Upload
0260480981
View
232
Download
0
Embed Size (px)
Citation preview
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 1/38
General Maintenance Procedures
DN9770958Issue 9-1 en
# Nokia Siemens Networks 1 (38)
MSC/HLR, Rel. M14.2, Product Documentation,
v.2
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 2/38
The information in this document is subject to change without notice and describes only theproduct defined in the introduction of this documentation. This documentation is intended for theuse of Nokia Siemens Networks customers only for the purposes of the agreement under whichthe document is submitted, and no part of it may be used, reproduced, modified or transmitted inany form or means without the prior written permission of Nokia Siemens Networks. Thedocumentation has been prepared to be used by professional and properly trained personnel,and the customer assumes full responsibility when using it. Nokia Siemens Networks welcomescustomer comments as part of the process of continuous development and improvement of thedocumentation.
The information or statements given in this documentation concerning the suitability, capacity, or performance of the mentioned hardware or software products are given “as is” and all liabilityarising in connection with such hardware or software products shall be defined conclusively andfinally in a separate agreement between Nokia Siemens Networks and the customer. However,Nokia Siemens Networks has made all reasonable efforts to ensure that the instructionscontained in the document are adequate and free of material errors and omissions. NokiaSiemens Networks will, if deemed necessary by Nokia Siemens Networks, explain issues which
may not be covered by the document.
Nokia Siemens Networks will correct errors in this documentation as soon as possible. IN NOEVENT WILL NOKIA SIEMENS NETWORKS BE LIABLE FOR ERRORS IN THISDOCUMENTATION OR FOR ANY DAMAGES, INCLUDING BUT NOT LIMITED TO SPECIAL,DIRECT, INDIRECT, INCIDENTAL OR CONSEQUENTIAL OR ANY LOSSES, SUCH AS BUTNOT LIMITED TO LOSS OF PROFIT, REVENUE, BUSINESS INTERRUPTION, BUSINESSOPPORTUNITY OR DATA, THAT MAY ARISE FROM THE USE OF THIS DOCUMENT OR THEINFORMATION IN IT.
This documentation and the product it describes are considered protected by copyrights andother intellectual property rights according to the applicable laws.
The wave logo is a trademark of Nokia Siemens Networks Oy. Nokia is a registered trademark of Nokia Corporation. Siemens is a registered trademark of Siemens AG.
Other product names mentioned in this document may be trademarks of their respective owners,and they are mentioned for identification purposes only.
Copyright © Nokia Siemens Networks 2008. All rights reserved.
2 (38) # Nokia Siemens Networks DN9770958Issue 9-1 en
General Maintenance Procedures
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 3/38
Contents
Contents 3
List of tables 4
List of figures 5
Summary of changes 7
1 General maintenance procedures 91.1 Automatic maintenance functions 101.2 Maintenance recommendations 12
1.2.1 Service of peripheral devices 13
2 Performing daily maintenance routines 152.1 Outputting alarm history 152.2 Outputting current alarms 162.3 Checking working states of computer units 162.4 Checking working states of I/O devices 162.5 Outputting clear codes 162.6 Inspecting printers 172.7 Inspecting tape units 172.8 Updating FB build 182.9 Taking backup copies of FB build on DDS tape 18
2.10 Cleaning CTU 19
3 Performing weekly maintenance routines 233.1 Printing and saving unit states 233.2 Checking status of charging files 233.3 Checking blocked alarms 243.4 Checking date and time 243.5 Checking printers 24
4 Performing monthly maintenance routines 254.1 Checking hardware alarms 254.2 Cleaning visual display unit 254.3 Cleaning printer 26
5 Performing six-monthly maintenance routines 29
6 Performing yearly maintenance routines 316.1 Checking voltages 316.2 Cleaning Floppy Disk Unit 33
7 Marking unused blocks on a hard disk 35
Glossary 37
DN9770958Issue 9-1 en
# Nokia Siemens Networks 3 (38)
Contents
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 4/38
List of tables
Table 1. The service of peripheral devices on the DX 200 network element. 13
Table 2. Cleaning the Cartridge Tape Unit 20
Table 3. Cleaning the VDU 26
Table 4. Cleaning the LPT 26
Table 5. Feed voltage to DC/DC converters 31
Table 6. Voltages of racks 32
Table 7. Cleaning the floppy disk unit 33
4 (38) # Nokia Siemens Networks DN9770958Issue 9-1 en
General Maintenance Procedures
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 5/38
List of figures
Figure 1. DX 200 fault management principles. 11
DN9770958Issue 9-1 en
# Nokia Siemens Networks 5 (38)
List of figures
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 6/38
6 (38) # Nokia Siemens Networks DN9770958Issue 9-1 en
General Maintenance Procedures
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 7/38
Summary of changes
Changes between document issues are cumulative. Therefore, the latest
document issue contains all changes made to previous issues.
Changes between issues 9 –1 and 9
Further structural enhancements made in the document.
Changes between issues 9 and 8
The document's layout and structure has been updated.
Changes between issues 8 and 7 –
2
Structural enhancements made in the document, and outdated information
on cleaning a Magnetic Tape Unit (MTU) has been removed.
DN9770958Issue 9-1 en
# Nokia Siemens Networks 7 (38)
Summary of changes
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 8/38
8 (38) # Nokia Siemens Networks DN9770958Issue 9-1 en
General Maintenance Procedures
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 9/38
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 10/38
If you need to replace a faulty plug-in unit with a new one, consult the
instructions for replacing plug-in units.
For instructions on how to cancel the alarm situation, refer to Cancelling
alarms.
If a fault in the system stops the I/O system of the OMU, the maintenance
software, or the entire network element, no detailed information on the fault
is printed out. Refer to I/O system troubleshooting for more information.
Use Printouts of Starting Phases when monitoring the start or restart of the
network element using the service terminal.
Refer to Recovery and unit working state administration when you need to
know about the restart of functional units and how to change their working
states.
In addition to the instructions mentioned above, there are maintenance
instructions that describe how to change I/O devices, how to maintain the
network and how to use the auxiliary maintenance devices and software.
1.1 Automatic maintenance functions
System maintenance handles all the fault situations and user-initiated
configuration management tasks within the hardware and software of the
system. System Maintenance is responsible for availability performance
on the network element level. It is designed to perform its task as
automatically and autonomously as possible.
Usually all activities can be performed remotely unless the action to be
taken involves the hardware. Depending on the structure of your network,
you may need to change some of the logical file outputs e.g. diagnostic
and observation outputs to be able to receive all the information that is
needed to perform maintenance activities remotely.
The main areas of system supervision are presented in the figure below.
10 (38) # Nokia Siemens Networks DN9770958Issue 9-1 en
General Maintenance Procedures
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 11/38
Figure 1. DX 200 fault management principles.
Supervision of hardware and software for fault detection
. Hardware supervision relies on equipment database and routine
tests executed for hardware components.
. Software supervision detects loss of control in software. The
supervision is based on watchdog timers and supervision
messages.
.
Supervision of real time keeps the units of a system and systems inthe O&M network in the same time.
Alarm handling for analysing the fault information from differentsources and for informing the operator
. Is based on collecting fault observations. These are hardware
alarms and fault observations from program blocks and
preprocessors.
. Makes decisions by using predefined rulebases, and starts up
automatic recovery functions when necessary.
. Stores alarm data in an alarm log file.
. Informs the user with alarm printouts and alarm lamp panel controls.
SUPERVISIONSYSTEM
-Faultdetection
ALARMSYSTEM
-Alarmprintouts
-Updating of failureinformation
RECOVERYSYSTEM
-Faultelimination
FAULTLOCATIONSYSTEM
-Faultlocation
FAILUREAlarm
message
Activationof
faultlocation
Activationof
recovery
DN9770958Issue 9-1 en
# Nokia Siemens Networks 11 (38)
General maintenance procedures
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 12/38
Recovery for eliminating the effects of faults
. Eliminates the effects of faults by utilising the redundancy of the
hardware. Processor and preprocessor restarts are also used.
. Controls the restarting of the system so that restarts are carried out
in the correct order quickly and reliably.
. Starts up automatic fault location.
Fault location
. Faults in the system hardware are located in one plug –in unit in 70%
of cases, and in one of four plug –in units in 95% of cases.
. Complies with the ITU-T requirement for the average active repair
time of 30 minutes.
. System hardware configuration data is used for determining which
diagnostic programs should be executed and which configurationparameters should be used. The data is also used for determining
which plug –in units should be suspected as faulty when a fault has
been observed.
. The generated diagnostic reports contain lists of faulty plug –in units.
1.2 Maintenance recommendations
The recommended maintenance routines can be carried out by anyone
from the regular operating personnel of the network element, as these
routines do not require special training or disassembling of equipment.
They can be carried out during normal working hours except where stated
otherwise. The Customer is recommended to keep a network element
diary. The diary should be network element-specific, but you can store it in
the Operation and Maintenance Centre if the network element is not
usually manned.
Start filling in the network element diary already when the network element
is being set up and installed.
You are recommended to record the following events in the network
element diary:
. Hardware changes
. Software and hardware updates (change notes, correction
deliveries, etc.)
12 (38) # Nokia Siemens Networks DN9770958Issue 9-1 en
General Maintenance Procedures
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 13/38
. Essential modifications to the configuration or routing in the network
element. Safecopying
. Operational failures
. Any other relevant information
Entries must include the date, time and maintenance personnel's name.
1.2.1 Service of peripheral devices
This section describes the service of the different peripheral devices. Thefocus here is on the equipment, even though the service intervals for the
peripheral devices are mentioned.
This table does not contain any of the equipment that is not supplied by
Nokia but what may have an effect on the performance of the network
element. Nevertheless, it must be regularly tested according to the
manufacturer's instructions. Additionally, there are a few general
maintenance recommendations that you can take into account with the
service of the external equipment. See Performing maintenance routines
on external equipment for more information on the subject.
Table 1. The service of peripheral devices on the DX 200 network element.
DEVICE SERVICE INTERVAL DURATION ACTION
Visual Display Unit (VDU) Monthly 5 - 10 min General cleaning
Cartridge Tape Unit (CTU) Depends on the
operating hours. See
Cleaning CTU for
instructions.
5 - 10 min Cleaning using a
cleaning cartridge
Line Printer (LPT) Monthly , weekly , daily 5 - 10 min General cleaning, change
the printer ribbon
Floppy Disk Unit (FDU) Yearly 15 - 20 min Cleaning using cleaning
disk
Hard Disk Unit (WDU) Usually none, but see
Hard disk drive for
instructions on special
cases.
None None
MO Disk Unit None but if damaged,
send the unit to Nokia's
Hardware Service (HWS)
for repairing
None None
DN9770958Issue 9-1 en
# Nokia Siemens Networks 13 (38)
General maintenance procedures
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 14/38
14 (38) # Nokia Siemens Networks DN9770958Issue 9-1 en
General Maintenance Procedures
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 15/38
2 Performing daily maintenance routines
During normal hours, you must investigate the alarms as they are
reported.
2.1 Outputting alarm history
Steps
1. Output the alarm history for the previous 24hrs
2. Split the output into smaller units if there is a large number of
alarms.
You can use the CLS parameter to split the output into smaller units.
All alarms must be investigated and accounted for.
Further information
Example
Output all alarms from 16th May 97 at 9.30 (AHP).
ZAHP::1997–
05–
16,09–
30–
0
Example
Output 3-star alarms from 16th May 97 at 10.00
ZAHP::CLS=AL3:1997–05–16,10–0–0
DN9770958Issue 9-1 en
# Nokia Siemens Networks 15 (38)
Performing daily maintenance routines
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 16/38
2.2 Outputting current alarms
Steps
1. Output current alarms (AHO)
ZAHO;
2.3 Checking working states of computer units
Steps
1. Check that any abnormal working states are accounted for (USI)
ZUSI:COMP;
You can use the USL command to list units in an incorrect state. The
following command lists all the units in incorrect state (that is, other
than WO-EX or SP-EX or if the unit is in faulty state, FLTY):
ZUSL:,INCO:ALL;
2.4 Checking working states of I/O devices
Steps
1. Check the working states of I/O devices (ISI)
For example, to check the states of I/O devices connected to the
OMU, provide the following.
ZISI:,OMU:ALL;
2.5 Outputting clear codes
Steps
1. Output the clear codes (TUT)
ZTUT:CLR;
16 (38) # Nokia Siemens Networks DN9770958Issue 9-1 en
General Maintenance Procedures
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 17/38
2. Study the report and investigate any abnormal trends
You can obtain the previous measurement period using the TUL
command.
ZTUL:SER;
3. Use the TOF command to monitor an unexpectedly high amount
of certain clear codes
ZTOF:S,,<codes>;
You can monitor 5 different clear codes simultaneously. The results(in ASCII) will be output via the TRAOBS logical file.
Note
Remember that clear code monitoring, as well as any other monitoring,
is not meant to be left on permanently.
2.6 Inspecting printers
Steps
1. Ensure that all printers have enough paper for the next 24 hours
2. Ensure that all printers are operating correctly
2.7 Inspecting tape units
Steps
1. Ensure that all tape units have enough tape for the next 24
hours
2. Ensure that all tape units are operating correctly
DN9770958Issue 9-1 en
# Nokia Siemens Networks 17 (38)
Performing daily maintenance routines
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 18/38
2.8 Updating FB build
Before you start
To be able to update the FB build, you need to have the FB build created
already by using the mode=full parameter of the WKS command.
Note
Take fallbacks during low traffic, for example, at night.
Steps
1. Update the FB build (WKS)
ZWKS:MODE=DATA;
Note
You can do this only if the node contains a full fallback copy of the BU
build.
2. Check in the log file that the backup was successful (WKP)
ZWKP:DATA:EMODE;
Further information
For more information on the fallback copying procedure, see the
instructions on Safecopying .
2.9 Taking backup copies of FB build on DDS tape
This section describes how to copy the FB build to the Cartridge Tape Unit
(CTU).
18 (38) # Nokia Siemens Networks DN9770958Issue 9-1 en
General Maintenance Procedures
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 19/38
Note
Use several DAT tapes and swap them each week to prevent a tape
failure during the operation from destroying the only backup.
Steps
1. Check the name of the directory where the fallback copy is
stored (WQO)
ZWQO:CR;
Note
Make sure that the FB build has been updated as described in section
Updating the FB build .
2. Copy the files (IPS)
The following command copies data from the system disk located in
the OMU to the CTU located in the same OMU.
ZIPS:”OMU”,WDU-S,/FB980815,,,:,CTU-0,,,:
NAME=BACKUP1, DIR=INC, ISD=Y;
3. Always remove the tape from the drive
This prevents dust from entering the drive mechanism.
Further information
For more information on how to take a backup of the FB build, refer to
instructions on Safecopying .
2.10 Cleaning CTU
This section describes the service of the Cartridge Tape Unit (CTU).
DN9770958Issue 9-1 en
# Nokia Siemens Networks 19 (38)
Performing daily maintenance routines
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 20/38
Table 2. Cleaning the Cartridge Tape Unit
DEVICE All models
SERVICE INTERVAL In backup copying, service takes place after every 25 hours of use. It takes
approximately 25 hours to write 7 cartridge tapes full.
When information is stored continuously, as in charging, cleaning takes place after 5
cartridge tapes are written full. If the tapes are not written full, you can clean the
CTU less frequently.
Note, always clean the CTU if the indicator on the unit indicates that the read-write
head is dirty.
ESTIMATED
DURATION
5 - 10 min
TOOLS Cleaning cartridge (for example, HP92283K)
Note
The Cartridge Tape Unit (CTU) drive must be cleaned every 25 hours
working time using a cleaning tape (for example, HP92283K).
The 25 hours mentioned in the table above refers to active operating
time that the tape unit spends reading or writing on the tape. The
passive operating time is insignificant from the service point of view. Always remove the tape from the drive after backup copying.
Clean the CTU with a cleaning tape. Discard the cleaning tape after 25
uses and start using a new one. The cleaning must not be done too
often because it shortens the life of the cartridge tape unit. However,
cleaning must not be omitted, since it ensures the faultless functioning
of the CTU.
Steps
1. Remove the tape from the tape unit if necessary
2. Insert the cleaning tape into the drive
Make sure this is done with the same care as with a cartridge tape to
avoid damage to the loading system.
3. Wait until it is ejected automatically (2-3 mins)
20 (38) # Nokia Siemens Networks DN9770958Issue 9-1 en
General Maintenance Procedures
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 21/38
Note
Discard the cleaning tape after 25 uses and start using a new cleaning
tape.
4. Insert a cartridge tape into the tape unit
Storage of cartridge tapes
Store the cartridge tapes in their protective covers. Avoid storing the tapes
near strong magnetic fields.
Tape operating circumstances:
. Temperature from 5 to 45 degrees Celsius
. Relative humidity from 20 to 80 %
Tape storage circumstances:
. Temperature from 5 to 32 degrees Celsius
. Relative humidity from 20 to 60 %
Note
If you store tapes in temperatures other than the operating temperature,
do not insert them into the drive immediately. Before using such a tape,
let the temperature difference even out by keeping the tape in the
operating temperature for at least two hours.
DN9770958Issue 9-1 en
# Nokia Siemens Networks 21 (38)
Performing daily maintenance routines
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 22/38
22 (38) # Nokia Siemens Networks DN9770958Issue 9-1 en
General Maintenance Procedures
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 23/38
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 24/38
3.3 Checking blocked alarms
Steps
1. Check the blocked alarms (ABO)
ZABO;
2. Look for any blocked alarms that cannot be accounted for
3.4 Checking date and timeSteps
1. Check the date and time of the network element (DCD)
ZDCD;
Note
Remember that changing the time affects all time measurements
currently in progress in the network element (or elements). Thisincludes, for example, traffic measurement periods and measurement
of the conversation time in detailed charging. The effects of changing
the time must be taken into account in these measurements (in the
analysis and further processing of the results).
3.5 Checking printers
Steps
1. Check the printer ribbons
2. Clean the printers if required
24 (38) # Nokia Siemens Networks DN9770958Issue 9-1 en
General Maintenance Procedures
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 25/38
4 Performing monthly maintenance
routines
This section describes the routines to be carried out at one-monthintervals.
4.1 Checking hardware alarms
Steps
1. Check the hardware alarms and alarm inputs (WAE)
The following command tests the alarm inputs of all cartridges inrack 1A:
ZWAE:1A;
Note
This command only works in network elements with cartridge
construction.
4.2 Cleaning visual display unit
This section describes the service of the Visual Display Unit (VDU).
The table below shows the Visual Display Unit service interval, the
estimated duration of service, and the tools needed in service.
DN9770958Issue 9-1 en
# Nokia Siemens Networks 25 (38)
Performing monthly maintenance routines
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 26/38
Table 3. Cleaning the VDU
DEVICE All models
SERVICE INTERVAL Monthly
ESTIMATED DURATION 5 - 10 min
TOOLS Soft cloth and cleaning fluid or suitable cleaner tissue
Note
Fluids containing oils or alcohol must not be used for the cleaning. Amild soap solution is suitable.
Steps
1. Wipe the screen, the case, and the keyboard
Use a cloth moistened with the cleaning solution or with ready-made
cleaner tissues.
2. Adjust the brightness and contrast of the display if necessary
Note
Avoid having the display unit adjusted too bright since that shortens the
lifetime of the Cathod Ray Tube (CRT).
4.3 Cleaning printer
This section describes the service of printers (LPT).
The table below shows the printer service interval, the estimated duration
of service, and the tools needed in service.
Table 4. Cleaning the LPT
DEVICE All models
26 (38) # Nokia Siemens Networks DN9770958Issue 9-1 en
General Maintenance Procedures
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 27/38
Table 4. Cleaning the LPT (cont.)
SERVICE INTERVAL Monthly
ESTIMATED DURATION 5 - 10 min
TOOLS Soft cloth, vacuum cleaner equipped with an absolute filter
when necessary
Note
Cleaning fluids containing alcohol must not be used when cleaning therubber-coated parts of the printer.
Steps
1. Disconnect the printer from the mains power supply
2. Open the cover
3. Vacuum clean the inside of the printer
You need to do this with a vacuum cleaner that is equipped with an
absolute filter and a thin plastic nozzle.
4. Change the ribbon if necessary
5. Close the cover
6. Connect the printer to the mains power supply
DN9770958Issue 9-1 en
# Nokia Siemens Networks 27 (38)
Performing monthly maintenance routines
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 28/38
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 29/38
5 Performing six-monthly maintenance
routines
Running fault diagnoses and changing unit states
Run fault diagnoses on all spare computer units, message buses, and
clock units.
Note
The routines in this section should be carried out in low traffic periods.
Steps
1. Change the unit state to TE (USC)
For example, to change the SSU 0 –1 to test state:
ZUSC:SSU,0,1:TE;
2. Run the fault diagnosis (UDU)
For example, to run all fault diagnoses on SSU 0 –1:
ZUDU:SSU,0,1;
3. If any of the fault diagnoses fail, investigate and correct the
fault.
You can do this by using the normal maintenance procedures.
4. Change the unit states of the units diagnosed above to WO-EX
(USC)
ZUSC;
DN9770958Issue 9-1 en
# Nokia Siemens Networks 29 (38)
Performing six-monthly maintenance routines
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 30/38
Note
In larger network elements the above routines will be time-consuming.
The operator may first wish to perform the fault diagnoses followed by
unit changeovers one month later. The frequency of the routines can be
adjusted accordingly. Carry out the unit changeovers during low traffic.
30 (38) # Nokia Siemens Networks DN9770958Issue 9-1 en
General Maintenance Procedures
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 31/38
6 Performing yearly maintenance routines
This section presents the routines to be carried out yearly.
6.1 Checking voltages
Cartridge construction
There is no need to check the voltages in cartridge construction networkelements.
Subrack construction
If the network element construction is based on subracks, check thevoltages of the subracks at the vertical power buses.
Steps
1. Measure the supply voltage at the rack-specific power supply
points
Refer to the table below for the voltage tolerances.
Table 5. Feed voltage to DC/DC converters
Nominal voltage Tolerance
-48 V -41.5 V to -57 V
-60 V -48 V to -75 V
2. Check and measure the voltages of the vertical power busses
Refer to the table for the tolerances of idle voltages.
DN9770958Issue 9-1 en
# Nokia Siemens Networks 31 (38)
Performing yearly maintenance routines
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 32/38
Table 6. Voltages of racks
Nominal voltage Tolerances of idle voltages
5.1 V 5.10 - 5.20 V
12.1 V 12.10 - 12.25 V
120 V 120 - 130 V (49.5 - 50.5 Hz)
Note
Measured voltages must be within +/- 5% of the nominal voltage. If thevoltage does not meet the tolerance requirements, replace the power
supply unit and send the faulty unit to service.
3. Check the earthing connections visually
4. Measure the voltage difference between the earth (DOV) and +
lead (0V)
Note
The voltage difference must be under 1V. If the voltage difference is
greater than 1V, do the following:
a. Check what the difference was when the network element was
installed and commissioned
b. Check the results of previous measurements if there are any
c. Check that the voltage meter is correctly calibrated
d. Check that the voltage meter is properly connected
e. Measure the voltage difference in each earthing connection
5. If the measurement result is still not within the allowed limits,
note this down in the network element diary
32 (38) # Nokia Siemens Networks DN9770958Issue 9-1 en
General Maintenance Procedures
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 33/38
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 34/38
. When you remove a disk from the drive, always return it to the case.
. Keep the disks away from magnetic fields and ferromagneticsubstances which can become magnetized. A strong magnetic field
will destroy the data on the disks.
. Do not expose the disks to heat or sunshine.
. Do not touch or try to clean the surfaces of a disk. Rubbing may
destroy the data on the disk.
. Use 3,5" HD disks only.
34 (38) # Nokia Siemens Networks DN9770958Issue 9-1 en
General Maintenance Procedures
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 35/38
7 Marking unused blocks on a hard disk
Hard disk drives need no service.
However, with time there will be read and write errors on the disks due to
corrupted blocks. These blocks can be marked as 'bad blocks', that is,
unused blocks.
Steps
1. Mark these blocks as 'bad blocks', that is, unused blocks (IWB)
For example, to take block number 1234H out of use, do thefollowing:
Z I W B : : W B : B , 1 2 3 4 ;
For more information on bad blocks, see section Bad blocks in
Introduction to replacing WDUs .
If there are a lot of bad blocks on a disk, the disk can be replaced
with a new one. For instructions on replacing the hard disk, see
Replacing the hard disk unit .
DN9770958Issue 9-1 en
# Nokia Siemens Networks 35 (38)
Marking unused blocks on a hard disk
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 36/38
36 (38) # Nokia Siemens Networks DN9770958Issue 9-1 en
General Maintenance Procedures
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 37/38
Glossary
Abbreviations
BU (Backup) Backup, refer to Backup (BU) build in concepts.
FB (Fallback) Fallback, refer to Fallback (FB) build in concepts.
LFILES
(Loadable
Files directory)
The LFILES directory contains the data files loaded and updated by the file
system. The directory can also contain data files loaded by the initial
loading system.
SCMANA
(Software
Configuration
Management
directory)
The Software Configuration Management directory, that is, the directory for
managing the software builds. This directory only contains files (SOMAFI)
which are used by the build management function integrated into the
exchange. The name is identified by the software (including boot) and it
must not be changed.
UT (Untitled) Untitled, refer to Untitled (UT) build in concepts.
Concepts
BU (Backup
build)
A build on disk that is usually defined as active and in use, and which is
therefore normally loaded by the initial loading system when the exchange
is restarted. The BACKUP build cannot be removed with buildmanagement commands.
Cartridge Cartridge is a capsule into which the plug-in units are placed. The cartridge
is placed in a rack.
Change note Notification of a change or modification in a product (equipment or a plug-
in unit, software or hardware) sent to a customer.
Correction
delivery
Software which consists of chosen corrections to faults.
FB (Fallback
build)
A safecopy build of the BACKUP build on disk. The exchange can be
returned to the FALLBACK build with MML commands.
Preventive
maintenance
Maintenance carried out at predetermined intervals or according to
prescribed criteria and intended to reduce the probability of failure or the
degradation of the functioning of an item.
Service
terminal
A terminal which can be connected to a system for maintenance and
operating purposes.
DN9770958Issue 9-1 en
# Nokia Siemens Networks 37 (38)
Glossary
8/9/2019 General Maintenance Procedure
http://slidepdf.com/reader/full/general-maintenance-procedure 38/38
Subrack The subrack construction contains racks which are equipped with
subracks.
UT (Untitled
build)
Software build which is created without a need to make it active. The
system allows more than one build to have this status. For example, the
status of the FB build becomes UT when you use the WQS command to
create an FB build.
General Maintenance Procedures