Datasheet Grid feeding monitoring relay according to CEI 0-21 CM-UFD.M32 - 3 input contacts for remote trip, feedback signal, and external signal - Tripping delay for each threshold adjustable - Alarm memory for up to 10 entries (incl. cause of alarm, measured value, relative timestamp) - Autotest function - Password setting protection - 3 c/o (SPDT) contacts - 106.3 mm, 6 modules case for DIN rail - LEDs for the indication of operational states. Marks Characteristics - Monitoring of single and three-phase mains for grid feeding - Type-tested in accordance with CEI 0-21 - Over- and undervoltage, 10 minutes average value as well as over- and underfrequency monitoring - Two-tier threshold settings for over-/ undervoltage/ -frequency - Integrated management of redundancy function (mandatory in plants with P>20 kW) - Measured values, thresholds and settings shown on the display - All threshold values adjustable as absolute values - Default setting according to CEI 0-21 - True RMS measuring principle - High measurement accuracy CM-UFD.M32 is a multifunctional grid feeding monitoring relay. It provides different monitoring functions in accordance with CEI 0-21 ed. June 2012. It detects over- and undervoltage (10 minutes average value, voltage increase and decrease protection) as well as any changes in grid frequency (double thresholds, frequency increase and decrease protection). The device is connected between the decentralized electrical energy source and the public grid in order to disconnect it, in case of problems, faults or maintenance into the grid. Order data Type Rated control supply voltage Measuring range Order code CM-UFD.M32 24 V AC/DC or 230 V AC 10-520 V AC 1SVR 510 730 R4400

Grid feeding monitoring relay CM-UFD...Y30-Y31 Digital Input 3 external signal 11-12/14 Output Relay 1 trip relay (normally energized) 21-22/24 Output Relay 2 (2 nd DDI or closing

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

  • Datasheet

    Grid feeding monitoring relay according to CEI 0-21CM-UFD.M32

    - 3 input contacts for remote trip, feedback signal, and external signal

    - Tripping delay for each threshold adjustable - Alarm memory for up to 10 entries (incl. cause of alarm,

    measured value, relative timestamp) - Autotest function - Password setting protection - 3 c/o (SPDT) contacts - 106.3 mm, 6 modules case for DIN rail- LEDs for the indication of operational states.

    Marks

    Characteristics- Monitoring of single and three-phase mains for grid feeding - Type-tested in accordance with CEI 0-21- Over- and undervoltage, 10 minutes average value as well

    as over- and underfrequency monitoring - Two-tier threshold settings for over-/ undervoltage/

    -frequency- Integrated management of redundancy function (mandatory

    in plants with P>20 kW)- Measured values, thresholds and settings shown on the

    display - All threshold values adjustable as absolute values - Default setting according to CEI 0-21- True RMS measuring principle - High measurement accuracy

    CM-UFD.M32 is a multifunctional grid feeding monitoring relay. It provides different monitoring functions in accordance with CEI 0-21 ed. June 2012. It detects over- and undervoltage (10 minutes average value, voltage increase and decrease protection) as well as any changes in grid frequency (double thresholds, frequency increase and decrease protection). The device is connected between the decentralized electrical energy source and the public grid in order to disconnect it, in case of problems, faults or maintenance into the grid.

    Order data

    Type Rated control supply voltage Measuring range Order code

    CM-UFD.M32 24 V AC/DC or 230 V AC 10-520 V AC 1SVR 510 730 R4400

  • 2 CM-UFD.M32 - Grid feeding monitoring relay according to CEI 0-21 | Data sheet

    FunctionsOperating controls

    ApplicationThe grid feeding monitoring relay (SPI), that monitors network voltage and frequency, allows to disconnect distributed generation (GD) whenever the parameters are over the adjusted thresholds. Completely adjustable the CM-UFD.M32 assures the necessary flexibility to integrate medium and small production plants. In conformity to CEI 0-21 Ed. June 2012, the CM-UFD.M32 relay could be used in all the low voltage plants and in medium voltage plants with power less than 30 kW. The relay is mandatory in all low voltage production plants with power > 6 kW or with more than 3 generators (eg. Plants with more than 3 inverters).

    Operating principle

    Grid feeding monitoring relay according to CEI 0-21Programming mode and use

    Protective functionsIf control supply voltage is applied and all phases are present with correct voltage and frequency values, output relay 11-12/14 (DDI) energizes and the start-up delay begins. When the delay is complete, output relay 21-22/24 energizes or de-energizes, depending on the configuration. The green LED U is on. If the measured values exceed or fall below the set threshold values, output relay 11-12/14 de-energizes after the adjusted delay and output relay 21-22/24 energizes or de-energizes, depending on the configuration, when the adjusted delay is complete. The fault type is indicated by the red LEDs F1 or F2. The threshold value that has caused tripping is shown on the display.As soon as the measured value returns to the tolerance range, taking into account a fixed hysteresis (less than 100 ms as requested by standard CEI 0-21), output relay 11-12/14 re-energizes without delay; output relay 21-22/24 energizes or de-energizes, depending on the configuration, when the adjusted delay is complete. When output relay 11-12/14 is re-energized the red LEDs F1 or F2 turn off and the fault message on the display disappears. The event that has caused tripping of the relay is recorded in the menu “events”.Protective function V>59 S1 med. (10-minutes average value): The relay calculates the sliding root mean square of the voltage value (in case of 3 phase 3 voltage values) over a period of 10 minutes. The voltage values are updated every 3 seconds. If the 10-minutes average value exceeds the threshold value, the output relays trip when the adjusted delay is complete.

    CM-UFD

    U

    F1

    F2

    A1

    220V AC 24V AC/DC

    A2 A3 A4 L1 L2 L3 N Y31Y30Y21Y20

    34 31 32 24 21 11 121422Y11Y10

    Enter

    Set

    Display

    Enter programming/exit

    Values increase

    Confirm selection

    Remote trip

    Measurements

    External signal

    Local command

    Trip DDI

    Values decrease

    LEDs status

  • Data sheet | CM-UFD.M32 - Grid feeding monitoring relay according to CEI 0-21 3

    Event listThe relay records and logs the last 10 events that caused tripping of the relay. Relevant information is available in the menu “Events” where the type of event such as protection or auto test are recorded as well as the time passed since the last tripping of the relay in hours, minutes and seconds. If the relay is switched-off and switched-on again, the measured time is reset.

    Redundancy functionThe redundancy relay 31/32-34 (DG) is activated if relay 11/12-14 has de-energized and, within the adjustable time delay, no feedback from the external contact has been recognized by the internal logic via Y10-Y11. The external contact is connected in series to the coil of the relay itself, representing the status of the disconnection device. In case a feedback signal is present, the redundancy relay does not trip.

    Relay 2 (21/22-24)Output relay 2 can be used for the closing command of the breaker motor. In case output relay 11/12-14 energizes the adjustable delay T1 starts. When T1 is complete, output relay 21/22-24 will be activated for the duration of the pulse time T2 or until relay 11/12-14 de-energizes.In this last case T2 is inactive (T2= LOCK). The operating principle of the relay 21/22-24 is configurable as normally energized (closed-circuit principle) or normally de-energized (open-circuit principle).

    Local command and external signalThe CEI-021 standard defines “Restrictive thresholds”, the under- and overfrequency thresholds S1 (49.5-50.5 Hz), and “Permissive thresholds”, the under- and overfrequency thresholds S2 (47.5-51.5 Hz). Selection of S1 or S2 thresholds is made by the corresponding combination of the external signal and the local command, as shown in this table:

    Note: In order to activate restrictive thresholds S1 also input Y30-Y31 has to be closed.

    External Signal Local Command Frequency Range

    0 0 Permissive S2

    1 0 Permissive S2

    0 1 Permissive S2

    1 1 Restrictive S1

  • 4 CM-UFD.M32 - Grid feeding monitoring relay according to CEI 0-21 | Data sheet

    Electrical connection

    Connection

    Note: only one auxiliary power supply is allowed

    Output relays scheme

    Remote tripThe control input Y20-Y21 can be configured as normally open or normally closed. If normally closed is configured, the grid feeding monitoring relay trips if Y20-Y21 is opened. If normally open is configured, the relay trips if Y20-Y21 is closed. Within less than 50 ms after activation of the remote trip input, output relay 11/12-14 de-energizes, and output relay 21/22-24 energizes or de-energizes, depending on the configuration. When the remote trip input is deactivated the output relays 11/12-14 and 21/22-24 trip again.

    AutotestThe auto test function allows the verification of the protective functions operability. Selection of the function to be tested starts the auto test. The display shows the threshold value that increases or decreases until the input voltage or frequency value that causes tripping of the output relays is reached. If during the sweep any value of the function setting range meets the same value of the input quantity supplied to the relay (Voltage or Frequency), the function under test trips, operates the output relay and the display shows “OK”: the Autotest has verified that the relay trips correctly.If during the sweep no value of the function setting range meets the same value of the input quantity supplied to the relay (Voltage or Frequency), the function under test does not trip and the display shows “KO”: the Autotest has verified that the relay does not trip untimely.This is the case when the value of the input quantity supplied to the relay is the nominal one which, of course, is outside the functions setting range.To have the function tripping during the Autotest, the input quantity must be arranged to a value within the function setting range. The result is stored in the event list.

    CM-UFD

    U

    F1

    F2

    A1

    220V AC 24V AC/DC

    A2 A3 A4 L1 L2 L3 N Y31Y30Y21Y20

    34 31 32 24 21 11 121422Y11Y10

    Enter

    Set

    12

    11

    14 22

    21

    24 32

    31

    34

    A1-A2 control supply voltage 230 V AC

    A3-A4 control supply voltage 24 V AC/DC

    L1,L2,L3,N measuring inputs

    Y10-Y11 Input 1 DDI feedback

    Y20-Y21 Digital Input 2 remote trip for DDI

    Y30-Y31 Digital Input 3 external signal

    11-12/14 Output Relay 1 trip relay (normally energized)

    21-22/24 Output Relay 2 (2nd DDI or closing

    command for breaker motor)

    configurable

    (normally energized or de-energized)

    31-32/34 Output Relay 3 redundancy relay for DG. Configurable (normally

    energized or de-energized)

    Grid feeding monitoring relay according to CEI 0-21Programming mode and use

  • Data sheet | CM-UFD.M32 - Grid feeding monitoring relay according to CEI 0-21 5

    ConfigurationThe relay is delivered with default settings in accordance to CEI 0-21 table 8.Thanks to the wide display and to appropriate buttons it’s possible to set all the relay parameters in a very simple way. The menu structure starts with the main page that shows the real time measured values. Passing through diagnostic and test pages, it’s possible to view the protection functions parameters pages.The main page that shows the real time measured values:- press button SET to enter in the menu

    - press arrow buttons to move between functions and parameters

    - press button ENTER to enter in the chosen page- using arrow buttons it’s possible to modify the values of the

    parameters- press ENTER button to confirm the value and proceed into

    the menu- press SET button to return to, till the main pageVisualization of the parameter is always possible, modification only after having entered the password.

    Protective functions Threshold Tripping delay

    1st Overvoltage med. (59 S1) 253 V 3 sec

    2nd Overvoltage (59 S2) 265 V 0.2 sec

    1st Undervoltage (27 S1) 196 V 0.4 sec

    2nd Undervoltage (27 S2) 92 V 0.2 sec

    1st Overfrequency (81> S1) 50.5 Hz 0.1 sec

    1st Underfrequency (81< S1) 49.5 Hz 0.1 sec

    2nd Overfrequency (81> S2) 51.5 Hz 0.1 sec

    2nd Underfrequency (81< S2) 47.5 Hz 0.1 sec

    LEDs status Cause

    U green LED ON: normal working condition

    ALL 3 LEDs flashing: device malfunctioning

    F1 LED flashing: prewarning under-/overvoltage

    F1 LED ON: final switch-off under-/overvoltage

    F2 LED flashing: prewarning under-/overfrequency

    F2 LED ON: final switch-off under-/overfrequency

    Default settings table

    Indication of operational states LEDs, status information

    Set

    V 230 V

    V 231 V

    V 230 V

    F 50.02 Hz

    Enter

    Min V 27 S1

    Setting 195 V

    Time 400 ms

    Password

    I/O managem.

    Setting

    Events rec.

    Warning: any CM-UFD.M32 relay is delivered with the same default password. The installer is responsible for the verification of the parameter values and the change of the password with a personal one in order to avoid unwanted modifications.

    Note: the voltage settings are always referred to phase-neutral (Vn 230 V). In order to bring back values to phase-phase (Vn 400 V) or viceversa use the 1,732 constant.

  • 6 CM-UFD.M32 - Grid feeding monitoring relay according to CEI 0-21 | Data sheet

    Main menu

    Grid feeding monitoring relay according to CEI 0-21Menu structure

    Set

    I/O Managem.

    Options

    Connection

    Measurements

    V1

    V3

    V2

    f

    Password

    Autotest

    Setting

    Events rec.

    Language

  • Data sheet | CM-UFD.M32 - Grid feeding monitoring relay according to CEI 0-21 7

    Password management

    Measurements

    V1

    V3

    V2

    f

    Enter

    Enter

    Password

    Autotest

    Setting

    Events Recording

    Password

    Password Modification

    Set0

    0

    Enter the correct password (0-9999) by means of the buttons Up/Down. Press button SET to confirm.Now, programming can start (the authorization is displayed by the asterisk shown at the far right bottom of the display). Press button ENTER to go to the menu PASSWORD for changing the password

    Enter the new password (0-9999) by means of the buttons Up/Down

    *

    *

    Enter

    ConfirmPassword

    0

    Misure

    V1

    V3

    V2

    f

    Measurements

    V1

    V3

    V2

    f

    EnterEnter

    *

  • 8 CM-UFD.M32 - Grid feeding monitoring relay according to CEI 0-21 | Data sheet

    Password

    Autotest

    Setting

    Events Recording

    First enter the password, confirmation displayed by the asterisk shown at the far right bottom of the display.With the buttons Up/Down the threshold value and the tripping delay can be adjusted within the following ranges:Threshold: (46-230)V step 1 VDelay: (50-5.000)ms step 10 msPress button ENTER to confirm the new value.

    Threshold: (12-230)V step 1 VDelay: (50-5.000)ms step 10 msPress button ENTER to confirm the new value.

    Threshold: (230-276)V step 1 VDelay: (200-10.000)ms step 50 msPress button ENTER to confirm the new value.

    Enter

    Enter

    Enter

    Enter

    Enter

    Enter

    Misure

    V1

    V3

    V2

    f

    Measurements

    V1

    V3

    V2

    f

    EnterSet

    *

    Misure

    V1

    V3

    V2

    f

    Measurements

    V1

    V3

    V2

    f

    EnterSet

    *

    Misure

    V1

    V3

    V2

    f

    Measurements

    V1

    V3

    V2

    f

    EnterSet

    *

    Min V 27 S1

    Min V 27 S2

    Vmed. 59 S1

    Setting

    Setting

    Setting

    Time

    Time

    Time

    196

    92

    253

    400

    200

    3000

    Enter

    Threshold: (230-299)V step 1 VDelay (50-5.000)ms step 10 msPress button ENTER to confirm the new value.

    Enter

    Misure

    V1

    V3

    V2

    f

    Measurements

    V1

    V3

    V2

    f

    EnterSet

    *

    Max V 59 S2

    Setting

    Time

    265

    200

    Protective functions parameters setting

    Grid feeding monitoring relay according to CEI 0-21Menu structure

  • Data sheet | CM-UFD.M32 - Grid feeding monitoring relay according to CEI 0-21 9

    Enter

    Enter

    Enter

    Misure

    V1

    V3

    V2

    f

    Measurements

    V1

    V3

    V2

    f

    EnterSet

    *

    Min F 81 S1

    Setting

    Time

    49,5

    100

    Enter

    Enter

    Misure

    V1

    V3

    V2

    f

    Measurements

    V1

    V3

    V2

    f

    EnterSet

    *

    Min F 81 S2

    Setting

    Time

    47,5

    100

    Enter

    Enter

    Misure

    V1

    V3

    V2

    f

    Measurements

    V1

    V3

    V2

    f

    EnterSet

    *

    Max F 81 S1

    Setting

    Time

    50,5

    100

    Enter

    Misure

    V1

    V3

    V2

    f

    Measurements

    V1

    V3

    V2

    f

    EnterSet

    *

    Max F 81 S2

    Setting

    Time

    51,5

    100

    Threshold: (47-50)Hz step 0,1 HzDelay: (50-5.000)ms step 10 msPress button ENTER to confirm the new value.

    Threshold: (47-50)Hz step 0,1 HzDelay: (50-5.000)ms step 10 msPress button ENTER to confirm the new value.

    Threshold: (50-52)Hz step 0,1 HzDelay: (50-5.000)ms step 10 msPress button ENTER to confirm the new value.

    Threshold: (50-52)Hz step 0,1 HzDelay: (50-5.000)ms step 10 msPress button ENTER to confirm the new value.

  • 10 CM-UFD.M32 - Grid feeding monitoring relay according to CEI 0-21 | Data sheet

    Grid feeding monitoring relay according to CEI 0-21Menu structure

    V 27.S1

    F < 81.S1

    V 59.S1

    F > 81.S1

    V 27.S2

    F < 81.S2

    V 59.S2

    F > 81.S2

    Set

    Measurements

    V1

    V3

    V2

    f

    Password

    Autotest

    Setting

    Events rec.

    Enter

    V 27.S1 V 59.S1V 59.S1

    V 59.S1 OK V 59.S1 KO

    V 59.S1 T:T:

    T: T:

    V 27.S2 V: scrollingV: scrolling

    V: V:

    V 59.S2 F:F:

    F: F:

    Enter

    Autotest menu Autotest routine

  • Data sheet | CM-UFD.M32 - Grid feeding monitoring relay according to CEI 0-21 11

    Input / Output menuEvents menu

    - In the menu Events is recorded the following information (up to 10 entries):

    - All protective functions (27.S1 – 27.S2 – 59.S1 – 59.S2 -- 81.S2)

    - Last relay start-up- Auto-test

    Set

    Measurements

    V1

    V3

    V2

    f

    Password

    Autotest

    Setting

    Events rec.

    Enter

    Enter

    Enter

    Event: 0

    Event: 1

    Event: 10

    type FF.Sx Vx

    type FF.Sx Vx

    type FF.Sx Vx

    T 00000.00:00

    T 00000.00:00

    T 00000.00:00

    Set

    Measurements

    V1

    V3

    V2

    f

    I/O Managem.

    Local Command

    Rl 2 Logic

    Option

    Back-up

    Connection

    Relay 2

    Remote Trip

    Language

    Ext. Signal

    Enter

  • 12 CM-UFD.M32 - Grid feeding monitoring relay according to CEI 0-21 | Data sheet

    Local command

    Output relay 2, time delays

    Back up relay, logic and time delay

    External signal logic

    Grid feeding monitoring relay according to CEI 0-21Menu structure

    First enter the password, confirmation displayed by the asterisk shown at the far right bottom of the display.With the buttons Up/Down the parameter value can be modified.Setting: (0-1)Press button ENTER to confirm the new value.

    Local Command

    Back-up

    Relay 2

    Local Command

    Setting 0

    Ext. Signal

    Enter

    Comando Loc. First enter the password, confirmation displayed by the asterisk shown at the far right bottom of the display.With the buttons Up/Down the parameter value can be modified.T1: (1-50.000) msT2: (200-50.000) ms / LOCKPress button ENTER to confirm the new value.

    Local Command

    Back-up

    Relay 2

    Relay 2

    T1 1000

    T2 2500Ext. Signal

    Enter

    Comando Loc.First enter the password, confirmation displayed by the asterisk shown at the far right bottom of the display.With the buttons Up/Down the parameter value can be modified.Tbu: (0-50.000) msPress button ENTER to confirm the new value.

    Local Command

    Back-up

    Relay 2

    Back-up

    Tbu 500

    Ext. Signal

    Enter

    First enter the password, confirmation displayed by the asterisk shown at the far right bottom of the display.With the buttons Up/Down the parameter value can be modified.Setting: (0 - 1)Press button ENTER to confirm the new value.

    Local Command

    Back-up

    Relay 2

    Ext. Signal

    Setting 0

    Ext. Signal

    Enter

    Output relay 2 logic

    Comando Loc. First enter the password, confirmation displayed by the asterisk shown at the far right bottom of the display.With the buttons Up/Down the parameter value can be modified.Rl 2 Logic: (Pos-Neg)Press button ENTER to confirm the new value.

    Rl 2 Logic

    Remote Trip

    Rl 2 Logic

    Logic PosEnter

  • Data sheet | CM-UFD.M32 - Grid feeding monitoring relay according to CEI 0-21 13

    Remote trip logic

    Measurements connection

    Language setting

    Comando Loc.First enter the password, confirmation displayed by the asterisk shown at the far right bottom of the display.With the buttons Up/Down the parameter value can be modified.Logic: (Pos-Neg)Press button ENTER to confirm the new value.

    First enter the password, confirmation displayed by the asterisk shown at the far right bottom of the display.With the buttons Up/Down the parameter value can be modified.Type: (3 Ph – 1 Ph)Press button ENTER to confirm the new value.

    First enter the password, confirmation displayed by the asterisk shown at the far right bottom of the display.With the buttons Up/Down the parameter value can be modified.Lang: (Engl. – Ita.)Press button ENTER to confirm the new value.

    Rl 2 Logic

    Remote Trip

    Remote Trip

    Connection

    Language

    Logic Pos

    Type 3 ph

    lang. Engl

    Enter

    Enter

    Enter

    Set

    Set

    Measurements

    V1

    V3

    V2

    f

    Measurements

    V1

    V3

    V2

    f

    I/O Managem.

    I/O Managem.

    Options

    Options

    Connection

    Connection

    Language

    Language

  • 14 CM-UFD.M32 - Grid feeding monitoring relay according to CEI 0-21 | Data sheet

    Application examples

    + – L N

    G

    Y10Y11 34 31 32 24 21 22 14 11 12

    U

    F1

    F2

    A1 A2 A3 A4 Y20 Y21 L1 L2 L3 N Y30 Y31

    CM-UFD

    Set

    Enter

    1

    2

    4

    26

    5

    3

    L L1 L2 L3 NN

    G

    Y10Y11 34 31 32 24 21 22 14 11 12

    U

    F1

    F2

    A1 A2 A3 A4 Y20 Y21 L1 L2 L3 N Y30 Y31

    CM-UFD

    Set

    Enter

    21

    9 23

    25

    24

    28

    27

    26

    2

    + – L N

    G

    Y10Y11 34 31 32 24 21 22 14 11 12

    U

    F1

    F2

    A1 A2 A3 A4 Y20 Y21 L1 L2 L3 N Y30 Y31

    CM-UFD

    Set

    Enter

    1

    2

    4

    26

    5

    3

    L L1 L2 L3 NN

    G

    Y10Y11 34 31 32 24 21 22 14 11 12

    U

    F1

    F2

    A1 A2 A3 A4 Y20 Y21 L1 L2 L3 N Y30 Y31

    CM-UFD

    Set

    Enter

    21

    9 23

    25

    24

    28

    27

    26

    2

    Legend1) Control supply voltage for CM-UFD.M32 (SPI) relay and

    trip device coil (DDI)*2) Protection fuse for CM-UFD.M32 relay3) Main circuit breaker DG or DGL4) DDI short circuit protection5) DDI: automatic circuit breaker or contactor equipped with

    low voltage coil and motor for automatic closure6) Generator and/or inverter

    Grid feeding monitoring relay according to CEI 0-21Connection diagrams

    7) Generator/inverter circuit breaker (DDG)8) DDI auxiliary contact for feedback function (P>20kW)9) Shunt Trip coil for feedback function (P>20kW).

    This coil can control DG/DGL or DDG devices

    Note:* in accordance to CEI 0-21 regulation, in case of loss of control supply voltage it’s asked to guarantee, at least for 5 seconds, the functionality of the CM-UFD.M32, the operability of the DDI and when present the command coil for operating the redundancy device. This function has to be realized by external buffer or UPS devices.

  • Data sheet | CM-UFD.M32 - Grid feeding monitoring relay according to CEI 0-21 15

    Grid feeding monitoring relay according to CEI 0-21Technical data

    Technical dataData at Ta = 25 °C and rated values, unless otherwise indicated

    Input circuit - Supply circuit

    Rated control supply voltage US

    A1-A2 230 V AC

    A3-A4 24 V AC/DC

    Tolerance of the rated control supply voltage US

    -15…+10 %

    Rated frequency DC and 50 Hz

    Frequency range AC 50-60 Hz

    Typical current / power consumption 24 V DC 125 mA / 2,7 W

    230 V AC 15 mA / 3 VA

    Power failure buffering time 5 s with external device (e.g CP-B)

    Input circuit - Measuring circuit L1, L2, L3, (N)

    Monitoring functions according to CEI 0-21 ed. June 2012

    Measuring ranges over-/undervoltage 10-345V AC (L1, L2, L3, N)

    20-600 V AC (L1, L2, L3)

    10-345 V AC (L1, N)

    over-/underfrequency 45-55 Hz

    Threshold values over-/undervoltage, 10 minutes average value overvoltage 10-300 V AC,adjustable in 1 V steps (L1, L2, L3, N)

    20-520 V AC adjustable in 1V steps (L1, L2, L3)

    10-345 V AC adjustable in 1 V (L1, N)

    over-/underfrequency 47-52 Hz, adjustable in 0.01 Hz steps

    Hysteresis related to the threshold value undervoltage 2%

    overvoltage, 10 minutes average value 2%

    underfrequency 2%

    overfrequency 2%

    Accuracy of measurements voltage measurement ± 1 V ± 1 digit

    frequency measurement ± 0,01 Hz ± 1 digit

    Display accuracy ± 1 digit (1 V or 0,01 Hz)

    Rated frequency of measuring signal 50 Hz

    Frequency range of the measuring signal 45-55 Hz

    Measuring principle TRMS

    Max. reaction time (Measuring cycle CM-UFD.M32 +

    switching time of the relays) without intentional delay

    < 30 ms

    Accuracy within the rated control supply voltage tolerance∆U ≤ 2 %

    Accuracy within the temperature range ∆U ≤ 0,02 % / °C

  • 16 CM-UFD.M32 - Grid feeding monitoring relay according to CEI 0-21 | Data sheet

    Input circuit - Feedback circuits Y10-Y11, Y20-Y21, Y30-Y31

    Number 3

    Kind of inputs feedback from DDI auxiliary contact (Y10-Y11)

    isolated input for remote disconnection (Y20-Y21)

    isolated input for external signal (Y30-Y31)

    Electrical isolation from supply voltage yes

    from the measuring circuit yes

    from the relay outputs yes

    Type of triggering free voltage

    Max. switching current in the control circuit 60 mA

    Max. cable length at the control input 200 m

    No-load voltage at the control inputs 5 V DC

    Feedback time section switch 10 ms

    Timing circuits

    Start-up delay (prior to first grid connection) 10 ms

    Start-up delay (display) 5 s

    Tripping delay adjustable see CEI 0-21 ed. June 2012

    Adjustment range of the delay over-/undervoltage, over-/underfrequency 0,05-5 s with 0,05 s steps

    Tolerance of the delay 5 ms

    Accuracy within the rated control supply voltage tolerance∆t ≤ 1 % ± 20 ms

    Indication of operational states

    See table “LEDs, status information”

    Display

    Backlighted yes

    Back light on pressing any key button

    off automatic, after 5 minutes inactivity

    LCD clearly visible -10...+60 °C

    LCD visible -15...+70 °C

    Display area 27x 30 mm

    Grid feeding monitoring relay according to CEI 0-21Technical data

  • Data sheet | CM-UFD.M32 - Grid feeding monitoring relay according to CEI 0-21 17

    Output circuits - Relay outputs

    Kind of outputs 11-12/14 relay, 1 c/o (SPDT) contact

    21-22/24 relay, 1 c/o (SPDT) contact

    31-32/34 relay, 1 c/o (SPDT) contact

    Operating principle 11-12/14 closed-circuit principle

    21-22/24 open- or closed- circuit principle configurable

    31-32/34 open circuit principle

    Contact material AgNi

    Rated operational voltage Ue (IEC/EN 60947-1) 250 V AC

    Minimum switching voltage / minimum switching current12 V / 10 mA

    Maximum switching voltage / maximum switching current250V AC / 5A

    Rated operational current Ie (IEC/EN 60947-5-1) AC12 (resisitive) at 230 V 6 A

    AC15 (inductive) at 230 V 3 A

    DC12 (resistive) at 24 V 5 A

    DC13 (inductive) at 24 V 2 A

    Mechanical lifetime 100 x 103 switching cycles

    Electrical lifetime at standard condition 5 x 105 switching cycles

    Maximum fuse rating to achieve short-circuit protectionn/c contact 15 A, operating class gG/gL

    n/o contact 15 A, operating class gG/gL

    Maximum closing current (short time) t

  • 18 CM-UFD.M32 - Grid feeding monitoring relay according to CEI 0-21 | Data sheet

    Environmental data

    Ambient temperature ranges operation -25...+70 °C

    storage -40…+70 °C

    transport -40…+70 °C

    Climatic category (EN 50178) 3K3

    Vibration, sinusoidal (IEC/EN 60255-21-1) Class 1

    Shock (IEC/EN 60255-21-2) Class 1

    Isolation data

    Rated insulation voltage Ui supply/measuring 424 V

    (EN 50178) mesuring/output 424 V

    supply/output 424 V

    output circuit 1/output circuit 2/output circuit 3 424 V

    Rated impulse withstand voltage Uimp

    supply/measuring/output circuits 5 kV (CEI 0-21 , CEI 0-16 V2)

    output circuit 1/output circuit 2/output circuit 3 4 kV (EN 50178)

    Basic insulation supply/measuring/output circuits 424 V

    output circuit 1/output circuit 2/output circuit 3 424 V

    Test voltage, routine test supply/measuring/output circuits 2 kV

    output circuit 1/output circuit 2/output circuit 3 2 kV

    Test voltage, type test supply/measuring/output circuits 2 kV

    (CEI 0-21) output circuit 1/output circuit 2/output circuit 3 2 kV

    Protective separation (EN 50178) supply/measuring/output circuits 424 V

    output circuit 1/output circuit 2/output circuit 3 212 V

    Pollution degree (EN 50178) 3

    Overvoltage category (CEI 0-21) IV

    Standards / Directives

    Product standard IEC/EN 60255

    Application standards CEI 0-21 ed. 06-2012

    Low Voltage Directive 2006/95/EU

    EMC Directive 2004/108/EU

    RoHS Directive 2002/95/EU

    Electromagnetic compatibility

    Interference immunity to IEC/EN 61000-6-2, CEI 0-21 Tab.11

    Electrostatic discharge IEC/EN 61000-4-2 level 3, 6 kV / 8 kV

    Radiated, radio-frequency, electromagnetic field IEC/EN 61000-4-3 level 3, 10 V/m (80-1000 Mhz)

    level 2, 3 V/m (1400-2000 Mhz)

    level 1, 1 V/m (2000-2700 Mhz)

    Electrical fast transient / burst IEC/EN 61000-4-4 level 3 2 kV

    Surge IEC/EN 61000-4-5 level 3, 1 kV L-L, 2kV L-earth

    Conducted disturbances, induced by radio-frequency fields IEC/EN 61000-4-6 level 3, 10 V

    Voltage dips IEC/EN 61000-4-29 85% Us continuous, 80% Us max. 1 sec

    Short interruptions IEC/EN 61000-4-29 50ms

    Voltage variations IEC/EN 61000-4-29 120% Us continuous, 130% Us max. 1 sec.

    Interference emission IEC/EN 61000-6-3, IEC/EN 61000-6-4

    High-frequency radiated IEC/CISPR 22, EN 55022 class B

    High-frequency conducted IEC/CISPR 22, EN 55022 class B

    Grid feeding monitoring relay according to CEI 0-21Technical data

  • Data sheet | CM-UFD.M32 - Grid feeding monitoring relay according to CEI 0-21 19

    Grid feeding monitoring relay according to CEI 0-21Technical diagrams and dimensions

    Load limit curves

    Max. DC load breaking capacity Contact lifetime

    300

    200

    100

    50

    40

    30

    20

    100,1 0,2 0,5 1 2 5 10 20

    DC current [A]S0177-D S0024-B

    DC

    vol

    tage

    [V]

    resistive load

    107

    106

    105

    1040 1 2 3 4 5 6 7 8

    Sw

    itchi

    ng c

    ycle

    s

    Switching current [A]

    250VACresistive load

    AgNi90/10

    22 26

    62 90.5

    36

    14 106.3

    Dimensionsin mm

    Document title Document type Document number

    Electronic products and relays technical catalogue 2CDC 110 004 C020x

    CM-UFD.M32 Grid feeding monitoring relay instruction sheet 1SVC 510 811 M0000

    Further documentation

    Note: you can find the documentation on the internet at www.abb.com/lowvoltage -> Control Products -> Electronic Relays and Controls -> Three Phase Monitors.

  • Contacts

    ABB STOTZ-KONTAKT GmbHP. O. Box 10 16 8069006 Heidelberg, GermanyPhone: +49 (0) 6221 7 01-0Fax: +49 (0) 6221 7 01-13 25E-mail: [email protected] can find the address of your local sales organisation on the ABB home page

    http://www.abb.com/contacts -> Low Voltage Products and Systems

    2CD

    C 1

    12 2

    01 D

    0201

    - 0

    4/20

    13We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents - in whole or in parts - is forbidden without prior written consent of ABB AG.

    Copyright© 2013 ABB. All rights reserved.