44
Generation and Control of Vacuum in Furnace P M V Subbarao Professor Mechanical Engineering Department Safe and Efficient Combustion Needs Appropriate Furnace Pressure…

Generation and Control of Vacuum in Furnace

Embed Size (px)

DESCRIPTION

Furnace pressure

Citation preview

PowerPoint Presentation

Generation and Control of Vacuum in FurnaceP M V SubbaraoProfessorMechanical Engineering DepartmentSafe and Efficient Combustion Needs Appropriate Furnace Pressure

Development of Air & Flow Circuits

Pa

where p1 = total pressure drop from the furnace outlet to the dust collector, Pa p2 = pressure drop after the dust collector, Pa = ash content in the glue gas, kg/kg pa v = average pressure of the gas, Pa pg o = flue gas density at standard conditions, kg/Nm3

Total gas side pressure dropThe ash fraction of the flue gas calculated as,

where f h = ratio of fly ash in flue gas to total ash in the fuelA = ash content of working mass, %Vg = average volume of gas from furnace to dust collector calculated from the average excess air ratio, Nm3/kg of fuel

The pressure drop from the balance point of the furnace to the chimney base is

prest = pexit + pgas Dpnd

where pexit = pressure drop up to the boiler outlet

DpPercent Boiler RatingFurnace, SH & RH LossesEconomizer LossesDucts & dampers lossesDraught LossesTotal losses

ID fan power calculationID fan power is calculated as:

DpPercent Boiler RatingBurner LossesAPH LossesDucts & dampers lossesAir Pressure LossesTotal losses

FD FanDuct APH DuctFurnaceDuctAPHBack passESPIDFanChimneyDuctDuctModeling of 210 MW Draught SystemPressure drop calculation in air & gas path and its comparison with design value.Assessment of ID and FD fan power as a function of furnace pressure.Important variables along air and gas path

Pressure Variation

DuctFD Fan Duct SCAPHAPHDuctWindBoxBoilerAPHESPID FanOff Design Pressure VariationPressure Variation in Air & Gas Path at Part Load-2000-1500-1000-50005001000150020002500123456789101112Path ElementPressure (Pa)Calculated (168 MW)Design (168 MW)ID FanESPBoilerAPHWindBoxDuctAPHDuctSCAPHDuct FD Fan

Operational Data of 210 MW plant

Effect of Furnace Vacuum on Boiler Efficiency

The net effect is saving in energy of 117.32 kW due to increase in furnace vacuum from 58.9 Pa to 230.6 Pa.New Ideas for Future Research FD FanDuct APH DuctFurnaceDuctAPHBack passESPIDFanChimneyDuctDuctAnalysis of Flue Gas at the ID Fan InletPartial pressure of each constituent in flue gas, pCO2 = 16.366209 kPapO2 = 1.138404 kPaPN2 = 68.142138 kPapSO2 = 0.036081 kPapH2O = 13.363218 kPa Mass flow rate of each constituent in tons/hour is:Mass flow rate of O2 in the flue gas =13.2867 tphMass flow rate of CO2 in the flue gas = 262.646 tphMass flow rate of N2 in the flue gas = 695.893 tphMass flow rate of SO2 in the flue gas = 0.84219 tphMass flow rate of H20 in the flue gas = 118.33 tph

Energy Audit of Flue Gas Temperature of flue gas = 136 C 150oCDew point of water is (obtained based on partial pressure of 0.1336 bar) 51.59 CCooling of the exhaust gas below the dew point will lead to continuous condensation of water vapour and reduction of flue gas volume and mass. The temperature of the flue gas in order to remove x% of the available moisture can be obtained using partial pressures of water.

Energy Potential of Flue Gas with 10% water RecoveryFlue gas constituentsPartial pressure at 136 C in kPaEnthalpy* at 136 C (KJ/kg)Mass flow rate of each constituent at 136 C ( kg/s)Enthalpy*at 49.74 C KJ/kgMass flow rate of each constituent at 49.74 C ( kg/s)Total thermal power released (MW)CO216.37606.323.69075527.853.690.2895O21.11374.4372.957229472.95.8678N268.14425193.303335.09193.317.3797S020.0364870.23413430.550.23410.0132H2013.36275232.8694259130.44411.57635.1270Energy Potential of Flue Gas with 100% water RecoveryFlue gas constituentsPartial pressure at 136 C in kPaEnthalpy* at 136 C (KJ/kg)Mass flow rate of each constituent at 136 C ( kg/s)Enthalpy at 0 C (kJ/Kg)Mass flow rate at 0 C ( kg/s)Total thermal power released (MW)CO216.366209606.323.69075485.833.690.444698O21.138404374.4372.9572248.3572.959.198452N268.142138425193.303283.32193.327.38828S020.0360814870.23413399.580.23410.020468H2013.363218275232.86942501090.45671127.5086Model Experimentation

Expected Performance of the heat exchangerCooling capacity of the heat exchanger = 10 kWCooling load available with the heat exchanger = 115.3 kJ/kg of flue gasAvailable rate of condensation of the present heat exchanger = 37.85gms/kg of flue gas. Experimental validation Flue Gas heat exchanger measured data:

DATEFLUE GASI/L JUST OUTSIDE ID DUCTFLUE GASI/L TO HEAT EXCHANGERFLUE GASO/L TO HEAT EXCHANGERWATERI/L TO HEAT EXCHANGERWATERO/L TO HEAT EXCHANGERDPWATER FLOWQTY. OF WATER CONDENSEDTemp Ccm WCLPMlt. /Hr.1.2.10103603029305121.11.2.10105653231325100.92.2.10121693130315121.12.2.10121823231324.2121Calculation of Flue Gas Flow Rate

Dp (cm)Tin 0CDensity (kg/m3)Flow rate (kg/sec)5601.0517540.0071595651.0362030.0071065691.0240890.0070654.2820.9866040.006355Gas Flow rate (kg/sec)Mesured condensatekg/hrMesured condensateg/secCondensate loading (gms/kg of gas)0.0071591.10.30555642.678640.0071060.90.2535.179940.0070651.10.30555643.251260.00635510.27777843.70829Design rate of condensate loading using present heat exchanger = 37.85gms/kg of flue gas.Calculation of Condensate Flow rateCombustion and Draught ControlThe control of combustion in a steam generator is extremely critical.Maximization of operational efficiency requires accurate combustion.Fuel consumption rate should exactly match the demand for steam.The variation of fuel flow rate should be executed safely.The rate of energy release should occur without any risk to the plant, personal or environment.

Furnace Draught

The ControlFurnace (draft) pressure control is used in balanced draft furnaces in order to regulate draft pressure. Draft pressure is affected by both the FD and ID fans. The FD fan is regulated by the combustion control loop, and its sole function is to provide combustion air to satisfy the firing rate. The ID fan is regulated by the furnace pressure control loop and its function is to remove combustion gases at a controlled rate such that draft pressure remains constant. Furnace Draught Control

Windbox Pressure Control

Combustion Prediction & Control The Model for Combustion Control

Parallel Control of Fuel & Air Flow Rate

Flow Ratio Control : Fuel Lead

Flow Ratio Control : Fuel Lead

Cross-limited Control System

Oxygen Trimming of Fuel/air ratio Control

Combined CO & O2 Trimming of Fuel/Air Ratio Control

Resistance to Air & Gas Flow Through Steam Generator System