1g Digital Energy
Gen
erat
ion
• Detectgroundfaultsthrough100%ofthestatorwindingincludingneutralpoint
• Sub-harmonicinjectionbasedstatorgroundprotectionprovidesearlydetectionofgroundfaultconditions
• DesignedtooperatewithMultilin’sindustryleadingG60UniversalRelayGeneratorProtectionSystem
• Activeprotectionofthegeneratorevenundermachineshutdownconditionsforincreasedassetlife
• Providingawiderangeoffaultresistancecoveragewhichallowsforsuperiorgeneratorprotection
• IncreasegeneratorlifespanbyeasilyupgradingyourcurrentG60generatorprotectionrelaywiththe100%StatorGroundProtectionModule
• SimplifiedsetupandconfigurationusingEnerVistasetupsoftware
Protection• Twostagestatorgroundresistancebasedelement–64S• Widerangefaultresistancecoverage(1-20Kohms)• Overcurrentelementforlowresistancefaults• CTphaseangleerrorcompensation
Diagnostics• Sub-harmonicvoltagesupervision• Sub-harmoniccurrentsupervision• Extensiveinternaldiagnosticswithcritical-failrelay
• Mediumtolargegeneratorapplications• Generatorswithhighimpedancegrounding
• Deployablewithredundantgeneratorprotectionsystems• Suitableforunittransformerconnectedsystems
FEATURES
APPLICATIONS
KEY BENEFITS
GPM-S100% STATOR GROUND
PROTECTION MODULECompleteGeneratorSystemProtection
222
GPM-S 100% Stator Ground Protection ModuleG
ener
atio
n
www.GEDigitalEnergy.com
Protection & Control
Stator Ground Protection Module:
Stator ground module works incombination with UR G60 to provide a100%statorgroundfaultprotectionthatisoperationalduringgenerator start-up,running and stopped conditions. In the100%statorgroundfaultprotectionbasedonsub-harmonicinjection,a20Hzvoltageis injectedtodetectgroundfaultsatanypointacross100%ofthewindingtherebyprotecting the complete stator windingand allowing early detection of statorgroundfaultconditions.
Key components of the ground protection scheme:
• G60GeneratorProtectionSystem
• 20HzInjectionModule:GPM-S-G
• CouplingFilter:GPM-S-B
• CT:ITIPart#204-SD-43737
• SensitivegroundCT/VTmoduleinG60
G60 Generator Protection System
The G60 Generator Protection Systemprovides comprehensive protection formediumand largegenerators, includinglarge steam and combustion turbines,combined-cycle generators and multi-circuit hydro units. The G60 includesadvancedautomationandcommunicationcapabilities, extensive I/O options, andpowerfulfaultrecordingfeaturesthatcansimplifypostmortemdisturbanceanalysisandhelpminimizegeneratordowntime.
20Hz Injection Module
Using sub-harmonic injection providesearly detection of stator ground faultconditions. This isaccomplishedby theinjection module generating a squarewave pulse of 20Hz with a magnitudeof +/-26V into the stator winding. Theinjectionmodulemonitorsthefrequencyandmagnitudeofthesignalitgenerates,which allows for the Stator module todetermineifagroundfaulthasoccurredinthestatorwinding.Inaddition,thestatormoduleisalsoequippedwithacritical-failrelaythatcanbewiredtoalarmfailure.
Coupling filter
The coupling filter is used to meet twofunctions: to smooth the square waveand convert it into a sine wave and toprotect the injection module from ACvoltageimpressedfromthesecondaryofneutral grounding transformer. Couplingfiltercontainsonlypassivecomponents.ItalsocontainsvoltagedividercircuitstobeusedonapplicationswithNGTsecondaryvoltagegreaterthan500V.
100% Stator Ground Fault Detection
• The100%statorgroundfaultprotectionisbasedonsub-harmonicinjection• 20Hzvoltageisinjectedtodetectgroundfaultsatanypointacross100%ofthewinding• ThestatorgroundmoduleworksincombinationwiththeG60toprovide100%statorgroundfaultprotection• Operationalduringgeneratorstart-up,runningandstoppedconditions
StatorBus Duct Rotor Slip Rings
G60 Generator Protection Integration
•TheG60,GPM-S,andGPM-Fmodulesprovidecompletegeneratorprotection
•GPM-S&GPM-FProtectionunitsareconnecteddirectlytotheG60relay
•AllconfigurationandmonitoringisperformedthroughtheG60
NeutralGroundingTransformerCT
R
Band Pass Filter
Stator Module
333
GPM-S 100% Stator Ground Protection Module
Gen
erat
ion
www.GEDigitalEnergy.com
Stator Module Band Pass Filter Module
Device Number Function
21P PhaseDistanceBackup24 VoltsPerHertz25 SynchronismCheck27P PhaseUndervoltage27TN ThirdHarmonicNeutralUndervoltage27X AuxiliaryUndervoltage32 SensitiveDirectionalPower40 LossofFieldRelay46 GeneratorUnbalance49 ThermalOverloadRTD50G GroundInstantaneousOvercurrent50N NeutralInstantaneousOvercurrent50P PhaseInstantaneousOvercurrent50SP SplitPhaseInstantaneousOvercurrent50/27 AccidentalEnergization51G GroundTimeOvercurrent51P PhaseTimeOvercurrent59N NeutralOvervoltage59P PhaseOvervoltage59X AuxiliaryOvervoltage59_2 NegativeSequenceOvervoltage64F Fieldgroundprotection64S Sub-harmonicstatorgroundprotection64TN 100%statorground67_2 NegativeSequenceDirectionalOvercurrent67N NeutralDirectionalOvercurrent67P PhaseDirectionalOvercurrent68 PowerSwingBlocking78 Out-of-StepProtection81O Overfrequency81R RateofChangeofFrequency81U Underfrequency87G Restrictedgroundfault87S GeneratorStatorDifferential
ANSIDeviceNumbers&Functions
G15G78 G05
64TN
51P 51N 46 2_76 N76P76 68 78
24 59P27P 59_2
25
Metering
Trip
Close
32 50/2740
59N 81U81O
27TN X72 X95
G60 Generator Protection System
52
R
87S
50N
81R
50P21P
G
49
64S
EX GPM-F 64F
Dimensional Data
Functional Block Diagram
19.160
5.250
7.250
8.451
17.760
19.160
5.250
7.250
8.451
17.760
11.870
7.500
7.310
9.370
7.869
8.300
11.870
7.500
7.310
9.370
7.869
8.300
Top Top
Front Front
444
GPM-S 100% Stator Ground Protection ModuleG
ener
atio
n
www.GEDigitalEnergy.com
OrderingGPM-S DescriptionIncluded Components: 20HzGenerator
BandPassFilterCurrentTransformer
Protection Specifications
Sub-Harmonic 100% Stator Ground (64S)Statorgroundresistancepickupaccuracy:
+/-5%ofreadingovertherangefrom1kΩ-10kΩand+/-10%ofreadingovertherangeof10-20kΩ
TotalStatorCapacitancetoGround:
200nF–2µF
Sub-harmonicvoltagemeteringaccuracy:
+/-2%ofreadingor0.2Vovertherange0.5Vto25Vac
Sub-harmoniccurrentmeteringaccuracy:
+/-2%ofreadingor5mAovertherange5mAto200mA
Sub-harmonicelementoperatingtime:
0.6–1.2sec
Sub-harmonicelementdropoutlevelaccuracy:
102-103%ofpickup
Timedelayaccuracy: +/-3%oftimedelaysettingor+/-4mswhicheverisgreater
TestsDielectricvoltagewithstand
EN60255-5
Impulsevoltagewithstand
EN60255-5
Insulationresistance EN60255-5Dampedoscillatory IEC61000-4-18/IEC
60255-22-1Electrostaticdischarge EN61000-4-2/IEC60255-22-2RFimmunity EN61000-4-3/IEC60255-22-3Fasttransientdisturbance
EN61000-4-4/IEC60255-22-4
Surgeimmunity EN61000-4-5/IEC60255-22-5ConductedRFimmunity
EN61000-4-6/IEC60255-22-6
VoltageinterruptionandrippleDC
IEC60255-11
Radiatedandconductedemissions
CISPR11/CISPR22/IEC60255-25
Sinusoidalvibration IEC60255-21-1Shockandbump IEC60255-21-2Seismic IEC60255-21-3Powermagneticimmunity
IEC61000-4-8
Pulsemagneticimmunity
IEC61000-4-9
Dampedmagneticimmunity
IEC61000-4-10
Voltagedipandinterruption
IEC61000-4-11
Voltageripple IEC61000-4-17Ingressprotection IEC60529Environment(Cold) IEC60068-2-1Environment(Hot) IEC60068-2-2Humidity IEC60068-2-30SWCoscillatory IEEE/ANSIC37.90.1SWCtransients IEEE/ANSIC37.90.1RFimmunity IEEE/ANSIC37.90.2ESD IEEE/ANSIC37.90.3Safety UL508Safety ULC22.2-14Safety UL1053
EnvironmentalsTemperature: Storage:-40Cto+85C
Operating:-40Cto+70CHumidity: Upto95%(noncondensing)
@55C(asperIEC60068-2-30Variant1,6days)
Altitude: 2000m(maximum)PollutionDegree: IIOvervoltageCategory: IIIngressProtection: IP10
ApprovalsCEcompliance EN60255-5
EN60255-27EN60255-26EN50263
NorthAmerica UL508UL1053C22.2No.14
ISO ISO9001CEcompliance EN60255-5
EN60255-27EN60255-26EN50263
NorthAmerica UL508UL1053C22.2No.14
ISO ISO9001
• ViewGuideformspecifications
• Downloadtheinstructionmanual
• ReviewapplicationsNotesandsupportdocuments
• Buy100%statorgroundprotectiononline
• View/downloadthefieldgroundprotectionbrochure
Visit www.GEMultilin.com/GPM to: • URApplicationsIlearningCD TRCD-URA1-C-S-1
• MultilinkEthernetSwitch ML2400-F-HI-HI-A2-A2-A6-G1
• ViewpointEngineer VPE-1
• ViewpointMaintenance VPM-1
• ViewpointMonitoringIEC61850 VP-1-61850
Multilin Accessories