100
POWER SYSTEMS SIMULATION LAB ___YEAR __ SEM EEE By Dr. J. Sridevi Gokaraju Rangaraju Institute of Engineering & Technology Bachupally

Gokaraju Rangaraju Institute of Engineering and Technology PSS Lab... · 2019. 12. 28. · Author: GRIET-JSD Created Date: 5/9/2017 1:29:36 PM

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

  • POWER SYSTEMS SIMULATION LAB

    ___YEAR __ SEM

    EEE

    By

    Dr. J. Sridevi

    Gokaraju Rangaraju Institute of Engineering &

    Technology

    Bachupally

  • GOKARAJU RANGARAJU INSTITUTE OF

    ENGINEERING AND TECHNOLOGY

    (Autonomous)

    Bachupally , Hyderabad-500 072

    CERTIFICATE

    This is to certify that it is a record of practical work done in the Power

    Systems Simulation Laboratory in _____ sem of ________________

    year during the year ________________________.

    Name:

    Roll No:

    Branch: EEE

    Signature of staff member

  • INDEX

    List of Experiments

    S.No Date Name of the Experiment Page no Signature

    1 Sinusoidal Voltages and currents 1

    2 Computation of line parameters 6

    3 Modelling of transmission lines 11

    4 Formation of bus admittance matrix 18

    5 Load Flow solution using gauss seidel

    method 23

    6 Load flow solution using Newton

    Rapshon method in Polar coordinates 30

    7 Load flow solution using Newton

    Rapshon method in Rectangular coordinates 34

    8 Transient stability analysis of single-

    machine infinite bus 38

    system

    9 Power flow solution of 3 – bus system 43

    10

    a)Optimal dispatch neglecting losses b) Optimal dispatch including losses

    48 54

    11

    Three phase short circuit analysis in a

    synchronous machine(symmetrical fault

    analysis) 58

    12 Unsymmetrical fault analysis-LG,LL,LLG

    fault 64

    13 Z- Bus building algorithm 73

    14

    a)Obtain symmetrical components of a set of unbalanced currents b)Obtain the original unbalanced phase voltages from symmetrical components

    78 82

    15 Short circuit analysis of a power system

    with IEEE 9 bus system 85

    16 Power flow analysis of a slack bus

    connected to different loads 89

    17 Load flow analysis of 3 motor systems

    connected to slack bus 94

  • GRIET/EEE Power Systems Simulation Lab

    1

    Date: Experiment-1

    SINUSOIDAL VOLTAGES AND CURRENTS

    Aim: To determine sinusoidal voltages and currents

    Apparatus: MATLAB

    Theory : The RMS Voltage of an AC Waveform

    The RMS value is the square root of the mean (average) value of the squared function of the

    instantaneous values. The symbols used for defining an RMS value are VRMS or IRMS.

    The term RMS, refers to time-varying sinusoidal voltages, currents or complex waveforms were

    the magnitude of the waveform changes over time and is not used in DC circuit analysis or

    calculations were the magnitude is always constant. When used to compare the equivalent RMS

    voltage value of an alternating sinusoidal waveform that supplies the same electrical power to a

    given load as an equivalent DC circuit, the RMS value is called the “effective value” and is

    presented as: Veffor Ieff.

    In other words, the effective value is an equivalent DC value which tells you how many volts or

    amps of DC that a time-varying sinusoidal waveform is equal to in terms of its ability to produce

    the same power. For example, the domestic mains supply in the United Kingdom is 240Vac. This

    value is assumed to indicate an effective value of “240 Volts RMS”. This means then that the

    sinusoidal RMS voltage from the wall sockets of a UK home is capable of producing the same

    average positive power as 240 volts of steady DC voltage as shown below.

    RMS Voltage Equivalent

  • GRIET/EEE Power Systems Simulation Lab

    2

    Circuit diagram:

    Fig: Simulink model for voltage and current measurement

    Procedure:

    1. Open Matlab-->Simulink--> File ---> New---> Model

    2. Open Simulink Library and browse the components

    3. Connect the components as per circuit diagram

    4. Set the desired voltage and required frequency

    5. Simulate the circuit using MATLAB

    6. Plot the waveforms.

  • GRIET/EEE Power Systems Simulation Lab

    3

    Graph:

    Calculations:

  • GRIET/EEE Power Systems Simulation Lab

    4

  • GRIET/EEE Power Systems Simulation Lab

    5

    Result:

  • GRIET/EEE Power Systems Simulation Lab

    6

    Signature of the faculty

    Exp.No:2 Date:

    COMPUTATION OF LINE PARAMETERS AIM

    To determine the positive sequence line parameters L and C per phase per kilometre of a three

    phase single and double circuit transmission lines for different conductor arrangements and to

    understand modeling and performance of medium lines. SOFTWARE REQUIRED: MAT LAB THEORY

    Transmission line has four parameters namely resistance, inductance, capacitance and

    conductance. The inductance and capacitance are due to the effect of magnetic and electric fields

    around the conductor. The resistance of the conductor is best determined from the manufactures

    data, the inductances and capacitances can be evaluated using the formula. Inductance The general formula

    L = 0.2 ln (Dm / Ds)

    Where, Dm = geometric mean distance (GMD)

    Ds = geometric mean radius (GMR) I. Single phase 2 wire system GMD = D GMR = re-1/4 = r′ Where, r = radius of conductor II. Three phase – symmetrical spacing GMD = D GMR = re-1/4 = r′ Where, r = radius of conductor III. Three phase – Asymmetrical Transposed GMD = geometric mean of the three distance of the symmetrically placed conductors = (DABDBCDCA)1/3 GMR = re-1/4 = r′ Where, r = radius of conductors Composite conductor lines The inductance of composite conductor X, is given by Lx = 0.2 ln (GMD/GMR)

  • GRIET/EEE Power Systems Simulation Lab

    7

    where, GMD = (Daa Dab )…….(Dna …….Dnm ) GMR = n2

    (Daa Dab…….Dan )…….(DnaDnb…….Dnn) where, r’a

    = ra e(-1/ 4) Bundle Conductors The GMR of bundled conductor is normally calculated

    GMR for two sub conductor, Dsb = (Ds×d)1/2

    GMR for three sub conductor, Dsb = (Ds×d2)

    1/3 GMR

    for four sub conductor, Dsb = 1.09 × (Ds×d2)1/4

    where, Ds is the GMR of each subconductor d is bundle spacing Three phase – Double circuit transposed The inductance per phase in mH per km

    is L = 0.2×ln(GMD / GMRL) mH/km

    where, GMRL is equivalent geometric mean radius and is given by

    GMRL = (DSADSBDSC)1/3

    where, DSADSB and DSC are GMR of each phase group and given by

    1/2 DSA = 4 sb Da1a2)2 = [Dsb Da1a2]

    1/2 DSB = 4 sb Db1b2)2 = [Dsb Db1b2]

    DSC = 4 sb Dc1c2)2 = [Dsb Dc1c2]1/2

    where, Dsb =GMR of bundle conductor if conductor a1, a2….. are bundled conductor. Dsb = ra1’= rb1= ra’2 = rb’2 = rc’2 if a1, a2……. are bundled conductor GMD is the equivalent GMD per phase” & is given by GMD = [DAB * DBC *

    DCA]1/3

    where, DAB, DBC&DCA are GMD between each phase group A-B, B-C, C-A which are given by

    DAB = [Da1b1 * Da1b2 * Da2b1 * Da2b2]1/4

    DBC = [Db1c1 * Db1c2 * Db2c1 * Db2c2]1/4

    DCA = [Dc1a1 * Dc2a1 * Dc2a1 * Dc2a2]1/4

    Capacitance A general formula for evaluating capacitance per phase in micro farad per km of a transmission line is given by C = 0.0556/ ln (GMD/GMR) F/km Where, GMD is the “Geometric mean distance” which is same as that defined for inductance under various cases.

  • GRIET/EEE Power Systems Simulation Lab

    8

    PROCEDURE

    Enter the command window of the MAT LAB. Create a new M – file by selecting File - New – M – File. Type and save the program in the editor window. Execute the program by pressing Tools – Run. View the results.

    EXERCISE 1.A 500kv 3 φ transposed line is composed of one ACSR 1,272,000-cmil, 45/7 bittern conductor

    per phase with horizontal conductor configuration as show in fig.1. The conductors have a

    diameter of 1.345in and a GMR of 0.5328in. Find the inductance and capacitance per phase per

    kilometer of the line and justify the result using MAT LAB.

    a b c

    D12 =35’ D23 =35’

    D13=70’

    Fig.1

    2.The transmission line is replaced by two ACSR 636,000-cmil, 24/7 Rook conductors which have

    the same total cross-sectional area of aluminum as one bittern conductor. The line spacing as

    measured from the centre of the bundle is the same as before and is shown in fig.2. The conductors

    have a diameter of 0.977in and a GMR of 0.3924in.Bundle spacing is 18in. Find the inductance

    and capacitance per phase per kilometer of the line and justify the result using MAT LAB.

    a b c

    D12 =35’ D23 =35’

    D13=70’

  • GRIET/EEE Power Systems Simulation Lab

    9

    3.A 345- KV double –circuit three- phase transposed line is composed of two ACSR, 1,431,000-

    cmil, 45/7 Bobolink conductors per phase with vertical conductor configuration as shown in fig.3.

    The conductors have a diameter of 1.427in and a GMR of 0.564 in .the bundle spacing in 18in.

    find the inductance and capacitance per phase per kilometer of the line and justify the result using

    MAT LAB.

    a a’ S11 =11m

    H12=7m

    b S22=16.5m b’

    H23=6.5m

    S33=16.5m

    c c’

    PROGRAM

    [GMD, GMRL, GMRC] = gmd;

    L = 0.2*log(GMD/GMRL) C = 0.0556/log(GMD/GMRC)

    OUTPUT:

  • GRIET/EEE Power Systems Simulation Lab

    10

    RESULT:

    Thus the positive sequence line parameters L and C per phase per kilometre of a three phase single and double circuit transmission lines for different conductor arrangements were determined and verified with MAT LAB software. The value of L and C obtained from MAT LAB program are:

    Case1: L= C=

    Case2: L= C=

    Case3: L= C=

    Signature of the faculty

  • GRIET/EEE Power Systems Simulation Lab

    11

    Exp.No:3 Date:

    MODELLING OF TRANSMISSION LINES AIM:

    To understand modeling and performance of Short, Medium and Long transmission lines.

    SOFTWARE REQUIRED: MAT LAB

    THEORY:

    The important considerations in the design and operation of a transmission line are the

    determination of voltage drop, line losses and efficiency of transmission. These values are greatly

    influenced by the line constants R, L and C of the transmission line. For instance, the voltage drop

    in the line depends upon the values of above three line constants. Similarly, the resistance of

    transmission line conductors is the most important cause of power loss in the line and determines

    the transmission efficiency.

    A transmission line has three constants R, L and C distributed uniformly along the whole

    length of the line. The resistance and inductance form the series impedance. The capacitance

    existing between conductors for 1-phase line or from a conductor to neutral for a 3-phase line

    forms a shunt path throughout the length of the line. Short Transmission Line:

    When the length of an overhead transmission line is upto about 50km and the line voltage is comparatively low (< 20 kV), it is usually considered as a short transmission line. Medium Transmission Lines:

    When the length of an overhead transmission line is about 50-150 km and the line voltage is moderatly high (>20 kV < 100 kV), it is considered as a medium transmission line. Long Transmission Lines:

    When the length of an overhead transmission line is more than 150km and line voltage is very high (> 100 kV), it is considered as a long transmission line. Voltage Regulation:

    The difference in voltage at the receiving end of a transmission line between conditions of

    no load and full load is called voltage regulation and is expressed as a percentage of the receiving

    end voltage.

    Performance of Single Phase Short Transmission Lines

    As stated earlier, the effects of line capacitance are neglected for a short transmission line. Therefore, while studying the performance of such a line, only resistance and inductance of

    6

  • GRIET/EEE Power Systems Simulation Lab

    12

    the line are taken into account. The equivalent circuit of a single phase short transmission line is

    shown in Fig. (i).Here, the total line resistance and inductance are shown as concentrated or lumped

    instead of being distributed. The circuit is a simple a.c. series circuit. Let I = load current R = loop resistance i.e., resistance of both conductors XL = loop reactance VR = receiving end voltage cos ϕR = receiving end power factor (lagging) VS = sending end voltage cos ϕS = sending end power factor The phasor diagram of the line for lagging load power factor is shown in Fig. (ii). From the right angled traingle ODC, we get,

    (OC)2 = (OD)2+ (DC)2

    VS2 = (OE + ED)2 + (DB + BC)2

    = (VR cos ϕR + IR)2 + (VR sinϕR + IXL)2

  • GRIET/EEE Power Systems Simulation Lab

    13

    An approximate expression for the sending end voltage VS can be obtained as follows. Draw

    perpendicular from B and C on OA produced as shown in Fig. 2. Then OC is nearly equal to OF

    i.e.,

    OC = OF = OA + AF = OA + AG + GF = OA + AG + BH

    VS = VR + I R cos ϕR + I XL sin ϕR Medium Transmission

    Line Nominal T Method

    In this method, the whole line capacitance is assumed to be concentrated at the middle

    point of the line and half the line resistance and reactance are lumped on its either side as shown

    in Fig.1, Therefore in this arrangement, full charging current flows over half the line. In Fig.1, one

    phase of 3-phase transmission line is shown as it is advantageous to work in phase instead of line-

    to-line values.

    Let IR = load current per phase R = resistance per phase

  • GRIET/EEE Power Systems Simulation Lab

    14

    XL = inductive reactance per phase C = capacitance per phase cos ϕR = receiving end power factor (lagging) VS = sending end voltage/phase V1 = voltage across capacitor C The phasor diagram for the circuit is shown in Fig.2. Taking the receiving end voltage VR as the reference phasor, we have, Receiving end voltage, VR = VR + j 0 Load current, IR = IR (cos ϕR - j sin ϕR)

    Nominal π Method In this method, capacitance of each conductor (i.e., line to neutral) is divided into two halves;

    one half being lumped at the sending end and the other half at the receiving end as shown in

    Fig.3. It is obvious that capacitance at the sending end has no effect on the line drop. However,

    it’s charging current must be added to line current in order to obtain the total sending end

    current.

  • GRIET/EEE Power Systems Simulation Lab

    15

    IR = load current per phase R = resistance per phase XL = inductive reactance per phase C = capacitance per phase cos R = receiving end power factor (lagging) VS = sending end voltage per phase The phasor diagram for the circuit is shown in Fig.4. Taking the receiving end voltage as the reference phasor, we have, VR = VR + j 0 Load current, IR = IR (cos R - j sin R)

  • GRIET/EEE Power Systems Simulation Lab

    16

    EXERCISE:

    1. A 220- KV, 3φ transmission line is 40 km long. The resistance per phase is 0.15 Ω per

    km and the inductance per phase is 1.3623 mH per km. The shunt capacitance is negligible.

    Use the short line model to find the voltage and power at the sending end and the voltage

    regulation and efficiency when the line supplying a three phase load of a) 381 MVA at 0.8

    power factor lagging at 220 KV. b) 381 MVA at 0.8 power factor leading at 220 KV.

    PROGRAM

    VRLL=220; VR=VRLL/sqrt(3);

    Z=[0.15+j*2*pi*60*1.3263e-

    3]*40; disp=('(a)') SR=304.8+j*228.6; IR=conj(SR)/(3*conj(VR)); IS=IR; VS=VR+Z*IR; VSLL=sqrt(3)*abs(VS) SS=3*VS*conj(IS)

    REG=((VSLL-

    VRLL)/(VRLL))*100 E

    disp=('(b)') SR=304.8-

    j*228.6;

    IR=conj(SR)/(3*conj(VR));

    IS=IR; VS=VR+Z*IR; VSLL=sqrt(3)*abs(VS) SS=3*VS*conj(IS) REG=((VSLL-

    VRLL)/(VRLL))*100

    EFF=(real(SR)/real(SS))*100

    FF=(real(SR)/real(SS))*100

  • GRIET/EEE Power Systems Simulation Lab

    17

    OUTPUT: RESULT: Thus the program for modeling of transmission line was executed by using MAT LAB

    and the output was verified with theoretical calculation. The value of the voltage and power at the

    sending end, voltage regulation and efficiency obtained from the MAT LAB program are Voltage VS =

    Power SS = Voltage regulation REG = Efficiency EFF =

    Signature of the faculty

  • GRIET/EEE Power Systems Simulation Lab

    18

    Expt. No.:4 Date:

    FORMATION OF BUS ADMITTANCE MATRIX

    AIM To determine the bus admittance matrix for the given power system Network

    SOFTWARE REQUIRED: MAT LAB

    THEORY

    FORMATION OF Y BUS MATRIX

    Bus admittance matrix is often used in power system studies.In most of power system

    studies it is necessary to form Y-bus matrix of the system by considering certain power system

    parameters depending upon the type of analysis. For example in load flow analysis it is necessary

    to form Y-bus matrix without taking into account the generator impedance and load impedance.

    In short circuit analysis the generator transient reactance and transformer impedance taken in

    account, in addition to line data. Y-bus may be computed by inspection method only if there is no

    natural coupling between the lines. Shunt admittance are added to the diagonal elements

    corresponding to the buses at which these are connected. The off diagonal elements are unaffected.

    The equivalent circuit of tap changing transformer may be considered in forming[y-bus] matrix. FORMULA USED Yij=ΣYij for i=1 to n Yij= -Yij= -1/Zij Yij=Yji Where Yii=yjj= Sum of admittance connected to bus Yij= Negative admittance between buses

  • GRIET/EEE Power Systems Simulation Lab

    19

    START

    Read the no. Of buses , no of lines and line data

    Initialize the Y- BUS Matrix

    Consider line l = 1

    i = sb(1); I= eb(1)

    Y(i,i) =Y(i,i)+Yseries(l) +0.5Yseries(l)

    Y(j,j) =Y(j,j)+Yseries(l) +0.5Yseries(l)

    Y(i,j) = -Yseries(l)

    Y(j,i) =Y(i,j) NO Is l =NL? YES

    l = l+1 Print Y -Bus

    Stop

  • GRIET/EEE Power Systems Simulation Lab

    20

    Exercise:

    Line number

    Starting Bus

    Ending Bus Series Line Line Changing

    Impedance

    Admittance

    1 1 2 0.1+0.4j 0.15j

    2 2 3 0.15+0.6j 0.02j

    3 2 4 0.18+0.55j 0.018j

    4 3 4 0.1+0.35j 0.012j

    5 4 1 0.25+0.7j 0.03j

    PROGRAM function[Ybus] = ybus(zdata)

    nl=zdata(:,1); nr=zdata(:,2); R=zdata(:,3); X=zdata(:,4); nbr=length(zdata(:,1)); nbus =

    max(max(nl), max(nr)); Z = R + j*X; %branch impedance

    y= ones(nbr,1)./Z; %branch admittance Ybus=zeros(nbus,nbus); % initialize Ybus to zero

    for k = 1:nbr; % formation of the off diagonal elements if nl(k) > 0 & nr(k) > 0

    Ybus(nl(k),nr(k)) = Ybus(nl(k),nr(k)) - y(k); Ybus(nr(k),nl(k)) = Ybus(nl(k),nr(k)); end

    end for n = 1:nbus % formation of the diagonal elements for k = 1:nbr

    if nl(k) == n | nr(k) == n Ybus(n,n) = Ybus(n,n) + y(k); else, end

    end

    end

  • GRIET/EEE Power Systems Simulation Lab

    21

  • GRIET/EEE Power Systems Simulation Lab

    22

    OUTPUT:

    RESULT: Thus the bus admittance matrix of the given power system using inspection method

    was found and verified by theoretical calculation.

    Y Bus:

    Signature of the faculty

  • GRIET/EEE Power Systems Simulation Lab

    23

    Expt. No.:5 Date:

    LOAD FLOW SOLUTION USING GAUSS SEIDEL METHOD

    AIM: To carry out load flow analysis of the given power system network by Gauss Seidal

    method

    SOFTWARE REQUIRED: POWERWORLD

    THEORY

    Load flow analysis is the study conducted to determine the steady state operating condition of the

    given system under given conditions. A large number of numerical algorithms have been developed and

    Gauss Seidel method is one of such algorithm.

    PROBLEM FORMULATION

    The performance equation of the power system may be written of

    [I bus] = [Y bus][V bus] (1) Selecting one of the buses as the reference bus, we get (n-1) simultaneous equations. The bus

    loading equations can be written as Ii = Pi-jQi / Vi* (i=1,2,3,…………..n) (2)

    Where,

    n

    Pi=Re [ Σ Vi*Yik Vk] . (3) k=1

    n

    Qi= -Im [ Σ Vi*Yik Vk]. (4) k=1

    The bus voltage can be written in form

    of

    n

    Vi=(1.0/Yii)[Ii- Σ Yij Vj] (5) j=1

    j≠i(i=1,2,…………n)& i≠slack bus

    Substituting Ii in the expression for Vi, we get

    n

    Vi new=(1.0/Yii)[Pi-JQi / Vio* - Σ Yij Vio] (6) J=1

    The latest available voltages are used in the above expression, we get n n

    Vi new=(1.0/Yii)[Pi-JQi / Vo

    i* - Σ YijVjn- Σ Yij Vio] (7) J=1 j=i+1

    The above equation is the required formula .this equation can be solved for voltages in interactive manner.

  • GRIET/EEE Power Systems Simulation Lab

    24

    During each iteration, we compute all the bus voltage and check for convergence is carried out by comparison with the voltages obtained at the end of previous iteration. After the solutions is obtained. The stack bus real and reactive powers, the reactive power generation at other generator buses and line flows can be calculated.

    ALGORITHM Step1: Read the data such as line data, specified power, specified voltages, Q limits at the generator buses

    and tolerance for convergences Step2: Compute Y-bus matrix. Step3:

    Initialize all the bus voltages. Step4: Iter=1 Step5: Consider i=2, where i’ is the bus number. Step6: check whether this is PV bus or PQ bus. If it is PQ bus goto step 8 otherwise go to next step. Step7: Compute Qi check for q limit violation. QGi=Qi+QLi.

    7).a).If QGi>Qi max ,equate QGi = Qimax. Then convert it into PQ bus. 7).b).If

    QGi

  • GRIET/EEE Power Systems Simulation Lab

    25

    START

    Read

    1. Primitive Y matrix

    2. Bus incidence matrix A

    3. Slack bus voltages

    4. Real and reactive bus powers Pi& Qi

    5. Voltage magnitudes and their limits

    Form Ybus

    Make initial assumptions

    Compute the parameters Ai for i=m+1,…,n and Bik for i=1,2,…,n;

    k=1,2,…,n

    Set iteration count r=0

    Set bus count i=2 and ΔVmax=0

    Test for

    type of bus

    Qi(r+1) >Qi,

    max

    Qi(r+1) <

    Qi,min

    Compute Qi(r+1)

    Qi(r+1) = Qi,max Qi

    (r+1) = Qi,min Compute Ai(r+1)

    Compute Ai

    Compute Vi(r+1)

    Compute δi(r+1) and

    Vi(r+1) =|Vi

    s|/δi(r+1)

  • GRIET/EEE Power Systems Simulation Lab

    26

    FLOW CHART FOR GAUSS SEIDEL METHOD

    Exercise:

    1. The Fig.1 shows the single line diagram of a simple three bus power system with generation at buses 1.

    The magnitude of voltage at bus 1 is adjusted to 1.05 p.u. The scheduled loads at buses 2 & 3 are marked

    on the diagram .line impedances are marked in per unit on a 100-MVA base and the line charging charging

    susceptances are neglected. a). using the gauss-seidal method, determine the phasor values of the voltage at the load buses 2 and 3(P-

    Q buses) accurate to four decimal places. b).find the slack bus real and reactive power. c) Determine the line flow and line losses, Using software write an algorithm.

    Replace Vir by Vi(r+1) and

    advance bus count i = i+1

    Is i

  • GRIET/EEE Power Systems Simulation

    Lab

    27

    1 0.02 + j0.04 2

    256.6MW

    0.01+j0.03 0.0125+j0.025 110.2Mvar

    Slack bus v1 = 1.05L 3

    138.6 MW 45.2 Mvar

    PROCEDURE

    Create a new file in edit mode by selecting File - New File.

    Browse the components and build the bus sytem

    Execute the program in run mode by selecting power flow by gauss seidel method

    View the results in case information-Bus information.

    Tabulate the results.

    POWER WORLD bus diagram:

  • GRIET/EEE Power Systems Simulation Lab

    28

  • GRIET/EEE Power Systems Simulation Lab

    29

    RESULTS: A one line diagram has been developed using POWER WORLD for the given power system by

    Gauss Seidal method and the results are verified with model calculation.

    Signature of the faculty

  • GRIET/EEE Power Systems Simulation Lab

    30

    Exp.No. :6 Date:

    LOAD FLOW SOLUTION USING NEWTON RAPSHON METHOD IN

    POLAR COORDINATES AIM

    To carry out load flow analysis of the given power system by Newton Raphson method in

    polar coordinates

    SOFTWARE REQUIRED: POWERWORLD THEORY The Newton Raphson method of load flow analysis is an iterative method which approximates the

    set of non-linear simultaneous equations to a set of linear simultaneous equations using Taylor’s series expansion and the terms are limited to first order approximation. The load flow

    equations for Newton Raphson method are non-linear equations in terms of real and imaginary

    part of bus voltages.

    where, ep = Real part of Vp

    fp = Imaginary part of Vp Gpq, Bpq = Conductance and Susceptances of admittance Ypq respectively. ALGORITHM Step1: Input the total number of buses. Input the details of series line impendence and line

    charging admittance to calculate the Y-bus matrix. Step2: Assume all bus voltage as 1 per unit except slack bus. Step3: Set the iteration count as k=0 and bus count as p=1. Step4: Calculate the real and reactive power pp and qp using the formula

    P=ΣvpqYpq*cos(Qpq+εp-εq) Qp=ΣVpqYpa*sin(qpq+εp-εa)

  • GRIET/EEE Power Systems Simulation Lab

    31

    Evalute pp*=psp-pp* Step5: If the bus is generator (PV) bus, check the value of Qp*is within the limits.If it Violates

    the limits, then equate the violated limit as reactive power and treat it as PQ bus. If limit is not

    isolated then calculate, |vp|^r=|vgp|^rspe-|vp|r ; Qp*=qsp-qp* Step6: Advance bus count by 1 and check if all the buses have been accounted if not go to step5. Step7: Calculate the elements of Jacobean matrix. Step8: Calculate new bus voltage increment pk and fpk Step9: Calculate new bus voltage ep*h+ ep* Fp^k+1=fpK+fpK Step10: Advance iteration count by 1 and go to step3. Step11: Evaluate bus voltage and power flows through the line .

    EXERCISE 1. For the sample system of Fig. the generators are connected at all the four buses, while loads are

    at buses 2 and 3. Values of real and reactive powers are listed in Table 6.3. All buses other than

    the slack are PQ type.

    Assuming a flat voltage start, find the voltages and bus angles at the three buses using Newton

    Raphson Method

  • GRIET/EEE Power Systems Simulation Lab

    32

    PROCEDURE

    Create a new file in edit mode by selecting File - New File.

    Browse the components and build the bus sytem

    Execute the program in run mode by selecting power flow by Newton Raphson method

    View the results in case information-Bus information.

    Tabulate the results.

    POWER WORLD bus diagram:

  • GRIET/EEE Power Systems Simulation Lab

    33

    RESULT A one line diagram has been developed using POWERWORLD for the given power system by Newton raphson method and the results are verified with model calculation

    Signature of the faculty

  • GRIET/EEE Power Systems Simulation Lab

    34

    Exp.No. :7 Date:

    LOAD FLOW SOLUTION USING NEWTON RAPSHON METHOD IN

    RECTANGULAR COORDINATES AIM

    To carry out load flow analysis of the given power system by Newton Raphson method in

    Rectangular coordinates.

    SOFTWARE REQUIRED: POWERWORLD THEORY The Newton Raphson method of load flow analysis is an iterative method which approximates the

    set of non-linear simultaneous equations to a set of linear simultaneous equations using Taylor’s series expansion and the terms are limited to first order approximation. The load flow

    equations for Newton Raphson method are non-linear equations in terms of real and imaginary

    part of bus voltages.

    where, ep = Real part of Vp

    fp = Imaginary part of Vp Gpq, Bpq = Conductance and Susceptances of admittance Ypq respectively. ALGORITHM Step1: Input the total number of buses. Input the details of series line impendence and line

    charging admittance to calculate the Y-bus matrix. Step2: Assume all bus voltage as 1 per unit except slack bus. Step3: Set the iteration count as k=0 and bus count as p=1. Step4: Calculate the real and reactive power pp and qp using the formula

    P=ΣvpqYpq*cos(Qpq+εp-εq) Qp=ΣVpqYpa*sin(qpq+εp-εa)

  • GRIET/EEE Power Systems Simulation Lab

    35

    Evalute pp*=psp-pp* Step5: If the bus is generator (PV) bus, check the value of Qp*is within the limits.If it Violates

    the limits, then equate the violated limit as reactive power and treat it as PQ bus. If limit is not

    isolated then calculate, |vp|^r=|vgp|^rspe-|vp|r ; Qp*=qsp-qp* Step6: Advance bus count by 1 and check if all the buses have been accounted if not go to step5. Step7: Calculate the elements of Jacobean matrix. Step8: Calculate new bus voltage increment pk and fpk Step9: Calculate new bus voltage ep*h+ ep* Fp^k+1=fpK+fpK Step10: Advance iteration count by 1 and go to step3. Step11: Evaluate bus voltage and power flows through the line .

    EXERCISE 1. For the sample system of Fig. the generators are connected at all the four buses, while loads are at buses 2 and 3. Values of real and reactive powers are listed in Table 6.3. All buses other than the slack are PQ type. Assuming a flat voltage start, find the voltages and bus angles at the three buses using Newton Raphson Method

  • GRIET/EEE Power Systems Simulation Lab

    36

    PROCEDURE

    Create a new file in edit mode by selecting File - New File.

    Browse the components and build the bus sytem

    Execute the program in run mode by selecting power flow by Newton Raphson method

    View the results in case information-Bus information.

    Tabulate the results.

    POWER WORLD bus diagram:

  • GRIET/EEE Power Systems Simulation Lab

    37

    RESULT A one line diagram has been developed using POWERWORLD for the given power system by Newton raphson method and the results are verified with model calculation

    Signature of the faculty

  • GRIET/EEE Power Systems Simulation Lab

    38

    Exp.no.:8 Date:

    TRANSIENT STABILITY ANALYSIS OF SINGLE-MACHINE INFINITE BUS SYSTEM

    AIM To become familiar with various aspects of the transient stability analysis of Single-Machine-Infinite

    Bus (SMIB) system OBJECTIVES The objectives of this experiment are: 1. To study the stability behavior of one machine connected to a large power system subjected to a

    severe disturbance (3-phase short circuit) 2. To understand the principle of equal-area criterion and apply the criterion to study the stability of

    one machine connected to an infinite bus 3. To determine the critical clearing angle and critical clearing time with the help of equal-area

    criterion 4. To do the stability analysis using numerical solution of the swing equation. SOFTWARE REQUIRED: MAT LAB 7.7 THEORY The tendency of a power system to develop restoring forces to compensate for the disturbing forces to

    maintain the state of equilibrium is known as stability. If the forces tending to hold the machines in

    synchronism with one another are sufficient to overcome the disturbing forces, the system is said to

    remain stable. The stability studies which evaluate the impact of disturbances on the behavior of synchronous

    machines of the power system are of two types – transient stability and steady state stability. The

    transient stability studies involve the determination of whether or not synchronism is maintained after

    the machine has been subjected to a severe disturbance. This may be a sudden application of large load,

    a loss of generation, a loss of large load, or a fault (short circuit) on the system. In most disturbances,

    oscillations are such magnitude that linearization is not permissible and nonlinear equations must be

    solved to determine the stability of the system. On the other hand, the steady-state stability is concerned

    with the system subjected to small disturbances wherein the stability analysis could be done using the

    linearized version of nonlinear equations. In this experiment we are concerned with the transient stability of power systems. A method known as the equal-area criterion can be used for a quick prediction of stability of a one-

    machine system connected to an infinite bus. This method is based on the graphical interpretation of

  • GRIET/EEE Power Systems Simulation Lab

    39

    energy stored in the rotating mass as an aid to determine if the machine maintains its stability after a

    disturbance. The method is applicable to a one-machine system connected to an infinite bus or a two-

    machine system. Because it provides physical insight to the dynamic behavior of the machine, the

    application of the method to analyze a single-machine system is considered here. Stability: Stability problem is concerned with the behavior of power system when it is subjected to

    disturbance and is classified into small signal stability problem if the disturbances are small and

    transient stability problem when the disturbances are large. Transient stability: When a power system is under steady state, the load plus transmission loss equals

    to the generation in the system. The generating units run at synchronous speed and system frequency,

    voltage, current and power flows are steady. When a large disturbance such as three phase fault, loss

    of load, loss of generation etc., occurs the power balance is upset and the generating units rotors

    experience either acceleration or deceleration. The system may come back to a steady state condition

    maintaining synchronism or it may break into subsystems or one or more machines may pull out of

    synchronism. In the former case the system is said to be stable and in the later case it is said to be

    unstable.

    EXERCISE: A 60Hz synchronous generator having inertia constant H = 9.94 MJ/MVA and a direct axis transient

    reactance Xd’= 0.3 per unit is connected to an infinite bus through a purely resistive circuit as shown

    in fig.1. Reactances are marked on the diagram on a common system base. The generator is delivering

    real power of 0.6% unit, 0.8 pf lagging and the infinite bus at a voltage of 1 per unit. Assume the p.u

    damping power coefficient d=0.138. Consider a small disturbance change in delta=100 . Obtain the

    equation describes the motion of the rotor angle and generation frequency

  • GRIET/EEE Power Systems Simulation Lab

    40

    If the generation is operating at steady state at when the input power is increased by

    small amount . The generator excitation and infinite bus bar voltage are same

    as before Obtain a simulink block diagram of state space mode

    and simulate to obtain the response.

  • GRIET/EEE Power Systems Simulation Lab

    41

  • GRIET/EEE Power Systems Simulation Lab

    42

    RESULT:

    Signature of the faculty

  • GRIET/EEE Power Systems Simulation Lab

    43

    Exp.No: 9 Date:

    POWER FLOW SOLUTION OF 3 – BUS SYSTEM

    Aim: To perform power flow solution of a 3-Bus system.

    Apparatus: MATLAB-PSAT

    Theory:

    Slack Bus: To calculate the angles θi (as discussed above), a reference angle (θi = 0) needs to

    be specified so that all the other bus voltage angles are calculated with respect to this reference

    angle. Moreover, physically, total power supplied by all the generation must be equal to the sum

    of total load in the system and system power loss. However, as the system loss cannot be

    computed before the load flow problem is solved, the real power output of all the generators in

    the system cannot be pre-specified. There should be at least one generator in the system which

    would supply the loss (plus its share of the loads) and thus for this generator, the real power

    output can’t be pre-specified. However, because of the exciter action, Vi for this generator can

    still be specified. Hence for this generator, Vi and θi(= 0) are specified and the quantities Pi and

    Qi are calculated. This generator bus is designated as the slack bus. Usually, the largest generator

    in the system is designated as the slack bus.

    In the General Load Flow Problem the Bus with largest generating capacity is taken as the Slack

    Bus or Swing Bus. The Slack Bus Voltage is taken to be 1.0 + j 0 P.U. and should be capable of

    supplying total Losses in the System. But usually the generator bus are only having station

    auxiliary which may be only up to 3% of total generation . If the Generation at Slack Bus is

    more it can take more load connected to the slack bus.

    A slack bus is usually a generator bus with a large real and reactive power output. It is assumed

    that its real and reactive power outputs are big enough that they can be adjusted as required in

    order to balance the power in the whole system so that the power flow can be solved. A slack

    bus can have load on it because in real systems it is actually the bus of a power plant, which can

    have its own load. It also takes care of the Line losses

  • GRIET/EEE Power Systems Simulation Lab

    44

    Circuit Diagram:

    Procedure :

    Create a new file in MATLAB-PSAT

    Browse the components in the library and build the bus system.

    Save the file and upload the data file in PSAT main window

    Execute the program and run powerflow

    Get the network visualization.

  • GRIET/EEE Power Systems Simulation Lab

    45

  • GRIET/EEE Power Systems Simulation Lab

    46

  • GRIET/EEE Power Systems Simulation Lab

    47

    Result:

    Signature of the faculty

  • GRIET/EEE Power Systems Simulation Lab

    48

    Exp.No: 10(a) Date:

    OPTIMAL DISPATCH NEGLECTING LOSSES

    Aim : To develop a program for solving economic dispatch problem without transmission losses for a given load condition using direct method and Lambda-iteration method.

    Apparatus: MATLAB

    Theory:

    As the losses are neglected, the system model can be understood as shown in Fig, here n number

    of generating units are connected to a common bus bar, collectively meeting the total power

    demand PD. It should be understood that share of power demand by the units does not involve

    losses.

    Since transmission losses are neglected, total demand PD is the sum of all generations of n-

    number of units. For each unit, a cost functions Ci is assumed and the sum of all costs computed

    from these cost functions gives the total cost of production CT.

    Fig : System with n-generators

    where the cost function of the ith unit, from Eq. (1.1) is:

    Ci = αi + βiPi + γiPi2

    Now, the ED problem is to minimize CT, subject to the satisfaction of the following equality

    and inequality constraints.

    Equality constraint

    The total power generation by all the generating units must be equal to the power demand.

    http://my.safaribooksonline.com/9788131755914/navPoint-12#C1F7http://my.safaribooksonline.com/9788131755914/navPoint-9#C1E1

  • GRIET/EEE Power Systems Simulation Lab

    49

    where Pi = power generated by ith unit

    PD = total power demand.

    Inequality constraint

    Each generator should generate power within the limits imposed.

    Pimin ≤ Pi ≤ Pi

    max i = 1, 2, … , n

    Economic dispatch problem can be carried out by excluding or including generator power

    limits, i.e., the inequality constraint.

    The constrained total cost function can be converted into an unconstrained function by using

    the Lagrange multiplier as:

    The conditions for minimization of objective function can be found by equating partial

    differentials of the unconstrained function to zero as

    Since Ci = C1 + C2+…+Cn

    From the above equation the coordinate equations can be written as:

    The second condition can be obtained from the following equation:

  • GRIET/EEE Power Systems Simulation Lab

    50

    Equations Required for the ED solution

    For a known value of λ, the power generated by the ith unit from can be written as:

    which can be written as:

    The required value of λ is:

    The value of λ can be calculated and compute the values of Pi for i = 1, 2,…, n for optimal

    scheduling of generation.

    Exercise:

  • GRIET/EEE Power Systems Simulation Lab

    51

    𝑀𝑊 𝐿𝑖𝑚𝑖𝑡𝑠 = [10 8510 8010 70

    ] 𝑐𝑜𝑠𝑡 = [200 7 0.008180 6.3 0.009140 6.8 0.007

    ]

    Find the optimal dispatch neglecting losses.

    Procedure :

    Create a new file in edit mode by selecting File - New File.

    Browse the components and build the bus sytem

    Execute the program in run mode by selecting tools-opf areas-select opf

    Run the primal lp

    View the results in case information-Generator fuel costs.

    Tabulate the results.

    Power World diagram:

  • GRIET/EEE Power Systems Simulation Lab

    52

    Results:

    Calculations

  • GRIET/EEE Power Systems Simulation Lab

    53

    Result

    Signature of the faculty

  • GRIET/EEE Power Systems Simulation Lab

    54

    Exp.No: 10(b) Date:

    OPTIMAL DISPATCH INCLUDING LOSSES

    Aim : To develop a program for solving economic dispatch problem including transmission losses for a given load condition using direct method and Lambda-iteration method.

    Apparatus: MATLAB

    Theory : When the transmission losses are included in the economic dispatch problem, we

    can modify (5.4) as

    LOSSNT PPPPP 21

    where PLOSS is the total line loss. Since PT is assumed to be constant, we have

    LOSSN dPdPdPdP 210

    In the above equation dPLOSS includes the power loss due to every generator, i.e.,

    N

    N

    LOSSLOSSLOSSLOSS dP

    P

    PdP

    P

    PdP

    P

    PdP

    2

    2

    1

    1

    Also minimum generation cost implies dfT = 0 as given Multiplying by and combing we get

    N

    N

    LOSSLOSSLOSS dPP

    PdP

    P

    PdP

    P

    P

    2

    2

    1

    1

    0

    Adding with we obtain

    N

    i

    i

    i

    LOSS

    i

    T dPP

    P

    P

    f

    1

    0

    The above equation satisfies when

    NiP

    P

    P

    f

    i

    LOSS

    i

    T ,,1,0

    Again since

    NiP

    df

    P

    f

    i

    T

    i

    T ,,1,

  • GRIET/EEE Power Systems Simulation Lab

    55

    we get NN

    N

    i

    LdP

    dfL

    dP

    dfL

    dP

    df 2

    2

    21

    1

    where Li is called the penalty factor of load-i and is given by

    NiPP

    LiLOSS

    i ,,1,1

    1

    Consider an area with N number of units. The power generated are defined by the vector

    TNPPPP 21

    Then the transmission losses are expressed in general as

    BPPP TLOSS

    where B is a symmetric matrix given by

    NNNN

    N

    N

    BBB

    BBB

    BBB

    B

    21

    22212

    11211

    The elements Bij of the matrix B are called the loss coefficients. These coefficients are not

    constant but vary with plant loading. However for the simplified calculation of the penalty factor

    Li these coefficients are often assumed to be constant.

    Exercise:

  • GRIET/EEE Power Systems Simulation Lab

    56

    𝑀𝑊 𝐿𝑖𝑚𝑖𝑡𝑠 = [10 8510 8010 70

    ] 𝑐𝑜𝑠𝑡 = [200 7 0.008180 6.3 0.009140 6.8 0.007

    ]

    Find the optimal dispatch including losses.

    Procedure :

    Create a new file in edit mode by selecting File - New File.

    Browse the components and build the bus sytem

    Execute the program in run mode by selecting tools-opf areas-select opf

    Run the primal lp

    View the results in case information-Generator fuel costs.

    Tabulate the results.

    Power World Diagram:

  • GRIET/EEE Power Systems Simulation Lab

    57

    Results:

    Result

    Signature of the faculty

  • GRIET/EEE Power Systems Simulation Lab

    58

    Exp.No: 11 Date:

    THREE PHASE SHORT CIRCUIT ANALYSIS OF A

    SYNCHRONOUS MACHINE

    Aim: To Analyze symmetrical fault

    Apparatus: MATLAB

    Theory: The response of the armature current when a three-phase symmetrical short circuit occurs at the terminals of an unloaded synchronous generator.

    It is assumed that there is no dc offset in the armature current. The magnitude of the current

    decreases exponentially from a high initial value. The instantaneous expression for the fault

    current is given by

    where Vt is the magnitude of the terminal voltage, α is its phase angle and

    is the direct axis subtransient reactance

    is the direct axis transient reactance

    is the direct axis synchronous reactance

    with .

    The time constants are

  • GRIET/EEE Power Systems Simulation Lab

    59

    is the direct axis subtransient time constant

    is the direct axis transient time constant

    we have neglected the effect of the armature resistance hence α = π/2. Let us assume that the

    fault occurs at time t = 0. From (6.9) we get the rms value of the current as

    which is called the subtransient fault current. The duration of the subtransient current is

    dictated by the time constant Td . As the time progresses and Td´´< t < Td´ , the first

    exponential term will start decaying and will eventually vanish. However since t is still

    nearly equal to zero, we have the following rms value of the current

    This is called the transient fault current. Now as the time progress further and the second

    exponential term also decays, we get the following rms value of the current for the sinusoidal

    steady state

    In addition to the ac, the fault currents will also contain the dc offset. Note that a symmetrical

    fault occurs when three different phases are in three different locations in the ac cycle.

    Therefore the dc offsets in the three phases are different. The maximum value of the dc offset

    is given by

    where TA is the armature time constant.

    Procedure:

    1. Open Matlab-->Simulink--> File ---> New---> Model

    2. Open Simulink Library and browse the components

    3. Connect the components as per circuit diagram

    4. Set the desired voltage and required frequency

    5. Simulate the circuit using MATLAB

    6. Plot the waveforms

  • GRIET/EEE Power Systems Simulation Lab

    60

    Circuit Diagram:

  • GRIET/EEE Power Systems Simulation Lab

    61

    Graph:

    Calculations:

  • GRIET/EEE Power Systems Simulation Lab

    62

  • GRIET/EEE Power Systems Simulation Lab

    63

    Result

    Signature of the faculty

  • GRIET/EEE Power Systems Simulation Lab

    64

    Exp.No: 12 Date:

    UNSYMMETRICAL FAULT ANALYSIS

    Aim: To analyze unsymmetrical faults like LG,LL,LLG

    Apparatus: MATLAB

    Theory:

    Single Line-to-Ground Fault

    The single line-to-ground fault is usually referred as “short circuit” fault and occurs when

    one conductor falls to ground or makes contact with the neutral wire. The general

    representation of a single line-to-ground fault is shown in Figure 3.10 where F is the fault

    point with impedances Zf. Figure 3.11 shows the sequences network diagram. Phase a is

    usually assumed to be the faulted phase, this is for simplicity in the fault analysis calculations.

    [1]

    a

    c

    b

    +

    Vaf

    -

    F

    Iaf Ibf = 0 Icf = 0

    n

    Zf

    F0

    Z0

    N0

    +

    Va0

    -

    Ia0

    F1

    Z1

    N1

    +

    Va1

    -

    Ia1

    +

    1.0

    -

    F2

    Z2

    N2

    +

    Va2

    -

    Ia2

    3Zf

    Iaf

    General representation of a single Sequence network diagram of a

    line-to-ground fault. single line-to-ground fault

    Since the zero-, positive-, and negative-sequence currents are equals as it can be

    observed in Figure 3.11. Therefore,

    0 1 2

    0 1 2

    1.0 0

    3a a a

    f

    I I IZ Z Z Z

  • GRIET/EEE Power Systems Simulation Lab

    65

    With the results obtained for sequence currents, the sequence voltages can be obtained

    from

    0 0

    2

    1 1

    2

    22

    0 1 1 1

    1.0 0 1

    0 1

    a a

    b a

    ac

    V I

    V a a I

    a a IV

    By solving Equation

    0 0 0

    1 1 1

    2 2 2

    1.0

    a a

    a a

    a a

    V Z I

    V Z I

    V Z I

    If the single line-to-ground fault occurs on phase b or c, the voltages can be found by the

    relation that exists to the known phase voltage components,

    0

    2

    1

    2

    2

    1 1 1

    1

    1

    af a

    bf a

    cf a

    V V

    V a a V

    V a a V

    as

    2

    0 1 2

    2

    0 1 2

    bf a a a

    cf a a a

    V V a V aV

    V V aV a V

    Line-to-Line Fault

    A line-to-line fault may take place either on an overhead and/or underground

    transmission system and occurs when two conductors are short-circuited. One of the

    characteristic of this type of fault is that its fault impedance magnitude could vary over a wide

    range making very hard to predict its upper and lower limits. It is when the fault impedance is

    zero that the highest asymmetry at the line-to-line fault occurs

    The general representation of a line-to-line fault is shown in Figure 3.12 where F is the

    fault point with impedances Zf. Figure 3.13 shows the sequences network diagram. Phase b and

    c are usually assumed to be the faulted phases; this is for simplicity in the fault analysis

    calculations [1],

  • GRIET/EEE Power Systems Simulation Lab

    66

    a

    c

    b

    F

    Iaf = 0 Ibf Icf = -Ibf

    Zf

    F0

    Z0

    N0

    +

    Va0 = 0

    -

    Ia0 = 0

    Zf

    F1

    Z1

    N1

    +

    Va1

    -

    Ia1

    F2

    Z2

    N2

    +

    Va2

    -

    Ia2

    +

    1.0 0o

    -

    Sequence network diagram of a line-to-line fault Sequence network diagram of a single

    line-to-line fault.

    It can be noticed that

    0afI

    bf cfI I

    bc f bfV Z I

    And the sequence currents can be obtained as

    0 0aI

    1 2

    1 2

    1.0 0a a

    f

    I IZ Z Z

    If Zf = 0,

    1 2

    1 2

    1.0 0a aI I

    Z Z

    The fault currents for phase b and c can be obtained as

    13 90bf cf aI I I

    The sequence voltages can be found as

    0

    1 1 1

    2 2 2 2 1

    0

    1.0 -

    a

    a a

    a a a

    V

    V Z I

    V Z I Z I

    Finally, the line-to-line voltages for a line-to-line fault can be expressed as

  • GRIET/EEE Power Systems Simulation Lab

    67

    ab af bf

    bc bf cf

    ca cf af

    V V V

    V V V

    V V V

    Double Line-to-Ground Fault

    A double line-to-ground fault represents a serious event that causes a significant

    asymmetry in a three-phase symmetrical system and it may spread into a three-phase fault when

    not clear in appropriate time. The major problem when analyzing this type of fault is the

    assumption of the fault impedance Zf , and the value of the impedance towards the ground Zg.

    The general representation of a double line-to-ground fault is shown in Figure 3.14

    where F is the fault point with impedances Zf and the impedance from line to ground Zg . Figure

    3.15 shows the sequences network diagram. Phase b and c are assumed to be the faulted phases,

    this is for simplicity in the fault analysis calculations.

    a

    c

    b

    F

    Iaf = 0 Ibf Icf

    n

    Zf Zf

    Zg Ibf +Icf

    N

    Zf +3Zg

    F0

    Z0

    N0

    +

    Va0

    -

    Ia0 Zf

    F1

    Z1

    N1

    +

    Va1

    -

    Ia1 Zf

    F2

    Z2

    N2

    +

    Va2

    -

    Ia2

    +

    1.0 0o

    -

    General representation of a Sequence network diagram

    double line-to-ground fault. of a double line-to-ground fault

    It can be observed that

    0

    ( )

    ( )

    af

    bf f g bf g cf

    cf f g cf g bf

    I

    V Z Z I Z I

    V Z Z I Z I

    The positive-sequence currents can be found as

    12 0

    1

    2 0

    1.0 0

    ( )( 3 )( )

    ( ) ( 3 )

    af f g

    f

    f f g

    IZ Z Z Z Z

    Z ZZ Z Z Z Z

    02 1

    2 0

    ( 3 )[ ]( ) ( 3 )

    f ga a

    f f g

    Z Z ZI I

    Z Z Z Z Z

  • GRIET/EEE Power Systems Simulation Lab

    68

    20 1

    2 0

    ( )[ ]( ) ( 3 )

    fa a

    f f g

    Z ZI I

    Z Z Z Z Z

    An alternative method is,

    0 1 2

    0 1 2

    0

    ( )

    af a a a

    a a a

    I I I I

    I I I

    If Zf and Zg are both equal to zero, then the positive-, negative-, and zero-sequences can

    be obtained from

    12 0

    1

    2 0

    1.0 0

    ( )( )( )

    ( )

    aIZ Z

    ZZ Z

    02 1

    2 0

    ( )[ ]( )

    a aZ

    I IZ Z

    20 1

    2 0

    ( )[ ]( )

    a aZ

    I IZ Z

    The current for phase a is

    0afI

    2

    0 1 2

    2

    0 1 2

    bf a a a

    cf a a a

    I I a I aI

    I I aI a I

    The total fault current flowing into the neutral is

    03n a bf cfI I I I

    The resultant phase voltages from the relationship given in Equation 3.78 can be

    expressed as

    0 1 2 13

    0

    af a a a a

    bf cf

    V V V V V

    V V

    And the line-to-line voltages are

    0

    abf af bf af

    bcf bf cf

    caf cf af af

    V V V V

    V V V

    V V V V

  • GRIET/EEE Power Systems Simulation Lab

    69

    Circuit Diagram:

    Procedure:

    1. Open Matlab-->Simulink--> File ---> New---> Model

    2. Open Simulink Library and browse the components

    3. Connect the components as per circuit diagram

    4. Set the desired voltage and required frequency

    5. Simulate the circuit using MATLAB

    6. Plot the waveforms

    Graph:

  • GRIET/EEE Power Systems Simulation Lab

    70

    Calculations:

  • GRIET/EEE Power Systems Simulation Lab

    71

  • GRIET/EEE Power Systems Simulation Lab

    72

    Result

    Signature of the faculty

  • GRIET/EEE Power Systems Simulation Lab

    73

    Exp.No: 13 Date:

    Z-BUS BUILDING ALGORITHM

    Aim: To determine the bus impedance matrix for the given power system network.

    Apparatus: MATLAB

    Theory:

    Formation of Z BUS matrix

    Z-bus matrix is an important matrix used in different kinds of power system study such

    as short circuit study, load flow study etc. In short circuit analysis the generator uses transformer

    impedance must be taken into account. In quality analysis the two-short element are neglected

    by forming the z-bus matrix which is used to compute the voltage distribution factor. This can

    be largely obtained by reversing the y-bus formed by inspection method or by analytical method.

    Taking inverse of the y-bus for large system in time consuming; Moreover modification in the

    system requires whole process to be repeated to reflect the changes in the system. In such cases

    is computed by z-bus building algorithm.

    Algorithm

    Step 1: Read the values such as number of lines, number of buses and line data, generator data

    and transformer data.

    Step 2: Initialize y-bus matrix y-bus[i] [j] =complex.(0.0,0.0)

    Step 3: Compute y-bus matrix by considering only line data.

    Step 4: Modifies the y-bus matrix by adding the transformer and the generator admittance to the

    respective diagonal elements of y-bus matrix.

    Step 5: Compute the z-bus matrix by inverting the modified y-bus matrix.

    Step 6: Check the inversion by multiplying modified y-bus and z-bus matrices to check

    whether the resulting matrix is unit matrix or not.

    Step 7: Print the z-bus matrix.

  • GRIET/EEE Power Systems Simulation Lab

    74

    Procedure:

    Enter the command window of the MATLAB.

    Create a new M – file by selecting File - New – M – File.

    Type and save the program in the editor Window.

    Execute the program by pressing Tools – Run.

    View the results.

    Read the no. Of buses , no of

    lines and line data

    START

    Form Y bus matrix using the algorithm

    Y(i,i) =Y(i,i)+Yseries(l) +0.5Yseries(l)

    Y(j,j) =Y(j,j)+Yseries(l) +0.5Yseries(l)

    Y(i,j) = -Yseries(l)

    Y(j,i) =Y(i,j)

    Modifying the y bus by adding generator

    and transformer admittances to respective

    diagonal elements

    Compute Z bus matrix by inverting

    modified Y bus

    Multiply modified Y bus and Z bus and check

    whether the product is a unity matrix

    Print all the results

    STOP

  • GRIET/EEE Power Systems Simulation Lab

    75

    MATLAB Program: clc

    clear all

    z01 = 0.2j;

    z02 = 0.4j;

    z13 = 0.4j;

    z23 = 0.4j;

    z12 = 0.8j;

    disp('STEP1: Add an element between reference node(0) and node(1)')

    zBus1 = [z01]

    disp('STEP2: Add an element between existing node(1) and new node(2)')

    zBus2 = [zBus1(1,1) zBus1(1,1);

    zBus1(1,1) zBus1(1,1)+z12]

    disp('STEP3: Add an element between existing node(2) and reference node(0)')

    zBus4 = [zBus2(1,1) zBus2(1,2) zBus2(1,2);

    zBus2(2,1) zBus2(2,2) zBus2(2,2);

    zBus2(1,2) zBus2(2,2) zBus2(2,2)+z02]

    disp('Fictitious node(0) can be eliminated')

    zz11 = zBus4(1,1) - ((zBus4(1,3) * zBus4(3,1)) / zBus4(3,3));

    zz12 = zBus4(1,2) - ((zBus4(1,3) * zBus4(3,2)) / zBus4(3,3));

    zz21 = zz12;

    zz22 = zBus4(2,2) - ((zBus4(2,3) * zBus4(3,2)) / zBus4(3,3));

    zBus5 = [zz11 zz12;

    zz21 zz22]

    disp('STEP4: Add an element between existing node(2) and new node(3)')

    zBus6 = [zBus5(1,1) zBus5(1,2) zBus5(1,2);

    zBus5(2,1) zBus5(2,2) zBus5(2,2);

    zBus5(2,1) zBus5(2,2) zBus5(2,2)+z23]

    disp('STEP5: Add an element between existing nodes (3) and (1)')

    zBus7 = [zBus6(1,1) zBus6(1,2) zBus6(1,3) zBus6(1,3)-zBus6(1,1);

    zBus6(2,1) zBus6(2,2) zBus6(2,3) zBus6(2,3)-zBus6(2,1);

    zBus6(3,1) zBus6(3,2) zBus6(3,3) zBus6(3,3)-zBus6(3,1);

    zBus6(3,1)-zBus6(1,1) zBus6(3,2)-zBus6(1,2) zBus6(3,3)-zBus6(1,3) z23+zBus6(1,1)+zBus6(3,3)-

    2*zBus6(1,3)]

    disp('Fictitious node(0) can be eliminated')

    zzz11 = zBus7(1,1) - ((zBus7(1,4) * zBus7(4,1)) / zBus7(4,4));

  • GRIET/EEE Power Systems Simulation Lab

    76

    zzz12 = zBus7(1,2) - ((zBus7(1,4) * zBus7(4,2)) / zBus7(4,4));

    zzz13 = zBus7(1,3) - ((zBus7(1,4) * zBus7(4,3)) / zBus7(4,4));

    zzz21 = zzz12;

    zzz22 = zBus7(2,2) - ((zBus7(2,4) * zBus7(4,2)) / zBus7(4,4));

    zzz23 = zBus7(2,3) - ((zBus7(2,4) * zBus7(4,3)) / zBus7(4,4));

    zzz31 = zzz13;

    zzz32 = zzz23;

    zzz33 = zBus7(3,3) - ((zBus7(3,4) * zBus7(4,3)) / zBus7(4,4));

    disp('RESULT:')

    zBus = [zzz11 zzz12 zzz13;

    zzz21 zzz22 zzz23;

    zzz31 zzz32 zzz33]

    OUTPUT:

    Calculations:

  • GRIET/EEE Power Systems Simulation Lab

    77

    Result:

    Signature of the faculty

  • GRIET/EEE Power Systems Simulation Lab

    78

    Exp.No: 14(a) Date:

    SYMMETRICAL COMPONENTS

    Aim: To obtain symmetrical components of set of unbalanced currents

    Apparatus: MATLAB

    Theory:

    Before we discuss the symmetrical component transformation, let us first define the a-

    operator.

    2

    3

    2

    10120 jea j

    Note that for the above operator the following relations hold

    on so and

    1

    2

    3

    2

    1

    22403606005

    1203604804

    3603

    2402

    000

    000

    0

    0

    aeeea

    aeeea

    ea

    ajea

    jjj

    jjj

    j

    j

    Also note that we have

    02

    3

    2

    1

    2

    3

    2

    111 2 jjaa

    Using the a-operator we can write from Fig. 7.1 (b)

    111

    2

    1 and acab aVVVaV

    Similarly

    2

    2

    222 and acab VaVaVV

    Finally

    000 cba VVV

    The symmetrical component transformation matrix is then given by

  • GRIET/EEE Power Systems Simulation Lab

    79

    c

    b

    a

    a

    a

    a

    V

    V

    V

    aa

    aa

    V

    V

    V

    2

    2

    2

    1

    0

    1

    1

    111

    3

    1

    Defining the vectors Va012 and Vabc as

    c

    b

    a

    abc

    a

    a

    a

    a

    V

    V

    V

    V

    V

    V

    V

    V ,

    2

    1

    0

    012

    Program:

    V012 = [0.6 90

    1.0 30

    0.8 -30];

    rankV012=length(V012(1,:));

    if rankV012 == 2

    mag= V012(:,1); ang=pi/180*V012(:,2);

    V012r=mag.*(cos(ang)+j*sin(ang));

    elseif rankV012 ==1

    V012r=V012;

    else

    fprintf('\n Symmetrical components must be expressed in a one column array in

    rectangular complex form \n')

    fprintf(' or in a two column array in polar form, with 1st column magnitude & 2nd column

    \n')

    fprintf(' phase angle in degree. \n')

    return, end

    a=cos(2*pi/3)+j*sin(2*pi/3);

    A = [1 1 1; 1 a^2 a; 1 a a^2];

    Vabc= A*V012r

    Vabcp= [abs(Vabc) 180/pi*angle(Vabc)];

    fprintf(' \n Unbalanced phasors \n')

    fprintf(' Magnitude Angle Deg.\n')

    disp(Vabcp)

    Vabc0=V012r(1)*[1; 1; 1];

    Vabc1=V012r(2)*[1; a^2; a];

    Vabc2=V012r(3)*[1; a; a^2];

  • GRIET/EEE Power Systems Simulation Lab

    80

    Procedure:

    1. Open Matlab--> File ---> New---> Script

    2. Write the program

    3. Enter F5 to run the program

    4. Observe the results in MATLAB command window.

    Result:

    Vabc =

    1.5588 + 0.7000i

    -0.0000 + 0.4000i

    -1.5588 + 0.7000i

    Unbalanced phasors

    Magnitude Angle Deg.

    1.7088 24.1825

    0.4000 90.0000

    1.7088 155.8175

  • GRIET/EEE Power Systems Simulation Lab

    81

    Result

    Signature of the faculty

  • GRIET/EEE Power Systems Simulation Lab

    82

    Exp.No: 14(b) Date:

    UNBALANCED VOLTAGES FROM SYMMETRICAL

    COMPONENTS

    Aim: To obtain the original unbalanced phase voltages from symmetrical components

    Apparatus: MATLAB

    Theory:

    abca CVV 012

    where C is the symmetrical component transformation matrix and is given by

    aa

    aaC2

    2

    1

    1

    111

    3

    1

    The original phasor components can also be obtained from the inverse symmetrical

    component transformation, i.e.,

    012

    1

    aabc VCV

    Inverting the matrix C we get

    2

    1

    0

    1

    2

    1

    0

    2

    2

    1

    1

    111

    a

    a

    a

    a

    a

    a

    c

    b

    a

    V

    V

    V

    C

    V

    V

    V

    aa

    aa

    V

    V

    V

    210 aaaa VVVV

    21021

    2

    0 bbbaaab VVVaVVaVV

    2102

    2

    10 cccaaac VVVVaaVVV

    Finally, if we define a set of unbalanced current phasors as Iabc and their symmetrical

    components as Ia012, we can then define

    012

    1

    012

    aabc

    abca

    ICI

    CII

  • GRIET/EEE Power Systems Simulation Lab

    83

    Program:

    Iabc = [1.6 25

    1.0 180

    0.9 132];

    rankIabc=length(Iabc(1,:));

    if rankIabc == 2

    mag= Iabc(:,1); ang=pi/180*Iabc(:,2);

    Iabcr=mag.*(cos(ang)+j*sin(ang));

    elseif rankIabc ==1

    Iabcr=Iabc;

    else

    fprintf('\n Three phasors must be expressed in a one column array in rectangular complex

    form \n')

    fprintf(' or in a two column array in polar form, with 1st column magnitude & 2nd column

    \n')

    fprintf(' phase angle in degree. \n')

    return, end

    a=cos(2*pi/3)+j*sin(2*pi/3);

    A = [1 1 1; 1 a^2 a; 1 a a^2];

    I012=inv(A)*Iabcr;

    symcomp= I012

    I012p = [abs(I012) 180/pi*angle(I012)];

    fprintf(' \n Symmetrical components \n')

    fprintf(' Magnitude Angle Deg.\n')

    disp(I012p)

    Iabc0=I012(1)*[1; 1; 1];

    Iabc1=I012(2)*[1; a^2; a];

    Iabc2=I012(3)*[1; a; a^2];

    Result:

    symcomp =

    -0.0507 + 0.4483i

    0.9435 - 0.0009i

    0.5573 + 0.2288i

    Symmetrical components

    Magnitude Angle Deg.

    0.4512 96.4529

    0.9435 -0.0550

    0.6024 22.3157

  • GRIET/EEE Power Systems Simulation Lab

    84

    Result

    Signature of the faculty

  • GRIET/EEE Power Systems Simulation Lab

    85

    Exp.No: 15 Date:

    SHORT CIRCUIT ANALYSIS OF IEEE 9 BUS SYSTEM

    Aim: To obtain the short circuit analysis for a IEEE 9 bus system

    Apparatus: POWERWORLD

    Theory:

    ff IZV 44

    3,2,1,44

    44 iV

    Z

    ZIZV f

    ifii

    We further assume that the system is unloaded before the fault occurs and that the magnitude

    and phase angles of all the generator internal emfs are the same. Then there will be no current

    circulating anywhere in the network and the bus voltages of all the nodes before the fault will

    be same and equal to Vf. Then the new altered bus voltages due to the fault will be given from

    by

    4,,1,144

    4

    iV

    Z

    ZVVV f

    iifi

    IEEE 9 bus system :

    Sbase = 100 MVA . Vbase = 220KV

    Vmax = 1.06 p.u Vmin = 1 p.u

    NUMBER OF LINES = 8 NUMBER OF BUSES = 9

  • GRIET/EEE Power Systems Simulation Lab

    86

    Case Data

    Bus Records

    Bus No Area PU Volt Volt (kV) Ang(Deg)

    Load

    MW

    Load

    Mvar Gen MW Gen Mvar

    1 1 1 345 0 0 0

    2 1 1 345 0 163 0

    3 1 1 345 0 85 0

    4 1 1 345 0

    5 1 1 345 0 90 30

    6 1 1 345 0

    7 1 1 345 0 100 35

    8 1 1 345 0

    9 1 1 345 0 125 50

    Line Records

    Generator Data

    Generator Cost Data

    Number

    Gen

    MW IOA IOB IOC IOD

    Min

    MW

    Max

    MW Cost $/Hr IC LossSens Lambda

    1 0 150 5 0.11 0 10 250 150 5 0 5

    From To Xfrmr R X C

    Lt A

    MVA

    LtB

    MVA

    Lt C

    MVA

    1 4 No 0 0.0576 0 250 250 250

    8 2 No 0 0.0625 0 250 250 250

    3 6 No 0 0.0586 0 300 300 300

    4 5 No 0.017 0.092 0.158 250 250 250

    9 4 No 0.01 0.085 0.176 250 250 250

    5 6 No 0.039 0.17 0.358 150 150 150

    6 7 No 0.0119 0.1008 0.209 150 150 150

    7 8 No 0.0085 0.072 0.149 250 250 250

    8 9 No 0.032 0.161 0.306 250 250 250

    Number Gen MW Gen Mvar Min MW Max MW Min Mvar

    Max

    Mvar

    Cost

    Model Part. Fact

    1 0 0 10 250 -300 300 Cubic 10

    2 163 0 10 300 -300 300 Cubic 10

    3 85 0 10 270 -300 300 Cubic 10

  • GRIET/EEE Power Systems Simulation Lab

    87

    2 163 600 1.2 0.085 0 10 300 3053.97 28.91 0 28.91

    3 85 335 1 0.1225 0 10 270 1305.06 21.83 0 21.83

    Procedure :

    Create a new file in edit mode by selecting File - New File.

    Browse the components and build the bus sytem

    Execute the program in run mode by selecting tools-fault analysis

    Select the fault on which bus and calculate

    Tabulate the results.

    Results

    Fault current =

    Fault current angle =

  • GRIET/EEE Power Systems Simulation Lab

    88

    Result

    Signature of the faculty

  • GRIET/EEE Power Systems Simulation Lab

    89

    Exp.No: 16 Date:

    POWER FLOW ANALYSIS OF SLACK BUS CONNECTED TO DIFFERENT LOADS

    Aim: To perform power flow analysis of a slack bus connected to different loads.

    Apparatus: MATLAB-PSAT

    Theory:

    Slack Bus: To calculate the angles θi (as discussed above), a reference angle (θi = 0) needs to

    be specified so that all the other bus voltage angles are calculated with respect to this reference

    angle. Moreover, physically, total power supplied by all the generation must be equal to the sum

    of total load in the system and system power loss. However, as the system loss cannot be

    computed before the load flow problem is solved, the real power output of all the generators in

    the system cannot be pre-specified. There should be at least one generator in the system which

    would supply the loss (plus its share of the loads) and thus for this generator, the real power

    output can’t be pre-specified. However, because of the exciter action, Vi for this generator can

    still be specified. Hence for this generator, Vi and θi(= 0) are specified and the quantities Pi and

    Qi are calculated. This generator bus is designated as the slack bus. Usually, the largest generator

    in the system is designated as the slack bus.

    In the General Load Flow Problem the Bus with largest generating capacity is taken as the Slack

    Bus or Swing Bus. The Slack Bus Voltage is taken to be 1.0 + j 0 P.U. and should be capable of

    supplying total Losses in the System. But usually the generator bus are only having station

    auxiliary which may be only up to 3% of total generation . If the Generation at Slack Bus is

    more it can take more load connected to the slack bus.

    A slack bus is usually a generator bus with a large real and reactive power output. It is assumed

    that its real and reactive power outputs are big enough that they can be adjusted as required in

    order to balance the power in the whole system so that the power flow can be solved. A slack

    bus can have load on it because in real systems it is actually the bus of a power plant, which can

    have its own load. It also takes care of the Line losses

  • GRIET/EEE Power Systems Simulation Lab

    90

    Circuit Diagram:

  • GRIET/EEE Power Systems Simulation Lab

    91

    Procedure :

    Create a new file in MATLAB-PSAT

    Browse the components in the library and build the bus system.

    Save the file and upload the data file in PSAT main window

    Execute the program and run powerflow

    Get the network visualization.

  • GRIET/EEE Power Systems Simulation Lab

    92

  • GRIET/EEE Power Systems Simulation Lab

    93

    Result:

    Signature of the faculty

  • GRIET/EEE Power Systems Simulation Lab

    94

    Exp.No:17 Date:

    LOAD FLOW ANALYSIS OF 3 MOTOR SYSTEMS CONNECTED TO SLACK BUS

    Aim: To perform load flow analysis of 3 motor systems connected to slack bus

    Apparatus: MATLAB-PSAT

    Theory:

    Slack Bus: To calculate the angles θi (as discussed above), a reference angle (θi = 0) needs to be

    specified so that all the other bus voltage angles are calculated with respect to this reference angle.

    Moreover, physically, total power supplied by all the generation must be equal to the sum of total

    load in the system and system power loss. However, as the system loss cannot be computed before

    the load flow problem is solved, the real power output of all the generators in the system cannot

    be pre-specified. There should be at least one generator in the system which would supply the

    loss (plus its share of the loads) and thus for this generator, the real power output can’t be pre-

    specified. However, because of the exciter action, Vi for this generator can still be specified.

    Hence for this generator, Vi and θi(= 0) are specified and the quantities Pi and Qi are calculated.

    This generator bus is designated as the slack bus. Usually, the largest generator in the system is

    designated as the slack bus.

    In the General Load Flow Problem the Bus with largest generating capacity is taken as the Slack

    Bus or Swing Bus. The Slack Bus Voltage is taken to be 1.0 + j 0 P.U. and should be capable of

    supplying total Losses in the System. But usually the generator bus are only having station

    auxiliary which may be only up to 3% of total generation . If the Generation at Slack Bus is more

    it can take more load connected to the slack bus.

    A slack bus is usually a generator bus with a large real and reactive power output. It is assumed

    that its real and reactive power outputs are big enough that they can be adjusted as required in

    order to balance the power in the whole system so that the power flow can be solved. A slack bus

    can have load on it because in real systems it is actually the bus of a power plant, which can have

    its own load. It also takes care of the Line losses

  • GRIET/EEE Power Systems Simulation Lab

    95

    Circuit Diagram:

    Procedure :

    Create a new file in MATLAB-PSAT

    Browse the components in the library and build the bus system.

    Save the file and upload the data file in PSAT main window

    Execute the program and run powerflow

    Get the network visualization.

  • GRIET/EEE Power Systems Simulation Lab

    96

  • GRIET/EEE Power Systems Simulation Lab

    97

    RESULT:

    Signature of the faculty