20
GCU compact Operating manual Types GCU compact 315 GCU compact 320 GCU compact 515 GCU compact 520 GCU compact 524 GCU compact 528 GCU compact 315 Biv GCU compact 320 Biv GCU compact 515 Biv GCU compact 520 Biv GCU compact 524 Biv GCU compact 528 Biv EN Edition 9 7 0 /201 For the operator

GCU compact - Daikin · GCU compact Operating manual Types ... GCU compact 528 Biv EN Edition 9 7 0 /201 For the operator. ... 6 BH GCU compact II - 09/2017

  • Upload
    buihanh

  • View
    230

  • Download
    0

Embed Size (px)

Citation preview

Page 1: GCU compact - Daikin · GCU compact Operating manual Types ... GCU compact 528 Biv EN Edition 9 7 0 /201 For the operator. ... 6 BH GCU compact II - 09/2017

GCU compact

Operating manual

TypesGCU compact 315 GCU compact 320 GCU compact 515 GCU compact 520 GCU compact 524 GCU compact 528

GCU compact 315 Biv GCU compact 320 Biv GCU compact 515 Biv GCU compact 520 Biv GCU compact 524 Biv GCU compact 528 Biv

ENEdition 9 7 0 /201

For the operator

Page 2: GCU compact - Daikin · GCU compact Operating manual Types ... GCU compact 528 Biv EN Edition 9 7 0 /201 For the operator. ... 6 BH GCU compact II - 09/2017

2 BH GCU compact II - 09/2017

1 x Guarantee, plant data1 Guarantee, plant data

1.1 Guarantee conditionsThe legal guarantee conditions fundamentally apply. Our war-ranty conditions beyond that can be found online on your sales presentative's webpage.

Regular inspection and maintenance is essential to sustainedly operate your heating system reliably and effectively

To maintain your full guarantee claim, you are obliged to use the device/heating system solely for the intended purpose and at re-gular intervals perform the inspection and maintenance work specified in the technical documents supplied with the product. All maintenance and repair work on the device/heating system must be logged comprehensibly in this operating manual.

1.2 System data

1.2.1 Operator

1.2.2 System1.2.3 Further details on the heating systemType of heating surfaces:

Solar system installed:

Other remarks about heating systems:

Other remarks on heating system:

Name:Company:Street & house number:Postal code & town:Phone:

Fig. 1-1 Type plate (above) and setting sticker (below)

Type of device and setting1 - Condensing boiler type2 - Rated thermal output P= kW3 - Serial number (Mfg no.)4 - Gas type5 - Burner loading min. kW6 - Burner loading max. kW

With changed base setting:7 - Gas type8 - Burner loading min. kW9 - Burner loading max. kWDate of first start-up

All maintenance and repair work on the burner and hea-ting boiler must be performed by certified personnel and documented in the following records. An unbroken record of compliance with the maintenance and inspec-tion work stipulated by ROTEX is a prerequisite for any guarantee claim within the guarantee period and any possible ex-gratia payment by the manufacturer.

Radiators Floor heating Other: _________________________________

Yes NoManufacturer: _________________________________Type of collector: _________________________________Number of collec-tors:

_________________________________

Total collector surface area (m2): ____________________System: Drainback (non-pressurised)

Pressurized system

Yes NoIf yes, which: _________________________________(Heat pump, wood boiler,...)

_________________________________

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

XXXXXXXXXXXXXX

XXXXXXXXXXXXXX

3.

4.

1.

7.

6.5.

8. 9.

Made in Germany

GCU compact Brennwertkessel, Condensing boiler, Chaudière à condensation

kg

2.

Page 3: GCU compact - Daikin · GCU compact Operating manual Types ... GCU compact 528 Biv EN Edition 9 7 0 /201 For the operator. ... 6 BH GCU compact II - 09/2017

BH GCU compact II - 09/2017 3

2 x Certificates2 Certificates1st maintenance

2nd maintenance

Activities Yes No Comments1. All inspection and cleaning tasks completed in accordance with

inspection and maintenance instructions for ROTEX Gas Combi Unit compact?

2. System water pressure checked? bar

3. Pre-pressure measurement performed with gas valve closed (burner off): mbar

4. Burner setting checked? Burner loading

before correction after correction5. Burner setting corrected? Min. Max. Min. Max.

– Pre-pressure at gas valve: mbar mbar mbar mbar

– CO2 in flue gas pipe: % % % %

– O2 in flue gas pipe: % % % %

– Temperature in flue gas pipe: °C °C °C °C

– CO2 in supply air (annular gap): % % % %

– Temperature of intake air: °C °C °C °C

6. Any faults detected? Fault rectified? (See repair/service log page _____)

Faults detected:

7. Operator informed of existing faults?

8. Control settings changes? See repair/service log page _____

Company stamp / company address Name of technician in capitals Date Signature of technician

Activities Yes No Comments1. All inspection and cleaning tasks completed in accordance with

inspection and maintenance instructions for ROTEX Gas Combi Unit compact?

2. System water pressure checked? bar

3. Pre-pressure measurement performed with gas valve closed (burner off): mbar

4. Burner setting checked? Burner loading

before correction after correction5. Burner setting corrected? Min. Max. Min. Max.

– Pre-pressure at gas valve: mbar mbar mbar mbar

– CO2 in flue gas pipe: % % % %

– O2 in flue gas pipe: % % % %

– Temperature in flue gas pipe: °C °C °C °C

– CO2 in supply air (annular gap): % % % %

– Temperature of intake air: °C °C °C °C

6. Any faults detected? Fault rectified? (See repair/service log page _____)

Faults detected:

7. Operator informed of existing faults?

8. Control settings changes? See repair/service log page _____

Company stamp / company address Name of technician in capitals Date Signature of technician

Page 4: GCU compact - Daikin · GCU compact Operating manual Types ... GCU compact 528 Biv EN Edition 9 7 0 /201 For the operator. ... 6 BH GCU compact II - 09/2017

4 BH GCU compact II - 09/2017

2 x Certificates3rd maintenance

4th maintenance

Activities Yes No Comments1. All inspection and cleaning tasks completed in accordance with

inspection and maintenance instructions for ROTEX Gas Combi Unit compact?

2. System water pressure checked? bar

3. Pre-pressure measurement performed with gas valve closed (burner off): mbar

4. Burner setting checked? Burner loading

before correction after correction5. Burner setting corrected? Min. Max. Min. Max.

– Pre-pressure at gas valve: mbar mbar mbar mbar

– CO2 in flue gas pipe: % % % %

– O2 in flue gas pipe: % % % %

– Temperature in flue gas pipe: °C °C °C °C

– CO2 in supply air (annular gap): % % % %

– Temperature of intake air: °C °C °C °C

6. Any faults detected? Fault rectified? (See repair/service log page _____)

Faults detected:

7. Operator informed of existing faults?

8. Control settings changes? See repair/service log page _____

Company stamp / company address Name of technician in capitals Date Signature of technician

Activities Yes No Comments1. All inspection and cleaning tasks completed in accordance with

inspection and maintenance instructions for ROTEX Gas Combi Unit compact?

2. System water pressure checked? bar

3. Pre-pressure measurement performed with gas valve closed (burner off): mbar

4. Burner setting checked? Burner loading

before correction after correction5. Burner setting corrected? Min. Max. Min. Max.

– Pre-pressure at gas valve: mbar mbar mbar mbar

– CO2 in flue gas pipe: % % % %

– O2 in flue gas pipe: % % % %

– Temperature in flue gas pipe: °C °C °C °C

– CO2 in supply air (annular gap): % % % %

– Temperature of intake air: °C °C °C °C

6. Any faults detected? Fault rectified? (See repair/service log page _____)

Faults detected:

7. Operator informed of existing faults?

8. Control settings changes? See repair/service log page _____

Company stamp / company address Name of technician in capitals Date Signature of technician

Page 5: GCU compact - Daikin · GCU compact Operating manual Types ... GCU compact 528 Biv EN Edition 9 7 0 /201 For the operator. ... 6 BH GCU compact II - 09/2017

BH GCU compact II - 09/2017 5

2 x Certificates5th maintenance

6th maintenance

Activities Yes No Comments1. All inspection and cleaning tasks completed in accordance with

inspection and maintenance instructions for ROTEX Gas Combi Unit compact?

2. System water pressure checked? bar

3. Pre-pressure measurement performed with gas valve closed (burner off): mbar

4. Burner setting checked? Burner loading

before correction after correction5. Burner setting corrected? Min. Max. Min. Max.

– Pre-pressure at gas valve: mbar mbar mbar mbar

– CO2 in flue gas pipe: % % % %

– O2 in flue gas pipe: % % % %

– Temperature in flue gas pipe: °C °C °C °C

– CO2 in supply air (annular gap): % % % %

– Temperature of intake air: °C °C °C °C

6. Any faults detected? Fault rectified? (See repair/service log page _____)

Faults detected:

7. Operator informed of existing faults?

8. Control settings changes? See repair/service log page _____

Company stamp / company address Name of technician in capitals Date Signature of technician

Activities Yes No Comments1. All inspection and cleaning tasks completed in accordance with

inspection and maintenance instructions for ROTEX Gas Combi Unit compact?

2. System water pressure checked? bar

3. Pre-pressure measurement performed with gas valve closed (burner off): mbar

4. Burner setting checked? Burner loading

before correction after correction5. Burner setting corrected? Min. Max. Min. Max.

– Pre-pressure at gas valve: mbar mbar mbar mbar

– CO2 in flue gas pipe: % % % %

– O2 in flue gas pipe: % % % %

– Temperature in flue gas pipe: °C °C °C °C

– CO2 in supply air (annular gap): % % % %

– Temperature of intake air: °C °C °C °C

6. Any faults detected? Fault rectified? (See repair/service log page _____)

Faults detected:

7. Operator informed of existing faults?

8. Control settings changes? See repair/service log page _____

Company stamp / company address Name of technician in capitals Date Signature of technician

Page 6: GCU compact - Daikin · GCU compact Operating manual Types ... GCU compact 528 Biv EN Edition 9 7 0 /201 For the operator. ... 6 BH GCU compact II - 09/2017

6 BH GCU compact II - 09/2017

2 x Certificates7th maintenance

8th maintenance

Activities Yes No Comments1. All inspection and cleaning tasks completed in accordance with

inspection and maintenance instructions for ROTEX Gas Combi Unit compact?

2. System water pressure checked? bar

3. Pre-pressure measurement performed with gas valve closed (burner off): mbar

4. Burner setting checked? Burner loading

before correction after correction5. Burner setting corrected? Min. Max. Min. Max.

– Pre-pressure at gas valve: mbar mbar mbar mbar

– CO2 in flue gas pipe: % % % %

– O2 in flue gas pipe: % % % %

– Temperature in flue gas pipe: °C °C °C °C

– CO2 in supply air (annular gap): % % % %

– Temperature of intake air: °C °C °C °C

6. Any faults detected? Fault rectified? (See repair/service log page _____)

Faults detected:

7. Operator informed of existing faults?

8. Control settings changes? See repair/service log page _____

Company stamp / company address Name of technician in capitals Date Signature of technician

Activities Yes No Comments1. All inspection and cleaning tasks completed in accordance with

inspection and maintenance instructions for ROTEX Gas Combi Unit compact?

2. System water pressure checked? bar

3. Pre-pressure measurement performed with gas valve closed (burner off): mbar

4. Burner setting checked? Burner loading

before correction after correction5. Burner setting corrected? Min. Max. Min. Max.

– Pre-pressure at gas valve: mbar mbar mbar mbar

– CO2 in flue gas pipe: % % % %

– O2 in flue gas pipe: % % % %

– Temperature in flue gas pipe: °C °C °C °C

– CO2 in supply air (annular gap): % % % %

– Temperature of intake air: °C °C °C °C

6. Any faults detected? Fault rectified? (See repair/service log page _____)

Faults detected:

7. Operator informed of existing faults?

8. Control settings changes? See repair/service log page _____

Company stamp / company address Name of technician in capitals Date Signature of technician

Page 7: GCU compact - Daikin · GCU compact Operating manual Types ... GCU compact 528 Biv EN Edition 9 7 0 /201 For the operator. ... 6 BH GCU compact II - 09/2017

BH GCU compact II - 09/2017 7

2 x Certificates9th maintenance

10th maintenance

Activities Yes No Comments1. All inspection and cleaning tasks completed in accordance with

inspection and maintenance instructions for ROTEX Gas Combi Unit compact?

2. System water pressure checked? bar

3. Pre-pressure measurement performed with gas valve closed (burner off): mbar

4. Burner setting checked? Burner loading

before correction after correction5. Burner setting corrected? Min. Max. Min. Max.

– Pre-pressure at gas valve: mbar mbar mbar mbar

– CO2 in flue gas pipe: % % % %

– O2 in flue gas pipe: % % % %

– Temperature in flue gas pipe: °C °C °C °C

– CO2 in supply air (annular gap): % % % %

– Temperature of intake air: °C °C °C °C

6. Any faults detected? Fault rectified? (See repair/service log page _____)

Faults detected:

7. Operator informed of existing faults?

8. Control settings changes? See repair/service log page _____

Company stamp / company address Name of technician in capitals Date Signature of technician

Activities Yes No Comments1. All inspection and cleaning tasks completed in accordance with

inspection and maintenance instructions for ROTEX Gas Combi Unit compact?

2. System water pressure checked? bar

3. Pre-pressure measurement performed with gas valve closed (burner off): mbar

4. Burner setting checked? Burner loading

before correction after correction5. Burner setting corrected? Min. Max. Min. Max.

– Pre-pressure at gas valve: mbar mbar mbar mbar

– CO2 in flue gas pipe: % % % %

– O2 in flue gas pipe: % % % %

– Temperature in flue gas pipe: °C °C °C °C

– CO2 in supply air (annular gap): % % % %

– Temperature of intake air: °C °C °C °C

6. Any faults detected? Fault rectified? (See repair/service log page _____)

Faults detected:

7. Operator informed of existing faults?

8. Control settings changes? See repair/service log page _____

Company stamp / company address Name of technician in capitals Date Signature of technician

Page 8: GCU compact - Daikin · GCU compact Operating manual Types ... GCU compact 528 Biv EN Edition 9 7 0 /201 For the operator. ... 6 BH GCU compact II - 09/2017

8 BH GCU compact II - 09/2017

2 x Certificates11th maintenance

12th maintenance

Activities Yes No Comments1. All inspection and cleaning tasks completed in accordance with

inspection and maintenance instructions for ROTEX Gas Combi Unit compact?

2. System water pressure checked? bar

3. Pre-pressure measurement performed with gas valve closed (burner off): mbar

4. Burner setting checked? Burner loading

before correction after correction5. Burner setting corrected? Min. Max. Min. Max.

– Pre-pressure at gas valve: mbar mbar mbar mbar

– CO2 in flue gas pipe: % % % %

– O2 in flue gas pipe: % % % %

– Temperature in flue gas pipe: °C °C °C °C

– CO2 in supply air (annular gap): % % % %

– Temperature of intake air: °C °C °C °C

6. Any faults detected? Fault rectified? (See repair/service log page _____)

Faults detected:

7. Operator informed of existing faults?

8. Control settings changes? See repair/service log page _____

Company stamp / company address Name of technician in capitals Date Signature of technician

Activities Yes No Comments1. All inspection and cleaning tasks completed in accordance with

inspection and maintenance instructions for ROTEX Gas Combi Unit compact?

2. System water pressure checked? bar

3. Pre-pressure measurement performed with gas valve closed (burner off): mbar

4. Burner setting checked? Burner loading

before correction after correction5. Burner setting corrected? Min. Max. Min. Max.

– Pre-pressure at gas valve: mbar mbar mbar mbar

– CO2 in flue gas pipe: % % % %

– O2 in flue gas pipe: % % % %

– Temperature in flue gas pipe: °C °C °C °C

– CO2 in supply air (annular gap): % % % %

– Temperature of intake air: °C °C °C °C

6. Any faults detected? Fault rectified? (See repair/service log page _____)

Faults detected:

7. Operator informed of existing faults?

8. Control settings changes? See repair/service log page _____

Company stamp / company address Name of technician in capitals Date Signature of technician

Page 9: GCU compact - Daikin · GCU compact Operating manual Types ... GCU compact 528 Biv EN Edition 9 7 0 /201 For the operator. ... 6 BH GCU compact II - 09/2017

2 x Certificates13th maintenance

14th maintenance

Activities Yes No Comments1. All inspection and cleaning tasks completed in accordance with

inspection and maintenance instructions for ROTEX Gas Combi Unit compact?

2. System water pressure checked? bar

3. Pre-pressure measurement performed with gas valve closed (burner off): mbar

4. Burner setting checked? Burner loading

before correction after correction5. Burner setting corrected? Min. Max. Min. Max.

– Pre-pressure at gas valve: mbar mbar mbar mbar

– CO2 in flue gas pipe: % % % %

– O2 in flue gas pipe: % % % %

– Temperature in flue gas pipe: °C °C °C °C

– CO2 in supply air (annular gap): % % % %

– Temperature of intake air: °C °C °C °C

6. Any faults detected? Fault rectified? (See repair/service log page _____)

Faults detected:

7. Operator informed of existing faults?

8. Control settings changes? See repair/service log page _____

Company stamp / company address Name of technician in capitals Date Signature of technician

Activities Yes No Comments1. All inspection and cleaning tasks completed in accordance with

inspection and maintenance instructions for ROTEX Gas Combi Unit compact?

2. System water pressure checked? bar

3. Pre-pressure measurement performed with gas valve closed (burner off): mbar

4. Burner setting checked? Burner loading

before correction after correction5. Burner setting corrected? Min. Max. Min. Max.

– Pre-pressure at gas valve: mbar mbar mbar mbar

– CO2 in flue gas pipe: % % % %

– O2 in flue gas pipe: % % % %

– Temperature in flue gas pipe: °C °C °C °C

– CO2 in supply air (annular gap): % % % %

– Temperature of intake air: °C °C °C °C

6. Any faults detected? Fault rectified? (See repair/service log page _____)

Faults detected:

7. Operator informed of existing faults?

8. Control settings changes? See repair/service log page _____

Company stamp / company address Name of technician in capitals Date Signature of technician

BH GCU compact II - 09/2017 9

Page 10: GCU compact - Daikin · GCU compact Operating manual Types ... GCU compact 528 Biv EN Edition 9 7 0 /201 For the operator. ... 6 BH GCU compact II - 09/2017

2 x Certificates15th maintenance

16th maintenance

Activities Yes No Comments1. All inspection and cleaning tasks completed in accordance with

inspection and maintenance instructions for ROTEX Gas Combi Unit compact?

2. System water pressure checked? bar

3. Pre-pressure measurement performed with gas valve closed (burner off): mbar

4. Burner setting checked? Burner loading

before correction after correction5. Burner setting corrected? Min. Max. Min. Max.

– Pre-pressure at gas valve: mbar mbar mbar mbar

– CO2 in flue gas pipe: % % % %

– O2 in flue gas pipe: % % % %

– Temperature in flue gas pipe: °C °C °C °C

– CO2 in supply air (annular gap): % % % %

– Temperature of intake air: °C °C °C °C

6. Any faults detected? Fault rectified? (See repair/service log page _____)

Faults detected:

7. Operator informed of existing faults?

8. Control settings changes? See repair/service log page _____

Company stamp / company address Name of technician in capitals Date Signature of technician

Activities Yes No Comments1. All inspection and cleaning tasks completed in accordance with

inspection and maintenance instructions for ROTEX Gas Combi Unit compact?

2. System water pressure checked? bar

3. Pre-pressure measurement performed with gas valve closed (burner off): mbar

4. Burner setting checked? Burner loading

before correction after correction5. Burner setting corrected? Min. Max. Min. Max.

– Pre-pressure at gas valve: mbar mbar mbar mbar

– CO2 in flue gas pipe: % % % %

– O2 in flue gas pipe: % % % %

– Temperature in flue gas pipe: °C °C °C °C

– CO2 in supply air (annular gap): % % % %

– Temperature of intake air: °C °C °C °C

6. Any faults detected? Fault rectified? (See repair/service log page _____)

Faults detected:

7. Operator informed of existing faults?

8. Control settings changes? See repair/service log page _____

Company stamp / company address Name of technician in capitals Date Signature of technician

10 BH GCU compact II - 09/2017

Page 11: GCU compact - Daikin · GCU compact Operating manual Types ... GCU compact 528 Biv EN Edition 9 7 0 /201 For the operator. ... 6 BH GCU compact II - 09/2017

2 x Certificates17th maintenance

18th maintenance

Activities Yes No Comments1. All inspection and cleaning tasks completed in accordance with

inspection and maintenance instructions for ROTEX Gas Combi Unit compact?

2. System water pressure checked? bar

3. Pre-pressure measurement performed with gas valve closed (burner off): mbar

4. Burner setting checked? Burner loading

before correction after correction5. Burner setting corrected? Min. Max. Min. Max.

– Pre-pressure at gas valve: mbar mbar mbar mbar

– CO2 in flue gas pipe: % % % %

– O2 in flue gas pipe: % % % %

– Temperature in flue gas pipe: °C °C °C °C

– CO2 in supply air (annular gap): % % % %

– Temperature of intake air: °C °C °C °C

6. Any faults detected? Fault rectified? (See repair/service log page _____)

Faults detected:

7. Operator informed of existing faults?

8. Control settings changes? See repair/service log page _____

Company stamp / company address Name of technician in capitals Date Signature of technician

Activities Yes No Comments1. All inspection and cleaning tasks completed in accordance with

inspection and maintenance instructions for ROTEX Gas Combi Unit compact?

2. System water pressure checked? bar

3. Pre-pressure measurement performed with gas valve closed (burner off): mbar

4. Burner setting checked? Burner loading

before correction after correction5. Burner setting corrected? Min. Max. Min. Max.

– Pre-pressure at gas valve: mbar mbar mbar mbar

– CO2 in flue gas pipe: % % % %

– O2 in flue gas pipe: % % % %

– Temperature in flue gas pipe: °C °C °C °C

– CO2 in supply air (annular gap): % % % %

– Temperature of intake air: °C °C °C °C

6. Any faults detected? Fault rectified? (See repair/service log page _____)

Faults detected:

7. Operator informed of existing faults?

8. Control settings changes? See repair/service log page _____

Company stamp / company address Name of technician in capitals Date Signature of technician

BH GCU compact II - 09/2017 11

Page 12: GCU compact - Daikin · GCU compact Operating manual Types ... GCU compact 528 Biv EN Edition 9 7 0 /201 For the operator. ... 6 BH GCU compact II - 09/2017

3 x Repair/service records3 Repair/service records

Repair/service recordDescription and reason for work on device/heating system - subsequent function check per-

formed? Please fill in!Date/signature of technician

12 BH GCU compact II - 09/2017

Page 13: GCU compact - Daikin · GCU compact Operating manual Types ... GCU compact 528 Biv EN Edition 9 7 0 /201 For the operator. ... 6 BH GCU compact II - 09/2017

3 x Repair/service records

Repair/service recordDescription and reason for work on device/heating system - subsequent function check per-

formed? Please fill in!Date/signature of technician

BH GCU compact II - 09/2017 13

Page 14: GCU compact - Daikin · GCU compact Operating manual Types ... GCU compact 528 Biv EN Edition 9 7 0 /201 For the operator. ... 6 BH GCU compact II - 09/2017

14 BH GCU compact II - 09/2017

3 x Repair/service records

Repair/service recordDescription and reason for work on device/heating system - subsequent function check per-

formed? Please fill in!Date/signature of technician

Page 15: GCU compact - Daikin · GCU compact Operating manual Types ... GCU compact 528 Biv EN Edition 9 7 0 /201 For the operator. ... 6 BH GCU compact II - 09/2017

3 x Repair/service records

Repair/service recordDescription and reason for work on device/heating system - subsequent function check per-

formed? Please fill in!Date/signature of technician

BH GCU compact II - 09/2017 15

Page 16: GCU compact - Daikin · GCU compact Operating manual Types ... GCU compact 528 Biv EN Edition 9 7 0 /201 For the operator. ... 6 BH GCU compact II - 09/2017

16 BH GCU compact II - 09/2017

3 x Repair/service records

Repair/service recordDescription and reason for work on device/heating system - subsequent function check per-

formed? Please fill in!Date/signature of technician

Page 17: GCU compact - Daikin · GCU compact Operating manual Types ... GCU compact 528 Biv EN Edition 9 7 0 /201 For the operator. ... 6 BH GCU compact II - 09/2017

3 x Repair/service records

Repair/service recordDescription and reason for work on device/heating system - subsequent function check per-

formed? Please fill in!Date/signature of technician

BH GCU compact II - 09/2017 17

Page 18: GCU compact - Daikin · GCU compact Operating manual Types ... GCU compact 528 Biv EN Edition 9 7 0 /201 For the operator. ... 6 BH GCU compact II - 09/2017

18 BH GCU compact II - 09/2017

3 x Repair/service records

Repair/service recordDescription and reason for work on device/heating system - subsequent function check per-

formed? Please fill in!Date/signature of technician

Page 19: GCU compact - Daikin · GCU compact Operating manual Types ... GCU compact 528 Biv EN Edition 9 7 0 /201 For the operator. ... 6 BH GCU compact II - 09/2017

BH GCU compact II - 09/2017 19

3 x Repair/service records

Repair/service recordDescription and reason for work on device/heating system - subsequent function check per-

formed? Please fill in!Date/signature of technician

Page 20: GCU compact - Daikin · GCU compact Operating manual Types ... GCU compact 528 Biv EN Edition 9 7 0 /201 For the operator. ... 6 BH GCU compact II - 09/2017

www.rotex-heating.comwww.daikineurope.com