115
Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to Documentation Evaluation Committee Comments 1 Name of Manufacturer 2 Country of Origin 3 Reference Manufacturing Standards 4 Rated Voltage (Uo/U) kV 0.6/1 5 Clamp Bushing Material Weather and UV resistant Elastomer (EPDM) 6 Clamp Body Material Hot Galvanized Steel 7 Clamp Butterfly End Nut Material (Die Cast Wing Nut) Hot Galvanized Steel 8 Design Suspension Clamp for Four Core Cable 9 Phase Conductor Cross Sectional Area mm 2 50 10 Clamp Breaking Load KN 7.5 11 Bundle Diameter mm 26 - 30 12 Hole Diameter mm 25 13 Attached Drawing Drawing No. ABS_50 Technical Guarantees No. ABS_50 Suspension Clamp for ABC Aluminium Cable 4*50 mm 2 Tenderer’s Signature : ……………………..… Date: ……………………………… Studies and Documentation Branch 1/1

Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

  • Upload
    docong

  • View
    226

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

4 Rated Voltage (Uo/U) kV 0.6/1

5 Clamp Bushing Material

Weather and UV resistant Elastomer

(EPDM)

6 Clamp Body MaterialHot Galvanized

Steel

7Clamp Butterfly End Nut Material (Die Cast Wing Nut)

Hot Galvanized Steel

8 DesignSuspension

Clamp for Four Core Cable

9Phase Conductor Cross Sectional Area mm2 50

10 Clamp Breaking Load KN 7.5

11 Bundle Diameter mm 26 - 30

12 Hole Diameter mm 25

13 Attached DrawingDrawing No.

ABS_50

Technical Guarantees No. ABS_50

Suspension Clamp for ABC Aluminium Cable 4*50 mm2

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch

1/1

Page 2: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Page 3: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered DataNotes, Remarks

, Ref to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3 Standards

4 Description

Buckle to hold wrapped band

for cable bundling

5 Construction

with teeth and ears provide for

maximum clamping strength

6 Material201 Stainless

Steel

7 Width mm 12.7

8 Attached DrawingDrawing No

STB_254

Tenderer’s Signature : ……………………..… Date: ………………………………

Technical Guarantees No. STB_254

Stainless Steel Ear-Lokt Buckle

Studies and Documentation Branch1/1

Page 4: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to
Page 5: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered DataNotes, Remarks

, Ref to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3 Standards

4 Descriptionfor cable bundling

5 Material201 Stainless

Steel

6 Width mm 12.7

7 Thickness mm 0.76

8 Length m 30

9 Attached DrawingDrawing No

STB_204

Tenderer’s Signature : ……………………..… Date: ………………………………

Technical Guarantees No. STB_204

Stainless Steel Band

Studies and Documentation Branch1/1

Page 6: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to
Page 7: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered DataNotes, Remarks

, Ref to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3 Standards ANSI

4 Material Porcelain

5 Creepage distance mm 57

6 Dimensions as Drawing

7 Mechnical failing load kN 89

8 Transverse holes (Slots) each 2

a) Dry kv 35

b) Wet kv 18

10 Attached DrawingDrawing No

SSI_01

Technical Guarantees No. SSI_01

Stay Strain Insulator

Tenderer’s Signature : ……………………..… Date: ………………………………

Power frequency flashover voltage

9

Studies and Documentation Branch1/1

Page 8: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to
Page 9: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3 Design Standards BS

4 Test Standards IEC

5.1 a) Shackle Insulator Porcelain

5.2 b) U - BracketHot-Dip

Galvanized Steel

5.3 c) NailHot-Dip

Galvanized Steel

5.4 d) Buckle Copper Plated

5.4e) Steel Bolt with Nut and Washers (for Connectting with the Pole)

Hot Galvanized 5/8"

6 Dimensions As Drawing

7 Insulator Mechanical Failing Load KN 13

8 Bracket Ultimate Tensile Strength KN 20

9.1 a) Dry kV 25

9.2 b) Wet kV 12

10 Accessories U - Bracket ,

Nail & Buckle , Steel Bolt

11 Attached DrawingDrawing No

SPI_01

Technical Guarantees No. SPI_01

Low Tension Shackle Porcelain Insulator for Earth line

5- Material

9- Insulator Power Frequency withstand Voltage (1min)

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch

1/1

Page 10: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

H D d d1 R76 89 48 17.5 10

Page 11: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered DataNotes, Remarks

, Ref to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3 Description Stay Rod

4 Rod and Accessories MaterialHot Dip

Galvanized

5 Rod Diameter mm 16

6 Rod Total Length mm 1400

a) first SideWelded with Steel Angle

b) Another Side

made into a round

eye with best quality welding

8 Round eye Inner Diameter mm 25

9 Steel Angle Length mm 150

10 Steel Angle Size mm 40x40x4

11 Another Dimensions as drawing

12 Attached DrawingDrawing No.

SE_16

Technical Guarantees No. SE_16

Stay Electrode, 16 mm

Tenderer’s Signature : ……………………..… Date: ………………………………

7

Stay Rod Construction

Studies and Documentation Branch1/1

Page 12: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to
Page 13: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered DataNotes, Remarks

, Ref to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3 Material Concrete B300

4 Dimensions as Drawing

5 Attached DrawingDrawing No

SCB_300

Technical Guarantees No. SCB_300

Stay Concrete Base

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch1/1

Page 14: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to
Page 15: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3 Design StandardsIEC 61109 , IEC 60815

4 Nominal System Voltage kV 24

5 Type Pin Type

6 Insulating Material Composite

Polymer

7 Housing Silicon

8 Metal PartsHot Dip

Galvanized

9 Number of Sheds

10 Total High mm

11 Shed Diameter mm

12 Min. Creepage Distance mm 1050

13 Cantilever Strength KN 12.5

14 Weight Kg

15.1 a) Dry kV 125

15.2 b) Wet kV 95

15.3 c) Impulse +VE & -VE kV

Technical Guarantees No. PPYI_1050

22kv Overhead Line Pin Type Polymer Insulator with Creepage Distance 1050 mm

15- Power Frequency withstand Voltage (1 min)

Studies and Documentation Branch

1/2

Page 16: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

Technical Guarantees No. PPYI_1050

22kv Overhead Line Pin Type Polymer Insulator with Creepage Distance 1050 mm

16.1 a) Power Frequency (Dry) kV 140

16.2 b )Power Frequency (Wet) kV 110

16.3 c) Impulse +VE & -VE kV r+220/-245

17.1 Pin Diameter (stud) mm 25

17.2 Pin AccessoriesNut and Washers

17.3 Pin Toothed Part Length mm 120

18 Attached DrawingDrawing No. PPYI_1050

16- Flashover Voltage

17- Fittings

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch

2/2

Page 17: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Page 18: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3 Design StandardsIEC 61109 , IEC 60815

4 Nominal System Voltage kV 24

5 Type Pin Type

6 Insulating Material Composite

Polymer

7 Housing Silicon

8 Metal PartsHot Dip

Galvanized

9 Number of Sheds

10 Total High mm

11 Shed Diameter mm

12 Min. Creepage Distance mm 800

13 Cantilever Strength KN 12.5

14 Weight Kg

15.1 a) Dry kV 125

15.2 b) Wet kV 95

15.3 c) Impulse +VE & -VE kV

Technical Guarantees No. PPYI_800

22kv Overhead Line Pin Type Polymer Insulator with Creepage Distance 800 mm

15- Power Frequency withstand Voltage (1 min)

Studies and Documentation Branch

1/2

Page 19: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

Technical Guarantees No. PPYI_800

22kv Overhead Line Pin Type Polymer Insulator with Creepage Distance 800 mm

16.1 a) Power Frequency (Dry) kV 140

16.2 b )Power Frequency (Wet) kV 110

16.3 c) Impulse +VE & -VE kV r+220/-245

17.1 Pin Diameter (stud) mm 25

17.2 Pin AccessoriesNut and Washers

17.3 Pin Toothed Part Length mm 120

18 Attached DrawingDrawing No.

PPYI_800

16- Flashover Voltage

17- Fittings

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch

2/2

Page 20: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Page 21: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3 Design StandardsIEC 61109 ,

IEC 60815 , BS 3288

4 Nominal System Voltage kV 24

5 Insulating Material Composite

Polymer

6 Housing Silicon

7 Metal PartsHot Dip

Galvanized

8 Number of Sheds

9 Total Length mm

10 Shed Diameter mm

11 Min. Creepage Distance mm 1050

12 Min. Mechanical Failing Load kN 70

13 Socket and Ball Size mm Ф16

14 Weight Kg

15.1 a)Dry kV 130

15.2 b)Wet kV 120

Technical Guarantees No. PDI_1050

22kv Overhead Line Tension Polymeric Composite Insulator , with Ball and Socket with Creepage Distance 1050 mm

15- Power Frequency withstand Voltage ( 1min)

Studies and Documentation Branch

1/2

Page 22: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

Technical Guarantees No. PDI_1050

22kv Overhead Line Tension Polymeric Composite Insulator , with Ball and Socket with Creepage Distance 1050 mm

15.3 c)Positive Dry Impulse +VE kV 235

15.4 d)Negative Dry Impulse -VE kV 320

16Power Frequency Flashover Voltage (Wet)

kV 130

17 Attached DrawingDrawing No.

PDI_1050

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch

2/2

Page 23: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Page 24: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

DIN 48072-2

4 Description Copper Parallel Groove Clamps

a) Body High Strength Copper Alloy (Cu Ni 2 Si)

b) BoltsHigh Strength

Copper Alloy, F-60, DIN 933

c) NutsCopper, DIN

934

d) Conical WashersSteel, DIN

6796, Copper Plated

6 Surface Uncoated

7Copper Conductor Cross Sectional Area mm2 6-50

8 Conductor Diameter mm 2.7-9

9 Bolts (No. x Length) 2 x 30

10 Bolt Torque Moments 7Nm

11 Attached DrawingDrawing No.

NTC_650

Technical Guarantees No. NTC_650

Non-Tension Clamp 35 mm2 Copper

Tenderer’s Signature : ……………………..… Date: ………………………………

5

Material

Studies and Documentation Branch

1/1

Page 25: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to
Page 26: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

BS 2874 -CZ 112

4 Description Split-Bolt

Connector with hexagonal head

5 Material Brass (CuZn)

6 SurfaceUncoated or

Tin-Plated

7 Conductor Diameter mm 5.3-8.12

8 Attached DrawingDrawing No.

NTC_635

Technical Guarantees No. NTC_635

Non-Tension Clamp 6/35 mm2 Copper

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch

1/1

Page 27: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Conductor Cross-Section

sq. mm

Conductor Diameter Ø mm

Dimensions mm

Min Max A C D

35 5.30 8.12 31 18.00 23.30

 

Page 28: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

DIN 48072-2

4 Description Copper Parallel Groove Clamps

a) Body High Strength Copper Alloy (Cu Ni 2 Si)

b) BoltsHigh Strength

Copper Alloy, F-60, DIN 933

c) NutsCopper, DIN

934

d) Conical WashersSteel, DIN

6796, Copper Plated

6 Surface Uncoated

7Copper Conductor Cross Sectional Area mm2 16-150

8 Conductor Diameter mm 4.5-15.7

9 Bolts (No. x Length) 2 x 50

10 Bolt Torque Moments 39Nm

11 Attached DrawingDrawing No.

NTC_150

Technical Guarantees No. NTC_150

Non-Tension Clamp 16/150 mm2 Copper

Tenderer’s Signature : ……………………..… Date: ………………………………

5

Material

Studies and Documentation Branch

1/1

Page 29: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Conductor Dimensions Dimension mm.

Bolts Cross Section

mm2 Ø Diameter

mm L B D

16-150 4.5-15.7 52 50 27 2XM10x50

 Torque Moments:

M8 : 39Nm

 

Page 30: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

DIN 48072-2

4 Description Copper Parallel Groove Clamps

a) Body High Strength Copper Alloy (Cu Ni 2 Si)

b) BoltsHigh Strength

Copper Alloy, F-60, DIN 933

c) NutsCopper, DIN

934

d) Conical WashersSteel, DIN

6796, Copper Plated

6 Surface Uncoated

7Copper Conductor Cross Sectional Area mm2 10-95

8 Conductor Diameter mm 3.5-12.5

9 Bolts (No. x Length) 2 x 45

10 Bolt Torque Moments 20Nm

11 Attached DrawingDrawing No.

NTC_95

Technical Guarantees No. NTC_95

Non-Tension Clamp 10/95 mm2 Copper

Tenderer’s Signature : ……………………..… Date: ………………………………

5

Material

Studies and Documentation Branch

1/1

Page 31: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Conductor Dimensions Dimension mm.

Bolts Cross Section

mm2 Ø Diameter

mm L B D

10-95 3.5-12.5 42.5 42 22.5 2xM8x45

 

Torque Moments:

M8 : 20Nm

 

Page 32: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

DIN 48072-2

4 Description Copper Parallel Groove Clamps

a) Body High Strength Copper Alloy (Cu Ni 2 Si)

b) BoltsHigh Strength

Copper Alloy, F-60, DIN 933

c) NutsCopper, DIN

934

d) Conical WashersSteel, DIN

6796, Copper Plated

6 Surface Uncoated

7Copper Conductor Cross Sectional Area mm2 6-70

8 Conductor Diameter mm 2.7-10.5

9 Bolts (No. x Length) 2 x 40

10 Bolt Torque Moments 20Nm

11 Attached DrawingDrawing No.

NTC_70

Technical Guarantees No. NTC_70

Non-Tension Clamp 6/70 mm2 Copper

Tenderer’s Signature : ……………………..… Date: ………………………………

5

Material

Studies and Documentation Branch

1/1

Page 33: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Conductor Dimensions Dimension mm.

Bolts Cross Section

mm2 Ø Diameter

mm L B D

6-70 2.7-10.5 36 40 20 2xM8x40

 

 

Torque Moments:

M8 : 20Nm

 

Page 34: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

DIN 48201, DIN 48204

4 Description Bimetallic

Parallel Groove Clamp

a) Body

High strength, corrosion-resistant,

aluminium alloy (AlMgSi1) with

hot forged bimetallic sheet, for

copper tap-off

b) BoltsSteel 8.8, DIN 933, hot-dip galvanized

c) NutsSteel 8, DIN 934 hot-dip galvanized

d) Conical Washers

According to DIN 6796 corrosion-protected

Technical Guarantees No. NTAC_300

Non-Tension Clamp 35-300/35-240 mm2 Aluminium/Copper

5

Material

Studies and Documentation Branch

1/2

Page 35: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

Technical Guarantees No. NTAC_300

Non-Tension Clamp 35-300/35-240 mm2 Aluminium/Copper

6ACSR or Aluminium Conductor Diameter

mm 7.5-23

7 Copper Conductor Diameter mm 7.5-20.3

8 Bolts (No. x Length) 3 X 70

9 Bolt Torque Moments 46Nm

10 Attached DrawingDrawing No. NTAC_300

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch

2/2

Page 36: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Conductor Cross Section sq. mm

Conductor Diameter Ø mm

Dimension mm. Bolts

Al ACSR Cu Al Cu L B D

35-300 35/6-265/35 35-240 7.5-23.0 7.5-20.3 105 65 33 3xm10x70

 

Torque Moments: M10 : 46Nm

 

Page 37: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

DIN 48201, DIN 48204

4 Description Bimetallic

Parallel Groove Clamp

a) Body

High strength, corrosion-resistant,

aluminium alloy (AlMgSi1) with

hot forged bimetallic sheet, for

copper tap-off

b) BoltsSteel 8.8, DIN 933, hot-dip galvanized

c) NutsSteel 8, DIN 934 hot-dip galvanized

d) Conical Washers

According to DIN 6796 corrosion-protected

Technical Guarantees No. NTAC_12

Non-Tension Clamp 16-120/10-95 mm2 Aluminium/Copper

5

Material

Studies and Documentation Branch

1/2

Page 38: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

Technical Guarantees No. NTAC_12

Non-Tension Clamp 16-120/10-95 mm2 Aluminium/Copper

6ACSR or Aluminium Conductor Diameter

mm 5.1-14

7 Copper Conductor Diameter mm 3.5-12.5

8 Bolts (No. x Length) 2 x 45

9 Bolt Torque Moments 23Nm

10 Attached DrawingDrawing No.

NTAC_12

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch

2/2

Page 39: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Conductor Cross Section sq. mm

Conductor Diameter Ø mm

Dimension mm. Bolts

Al ACSR Cu Al Cu L B D

16-120 16/2.5-95/15 10-50 5.1-14.0 3.5-12.5 47.7 48.0 28.0 2xM8x45

 

Torque Moments: M8 : 23Nm

 

Page 40: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

DIN 48072-1

4 Description Aluminium

Parallel Groove Clamps

a) Body

High strength, corrosion-resistant,

aluminium alloy (AlMgSi1)

b) BoltsDIN 933, steel

8.8, hot-dip galvanized

c) Conical Washers DIN 6796, corrosion-protected

7Aluminium or/and ACSR Conductor Cross Sectional Area mm2

35/240 (for AL) & 35/6-210/35

(for ACSR)

8 Conductor Diameter mm 7.5-20.3

9 Bolts (No. x Length) 3 x 70

10 Bolt Torque Moments 46Nm

11 Attached DrawingDrawing No.

NTA_240

Technical Guarantees No. NTA_240

Non-Tension Clamp 35/240 mm2 Aluminium

Tenderer’s Signature : ……………………..… Date: ………………………………

5

Material

Studies and Documentation Branch

1/1

Page 41: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

 

Conductor Cross sq. mm Conductor

DiameterØmm

Dimension mm. Bolts

Al ACSR L B D

35-240 35/6-210/35 7.5-20.3 67 100 35 3xM10x70

Torque Moments: M10 : 46Nm

 

Page 42: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

DIN 48072-1

4 Description Aluminium

Parallel Groove Clamps

a) Body

High strength, corrosion-resistant,

aluminium alloy (AlMgSi1)

b) BoltsDIN 933, steel

8.8, hot-dip galvanized

c) Conical Washers DIN 6796, corrosion-protected

7Aluminium or/and ACSR Conductor Cross Sectional Area mm2

16/120 (for AL) & 16/2.5 -95/15

(for ACSR)

8 Conductor Diameter mm 5.1-14

9 Bolts (No. x Length) 2 x 50

10 Bolt Torque Moments 23Nm

11 Attached DrawingDrawing No.

NTA_120

Technical Guarantees No. NTA_120

Non-Tension Clamp 16/120 mm2 Aluminium

Tenderer’s Signature : ……………………..… Date: ………………………………

5

Material

Studies and Documentation Branch

1/1

Page 43: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Torque Moments: M8 : 23Nm

 

 

Conductor Cross sq. mm Conductor

DiameterØmm

Dimension mm. Bolts

Al ACSR L B D

16-120 16/2.5-95/15 5.1-14.0 45 50 25 2xM8x50

Page 44: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

DIN 48072-1

4 Description Aluminium

Parallel Groove Clamps

a) Body

High strength, corrosion-resistant,

aluminium alloy (AlMgSi1)

b) BoltsDIN 933, steel

8.8, hot-dip galvanized

c) Conical Washers DIN 6796, corrosion-protected

7Aluminium or/and ACSR Conductor Cross Sectional Area mm2

16/70 (for AL) & 16/2.5-70/12

(for ACSR)

8 Conductor Diameter mm 5.1-11.7

9 Bolts (No. x Length) 2 x 40

10 Bolt Torque Moments 23Nm

11 Attached DrawingDrawing No.

NTA_70

Technical Guarantees No. NTA_70

Non-Tension Clamp 16/70 mm2 Aluminium

Tenderer’s Signature : ……………………..… Date: ………………………………

5

Material

Studies and Documentation Branch

1/1

Page 45: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Torque Moments: M8 : 23Nm

 

 

Conductor Cross sq. mm Conductor

DiameterØmm

Dimension mm. Bolts

Al ACSR L B D

16-70 16/2.5-70/12 5.1-11.7 36 40 20 2xM8x40

Page 46: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

DIN 57295

4 Description

Copper Non-Tension

Compression Joint

5 MaterialElectrolytic

Copper

6 Surface Uncoated

7 Conductor Diameter mm 7.5

8 Hole Diameter mm 8.2

9 Joint Length mm 50

10 Dimensions As Drawing

11 Attached DrawingDrawing No.

NJ35

Technical Guarantees No. NJ_35

22Kv Copper Non Tension Compression Joint for Conductor 35 mm2

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch

1/1

Page 47: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to
Page 48: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Connecting Dimensions Standards

DIN 48064

4 Material Standards DIN 1692

5 Surface Standards DIN 50976

6 MaterialMalleable cast

iron GTS-45

7 SurfaceHot-dip

Galvanized

8 Nominal Load KN 110

9 Construction and Dimensions mm As Drawing

10 Attached DrawingDrawing No.

HMC_01

Technical Guarantees No. HMC_01

Strain Thimbles with Socket (Half Moon Clamp)

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch

1/1

Page 49: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to
Page 50: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

IEC243 , IEC251

4 Description

Environment friendly flame retardant heat shrinkable tube for Low Voltage

Cable

5 MaterialHigh Quality

Polymer

6 Cable Outer Diameter 32

7 Dielectric strength KV/mm ≥20

8 Tensile strength Mpa ≥13

9 Elongation at breek % ≥300

Technical Guarantees No. HIS_240

Shrinck Insulator for Lugs 240 mm2 (Color)

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch

1/1

Page 51: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3 Design StandardsBS137& IEC60120

4 Test Standards IEC

5 Insulator material Glass

6 Min. Mechanical Failing Load kN 80

7Min. Mechanical Residual Strength

kN 42

8 Weight Kg

9 Creepage Distance mm 320

10 Diameter mm 255

11 Ball Size mm Ф16

12 Dimensions as Drawing

13.1 a)Dry kV 70

13.2 b)Wet kV 40

13.3 c)Positive Dry Impulse +VE kV 100

13.4 d)Negative Dry Impulse -VE kV 103

Technical Guarantees No. GDI_320

22kv Overhead Line Toughened Tension Glass Disk Insulator with Ball and Socket

13- Power Frequency withstand Voltage ( 1min)

Studies and Documentation Branch

1/2

Page 52: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

Technical Guarantees No. GDI_320

22kv Overhead Line Toughened Tension Glass Disk Insulator with Ball and Socket

14 Min Puncture Voltage in Oil kV 130

15Phosphorous Bronze Security Clip (BS 3288 Part 4)

W-CLIP

16 Accessories Hot Galvanized Ball and Socket

17 Attached DrawingDrawing No.

GDI_320

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch

2/2

Page 53: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to
Page 54: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered DataNotes, Remarks

, Ref to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Connecting Dimensions Standards

DIN 48064

4 Material Standards DIN 1692

5 Surface Standards DIN 50976

6 MaterialMalleable cast

iron GTS-45

7 SurfaceHot-dip

Galvanized

8 Nominal Load KN 160

9 Construction and Dimensions mm As Drawing

10 Attached DrawingDrawing No.

FBH_16

Technical Guarantees No. FBH_16

Fork Ball Hook 16mm (SOCKET EYES-TYPE-A)

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch

1/1

Page 55: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to
Page 56: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

KEMA standard 83-C

4 Material Cooper

5 CoatingCopper shrink

jacket

6 Length mm

7 Diameter mm 15

Technical Guarantees No. ERJ_15

Earth Rod Joint 15 mm Diameter

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch

1/1

Page 57: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

4 Material Brass

5 Design

Suitable for earth rod 15

mm Dia to used for connection between Rod

and cable

6 Earth Rod Diameter mm 15

7 Copper Cable Diameter mm 10.7

8 Attached DrawingDrawing No.

ERC_15

Technical Guarantees No. ERC_15

Earth Rod Connection Clamp

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch

1/1

Page 58: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Page 59: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

KEMA standard 83-C

4 Material Steel St-60

5 CoatingCopper shrink

jacket

6 Length mm 1500

7 Diameter mm 15

Technical Guarantees No. ER_15

Earth Rod 15 mm Diameter , 1.5 m

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch

1/1

Page 60: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation

No Description Unit RequirementsOffered

Data

Notes, Remarks , Ref to

Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3 Reference Manufacturing Standards

4 Description Elastomeric End

Cap for ABC Cable 150 mm2

5 MaterialThermoplastic ,

UV Resistant

6 Voltage Test mm

6 kv Under_water

According NFC 33020

7 Recommended Cross Section mm2 150

8Nominal Cable Diameter over Insulation (Min. - Max)

mm 17.6 - 18

9 Cap Diameter mm 19

10 Attached Drawing Drawing No. EC

Technical Guarantees No. EC_150

Sealing Cap for ABC Cable 150 mm2 (Elastomeric End Cap)

Tenderer’s Signature : ……………………..… Date: ………………………………

1/1

Page 61: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to
zhoussaini
zhoussaini
Page 62: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3 Reference Manufacturing Standards

4 Description

Elastomeric End Cap for

ABC Cable 95 mm2

5 MaterialThermoplastic ,

UV Resistant

6 Voltage Test mm

6 kv Under_water

According NFC 33020

7 Recommended Cross Section mm2 95

8Nominal Cable Diameter over Insulation (Min. - Max)

mm 15.5-16

9 Cap Diameter mm 16.5

10 Attached Drawing Drawing No. EC

Technical Guarantees No. EC_95

Sealing Cap for ABC Cable 95 mm2 (Elastomeric End Cap)

Tenderer’s Signature : ……………………..… Date: ………………………………

1/1

Page 63: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to
zhoussaini
zhoussaini
Page 64: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation

No Description Unit RequirementsOffered

Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3 Reference Manufacturing Standards

4 Description

Elastomeric End Cap for

ABC Cable 50 mm2

5 MaterialThermoplastic ,

UV Resistant

6 Voltage Test mm

6 kv Under_water

According NFC 33020

7 Recommended Cross Section mm2 50

8Nominal Cable Diameter over Insulation (Min. - Max)

mm 11.5-12

9 Cap Diameter mm 12.5

10 Attached Drawing Drawing No. EC

Technical Guarantees No. EC_50

Sealing Cap for ABC Cable 50 mm2 (Elastomeric End Cap)

Tenderer’s Signature : ……………………..… Date: ………………………………

1/1

Page 65: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to
zhoussaini
zhoussaini
Page 66: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation

No Description Unit Requirements Offered DataNotes, Remarks

, Ref to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3 Reference Manufacturing Standards

4 Description Elastomeric End

Cap for ABC Cable 25 mm2

5 MaterialThermoplastic ,

UV Resistant

6 Voltage Test mm

6 kv Under_water

According NFC 33020

7 Recommended Cross Section mm2 25

8Nominal Cable Diameter over Insulation (Min. - Max)

mm 8.3-8.7

9 Cap Diameter mm 9.5

10 Attached Drawing Drawing No. EC

Technical Guarantees No. EC_25

Sealing Cap for ABC Cable 25 mm2 (Elastomeric End Cap)

Tenderer’s Signature : ……………………..… Date: ………………………………

1/1

Page 67: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to
zhoussaini
zhoussaini
Page 68: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered DataNotes, Remarks

, Ref to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3 Standards

4 MaterialSolid Copper Coated Steel

5 Tie TypeTop groove of

insulators

6 Conductor Type Copper

7 Conductor Diameter (Min. - Max.) 7.4 - 14.3

8 Length mm 1500

Tenderer’s Signature : ……………………..… Date: ………………………………

Technical Guarantees No. DTCT_01

Distribution Ties Performed , Copper (Top)

Studies and Documentation Branch1/1

Page 69: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered DataNotes, Remarks

, Ref to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3 Standards

4 MaterialSolid Copper Coated Steel

5 Tie TypeSide groove of

insulators

6 Conductor Type Copper

7 Conductor Diameter (Min. - Max.) 7.4 - 14.3

8 Length mm 1500

Tenderer’s Signature : ……………………..… Date: ………………………………

Technical Guarantees No. DTCS_01

Distribution Ties Performed , Copper (Side)

Studies and Documentation Branch1/1

Page 70: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered DataNotes, Remarks

, Ref to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3 Standards

4 MaterialSolid Aluminum

Coated Steel

5 Tie TypeTop groove of

insulators

6 Conductor Type ACSR

7 Conductor Diameter (Min. - Max.) 9.5 - 17.2

8 Length mm 1500

Tenderer’s Signature : ……………………..… Date: ………………………………

Technical Guarantees No. DTAT_01

Distribution Ties Performed , AL (Top)

Studies and Documentation Branch1/1

Page 71: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered DataNotes, Remarks

, Ref to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3 Standards

4 MaterialSolid Aluminum

Coated Steel

5 Tie TypeSide groove of

insulators

6 Conductor Type ACSR

7 Conductor Diameter (Min. - Max.) 9.5 - 17.2

8 Length mm 1500

Tenderer’s Signature : ……………………..… Date: ………………………………

Technical Guarantees No. DTAS_01

Distribution Ties Performed , AL (Side)

Studies and Documentation Branch1/1

Page 72: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

DIN 48201

4 Description Copper Dead

End Clamp

a) BodyHigh strength copper alloy

(CuNi2Si)

b) BoltsDIN 933, high

strength copper alloy (F60)

c) Nuts

DIN 934, copper. Option

to stainless steel

6 Surface Uncoated

7 Conductor Cross Sectional Area mm2 25-35

8 Conductor Diameter mm 6.3-7.5

9 Bolts (No. x Length) 2 x 30

10 Bolt Torque Moments 20Nm

11 Attached DrawingDrawing No.

DEC_25

Technical Guarantees No. DEC_25

Dead End Clamp , 25/35 mm2 Copper

Tenderer’s Signature : ……………………..… Date: ………………………………

5

Material

Studies and Documentation Branch

1/1

Page 73: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Conductor Cross Section

sq. mm

Conductor Diameter

Ømm

Dimension mm. Bolts

L B D

25-35 6.3-7.5 47 47 30 2xM8x30

 

Torque Moments:

M8 : 20Nm

 

Page 74: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

DIN 48201, DIN 48204

4 Description Aluminium Dead End

Clamp

a) Body

High strength, corrosion-resistant,

aluminium alloy (AlMgSi1)

b) BoltsSteel, 8.8,DIN

933 hot-dip galvanized

c) NutsSteel, 8, DIN 934 hot-dip galvanized

7Aluminium or/and ACSR Conductor Cross Sectional Area mm2

95/120 (for AL) & 95/15 (for

ACSR)

8 Conductor Diameter mm 12.5-13.6

9 Bolts (No. x Length) 2 x 45

10 Bolt Torque Moments 80Nm

11 Attached DrawingDrawing No.

DEA_120

Technical Guarantees No. DEA_120

Dead End Clamp , 95/120 mm2 Aluminium

Tenderer’s Signature : ……………………..… Date: ………………………………

5

Material

Studies and Documentation Branch

1/1

Page 75: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to
Page 76: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

DIN 48201, DIN 48204

4 Description Aluminium Dead End

Clamp

a) Body

High strength, corrosion-resistant,

aluminium alloy (AlMgSi1)

b) BoltsSteel, 8.8,DIN

933 hot-dip galvanized

c) NutsSteel, 8, DIN 934 hot-dip galvanized

7Aluminium or/and ACSR Conductor Cross Sectional Area mm2

50/70 (for AL) & 50/8-70/12 (for ACSR)

8 Conductor Diameter mm 9-11.7

9 Bolts (No. x Length) 2 x 35

10 Bolt Torque Moments 46Nm

11 Attached DrawingDrawing No.

DEA_70

Technical Guarantees No. DEA_70

Dead End Clamp , 50/70 mm2 Aluminium

Tenderer’s Signature : ……………………..… Date: ………………………………

5

Material

Studies and Documentation Branch

1/1

Page 77: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Conductor Cross-Section sq. mm

Conductor Diameter

Ømm

Dimension mm. Bolts

Al ACSR L B D

50-70 50/8-70/12 9.0-11.7 60 64 42 2xM10x35

 

Torque Moments: M10 : 46Nm

 

Page 78: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

DIN 46235

4 Description

Copper Compression

Lug with 13mm Hole

5 MaterialE-Cu, DIN

40500/2, F-25

6 Surface Tin-plated

7 TypeCompression, Longitudinally

Sealed

8 Conductor Cross Section mm2 240

9 Conductor Diameter mm 20.2

10 No of Compression 5

11 Dimensions as Drawing

12 Barrel

Capped and Filled with Grease to

Avoid Oxidation

13 Attached DrawingDrawing No.

CLC_240

Technical Guarantees No. CLC_240

Compression Terminal Lug with 13 mm Hole for 240 mm2 Copper Conductor

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch

1/1

Page 79: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Conductor Cross

Section mm2

Conductor Diameter

mm

Dimensions

d1 l b d2

240 20.2 21.5 92 42 13

 

Page 80: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

DIN 46235

4 Description

Copper Compression

Lug with 13mm Hole

5 MaterialE-Cu, DIN

40500/2, F-25

6 Surface Tin-plated

7 TypeCompression, Longitudinally

Sealed

8 Conductor Cross Section mm2 120

9 Conductor Diameter mm 14

10 No of Compression 4

11 Dimensions as Drawing

12 Attached DrawingDrawing No.

CLC_120

Technical Guarantees No. CLC_120

Compression Terminal Lug with 13 mm Hole for 120 mm2 Copper Conductor

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch

1/1

Page 81: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Conductor Cross

Section mm2

Conductor Diameter

mm

Dimensions

d1 l b d2

120 14 15.5 70 32 13

 

Page 82: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

DIN 46235

4 Description

Copper Compression

Lug with 13mm Hole

5 MaterialE-Cu, DIN

40500/2, F-25

6 Surface Tin-plated

7 TypeCompression, Longitudinally

Sealed

8 Conductor Cross Section mm2 95

9 Conductor Diameter mm 12.6

10 No of Compression 4

11 Dimensions as Drawing

12 Attached DrawingDrawing No.

CLC_95

Technical Guarantees No. CLC_95

Compression Terminal Lug with 13 mm Hole for 95 mm2 Copper Conductor

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch

1/1

Page 83: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Conductor Cross

Section mm2

Conductor Diameter

mm

Dimensions

d1 l b d2

95 12.6 13.5 65 28 13

 

Page 84: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

DIN 46235

4 Description

Copper Compression

Lug with 13mm Hole

5 MaterialE-Cu, DIN

40500/2, F-25

6 Surface Tin-plated

7 TypeCompression, Longitudinally

Sealed

8 Conductor Cross Section mm2 70

9 Conductor Diameter mm 10.7

10 No of Compression 3

11 Dimensions as Drawing

12 Attached DrawingDrawing No.

CLC_70

Technical Guarantees No. CLC_70

Compression Terminal Lug with 13 mm Hole for 70 mm2 Copper Conductor

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch

1/1

Page 85: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Conductor Cross

Section mm2

Conductor Diameter

mm

Dimensions

d1 l b d2

70 10.7 11.5 55 24 13

 

Page 86: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

DIN 46235

4 Description

Copper Compression

Lug with 13mm Hole

5 MaterialE-Cu, DIN

40500/2, F-25

6 Surface Tin-plated

7 TypeCompression, Longitudinally

Sealed

8 Conductor Cross Section mm2 35

9 Conductor Diameter mm 7.5

10 No of Compression 2

11 Dimensions as Drawing

12 Attached DrawingDrawing No.

CLC_35

Technical Guarantees No. CLC_35

Compression Terminal Lug with 13 mm Hole for 35 mm2 Copper Conductor

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch

1/1

Page 87: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Conductor Cross

Section mm2

Conductor Diameter

mm

Dimensions

d1 l b d2

35 7.5 8 42 21 13

 

Page 88: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

4 Description Bimetallic

Compression Lug

a) Barrel Part

Aluminium of Purity Equal to or Greater than

99.5%

b) Palm PartElectrolytic

Copper

6 Surface Uncoated

7 TypeCompression, Longitudinally

Sealed

8 Conductor Cross Section mm2 400

9 Hole Diameter mm 13

10 Barrel

Capped and Filled with Grease to

Avoid Oxidation

11 Attached DrawingDrawing No. CLAC_400

Technical Guarantees No. CLAC_400

Aluminium / Copper Compression Terminal Lug

with 13 mm Hole for 400 mm2 Aluminium Conductor

Tenderer’s Signature : ……………………..… Date: ………………………………

5

Material

Studies and Documentation Branch

1/1

Page 89: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Conductor Cross

Section mm2

Conductor Diameter

Ø mm

Dimensions mm.

No. of compressionsd1 d2 b L2 L1

400 24.5 26 13.0 36 85 117.5 6-3

 

Page 90: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

4 Description Bimetallic

Compression Lug

a) Barrel Part

Aluminium of Purity Equal to or Greater than

99.5%

b) Palm PartElectrolytic

Copper

6 Surface Uncoated

7 TypeCompression, Longitudinally

Sealed

8 Conductor Cross Section mm2 185

9 Hole Diameter mm 13

10 Barrel

Capped and Filled with Grease to

Avoid Oxidation

11 Attached DrawingDrawing No. CLAC_185

Technical Guarantees No. CLAC_185

Aluminium / Copper Compression Terminal Lug

with 13 mm Hole for 185 mm2 Aluminium Conductor

Tenderer’s Signature : ……………………..… Date: ………………………………

5

Material

Studies and Documentation Branch

1/1

Page 91: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Conductor Cross

Section mm2

Conductor Diameter

Ø mm

Dimensions mm.

No. of compressionsd1 d2 b L2 L1

185 17 17 13.0 35 66 97.5 6-3

 

Page 92: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

4 Description Bimetallic

Compression Lug

a) Barrel Part

Aluminium of Purity Equal to or Greater than

99.5%

b) Palm PartElectrolytic

Copper

6 Surface Uncoated

7 TypeCompression, Longitudinally

Sealed

8 Conductor Cross Section mm2 150

9 Hole Diameter mm 13

10 Barrel

Capped and Filled with Grease to

Avoid Oxidation

11 Attached DrawingDrawing No. CLAC_150

Technical Guarantees No. CLAC_150

Aluminium / Copper Compression Terminal Lug

with 13 mm Hole for 150 mm2 Aluminium Conductor

Tenderer’s Signature : ……………………..… Date: ………………………………

5

Material

Studies and Documentation Branch

1/1

Page 93: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Conductor Cross

Section mm2

Conductor Diameter

Ø mm

Dimensions mm.

No. of compressionsd1 d2 b L2 L1

150 15.5 15.5 13.0 30 66 100 6-3

 

Page 94: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

4 Description Bimetallic

Compression Lug

a) Barrel Part

Aluminium of Purity Equal to or Greater than

99.5%

b) Palm PartElectrolytic

Copper

6 Surface Uncoated

7 TypeCompression, Longitudinally

Sealed

8 Conductor Cross Section mm2 120

9 Hole Diameter mm 13

10 Barrel

Capped and Filled with Grease to

Avoid Oxidation

11 Attached DrawingDrawing No. CLAC_120

Technical Guarantees No. CLAC_120

Aluminium / Copper Compression Terminal Lug

with 13 mm Hole for 120 mm2 Aluminium Conductor

Tenderer’s Signature : ……………………..… Date: ………………………………

5

Material

Studies and Documentation Branch

1/1

Page 95: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Conductor Cross

Section mm2

Conductor Diameter

Ø mm

Dimensions mm.

No. of compressionsd1 d2 b L2 L1

120 13.7 13.7 13.0 30 66 100 6-3

 

Page 96: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

4 Description Bimetallic

Compression Lug

a) Barrel Part

Aluminium of Purity Equal to or Greater than

99.5%

b) Palm PartElectrolytic

Copper

6 Surface Uncoated

7 TypeCompression, Longitudinally

Sealed

8 Conductor Cross Section mm2 95

9 Hole Diameter mm 13

10 Barrel

Capped and Filled with Grease to

Avoid Oxidation

11 Attached DrawingDrawing No.

CLAC_95

Technical Guarantees No. CLAC_95

Aluminium / Copper Compression Terminal Lug

with 13 mm Hole for 95 mm2 Aluminium Conductor

Tenderer’s Signature : ……………………..… Date: ………………………………

5

Material

Studies and Documentation Branch

1/1

Page 97: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Conductor Cross

Section mm2

Conductor Diameter

Ø mm

Dimensions mm.

No. of compressionsd1 d2 b L2 L1

95 12.5 12.5 13.0 25 49 77.5 5-2

 

Page 98: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

4 Description Bimetallic

Compression Lug

a) Barrel Part

Aluminium of Purity Equal to or Greater than

99.5%

b) Palm PartElectrolytic

Copper

6 Surface Uncoated

7 TypeCompression, Longitudinally

Sealed

8 Conductor Cross Section mm2 70

9 Hole Diameter mm 13

10 Barrel

Capped and Filled with Grease to

Avoid Oxidation

11 Attached DrawingDrawing No.

CLAC_70

Technical Guarantees No. CLAC_70

Aluminium / Copper Compression Terminal Lug

with 13 mm Hole for 70 mm2 Aluminium Conductor

Tenderer’s Signature : ……………………..… Date: ………………………………

5

Material

Studies and Documentation Branch

1/1

Page 99: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Conductor Cross

Section mm2

Conductor Diameter

Ø mm

Dimensions mm.

No. of compressionsd1 d2 b L2 L1

70 10.5 11.0 13.0 25 49 77.5 5-2

 

Page 100: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

DIN 46329

4 Description

Aluminium Compression

Lug with 13mm Hole

5 Material Al 99.5

6 Surface Tin-plated

7 TypeCompression, Longitudinally

Sealed

8 Conductor Cross Section mm2 70

9 Conductor Diameter mm 10.5

10 Dimensions as Drawing

11 Barrel

Capped and Filled with Grease to

Avoid Oxidation

12 Attached DrawingDrawing No.

CLA_70

Technical Guarantees No. CLA_70

Compression Terminal Lug with 13 mm Hole for 70 mm2 Aluminium Conductor

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch

1/1

Page 101: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Conductor Cross

Section mm2

Conductor Diameter

mm

Dimensions

d1 l b d2

70 10.5 11.5 83 28 13

 

Page 102: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3 Description Cable Clamps

4 Cable Outer Diameter mm 36-53

5 No. of Cables 1

6 MaterialPolyamide, Glass Fiber Reinforced

7 Tensile strength N/mm2 120

8 Flexural Strength N/mm2 200

9 Thermal Expansion 0.02% / 1°C

10 Fire ResistanceUL 94 , VDE 0304, Part 3

11 Accessories

2 Hot Galvanized Bolt with nuts and

washers

12 Dimensions As Drawing

13 Attached DrawingDrawing No.

CC_52

Technical Guarantees No. CC_52

Clamp to Holder the Cable (Single , Large )

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch

1/1

Page 103: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Cable Out Side Diameter (D)

Ø mm

No. of Cables

Dimensions mm Weight Kg. L B I Ød H

36-53 1 108 60 75 12.4 40-57 .17

 

Page 104: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3 Description Cable Clamps

4 Cable Outer Diameter mm 26-38

5 No. of Cables 1

6 MaterialPolyamide, Glass Fiber Reinforced

7 Tensile strength N/mm2 120

8 Flexural Strength N/mm2 200

9 Thermal Expansion 0.02% / 1°C

10 Fire ResistanceUL 94 , VDE 0304, Part 3

11 Accessories

2 Hot Galvanized Bolt with nuts and

washers

12 Dimensions As Drawing

13 Attached DrawingDrawing No.

CC_51

Technical Guarantees No. CC_51

Clamp to Holder the Cable (Single , Small )

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch

1/1

Page 105: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Cable Out Side Diameter (D)

Ø mm

No. of Cables

Dimensions mm Weight Kg. L B I Ød H

26-38 1 92 60 60 12.4 32-44 .11

 

Page 106: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

4 Rated Voltage (Uo/U) kV 0.6/1

5Clamp Wedges and Thimble Material

Weather and UV resistant

Glass Reinforced

Polymer

6 Clamp Body Material (Straps)Corrosion Resistant

Aluminium Alloy

7 Stay wire

Galvanized steel stranded

wire with insulation

wear_resistant Saddle

8 Designto Tension Messenger Cable only

9Messenger Conductor Cross Sectional Area mm2 95

10 Clamp Breaking Load KN

11 Attached DrawingDrawing No.

ABT_150

Technical Guarantees No. ABT_150

Tension Clamp for ABC Aluminium Cable 3*150+1*95+2*25 mm2

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch

1/1

Page 107: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to
Page 108: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

VDE0211

4 Rated Voltage (Uo/U) kV 0.6/1

5 Wedges Material

weather and UVResistant Glass

Fibre Reinforced

Polymer

6 All ferrous partsHot Galvanized

Steel

7 Design

to anchor self supporting 4

Cores LV-ABC lines

8 Constructionwith movable

arm

9 Conductor Cross Sectional Area mm2 4x95

10 Clamp Breaking Load KN 43

11 Attached DrawingDrawing No.

ABT_95

Technical Guarantees No. ABT_95

Tension Clamp for ABC Aluminium Cable 4*95 mm2

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch

1/1

Page 109: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Page 110: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

VDE0211

4 Rated Voltage (Uo/U) kV 0.6/1

5 Wedges Material

weather and UVResistant Glass

Fibre Reinforced

Polymer

6 All ferrous partsHot Galvanized

Steel

7 Design

to anchor self supporting 4

Cores LV-ABC lines

8 Constructionwith movable

arm

9 Conductor Cross Sectional Area mm2 4x50

10 Clamp Breaking Load KN 30

11 Attached DrawingDrawing No.

ABT_50

Technical Guarantees No. ABT_50

Tension Clamp for ABC Aluminium Cable 4*50 mm2

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch

1/1

Page 111: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Page 112: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

4 Rated Voltage (Uo/U) kV 0.6/1

5 Clamp and Movable Link Material

Weather and UV resistant Glass Fibre Reinforced

Polymer

6 Design

Suspension Clamp for

Messenger Cable only

7Phase Conductor Cross Sectional Area mm2 150

8Messenger Conductor Cross Sectional Area mm2 95

9 Clamp Breaking Load KN 30

10 Bundle Diameter mm 15 - 17.5

11 Hole Diameter mm 22

12 Attached DrawingDrawing No.

ABS_150

Technical Guarantees No. ABS_150

Suspension Clamp for ABC Aluminium Cable 3*150+1*95+2*25 mm2

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch

1/1

Page 113: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

 

Page 114: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to

Gaza Electricity Distribution Corporation LTD.

No Description Unit Requirements Offered Data

Notes, Remarks , Ref

to Documentation

Evaluation Committee Comments

1 Name of Manufacturer

2 Country of Origin

3Reference Manufacturing Standards

4 Rated Voltage (Uo/U) kV 0.6/1

5 Clamp Bushing Material

Weather and UV resistant Elastomer

(EPDM)

6 Clamp Body MaterialHot Galvanized

Steel

7Clamp Butterfly End Nut Material (Die Cast Wing Nut)

Hot Galvanized Steel

8 DesignSuspension

Clamp for Four Core Cable

9Phase Conductor Cross Sectional Area mm2 95

10 Clamp Breaking Load KN 7.5

11 Bundle Diameter mm 36 - 40

12 Hole Diameter mm 25

13 Attached DrawingDrawing No.

ABS_95

Technical Guarantees No. ABS_95

Suspension Clamp for ABC Aluminium Cable 4*95 mm2

Tenderer’s Signature : ……………………..… Date: ………………………………

Studies and Documentation Branch

1/1

Page 115: Gaza Electricity Distribution Corporation LTD. Technical ... A...Gaza Electricity Distribution Corporation LTD. No Description Unit Requirements Offered Data Notes, Remarks , Ref to