50
EAME/CIS TC Conf erence EP/Pet roleum - Malaga, October 200 7 Generator Insulation Testing TC Conference Malaga October 2007

Generator Testing

Embed Size (px)

Citation preview

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 1/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Generator Insulation Testing

TC Conference

Malaga

October 2007

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 2/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Agenda

• Purpose

• When to Test

• Safety

• Prepare for the Test

• The Tests

• Post Test

• References

• Other Tests

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 3/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Insulation Quality

• Insulation Degrades Due To:

 – Electrical Stress

 – Mechanical Stress

 – Chemical Attack

 – Thermal Stress

 – Environmental Contamination

 – Time

• Can be Measured >> Maintenance Tool

 – Insulation resistance as high as 55 GOhm

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 4/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Generator Insulation Testing purpose

• Manage the generator maintenance

• Determine the condition of the insulation

• Identify insulation systems in need of drying

• Identify potential future or immediate repair need

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 5/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

When is it Necessary to Test the Generator Insulation?

• After receipt of generator

 – Before storing

 – Before initial startup

 – This Is “The Base-Line”

• Prior to commissioning

 – Don’t commission if results are questionable!

• Prior to running after long period of no use

• After routine maintenance

• Periodically

• KEEP RECORDS of all test results

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 6/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Periodic Testing

• Annually in clean, controlled environment

• Quarterly in severe environments

 – High humidity

 – Water or snow ingestion

 – Smoke

 – Chemicals in air

 – Salty air (such as near the ocean)

 – Dusty environments (sand)

 – Construction debris

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 7/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Monitoring Operations

• Trending

 – Understand the Monitored Process

 – Normalized Readings

 – Record on Chart

 – Focus on Changes Occurring Over Time

• A plot of results over time

› Deterioration over time

› Abrupt changes from “normal”

» For example when moisture makes its way into thewindings

 – Scheduled Repairs Instead of Unplanned Downtime

• Requires normalized test results

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 8/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Safety

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 9/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Insulation Testing Safety Preparations

• People

 – Have multiple people present for testing

 – Electrical safety training !

 – Comply with all applicable safety standards

• For example IEEE510

 – First aid training !

• Before testing

 – Isolate the system to be tested

• Lock it out

 – Barricade around the generator to keep people away

 – Use personal protection devices – Dissipate stored energy before the test

• Short circuit the windings

› Use a grounding stick for high voltages

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 10/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Insulation Testing Safety

• During testing

 – External arcing can occur

• For example if bare conductor is too close to ground

• Stay clear of the test equipment, conductors, and item beingtested

• After testing

 – Dissipate the energy after the test

• Short circuit the windings

› Use a grounding stick for high voltages

• Leave short circuited for 5x to 10x test duration

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 11/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Pre-Test

• Understanding the test process

• Tester selection

• Testing voltage

• Temperature compensation

• Guard terminal

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 12/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Test Process

• READ instruction manual of your instrument for detailed instructions

 – Test safety is paramount

• Test Process

 – Apply a Test Voltage

• Less Than or Equal to Generator Operating Voltage

• Test Current Will Flow

 – Measure response

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 13/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Test Current Components

• Different processes cause insulation current to flow

• Leakage Current

 – High resistance in parallel with insulation capacitance

 – Reaches constant value quickly

• Polarization (absorption) Current

 – Electric field causes charges to align themselves to the field

 – Moisture & contamination has large impact

 – Duration in generators is usually minutes or more

• Capacitive Charging Current

 – Initially large, goes to zero

 – Duration relatively short but not insignificant

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 14/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Insulation Tester Selection

• Tester models available from multiple vendors

 – EAMC (Chauvin Arnoux)

 – Megger

 – Numerous others

 – Newer models are very portable

• Key things to look for

 – Adequate range

• At least to 100 GigaOhm (100,000 MegaOhm)

 – Preprogrammed, automatic tests

 – Test voltages

• 500 Vdc, 1,000 Vdc, 5,000 Vdc

 – Calibration program

 – Scheduled maintenance options

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 15/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Testing Voltage

• Test at a voltage near the rated voltage

 – Higher voltage

• Increases stress

• More likely to find weakness

• More expensive test as voltage goes up

• GM EMD study on their locomotive generators

 –  5k Vdc is sufficient

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 16/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Test Voltage Recommendations

• Main Stators

 – Low voltage generators (100 v – 500 v)

• Test at 500 Vdc

 – Low voltage generators (500 v – 1000 v)

• Test at 1,000 Vdc

 – Medium voltage generators (2,400 v – 7,200 v)

• Test at 5,000 Vdc

 – High voltage generators (10,000 v – 15,000 v)

• Test at 5,000 Vdc

• Can be tested at 10,000 Vdc

• Main rotors – Test at 500 Vdc

• Exciters (stator and rotor)

 – Test at 500 Vdc

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 17/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Three phase machine testing

• Preferred to test each phase separately

 – Significantly different results for each phase are a concern

• Can test three phases at once

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 18/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Interpreting the Results

• General result interpretation rules are included

• Result interpretations are device dependent

 – Test history

• Other vital information – Previous history of the machine

 – Careful visual inspection

 – Comparison with like devices in like circumstances

 – Log of previous testing

• Possible outcomes

 – Machine is returned to service

 – Schedule repairs – Clean, dry, retest

 – Repair immediately, retest

 – Replace machine

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 19/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Temperature Compensation

• Insulation resistance measurements are temperature dependent

• Normalize to a standard temperature

 – Typically either 25 °C or 40 °C

 – Get exact temperature coefficient from manufacturer• Rough estimate

› Resistance is cut by 50% for 10 °C increase intemperature

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 20/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Guard Terminal - Leakage Current

• Leakage currents in parallel with the insulation

 – Voltage tracking

 – Surface currents on exposed insulation

 – Can give false low resistance readings• Guard terminal connection

 – Part of instrument

 – Eliminates undesired currents

 – Must be isolated from other connections

• Guard against flashover

 – Usually connected to ground through a low impedanceconnection

• Older instruments may connect guard to high potentialthrough a low impedance!

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 21/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Flashover

• Be prepared for arcing

 – Not common but does happen

 – Will distort results if not prevented – Careful

• Internal arcing – Test failure

• External arcing

 – Bare conductors too close together or too close to ground

 – Voltage tracking on insulation?

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 22/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Insulation Quality Tests

• Visual Inspection

• Insulation resistance

• Polarization Index

• Dielectric Absorption Ratio• Dielectric Discharge

• Step Voltage

• Hi-pot

• Other tests (appendix)

 – Isothermal Relaxation Current (KDA test)

 – EDA Test

 – Power Factor Test

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 23/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Visual Inspection

• Quick Look at Appearance

 – Remove Terminal Box Panel

 – Look at Winding End Turns Using Flashlight

 – Can look at internals with boroscope• Indications

 – Cleanliness

 – Voltage Tracking

 – Visual Damage

• Black from arcing

• Discolored steel from overheating

• Cracking from multiple causes

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 24/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Basic insulation resistance

• Insulation resistance reading

 – Resistance

 – Temperature of insulation (windings)

• Or reference temperature if normalized – Length of time voltage applied before reading

• Document instrument used

 – Calibration

• This basic test should be done regularly

 – Use trend charts

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 25/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Insulation resistance – Test Considerations

• Insulation resistance measurements are temperature sensitive

 – Resistance measurements without the winding temperature aremeaningless!

• Use the resistance reading at same point in time – Suggest at 60 sec

• Allows for dissipation of short time constant currents

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 26/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Insulation resistance – 3-Phase Test Process

• 3-Phase testing – Lock out device under test

 – Discharge leads

 – Measure winding temperature

 – Disconnect the 3 phases from the load, PTs, ground (neutral side)

 – Connect the 3 phases together

 – Hook up tester – See tester instruction manual

• High side to the phase leads

• Low side to the core (laminations), steel frame, or rotor shaft

• Ground the frame

 – Apply voltage

 – Take reading - Typically after 60 sec – Discharge windings

• Tester may have provision for discharging

 – Disconnect

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 27/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Insulation resistance – 1-Phase Test Process

• 1-Phase testing – Lock out device under test

 – Discharge leads

 – Measure winding temperature

 – Disconnect the 3 phases from the load, PTs, ground (neutral side)

 – Connect the 2 phases not tested to the core, frame, or shaft

 – Hook up tester – See tester instruction manual

• High side to the phase lead

• Low side to the core (laminations), steel frame, or rotor shaft

• Ground the frame

 – Apply voltage

 – Take reading - Typically after 60 sec – Discharge windings

• Tester may have provision for discharging

 – Disconnect

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 28/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Insulation Resistance - Results Interpretation

• Interpretation of resistances corrected to 25 °C (or 40 °C)

 – Dry, new generator

• Very high resistance

• Typically higher than 1,000 MOhm (1 GOhm)› Can be as high as 50,000 MOhm (50 GOhm)

 – Used generator

• Anywhere from a few MOhm to many GOhm

 – Generator in questionable condition

• Significant decrease from readings when new

• Low MOhm readings

• Significant difference between phase readings

• Significant difference between component readings

› Main stator, main rotor, exciter stator, exciter rotor, PMGstator

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 29/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Polarization Index (PI)

• Measurement

 – The ratio of 10 min. reading to 1 min. reading

 – Valuable test if no historical readings are available

 – Sensitive to moisture in or contamination of Insulation• Indicates

 – Moisture Content of the Insulation

 – Good Indicator of the Drying Process

• Will not indicate the failure of an insulation layer in a multi-layerinsulation

• Does not work if there is no absorption current

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 30/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

PI Results Interpretation

• PI > 6

 – Very good

 – Usually only seen when

winding system is new• Newer designs

 – 1.5 < PI < 6

• Normal range

 – PI < 1.5• Significant moisture in

the windings

• Failure may occur at

any time• Recommend to clean

and dry immediately

• Older designs

 – 2 < PI < 6

• Normal range

 – PI < 2• Significant moisture in

the windings

• Failure may occur at

any time• Recommend to clean

and dry immediately

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 31/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Dielectric Absorption Ratio (DAR)

• Similar to Polarization Index

• Time at measurements different

 – One typical combination is 60 sec divide by 30 sec reading

• > 1.4 is good• Interpretation more difficult because currents may not have

stabilized

• Far less common than Polarization Index

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 32/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Dielectric Discharge (DD)

• Measurement

 – Insulation is Charged to Stable Condition

 – Insulation Discharge Current is Measured

• Voltage & Capacitance also measured – Dielectric Discharge = I1 min / (V * C)

• Indicates

 – Moisture Content

 – Internal Damage to a Single Insulation Layer

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 33/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

DD Results Interpretation

• DD > 7

 – Layer of multilayer insulation is damaged

• 4 < DD < 7

 – Questionable, damage may be possible• 2 < DD < 4

 – Poor

• DD < 2

 – Good

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 34/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Step Voltage

• Measurement

 – Response to Increasing Voltage Steps

 – Differences in Response Between Increasing Voltage Steps

• Indicates – Local Weak Spots

 – Response Changes as Electrical Stress is Increased

• Comments

 – Use trend analysis.

 – Used for medium or high voltage windings

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 35/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Step Voltage Results Interpretation

• Traces for subsequent voltage steps overlay each other

 – Good, no layer damage

• Significant differences between traces

 – One or more damaged layers

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 36/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Hi-Pot Test

• NOT RECOMMENDED

 – Not recommended due to high stress placed on windings

 – Already Hi-Pot tested at the factory

 – Wet insulation system increases likelihood of failure• Potentially destructive test!

 – Pass / Fail

• Indicates condition under high stress conditions

• Test failure means repairs are mandatory! And may be expensive.

• Test

 – DC Voltage, between rated and twice rated, slowly ramped up

 – Applied for typically 1 min

 – Turned off immediately in case of arcing (failure)

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 37/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Post-Test

• Discharging

• Cleanup

• Record keeping

• Insulation drying• Insulation repairs

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 38/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Discharging

• Tester may have provision for discharging the windings – Use it

• Recommend using a ground-stick for discharging

 – Has built-in resistance to limit surges and voltage/current

reflections – Should be used if testing at higher voltages

• Short circuit for 5x to 10x test time

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 39/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Cleanup

• Clean up the test site

• Remove the lockout only after test location is completely safe

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 40/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Record Keeping

• Keep a permanent record of all testing

• Use charts to uncover trends

• Records can be used as reference for other tests

• Will help in diagnosing failures

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 41/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Insulation Drying

• Follow manufacturer drying instructions

• Apply heat to raise generator temperature above ambient

• Heating insulation too fast will lead to steam formation

 –  Keep winding temperature below 100 °C – Steam expands Causes cracks in insulation

• Retest to verify drying success

• Drying may take days

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 42/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Insulation Repairs

• Repair will be required if drying does not sufficiently raise theinsulation resistance and polarization index

• Repairs must be undertaken by qualified generator / motor repair (orrewind) shop

• Repairs

 – Deep clean & drying

• Repair shop can frequently do a more thorough cleaning at

their facility – Local insulation replacement

• MAIA uses a rewind shop with true repair artists in Sardinia

 – Rewind

• Be sure the rewind shop can handle the type of generator• Rewind quality is critical

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 43/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Summary

• Insulation testing is a predictive maintenance tool

• Tracking results over time helps identify problems before they occur

• Good tests are available even if no history exists

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 44/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

References - AEMC

• AEMC Instruments Inc.

» www.aemc.com

» Chauvin Arnoux Inc

 – “Understanding Insulation Resistance Testing” 02/06 rev 02 – “Dielectric Discharge (DD) Testing” 08/02

 – “Poor Man’s Step Voltage Testing” 09/03

 – “Megohmmeter 5050/5060 User Manual” 03/07

 – “Megohmmeter 5070 User Manual” 06/07

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 45/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

References – Megger® 

• Megger Group Ltd

» www.megger.com

» www.biddlemegger.com (distributor site with information)

 – “5kV Testing. How Much Is Enough?”

• Utility Products Showcase © 2002

 – “Insulation Testing Large Rotating Machines”

 – “Advanced Insulation Analysis Using Megger Insulation Testers”

 – “Salvaging Flood Damaged Electrical Equipment”

 – “Choosing a Megger Insulation Tester”

 – “The Lowdown On High-Voltage DC Testing” November 2002 Rev B

 – “A Guide To Diagnostic Insulation Testing Above 1kV” June 2002

 – “’A Stitch in Time…’ The Complete Guide to Electrical Insulation

Testing” June 1992 – “MIT1020 10kV Digital Insulation Tester User Manual”

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 46/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

References - Standards

• IEEE 43

• IEEE 510

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 47/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Other Tests

• Not commonly performed in the field

• Power factor test

 – Also Tan Delta Test

 – Used on generators, generally not in the field• EDA

 – Advanced instruments

• Isothermal relaxation current

 – Used on cables

P F T

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 48/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Power Factor Test

• Also Known as Tan Delta Test

• Measurement

 – Changes in Power Factor or Loss Angle

 – Bulky Test Equipment

• Difficult for Field Testing

• Indicates – Small Changes in Insulation Condition

EDA T t

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 49/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

EDA Test

• Measurement

 – Combines Insulation Resistance, Polarization Index, andDielectric Discharge Tests

• Indicates

 – Same as Above Mentioned Tests

 – Software is Used to Calculate Additional Indicators

I th l R l ti C t

7/14/2019 Generator Testing

http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 50/50

EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007

Isothermal Relaxation Current

• KDA test

• Applied to Cables

 – Use with Generators is Unknown

• Measurement – Measures Discharge Current

 – Using Modeling, Standard Discharge Shapes Are Curve Fit toDetermine Time Constants

• Indicates – Time Constants Correlate to Cable Insulation Aging