GeneralSpecifications
<<Contents>> <<Index>>
Data Acquisition Unit DA100Main unit —stand-alone type (style number:S10)
—expandable type (style number:S10)
Sub units —DS400/DS600 (style number:S10)
Refer to the following cautionary notesbefore you configure your system.
DARWIN is a system comprising a number of data-acquisition equipment components.In the course of system growth, new models, software,various input/output modules and optional features areadded to the family to enhance the systems expandabilityand flexibility.You can check the versions of yourequipment and software by referring to the stylenumber:Sn* shown on the nameplate of the main unit.When configuring a system, you must confirm that thestyle number of each component unit and softwaremeets the following requirements:
* release number in the case of software:Rn
(1) The style number of each input/output module mustbe the same as or lower than that of the main unit orsub-unit to which the module is connected.
(2) The release number of a dedicated software packagemust be the same as or higher than the style numberof the main unit or sub-unit where the package isinstalled and where it performs control.
Any equipment/software not meeting these require-ments is incompatible with your system configuration.For information on how to upgrade to compatibleequipment/software, consult our sales personnel.
Model
DA100 Data acquisition unit
DA100 stand-alone typeFeatures
Increasing number of input channels, changing kinds of inputsKinds of inputsInput and output modules that can be connected to the main unitConnection of sub units, and remote measurement distanceInput and output modules that can be connected to the sub unitsMax scanning speed
Integrated type capable of measuring data from up to 40channels. Can be carried about easily and is suitable for small scale data logging.The number of channels can be increased from 10 to 40 channels in a module steps, and also the kinds of inputs can be changed.Universal, DC V/TC/DI, mA, power monitor, strain, Pulse, DI Input modules, communication module, DI/DO module, alarm output modules, retransmission modules
Not applicable
Not applicable
All channels/0.5 sec
DA100 expandable typeCan be expanded up to 300 channels.You can perform multi-channel measurement with the minimum of wiring by connecting sub units to the main unit with dedicated cable.The number of channels can be increased from 10 to 300 channels in a module steps, and also the kinds of inputs can be changed.Universal, DC V/TC/DI, mA, power monitor, strain, Pulse, DI(Input modules are connected to the sub units.)Communications module, DI/DO module, alarm output modulesUp to 6 units, 500 m max (Full extension)
Input modules, DI/DO module, alarm output module , retransmission modules
All channels/0.5 sec
5.27
5.29
5.33
5.46
4.98
5.21
5.46
5.15
5.14
5.38
5.00
5.25
5.07
5.27
5.29
5.33
5.46
4.98
5.21
5.46
5.15
5.14
5.38
5.00
5.25
5.07
STATUS
DATA ACQUISITION UNIT
stand-alone type
STATUS
DATA ACQUISITION UNIT
STATUS
SUB UNIT
5.27
5.29
5.33
5.46
4.98
5.21
5.46
5.15
5.14
5.38
5.00
5.25
5.07
5.27
5.29
5.33
5.46
4.98
5.21
5.46
5.15
5.14
5.38
5.00
5.25
5.07
expandable type
GS 04M01B01-11E© Copyright November 1995 (YK)
13th Edition: Aug. 2013 (KP)
GS 04M01B01-11E
The following product was discontinued as of March, 2013.Discontinued products: DA100-2 Data Acquisition Unit (Expandable Model)
GS 04M01B01-11E2
<<Contents>> <<Index>>
Main features(1) Compact:
Occupies only 1/5 of the volume of other Yokogawa units.(Comparison between a system consisting of the DA100 main unit+ one sub unit and a system consisting of one DA2500E + oneremote scanner)
(2) High speed:Can measure data from 300 channels at 0.5-second intervalsmaximum.
(3) A wide range of inputs:Universal (DC voltage, thermocouple, RTD, contact), DC voltage/thermocouple/contact dedicated inputs, mA, power monitor, strain,pulse, DI input.
(4) Remote measurement:The sub unit is designed to be connected to the main unit withdedicated cable, enabling it to be located up to 500 m away fromthe main unit.
Outline of functions(1) Setting and control of input/output modules on the sub units
connected with dedicated cable (Setting is done using the connectedpersonal computer and the setting software provided.)
(2) Control of alarm output modules, DI/DO modules, communicationinterface modules connected to the DA100 main unit.
(3) Acquisition by the DA100 main unit of the measured results fromthe input modules, via the sub units.
(4) Transfer of the measured results acquired by the DA100 main unitto a personal computer, via a GP-IB, RS-232-C, or RS-422-A/RS-485, and Ethernet communication interfaces.
Outline of sub unitsThe DS400/DS600 sub unit functions as an interface between theexpandable version of the DA100 data acquisition and the various input/output modules to which it is connected.A maximum of four input and output modules of various kinds (4 slots)can be connected to the DS400, and a maximum of six input and outputmodules (6 slots) can be connected to the DS600.A maximum of six sub units can be connected to one main unit. BothDS400 and DS600 sub units can be connected to the same main unit.The main unit can be connected to the sub units, or the sub units to eachother, with dedicated cable, enabling them to be separated by up to 500m.The sub units have excellent environmental toughness and can beinstalled very easily, enabling them to be installed over a wide areawithout environmental restrictions.
Outline of functions(1) Setting and control of the connected input/output modules (by
means of commands from the DA100 main unit.)(2) Measured values output to the DA100 main unit .
Outline of the stand-alone typeThe DA100 data acquisition unit (stand-alone type) measures inputsignals from between 10 and 40 channels, and transfers the measureddata in realtime to a personal computer. This highly portable unit is alsosuitable for on-site data logging.
DA100 stand-alone type main unit + PC
5.27
5.29
5.33
5.46
4.98
5.21
5.46
5.15
5.14
5.38
5.00
5.25
5.07
5.27
5.29
5.33
5.46
4.98
5.21
5.46
5.15
5.14
5.38
5.00
5.25
5.07
STATUS
DATA ACQUISITION UNIT
Main features(1) Compact:
Occupies only 1/5 of the space of Yokogawa’s remote scanner forthe DA2500E.
(2) High speed:Can measure data from 40 channels in 0.5 second maximum.
(3) A wide range of inputs:Universal (DC voltage, thermocouple, RTD, contact), DC voltage/thermocouple/contact dedicated inputs, mA, power monitor, strain,pulse, DI input.
Outline of functions(1) Setting and control of connected input/output modules(2) The measured results obtained using input modules can be
transferred to a personal computer via a GP-IB, RS-232-C, RS-422-A/RS-485, Ethernet communications interface.
Outline of expandable typeThe main unit of the DA100 data acquisition unit (expandable type) canbe connected to DS400 (4-slot type) or DS600 (6-slot type) sub unitscontaining various input modules, in order to configure a system thatcan acquire data from a maximum of 300 channels. The measured datais transferred in realtime to a personal computer.
DA100 expandable type main unit + sub unit + PC
STATUS
DATA ACQUISITION UNIT
STATUS
SUB UNIT
5.27
5.29
5.33
5.46
4.98
5.21
5.46
5.15
5.14
5.38
5.00
5.25
5.07
5.27
5.29
5.33
5.46
4.98
5.21
5.46
5.15
5.14
5.38
5.00
5.25
5.07
GS 04M01B01-11E 3
<<Contents>> <<Index>>
DA100 expandable type:Expandable type main unit + sub units (DS400 or DS600)+ various input/output modules + communication interface + dataacquisition software
Available module groupsThe DA100 data acquisition unit can be freely configured for differentfunctions by selecting modules from the following module groups andconnecting them to the main or sub units.Input modules:
Universal (DC voltage, thermocouple, RTD, contact), DC voltage/thermocouple/contact dedicated input modules, mA, power monitor,strain, pulse, DI input.
Alarm modules:4 point out put (transfer contact) or 10 point out put (make contact)(The number of alarm channels can be increased in module units.)
Communications modules:Select one type from GP-IB, RS-232-C, RS-422-A/RS-485, Ethernet.
DI/DO modules:Alarm 2-point output (transfer contact), fail output, command DO,remote control signal input.
Retransmission modules:Re-output of measured values and computed results.
NOTE
Refer to “Standard connection modules” in GS 04M01E01-11E, orGS 04M01E01-50E for detailed specifications of the abovemodules.
Package software• DARWIN DAQ 32 (Standard Package)• DARWIN DAQ 32 Plus (Optional Package)
GeneralDAQ 32 and DAQ 32 Plus are software packages developed byYOKOGAWA specially for the DARWIN series.These packages run on a personal computer, achieving highlydependable data acquisition using DARWIN series units (DA100,DC100, DR130, DR230, and DR240) and superb operability.The main differences between the two packages are in themonitoring functions. The DAQ 32 only offers two displayformats - waveform trend and digital; has 2 groups of 10 channels/window; and does not support alarm display. If simultaneousmulti point monitoring or more flexible display forms of data suchas level meter, analog meter, and thermometer faceplates, andalarm indications are required, use the optional DAQ 32 Plus.
ConfigurationComponent units
STATUS
DATA ACQUISITION UNIT
100-240VAC 50/60Hz 70VA MAX
POWER
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH9
CH10
b -/B -/A
b -/B -/A
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH9
CH10
b -/B -/A
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH9
CH10
DA100 main unit stand-alone type
NO C
ALM1
ALM2
ALM3
ALM4
ALM5
ALM6
ALM7
ALM8
ALM9
ALM10
NO C
ALM1
ALM2
ALM3
ALM4
ALM5
ALM6
ALM7
ALM8
ALM9
ALM10
STATUS
DATA ACQUISITION UNIT
100-240VAC 50/60Hz 70VA MAX
POWER
DA100 main unit expandable type
STATUS
SUB UNIT
100-240VAC 50/60Hz 70VA MAX
POWER
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH9
CH10
b -/B -/A
b -/B -/A
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH9
CH10
b -/B -/A
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH9
CH10
b -/B -/A
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH9
CH10
DS400 sub unit
STATUS
SUB UNIT
100-240VAC 50/60Hz 70VA MAX
POWER
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH9
CH10
b -/B -/A
b -/B -/A
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH9
CH10
b -/B -/A
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH9
CH10
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH9
CH10
b -/B -/A
b -/B -/A
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH9
CH10
DS600 sub unit
Unit configurationThe DA100 comes in the following two types, each of which is intendedto be set and controlled by a personal computer via a general purposecommunications interface.DA100 stand-alone type:
Stand-alone type main unit + various input/output modules +communication interface modules + data acquisiton software
GS 04M01B01-11E4
<<Contents>> <<Index>>
DA
RW
IND
AQ
32
DA
RW
IND
AQ
32
Plu
sD
AQ
LOG
GE
R
pack
age
softw
are
Per
son
al c
om
pu
ter
Set
-up
an
d c
on
tro
l so
ftw
are
DA
100
mai
n u
nit
Mo
du
le Inp
ut
STA
TU
S
DA
TA
AC
QU
ISIT
ION
UN
IT
100-
240V
AC
50
/60H
z
70V
A M
AX
PO
WE
R
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH9
CH10
b-/
B-/
A
b-/
B-/
A
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH9
CH10
b-/
B-/
A
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH9
CH10
Inst
all
Com
mun
icat
ion
inte
rfac
e ca
ble
RS
-422
-A/4
85
mod
ule
RS
-232
-C
mod
ule
GP
-IB
mod
ule
mA
(cur
rent
)
mod
ule
Str
ain
mod
ule
DI
mod
ule
Uni
vers
alD
C V
/TC
/DI
mod
ule
4-20
mA
mod
ule
1-5
V m
odul
eP
ulse
mod
ule
Com
mun
icat
ion
inte
rfac
e m
odul
eIn
put m
odul
eR
etra
nsm
issi
on m
odul
e
curr
ent
AC
Con
tact
Sta
tus
RT
DT
CD
C V
DI/D
O
mod
ule
Ala
rm o
utpu
t
mod
ule
I/O m
odul
e
Pow
er
mod
ule
ST
RA
INP
ULS
E
No alarm module or DI/DO module can beconnected to theright side of this input module.
A~
Eth
erne
t
mod
ule
DA
100
stan
d-al
one
type
sys
tem
con
figu
rati
on
GS 04M01B01-11E 5
<<Contents>> <<Index>>
DA
100
expa
ndab
le t
ype
syst
em c
onfi
gura
tion
Per
son
al c
om
pu
ter
Set
-up
an
d c
on
tro
l so
ftw
are
DA
100
mai
n u
nit
Su
b u
nit
Su
b u
nit
Mo
du
le Inp
ut
NO
C
ALM
1
ALM
2
ALM
3
ALM
4
ALM
5
ALM
6
ALM
7
ALM
8
ALM
9
ALM
10
NO
C
ALM
1
ALM
2
ALM
3
ALM
4
ALM
5
ALM
6
ALM
7
ALM
8
ALM
9
ALM
10
STA
TU
S
DA
TA
AC
QU
ISIT
ION
UN
IT
100-
240V
AC
50
/60H
z
70V
A M
AX
PO
WE
R
Inst
all
Com
mun
icat
ion
inte
rfac
e ca
ble
ST
RA
INP
ULS
Ecu
rren
tA
CC
onta
ct S
tatu
sR
TD
TC
DC
V
Str
ain
mod
ule
Pul
se in
put
mod
ule
mA
(cur
rent
)
mod
ule
Pow
er
mod
ule
DI
mod
ule
Uni
vers
alD
C V
/TC
/DI
mod
ule
Ext
ensi
on
mod
ule
4-20
mA
mod
ule
1-5
V m
odul
e
Inpu
t mod
ule
Rem
ote
mea
sure
men
tR
etra
nsm
issi
on m
odul
e
DI/D
O
mod
ule
Ala
rm o
utpu
t
mod
ule
I/O m
odul
e
Ded
icat
ed c
able
(up
to 5
00 m
)
No alarm module or DI/DO module can beconnected to theright side of this input module.
A~
RS
-422
-A/4
85
mod
ule
RS
-232
-C
mod
ule
GP
-IB
mod
ule
Com
mun
icat
ion
inte
rfac
e m
odul
e
Eth
erne
t
mod
ule
DA
RW
IND
AQ
32
DA
RW
IND
AQ
32
Plu
sD
AQ
LOG
GE
R
pack
age
softw
are
GS 04M01B01-11E6
<<Contents>> <<Index>>
Connecting modulesConnecting modules to the stand-alone type
Modules that can be connectedInput modules:
Universal (DC voltage, thermocouple, RTD, contact), DC voltage/thermocouple/contact dedicated, mA, power monitor, strain, pluse,DI input modules
Alarm modules:4 channels (transfer contact) or 10 channels (make contact) (Thenumber of alarm channels can be increased in module units.)
Communications modules:Select one type from GP-IB, RS-232-C, RS-422-A/RS-485,Ethernet
DI/DO modules:Alarm 2-point output (transfer contact), fail output, command DO,remote control signal input
Retransmission modules:Re-output of measured values and computed results
Extension module:For remote measurment
Definition of number of connections• A maximum of six modules can be connected to the main unit.• One of these must always be a communications module.• The number of DI/DO modules must be no greater than one.• The alarm output module, DI/DO module, and retrandmission
module must be connected on the left side of the input modules.• Number of input modules ≤ 4• Number of input modules + number of alarm modules + DI/DO
module + communications module ≤ 6• One extension module can be connect to the main unit• Number of retransmission modules ≤ 4• The standard operating temperature and humidity are different for
each module type.Therefore,always make sure to verify this when connecting themodule.
Connecting modules to the expandable typeModules that can be connectedMain unitAlarm modules:
4-point output (transfer contact) or 10-point output (make contact)(The number of alarm channels can be increased in module units.)
Communications modules:Select one type from GP-IB, RS-232-C, RS-422-A/RS-485,Ethernet
DI/DO modules:Alarm 2-point output (transfer contact), fail output, command DO,remote control signal input.
Sub unit DS400/DS600Input modules:
Universal (DC voltage, thermocouple, RTD, contact), DC voltage,thermocouple, contact dedicated input modules, pulse
Alarm modules:4-point output (transfer contact) or 10-point output (make contact)(The number of alarm channels can be increased in module units.)
DI/DO modules:Alarm 2-point output (transfer contact), fail output, command DOmodules and remote control signal input
Extension module:For remote measurment
Retransmission modules:Re-output of measured values and computed results
Definition of number of connections for the expandabletypeDA100 main unit:
• The number of input modules and retransmission modules is 0.Also, 1 communications module must always be connected.
• Number of alarm modules + DI/DO module ≤ 3Sub unit DS400:
• The maximum number of modules per slot that can be connectedis 4.
• Number of input modules + DI/DO module + alarm modules +retransmission modules ≤ 4
Sub unit DS600:• The maximum number of modules per slot that can be connected
is 6.• Number of input modules + DI/DO module + alarm modules +
retransmission modules ≤ 6Common to all:
• One DI/DO module can be connected to one expandable typesystem
• The alarm output module and DI/DO module must be connectedon the left side of the input modules.
• One extension module can be connected to one sub unit.• The retransmission module can be connected to the sub unit only.
Up to 30 modules.• The standard operating temperature and humidity are different for
each module type.Therefore, always make sure to verify this when connecting themodule.
Method of connecting modulesThe standared operating temperature and humidity are different for eachmodule type.Therefore, always make sure to verify these when connecting themodule.Stand-alone type:
Connect directly to the main unit.The alarm output modlues and DI/DO module must be connectedon the left side of the input modules.
Expandable type:Connect the input modules, retransmission modules, or extensionmodule directly to the sub unit. (You cannot connect these modulesdirectly to the main unit.)Connect the alarm modules, communications module and DI/DOmodule directly to the main unit.The alarm output modlues and DI/DO module must be connectedon the left side of the input modules.
Connecting sub unitsKinds of sub units (type name):
DS400 sub unit: For 4 slotsDS600 sub unit: For 6 slots
Number of sub units to be connected:Stand-alone type:Cannot be connected.Expandable type:A maximum of six sub units can be connected.
(This also applies when 4-slot sub units and 6-slotsub units are connected to the same main unit.)
Method of connecting sub units:A sub unit can be connected to either the main unit or another subunit with dedicated cable. Maximum total extension length is 500m.
GS 04M01B01-11E 7
<<Contents>> <<Index>>
Standard specificationsGeneral specificationsConstructionInstallation method:
Floor mounting: Use the stand at the bottom of each unit.Direct panel mounting: Screw the unit directly to the panel at the
specified points.Rack mounting: Use the dedicated mounting brackets.
(Regardless of which mounting method you use,be sure to install the units in an upright position.)
Materials:Steel plate, aluminum castings, plastic moldings
Paint color:Base unit: Lamp black (equivalent to Munsell 0.8Y2.5/0.4)
Slate gray light (equivalent to Munsell 0.1PB4.6/0.2)
Modules: Slate gray light (equivalent to Munsell 0.1PB4.6/0.2)
External dimensions:Stand-alone type main unit:
Approx. 422 (W) × 176 (H) × 100 (D) mmExpandable type main unit:
Approx. 336 (W) × 165 (H) × 100 (D) mmDS400 sub unit: Approx. 336 (W) × 165 (H) × 100 (D) mmDS600 sub unit: Approx. 422 (W) × 176 (H) × 100 (D) mm
Weight:Stand-alone type main unit:
Approx. 3.5 kg (with 4 input modules + 1 alarmoutput module + 1 communications moduleinstalled)Approx. 1.1 kg*
Expandable type main unit:Approx. 2.5 kg (with 4 input/output modulesinstalled)Approx. 0.9 kg*
DS400 sub unit: Approx. 2.5 kg (with 4 input/output modulesinstalled) Approx. 0.9 kg*
DS600 sub unit: Approx. 3.5 kg (with 6 input/output modulesinstalled) Approx. 1.1 kg*
*: is the weight of each unit without modules installed.
InputMeasurement range:
NOTE
Refer to “Standard connection modules” in GS 04M01E01-11E fordetailed specifications of the measurement range.
Measurement interval:Selectable from 0.5, 1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, and 60 secdepending on the minimum measurement interval (when moduleswith different minimum intervals are installed together, themeasurement interval is determined by whichever module has themaximum interval).Stand-alone type:
Max 40 channels/500 ms (when the softwareprovided is used)
Expandable type:Max 300 channels/500 ms (when the softwareprovided is used)
A/D integration period (dependent on the module):Selectable from 20 ms (50 Hz), 16.7 ms (60 Hz), 100 ms (10 Hz),and auto switching (unavailable for a DC power supply model).
AlarmNumber of settings:
Up to four settings can be made for each channel.Kinds of alarms:
Selection from higher limit, lower limit, difference higher limit,difference lower limit, higher limit of rate of change, lower limitof rate of change.
Rate of change alarm time interval:Can be set to measurement interval × 1 to 15 (common to bothrising and falling limits)
Output mode:Excitation/non-excitation selection, AND/OR mode selection, andoutput hold/non-hold specification can be made. (common to allchannels)Six reflash alarm output contacts can be specified.
Number of alarm output points:Stand-alone type:
2 points (DI/DO module) to 40 points maxExpandable type:
Up to 30 points can be connected to the DA100main unit (the number of alarm points can beincreased in module units)By connecting sub units, (the number of alarmpoints can be increased in module units).
Number of alarm output modules that can be connected:Stand-alone type:
The number of alarm points can be increased inmodule units.
Expandable type:Up to 3 modules can be connected to the DA100main unit, up to 6 modules can be connected toone sub unit, and up to 4 modules can beconnected to one subunit.
Standard computation functionsComputation functions:
Difference between arbitrary channels, linear scaling, movingaverage
Scaling:Ranges for which scaling can be done:
DC voltage, thermocouple, RTD, contact, strain,mA,
Scaling range: –30000 to +30000Decimal point: Can be set freely.Measurement accuracy for scaling:
Measurement accuracy for scaling (digits) =Measurement accuracy (digits) × Scaling span(digits)/Measurement span (digits) + 2 digits(Numbers below the decimal point are roundedup.)
Moving average:The moving average results for between 2 to 64 scans are computed.
Communications functionsCommunication modules:
GP-IB, RS-232-C, RS-422-A/RS-485, Ethernet communicationsinterface modules
GS 04M01B01-11E8
<<Contents>> <<Index>>
Withstand voltage:Between AC power supply terminal and case ofDA100 main unit:1500 VAC (50/60 Hz) for oneminuteBetween DC power supply terminal and case ofDA100 main unit:1000 VAC (50/60 Hz) for oneminuteBetween input terminal and case of DA100 mainunit:1500 VAC (50/60 Hz) for one minuteBetween output terminal and case of DA100main unit:2300 VAC (50/60 Hz) for one minute
Normal operation conditionsSupply voltage: 90 to 250 VAC, 10 to 32 VDCSupply frequency:50 Hz ± 2%, 60 Hz ± 2%Ambient temperature:
Stand-alone type main unitExpandable type main unitWhen floor-mounted and Desk top : 0 to 50˚CWhen panel-mounted : 0 to 50˚CWhen Rack-mounted : 0 to 50˚CDS400/DS600 sub unitWhen floor-mounted and Desk top : -10 to 50˚CWhen panel-mounted : -10 to 60˚CWhen Rack-mounted : -10 to 50˚CWhen DC power operation : 0 to 50˚C
Ambient humidity:
Temperature
–10 to 40°C
40 to 50°C
50 to 60°C
Humidity
20 to 80% RH
10 to 50% RH
5 to 30% RH
* no ice formation
Vibration: 10 to 60 Hz 0.2 m/s2
Shock: Not allowedMagnetic field: 400 A/m max (50/60 Hz)Position: Mount the unit left-right horizontally or
vertically, as a general rule.Installation location:
RoomInstallation height:
Altitude up to 2,000 mInstallation category:
II (according to CSA22.2 No.1010.1)Measurement category:
II (according to IEC61010-1)Degree of pollution: 2Warm-up time: At least 30 minutes after power switch-on
Standard performanceMeasurement accuracy:
Reference operation state:23 ± 2°C, 55 ± 10% RH, supply voltage: 90 to250 VAC, supply frequency: 50/60 Hz ± 1%,Warmup: At least 30 minutes; When operating,the system must not adversely affect the operationof other measuring instruments by generatingvibration, for example. enerating vibration, forexample.
NOTE
Refer to “Standard connection modules” in GS 04M01E01-11E fordetailed specifications of the measurement accuracy.
Output functionsDI/DO module:
Internal alarm output 2 points, fail output function, command Do.Retransmission modules:
Re-output of measured values and computed results.10 voltage and 2 current channels.
AC power supply sectionRated supply voltage:
100 to 240 VAC (free supply voltage selection)Usable supply voltage range:
90 to 250 VACRated supply frequency:
50/60 HzPower consumption:
Stand-alone type main unit (when 6 connectable modules are installed)max approx. 55 VA (when 100 VAC is input) max approx. 70 VA (when 240 VAC is input)Expandable type main unit (when 4 connectable modules are installed)max approx. 45 VA (when 100 VAC is input) max approx. 55 VA (when 240 VAC is input)DS400 sub unit (when 4 connectable input/output modules are installed) max approx. 45VA (when 100 VAC is input) max approx. 55 VA (when 240 VAC is input)DS600 sub unit (When 6 connectable input/output modules are installed) max approx. 55 VA (when 100 VAC is input) max approx. 70 VA (when 240 VAC is input)
DC power Supply section (DC power supply only, Specify when ordering)
Rated supply voltage:12 to 28 VDC
Usable supply voltage range:10 to 32 VDC
Power consumption:Approx. 25 VA max.
Terminal: Dedicated connectorOther: Automatic selection of A/D integral period does
not function.
AC Adapter (for DC power supply model only, optional accessary)
Rated supply voltage:100 to 240 VAC
Usable supply voltage range:90 to 250 VAC
Rated supply frequency:50/60 Hz
Power consumption:max. 90 VA
OthersClock: With calendar function (Western calendar).Clock accuracy: ±100 ppmSystem alarm: Contact output (when DI/DO module is
connected)Set value backup:
Lithium battery backup (approx. 10 years),excluding clock function
Insulation resistance:At least 20 MΩ between each terminal andground (measured with 500 VDC)
GS 04M01B01-11E 9
<<Contents>> <<Index>>
Effect of Operation ConditionsAmbient temperature:
Variation for a temperature change of 10°Cwithin ±(0.1% of rdg + 1 digit)±(0.2% of span + 1 digit) for Cu 10 Ω
Voltage variation: Within ±1 digit over the range of 90 to 132, or180 to 250 VAC (frequency 50/60 Hz)
External magnetic field:Variation with respect to AC (50/60 Hz) and DCmagnetic fields of 400 A/m ... Within ±(0.1% ofrdg + 10 digits)
Radio wave: Within ±(1% of span) at 1 m from 150 MHz or460 MHz field
Signal source resistance:Variation with respect to signal source resistance+ 1 kΩ change
(1) Voltage 2 V range or below ... Within ±10 µV 6 V range or above ... Within ±0.1% of rdg
(2) ThermocoupleWithin ±10 µV; However, it must be within ±100µ when burnout is specified.
(3) RTD Variation with respect to change of 10 Ω per wire(when all three wires are the same resistancevalue)
Indication ... Within ±(0.1% of rdg + 1 digit)Variation in indication with respect to adifference of 40 mΩ in the resistancebetween conductors (max difference between3 wires) ... Approx. 0.1°C
Mounting position:Variation when the unit is mounted horizontallyon a panel ... Within ±(0.1% of rdg + 1 digit)excluding RJC error
Vibration: Variation when sinusoidal vibration ofacceleration 0.2 m/s2 is applied for 2 hours in eachof the 3 axial directions over a frequency range of10 to 60 Hz ... Within ±(0.1% of rdg + 1 digit)
Transportation and storage conditionsThese refer to the environmental conditions existing during transporta-tion and storage from the time of shipment from the factory untilcommencement of use, and also during transportation and storage in thecase of a temporary period of non-use.If the environmental conditions are maintained within the specifiedrange, the unit will not incur permanent damage, and can be returned toa normal working condition (re-adjustment may be required in somecases).
Ambient temperature: –25 to 60°CHumidity: 5 to 95% RHVibration: 10 to 60 Hz 4.9 m/s2 maxShock: 392 m/s2 max (in packed condition)
Supported standardsCSA
ULCE
C-TickKC marking
Obtained CSA22.2 No.61010-1 Installation category (Overvoltage category): II,Degree of pollution: 2Obtained UL No.61010-1 (CSA NRTL/C)CE marking was removed under the publication of the 3rd edition of IEC Standard. EN 55011 Class A, Group 1Electromagnetic wave interference prevention standard, electromagnetic wave protection standard compliance
/M1: MATH FunctionComputation typesTypes:
Four arithmetical operations, SQR (square root), ABS (absolutevalue), LOG (common logarithm), LN (natural logarithm), EXP(exponent), statistical computation*, logical computation (AND,OR, NOT, and XOR), relational computation, exponentiation,previously-measured value reference, hold**, reset, clear, andremote RJC.
* Statistical computationCLOG: Computation process of simultaneously measured
values within a group (total, maximum,minimum, average, and maximum - minimum)
TLOG: Computation process of a specific channel overtime axis (total, maximum, minimum, average,and maximum - minimum)
Statistical computation interval:Set by the event/action function (effective when/M1 option is selected)
**Temporary hold of the computed resultCan be controlled by event/action function (such as remote controlsignal, time specified, and alarm status). (effective when /M1 optionis selected)
Number of channels for computing (Number of channels that canbe allocated for computational purposes.):
Stand-alone type: 30ch maximumExpandable type: 60ch maximum
Computation interval:Every measurement interval (except when the computationbecomes too difficult to be processed every measured interval, inwhich case an alarm is generated)
Significant digits during computation:±1038
Significant digits of the computed result:-9999999 to +99999999 (Decimal point can be set to have 1 to 4digits on the right of the decimal point)
Input from communication interface:Digital value (ASCII numerical array) input from the communica-tion interface
Computation start/stop:Can be controlled by communication commands and event/actionfunction (such as remote control signal, time specified, and alarmstatus)
Other functions included in the math function:Remote RJCInput type: Thermocouple (TC)Accuracy: (Twice the measurement accuracy of the standard
thermocouple input) + (temperature differencebetween the terminal of the remote terminalsection and thermocouple section for measuringthe remote terminal temperature)
Thermocouple burnout: not selectable
/M3: Report FunctionRefer to the GS 04M01B01-31E
GS 04M01B01-11E10
<<Contents>> <<Index>>
Type name and specification codeData Acquisition Unit DA100
Model
DA100
Type
Software
Power Supply
Power Inlet & Power Cable
Optional Features
Suffix Code
-1
-2
3
-1
-2
D
F
H
R
S
W
Y
Optional Code
/M1
/M3
/FC
Description
Data acquisition unit
Stand-alone type
Expandable type
DARWIN DAQ 32 for IBM PC-AT
100 VAC to 240 VAC
12 VDC to 28 VDC (DC power supply only)
(always specify Y for the power cable)
3-pin power inlet w/UL, CSA cable
3-pin power inlet w/VDE cable
3-pin power inlet w/CCC cable
3-pin power inlet w/SAA cable
3-pin power inlet w/BS cable
3-pin power inlet w/screw terminal
Dedicated connector for DC power supply w/o power cable
Math function (including RRJC)
Report function
DARWIN DAQ 32 is supplied with floppy disks
Subunit DS400/DS600
Model
DS400
DS600
Type
Power Supply
Power Inlet & Power Cable
Suffix Code
-00
-1
-2
D
F
H
R
S
W
Y
Optional Code Description
4 slots subunit for inputs and alarm output
6 slots subunit for inputs and alarm output
Always-00
100 VAC to 240 VAC
12 VDC to 28 VDC (DC power supply only)
(always specify Y for the power cable)
3-pin power inlet w/UL, CSA cable
3-pin power inlet w/VDE cable
3-pin power inlet w/CCC cable
3-pin power inlet w/SAA cable
3-pin power inlet w/BS cable
3-pin power inlet w/screw terminal
Dedicated connector for DC power supply w/o power cable
GS 04M01B01-11E 11
<<Contents>> <<Index>>
Input module
Model Code
DU100-11
DU100-21
DU100-31
DU100-12
DU100-22
DU100-32
DU200-11
DU200-21
DU200-31
DU200-12
DU200-22
DU200-32
DU300-11
DU300-12
DU400-12
DU400-22
DU500-12
DU500-13
DU500-14
DU600-11
DU700-11
Description
10ch universal input module (DCV/TC/DI & RTD)
20ch universal input module (DCV/TC/DI & RTD)
30ch universal input module (DCV/TC/DI & RTD)
10ch universal input module (DCV/TC/DI & RTD)
20ch universal input module (DCV/TC/DI & RTD)
30ch universal input module (DCV/TC/DI & RTD)
10ch DCV/TC/DI input module
20ch DCV/TC/DI input module
30ch DCV/TC/DI input module
10ch DCV/TC/DI input module
20ch DCV/TC/DI input module
30ch DCV/TC/DI input module
10ch mA input module
10ch mA input module
Power monitor module for single phase
Power monitor module for 3 phase
10ch strain input module (120 Ω)
10ch strain input module (350 Ω)
10ch strain input module (External bridge box)
10ch pulse input module
10ch DI input module
Terminal
Screw
Screw
Screw
Clamp
Clamp
Clamp
Screw
Screw
Screw
Clamp
Clamp
Clamp
Screw
Clamp
Clamp
Clamp
Clamp
Clamp
NDIS
Screw
Screw
Other module
Model Code
DT100-11
DT200-11
DT200-21
DT300-11
DT300-21
DT300-31
DT300-41
DT500-11
DT500-21
Description
2 alarm, 12 remote, fail/chart end Screw terminal
4 alarm relay output (transfer contacts) Screw terminal
10 alarm relay output (make contacts) Screw terminal
GP-IB interface module
RS-232-C interface module
RS-422-A/RS-485 interface module
Ethernet interface module
10 channels, 1-5 V output retransmission module
2 channels, 4-20 mA output retransmission module
GS 04M01B01-11E12
<<Contents>> <<Index>>
Accessories
Model Code
DV100-011
DV100-012
DV200-000
DV200-001
DV200-002
DC200-005
DV200-010
DV200-020
DV200-050
DV200-100
DV200-200
DV200-300
DV200-400
DV200-500
DV250-001
DV300-011
DV300-012
DV300-101
DV300-102
DV300-251
DV300-252
DV400-011
DV400-012
DV450-001
DV500-001
DV500-002
DV500-003
DV500-004
DV500-005
Description
Extension module
Extension base unit
Extension cable (0.5 m)
Extension cable (1 m)
Extension cable (2 m)
Extension cable (5 m)
Extension cable (10 m)
Extension cable (20 m)
Extension cable (50 m)
Extension cable (100 m)
Extension cable (200 m)
Extension cable (300 m)
Extension cable (400 m)
Extension cable (500 m)
Cable adapter
Shunt resistor 10 Ω for screw input terminal
Shunt resistor 10 Ω for clamped input terminal
Shunt resistor 100 Ω for screw input terminal
Shunt resistor 100 Ω for clamped input terminal
Shunt resistor 250 Ω for screw input terminal
Shunt resistor 250 Ω for clamped input terminal
Rack mount kit (DA100 exp./DS400) for ANSI
Rack mount kit (DA100 stand./DS600) for ANSI
Strain conversion cable
AC adapter W/UL, CSA cable
AC adapter W/VDE cable
AC adapter W/SAA cable
AC adapter W/BS cable
AC adapter W/CCC cable
Package software
Model Code
DP120-13
WX102/CD1
WX101/CD1
Description
DARWIN DAQ 32 software (Windows XP/Vista/7) (comes standard)
DARWIN DAQ 32 Plus software (Windows 2000/XP/Vista/7) (optional)
DAQLOGGER for multi-channel data logging software (Windows 2000/XP/Vista/7) (optional)
GS 04M01B01-11E 13
<<Contents>> <<Index>>
Wiring Input Signal Lines (to Universal and DCV/TC/DI input modules)Terminals
Screw type terminal Clamp type terminal
+-
ABb
DC voltage • TC •contact
RTD*
ABb
CH1CH2
CH10
CH1CH2
CH3CH4
CH9CH10
+-
*There are no RTD input terminals on the DCV/TC/DI input module.
Wiring Diagram
DC voltage input
Compensation lead
DC current input
Shunt resistorNote:For 4 to 20 mA input, shunt resistance value should be 250 Ω ± 0.1%
10 Ω* max./leadwire Three wire resistances should be approx. equal.
*10 Ω max. for Pt 100 Ω and Pt 50 Ω, 1 Ω max. for Cu 10 Ω.
DC input
RTD inputTC input
DC voltage input/DI input (contact)
b AB
AbB
+
-
+-+-
+
-
+-
Wiring Alarm Output SIgnal Lines (to DI/DO and Alarm output modules)Terminals
NO C
12
NC
Fail output (transfer contact)
Alarm output (transfer contact)
Remote control inputCan be used for event/action function only when the /M1 option of DA100 is specified.
DT100-11 NO C
12
4
NC
3
Alarm output (transfer contact)
Alarm output (transfer contact)
DT200-11 NO C
12
10
Alarm output (make contact)
DT200-21
Contact capacity:250 VDC/0.1 A (with aresistor load)250 VAC/2 A (with aresistor load)30 VDC/2 A (with a resistorload)
Fail output:becomes de-activated whenan error is detected in thesystem.
GS 04M01B01-11E14
<<Contents>> <<Index>>
Location and Location Number (Channel Number, Alarm Output Number, DI/DO Number)The location numbers correspond to channel numbers for locations where the input module is connected,to alarm output numbers for locations where the alarm output module is connected, and to DI/DOnumbers for locations where the DI/DO module is connected.
In case of the DA100 Stand-alone typeThe location numbers correspond to the location of each module as shown in the figure below.
Module 0 (Location numbers:001 to 010)
Module 1 (Location numbers:011 to 020)Module 2 (Location numbers:021 to 030)
Module 3 (Location numbers:031 to 040)Module 4 (Location numbers:041 to 050)
Module 5 (Location numbers:051 to 060)
In case of the DA100 Expandable typeThe unit number (the number of the main unit is fixed at “I”) and location numbers correspond to thelocation of each module as shown in the figure below.
Module 0 (Location numbers:001 to 010)Module 1 (Location numbers:011 to 020)
Module 2 (Location numbers:021 to 030)Module 3 (Location numbers:031 to 040)
Module 4 (Location numbers:041 to 050)Module 5 (Location numbers:051 to 060)
Main unit
Unit No.:0
Subunit DS600
Module 0 (Location numbers:101 to 110)Module 1 (Location numbers:111 to 120)
Module 2 (Location numbers:121 to 130)Module 3 (Location numbers:131 to 140)
Unit No.:1
Subunit DS400
Input modules cannot be connected.
Module 0 (Location numbers:101 to 110)Module 1 (Location numbers:111 to 120)
Module 2 (Location numbers:121 to 130)Module 3 (Location numbers:131 to 140)
Unit No.:I
GS 04M01B01-11E 15
<<Contents>> <<Index>>
Name and Function of Each PartDA100 Stand-alone type (DA100-1)
Power connector(when specifying W, changed to screw terminal)(when specifying Y, changed to dedicated connector)
Power switch
Feet
Status indicator
Module connector
Installationholes
Screw holes formodule installation
Function groundingterminal (below power switch)
Holes for fasteningthe feet
DA100 Expandable type (DA100-2)
Power connector(when specifying W, changed to screw terminal)(when specifying Y, changed to dedicated connector)
Power switch
Feet
Status indicator
Module connector
Installation holesScrew holes for module installation
Holes for fastening the feet
Lid covering the extensioncable connector
Function groundingterminal (below power switch)
Subunit DS400
Power connector(when specifying W, changed to screw terminal)(when specifying Y, changed to dedicated connector)
Power switch
Feet
Status indicator
Module connector
Installation holesScrew holes for module installation
Holes for fastening the feet
Lid covering the extensioncable connectorSwitch to set the
unit number
Function groundingterminal (below power switch)
GS 04M01B01-11E16
<<Contents>> <<Index>>
Subunit DS600
Power connector(when specifying W, changed to screw terminal)(when specifying Y, changed to dedicated connector)
Power switch
Feet
Status indicator
Module connector
Installationholes
Screw holes formodule installation
Holes for fasteningthe feet
Lid covering the extension cable connector
Switch to setthe unit number
Function groundingterminal (below power switch)
Rack Mount Fitting (ANSI/EIA)DA100 expandable type/DS400 subunit
482.6453.214.7
177
37.7
101.
6
6.8
DA100 stand-alone type/DS600 subunit
482.6
453.214.7
177
37.7
101.
6
6.8
GS 04M01B01-11E 17
<<Contents>> <<Index>>
Subject to change withut notice.
Dimensional DrawingsDA100 Stand-alone type/Subunit DS600 Unit: mm
156
168
20
100422
145
2216255
176
115
369
20
DA100 Expandable type/Subunit DS400
165
40
100336
145
223208
5050
115
290
20
If not specified, the tolerance is ±3%. However, in cases of less than 10 mm, the tolerance is ±0.3 mm.