GENERAL STRUCTURAL NOTES

GENERAL: DETAILS AND SECTIONS SHOWN ON THE DRAWINGS ARE TYPICAL AND APPLY TO SIMILAR SITUATIONS ELSEWHERE, EXCEPT AS OTHERWISE INDICATED.ADAPT REQUIREMENTS OF DETAILS, SECTIONS, PLANS, AND NOTES AT LOCATIONS WHERE CONDITIONS ARE SIMILAR.

CENTER ALL FOOTINGS UNDER COLUMNS UNLESS SPECIFICALLY DIMENSIONED OTHERWISE.

STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH JOB SPECIFICATIONS AND ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, AND SITEDRAWINGS. CONSULT THESE DRAWINGS FOR SLEEVES, DEPRESSIONS, AND OTHER DETAILS NOT SHOWN ON STRUCTURAL DRAWINGS.

CONTRACTOR SHALL LOCATE ALL BURIED UTILITIES PRIOR TO EXCAVATION FOR BUILDING FOUNDATIONS. THE STRUCTURAL ENGINEER SHALL BE NOTIFIED OFPOTENTIAL CONFLICTS BETWEEN FOUNDATIONS AND BURIED UTILITIES.

GENERAL CONTRACTOR: DO NOT SCALE DRAWINGS. COORDINATE DIMENSIONS BETWEEN STRUCTURAL AND ARCHITECTURAL DRAWINGS. NOTIFY STRUCTURALENGINEER AND ARCHITECT OF ANY DISCREPANCIES BEFORE PROCEEDING WITH WORK.

CODE REQUIREMENTS: THE BUILDING STRUCTURE IS DESIGNED IN ACCORDANCE WITH THE 2010 EDITION OF THE FLORIDA BUILDING CODE. FOLLOW ALL APPLICABLEPROVISIONS FOR ALL PHASES OF CONSTRUCTION.

TEMPORARY CONDITIONS: THE STRUCTURAL INTEGRITY OF THE COMPLETED STRUCTURE DEPENDS ON INTERACTION OF VARIOUS CONNECTED COMPONENTS.PROVIDE ADEQUATE BRACING, SHORING, AND OTHER TEMPORARY SUPPORTS AS REQUIRED TO SAFELY COMPLETE THE WORK. THE STRUCTURE SHOWN ON THEDRAWINGS HAS BEEN DESIGNED FOR STABILITY UNDER FINAL CONFIGURATION ONLY.

RETAINING WALLS WHICH TIE TO UPPER SLABS SHALL NOT BE BACKFILLED UNTIL THE UPPER SLABS REACH FULL STRENGTH, UNLESS ADEQUATE BRACING ISPROVIDED AT THE TOP OF THE WALL.

DESIGN CRITERIA: DESIGN WAS BASED ON STRENGTH AND DEFLECTION CRITERIA OF THE 2010 FLORIDA BUILDING CODE. IN ADDITION TO THE DEAD LOADS, THEFOLLOWING LOADS AND ALLOWABLES WERE USED FOR DESIGN, WITH LIVE LOADS REDUCED PER THE 2010 FBC:

ROOF: 20 PSF LL 30 PSF SDLFLOORS:

OFFICES 50 PSF LL 20 PSF SLLSLEEPING ROOMS 40 PSF LL 20 PSF SLLLOBBIES, PUBLIC ROOMS 100 PSF LLCORRIDORS, STAIRS 100 PSF LLSTORAGE ROOMS 125 PSF LL

NOTE: LOADINGS ABOVE INCLUDES 5 PSF FOR SPRINKLER PIPING

WIND SPEED 200 MPH (ULT) / 155 MPH (ASD)EXPOSURE CRISK CATEGORY IVINTERNAL PRESSURE COEFF +/-0.18 ENCLOSED (PROTECTED OPENINGS)

SOIL BEARING PRESSURE 3,000 PSF ALLOWABLE PER SOILS REPORT BY PSI, DATED JULY 20, 2009.

FOUNDATIONS: FOUNDATIONS ARE DESIGNED IN ACCORDANCE WITH THE RECOMMENDATIONS OF THE SOILS REPORT PROVIDED BY PSI, DATED JULY 20, 2009. THECONTRACTOR SHALL ALSO FOLLOW THE RECOMMENDATIONS OF THE REPORT TO ENSURE THAT THE STRUCTURAL DESIGN REQUIREMENTS ARE ACHIEVED FOR THEFOUNDATIONS, INCLUDING THE ROCK ANCHORS. GROUNDWATER LEVELS FLUCTUATE SEASONALLY AND THEREFORE SHOULD BE VERIFIED AT THE TIME OFCONSTRUCTION TO DETERMINE IF THERE WILL BE ANY IMPACT ON CONSTRUCTION PROCEDURE.

SUBMITTALS: SHOP DRAWINGS SHALL BE SUBMITTED TO THE ARCHITECT PRIOR TO FABRICATION AND CONSTRUCTION REGARDING ALL STRUCTURAL ITEMSINCLUDING THE FOLLOWING: CONCRETE MIX DESIGNS, CONCRETE REINFORCING, EMBEDDED STEEL ITEMS, STRUCTURAL STEEL, AND STEEL DECK .

IF THE SHOP DRAWINGS DIFFER FROM OR ADD TO THE DESIGN OF THE STRUCTURAL DRAWINGS, THEY SHALL BEAR THE SEAL AND SIGNATURE OF A STRUCTURALENGINEER REGISTERED IN THE STATE OF FLORIDA. ANY CHANGES TO THE STRUCTURAL DRAWINGS SHALL BE SUBMITTED TO THE ARCHITECT AND ARE SUBJECT TOTHE REVIEW AND ACCEPTANCE BY THE ENGINEER.

DESIGN DRAWINGS, SHOP DRAWINGS, AND CALCULATIONS FOR THE DESIGN AND FABRICATION OF ITEMS THAT ARE DESIGNED BY OTHERS, INCLUDING:ARCHITECTURAL/STRUCTURAL PRECAST PANELS, PRECAST CONCRETE MEMBERS, PRESTRESSED CONCRETE MEMBERS, STAIRS, COLD FORMED METAL STUDS,PREMANUFACTURED METAL TRUSSES, SKYLIGHTS, WINDOW WALL AND ALL OTHER GLAZING SYSTEMS, SHALL BEAR THE SEAL AND SIGNATURE OF A STRUCTURALENGINEER REGISTERED IN THE STATE OF FLORIDA, AND SHALL BE SUBMITTED TO THE ARCHITECT PRIOR TO FABRICATION. CALCULATIONS SHALL BE INCLUDED FORALL CONNECTIONS TO THE STRUCTURE, CONSIDERING LOCALIZED EFFECTS ON THE STRUCTURAL ELEMENTS INDUCED BY THE CONNECTION LOADS. DESIGN SHALLBE BASED ON THE REQUIREMENTS OF THE 2010 FBC.

SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGN INTENT OF THE CONTRACT DOCUMENTS ONLY. IT SHALL BE THERESPONSIBILITY OF THE CONTRACTOR TO VERIFY COMPLIANCE WITH THE CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC.CONTRACTOR SHALL NOT BE RELIEVED FROM RESPONSIBILTY FOR ERRORS OR OMISSIONS IN SHOP DRAWINGS OR MIX DESIGNS BY THE ENGINEER’S REVIEW.

CONCRETE AND PRECAST CONCRETE: REINFORCED CONCRETE CONSTRUCTION SHALL CONFORM TO THE FBC AND ACI 318 "BUILDING CODE REQUIREMENTS FORREINFORCED CONCRETE". CONCRETE STRENGTHS SHALL BE VERIFIED BY STANDARD 28-DAY CYLINDER TESTS PER ASTM C39, AND SHALL BE AS FOLLOWS:

f’c ABS W/C MIN CEMENT SLUMP USE3000 PSI 0.58 470 LBS 5” +/- 1 FOUNDATIONS4000 PSI 0.44 550 LBS 4”+/- 1 ALL USES, U.N.O.5000 PSI 0.40 630 LBS 3” +/- 1 PRECAST**

** PROVIDE CORROSION-INHIBITING ADMIXTURE WHERE PERMANENTLY EXPOSED TO WEATHER OR EARTH.WATER USED FOR CONRETE MIXES SHALL BE CLEAN AND POTABLE.

CEMENT SHALL CONFORM TO ASTM C150, TYPE 1. FLY ASH CONFORMING TO ASTM C618, TYPE F OR TYPE C, MAY BE USED TO REPLACE UP TO 20% OF THE CEMENTCONTENT, PROVIDED THAT THE MIX STRENGTH IS SUBSTANTIATED BY TEST DATA AND COLOR HAS BEEN APPROVED BY THE ARCHITECT. COARSE AGGREGATESHALL CONFORM TO ASTM C33 WITH A MAXIMUM SIZE OF 3/4". FINE AGGREGATE SHALL BE CLEAN, DURABLE, NATURAL SAND CONFORMING TO ASTM C33.

A WATER-REDUCING ADMIXTURE CONFORMING TO ASTM C494, USED IN STRICT ACCORDANCE WITH THE MANUFACTURER’S RECOMMENDATIONS, SHALL BEINCORPORATED IN CONCRETE DESIGN MIXES. A HIGH-RANGE WATER-REDUCING ADMIXTURE CONFORMING TO ASTM C494, TYPE F OR G, MAY BE USED IN CONCRETEMIXES, PROVIDING THAT THE SLUMP DOES NOT EXCEED 8”.

SLEEVES, OPENINGS, CONDUIT, AND OTHER EMBEDDED ITEMS NOT SHOWN ON THE STRUCTURAL DRAWINGS SHALL BE APPROVED BY THE STRUCTURAL ENGINEERBEFORE POURING. NO SLEEVE, OPENING, OR INSERT MAY BE PLACED IN BEAMS, JOISTS, OR COLUMNS UNLESS APPROVED BY THE ENGINEER. CONDUITSEMBEDDED IN SLABS SHALL NOT BE LARGER IN OUTSIDE DIMENSION THAN ONE THIRD OF THE THICKNESS OF THE SLAB AND SHALL NOT BE SPACED CLOSER THANTHREE DIAMETERS ON CENTER.

PROVIDE 3/4” CHAMFERS ON ALL EXPOSED CONCRETE EDGES, UNLESS NOTED OTHERWISE. WHERE INDICATED OR REQUIRED, SLOPE CONCRETE SLABS TO DRAINSSHOWN ON PLUMBING AND/OR ARCHITECTURAL DRAWINGS. SLOPE TO COMPLY WITH ADA REQUIREMENTS.

ALL CONCRETE SHALL BE CURED IMMEDIATELY AFTER FINISHING OPERATIONS.

WEATHER RESISTANCE: ALL CONCRETE, INCLUDING BALCONY CONCRETE, EXPOSED TO CHLORIDES SHALL CONTAIN A CALCIUM-NITRITE BASED CORROSION-INHIBITING ADMIXTURE. THE DOSAGE FOR CONCRETE EXPOSED TO AIRBORNE CHLORIDES SHALL BE MINIMUM TWO GALLONS PER CUBIC YARD. THE WATERCONTAINED IN THE CORROSION-INHIBITING ADMIXTURE SHALL BE USED IN THE CALCULATION OF THE WATER-TO-CEMENTITIOUS RATIO OF THE CONCRETE.

CONCRETE BALCONIES OR OTHER CONCRETE FLAT SURFACES EXPOSED TO THE WEATHER THROUGHOUT THE LIFE OF THE BUILDING, SHALL BE TREATED WITH ACLEAR NONFLAMMABLE PENETRATING SEALER OF THE ALKYL-ALKOXY SILANE CLASSIFICATION, SUCH AS SONNEBORN PENETRATING SEALER 20, HYDROZOENVIROSEAL 20, OR OTHER APPROVED WEATHER RESISTANT SYSTEM. APPLICATION AND SURFACE PREPARATION SHALL BE IN ACCORDANCE WITHMANUFACTURER'S SPECIFICATIONS.

SHORING AND RESHORING: SHORING AND RESHORING SHALL CONFORM TO ACI 347R-01. SHORING AND SUPPORTING FORMWORK SHALL NOT BE REMOVED FROMHORIZONTAL MEMBERS BEFORE CONCRETE STRENGTH IS AT LEAST 70 PERCENT OF DESIGN STRENGTH, AS DETERMINED BY FIELD CURE CYLINDERS. IN ADDITION,SHORING SHALL NOT BE REMOVED SOONER THAN RECOMMENDED BY ACI 347R-01, SECTION 3.7.2.3. FORMWORK SHALL NOT BE REMOVED IN LESS THAN TEN (10)DAYS.

REINFORCING STEEL: REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 60, FOR DEFORMED BARS AND ASTM A185 FOR SMOOTH WELDED WIRE FABRIC(WWF), UNLESS OTHERWISE NOTED. REINFORCING STEEL TO BE WELDED SHALL CONFORM TO ASTM A706. REINFORCING STEEL SHALL BE SECURELY TIED INPLACE WITH #16 ANNEALED IRON WIRE.

ALL DETAILING AND ACCESSORIES SHALL CONFORM TO ACI DETAILING MANUAL SP-66. PROVIDE CHAIRS, SPACERS, BOLSTERS, AND ITEMS IN CONTACT WITH FORMSWITH HOT-DIP GALVANIZED LEGS OR PLASTIC LEGS. ACCURATELY POSITION, SUPPORT, AND SECURE REINFORCEMENT AGAINST DISPLACEMENT BY FORMWORKCONSTRUCTION OR CONCRETE PLACEMENT OPERATIONS. "WET-STICKING" OF REINFORCING IS PROHIBITED.

REQUIRED CONCRETE COVER FOR REINFORCING STEEL (UNLESS NOTED OTHERWISE):PILES 2" SIDESFOOTINGS 3" BOTTOM AND SIDES, 2" TOPSLABS 3/4"COLUMNS 1-1/2" TO TIES, 2" TOPBEAMS 1-1/2" TO STIRRUPSWALLS 1-1/2”

LAP SPLICE CONTINUOUS VERTICAL OR HORIZONTAL BARS IN CONCRETE MEMBERS IN ACCORDANCE WITH ACI 318, LATEST EDITION, FOR CLASS "B" TENSION LAPSPLICES. DO NOT SPLICE CONTINUOUS TOP BARS IN BEAMS AT ENDS OF CLEAR SPANS. DO NOT SPLICE CONTINUOUS BOTTOM BARS IN BEAMS IN CLEAR SPANSBETWEEN SUPPORTS. SHOW ALL SPLICES ON SHOP DRAWINGS. SPLICE LOCATIONS AND METHODS SUBJECT TO APPROVAL OF STRUCTURAL ENGINEER.

AT SLAB AND WALL OPENINGS PROVIDE A MINIMUM OF (2) #5 BARS ALL FOUR SIDES AND DIAGONALLY; EXTEND THESE BARS A LAP DISTANCE OR A MINIMUM OF 24”PAST THE OPENING OR HOOK BARS IF DISCONTINUOUS.

DOWEL ALL WALLS AND COLUMNS TO FOOTINGS WITH BAR SIZE AND SPACING TO MATCH VERTICAL REINFORCING UNLESS OTHERWISE SHOWN.

CONCRETE ACCESSORIES: HEADED SHEAR STUDS SHALL BE NELSON HEADED ANCHORS (BASIS OF DESIGN) WITH FLUXED ENDS OR APPROVED EQUAL. DEFORMEDBAR ANCHORS (DBA) SHALL BE NELSON, TYPE D2L, OR APPROVED EQUAL. STUDS AND DBA SHALL BE AUTOMATICALLY END WELDED WITH THE MANUFACTURER'SSTANDARD EQUIPMENT IN ACCORDANCE WITH THEIR RECOMMENDATIONS. HAND WELDING NOT PERMITTED.

PERMANENTLY EXPOSED EMBEDDED PLATES AND ANGLES SHALL BE HOT-DIPPED GALVANIZED AFTER FABRICATION, MINIMUM G90. ACCURATELY POSITION,SUPPORT, AND SECURE EMBEDDED ITEMS AGAINST DISPLACEMENT BY FORMWORK CONSTRUCTION OR CONCRETE PLACEMENT OPERATIONS. SECURELY ATTACHEMBEDDED ITEMS TO FORMWORK PRIOR TO START OF CONCRETE PLACEMENT. “WET-STICKING" OF EMBEDDED ITEMS IS PROHIBITED. NO LOADS OR WELDS SHALLBE PLACED ON EMBEDDED PLATES OR ANGLES FOR A MINIMUM OF 7 DAYS AFTER CASTING.

WHERE NEW CONCRETE IS PLACED AGAINST EXISTING CONCRETE, THE EXISTING CONCRETE SURFACE SHOULD BE CLEANED AND ROUGHENED TO A MINIMUM 1/4”AMPLITUDE.

HOLLOW-CORE SLABS: PRESTRESSED CONCRETE HOLLOW-CORE SLABS WITH COMPOSITE TOPPING, WHERE SHOWN ON PLANS, SHALL BE DESIGNED INACCORDANCE WITH ACI 318. COMPOSITE HOLLOW-CORE SLABS SHALL BE DESIGNED TO SUPPORT THE SELFWEIGHT OF THE COMPOSITE SYSTEM, INDICATEDSUPERIMPOSED DEAD AND LIVE LOADS, AND ADDITIONAL UNIFORM AND CONCENTRATED LOADS INDICATED ON DRAWINGS.

SUBMIT COMPLETE SHOP DRAWINGS AND CALCULATIONS, SIGNED AND SEALED BY A STRUCTURAL ENGINEER LICENSED IN THE STATE OF FLORIDA, SUBSTANTIATINGALL STRENGTH AND SERVICEABILITY CRITERIA.

PRECAST DOUBLE TEES: FLOOR DECKS SHOWN ON THE STRUCTURAL DRAWINGS SHALL CONSIST OF PRESTRESSED CONCRETE DOUBLE TEES ON PRECASTCONCRETE BEAMS AND COLUMNS. THE SYSTEM SHALL BE DESIGNED AND DETAILED BY THE MANUFACTURER TO SUPPORT THE SELF WEIGHT OF THE MEMBERS,INDICATED SUPERIMPOSED DEAD AND LIVE LOADS, AND ADDITIONAL UNIFORM AND CONCENTRATED LOADS INDICATED ON DRAWINGS.

SUBMIT COMPLETE SHOP DRAWINGS AND CALCULATIONS, SIGNED AND SEALED BY A STRUCTURAL ENGINEER LICENSED IN THE STATE OF FLORIDA, SUBSTANTIATINGALL STRENGTH AND SERVICEABILITY CRITERIA.

STRUCTURAL ANCHORING: WEDGE STYLE ANCHORS SHALL BE USED IN SOLID CONCRETE APPLICATIONS. WEDGE ANCHORS ARE A ONE-PIECE STUD ANCHOR WITHSTEEL CLIP (EXPANDING RING) CONFORMING TO FEDERAL SPECIFICATION FF-S-325, GROUP II, TYPE 4, CLASS I. ANCHORS SHALL BE TESTED TO ASTM E488 AND ICBOACOI. ICBO AND/OR SBCCI CODE COMPLIANCE ARE REQUIRED IN APPROPRIATE AREAS. MIAMI-DADE COMPLIANCE AND FLORIDA PRODUCT APPROVAL COMPLIANCEARE REQUIRED IN FLORIDA. ACCEPTED ANCHORS ARE ITW RED HEAD TRUBOLTS, HILTI KWIK-BOLT III OR ENGINEER APPROVED SUBSTITUTION.

CARBON STEEL ANCHORS SHALL BE ZINC PLATED IN ACCORDANCE WITH ASTM B633 OR MECHANICALLY GALVANIZED ACCORDING TO ASTM B695 (CLASS 65).PERMANENTLY EXPOSED ANCHORS SHALL BE MECHANICALLY GALVANIZED OR STAINLESS STEEL. USE 316 STAINLESS STEEL FOR SERVICING EQUIPMENT AND FORALUMINUM AND FIBERGLASS STRUCTURES AND ASSEMBLIES.

CHEMICAL ADHESIVE ANCHORING AND DOWELING TO CONCRETE: ADHESIVE ANCHORS (EPOXY STYLE) SHALL BE USED IN SOLID CONCRETE OR GROUT-FILLEDAPPLICATIONS FOR STRUCTURAL ANCHORING AND REBAR DOWELING. ANCHORS SHALL BE TESTED TO ASTM E488 AND ICBO AC58. ICBO AND/OR SBCCI CODECOMPLIANCE IS REQUIRED IN APPROPRIATE AREAS. MIAMI-DADE COMPLIANCE AND FLORIDA PRODUCT APPROVAL COMPLIANCE ARE REQUIRED IN FLORIDA.ACCEPTED PRODUCTS ARE ITW RED HEAD. GRANITE 5, ACRYLIC 7, ALLIED A1000+, BRINKER BROWN 20/20 OR ENGINEER APPROVED SUBSTITUTION.

ADHESIVE SHALL BE MOISTURE INSENSITIVE. (ALLOWING INSTALLATIONS IN DAMP OR WATER-FILLED HOLES). ADHESIVE SHALL HAVE A FULL-CURE LOAD OF 2HOURS OR LESS AT 70°F OR SAFETY ISSUES.

THREADED STUDS SHALL CONFORM TO ASTM A36 (STANDARD CARBON STEEL), UNLESS NOTED OTHERWISE. PERMANENTLY EXPOSED STUDS SHALL BE STAINLESSSTEEL. NUTS AND WASHERS SHALL CONFORM TO SAME SPECIFICATION AS THE SUPPLIED ANCHOR RODS.

INSTALLATION SHALL BE IN CONFORMANCE WITH MANUFACTURER'S PRINTED LITERATURE. INSTALLATION SHALL ALSO INCLUDE BRUSHING AND CLEANING OF DRILLEDHOLES WITH COMPRESSED AIR AS INSTRUCTED. INSTALLERS SHALL BE TRAINED BY THE MANUFACTURER'S REPRESENTATIVE. EMBEDMENT SHALL BE AS INDICATEDON THE STRUCTURAL DRAWINGS.

MASONRY WALLS: MASONRY UNITS SHALL MEET ASTM C90, TYPE 2. ASSEMBLIES SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF f’m= 1500. MORTAR SHALLBE TYPE "M" OR "S" AND MEET ASTM C270. GROUT SHALL BE 2000 PSI MINIMUM COMPRESSIVE STRENGTH AND MEET ASTM C476. GROUT SHALL CONSIST OF AMIXTURE OF CEMENTITIOUS MATERIALS AND AGGREGATE TO WHICH SUFFICIENT WATER HAS BEEN ADDED TO CAUSE THE MIXTURE TO FLOW WITHOUTSEGREGATION OF THE CONSTITUENTS. ALL CELLS CONTAINING VERTICAL BARS, BOND BEAMS, AND ALL CELLS BELOW GRADE SHALL BE FILLED WITH GROUT.MAXIMUM HEIGHT OF GROUT POUR ALLOWED IS 4'-0" UNLESS CLEAN-OUT OPENING IS PROVIDED AT BOTTOM OF CELLS TO BE FILLED. LOCATE CLEAN-OUT OPENINGSIN AREAS NOT EXPOSED TO VIEW.

UNLESS NOTED OTHERWISE EIGHT INCH MASONRY WALLS SHALL BE PARTIALLY REINFORCED MASONRY WALL CONSTRUCTION WITH #5 AT 24 INCH O.C. IN GROUTFILLED CELLS. ADD (1) #5 REINFORCING BAR EACH SIDE OF OPENINGS EXCEEDING 3 FEET.

PROVIDE REINFORCING BARS AT CORNERS, INTERSECTIONS, AND EACH SIDE OF OPENINGS. PROVIDE (2) REINFORCING BARS EACH SIDE OF OPENINGS OVER 4FEET WIDE, AND AS SHOWN ON THE PLANS. PROVIDE HOOKED DOWELS INTO FOOTINGS AND STRUCTURE ABOVE AND/OR BELOW TO PROVIDE CONTINUITY.PROVIDE 9 GAGE GALVANIZED HORIZONTAL JOINT REINFORCING (DUR-O-WAL OR ENGINEER-APPROVED EQUAL) AT 16” O.C.

DO NOT PLACE CONDUITS, PIPES, ETC., IN CELLS WITH VERTICAL REINFORCING. DO NOT RUN CONDUITS, PIPES, ETC., HORIZONTALLY IN CMU WALLS PARALLEL TOLENGTH OF WALL. WHERE MASONRY WALLS ABUT CONCRETE COLUMNS TO BE PLACED PRIOR TO ERECTION OF MASONRY WALLS, PROVIDE DOVETAIL SLOTSBETWEEN COLUMN AND WALLS AND GROUT THE CMU CELL CONTAINING THE DOVETAIL ANCHORS. OTHERWISE, EXTEND CMU HORIZONTAL JOINT REINFORCINGTHROUGH CONCRETE COLUMN.

CONTROL JOINTS SHALL BE PROVIDED IN ALL CONCRETE MASONRY CONSTRUCTION AT LOCATIONS INDICATED ON THE ARCHITECTURAL DRAWINGS. HORIZONTALWALL REINFORCING SHALL BE STOPPED EACH SIDE OF CONTROL JOINTS. SEE ARCHITECTURAL DRAWINGS FOR SEALANT REQUIREMENTS AT CONTROL JOINTS.

USE METAL LATH OR WIRE SCREEN FOR CAVITY CAPS. SHEET METAL, FELT, BUILDING PAPER, OR LIKE MATERIALS ARE PROHIBITED.

TIE BEAMS: TIE BEAMS SHALL BE CONCRETE, POURED AFTER THE BLOCK WALLS BELOW ARE IN PLACE. REINFORCING SHALL BE CONTINUOUS THROUGH TIEBEAMS WITH MINIMUM LAP SPLICES OF 48 BAR DIAMETERS AND BENT BARS AT CORNERS. USE METAL LATH, MORTAR, OR SPECIAL UNITS TO CONFINE CONCRETETO AREA REQUIRED, IN ACCORDANCE WITH ACI 530.1, SECTION 3.5 B. SOLID METAL OR FELT CAVITY CAPS ARE PROHIBITED.

PRECAST CONCRETE LINTELS: UNLESS INDICATED OTHERWISE, ALL LINTELS TO BE "U" TYPE PRECAST CONCRETE UNITS EQUAL TO UNITS MANUFACTURED BY CAST-CRETE CORP. AND PRESTRESSED (AND ADDITIONALLY REINFORCED AS REQUIRED) IN ACCORDANCE WITH CAST-CRETE CORP. ''DESIGN MANUAL", LATEST EDITION,FOR THE SPAN AND LOADING CONDITION RELATIVE TO LINTEL LOCATION.

LINTEL SIZE IF NOT SHOWN ON THE PLANS SHALL BE 8F8-1B FOR OPENINGS LESS THAN 10 FEET AND 8F16-1B/1T FOR OPENINGS 10 FEET TO 20 FEET. PROVIDE 8"MINIMUM BEARING FOR LINTELS UNLESS NOTED OTHERWISE.

STRUCTURAL STEEL: STRUCTURAL STEEL W-SHAPES SHALL CONFORM TO ASTM A992, GRADE 50. CHANNELS SHALL CONFORM TO ASTM A36. PLATES AND ANGLESSHALL CONFORM TO ASTM A36. RECTANGULAR AND SQUARE TUBES SHALL CONFORM TO ASTM A500, GRADE B (Fy= 46KSI). ROUND HSS SHALL CONFORM TO ASTMA500 GRADE B (Fy=42KSI). PIPES SHALL CONFORM TO ASTM A53 GRADE B (Fy=35KSI). DESIGN, FABRICATION AND ERECTION SHALL BE IN ACCORDANCE WITH THE"AISC SPECIFICATION FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS". BOLTS SHALL CONFORM TO THE ASTM SPECIFICATIONFOR A325 OR A490, HIGH STRENGTH BOLTS. WELDING SHALL CONFORM TO THE AWS CODES FOR ARC AND GAS WELDING IN BUILDING CONSTRUCTION. WELDSSHALL BE MADE USING E70XX ELECTRODES AND SHALL BE 3/16” MINIMUM UNLESS OTHERWISE NOTED. WELDING SHALL BE BY AWS CERTIFIED WELDERS.PREQUALIFIED WELDING PROCEDURES ARE TO BE USED, UNLESS AWS QUALIFICATION IS SUBMITTED TO THE ENGINEER PRIOR TO FABRICATION. STEEL TO RECEIVEONE SHOP COAT AND ONE FIELD TOUCH UP COAT OF APPROVED PAINT, EXCEPT WHERE GALVANIZING IS INDICATED ON THE DRAWINGS.

ALL BOLTED CONNECTIONS SHALL CONSIST OF MINIMUM 3/4 INCH DIAMETER ASTM A325 HIGH STRENGTH BOLTS. BEAM CONNECTIONS SHALL BE DESIGNED BY THEFABRICATOR FOR THE REACTIONS SHOWN ON THE PLANS. IF NOT SHOWN, THE FABRICATOR SHALL DESIGN THE BEAM CONNECTIONS TO SUPPORT AN ENDREACTION OF 1/2 THE ALLOWABLE UNIFORM LOAD CAPACITY WITH A MINIMUM OF 2 BOLTS.

SHEAR STUD CONNECTORS: SHEAR STUD CONNECTORS SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE WITH AWS D1.1 "STRUCTURAL WELDING CODE",SECTION 7 - STUD WELDING. STUDS SHALL BE TYPE 'B', HEADED STUDS HAVING A MINIMUM TENSILE STRENGTH OF 60,000 PSI AND SHALL BE OF LENGTH ANDDIAMETER SHOWN ON STRUCTURAL DRAWINGS.

ANCHOR RODS: UNLESS INDICATED OTHERWISE ON THE DRAWINGS, ANCHOR RODS SHALL BE ASTM F1554, GRADE 55, 3/4 DIA. AND SHALL BE EMBEDDED INTO THECONCRETE FOUNDATION A DISTANCE OF 1’-0” WITH A HEAVY HEX NUT AT THE EMBEDDED END.

STEEL ROOF DECK: STEEL ROOF DECK SHALL BE GALVANIZED AND CONFORM TO ASTM A653, STRUCTURAL QUALITY. THE GALVANIZED COATING SHALL BE G90,MINIMUM. ATTACHMENTS, CLOSURES ETC. SHALL BE IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS UNLESS NOTED OTHERWISE.

DECK ATTACHMENT SHALL BE A MINIMUM OF #12 SELF TAPPING SCREWS AT 6” O.C. AT TRANSVERSE AND PERIMETER SUPPORTS, 6” O.C. AT LONGITUDINALSUPPORTS, AND SIDE LAP CONNECTIONS USING #12 SELF TAPPING SCREW AT 6” O.C. UNLESS NOTED OTHERWISE ON THE DRAWINGS.

PREFABRICATED LIGHT GAUGE METAL TRUSSES: DESIGN AND MANUFACTURE PREFABRICATED LIGHT GAUGE METAL TRUSSES, INCLUDING ALL CONNECTIONS,UPLIFT ANCHORAGE HARDWARE AND FASTENERS IN ACCORDANCE WITH THE REQUIREMENTS OF AISI SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEELSTRUCTURAL MEMBERS (LATEST EDITION) OR THE AISI LOAD AND RESISTANCE FACTOR DESIGN SPECIFICATION FOR COLD-FORMED STEEL STRUCTURAL MEMBERS(LATEST EDITION) AND THE RECOMMENDATIONS OF THE PREFABRICATED METAL LIGHT GAUGE TRUSS MANUFACTURER.

LIGHT GAUGE METAL TRUSSES SHALL BE DESIGNED TO SUPPORT THE INDICATED WIND UPLIFT, SUPERIMPOSED DEAD AND LIVE LOADS, AND ADDITIONAL UNIFORMAND CONCENTRATED LOADS ON THE DRAWINGS. A MAXIMUM 5 PSF DEAD LOAD MAY BE USED FOR UPLIFT DESIGN.

PROVIDE TRUSS MEMBER TEMPORARY AND PERMANENT BRACING CONSISTENT WITH TRUSS MANUFACTURER’S DESIGN CALCULATIONS. ALL TRUSS ANCHORAGESTO BE INSTALLED USING TRUSS ANCHORAGE MANUFACTURER’S RECOMMENDED FASTENERS FOR MAXIMUM PUBLISHED CAPACITY. ALL METAL CONNECTIONHARDWARE AND FASTENERS SHALL HAVE A G90 HOT-DIPPED GALVANIZED COATING, MINIMUM.

TRUSS DIAGRAMS, IF SHOWN, ARE DIAGRAMMATIC ONLY. TRUSS DESIGNER TO DETERMINE AND ESTABLISH EXACT HEIGHT, LENGTH, LOCATION, SPACING, AND WEBMEMBER LAYOUT FOR EACH TRUSS.

SUBMIT COMPLETE SHOP DRAWINGS AND DESIGN CALCULATIONS, PREPARED, SIGNED, AND SEALED BY A PROFESSIONAL ENGINEER LICENSED IN THE STATE OFFLORIDA, SUBSTANTIATING ALL STRENGTH AND SERVICEABILITY CRITERIA.

STEEL STAIRS & LADDERS: STEEL STAIR SYSTEM AND ALL CONNECTIONS SHALL BE DESIGNED FOR ALL APPLICABLE LOADS AS INDICATED ON THE PLANS AND INTHE BUILDING CODE. THE CONFIGURATION OF THE STEEL STAIR SYSTEM SHALL BE AS SHOWN ON THE ARCHITECTURAL DRAWINGS.

PRIOR TO CONSTUCTION, SUBMIT COMPLETE SHOP DRAWINGS AND CALCULATIONS, SIGNED AND SEALED BY A STRUCTURAL ENGINEER LICENSED IN THE STATE OFFLORIDA, SUBSTANTIATING ALL STRENGTH AND SERVICEABILITY CRITERIA. THE LOADS SHALL BE CLEARLY INDICATED ON ALL SHOP DRAWINGS, AND SHALL SHOWAND SPECIFY ALL CONNECTIONS UTILIZED WITHIN THE STEEL STAIR SYSTEM AS WELL AS CONNECTIONS TO AND LOADS IMPOSED UPON THE STRUCTURAL SYSTEMSHOWN ON THESE PLANS.

RAILINGS: RAILING SYSTEM AND ALL CONNECTIONS SHALL BE DESIGNED FOR ALL APPLICABLE LOADS AS INDICATED ON THE PLANS AND IN THE BUILDING CODE.THE CONFIGURATION OF THE RAILING SYSTEM SHALL BE AS SHOWN ON THE ARCHITECTURAL DRAWINGS.

PRIOR TO CONSTRUCTION, SUBMIT COMPLETE SHOP DRAWINGS AND CALCULATIONS, SIGNED AND SEALED BY A STRUCTURAL ENGINEER LICENSED IN THE STATE OFFLORIDA, SUBSTANTIATING ALL STRENGTH AND SERVICEABILITY CRITERIA. THE LOADS SHALL BE CLEARLY INDICATED ON ALL SHOP DRAWINGS, AND SHALL SHOWAND SPECIFY ALL CONNECTIONS UTILIZED WITHIN THE STEEL RAILING SYSTEM AS WELL AS CONNECTIONS TO AND LOADS IMPOSED UPON THE STRUCTURAL SYSTEMSHOWN ON THESE PLANS.

MK-12060

City o

f K

ey W

est, 3

13

2 F

lagle

r A

ven

ue

, K

ey W

est, F

lorida

330

40

FIR

E S

TA

TIO

N #

26

16 S

imo

nto

n S

tree

t, K

ey W

est, F

lorida

FO

R

BU

ILD

ING

AN

D S

ITE

DE

VE

LO

PM

EN

T

Seal:

February 15, 2013Date:

Sheet Number:

Title:

Drawn By:

Project #:

Checked By:

Drawing Size

Submissions:

©2012 by mbi | k2m Architecture, Inc.

Consultants:

ARCHITECT:

2013.02.15 - Bidding Documents

1001 Whitehead StreetKey West, Florida 33040

Tel: 305.292.7722Fax: 305.292.2162

Email: [email protected]

PROF. REG. AA26001059

Architecture, Interior Design,Procurement,

Owner Representation,Specialty Consulting

Building RelationshipsBased on Trust and Results

Cleveland | Key West | CharlotteSouthwest Florida | Washington DC

STRUCTURAL ENGINEER:TKW Consulting Engineers5621 Banner Drive,Fort Myers, Florida 33912

CIVIL ENGINEER:Perez Engineering & Development, Inc.1010 Kennedy Dr., Suite 201Key West, Florida 33040

LANDSCAPE ARCHITECTLandscape Architecture, LLC

2525 Ponce de Leon Blvd., Suite 300Coral Gables, Florida 33134

MEP / FP ENGINEER:TLC Engineering for Architecture1400 Colonial Boulevard, Suite 203Fort Myers, Florida 33907

24x36

LAG JTL

Fort Myers, Florida 33912

E-MAIL: [email protected] Certification # 5762

239.278.1992 • FAX 239.278.0922

Survey LB # 734

5621 Banner Drive

CONSULTING ENGINEERS

James T. Lange, P.E.Reg.# 62694TKW Job # 12164.00

2/15/2013 11:47:33 AM

S1.1.1

GENERAL NOTES

Page 3: GENERAL STRUCTURAL NOTES - D.N. Higgins

FOUNDATION PLAN NOTES:

1. FOR TYPICAL DETAILS SEE SHEET S3.3.1, S3.3.2, AND S3.3.6

2. INDICATES TOP OF SLAB ELEVATION.

3. SEE SHEET S1.1.1 FOR GENERAL STRUCTURAL NOTES.

4. SEE ARCHITECTURAL DRAWINGS FOR SLOPES, DROPS, AND DRAIN LOCATION INFLOOR SLABS. SEE CIVIL FOR PARKING GARAGE.

5. VERIFY/COORDINATE LOCATION OF UNDERGROUND PIPING WITH FOUNDATION.

6. VERIFY/COORDINATE ALL DIMENSIONS AND ELEVATIONS WITH ARCHITECTURALDRAWINGS BEFORE COMMENCING CONSTRUCTION. SEE ARCHITECTURALDRAWINGS FOR ADDITIONAL DIMENSIONAL INFORMATION.

7. VERIFY/COORDINATE EDGE OF SLAB DETAILS AT EXTERIOR DOORS WITHARCHITECTURAL DRAWINGS.

8. VERIFY/COORDINATE SILL HEIGHTS AND DETAILS OF WALL OPENINGS WITHARCHITECTURAL DRAWINGS.

9. "FX" INDICATES FOOTING TYPE, SEE SCHEDULE THIS SHEET.

10. (X'-X") INDICATES TOP OF FOOTING ELEVATION. TYPICAL ELEVATION UNO.

11. INDICATES PRECAST PANELS.

12. INDICATES STEP IN SLAB.

13. 4" SOG INDICATES 4" THICK CONC SLAB ON GRADE WITH 6x6-W2.1xW2.1 WWF(CENTERED) AND 10 MIL POLY VAPOR BARRIER OVER TERMITE TREATED SOIL.

14. 8" SOG INDICATES 8" THICK CONC SLAB ON GRADE WITH #4 @ 12" O.C. EA. WAYT&B AND 10 MIL POLY VAPOR BARRIER OVER TERMITE TREATED SOIL.

15. INDICATES LOAD BEARING 8" CMU WALL.

16. INDICATES NON-LOAD BEARING CMU WALL.

17. INDICATES LOUVERED FENCE ENCLOSURE.

18. PRECAST MANUFACTURE TO SUPPLY ALL EMBED PLATES AND HARDWARE FORFOUNDATION CONNECTION.

19. CONTRACTOR TO COORDINATE AND INSTALL ALL EMBED PLATES AND ANCHORBOLTS IN FOUNDATIONS.

20. FOUNDATION CONSTRUCTION SHALL NOT COMMENCE UNTIL PRECAST SHOPDRAWINGS HAVE BEEN REVIEWED AND APPROVED BY ENGINEER OF RECORD.

X'-X"

AUGERCAST PILE PLAN NOTES:

1. INDICATES AUGERCAST PILES - 16-INCH DIAMETER DRILLED CAST-IN-PLACEROCK ANCHORS INSTALLED A MINIMUM OF 3’-0” INTO THE NATURAL LIMESTONE STRATUM(SEE SOILS REPORT). REINFORCE AUGERCAST PILES WITH FOUR #5 VERTICAL REBAREXTENDING UP INTO THE FOOTING ABOVE A MINIMUM OF 1’-6”. SEE TYPICAL DETAILS THISSHEET.

2. LOCATE AUGERCAST PILES ON COLUMN CENTERLINES, WALL CENTERLINES, OR ASSHOWN. SPACE AUGERCAST PILES EQUALLY BETWEEN SPECIFIED LOCATIONS AT 10’-0”ON-CENTER MAXIMUM.

3. FOR FOUNDATION LOCATIONS AND ELEVATIONS SEE FOUNDATION PLANS. FORFOUNDATION SIZES AND REINFORCING SEE FOUNDATION SCHEDULES THIS SHEET.

FRAMING PLAN NOTES:

1. FOR TYPICAL DETAILS SEE SHEETS S3.3.2, S3.3.3, S3.3.4, S3.3.5 AND S3.3.6.

2. SEE SHEET S1.1.1 FOR GENERAL STRUCTURAL NOTES.

3. SEE ARCHITECTURAL DRAWINGS FOR SLOPES, DROPS, AND DRAIN LOCATION INFLOOR PLANS.

4. VERIFY/COORDINATE ALL DIMENSIONS AND ELEVATIONS WITH ARCHITECTURALDRAWINGS BEFORE COMMENCING CONSTRUCTION. SEE ARCHITECTURAL DRAWINGSFOR ADDITIONAL DIMENSIONAL INFORMATION.

5. VERIFY/COORDINATE EDGE OF SLAB DETAILS AT EXTERIOR DOORS WITHARCHITECTURAL DRAWINGS.

6. VERIFY/COORDINATE SILL HEIGHTS AND DETAILS OF WALL OPENINGS WITHARCHITECTURAL DRAWINGS.

7. INDICATES STEP IN SLAB ELEVATION.

8. SEE MECHANICAL DRAWINGS FOR SLAB OPENINGS AND SLEEVES NOT SHOWN.

9. INDICATES SPAN DIRECTION OF 8" PRECAST HOLLOW COREPLANK WITH 3" CONCRETE TOPPING. COORDINATE SLAB DEPRESSIONS WITHARCHITECT FLOOR FINISHES (TOTAL DEPTH 11").

10. INDICATES SPAN DIRECTION OF 24" PRECAST DOUBLE TEESWITH 3" STRUCTURAL CONCRETE TOPPING. COORDINATE SLAB DEPRESSIONS WITHARCHITECT FLOOR FINISHES.

11. INDICATES SPAN DIRECTION OF 8" PRECAST SOLID PLANKWITH NO STRUCTURAL CONCRETE TOPPING.

12. STRUCTURAL TOPPING ON PRECAST MEMBERS SHALL BE 4KSI CONCRETEREINFORCED WITH 6x6-W2.1xW2.1 WWF. HOLLOW CORE PLANK KEYWAYS SHALL BEGROUTED BY PRECAST SUPPLIER PRIOR TO POURING ANY CONCRETE TOPPING.

13. PENETRATIONS LESS THAN 4" IN DIAMETER MAY BE FIELD LOCATED AND DRILLEDTHRU THE HOLLOW CORE PLANK IF COORDINATED WITH THE PLANK CORES SO THATPRESTRESS TENDONS ARE NOT SEVERED OR DAMAGED. ALL OTHER PENETRATIONSSHALL BE COORDINATED WITH THE PRECAST MFR SO THAT ANY LOSS OF PRESTRESSTENDONS ARE DESIGNED AND DETAILED ADEQUATELY.

14. MECHANICAL PENETRATIONS SIZE AND LOCATION THRU THE HOLLOW CORE PLANKSHALL BE COORDINATED BY THE GENERAL CONTRACTOR WITH TRUSS AND PRECASTSHOP DRAWINGS.

8 HC+3

24DT+3

8SP

ROOF FRAMING PLAN NOTES:

1. FOR TYPICAL DETAILS SEE SHEETS S3.3.2, S3.3.3, S3.3.4, S3.3.5 AND S3.3.6.

2. SEE SHEET S1.1.1 FOR GENERAL STRUCTURAL NOTES.

3. PRE ENGINEERED METAL TRUSSES SHALL BE AT 4'-0" OC (MAX) WITH 18GA (MIN) TOPCHORD.

4. PRE-ENGINEERED TRUSS MANUFACTURER SHALL PROVIDE ALL OF THE CONNECTIONHARDWARE AND ENGINEERING. EMBED PLATES REQUIRED FOR TRUSS HOLD DOWNCONNECTIONS SHALL BE COORDINATED W/ PRE CAST MANUFACTURER.

5. T.G. INDICATES PRE ENGINEERED METAL TRUSS GIRDER.

6. INDICATES ROOF SLOPE.

7. INDICATES SPAN DIRECTION OF 1 1/2", 20 GA TYPE 'B' ROOF DECK.ATTACH METAL DECK TO PRE ENGINEERED METAL TRUSSES WITH #12 SCREWS IN A 36/14PATTERN (2 SCREWS PER FLUTE). ATTACH METAL DECK TO HIP, VALLEY, RIDGE, ANDPERIMETER BENT PLATES WITH #12 SCREWS @ 6" OC. SIDELAP FASTENERS SHALL BE #12 SCREWS AT 6" OC (6 PER SPAN).

D-1

12

6X

3' -

0"

LIMESTONE

HOOK

SEE FTG SCHEDULE FORSIZE AND REINF

(4) #5 VERT

MIN

1' -

6"

CLR2"

1' - 4" DIA

LIMESTONE

HOOK

SEE FTG SCHEDULE FORSIZE AND REINF

ENGFILL

3' -

0"

1' - 4" DIA

MIN

1' -

6"

2"

MIN

2" CLR

(4) #5 VERT

ZO

NE

5Z

ON

E 4

ZO

NE

5

ZONE 5

3

3 32

2

22

2

2

ZO

NE

5

ZONE 5 ZONE 4 ZONE 5

3

3 3

3

3

3

22

ZONE 5

ZO

NE

4

ZONE 5

ZO

NE

5

2

1

1

1

1

3

ZONE 4

ZONE 4ZONE 5 ZONE 4ZONE 5 ZONE 4

ZO

NE

5

#4

#5

#6

#7

#8

#9

#10

31" 28"

37" 33"

54" 49"

62" 55"

70" 63"

79" 70"

NOTE:FOR TOP BARS, LAP LENGTHS SHALL BE MULTIPLIED BY 1.3. TOP BARS ARE HORIZONTAL BARSWITH 12" OR MORE OF FRESH CONCRETE CAST IN THE MEMBER BELOW THE REINFORCING BAR.

22"25"29"

36"

43"

63"

72"

81"

91"

21"

26"

31"

45"

51"

57"

64"

15"

19"

23"

27"

30"

34"

39"

#11 87" 78"101" 71" 43"

5000 PSI3000 PSI 6000 PSI

COMPRESSION BARS

4000 PSI

BAR SIZEFy= 60 ksi

CAST-IN-PLACE CONCRETE REINFORCINGBAR LAP SPLICE SCHEDULE

TENSION BARS

ALL STRENGTHS

COMPONENTS AND CLADDINGVasd - DESIGN WIND PRESSURE (PSF)

ZONETRIBUTARY AREA

10 FT^2 20 FT^2 50 FT^2 100FT^2

INTERIOR 1

RO

OF

WA

LL

+42/-66 +38/-64 +33/-62 +30/-60

+30/-84-134

+33/-93-134

+38/-106-134

+42/-115-134

+61/-67+69/-75+72/-78

+72/-97 +69/-90 +65/-81 +61/-75

+65/-71

EDGE 2OVERHANG

CORNER 3OVERHANG

INTERIOR 4

CORNER 5

1 GENERAL UPLIFT ZONE 4 TYPICAL WALL

2 EDGE UPLIFT ZONE 5

3 CORNER UPLIFT ZONE

WALL AT CORNER

NOTES:

1. PLUS AND MINUS SIGNS SIGNIFY PRESSURES ACTINGTOWARD AND AWAY FROM THE BUILDING SURFACES.

2. EDGE DISTANCE = 14'-0".

3. ZONE 2 PRESSURES ARE USED AT ZONE 3 BECAUSE THEHIP ROOF IS LESS THAN 25 DEGREES.

+30/-84-134

+33/-93-134

+38/-106-134

+42/-115-134

MK-12060

City o

f K

ey W

est, 3

13

2 F

lagle

r A

ven

ue

, K

ey W

est, F

lorida

330

40

FIR

E S

TA

TIO

N #

26

16 S

imo

nto

n S

tree

t, K

ey W

est, F

lorida

FO

R

BU

ILD

ING

AN

D S

ITE

DE

VE

LO

PM

EN

T

Seal:

February 15, 2013Date:

Sheet Number:

Title:

Drawn By:

Project #:

Checked By:

Drawing Size

Submissions:

©2012 by mbi | k2m Architecture, Inc.

Consultants:

ARCHITECT:

2013.02.15 - Bidding Documents

1001 Whitehead StreetKey West, Florida 33040

Tel: 305.292.7722Fax: 305.292.2162

Email: [email protected]

PROF. REG. AA26001059

Architecture, Interior Design,Procurement,

Owner Representation,Specialty Consulting

Building RelationshipsBased on Trust and Results

Cleveland | Key West | CharlotteSouthwest Florida | Washington DC

STRUCTURAL ENGINEER:TKW Consulting Engineers5621 Banner Drive,Fort Myers, Florida 33912

CIVIL ENGINEER:Perez Engineering & Development, Inc.1010 Kennedy Dr., Suite 201Key West, Florida 33040

LANDSCAPE ARCHITECTLandscape Architecture, LLC

2525 Ponce de Leon Blvd., Suite 300Coral Gables, Florida 33134

MEP / FP ENGINEER:TLC Engineering for Architecture1400 Colonial Boulevard, Suite 203Fort Myers, Florida 33907

24x36

LAG JTL

Fort Myers, Florida 33912

E-MAIL: [email protected] Certification # 5762

239.278.1992 • FAX 239.278.0922

Survey LB # 734

5621 Banner Drive

CONSULTING ENGINEERS

James T. Lange, P.E.Reg.# 62694TKW Job # 12164.00

2/15/2013 11:47:33 AM

S1.1.2

PLAN NOTESAND

SCHEDULES

WALL FOUNDATION SCHEDULE

TYPEMARK WIDTH DEPTH REINFORCING

F20W 2' - 0" 1' - 8"

F22W 2' - 2" 1' - 8" (3) #5 CONT & #5 @ 24" OC SHORT WAY (BOT)

F26W 2' - 6" 1' - 8" (4) #5 CONT & #5 @ 12" OC SHORT WAY (BOT)

F30W 3' - 0" 1' - 8" (4) #5 CONT & #5 @ 12" OC SHORT WAY (BOT)

F50W 5' - 0" 1' - 8" (5) #6 CONT & #6 @ 12" OC SHORT WAY (BOT)

F60W 6' - 0" 1' - 8" (6) #6 CONT & #6 @ 12" OC SHORT WAY (BOT)

COLUMN FOUNDATION SCHEDULE

TYPEMARK WIDTH LENGTH DEPTH REINFORCING Comments

F40 4' - 0" 4' - 0" 1' - 8" (5) #6 EA WAY (BOT)

F50 5' - 0" 5' - 0" 1' - 8" (5) #6 EA WAY (BOT)

F60 6' - 0" 6' - 0" 1' - 8" (6) #6 EA WAY (BOT)

F70 7' - 0" 7' - 0" 1' - 8" (6) #7 EA WAY (BOT)

F80 8' - 0" 8' - 0" 2' - 0" (7) #7 EA WAY (BOT)

3/4" = 1'-0"1

FOUNDATION ONLIMESTONE STRATUM

3/4" = 1'-0"2

FOUNDATION ONSTRUCTURAL FILL ORNATIVE SOILS

COMPONENTS AND CLADDING WIND PRESSURE DIAGRAM

Page 4: GENERAL STRUCTURAL NOTES - D.N. Higgins

AUGERCAST PILESEE DETAILS 1 & 2 /S1.1.2

3 EQ. SPACES = 21' - 8"

5 1/2"

5 1

/2"

6' - 0"

7 EQ. SPACES = 69' - 9"

8' -

0"

6 E

Q. S

PA

CE

S =

50

' - 1

1"

7 EQ. SPACES = 69' - 9"5 1/2"

5 1

/2"

2' - 5"

4' -

11

3/4

"

3 EQ. SPACES = 22' - 8"

3 EQ. SPACES = 22' - 8"

5 1/2"

5 1

/2"

5 1/2"

5 1

/2"

7' - 8"

22

' - 1

1"

28

' - 1

1"

51

' - 1

0"

8' -

11

"

3 E

Q. S

PA

CE

S =

41

' - 4

1/2

"

7 EQ. SPACES = 96' - 6 1/2"

1' - 0" 22' - 7 5/8"

4 1/2" REF

5 1

/2"

6' - 4"

22' - 8" 70' - 8"

3 E

Q. S

PA

CE

S =

26

'-8

"5

1/2

"

16

' - 1

1 1

/2"

EQ

EQ

13

' - 5

1/2

"1

' - 0

"

8' -

5 1

/2"

5 1

/2"

51

' - 1

0"

4' - 7 3/8"

7' -

9 1

/2"

8' -

9 7

/8"

5 1/2"5 1/2"

SEE CIVILPLANS

1' - 7"

93' - 4"

15' - 10"

13' - 9 1/2"1' - 0"

1' - 0"

17

' - 0

"1

6' -

11

1/2

"

EQ

EQ

8' -

6"

8' -

6"

22' - 7" 22 - 7 1/2"

MK-12060

City o

f K

ey W

est, 3

13

2 F

lagle

r A

ven

ue

, K

ey W

est, F

lorida

330

40

FIR

E S

TA

TIO

N #

26

16 S

imo

nto

n S

tree

t, K

ey W

est, F

lorida

FO

R

BU

ILD

ING

AN

D S

ITE

DE

VE

LO

PM

EN

T

Seal:

February 15, 2013Date:

Sheet Number:

Title:

Drawn By:

Project #:

Checked By:

Drawing Size

Submissions:

©2012 by mbi | k2m Architecture, Inc.

Consultants:

ARCHITECT:

2013.02.15 - Bidding Documents

1001 Whitehead StreetKey West, Florida 33040

Tel: 305.292.7722Fax: 305.292.2162

Email: [email protected]

PROF. REG. AA26001059

Architecture, Interior Design,Procurement,

Owner Representation,Specialty Consulting

Building RelationshipsBased on Trust and Results

Cleveland | Key West | CharlotteSouthwest Florida | Washington DC

STRUCTURAL ENGINEER:TKW Consulting Engineers5621 Banner Drive,Fort Myers, Florida 33912

CIVIL ENGINEER:Perez Engineering & Development, Inc.1010 Kennedy Dr., Suite 201Key West, Florida 33040

LANDSCAPE ARCHITECTLandscape Architecture, LLC

2525 Ponce de Leon Blvd., Suite 300Coral Gables, Florida 33134

MEP / FP ENGINEER:TLC Engineering for Architecture1400 Colonial Boulevard, Suite 203Fort Myers, Florida 33907

24x36

LAG JTL

Fort Myers, Florida 33912

E-MAIL: [email protected] Certification # 5762

239.278.1992 • FAX 239.278.0922

Survey LB # 734

5621 Banner Drive

CONSULTING ENGINEERS

James T. Lange, P.E.Reg.# 62694TKW Job # 12164.00

2/15/2013 11:47:33 AM

S2.2.0

AUGERCASTPILE PLAN

1/4" = 1'-0"

AUGERCAST PILE PLANFOR AUGERCAST PILE PLANNOTES SEE SHEET S1.1.2

Page 5: GENERAL STRUCTURAL NOTES - D.N. Higgins

4

S3.3.2

STEEL LADDER

8

S3.3.2

PRE ENGINEEREDPRECAST STAIR

-SEE ARCH

TRENCH DRAIN-SEE PLUMBINGDWGS

TRENCH DRAIN-SEE PLUMBINGDWGS

TRENCH DRAIN-SEE PLUMBINGDWGS

8

S3.3.1

FIN FLR 11' - 0"

CAST IN PLACE STAIR-SEE ARCH

9'-0"

FIN FLOOR

9

S3.3.2

SLOPE FLOOR TOSHOWER DRAIN.SEE ARCH. DRAWINGS

F50W

F5

0W

( 7' - 0" )

( 7

' - 0

" )

F5

0W

( 7

' - 0

" )

F30W ( 7' - 0" )

SL

OP

ES

LO

PE

SL

OP

ES

LO

PE

SL

OP

ES

LO

PE

1

S3.3.6

24x24 PRECASTCOLUMN

ARCH PRECASTCOLUMN

4" SOG

8" SOG

11" PRECAST COMPOSITE PANEL(5" CONCRETE + 3" INSULATION + 3" CONCRETE)

S3.3.2

7

4"

4"

LAUNDRY EQUIPMENTPAD

4

S3.3.1

F40

( 7' - 0" )

F40

( 7' - 0" )

F40

( 7' - 0" )

F40

( 7' - 0" )

F40

( 7' - 0" )

F40

( 7' - 0" )

F40

( 7' - 0" )

F40

( 7' - 0" )

F40

( 7' - 0" )

F40

( 7' - 0" )

F40

( 7' - 0" )

F5

0W

11'-0"

FIN FLOOR

11'-0"

FIN FLOOR

F50W

F5

0W

F50W

9'-0"

FIN FLOOR

F20W

F2

0W

F20W

4" SOG W/ PAVERS -SEE LANDSCAPE PLAN

( 7

' - 0

" )

( 7' - 0" )

( 7' - 0" )

4" SOG

7' - 8"

22

' - 1

1"

28

' - 1

1"

51

' - 1

0"

8' -

11

"

3 E

Q. S

PA

CE

S =

41

' - 4

1/2

"

5' -

7"

1' -

4"

7 EQ. SPACES = 96' - 6 1/2"

1' - 0" 3' - 11" REF. 4 1/2" REF

6

S3.3.1

1

S3.3.2

2

S3.3.2

5

S3.3.2

1

S3.3.2

SIM

F20W

F2

0W

F30W

F20W

( 7

' - 0

" )

F3

0W

F3

0W

( 7

' - 0

" )

( 7

' - 0

" )

( 7' - 0" )

F50W ( 7' - 0" )

6' - 4"

22' - 8" 70' - 8"

FD FD

FDFD

F60W ( 7' - 0" )

14' - 0"

WIDEN FOOTING TO 6'-0"

( 7' - 0" )F60W

EL. 8'-10"

EL. 9'-0"

EL. 8'-10"

EL. 9'-0"

EL. 8'-10"

EL. 9'-0"

EL. 8'-10"

EL. 8'-10"

EL. 8'-10"

EL. 9'-0"

( 7' - 0" )F80

WIDEN FOOTING TO 6'-0"

9'-0"

FIN FLOOR

THICKENED EDGE

THICKENED EDGE

THICKENED EDGE

THICKENED EDGE

F2

0W

F2

0W

THICKENED EDGE

THICKENED EDGE

THICKENED EDGE

( 7

' - 0

" )

( 7

' - 0

" )

10

S3.3.1

SLOPE

6

S3.3.2

SLOPE

TIME VAULT,SEE ARCH

4" SOG W/ PAVERS -SEE LANDSCAPE PLAN

4" SOG W/ PAVERS -SEE LANDSCAPE PLAN

NOTE:NEW CONCRETE PADREQUIRED TO SUPPORTRELOCATED EXISTINGGENERATOR.

LOCATION, SIZE ANDREINFORCING TO BEDETERMINED AFTER RECEIPTOF GENERATOR INFORMATION.

SEE CIVILPLANS

17

' - 5

"1

7' -

0"

17

' - 5

"

51

' - 1

0"

13

' - 5

1/2

"

12

S3.3.2

20x20 COLUMNIN WALL PANEL

4" SOG

W/DOOR

SEE ARCH. COORD

SLAB EDGE

10

S3.3.2

14' - 9 1/2" 22' - 8" 23' - 1 1/8" 22' - 7" 25' - 0" 23' - 1"

93' - 4"

MK-12060

City o

f K

ey W

est, 3

13

2 F

lagle

r A

ven

ue

, K

ey W

est, F

lorida

330

40

FIR

E S

TA

TIO

N #

26

16 S

imo

nto

n S

tree

t, K

ey W

est, F

lorida

FO

R

BU

ILD

ING

AN

D S

ITE

DE

VE

LO

PM

EN

T

Seal:

February 15, 2013Date:

Sheet Number:

Title:

Drawn By:

Project #:

Checked By:

Drawing Size

Submissions:

©2012 by mbi | k2m Architecture, Inc.

Consultants:

ARCHITECT:

2013.02.15 - Bidding Documents

1001 Whitehead StreetKey West, Florida 33040

Tel: 305.292.7722Fax: 305.292.2162

Email: [email protected]

PROF. REG. AA26001059

Architecture, Interior Design,Procurement,

Owner Representation,Specialty Consulting

Building RelationshipsBased on Trust and Results

Cleveland | Key West | CharlotteSouthwest Florida | Washington DC

STRUCTURAL ENGINEER:TKW Consulting Engineers5621 Banner Drive,Fort Myers, Florida 33912

CIVIL ENGINEER:Perez Engineering & Development, Inc.1010 Kennedy Dr., Suite 201Key West, Florida 33040

LANDSCAPE ARCHITECTLandscape Architecture, LLC

2525 Ponce de Leon Blvd., Suite 300Coral Gables, Florida 33134

MEP / FP ENGINEER:TLC Engineering for Architecture1400 Colonial Boulevard, Suite 203Fort Myers, Florida 33907

24x36

LAG JTL

Fort Myers, Florida 33912

E-MAIL: [email protected] Certification # 5762

239.278.1992 • FAX 239.278.0922

Survey LB # 734

5621 Banner Drive

CONSULTING ENGINEERS

James T. Lange, P.E.Reg.# 62694TKW Job # 12164.00

2/15/2013 11:47:34 AM

S2.2.1

FOUNDATION PLAN

1/4" = 1'-0"

FOUNDATION PLANFOR FOUNDATION PLANNOTES SEE SHEET S1.1.2

Page 6: GENERAL STRUCTURAL NOTES - D.N. Higgins

T.O MEZZ

8" DEEPPRE CAST SOLID PLANK

STEEL LADDER

AHU1-3

EF-1

5

S3.3.3

5

S3.3.3

17' - 2 1/2" BEARING

17' - 2 1/2" BEARING

8S

P

8S

P

PRE CAST WALL BELOWAT 17' 2 1/2" BEARING

5

S3.3.3

CONCRETE HOUSEKEEPING PADCOORD W/ PLUMBING DRAWINGS

9

S3.3.3

3

S3.3.3

NOTE:COORDINATE PENETRATIONS WITH MECH.,ELEC., PLUMBING, & FIRE PROTECTION PLANS.

17' - 11"

MK-12060

City o

f K

ey W

est, 3

13

2 F

lagle

r A

ven

ue

, K

ey W

est, F

lorida

330

40

FIR

E S

TA

TIO

N #

26

16 S

imo

nto

n S

tree

t, K

ey W

est, F

lorida

FO

R

BU

ILD

ING

AN

D S

ITE

DE

VE

LO

PM

EN

T

Seal:

February 15, 2013Date:

Sheet Number:

Title:

Drawn By:

Project #:

Checked By:

Drawing Size

Submissions:

©2012 by mbi | k2m Architecture, Inc.

Consultants:

ARCHITECT:

2013.02.15 - Bidding Documents

1001 Whitehead StreetKey West, Florida 33040

Tel: 305.292.7722Fax: 305.292.2162

Email: [email protected]

PROF. REG. AA26001059

Architecture, Interior Design,Procurement,

Owner Representation,Specialty Consulting

Building RelationshipsBased on Trust and Results

Cleveland | Key West | CharlotteSouthwest Florida | Washington DC

STRUCTURAL ENGINEER:TKW Consulting Engineers5621 Banner Drive,Fort Myers, Florida 33912

CIVIL ENGINEER:Perez Engineering & Development, Inc.1010 Kennedy Dr., Suite 201Key West, Florida 33040

LANDSCAPE ARCHITECTLandscape Architecture, LLC

2525 Ponce de Leon Blvd., Suite 300Coral Gables, Florida 33134

MEP / FP ENGINEER:TLC Engineering for Architecture1400 Colonial Boulevard, Suite 203Fort Myers, Florida 33907

24x36

LAG JTL

Fort Myers, Florida 33912

E-MAIL: [email protected] Certification # 5762

239.278.1992 • FAX 239.278.0922

Survey LB # 734

5621 Banner Drive

CONSULTING ENGINEERS

James T. Lange, P.E.Reg.# 62694TKW Job # 12164.00

2/15/2013 11:47:34 AM

S2.2.2

MEZZANINEFRAMING PLAN

1/4" = 1'-0"

MEZZANINE FRAMING PLAN

Page 7: GENERAL STRUCTURAL NOTES - D.N. Higgins

PRE ENG METAL TRUSSES (TYP)

PR

E E

NG

ME

TA

L T

RU

SS

ES

(T

YP

)

8HC +3

FIN FLOOR

25'-10"

24

DT

+3

FIN FLOOR

25'-10"

PRE ENGINEEREDPRECAST STAIR

1

S3.3.6

6

S3.3.4

8x20

5

S3.3.4

( 2

5' -

4"

)8

x20

( 2

5' -

4"

)8

x20

( 2

5' -

4"

)

11

x4

2(

27

' - 4

" )

11

x4

2(

27

' - 4

" )

11

x4

2(

27

' - 4

" )

COORDW/ ARCH

S3.3.4

3

ARCH PRECASTCOLUMN-SEE ARCHDWGS

S3.3.4

2

11" PRECAST COMPWALL PANEL

2

S3.3.3

2

S3.3.3

7

S3.3.3

MECH OPENINGSCOORD W/ MECH DWGS

D-1

12

4

12

4

12

4

12

4

12

4

D-1

FIN FLOOR

25'-10"

FIN FLOOR

25'-10"

24' - 8 1/4" BEARING

93' - 4"

22

' - 1

1"

28

' - 1

1"

51

' - 1

0"

8' -

11

"

3 E

Q. S

PA

CE

S =

41

' - 4

1/2

"

PRE ENGINEEREDPRECAST STAIR

6

S3.3.5

10

S3.3.3

8

S3.3.3

1

S3.3.3

6

S3.3.3

70' - 8"

6' - 4"

24' - 10 1/2" BEARING

2.0 KIP/FT

2.0 KIP/FT

0.2

5 K

IP/F

T

7.5K

7.5K

1

S3.3.4

SLO

PE

TAPER TOPPINGFOR DRAINAGE

TG

TG

TG

TG

TG

TG

TG

TG

SLO

PE

SLO

PE

SLO

PE

TG

TG TG TG TG TG TG TG

TG

TG

TG

TG

12"x42" HIGH RAILING

12x16 BEAMSBELOW STAIRS

12x66 BEAM(42" HIGH RAILING)

(T/BEAM +29'-4")

12x24 BEAM(T/BEAM +25'-10")

8" PRECAST SLABW/ 2" TOPPING

8x12CORBEL

20x20 COLUMNIN WALL PANEL

1' - 4" 15' - 6" 5' - 10"

21' - 4"

22' - 8"

METAL GUTTER-SEE ARCH.

17

' - 4

1/2

"1

7' -

4 1

/2"

17

' - 1

"

51

' - 1

0"

MK-12060

City o

f K

ey W

est, 3

13

2 F

lagle

r A

ven

ue

, K

ey W

est, F

lorida

330

40

FIR

E S

TA

TIO

N #

26

16 S

imo

nto

n S

tree

t, K

ey W

est, F

lorida

FO

R

BU

ILD

ING

AN

D S

ITE

DE

VE

LO

PM

EN

T

Seal:

February 15, 2013Date:

Sheet Number:

Title:

Drawn By:

Project #:

Checked By:

Drawing Size

Submissions:

©2012 by mbi | k2m Architecture, Inc.

Consultants:

ARCHITECT:

2013.02.15 - Bidding Documents

1001 Whitehead StreetKey West, Florida 33040

Tel: 305.292.7722Fax: 305.292.2162

Email: [email protected]

PROF. REG. AA26001059

Architecture, Interior Design,Procurement,

Owner Representation,Specialty Consulting

Building RelationshipsBased on Trust and Results

Cleveland | Key West | CharlotteSouthwest Florida | Washington DC

STRUCTURAL ENGINEER:TKW Consulting Engineers5621 Banner Drive,Fort Myers, Florida 33912

CIVIL ENGINEER:Perez Engineering & Development, Inc.1010 Kennedy Dr., Suite 201Key West, Florida 33040

LANDSCAPE ARCHITECTLandscape Architecture, LLC

2525 Ponce de Leon Blvd., Suite 300Coral Gables, Florida 33134

MEP / FP ENGINEER:TLC Engineering for Architecture1400 Colonial Boulevard, Suite 203Fort Myers, Florida 33907

24x36

LAG JTL

Fort Myers, Florida 33912

E-MAIL: [email protected] Certification # 5762

239.278.1992 • FAX 239.278.0922

Survey LB # 734

5621 Banner Drive

CONSULTING ENGINEERS

James T. Lange, P.E.Reg.# 62694TKW Job # 12164.00

2/15/2013 11:47:34 AM

S2.2.3

SECOND FLOORFRAMING PLAN

FOR FRAMING PLAN NOTES SEE SHEET S1.1.2

1/4" = 1'-0"

SECOND FLOOR FRAMING PLAN

Page 8: GENERAL STRUCTURAL NOTES - D.N. Higgins

OPEN

PRE ENGINEEREDPRECAST GUTTER

2

S3.3.5

10

x2

8

11

x4

7

T.O WALL 37' - 2"

T.O WALL 37' - 2"

T.O WALL 38' - 9"

T.O WALL 38' - 9"

35' - 6" BEARING

6SP

( 3

7' -

2"

)

( 3

8' -

9"

)1

1x4

71

1x4

7

35' - 6" BEARING

3

S3.3.5

PRE ENGINEEREDPRECAST GUTTER

4

S3.3.5

1

S3.3.5

TO WALL 38' - 9"

TO WALL 38' - 9"

22' - 8" 70' - 8"

93' - 4"

22

' - 1

1"

28

' - 1

1"

51

' - 1

0"

8' -

11

"

TO WALL 38' - 9"

1' -

4"

4

S3.3.5

1

S3.3.4

4

S3.3.5

22' - 8" 23' - 1 1/8" 22' - 7" 25' - 0"

93' - 4"

17

' - 4

1/2

"1

7' -

1"

17

' - 4

1/2

"

51

' - 1

0"

8' -

11

"

23' - 1"

MK-12060

City o

f K

ey W

est, 3

13

2 F

lagle

r A

ven

ue

, K

ey W

est, F

lorida

330

40

FIR

E S

TA

TIO

N #

26

16 S

imo

nto

n S

tree

t, K

ey W

est, F

lorida

FO

R

BU

ILD

ING

AN

D S

ITE

DE

VE

LO

PM

EN

T

Seal:

February 15, 2013Date:

Sheet Number:

Title:

Drawn By:

Project #:

Checked By:

Drawing Size

Submissions:

©2012 by mbi | k2m Architecture, Inc.

Consultants:

ARCHITECT:

2013.02.15 - Bidding Documents

1001 Whitehead StreetKey West, Florida 33040

Tel: 305.292.7722Fax: 305.292.2162

Email: [email protected]

PROF. REG. AA26001059

Architecture, Interior Design,Procurement,

Owner Representation,Specialty Consulting

Building RelationshipsBased on Trust and Results

Cleveland | Key West | CharlotteSouthwest Florida | Washington DC

STRUCTURAL ENGINEER:TKW Consulting Engineers5621 Banner Drive,Fort Myers, Florida 33912

CIVIL ENGINEER:Perez Engineering & Development, Inc.1010 Kennedy Dr., Suite 201Key West, Florida 33040

LANDSCAPE ARCHITECTLandscape Architecture, LLC

2525 Ponce de Leon Blvd., Suite 300Coral Gables, Florida 33134

MEP / FP ENGINEER:TLC Engineering for Architecture1400 Colonial Boulevard, Suite 203Fort Myers, Florida 33907

24x36

LAG JTL

Fort Myers, Florida 33912

E-MAIL: [email protected] Certification # 5762

239.278.1992 • FAX 239.278.0922

Survey LB # 734

5621 Banner Drive

CONSULTING ENGINEERS

James T. Lange, P.E.Reg.# 62694TKW Job # 12164.00

2/15/2013 11:47:35 AM

S2.2.4

ROOF EAVEFRAMING PLAN

1/4" = 1'-0"

ROOF EAVE FRAMING PLANFOR FRAMING PLAN NOTES SEE SHEET S1.1.2

Page 9: GENERAL STRUCTURAL NOTES - D.N. Higgins

PRE ENG METAL TRUSSES (TYP)

TG

2

S3.3.5

4

S3.3.5

TRUSS BEARING ELEV37'-4" (TYPICAL)

12

4

12

4

D-1

12

4 12

4

12

4

1

S3.3.5

TRUSS BEARING37'-4" (TYPICAL)

10

S3.3.5

12

4

D-1

12

4

12

4

TG

D-1 D-1

12

4

D-1

TGTRUSS BEARING37'-4" (TYPICAL)

22' - 8" 70' - 8"

93' - 4"5

1' -

10

"

TG

D-1

S3.3.5

9

S3.3.5

8

7

S3.3.5

L3"X3"X1/4", TYP.

L2 1/2"X2 1/2"X1/4", TYP.

3"X3"X1/4" BENT PLATE

1

S3.3.4

8' -

0"

22' - 8" 23' - 1 1/8" 22' - 7" 25' - 0"

93' - 4 1/8"

23' - 1"

93' - 4"

51

' - 1

0"

8' -

11

"

22

' - 1

1"

27

' - 7

"1

' - 4

"

MK-12060

City o

f K

ey W

est, 3

13

2 F

lagle

r A

ven

ue

, K

ey W

est, F

lorida

330

40

FIR

E S

TA

TIO

N #

26

16 S

imo

nto

n S

tree

t, K

ey W

est, F

lorida

FO

R

BU

ILD

ING

AN

D S

ITE

DE

VE

LO

PM

EN

T

Seal:

February 15, 2013Date:

Sheet Number:

Title:

Drawn By:

Project #:

Checked By:

Drawing Size

Submissions:

©2012 by mbi | k2m Architecture, Inc.

Consultants:

ARCHITECT:

2013.02.15 - Bidding Documents

1001 Whitehead StreetKey West, Florida 33040

Tel: 305.292.7722Fax: 305.292.2162

Email: [email protected]

PROF. REG. AA26001059

Architecture, Interior Design,Procurement,

Owner Representation,Specialty Consulting

Building RelationshipsBased on Trust and Results

Cleveland | Key West | CharlotteSouthwest Florida | Washington DC

STRUCTURAL ENGINEER:TKW Consulting Engineers5621 Banner Drive,Fort Myers, Florida 33912

CIVIL ENGINEER:Perez Engineering & Development, Inc.1010 Kennedy Dr., Suite 201Key West, Florida 33040

LANDSCAPE ARCHITECTLandscape Architecture, LLC

2525 Ponce de Leon Blvd., Suite 300Coral Gables, Florida 33134

MEP / FP ENGINEER:TLC Engineering for Architecture1400 Colonial Boulevard, Suite 203Fort Myers, Florida 33907

24x36

LAG JTL

Fort Myers, Florida 33912

E-MAIL: [email protected] Certification # 5762

239.278.1992 • FAX 239.278.0922

Survey LB # 734

5621 Banner Drive

CONSULTING ENGINEERS

James T. Lange, P.E.Reg.# 62694TKW Job # 12164.00

2/15/2013 11:47:35 AM

S2.2.5

ROOFFRAMING

PLAN

1/4" = 1'-0"

ROOF FRAMING PLANFOR FRAMING PLAN NOTESSEE SHEET S1.1.2

Page 10: GENERAL STRUCTURAL NOTES - D.N. Higgins

CONCRETE FOOTING-SEE SCHEDULE

REINFORCING- SEE SCHEDULE

CENTERBAR

CENTERBAR

(1) 2'-0"

NOTE:USE SAME CORNER REINFORCING @ OTHER ANGLED CORNERS.

2'-0"

KEYED JOINT (AT SLAB MID-DEPTH)PAINT W/CURING COMPOUND AS

BOND BREAK BEFORE ADJACENTSLAB IS PLACED

SLABREINF

3/4" SAW CUT (SAWSAME DAY AS POUR)

FILL W/JOINT SEALER

SLABREINF

1/8x3/4" PREMOLDED STRIPFLUSH W/ SURFACE

SAW CUTJOINT

FORMEDJOINT

NOTE: CONTROL JOINTS TO BE 15'-0" OC MAX

CONSTRUCTION JOINT

CONTROL JOINT

(3/4" MIN)

T/4

(1

1/2

" M

IN)

"T"

IV:3H

SEE FTG SCHEDULEFOR SIZE AND REINF AUGERCAST PILE

-SEE PLAN

1/2" COLUMNISOLATION JOINT

11' - 0"

CONC SLAB-SEE PLAN

7' - 0"

2#5 CONT1' - 0"

PRECAST COLUMN ANDCONNECTION BYPRECAST MANUF

(2) #5 x CONT

PRE-ENGINEEREDMETAL LADDER

CONNECTIONBY LADDERMANUFACTURER

1

1

1' - 4"

1' -

0"

#4xCONT

1

14"

- 1

'-0

"

SLAB THICKNESS

0"-

4"

6

1

PRECAST STAIRS-SEE ARCH DRAWINGS

MIN

1' -

0"

SEE FTG SCHEDULEFOR SIZE AND REINF

PRECAST STAIRS-SEE ARCH DRAWINGS

CONNECTION BY MANUF

1' - 4"

MATCH BOTTOMREINFORCING

MATCH FOOTINGREINFORCING1

1

4' - 0" MIN

MIN

1' - 6"

MA

X

2' -

0"

NO AUGERCAST PILESREQUIREDS

EE

PL

AN

SE

E P

LA

N

PROVIDE & COORD CAST IN PLACE WALL PANEL.THICKNESS TO MATCH PRECAST PANEL

PROVIDE #5 @ 12" OC EAWAY W/ 8" EMBED @

CONC STEM WALL

CONC SLAB-SEE PLAN

(2) #5 CONT

1

1

1' -

0"

MIN

.

1' - 0"

1' -

0"

MA

X

2ND POUR

PRECASTCOLUMN

-SEE PLANC

J

THICKENED EDGE

1' -

0"

ISOLATION JOINT

COMPACTED SUB-BASE

GRADE

CONCRETE PAD-SEE ARCH

(1) #4 - 4 SIDES

NOTE:

1. COORDINATE LOCATION OF EQUIPMENT BOLTS AND PAD WITH

EQUIPMENT SUPPLIER'S CERTIFIED DRAWING. SEE ARCH, MECH

AND ELECT DRAWINGS FOR LOCATION AND SIZE OF EQUIPMENT PADS.

8"

MIN8"

TY

P

4"

EQUIPMENT PAD

ISOLATION JOINTALL SIDES

SLAB ONGRADE

NOTE:GENERAL CONTRACTOR TO COORDINATE W/MECH DRAWINGS ANDSPECIFICATIONS TO DETERMINE REQUIREMENTS FOR EQUIPMENT PAD

#4@12 EW T&B

CONC SLAB-SEE PLAN

CONC SLAB-SEE PLAN

CAST-IN-PLACE STAIRS-SEE ARCH DWGS

T.O SLAB

11'-0"

AUGERCAST PILE-SEE PLAN

SEE FTG SCHEDULEFOR SIZE AND REINF

(2) #5 CONT

8"

1' - 4"

T.O SLAB

9'-0"

8"

1' - 0"

1

1

1

1

2"

(2) #5 x CONT

1

1

1' - 4"

1' -

0"

CAST IN PLACE STAIRS

DRILL & EPOXY#5 @ 8" OC TOPW/ 4" EMBED

3' - 0"

3' - 0"

#5 @ 12" OCTRANSV., TYP.

#5 x 3'-0" DOWELS@16" OC T&B, TYP.

#5 @ 12" OCTRANS., TYP.

#5 @ 8" OCBOTTOM, TYP.

#5 @ 8" OCTOP, TYP.

MK-12060

City o

f K

ey W

est, 3

13

2 F

lagle

r A

ven

ue

, K

ey W

est, F

lorida

330

40

FIR

E S

TA

TIO

N #

26

16 S

imo

nto

n S

tree

t, K

ey W

est, F

lorida

FO

R

BU

ILD

ING

AN

D S

ITE

DE

VE

LO

PM

EN

T

Seal:

February 15, 2013Date:

Sheet Number:

Title:

Drawn By:

Project #:

Checked By:

Drawing Size

Submissions:

©2012 by mbi | k2m Architecture, Inc.

Consultants:

ARCHITECT:

2013.02.15 - Bidding Documents

1001 Whitehead StreetKey West, Florida 33040

Tel: 305.292.7722Fax: 305.292.2162

Email: [email protected]

PROF. REG. AA26001059

Architecture, Interior Design,Procurement,

Owner Representation,Specialty Consulting

Building RelationshipsBased on Trust and Results

Cleveland | Key West | CharlotteSouthwest Florida | Washington DC

STRUCTURAL ENGINEER:TKW Consulting Engineers5621 Banner Drive,Fort Myers, Florida 33912

CIVIL ENGINEER:Perez Engineering & Development, Inc.1010 Kennedy Dr., Suite 201Key West, Florida 33040

LANDSCAPE ARCHITECTLandscape Architecture, LLC

2525 Ponce de Leon Blvd., Suite 300Coral Gables, Florida 33134

MEP / FP ENGINEER:TLC Engineering for Architecture1400 Colonial Boulevard, Suite 203Fort Myers, Florida 33907

24x36

LAG JTL

Fort Myers, Florida 33912

E-MAIL: [email protected] Certification # 5762

239.278.1992 • FAX 239.278.0922

Survey LB # 734

5621 Banner Drive

CONSULTING ENGINEERS

James T. Lange, P.E.Reg.# 62694TKW Job # 12164.00

2/15/2013 11:47:35 AM

S3.3.1

DETAILSAND

SECTIONS

3/4" = 1'-0"1

TYPICAL FOOTINGCORNER DETAIL

3/4" = 1'-0"2

TYPICAL SLABJOINT DETAILS

3/4" = 1'-0"6

COLUMN FOUNDATION

3/4" = 1'-0"11

PRE ENGINEEREDMETAL LADDER FOOTING

3/4" = 1'-0"4

TYPICAL STEPPED SLAB

3/4" = 1'-0"9

PRECAST STAIR FOOTINGS

1/2" = 1'-0"5

TYPICAL STEPPEDFOOTING DETAIL

3/4" = 1'-0"3

TYPICAL THICKENED SLAB

3/4" = 1'-0"7

TYPICAL ISOLATION JOINT

3/4" = 1'-0"13

EQUIPMENT PAD

3/4" = 1'-0"12

EQUIPMENT PAD

3/4" = 1'-0"8

STAIR DETAIL

3/4" = 1'-0"10

CAST IN PLACE STAIRS

Page 11: GENERAL STRUCTURAL NOTES - D.N. Higgins

1/8" CHAMFER

COORD W/ TRENCHDRAIN MANUF

CO

OR

D W

/ T

RE

NC

HD

RA

IN M

AN

UF

ENG FILL

8" CONC SLAB ON GRADE,SLOPED TOWARD DRAIN

TRENCH DRAIN AND GRATESUPPORT BY OTHERS. REFPLUMBING DRAWINGS. INSTALLPER MANUF RECOMMENDATIONS.

6"

MIN

10" MIN 10" MIN

(3) #5 CONT BOT(2) #5 CONT TOP#3 STIRRUPS @ 24" OC

PRECASTCOLUMN

SEE FTG SCHEDULEFOR SIZE AND REINF

COLUMN TO FOOTINGCONNECTIONS BYPRECAST MANUF

AUGERCAST PILE-SEE PLAN

11' - 0"

CONC SLAB-SEE PLAN

7' - 0"

2#5 CONT

1' -

0"

MIN

.

1' - 0"

VA

RIE

S1

' - 0

" M

AX

11" PRECASTCOMPOSITEWALL PANELCONC SLAB

-SEE PLAN

SEE FTG SCHEDULEFOR SIZE AND REINF

FOOTING TO PANELCONNECTIONS BYPRECAST MANUF

AUGERCASTPILE-SEE PLAN

1'-0

" M

IN.

2#5 CONT

1/2" EXP JOINT

1' - 0"

CL

5 1/2"

T.O. SLAB

SEE PLAN

CONC SLAB-SEE PLAN

11'-0"

T.O. SLAB

(4) #5 LW BOT#5 @ 12" O.C. SW BOT

4" CMU WALL

3' - 0"

1' - 6"

AUGERCAST PILESEE PLAN

SEE FTG SCHEDULEFOR SIZE AND REINF

ARCH. PRECAST COLUMN-SEE ARCH DWGS

CONC SLAB-SEE PLAN

STRUCTURALPRECAST COLUMN

STRUCT.

1' - 7"

(2) #5 CONT

SEE CIVIL DWGS

1' - 0"

7' - 0"

1/2" EXP JOINT

1/2"

9' - 0"

ARCH.

1' - 10"

5 1/2" TO EXT. FACE

.EXTERIOR FACE OF STRUCTURALPANELS, COLUMNS & BEAMS

9'-0"

SEE FTG SCHEDULEFOR SIZE AND REINF

CONC SLAB-SEE PLAN

AUGERCAST PILE-SEE PLAN

(3) #5 CONT

1

1

SEE ARCH. COORD W/ DOOR

#5x1'-4"x6'-0"@ 24"OC

CONC SLAB-SEE CIVIL DWGS

3K (MIN)

EA SIDE OF DOOR

DOOR LOCKING MECHANISM REQ'D TORESIST WIND PRESSURE. REFER TO DOOR

MANUF FOR LOCATION AND LOADS. HYDRAULIC DOOR &FRAME BY OTHERS

5 1/2" TO EXT. FACE

#5 @ 24" O.C.

7' - 0"

EXTERIOR FACE OF STRUCTURALPANELS, COLUMNS, & BEAMS

2' - 2"

SLAB EDGE

FOUNDATION-SEE PLAN

ARCHITECTURALPRECAST COLUMN-SEE ARCH DWGS

STRUCT.

1' - 7"

4' -

0"

ARCH.

1' - 10"

EXTERIOR FACE OF STRUCTURALPANELS, COLUMNS & BEAMS

ARMOR CORNERSFOR DOORS

STRUCTURALPRECAST COLUMN

1' -

0"

(2) #5 CONT

CONC SLAB-SEE PLAN

6" PRECASTWALL PANEL

FOOTING TO PANELCONNECTIONS BYPRECAST MANUF

1' - 0"

1' -

0"

(2) #5 CONT

CONC SLAB-SEE PLAN

1' - 0"

T.O. SLAB

SEE PLAN

1' -

0"

(2) #5 CONT

CONC SLAB-SEE PLAN

1' - 0"

1' -

0"

(2) #5 CONT

CONC SLAB-SEE PLAN

1' - 0"

11'-0"

48

BA

R D

IA

9 GA. LADDER TYPEHORIZONTAL REINF.AT 16" O.C.

8" CMU WALLW/ #5 @ 24" O.C

GROUT SOLIDBELOW GRADE

7'-0"

1' -

0"

(2) #5 CONT

CONC SLAB-SEE PLAN

1' - 0"

11'-0"

48

BA

R D

IA

GROUT SOLIDBELOW GRADE

7'-0"

8" CMU WALLW/ #5 @ 48" O.C

#5 BAR @ 24" O.C.4'-0"

(1) #5 CONT.

SEE FTG SCHEDULEFOR SIZE AND REINF

1' -

0"

(2) #5 CONT BOT

CONC SLAB-SEE PLAN

1' - 0"

11'-0"

48

BA

R D

IA

7'-0"

12" CONCRETE WALLWITH #5 @ 12" O.C.EA. WAY EA. FACE

1' - 0"

45.0

#4 @ 10" T & B

(1) #4 @ MIDDEPTH OF SLAB

PRE CAST PANEL

1/2" COMPRESSIBLEFILLER X WIDTH &DEPTH OF SLAB (TYP)OPENING

CLR

1 1

/2"

HOOK TOP BARS

2'-0

" (TY

P)

4'-0

" M

IN

MK-12060

City o

f K

ey W

est, 3

13

2 F

lagle

r A

ven

ue

, K

ey W

est, F

lorida

330

40

FIR

E S

TA

TIO

N #

26

16 S

imo

nto

n S

tree

t, K

ey W

est, F

lorida

FO

R

BU

ILD

ING

AN

D S

ITE

DE

VE

LO

PM

EN

T

Seal:

February 15, 2013Date:

Sheet Number:

Title:

Drawn By:

Project #:

Checked By:

Drawing Size

Submissions:

©2012 by mbi | k2m Architecture, Inc.

Consultants:

ARCHITECT:

2013.02.15 - Bidding Documents

1001 Whitehead StreetKey West, Florida 33040

Tel: 305.292.7722Fax: 305.292.2162

Email: [email protected]

PROF. REG. AA26001059

Architecture, Interior Design,Procurement,

Owner Representation,Specialty Consulting

Building RelationshipsBased on Trust and Results

Cleveland | Key West | CharlotteSouthwest Florida | Washington DC

STRUCTURAL ENGINEER:TKW Consulting Engineers5621 Banner Drive,Fort Myers, Florida 33912

CIVIL ENGINEER:Perez Engineering & Development, Inc.1010 Kennedy Dr., Suite 201Key West, Florida 33040

LANDSCAPE ARCHITECTLandscape Architecture, LLC

2525 Ponce de Leon Blvd., Suite 300Coral Gables, Florida 33134

MEP / FP ENGINEER:TLC Engineering for Architecture1400 Colonial Boulevard, Suite 203Fort Myers, Florida 33907

24x36

LAG JTL

Fort Myers, Florida 33912

E-MAIL: [email protected] Certification # 5762

239.278.1992 • FAX 239.278.0922

Survey LB # 734

5621 Banner Drive

CONSULTING ENGINEERS

James T. Lange, P.E.Reg.# 62694TKW Job # 12164.00

2/15/2013 11:47:38 AM

S3.3.2

DETAILSAND

SECTIONS

1 1/2" = 1'-0"9

TRENCH DETAIL

3/4" = 1'-0"2

COLUMN FOOTING @ ARCADE

3/4" = 1'-0"1

TYPICAL WALL FOOTING

3/4" = 1'-0"5

THICKENED SLAB AT WALL CHASE

3/4" = 1'-0"4

COLUMN FOOTING DETAILAT FIRE STATION DOORS

3/4" = 1'-0"8

DOOR THRESHOLD

3/4" = 1'-0"7

COLUMN SECTION

3/4" = 1'-0"6

NON-BEARING WALL FOOTING

3/4" = 1'-0"3

FOOTING @ CMU WALL

3/4" = 1'-0"10

MASONRY STEMWALL

3/4" = 1'-0"11

CONCRETE WALL

3/4" = 1'-0"12

SLAB ON GRADE@ WALL OPENING

Page 12: GENERAL STRUCTURAL NOTES - D.N. Higgins

WELD PLATE CONNBY PRECAST MNF

8" SOLID PRECASTPLANK - SEE PLAN

INSULATEDPRECAST WALL

8"x12" CORBEL

OPENING

STEEL HEADERSWHERE REQDBY MANUF

PC

PL

AN

K S

PA

N

24" DOUBLE TEE-SEE PLAN

CORBEL

TOPPING-SEE PLAN

11" PRECASTCOMPOSITEWALL PANEL

FIN FLR

25'-10"

BEARING

24'-8 1/4"

PRECAST PLANKW/ TOPPING

-SEE PLAN

FIN FLR

25'-10"

11" PRECASTCOMPOSITEWALL PANEL

PRE ENGINEEREDMETAL TRUSS &

CONNECTION BYOTHERS

8" PRECAST SLABW/ 2" TOPPING

12"X24"PRECAST BEAM

PRECAST GUARD &RAIL - SEE ARCH.

FIN. FLOOR

25'-10"

11" PRECASTCOMPOSITE WALL

PANEL PRECAST DOUBLE TEEW/ TOPPING -SEE PLAN

8"x12" CORBEL

FIN FLR

25'-10"

PRE ENGINEEREDMETAL TRUSS &

CONNECTION BYOTHERS

WELD PLATE CONNBY PRECAST MANUF

PRECAST DOUBLE TEE W/TOPPING -SEE PLAN

8"x12" CORBEL

PRECAST PLANK W / TOPPING-SEE PLAN

11" PRECASTCOMPOSITE WALL

PANEL

FIN FLR

25'-10"

WELD PLATE CONNBY PRECAST MNF

PRECAST PLANKW/ TOPPING

-SEE PLAN

8"x12" CORBEL

FIN FLR

25'-10"

11" PRECASTCOMPOSITEWALL PANEL

PRE ENGINEEREDMETAL TRUSS &

CONNECTION BYOTHERS

2' -

6 1

/4"

SPANDREL BEAM

SPANDREL BEAM

PRECAST COLUMNSEE PLAN

ARCHPRECAST CAP

10"3' - 0"8"

4' - 6"

1' -

6"

1' -

6"

1' -

0"

4' -

0"

2' -

0"

2' -

0"

4"

4" HOUSEKEEPER SLAB W/6x6-W1.4xW1.4 WWF & (1) #4CONT AROUND PERIMETER

DRILL & EPOXY 1/2" DIAx6" DOWELSW/ 3" EMBED @ 24" OC AROUNDPERIMETER

PRECAST PLANK

EMBED PLATE3/8"x10"x0'-10"

W/ (40 3/4"DIA x 5" HS

1/4"x4"x6" PLATE WELED TOEMBED PLATE EA. SIDE OF

WALL @ 48" O.C. (MAX)

3/16 6 @ 482 SIDES

17'-11"

8" SOLIDPRECAST PLANK

WITH NON STRUCTURALCONCRETE TOPPING

17'-11"

8" SOLIDPRECAST PLANK

WITH NON STRUCTURALCONCRETE TOPPING

EMBED PLATE3/8"x10"x0'-10"

W/ (40 3/4"DIA x 5" HS

1/4"x4"x6" PLATE WELED TOEMBED PLATE EA. SIDE OF

WALL @ 48" O.C. (MAX)

3/16 6 @ 482 SIDES

8" BOND BEAMW/ 1#5 CONT.

MK-12060

City o

f K

ey W

est, 3

13

2 F

lagle

r A

ven

ue

, K

ey W

est, F

lorida

330

40

FIR

E S

TA

TIO

N #

26

16 S

imo

nto

n S

tree

t, K

ey W

est, F

lorida

FO

R

BU

ILD

ING

AN

D S

ITE

DE

VE

LO

PM

EN

T

Seal:

February 15, 2013Date:

Sheet Number:

Title:

Drawn By:

Project #:

Checked By:

Drawing Size

Submissions:

©2012 by mbi | k2m Architecture, Inc.

Consultants:

ARCHITECT:

2013.02.15 - Bidding Documents

1001 Whitehead StreetKey West, Florida 33040

Tel: 305.292.7722Fax: 305.292.2162

Email: [email protected]

PROF. REG. AA26001059

Architecture, Interior Design,Procurement,

Owner Representation,Specialty Consulting

Building RelationshipsBased on Trust and Results

Cleveland | Key West | CharlotteSouthwest Florida | Washington DC

STRUCTURAL ENGINEER:TKW Consulting Engineers5621 Banner Drive,Fort Myers, Florida 33912

CIVIL ENGINEER:Perez Engineering & Development, Inc.1010 Kennedy Dr., Suite 201Key West, Florida 33040

LANDSCAPE ARCHITECTLandscape Architecture, LLC

2525 Ponce de Leon Blvd., Suite 300Coral Gables, Florida 33134

MEP / FP ENGINEER:TLC Engineering for Architecture1400 Colonial Boulevard, Suite 203Fort Myers, Florida 33907

24x36

LAG JTL

Fort Myers, Florida 33912

E-MAIL: [email protected] Certification # 5762

239.278.1992 • FAX 239.278.0922

Survey LB # 734

5621 Banner Drive

CONSULTING ENGINEERS

James T. Lange, P.E.Reg.# 62694TKW Job # 12164.00

2/15/2013 11:47:39 AM

S3.3.3

DETAILSAND

SECTIONS

3/4" = 1'-0"5

WALL SECTION @MEZZANINE

3/4" = 1'-0"11

TYPICALPRECAST OPENING

3/4" = 1'-0"2

WALL SECTION

3/4" = 1'-0"7

WALL SECTION

1/2" = 1'-0"10

ELEVATED WALKWAY

3/4" = 1'-0"8

WALL SECTION

3/4" = 1'-0"1

WALL SECTION

3/4" = 1'-0"6

WALL SECTION

3/4" = 1'-0"12

TYPICAL COLUMN SECTION

1" = 1'-0"9

HOUSEKEEPING PAD

3/4" = 1'-0"3

T.O PRECAST WALL @ MEZZ

3/4" = 1'-0"4

T.O. CMU WALL

Page 13: GENERAL STRUCTURAL NOTES - D.N. Higgins

DOUBLE TEE-SEE PLAN

CONC TOPPING-SEE PLAN

8X30 PRECAST BEAM-SEE PLAN

PRECAST COMPOSITEWALL PANEL BEYOND

11X42 SPANDRELBEAM - SEE PLAN

T.O BEAM 27' - 4"

T.O SLAB

25'-10"

36" MIN. TO FIRST TEE

ARMOR EDGESFOR DOOR

COLUMNBELOW

8x30+ DOORBEAM BELOW

DOUBLE TEECORBEL

11" PRECAST COMPWALL PANEL

11"

11x42SPANDREL BEAM-SEE PLAN

12x54 PRECASTCOLUMN- SEE PLAN

1

S3.3.4

8" 1' - 10"

4' - 6"

11X42 SPANDRELBEAM -SEE PLAN

11"

11" PRECAST COMPWALL PANEL

12x33 PRECASTCOLUMN

DOUBLE TEE BELOW

8x30+ DOORBEAM BELOW

1' - 10"8"

COLUMNBELOW

CONC TOPPING-SEE PLAN

8x30+PRECAST BEAM

-SEE PLAN

PRECAST COMPOSITEWALL PANEL

DOUBLE TEE-SEE PLAN

1' - 1" 3" 3"

24' - 8"

27' - 4"

12x33PRECAST COLUMN

T.O SLAB

25'-10"

4

S3.3.4

1' - 7"

1' - 10"

1' -

0"

11"

12x33PRECAST COLUMN

SPANDREL BEAM-SEE PLAN

COLUMN BELOW

PRE ENGINEEREDPRECAST GUTTER

12X54 PRECASTCOLUMN

27' - 4"

24' - 8"

35' - 6"

11X47 PRECASTBEAM

8X30 PRECASTBEAM BEYOND

11X42 PRECASTBEAM BEYOND

PRE ENGINEERED METAL TRUSSES

METAL ROOF DECK-SEE PLANS

11" PRECAST COMPOSITE PANEL

11" PRECASTCOMP. PANEL

MK-12060

City o

f K

ey W

est, 3

13

2 F

lagle

r A

ven

ue

, K

ey W

est, F

lorida

330

40

FIR

E S

TA

TIO

N #

26

16 S

imo

nto

n S

tree

t, K

ey W

est, F

lorida

FO

R

BU

ILD

ING

AN

D S

ITE

DE

VE

LO

PM

EN

T

Seal:

February 15, 2013Date:

Sheet Number:

Title:

Drawn By:

Project #:

Checked By:

Drawing Size

Submissions:

©2012 by mbi | k2m Architecture, Inc.

Consultants:

ARCHITECT:

2013.02.15 - Bidding Documents

1001 Whitehead StreetKey West, Florida 33040

Tel: 305.292.7722Fax: 305.292.2162

Email: [email protected]

PROF. REG. AA26001059

Architecture, Interior Design,Procurement,

Owner Representation,Specialty Consulting

Building RelationshipsBased on Trust and Results

Cleveland | Key West | CharlotteSouthwest Florida | Washington DC

STRUCTURAL ENGINEER:TKW Consulting Engineers5621 Banner Drive,Fort Myers, Florida 33912

CIVIL ENGINEER:Perez Engineering & Development, Inc.1010 Kennedy Dr., Suite 201Key West, Florida 33040

LANDSCAPE ARCHITECTLandscape Architecture, LLC

2525 Ponce de Leon Blvd., Suite 300Coral Gables, Florida 33134

MEP / FP ENGINEER:TLC Engineering for Architecture1400 Colonial Boulevard, Suite 203Fort Myers, Florida 33907

24x36

LAG JTL

Fort Myers, Florida 33912

E-MAIL: [email protected] Certification # 5762

239.278.1992 • FAX 239.278.0922

Survey LB # 734

5621 Banner Drive

CONSULTING ENGINEERS

James T. Lange, P.E.Reg.# 62694TKW Job # 12164.00

2/15/2013 11:47:39 AM

S3.3.4

DETAILSAND

SECTIONS

3/4" = 1'-0"6

DETAIL @ FIRE STATIONENTRANCE

3/4" = 1'-0"2

COLUMN SECTION(HIGH CORNER)

3/4" = 1'-0"3

COLUMN SECTION HIGH

3/4" = 1'-0"5

SECTION @ GARAGE DOOR

3/4" = 1'-0"4

SPANDREL SECTION

3/4" = 1'-0"1

COLUMN DETAIL

Page 14: GENERAL STRUCTURAL NOTES - D.N. Higgins

35' - 6"

PRE ENGINEEREDMETAL TRUSSES-SEE PLAN

INSULATED PRECASTCOMPOSITE

SOFFIT PANEL

CONN BYPRECASTER

3" 7

"6

"2

"

3"

4"

PRE ENGINEERED METAL TRUSSESAND CONNECTIONS BY OTHERS

1 1/2" METAL ROOF DECK

37' - 4"

PRE ENGINEEREDPRECAST GUTTER

11" PRECAST COMPOSITEWALL PANEL

NOTE: STATED TRUSS REACTIONS ARE UNFACTORED MINIMUMDESIGN REQ'T'S FOR THE EMBED PLATES. ACTUAL DESIGNREACTIONS SHALL BE USED WHEN THEY EXCEED THESE VALUES.

TRUSS BRG

4x4x12 GA BENT PLATE CONTW/ 1/2" DIA x 3" CONC SCREWARCH'S @ 18" OC INTO PRECAST

EMBED PLATE FOR TRUSSCONN SUPPLIED BY TRUSS

MANUF, INSTALLED BYPRECASTER

P=35K(MIN)

38' - 9"

35' - 6"

PRE ENGINEEREDPRECAST CUTTER

11x47 PRECAST BEAM-SEE PLAN

35' - 6"

PRE ENGINEERED METAL TRUSSESAND CONNECTIONS BY OTHERS

1 1/2" METAL ROOF DECK-SEE PLANS

COLUMN BEYOND

4x4x18GA BENT PLATE CONTW/ 1/4" DIA x 2" CONC SCREWARCH'S @ 18" OC INTO PRECAST

T.O PLANK

TRUSS CONNECTION. PRECASTER TO COORDEMBED LOCATIONS W/ TRUSS SHOP DRAWINGS

EMBED PLATE FOR TRUSSCONNECTION SUPPLIED BYTRUSS MANUF, INSTALLEDBY PRECASTER

INSULATED PRECAST COMPOSITESOFFIT PANEL

PRECASTGUTTER

PRECAST BEAM-SEE PLAN

37' - 2"

PRECAST BEAM-SEE PLAN

PRE ENGINEEREDMETAL TRUSS ANDCONNECTIONS BY

OTHERS

METAL ROOF DECK-SEE PLAN

PLYWOOD SHEATHING-SEE ARCH

& A

DJU

ST

1"

FO

R S

HIM

CONN BYPRECASTER

3"

3"

4"

7"

6"

38' - 9"

2"

& A

DJU

ST

1"

FO

R S

HIM

38' - 0"

1 1/2" METAL ROOF DECK

#12 SCREWS @ 6" OC

MIN 4x4x18GA BENTPLATE CONT

1 1/2" METAL ROOF DECK

#12 SCREWS @ 6" OCMIN 4x4x18GA BENTPLATE CONT

PRE ENGINEEREDMETAL TRUSS

LG TRUSSES @ 4'-0" MAX.(SPACED BTWN COLUMNS)

TRUSS GIRDERS AT COLUMNS

3/8" EMBED PLATE

PRECASTCOLUMN

18" DP LG SPANDRELTRUSS GIRDER

METAL GUTTER,SEE ARCH.

TRUSS CONNECTION BYMANUFACTURER

45.0

+/-

L3"X3"X1/4"

L2 1/2" X 2 1/2" X 1/4"

PRE ENGINEERED METAL TRUSS

1/8 3

1/8 1

1/8 1

1/8 3

L2 1/2" X 2 1/2" X 1/4"

45.0

0° +

/-

PRE ENGINEERED METAL TRUSS

3/16 2

3"X3"X1/4"BENT PLATE

L2 1/2" X 2 1/2" X 1/4"

L2 1/2" X 2 1/2" X 1/4"

8' - 0"

L3"X3"X1/4"

L2 1/2" X 2 1/2" X 1/4"

PRE ENGINEERED METAL TRUSS

3"X3"X1/4"BENT PLATE

1/8 2

1/8 1

1/8 1

3/16 4

11" PRECASTCOMPOSITE

WALL PANEL

EMBED PLATE3/8" x 12" x 1'-0" W/4 - 3/4" DIA. x 6" HS@ PANEL POINTS

(APPROX. 8 FTOC)

3/16 2

38'-0"

2"

2"

8"

2" 8" 2"

1' - 0"

2"

8"

2"

1' -

0"

EMBED PLATE3/8" x 12" x 1'-0"W/ 4 - 3/4" DIA. x 6" HS

MK-12060

City o

f K

ey W

est, 3

13

2 F

lagle

r A

ven

ue

, K

ey W

est, F

lorida

330

40

FIR

E S

TA

TIO

N #

26

16 S

imo

nto

n S

tree

t, K

ey W

est, F

lorida

FO

R

BU

ILD

ING

AN

D S

ITE

DE

VE

LO

PM

EN

T

Seal:

February 15, 2013Date:

Sheet Number:

Title:

Drawn By:

Project #:

Checked By:

Drawing Size

Submissions:

©2012 by mbi | k2m Architecture, Inc.

Consultants:

ARCHITECT:

2013.02.15 - Bidding Documents

1001 Whitehead StreetKey West, Florida 33040

Tel: 305.292.7722Fax: 305.292.2162

Email: [email protected]

PROF. REG. AA26001059

Architecture, Interior Design,Procurement,

Owner Representation,Specialty Consulting

Building RelationshipsBased on Trust and Results

Cleveland | Key West | CharlotteSouthwest Florida | Washington DC

STRUCTURAL ENGINEER:TKW Consulting Engineers5621 Banner Drive,Fort Myers, Florida 33912

CIVIL ENGINEER:Perez Engineering & Development, Inc.1010 Kennedy Dr., Suite 201Key West, Florida 33040

LANDSCAPE ARCHITECTLandscape Architecture, LLC

2525 Ponce de Leon Blvd., Suite 300Coral Gables, Florida 33134

MEP / FP ENGINEER:TLC Engineering for Architecture1400 Colonial Boulevard, Suite 203Fort Myers, Florida 33907

24x36

LAG JTL

Fort Myers, Florida 33912

E-MAIL: [email protected] Certification # 5762

239.278.1992 • FAX 239.278.0922

Survey LB # 734

5621 Banner Drive

CONSULTING ENGINEERS

James T. Lange, P.E.Reg.# 62694TKW Job # 12164.00

2/15/2013 11:47:40 AM

S3.3.5

DETAILSAND

SECTIONS

3/4" = 1'-0"3

ROOF DETAIL

3/4" = 1'-0"4

ROOF DETAIL

3/4" = 1'-0"1

ROOF DETAIL

3/4" = 1'-0"2

ROOF DETAIL @ BALCONY

1 1/2" = 1'-0"11

HIP SECTION

1 1/2" = 1'-0"10

RIDGE SECTION

1/2" = 1'-0"6

ROOF SECTION @ COVERED PORCH

1" = 1'-0"9

TRUSS DETAIL @ ANGLE

1" = 1'-0"8

TRUSS DETAIL @ BENT PLATE

1" = 1'-0"7

TRUSS SECTION

1 1/2" = 1'-0"12

8"x12" EMBED PLATE

Page 15: GENERAL STRUCTURAL NOTES - D.N. Higgins

TO LANDING

SEE ARCH DWGS

T.O SLAB

SEE PLAN

PRECAST LANDINGW/ TOPPING

PRECAST STAIRSBEYOND

PRECAST STAIRS

PRECAST LANDING

PRECAST WALL

PRECAST WALL

SEE FTG SCHEDULEFOR SIZE AND REINFORCING

AUGERCAST PILE-SEE PLAN

(2) #5 CONT1' - 0"

CONC SLAB- SEE PLAN

1' - 4"

1' -

0"

(2) # 5 CONT

SEE FTG SCHEDULEFOR SIZE AND REINFORCING

1' - 0"

(2) #5 CONT

CONC SLAB- SEE PLAN

T.O LANDING

SEE ARCH

1' -

0"

1' - 0"

(2) #5 CONT

CONC SLAB- SEE PLAN

1' - 0"

(2) #5 CONT

SOFFIT PRECAST SOFFIT

PRE ENGINEEREDMETAL TRUSS - SEEPLAN

PRE ENGINEEREDMETAL TRUSSES-SEE PLAN

TO WALL

SEE ARCH DWGS

PRECAST GUTTER

TO WALL

SEE ARCH DWGS

PRECAST GUTTER

MK-12060

City o

f K

ey W

est, 3

13

2 F

lagle

r A

ven

ue

, K

ey W

est, F

lorida

330

40

FIR

E S

TA

TIO

N #

26

16 S

imo

nto

n S

tree

t, K

ey W

est, F

lorida

FO

R

BU

ILD

ING

AN

D S

ITE

DE

VE

LO

PM

EN

T

Seal:

February 15, 2013Date:

Sheet Number:

Title:

Drawn By:

Project #:

Checked By:

Drawing Size

Submissions:

©2012 by mbi | k2m Architecture, Inc.

Consultants:

ARCHITECT:

2013.02.15 - Bidding Documents

1001 Whitehead StreetKey West, Florida 33040

Tel: 305.292.7722Fax: 305.292.2162

Email: [email protected]

PROF. REG. AA26001059

Architecture, Interior Design,Procurement,

Owner Representation,Specialty Consulting

Building RelationshipsBased on Trust and Results

Cleveland | Key West | CharlotteSouthwest Florida | Washington DC

STRUCTURAL ENGINEER:TKW Consulting Engineers5621 Banner Drive,Fort Myers, Florida 33912

CIVIL ENGINEER:Perez Engineering & Development, Inc.1010 Kennedy Dr., Suite 201Key West, Florida 33040

LANDSCAPE ARCHITECTLandscape Architecture, LLC

2525 Ponce de Leon Blvd., Suite 300Coral Gables, Florida 33134

MEP / FP ENGINEER:TLC Engineering for Architecture1400 Colonial Boulevard, Suite 203Fort Myers, Florida 33907

24x36

LAG JTL

Fort Myers, Florida 33912

E-MAIL: [email protected] Certification # 5762

239.278.1992 • FAX 239.278.0922

Survey LB # 734

5621 Banner Drive

CONSULTING ENGINEERS

James T. Lange, P.E.Reg.# 62694TKW Job # 12164.00

2/15/2013 11:47:40 AM

S3.3.6

DETAILSAND

SECTIONS

1/2" = 1'-0"1

STAIR SECTION

Page 16: GENERAL STRUCTURAL NOTES - D.N. Higgins

Seal:

ARCHITECT:

February 15, 2013Date:

Sheet Number:

Title:

Drawn By:

Project #:

Checked By:

Drawing Size

Submissions:

MK-12060

1001 Whitehead StreetKey West, Florida 33040

Tel: 305.292.7722Fax: 305.292.2162

Email: [email protected]

PROF. REG. AA26001059

Architecture, Interior Design,Procurement,

Owner Representation,Specialty Consulting

Building RelationshipsBased on Trust and Results

Cleveland | Key West | Charlotte

Southwest Florida | Washington DC

Consultants:

24x36

STRUCTURAL ENGINEER:TKW Consu lt ing En gineers5621 Ba nner Drive,For t Myers, F lo r ida 33912

CIVIL ENGINEER:

LANDSCAPE ARCHITECTLandscape A rchi te ct ure, LLC2525 Ponce de Leon Blvd., Suite 300Coral Gables, Florida 33134

MEP / FP ENGINEER:TLC E ng inee ring f or A rchi tecture1400 Co lonial B ou leva rd , Suite 203For t Myers, F lo r ida 33907

P erez E ng inee ring & Development, Inc.1010 Ke nnedy Dr. , Sui te 201K ey West, F lo r ida 33040

2013.02.15 - Bidding Documents

City

of K

ey W

est,

3132

Fla

gler

Ave

nue,

Key

Wes

t, Fl

orid

a 33

040

©2013 by mbi | k2m Architecture, Inc.

FIR

E ST

ATIO

N #

261

6 S

imon

ton

Stre

et, K

ey W

est,

Flor

ida

FOR

BU

ILD

ING

AN

D S

ITE

DE

VE

LOP

ME

NT

M0.1.1

LEGEND, GENERALNOTES, SHEET INDEX

HVAC

TCH LTE

Page 17: GENERAL STRUCTURAL NOTES - D.N. Higgins

STAIR #1001

STAIR #2002

STORAGE102

RESTROOM103

LAUNDRY104

MENS RESTROOM106

WOMENS RESTROOM105

TRUCK AND EQUIPMENT BAY101

COVERED ARCADE003

NOTES KEYED TO PLAN

Seal:

ARCHITECT:

February 15, 2013Date:

Sheet Number:

Title:

Drawn By:

Project #:

Checked By:

Drawing Size

Submissions:

MK-12060

1001 Whitehead StreetKey West, Florida 33040

Tel: 305.292.7722Fax: 305.292.2162

Email: [email protected]

PROF. REG. AA26001059

Architecture, Interior Design,Procurement,

Owner Representation,Specialty Consulting

Building RelationshipsBased on Trust and Results

Cleveland | Key West | Charlotte

Southwest Florida | Washington DC

Consultants:

24x36

STRUCTURAL ENGINEER:TKW Consu lt ing En gineers5621 Ba nner Drive,For t Myers, F lo r ida 33912

CIVIL ENGINEER:

LANDSCAPE ARCHITECTLandscape A rchi te ct ure, LLC2525 Ponce de Leon Blvd., Suite 300Coral Gables, Florida 33134

MEP / FP ENGINEER:TLC E ng inee ring f or A rchi tecture1400 Co lonial B ou leva rd , Suite 203For t Myers, F lo r ida 33907

P erez E ng inee ring & Development, Inc.1010 Ke nnedy Dr. , Sui te 201K ey West, F lo r ida 33040

2013.02.15 - Bidding Documents

City

of K

ey W

est,

3132

Fla

gler

Ave

nue,

Key

Wes

t, Fl

orid

a 33

040

©2013 by mbi | k2m Architecture, Inc.

FIR

E ST

ATIO

N #

261

6 S

imon

ton

Stre

et, K

ey W

est,

Flor

ida

FOR

BU

ILD

ING

AN

D S

ITE

DE

VE

LOP

ME

NT

M1.1.1

FIRST FLOORPLAN - HVAC

SCALE: 1/4" = 1'-0"

FIRST FLOOR PLAN - HVAC

N

TCH LTE

Page 18: GENERAL STRUCTURAL NOTES - D.N. Higgins

STAIR #1001

LIVING AREA202

KITCHEN201

EXERCISE ROOM218

ENTRY217

LAUNDRY216

BATHROOM215

BATHROOM214

HALLWAY213

JANITOR212

BALCONY203

OFFICE205

BEDROOM 1206

BEDROOM 2207

BEDROOM 3208

BEDROOM 4209

BEDROOM 5210

BEDROOM 6211

DINING204

OPEN STORAGE

STORAGE220

ELEC. ROOM219

NOTES KEYED TO PLAN

Seal:

ARCHITECT:

February 15, 2013Date:

Sheet Number:

Title:

Drawn By:

Project #:

Checked By:

Drawing Size

Submissions:

MK-12060

1001 Whitehead StreetKey West, Florida 33040

Tel: 305.292.7722Fax: 305.292.2162

Email: [email protected]

PROF. REG. AA26001059

Architecture, Interior Design,Procurement,

Owner Representation,Specialty Consulting

Building RelationshipsBased on Trust and Results

Cleveland | Key West | Charlotte

Southwest Florida | Washington DC

Consultants:

24x36

STRUCTURAL ENGINEER:TKW Consu lt ing En gineers5621 Ba nner Drive,For t Myers, F lo r ida 33912

CIVIL ENGINEER:

LANDSCAPE ARCHITECTLandscape A rchi te ct ure, LLC2525 Ponce de Leon Blvd., Suite 300Coral Gables, Florida 33134

MEP / FP ENGINEER:TLC E ng inee ring f or A rchi tecture1400 Co lonial B ou leva rd , Suite 203For t Myers, F lo r ida 33907

P erez E ng inee ring & Development, Inc.1010 Ke nnedy Dr. , Sui te 201K ey West, F lo r ida 33040

2013.02.15 - Bidding Documents

City

of K

ey W

est,

3132

Fla

gler

Ave

nue,

Key

Wes

t, Fl

orid

a 33

040

©2013 by mbi | k2m Architecture, Inc.

FIR

E ST

ATIO

N #

261

6 S

imon

ton

Stre

et, K

ey W

est,

Flor

ida

FOR

BU

ILD

ING

AN

D S

ITE

DE

VE

LOP

ME

NT

M1.1.2

SECOND FLOORPLAN - HVAC

SCALE: 1/4" = 1'-0"

SECOND FLOOR PLAN - HVAC

N

TCH LTE

Page 19: GENERAL STRUCTURAL NOTES - D.N. Higgins

Seal:

ARCHITECT:

February 15, 2013Date:

Sheet Number:

Title:

Drawn By:

Project #:

Checked By:

Drawing Size

Submissions:

MK-12060

1001 Whitehead StreetKey West, Florida 33040

Tel: 305.292.7722Fax: 305.292.2162

Email: [email protected]

PROF. REG. AA26001059

Architecture, Interior Design,Procurement,

Owner Representation,Specialty Consulting

Building RelationshipsBased on Trust and Results

Cleveland | Key West | Charlotte

Southwest Florida | Washington DC

Consultants:

24x36

STRUCTURAL ENGINEER:TKW Consu lt ing En gineers5621 Ba nner Drive,For t Myers, F lo r ida 33912

CIVIL ENGINEER:

LANDSCAPE ARCHITECTLandscape A rchi te ct ure, LLC2525 Ponce de Leon Blvd., Suite 300Coral Gables, Florida 33134

MEP / FP ENGINEER:TLC E ng inee ring f or A rchi tecture1400 Co lonial B ou leva rd , Suite 203For t Myers, F lo r ida 33907

P erez E ng inee ring & Development, Inc.1010 Ke nnedy Dr. , Sui te 201K ey West, F lo r ida 33040

2013.02.15 - Bidding Documents

City

of K

ey W

est,

3132

Fla

gler

Ave

nue,

Key

Wes

t, Fl

orid

a 33

040

©2013 by mbi | k2m Architecture, Inc.

FIR

E ST

ATIO

N #

261

6 S

imon

ton

Stre

et, K

ey W

est,

Flor

ida

FOR

BU

ILD

ING

AN

D S

ITE

DE

VE

LOP

ME

NT

M1.1.3

MEZZANINE PLAN -HVAC

SCALE: 1/4" = 1'-0"

MEZZANINE FLOOR PLAN - HVAC

N

SCALE: 1/4" = 1'-0"

SECTION A

TCH LTE

Page 20: GENERAL STRUCTURAL NOTES - D.N. Higgins

Seal:

ARCHITECT:

February 15, 2013Date:

Sheet Number:

Title:

Drawn By:

Project #:

Checked By:

Drawing Size

Submissions:

MK-12060

1001 Whitehead StreetKey West, Florida 33040

Tel: 305.292.7722Fax: 305.292.2162

Email: [email protected]

PROF. REG. AA26001059

Architecture, Interior Design,Procurement,

Owner Representation,Specialty Consulting

Building RelationshipsBased on Trust and Results

Cleveland | Key West | Charlotte

Southwest Florida | Washington DC

Consultants:

24x36

STRUCTURAL ENGINEER:TKW Consu lt ing En gineers5621 Ba nner Drive,For t Myers, F lo r ida 33912

CIVIL ENGINEER:

LANDSCAPE ARCHITECTLandscape A rchi te ct ure, LLC2525 Ponce de Leon Blvd., Suite 300Coral Gables, Florida 33134

MEP / FP ENGINEER:TLC E ng inee ring f or A rchi tecture1400 Co lonial B ou leva rd , Suite 203For t Myers, F lo r ida 33907

P erez E ng inee ring & Development, Inc.1010 Ke nnedy Dr. , Sui te 201K ey West, F lo r ida 33040

2013.02.15 - Bidding Documents

City

of K

ey W

est,

3132

Fla

gler

Ave

nue,

Key

Wes

t, Fl

orid

a 33

040

©2013 by mbi | k2m Architecture, Inc.

FIR

E ST

ATIO

N #

261

6 S

imon

ton

Stre

et, K

ey W

est,

Flor

ida

FOR

BU

ILD

ING

AN

D S

ITE

DE

VE

LOP

ME

NT

M1.1.4

ROOF PLAN -HVAC

SCALE: 1/4" = 1'-0"

ROOF PLAN - HVAC

N

TCH LTE