    Description

    Special grille type G is a range of aluminium grilles with fixed

    slanting horizontal bars for air exhaust. The grille can be

    configured on the basis of the summary. As part of the con-

    figuration you can select the type of mounting and accesso-

    ries. Finally, A x B dimensions are specified. These have

    certain limitations, which are shown under the order code.

    MaintenanceDepending on the configuration, the grille can be removed

    to enable cleaning. The external parts should be wiped with

    a damp cloth.

    Mounting

    0. Not prepared for installation

    1. With screw holes

    2. With springs only for installation in box

    3. With springs and mounting frame

    Accessories

    0. Without accessories

    2. With damper

    Ordering exampleG a b ccc ddd

    Type

    Mounting

    Accessories

    A - measure

    B - measure

    A x B: Duct/cutout

    A dimension: along the bars

    B dimension: across the bars

    Can be supplied in all dimensions.

    Max. A x B = 2000 x 2000Min. A x B = 100 x 60

    Free area F [m2]= (A-25) x (B-25) x 0.5 x 10-6

    Mounting frame and volume regulator - see GGR/GAT.

    B+25/A+25

    B-25/A-25

    BA

    24

    6

    B-6/A-6

    8

    62

    Materials and finishGrille and accessories: Aluminium

    Mounting frame: Galvanised steel

    Standard finish: Natural anodisedOn request: RAL 9010 Gloss 30

    The grille is available in other colours. Please contact

    Lindabs sales department for further information.

  • 7/31/2019 Grilles G20 - G

    3/3

    comfort | grilles

    We reserve the right to make changes without prior notice 429

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    18

    Ventilation grille/special grille G20/G

    Technical data

    CapacityVolume flow q [l/s] and [m3/h], total pressure drop pt [Pa],

    throw l0.2 and sound level LWA [dB(A)] can be seen in the

    diagrams.

    Frequency-related sound effect levelThe sound effect level in the frequency band is defined as

    LWA+Kok.KKok values are given in chart. See table below.

    Volume regulatorCorrection of sound pressure pt [Pa] and sound level LWA[dB(A)] using volume regulator. See table below.

    Centre frequency Hz

    63 125 250 500 1K 2K 4K 8K

    Kok 4 -1 3 -1 -6 -14 -22 -22

    Exhaust Open 45o Closed

    Pressure [Pa] x1,3 x 3 x12

    Sound power leveldB(A)

    +3 +12 +32

    20 30 40 50 60 100 150 200 300 500 700 1000 1500

    qV [l/s]3

    5

    7

    10

    15

    20

    30

    50

    70p t [Pa]

    100 150 200 300 400 700 1000 2000 3000 5000qV [m

    3/h ]

    0.01052 0.015 0.02 0.03 0.05 0.0791F [m

    2]

    G20

    LWA dB(A)30

    35

    40

    45

    50