Gas Furnace Venting
above dew point
80% Induced Draft furnaces fall into class I, the inducer motor is only for moving gases through the heat exchanger.
Combustion Air / Vent Sizing
Termination elbows counted?
Consequences of too many elbows or smaller pipe than required?
When Using The Concentric Vent Termination Kit
Subtract 5 ft From Total Pipe Length.
The type of installation shown next will draw the air required for combustion from within the space surrounding the appliance and from areas or rooms adjacent to the space surrounding the appliance. This may be from within the space in a non-confined location or it may be brought into the furnace area from outdoors through permanent openings or ducts. It is not piped directly into the burner box. A single, properly sized pipe from the furnace vent connector to the outdoors must be provided. For upflow models, combustion air is brought into the furnace through the unit top panel opening. Do not install a pipe into the intake collar on top of the burner box. An unconfined space is not less than 50 cu. ft. per 1,000 Btu/ hr input rating for all of the appliances installed in that area. Rooms communicating directly with the space containing the appliances are considered part of the unconfined space, if openings are furnished with doors. A confined space is an area with less than 50 cu. ft. per 1,000 Btu/hr input rating for all of the appliances installed in that area. The following must be considered to obtain proper air for combustion and ventilation in confined spaces. Combustion Air Source From Outdoors The blocking effects of louvers, grilles and screens must be given consideration in calculating free area. If the free area of a specific louver or grille is not known, to estimate free area.
Ambient Combustion Air
Calculate for all of the appliances installed in that area.
.
Vent Pipe Clearances IMPORTANT: The vent must be installed with the following minimum clearances. The vent must also comply with local codes and requirements. On a two pipe system follow instructions on keeping pipes together.
Avoid This….
Clearance Above Grade
• Clearance above: – Grade – Veranda – Porch – Deck – Balcony
• * = 9” for 10k to 50K BTUH and 12” for 50K BTUH and larger furnaces
Window Clearance • Clearance:
– From fixed window to vent = 6”
– Outside corner = 6” • * = 9” for 10k to 50K BTUH
and 12” for 50K BTUH and larger furnaces
Window Clearance * = 9” for 10k to 50K BTUH
and 12” for 50K BTUH and larger furnaces
J= same as above
Fixed Window
Combustion air inlet on Two pipe systems
Clearance To A Meter/Regulator • H = 9” for 10k to 50K
BTUH and 12” for 50K BTUH and larger furnaces from centerline of meter/regulator
• I = * = 9” for 10k to 50K BTUH and 12” for 50K BTUH and larger furnaces Gas regulator vent outlet.
I
*Around the electrical and gas meters as well as a LP regulator there will always be a hole through the Building exterior. Keep vent terminations away from These.
Soffit Clearance • Clearance D, B and E
are = 9” for 10k to 50K BTUH and 12” for 50K BTUH and larger furnaces Gas regulator vent outlet.
• E is for unventilated soffit • L is 3 feet clearance above
a sidewalk,or paved driveway located on Public property.
Clearance Under Veranda
• M = 9” for 10k to 50K BTUH and 12” for 50K BTUH and larger furnaces
• K = Clearance to mechanical supply inlet (x) 3’ above it within 10 horizontal.
Ventilated Combustion Air
*When bring in combustion air from the vented attic be sure to prevent the intake pipe from being blocked by insulation.
Vent Applications
Roof mounted vertical terminals may be field fabricated. Standard PVC/ SRD fittings may be used. If installing a vertical venting system through any unconditioned space such as an attic or crawl space, it must be insulated.
1. Observe all clearances listed in vent clearances in these
instructions. 2. Termination should be positioned where vent vapors are not
objectionable. 3. Termination should be located where it will not be affected by wind
gusts, light snow, or allow recirculation of flue gases. 4. Termination should be located where it cannot be damaged,
plugged or restricted by tree limbs, leaves and branches. 5. Sealed combustion air systems must be installed so the vent and the
combustion air pipes terminate in the same atmospheric zone.
Multiple Unit Termination Observe all clearances listed in vent clearances in the installation instructions. The sealed combustion system can be used for installations requiring more than one furnace in a structure. A separate sealed combustion air pipe and a separate vent pipe must be installed for each furnace. Do not connect more than one furnace to a combustion air pipe or a vent pipe. The combustion air and vent termination must be located as shown.
Vertical Roof Mounting NOTE: Roof mounting is the recommended location.
Horizontal Sidewall Mounting
This is not a mistake – keep vents within 4” or get them apart by at least 24”
above dew point
B-Vent
The “Three C’s”!
Condensation
Corrosion
CO
Combustion Process • Proper Combustion: 1ft3 gas to 10ft3
air • By-products: CO2, water vapor,
nitrogen • Incomplete Combustion: CO is
produced • Since water vapor is a by-product of
combustion, the key is to make sure the flue gas temp stays above the condensation point (“dew point” until exiting the vent system
Reducing Condensation
• B-Vent connectors • Correct Manifold Pressure • Correct Temp Rise • Common Vent Size
– Critical when removing old furnace from common vent with water heater
• Make sure equipment cycle rate is acceptable
Dew Point • Temp at which condensation occurs
(Water vapor condenses to a liquid) • Natural Draft with 40-50% excess air
– dew point typically 121F – Flue Gas must be cooler than 121F for
condensation to occur • Induced draft furnace flue gas has a
higher dew point
Corrosion only occurs when vent walls are wet
It’s common for vent walls to be wet on initial startup
Vent must heat up quickly to dry condensation before equipment cycles off
Natural Draft vs. Induced Draft
• Natural Draft appliances: Lifting Force is Heat – The greater difference between flue gas
temp and air, the greater the lifting force • Induced Draft: Flue products are
forced out • Inducer designed to assist the flow
thru the appliance, not the vent! We are still relying on buoyancy of flue gases.
Combustion Air: The 2-Q’s!
Combustion Air Requirements : Quality
• Be aware of quality of combustion air
• Bleaches, paints, varnish, hairsprays, laundry products, etc. can create acid in flue products
Combustion Air Requirements : Quantity
• Is additional combustion air required?
“Space volume is less than 50 cubic feet per 1000 bth per hour of all appliances installed in that space”
“Space volume is greater than 50 cubic feet per 1000 bth per hour of all appliances installed in that space”
20’
15’ 8’
40,000 100,000
Cubic Feet?
2400 ft3
Combined Inputs ?
140,000
Min space to not need combustion air:
140x50 = 7000 ft3
1 sq in per 4,000 btuh if connected directly to outdoors
1 opening within 12” of floor and 1 opening within 12” of ceiling
20’
15’ 8’
40,000 100,000
Cubic Feet?
2400 ft3
Combined Inputs ?
140,000
Min Space to not need combustion air:
140x50 = 7000 ft3
140,000/4,000
35in2 each
Vent Materials: Single Wall
• Allows great heat loss which can affect strength of draft and allow flue gases to drop below dew point
• 6” clearance to combustibles
• Minimize use!
Vent Materials: B-Vent • Dual wall pipe • Aluminum liner with galvanized
outer wall • Reduces heat loss
– Improves draft – Reduces condensation – Aluminum heats up quickly!
• 1” clearance to combustibles • Type BW: Oval
Good Venting Practices: Avoid Restrictions
• Limit # of ells • 40 or 60 deg elbows are
preferable to 90s • Charts allow 2 90s
– Reduce capacity by 10% for each additional elbow
– No more than 4 elbows allowed!
Good Venting Practices
• Minimum vent height 5’ – 12’ for wall furnaces
• No outdoor pipe runs – Construct a chase if necessary
• Use an approved cap • Insure minimum height above
roof based on roof pitch
Good Venting Practices
• Connector rise should be as high as possible
• Increases ability to draft
• Decreases material cost
True or False???
A fan assisted appliance with a 5” flue connection is always run in 5” pipe
False!!! Use the venting tables.
• Tables allow two elbows. – More than two,
reduce max capacity 10% for each elbow
• 20% Reduction from max capacity for flex liner
Proper Firing Rate and Airflow Setup is Critical!
COMBUSTION PROCESS CH4
O2 O2
CO2
H2O H2O
INCOMPLETE COMBUSTION
CH4 CH4 CH4 CH4
O2 O2 O2
CO2 H2O H2O
H2 H2 H2 H2 H2 H2
C C CO