Upload
ngophuc
View
217
Download
3
Embed Size (px)
Citation preview
Satoshi Konishi and Yasushi Yamamoto,Institute for Advanced Energy, Kyoto University
Jan.25, 2006
Fusion energy introduction: Impacts on grid and hydrogen production
Contents
1.Introduction of fusion electricity and its impacton grids
2.Hydrogen production by fusion update
US-Japan Workshop on Power Plant Studies and RelatedAdvanced Technologies with EU Participation
Photo by K. Okano
Introduction
In order to maximize the market chance of fusion,we study
0. Socio-economic aspects of fusion1. Improvement in adoptability to electricity grid2. Development of hydrogen production process
3. High temperature blanket with SiC-LiPb system.
Institute of Advanced Energy, Kyoto University
1. Study on the impacts on grids1. Study on the impacts on grids
Startup powerStartup power
Grid capacity and sourcesGrid capacity and sources
Future trendsFuture trends
Energy flows in fusion reactorEnergy flows in fusion reactor
Q=50, Pi=60MW Q=50, Pi=60MW →→ auxiliary power ratio = ~13%auxiliary power ratio = ~13%
Pc=Pi+Pα
PlasmaQ
BlanketM
Generatorηe
Driving System
ηd
Auxiliary System
ηanc
Pα = Pf / 5
Pi = ηd Pd
Pf + Pi
Pn
MPn
Pnet=(1-ε)Pe
Pe=ηePth
Pth=Pc+MPn
Pd
Paux
Pcir=εPee
60MW 0.5
1.13
120MW
3060MW
3372MW
0.4 1450MW
~5% 80MW
200MW
1250MW
Grid
Grid
Fusion needs power to start and continue to run.Fusion needs power to start and continue to run.
Institute of Advanced Energy, Kyoto University
Auxiliary power in power plantsAuxiliary power in power plantsCoal Oil Nuclear Fusion
Control system
Condensate water pumpCooling water pump
Coal feeder Oil feeding pump
Coal crusher
Exhaust gas treatment system
Current drive / Auxiliary heating
Recirculation pump Magnet cooling
Tritium handing
Others
Institute of Advanced Energy, Kyoto University
Auxiliary power ratio of various systemAuxiliary power ratio of various system
~13.0~13.075751,0001,000FusionFusion
5500
15151515
1.01.00.0030.003
PhotovoltaicPhotovoltaicutilityutilityhomehome
101020200.10.1wind powerwind power7.07.060605555geothermalgeothermal
0.250.2545451010HydroHydro7.47.475751,0001,000Coal thermalCoal thermal3.53.575751,0001,000LNG thermalLNG thermal6.16.175751,0001,000Oil thermalOil thermal3.43.475751,0001,000Nuclear FissionNuclear Fission
Auxiliary Auxiliary power ratio power ratio
[%][%]
utilization utilization of facilities of facilities
[%][%]
Capacity Capacity [MW][MW]SystemSystem
Source: 内山洋司;発電システムのライフサイクル分析,研究報告,(財)電力中央研究所(1995)
Institute of Advanced Energy, Kyoto University
Electric GridsElectric Grids
Electricity can not be stored.Electricity can not be stored.Generation must respond to the demand.Generation must respond to the demand.Grid capacity is different for each regionsGrid capacity is different for each regions
United StatesUnited StatesJapanJapanEuropeEuropeAsia Asia
Grid capacity changes timeGrid capacity changes time--toto--time.time.Response time of the grid is limited.Response time of the grid is limited.
Institute of Advanced Energy, Kyoto University
Electric grid capacitiesElectric grid capacities
Physics Today, vol.55, No.4 (2002)
Eastern Grid~500GW
Texas Grid~53GW
Western Grid~140GW
East Japan~80GW
West Japan~100GW
UTPTE~270GW
Thailand~20GW
Vietnam~8GW
Institute of Advanced Energy, Kyoto University
Electric Grid in Japan Electric Grid in Japan ––Structure Structure ––
Hokkaido5,345MW
579MW
Tokyo64,300MW
1,356MW
Chubu27,500MW
1,380MW
Hokuriku5,508MW
540MW
Kansai33,060MW
1,180MW
Chugoku12,002MW
820MW
Shikoku5,925MW
890MW
Kyushu17,061MW
1,180MW
Tohoku14,489MW
825MW
600MW
600MW
300MW
West Japan Grid60Hz, ~100GW
Utility NameUtility NameMax. demand (~2003)Max. demand (~2003)Largest Unit (Nuclear)Largest Unit (Nuclear)
DC connectionDC connection
East Japan Grid50Hz, ~80GW
Comb structure due to geographical reasonComb structure due to geographical reason
Institute of Advanced Energy, Kyoto University
Dem
and
(GW
)
HourHour
Grid capacity is almost a half of maximum at early morning.Grid capacity is almost a half of maximum at early morning.
Requirements different in each country.Requirements different in each country.
Electric Grid in JapanElectric Grid in JapanInstitute of Advanced Energy, Kyoto University
Demands in the Demands in the southasiansouthasian countriescountries
ThailandThailand
Peak
Pow
er (M
W)
VietnamVietnam* Source JBIC report 18
CambodiaCambodia LaosLaos
Peak
Pow
er (M
W)
Peak
Pow
er (M
W)
Peak
Pow
er (M
W)
Institute of Advanced Energy, Kyoto University
Fusion startup powerFusion startup power
Power demand in ITER standard operation scenario
Active power
P = ~300MW
dP/dt = ~230MW/s
Reactive power
Q > 600MVA
by on-site compensation
Qgrid = ~ 400MVA
Institute of Advanced Energy, Kyoto University
Power generation controlPower generation control
In Japan, usual value of spinning In Japan, usual value of spinning reserve is ~3% of total generationreserve is ~3% of total generationSpectrum of Demand changeSpectrum of Demand change
TimeTime
Dem
and
Dem
and
Demand curve
Sustained Element
Fringe element
Cyclic element
> ~10min > ~10min ELD or manual ELD or manual
3min< t < 10min 3min< t < 10min AFCAFC
< ~3min < ~3min governorgovernorof each UNIT of each UNIT
(spinning reserve)(spinning reserve)
< ~0.1min< ~0.1min
SelfSelf--regulatingregulating
Institute of Advanced Energy, Kyoto University
Calculation modelCalculation modelThermal Generator
Demand
100km Transmission Line
Fusion Reactor
Hydroelectric Generator
10km
10km
Reference Capacity : 1000MVATransmission Voltage : 115kVSystem capacity : 7-15GWeImpedance per 100km : 0.0023+j0.0534[p.u.]Capacitance : jY/2 = j0.1076[p.u.]
Calculation modelCalculation modelInstitute of Advanced Energy, Kyoto University
050
100150200250
0 10 20 30t ime(sec)
activ
epo
wer(
MW
)
Demand of active power
200MW/s
- 0.16- 0.14- 0.12- 0.10- 0.08- 0.06- 0.04- 0.02
0.00
0 20 40 60 80time(sec)
frequ
ency
(Hz)
12GWe系統
56GWe系統
Frequency deviation
Frequency deviation by Fusion reactor Frequency deviation by Fusion reactor startupstartup
12GWe12GWe GridGrid
5656GWeGWe GridGrid
Institute of Advanced Energy, Kyoto University
- 0.5- 0.4- 0.3- 0.2- 0.10.0
0 20 40 60time(sec)
frequ
ency
(Hz)
5MW/ sec23MW/ sec77MW/ sec230MW/ sec
050
100150200250
0 20 40 60t ime(sec)
activ
epo
wer
(MW
)
5MW/ sec23MW/ sec77MW/ sec230MW/ sec
Grid Capacity: 8.3GWe
Deviation becomes small with decrease of load variation rateThere exists large difference between 23MW/s and
77MW/s
Load variation pattern
Effects of load variation time Effects of load variation time
Frequency deviation
Institute of Advanced Energy, Kyoto University
Influence to the power gridInfluence to the power gridMaximum Frequency Fluctuation [Hz] for 7GW gridMaximum Frequency Fluctuation [Hz] for 7GW grid
Peak Load [M
Peak Load [M
WW]] 0.330.330.300.300.110.11330330
0.160.160.150.150.080.08230230
0.080.080.070.070.050.05130130
23023077772323
Load change rate [MW/s] Load change rate [MW/s]
Maximum Frequency Fluctuation [Hz] for 15GW gridMaximum Frequency Fluctuation [Hz] for 15GW grid
0.060.060.050.050.030.03330330
23023077772323
Load change rate [MW/s] Load change rate [MW/s]
Institute of Advanced Energy, Kyoto University
- 1.2- 1.0- 0.8- 0.6- 0.4- 0.2
0.0
0 20 40 60 80time(sec)
frequ
ency
(Hz)
5MW/ sec23MW/ sec77MW/ sec230MW/ sec
- 1.2- 1.0- 0.8- 0.6- 0.4- 0.20.0
0 20 40 60 80time(sec)
frequ
ency
(Hz)
5MW/ sec23MW/ sec77MW/ sec230MW/ sec
Maximum load : 230MW
・When maximum load exceeds some value, large frequency deviation is observed.(Setting of spinning reserve configuration largely affects )
・If variation rate is small, 330MW demand which is almost same as spinning reserve capacity, does not cause large frequency deviation.
Effects of maximum load value Effects of maximum load value
Grid Capacity: 8.3GWe
Maximum load : 330MW
Institute of Advanced Energy, Kyoto University
The grid capacity of 10The grid capacity of 10--20GW is required to supply startup 20GW is required to supply startup power of ITER like fusion reactor. In the small grid, more thapower of ITER like fusion reactor. In the small grid, more than n the usual value (3% of total capacity) of spinning reserve is the usual value (3% of total capacity) of spinning reserve is required required The influence also depends on the grid configuration, as The influence also depends on the grid configuration, as response time of each power unit is different.response time of each power unit is different.
Response speedResponse speed
No responseNo responseSolar/WindSolar/Wind
not allowed now in Japannot allowed now in JapanNuclearNuclear
slow 1%/min slow 1%/min CoalCoal
5%/min 5%/min OilOil
fast 10~50%/minfast 10~50%/minHydroHydro
Effects of grid configurationEffects of grid configurationInstitute of Advanced Energy, Kyoto University
Fusion role in the gridFusion role in the grid
Thailand Thailand Japan Japan Solar/WindSolar/Wind
HydroHydro
GasGas
OilOil
CoalCoalSolar/WindSolar/Wind
HydroHydro
GasGas
OilOil
CoalCoal
FusionFusion
Solar/WindSolar/Wind
HydroHydro
GasGas
OilOil
CoalCoal
FissionFission
Solar/WindSolar/Wind
HydroHydro
GasGas
OilOil
CoalCoalFusionFusion
FissionFission
Institute of Advanced Energy, Kyoto University
Difference in Grid CompositionDifference in Grid Composition
Kansai, night : 14GWeKansai, daytime : 30GWeThai : 15GWe
Composition of grid
Frequency change
Grid Capacity
・Grid in Thailand is smaller than Kansai, but has more capacity toaccept fusion load.
Change of the Load200MW, 200MW/sec
Institute of Advanced Energy, Kyoto University
05
101520253035
Kansai,night Kansai,day Thai
outp
ut(G
W) Nuclear
HydroFossil fire
-0.16-0.14-0.12-0.10-0.08-0.06-0.04-0.020.00
0 10 20 30time(sec)
frequ
ency
(Hz)
Kansai, NightKansai, daytimeThai
・Large and fast load affects grid.Small capacity cannot respond.
Starting fusion plant can be a major impact on Starting fusion plant can be a major impact on some small grids.some small grids.
-- fusion must minimize startup demand.fusion must minimize startup demand.Response and reserve of the grid are different.Response and reserve of the grid are different.-- grids in developing countries could be grids in developing countries could be suitable for fusion introduction.suitable for fusion introduction.
Fusion must study the characteristics of futureFusion must study the characteristics of futurecustomers.customers.study study ““best mixbest mix”” for each country.for each country.
Conclusion and suggestionsConclusion and suggestionsInstitute of Advanced Energy, Kyoto University
・Carbon-free fuels required- Exhausting fossil resources- Global warming and CO2 emission
・Future fuel use- Fuel cells for automobile- aircrafts
・Dispersed electricity system- Cogeneration- Fuel cell, - micro gas turbine
(could be other synthetic fuels)
Hydrogen market
Aircraft
Automobile
Institute of Advanced Energy, Kyoto University
21000
5
10
15
20
25
2000 2020 2040 2060 2080Year
ElectricitySolid FuelLiquid FuelGaseous Fuel
Ener
gy de
mand
(GTO
E)
Example of Outlook of Global Energy Consumption by IPCC92a
Market 3 times larger than electricity
Substitute fewer than electricity source
Institute of Advanced Energy, Kyoto University
◯Processing capacity・4240t/h waste 280t of H2
◯endothermic reaction converts both biomass and fusion into fuel.・2.5GWt 5.1GWe equivalent with FC(@70%)
Fusion can produce Hydrogen
2120 t/h
H2 280 t/h
600℃
FusionReactor2.5GWth
biomassCO 2.0E+06 kg/hH2 1.4E+05 kg/h
CO2 3.1E+06 kg/h
ChemicalReactor
Heat exchange,Shift reaction
cooler
Turbine
Steam(640 t/h)He
1.16E+07 kg/h
H2O
Proposed reaction : (C6H10O5 )+H2O+814kJ = 6CO+6H26CO+6H2O = 6H2+6CO2 18.6Mt/y waste←60Mt/inJapan
Feeds 1.1M FCV /day or17M FCV/year*
(*assuming 6kg/dayor 460g/year, MITI,Japan)
From 3GW heat efficiency electricity Energyconsumption
Hydrogenproduction
300C-electrolysis 1GW 28 6kJ/ mol 25 t / h900C-SPE electrolysis 1 .5GW 23 1kJ/ mol 44t /h900C-vapor electrolysis 1 .5GW 18 1kJ/ mol 56t /h
33 %50 %50 %
900C-biomass ー ー 60 kJ/ mol 34 0t / h
Energy Eficiency
◯amount of produced hydrogen from unit heat・low temperature(300℃)generation→ conventional electrolysis
・high temperature(900℃)generation→ vapor electrolysis
・ high temperature(900℃) → thermochemicalproduction
Institute of Advanced Energy, Kyoto University
Conversion of Cellulose by HeatInstitute of Advanced Energy, Kyoto University
n(C6H10O5) + mH2O H2 + CO + HCs
0
0.5
1.0
1.5
2.0
2.5
3.0
700 800 900 1000 1100Temperature [℃]
Gas
pro
duct
ion
[×10
-3m
ol]
H2
CO
CH4CO2
Gas flow rate 85ml/sCellulose0.15gVapor concentration 4%
Con
vers
ion
ratio
50%
Current result is 37% conversion efficiency, w/o catalyst.
0
5
10
15
20
25
30
600 650 700 750 800 850 900 950 1000time[s]
The
gas
gen
erat
ion
rate
s[vo
l.%]
0
200
400
600
800
100
120
COCO2CH4H2Tempareture
Heat BalanceInstitute of Advanced Energy, Kyoto University
Absorbed heat was measured with endothermic reaction.
Estimated heat efficiency was ca. 50%. (not limitedby Carnot efficiency)
Measure heat transfer was19 kw/m2.
-80
-30
20
70
120
170
220
270
320
0 50 100 150 200
[Time]
[Tem
pera
ture
diff
eren
ce d
ue to
end
othe
rmic
rea
ctio
n]
8/10-0.05g
8/10-0.15g
8/10-0.3g
0
0.1
0.2
0.3
0.4
0.5
0.6
0 0.1 0.2 0.3 0.4
(C6H10O5)[g]
Hea
t qua
ntity
of e
ndot
herm
ic
reac
tion[
kJ]
(8/10mm) (17/19mm)
100% H2 Generated H2
Hydrogen Production by Fusion
Fusion can provide both high temperature heat and electricity- Applicable for most of hydrogen production processes
There may be competitors…As Electricity
-water electrolysis, SPE electrolysis : renewables, LWR-Vapor electrolysis : HTGR
As heat-Steam reforming:HTGR(800C),
-membrane reactor:FBR(600C)-IS process :HTGR(950C)
-biomass decomposition: HTGR
Institute of Advanced Energy, Kyoto University
Reactor DesignInstitute of Advanced Energy, Kyoto University
Reference reactor designHeat transfer pipes : 20mm diameterHeat exchange surface : 12.5m2/m3 Per unit volume.Height : 20m (reaction section : 10m)Diameter : 10mHeat flux : 19kw/m2Total heat consumption : 170MWProcessing rate :80t/hr (at 100% conversion)of cellulose (dry weight): 210t/hr (at 40% conversion)H2 production rate : 11 t/hr(at 100% efficiency)
4 t/hr(at 30% efficiency)He (high temperature)
Waste Feed(×4)
High temperature steam
Product (CO+H2) gas
HeChar
With fusion reactor generating 2.5GW heat, 25 of above reactor can be operated.
Energy Source Options
renewables LWR fusion(HTGRConv.electrolysis ○ ○ ○Vapor electrolysis × × ○ ×IS process × × ○ ×Steam reforming × × ○Biomass hydrogen × × ○
For hydrogen production, some energy sources provide limited options.
Institute of Advanced Energy, Kyoto University
Renewables (PV, wind, hydro) cannot provide heat.LWR temperature not suitable for chemical process.
Fusion (with high temperature blanket) has stronger advantagein hydrogen production applications.
Advantage of fusion over other energy
○Possible high temperature・impossible for PV, wind or LWRs.・higher than FBR.・Equivalent to HTGR.
Institute of Advanced Energy, Kyoto University
○Site and location, deployment in developing country・less limitation of nuclear fuel cycle, nuclear proliferation.・while nuclear policies differ by the governments, fusionis internationally pursued.・possible location near industrial area.・independent from natural circumstance.
Institute of Advanced Energy, Kyoto UniversityUse of Fusion Heat
Blanket option temperature technology efficiency challenge
WCPB 300 ℃ Rankine 33% proven
HCPB/HCLL ~500℃ Rankine ~40% proven
Supercritical 500 ℃ SCW >40% available
DCLL ~700℃ SC-CO2 ~50% GEN-IV
LL-SiC 900℃ SC-CO2 50% IHX?
900℃ Brayton ~60% GEN-IV
900℃ H2 ?? ??
Blanket and generation technology combinationrequires more consideration.
Development of SiC-based intermediate heat exchanger started.
mill/
kWh
65
92109
125
0
25
50
75
100
125
150
2050 2060 2070 2080 2090 2100
year
Poss
ible
Intro
duct
ion
price
145
Fusion is introduced into the market at this crossover probably with fossil.
When fusion will be used?Institute of Advanced Energy, Kyoto University
Possible introduction price of Fusion :increases with time as fossil price increases.
Current target of the development
year
pric
e
technology
resource
renewable
Investment and contribution factor
・various sponsors provide funding・fusion must look for sponsors from future market.
is it electricity?
1960
transfer
6.2%For R&D
industryutilityResearch
institute
Basic research
Fission reactor casesales
Further competitivenessimprovements
commercialization
Researchinstitutes
Institute of Advanced Energy, Kyoto University
basic
5.4%
2.4%
1.9%
1.4%
4.0%
5.9%
5.7%
6.8%
8.4%
14.7%
8.1%
6.3%
4.0%
5.4%
5.8%
2.7%
4.0%
0.7%
59.3%
68.4%
78.0%
85.0%
71.6%
66.7%
83.8%
73.5%
95.1%
40.7%
31.6%
22.0%
15.0%
28.4%
33.2%
16.3%
26.6%
5.0%
26.0%
23.5%
15.7%
11.0%
23.0%
27.4%
13.6%
22.6%
4.3%
R&D/total sales
Basicresearch
appliedresearch
commercialdevelopmentIndustry
Chemical
ceramics
steel
Metal
machinery
electricalElectronic/instruments
Fine machinery
softwares
Research contribution
R&D budget to total sales
ConclusionInstitute of Advanced Energy, Kyoto University
Socio-economic study suggests more advantages andTechnical challenges for fusion.
For electricity generation, characteristics of fusion shouldbe improved in terms of grid operation.
Hydrogen production has advantage, but needs significant development.-market study-components and processes-material, tritium contamination
High temperature blanket and energy application may bekey issues.
What will happen in Reactor Design Studies
International activities toward DEMO- Updated plasma data from physics- Concepts on timetable (within 25 years?)- “Broader Approach” activity
Needs to respond to Socio-Economic requirements- safety- electricity cost and quality- hydrogen production
Correlated technology developments- high temperature blankets- power conversion- high temperature divertor- tritium compatible power train
Institute of Advanced Energy, Kyoto University