GIC research in Finland and Europe Risto Pirjola Finnish Meteorological Institute, Helsinki, Finland Space Weather & EU-FP7 Meeting Paris, January 23, 2007

GIC research in Finland and Europe Risto Pirjola Finnish Meteorological Institute, Helsinki, Finland Space Weather & EU-FP7 Meeting Paris, January 23,

Embed Size (px)

Citation preview

Page 1: GIC research in Finland and Europe Risto Pirjola Finnish Meteorological Institute, Helsinki, Finland Space Weather & EU-FP7 Meeting Paris, January 23,

GIC research in Finland and Europe

Risto Pirjola

Finnish Meteorological Institute, Helsinki, Finland

Space Weather & EU-FP7 MeetingParis, January 23, 2007

Page 2: GIC research in Finland and Europe Risto Pirjola Finnish Meteorological Institute, Helsinki, Finland Space Weather & EU-FP7 Meeting Paris, January 23,

in

-electric power transmission systems

-oil and gas pipelines

-telecommunication cables

-railway equipment

-in principle all long conductors

Ground Effects of Space Weather

=

Geomagnetically Induced Currents (GIC)

Page 3: GIC research in Finland and Europe Risto Pirjola Finnish Meteorological Institute, Helsinki, Finland Space Weather & EU-FP7 Meeting Paris, January 23,
Page 4: GIC research in Finland and Europe Risto Pirjola Finnish Meteorological Institute, Helsinki, Finland Space Weather & EU-FP7 Meeting Paris, January 23,

Effects of GIC on power systems-depend much on technological details of the grid, on

transformer types, etc-experiences in one country cannot directly be extrapolated

to another• Possible GIC problems are due

to saturation of transformers, which may lead to:

• Production of harmonics

• Relay trippings

• Increased reactive power demands

• Voltage fluctuations

• Unbalanced network, even a collapse

• Magnetic stray fluxes in transformers

• Hot spots in transformers, even permanent damage

Page 5: GIC research in Finland and Europe Risto Pirjola Finnish Meteorological Institute, Helsinki, Finland Space Weather & EU-FP7 Meeting Paris, January 23,

Québec blackout -- March 13, 1989

• Harmonics (created by transformer saturation due to GIC) caused, by a “domino effect”, a collapse of the whole system in about one and a half minutes.

• Six million people were without electricity for several hours.• Total costs 13.2 MCAD--------------------------------------------------------------Malmö blackout -- October 30, 2003

• About 50000 customers were without electricity in Malmö, southern Sweden, for 20-50 minutes.

• The first (and so far only?) known power grid blackout due to GIC in Europe

• An overcurrent relay was too sensitive to the third harmonic of 50 Hz. It has been replaced by a less sensitive relay later.

Page 6: GIC research in Finland and Europe Risto Pirjola Finnish Meteorological Institute, Helsinki, Finland Space Weather & EU-FP7 Meeting Paris, January 23,
Page 7: GIC research in Finland and Europe Risto Pirjola Finnish Meteorological Institute, Helsinki, Finland Space Weather & EU-FP7 Meeting Paris, January 23,

GIC research in Finland

High-Voltage (400 & 220 kV) power system

• Collaboration between FMI and the Fingrid Oyj power company• Started in 1976• GIC recordings in earthing leads of 400 kV transformer neutrals

since 1977 (Fingrid, FMI)- At present at three sites- Also a one-year campaign of GIC recordings in a 400 kV line in

the 1990’s• Theoretical modelling of geoelectric fields and GIC (FMI)• Several statistical studies of GIC occurrence based on model

calculations, geomagnetic data and GIC recordings (FMI)• Tests of the effects of dc currents injected into transformers

(Fingrid)

Page 8: GIC research in Finland and Europe Risto Pirjola Finnish Meteorological Institute, Helsinki, Finland Space Weather & EU-FP7 Meeting Paris, January 23,

GIC research in FinlandHigh-Voltage (400 & 220 kV) power system (continues)

• Conclusions:- GIC are a potential risk in Finland due to the high-latitude location,

so contacts between Fingrid and FMI continue.- Largest measured GIC = 201 A (March 24, 1991); only 42 A on

October 30, 2003- Only one GIC disturbance so far: A protective relay caused an

unwanted tripping in northern Finland in January 2005 because the relay had been configured erroneously.

- The resistances provided by neutral point reactors efficiently reduce GIC.

- Series capacitors block the flow of GIC.- The transformer structures and design specifications efficiently

prevent overheating and gassing problems.- The Swedish high-voltage system is clearly more sensitive to GIC, so

FMI and IRF continue research together with Swedish power industry.

Page 9: GIC research in Finland and Europe Risto Pirjola Finnish Meteorological Institute, Helsinki, Finland Space Weather & EU-FP7 Meeting Paris, January 23,
Page 10: GIC research in Finland and Europe Risto Pirjola Finnish Meteorological Institute, Helsinki, Finland Space Weather & EU-FP7 Meeting Paris, January 23,

GIC research in Finland

Natural gas pipeline

• Collaboration between FMI and the Gasum Oy pipeline company• Started in 1981• Theoretical modelling of geoelectric fields, GIC and pipe-to-soil

voltages (FMI)• Statistical studies of GIC occurrence based on model calculations

and geomagnetic data (FMI)• Pipe-to-soil voltage monitoring at several sites (Gasum)• Recording of GIC at one site since 1998 (FMI)• Web-based service “GICNow!” developed for Gasum in the ESA

Space Weather Applications Pilot Project in 2003 to 2005 (FMI)

Page 11: GIC research in Finland and Europe Risto Pirjola Finnish Meteorological Institute, Helsinki, Finland Space Weather & EU-FP7 Meeting Paris, January 23,
Page 12: GIC research in Finland and Europe Risto Pirjola Finnish Meteorological Institute, Helsinki, Finland Space Weather & EU-FP7 Meeting Paris, January 23,

Facts to be remembered in the estimation of GIC risks in the European high-voltage power system

• The society is more and more dependent on reliable power supply.• Electric energy is much transported from one country to another.• A local disturbance in the power grid may propagate as a “domino effect”

to other parts of the network, possibly resulting in a collapse of the whole system.

• The blackout in central Europe in November 2006 was a good example though not caused by GIC.

• On the other hand, GIC may also impact many sites simultaneously.• Use of higher voltages implies smaller line resistances and larger GIC.• Longer transmission lines imply larger induced geovoltages.• GIC magnitudes do not only depend on the latitude but power system

configuration details also affect.• Problems caused by GIC depend on transformer types and other

technological matters, so power engineering expertise is needed.• The next sunspot maximum approaches.

Page 13: GIC research in Finland and Europe Risto Pirjola Finnish Meteorological Institute, Helsinki, Finland Space Weather & EU-FP7 Meeting Paris, January 23,

EU FP6 STREP Pre-Proposal (GREPON) in 2004

– NEST INSIGHT area; Call: FP6-2003-NEST-B-3 closed on September 15, 2004

– Title: “Geomagnetically Induced Currents (GIC) Risk in the European Power Network” (GREPON)

– Duration 24 months (about July 2005 to June 2007)– Budget 1600 kEuros (request from EU 800 kEuros)– 8 consortium partners (with 150 man-months):• FMI, Finland• BGS-Edinburgh, UK• LPCE/CNRS-Orleans, France• DMI, Denmark• IRF-Lund, Sweden• Natural Resources Canada• University of Sheffield, UK• Power industry [ANF Energy Solutions (Canada), RTE/EDF (France)]

Page 14: GIC research in Finland and Europe Risto Pirjola Finnish Meteorological Institute, Helsinki, Finland Space Weather & EU-FP7 Meeting Paris, January 23,

GREPON evaluation on December 23, 2004

• Relevance to the objectives of the programme = 4.0 (threshold = 4) • Scientific and technological excellence = 3.2 (threshold = 4)

• Potential impact = 2.5 (threshold = 3)

“The panel considers that GREPON addresses a true risk to society which is relevant to INSIGHT but of moderate novelty and impact.”

“The panel considers that the potential impact of the proposed work is limited since the frequency of GIC storms and the breakdowns of electrical power networks is quite low.”

“More integrated power networks might not increase the risk because a more integrated network has also more connecting nodes that receive energy from other plants.”

“The panel has therefore decided to recommend that the proposal should not be retained for the second stage evaluation.”

Page 15: GIC research in Finland and Europe Risto Pirjola Finnish Meteorological Institute, Helsinki, Finland Space Weather & EU-FP7 Meeting Paris, January 23,

EU FP6 STREP Pre-Proposal (GREPON-2) in 2005

– NEST INSIGHT area; Call: FP6-2004-NEST-C-1 closed on April 13, 2005

– Title: “Geomagnetically Induced Currents (GIC) Risk in the European Power Network” (GREPON-2)

– Duration 24 months (about July 2006 to June 2008)– Budget 1860 kEuros (request from EU 960 kEuros)– 8 consortium partners (with 186 man-months):• FMI, Finland• LPCE/CNRS-Orleans, France [+ NRCan (Canada), CETP (France)]• IRF-Lund, Sweden• DMI, Denmark• BGS-Edinburgh, UK• University of Sheffield, UK [+ ANF Energy Solutions (Canada)]• RTE/EDF power company, France• NGT power company, UK

Page 16: GIC research in Finland and Europe Risto Pirjola Finnish Meteorological Institute, Helsinki, Finland Space Weather & EU-FP7 Meeting Paris, January 23,

GREPON-2 evaluation on July 18, 2005

• Relevance to the objectives of the programme = 3.5 (threshold = 4;

GREPON 4.0) • Scientific and technological excellence = 3.9 (threshold = 4;

GREPON 3.2)

• Potential impact = 3.0 (threshold = 3; GREPON 2.5))

“The panel considers that the phenomenon addressed is not really that new and does not seem to be of such high concern with a relevant potential for serious problems or risks to European society.”

“The panel has therefore decided to recommend that the proposal should not be retained for the second stage of the evaluation.”

50 pre-proposals out of 330 were accepted for the second stage.

Page 17: GIC research in Finland and Europe Risto Pirjola Finnish Meteorological Institute, Helsinki, Finland Space Weather & EU-FP7 Meeting Paris, January 23,

Evaluation summaries of SWEET and SW-RISK

• Relevance: st- 4, sr- 2 (threshold 3/5)

• Potential impact: st- 3, sr- 2 (threshold 3/5)

• S & T excellence: st- 3, sr- 3 (threshold 4/5)

• Quality of the consortium: st- 2, sr- 3 (threshold 3/5)

• Quality of the management: st- 2, sr- 3 (threshold 3/5)

• Mobilisation of the resources: st- 3, sr- 2.5 (threshold 3/5)

---------------------------------------------------------------------------------------

===> total: SWEET: 17 (threshold 21/30)

SW-RISK: 15.5 (threshold 21/30)