Smart Cabling InfrastructureSolutions for Data Centers
Smart Cabling InfrastructureSolutions for Data Centers
Constantin CiupercaProject ManagerGenesys Systems
Constantin CiupercaProject ManagerGenesys Systems
www.genesys4s.ro
AgendaAgenda
Data Center Infrastructure requirements
Smart Cabling Solutions for Data Center Infrastructures
www.genesys4s.ro
Strategic Division for Strategic Division for Complete Communication InfrastructuresComplete Communication Infrastructures
Tyco Electronics – Tyco Electronics – AMP NETCONNECTAMP NETCONNECT
www.genesys4s.ro
Data Center InfrastructureRequirements
Data Center InfrastructureRequirements
www.genesys4s.ro
CablingInfrastructure
IT Security
Control system
Raised floor
Air Conditioning & Ventilation
Systems
Early fireWarning system
Fire detectionFire
extinguishing
Water warning systems Access control
Monitoring&
InfrastructureManagement
Systems
Power Supply,UPS & Generator
Systems
Data Center – Data Center – Overview / SubsystemsOverview / Subsystems
www.genesys4s.ro
Main issues & concerns of Data Center Owners &
Operators
0,0% 5,0% 10,0% 15,0% 20,0% 25,0% 30,0% 35,0%
Power Consumption
Speed of Change
Cooling
Lack of standardization
Datacenter Management
Costs of Operation
Security
Power Shortage
High Density
Environmental concerns
Nothing in particular
(Source: Datacenter Dynamics)
Data Center – Data Center – What is important ?What is important ?
www.genesys4s.ro
Power supply and air conditioning have become the limiting factor for implementation of Data Centers.
Picture: Knürr
Data CenterData Center - Limiting Factors - Limiting Factors
www.genesys4s.ro
Sources: EYP Mission Critical Facilities, Cisco IT, Network World, Customer Interviews, APC
Reducing Data Center Power Consumption is a multi-faceted challenge. All areas need to be addressed to maximize data center compute capacity and minimize power costs.
Network Equip, 12%
Pwr Loss, 10%
Lighting, 3%
Cooling, 50%Server, 25%
Data Center – Data Center – Power ConsumptionPower Consumption
www.genesys4s.ro
Cold air pumped into plenum space beneath floor tiles and vented into cold aisles and returns through a ceiling plenum.
Data Center – Data Center – Airflow EfficiencyAirflow Efficiency
www.genesys4s.ro
Airflow is blocked by a fully loaded raised floor
For new buildings, cabling in the ceiling shall be considered for better management and improved airflow.
Cable trays
Cable trays
Cable trays
Cable trays
Cable trays
Cable trays
Power cables Power cables Power cables
Data Center – Data Center – Airflow & Cable PlacementAirflow & Cable Placement
www.genesys4s.ro
0
5
10
15
20
25
302
00
0
20
01
20
02
20
03
20
04
20
05
20
06
20
07
20
08
20
09
20
10
20
11
20
12
20
13
20
14
20
15
20
16
20
17
20
18
20
19
20
20
100M 1G 10G 40G 100G
mill
ion
s se
rver
un
its
Data Center – Data Center – Server TrendsServer Trends(1G, 10G, 40G and 100G)(1G, 10G, 40G and 100G)
Source: Intel & Broadcom
10 year transition for 1G Ethernet 6 years for 10GBE 5 years for 40GBE
www.genesys4s.ro
Comparison: Comparison: Office Cabling <> Data Center CablingOffice Cabling <> Data Center Cabling
Office Cabling: Static after installation Technology cycle: 5-10 years Lower density acceptable Downtimes less critical Physical environment
less important
Data Center Cabling: Dynamic Technology cycle: 3-5 years Highest density required Downtimes very critical Physical environment
very important
www.genesys4s.ro
Data Center – Data Center – Infrastructure RequirementsInfrastructure Requirements
Highest Reliability and Availability (= Quality).
High Infrastructure Performanceto support various kinds of services.
Shortest Deployment Time for Moves, Adds & Changes (MAC’s).
Highest Density of all equipment.
Redundancy
Support to save Power
Best possible control via Network and InfrastructureManagement (including reliable documentation).
www.genesys4s.ro
Smart Cabling Solutionsfor Data Center Infrastructures
Smart Cabling Solutionsfor Data Center Infrastructures
www.genesys4s.ro
EN 50173-5 Data Center Cabling
ISO/IEC 24764(created according EN 50173-5)
EIA/TIA 942 “Telecommunications Infrastructure Standards for Data Centers”
Data CenterData Center – – Relevant Standards Relevant Standards
www.genesys4s.ro
Ad-hoc growth and cabling Point to point cabling
Pathway confusion Documentation errors
Network Cabinets
Server Cabinets
Server Cabinets
Server Cabinets
Server Cabinets
More an evolution than a real planning fromthe beginning
Finally leading to a difficult to handle chaos !
Data CenterData Center – – Why standards ?Why standards ?
www.genesys4s.ro
Data CenterData Center – – Structure acc. StandardsStructure acc. Standards
MDAMDA
HDAHDA
EDAEDA
TelecommunicationRoom
www.genesys4s.ro
Data CenterData Center – – Structure & Cabling RequirementsStructure & Cabling Requirements
HDAHDA
EDAEDA
ZDAZDA
HC HC HC
MC
PrimaryEntrance Room
HC ScondaryEntrance Room
Access Providers
Access Providers
Access Providers
Offices, Operations CenterSupport Rooms
Telecom Room
Interconnect
Active Equip.Storage AreaDevices etc.
Interconnect
ActiveEquipment
Interconnect
ActiveEquipment
ActiveEquipment
Interconnect
Backbone Cabling
Backbone Cabling
Backbone Cabling
Horizontal Cabling
Horizontal Cabling
Horizontal Cabling
MDAMDA
Main DistributionArea (MDA)
Horizontal DistributionArea (HDA)
Equipment DistributionArea (EDA)
Optional:Zone DistributionArea (ZDA)
Highest Performance Cat. 6A / 7A or Fiber Optic
Density & Flexibility MRJ 21 MPO “Plug & Go”
www.genesys4s.ro
Complete Data Center SolutionsComplete Data Center Solutions
AMP NETCONNECT provide the complete
Cabling Infrastructure:
Classical High PerformanceCabling Systems
Data Center OptimizedPlug&Go Solutions“Smart Cabling for Data Centers”“Smart Cabling for Data Centers”
Cable Management Systems
ready to be integrated into Intelligent Infrastructure Management System (IIMS)
www.genesys4s.ro
Data Center Optimized SolutionsData Center Optimized Solutions“Smart Cabling for Data Centers”“Smart Cabling for Data Centers”
MRJ21, Σ-LinkΣ-Link & MPO Cabling Systems Shortest deployment time Fastest Moves, Adds & Changes 100% factory pre-tested Highest Density Easy to plan & design Re-useable AMPTRAC Ready
www.genesys4s.ro
Data Center Optimized – Pre-Terminated SolutionsData Center Optimized – Pre-Terminated Solutions
“AMP Σ-Link System”“AMP Σ-Link System”
Pre-Terminated Solutions based onBundled Cables & Cassettes.
Class FA (Cat.7A), Class EA (Cat.6A)Shielded Solutions
Class E (Cat.6) UTP Solution
www.genesys4s.ro
Special designed High Density Systems: Easy to install (just Plug & Go) Easy to change without interference of other channels 6 x 1000Base-T in one compact cable & interface Space saving Compact Pre-Terminated
Trunk Cables allow efficientairflow
Re-useable
Example: MRJ21 Plug&Go System
http://www.cisco.com/pcgi-bin/ctdp/displayProfile.pl?PARTNER_ID=59368
Data Center Optimized – Pre-Terminated SolutionsData Center Optimized – Pre-Terminated Solutions
MRJ21 SystemMRJ21 System
www.genesys4s.ro
Data Center Optimized - Pre-Terminated SolutionsData Center Optimized - Pre-Terminated Solutions MRJ21 Plug & Go SystemMRJ21 Plug & Go System
MRJ21 Panel to Panel configuration:
www.genesys4s.ro
MRJ21 System - MRJ21 System - ApplicationsApplications Compact, Flexible & Easy to manage Consistent Quality & Performance
www.genesys4s.ro
Fiber Optic Plug&Go System: Based on the industry standard MT-Ferrule 12 Fibers OM2, OM3, OM4 or Singlemode Cassettes for all important
Interfaces (LC, SC, MT-RJ) Compact & Consistent Quality
(100% Factory tested!) No installation errors AMPTRAC Ready!
Data Center Optimized – Pre-Terminated SolutionsData Center Optimized – Pre-Terminated Solutions
MPO Fiber Optic SystemMPO Fiber Optic SystemStandard MT
2.45mm
6.4mm
www.genesys4s.ro
ZDMD LDP EQENI
ISO/IEC 24764 model for Data CentersENI
Network access cabling
subsystem
Main distribution cabling
subsystem
Zone distribution cabling subsystem
MPO Next Generation Low LossMPO Next Generation Low Loss
MPOptimate MPOptimate SystemSystem
Insertion Loss: 0,35 dB/Cassette maximum != Best performing MPO System in the world market
www.genesys4s.ro
Benefits:
Fast Setup Time and MAC’s All Performance requirement (1/10/40/100 GBit) Pre-Tested Improved Cable Management Efficient Airflow Management
Data Center Optimized SolutionsData Center Optimized Solutions“Smart Cabling for Data Centers”“Smart Cabling for Data Centers”
www.genesys4s.ro
Unmanaged and unstructured connections No documentation 30-40% abandoned patch cords after
1 year of operation Dead ports in switches and cable
runs 30-40% unused capacity MAC time > 1h per port Adds up to 150% of operational cost Adds up to 200% of floorspace needed Heat sinks creation (blocking of air flow)
Poor Cable Management - Poor Cable Management - ConsequencesConsequences
www.genesys4s.ro
Hi-D – Hi-D – Cable Management PlatformCable Management Platform
Very high density Side Cable Management
saves space for horizontalmanagement
Requires 800mm Rack Compatible with all
Copper & Fiber Panels Controlled Bend Radius
= Easy access to eachPatchcord in caseof changes!
www.genesys4s.ro
www.genesys4s.ro
SystemBenefits:
Integrates all AMP NETCONNECTHigh Density Data Center Solutions(MPO, MRJ21 & Classical Cabling)
Visualizes & Documents complete Data Center Network(Updates all changes automatically)
Notifies all changes
= Increasing control over complex Data Center Infrastructures
= Reduction of Downtimes!
www.genesys4s.ro
System – Process overview
www.genesys4s.ro
Infrastructure Manager
www.genesys4s.ro
AMP NETCONNECT – Total Solution
www.genesys4s.ro
Data Center – Data Center – Green ITGreen IT
The AMP NETCONNECT Data CenterSolutions support the Green Initiative:
Re-duce Energy consumption= cost saving= preserves natural resources
Re-useable solutions= cost saving= preserves natural resources
Re-cycable solutionsUse only environmental friendly materials(RoHS compliant)
www.genesys4s.ro
It is worthwhile to invest into guaranteed Performance & Quality!
One Solution for Your Datacenter !One Solution for Your Datacenter !
www.genesys4s.ro
AMP NETCONNECT AMP NETCONNECT Data Center SolutionsData Center Solutions
Your Benefits
Unique Solution – optimized exactly for the special needsin a Data Center(we do not just try to implement office infrastructures into a data center – as many others do)
All changes in a data center (which happens often!) can be donein very short time – without interruption of other services.= maximized uptime!= highest flexibility
Space & Energy saving solution= $$$$ savings on operational costs= fast return on investment
Complete Management & Documentation Solution (AMPTRAC)= comes up with IT SM requirements from ITIL
www.genesys4s.ro
Thank You ! - Thank You ! - Questions ?Questions ?
A Solid Foundationfor Your
Communication Infrastructure