25
S B GENIEEVO Range Protection and Control Module P5 Unit Protection Cable Feeder with Backup Overcurrent and Earth fault Functional Description Issue A5

GENIEEVO Range - UK Power Networkslibrary.ukpowernetworks.co.uk/library/asset/9831b9a0-5afa-4d0c-a12... · RS485/Modbus serial interface . ... number of operations -cumulative breaking

  • Upload
    buidieu

  • View
    225

  • Download
    1

Embed Size (px)

Citation preview

S

B

GENIEEVO Range Protection and Control Module P5 Unit Protection Cable Feeder with Backup Overcurrent and Earth fault Functional Description Issue A5

Revisions Issue A0 22.02.00 Draft Issue A1 09.03.00 Changed outputs O2 to be tripped on fault & for O12 to be Close

inhibit. Issue A2 19.04.00 Summary page updated, trip circuit supervision added to Output

O13 – changed to common alarm. Issue A3 21.09.00 Changed outputs O12 to be tripped on fault & for O2 to be Close

inhibit. Label (1) – L5 to L9. Summary sheet.

Issue A5

01.04.03

Changed to evo specification. Inclusion of disconnector and Vacuum bottles.

P5 rev A5 Page 2 of 25 2004 Schneider Electric

Abbreviations and Glossary of Terms

P5 rev A5 Page 3 of 25 2004 Schneider Electric

Contents REVISIONS....................................................................................................................................................... 2 CONTENTS ...................................................................................................................................................... 3 GENERAL......................................................................................................................................................... 4 ANSI CODE NUMBERS..................................................................................................................................... 4 CONTROL LOGIC .............................................................................................................................................. 4 PROTECTION SETTINGS.................................................................................................................................... 4 APPLICATION ................................................................................................................................................... 6 INTEGRATION OF UNIT PROTECTION................................................................................................................... 8 OVERCURRENT (ANSI 50/51) .......................................................................................................................... 9 EARTH FAULT (ANSI 50N/51N) ..................................................................................................................... 10 NEGATIVE SEQUENCE / UNBALANCE (ANSI 46)............................................................................................... 11 INPUT/OUTPUT LIST ........................................................................................................................................ 14 MESSAGE LIST............................................................................................................................................... 14 ANNUNCIATION .............................................................................................................................................. 15 TELECONTROL SIGNALS LIST.......................................................................................................................... 16 TELECONTROL COMMANDS LIST ..................................................................................................................... 16 GLOSSARY OF SYMBOLS ................................................................................................................................ 17 LOGIC SCHEME NAVIGATION........................................................................................................................... 17 CIRCUIT BREAKER PROTECTION, MONITOR & CONTROL .................................................................................. 18 PROTECTION FUNCTIONS ............................................................................................................................... 19 CIRCUIT BREAKER TRIP & CLOSE ................................................................................................................... 20 LOGIC DISCRIMINATION .................................................................................................................................. 21 RESETTING OF PROTECTION AND MESSAGES .................................................................................................. 22

Principle.................................................................................................................................................22 TRIP CIRCUIT SUPERVISION............................................................................................................................ 23

Principle.................................................................................................................................................23 Operation...............................................................................................................................................23

INTERTRIP OUTPUT SIGNAL (O14) .................................................................................................................. 24 Principle.................................................................................................................................................24 Operation...............................................................................................................................................24

DISTURBANCE RECORDER.............................................................................................................................. 25 Principle.................................................................................................................................................25 Operation...............................................................................................................................................25

Abbreviations and Glossary of Terms

P5 rev A5 Page 4 of 25 2004 Schneider Electric

General SEPAM1000+ S20 Base unit SEPAM1000+ with Fixed Advanced UMI (4 outputs) Fixed Advanced UMI User Machine Interface integral with the SEPAM1000+ base unit MES114 Additional I/O module (10 Inputs / 4 Outputs)

ANSI Code Numbers

50 Instantaneous overcurrent

51 Time delayed overcurrent

50N Instantaneous earth fault

51N Time delayed earth fault

87F Unit protection (pilot wire differential)

46 Negative sequence overcurrent (unbalance protection)

74 Alarm relay

99 Sepam multifunction protection and control unit

Control Logic

Ixx Sepam input - physical connections to the rear of the unit

Oxx Sepam output - physical connections to the rear of the unit

Lx Sepam Light Emitting Diode (LED) – circuit breaker status indications

TSxx Telecontrol signal bit – used to send alarms and indications from Sepam to a host via the RS485/Modbus serial interface

TCxx Telecontrol command bit – used to send controls to Sepam from a host via the RS485/Modbus serial interface, e.g. open CB, and close CB

Protection Settings

In CT primary rated current

Ib Equipment primary rated current

P5 Summary Sheet

P5 rev A5 Page 5 of 25 2004 Schneider Electric

Unit protected cable feeder with back up overcurrent and earth fault

Optional Control / Diagnosis

Optional control and diagnosis for Sepam 1000+ with MES114 optional I/O module (1)

- intertrip send/receive - trip circuit supervision - logic selectivity - breaker local / remote Indication - external protection trip - remote emergency trip - number of operations - cumulative breaking current

PM600, PM620 or PM650 digital PowerMeter with Modbus communications providing :

- current, voltage, frequency - power, energy, power factor - THD voltage and current per phase - kWh pulse output

See PowerLogic selection guide for further information Interposing trip/close relays Trip/Neutral/Close switch Wired out disconnector status indication

Application This protection and control module is similar to P4 in that it provides a high speed differential protection in interconnected systems using pilot wires between each substation. In addition to the differential protection, backup overcurrent and earth fault is provided by a Sepam 1000+ S20. A typical application is a cable feeder or incomer. Several standard options are available to ensure maximum flexibility and cost effectiveness in meeting the requirements of different systems. Protection 87F Pilot wire unit protection relay, choice of :

- Solkor Rf - MBCI

SEPAM1000+ S20 c/w

- 50/51 3 phase OC – IDMT, DT (4 elements) - 50N/51N EF – IDMT, DT (4 elements) - 46 Unbalance / Negative Sequence OC

Instrumentation SEPAM1000+ S20 UMI displays

- phase current: I1, I2, I3 RMS - residual current Io - average current I1, I2, I3

Network, Switchgear & Self Diagnosis SEPAM1000+ S20 c/w

- tripping current I1, I2, I3, Io - unbalance ratio / negative sequence current - peak demand phase current: IM1, IM2, IM3 - disturbance recording - watchdog - output relay test - output alarm contact, O13

Spring charge motor on/off switch Local/Remote selector switch (1) Note: not all functionality is available simultaneously.

Application

P5 rev A5 Page 6 of 25 2004 Schneider Electric

Application This protection and control module is intended for substation secure feeder and incomer applications with pilot wire differential as the main protection with overcurrent and earth fault protection as the a back-up. It could be used for protection of a incoming cable to a switchboard, as in figure 1.

Figure 1 Single cable unit protection It could also be used in closed ring applications where conventional time graded directional protection is not sufficient, as shown in figure 2.

Figure 2 Closed ring system

Operation Pilot wire differential protection compares currents entering and leaving the protected zone. For faults within the zone it is required to trip the circuit breakers at both ends to isolate the fault. Two unit protection relays are therefore required, one at each end of the feeder. A pair of pilot wires is used to transmit information between the two relays so that each relay is able to compare the current flowing at its respective end with the current at the other. The relays at both ends operate simultaneously, providing rapid fault clearance irrespective of whether the fault current is fed from both ends or just one. Choice of unit protection relay Usually when installing a circuit breaker with unit protection relay on the other end already exists and must be matched. In order to achieve this P5 provides a choice of the most common relays, as below. Reyrolle Solkor R/Rf Alstom MBCI Translay “S”

For detailed information on each relay including settings and technical specifications please consult the manufacturers documentation.

Pilo

t wire

s

50/51

87F

P5

87FP4

Pilo

t wire

s

50/51

87F

P5

87FP4

87FP4

Pilo

t wire

s

50/51

87F

P5

87FP4

87F P4

87F

P4

87F

P4

Pilot wires Pilot wires

Application

P5 rev A5 Page 7 of 25 2004 Schneider Electric

Sepam 1000+ backup overcurrent and earth fault The Genie SEPAM1000+ S20 includes the ‘Fixed Advanced User Machine Interface’ (UMI) which allows: display of measurements + switchgear

diagnosis data, display, clearing and resetting of alarm

messages display and input of protection settings

(multi-level password protected) access and input of relay parameter

settings (multi-level password protected) As a complement to the UMI integral with the unit, the ‘Expert UMI’ is available on a PC screen in the form of the SFT2841 software package and a connection to the RS232 link on the front panel of the SEPAM. The main functions performed by the SFT2841 software: changing of passwords, entry of general parameters (ratings,

integration period,….), entry of protection settings,

changing of program logic assignments,

enabling / disabling of functions,

saving of files & printing of reports

Note 1: Changing of passwords, output configuration and LED indicator assignment is only possible with the SFT2841 software. Note 2: The Sepam 1000+ used on Genie has a standard SFT2841 configuration file which can be supplied upon request.

Protection Functions

P5 rev A5 Page 8 of 25 2004 Schneider Electric

Integration of unit protection The output contact from the chosen unit protection relay is wired to digital input I23 (external protection trip) of the Sepam 1000+ and trips the circuit breaker as shown in logic scheme 1. Once the input has operated, it can be latched if required - breaker closing is then inhibited until it is reset. Reset from lockout can be achieved in several ways:

Manually by pressing the “reset” button on the front of the fixed advanced UMI By sending a remote reset command on the communication link using telecontrol bit TC5 Remotely via RS232 link and SFT2841 software

Manual reset also deletes ALL messages from the Sepam display Other information Remote Indication (Modbus/RS485)

I23 External protection operated

Relay Indication / Operation O1 CB trip command

O12 Tripped on fault indication

Protection Functions

P5 rev A5 Page 9 of 25 2004 Schneider Electric

Overcurrent (ANSI 50/51) SEPAM1000+ S20 provides four independent three-phase overcurrent elements (two of the elements can be used for logic discrimination) for protection against phase-phase faults, with a choice of definite or inverse time characteristics. Resetting of the overcurrent protection (on clearance of fault) can be either instantaneous or definite time with an adjustable delay.

Function Name 1 Description Message2

50/51-1 Group A Overcurrent – logic discrimination3 PHASE FAULT

50/51-1 Group B Overcurrent – time discrimination PHASE FAULT

50/51-2 Group A Overcurrent – logic discrimination3 PHASE FAULT

50/51-2 Group B Overcurrent – time discrimination PHASE FAULT 1. the names of the protection functions correspond to the text used on the fixed advanced UMI and in the SFT2841 software 2. the wording of the messages can be changed (please consult Schneider Electric)

3. depending on parameter setting The protection will trip the CB if the settings are exceeded. Once the protection has timed out, it can be latched if required - breaker closing is then inhibited until it is reset. Reset from lockout can be achieved in several ways:

Manually by pressing the “reset” button on the front of the fixed advanced UMI By sending a remote reset command on the communication link using telecontrol bit TC5 Remotely via RS232 link and SFT2841 software

Manual reset also deletes ALL messages from the Sepam display Setting ranges for Overcurrent elements Characteristic Pick-up current setting range 5 Time delay setting range 6

Definite time 0.3 to 24In Inst.; 50ms to 300s

IDMT 4 0.3 to 2.4In 100ms to 12.5s at 10Is

0.04 to 4.2 tms In : Primary rating of CT 4. IDMT curves according to BS142, IEC 255-4: standard inverse SI, very inverse VI, extremely inverse EI, ultra inverse UI, long time inverse LTI 5. 1A or 1 digit resolution, 5% accuracy 6. Time setting for IDMT can be either in ‘time at 10Is’ or tms format – depending on parameter setting.

Other information Timers

T1 Time delay reset 0; 0.05 to 300s (definite time)

Remote Indication (Modbus/RS485)

TS1 – 4 Overcurrent protection operated (4 elements)

Remote Control

TC1 Trip

TC2 Close

Disturbance Recorder

TS44 Disturbance recording record stored

Relay Indication / Operation O1 CB trip command

O12 Tripped on fault indication

Protection Functions

P5 rev A5 Page 10 of 25 2004 Schneider Electric

Earth Fault (ANSI 50N/51N) SEPAM1000+ S20 provides four independent elements (two of the elements can be used for logic discrimination) for protection against earth faults, with a choice of definite or inverse time characteristics. Resetting of the earth fault protection can be either instantaneous or definite time with an adjustable delay.

Function Name 1 Description Message2

50N/51N-1 Group A Earth fault – logic discrimination3 EARTH FAULT

50N/51N-1 Group B Earth fault – time discrimination EARTH FAULT

50N/51N-2 Group A Earth Fault – logic discrimination3 EARTH FAULT

50N/51N-2 Group B Earth Fault – time discrimination EARTH FAULT 1. the names of the protection functions correspond to the text used on the fixed advanced UMI and in the SFT2841 software 2.

the wording of the messages can be changed (please consult Schneider Electric)

3. depending on parameter setting

The protection will trip the CB if the settings are exceeded. Once the protection has timed out, it can be latched if required - breaker closing is then inhibited until it is reset. Reset from lockout can be achieved in several ways: Manually by pressing the “reset” button on the front of the fixed advanced UMI By sending a remote reset command on the communication link using telecontrol bit TC5 Remotely via RS232 link and SFT2841 software Manual reset also deletes ALL messages from the Sepam display Setting ranges for Earth Fault elements Characteristic Pick-up current setting range5 Time delay setting range

Definite time 0.1 to 15Ino Inst; 50ms to 300s

IDMT 4 0.1 to 1Ino 100ms to 12.5s at 10Iso

0.04 to 4.2 tms Note : Residual current is calculated vectorially from phase current CTs Ino : Primary rating of CT 4. IDMT curves according to BS142, IEC 255-4: standard inverse SI, very inverse VI, extremely inverse EI, ultra inverse UI, long time inverse LTI 5. 0.1A or 1 digit resolution, 5% accuracy Other information Timers

T1 Time delay reset 0; 0.05 to 300s (definite time)

Remote Indication (Modbus/RS485)

TS5 – 8 Earth fault protection operated (4 elements)

Remote Control

TC1 Trip

TC2 Close

Disturbance Recorder

TS44 Disturbance recording record stored

Relay Indication / Operation

O1 CB trip command

O12 Tripped on fault indication

Protection Functions

P5 rev A5 Page 11 of 25 2004 Schneider Electric

Negative Sequence / Unbalance (ANSI 46) SEPAM1000+ S20 provides protection against phase unbalance. Phase unbalance results in a negative sequence component in the phase current which can cause unwanted heating in electrical plant. It can be caused by an unbalanced supply, incorrect phase rotation, the loss of a phase, or two phase faults on long feeders. For the latter, it can offer protection against low levels of fault current which will not operate conventional overcurrent protection at sufficient speed to safeguard the system.

Function Name 1 Description Message 2

46 Negative Sequence / Unbalance UNBALANCE

1 the names of the protection function correspond to the text used on the fixed advanced UMI and in the SFT2841 software 2

the wording of the messages can be changed (please consult Schneider Electric).

The protection will pick-up when the negative sequence component of the phase currents is greater than the set point. Once the protection has timed out, it can be latched if required - breaker closing is then inhibited until it is reset. Reset from lockout can be achieved in several ways:

Manually By pressing the “reset” button on the front of the fixed advanced UMI By sending a remote reset command on the communication link using TC5 Remotely via RS232 link and SFT2841 software

Manual reset also deletes ALL messages from the Sepam display Setting range for negative sequence / unbalance element Characteristic Pick-up current setting range Time delay, T

Definite time 10% Ib to 500% Ib 100ms to 300s

IDMT 3 10% Ib to 50% Ib 100ms to 1s (time at 5Ib) Ib : rated primary current of equipment (40% to 130% In, primary rating of CT) 3. the IDMT Tripping curve is shown below and defined according to following equations:

For Is/Ib Ii / Ib 0.5 For 0.5 Ii / Ib 5 For Ii / Ib > 5

T

)Ib/Ii(

19.3t

5.1 T

)Ib/Ii(

64.4t

96.0 Tt

T corresponds to the time delay for Ii / Ib = 5

Is 5Ib Ii

T

t

Protection Functions

P5 rev A5 Page 12 of 25 2004 Schneider Electric

Other information Remote Indication (Modbus/RS485)

TS12 Negative sequence protection operated Remote Control TC1 Trip

TC2 Close

Disturbance Recorder

TS44 Disturbance recording record stored

Relay Indication / Operation O1 CB trip command

O12 Tripped on fault indication

Instrumentation

P5 rev A5 Page 13 of 25 2004 Schneider Electric

Instrumentation Functions The following instrumentation functions are available in the SEPAM1000+ S20.

Function Range Accuracy 2

Ammeter: Phase current I1, I2, I3 RMS

Residual current Io

0.1 to 1.5 In 1

0.1 to 1.5 Ino

Typically 1%

5%

Tripping currents: Phase I1, I2, I3

Earth Io

0.1 to 40 In

0.1 to 20 Ino

5%

5%

Maximum demand current IM1, IM2, IM3 0 to 1.5 In Typically 1%

Average current I1, I2, I3 0 to 1.5 In Typically 1%

Unbalance ratio (negative sequence current) 10 to 500% Ib 2% Ib : rated primary current of equipment (40% to 130% In, primary rating of CT)

In, Ino : Primary rating of CT (1)

Measurement up to 40In with reduced accuracy (2)

Typical accuracy for range specified with nominal values according to IEC 60255-6

Resource Allocation Tables

P5 rev A5 Page 14 of 25 2004 Schneider Electric

Input/output list The following inputs and outputs are configured by the Genie SEPAM1000+ S20.

Board In/Output Details State 1

Base Unit O1 CB Trip contact Trip CB

O2 Close inhibit CB Close inhibited

O3 Logic selectivity - block send Block signal sent

O4 Watchdog3 Relay fault

Mes114 I11 CB open1 & trip circuit supervision CB open

I12 CB closed1 & trip circuit supervision CB closed

I13 Logic selectivity – block receive Blocked

I14 Earth position selected2 In earth position

I21 Intertrip receive1 Intertrip received

I22 Emergency trip1 Tripped

I23 External protection trip1 Tripped

I24 Spare -

I25 Local / Remote selector In local position

I26 Spare -

O11 Close CB Close CB

O12 Tripped on fault Protection tripped

O13 CB fault

trip circuit supervision

CB common alarm active

O14 Intertrip send intertrip

(1) Indication of status inputs is displayed on the LEDs on front of relay UMI. (2) Used for remote indication purposes, this gives position of the disconnector (3) watchdog is normally closed contact.

Message List The following messages are used by the program logic:

Message Type Details Function

PHASE FAULT Steady Overcurrent trip 50/51-1, 50/51-2

EARTH FAULT Steady Earth fault trip 50/51N-1, 50/51N-2

UNBALANCE Steady Negative sequence / unbalance 46

Resource Allocation Tables

P5 rev A5 Page 15 of 25 2004 Schneider Electric

Annunciation The LED’s on the front of the UMI are assigned as follows: Label (1) is for Sepam 1000+ S20 base unit without MES114 I/O module Label (2) is for Sepam 1000+ S20 base unit with MES114 I/O module

LED Label (1) Details Label (2) Details

L1 TRIP Tripped on fault TRIP Tripped on fault

L2 PICKUP Protection pickup PICKUP Protection pickup

L3 O/C 51 Overcurrent trip O/C 51 Overcurrent trip

L4 E/F 51N Earth fault trip E/F 51N Earth fault trip

L5 - - PH UNBAL Negative sequence/

Unbalance trip

L6 - - EXT TRIP External & emergency trip, intertrip receive

L7 - - CB FAULT Circuit breaker alarm

( trip circuit fault)

L8 - - CB ON Circuit breaker On

L9 - - CB OFF Circuit breaker Off

Resource Allocation Tables

P5 rev A5 Page 16 of 25 2004 Schneider Electric

Telecontrol Signals List

Signal Details

TS1 Protection 50/51 relay 1 group A

TS2 Protection 50/51 relay 2 group A

TS3 Protection 50/51 relay 1 group B

TS4 Protection 50/51 relay 2 group B

TS5 Protection 50N/51N relay 1 group A

TS6 Protection 50N/51N relay 2 group A

TS7 Protection 50N/51N relay 1 group B

TS8 Protection 50N/51N relay 2 group B

TS12 Protection 46 (neg. seq. / unbalance)

TS38 Send blocking input

TS39 Remote setting inhibited

TS40 Remote control inhibited

TS41 Sepam not reset after fault

TS42 Remote control / position discrepancy

TS43 Matching fault or trip circuit supervision

TS44 Disturbance recorder record stored

Note: All input status can be accessed remotely.

Telecontrol Commands List

Signal Details

TC1 Trip CB

TC2 Close CB

TC3 Switching to setting group A

TC4 Switching to setting group B

TC5 Sepam reset

TC6 Peak demand current zero reset

TC8 Disable fault recorder triggering

TC9 Enable fault recorder triggering

TC10 Manual disturbance recorder triggering

Control Logic

P5 rev A5 Page 17 of 25 2004 Schneider Electric

Glossary of Symbols

Logic Scheme Navigation

> 1

" OR "

X

Y

Z

S

Ouput S=1 if either inputX, Y or Z=1

Output S=1 if all inputsX, Y and Z=1

&

" AND"

X

Y

Z

S

Output S=1 if only one ofthe inputs X, Y or Z=1

=1

" Exclusive OR "

X

Y

Z

S

complement("NOT")

X S

Ouput S=1 if input X=0

"delay on pick-up"

SX t o

delays the pick-up of anitem for a time T

"delay on drop-off"

SX o t

delays the drop-off of anitem for a time T

Output B is set to 1 if input S=1,output B is reset to 0 when inputR=1. If both input S and input R=1,output B is set to 1

bistable

BS

R

1

0

TX

S

TX

S

prot close inhibit(09:LK3)

go to logic scheme no.9 and LK3

Logic scheme.No. 01

LK3:prot close inhibit01(09:LK3)

logic scheme no.9 link LK3trace back to logic scheme no.01 ref: (09:LK3)

Logic scheme.No. 09

Control Logic

P5 rev A5 Page 18 of 25 2004 Schneider Electric

Circuit Breaker Protection, Monitor & Control

Note : some of the above functionality is optional and requires the MES114 I/O module

L6:EXT TRIP

time delaysettings

for time-baseddiscrimination

* time delaysettings

for logic-baseddiscrimination

**Logic scheme.

No. 01

input I13receiveblocking

overcurrent (51)(time)*

t-d set point Group B

t-d set point Group B

overcurrent (51)(logic)**

t-d set point Group A

t-d set point Group A

> 1

> 1

earth fault (51N)(time)*t-d set point Group B

t-d set point Group B

> 1

> 1

earth fault (51N)(logic)**

t-d set point Group A

t-d set point Group A> 1

&

& > 1

50/51 relay1

group A

50/51 relay2

group A

50/51 relay1

group B

50N/51N relay1

group A

50N/51N relay2

group A

50N/51N relay1

group B

TS850N/51N relay

2group B

TS5

TS6

TS7

Negative sequence / Unbalance(46)

O12

faulttripping

Input I21Intertrip

Input I22emergency trip

Input I23external protection trip

(TC1) open order

O2

inhibitclosing

> 1 > 1O1

tripping

T-200 ms

0 T

> 1

T-200 ms

0 T

&&

Input I25Remote control enable

(TC2) closeorder

Input I12CB closed

&

O11

closeorder

L1: CB Trip

TS250/51 relay

2group B

= PHASE FAULT

L4: E/F 51N

TS1

TS2

TS1

L3: O/C 51

L5:PH UNBAL

Input I26 Spare

&

> 1

overcurrent (50)

inst. set point 1 Group A

inst. set point 2 Group A

earth fault (50N)

inst. set point 1Group A

inst. set point 2 Group A

> 1

> 1

> 1

TS38

O3

transmitblocking

T-200 ms

t o

L2:PICKUP

O13

Circuit breaker fault (trip circuitsupervision)

= EARTH FAULT

= UNBALANCE

Logic discrimination & instanteous Protectionreset

Protection

Circuit breaker trip andclose

&

1

0rese

t

1

0reset

1

0reset

1

0reset

1

0reset

> 11

0reset

1

0reset

1

0reset

1

0reset

> 1

> 1

LK1: trip cctinhibit

(04:LK1)

LK2: trip cct alarm(04:LK2)

Control Logic

P5 rev A5 Page 19 of 25 2004 Schneider Electric

Protection Functions

Principle

The time delayed Overcurrent (51) and Earth fault (51N) protection function groups A and B are split in two, time delay settings for: Time-based discrimination – group B Logic-based discrimination – group A

Circuit breaker protection function Negative sequence / unbalance (46) will initiate circuit breaker tripping order. Output O2 is circuit breaker “Tripped on fault indication” activated when the circuit breaker has tripped on protection function fault, Output O13. Remote indication is provided for Overcurrent (51) and Earth fault (51N) protection operation. Common circuit breaker alarm is available on output O13 when trip circuit supervision activated.

Operation

The circuit breaker will initiate a trip as follows : Protection :

Time-based protection (51, 51N, 46) Logic-based discrimination (see Logic Discrimination)

The LED’s associated with protection trip are :

LED1 – Circuit breaker tripped on fault (protection trip) LED3 – Overcurrent (51) time or logic delayed protection trip operated LED4 – Earth fault (51N) time or logic delayed protection trip operated LED5 – Negative sequence / Unbalance (46) time-delayed protection trip operated LED6 – External protection trip inputs activated (input I21 intertrip receive, input I22

emergency trip or input I23 external protection trip) Remote indications :

TS1 – TS4 Overcurrent (51) relays 1 & 2 group A & B TS5 – TS8 Earth fault (51N) relays 1 & 2 group A & B

Control Logic

P5 rev A5 Page 20 of 25 2004 Schneider Electric

Circuit Breaker Trip & Close

Principle

The circuit breaker can only be tripped if the breaker is closed and in service position. Circuit breaker tripping order is issued via output O1 following initiation of a trip. Timer T provides a tripping order pulse for duration of 200ms. The circuit breaker closing order is issued via output O11. The closing order can only be issued providing no tripping order is currently issued, there is no circuit breaker fault and the circuit breaker is in the open position. Closing order is also issued via remote control close order (TC2). Timer T provides a closing order pulse for duration of 200ms. The reclosing of the circuit breaker is inhibited when output O12 is de-activated following the operation of circuit breaker protection. The reclosing of the circuit breaker is re-enabled once output O12 is activated.

Operation

The circuit breaker is controlled as follows : Tripped by :

protection (50/51, 50/51N, 46) remote control (TC1) external protection device1 Intertrip1 emergency trip push button1

Closed by :

local close switch remote control (TC2)

Close Inhibited by: protection trip circuit breaker open /close status mismatch (trip circuit supervision)

LED’s activated :

LED6 - External protection trip (input I21 intertrip receive, input I22 emergency trip & input I23 external protection trip).

Control Logic

P5 rev A5 Page 21 of 25 2004 Schneider Electric

Logic Discrimination

Principle

Logic discrimination can be used to achieve full tripping discrimination between devices and to reduce the tripping times of circuit breakers located nearest to the source (this is a drawback of time discrimination). It requires the use of pilot wires to transmit a “block” control signal from a downstream relay to an upstream device.

As soon as the downstream relay detects a fault, it closes output contact O3 to send a blocking order to input I13 of the upstream relay. The upstream relay has a short definite time delay, typically 100ms, to ensure that the blocking order can arrive before tripping is initiated. When the blocking order is received, tripping of the overcurrent and earth fault elements assigned for logic discrimination is inhibited. The downstream relay trips after its selected time delay and the block signal to the upstream relay is removed following a further time delay T. This allows the upstream protection to trip if the downstream device fails to clear the fault. As the blocking order only inhibits tripping, the upstream protection can still time out, permitting instantaneous tripping when the blocking order is removed. If the upstream relay does not receive a block, tripping occurs as in a conventional overcurrent protection scheme.

Operation To send a blocking order to an upstream device when a fault is detected

Output O3 ‘logic selectivity – block send’ is activated The overcurrent and earth fault protection trips after the pre-set delay (if a blocking signal is not

received by a downstream device) Following a time delay (which takes account of breaking device operation time and the protection

reset time), O3 is reset and the blocking signal is removed. This allows the upstream device to clear the fault if the downstream device has failed.

“Send blocking input” TS38 remote indication is transmitted To receive a blocking order from a downstream device when a fault is detected

Input I13 “Logic selectivity – block receive” is activated Tripping is inhibited until input I13 resets

I13

O3

I13

O3

Sepam

Sepam

_

+

I13

O3

Sepam

Control Logic

P5 rev A5 Page 22 of 25 2004 Schneider Electric

Resetting of Protection and Messages

Principle Output relay latching may be chosen. Latched tripping orders are stored and must be reset in order for the device to be put back in service. The user can initiate a reset via the integral UMI keypad, remotely via the communication link, or from the SFT2841 software.

Reset> 1

"Reset" key

&Comms reset (TC5)

Input I25Remote control enable

SFT 2841SoftwareReset

Logic scheme.No. 03

Control Logic

P5 rev A5 Page 23 of 25 2004 Schneider Electric

Trip Circuit Supervision

Principle This function is designed to monitor the trip circuit and provide an alarm should a failure occur. Failure could be due to a disconnected wire or the trip coil becoming open circuit. An alarm is also raised if the state of the circuit breaker is indicated as neither open nor closed (both input I11 and input I12 inactive), or simultaneously open and closed (both input I11 and input I12 active). The time delay T prevents false indications due to contact discrepancies that occur during normal CB open and close operations. In order for this function to work properly the circuit breaker tripping circuit must be wired as below.

Operation

When the function detects a fault

Output O13 is activated common CB alarm Closing of the CB is inhibited LED7 is activated Remote indication TS43 is transmitted as an alarm

O1

Sepamoutput

I11

I12

Sepaminput

Sepaminput

tripcoil

52

+ -

&

&

T-200ms

t oinput I11CB open

Logic scheme.No. 04

input I12CB closed

L7:CB fault

trip cct inhibit(01:LK1)

TS43

> 1reset

o

1

trip cct alarm(01:LK2)

Control Logic

P5 rev A5 Page 24 of 25 2004 Schneider Electric

Intertrip Output Signal (O14)

Principle This function is used to intertrip other circuit breakers when a fault is detected. Intertrip output O14 is activated by Overcurrent (51) group B, earth fault (51N) group B, Negative sequence / Unbalance (46) or external protection (input I21 intertrip receive, input I22 emergency trip, input I23 external protection trip).

Operation When this function is activated

Output O14 “Intertrip” is activated No message is displayed

overcurrent (51)(time)*

t-d set point Group B

t-d set point Group B

> 1

> 1

earth fault (51N)(time)*t-d set point Group B

t-d set point Group B

> 1

Input I21Intertrip

Input I22emergency trip

Input I23external protection trip

> 1

O14

intertripsend

> 1Negative sequence overcurrent(46)

Logic scheme.No. 08

Control Logic

P5 rev A5 Page 25 of 25

Disturbance Recorder

Principle This function is used to record analogue signals (current and voltage) and logical states. Storage of the record is initiated by a triggering event. Inputs and protection trips can be specified as triggering events. The stored record begins a set period before the triggering event and continues for a set period afterwards.

The stored record comprises the following information: values sampled from the different signals date characteristic of the recorded channels The files are recorded in FIFO (First In First Out) type shift storage – the oldest record is erased when a new record is triggered

Operation The following logic scheme describes the Disturbance recorder triggering (OPG) :

Overcurrent (51) - group A & BEath fault (51N) - group A & BNegative sequence / Unbalance

> 1

Logic scheme.No. 12

Pick-up

SFT 2841manual trig

> 1

&

&

TC10

TC8

> 1TC9

TC10

tri inhibit

tri inhibit

SFT 2841

SFT 2841

manual trig

SFT 2841

OPG trig

2004 Schneider Electric