For current information and promotional literature refer to: www.genflex.comEPDM Standard Details
GENFLEX EPDM DETAILS
Detail DetailName Page
WALL TERMINATIONSE-1.01 Termination Bar 1E-1.02 Wall Termination with Counter-Flashing 1E-1.03 Common Counter-Flashing & Membrane Securement 2E-1.04 Coping Termination Over Membrane Flashing 2E-1.05 Parapet Wall with Metal Edge 3E-1.07 Masonry or Concrete Parapet Wall with Termination Bar 4E-1.09 Vertical Termination 5E-1.10 Termination Bar at Joint in Precast Concrete Panel 6E-1.11 Reglet-Mounted Counter-Flashing Termination 7E-1.12 Surface-Mounted Counter-Flashing Termination 7BASE FLASHINGE-2.01 Continuous Membrane Base Flashing - Vertically Secured 8E-2.02 Vertically Secured Wall Base Flashing 8E-2.04 Continuous Membrane Base Flashing - Horizontally Secured 9E-2.08 Horizontally Secured Peel & Stick EPDM RPS 9E-2.09 Vertically Secured Peel & Stick EPDM RPS 10E-2.10 Layout for Vertically and Horizontally Secured Peel & Stick EPDM RPS 11
CURB FLASHINGE-3.01 Vertical Seam in Base Flashing Using Cured EPDM 12E-3.02A Intermediate Securement Into Structural Substrate 13E-3.02B Intermediate Securement Into Non-Structural Substrate 14E-3.03 Sloped Wall Transition 15E-3.04 Vertically Secured Curb / Skylight Flashing 15E-3.05 Welded Watertight Curb / Skylight Flashing 16E-3.06 Curb / Skylight / Roof Hatch with Backer Rod Termination 17E-3.08 Horizontally Secured Curb / Skylight Flashing 17E-3.10 Sleeper Curb Assembly 18E-3.11 Gravel Stop to Wall Flashing 19E-3.12 Sleeper Support Assembly 20CORNERE-4.02 Field Fabricated Inside Corner 21E-4.03 Inside Corner with Peel & Stick EPDM Corner 22E-5.02 Field Fabricated Outside Corner 23E-5.03 Outside Corner with Peel & Stick EPDM Corner 23SEAMSE-6.01 Seam Tape Application 24E-6.07 Bar-in-Seam System Seam Tape Application 24E-6.08 FRM In-Seam Systems Seam Tape Application 25E-6.10 T-Joint / Seam Intersection Cover 25E-6.12 Seam Tape End Lap Splice 26PIPE FLASHINGE-7.03 Peel & Stick EPDM Pipe Boot 26E-7.04 Field Fabricated Pipe Flashing 27E-7.06 Field Fabricated Hot Stack Flashing 27DRAINSE-8.01 Roof Drain 28E-8.02 Membrane Securement at Drain with Sump Greater Than or Equal to 2/12 28PITCH POCKETSE-9.01 Pourable Sealer Pocket Formed with Metal 29E-9.02 Watertight Pitch Pan 29E-9.03 EPDM Pipe Boot as a Pourable Sealer Pocket 30E-9.04 Three-Sided Pourable Sealer Pocket 31E-9.05 GenPocket E 32
SCUPPERSE-10.01 Scupper 33E-10.02 Overflow Scupper 34
07/2010
For current information and promotional literature refer to: www.genflex.comEPDM Standard Details
EXPANSION OR CONTROL JOINTSE-11.01 Expansion or Control Joint 35E-11.02 Curb Expansion Joint 35E-11.03 Deck to Deck Sliding Expansion Joint (Ballasted Systems Only) 36E-11.04 Basewall Expansion Joint 36EDGE METALE-14.01 Metal Gravel Stop 37E-14.03 Two Piece Snap on Gravel Stop (Option A) 37E-14.04 Two Piece Snap on Gravel Stop (Option B) 38E-14.05 Gutter With Flange 38E-14.06 Slotted Drain Bar 39E-14.08 Edge Termination 39E-14.09 Gravel Stop / Edging Lap Joint 40E-14.10 Gravel Stop with Face Plate 41E-14.11 Two-Piece Snap-On Gravel Stop with Peel & Stick EPDM RPS 42E-14.12 GenFlex Fascia Edge Metal 43E-14.13 GF One Edge Metal Installation 44COVER TAPEE-15.01 Cover Tape Application 44E-15.05 Cover Tape Over Field Seam Intersection 45E-15.06 Cover Tape End Lap Splice 45WALKWAYS & PIPE SUPPORTE-16.02 Concrete Walkway 46E-16.03 Pipe Support 46E-16.05 FlexGuard Peel & Stick Walkway Pad Installation 47CAULKE-17.01 High Profile Edge Caulk 48TIE-INSE-18.01 Tie-In to Existing EPDM System 48E-18.02 Curb Tie-In 49E-18.03 Tie-In to BUR with Pourable Sealer 50E-18.04 Tie-In to BUR with Cold Process or Asphalt 51MISCELLANEOUSE-19.01 Lightning Rod 52E-19.02 Lightning Rod 52E-19.03 Temporary Night Seal 53E-19.04 Grease Vent 53
Supplemental Details (These are also in the application sections for the appropriate system.)N/A Table: Insulation Attachment for Fully Adhered Systems 54ISP 1-4 Insulation Securement Patterns 1-4 55ISP 5-8 Insulation Securement Patterns 5-8 56E-1.03-4-5 Ballasted System Cross Sections 57E-11.06 Fully Adhered System Cross Section 58E-11.07 Fully Adhered System Insulation Securement 58E-25.01 & 26.01 Bar-In-Seam System Insulation Cross Section 59E-26.06 & 26.07 Bar-In-Seam Insulation Securement 59E-25.02 & 26.02 Bar-In-Seam System Perimeter Layout Patterns 60E-22.04 & 27.01 Bar Cover Tape System Insulation Cross Section 61E-27.05 & 27.06 Bar Cover Tape Insulation Securement 61E-22.05 & 27.02 Bar Cover Tape System Perimeter Layout Patterns 62E-70.01 FRM System Perimeter Layout Pattern 63E-71.00 FRM System Insulation Cross Section 63E-71.03 & 71.05 FRM System Insulation Securement 64EMR-1.13 Metal Roof to Metal Siding - Vertical Termination and Counter-Flashing 65EMR-2.08A Metal Roof Base Flashing 66EMR-2.08B Metal Roof to Vertical Siding Base Flashing 67EMR-11.06 Fully Adhered Metal Recover System Insulation Cross Section 68EMR-11.07 Fully Adhered Metal Recover System Insulation Securement 68EMR-14.01 Metal Edge Flashing 69FW-6.10 T-Joint / Seam Intersection Cover 70FW-16.05 Installation of Walkway Pad 70
For current information and promotional literature refer to: www.genflex.com 111EPDM Standard Details
GenFlex Termination Caulk
GenFlex Water StopSee Note #1
GenFlex Fasteners On Reroof Projects 8" (203.2 mm) o.c.On New Construction 12" (304.8 mm) o.c.With Neoprene/Metal Washer or CaulkSee Note #4
1.
2.
GenFlex Bonding Adhesive See Note #3
GenFlex Termination Bar
GenFlex Cured EPDM MembraneSee Note #2
EPDM Systems07/10
Termination Bar Detail #: E-1.01
Compression fit details that incorporate GenFlex Water Stop must have all existing flashing removed to the bare substrate, e.g. masonry block.When cured flashing is used on wall or curb flashing, vertical seams must be stripped-in at the base of angle change with 6" (152.4 mm) strip of EPDM Flashing, or 7" (177.8 mm) Peel & Stick EPDM Flashing. See Detail E-3.01.All parapet walls and roof curbs must be suitable for flashing, i.e. clean, tight, smooth, no cracks, etc.
4.
3.
Any approved pre-drilled fastener for curb and parapet terminations must have a minimum 125 lb (556.0 N) pullout. See approved fastener list. GenFlex
EPDM Systems
07/10
Wall Termination withCounter-Flashing Detail #: E-1.02
GenFlex Water StopSee Note #1
GenFlex Bonding AdhesiveSee Note #5
GenFast Bar Anchorwith Approved Fasteners12" (304.8 mm) o.c.See Note #3 GenFlex Cured EPDM Membrane
See Note #4
New or Existing Metal Counter-FlashingSee Note #2
1.
2.
3.
4.
5.
Compression fit details that incorporate GenFlex Water Stop must have all existing flashing removed to the bare substrate, e.g. masonry block.Metal coping cap, expansion joint, and edge details are typical only. All metalwork should be installed to sheet metal codes (SMACNA). Clean all metal prior to installation of GenFlex materials.Polymer batten strips cannot be used for attachments into masonry wall substrates. Use only on smooth surfaces, e.g. wood or insulation.When cured flashing is used on wall or curb flashing, vertical seams must be stripped-in at the base of angle change with 6" (152.4 mm) strip of EPDM Flashing, or 7" (177.8 mm) Peel & Stick EPDM Flashing. See Detail E-3.01.All parapet walls and roof curbs must be suitable for flashing, i.e. clean, tight, smooth, no cracks, etc.
3" (76.2 mm) Minimum
GenFlex
For current information and promotional literature refer to: www.genflex.com222EPDM Standard Details
EPDM Systems07/10
Coping TerminationOver Membrane Flashing Detail #: E-1.04
GenFlex EPDM Membrane See Note #4
Continuous Metal Cleat
GenFlex Bonding AdhesiveSee Note #3
Wood Nailer - See Note #2
Metal Coping - See Note #1
For Interior Securement OnlyApproved Fasteners Spaced 12" (304.8 mm) o.c. with Neoprene Washeror Sealed with Caulk
Or
Metal coping cap, expansion joint, and edge details are typical only. All metalwork should be installed to sheet metal codes (SMACNA). Clean all metal prior to installation of GenFlex materials.All wood nailers to be approved material. Attachment of wood nailer to be accomplished by using fasteners providing no less than 125 lb (556.0 N) of pullout resistance per linear foot, with fastener spacing no greater than 24" (609.6 mm) between fasteners.All parapet walls and roof curbs must be suitable for flashing, i.e. clean, tight, smooth, no cracks, etc.When field membrane is used as wall or curb flashing, vertical seams must be stripped-in at base of angle change with a 6" (152.4 mm) wide strip of EPDM Flashing, or 7" (177.8 mm) Peel & Stick EPDM Flashing. See Detail E-3.01.
1.
2.
3.
4. GenFlex
EPDM Systems
07/10
Common Counter-Flashing & Membrane Securement Detail #: E-1.03
GenFlex Water StopSee Note #4
GenFlex Bonding AdhesiveSee Note #5
GenFlex EPDM MembraneSee Note #3
New or Existing Metal Counter-Flashing See Note #1
GenFast Fasteners Spaced 12" (304.8 mm) o.c. on New ConstructionGenFast Fasteners Spaced 8" (203.2 mm) o.c. on Reroofs & Recovers with Neoprene Washers or Sealed with an appropriate CaulkSee Note #2
Metal coping cap, expansion joint, and edge details are typical only. All metalwork should be installed to sheet metal codes (SMACNA). Clean all metal prior to installation of GenFlex materials.Any approved pre-drilled fastener for curb or parapet terminations must have a minimum of 125 lb (556.0 N) pullout. See approved fastener list.When field membrane is used as wall or curb flashing, vertical seams must be stripped-in at base of angle change with a 6" (152.4 mm) wide strip of EPDM Flashing, or 7" (177.8 mm) Peel & Stick EPDM Flashing. See Detail E-3.01.Compression fit details that incorporate GenFlex Water Stop must have all existing flashing removed to the bare substrate, e.g. masonry block.All parapet walls and roof curbs must be suitable for flashing, i.e. clean, tight, smooth, no cracks, etc.
1.
2.
3.
4.
5. GenFlex
For current information and promotional literature refer to: www.genflex.com 333EPDM Standard Details
EPDM Systems
07/10
Parapet Wallwith Metal Edge Detail #: E-1.05
Metal coping cap, expansion joint, and edge details are typical only. All metalwork should be installed to sheet metal codes (SMACNA). Clean all metal prior to installation of GenFlex materials.
All parapet walls and roof curbs must be suitable for flashing, i.e. clean, tight, smooth, no cracks, etc.All wood nailers to be approved material. Attachment of wood nailer to be accomplished by using fasteners providing no less than 125 lb (556.0 N) of pullout, and fasteners shall be spaced no greater than 24" (609.6 mm) o.c.When cured flashing is used on wall or curb flashing, vertical seams must be stripped-in at the base of angle change with a 6" (152.4 mm) strip of EPDM Flashing, or 7" (177.8 mm) Peel & Stick EPDM Flashing. See Detail E-3.01
1.2.
3.
4.
GenFlex Cured EPDM Membrane See Note #3
Metal Drip EdgeSee Note #4
Wood NailerSee Note #2
GenFlex Bonding AdhesiveSee Note #1
Approved Fasteners 8" (203.2 mm) o.c.See Note #4
Bar Cover Tape
GenFlex Primer Applied with Scrub Pad & Handle
5" (127.0 mm)Typical
Continuous Cleat(Refer to SMACNA recommendations.)
GenFlex
For current information and promotional literature refer to: www.genflex.com444EPDM Standard Details
GenFlex Cured EPDM MembraneSee Note #1
GenFlex Bonding AdhesiveSee Note #2
GenFast Termination BarSee Note #5
GenFlex Termination CaulkSee Note #5
GenFlex Water Stop
GenFast Fasteners 8" (203.2 mm) o.c. with Neoprene / Metal Washers or Caulk - See Note #4
1.
2.3.
4.
5.6.
All parapet walls and roof curbs must be suitable for flashing, i.e. clean, tight, smooth, no cracks, etc.Compression fit details that incorporate GenFlex Water Stop must have all existing flashing removed to the bare substrate, e.g. masonry block.Any approved pre-drilled fastener for curb and parapet terminations must have a minimum 125 lb (556.0 N) pullout. See approved fastener list.For horizontal application of termination bar, all edges of bar and pre-drilled holes must be caulked with GenFlex Termination Caulk.
When cured flashing is used on wall or curb flashing, vertical seams must be stripped-in at the base of angle change with a 6" (152.4 mm) strip of EPDM Flashing or 7" (177.8 mm) Peel & Stick EPDM Flashing. See Detail E-3.01.
EPDM Systems07/10
Detail #: E-1.07Masonry or ConcreteParapet Wall with Termination Bar
GenFlex
Option A
Option B
Masonry or Concrete Wall or CurbSee Note #6
2" Min.(50.8 mm)
GenFlex Cured EPDM MembraneSee Note #1
GenFlex EPDM Bonding AdhesiveSee Note #2
GenFast Termination BarSee Note #5
GenFlex Termination CaulkSee Note #5
GenFlex Water Stop
GenFlex Fasteners 8" (203.2 mm) o.c. with Neoprene / Metal Washers or Caulk - See Note #4
Masonry or Concrete Wall or CurbSee Note #6
GenFast Termination BarSee Note #5
GenFlex Water Stop
GenFast Fasteners 8" (203.2 mm) o.c. with Neoprene / Metal Washers or Caulk - See Note #4
Masonry and concrete walls or cubs must be waterproofed and maintained in order for any surface mounted termination to be effective.
For current information and promotional literature refer to: www.genflex.com 555EPDM Standard Details
EPDM Systems07/10
Vertical Termination Detail #: E-1.09
1.
2.
3.
4.
Compression fit details that incorporate GenFlex Water Stop must have all existing flashing removed to the bare substrate, e.g. masonry block.Any approved pre-drilled fastener for curb and parapet terminations must have a minimum 125 lb (556.0 N) pullout. See approved fastener list.When cured flashing is used on wall or curb flashing, vertical seams must be stripped-in at the base of angle change with 6" (152.4 mm) strip of EPDM Flashing, or 7" (177.8 mm) Peel & Stick EPDM Flashing. See Detail E - 3.01.
Gravel Stop or Edge Metal
GenFlex Cured EPDM MembraneSee Note #3
GenFlex Water StopBehind Edge of FlashingSee Note #1
GenFlex Termination Caulk
GenFast Termination Bar
GenFast FastenersOn Reroof Projects 8" (203.2 mm) o.c.On New Construction 12" (304.8 mm) o.c.with Neoprene / Metal Washer or CaulkSee Note #2
GenFlex PrimerSee Note #4
EPDM Cover Tape
GenFlexGenFlex Primer must be applied with a Scrub Pad & Handle. Roller or brush application is not permitted.
For current information and promotional literature refer to: www.genflex.com666EPDM Standard Details
Option A
Option B
Caulked Joint in Precast Concrete(By Others)See Note #1
Precast Concrete Panel
GenFlex Termination Caulk
GenFlex Termination BarSee Detail E-1.01.
GenFlex Cured EPDM Membrane
3/8" (9.5 mm) Minimum
1" (25.4 mm)Maximum
GenFlex Water Stop
GenFlex Bonding Adhesive
EPDM Systems
07/10
Termination Bar at Jointin Precast Concrete Panel Detail #: E-1.10
Joint and precast must be filled to support membrane flashing fully.1.2.
3.4.
This detail may also be used for vertical termination to span a control joint in any masonry substrate. GenFlex
GenFlex Fasteners
1" (25.4 mm)Maximum
GenFlex Water Stop
GenFlex Bonding Adhesive
GenFast Fasteners
Caulked Joint in Precast Concrete(By Others)See Note #1
Precast Concrete Panel
GenFlex Termination CaulkGenFast Termination BarSee Detail E-1.01.GenFlex Cured EPDM Membrane
Sealant (By Others)
8" (203.2 mm)Minimum
Counter-flashing in Reglet (By Others)See Note #3
Do not cross expansion joint with termination bar or base tie-in.Cut reglet long enough to allow for movement of counter-flashing.
For current information and promotional literature refer to: www.genflex.com 777EPDM Standard Details
EPDM Systems07/10
Reglet-MountedCounter-Flashing Termination Detail #: E-1.11
3" Min.(76.2 mm)
GenFlex Termination Caulk
GenFlex Bonding Adhesive
GenFlex EPDM Membrane
NOTE: Alternate two-piece counter-flashing application possible per SMACNA.
GenFast Bar Anchor secured with Approved Fasteners 6" (152.4 mm) o.c.
GenFlex Water Stop
Reglet-Mounted Counter-Flashing(per SMACNA)
GenFlex
Approved Fasteners 6" (152.4 mm) o.c.
All parapet walls and roof curbs must be suitable for flashing, i.e. clean, tight, smooth, no cracks, etc.
Approved SubstrateSee Note #1
1.
EPDM Systems07/10
Surface-MountedCounter-Flashing Termination Detail #: E-1.12
3" Min. (76.2 mm)
GenFlex Termination Caulk
GenFlex Bonding Adhesive
GenFlex EPDM Membrane
GenFlex Water Stop
Surface-Mounted Counter-Flashing (per SMACNA)
GenFast Bar Anchor secured with Approved Fasteners 6" (152.4 mm) o.c.
GenFlexAll parapet walls and roof curbs must be suitable for flashing, i.e. clean, tight, smooth, no cracks, etc.
1.
Approved Substrate
For current information and promotional literature refer to: www.genflex.com888EPDM Standard Details
GenFlex EPDM Membrane
EPDM Systems
07/10
Continuous Membrane BaseFlashing - Vertically Secured Detail #: E-2.01
1.
2.
3. Polymer batten strips cannot be used for attachment into masonry wall substrates. Use only on smooth surfaces, e.g. wood or insulation.
All parapet walls and roof curbs must be suitable for flashing, i.e. clean, tight, smooth, no cracks, etc.
GenFlex Bar Anchor secured with Approved Fasteners 12" (304.80 mm) o.c.See Note #3
GenFlex EPDM Bonding AdhesiveSee Note #2
Approved Substrate
GenFlex ISO
GenFlex EPDM Cover Tape CenteredOver Bar AnchorSee Note #1
When using GenFlex EPDM Cover Tape, apply GenFlex Primer to bonding surface (s) with Scrub Pad & Handle.
GenFlex Primer Applied with Scrub Pad & Handle
GenFlex
07/10
Detail #: E-2.02 EPDM SystemsVertically SecuredWall Base Flashing
Polymer batten strips cannot be used for attachments into masonry wall substrates. Use only on smooth surfaces, e.g. wood or insulation.
When cured flashing is used on wall or curb flashing, vertical seams must be stripped-in at the base of angle change with a 6" (152.4 mm) strip of EPDM Flashing, or 7" (177.8 mm) Peel & Stick EPDM Flashing. See Detail E-3.01.
GenFlex EPDM Membrane
GenFlex Bonding AdhesiveSee Note #1
GenFlex ISO
Approved Substrate
GenFlex EPDM FlashingSee Note #4
When using GenFlex EPDM Seam Tape, apply GenFlex Primer with a Scrub Pad & Handle. Do not roller or brush apply Primer.
Any approved pre-drilled fastener for curb and parapet terminations must have a minimum 125 lb (556.0 N) pullout. See approved fastener list.
All parapet walls and roof curbs must be suitable for flashing, i.e. clean, tight, smooth, no cracks, etc.
1.
2.
3.
4.
5.
3" Min.(76.2 mm)
GenFlex Primer
GenFlex EPDM Seam Tape
GenFlex
GenFast Bar Anchor secured with Approved Fasteners 6" (152.4 mm) o.c. See Note #3
For current information and promotional literature refer to: www.genflex.com 999EPDM Standard Details
GenFast Bar Anchor with Approved Fasteners 12" (304.8 mm) o.c. Fastener Length not to Exceed 6" (152.4 mm)
07/10
Detail #: E-2.04EPDM Adhered andMAS Systems Only
Continuous Membrane BaseFlashing - Horizontally Secured
GenFlex Bonding AdhesiveSee Note #1
GenFlex EPDM MembraneSee Note #2
GenFlex EPDM Cover TapeSee Note #3
GenFlex Primer
GenFlex ISO
Approved Substrate
1.
2.
3.When using GenFlex EPDM Cover Tape, apply GenFlex Primer using a GenFlex Scrub Pad and Handle.
When membrane is used as wall or curb flashing, vertical seams must be stripped-in at the base of angle change with a 6" (152.4 mm) strip of EPDM Flashing or 7" (177.8 mm) Peel & Stick EPDM Flashing. See Detail E-3.01.
All parapet walls and roof curbs must be suitable for flashing, i.e. clean, tight, smooth, no cracks, etc.
GenFlex
07/10
Detail #: E-2.08 EPDM Adhered &MAS Systems Only
Horizontally SecuredPeel & Stick EPDM RPS
GenFlex EPDM Membrane
GenFlex Bonding AdhesiveSee Note #1
GenFast 2" (50.8 mm) Plate or Bar Anchor with Approved Fasteners at 12" o.c. (304.8 mm) Maximum Spacing. Fastener Length not to Exceed 6" (152.4 mm). See Note #2
Approved Substrate
GenFlex ISO 4" Max. (101.6 mm) From Deck without Wood Nailer
GenFlex Peel & Stick EPDM RPS
1" (25.4 mm) Gap Required Between Edge of Bar / Disc and Edge of Peel & Stick EPDM RPS
All parapet walls and roof curbs must be suitable for flashing, i.e. clean, tight, smooth, no cracks, etc.GenFlex Peel & Stick EPDM RPS may be secured a maximum of 6" (152.4 mm) out from vertical surface to avoid under-deck obstructions, e.g. structural steel.
1.
2.
GenFlex Primer Applied to Underside of EPDM using a GenFlex Scrub Pad & Handle.
GenFlex
For current information and promotional literature refer to: www.genflex.com101010EPDM Standard Details
07/10
Detail #: E-2.09 EPDM SystemsVertically Secured Peel &Stick EPDM RPS
All parapet walls and roof curbs must be suitable for flashing, clean, tight, smooth, no cracks, etc.1.2.
3.
4.
GenFast Anchor Bar or GenFast Seam Plates may be used to secure the Peel & Stick EPDM RPS vertically into an approved structural substrate (masonry, wood, concrete, etc.). Use an appropriate GenFlex Fastener spaced a maximum of 12" (304.8 mm) o.c. Polymer batten strips cannot be used for vertical attachment.GenFast Bar Anchor, Polymer Batten Strip, or Seam Plates may be used to secure the Peel & Stick RPS horizontally into an approved structural substrate (steel, wood, concrete, etc.). Use an appropriate GenFlex Fastener spaced a maximum of 12" (304.8 mm) o.c.Note: GenFast Polymer Batten Strip can only be used with a GenFlex screw type fastener.
GenFlex
GenFlex EPDM Membrane
GenFlex Peel & Stick EPDM RPS GenFlex ISO
Approved Substrate
GenFlex Bonding AdhesiveSee Note #1
GenFast 2" (50.8 mm) Plate or Bar Anchor with Approved Fasteners 12" (304.8 mm) o.c.See Note #2
Maximum 6" (152.4 mm) long fasteners. (Note: Wood blocking may be substituted for insulation to reduce fastener length required).
For current information and promotional literature refer to: www.genflex.com 111111EPDM Standard Details
07/10
Detail #: E-2.10 EPDM SystemsLayout for Vertically and HorizontallySecured Peel & Stick EPDM RPS
GenFast 2" (50.8 mm) Plate, Bar Anchor or Polymer Batten Strip with Approved Fasteners 12" (304.8 mm) o.c.See Note #3
GenFlex Peel & Stick EPDM RPS
GenFast Bar Anchor or Seam Plates may be used to secure the Peel & Stick EPDM RPS vertically into an approved structural substrate (masonry, wood, concrete, etc.). Use an appropriate GenFast Fastener spaced a maximum of 12" (304.8 mm) o.c. See Notes #1 and 2.
GenFast Bar Anchor, Polymer Batten Strip, or Seam Plates may be used to secure the Peel & Stick EPDM RPS horizontally into an approved structural substrate (steel, wood, concrete, etc.). Use an appropriate GenFast Fastener spaced a maximum of 12" (304.8 mm) o.c. Note: GenFast Polymer Batten Strip can only be used with a GenFlex screw type fastener.
GenFlex
Option A
Option B
GenFlex Peel & Stick EPDM RPS
See Note #3
GenFast 2" (50.8 mm) Plate or Bar Anchor with Approved Fasteners 12" (304.8 mm) o.c.See Note #2
All parapet walls and roof curbs must be suitable for flashing, clean, tight, smooth, no cracks, etc.1.2.3.
Polymer batten strips cannot be used for vertical attachment.Maximum 6" (152.4 mm) long fasteners. (Note: Wood blocking may be substituted for insulation to reduce fastener length required).
For current information and promotional literature refer to: www.genflex.com121212EPDM Standard Details
GenFlex PrimerSee Note #2
Continuous High Profile Bead of GenFlex EPDM Edge Caulk Around Entire Strip
7" (177.8 mm) Wide Peel & Stick EPDM Flashing
07/10
Detail #: E-3.01 EPDM SystemsVertical Seam in Base FlashingUsing Cured EPDM
6" Min.(152.4 mm)
GenFlex EPDM Membrane
GenFlex ISO
Approved Substrate
GenFlex Bonding AdhesiveSee Note #1
1.
2.
All parapet walls and roof curbs must be suitable for flashing, i.e. clean, tight, smooth, no cracks, etc.
3" Min.(76.2 mm)
3" Min.(76.2 mm)
GenFlexWhen using GenFlex EPDM Seam Tape, first apply GenFlex Primer, to bonding surfaces with a GenFlex Scrub Pad & Handle.
GenFlex EPDM Seam Tape
For current information and promotional literature refer to: www.genflex.com 131313EPDM Standard Details
07/10
Detail #: E-3.02AIntermediate Securement IntoStructural Substrate EPDM Systems
For metal stud mounted substrates other than plywood or OSB, see Detail E-3.02B.
Intermediate securement is required on all vertical fully adhered flashings in excess of 48" (1.2 m) o.c. For applications greater than 48" (1.2 m), but less than 8' (2.4 m), install the intermediate securement along a horizontal line halfway between the top of the wall or parapet and the finished roof surface.Plywood or OSB securement to metal studs must be in accordance with industry standards and capable of preventing the plywood or OSB from warping or bowing. Special care should be taken to ensure tight and flush joints in the sheathing material. Securement must be achieved with an appropriate screw-type fastener in order to mitigate the possibility of fastener back-out.Intermediate securement may be achieved in-seam with a GenFast Bar Anchor as shown or by the application of the Bar Anchor through the flashing membrane. If the Bar Anchor is secured through the flashing membrane, it must be stripped-in with EPDM Cover Tape, and all TOP edges of EPDM Cover Tape must be caulked with EPDM Edge Caulk. GenFast Bar Anchor intermediate securement will be secured at 12" (304.8 mm) o.c. into the plywood or OSB substrate with #14 or #15 GenFast fasteners.
1.
2.
3.
4.
Alternate securement method.
EPDM Cover Tape and Scrub Pad & Handle-Applied Primer See Note #3
GenFast Bar AnchorSee Note #3
Masonry / Concrete
Refer to spacing dimensions shown above.
Masonry / Concrete
48" (1.2 m) Max.See Note #1
Exterior System by Architectural Design
See Notes #3 & #4
Plywood or OSB ONLYSee Note #2
GenFlex
GenFlex EPDM Membrane
GenFlex Peel & Stick EPDM RPS
GenFlex Bonding Adhesive
GenFast Bar Anchor and 7" (177.8 mm) Wide GenFlex EPDM Seam Tape
Primer Applied With Scrub Pad & Handle
For current information and promotional literature refer to: www.genflex.com141414EPDM Standard Details
Detail #: E-3.02BIntermediate Securement IntoNon-Structural Substrate
EPDM Systems
Exterior System by Architectural Design
4" Min. (101.6 mm)6" Max. (152.4 mm)
3" Min. (76.2 mm)
Not to Exceed48" o.c.(1.2 m)
GenFast Bar Anchor secured 12" o.c. (304.8 mm) through sheathing and into metal stud. See note #2.
Substrate Other Than Plywood or OSBSee Note #1
4" Min. (101.6 mm)6" Max. (152.4 mm)
GenFlex Peel & Stick EPDM RPS
GenFlex EPDM Cover Tape See Note #2
ALTERNATE METHOD:In situations where it is advantageous to mount the intermediate securement horizontally that involves a non-structural substrate a 22 ga (0.76 mm) metal securement strip may be secured through the non-structural substrate to the metal studs before the flashing is applied to serve as a point of anchorage for the intermediate membrane securement.
22 ga steel (0.76 mm) - 6" wide (152.4 mm)
See Note #3
Metal stud mounted sheathing applications using other than plywood or OSB that are acceptable to bond directly to membrane include: 1/2" (12.7 mm) or greater DensDeck Standard or DensDeck Prime (NOT DensGlass Gold), exterior exposure faced gypsum board in 1/2" (12.7 mm) or greater thickness, etc.Metal stud mounted parapet and wall sheathing other than plywood or OSB exceeding 48" (1.2 m) in height require vertically mounted intermediate securement spaced at most 48" (1.2 m) apart, secured through the sheathing to the metal studs with GenFast #14 Fasteners and GenFast Bar Anchor at 12" (304.8 mm) o.c. The intermediate securement Bar Anchors will extend from 4" (101.6 mm) minimum to 6" (152.4 mm) maximum from the finished roof surface and 4" (101.6 mm) minimum to 6" (152.4 mm) maximum from the metal coping or angle change at the top of the parapet. They must be stripped-in with EPDM Cover Tape, and all TOP edges of the EPDM Cover Tape must be caulked with EPDM Edge Caulk.Secure the metal strip to every metal stud with three GenFast #14 Fasteners with the strip centered at the point where you wishto mount the horizontally oriented intermediate membrane securement.
1.
2.
3.
07/10GenFlex
GenFlex EPDM Membrane
GenFlex Bonding Adhesive
Primer Applied With Scrub Pad & Handle
For current information and promotional literature refer to: www.genflex.com 151515EPDM Standard Details
GenFast Bar Anchor with Approved Fasteners12" (304.8 mm)See Note #1
Nail 6" o.c. (152.4 mm)Use Approved Fastener for Deck Type.
EPDM Membrane must be extended as required to reach a point 24" (609.6 mm) above the finished roof surface. Top of membrane to be sealed to deck with bead of GenFlex Water Stop and be counter-flashed with roofing felt by a minimum of 3" (76.2 mm).
Detail #: E-3.03 EPDM SystemsSloped Wall Transition
24" Min. (609.6 mm) **Measure Vertical
NOT Slope
Roofing Felt Shingle Underlayment to Counter-Flash EPDM Membrane
GenFlex EPDM Bonding Adhesive
GenFlex EPDM Membrane
Shingles Installed to Shingle Manufacturer's Specification Over Properly Installed Starter Course of Shingles
GenFlex Water Stop
Approved Substrate
Wood Nailer (Required only if insulation exceeds 4" (101.6 mm) in thickness)
GenFlex ISO
07/10GenFlex
GenFlex Peel & Stick EPDM RPS
1.
Detail #: E-3.04 EPDM SystemsVertically Secured
Curb / Skylight Flashing
1.
2.
3.
4.
5.
Polymer Batten Strip cannot be used for attachments into brick, block, or concrete wall substrates. Use only on smooth surfaces, e.g. wood or insulation.
Nails are approved where shown on details. Substrate will dictate type of nail used. Any nail type used must be corrosion resistant.
When using GenFlex EPDM Seam Tape, first apply GenFlex Primer with a Scrub Pad & Handle.When cured flashing is used on wall or curb flashing, vertical seams must be stripped-in at the base of angle change with a 6" (152.4 mm) strip of EPDM Flashing, or 7" (177.8 mm) Peel & Stick EPDM Flashing. See Detail E-3.01.
Approved Substrate
GenFlex ISO
GenFlex EPDM BondingAdhesive
GenFast Bar Anchorwith Approved FastenerEach 6" (152.4 mm) o.c.See Note #1 GenFlex
Primer
GenFlex EPDM Membrane
Metal Cap orCounter-FlashingSee Note #5
Nail 6" o.c. (152.4 mm)See Note #4
GenFlex Cured EPDM MembraneSee Note #3
3" Min.(76.2 mm)
8" Min.(203.20 mm)
Metal coping cap, expansion joint, and edge details are typical only. All metalwork should be installed to sheet metal codes (SMACNA). Clean all metal prior to installation of GenFlex materials.
GenFlex EPDMSeam TapeSee Note #2
3" Min.(76.2 mm)
Approved Curb / SkylightManufacturer Fastener
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com161616EPDM Standard Details
5" (127.0 mm)
4" (101.6 mm) 4" (101.6 mm)
5" (127.0 mm)
Detail #: E-3.05 EPDM SystemsWelded WatertightCurb / Skylight Flashing
Approved Substrate
GenFlex ISO
Continuous High ProfileEdge CaulkSee Note #2
GenFlex EPDM Membrane
Wood Nailer
GenFlex Water StopSee Note #3
Approved Curb / SkylightManufacturer Fastener
GenFlex Primer Applied with Scrub Pad & Handle
GenFlex EPDM Cover TapeSee Note #1
1. 2.
3. 4.
1.2. 3.
Welded curb flashings with flange only strip-in require a separate corner flashing.All edges of flashing material require GenFlex Edge Caulk.Flange must be secured through GenFlex EPDM membrane to wood nailer and set in bead of GenFlex Water Stop. Securement method must meet industry standards and be capable of resisting 200 lb (889.6 N) of pullout resistance per linear foot.
Welded Watertight Curb
GenFlex Peel & Stick EPDM Corner
GenFlex Primer Applied with Scrub Pad & Handle
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com 171717EPDM Standard Details
Detail #: E-3.06 EPDM SystemsCurb / Skylight / Roof Hatch withBacker Rod Termination
Approved Substrate
GenFlex ISO
GenFlex EPDMMembrane
GenFlexBonding AdhesiveSee Note #1
Metal Cap orCounter-Flashing(by Others)
GenFlex Cured EPDM MembraneSee Note #2
8" Min.(203.2 mm)
1.
2.
All parapet walls and roof curbs must be suitable for flashing, i.e. clean, tight, smooth, no cracks, etc.When cured flashing is used on wall or curb flashing, vertical seams must be stripped-in at the base of angle change with 6" (152.4 mm) strip of EPDM Flashing, or 7" (177.8 mm) Peel & Stick EPDM Flashing. See Detail E-3.01.
Solid Backer Rod Larger than Opening (by Others)
Approved Curb / SkylightManufacturer Fastener
Any GenFlexBase Flashing Detail
GenFlex Primer Applied with Scrub Pad & Handle
GenFlex EPDMSeam Tape
07/10GenFlex
Detail #: E-3.08 EPDM Systems
Approved Substrate
GenFlex ISO
GenFlex EPDMBondingAdhesive
GenFlex Bar Anchorwith Approved FastenerEach 6" o.c. (152.40 mm)See Note #1
GenFlex EPDMMembrane
Metal Cap orCounter-Flashing
Nail 6" o.c. (152.4 mm)See Note #3
GenFlex Cured EPDM MembraneSee Note #2
3" Min.(76.2 mm)
8" Min.(203.2 mm)
GenFlex EPDMSeam Tape
3" Min.(76.2 mm)
Approved Curb / Skylight Manufacturer Fastener
GenFlex Primer Applied with Scrub Pad & Handle
Horizontally SecuredCurb / Skylight Flashing
1.
2.
3.
4.
Polymer Batten Strips cannot be used for attachments into masonry wall substrates. Use only on smooth surfaces, e.g. wood or insulation.
Nails are approved where shown on details. Substrate will dictate type of nail used. Any nail type used must be corrosion resistant.
When cured flashing is used on wall or curb flashing, vertical seams must be stripped-in at the base of angle change with a 6" (152.4 mm) strip of EPDM Flashing, or 7" (177.8 mm) Peel & Stick EPDM Flashing. See Detail E-3.01.
Metal coping cap, expansion joint, and edge details are typical only. All metalwork should be installed to sheet metal codes (SMACNA). Clean all metal prior to installation of GenFlex materials. 07/10
GenFlex
For current information and promotional literature refer to: www.genflex.com181818EPDM Standard Details
Detail #: E-3.10 EPDM Systems
All parapet walls and roof curbs must be suitable for flashing, i.e. clean, tight, smooth, no cracks, etc.All wood nailers to be approved material. Attachment of wood nailer to be accomplished by using fasteners providing no less than 200 lb (889.6 N) of pullout. Fasteners shall be spaced no greater than 24" (609.6 mm) o.c.When cured flashing is used on wall or curb flashing, vertical seams must be stripped-in at the base of angle change with a 6" (152.4 mm) strip of EPDM Flashing, or 7" (177.8 mm) Peel & Stick EPDM Flashing. See Detail E-3.01.Polymer Batten Strips cannot be used for attachments into brick, block, or concrete wall substrates. Use only on smooth surfaces, e.g. wood or insulation.When using GenFlex EPDM Seam Tape, first apply Primer with a GenFlex Scrub Pad & Handle to the bonding surfaces.
1.
2.
3.
4.
5.
8" Min.(203.2 mm)
ApprovedInsulation
Anchor Bolt with NeopreneWasher or Caulk
Metal Cap(by Others)
GenFlex Water Stop
GenFlex EPDMSeam TapeSee Note #5
GenFast Bar Anchorwith Approved Fasteners12" o.c. (304.8 mm)See Note #4
Equipment Support
Approved Substrate
GenFlex Primer Applied with Scrub Pad & Handle
GenFlex Bonding AdhesiveSee Note #1
GenFlex CuredEPDM MembraneSee Note #3
Wood NailerSee Note #2
GenFlexEPDMMembrane
Sleeper Curb Assembly
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com 191919EPDM Standard Details
EPDM SystemsGravel Stop to Wall Flashing Detail #: E-3.11
When cured flashing is used on wall or curb flashing, vertical seams must be stripped-in at the base of angle change with 7" (177.8 mm) Peel & Stick. See Detail E-3.01.
1.
2.3.
GenFlexWater Stop
Continuous GenFlex EPDMEdge Caulk AroundGenFlex EPDM Cover Tape
Gravel Stop or Metal Edge
CMU
Approved SubstrateGenFlex ISO
Termination Caulk
Approved Wood Nailer
GenFlex CuredEPDM MembraneSee Note #1
GenFlex EPDM Cover TapeSee Note #3
GenFlex EPDM Cover Tape
GenFast Bar Anchorwith Approved Fasteners12" o.c. (304.8 mm)See Note #3
3" Min.(76.2 mm)
Ensure that GenFlex Termination Bar is beneath coping.Install GenFlex EPDM Cover Tape prior to installing vertical termination bar.
Termination BarSee Note #2
1. 2.
3. 4.
5.
GenFlex Primer Applied with Scrub Pad & Handle
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com202020EPDM Standard Details
Detail #: E-3.12Sleeper Support Assembly EPDM Systems
GenFlex EPDM Membrane
GenFlex EPDM Membrane Slip-Sheet Extending 3" (76.2 mm) Beyond Sleeper in All Directions
GenFlex ISO
Wood Nailer Exceeding the Size of the Supported Sleeper by 1/2" Min. (12.7 mm) on All Sides
Approved Substrate
* For use when the roof supported load exceeds 5 lb/in (3.5 g/mm ). For loads less than 5 lb/in (3.5 g/mm ), the sleeper may be set on a slip-sheet directly on the cleaned roof surface.
2 22 2
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com 212121EPDM Standard Details
Detail #: E-4.02Field Fabricated Inside Corner EPDM Systems
1.
2.
3.
4.
All parapet walls and roof curbs must be suitable for flashing, i.e. clean, tight, smooth, no cracks, etc.When using GenFlex EPDM Seam Tape, first prime the bonding surface(s) with GenFlex Primer, using a GenFlex Scrub Pad & Handle.
Polymer Batten Strips cannot be used for attachments into masonry wall substrates. Use only on smooth surfaces, e.g. wood or insulation.
5.
GenFast Bar Anchor with Approved Fastener 6" o.c. (152.4 mm) See Note #4
GenFlex Clear Primer & Seam Tape - See Note #2
GenFlexEPDMMembrane
GenFlex ISO
ApprovedSubstrate
1. GenFlexEPDMBonding AdhesiveSee Note #1
2.GenFlex Primer Applied with Scrub Pad & Handle
3.GenFlex Peel & Stick EPDMFlashing
Fold
4.
GenSplice
For seams assembled with GenFlex GenSplice seam adhesive, a bead of GenFlex EPDM Edge Caulk is required on all exposed edges, following a pre-cleaning of the seam area with GenFlex Cleaner.
6.
GenFlex EPDM Flashing
Continuous High Profile Bead of EPDM Edge Caulk See Note #3
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com222222EPDM Standard Details
5.
Continuous BeadHigh ProfileEPDM Edge CaulkSee Note #3
4.3.GenFlex Peel & Stick EPDM Corner
Fold
Detail #: E-4.03Inside Corner with Peel &Stick EPDM Corner EPDM Systems
1.2.
3.
All parapet walls and roof curbs must be suitable for flashing, i.e. clean, tight, smooth, no cracks, etc.Polymer batten strips cannot be used for attachments into brick, block, or concrete wall substrates. Use only on smooth surfaces, e.g. wood or insulation.
2.1.
Approved Substrate
GenFlex ISO
GenFlex EPDMMembrane
GenFlex BarAnchor with ApprovedFasteners 6" o.c.(152.40 mm)See Note #2
GenFlexEPDMBonding AdhesiveSee Note #1
GenFlex Primer & EPDM Seam Tape
Apply GenFlex Primer with Scrub Pad & Handle
For seams assembled with GenFlex GenSplice seam adhesive, a bead of GenFlex EPDM Edge Caulk is required on all exposed edges, following a pre-cleaning of the seam area with GenFlex Cleaner.
GenSpliceSee Note #3
GenFlex Primer Applied with Scrub Pad & Handle
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com 232323EPDM Standard Details
EPDM SystemsField Fabricated Outside Corner Detail #: E-5.02
All parapet walls and roof curbs must be suitable for flashing, i.e. clean, tight, smooth, no cracks, etc.
Apply a high profile bead of GenFlex EPDM Edge Caulk to all flashing edges and 6" (152.4 mm) in each direction at overlaps in flashing.
GenFlex EPDM Membrane
GenFlex EPDM BondingAdhesive - See Note #1
GenFlex Peel & Stick EPDM Flashing
ApprovedSubstrate
GenFlex ISO
Continuous High Profile Bead of EPDM Edge CaulkSee Note #2
GenFlex Primer Applied with Scrub Pad & Handle
2" Min.(50.8 mm)
Continuous High Profile Bead of EPDM Edge CaulkSee Note #2
4" Min.(101.6 mm)
3" Min.(76.2 mm.)
Note: This Detail is not appropriate for use on projects requiring system warranties greater than ten (10) years in duration.
3.
1.
2.
07/10GenFlex
GenFlex EPDM Seam Tape
Detail #: E-5.03 EPDM SystemsOutside Corner with Peel &Stick EPDM Corner
All parapet walls and roof curbs must be suitable for flashing, i.e. clean, tight, smooth, no cracks, etc.Apply GenFlex EPDM Edge Caulk around entire perimeter of GenFlex Peel & Stick EPDM Corner and along seams for 6" (152.4 mm) past intersection.
1.
2.
3.When using GenFlex Seam Tape, first apply GenFlex Primer to the bonding surface(s) with a Scrub Pad & Handle.
High Profile Bead of GenFlex EPDM Edge CaulkSee Note #2
GenFlex Peel & Stick EPDM Corner
GenFlexBonding AdhesiveSee Note #1
GenFlexEPDMMembrane
GenFlex ISO
Approved Substrate
GenFlex Seam TapeSee Note #3
GenFlex Primer Applied with Scrub Pad & Handle
Apply GenFlex Primer with Scrub Pad & Handle
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com242424EPDM Standard Details
GenFlex 3" (76.20 mm) Wide EPDM Seam Tape Attached to the Bottom Membrane. See Notes #1 & #2
Detail #: E-6.01 EPDM SystemsSeam Tape Application
GenFlex EPDMMembrane
GenFlex Primer Applied with Scrub Pad & Handle
1/8" to 1/4" Exposed (3.2 mm to 6.4 mm)
1.
2.
When using GenFlex Seam Tape, first apply GenFlex Primer to the bonding surface(s), using a GenFlex Scrub Pad & Handle.
GenFlex EPDM Membrane
ApprovedSubstrate
GenFlex ISO
GenFlex Primer Applied with Scrub Pad & Handle
For GenFlex Seam Tape end lap splice, refer to Detail E-6.12.
3" (76.2 mm)
07/10GenFlex
Detail #: E-6.07 EPDM SystemsBar-in-Seam SystemSeam Tape Application
3 1/2"(88.9 mm)
GenFlex Primer Applied with Scrub Pad & Handle7" (177.8 mm)
1. When using GenFlex Seam Tape, first apply GenFlex Primer to the bonding surface(s), using a GenFlex Scrub Pad & Handle.
GenFast Bar Anchor Centered at 3 1/2" (88.9 mm)
ApprovedSubstrate
GenFlex ISO
GenFlex EPDM Membrane
GenFlex Primer Applied with Scrub Pad & Handle
GenFlex 7" (177.8 mm) Wide EPDM Seam Tape
1/8" to 1/4" Exposed (3.2 mm to 6.4 mm)
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com 252525EPDM Standard Details
Detail #: E-6.08 EPDM SystemsFRM In-Seam SystemsSeam Tape Application
GenFast 2" (50.8 mm) Seam Plate
1.
GenFlex Primer Applied with Scrub Pad & Handle
7" (177.80 mm)
GenFlex FRMMembrane
When using GenFlex Seam Tape, first apply GenFlex Primer to the bonding surface(s), using a GenFlex Scrub Pad & Handle.
GenFlex 7" (177.8 mm) Wide EPDMSeam Tape
GenFlex FRMMembrane
ApprovedSubstrate
GenFlex ISO GenFlex Primer Applied with Scrub Pad & Handle
3 1/2"(88.9 mm)
1/8" to 1/4" Exposed (3.2 mm to 6.4 mm)
07/10GenFlex
GenFlex 7" (177.8 mm) Wide EPDMSeam Tape
6" (152.4 mm)All sides
10" (254.0 mm)8" (203.2 mm)
GenFlex Peel & Stick EPDM T-Joint CoverSee Note #2
GenFlex EPDMMembrane
Detail #: E-6.10 EPDM SystemsT-Joint / SeamIntersection Cover
ApprovedSubstrate
GenFlex ISO
GenFlex EPDM Seam TapeSee Note #1
High Profile Bead of EPDM Edge CaulkRequired
GenFlex Primer Applied with Scrub Pad & Handle
1.
2.
When using GenFlex Seam Tape, first apply GenFlex Primer to the bonding surface(s), using a GenFlex Scrub Pad & Handle.Apply GenFlex EPDM Edge Caulk around entire perimeter of GenFlex Peel & Stick EPDM T-Joint Cover and along seams for 6" (152.4 mm) past intersection.
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com262626EPDM Standard Details
Detail #: E-6.12 EPDM SystemsSeam Tape End Lap Splice
When using GenFlex Seam Tape, first apply GenFlex Primer to the bonding surface(s), using GenFlex Scrub Pad & Handle.Apply a high profile bead of GenFlex EPDM Edge Caulk on the outside edge of the completed seam, allowing for 3" (76.2 mm) past overlap.
1.
2.
Approved Substrate
GenFlex ISO
GenFlex Primer Applied with Scrub Pad & Handle
GenFlex EPDM Edge CaulkSee Note #2
GenFlex EPDMMembrane
GenFlex EPDMSeam TapeSee Note #1
3" (76.2 mm) overlapExtend 3" (76.2 mm) Past Overlap Area in Both Directions.
07/10GenFlex
Detail #: E-7.03 EPDM Systems
1.
2.3.4.
5.
6.
When using GenFlex Seam Tape Products, first apply GenFlex Primer to the bonding surface(s), using a GenFlex Scrub Pad & Handle.Cut above rib to fit desired pipe size.If field seam intersects within the pipe boot flange, T-Joint Cover is required.Apply Water Stop to the penetration where the boot will be compressed with the clamping ring.Install membrane securement, consisting of 4 GenFlex fasteners & seam plates per pipe flashing. When possible, install close enough to be covered by boot flange without interfering with the boot to deck membrane seam area.Apply Termination Caulk to the top of the pipe boot as shown above.
GenFlex ISO
GenFlex Peel & Stick EPDM Pipe BootSee Note #3
Pipe
Water StopTerminationCaulk
Stainless SteelClamp
Pre-Molded Pipe Boot
Cut View
Peel & Stick EPDM Pipe Boot
For 1" to 8" (25.4 mm to 203.2 mm)Diameter Pipe Terminations
GenFlex MembraneTermination
For MAS SystemsSee Cut Viewfor Sealants
ClampingRing
GenFlex TerminationCaulkSee Note #6
Water StopSee Cut ViewSee Note #4
ApprovedSubstrate
GenFlex Primer
GenFlex EPDM Membrane
RibSee Note #2
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com 272727EPDM Standard Details
Detail #: E-7.04 EPDM SystemsField Fabricated Pipe Flashing
1.
2.
For seams assembled with GenFlex GenSplice seam adhesive, a bead of GenFlex Edge Caulk is required on all exposed edges, following a pre-cleaning of the seam area with GenFlex Cleaner.
4" Min.(101.6 mm)
4" Min.(101.6 mm)
GenFlex CuredEPDM Membrane
Example Target Patch
GenFlex ISO
Pipe (Clean Thoroughly)
Approved Substrate
Continuous High Profile Bead of GenFlex EPDM Edge CaulkSee Note #1
GenSplice
GenFlex EPDM Flashing Adhered with Bonding AdhesiveSee Note #2
1" (25.4 mm)
1"(25.4 mm)
8" Min.(203.2 mm)
07/10GenFlex
Continuous High Profile Bead of GenFlex EPDM Edge CaulkSee Note #1
Vertical pipe flashing may also be created from GenFlex Peel & Stick EPDM Flashing after vertical substrate has been primed.
Detail #: E-7.06 EPDM SystemsField FabricatedHot Stack Flashing
4" Min.(101.6 mm)
4" Min.(101.6 mm)
GenFlex CuredEPDM Membrane
Example Target Patch
High Profile Bead of GenFlex EPDM Edge CaulkSee Note #1
For seams assembled with GenFlex GenSplice seam adhesive, a high profile bead of GenFlex EPDM Edge Caulk is required on all exposed edges, following a pre-cleaning of the seam area with GenFlex Cleaner.
1.
2.
1" (25.4 mm)High Profile Bead of GenFlex EPDM Edge CaulkSee Note #1
GenFlex EPDM Flashing Adhered with Bonding Adhesive
ApprovedSubstrate
GenSplice
GenFlex ISO
GenFlex CuredEPDM Membrane
Rain Hood(by Others)
Metal Pipe
1"(25.4 mm)
8" Min.(203.2 mm)
07/10GenFlexVertical pipe flashing may also be created from GenFlex Peel & Stick EPDM
Flashing after vertical substrate has been primed.
For current information and promotional literature refer to: www.genflex.com282828EPDM Standard Details
ClampingBolt
DrainStrainer
ClampingRing
Detail #: E-8.01 EPDM SystemsRoof Drain
Approved Substrate
GenFlex EPDMMembrane
Hole in field membrane for drain must be equal in diameter or greater than drain pipe diameter, while still achieving a minimum of 1/2" (12.7 mm) inside compression ring.
NOTE: All drain bolts must be installed and tightened. Missing or loose drain bolts require re-inspection.
Down
GenFlexWater Stop
1/2" Min.(12.7 mm)
GenFlex ISO
07/10GenFlex
Detail #: E-8.02 EPDM MechanicallyAttached Systems
Membrane Securement at Drain withSump Greater Than or Equal to 2/12
12" o.c. (304.8 mm)
Refer to Detail E-8.01 for Drain Flashing requirements.
GenFlex ISO
GenFlex EPDM Membrane
Approved Substrate
Membrane securement at 12" (304.8 mm) out from drain or at top of sump area and 12" o.c. (304.8 mm) required for Mechanically Attached Roof Systems. For FRM systems, this can be accomplished with seam plates and fasteners overlaid with either EPDM Cover Tape or a target patch of EPDM Membrane. For non-reinforced membranes, use Bar Anchor instead of Seam Plates, and flash in one of the methods mentioned.
1/2" Min. (12.7 mm) of Membrane InsideCompression Ring
Down
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com 292929EPDM Standard Details
Detail #: E-9.01 EPDM SystemsPourable Sealer PocketFormed with Metal
Clean inside of pitch pan with approved cleaner.Wood nailer is optional with insulation up to 3" (76.2 mm) maximum and pitch pan no larger than 12" x 12" (304.8 mm x 304.8 mm).
Existing Pipe(s) Must be Free from All Contaminants.GenFlex EPDM
Membrane
3" Min.(76.2 mm)
GenFlex Primer - See Note #1
GenFlex Peel & Stick EPDM FlashingSee Note #2
GenFlex Peel & Stick EPDM Corner
GenFlex ISO
Refer to SMACNA for pourable sealer pocket Fabrication Directions - Must be sized to provide 1" (25.4 mm) of clearance between penetrations and between penetrations and sides of pocket. Job site conditions may require that the pocket be assembled onsite due to fixed, continuous penetrations. See Notes #4 and #5.
GenFlex EPDM Edge CaulkSee Note #3
GenFlex Pourable Sealer 2" (50.8 mm) Min. Mounded to Shed Water
07/10GenFlex
1.2.
3.4.5.
Apply GenFlex Primer using a GenFlex Scrub Pad & Handle.Cut GenFlex Peel & Stick EPDM Flashing so that vertically bonded section extends past the vertical angle change by 2" (50.8 mm).Apply a high profile bead of GenFlex EPDM Edge Caulk to all flashing edges.
2" (50.8 mm)
GenFlex Pourable Sealer 2" (50.8 mm) Min. Mounded to Shed Water
Detail #: E-9.02 EPDM SystemsWatertight Pitch Pan
Metal Pitch Pan with soldered corners, 3" (76.2 mm) wide flange with continuous, rounded corners. For pourable sealer pockets containing more than one penetration, clearance between all penetrations and penetrations from the pocket edges must be minimum 1" (25.4 mm).
Approved Substrate
GenFlex ISO
GenFlex Pourable Sealer 2" Min. (50.8 mm) Mounded to Shed Water.
Filler (Grout Type)
Existing Pipe(s) Must be Free From All Contaminants.
GenFlex EPDMMembrane
GenFlex EPDM Edge Caulk - See Note #1
GenFlex Primer
GenFlex EPDMCover TapeSee Note #2 Approved Fasteners
Each 6" o.c.(152.4 mm)
3" Min.(76.2 mm)
Apply a high profile bead of GenFlex EPDM Edge Caulk on the outside edge of the completed seam.When using GenFlex EPDM Cover Tape, first apply GenFlex Primer to the bonding surface(s) with a GenFlex Scrub Pad & Handle.
1.
2.07/10
GenFlex
For current information and promotional literature refer to: www.genflex.com303030EPDM Standard Details
Detail #: E-9.03 EPDM SystemsEPDM Pipe Boot
as a Pourable Sealer Pocket
GenFlex EPDM Pipe Boot
GenFlex EPDM Membrane
If the boot cannot be installed over the top of a penetration, the boot may be cut in order to place the boot around the object being sealed. If a cut is required, it must be overlaid with Peel & Stick EPDM Flashing and spliced back together prior to filling the boot with GenFlex Pourable Sealer. Ensure the strip-in flashing extends a minimum of 3" (76.2 mm) beyond the step-off of the flange to ensure an adequate seal.
NOTE: In order to achieve an adequate seal, there must be 1" (25.4 mm) of space between penetrations and also between penetrations and the sides of the pipe boot .
GenFlex Pourable Sealer
Cut the boot at the lowest ring. Clean the deck membrane, the boot flange and the inside of the pipe boot with GenFlex Cleaner, and allow to flash-off. For Peel & Stick EPDM Pipe Boots, use a GenFlex Scrub Pad & Handle to apply Primer to the deck membrane and to the inside of the boot and allow to flash off. Peel the release liner from the boot flange and mate to the prepared deck membrane. Roll with a 2" (50.8 mm) roller.For EPDM Pipe Boots (non Peel & Stick) apply GenSplice to the bottom of the boot flange and the deck membrane and allow to flash off before mating the flange to the prepared deck membrane.Fill the pipe boot with GenFlex Pourable Sealer, mounding the sealer to allow water to shed. Extend the sealer to cover the top edges of the boot.
In order to use a GenFlex EPDM Pipe Boot as a pourable sealer pocket follow these steps:1.2.
3.
4.
5.
EPDM PrimerSee step #3 or #4
07/10GenFlex
Cut Along Lowest Ring
For current information and promotional literature refer to: www.genflex.com 313131EPDM Standard Details
Pourable Sealer
Grout Filler (if applicable)
5.
4.3.
Three-SidedPourable Sealer Pocket
Detail #: E-9.04 EPDM Systems
3-sided Pourable Sealer Pocket fabricated with 24 ga (0.61 mm) steel metal. Follow SMACNA Guidelines.
Apply Peel & Stick EPDM Corners to the pocket after applying GenFlex Primer to bonding surface(s) with a GenFlex Scrub Pad & Handle. (Required because of the need to fill out flange radius corners with a separate piece of coated metal)
Peel & Stick EPDM CornersEPDM Edge Caulk
Peel & Stick EPDM Flashing
1. 2.
07/10GenFlex
GenFlex Primer Applied with Scrub Pad & Handle
Using a GenFlex Scrub Pad & Handle, apply GenFlex Primer to pocket flange and allow to flash off properly. Strip in pocket flange with Peel & Stick EPDM Flashing.
Apply EPDM Edge Caulk to the flashing edge that rests next to the metal pan all the way around the detail to keep water from sitting in the void. Also, apply a high profile bead of EPDM Edge Caulk to all flashing edges.
Penetrations must be positioned a minimum of 1" (25.4 mm) apart and also 1" (25.4 mm) from the pocket sides. Pourable Sealer must be a minimum of 2" (50.8 mm) deep - non-shrinking grout filler may be used to fill a pocket to a point 2" (50.8 mm) from top if the pocketexceeds 2" (50.8 mm) in depth.
2" Min.(50.8 mm)
For current information and promotional literature refer to: www.genflex.com323232EPDM Standard Details
Detail #: E-9.05 EPDM SystemsGenPocket E
Remove existing flashing materials, rust, dirt, etc., from penetration prior to installing the GenPocket E.Seal around the penetration(s) prior to installation to prevent Pourable Sealer from entering roof systemUsing a GenFlex Scrub Pad & Handle, apply GenFlex Primer to penetrations and deck sheet where flange of GenPocket E will bond. Also apply primer to inside of the PVC ring (included with GenPocket E), and allow to flash off properly. Once the primer has flashed-off, place the PVC ring around the penetration. Be sure there is a 1" (25.4 mm) space between all penetrations and the PVC ring.Install penetration pocket over the PVC ring so that the ring fits completely inside the top overhang of the pocket.Center the pocket around the penetration, and locate the pre-cut area of the release paper on the underside of the pocket flange. Remove a small area of the paper closest to the PVC ring, and use hand pressure to mate inside edge of the flange to the deck membrane. This will help ensure the pocket does not shift while you remove the rest of the release paper. Pull the remainder of the release paper from the flange at a 45 degree angle, and mate the flange to the deck membrane. Roll flange from the inside to outside edge, using a rubber seam roller. Fill the pipe boot with GenFlex Pourable Sealer, mounding the sealer to allow water to shed. Extend the sealer to cover the top edges of the pocket walls.
If the GenPocket E cannot be installed over the top of a penetration, the pocket may be cut in order to place it around the penetration. If a cut is required, it must be overlaid with Peel & Stick EPDM Flashing and spliced back together prior to being filled with GenFlex Pourable Sealer. Ensure the strip-in flashing extends a minimum of 3" (76.2 mm) beyond the step-off of the flange to ensure an adequate seal.
NOTE: In order to achieve an adequate seal, there must be 1" (25.4 mm) of space between penetrations as well as between penetrations and the sides of the pipe boot .
1.2.3.
4.
5.6.
7.
8.
07/10GenFlex
GenFlex EPDM Membrane
GenFlex Pourable Sealer
5.
Clear PrimerSee step #7
GenPocket E
PVC Ring (Included with GenPocket E)
GenFlex Primer Applied with Scrub Pad & Handle
For current information and promotional literature refer to: www.genflex.com 333333EPDM Standard Details
Detail #: E-10.01 EPDM SystemsScupper
All parapet walls must be suitable for flashing, i.e. clean, tight, smooth, no cracks, an acceptable substrate.When cured flashing is used on wall or curb flashing, vertical seams must be stripped-in at the base of angle change with a 6" (152.4 mm) strip of GenFlex EPDM Flashing, or 7" (177.8 mm) Peel & Stick EPDM Flashing. See Detail E-3.01.For seams assembled with GenFlex GenSplice seam adhesive, a continuous high profile bead of GenFlex EPDM Edge Caulk is required on all exposed edges, following a pre-cleaning of the seam area with GenFlex Cleaner. For scuppers flashed-in with GenFlex 7" (177.8 mm) Peel & Stick EPDM Flashing or EPDM Cover Tape, all transitions, T-joints, and overlaps must have an application of GenFlex Edge Caulk extending 3" (76.2 mm) from the transition, overlap, or T-joint in all directions.
1.2.
3.
4.
GenFlex Bonding AdhesiveSee Note #1
GenFlex GenSpliceSee Note #4
EPDM FlashingSee Note #4
GenFlex Cured EPDM MembraneSee Note #2
Wood Nailer
GenFlex ISO
Approved Substrate
GenFlex EPDMMembrane
GenFlex Water Stop
Flash wall in accordance with GenFlex specification, and cut wall flashing at scupper opening. Mount scupper with 3" (76.2 mm) wide metal mounting flange and continuous, rounded corners onto the wall substrate, with a bead of GenFlex Water Stop between the metal flange and the wall flashing membrane. Secure per SMACNA recommendations and as required to hold Water Stop under constant compression. Flash the scupper assembly with a large enough piece of EPDM Flashing to cover the entire assembly, and extend 3" (76.2 mm) beyond the flange in all directions. Cut the EPDM Flashing at the scupper opening, and turn flashing 1 1/2" to 2" (38.1 mm to 50.8 mm) into the scupper outlet tube. If outlet tube seam is not soldered, extend EPDM Flashingto outer edge of outlet tube. Caulk all flashing edges with properly applied GenFlex EPDM Edge Caulk.
3" Min.(76.2 mm)
Continuous High Profile Bead of GenFlex EPDM Edge CaulkSee Note #3
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com343434EPDM Standard Details
Detail #: E-10.02 EPDM SystemsOverflow Scupper
Flash wall in accordance with GenFlex specification and cut wall flashing at scupper opening. Mount scupper with 3" (76.2 mm) wide metal mounting flange and continuous, rounded corners onto the wall substrate with a bead of GenFlex Water Stop between the metal flange and the wall flashing membrane. Secure per SMACNA recommendations and as required to hold Water Stop under constant compression. Flash the scupper assembly with a large enough piece of GenFlex EPDM Flashing, Peel & Stick EPDM Flashing, or EPDM Cover Tape to cover the entire assembly and extend 3" (76.2 mm) beyond the flange in all directions. Cut the flashing material at the scupper opening, and turn flashing 1 1/2" to 2" (38.1 mm to 50.8 mm) into the scupper outlet tube. If outlet tube seam is not soldered, extend the flashing material to outer edge of outlet tube. Caulk all flashing edges with properly applied GenFlex Edge Caulk.
For seams assembled with GenFlex GenSplice seam adhesive, a continuous high profile bead of GenFlex EPDM Edge Caulk is required on all exposed edges, following a pre-cleaning of the seam area with GenFlex Cleaner. For scuppers flashed-in with GenFlex Peel & Stick EPDM Flashing or EPDM Cover Tape, first apply GenFlex Primer to bonding surface(s) with a GenFlex Scrub Pad & Handle. All transitions, T-joints, and overlaps must have an application of GenFlex Edge Caulk extending 3" (76.2 mm) from the transition, overlap, or T-joint in all directions.
GenFlex ISO
Approved Substrate
Any GenFlex approved Base Tie-In
GenFlex EPDM Flashing, Peel & Stick EPDM Flashing, or EPDM Cover Tape
Turn Flashing into
Scupper Sleeve Min.
1½" (38.1 mm)
GenFlex GenSplice or Primer Applied with Scrub Pad & HandleSee Note #2
GenFlex Water Stop Behind Metal Flange - See Note #3
Continuous High Profile Bead of GenFlex EPDM Edge Caulk
GenFlex EPDM Bonding AdhesiveSee Note #1
All parapet walls must be suitable for flashing, i.e. clean, tight, smooth, no cracks, acceptable substrate, etc.1.2.
3.
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com 353535EPDM Standard Details
Detail #: E-11.01 EPDM SystemsExpansion or Control Joint
GenFlex EPDM Membrane
GenFlex Primer Applied with GenFlex Scrub Pad & Handle
GenFast Bar Anchor with Approved Fasteners 12" o.c. (304.8 mm) or GenFast 2" (50.8 mm) Seam Plate
Peel & Stick EPDM Flashing
GenFlex EPDM Membrane
GenFlex ISOApproved Substrate
Wood Nailer
Foam Tube (by Others)
3" Min. Typical(76.2 mm)
6" Min. Typical(152.4 mm)
GenFlex Membrane
Continuous High Profile Bead of EPDM Edge Caulk, Extending 3" (76.2 mm) Beyond Strip-in Along Seam in Both Directions.
Peel & Stick EPDM Flashing
GenFlex EPDM Seam Tape
07/10GenFlex
Detail #: E-11.02 EPDM SystemsCurb Expansion Joint
GenFlex ISO
ApprovedSubstrate
GenFlex EPDM Membrane
3" (76.2 mm) Wide GenFlex EPDM Seam Tape
When cured flashing is used on wall or curb flashing, vertical seams must be stripped-in at the base of angle change with a 6" (152.4 mm) strip of GenFlex EPDM Flashing or 7" (177.8 mm) Peel & Stick EPDM Flashing. See Detail E-3.01.
1.
8" Min.(203.2 mm)
GenFlex Peel & Stick EPDM FlashingGenFlex Cured EPDM MembraneSee Note #3
Any GenFlex Approved Base Flashing Detail
GenFlex EPDM Bonding Adhesive
3" Min. Typical(76.2 mm)
6" Min. Typical(152.4 mm)
GenFlex EPDM Membrane
Continuous High Profile Bead of GenFlex EPDM Edge Caulk, Extending 3" (76.2 mm) Beyond Strip-in Along Seam in Both Directions.
GenFlex Seam TapeGenFlex Primer Applied with Scrub Pad & Handle
07/10GenFlex
GenFlex Primer Applied with Scrub Pad & Handle
For current information and promotional literature refer to: www.genflex.com363636EPDM Standard Details
Detail #: E-11.03 EPDM Ballasted SystemsDeck to DeckSliding Expansion Joint
GenFlex ISO - See Note #1
GenFlex EPDM Membrane
Approved Substrate
20 ga (0.91 mm) Galvanized Steel (by Others)
07/10GenFlex1. Excessive movement due to thermal expansion/contraction may cause
insulation buckling and bowing. It is the Design Professional's responsibility to determine the appropriateness of this detail.
Approved Fastener24" o.c. (609.6 mm)
6" o.c.(152.4 mm)
6" o.c.(152.4 mm)
Detail #: E-11.04 EPDM SystemsBasewall Expansion Joint
Approved Substrate
GenFlex ISO 4" Max. (101.6 mm) Thickness without a Wood Nailer
GenFlex EPDM Bonding Adhesive - See Note #1
GenFlex EPDM Membrane
GenFast 2" (50.8 mm) Seam Plate or GenFast Bar Anchor with Approved Fastener 12" o.c. (304.8 mm) See Note #2
Foam Tube (by Others)
GenFlex Peel & Stick EPDM RPSSee Note #3
1.
2.
3.
All parapet walls and roof curbs must be suitable for flashing, i.e. clean, tight, smooth, no cracks, etc.Polymer batten strips cannot be used for attachment into brick, block, or concrete wall substrates. Use only on smooth surfaces, e.g. wood or insulation.
Filler
07/10GenFlexUsing a GenFlex Scrub Pad & Handle, apply GenFlex Primer to the
underside of the EPDM Membrane where the Peel & Stick EPDM RPS will bond.
For current information and promotional literature refer to: www.genflex.com 373737EPDM Standard Details
Detail #: E-14.01 EPDM SystemsMetal Gravel Stop
1.2.
3.
4.
Caulk metal joints. See Detail E-14.09.All wood nailers to be approved material. Attachment of wood nailer to be accomplished by using fasteners providing no less than 125 lb (556.0 N) of pullout. Fasteners shall be spaced no greater than 24" o.c. (609.6 mm).When using GenFlex EPDM Cover Tape, first apply GenFlex Primer to the bonding surface(s), using a GenFlex Scrub Pad & Handle.Metal coping cap, expansion joint, and edge details are typical only. All metalwork should be installed to sheet metal codes (SMACNA). Clean all metal prior to installation of GenFlex materials.
Approved Substrate
GenFlex ISO
Wood NailerSee Note #2
Approved FastenerEach 8" o.c.(203.2 mm)
GenFlex EPDM Membrane
GenFlex EPDM Cover Tape See Note #3
GenFlex Primer Applied with GenFlex Scrub Pad & Handle
Metal FasciaSee Note #5
Metal Fascia ClipSee Note #4
1 1/2" Min.(38.1 mm)
See Note #1
5" (127.0 mm)
2"(50.8 mm)
3"(76.2 mm)
1/4" Min.(6.4 mm)
NOTE: EPDM Edge Caulk is required only on the dam side of strip-in on EPDM Cover Tape applications.
07/10GenFlex
Detail #: E-14.03 EPDM SystemsTwo-Piece Snap OnGravel Stop (Option A)
All wood nailers to be approved material. Attachment of wood nailer to be accomplished by using fasteners providing no less than 125 lb (556.0 N) of pullout. Fasteners shall be spaced no greater than 24" o.c. (609.6 mm).Metal coping cap, expansion joint, and edge details are typical only. All metalwork should be installed to sheet metal codes (SMACNA). Clean all metal prior to installation of GenFlex materials.
Wood NailerSee Note #1
Approved Substrate
GenFlex ISO
GenFlex EPDMMembrane
Metal Fascia ClipSee Note #2
1.
2.
GenFlex EPDM Bonding Adhesive
GenFlex EPDMMembrane
Metal Fascia (by Others)See Note #2
Approved FastenerEach 12" o.c. (304.8 mm)
GenFlex Primer Applied with Scrub Pad & Handle
GenFlex EPDMSeam Tape
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com383838EPDM Standard Details
Detail #: E-14.04EPDM Fully
Adhered SystemsTwo-Piece Snap On
Gravel Stop (Option B)
GenFlex EPDM Membrane
GenFlex ISO
Approved Substrate
Wood NailerSee Note #2
Metal Fascia (by Others)See Note #3
Metal Fascia ClipSee Note #3
Approved FastenerEach 12" o.c. (304.8 mm)
GenFlex EPDM Bonding Adhesive
1.
2.
3.
All wood nailers to be approved material. Attachment of wood nailer to be accomplished by using fasteners providing no less than 125 lb (556.0 N) of pullout. Fasteners shall be spaced no greater than 24" o.c. (609.6 mm).Metal coping cap, expansion joint, and edge details are typical only. All metalwork should be installed to sheet metal codes (SMACNA). Clean all metal prior to installation of GenFlex materials.
This detail may be used on Fully Adhered Systems only. For other system types, refer to Detail E-14.03.
07/10GenFlex
Detail #: E-14.05 EPDM SystemsGutter with Flange
GenFlex EPDMMembrane
GenFlex ISO
Approved Substrate
Wood NailerSee Note #1
GenFlex PrimerSee Note #2
Gutter
GenFlex EPDM Cover Tape See Note #2
Approved FastenerEach 8" o.c. (203.2 mm)
Approved Fastenerwith Neoprene Washeror Approved CaulkSpaced in accordance with SMACNA Recommendations
1.
2.
All wood nailers to be approved material. Attachment of wood nailer to be accomplished by using fasteners providing no less than 125 lb (556.03 N) of pullout. Fasteners shall be spaced no greater than 24" o.c. (609.60 mm).When using GenFlex EPDM Cover Tape, first apply GenFlex Primer to the bonding surface(s), using a GenFlex Scrub Pad & Handle.
2"(50.8 mm)
3"(76.2 mm)
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com 393939EPDM Standard Details
1.
2.
3.4.
Minimum height of perforated bar must exceed specified ballast/paver height.Membrane must be fully bonded to nailer with GenFlex Bonding Adhesive.
1 1/2" Min.(38.1 mm)
Detail #: E-14.06 EPDM Ballasted SystemsSlotted Drain Bar
GenFlex EPDM Membrane
Approved FastenerEach 8" o.c. (203.2 mm)See Note #2
GenFlex ISO
Approved Substrate
Wood Nailer - See Note #1
GutterGenFlex Water Stop
Approved FastenerEach 6" o.c. (152.4 mm)with Approved Caulkor Neoprene Washer
Approved Perforated Bar1/8" Min. (3.2 mm) Thick (by Others)See Note #3
07/10GenFlex
Nails are approved where shown on details. Substrate will dictate type of nail used. Any nail type used must be corrosion resistant.
All wood nailers to be approved material. Attachment of wood nailer to be accomplished by using fasteners providing no less than 125 lb (556.03 N) of pullout. Fasteners shall be spaced no greater than 24" o.c. (609.60 mm).
GenFlex Bonding Adhesive
Detail #: E-14.08Edge Termination
Approved FastenerEach 8" o.c. (203.2 mm) with Approved Caulk or Neoprene WasherSee Note #2
Wood NailerSee Note #1
Masonry Substrate
GenFlexWater Stop
GenFlex EPDMMembrane
GenFlex ISO
1.
2.
3.
All wood nailers to be approved material. Attachment of wood nailer to be accomplished by using fasteners providing no less than 125 lb (556.03 N) of pullout. Fasteners shall be spaced no greater than 24" o.c. (609.60 mm).Any approved pre-drilled fastener for curb and parapet terminations must have a minimum of 125 lb (556.03 N) pullout. See approved fastener list.
GenFlexTermination Bar
GenFlex Bonding Adhesive
Membrane must be fully bonded to nailer with GenFlex Bonding Adhesive.07/10
GenFlexEPDM Systems
(Not for Use on Ballasted Roofs)
For current information and promotional literature refer to: www.genflex.com404040EPDM Standard Details
Detail #: E-14.09 EPDM SystemsGravel Stop / Edging Lap Joint
Gravel Stop orEdge Metal
GenFlex EPDM Membrane to Extend Over the Wood Nailer, Under the Edge Metal 2" Min. (50.8 mm).
High Profile Bead of GenFlex EPDM Edge Caulk Required Only on the Dam Side of Strip-in EPDM Cover Tape Applications.
Wood NailerSee Note #1
GenFlex ISO
GenFlex Primer Applied with GenFlex Scrub Pad & Handle
Approved Substrate
1.
2.
All wood nailers to be approved material. Attachment of wood nailer to be accomplished by using fasteners providing no less than 125 lb (556.0 N) of pullout. Fasteners shall be spaced no greater than 24" o.c. (609.6 mm).When using GenFlex EPDM Cover Tape, first apply GenFlex Primer to bonding surface(s), using a GenFlex Scrub Pad & Handle.
GenFlex EPDM Cover TapeSee Note #2
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com 414141EPDM Standard Details
Detail #: E-14.10 EPDM SystemsGravel Stop with Face Plate
Approved FastenerSee Note #1
Wood NailerSee Note #2
Continuous High Profile Bead of GenFlex EPDM Edge Caulk
GenFlex EPDMCover TapeSee Note #3
GenFlex EPDMMembrane
Metal coping cap, expansion joint, and edge details are typical only. All metalwork should be installed to sheet metal codes (SMACNA). Clean all metal prior to installation of GenFlex materials.All wood nailers to be approved materials. Attachment of wood nailer to be accomplished by using fasteners providing no less than 125 lb (556.0 N) of pullout. Fasteners shall be spaced no greater than 24" o.c. (609.6 mm).
1.
2.
3.
4.
Cover Plate
GenFlex Primer Applied with Scrub Pad & HandleSee Note #4
2" Min.(50.8 mm)
1. 2.
3. 4.
When using GenFlex EPDM Cover Tape, first apply GenFlex Primer to the bonding surface(s), using a GenFlex Scrub Pad & Handle.Apply a continuous high profile bead of GenFlex EPDM Edge Caulk exposed flashing edges, following a pre-cleaning of the area with GenFlex Cleaner.
3"(76.2 mm)
Edge Metal with 1" (25.4 mm) Kick
9" (228.6 mm) Wide GenFlex Peel & Stick EPDM
1"(25.4 mm)
3. 4.
07/10GenFlex
GenFlex Primer Applied with Scrub Pad & Handle
For current information and promotional literature refer to: www.genflex.com424242EPDM Standard Details
Detail #: E-14.11 EPDM SystemsTwo-Piece Snap OnGravel Stop with RPS
1.
2.
3.
Metal coping cap, expansion joint, and edge details are typical only. All metalwork should be installed to sheet metal codes (SMACNA). Clean all metal prior to installation of GenFlex materials.All wood nailers to be approved material. Attachment of wood nailer to be accomplished by using fasteners providing no less than 125 lb (556.03 N) of pullout. Fasteners shall be spaced no greater than 24" o.c. (609.60 mm).
Metal Fascia (by Others)See Note #1
Metal Fascia ClipSee Note #1
GenFlex EPDM Membrane
GenFlex ISO
Approved Substrate
Wood Nailer(Wood Blocking)See Note #2
Approved FastenerEach 12" o.c. (304.8 mm)
GenFlex Peel & Stick EPDM RPS - See Note #3
GenFlex Anchor Bar or 2" (50.8 mm) Plate with Approved Fastener Each 12" o.c. (304.8 mm).
07/10GenFlexUsing a GenFlex Scrub Pad & Handle, apply GenFlex Primer to the underside of
the EPDM Membrane where the Peel & Stick EPDM RPS will bond.
GenFlex Bonding Adhesive
For current information and promotional literature refer to: www.genflex.com 434343EPDM Standard Details
Detail #: E-14.12 EPDM SystemsGenFlex Fascia Edge Metal
All wood nailers to be approved material. Attachment of wood nailer to be accomplished by using fasteners providing no less than 125 lb (556.0 N) of pullout. Fasteners shall be spaced no greater than 2' (609.6 mm) o.c.Apply GenFlex Water Stop 1" (25.4 mm) in from roof edge prior to mounting Cleat / Termination Metal Bar at the rate of 15 linear feet (4.6 m) per tube.Secure Cleat / Termination Bar at roof edge through membrane into nailer with provided 1 5/8" (41.3 mm) Corrosion Resistant Fasteners spaced at 12" o.c. (304.8 mm) through pre-punched slots in bar.Membrane must be fully bonded to nailer with GenFlex Bonding Adhesive unless a Peel & Stick EPDM RPS is installed at edge.
1.
2.
3.
4.
GenFlex Fascia Assembly (Extruded Aluminum CleatTermination & Cover)See Note #3
GenFlex EPDM Membrane
GenFlex ISO
Approved Substrate
Wood NailerSee Note #1
GenFlex Water StopSee Note #2
GenFlex Bonding AdhesiveSee Note #4
Ballasted Applications
07/10GenFlex
GenFlex Fascia AssemblySee Note #3
GenFlex Water Stop
Approved Substrate
GenFlex ISO
GenFlex Bonding Adhesive
Fully Adhered Applications
GenFlex Fascia AssemblySee Note #3
GenFlex Water Stop
Approved Substrate
GenFlex ISO
GenFlex PrimerGenFlex Peel & Stick EPDM RPS
Mechanically Attached Applications
For current information and promotional literature refer to: www.genflex.com444444EPDM Standard Details
07/10
Detail #: E-14.13
GenFlexEPDM SystemsGF One Edge Metal Installation
GenFlex EPDM Membrane Extending 1/2" Min. (12.7 mm) Past Nailer
GenFlex EPDMMembrane
GenFlex ISO
Approved SubstrateWood Nailer
#9 Fastener, spaced 12" o.c. (25.4 mm o.c.)See Note #3
GenFlex Water StopSee Note #1
20 ga. Galvanized Formed Base RailSee Note #2
Fascia Cover - See Note #1
6" Stainless Steel Spring Clips, 4' (1.2 m) o.c.
1.
2.3.4.
Install additional sections of base rail by overlapping 1" (25.4 mm).
If necessary, clean the back side of the base rail of dust or dirt prior to application of Water Stop.
#9 x 2" (51.8 mm) Stainless Steel Fasteners are provided with base rail.
GenFlex Bonding Adhesive - See Note #4
Membrane must be fully bonded to nailer with GenFlex Bonding Adhesive unless a Peel & Stick EPDM RPS is installed at edge.
EPDM SystemsDetail #: E-15.01Cover Tape Application
GenFlex Primer Applied with Scrub Pad & Handle
GenFast Bar Anchor or 2" (50.8 mm) Seam Plate withApproved Fastener12" o.c. (304.8 mm)See Note #1
GenFlex EPDM Cover Tape Centered on Bar
GenFlex EPDMMembrane
GenFlex ISO
ApprovedSubstrate
Polymer batten strips cannot be used for attachments into brick, block, or concrete wall substrates. Use only on smooth surfaces, e.g. wood or insulation.
1.
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com 454545EPDM Standard Details
Detail #: E-15.05 EPDM SystemsCover Tape OverField Seam Intersection
GenFlex Cover Tape Centered Over Bar AnchorSee Note #1
GenFlex EPDM Edge Caulk Applied to the Entire Perimeter of Flashing
3"(76.2 mm)
3"(76.2 mm)
3" (76.2 mm)Field Seam
3"(76.2 mm)
ApprovedSubstrate
GenFlex ISO
GenFlex EPDMMembrane
GenFast Bar Anchor
GenFlex Peel & Stick EPDM Flashing
Polymer batten strips cannot be used for attachments into brick, block, or concrete wall substrates. Use only on smooth surfaces, e.g. wood or insulation.
1.
GenFlex Primer Applied with Scrub Pad & Handle
07/10GenFlex
EPDM SystemsDetail #: E-15.06Cover Tape End Lap Splice
7" or 9"(177.8 or 228.6 mm)
3"(76.2 mm)
2"(50.8 mm)
Approved Substrate
GenFlex ISO
GenFlex EPDMMembrane
GenFlex Peel & Stick EPDM Flashing
GenFast Bar Anchor
GenFlex EPDM Cover TapeCentered Over Bar AnchorSee Note #1
Polymer batten strips cannot be used for attachments into brick, block, or concrete wall substrates. Use only on smooth surfaces, e.g. wood or insulation.
1.
GenFlex Primer Applied with Scrub Pad & Handle
GenFlex Primer Applied with Scrub Pad & Handle
GenFlex EPDM Edge Caulk Applied to the Entire Perimeter of Flashing
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com464646EPDM Standard Details
Detail #: E-16.02 EPDM SystemsConcrete Walkway
GenFlex EPDM Membrane45 mil (1.14 mm)or AcceptableSlip-sheet
GenFlex EPDM Membrane
GenFlex ISOApproved Substrate
Precast Concrete PaversPer Specifications 2" x 2' x 2' (50.8 mm x 609.6 mm x 609.6 mm)85 lb Max. (38.6 kg)
Do not install over field seams, bar covers, or flashing splice joints.1. 07/10GenFlex
GenFlex EPDM Membrane
3" Min.(76.2 mm)
GenFlex ISO
Wood Support
Detail #: E-16.03 EPDM SystemsPipe Support
Pipe or Conduit
GenFlex EPDM Membrane or GenFlex FlexGuard Peel & Stick Walkway PadSee Note #2
Approved Substrate
Do not install over field seams or bar cover tape.Extend 2" (50.8 mm) beyond wood support in all directions.Use caution to prevent punctures in membrane.
1.2.3.
1/4" Min. (6.35 mm)
Clamps & Fasteners (by Others)See Note #3
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com 474747EPDM Standard Details
Using a GenFlex Scrub Pad & Handle, apply GenFlex Primer to the EPDM Membrane, and allow to flash-off properly. Position the GenFlex FlexGuard Peel & Stick Walkway Pad as required to line up the Seam Tape and the primed areas of the membrane.
Detail #: E-16.05 EPDM SystemsFlexGuard Peel & StickWalkway Pad Installation
Walkway pads are recommended at all permanent points of roof access and points on the roof requiring once-a-month or more service. Installation of walkway pads will reduce wear on the roofing membrane but will do little to mitigate the effects of "heavy" traffic, which can cause insulation damage if a suitable walk substrate is not designed to handle heavy traffic.
GenFlex EPDM Membrane
GenFlex Seam Tape
Remove the release paper from the seam tape, and mate the walkway pad to the prepared surface in a smooth motion, avoiding buckles in the walkway pad. Walk the walkway pad into place, or roll with a suitable roller.
GenFlex Primer Applied with Scrub Pad & Handle
30" (762.0 mm)
30" (762.0 mm)
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com484848EPDM Standard Details
Detail #: E-17.01 EPDM SystemsHigh Profile Edge Caulk
1. Do not install ballast into freshly applied caulk!
GenPrime
GenFlex Edge Caulk
1/4" Min. (6.4 mm)
GenFlex EPDMMembrane
07/10GenFlex
Detail #: E-18.01 EPDM SystemsTie-In to Existing EPDM System
All wood nailers to be approved material. Attachment of wood nailer to be accomplished by using fasteners providing no less than 125 lb (556.0 N) of pullout. Fasteners shall be spaced no greater than 24" o.c. (609.6 mm).When using GenFlex EPDM Seam Tape or GenFlex EPDM Cover Tape, first apply GenFlex Primer to the bonding surface(s), using a GenFlex Scrub Pad & Handle.Polymer batten strips cannot be used for attachment into brick, block, or concrete wall substrates. Use only on smooth surfaces, e.g. wood or insulation.Tie-In must also be acceptable with existing membrane manufacturer.Tie-In must be with compatible material.
1.
2.
3.
4.5.
GenFlex Primer Applied with Scrub Pad & Handle
GenFlex EPDMMembrane
ApprovedSubstrate
EPDM Membrane(by Others)
GenFlexWater Stop
Wood NailerSee Note #1
GenFast Bar Anchorwith Approved FastenersEach 12" o.c. (304.8 mm)See Note #3
GenFlex EPDM Seam Tape - Leave 1/4" to 1/2" (6.4 mm to 12.7 mm Exposed. See Note #2
GenFlex EPDM Cover Tape - See Note #2
GenFlex Primer Applied with Scrub Pad & Handle
GenFlex ISO
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com 494949EPDM Standard Details
Detail #: E-18.02Curb Tie-In EPDM Systems
ApprovedSubstrate
GenFlex ISO
Roof by Others
Metal Cap(by Others)See Note #1
GenFlexWater Stop
GenFlex CuredEPDM Membrane
Approved Wood NailerSee Note #2
Approved Fastener Each 12" o.c. (304.8 mm)with Neoprene Washer or Approved Caulk
See Detail E-2.02
GenFlexBonding Adhesive
GenFlex EPDM Membrane
GenFlex EPDM Seam Tape - Leave 1/4" to 1/2" (6.4 mm to 12.7 mm) Exposed - See Note #2
GenFlex Primer Applied with Scrub Pad & Handle
Metal coping cap, expansion joint, and edge details are typical only. All metalwork should be installed to sheet metal codes (SMACNA). Clean all metal prior to installation of GenFlex materials.All wood nailers to be approved material. Attachment of wood nailer to be accomplished by using fasteners providing no less than 125 lb (556.0 N) of pullout. Fasteners shall be spaced no greater than 24" o.c. (609.6 mm).When using GenFlex EPDM Seam Tape, first apply GenFlex Primer to the bonding surface(s), using a GenFlex Scrub Pad & Handle.
1.
2.
3.07/10
GenFlex
8" Min.(203.2 mm)
GenFlexWater Stop
For current information and promotional literature refer to: www.genflex.com505050EPDM Standard Details
Detail #: E-18.03 EPDM SystemsTie-In to BUR
with Pourable Sealer
When using GenFlex EPDM Seam Tape, first apply GenFlex Primer to bonding surface(s), using a GenFlex Scrub Pad & Handle.
1.2.3.
4.
Remove all existing stone, and thoroughly clean.GenFlex Roofing Systems is not responsible for damage to BUR.All wood nailers to be approved material. Attachment of wood nailer to be accomplished by using fasteners providing no less than 125 lb (556.03 N) of pullout. Fasteners shall be spaced no greater than 24" o.c. (609.60 mm).
Wood NailerSee Note #3
GenFlexPourable SealerSee Notes #1, #2
GenFlex ISO
Existing BUR
GenFlex Primer ShownAs Dotted Line
Pourable Sealer
6" Min.(152.4 mm)
Membrane Edge
ApprovedSubstrate
GenFlex EPDM Flashing
GenFlex EPDM Membrane
GenFlexWater Stop
6" Min. (152.4mm)
GenFlex EPDM Seam TapeSee Note #4GenFlex Primer Applied with a GenFlex Scrub Pad & HandleGenFlex Metal Bar Anchor (See Detail E-2.07.)with Approved Fastener Each 6" o.c. (152.40 mm)
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com 515151EPDM Standard Details
Detail #: E-18.04 EPDM SystemsTie-In to BUR withCold Process or Asphalt
When using GenFlex EPDM Seam Tape, first apply GenFlex Primer to the bonding surface(s), using a GenFlex Scrub Pad & Handle.
1.
2.
3.
All wood nailers to be approved material. Attachment of wood nailer to be accomplished by using fasteners providing no less than 125 lb (556.0 N) of pullout. Fasteners shall be spaced no greater than 24" o.c. (609.6 mm).Polymer batten strips cannot be used for attachments into brick, block, or concrete wall substrates. Use only on smooth surfaces, e.g. wood or insulation.
3" Min.(76.2 mm)
GenFlex EPDM Flashing
GenFlex EPDM Seam Tape See Note #1
Wood NailerSee Note #2
2 Layers of Felt
Existing BUR
Approved Substrate
Approved FastenerEach 24" o.c.(609.6 mm)
GenFlexWater Stop
ApprovedInsulation
GenFlex EPDMMembrane
GenFast Bar Anchorwith Approved FastenerEach 6" o.c. (152.4 mm) See Note #3
GenFlex Primer Applied with Scrub Pad & Handle
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com525252EPDM Standard Details
All parapet walls and roof curbs must be suitable for flashing, i.e. clean, tight, smooth, no cracks, etc.
3" Min. (76.2 mm)
Sacrificial Sheet(45 mil (1.14 mm) GenFlex EPDM Membrane)
GenFlex Bonding AdhesiveSee Note #6
GenFlex EPDMMembrane
GenFlex EPDM MembraneSee Note #4
Precast Concrete Paver per Specifications
Lightning Rod
Base
ApprovedInsulation
ApprovedSubstrate
GenFlex Pourable Sealer
Approved CaulkSee Note #5
1.2.
3.4.
5.
6.
7.
It is the responsibility of the building owner to ensure code compliance.GenFlex Roofing Systems assumes no responsibility for attachment of lightning rods or damages to the roof system because of failure or detachment.Contact the GenFlex Technical Department for detail on mechanically attached systems.When cured flashing is used on wall or curb flashing, vertical seams must be stripped-in at the base of angle change with 6" (152.4 mm) strip of GenFlex EPDM Flashing, or 7" (177.8 mm) Peel & Stick EPDM Flashing. See Detail E-3.01.Compression fit details that incorporate GenFlex Water Stop must have all existing flashing removed to the bare substrate, e.g. masonry block.
Detail #: E-19.01 EPDM SystemsLightning Rod
Rows of lightning rod attachment must follow lines of securement. 07/10GenFlex
2" x 6"(50.8 mm x 152.4 mm)
Coupling Set in GenFlex Pourable Sealer
Detail #: E-19.02 EPDM SystemsLightning Rod
GenFlex 6" (152.4 mm) Reinforced EPDM Sacrificial Sheet Fully Adhered to Membrane or GenFlex EPDM Cover Tape. Install EPDM Cover Tape Per Specifications.
GenFlexMembrane
ApprovedSubstrate
GenFlex ISO
Lightning Rod
GenFlex Pourable Sealer
GenFlex EPDM Cover Tape
GenFlex Primer Applied with Scrub Pad & Handle
24" Max. (609.6 mm)
GenFlex Bonding Adhesive
Lightning Rod
GenFlex Termination Caulk
GenFlex EPDMMembrane
Base
All parapet walls and roof curbs must be suitable for flashing, i.e. clean, tight, smooth, no cracks, etc.
1.
2.
3.4.
5.
6.
7.
It is the responsibility of the building owner to ensure code compliance.GenFlex Roofing Systems assumes no responsibility for attachment of lightning rods or damages to the roof system because of failure or detachment.Contact the GenFlex Technical Department for detail on mechanically attached systems.When cured flashing is used on wall or curb flashing, vertical seams must be stripped-in at the base of angle change with 6" (152.4 mm) strip of GenFlex EPDM Flashing, or 7" (177.8 mm) Peel & Stick EPDM Flashing. See Detail E-3.01.Compression fit details that incorporate GenFlex Water Stop must have all existing flashing removed to the bare substrate, e.g. masonry block.
Rows of lightning rod attachment must follow lines of securement. 07/10GenFlex
For current information and promotional literature refer to: www.genflex.com 535353EPDM Standard Details
Detail #: E-19.03Temporary Night Seal EPDM Systems
GenFlex EPDM Membrane
GenFlex ISO
Approved Substrate
Approved Sealer
Wood Blocking 2" x 4" (50.8 mm x 101.6 mm)
Clean & Dry Before installation of Approved Sealer
Fastener 24" o.c. (609.6 mm) As Required
1. It is the responsibility of the Roofing Contractor to ensure seal is watertight. 07/10GenFlex
Detail #: E-19.04 EPDM SystemsGrease Vent
GenFlex EPDM Membrane
Salvage Sheet(Consult the GenFlex Technical Department) See Note #1
Salvage sheet area to be determined by design professional and must be sized to protect roofing membrane from contamination by expelled grease / oil. Regular inspection and maintenance by building owner is required.
1.
Continuous High Profile Bead of EPDM Edge Caulk
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com545454EPDM Standard Details
INSULATION ATTACHMENT RATES FOR FULLY ADHERED SYSTEMS
Insulation FM Rating Thickness
Frequency# per 4’ x 8’ bd.
(1.2 m x 2.4 m)Fastener & Plate Pattern
GenFlex Polyiso
I-60A1” to 1.4”
(25.4 to 35.6 mm)16
GenFast #12, #14, #15 and
GenFast Insulation Plate
1
I-90B1.5” to 1.9”
(38.1 to 48.3 mm)12 3
I-90B2” to 4”
(50.8 to 101.6 mm)8 7
GenFlex 1/2” HD ISO (Cover Board)
I-90B 1/2” (12.7 mm) 12GenFast #12, #14, #15 and
GenFast Insulation Plate4
GenFlex Wood Fiber Board
I-60A 1/2” (12.7 mm) 16 GenFast #12, #14, #15 and
GenFast Insulation Plate
1
I-90B 1” (25.4 mm) 16 1
GP DensDeck
I-60A 1/4” (6.4 mm) 12
GenFast #12, #14, #15 and
GenFast Insulation Plate
5
I-90B 1/4” (6.4 mm) 16 2
I-60A 1/2” (12.7 mm) 10 6
I-90B 1/2” (12.7 mm) 16 2
I-60A / I-75A / I-90B 5/8” (15.9 mm) 8 8
GP DensDeck Prime
I-60A / I-75A / I-90B 1/4” (6.4 mm) 12
GenFast #12, #14, #15 and
GenFast Insulation Plate
5
I-60A 1/2” (12.7 mm) 10 6
I-90B 1/2” (12.7 mm) 12 5
I-60A / I-75A / I-90B 5/8” (15.9 mm) 8 8
NOTES:A On I-60 and I-75 systems, for all mechanically fastened insulations or thermal barriers, the number of fasteners per board should be
increased over the FMRC-approved field of roof spacing by:
50% In the roof perimeter
100% In the roof corners
Round up to the next whole number of fasteners.B For I-90 systems, refer to the Loss Prevention Data Sheet 1-29.
The width of the roof corners and perimeter is defined as the smaller of:
0.1 Times the building lesser plan dimension
0.4 Times the eave height
Subject to a minimum width of 4’ (1.2 m)
For GenFlex warranted projects on which no FM requirements apply, follow FM I-60 fastening patterns for buildings less than 50’ (15.2 m)high in non-hurricane zones. Please contact the GenFlex Technical Department for buildings over 50’ (15.2 m) high or located in hurricane or high wind zones.
On recover systems, Factory Mutual limits the insulation thickness to a maximum of one (1) inch (25.4 mm). Contact the GenFlex Technical Department for approvals over deck types other than metal or concrete, e.g. cementitious wood fiber, gypsum, etc. Minimum #14 Fasteners are required for concrete decks.
07/2010
For current information and promotional literature refer to: www.genflex.com 555555EPDM Standard Details
8'
4'
6"6"
12"
12"
12"
12"
12"
12"
12" 12" 12"
All Adhered Systems
07/10
Insulation Securement Patterns Detail #: ISP 1 - 4
Pattern #1For use with:0.5" to 1.4" GenFlex Polyiso1/2" GenFlex Wood Fiber1" GenFlex Wood Fiber
Pattern #2For use with 1/4" and 1/2" DensDeck
Pattern #3For use with 1.5" to 1.9" GenFlex Polyiso
Pattern #4For use with GenFlex 1/2" HD ISO (Cover Board)
Base Pattern Perimeter + 50% Corner + 100%
Use this visual reference in conjunction with the Insulation For Fully Adhered Systems table located in the Design Criteria section of this manual and in the back of the Fully Adhered Application Specification.
Metric Conversions:0.5" to 1.4" = 12.7 mm to 35.6 mm1/2" = 12.7 mm1" = 25.4 mm6" = 152.4 mm12" = 304.8 mm18" = 457.2 mm24" = 609.6 mm4' = 1.2 m8' = 2.4 m
Metric Conversions:1.5" to 1.9" = 38.1 mm to 48.3 mm6" = 152.4 mm 12" = 304.8 mm18" = 457.2 mm24" = 609.6 mm36" = 914.4 mm4' = 1.2 m8' = 2.4 m
Metric Conversions:1/2" = 12.7 mm6" = 152.4 mm12" = 304.8 mm18" = 457.2 mm36" = 914.4 mm4' = 1.2 m8' = 2.4 m
GenFlex
8'
4'
8'
4'
8'
4'
8'
4'
8'
4'
6"6"
12"
12"
12"
12"
12"
12"
12" 12" 12"
6"6"
18"
18"
18"
12"
12" 12" 12"
Metric Conversions:1/4" = 6.4 mm1/2" = 12.7 mm6" = 152.4 mm12" = 304.8 mm18" = 457.2 mm24" = 609.6 mm4' = 1.2 m8' = 2.4 m
8'
4'
6"6"
18"
18"
18"
12"
18"
12"
18"
18"
12"
12"18"
8'
4'
6"
6"
18"
18"
18"
12"
18"
12"
18"
18"
12"
12"18"
6"
6"
36"
12"
24"
24"
24"
12"6"
6"
12" 12" 12"
6"
18"
18"
12"
18" 18" 6"
12"
6"
8'
4'
8'
4'
6"6"
18"
18"
18"
12"
18"
12"
18"
18"
12"
12"18"
6"6"
12" 12" 12"
6"
18"
18"
12"
18" 18" 6"
12"
6"
6"6"
36"
12"
18" 18" 6"6"
6"6"
12"
12" 8'
4'
12"
12"
6"
6"
12"
6" 6" 12" 6"6"12"
6"6"
12"
12" 8'
4'
12"
12"
6"
6"
12"
6" 6" 12" 6"6"12"
For current information and promotional literature refer to: www.genflex.com565656EPDM Standard Details
8'
4'
8'
4'
8'
4'
8'
4'
8'
4'
8'
4'
All Adhered Systems
07/10
Insulation Securement Patterns Detail #: ISP 5 - 8
Pattern #5For use with:1/4" DensDeck1/4" and 1/2" DensDeck Prime
Pattern #6For use with 1/2" DensDeck1/2" DensDeck Prime
Pattern #7For use with 2.0" to 4.0" GenFlex Polyiso
Pattern #8For use with 5/8" DensDeck5/8" DensDeck Prime
Base Pattern Perimeter + 50% Corner + 100%
Metric Conversions:1/4" = 6.4 mm1/2" = 12.7 mm6" = 152.4 mm12" = 304.8 mm18" = 457.2 mm24" = 609.6 mm4' = 1.2 m8' = 2.4 m
Metric Conversions:2.0" to 4.0" = 50.8 mm to 101.6 mm6" = 152.4 mm 12" = 304.8 mm18" = 457.2 mm24" = 609.6 mm36" = 914.4 mm4' = 1.2 m8' = 2.4 m
Metric Conversions:1/2" = 12.7 mm5/8" = 15.9 mm6" = 152.4 mm12" = 304.8 mm18" = 457.2 mm24" = 609.6 mm36" = 914.4 mm4' = 1.2 m8' = 2.4 m
GenFlex
Metric Conversions:1/2" = 12.7 mm6" = 152.4 mm12" = 304.8 mm18" = 457.2 mm24" = 609.6 mm4' = 1.2 m8' = 2.4 m
Use this visual reference in conjunction with the Insulation For Fully Adhered Systems table located in the Design Criteria section of this manual and in the back of the Fully Adhered Application Specification.
8'
4'
8'
4'
12"
24"
24"
12" 12" 12"12"
6"
6"
18"
18"
18"
12"
18"18"
8'
4'
6"6"
18"
18"
18"
12"
12" 12" 12"
12"
12"
24"
12"
12"
12" 12" 12"12"
18"
18"
18"
12"
12" 12" 12"12"
18"
18"
18"
12"
12" 12" 12"6" 6"
12"
24"
24"
24" 12"12"
8'
4'
6"
6"
36"
12"
24"
24"
24"
12"
12"
24"
24"
12" 12" 12"12"
6"6"
12"
12" 8'
4'
12"
12"
6"
6"
12"
6" 6" 12" 6"6"12"
6"
6"12"
12" 8'
4'
12"
12"
6"
6"
12"
6" 6" 12" 6"6"12"
12"
18"
18"
18"
12" 12"12" 12"
Note: Pattern #7 Base Pattern is also acceptable.
For current information and promotional literature refer to: www.genflex.com 575757EPDM Standard Details
EPDM Ballasted SystemsBallasted System Cross Sections Detail #: 1.03-4-5
Position insulation with board ends resting on the top flutes.
GenFlex ISO or Approved Substrate
GenFlex EPDM Membrane
Approved Deck
Refer to the Detail E-6.01 for Dimensions and Layout Requirements.Standard Ballasted Assembly
GenFlex ISO or Approved Substrate
GenFlex EPDM Membrane
Approved Deck
Paver Ballasted Assembly
GenFlex Approved Slip-sheet
The property owner's design professional must ensure that the structure is sound and capable of supporting the intended roof system. Care must be taken when installing a ballasted roof system to prevent overloading the deck during ballasting operations. If the ballasted roof is installed in a high wind area, and mechanical securement of the insulation is specified by the roof system designer, contact the GenFlex Technical Department to discuss securement requirements.
GenFlex ISO or Approved Substrate
GenFlex EPDM Membrane
Approved Deck
IRMA Assembly GenFlex Approved Slip-sheet
Minimum 10 lb/ft (48.8 kg/m ) of Approved Ballast
2 2
Approved Roof Pavers
Minimum 10 lb/ft (48.8 kg/m ) of Approved Ballast
2 2
07/10GenFlex
Extruded Polystyrene
For current information and promotional literature refer to: www.genflex.com585858EPDM Standard Details
EPDM Fully Adhered Systems
07/10
Fully Adhered SystemCross Section Detail #: 11.06
Position insulation to enable securement into the top flutes on steel decks, ensure positive attachment, and reduce fastener movement. Insulation should be installed with board ends resting on the top flutes.
GenFlex ISO
GenFlex EPDM Membrane
Approved Substrate
Refer to Detail E-6.01 for dimensions and layout requirements.
GenFlex Bonding Adhesive
GenFlex
EPDM Fully Adhered Systems
07/10
Fully Adhered SystemInsulation Securement Detail #: 11.07
6"(152.4 mm)
4'(1.2 m)
4' (1.2 m)
Always stagger insulation jointsregardless of boardsize used.
For use on buildings up to 50' (15.2 m) high. If building heightexceeds 50' (15.2 m), contact the GenFlex Technical Department for attachment pattern.
18"(457.2 mm)
18"(457.2 mm)
6"(152.4 mm)
18"(457.2 mm)
18"(457.2 mm)
Repeat pattern below
Reduced Fastening Patterns Are Available For GenFlex ISO Insulation. Minimum Thickness RestrictionsApply. Refer to Insulation Securement Pattern for attachment options.
GenFlex
24"(609.6 mm)
6"(152.4 mm)
8'(2.4 m)
6"(152.4 mm)
18"(457.2 mm)
18"(457.2 mm)
24"(609.6 mm)
4' (1.2 m)
4'(1.2 m)
18"(457.2 mm)
18"(457.2 mm)
12"(304.8 mm)
For current information and promotional literature refer to: www.genflex.com 595959EPDM Standard Details
Detail #: 25.01 & 26.01
GenFlex EPDM Membrane
GenFlex ISO
Position insulation and membrane sheets to enable securement into the top flutes on steel decks, ensure positive attachment, and reduce fastener movement. Insulation should be installed with board ends resting on the flute tops.
GenFlex 7" (177.8 mm) Seam Tape Bonded to Primed Membrane - Apply GenFlex Primer with Scrub Pad & Handle
6' 0" (1.8 m)
3 1/2" (88.9 mm)
7"(177.8 mm)
6' 0" (1.8 m) System Layout Pattern(For use with 6' 6" (2.0 m) membrane panels.)
26.01
7' 0" (2.1 m)
3 1/2" (88.9 mm)
7"(177.8 mm)
7' 0" (2.1 m) System Layout Pattern(For use with 7' 6" (2.3 m) membrane panels.)
25.01
EPDM Bar-In-Seam SystemsBar-In-Seam SystemInsulation Cross Section
Field Seams with GenFast Bar Anchor and GenFast Fasteners Spaced in Accordance with the EPDM Bar-In-Seam MAS Code Matrix in the EPDM Code Section.
07/10GenFlex
EPDM Bar-In-Seam SystemsBar-In-SeamInsulation Securement Detail #: 26.06 & 26.07
4' (1.2 m)
4'(1.2 m)
8'(2.4 m)
8"(203.2 mm)
8"(203.2 mm)
24"(609.6 mm)
4' (1.2 m)
4'(1.2 m)
8"(203.2 mm)
8"(203.2 mm)
Always stagger insulation joints, regardless of panelsize used.
For use on buildings up to 50' (15.2 m) high. If building height exceeds 50' (15.2 m), contact the GenFlex Technical Departmentfor attachment pattern.
26.07
26.06
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com606060EPDM Standard Details
Bar-In-Seam SystemPerimeter Layout Patterns Detail #: 25.02 & 26.02
Roof Edge
6' 0" (1.8 m) Bar-In-Seam Mechanically AttachedSystem Perimeter Layout Pattern
GenFlex Membrane
GenFast Bar Anchor and appropriate GenFlex Fasteners spaced 12" (304.8 mm) o.c. and overlaid with GenFlex EPDM Cover Tape applied to a primed deck sheet and centered on fasteners.
3' (914.4 mm)
3' (914.4 mm)
6' (1.8 m)
6' (1.8 m)
3'(914.4 mm)
12"(304.8 mm)
Roof Edge
7' 0" (2.1 m) Bar-In-Seam Mechanically AttachedSystem Perimeter Layout Pattern
Field Seams with Anchor Bar and GenFlex Fasteners Spaced in Accordance with the EPDMBar-In-Seam MAS Code Matrix in the EPDM Code Section.
GenFlex Membrane
GenFast Bar Anchor and appropriate GenFlex Fasteners spaced 12" o.c. (304.8 mm) and overlaid with GenFlex EPDM Cover Tape applied to primed deck sheet and centered on fasteners.
2' (609.6 mm)
5' (1.5 m)
7' (2.1 m)
2'(609.6 mm)
5'(1.5 m)
7' 0"(2.1 m)
Field Seams with Anchor Bar and GenFlex Fasteners Spaced in Accordance with the EPDMBar-In-Seam MAS Code Matrix in the EPDM Code Section.
EPDM Bar-In-Seam Systems
26.02
25.02
7' (2.1 m)
12"(304.8 mm)
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com 616161EPDM Standard Details
EPDM Bar CoverTape Systems
Bar Cover Tape SystemInsulation Cross Section Detail #: 22.04 & 27.01
GenFlex EPDM Membrane
GenFlex Insulation
Position insulation and membrane sheets to enable securement into the top flutes on steel decks, ensure positive attachment, and reduce fastener movement. Insulation should be installed with board ends resting on the flute tops.
GenFlex EPDM Cover Tape Mated to Primed Membrane and Centered on Bar Anchor
6' 0" (1.8 m)
3" (76.2 mm)
6" (152.4 mm)
6' 0" (1.8 m) Bar Cover TapeSystem Layout Pattern
7' 0" (2.1 m)
3" (76.2 mm)
6" (152.4 mm)
7' 0" (2.1 m) Bar Cover TapeSystem Layout Pattern
Field Seams with Anchor Bar and GenFlex Fasteners Spaced in Accordance with the EPDMBar Cover Tape Code Matrix in the EPDM Code Section.
27.01 22.04
07/10GenFlex
EPDM Bar Cover Tape SystemsBar Cover TapeInsulation Securement
4' (1.2 m)
4'(1.22 m)
8'(2.4 m)
8"(203.2 mm)
8"(203.2 mm)
24"(609.6 mm)
4' (1.2 m)
4'(1.2 m)
8"(203.2 mm)
Always stagger insulation joints regardless of panelsize used.
For use on buildings up to 50' (15.2 m) high. If building height exceeds 50' (15.2 m), contact the GenFlex Technical Departmentfor attachment pattern.
Detail #: 27.05 & 27.06
27.05
27.06
8"(203.2 mm)
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com626262EPDM Standard Details
EPDM Bar CoverTape Systems
Bar Cover Tape SystemPerimeter Layout Patterns
Detail #: 22.05 & 27.02
Roof Edge
3' (914.4 mm)
3'(914.4 mm)
6'(1.8 m)
6'(1.8 m)
6'(1.8 m)
GenFlex EPDM MembraneRefer to standard seaming details for splicing information.
6' 0" (1.8 m) Bar Cover Tape SystemPerimeter Layout Pattern
4" Max.(101.6 mm) 4" Max.
(101.6 mm)
2' (609.6 mm)
5' (1.5 m)
2'(609.6 mm)
5'(1.5 m)
7'(2.1 m)
7'(2.1 m)
7'(2.1 m)
4" Max.(101.6 mm)
4" Max.(101.6 mm)
Roof Edge
GenFlex EPDM MembraneRefer to standard seaming details for splicing information.
7' 0" (2.1 m) Bar Cover Tape SystemPerimeter Layout Pattern
27.02
22.05
07/10GenFlex
Field Seams with Bar Anchor and GenFlex Fasteners Spaced in Accordance with the EPDMBar Cover Tape Code Matrix in the EPDM Code Section.
Field Seams with Bar Anchor and GenFlex Fasteners Spaced in Accordance with the EPDMBar Cover Tape Code Matrix in the EPDM Code Section.
For current information and promotional literature refer to: www.genflex.com 636363EPDM Standard Details
07/10GenFlex
FRM SystemPerimeter Layout Pattern Detail #: E-70.01
Roof Edge
9' 6" (2.9 m) FRM EPDM In-Seam Attachment SystemPerimeter Layout Pattern
GenFlex FRM Membrane
GenFast 2" (50.8 mm) Seam Plates and appropriate GenFlex Fasteners spaced 12" o.c. (304.8 mm) and overlaid with GenFlex EPDM Cover Tape applied to primed deck sheet and centered on fasteners.
5' (1.5 m)
4' 6" (1.4 m)
9' 6" (2.9 m)
9' 6" (2.9 m)
5'(1.5 m)
12"(304.8 mm)
Field Seams with Anchor Bar and GenFlex Fasteners Spaced in Accordance with the EPDM FRM MAS Code Matrix in the EPDM Code Section.
FRM In-SeamAttachment Systems
FRM SystemInsulation Cross Section Detail #: E-71.00
GenFlex FRM EPDM Membrane
GenFlex Insulation
Position insulation and membrane sheets to enable securement into the top flutes on steel decks, ensure positive attachment, and reduce fastener movement. Insulation should be installed with board ends resting on the flute tops.
7" (177.8 mm) Wide GenFlex EPDM Seam Tape Bonded to Primed Membrane
Field Seams with GenFast Bar Anchor and Appropriate GenFlex Fasteners Spaced in Accordance with the EPDM FRM MAS Code Matrix in the EPDM Code Section.
FRM In-SeamAttachment Systems
9' 6" (2.9 m)
3 1/2" (88.9 mm)
7"(177.8 mm)
9' 6" (2.9 m) System Layout Pattern(For use with 10' (3.0 m) membrane panels.)
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com646464EPDM Standard Details
FRM SystemInsulation Securement Detail #: 71.03 & 71.05
4' (1.2 m)
4'(1.2 m)
8'(2.4 m)
8"(203.2 mm)
24"(609.6 mm)
4' (1.2 m)
4'(1.2 m)
8"(203.2 mm)
8"(203.2 mm)
Always stagger insulation joints, regardless of panelsize used.
For use on buildings up to 50' (15.2 m) high. If building height exceeds 50' (15.2 m), contact the GenFlex Technical Departmentfor attachment pattern.
71.05
71.03
FRM In-SeamAttachment Systems
8"(203.2 mm)
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com 656565EPDM Standard Details
Detail #: EMR-1.13 EPDM Metal RoofRecover Systems
Metal Roof to Metal Siding - VerticalTermination and Counter-Flashing
Vertical TerminationExisting Condition
Cut a 1" (25.40 mm) strip out of the metal siding starting at the upper edge of the purlin. Sand, prime, and paint the raw metal edge to prevent rust. Contact metal siding manufacturer for proper primer and paint types.
Secure the top edge of the GenFlex EPDM with roofing nails into the plywood substrate spaced at 8" o.c. (203.20 mm).
Fabricate a counter-flashing enclosurefrom 24 gauge (0.61 mm) Pre-Finished Steel in an owner-approved color as shown below.
*= as required to span from behind vertical siding, over plywood vertical substrate and membrane flashing with 1/4" (6.4 mm) of clearance from membrane.
2"(50.8 mm)
3"(76.2 mm)
*"
1"(25.4 mm)
Original Metal Siding
New Counter-Flashing EnclosureFastened with neoprened washeredTek screws 12" o.c. (304.80 mm) through membrane into vertical substrate and at every recessed rib through siding and counter-flashing into wood nailers.
GenFlex EPDM
Wood nailer(s) as required to provide ananchor point for the loose siding cut in step 1" (25.40 mm) above and to secure the counter-flashing to. Fasten to purlin as required to achieve 200 lb (889.64 N) of pullout resistance per linear foot but with fasteners spaced no more than 24" (609.60 mm) apart.
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com666666EPDM Standard Details
Detail #: EMR-2.08A EPDM Metal RoofRecover SystemsMetal Roof Base Flashing
Secure acceptable vertical substrate material to metal siding, and ensure structural attachment (purlin) along at least two lines of securement.Overlay insulation must comply with minimum requirements called for to span openings in filler insulation and to comply with GenFlex Fully Adhered System requirements. Secure at the rate of one GenFlex #15 (WH) Fastener and Insulation Plate per 2 ft (0.19 m ), or 16 per 4' X 8' (1.22 m x 2.44 m).Filler insulation should be sized to fit snugly between ribs and of equal thickness to rib height. Wood nailers must be secured to purlins as required to achieve 200 lb (889.64 N) of pullout resistance per linear foot.
1.
2.
3.4.5.
6.
GenFlex EPDM Membrane
GenFlex Bonding Adhesive
Peel & Stick EPDM RPS secured at 12" o.c. (304.8 mm) with GenFast #15 (WH) Fastener and 2 3/8" (60.3 mm) Seam Plate
Overlay InsulationSee Note #2
Filler Insulation See Note #3
Wood NailersSee Note #4
Compression fit details that incorporate Water Stop must have all existing flashing removed to the bare substrate, e.g. masonryblock.Any approved pre-drilled fastener for curb and parapet terminations must have a minimum 125 lb (556.03 N) pullout. See approvedfastener list.
2
2
GenFlex EPDM Membrane
Continuous Metal Cleat
GenFlex Bonding Adhesive
Wood Nailer
Metal Coping
Or
For Interior Securement OnlyApproved Fasteners Spaced 12" (304.8 mm) o.c. with Neoprene Washeror Sealed with Caulk
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com 676767EPDM Standard Details
Detail #: EMR-2.08B EPDM Metal RoofRecover Systems
Metal Roof to Vertical SidingBase Flashing
Existing Condition
GenFlex EPDM Membrane
GenFlex EPDM Bonding Adhesive
5/8" (15.9 mm) Pressure Treated Exterior Grade Plywood or OSB.See Note #1
Peel & Stick EPDM RPS secured at 12" o.c. (304.8 mm) with GenFast #15 (WH) Fastener and 2 3/8" (60.3 mm) Seam Plate - See Note #5
Overlay InsulationSee Note #2
Filler Insulation See Note #3
For Vertical Termination of this Condition, See Detail EMR-1.13
Wood NailersSee Note #4
Secure acceptable vertical substrate material to metal siding, andensure structural attachment (purlin) along at least two lines of securement.Overlay insulation must comply with minimum requirements called for to span openings in filler insulation and to comply with GenFlex Fully Adhered System requirements. Secure at the rate of one GenFast #15 (WH) Fastener and Insulation Plate per 2 ft (0.2 m ).Filler insulation should be sized to fit snugly between ribs and of equal thickness to rib height. Wood Nailers must be secured to purlins as required to achieve 200 lb(889.6 N) of pullout resistance per linear foot. Using a GenFlex Scrub Pad & Handle, apply GenFlex Primer to the underside of the EPDM Membrane where it will bond with the Peel & Stick EPDM RPS.
1.
2.
3.
4.
5.
2 2
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com686868EPDM Standard Details
EPDM Metal RoofRecover Systems
Detail #:EMR-11.06
Position insulation to enable securement into the steel roofing panels to ensure positive attachment. Do not attach to the ribs. For fastener spacing criteria on projects with less than 300 lb (1 334.5 N) of pullout resistance, refer to the Pullout Value Matrix Table within the Metal Recover Specification. On projects with greater than 300 lb (1 334.5 N) of pullout resistance, reduced securement patterns may be applicable if minimum insulation thickness requirements are also met. Contact GenFlex Technical for information on reduced fastening patterns.
GenFlex ISO
GenFlex EPDM Membrane
Approved Filler Insulation
Refer to Detail E-6.01 for dimensions and layout requirements.
GenFlex Bonding Adhesive
Existing Metal Roof Panels
Fully Adhered Metal Recover SystemInsulation Cross Section
07/10GenFlex
Detail #: EMR-11.07
4'(1.2 m)
8'(2.4 m)
4' (1.2 m)
8"(203.2 mm)
4'(1.2 m)
4' (1.2 m)
Always stagger insulation joints,regardless of boardsize used.
For use on buildings up to 50' (15.2 m) high. If building heightexceeds 50' (15.2 m), contact the GenFlex Technical Department attachment pattern.
16"(406.4 mm)
16"(406.4 mm)
8"(203.2 mm)
16"(406.4 mm)
16"(406.4 mm)
8"(203.2 mm)
16"(406.4 mm)
16"(406.4 mm)
8"(203.2 mm)
16"(406.4 mm)
16"(406.4 mm)
Repeat pattern below
Fully Adhered Metal RecoverInsulation Securement
EPDM Metal RoofRecover Systems
07/10GenFlex
For current information and promotional literature refer to: www.genflex.com 696969EPDM Standard Details
Wood Blocking - Flute Blocking must be equal in height to the rib tops, edge blocking must be equal in height to the roof insulation and wider than the edge metalflange. All blocking must be installed in accordance withindustry standards and be capable of resisting 200 lb(889.6 N) of force per foot in any direction. See Note #2.Filler panels of insulation must be equal in height to the metal roof ribs and provide a smooth supporting surface for the overlay insulation board.
GenFlex ISO as required secured to the 26 gauge (0.45 mm) minimumsteel roof panels at the rate of one #15 fastener and insulation plate per 2 ft (0.2 m ), or 16 per 4' x 8' (1.2 m x 2.4 m) board. Fastener spacing is contingent upon metal roof achieving 300 lb (1 334.5 N) of pullout resistance. For pullout values less than 300 lb (1 334.5 N), refer to Pullout Value Matrix Table in the Metal Recover Fully Adhered System Specification. Reduced fastening patterns may be available if the project meets minimum insulation thickness and pullout value criteria. Contact GenFlex Technical for information on reduced insulation securement patterns.
Install the GenFlex Fully Adhered EPDM Roof System in accordance with current GenFlex requirements.
*NOTE: This assembly does not meet Factory Mutual Rating Criteria.
Metalwork may consist of drip edge if gutter is not desired. Metalwork must enclose end of roof system and completely cover nailer face. See Note #1.
Metalwork must be fabricated and installed in accordance with SMACNAand NRCA recommendations and include continuous metal cleats where applicable. Metalwork will completely enclose roof assembly ends and extend below the wood nailer face.Wood nailers are to be secured to the structural steel members as required to resist 200 lb (889.6 N) minimum of pullout force per linear foot.Additional metalwork may be required to seal off the roof edge effectively to prevent wind, birds, and pests from entering roof assembly.
1.
2.
3.
Detail #: EMR-14.01EPDM Metal RoofRecover SystemsMetal Edge Flashing
2 2
07/10GenFlex
Fasten GenFlex EPDM Membrane in to wood nailer, using approved fasteners spaced 12" o.c. (304.8 mm)
For current information and promotional literature refer to: www.genflex.com707070EPDM Standard Details
6" (152.4 mm)All sides
GenFlex FlexWhite Peel & Stick T-Joint Cover - See Note #2
GenFlex FlexWhite EPDM Membrane
07/10
Detail #: FW-6.10FlexWhite EPDM
Fully Adhered SystemsT-Joint / Seam
Intersection Cover
Approved Substrate
GenFlex ISO
GenFlex FlexWhite Seam Tape See Note #1
High Profile Bead of GenFlex FlexWhite Edge Caulk
GenFlex FlexWhite Clear Primer
1.
2.
When using GenFlex FlexWhite Seam Tape, first apply FlexWhite Clear Primer to the seaming area using a GenFlex Scrub Pad & Handle. Primer is required on both membrane surfaces to which the seam tape will bond.Apply GenFlex FlexWhite Edge Caulk around entire perimeter of GenFlex FlexWhite Peel & Stick T-Joint Cover and along seams for 6" (152.4 mm) past intersection. GenFlex
GenFlex FlexWhite Clear Primer
07/10
Installation of Walkway Pad
Installed sections of GenFlex TPO Walkway Pads should not exceed 10' (3.0 m) in length. Allow for a 4" (101.6 mm) space between ends of adjacent sections of walkway pad.
GenFlex TPO Heat Weldable Walkway PadSee Note #1
Detail #: FW-16.05 FlexWhite EPDMFully Adhered Systems
GenFlex
GenFlex FlexWhite EPDM Membrane
GenFlex FlexWhite Seam TapeSee Note #2
GenFlex FlexWhite Clear Primer
When using GenFlex FlexWhite Seam Tape, first apply FlexWhite Clear Primer to the FlexWhite EPDM field sheet and to the underside of the TPO Walkway Pad where the seam tape will bond. Apply the primer using a GenFlex Scrub Pad & Handle.
1.
2.