14
California WDR Subcommittee Group June 6, 2017 Prepared for: Grease Interceptor Sizing Using UPC (AC27650, SO #3) DraftFinal Department of Environmental Services 200 E. Santa Clara Street, 7 th Floor San Jose, California 95113

Grease Interceptor Sizing Using UPC - City of MilpitasGrease Interceptor Sizing Using UPC – Draft-Final June 6, 2017 W‐2978 City of San José 3 EEC 2.0 FIXTURE AND DRAIN CONNECTIONS

  • Upload
    others

  • View
    7

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Grease Interceptor Sizing Using UPC - City of MilpitasGrease Interceptor Sizing Using UPC – Draft-Final June 6, 2017 W‐2978 City of San José 3 EEC 2.0 FIXTURE AND DRAIN CONNECTIONS

California WDR Subcommittee Group

June 6, 2017

Prepared for:

Grease Interceptor SizingUsing UPC(AC27650, SO #3)

Draft‐Final

Department of Environmental Services200 E. Santa Clara Street, 7th Floor

San Jose, California 95113

Page 2: Grease Interceptor Sizing Using UPC - City of MilpitasGrease Interceptor Sizing Using UPC – Draft-Final June 6, 2017 W‐2978 City of San José 3 EEC 2.0 FIXTURE AND DRAIN CONNECTIONS

Grease Interceptor Sizing Using UPC – Draft-Final June 6, 2017

W‐2978 City of San José  2 EEC

1.0 INTRODUCTION Pursuant  to  Service  Order  No.3  of  AC  Contract  No.  AC27650,  EEC  Environmental  (EEC) was tasked  with  assessing  sizing  of  grease  interceptors  in  accordance  with  the  current  Uniform Plumbing  Code  (UPC)1.  The  task  includes  identification  of  the  fixtures  and  drains  that  are  to connect  to  grease  interceptors  at  food  service  establishments  as well  as  assignment  of  the appropriate number of drainage  fixture units  (DFUs)  for each  fixture/drain, which  factors  into interceptor  sizing.  The  task  also  includes  discussion  on  the  circumstances  when  a hydromechanical  grease  interceptor  (HGI)  can  be  a  suitable  alternative  to  a  gravity  grease interceptor (GGI).  The  purpose  of  the  City’s  FOG  Control  Program  is  to  prevent  grease  blockages  in  the  City’s sanitary sewer lines that can cause sanitary sewer overflows (SSOs).  Key elements in controlling such blockages/SSOs  include  the use of grease  interceptors as well as  implementation of Best Management Practices (BMPs) at food service establishments (FSEs).  Grease interceptors (aka: Grease Control Devices or GCDs) come in many shapes and sizes, each with their own benefits and deficiencies. Hydromechanical grease interceptors (HGI or trap) are smaller devices  that can be  installed above or below ground, as well as outside or  inside of a facility. Gravity grease  interceptors (GGIs) are  larger  in‐ground tanks, typically  installed outside the facility. Because of their size, HGIs tend to be less expensive to install; however, due to their smaller size, multiple devices may be needed  to  treat  the appropriate  fixtures and drains and more frequent maintenance  is required to ensure  its proper operation. GGIs are more suitable for  connection  of  all  appropriate  fixtures  and  drains  to  a  single  device  and  because  of  their relatively  large sizes,  typically require  less  frequent maintenance; however, GGIs are generally more expensive to install, particularly where an existing facility is being retrofitted with a GCD.  Most types of grease interceptors can be effective in reducing FOG discharges to the sewer if:  

The fixtures and drains with FOG‐laden wastewater are connected to the device 

The device is property sized for the connected fixtures/drains 

The device is properly installed and maintained   The focus of this report  is  in ensuring the appropriate fixtures and drains are connected to the grease  interceptor,  the  grease  interceptor  is  sized  appropriately,  and  the  appropriate  grease interceptor configuration is applied fairly and equitably.      

1 EEC has been a national consulting leader on the pretreatment and processing of FOG for over 20 years.  EEC’s 2004 national FOG control study for the Orange County Sanitation District (OCSD) and their 26 satellite agencies is still considered the largest study of its kind in addressing FOG related sewer blockages and SSO issues.  EEC has extensive experience in grease interceptor design, sizing and installation, as well as grease interceptor configuration criteria development. 

Page 3: Grease Interceptor Sizing Using UPC - City of MilpitasGrease Interceptor Sizing Using UPC – Draft-Final June 6, 2017 W‐2978 City of San José 3 EEC 2.0 FIXTURE AND DRAIN CONNECTIONS

Grease Interceptor Sizing Using UPC – Draft-Final June 6, 2017

W‐2978 City of San José  3 EEC

2.0 FIXTUREANDDRAINCONNECTIONSCurrent City of San Jose Code Section 15.14.630D states ‐ Waste discharged from fixtures and equipment in establishments which may contain grease or other objectionable materials including, but not limited to, scullery sinks, pot and pan sinks, dishwashers, food waste disposals, soup kettles, and floor drains located in areas where such objectionable materials may exist, may be drained into the sanitary sewer through the grease control device if approved by the director provided, however, that toilets, urinals, wash basins, and other fixtures containing fecal material shall not flow through the grease control device. Generally, all sinks, fixtures and/or drains in food preparation, cooking or dish washing areas are candidates  for  connection  to  the  GCD  and  in  most  cases,  should  be  connected  to  a  GCD. Determination of the specific fixtures and drains that must connect to a GCD is based primarily on  the  potential  for  FOG‐laden  wastewater  to  be  encountered  at  each  fixture/drain.  Some sinks/drains present less risk for FOG laden wastewater and present less risk if not connected to the  GCD.  Table  2.1  below  provides  a  summary  of  the  typical  FSE  fixtures/drains  and  their associated potential for FOG‐laden wastewater discharge: 

Table 2.1 – Fixture and Drain Connections to a GCD

Fixture  Location Potential for FOG Connection to GCD 

Multi‐Compartment/ Scullery Sink 

Dish Wash, Food Prep, Cooking Areas 

High  Recommended 

Pot/Pan Wash Sink Dish Wash, Food Prep, Cooking Areas 

High  Recommended 

Pre‐Rinse Sink  (for dishwashing) 

Dish Wash Area  High  Recommended 

Floor Drain/Trench Drain Cooking Area (for Kettles or other Equip) 

High  Recommended 

Floor Sinks (with equipment drains) 

Cooking Area (for Wok Ranges, Hoods Drains, other Equipment) 

High  Recommended 

Floor Sinks/Floor Drains/Trench Drains 

Dish Wash Area  Moderate  Recommended 

Mop Sink Dish Wash, Food Prep, Cooking Areas 

Moderate  Recommended 

Floor Drains  Food Prep, Cooking Area Moderate Recommended

Commercial Dishwasher (without a pre‐rinse sink) 

Dish Wash Area  Moderate  Recommended 

Prep‐Sinks (General)  Food Prep, Cooking Area Moderate or Low Optional

Floor Sinks (no equipment drains) 

Food Prep, Cooking Area  low  Optional 

Prep‐Sink (Vegetable Prep Only) 

Food Prep Area  Low  Optional 

Commercial Dishwasher (with a pre‐rinse sink) 

Dish Wash Area  Low  Not Necessary 

Commercial Dishwasher  Beverage, Bar Area Low Not Necessary

Hand Sinks  Any  Low Not necessary

Floor Sinks  (for Bev/Ice Machines) 

Any  Low  Not necessary 

Toilets and Hand Sinks  Restrooms  N/A Never

Page 4: Grease Interceptor Sizing Using UPC - City of MilpitasGrease Interceptor Sizing Using UPC – Draft-Final June 6, 2017 W‐2978 City of San José 3 EEC 2.0 FIXTURE AND DRAIN CONNECTIONS

Grease Interceptor Sizing Using UPC – Draft-Final June 6, 2017

W‐2978 City of San José  4 EEC

Multi‐Compartment/Scullery Sinks Multi‐compartment sinks, most frequently 3‐compartments, are typically the most used sink  in the food service establishment. This sink is used for a variety of functions including dish washing (in lieu of an automatic dishwasher), utensil washing, and pot/pan washing. Additionally, multi‐compartment  sinks  are  sometimes  used  for  pre‐rinsing  of  dishes  prior  to  insertion  into  an automatic dishwasher/sanitizer. Due to its extensive uses, this sink has a high potential for FOG laden wastewater and connection to the facility’s GCD should be required.  

Potential  Exceptions:  Some  FSEs  have  multi‐compartment  sinks  in  beverage  or  bar areas, used primarily for glass ware washing. In this type of location, these sinks present a  very  low  potential  for  FOG‐laden  wastewater  and  connection  to  a  GCD  is  not necessary.    

 Pot/Pan Wash Sinks Many FSEs have a sink designated for washing/rinsing cooking residue from pots and pans. Such a sink has a high potential for FOG laden wastewater connection to the facility’s GCD should be required. 

Potential Exceptions: Rare     Dishwasher Pre‐Rinse Sinks Some  FSEs  with  a  commercial  dishwasher  have  a  sink  designated  for  pre‐rinsing  of  dishes, utensils, trays, pots, and pans prior to processing through the dishwasher. Because this sink will be  routinely  exposed  to  food  scraps  and  residue,  there  is  a  high  potential  for  FOG  laden wastewater from this sink. Connection of this sink to the facility’s GCD should be required.  

Potential Exceptions: Rare     Floor Drain/Trench Drains (food cook areas)   FSEs may have floor or trench drains near cooking equipment such as tilt kettles or tilt skillets. Such drains are designed to facilitate cleaning/rinsing of the large cooking equipment, which can contain  significant  amounts  of  food  residue.  This  drain  has  a  high  potential  for  FOG  laden wastewater and connection to the facility’s GCD should be required. 

Potential Exceptions: If the drain is designated to receive the water from steam tables, connection  to  the GCD may not be necessary as  there  is  little potential  for FOG  laden wastewater to be encountered.    

 Floor Sinks (with equipment drains in food cooking areas) Floor sinks  in  food cooking areas are often designated  to  receive  the drainage or  runoff  from cooking equipment such as wok ranges, char‐broilers, and exhaust hoods. This equipment can discharge significant amounts of FOG‐laden waste and connection to the facility’s GCD should be required. 

Potential Exceptions: Rare     Floor Sinks/Floor Drains/Trench Drains (Dish wash areas) Floor sinks, floor drains and/or trench drains  in dish wash areas are frequently exposed to the drainage  or  spills  from  dish washing  activities, which  can  include  food waste  from  dishes  or pots/pans. Additionally, spills  in  these areas are  likely  to be directed  to  the area drains rather than cleaned up with absorbents. Therefore,  these drains have a moderate potential  for FOG laden wastewater and where practicable, connection to the facility’s GCD should be required. 

Potential Exceptions: Rare     

Page 5: Grease Interceptor Sizing Using UPC - City of MilpitasGrease Interceptor Sizing Using UPC – Draft-Final June 6, 2017 W‐2978 City of San José 3 EEC 2.0 FIXTURE AND DRAIN CONNECTIONS

Grease Interceptor Sizing Using UPC – Draft-Final June 6, 2017

W‐2978 City of San José  5 EEC

Mop Sink (located in dish wash, food prep/cooking areas) Mop sinks  receive water  from  routine  floor cleaning/disinfecting activities as well as  from  the clean‐up  of  accidental  spills.  Since  is  not  uncommon  for  grease  and  oils  that  are  spilled  or spattered onto the floor to be tracked across the floor by kitchen personnel, there is a moderate potential for FOG laden wastewater to be dumped  into this sink. Therefore, where practicable, connection to the facility’s GCD should be required.  

Potential  Exceptions:  For  some  facilities,  the mop  sink may  be  located  in  a  remote janitor/utility  closet, where  it may not be practicable  to gravity  flow  the drain  to  the GCD. In such cases, connection directly to the sanitary sewer can be considered.      

 Floor Drains (in food prep/cooking areas) Floor  drains  in  food  preparation  and  cooking  areas  often  receive water  from  floor  cleaning activities  as  well  as  from  the  clean‐up  of  accidental  spills.  Therefore,  these  drains  have  a moderate  potential  for  FOG‐laden  wastewater  and  where  practicable,  connection  to  the facility’s GCD should be required. 

Potential Exceptions: Rare     Prep‐Sinks (Food prep, cooking areas) Prep sinks are intended for washing fruits and vegetables. Depending on their physical location in the kitchen area, they can be used for other purposes such as dish or pot/pan washing. The potential  for  FOG‐laden wastewater  from  this  sink  can  be moderate  and  connection  to  the facility’s GCD should be required.  

Potential Exceptions: Where it is clear that the prep sink will be used for vegetable prep only (BMPs in place to reinforce its use), connection to the GCD may not be necessary. 

 Floor Sinks (no equipment drains in food prep/cooking areas) Floor  sinks  with  no  equipment  drains  (unused)  are  not  likely  to  receive  much  wastewater drainage.  If the floor sink rim  is set above the floor, there  is minimal potential for wash water from floor clean‐up activities to be directed to the floor sink. Therefore such a sink presents a low potential for FOG‐laden wastewater and connection to a GCD may not be necessary. 

Potential Exceptions: Rare  Commercial Dishwasher (with a pre‐rinse sink) Commercial dishwashers in FSEs with a pre‐rinse sink, are generally used for sanitizing purposes. The vast majority of residual food waste (and corresponding FOG) are washed away during the pre‐rinse process. There can be  some  residual  food/FOG material on  the dishes placed  in  the dishwasher, and  the high  temperature water  from a dishwasher can be beneficial  to  the FOG separation process; however, emulsification from dishwasher detergents can negatively impact the FOG separation process and contribute  to FOG pass‐through. Since  the potential  for FOG‐laden wastewater from a dishwasher (with a pre‐rinse sink)  is typically  low, and there  is some potential  for  the dishwasher discharge  to negatively  impact GCD performance,  connection  to the GCD is not recommended.   

Potential Exceptions: If there is no pre‐rinse of wares prior to the dishwasher, there is then a high likelihood of significant FOG‐laden wastewater from the dishwasher process. In these cases, connection to a GCD should be required. A GGI is suitable to receive the dishwasher discharge; however, a HGI is not. Therefore, a facility needing a GCD that utilizes a commercial dishwasher but has no pre‐rinse sink, must use a GGI. It is also important that GGI sizing account for the discharge flow rate from the connected dishwasher machine (refer to sections 3 and 4 below).       

Page 6: Grease Interceptor Sizing Using UPC - City of MilpitasGrease Interceptor Sizing Using UPC – Draft-Final June 6, 2017 W‐2978 City of San José 3 EEC 2.0 FIXTURE AND DRAIN CONNECTIONS

Grease Interceptor Sizing Using UPC – Draft-Final June 6, 2017

W‐2978 City of San José  6 EEC

3.0 FIXTUREUNITVALUEDETERMINATION Once fixtures and drains have been designated for connection to the GCD, the Drainage Fixture Unit (DFU) value for each will be needed to determine interceptor sizing. DFU determination is based primarily on the fixture drain line or trap size as follows:  

Table 3.1 – Fixture/Drain DFUs 

Drain/Trap Size (inch) 

Fixture Unit Equivalent(DFUs)  

1‐¼ 1

1‐½ 3

2  4

3  6

4  8

>4 Consult with City

 Exceptions/Special Circumstances:  

Emergency floor drains, regardless of their size, can be assigned a DFU value of 0 (zero) as they are not intended to receive water flow on a regular basis and should not factor into GCD sizing. 

 

For multi‐compartment  sinks with  individual  drain  lines  for  each  compartment, DFUs should  be  determined  for  each  drain  individually.  Where  compartment  drains  are combined, the DFU value shall be determined based on the shared drain line size.    

 

Fixture unit values of floor sinks receiving drainage from other fixtures/equipment (e.g., indirect drainage from a prep sink) shall be determined by: 

o Combining the fixture DFU values for each of the fixtures received, or  o Using the drain/trap size of the floor sink o NOT both. 

 

Fixture unit equivalents for equipment with continuous drainage (e.g., wok range), shall be assigned 2 DFU for each gallon per minute (GPM) of rated flow.  

Fixture  unit  equivalents  for  equipment  with  intermittent  drainage  (e.g.,  commercial dishwasher), shall be assigned fixture unit values per UPC Table 702.2(b) as follows:   

Table 3.2 –Fixture Unit Equivalents (for Intermittent Flow Only) 

 

GPM Fixture Unit 

Up to 7 ½ 1

Greater than 7 ½ to 15 2

Greater than 15 to 30 4

Greater that 30‐50 6

Greater than 50 Consult with City

  

Page 7: Grease Interceptor Sizing Using UPC - City of MilpitasGrease Interceptor Sizing Using UPC – Draft-Final June 6, 2017 W‐2978 City of San José 3 EEC 2.0 FIXTURE AND DRAIN CONNECTIONS

Grease Interceptor Sizing Using UPC – Draft-Final June 6, 2017

W‐2978 City of San José  7 EEC

DFU values typical of common FSE fixtures and drains are summarized in the table 3.2 below.  

Table 3.3 – Common Fixture/Drain DFU Values  

Fixture  Connection to GCD 

DFU Value 

3‐Compartment Sink  Required  4 

Pot/Pan Wash Sink  Required  4 

Dishwasher Pre‐Rinse Sink  Required  4 

Trench Drain  Required 3 

(per trench outflow) 

Floor Sinks (Indirect sink drains) 

Required 4 

(or sum of indirect  sink drain DFU values) 

Floor Sinks (with equipment drains) 

Required 4 

(or equipment  discharge flow rates) 

Floor Sinks/Floor Drains/Trench Drains 

Required  4 

Mop Sink  Required  3 

Commercial Dishwasher (without a pre‐rinse sink) 

Required 8 

(or equipment  Discharge flow rates) 

Floor Drains (emergency)  Required  0 

Prep‐Sinks (General) 

Optional  3 

Floor Sinks (no equipment drains) 

Optional  1 

Prep‐Sink (Vegetable Prep Only) 

Optional  3 

Commercial Dishwasher (with a pre‐rinse sink) 

Not necessary 8 

(or equipment  Discharge flow rates) 

Hand Sinks  Not necessary  2 

Floor Sinks  (for Bev/Ice Machines) 

Not necessary  3 

     

 

Page 8: Grease Interceptor Sizing Using UPC - City of MilpitasGrease Interceptor Sizing Using UPC – Draft-Final June 6, 2017 W‐2978 City of San José 3 EEC 2.0 FIXTURE AND DRAIN CONNECTIONS

Grease Interceptor Sizing Using UPC – Draft-Final June 6, 2017

W‐2978 City of San José  8 EEC

4.0 GGISIZING When  the DFU values of  the  fixtures and drains connected to a GGI are known, the minimum volume of the GGI shall be determined by Table 4.1 (pursuant to UPC 1014.3.6) as follows:   

Table 4.1 – GGI Sizing (DFU Based) 

Drainage Fixture Units(DFUs) 

Minimum Interceptor Volume (Gallons) 

21 750

35 1000

90 1250

172 1500

216 2000

>216 Consult with City

 When the DFU values are not known, the minimum GGI size can be determined based on the maximum DFUs  allowed  for  the  grease waste pipe  size  connected  to  the  inlet of  the GGI  as follows:  

Table 4.2 – GGI Sizing (Pipe Size Based) 

Pipe Size (Inch) 

Maximum DFUs Minimum Interceptor Volume (Gallons) 

3  35 1000 

4  172 1500 

4  216 2000 

>4  >216 Consult with City 

 Note: Where  the  flow  rate of directly connected  fixtures or appliances have no assigned DFU values,  the  additional  grease  interceptor  volume  shall  be  based  on  the  known  flow  rate multiplied by 30 minutes.  5.0 HGISIZING Hydromechanical Grease Interceptors (HGI) are equipped with a flow control device that  limits the  flow  of  wastewater  into  and  through  the  HGI.  Flow  control  devices  are  designed  and installed  so  that  the  total  flow  through  the  device  is  not  greater  than  the  rated  flow  of  the connected HGI. Because of this flow limiting functionality, HGI sizing can vary depending on the fixture drainage period  that  is  tolerable  to  the FSE  (or  required by  the City). Drainage periods typically  considered  in HGI  sizing  are  one‐minute  and  two‐minute.  A  longer  drainage  period allows for a smaller HGI size. Most agencies that allow installation of HGI devices leave it to the FSE’s discretion to select the drainage period.         Given a defined drainage period, HGI sizing can be determined through one of the following two methods (reference UPC 1014.2):     

Page 9: Grease Interceptor Sizing Using UPC - City of MilpitasGrease Interceptor Sizing Using UPC – Draft-Final June 6, 2017 W‐2978 City of San José 3 EEC 2.0 FIXTURE AND DRAIN CONNECTIONS

Grease Interceptor Sizing Using UPC – Draft-Final June 6, 2017

W‐2978 City of San José  9 EEC

1. HGI Sizing Using Gravity Flow Rates   This  method  considers  the  maximum  flow  a  pipe  can  convey  under  gravity  flow conditions in determining the appropriate HGI size. In the table below, full pipe flow for various pipe sizes is calculated using Manning formula (assumes ¼ inch/foot slope and a friction factor of N=0.012). The minimum HGI size is defined based on the full pipe flow rates  corresponding  to  the  grease waste  pipe  size.  These  values  are  summarized  as follows: 

 Table 5.1 – HGI Sizing (Flow Rates)

 

Diameter of Grease Waste Pipe (inches) 

Full Pipe Flow1 (gpm) 

HGI Size 

One‐MinuteDrainage Period 

(GPM) 

Two‐MinuteDrainage Period 

(GPM) 

2 20 20 10 

3 60 75 35 

4 125 150 75 

5 230 250 125 

6 375 500 250 1  Assumes slope of ¼‐Inch per foot, using Manning’s formula with N=0.012 

 2. HGI Sizing Using Fixture Capacity 

 This method considers  the capacities  (volumes) of  the  fixtures discharging  to  the HGI device  in  determining  the  appropriate  HGI  size.  The  following  steps  are  used  to determine fixture capacities and the corresponding HGI size using this method.   Step 1 – Calculate Fixture Capacities 

Sinks/basins = Length x Width x Depth x 0.75 (fill factor); or Rated Appliance = Specified flow rate 

Step 2 – Calculate total wastewater load (sum of capacities) Step 3 – Determine HGI size based on total wastewater load   An example of this method is provided in Table 5.2 below:  

Table 5.2 – HGI Sizing Example (Fixture Capacity) 

Fixtures Compartment Size/Flow Rate 

Qty Wastewater 

Load (Gallons) 

HGI Size 

One‐Minute Drainage Period (GPM) 

Two‐MinuteDrainage Period (GPM) 

3‐comp Sink  24in x 24in x 12in 3 67.3  

1‐comp Sink   24in x 24in x 12in 1 22.4  

Hood Wash  4 GPM  1 4  

Total 93.7 100 50 

 In the above example, a 50 GPM to 100 GPM HGI would be acceptable, depending on the desired (or required) drainage period.  

Page 10: Grease Interceptor Sizing Using UPC - City of MilpitasGrease Interceptor Sizing Using UPC – Draft-Final June 6, 2017 W‐2978 City of San José 3 EEC 2.0 FIXTURE AND DRAIN CONNECTIONS

Grease Interceptor Sizing Using UPC – Draft-Final June 6, 2017

W‐2978 City of San José  10 EEC

With either of the two sizing methods, the total capacity (in gallons) of the fixtures discharging into the HGI cannot exceed two and one‐half times the certified flow rate of the HGI. This will impose a limitation on the total number of fixtures that can be connected to an individual HGI.  Note: A HGI is not appropriate for use in a facility with a commercial dishwasher without a pre‐rinse sink.   Pursuant  to UPC 1014.2,  the  vent or  air  inlet of  the  flow  control device  shall  connect  to  the sanitary drainage vent system or through the roof of the building, and shall not terminate to the free atmosphere inside the building.   6.0 HGITYPES Pursuant to UPC section 210.0, HGI is defined as follows:  A Plumbing appurtenance or appliance that is installed in a sanitary drainage system to intercept non‐petroleum fats, oil and grease (FOG) from a wastewater discharge and is identified by flow rate,  and  separation  and  retention  efficiency.  The  design  incorporates  air  entrainment, hydromechanical separation, interior baffling, or barriers in combination or separately, and one of the following: 

A – External flow control, with air intake (vent), directly connected. B – External flow control, without air intake (vent), directly connected. C – Without external flow control, directly connected. D – Without external flow control, indirectly connected.  

While there is a wide variety of manufactures and configurations of HGI devices, operationally, there are two general categories:  

“Passive” HGIs, which simply trap and retain separated FOG. 

Grease Removal Devices  (GRD), which  automatically  remove  the  separated  FOG  from the HGI, typically into a separate holding container. 

 Both categories have similarities that include:  

When properly sized,  installed and maintained, both can be effective  in removing FOG from the wastewater discharged to them. 

Sized pursuant to UPC Section 1014.2. 

Typically installed indoors but can be installed outdoors. 

Construction materials include metal, fiberglass, or plastic. 

If  compliant with  UPC,  been  certified  by  an  accredited  conformity  assessment  body (listing agency),  indicating that the device has been certified to  its  listed flow rate and grease retention capacity, pursuant to applicable standards (e.g., ASME A112.14.3‐2000 and ASME A112.14.4‐2001).  

Require internal or external flow control devices, some with (others without) air intake (vent). 

Require  access  to  external  flow  control  devices  for  maintenance,  particularly  when installed below ground. 

Page 11: Grease Interceptor Sizing Using UPC - City of MilpitasGrease Interceptor Sizing Using UPC – Draft-Final June 6, 2017 W‐2978 City of San José 3 EEC 2.0 FIXTURE AND DRAIN CONNECTIONS

Grease Interceptor Sizing Using UPC – Draft-Final June 6, 2017

W‐2978 City of San José  11 EEC

Require  routine maintenance  (removal  of  accumulated  FOG/solids)  to  ensure  device performance. 

Common sizes range from 15 GPM to 150 GPM (and higher).  While  both  categories  are  HGIs,  there  are  some  differences  that  will  factor  into  their applicability in certain situations. Key differences include:   

The  automated  functionality  of  a  GRD  can  help  simplify  the  level  and  frequency  of maintenance interaction by FSE personnel; however, GRDs also introduce an added level of maintenance complexity with electrical timers, heaters, scrapers, motors, etc., all of which must be properly set‐up and maintained to provide the automated functionality.   

Passive HGIs are well suited for sub‐slab installation (vaulted). When covers are properly installed and attached,  they are generally sealed and are not susceptible  to  leaking  in the event of a downstream blockage.  

GRDs are not well suited for sub‐slab installation. Even with all covers properly installed, GRDs are not  sealed and a downstream blockage  can  result  in  spillage  from  the unit. Additionally, a key  feature of a GRD  is  the visual  indication of FOG  levels  in collection containers. When installed sub‐slab, this visual indication is likely lost. 

 7.0 GGIVS.HGI As  discussed  above, Most  types  of GCDs  can  be  effective  in  reducing  FOG  discharges  to  the sewer if:  

The fixtures and drains with FOG‐laden wastewater are connected to the device  

The device is properly sized for the connected fixtures/drains 

The device is properly installed and maintained   Historically, GGIs have been the grease control technology of choice for FOG Control programs across  the country. Because of  their  larger size and  typical underground  installation, GGIs are well suited to receive the drainage from all grease bearing fixtures/drains  in the FSE,  including floor mounted sinks and drains. GGIs  require  routine maintenance, which  typically consists of pumping/hauling  the  accumulated  FOG  and  solids  (and water)  for  off‐site  disposal  every  2‐4 months. This maintenance service is not typically performed by the FSE personnel so reliance on the FSE to ensure proper operation of a GGI  is  limited to arranging the service (scheduling and paying).  Additionally,  because  GGIs  are  typically  located  outside  the  FSE,  they  are  readily available for inspection by regulatory personnel to assess the maintenance condition.  The downside of GGIs is that they require significant space, can be costly to install (particularly in  a  retrofit  situation),  and  can  contribute  to  sewer  system  odor  and  corrosion  issues (particularly when oversized). For these reasons, HGIs are often considered as an alternative to a GGI in certain situations.  HGIs are  smaller devices  that may be  installed above or below ground, as well as outside or inside of a food facility. Because of their smaller size, HGIs tend to be less expensive for the FSE to  install; however, multiple devices may be needed  to capture  the  flow  from all appropriate fixtures  and  drains,  which  increases  installation/maintenance  costs.  Additionally  the  smaller device size results in a need for more frequent service and maintenance (weekly to monthly) to ensure the proper operation of the device(s). This frequent maintenance is often self‐performed 

Page 12: Grease Interceptor Sizing Using UPC - City of MilpitasGrease Interceptor Sizing Using UPC – Draft-Final June 6, 2017 W‐2978 City of San José 3 EEC 2.0 FIXTURE AND DRAIN CONNECTIONS

Grease Interceptor Sizing Using UPC – Draft-Final June 6, 2017

W‐2978 City of San José  12 EEC

by the FSE, thereby increasing the reliance on FSE personnel and FSE practices to ensure device performance.  Because  the  frequent  maintenance  of  HGIs  is  critical  to  their  performance, increased  regulatory oversight  (i.e.,  inspection)  is  often  implemented  for  facilities with  these devices.  The City  requires FSEs  to  install a GCD  for all potential FOG‐bearing  fixtures and drains  in  the FSE’s food preparation and clean‐up areas. GGIs are generally the preferred GCD technology for FOG source control, particularly when the FSE is associated with new construction. For existing FSEs  required  to  install  a GCD  (typically  triggered  by  the  permitting  process  for  remodels  or other changes in operations), the City considers both GGIs and HGIs as suitable GCD options, as long as all of the required fixtures and drains are connected to the GCD.   Several key  factors are considered  in determining  the appropriate GCD configuration  for each FSE. These primary factors include:  

Scope of construction activities 

The risk of the facility to discharge FOG to the sewer system 

Physical site limitations of the FSE/property  Scope of Construction Activities Installation  of  a  GCD  and  its  associated  piping  is  an  intrusive  activity,  best  suited  to  be conducted  during  other  facility  construction  activities.  For  existing  operational  FSEs,  a  GCD retrofit can require significant operational downtime, resulting in business losses in addition to the installation costs. These potential impacts to the FSE should be considered in determination of GCD requirements for FSEs in GCD retrofit situations.         Risk of Facility to Discharge FOG Generally,  the  risk  of  a  facility  to  discharge  FOG  should  be  evaluated  based  on  the  type  of cooking equipment and/or processes employed by the FSE. This approach helps to eliminate the consideration  of  the  food  types  being  cooked  (which  can  change  at  any  time  without notification to the City) as a factor in determining FOG‐risk. If the facility uses equipment with a high risk for generating FOG (e.g., deep fryers, griddles, stoves, woks, tilt skillets, char broilers, etc.), or employs practices with a high risk  for discharging FOG  (e.g., reusable dishes requiring dishwashing),  the FSE  is considered a High FOG Risk  facility and GCD  requirements  should be applied accordingly.    Physical Site Limitations Space constraints and the depth of the existing sewer can  limit the CGD options that a facility can feasibly implement. There are situations where there is simply no physical space for a GGI. In some cases,  there may be a space available  for a GGI; however  there  is no  feasible way  to access  that  space  for  connection  from  the FSE or maintenance of  the GGI  (e.g., underground parking structure). Similarly, the existing sewer  line that will receive the effluent from the GCD must  be  sufficiently  deep  to  accommodate  the  appropriate  pipeline  slope  to  ensure  proper gravity flow.   Figure  7.1  –  GCD  Requirements  Guideline,  provides  a  decision  process  that  considers  these factors for a fair and equitable determination of appropriate CGD configurations. In considering this  process,  Table  7.1  summarizes  applicable  GCD  configurations  for  New  FSEs  (new construction), and Table 7.2 summarized applicable GCD configurations for Existing FSEs. 

Page 13: Grease Interceptor Sizing Using UPC - City of MilpitasGrease Interceptor Sizing Using UPC – Draft-Final June 6, 2017 W‐2978 City of San José 3 EEC 2.0 FIXTURE AND DRAIN CONNECTIONS

Grease Interceptor Sizing Using UPC – Draft-Final June 6, 2017

W‐2978 City of San José  13 EEC

 Table 7.1 ‐ Applicable GCD Configurations For New FSEs 

(New Construction)  

High FOG‐Risk Equipment/Practices 

Sufficient Space/Slope 

Acceptable GCD Configuration 

Yes  Yes  GGI (for all potential FOG‐bearing fixtures/drains) 

No  NA  Provide for future GGI or HGI Installation 

 Table 7.2 ‐ Applicable GCD Configurations For Existing FSEs

(Remodel, Change in Operations/Ownership)  

High FOG‐Risk Equipment/Practices 

Sufficient Space/Slope 

Acceptable GCD Configuration 

Yes  Yes  GGI or HGI (for all potential FOG‐bearing fixtures/drains)

Yes  No  HGI (for all potential FOG‐bearing fixtures/drains) 

No  NA  GCD Installation not required

 

Page 14: Grease Interceptor Sizing Using UPC - City of MilpitasGrease Interceptor Sizing Using UPC – Draft-Final June 6, 2017 W‐2978 City of San José 3 EEC 2.0 FIXTURE AND DRAIN CONNECTIONS

Grease Interceptor Sizing Using UPC – Draft-Final June 6, 2017

W‐2978 City of San José  14 EEC