Job Name:
Job Number:
Model Numbers:
PageSPECIFICATION SUBMITTAL
GRAFIK Eye® QS Control Unit
LUTRON
1
2
3
4
Off
Preset
Close
Open
DescriptionGRAFIK Eye® QS is the premier energy-saving light and shade control. GRAFIK Eye® QS includes an astronomic timeclock, intuitive lighting presets, and direct shade control. Additionally, the GRAFIK Eye® QS is compatible with all Lutron wired QS products and systems, including Quantum®.
Mechanical Dimensions
4$ in (119 mm)
94 in (239 mm) 4 in
(10 mm) 2 in (51 mm)
Front View Side View
Fits into a 4-gang U.S. backbox, 3` in (89 mm) deep; Lutron P/N 241-400.
System Topology
LUTRONLUTRON
LUTRON LUTRON
LUTRON
LUTRON LUTRON
LUTRON
LUTRON
LUTRON
LUTRONLUTRON
LUTRON LUTRON
LUTRON
LUTRON LUTRON
LUTRON
LUTRON
LUTRON
Example of Wired System
QSE-CI-NWK-E
Sivoia® QS shade
seeTouch® QS
seeTouch® QS
Wired occupancy
sensor
GRAFIK Eye® QS GRAFIK Eye® QS
Wired QS link
Quantum® (optional)
QS Sensor Module
Energi Savr NodeTM
Preset Dimming Controls
369430 Rev. A 1 04.25.11
100 V Control Unit
®
Job Name:
Job Number:
Model Numbers:
PageSPECIFICATION SUBMITTAL
Features•Pushbuttonrecalloffourpresetlightingscenes,plusOff.
•Twelve(12)additionalscenesaccessiblethrough other QS devices, such as seeTouch® QS wallstations.
•Optionalintegratedshadecontrolbuttons,whichcanalsobeaddedtotheunitafterinstallation.
•Masteroverridebuttonstoraiseandloweralllights.
•Allowssetupoflightingscenesandshadepresets using buttons on the control unit.
•Built-ininfrared(IR)receiver.•ExternalIRconnection.•Built-inastronomictimeclock.• Infoscreenshowszonelightlevelpercentage,energysavings,zonelabeling,andprogramming.
•Lockoutoptionpreventsaccidentalchanges.•Oneoccupancysensorinputand24V powerforoccupancysensor.
•QScommunicationlinkforseamlessintegrationoflights,motorizedwindowtreatments, occupancy sensors, wallstations, andintegrationinterfaces.
•CompatiblewithallLutronQSsystemcomponents.
•Backlitbuttonswithengravingmakeuniteasyto locate and operate.
•Availableinavarietyofcolorsandfinishes.
LUTRON
OK
1 2 3 4 5 6
Optional shade control keypad
Zone control
Infraredreceiver
USB type mini B
Infoscreen
Lighting control keypad
1
2
3
4
Off
Off
Preset
Close
1
2
3
4
Open
Preset
Close
Open
Note: General Engraving (-EGN) shown.
Preset Dimming Controls
369430 Rev. A 2 04.25.11
100 V Control Unit
®
Model Numbers:
PageSPECIFICATION SUBMITTAL
Job Name:
Job Number:
Key Design Features•LightningstrikeprotectionmeetsANSI/IEEEstandard62.41-1980.Canwithstandvoltagesurgesofupto 6000 V andcurrentsurgesofupto3000A.
•Testedtowithstand16kVelectrostaticdischargewithout damage or memory loss.
•RTISSTM-equipped:Compensatesinrealtimeforincominglinevoltagevariations(novisibleflickerwith+/-2%changeinRMSvoltagepercycle,and+/-2%Hzchangeinfrequencypersecond).
•Powerfailurememoryretainsprogrammingandlightlevelsettingsforupto10yearsintheeventofapowerloss.
•TheGRAFIKEye® QS supplies 3 Power Draw Units (PDUs) on the QS link. Forcompleteinformation,see“PowerDrawUnitsonthe QS Link,” Lutron PN 369405.
•Faceplateishingedatthetopandbottom,andstaysopenat180°foreaseofaccess.
Scene and Shade Buttons•Large,roundedbuttonsareeasytouse.•Backlitbuttonswithoptionalengravingmakeiteasytofindandtooperatethecontrolunitinlowlightconditions (backlight can be disabled).
•Optionalbuttonengravingisangleduptotheeyeforeasy reading.
•Predefinedlabelstickersareincludedforfieldlabeling.•4presetlightingscenes,plusOff,areaccessiblefromthefrontofthecontrolunit.
•12additionalscenesarestoredinthecontrolunitandareaccessiblefromseeTouch® QS wallstations and QSinterfaces.
•Lightlevelsfadesmoothlybetweenscenes.Fadetimecanbesetdifferentlyforeachscene:0to59seconds,or1to60minutes.MaximumfadetimefromOffis 3 seconds.
Input Power•100V 50/60Hz
Environment•32to104°F(0to40°C).•Relativehumiditylessthan90%non-condensing.
Lighting Sources/Load TypesControlsthefollowinglightingsourceswithasmooth,continuoussquarelawdimmingcurveoronafullconduction non-dim basis:
• Incandescent•Halogen•Magneticlow-voltagetransformer•Neonandcoldcathode•Non-dim(incandescent,magneticlow-voltage,
or neon/cold cathode) Pleasereferto“Capacities”formoreinformation.
Controlsthefollowinglightingsourceswithasmooth,continuoussquarelawdimmingcurveoronafullconduction non-dim basis through separate Lutron power interfaces:
•Electroniclow-voltagetransformer•Non-dim•0-10V
Capacities
100 V 50 / 60 Hz
Unit Capacity (watts) 1600
MLV 1600 VA / 1200 W
Zone Capacity (watts) 25 – 600
MLV 25 – 600 VA / 25 – 480 W
Load Type Notes•Allelectroniclow-voltage(ELV)lightingusedwithaninterfacemustberatedforreversephasecontroldimming.BeforeinstallinganELVlightsource,verifywiththemanufacturerthattheirtransformercanbedimmed.Whendimming,anELVinterface(suchasthePHPM-PA-DV-WH) must be used with the control unit.
•Notallzonesmustbeconnected;however,connectedzonesmusthaveaminimumloadasspecifiedabove.
•Nozonemaybeloadedwithmorethanthecapacityspecifiedabove.Forhigherwattageapplications,useLutron power module PHPM-PA-JA or PHPM-SW-JA.
System Limits•TheQSwiredcommunicationlinkislimitedto100devicesor100zones.
Specifications
Preset Dimming Controls
369430 Rev. A 3 04.25.11
100 V Control Unit
®
Job Name:
Job Number:
Model Numbers:
PageSPECIFICATION SUBMITTAL
Astronomic Timeclock• Integraltoallunits.•7dailyschedulesavailable.•Oneavailableholidayscheduleisprogrammableby
date up to one year in advance.•25eventsperdaymaximum.•TimeclockeventsareprogrammabletocontrolscenesthataffectanyEnergiSavrNodeTM unit connected on the QS link without changing the local scene on the GRAFIK Eye® QS.
•Astronomictimesareprogrammablebyintegralcitydatabase or by entering latitude and longitude. Times automatically adjust throughout the year based on location.
•Localtimeclockeventscanactivateanyofthefollowingfeatures:
-Scenes1to16andOff - Any available shade presets -StartandEndafterhoursmode -EnableandDisabledaylightingforallzones/groups -EnableandDisableoccupancyforoccupancy/
vacancy sensors -EnableandDisableoccupiedeventsforalloccupancy
sensors
System Communications and Capacities•Low-voltagetypeIECPELV/NEC® Class 2 wiring connectscontrolunits,wallstations,motorizedshades,andcontrolinterfaces.
•AQSsystemcanhaveupto100devicesand100zones.
Infrared• Infrared(IR)receiverallowsinfraredtransmitterstoselect8scenes,raise/lowerlightingzones,orraise/lower shades.
•Transmitterbuttonsimitatebuttonsonfaceplate.•50ft(15m)lineofsightrange.•TerminalblockinfraredinputforconnectiontoawiredIRinputfromthird-partyequipment.
• IRcanbedisabledviaprogramming.•WorkswithLutronGRX-ITandGRX-8ITinfraredremote
controls.
Shade Control•TheGRAFIKEye® QS can include up to 3 shade button
columns. Each column has backlit open, preset, close, and raise/lower buttons.
•Eachshadebuttoncolumncanbeprogrammedtooperateoneshadeoragroupofshades.(Shadesmaybe assigned to more than one shade button column).
•Faceplatesareavailablewith1,2and3shadebuttoncolumns.
Zone Control•Eachzonehasadedicatedraiseandlowerbuttontoadjustthezone.
•Eachzonehasadedicated7LEDbargraphforlevelstatus.Percentageoflightlevelandenergysavedisdisplayedontheinfoscreen.
•AllzoneinformationhasbluebacklitLEDs.Backlightturnsoffwhenidlefor30seconds.
Info Screen•OLED(organicLED)screenisviewablefromallangles.•Screenturnsoffwhenidlefor30seconds.•Programmablezonelabels.•Programmablescenelabels.•Statusofreal-timezonepercentageandenergysavings.•Programmabletimeclockschedules.•Programmableshadelabels.
Specifications
Preset Dimming Controls
369430 Rev. A 4 04.25.11
100 V Control Unit
®
Job Name:
Job Number:
Model Numbers:
PageSPECIFICATION SUBMITTAL
SpecificationsAccessory Controls: seeTouch® QS Wallstations (QSWS2)
•WiredseeTouch®QSkeypadsprovidethefollowingfeatures:
-Accesstooneormoreofthe16scenesontheGRAFIK Eye® QS
-Zonetoggle,partitioning,sequencing,finetune,panicmode, and timeclock enable/disable
- Contact closure inputs -Certainfunctionsareonlyavailableonspecific
wallstationconfigurations.RefertotheseeTouch QS specificationsubmittal.
Accessory Controls: QS Sensor Module (QSMX-4W)•TheQSSensorModuleprovidesameanstolinkwired
occupancy and daylight sensors to a GRAFIK Eye® QS via the wired QS link.
- Occupancy sensors wired to a QS Sensor Module can be used by one or more GRAFIK Eye® QS control units on the wired link.
- Daylight sensors wired to a QS Sensor Module can be used by one or more GRAFIK Eye® QS control units on the wired link.
-Infraredsensorscancontroleitheroneormorezonesor scenes on the GRAFIK Eye® QS. Functionality varies; refertothedocumentationfortheQSSensorModulefordetails.
Accessory Controls: Contact Closure Input/Output Interface (QSE-IO)
•Recallspresetlightlevelsforthefollowingsetofsceneson the GRAFIK Eye® QS:Scenes1-4andOff Scenes9-12andOff Scenes5-8andOff Scenes13-16andOff
•Sequencescenes5-16,Enable/DisableZoneLockout,Enable/Disable Scene Lockout, Enable/Disable Panic Mode, Enable/Disable Timeclock.
•OccupancySensors.Anindividualinputcountsas1occupancysensorfortheGRAFIKEye® QS. Each input can be assigned to either Scene Control or Zone Control (pleaserefertotheOccupancySensor(s)sectionofthisguide).
• ZoneToggle.Allowsaninputtotoggleoneormorezonestoapresetlevelandoff.
•ShadeOutputmode.AShadeColumnontheGRAFIKEye® QS can be linked to control outputs 1-3 and/or outputs 4-5 on the QSE-IO.
Accessory Controls: DMX Output Interface (QSE-CI-DMX)
•AnyzoneontheGRAFIKEye® QS control unit can be mappedtoanysingleDMX512Channel.
•AnyzoneontheGRAFIKEye® QS control unit can be simultaneouslymappedtoanythreeDMX512channels(providing RGB/CMY control).
•DMXloadscannotbeusedwithdaylighting.
Accessory Controls: Ethernet and RS232 Interface (QSE-CI-NWK-E)
•AllowsformonitoringandcontroloftheoutputsandlocalscenesoftheGRAFIKEye® QS.
Accessory Controls: QS Keyswitch Wallstations (QSWS2-KS)
•RecallspresetlightlevelsforanytwoscenesincludingOff.•Allowsfine-tuning(raise/lowerlevel)ofazoneorgroupofzones.
•Starts/Stopsscenesequencings(Scenes1-4orScenes5-16)
•Enables/DisablesTimeclock•Enables/Disablesoccupancysensors•Enables/Disableddaylightsensors•AllowstoggleofZone(s)toapresetlevelandoff.•Enables/Disablespanicmode.•Starts/Stopsafterhoursmode.
Other Accessory Controls and Devices•EnergiSavrNodeTM QS (ESN)
Occupancy Sensor(s)•TheGRAFIKEye® QS works with occupancy sensors
through either: -SceneControl:Uptofoursensorsactivateuser-
selectable occupancy and vacancy scenes. -ZoneControl:uptofoursensorsperzoneactivateuser-
selectedoccupancyandvacancyzonelevels.•Occupancysensorsmayinclude: -ContactclosuresensorswiredtoCCIinputonbackof
GRAFIK Eye® QS - Wired sensors connected QS Sensor Module (QSM)• Ifanysensorinagroupdetectsoccupancy,thenthe
GRAFIK Eye® QS will go to the designated occupancy sceneorzonelevel.
• Ifallsensorsinagroupdetectvacancy,thentheGRAFIKEye®QSwillgotothedesignatedvacancysceneorzonelevel.
Preset Dimming Controls
369430 Rev. A 5 04.25.11
100 V Control Unit
Preset Dimming Controls
369430 Rev. A 6 04.25.11
®
Job Name:
Job Number:
Model Numbers:
PageSPECIFICATION SUBMITTAL
100 V Control Unit
®
Job Name:
Job Number:
Model Numbers:
PageSPECIFICATION SUBMITTAL
Specifications
Daylight Sensor(s)•TheGRAFIKEye® QS allows daylight sensors to control oneormorelightingzonestoadjustelectriclightlevelsbased on measured daylight levels.
•Daylightsensorsmayinclude: - Wired sensors connected to a QS sensor module (QSM)•AdaylightsensorcancontroloneormoreGRAFIKEye® QSzones:
-Eachzonecanbecalibratedtotargetlightlevels -Azonecanbecontrolledbynomorethanonedaylight
sensor•Daylightcontrolcanbeenabledordisabledonascene-
by-scene basis -Bydefault,daylightcontrolisenabledinallscenes
Note: Daylight control through the GRAFIK Eye® QS only affectslightingloads.Shadegroupscannotbecontrolledbydaylightsensors.DaylightingdoesnotaffectDMXorRGB/CMYDMXloads.
Contact Closure Input (CCI) with Power Supply Output
•EachGRAFIKEye® QS has one contact closure input (Terminal A).
- The attached device must provide a dry contact closure or solid-state output.
- Input is miswire-protected up to 36 V .•Thecontactclosureiscapableofacceptingthefollowingtypesofinputs:
-Maintained(default):TheGRAFIKEye® QS control unit will act on both a contact closure and a contact open/release event.
- Momentary: The GRAFIK Eye® QS control unit will act on only contact closure events.
•EachGRAFIKEye® QS can supply 50 mA maximum at 24 V .
-Usefulforpoweringoccupancysensors. -Anauxiliarypowersupplymustbeusedifthedevice
requires more than 50 mA.
•TheCCIiscapableofoperatinginthefollowingmodes -Occupancy:Ifanoccupancysensoriswireddirectlyto
the GRAFIK Eye® QS. - Emergency: This setting allows the GRAFIK Eye® QS to
work with a LUT-ELI. When an emergency situation is detected,alllightswillgotofullon,andnooperationswill be allowed until the emergency signal is cleared.
-Afterhours:AllowstheCCItostartandendtheafterhoursmode.
- Timeclock: Allows the CCI to enable and disable the timeclock.
-SceneLockout:Preventstheuserfrommakinganychanges to the control unit. The current scene will stay on until the CCI enables normal operation.
-SaveNever:Preventsanychangesfrombeingsavedwhile the CCI is being used.
-DisableCCI:TheCCIwillhavenoeffectonthesystemandwillnotappearonthelistofavailablesensors.
Security Lockout Password•A4-digitpassword(usingcharactersAtoZand0to
9) can be enabled/disabled to lock out access to the Programming Menu.
•BydefaultthereisnopasswordenabledontheGRAFIKEye® QS.
• Ifcasethe4-digitpasswordisforgotten,contactLutronTechnical Support to regain access.
®
Job Name:
Job Number:
Model Numbers:
PageSPECIFICATION SUBMITTAL
GRAFIK Eye® QS Custom Color Options and Model Numbers You must order a Base Unit and a Faceplate KitSee Standard Color Combinations page for faceplate, stripe, and button colors
QSGFP - - Faceplate Prefix
Color/ Finish
Number ofShadeColumns
Omit = none 1 = 1 column 2 = 2 columns 3 = 3 columns
Architectural Matte FinishesStandard (ship in 48 hours)White WHIvory IVBeige BEGray GRBrown BRBlack BLAlmond ALLight Almond LA
Architectural Metal FinishesBright Brass BBBright Chrome BCBright Nickel BNSatin Brass SBSatin Chrome SCSatin Nickel SNAntique Brass QBAntiqueBronze QZ
Anodized Aluminum FinishesClear CLABlack BLABrass BRA
Satin Color Matte FinishesSnow SWBiscuit BIEggshell ESTaupe TPMidnight MNLimestone LSStone STDesert Stone DSTerracotta TCHot HTGoldstone GSPalladium PDPlum PLTurquoise TQBluestone BGSea Glass SGGreenbrier GBSienna SIMerlot MRMocha Stone MS
Top Door Color
Faceplate Kit (includes coordinating stripe and buttons)
Faceplate Custom Color/Finish Codes
Keypad Engraving
Code
Keypad Engraving Codes
Omit = Unengraved Shipswithengravingcertificatethatcustomer can redeem at no charge
EGN = General Engraving
NST = Non-Standard Text Engraving Please visit the GRAFIK Eye® QS website at www.lutron.com/grafikeyeqs forcustomengravingforms.Submitcompletedformwithorder,andunitwillshipengravedasspecifiedbycustomer.
Omit = same as unit
T = Translucent
Base Unit
QSGR - _ PJAPrefix
Number ofZones 3=3zones
4=4zones6=6zones
Phase Control Triac
OK
1 2 3 4 5 69 10 11 12 13 14 7 815 16
9-161-8
1
2
3
4
Off
OK
1 2 3 4 5 69 10 11 12 13 14 7 815 16
9-161-8
Open
Preset
Close
Lighting keypad
Shade column
Example:
QSGR-6PJA6-zonebaseunit andQSGFP-2IV-EGNIvoryfaceplatekitwithtwoshade columns and general engraving
Preset Dimming Controls
369430 Rev. A 7 04.25.11
100 V Control Unit
®
Job Name:
Job Number:
Model Numbers:
PageSPECIFICATION SUBMITTAL
QSGB - 5B - WH - Custom Button
KitPrefixKeypad
Engraving Code
Button Configuration
3BRL = 3-button with raise/lower (shade column)
5B = 5-button (lighting keypad)
Button Color/ Finish
GRAFIK Eye® QS Custom Options and Model Numbers See previous page for Other Custom Model NumbersSee Standard Color Combinations page for faceplate, stripe, and button colors
Custom Button Kit
Button Kit Custom Color/Finish CodesArchitectural Matte FinishesWhite WHIvory IVBeige BEGray GRBrown BRBlack BLAlmond ALLight Almond LA
Satin Color Matte FinishesSnow SWBiscuit BIEggshell ESTaupe TP
Custom Stripe Kit
QSGS - WHStripe
Kit Prefix
Stripe Color/Finish
Stripe Custom Color/Finish CodesSame as Faceplate colors on previous page
Keypad Engraving Codes
Omit = Unengraved Shipswithengravingcertificatethatcustomer can redeem at no charge
EGN = General Engraving
NST = Non-Standard Text Engraving Please visit the GRAFIK Eye® QS website at www.lutron.com/grafikeyeqs forcustomengravingforms.Submitcompletedformwithorder,andunitwillshipengravedasspecifiedbycustomer.
OK
1 2 3 4 5 69 10 11 12 13 14 7 815 16
9-161-8
1
2
3
4
Off
OK
1 2 3 4 5 69 10 11 12 13 14 7 815 16
9-161-8
Open
Preset
Close
Lighting keypad
Shade column
Preset Dimming Controls
369430 Rev. A 8 04.25.11
100 V Control Unit
®
Job Name:
Job Number:
Model Numbers:
PageSPECIFICATION SUBMITTAL
GRAFIK Eye® QS Standard Color CombinationsSee previous pages for Custom Model Numbers
Suffix Faceplate (F) Stripe (S) Button (B)Architectural MatteWH White Gray WhiteIV Ivory Beige IvoryBE Beige Ivory BeigeGR Gray Black GrayBR Brown Black BrownBL Black Gray BlackAL Almond Light Almond AlmondLA Light Almond Almond Light AlmondArchitectural MetalBB Bright Brass Black BlackBC Bright Chrome Black BlackBN Bright Nickel Black BlackSB Satin Brass Black BlackSC Satin Chrome Black BlackSN Satin Nickel Black BlackQB Antique Brass Black BlackQZ AntiqueBronze Black BlackAnodizedCLA Clear Black BlackBLA Black Black BlackBRA Brass Black Black
Suffix Faceplate (F) Stripe (S) Button (B)Satin MatteMN Midnight Gray BlackTP Taupe Gray TaupeSW Snow Gray SnowES Eggshell Beige EggshellBI Biscuit Eggshell BiscuitLS Limestone Gray GrayST Stone Gray GrayDS Desert Stone Taupe TaupeTC Terracotta Taupe TaupeBG Bluestone Gray GrayHT Hot Taupe TaupeMR Merlot Taupe TaupeSI Sienna Brown BrownGB Greenbrier Gray GraySG Sea Glass Gray GrayMS Mocha Stone Taupe TaupeGS Goldstone Ivory IvoryPD Palladium Gray GrayPL Plum Taupe TaupeTQ Turquoise Gray Gray
LUTRON
1
2
3
4
Off
Preset
Close
Open
F(faceplate)
F(faceplate)
B (buttons)
S (stripe)
Faceplateiscomprisedofatopandbottom.The bottom will always be the color indicated under“faceplate.”Thetopmaybethesamecolorortranslucent.Usethechartforfaceplatesthathavethesamecolortopandbottom.Ifatranslucentlidischosen,thestripe will automatically be the same color as the bottom lid.
Example:IfyouorderQSGR-4P-1WH,yourGRAFIKEye®QSwith4lightingzonesand1shadezonewillcomewithawhitefaceplate(bothtop and bottom), gray stripe, and white buttons.
Preset Dimming Controls
369430 Rev. A 9 04.25.11
100 V Control Unit
Preset Dimming Controls
369430 Rev. A 10 04.25.11
®
Job Name:
Job Number:
Model Numbers:
PageSPECIFICATION SUBMITTAL
100 V Control Unit
Wiring Diagrams
12
34
12
AB
C
123456LN
Load wiring
Communication link
Occupancy sensor/contact closure input and 24 V power
IR input
Terminations
®
Job Name:
Job Number:
Model Numbers:
PageSPECIFICATION SUBMITTAL
Preset Dimming Controls
369430 Rev. A 11 04.25.11
100 V Control Unit
Power Group Wiring ExampleOntheQSlink,therearedevicesthatsupplypoweranddevicesthatconsumepower.EachdevicehasaspecificnumberofPowerDrawUnits(PDUs)iteithersuppliesorconsumes.APowerGroupconsistsofonedevicethatsupplies power and one or more devices that consume power; each Power Group may have only one power-supplying device.RefertotheQSLinkPowerDrawUnitsspecificationsubmittal(LutronPN369405)formoreinformationconcerning PDUs. Within Power Groups on the QS link, connect all 4 terminals (1, 2, 3, and 4), shown by the letter A in the diagram. Between devices on the QS link that supply power, connect only terminals 1, 3, and 4 (NOT terminal 2), shown by the letter B on the diagram.Wiring can be T-tapped or daisy-chained.
LUTRON
LUTRON LUTRON
LUTRON
LUTRON
LUTRON
Power Group 1
Power Group 2
Power Group 3
A
A
A
B
B
B(Do not connect
terminal 2: 24 V )
(Do not connect terminal 2: 24 V )
(Do not connect terminal 2: 24 V )
Connect all 4 terminals within a power group:
1: Common 2: 24 V3 and 4: Data
Connect only 3 terminals between power groups:
1: Common 3 and 4: Data
Do not connect Terminal 2: 24 V
A
B
GRAFIK Eye® QScontrol unit Supplies PDUs
QS Power SupplySupplies PDUs
Energi Savr NodeTM QS Supplies PDUs
Control Interfaces Consume PDUs
Control Interfaces Consume PDUs
Quantum®
Supplies PDUs
Wallstations Consume PDUs
Wallstations Consume PDUs
Wallstations Consume PDUs
QS Sensor Module with wired Occupancy SensorConsumes PDUs
®
Job Name:
Job Number:
Model Numbers:
PageSPECIFICATION SUBMITTAL
Mounting
Line Voltage Wiring
Standard 4-gang U.S. wallbox, 3` in (89 mm) deep
12
34
12
AB
C
1 2 3 4 5 6 L N
Distribution Panel100 V 50 / 60 Hz
12
34
12
AB
C
1 2 3 4 5 6 L N
To Load 1
To Load 2
To Load 3
To Load 4
To Load 5
To Load 6
Rear of QS control unit
•Pullpowerwiringfromdistributionpanelandtolightfixtures.•Eachlinevoltageterminalcanacceptone12AWG(2.5mm2) wire.•ConsultLutronfornon-dimrelaywiringand/orloadsideemergencytransferwiring.
Mounting screws (4)
GRAFIK Eye® QS control unit
Hinged bottom lid
Hinged top lid
Line voltage (hot/live) is labeled L.
Preset Dimming Controls
369430 Rev. A 12 04.25.11
100 V Control Unit
®
Job Name:
Job Number:
Model Numbers:
PageSPECIFICATION SUBMITTAL
IEC PELV/NEC® Class 2 QS System Low-Voltage Wiring•Systemcommunicationuseslow-voltagewiring.•Wiringcanbedaisy-chainedorT-tapped.•Wiringmustberunseparatelyfromline/mainsvoltage.• IECPELV/NEC® Class 2 wiring link requires: - Two 18 AWG (1.0 mm2)conductorsforcontrolpower. -Onetwisted,shieldedpairof22AWG(0.5mm2)fordatalink. -AvailablefromLutron,P/NGRX-CBL-346S;checkcompatibilityinyourarea.•Totallengthofcontrollinkmustnotexceed2000ft(610m).
LUTRON
LUTRON
LUTRON
LUTRONLUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON LUTRON LUTRON
LUTRON
GRAFIK Eye® QS Control Unit Sivoia® QS
Shade
seeTouch® QS wallstations
LUTRON
LUTRON
LUTRON
LUTRONLUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON LUTRON LUTRON
LUTRON
Daisy-Chain Wiring Example
T-Tap Wiring Example GRAFIK Eye® QS
Control Unit
Sivoia® QS Shade
Sivoia® QS smart panel
Sivoia® QS smart panel
seeTouch® QS wallstations
Preset Dimming Controls
369430 Rev. A 13 04.25.11
100 V Control Unit