24V
230V
B
A
This wire is connected to boardrack housing in the first drive section only
pair cableFibre-optic
Fibre-optic pair cable
BUTORDISTRI-OPTICAL
APPLICATIONCONTROLLER(APC)
(APC)CONTROLLERAPPLICATION
SERIAL
UNITLINK
ADMINISTATORMB90 BUS
1X321X2
INCOMER SECTION DRIVE SECTIONDRIVE SECTIONDRIVE SECTION
BLOCKTERMINALAPC
INTERFACEMB90 BUS
X2 1 2
MB90 BUSINTERFACE
X3
MEB
24V
=~
PE
TE
FREQUENCE
GND0VP
+5VP
TE0
1
TE
2)
2) Boardrack
2)
RED BLUELINE 1 LINE 2
0VP
0VP0V+24V
24V
EXTENDEDI/O
0V+24V
COMPACTOPERATOR STATION(AOS,COS)
GND
GND
A
B
A
B
B
A
GND
+24V0V
EXTENDEDI/O
CHA2CHA124V
TE
ADVANCED,
CONVERTER
+24V0V
CONTROLLER (APC)
OPERATORSTATION (AOS)
+5VP 0VPGND
24V
0V
+24V
GND
A
B
A B1)
APPLICATION
1X3
21X2
MB90 BUS INTERFACE
24V
ADVANCED
TERMINALBLOCK
DIGITAL ANALOGUE
BLOCKTERMINAL
-M
CONVERTORCONVERTOR
M-
TE
TERMINALBLOCK
DIGITAL
ANALOGUE TERMINAL BLOCK
TE
2)
TE
TE
TE TE
CONVERTOR
TERMINALBLOCK
DIGITAL ANALOGUE
PULL-OUT UNIT
-M
BLOCKTERMINAL
Figure 3 - 18. Typical example of DC drive system grounding
Grounding and cabling of the drive system 3-19
Cabling of variable speed drives
Galvanic isolation of control signals improves the interference immunity and is recommended specially at long distances. Isolation prevents interference caused by common impedance coupling (ground loop) and suppresses inductive coupling interference. Weak signals are isolated and amplified at the source, normal signals can also be isolated at the receiving end.
Galvanic isolation
Cable routes Avoid parallel running of power cables and signal cables. The distance between power and control cables should be at least 500 mm. When control cables must cross power cables, make sure they are arranged at an angle as near to 90 degrees as possible.
The cable trays shall have good electrical bonding to each other and to the grounding electrodes. Aluminium tray systems can be used to improve local equalization of potential.
Common mode inductor
In applications of high emission level such as trains, trams and moving machines, common mode inductors can be used in signal cables to avoid interfacing problems between different systems.
Common mode disturbances can be suppressed by wrapping the signal conductors through a common mode inductor ferrite core (Figure 3-19). The ferrite core increases inductance of conductors and their mutual inductance so that common mode disturbance signals above a certain frequency are suppressed. An ideal common mode inductor does not suppress differential mode signals.
Figure 3 - 19. Common mode inductor
3-20 Grounding and cabling of the drive system
Chapter 4 Interference coupling, informative annex
Common impedance coupling
Common impedance coupling appears, if interference source circuits have a common current path (Figure 4-1), e.g. in the grounding or power supply circuit. Current changes in the interfering circuit cause potential changes in the common impedance: u = R * i - L * di/dt.
Coupling via a ground loop can be reduced as follows:
- Low-frequency coupling can be prevented by using one-point grounding.
- For high frequency, it is most essential to keep inductance as low as possible. To achieve lowest impedance, the relation between the length and width of a conductor should be less than five. In practice, this rule is implemented by multi-point grounding.
Figure 4 - 1. Common impedance coupling
Grounding and cabling of the drive system 4-1
Capacitive disturbance is coupled by changing electric field. Capacitive coupling appears in circuits that have stray capacitance with each other. Interference current (IN) is proportional to frequency (f), voltage level of the interfering conductor (V1) and stray capacitance between conductors (C12).
Capacitive coupling
V j2 f V CN 1 1= R2× × ×π (Figure 4-2)
Capacitive coupling can be reduced by:
- reducing stray capacitances between circuits
- reducing the impedance level of the victim circuit
- limiting the frequency level of the interfering circuit
- limiting voltage level of the interfering circuit.
Stray capacitance can be reduced by:
- using metal casings for devices
- using shielded conductors
- increasing the distance between conductors
- using a ground plane between conductors.
Figure 4 - 2. Capacitive coupling
4-2 Grounding and cabling of the drive system
Cabling of variable speed drives
Inductive disturbance is coupled via magnetic field. Current in the interfering circuit will generate magnetic flux around the conductor. When a changing magnetic flux perforates a closed loop, an alternative voltage will be induced to the victim circuit and interference current will flow in the closed loop. Interference voltage (VN) is proportional to frequency (f), current (I1) of the interfering conductor, mutual inductance of circuits (M12). Mutual inductance can be calculated by the area of the loop perpendicular to the magnetic lines (Acosθ) and the distance between conductors (r).
Inductive coupling
V j f MN = I× ×2 12 1π (Figure 4-3)
M Acos12 2= r×µ θ π (long, straight conductors)
Inductive coupling can be reduced by:
- reducing mutual inductance between circuits - filtering the high frequency content of the interfering circuit - reducing the current of the interfering circuit.
Mutual inductance can be reduced by:
- using twisted pairs as signal cables - increasing the distance between conductors - reducing the loop area by galvanic isolation - avoiding parallel conductors and coils.
By shielding the victim conductor with a material that has high permeability, some extra suppression will be achieved. (High-permeability material "short-circuits" magnetic circuits, so most of the flux flows through this material.)
High-frequency disturbance is reduced by using a metal enclosure or shield.
Highly-conductive metals such as aluminium and copper are good shield materials.
Figure 4 - 3. Inductive coupling
Grounding and cabling of the drive system 4-3
Electromagnetic energy can propagate in free space as a wave motion. Each conductor carrying a changing current is a potential transmitter antenna of electromagnetic waves.
Electromagnetic coupling
Reciprocally, all conductors can operate as receiver antennas. In addition, each conductor, whether part of the active circuit or not, will shape the fields and perhaps amplify the antenna operation. Sometimes, a solid insulator may behave in the same way. The efficiency of the antenna increases at high frequencies when the antenna dimensions exceed about 1/100 of the wave length. Therefore, the problem worsens above 10 MHz frequencies due to improved antenna function, suitable dimensions of normal digital electronics and their operation at those speeds.
Also, part of the climatic interference, e.g. lightning at a long distance, lies at frequencies from 10 to 100 MHz. A stroke of lightning close to electronic equipment easily stops normal function and may damage the equipment. The coupling decreases as the distance increases.
How to protect against electromagnetic waves?
- Use ground planes or mesh structures as local ground.
- Use shielded cables.
- Use metal enclosures for equipment (leaky doors are problematic).
- Openings in enclosures must be small.
- Prevent unintentional antenna structures.
- Ground systematically at short (< 1/10 wavelength) intervals.
- Pay attention to high-frequency grounding, i.e. capacitive grounding of coaxial cables, for instance.
Due to reciprocity, these rules apply to both sides, the source and the victim.
4-4 Grounding and cabling of the drive system
Chapter 5 Terms and literature
Terms Some terms used in this manual or related to the subjects of this manual are described briefly below.
Armour Metal sheath commonly of woven wire, spiralled tape or solid corrugated metal covering the insulation of an electrical conducting cable and serving both as a mechanical protection and as a shield against electrostatic or electromagnetic induction.
Note that sometimes a cable may contain both an electromagnetic shield and a separate armour for mechanical protection, but both are electrically bonded.
Availability Capability of a device or system to be used for the intended purpose.
GND General ground
EMI Electromagnetic interference
FB Functional bonding
FE Functional earthing (grounding). Earthing a point or points in a system, installation or equipment, for purposes other than electrical safety. IEC 60050-195 (195-01-13) 1998.
PE Protective earthing (grounding). Earthing a point or points in a system, installation or equipment for purposes of electrical safety. IEC 60050-195 (195-01-11) 1998.
Shield Part of an electromagnetic barrier that separates the shielded circuits from the external sources of EMI (or confines EMI effects to the shielded volume). An electromagnetic barrier is a closed surface made up of shields and other elements to exclude (or to confine) electromagnetic waves propagating in space or guided along conductors. The barrier may be made of metal, conductively coated equipment cases, interconnecting cable shields, filters or surge arresters on wires that penetrate the shield and mesh or wave guides (below cut-off frequency) at ventilation openings. In a protected system, the barrier is everywhere sufficiently impervious for guided and space waves of EMI sources outside the barrier not to degrade the performance of the protected system.
TE Technical earth (ground). This term has been replaced with FE.
Grounding and cabling of the drive system 5-1
Literature EMC "Interference-free electronics" by Dr. Sten Benda.
Ordering number ABB 3BSE 000877R0001, ISBN 91-44-3140-9, ISBN 0-86238-255-6.
Bearing currents "High Frequency Bearing Currents in Low Voltage Asynchronous Motors" 3GZF500930-8.
A New Reason for Bearing Current Damage in Variable Speed AC Drives by J. Ollila, T. Hammar, J. Iisakkala, H. Tuusa. EPE 97. The European Conference on Power Electronics and Applications 810 September 1997 Trondheim, Norway pp. 2.539 to 2.542.
On the Bearing Currents in Medium Power Variable Speed AC Drives by J. Ollila, T. Hammar, J. Iisakkala, H. Tuusa. Proceedings of the IEEE IEDMC in Milwaukee, May 1997.
Evaluation of Motor Power Cables for PWM AC Drives by John M. Bentley, Patric J. Link. IEEE Trans. Ind. Appl., 1997, Vol 33, pages 342358.
Minimizing Electric Bearing Currents in Adjustable Speed Drive Systems by Patric J. Link. IEEE IAS Pulp & Paper Conference Portland, ME, USA June 1998.
IEC 61000-5-2: 1997. Installation and mitigation guidelines Earthing and cabling.
IEC 60034-17:2002 Rotating electrical machines, Cage induction motors when fed from converters Application guide.
IEC 60034-25:2004. Rotating electrical machines Guide for the design and performance of cage induction motors specifically designed for converter supply.
Laakerivirta ja sen minimoiminen säädettyjen vaihtovirtakäyttöjen moottoreissa. Ilkka Erkkilä. Automaatio 1999 14.16.9. Helsinki.
GAMBICA/REMA Technical Report No. 2 Motor Shaft Voltages and Bearing Currents under PWM Inverter Operation. 2002.
GAMBICA/REMA User guide No. 3 Installation Guidelines for Power Drive Systems. 2003.
5-2 Grounding and cabling of the drive system
3AFY
6120
1998
Rev
B E
NEF
FEC
TIV
E: 2
3.6.
2005
ABB OyAC DrivesP.O. Box 184FIN-00381 HELSINKIFINLANDTelephone +358 10 22 11Fax +358 10 22 22681Internet http://www.abb.com