Upload
zamani-mahdi
View
93
Download
1
Embed Size (px)
Citation preview
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 1/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Generator Insulation Testing
TC Conference
Malaga
October 2007
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 2/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Agenda
• Purpose
• When to Test
• Safety
• Prepare for the Test
• The Tests
• Post Test
• References
• Other Tests
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 3/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Insulation Quality
• Insulation Degrades Due To:
– Electrical Stress
– Mechanical Stress
– Chemical Attack
– Thermal Stress
– Environmental Contamination
– Time
• Can be Measured >> Maintenance Tool
– Insulation resistance as high as 55 GOhm
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 4/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Generator Insulation Testing purpose
• Manage the generator maintenance
• Determine the condition of the insulation
• Identify insulation systems in need of drying
• Identify potential future or immediate repair need
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 5/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
When is it Necessary to Test the Generator Insulation?
• After receipt of generator
– Before storing
– Before initial startup
– This Is “The Base-Line”
• Prior to commissioning
– Don’t commission if results are questionable!
• Prior to running after long period of no use
• After routine maintenance
• Periodically
• KEEP RECORDS of all test results
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 6/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Periodic Testing
• Annually in clean, controlled environment
• Quarterly in severe environments
– High humidity
– Water or snow ingestion
– Smoke
– Chemicals in air
– Salty air (such as near the ocean)
– Dusty environments (sand)
– Construction debris
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 7/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Monitoring Operations
• Trending
– Understand the Monitored Process
– Normalized Readings
– Record on Chart
– Focus on Changes Occurring Over Time
• A plot of results over time
› Deterioration over time
› Abrupt changes from “normal”
» For example when moisture makes its way into thewindings
– Scheduled Repairs Instead of Unplanned Downtime
• Requires normalized test results
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 8/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Safety
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 9/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Insulation Testing Safety Preparations
• People
– Have multiple people present for testing
– Electrical safety training !
– Comply with all applicable safety standards
• For example IEEE510
– First aid training !
• Before testing
– Isolate the system to be tested
• Lock it out
– Barricade around the generator to keep people away
– Use personal protection devices – Dissipate stored energy before the test
• Short circuit the windings
› Use a grounding stick for high voltages
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 10/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Insulation Testing Safety
• During testing
– External arcing can occur
• For example if bare conductor is too close to ground
• Stay clear of the test equipment, conductors, and item beingtested
• After testing
– Dissipate the energy after the test
• Short circuit the windings
› Use a grounding stick for high voltages
• Leave short circuited for 5x to 10x test duration
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 11/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Pre-Test
• Understanding the test process
• Tester selection
• Testing voltage
• Temperature compensation
• Guard terminal
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 12/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Test Process
• READ instruction manual of your instrument for detailed instructions
– Test safety is paramount
• Test Process
– Apply a Test Voltage
• Less Than or Equal to Generator Operating Voltage
• Test Current Will Flow
– Measure response
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 13/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Test Current Components
• Different processes cause insulation current to flow
• Leakage Current
– High resistance in parallel with insulation capacitance
– Reaches constant value quickly
• Polarization (absorption) Current
– Electric field causes charges to align themselves to the field
– Moisture & contamination has large impact
– Duration in generators is usually minutes or more
• Capacitive Charging Current
– Initially large, goes to zero
– Duration relatively short but not insignificant
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 14/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Insulation Tester Selection
• Tester models available from multiple vendors
– EAMC (Chauvin Arnoux)
– Megger
– Numerous others
– Newer models are very portable
• Key things to look for
– Adequate range
• At least to 100 GigaOhm (100,000 MegaOhm)
– Preprogrammed, automatic tests
– Test voltages
• 500 Vdc, 1,000 Vdc, 5,000 Vdc
– Calibration program
– Scheduled maintenance options
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 15/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Testing Voltage
• Test at a voltage near the rated voltage
– Higher voltage
• Increases stress
• More likely to find weakness
• More expensive test as voltage goes up
• GM EMD study on their locomotive generators
– 5k Vdc is sufficient
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 16/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Test Voltage Recommendations
• Main Stators
– Low voltage generators (100 v – 500 v)
• Test at 500 Vdc
– Low voltage generators (500 v – 1000 v)
• Test at 1,000 Vdc
– Medium voltage generators (2,400 v – 7,200 v)
• Test at 5,000 Vdc
– High voltage generators (10,000 v – 15,000 v)
• Test at 5,000 Vdc
• Can be tested at 10,000 Vdc
• Main rotors – Test at 500 Vdc
• Exciters (stator and rotor)
– Test at 500 Vdc
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 17/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Three phase machine testing
• Preferred to test each phase separately
– Significantly different results for each phase are a concern
• Can test three phases at once
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 18/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Interpreting the Results
• General result interpretation rules are included
• Result interpretations are device dependent
– Test history
• Other vital information – Previous history of the machine
– Careful visual inspection
– Comparison with like devices in like circumstances
– Log of previous testing
• Possible outcomes
– Machine is returned to service
– Schedule repairs – Clean, dry, retest
– Repair immediately, retest
– Replace machine
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 19/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Temperature Compensation
• Insulation resistance measurements are temperature dependent
• Normalize to a standard temperature
– Typically either 25 °C or 40 °C
– Get exact temperature coefficient from manufacturer• Rough estimate
› Resistance is cut by 50% for 10 °C increase intemperature
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 20/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Guard Terminal - Leakage Current
• Leakage currents in parallel with the insulation
– Voltage tracking
– Surface currents on exposed insulation
– Can give false low resistance readings• Guard terminal connection
– Part of instrument
– Eliminates undesired currents
– Must be isolated from other connections
• Guard against flashover
– Usually connected to ground through a low impedanceconnection
• Older instruments may connect guard to high potentialthrough a low impedance!
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 21/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Flashover
• Be prepared for arcing
– Not common but does happen
– Will distort results if not prevented – Careful
• Internal arcing – Test failure
• External arcing
– Bare conductors too close together or too close to ground
– Voltage tracking on insulation?
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 22/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Insulation Quality Tests
• Visual Inspection
• Insulation resistance
• Polarization Index
• Dielectric Absorption Ratio• Dielectric Discharge
• Step Voltage
• Hi-pot
• Other tests (appendix)
– Isothermal Relaxation Current (KDA test)
– EDA Test
– Power Factor Test
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 23/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Visual Inspection
• Quick Look at Appearance
– Remove Terminal Box Panel
– Look at Winding End Turns Using Flashlight
– Can look at internals with boroscope• Indications
– Cleanliness
– Voltage Tracking
– Visual Damage
• Black from arcing
• Discolored steel from overheating
• Cracking from multiple causes
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 24/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Basic insulation resistance
• Insulation resistance reading
– Resistance
– Temperature of insulation (windings)
• Or reference temperature if normalized – Length of time voltage applied before reading
• Document instrument used
– Calibration
• This basic test should be done regularly
– Use trend charts
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 25/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Insulation resistance – Test Considerations
• Insulation resistance measurements are temperature sensitive
– Resistance measurements without the winding temperature aremeaningless!
• Use the resistance reading at same point in time – Suggest at 60 sec
• Allows for dissipation of short time constant currents
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 26/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Insulation resistance – 3-Phase Test Process
• 3-Phase testing – Lock out device under test
– Discharge leads
– Measure winding temperature
– Disconnect the 3 phases from the load, PTs, ground (neutral side)
– Connect the 3 phases together
– Hook up tester – See tester instruction manual
• High side to the phase leads
• Low side to the core (laminations), steel frame, or rotor shaft
• Ground the frame
– Apply voltage
– Take reading - Typically after 60 sec – Discharge windings
• Tester may have provision for discharging
– Disconnect
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 27/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Insulation resistance – 1-Phase Test Process
• 1-Phase testing – Lock out device under test
– Discharge leads
– Measure winding temperature
– Disconnect the 3 phases from the load, PTs, ground (neutral side)
– Connect the 2 phases not tested to the core, frame, or shaft
– Hook up tester – See tester instruction manual
• High side to the phase lead
• Low side to the core (laminations), steel frame, or rotor shaft
• Ground the frame
– Apply voltage
– Take reading - Typically after 60 sec – Discharge windings
• Tester may have provision for discharging
– Disconnect
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 28/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Insulation Resistance - Results Interpretation
• Interpretation of resistances corrected to 25 °C (or 40 °C)
– Dry, new generator
• Very high resistance
• Typically higher than 1,000 MOhm (1 GOhm)› Can be as high as 50,000 MOhm (50 GOhm)
– Used generator
• Anywhere from a few MOhm to many GOhm
– Generator in questionable condition
• Significant decrease from readings when new
• Low MOhm readings
• Significant difference between phase readings
• Significant difference between component readings
› Main stator, main rotor, exciter stator, exciter rotor, PMGstator
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 29/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Polarization Index (PI)
• Measurement
– The ratio of 10 min. reading to 1 min. reading
– Valuable test if no historical readings are available
– Sensitive to moisture in or contamination of Insulation• Indicates
– Moisture Content of the Insulation
– Good Indicator of the Drying Process
• Will not indicate the failure of an insulation layer in a multi-layerinsulation
• Does not work if there is no absorption current
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 30/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
PI Results Interpretation
• PI > 6
– Very good
– Usually only seen when
winding system is new• Newer designs
– 1.5 < PI < 6
• Normal range
– PI < 1.5• Significant moisture in
the windings
• Failure may occur at
any time• Recommend to clean
and dry immediately
• Older designs
– 2 < PI < 6
• Normal range
– PI < 2• Significant moisture in
the windings
• Failure may occur at
any time• Recommend to clean
and dry immediately
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 31/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Dielectric Absorption Ratio (DAR)
• Similar to Polarization Index
• Time at measurements different
– One typical combination is 60 sec divide by 30 sec reading
• > 1.4 is good• Interpretation more difficult because currents may not have
stabilized
• Far less common than Polarization Index
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 32/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Dielectric Discharge (DD)
• Measurement
– Insulation is Charged to Stable Condition
– Insulation Discharge Current is Measured
• Voltage & Capacitance also measured – Dielectric Discharge = I1 min / (V * C)
• Indicates
– Moisture Content
– Internal Damage to a Single Insulation Layer
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 33/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
DD Results Interpretation
• DD > 7
– Layer of multilayer insulation is damaged
• 4 < DD < 7
– Questionable, damage may be possible• 2 < DD < 4
– Poor
• DD < 2
– Good
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 34/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Step Voltage
• Measurement
– Response to Increasing Voltage Steps
– Differences in Response Between Increasing Voltage Steps
• Indicates – Local Weak Spots
– Response Changes as Electrical Stress is Increased
• Comments
– Use trend analysis.
– Used for medium or high voltage windings
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 35/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Step Voltage Results Interpretation
• Traces for subsequent voltage steps overlay each other
– Good, no layer damage
• Significant differences between traces
– One or more damaged layers
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 36/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Hi-Pot Test
• NOT RECOMMENDED
– Not recommended due to high stress placed on windings
– Already Hi-Pot tested at the factory
– Wet insulation system increases likelihood of failure• Potentially destructive test!
– Pass / Fail
• Indicates condition under high stress conditions
• Test failure means repairs are mandatory! And may be expensive.
• Test
– DC Voltage, between rated and twice rated, slowly ramped up
– Applied for typically 1 min
– Turned off immediately in case of arcing (failure)
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 37/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Post-Test
• Discharging
• Cleanup
• Record keeping
• Insulation drying• Insulation repairs
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 38/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Discharging
• Tester may have provision for discharging the windings – Use it
• Recommend using a ground-stick for discharging
– Has built-in resistance to limit surges and voltage/current
reflections – Should be used if testing at higher voltages
• Short circuit for 5x to 10x test time
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 39/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Cleanup
• Clean up the test site
• Remove the lockout only after test location is completely safe
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 40/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Record Keeping
• Keep a permanent record of all testing
• Use charts to uncover trends
• Records can be used as reference for other tests
• Will help in diagnosing failures
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 41/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Insulation Drying
• Follow manufacturer drying instructions
• Apply heat to raise generator temperature above ambient
• Heating insulation too fast will lead to steam formation
– Keep winding temperature below 100 °C – Steam expands Causes cracks in insulation
• Retest to verify drying success
• Drying may take days
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 42/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Insulation Repairs
• Repair will be required if drying does not sufficiently raise theinsulation resistance and polarization index
• Repairs must be undertaken by qualified generator / motor repair (orrewind) shop
• Repairs
– Deep clean & drying
• Repair shop can frequently do a more thorough cleaning at
their facility – Local insulation replacement
• MAIA uses a rewind shop with true repair artists in Sardinia
– Rewind
• Be sure the rewind shop can handle the type of generator• Rewind quality is critical
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 43/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Summary
• Insulation testing is a predictive maintenance tool
• Tracking results over time helps identify problems before they occur
• Good tests are available even if no history exists
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 44/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
References - AEMC
• AEMC Instruments Inc.
» www.aemc.com
» Chauvin Arnoux Inc
– “Understanding Insulation Resistance Testing” 02/06 rev 02 – “Dielectric Discharge (DD) Testing” 08/02
– “Poor Man’s Step Voltage Testing” 09/03
– “Megohmmeter 5050/5060 User Manual” 03/07
– “Megohmmeter 5070 User Manual” 06/07
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 45/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
References – Megger®
• Megger Group Ltd
» www.megger.com
» www.biddlemegger.com (distributor site with information)
– “5kV Testing. How Much Is Enough?”
• Utility Products Showcase © 2002
– “Insulation Testing Large Rotating Machines”
– “Advanced Insulation Analysis Using Megger Insulation Testers”
– “Salvaging Flood Damaged Electrical Equipment”
– “Choosing a Megger Insulation Tester”
– “The Lowdown On High-Voltage DC Testing” November 2002 Rev B
– “A Guide To Diagnostic Insulation Testing Above 1kV” June 2002
– “’A Stitch in Time…’ The Complete Guide to Electrical Insulation
Testing” June 1992 – “MIT1020 10kV Digital Insulation Tester User Manual”
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 46/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
References - Standards
• IEEE 43
• IEEE 510
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 47/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Other Tests
• Not commonly performed in the field
• Power factor test
– Also Tan Delta Test
– Used on generators, generally not in the field• EDA
– Advanced instruments
• Isothermal relaxation current
– Used on cables
P F T
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 48/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Power Factor Test
• Also Known as Tan Delta Test
• Measurement
– Changes in Power Factor or Loss Angle
– Bulky Test Equipment
• Difficult for Field Testing
• Indicates – Small Changes in Insulation Condition
EDA T t
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 49/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
EDA Test
• Measurement
– Combines Insulation Resistance, Polarization Index, andDielectric Discharge Tests
• Indicates
– Same as Above Mentioned Tests
– Software is Used to Calculate Additional Indicators
I th l R l ti C t
7/14/2019 Generator Testing
http://slidepdf.com/reader/full/generator-testing-56327b4f73d71 50/50
EAME/CIS TC Conference EP/Petroleum - Malaga, October 2007
Isothermal Relaxation Current
• KDA test
• Applied to Cables
– Use with Generators is Unknown
• Measurement – Measures Discharge Current
– Using Modeling, Standard Discharge Shapes Are Curve Fit toDetermine Time Constants
• Indicates – Time Constants Correlate to Cable Insulation Aging