36
INSTRUCTIONS TIME O VE RCU R RENT RELAYS TY PE IFC95F (-)A GENERAL ELECTRIC GEK-49951 A Supersedes GEK-4995 1 www . ElectricalPartManuals . com

GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

INSTRUCTIONS

TIME O VE RCU R RENT RELAYS

TYPE

I FC95F (-)A

GENERAL fj ELECTRIC

GEK-49951A Supersedes GEK-4995 1

www . El

ectric

alPar

tMan

uals

. com

Page 2: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

GEK-49951

CONTENTS

DESC RI PTION................................. 3 A P PLICATION................................. 3 CONST RUCTION................................ 3 RATINGS..................................... 4

TIME O VE RCU R RENT UNIT.................... 4 HIGH -SEISMIC INSTANTANEOUS UNIT.......... 5 HIGH -SEISMIC TA RGET AND SEAL-IN UNIT..... 6

BU RDENS.. • • • • • • • • • • • • . • • • • • • . • . • • • • • • • • • • • • • 7 CHA RACTERISTICS............................. 7

TIME-O VE RCU R RENT UNIT.................... 7 HIGH -SEISMIC INSTANTANEOUS UNIT.......... 8 HIGH -SEISMIC TA RGET AND SEAL -IN UNIT..... 8

RECEI VING, HANDLING AND STO RAGE............. 8 ACCE PTANCE TESTS............................ 9

VISUAL INS PECTION........................ 9 MECHANICAL INS PECTION.................... 9 D RA W -OUT RELAY TESTING................... 9 PO WE R REQUIREMENTS, GENERAL.............. 10 TIME O VE RCU R RENT UNIT.................... 10 HIGH -SEISMIC INSTANTANEOUS UNIT.......... 1 1 HIGH-SEISMIC TA RGET AND SEAL-IN UNIT..... 12

INSTALLATION • . . • • • . . • . . . . . . • • . • . . . . . . . . • • • . 12 TIME O VE RCU R RENT UNIT.................... 13 HIGH-SEISMIC TA RGET AND SEAL -IN UNIT..... 13 HIGH-SEISMIC INSTANTANEOUS UNIT.......... 13

PE RIODIC CHECKS AND ROUTINE MAINTENANCE.... 13 TIME O VE RCU R RENT UNIT.................... 13 HIGH -SEISMIC INSTANTANEOUS UNIT.......... 14 HIGH-SEISMIC TA RGET AND SEAL-IN UNIT..... 14 CONTACT CLEAN! NG......................... 14 CO VE R CLEANING........................... 14 SYSTEM TEST.............................. 14

SERVICING................................... 14 TIME O VE RCUR RENT UNIT.................... 14 HIGH -SEISMIC INSTANTANEOUS UNIT.......... 16 HIGH-SEISMIC TA RGET AND SEAL-IN UNIT..... 1 7

RENEWAL PA RTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 7 LIST OF FIGU RES............................. 18

Cover Photograph (8043004)

2 www . El

ectric

alPar

tMan

uals

. com

Page 3: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

GEK-49951

TIME OVERCURRENT RELAYS

TYPE IFC95F (-)A

DESCRIPTION

The type IFC95F ( -)A relay is an extended range, single phase, time overcurrent relay, having a short inverse time characteristic, a target/seal-in unit and a hinged armature instantaneous overcurrent unit. Both the time overcurrent unit and the instantaneous overcurrent unit are described in detail in the section on CONSTRUCTION.

The relays are mounted in a size C 1 draw -out case of molded construction. The outline and panel drilling are shown in Figures 14 and 15. The relay internal connections are shown in Figure 3 for the IFC95F (-)A relay.

When semiflush mounted on a suitable panel, these relays have a high seismic capability, including both the target seal-in unit and the instantaneous overcurrent unit. Also, these relays are recognized under the Components Program of Underwriters Laboratories, Inc.

APPLICATION

The type IFC95F relays are designed for application where a fast inverse time characteristic in combination with a relatively low burden is required. A typical application is illustrated by Figure 6, where the relay is used to provide sensitive ground fault protection for equipment 1 1 downstream1 1 from a grounded transformer.

CONSTRUCTION

The IFC induction disk relays consist of a molded case, cover, support structure assembly, and a connection plug to make up the electrical connection. See cover figure and Figures 1, 2 and 13. Figure 2 shows the induction unit mounted to the molded support structure. This disk is activated by a current -operating coil mounted on a laminated U-magnet. The disk and shaft assembly carries a moving contact which completes the alarm or trip circuit when it touches a stationary contact. The disk assembly is restrained by a spiral spring to give the proper contact closing current. The disk•s rotation is retarded by a permanent magnet mounted in a molded housing on the support structure.

These instructions do not purport to cover all details or variations in equipment nor to provide for

every possible contingency to be met in connection with installation, operation or .. intenance. Should

further information be desired or should particular problems arise which are not covered sufficiently for the purchaser's purposes, the matter should be referred to the General Electric Conpany.

To the extent required the products described herein meet applicable ANSI, IEEE and NENA standards!

but no such assurance is given with respect to local codes and ordinances because they vary greatly.

3 www . El

ectric

alPar

tMan

uals

. com

Page 4: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

GEK-49951

The draw-out connection/test system for the C1 case, shown in Figure 1 3, has provisions for 14 connection points, and a visible CT shorting bar located up front. As the connection plug is withdrawn, it clears the shorter contact fingers in the output contact circuits first. Thus, the trip circuit is opened before any other circuits are disconnected. Next, current circuit fingers on the case connection block engage the shorting bar (located at the lower front of the case ) to short circuit external current transformer secondary connections. The window provides visual confirmation of CT shorting. The connection plug then clears the current circuit contact fingers on the case, and finally those on the relay support structure to completely de-energize the draw-out element.

There is a high-seismic target and seal-in unit mounted on the front to the left of the shaft of the time overcurrent unit (see Figure 1). The seal-in unit has its coil in series and its contacts in parallel with the contacts of the time overcurrent unit such that when the induction unit contacts close, the seal-in unit picks up and seals in. When the seal-in unit picks up, it raises a target into view that latches up and remains exposed until released by pressing a reset button located on the upper left side of the cover.

In addition to the above, the relay contains a high-seismic instantaneous unit (see Figure 1). The instantaneous unit is a small hinged-type unit that is mounted on the front to the right of the shaft of the time overcurrent unit. Its contacts are normally connected in parallel with the contacts of the time overcurrent unit and its coil is connected in series with the time overcurrent unit. When the instantaneous unit picks up, it raises a target that latches up and remains exposed until it is released. The same reset button that relases the target seal-in unit also releases the target of the instantaneous unit.

A magnetic shield is mounted to the support structure of the IFC relay, to eliminate the proximity effect of external magnetic materials.

Both the high-seismic target and seal-in unit and the high-seismic instantaneous unit have the letters "Hi-G" molded into their target blocks to distinguish them as high-seismic units. Seismic Fragility Level exceeds peak axial acceleration of 7.5 g's {4g ZPA ) when tested using a biaxial multi­frequency input motion to produced a Required Response Spectrum ( R RS ) in accordance with IEEE Standard 50 1, Seismic Testing of Relays, 1978.

RATINGS

The relays are designed for operation in an ambient air temperature from -2ooc to +ssoc.

TIME O VE RCU RRENT UNIT

Ranges for the time overcurrent unit are shown in Table I.

4

www . El

ectric

alPar

tMan

uals

. com

Page 5: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

GEK-49951

TABLE I

,-··--�.-------��-------�� .. --�·--��----�-----------. Relay Frequency (Hertz) Current Range (Amperes)

IFC95F 50 and 60 0.5 - 4.0 1.0 - 12.0

Available taps for the time overcurrent unit are shown in Table II.

TABLE II

Range Taps Ava il a b 1 e ( Am pe re s ) (Amperes) 0.5 - 4.0 0.5 , 0.6 , 0.7 , 0.8 , 1.0 1 1.2 1.5 , 2.0 2.5 , 3.0 ) 4.0 ) ) 1 - 12 1.0 1.2 1.5 2.0 2.5 3.0 4.0 5.0 6.0 7.0 8.0 10.0 12.0

The one-second thermal ratings are listed in Table III.

(Amperes) .5 - 4.0 .0 - 12.0

TABLE I II

One-Second Rating Any Tap (Amperes)

82 164

6vercurrent Unit

·------------------------

K

6724 26896

Ratings less than one second may be calculated according to the formula: I = JK/T, where T is the time in seconds that the current flows.

The continuous ratings for the time overcurrent unit are shown in Tables IV and V.

-

-,--ap l.U r: Cont.Curr. 2.0 2.

HIGH-SEISMIC INSTANTANEOUS UNIT

TABLE IV

2.�f�:�p·o 4.0 2.9 3.3 3. 7 4.5 -- ----

The instantaneous coil is tapped for operation on either one of two ranges (H or L). Selection of the high or low range is accomplished by the positioning of the link located on the top of the support structure. See Figure 1 and Table VI.

5

www . El

ectric

alPar

tMan

uals

. com

Page 6: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

GEK-49951

TABLE VI

High Seismic Continuous **One Second Instantaneous Unit Link * Range Rating Rating K

(Amps) Position (Amps) (Amps) (Amps)

2 - 50 L 2 - 10 3. 7 130 16,900 H lU - !:>U /.!:>

6 - 150 L 6 - 30 10.2 260 67,600 H 30 - 1�0 l�.b

*The range 1s approx1mate, wh1ch means that the 2- 10, 10-50 may be 2-8, 8-50. There wi 11 always be at 1 east 1 ampere overlap between the maximum L setting and the minimum H setting. Whenever possible, be sure to select the higher range, since it has the higher continuous rating.

**Higher currents may be applied for shorter lengths of time in accordance with the formula:

I "' JK/T

Since the instantaneous unit coil is in series with the time overcurrent unit coil, see Tables III, IV, V and VI to determine the current-limiting element for both continuous and short-time ratings.

HIGH-SEISMIC TA RGET AND SEAL-IN UNIT

Ratings for the target and seal-in unit are shown in Table VII.

TABLE VII

DC Resistance � 10% (Ohms ) Min. Operating (Amp.) +0 -60% Carry Continuous (Amperes) Carry 30 Amps for (Seconds) Carry 10 Amps for (Seconds) 60 Hz Impedance (Ohms)

'----

0.2 8.0 0.3 0.3 0.03 0.25

68.6

Tap 2 0.24 2.0 3.0

4 30 0.73

If the tripping current exceeds 30 amperes an auxiliary relay should be used, the connections being such that the tripping current does not pass through the contacts or the target and seal-in coils of the protective relay.

CONTACTS

The current-closing rating of the contacts is 30 amperes for voltages not exceeding 250 volts. The current-carrying rating is limited by the ratings of the seal-in unit.

6 www . El

ectric

alPar

tMan

uals

. com

Page 7: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

GEK-49951

BURDENS

Burdens for the time overcurrent unit are given in Table VIII.

TABLE VI II

Min Burdens at Min. Pickup Burdens in Ohms Tap Min. Tap (Ohms) (Z) Times Pickup

HZ Range Amps R Jx z 3 10 20

60 0.5 - 4.0 0.5 6.30 24.20 25.00 2 1.30 9.96 6. 13 1.0 - 12.0 1.0 1.49 6.09 6.27 5.44 2.55 1.09

50 0.5 - 4.0 0.5 5.25 20.17 20.83 17.75 8.30 5. 1 1 1.0 - 12.0 1.0 1.24 5.08 5.23 4.53 2. 13 0. 9 1

Note: The impedance values given are those for minimum tap of each range; the impedance for other taps at pickup current (tap rating) varies inversely (approximately) as the square of the tap rating. For example, an IFC95 60 Hz relay with 1 - 12 amp range has an impedance of 6.27 ohms on the 1.0 amp tap. The impedance of the 2.0 amp tap is ( 1.0/2.0)2 X 6.27

= 1.57 ohms.

The high-seismic instantaneous unit burdens are listed in Table IX.

TABLE IX

High Min. Burdens at Min. Burdens in Seismic HZ Link Range Pickup Pickup (Ohms) Ohms ( Z)

Inst.Unit Position (Amps) (Amps) Times Pickup (Amps) R Jx z 3 10 20

2- 50 60 L 2 - 10 2 0.750 0.650 0.992 0.634 0.480 0.457 H 10- 50 10 0.070 0.024 0.074 0. 072 0. 07 1 0. 070

6- 150 60 L 6- 30 6 0. 1 10 0.078 0.135 0. 095 0.08 1 0.079 H 30- 150 30 0.022 0.005 0.023 0.022 0.022 0.022

2- 50 50 L Z- IU z U.6Zt> U.b4Z 0.827 U.b28 U.4UU 0 .38U H 10- 50 10 0.058 0.020 0.062 0.060 0. 059 0.058

6- 150 50 L 6- 30 6 0.092 0. 065 0. 1 12 0.079 0.068 0.066 H 30-150 30 10.018 0.004 0.019 0.018 0.018 0.018

CHARACTERISTICS

TIME OVERCU R RENT UNIT

Pickup

Pickup in these relays is defined as the current required to close the contacts from the 0.5 time-dial position. Current settings are made by means of two movable leads, which connect to the tap block at the top of the support structure (see Figure 1). The tap block is marked A through N.

Example: The 2-amp tap for a 1 - 12 amp IFC95 time overcurrent relay requires one mov

)able lead in position C and the other in position L (see

Table X .

7

www . El

ectric

alPar

tMan

uals

. com

Page 8: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

GEK-49951

TABLE X

Taps ��� B/ � 1/{ v: D/< �� l.�/: 7 ; L L V/K t../ 15""· 1 c k u p , Am pe re s 0.5 0.6 0.7 � 1.0 1.2 1.5 2.0 2.5 3.0 4.0

--'---

Taps A / B / _./ c _/ c "l/( X 0/ /� l/{ �� ��� � /.N v M M L /. J P1ckup, A 1.0 1.2 1.5 2.0 2.5 3.0 4.0 5.0 6.0 7.0 8.0 l 10 12

p per at in g Time Accuracy

IFC relays should operate within � 7% or � the time dial setting times 0.0 10 seconds, whichever is greater, of the published time curve. Figures 4 and 5 show the various time-current characteristics for the IFC relays. The setting of the time dial determines the length of the time required to close the contacts for a given current. The higher the time-dial setting, the longer the operating time.

The contacts are just closed when the time dial is set to 0. The maximum time setting occurs when the time dial is set to 10 and the disk has to travel its maximum distance to close the contacts.

Reset

The unit resets at 90% of the m1n1mum closing current. Reset times are proportionate to the time dial settings. The time to reset to the Number 10 time­dial position when the current is reduced to 0 is approximately 4 seconds for the I FC95 relays.

HIGH -SEISMIC INSTANTANEOUS UNIT

The instantaneous unit has a 25-to- 1 range with a tapped coil. There are high and low ranges, selected by means of a link located on the top of the support structure (see Figure 1). The time-current curve for the instantaneous unit is shown in Figure 8.

HIGH-SEISMIC TA RGET AND SEAL-IN UNIT

The target and seal-in unit has two tap selections located on the front of the unit (see Figure 1).

RECEIVING, HANDLING AND STORAGE

These relays, when not included as part of a control panel will be shipped in cartons designed to protect them against damage. Immediately upon receipt of a relay, examine it for any damage sustained in transit. If damage resulting from rough handling is evident, file a damage claim at once with the transportation company and promptly notify the nearest General Electric Sales Office.

Reasonable care should be exercised in unpacking the relay in order that none of the parts are damaged or the adjustments disturbed.

If the relays are not to be installed immediately, they should be stored in their original cartons in a place that is free from moisture, dust and metallic chips.

8 www . El

ectric

alPar

tMan

uals

. com

Page 9: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

GEK-49951

Foreign matter collected on the outside of the case may find its way inside when the cover is removed, and cause trouble in the operation of the relay.

ACCEPTANCE TESTS

Immediately upon receipt of the relay an Inspection and Acceptance Test should be made to ensure that no damage has been sustained in shipment and that the relay calibrations have not been disturbed. If the examination or test indicates that readjustment is necessary, refer to the section on SERVICING.

Si nee operating companies use different procedures for acce pta nee and installation tests, the following section includes all applicable tests that may be performed on these relays. These tests may be performed as part of the installation or acceptance tests at the discretion of the user.

VISUAL INS PECTION

Check the nameplate to ensure that the model number and rating of the relay agree with the requisition.

Remove the relay from its case and check that there are no broken or cracked parts or any other signs of physical damage.

MECHANICAL INS PECTION

1. There should be no noticeable friction when the disk is rotated slowly clockwise. The disk should return by itself to its rest position.

2. Make sure the control spring is not deformed, nor its convolutions tangled or touching each other.

3. The armature and contacts of the seal -in units, as well as the armature and contacts of the instantaneous unit, should move freely when operated by hand; there should be at least 1/64 inch wipe on the seal-in and the instantaneous contacts.

4. The targets in the seal-in unit and in the instantaneous unit must come into view and latch when the armatures are operated by hand, and should unlatch when the target release button is operated.

5. Make sure that the brushes and shorting bars agree with the internal connections diagram.

-------�cAUTiON ___________________ -------

Should there be a need to tighten any screws DO NOT OVER TIGHTEN, to prevent stripping.

D RAW-OUT RELAY TESTING

IFC relays may be tested without removing them from the panel by using the 12XCA 1 1Al four-point test probes. The 12XCA 1 1Al four-point test probe rna kes

9 www . El

ectric

alPar

tMan

uals

. com

Page 10: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

GEK-49951

connections to both the relay and the external circuitry, which provides maximum flexibility, but requires reasonable care since a CT shorting jumper is necessary when testing the relay. The CT circuit may also be tested by using an ammeter instead of the jumper. See the test circuit in Figure 9.

PO WE R REQUI REMENTS, GENE RAL

All alternating-current-operated devices are affected by frequency. Since non-sinusoidal waveforms can be analyzed as a fundamental frequency plus harmonics of the fundamental frequency, it follows that alternating-current (AC) devices (relays) will be affected by the applied waveform. Therefore, in order to test alternating-current relays properly it is essential to use a sine wave of current and/or voltage. The purity of the sine wave (i.e., its freedom from harmonics) cannot be expressed as a finite number for any particular relay; however, any relay using tuned circuits, R-L or RC networks, or saturating electromagnets, (such as time overcurrent relays) would be essentially affected by non-sinusoidal waveforms. Hence a resistance-limited circuit, as shown in Figures 10- 12, is recommended.

TIME OVE RCU R RENT UNIT

Rotate the time dial slowly and check by means of a lamp that the contacts just close at the 0 time-dial setting.

The point at which the contacts just close can be adjusted by running the stationary contact brush in or out by means of its adjusting screw.

With the contacts just closing at No.O time setting, there should be sufficient gap between the stationary contact brush and its metal backing strip to ensure approximately 1/32 inch wipe.

The minimum current at which the contacts will just close is determined by the tap setting in the tap block at the top of the support structure. See CHARACTERISTICS section.

The pickup of the time overcurrent unit for any current tap setting is adjusted by means of a spring-adjusting ring. See Figure 1. The spring­adjusting ring either winds or unwinds the spiral control spring. By turning the ring, the operating current of the unit may be brought into agreement with the tap setting employed, if this adjustment has been disturbed. This adjustment also permits any desired setting intermediate between the various tap settings to be obtained. If such adjustment is required, it is recommended that the higher tap be used. It should be noted that the relay wi 11 not necessarily agree with the time-current characteristics of Figures 4 and 5 if the relay has been adjusted to pick up at a value other than tap value, because the torque level of the relay has been changed.

Time Setting

The setting of the time dial determines the length of time the unit requires to close the contacts when the current reaches a predetermined value. The

10

www . El

ectric

alPar

tMan

uals

. com

Page 11: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

GEK-49951

contacts are just closed when the time dial is set on 0. When the time dial is set on 10, the disk must travel the maximum amount to close the contacts and therefore this setting gives the maximum time setting.

The primary adjustment for the time of operation of the unit is made by means of the time dial. However, further adjustment is obtained by moving the permanent magnet along its supporting shelf; moving the magnet toward the disk and shaft decreases the time, while moving it away increases the time.

Pickup Test

Set the relay at 0.5 time-dial position and the lowest tap. Using the test connections in Figure 10, the main unit should close the contacts within � 3% of tap value current.

Time Test

Set the relay at No.5 time-dial setting and the lowest tap. Using the test connection in Figure 1 1, apply 10 times tap current to the relay. The relay operating times to close its contact are listed in Table XI.

Hz

60 50

HIGH-SEISMIC INSTANTANEOUS UNIT

TABLE XI

Time (Seconds) Min. Max.

0.505 0.545 0.565 0.640

Make sure that the instantaneous unit link is in the correct position for the range in which it is to operate. See the internal connections diagram, Figure 3, and connect as indicated in the test circuit of Figure 1 1. Whenever possible use the higher range s i nee the higher range has a higher continuous rating.

Seting the High-Seismic Instantaneous Unit

The instantaneous unit has an adjustable core located at the top of the unit, as shown in Figure 1. To set the instantaneous unit to a desired pickup, loosen the locknut and adjust the core. Turning the core clockwise decreases the pickup; turning the core counterclockwise increases the pickup. Bring up the current slowly until the unit picks up. It may be necessary to repeat this operation until the desired pickup value is obtained. Once the desired pickup value is reached, tighten the locknut.

CAUTION Refer to Table VI for the continuous and 1-second ratings of the instantaneous unit. Do not exceed these ratings when applying current to the instantaneous unit.

1 1 www . El

ectric

alPar

tMan

uals

. com

Page 12: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

GEK-49951

The range of the instantaneous unit (see Table VI) core position of 1/8 of a turn from 11full counterclockwise from the full-clockwise position. the full-clockwise position.

HIGH-SEISMIC TA RGET AND SEAL -IN UNIT

must be obtained between a clockwise11 and 20 turns

Do not leave the core in

The target and seal-in unit has an operating coil tapped at 0.2 and 2.0 ameres. The relay is shipped from the factory with the tap screw in the higher ampere position. The tap screw is the screw holding the right-hand stationary contact. To change the tap setting, first remove one screw from the left-hand stationary contact and place it in the desired tap. There will now be two screws in the right-hand stationary contact, one in each tap. Screws should never be allowe d to remain in both taps at the same time, so next, remove the screw from the undesired tap and place it on the left-hand stationary contact where the first screw was removed (see Figure 1). This procedure is necessary to prevent the right-hand stationary contact from getting out of adjustment.

Pickup and Dropout Test

1. Connect relay studs 1 and 2 (see the test circuit of Figure 12) to a DC source, ammeter and load box so that the current can be controlled over a range of 0.1 to 2.0 amperes.

2. Turn the time dial to the 0 time-dial position.

3. Increase the current slowly until the seal-in unit picks up. See Table XI.

4. Move the time dial away from the 0 time-dial position; the seal-in unit should remain in the picked up position.

5. Decrease the current slowly until the seal-in unit drops out. See Table XI I.

TABLE XII 6-a

-=-p _____ P

::-i c

-:k:--:u::-p current D ro pout Cu r8en t

.2 0.12 - 0.20 0.05 or more

.0 1.2 - 2.0 0.50 or more -----------------------------

INSTALLATION

The relay should be installed in a clean, dry location, free from dust and well lighted to facilitate inspection and testing.

The relay should be mounted on a vertical surface. The outline and panel drillings are shown in Figure 14 for semi-flush mounting and Figure 15 for various methods of surface mounting.

The internal connection diagram for the relays is shown in Figure 3. Typical external connections are shown in Figure 6.

12

www . El

ectric

alPar

tMan

uals

. com

Page 13: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

GEK-49951

The following tests are to be performed at the time of installation:

TIME OVE RCU R RENT UNIT

Set the tap block to the desired tap setting, and the time dial to the 0.5 position. Using the test circuit in Figure 10, gradually apply current until the contacts just close. This value of current is defined as pickup and should be within 3% of tap value.

Check the operating time at some multiple of tap value and the desired time­dial setting. This multiple of tap value may be 10 times tap rating, or the maximum fault current for which the relay must coordinate. The value used is left to the discretion of the user.

HIGH-SEISMIC INSTANTANEOUS UNIT

1. Select the desired range by setting the link in the proper position (see Figures 1 and 3). Whenever possible, be sure to select the higher range since it has a higher continuous rating.

2. Set the instantaneous unit to pick up at the desired current level. See Setting the High-Seismic Instantaneous Unit in the ACCEPTANCE TESTS section.

HIGH-SEISMIC TA RGET AND SEAL-IN UNIT

1. Make sure that the tap screw is in the desired tap.

2. Perform pickup and dropout tests as outlined in the ACCEPTANCE TESTS section.

All tests described above under INSTALLATION TESTS must be performed at the time of installation. In addition, if those tests described in the ACCEPTANCE TESTS section were not performed prior to installation, it is recommended that they be performed at this time.

PERIODIC CHECKS AND ROUTINE MAINTENANCE

In view of the vital role of protective relays in the operation of a power system, it is important that a periodic test program be followed. The interval between periodic checks will vary depending upon environment, type of relay and the user•s experience with periodic testing. Until the user has accumulated enough experience to select the test interval best suited to his individual requirements, it is suggested that the points listed below be checked at an interval of from one to two years.

These tests are intended to ensure that the relays have not deviated from their original settings. If deviations are encountered, the relay must be retested and serviced as described in this manual.

TIME OVERCU R RENT UNIT

1. Perform pickup test as described in the INSTALLATION section for the tap setting in service.

13 www . El

ectric

alPar

tMan

uals

. com

Page 14: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

GEK-49951

2. Perform the time test as described in the ACCEPTANCE TESTS section.

HIGH-SEISMIC INSTANTANEO US UNIT

Check that the instantaneous unit picks up at the desired current level, as outlined in the ACCEPTANCE TESTS section.

HIGH-SEISMIC TA RGET AND SEAL-IN UNIT

1. Check that the unit picks up at the values shown in Table X 1.

2. Check that the unit drops out at 25% or more of tap value.

CONTACT CLEANING

A flexible burnishing tool should be used for cleaning relay contacts. This is a flexible strip of metal with an etched-roughened surface, which in effect resembles a superfine file. The polishing action of this file is so delicate that no scratches are 1 eft on the contacts, yet it cleans off any corrosion thoroughly and rapidly. The flexibility of the tool insures the cleaning of the actual points of contact. Relay contacts should never be cleaned with knives, files, or abrasive paper or cloth.

COVE R CLEANING

The clear Lexan R cover should be cleaned with a soft cloth and water only. Cleaning solutions may damage the cover.

SYSTEM TEST

Although this instruction book is primarily written to check and set the IFC re 1 ay, overall functi anal tests to check the system operation are recommended at intervals based on the customer's experience.

SERVICING

TIME OVERCUR RENT UNIT

If it is found during installation or periodic testing that the time overcurrent unit is out of limits, the unit may be recalibrated as follows:

Pickup Tests

Rotate time dial to No.O time-dial setting and check by means of an external contact-closing indicating light that the contacts just close.

The point at which the contacts just close can be adjusted by running the stationary contact brush in or out by means of its adjusting screw.

With the contacts just closing at No.O time setting, there should be sufficient gap between the stationary contact brush and its metal backing strip to ensure approximately 1/32 inch wipe.

14 www . El

ectric

alPar

tMan

uals

. com

Page 15: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

GEK-49951

The pickup of the unit for any current tap setting is adjusted by means of a spring-adjusting ring. By turning the ring, the operating current of the unit may be brought into agreement with the tap setting employed, if for some reason this adjustment has been disturbed. This adjustment also permits any desired setting, intermediate between the various tap settings, to be obtained. If such adjustment is required, it is recommended that the higher tap setting be used. It should be noted that the relay will not necessarily agree with the time current characteristics of Figures 4 and 5 if the relay has been adjusted to pick up at a value other than tap value, because the torque level of the relay has been changed.

Connect the operating coil terminals to a source of the proper frequency and good waveform, having a voltage of 1 10 or more, with resistance load boxes for setting the current. See test circuit, Figure 10.

With the tap block set for the lowest tap and the time dial set where contacts are just open, adjust the control spring to just close the contacts within the limits given in Table XIII, which are � 1% of the tap amps.

Tap Range Tap 0.5 - 4 0.5 1.0 - 12.0 1.0

TABLE XIII

Min. Amps 0.495 0.99

Max. Amps 0.505 1.0 1

It should never be necessary to wind up the control-spring adjuster more than 300 (one notch) or unwind it more than 1200 (three notches) from the factory setting to obtain the above pickup setting.

Time Tests

With the tap block set for the lowest tap and the time dial at No. 10 setting, apply 10 times tap current to the relay.

Adjust the position of the drag magnet assembly to obtain an operating time at least within the limits listed in Table XIV, but preferably as near as possible to 0.525 seconds for 60 Hz relays and 0.595 seconds for 50 Hz relays • .

TABLE X IV

Relay Hz Time (Seconds) Min. Max.

I FC95 50 0.578 0.6 12 60 0.5 10 0.540

The drag magnet assembly should be approximately in the middle of its travel. The drag magnet assembly is adjusted by loosening the two screws securing it to the support structure. See Figure 1. Moving the drag magnet towards the disk and shaft decreases the operating time, and moving the drag magnet away

15

www . El

ectric

alPar

tMan

uals

. com

Page 16: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

GEK-49951

from the disk and shaft increases the operating time. The screws secur ing the drag magnet assembly to the support structure must be tight before proceeding with other time checks.

Mechanical Adjustment

The disk does not have to be in the exact center of either air gap for the relay to perform correctly. Should the disk not clear all gaps, the following adjustment can be made.

1. Determine which way the disk must be aligned to clear all gap surfaces by 0.0 10 inch.

2. Remove the drag magnet assembly by loosening the two screws securing it to the support structure.

3. Loosen the upper pivot-bearing set screw ( 1/ 16 inch hex wrench) slightly, so the upper pivot can move freely. Do not remove the set screw from the support structure.

4. Loosen the jewel-bearing set screw as in Item 3. above.

5. Apply a slight downward finger pressure on the upper pivot and turn the jewel-bearing screw, from the underside of the support structure, to position the disk as determined in Item 1. above.

6. Turn the jewel-bearing screw 1/8 turn clockwise and tighten the upper pivot set screw to 2.5-3.5 inch-pounds of torque.

7. Turn the jewel-bearing screw 1/8 turn counterclockwise. This will lower the disk and shaft assembly approximately 0.005 inch and permit proper end play. The shaft must have 0.005 to 0.0 10 inch of end play.

8. Tighten the jewel-bearing set screw to 2.5-3.5 inch-pounds of torque.

9. Rotate the disk through the electromagnet gap. The disk should clear the gap surfaces by 0.0 10 inch and be within 0.005 inch flatness. If the disk is not within 0.005 inch flatness, the disk should be replaced.

10. Reinstall the drag magnet assembly and check that the disk has at least 0.0 10 inch clearance from the drag magnet assembly surfaces.

1 1. Tighten the drag magnet assembly mounting screw with 7-to- 10 inch-pounds of torque, after securely seating the assembly and positioning it according to the time test above.

HIGH-SEISMIC INSTANTANEOUS UNIT

1. Since mechanical adjustments may affect the Seismic Fragility Level, it is advised that no mechanical adjustments be made if seismic capability is of concern.

2. Both contacts should close at the same time.

16 www . El

ectric

alPar

tMan

uals

. com

Page 17: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

GEK-49951

3. The backing strip should be so formed that the forked end (front) bears against the molded strip under the armature.

4. With the armature against the pole piece, the cross member of the 11T11 spring should be in a horizontal plane and there should be at least 1/64 inch wipe on the contacts. Check this by inserting a 0.0 10 inch feeler gage between the front half of the shaded pole and the armature, with the armature held closed. Contacts should close with the feeler gage in place.

HIGH-SEISMIC TARGET AND SEAL-IN UNIT

Si nee mechani ca 1 adjustments may affect the Seismic Fragility Leve 1, it is advised that no mechanical adjustments be made if seismic capability is of concern.

Check Items 2 and 3 as described under INSTANTANEOUS UNIT.

To check the wipe of the seal-in unit, insert a 0.0 10 inch feeler gage between the plastic residual of the armature and the pole piece, with the armature held closed. Contacts should close with the feeler gage in place.

RENEWAL PARTS

It is recommended that sufficient quantities of renewal parts be kept in stock for the prompt replacement of any that are worn, broken or damaged.

When ordering renewal parts, address the nearest Sales Office of the General Electric Company. Specify the name of the part wanted, quantity required, and complete nameplate data, including the serial number, of the relay for which the part is required.

17 www . El

ectric

alPar

tMan

uals

. com

Page 18: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

GEK-49951

LIST OF FIGU RES

Figure Page

1. IFC95F Relay, Front View 19

2. IFC95F Relay, Rear View 20

3. IFC95F Internal Connections, Front View 2 1

4. 60 Hertz Time-Current Characteristics 22

5. 50 Hertz Time-Current Characteristics 23

6. External Connections 24

7. Transient Overreach Characteristics of the Hi-Seismic Instantaneous Unit 25

8. Time-current Characteristics of the Hi-Seismic Instantaneous Unit 26

9. Test Connections - CT Testing 27

10 Test Connections - Time Overcurrent Unit

1 1. Test Connections - High Seismic Instantaneous Unit

12. Test Connections - High Seismic Target and Seal-in

13. Cross Section of IFC Draw-out Case Connections

14. Outline and Panel Drilling for Semi-Flush Mounting

15. Outline and Panel Drilling for Surface Mounting

18

Unit

28

29

30

3 1

32

33

www . El

ectric

alPar

tMan

uals

. com

Page 19: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

.'

..1

'I

·� I

SEAL-•N lARGe T li.AiiP SElECTOR SCREW--�"""

SEAL-IN UN)l STATIONARY CONTACT

GEK-49951

111/*'f 0� RC l!J��'EN T 1� S.l!I!ECTORS.

TIMI: DIAl

Figure 1 (804 3006) IFC95F Relay, Removed from Case, Front View

19

UNIT

www . El

ectric

alPar

tMan

uals

. com

Page 20: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

SUPPOI'J! --­

STRUCII�

BOTTOM ---­

JEWEL BEARING

GEK-49951

Ur-MAGNET ANO TAP BLOCK ASSEMBlY TlME OVERCURRENT UNIT

Figure 2 (80430 10) IFC95F Relay, Removed from Case, Rear View

20 www . El

ectric

alPar

tMan

uals

. com

Page 21: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

TJ,P'::-FT A�JD SFAL-I�J UNIT

GEK-49951

TIME OVERCUPRENT UNIT

/��

* r 2

*=SHORT Fl NGER·

L H

r 7

INST UNIT

9

Figure 3 (0275A32 14-0) IFC95F Internal Connections, Front View

2 1

*

!0

www . El

ectric

alPar

tMan

uals

. com

Page 22: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

1000 ... 100 , .. ...

...

-

, ..

, ..

100

.. 10 TO 10 "'

Q .. z

§ 4G "' ,. � ... � 20 ..

10

I

I 1

'

I

.I

U: .I

..

.•

..

..

.I ·" .II .11 ·" ...

...

.I '

...

.01

5 I 1 I I I

\\ \\� � \

\. '\.

.5 .I .7 .1 II

4 5 I 1 I 110

� " "'" � I'

.._ '\. .._

I'-.. r- -

1'\ -

" t- -

1"-1"- -

t-

t--

TIME UNIT

4 S I 1 I I 10

GEK-49951

20 30 4G 51 II 71 totG0 -

I

10 ��9 � 7 -

6 t-t-5 UJ - 4 1/1

1- 3 ...J

1-- 2 � 0

UJ I ::;: -

I t-

2

21 )I ... 5I 10 70 1110!

MULTIPLES OF PICK UP SETTING

-

I

' I I I

I ! I I I I

I

'

Figure 4 (0 108B8966-I) 60 Hertz Time-Current Characteristics for IFC95F

22

-I ...

... 100 700 '" , ..

...

, ..

, ..

1 00 .. 10 70

10 " ..

lO

20

I

I .I

I

.7

.I

. .

.2

..

" 02

""'�

www . El

ectric

alPar

tMan

uals

. com

Page 23: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

"'

IMI .. ... 110 ... ... ...

, ..

100 .. .. " ..

Q .. z 8 .. ... "' .. 3!:

i ,. ...

• • • 1 •

S I 7 I II

. � •

2

.I

.• 1 .. • ..

.J

..

.I

...

...

.. 1

.II

... ...

. I •

.. '

II . .5 .• . 7 .1.11

' ' • ' I 7 I 110

l\ \\\ � � � �

\

1\ r- t---1:::::

\

\ " i' r-

I' r--

TIME UNIT

4 S I T I liD

GEK-49951

" • -

10 89

l.!> z -t-l r- ...... - 5 ......

-1-4 w 1./)

-1-3 _.J 2 <( -

0 I w I 2 -2 ......

70 GH 21 J1 41 5010 1 !

MULTIPLES OF PICK-UP SETTING

- � ! I !!1!11

0 0 0 0 0 8 8

Figure 5 (0 10888965-1 ) 50 Hertz Time-Current Characteristics for I FC95 F

23

I

I

I

I

... ... .. •

1 .. ... ' .. ...

l ..

' ..

.. .. • • 1

• .. ..

lO

"

.I

.I

.J

.I

..

..

..

I ... I "' ::ill ., ... •! .. ..

..

12

www . El

ectric

alPar

tMan

uals

. com

Page 24: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

NOTE: DEVICE SON IN IFC�SB ONLY.

GEK-49951

NEUTRAL BUS (IF PRESENT)

GROUND FAULT SCHEMi FOR TRANSFORMER MAH4 SECONDARY BREAKER

Figure 6 (0269A3078-0) External Connections of Four IFC Relays used for Multi- Phase and Phase-to-Ground Fault Protection of a Three- Phase Circuit

24 www . El

ectric

alPar

tMan

uals

. com

Page 25: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

� :z :;) Cl') § � i t; :z

a U.l �· � 0 -t1; w VJ

%

� Ol 10 co <(

co 0 C\J 0

� I w > 0

ffi ;:;; � �

-

GEK-49951

--(..) �Q_-=r�· -::.c::-

Xv.._. �-(1)

�"" � C.. I

::r: -rT

�� "J r " T <:) � -:;:E:Q..

\ ��::r I - - x W:z(..) Cl')--I:;:E:a_ - [\ :r -

\ l \

Cl

1� I � <( >- Cl L..J:j LJ.J -

< .....1

8 B Q.. Q..

<t <( - a: II <..!' >-.....1 § 1- ffi :z LJ.J c LJ.J a: � � 0:: a > 1-0 0.. i£ 1- � 0:: as 0::: - a � �

II II 1--Q.. <( co

0

1N3J�3d Nl H3V3��3AO

Figure 7 (0208A8694- 1) Transient Overreach Characteristics of the Hi-Seismic Instantaneous Unit

25

...... �

-a. 10

f-1?,

g

M

0

www . El

ectric

alPar

tMan

uals

. com

Page 26: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

w V)

LO 0) \0 OJ c:[ OJ 0 N 0

GEK-49951

I / ! I

I i

I _;

,f I/

J w G

I :::E >- z

.,_ �-a:: � �

/ z OVl LL.. 1- c... <( w :::;) cr (.!j � w �- v � O:c...

� "

tf J v L

I /

/

v v

L

LO IJ� Q tt\ 0 0 8

- ------------------�· ��3S Nl 3Wil d�ld

Figure 8 (0208A8695-0) Time-current Characteristics of the Hi-Seismic Instantaneous Unit

26

0

OJ

CL. � ¥

\0 u c... lL 0 V1 w .....J CL -

LO t-.....J P'' :::> ::E.

LO

www . El

ectric

alPar

tMan

uals

. com

Page 27: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

GEK-49951

REL.LlY COIL l�l Cl RC U IT

RELAY CCIL NOT IN CIRCUIT

5 !"\ r----+� RELAY TE R�11NA L S 0

5 CASE SIDE

6/

6 12XCAIIAI

OR 12XCAIIA2

12XGAIIAI

0 RELAY SlOE

CASE Sl C'E

5 6

TEST CONNECTIONS FCR TESTING GT SECONDARY USED WITH THE IFG RELAY

Figure 9 (0269A1787-1) Test Connections for Testing CT Secondary Current Used with the IFC Relay

27 www . El

ectric

alPar

tMan

uals

. com

Page 28: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

GEK-49951

TO START TIMER

VARIABLE

RES IS TOR

MIN l� r-+----'----t'----:�____.

REGOrv11'v1E N OED VOLTS l20 AT RATED FREQ I

------------a/<�--------------------�

TO STOP

T 1!\�E R TO I �DICATING

----+LIGHT WHEN �CHECKING PICKUP

RELAY � I 2 TERMINALS.---+---+---...

12XCAIIAI

( RELAY SIDE ----CASE SIDE

0 0

5

RELAY SIDE

5 CT JUMPER

TEST CONNECTIONS FOR TESTING PICKUP AND OPERATING TIMES OF THE IFC RELAY TIME OVERCURRENT UNIT

Figure 10 (0269Al789-0) Test Connections for Testing Pickup and Operating Times of the IFC Relay Time Overcurrent Unit

28 www . El

ectric

alPar

tMan

uals

. com

Page 29: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

GEK-49951

T O S TA R T T I I\� E l�

----------� .� �----�--� M I N I M U M R E C 0 1\M vl � N 0 E D V O L T S J 1 2 0 AT R AT E D F R E G . I

------ --c Y, )-------'------------___,

TO STO P T I M E R

TO I N DICAT J N G - - - -· � L I G H T W HEN

7 C H EC K I N G P I C K U P

R E L AY ----­ 2 T E R M I N A L S r----+----------r

1 2 X C A I I A I

R ELAY S I D E

- - �- - -

CAS E S I D E

0

0

0

3 4

R E LAY S I D E - - -

C AS E SI D E

0 C)

5

0 R E L AY S I D E

- - -- -

C AS E S I D E

5 C T

J U M P E R

T E S T C O N N E G T I C NS FO R T ES T I NG P IC K U P A N D

O P E R AT I N G T I M E S O F T H E i F G R E L A Y I N STA N TA N EO U S U N I T

Figure 1 1 (0269A 1788- 1) Test Connections for Testing Pickup and Operating Times of t he IFC Relay Hig h-Seismic Instantaneous Unit

29 www . El

ectric

alPar

tMan

uals

. com

Page 30: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

VA R I A B L E R E S I S T O R

GEK-49951

-�1 / t--®--7

o , c . V O LT S

REL AY T E R M I N A LS

2

I I R E L A Y ! S I D E I CASE - l S I D E

1 2 X C A I I A I -� 0 0

T E S T C O N NEC TI O NS F O R T E S T I N G A N D S E A L I N U N I T U S E D W I T H

R E L AY

T H E T A R G E T T H E I F C

Figure 12 (0269A 1790-0) Test Connections :or Testing the High Seismic Target and Seal-in Unit Used w1th the IFC Relay

30

.�.

··.""

www . El

ectric

alPar

tMan

uals

. com

Page 31: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

GEK-49951

CONNECTI ON PLUG CONTACT F I N G ERS ORAWOUT E L EMENT SUPPORT STRUCTURE

Figure 13 (80427 15) Cross Section of IFC Draw-out Case Showing Shorting Bar

3 1 www . El

ectric

alPar

tMan

uals

. com

Page 32: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

1------ 6.062 -l I IS4NM I 1- -- r;;.====:::::$===:::::'1

I RE L AY 0

�376 1 187MM 1----- _ t-- _

L () 1- 3.0 31 --1

7 7MM

F R O N T V I EW

GEK-49951

,, ,,

S E E V I E W D

<D

5.562 _ __. 1 4 1 MM

2.7 6 1 7 1MM

R EA R V I E W

<D

5.1 2 4

-- -T I

j 6J2 4 1 56 MM

S T U D N U MB E R I NG

l tl.31 2 33MM ----

7, 000 ---1 --

- 1 30 MM 1 78 M M I 2.5 62

, .1 8 8 H LS . 5 M M

/ - '\;_....- S EE I

MOU N T I N<3 SUr-FA C E

' ' - � 1 J 3,3 75 ! T

1 7 1 M� Ci_ 79MM

C O N N EC T I O NS l' -72.MM 5.6 88 i 0-32 SC R EW S - �

E X TE RNAL L - - 2.844-j j Sl D �--- _y �-� 1 44�M

S EMI - F LUSH MOU N Tl NG P A N E L QBJ k-_I, I NG S H � I - F �_l.!_�H MOU_tiTI NG

WASH E R LOC KWAS H E R 8- 32 SC F\ EW �-N:_:;UT

V l E W "A "

# I O X I / 2 T Y P E B T

T H R E A D CU T T I N G -�

T I E SU P P O RT O R T I E A N C H O R

- C A B L E T I E

C A B L ES 11 I I

HD W.- 0 257A 8 549 G-1 SC F\ E W V I E W 0

Figure 14 (0257A8452- 3 Sheet 1) Outline and Panel Drilling for Semi-Flush Mounting of IFC95 Relay

32 www . El

ectric

alPar

tMan

uals

. com

Page 33: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

GEK-49951

�- 6.062 - -- -l I 154HM I '

1--- 1 4 1 M M ---! : 5 5 6 2

0 6 6 2 3. 7 8 M M

<D I a5f I I 1.2.7 8 1 __

6. 1 7. 3 7 G I

1 8 7 M M - - - --t -<t_ - - - - l 1_ -- t 7 1 M M

�� - - -------z-IOIOIO !dto� 2 4 H M - 1 5 6 j L 3.6 8 8

---

I ==· ll!::::=: � _TM_ - --

lsloi<Diolo o o I : 1 -��

CD i <D F RO N T V I EW

'---- . 7.5 6 3_�� , - 1 9 2HM

E XT E R NAL-- -.,==-----, CO NN E C T I O NS ­I O -Z2 SC REWS

MOU N Tl NG ---..� S U R FACE

S i D E V I E W (REC S U RFAC E M T'G FO R

) -��tTHK. PAN E LS A N D ABO V E

REAR V I EW S T U D NUMBE R I NG

OVE R S I 2 E WAS H E RS WAS H ER

S - 3 6 SC R E W

1-1'---���.) N U T

L R E HOV � K N O C K OU T

E N L A R G E D V I E W "e ''

H D W. 0 2 5 7 A 8 5 4 9 G-2

/ � )·2 1 9 H OLE S l � SHH

1- .4 6 9 2.3 7 '5 1 ! 1 2 H H G I M H (; I .750

t 't_ 1 9 H H 4.7so -0 0 0 a o o e- - -� 1 2 1 ��H -110 0 G Q _]

j - . 6 25 . 6 2 5 � 1 6 M M 1 6 M M . . ! 56

H OU N T 1 N G S U R FAC E \

WAS H E R

R E M OV E K N OC K O U T TY P I C A L -- . I-4MN FOR-31 2 H O L ES E N LA RG E D V I E W '' c "

8MM H D W · 0 2 5 7A 8 54 9 G-2 PA N E L D RI LLING

( �b�Efbul��-�b�Js)

Figure 15 (0257A8452-3 Sheet 2 ) Outline and Panel Drilling for Surface Mounting of IFC95A Relay

33 www . El

ectric

alPar

tMan

uals

. com

Page 34: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

NOTES www .

Elec

tricalP

artM

anua

ls . c

om

Page 35: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

NOTES www .

Elec

tricalP

artM

anua

ls . c

om

Page 36: GEK-49951A . com . ElectricalPartManualsGEK-49951 The draw-out connection/test system for the C1 case, shown in Figure 13, has provisions for 14 connection points, and a visible CT

3-80 9· 8 7

G EN E RAL ELECTR IC COMPANY POW E R SYSTEMS MANAG EMENT BUS I N ESS DEPT.

MALVERN, PA 1 9355

GE N ER AL ELECT RIC