1 Generator Breaker Failure Applications Christopher Dall, Dennis Tierney Calpine Corporation

Generator Breaker Failure Applications · PDF file2 • Overview of Standards discussing breaker failure for generator applications • Case studies – CT location – Flashover protection

  • Upload
    letruc

  • View
    221

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Generator Breaker Failure Applications · PDF file2 • Overview of Standards discussing breaker failure for generator applications • Case studies – CT location – Flashover protection

1

Generator Breaker Failure ApplicationsChristopher Dall, Dennis Tierney

Calpine Corporation

Page 2: Generator Breaker Failure Applications · PDF file2 • Overview of Standards discussing breaker failure for generator applications • Case studies – CT location – Flashover protection

2

• Overview of Standards discussing breaker failure for generator applications

• Case studies– CT location– Flashover protection– Noise and instantaneous re-trip– Breaker lockouts– Current detectors (exciters online or offline)

Contents

Page 3: Generator Breaker Failure Applications · PDF file2 • Overview of Standards discussing breaker failure for generator applications • Case studies – CT location – Flashover protection

3

• Two main standards to consider:– IEEE Std C37-102– IEEE Std C37-119

• Breaker failure has two classifications:– Failure to Trip (e.g. mechanical issues)– Failure to Clear (e.g. loss of dielectric, flashover)

Overview of BF for generator applications

Page 4: Generator Breaker Failure Applications · PDF file2 • Overview of Standards discussing breaker failure for generator applications • Case studies – CT location – Flashover protection

4

• Other situations not classified as Breaker Failure (C37.119)– Loss of dielectric– Contact flashover

• Given the potential damage to a generator these situations should be considered in a breaker failure scheme.

Overview of BF for generator applications

Page 5: Generator Breaker Failure Applications · PDF file2 • Overview of Standards discussing breaker failure for generator applications • Case studies – CT location – Flashover protection

5

Minimum fault current scheme (C37-119)

Overview of BF for generator applications

Page 6: Generator Breaker Failure Applications · PDF file2 • Overview of Standards discussing breaker failure for generator applications • Case studies – CT location – Flashover protection

6

Flashover protection scheme (C37-102)

Overview of BF for generator applications

Page 7: Generator Breaker Failure Applications · PDF file2 • Overview of Standards discussing breaker failure for generator applications • Case studies – CT location – Flashover protection

7

• Consider all possible fault locations…

Case 1 – Current transformer location

Page 8: Generator Breaker Failure Applications · PDF file2 • Overview of Standards discussing breaker failure for generator applications • Case studies – CT location – Flashover protection

8

Case 1 – Current transformer location

Page 9: Generator Breaker Failure Applications · PDF file2 • Overview of Standards discussing breaker failure for generator applications • Case studies – CT location – Flashover protection

9

• After the BFI has de-asserted necessary to re-enable breaker failure scheme for flashovers

Case 2 – Flashover protection

GSU High Side Currents

GSU Low Side Currents

GSU NeutralCurrent

Page 10: Generator Breaker Failure Applications · PDF file2 • Overview of Standards discussing breaker failure for generator applications • Case studies – CT location – Flashover protection

10

Case 2 – Flashover protection

*Current detector must be set sensitively enough to declare breaker failure

Page 11: Generator Breaker Failure Applications · PDF file2 • Overview of Standards discussing breaker failure for generator applications • Case studies – CT location – Flashover protection

11

• Consideration for flashover protection:

1. Use separate 52a and 52b contacts (i.e. do not invert 52a)

2. Implement a 52 contact disagreement scheme3. Ring bus and breaker and a half schemes should

require both 52b contacts to enable• Susceptible to tripping for transmission LG faults

Case 2 – Flashover protection

Page 12: Generator Breaker Failure Applications · PDF file2 • Overview of Standards discussing breaker failure for generator applications • Case studies – CT location – Flashover protection

12

• For latched BFI signals or instantaneous re-trips noise can cause nuisance tripping

Case 3 – Noise on Breaker Failure Initiate

Page 13: Generator Breaker Failure Applications · PDF file2 • Overview of Standards discussing breaker failure for generator applications • Case studies – CT location – Flashover protection

13

Case 3 – Noise on BFI and instantaneous re-trip

*62BFI + 62BF = total breaker failure time

Page 14: Generator Breaker Failure Applications · PDF file2 • Overview of Standards discussing breaker failure for generator applications • Case studies – CT location – Flashover protection

14

Case 4 – Circuit breaker lockouts

• Circuit breakers may have alarms which will block them from opening– Low spring charge– Low gas (SF6) pressure

• In the event of a protective trip we must declare a breaker failure if we know the circuit breaker is blocked from opening.

Page 15: Generator Breaker Failure Applications · PDF file2 • Overview of Standards discussing breaker failure for generator applications • Case studies – CT location – Flashover protection

15

Case 4 – Circuit breaker lockouts

Page 16: Generator Breaker Failure Applications · PDF file2 • Overview of Standards discussing breaker failure for generator applications • Case studies – CT location – Flashover protection

16

• Depending on the system conditions when the generator circuit breaker is required to open the currents can vary drastically– System fault– Problem at minimal load

• If the breaker fails and the turbine and exciter have been tripped the generator will be motored potentially causing serious damage to the rotor, stator and turbine.

Case 5 – Current detector pickup

Page 17: Generator Breaker Failure Applications · PDF file2 • Overview of Standards discussing breaker failure for generator applications • Case studies – CT location – Flashover protection

17

• Example of unbalanced currents on generator after breaker failure

Case 5 – Current detector pickup

IN101TRIP1OUT101

Page 18: Generator Breaker Failure Applications · PDF file2 • Overview of Standards discussing breaker failure for generator applications • Case studies – CT location – Flashover protection

18

Case 5 – Current detector pickup

Simplified Sequence network for two‐phase flashoverGSU High Side Currents

GSU Neutral Currents

GSU Low Side Currents

Ibsys – base current on system voltageIbase – base current on generator voltage

Page 19: Generator Breaker Failure Applications · PDF file2 • Overview of Standards discussing breaker failure for generator applications • Case studies – CT location – Flashover protection

19

• If the exciter remains online after the failed GCB is opened then the current magnitudes can be undetectable on the GSU high voltage side

Case 6 – Detection with exciter online

Page 20: Generator Breaker Failure Applications · PDF file2 • Overview of Standards discussing breaker failure for generator applications • Case studies – CT location – Flashover protection

20

Case 6 – Detection with exciter online

GCB Trip Signal SWYD CB Opens

0

25

50

75

100

125

0

500

1000

1500

2000

2500

Current (referred to 345 kV)

Current (referred to 18 kV)

Time

A (18 kV @gen)A (345 kV @SWYD)Min 50BF Pickup

Measured current 

Minimum Pickup for 50BF in switchyard relay

Page 21: Generator Breaker Failure Applications · PDF file2 • Overview of Standards discussing breaker failure for generator applications • Case studies – CT location – Flashover protection

21

Case 6 – Detection with exciter online

GCB Trip Signal Exciter Tripped SWYD CB Opens

0

50

100

150

200

250

300

350

0

500

1000

1500

2000

2500

3000

3500

4000

Current (referred to 345 kV)

Current (referred to 18 kV)

Time

A (18 kV @gen)A (345 kV @SWYD)Min. 50BF Pickup

Measured current 

Minimum Pickup for 50BF in switchyard relay

Page 22: Generator Breaker Failure Applications · PDF file2 • Overview of Standards discussing breaker failure for generator applications • Case studies – CT location – Flashover protection

22

Case 6 – Detection with exciter online

GCB Trip Signal

SWYD CB Opens

‐10

‐5

0

5

10

15

20

25

30Generator MW/M

VAr

Time

MWMVArRev. Power (MW) PUReverse power element 

pickups

Page 23: Generator Breaker Failure Applications · PDF file2 • Overview of Standards discussing breaker failure for generator applications • Case studies – CT location – Flashover protection

23

Case 6 – Detection with exciter online

GCB Trip Signal Exciter Tripped SWYD CB Opens

‐60

‐40

‐20

0

20

40

60Generator MW/M

VAr

Time

MWMVArRev. Power (MW) Pickup

Reverse power element pickups

Page 24: Generator Breaker Failure Applications · PDF file2 • Overview of Standards discussing breaker failure for generator applications • Case studies – CT location – Flashover protection

24

Case 6 – Detection with exciter online

Page 25: Generator Breaker Failure Applications · PDF file2 • Overview of Standards discussing breaker failure for generator applications • Case studies – CT location – Flashover protection

25

• Locate Current transformers on the circuit breaker

• Desensitize the scheme to noise

• Special considerations for flashover protection

• Current detectors based on motoring events

• Use of reverse power element to detect failure

Conclusions

Page 26: Generator Breaker Failure Applications · PDF file2 • Overview of Standards discussing breaker failure for generator applications • Case studies – CT location – Flashover protection

26

• Power plant operators should have defined procedures in the event that a breaker failure of a GCB goes undetected by the protection.

Conclusions