Upload
nicole
View
24
Download
0
Tags:
Embed Size (px)
DESCRIPTION
FUNDAMENTAL BEHAVIOR OF COMPOSITE MEMBERS UNDER FIRE LOADING. Amit H. Varma Assistant Professor School of Civil Engineering, Purdue University Contributors: Victor Hong, Ph.D. Student at Purdue University Guillermo Cedeno, Ph.D. Student at Purdue University - PowerPoint PPT Presentation
Citation preview
FUNDAMENTAL BEHAVIOR OF COMPOSITE MEMBERS UNDER FIRE LOADING
Amit H. Varma
Assistant Professor
School of Civil Engineering, Purdue University
Contributors:
Victor Hong, Ph.D. Student at Purdue University
Guillermo Cedeno, Ph.D. Student at Purdue University
Jarupat Srisa-Ard, M.S. Student at Michigan St. Univ.
PRESENTATION OUTLINE
• Current Knowledge Base and Issues
• Research Goals and Objectives
• Behavior of Composite CFT Columns Under Fire Loading
• Analytical models, investigations, and findings
• Need for fundamental measures of behavior under fire loading
• Analytical investigations of fundamental behavior
• Experimental investigations of fundamental behavior
• Conclusions so far
• Future research needs and capabilities
CURRENT KNOWLEDGE BASE
Current building codes emphasize prescriptive fire resistant
design provisions that are rooted firmly in the standard
ASTM E119 fire test of building structure components. The standard fire test determines the fire resistance rating FRR
of structural components for comparative purposes. It does not provide knowledge or data of the fundamental
behavior of structural components that can be used to calibrate
analytical models.
This design paradigm has been challenged by several
engineers and researchers over the years.
More recently, NIST BFRL researchers have conducted an
exhaustive investigation of the 9/11 WTC collapse. They
have developed twenty-nine major recommendations for
future work.
ISSUES Three of these recommendations R5, R8, and R9 are
extremely important for building design (structural) engineers. R5 - The technical basis for the ASTM E119 standard fire test
should be improved. R8 - The fire resistance of structures should be enhanced by
requiring a performance objective that uncontrolled building fires
result in burnout without local or global failure /collapse. R9.1 – Develop and validate analytical tools, guidelines, and test
methods necessary to evaluate the fire performance of the
structure as a whole system. R9.2 – Develop performance-based standards and code
provisions, as an alternative to current prescriptive design
methods, to enable the design and retrofit of structures to resist
real building fire conditions.
Our current research focuses on R9.1 – because it is my area
of expertise as a structural engineer
EXPLORATORY RESEARCH GOALS
We initiated an exploratory study (2002) of the fire behavior of
structural components to: Develop an understanding of the current knowledge base Develop analytical approaches for predicting and investigating
behavior Determine the type of knowledge or data needed to develop and
validate analytical models that can be used to investigate the
behavior of complete structural systems
We selected a structural component to explore these questions Composite concrete filled steel tube (CFT) columns
Why? Combines both steel and concrete materials – of interest to industry. Area of significant expertise for the researcher (seismic behavior of
CFTs) CFT columns are considered to have good fire resistance due to the
presence of concrete Lots of data from various sources.
PRIOR EXPERIMENTAL RESEARCH
Standard ASTM E119 fire behavior of CFT columns
investigated by researchers in Canada (NRC), China, and
Japan
Experiments conducted in expensive and specially-built
column furnaces in these countries Column placed in the furnace. Fix-end boundary conditions Subjected to axial force Furnace air follows the ASTM E119 T-t curve
Columns expand, then contract, and eventually fail mostly
by columns buckling No fire protection material needed Lack of clarity regarding loads and boundary conditions
achieved in the experiments Experimental results are limited to the overall displacement-
time response and temperatures through the section
TYPICAL EXPERIMENTAL BEHAVIOR
Expansion
Reversal
Sustenance
Buckling failure
TYPICAL CFT COLUMNS L > 10 b
Circular as well as square CFTs
NRC Researchers in Canada
PRIOR ANALYTICAL MODELS
Heat transfer analysis: Finite difference method (FDM)
simulations of heat transfer from furnace air to column surfaces,
and then from column surfaces through the sections, using
temperature dependent thermal properties (Lie and Irwin 1995)
Structural analysis: Fiber model simulation of the column
buckling behavior. Cross-section modeled using elements with
uniaxial -T behavior. Assumptions include: plane sections remain plane, linear curvature variation along column length, no slip, and no transverse interaction between the steel and
concrete.
No basis presented for making these simplifying assumptions
Such models do not provide knowledge of fundamental behavior
or complex stress and strain states at elevated temperatures
ANALYTICAL APPROACH
Need a more general and more robust analytical approach
to model the fire behavior of structural members.
We use a three step sequentially coupled analytical
approach, where the results from each step are required to
continue the analysis in the subsequent step.
Step I - Fire Dynamics Analysis is conducted to simulate the
convection and radiation heat transfer from the fire source
to the surfaces of the structural component. It is conducted
using FDS, which is a program developed by NIST BFRL
researchers.
Step II – Nonlinear Heat Transfer Analysis is conducted to
simulate the heat transfer through the section and along
the length. It is conducted using 3D finite element models
and nonlinear temperature-dependent thermal properties
ANALYTICAL APPROACH
Step II – Nonlinear Heat Transfer Analysis (continued) The results from Step I (surface T-t curves) serve as thermal
loads The results from Step II include the temperature histories (T-t)
for all nodes of the finite element model
Step III – Nonlinear Stress Analysis is conducted to
determine the structural response of the component for the
applied structural and calculated thermal loads. It is conducted using 3D finite element meshes that are
identical or similar to the heat transfer analysis meshes, and
nonlinear temperature -dependent material models The nodal temperature histories from Step II define the thermal
loads for this analysis
ANALYTICAL MODELING
CFT columns tested by researchers from different parts of
the world NRC Canada (1-3), Sakumoto et al. from Japan using FR steel (4, 5) Han et al. from China (6-10)
Column
Cross-Section Length fy f'c Load Eccentricity Fire
(mm x mm x mm) (mm)Re-bar (MPa
) (MPa) (kN) (mm) Protection
1 200x200x6.35 3810 4 x 16 mm 350 47 500 0 -
2 250x250x6.35 3810 4 x 16 mm 350 47 1440 0 -
3 300x300x6.35 3810 4 x 25 mm 350 47 2000 0 -
4 300x300x9 3500 - 357.9 2020 0 -
5 300x300x9 3500 - 357.9 37.5 1350 0 ceramic
6 300x200x7.96 3810 - 341 49 2486 0 spray-type
7 300x150x7.96 3810 - 341 49 1906 0 spray-type
8 219x219x5.30 3810 - 246 18.7 950 0 spray-type
9 10
350x350x7.70 3810 - 284 18.7 2700 0 spray-type
350x350x7.70 3810 - 284 18.7 1670 52.5 spray-type
Results from Step 1 FIRE DYNAMICS ANALYSIS
FDS model of the furnace. Used to predict the surface T-t
curves for 200, 250, and 300 mm CFT columns that were
tested at NRC. The FDS predictions compare well with the experimentally
measured and FDM predicted T-t curves. FDM is less
conservative Surface T-t curves are slightly lower than the ASTM E119 T-t
curves The column size (200-300 mm) seems have small influence
(b)
Quarter volum
e of CFT column
(a)
Quarter volum
e of CFT column
Hot air flow direction
(a)
Symmetry plane
Symmetry plane
Heated wall
Heated w
all
Hot air flow direction
Hot air
flow direction
Quarter volume of CFT column
(b)
Figure 1. FDS model of NRC Furnace with CFT column
(a)
Symmetry plane
Symmetry plane
Heated wall
Heated w
all
Hot air flow direction
Hot air flow
direction
Quarter volume of CFT column
0
200
400
600
800
1000
1200
0 30 60 90 120 150
Time (min)
Te
mp
era
ture
(C
)
ASTM E119
FDS
ExperimentFDM
Results from Step IIHeat Transfer Analysis
The heat transfer analysis models were developed and
analyzed using ABAQUS. The steel and concrete
temperature dependent thermal properties Lie and Irwin
(1995) The latent heat of water was included in the model The results from the heat transfer analysis were found to
compare well with the experimental results !
0
200
400
600
800
1000
1200
0 30 60 90 120 150Time (min)
Te
mpe
ratu
re (
C)
C2, surface, calculatedC2, surface, measuredC2, d=60mm, calculatedC2, d=60mm, measured
250 mm CFT
0
200
400
600
800
1000
1200
0 30 60 90 120 150 180 210 240
Time (min)
Tem
pera
ture
(C)
C3, surface, calculated
C3, surface, measured
C3, d=37mm, calculated
C3, d=37mm, measured
300 mm CFT
0
200
400
600
800
1000
1200
0 30 60 90 120 150 180
Time (min)
Te
mp
era
ture
(C
)
C1, surface, calculatedC1, surface, measuredC1, d=71mm, calculatedC1, d=71mm, measured
200 mm CFT
MATERIAL PROPERTIES – T Dependent
Temperature dependent thermal and structural material
properties were used along with the 3D finite element
models These material properties were based on values generally
reported in the literature (Lie and Irwin 1995 etc.).
900oC
700oC
500oC
300oC
100oC
0
100
200
300
400
0 0.002 0.004 0.006 0.008 0.01
Strain (mm/mm)
Str
ess
(MP
a)
Steel --T
0
10
20
30
40
0.000 0.010 0.020 0.030 0.040
Strain (mm/mm)
Str
ess,
MP
A
500o
C600o
C
700o
C
800o
C
400o
C
Concrete --T
T=100oC
T=300oC
T=500oC
T=700oC
T=900oC
Results from Step IIINonlinear Stress Analysis
Column failure mode at elevated temperatures global buckling and local buckling mixed similar to experiments
Results from Step IIINonlinear Stress Analysis
The results from the nonlinear stress analysis seem to have
some variation from the experimental results.
200x 200x 6.35mm CFT
Fy=350; f’c=47 MPaL=3.8 m; P/Po=15%
250x 250x 6.35mm CFT
Fy=350; f’c=47 MPaL=3.8 m; P/Po=30%
300x 300x 6.35mm CFT
Fy=350; f’c=47 MPaL=3.8 m; P/Po=33%
NRC Column Tests
??
?
X
Comparisons with experimental results are somewhat
reasonable!
0
5
10
15
20
25
30
0 40 80 120 160 200
Time (min)
Ax
ial
Dis
pla
cem
ent
(mm
)
Calculated
Measured
-30
-20
-10
0
10
20
30
0 10 20 30 40
Time (min)
Axi
al D
ispl
acem
ent (
mm
)
Calculated
Measured
300x 300x 9mm CFT
Fy=358; f’c= ---L=3.5 m; P/Po=80%
FR Steel Japanese Column Tests
300x 300x 9mm CFT
Fy=358; f’c=37 MPa
L=3.5 m; P/Po=25%
Results from Step IIINonlinear Stress Analysis
Results from Step IIINonlinear Stress Analysis
Tests done by Han et al. in China. Again comparisons have
issues.300x 200x 8mm CFTFy=341; f’c= 49
L=3.8 m; P/Po=50%
300x 150x 8mm CFTFy=341; f’c= 49
L=3.5 m; P/Po=45%
219x 219x 5.3mm CFTFy=246; f’c= 19
L=3.5 m; P/Po=41%
350x 350x 7.7mm CFTFy=284; f’c= 19
L=3.5 m; P/Po=56%
350x 350x 7.7mm CFTFy=284; f’c= 19
L=3.5 m; P/Po=34% ecc.
Results from Step IIINonlinear Stress Analysis
Authors claim pin end conditions were achieved in the
furnace column tests, and then provide the following picture
of the buckled specimen
PIN FIX
SENSITIVITY ANALYSIS
Parametric studies were conducted to determine the
sensitivity of column behavior with respect to various
parameters: (1) Boundary Conditions (2) Steel and concrete material properties as functions of T (3) Axial load level (4) Geometric imperfections
Column behavior at elevated temperatures is too sensitive to end conditionsNRC Column 1
NRC Column 2
Pin
Inter
Fix Pin
Inter Fix
SENSITIVITY ANALYSIS
Column behavior at elevated temperatures is too sensitive
to the applied axial load. Fluctuations in axial load can cause
variation
The sensitivity of column behavior to elevated temperature
material --T models is currently ongoing
P
P +0.05Po
P-0.05Po
P-0.10Po
P
P + 0.05Po
P-0.05Po
P-0.10Po
FINDINGS FROM EXPLORATORY PROGRAM
The three step analytical approach with FDS and 3D finite
element models for heat transfer and stress analysis can be
used to predict the behavior of members under fire loading. The results from FDS and heat transfer analysis compare
favorably with experimental data. The results from stress
analysis, however have significant variations. The behavior of columns at elevated temperatures is
extremely sensitive to the loading and boundary conditions
achieved in the experiments. The experimental results of fire resistance rating must be
considered carefully before any general conclusions are
made. The ASTM E119 gets around this situation by saying that the
members should be tested with the same boundary
conditions as those achieved in a real structure --!
FUNDAMENTAL BEHAVIOR
The experimental results from a standard fire test do not
provide knowledge of the fundamental behavior of
structural members independent of boundary conditions
and other issues.
We need a more fundamental measure, for e.g., the axial
force-moment-curvature P-M--T behavior of the
composite member at elevated temperatures from fire
loading.
This P-M--T behavior defines the fundamental behavior of
the member (sort of like a material -T behavior) and
can be used in a variety of ways to: (a) conduct analytical parametric studies (a) develop and calibrate analytical models, e.g., fiber models (c) predict actual member behavior and failure (d) and to design fire proofing.
FUNDAMENTAL BEHAVIOR – Why?
For example, the behavior and failure of columns under constant
axial load and elevated temperatures from fire loading also depends
on the section
P-M--T response of the failure segment.
-16
-14
-12
-10
-8
-6
-4
-2
0
0 50 100 150Time (min)
Axi
al D
isp
lace
me
nt (
mm
)
0
20
40
60
80
100
120
0 20 40 60 80 100 120Time (min)
Mom
ent (
KN
-m)
P
P
P
M=P
P0
1000
2000
3000
4000
5000
6000
0 100 200 300 400 500Moment (KN-m)
Axi
al F
orce
(KN
)
FUNDAMENTAL BEHAVIOR – Why?
Researchers around the world have developed finite element
method based computer programs to conduct structural
analysis under fire loading. For example, researchers at Liege Univ. (SAFIR), Sheffield Univ.
(FEMFAN), Univ. of Manchester, Nat. Univ. of Singapore (SINTEF)
Most of these programs use fiber-based or concentrated
hinge based beam-column finite elements for modeling the
behavior of columns and beam-columns under fire loading These finite elements must be validated (or calibrated) using
experimental data and realistic P-M--T behavior
ANALYTICAL INVESTIGATIONS
The three-step analytical approach was used to investigate
the fundamental P-M--T behavior of CFT beam-columns
subjected to standard fire loading. The effects of various geometric (width b and width-to-
thickness b/t) parameters and insulation parameters on the
behavior were also evaluated analytically.
CFT beam-columns with parameters: Width b = 200 or 300 mm. Width-to-thickness ratio = 32 or 48 Steel tube A500 Gr. B (300 MPa) Concrete strength (f’c=35 MPa) Axial load levels (P=0, 20%, 40%) Thermal insulation thickness (0, 7.5, 13 mm thick)
PRELIMINARY ANALYTICAL INVESTIGATIONS
The analytical investigations were conducted on a segment
of the CFT beam-columns. The length of the segment was
equal to the cross-section width b. It represents the critical segment of CFT column or beam-
column subjected to axial and flexural loads and elevated
temperatures from fire loading.
CFT WITHOUT INSULATION – THERMAL BEHAVIOR
0
200
400
600
800
1000
1200
0 30 60 90 120 150 180Time (minutes)
Tem
per
atu
re
ASTM E119 T-t No Insulation
Step 1 – Results from FDS Analysis for ASTM E119 T-t curve
Step 2 – Results from heat transfer analysis
Surface Temperature =300oCTime = 5.6 mts.
Surface Temperature =600oCTime = 14.2 mts.
Structural Response – CFT without ins.
0.00
30,000.00
60,000.00
90,000.00
120,000.00
150,000.00
0 0.005 0.01 0.015 0.02 0.025
Curvature (1/mm)
Mom
ent (N
-m)
2.5E-5 5.0E-5 7.5E-5 10.0E-5 12.5E-5
P/Po=20%, T=20oC
P/Po=20%, T=300oC
P/Po=20%, T=600oC
P/Po=20%, T=900oC
P/Po=0%, T=20oC
P/Po=0%, T=300oC
P/Po=0%, T=600oC
P/Po=0%, T=900oC
Step 3 – P-M--T curves for CFT without insulation
0.0
0.3
0.6
0.9
1.2
0 200 400 600 800 1000 1200Temperature (T)
Mom
ent/
Mom
ent
@ 2
0o C
(M/M
20)
P=20%, No Insul
P=0, No Insul
Findings for CFTs Without Insulation
For CFTs without insulation: Fire loading results in quick heating of the steel tube
(broiling) while the concrete infill remains relatively
cooler. Significant portions remain at T< 100oC till much
later This relative heating causes rapid reduction in flexural
stiffness and strength of the CFT section under fire
loading effects This reduction depends primarily on the rise in steel
temperature, and is independent of axial load level,
width, and other parameters
This by itself, may not be a cause of concern unless the
demands placed on the CFT without insulation exceed the
reduced stiffness and strength at elevated temperatures
CFT WITH INSULATION – THERMAL BEHAVIOR
Consider CFTs with some insulation. Assume commonly used
insulation materials – gypsum cement The presence of thermal insulation results in a slow increase
in the steel surface temperature.
0
200
400
600
800
1000
1200
0 30 60 90 120 150 180Time (minutes)
Te
mpe
ratu
re
ASTM E119 T-t No InsulationInsulation = 13 mm Insulation=6.5 mm
Steel surface w/o insulation
Steel surface with insulation
Insulation thick = 6.5 mmTime=180 mts
Insulation thick = 13.0 mmTime=180 mts
The heating of the composite CFT section becomes more uniform (not broiling)
Structural Response of CFT with Insulation
0
30,000
60,000
90,000
120,000
150,000
0 0.005 0.01 0.015 0.02 0.025
Rotation (rad.)
Mo
me
nt
(N-m
)
P-M--T curves for CFT with b/t=32
Ins. Thick = 13 mm
Ins. Thick = 6.5 mm
Ambient T=20oCP/Po=0
P/Po=20%
P/Po=40%
P/Po=0P/Po=20%
P/Po=40%
P/Po=0
P/Po=20%
P/Po=40%
2.5E-5 5.0E-5 7.5E-5 10.0E-5 12.5E-5
Curvature (1/mm)
0
30,000
60,000
90,000
120,000
150,000
0.000 0.005 0.010 0.015 0.020 0.025
Rotation (Rad.)
Mo
men
t (N
-m)
P-M--T curves for CFT with b/t=48
Ins. Thick = 13 mm
Ins. Thick = 6.5 mm
Ambient T=20oCP/Po=0
P/Po=20%
P/Po=40%P/Po=0P/Po=20%
P/Po=40%
P/Po=0
P/Po=20%
P/Po=40%
2.5E-5 5.0E-5 7.5E-5 10.0E-5 12.5E-5
Curvature (1/mm)
0
10
20
30
40
50
0 0.2 0.4 0.6 0.8 1 1.2
Moment /Moment @ P=0
Ax
ial L
oad
Lev
el P
/Po %
Ins=13 mm
Ins=6.5 mm
T=20oC
b=200 mm, b/t=32
b=200 mm, b/t=48
b=300 mm, b/t=32
Normalized Strength P-M Interaction
CFTs with Insulation
The insulation thickness becomes the most important
parameter influencing P-M--T behavior and strength (P-M)
under elevated temperatures from fire loading.
As expected, CFTs with b/t =48 have greater increase in
moment capacity with increase in axial load (below the
balance point). This continues to be true at elevated
temperatures also.
The tube width (b) and width-to-thickness (b/t) ratio do not
have significant influence on the P-M--T behavior of CFTs at
elevated temperatures from fire loading
FAILURE MODE
Material inelasticity combined with local buckling produce
failure
Stress analysis results for CFT with b/t=32, axial load level = 20%, and insulation thickness=6.5 mm (curvature = 12.5 x 10-5 1/mm)
Steel tube longitudinal strain Steel tube longitudinal stress
Concrete longitudinal strain Concrete longitudinal stress
(Pa)
(Pa)
Longitudinal Strain Longitudinal Stress (Pa)
Longitudinal Stress (Pa)Longitudinal Strain
Steel Tube Steel Tube
Concrete Infill Concrete Infill
Steel tube longitudinal strain Steel tube longitudinal stress
Concrete longitudinal strain Concrete longitudinal stress
(Pa)
(Pa)
Steel tube longitudinal strain Steel tube longitudinal stress
Concrete longitudinal strain Concrete longitudinal stress
(Pa)
(Pa)
Longitudinal Strain Longitudinal Stress (Pa)
Longitudinal Stress (Pa)Longitudinal Strain
Steel Tube Steel Tube
Concrete Infill Concrete Infill
EXPERIMENTAL INVESTIGATIONS
Real challenge is to determine this fundamental P-M--T behavior of
a structural member experimentally. This has never been done
before (although a group of researchers from U.K. considered it) Need experimental data to validate the analytical approach and models Need experimental data to show that the fundamental P-M--T behavior
can be measured in the laboratory – efficiently
The experimental investigations are being conducted in two phases: Phase I – focusing on the thermal behavior of CFT beam-columns Phase II – focusing on the structural behavior of CFT beam-columns
The results from Phase I will be used to validate or calibrate the
nonlinear heat transfer analysis models of the CFT (Step II).
The results from Phase II will be used to validate the nonlinear
stress analysis models developed in Step III.
HEAT TRANSFER EXPERIMENTS The heat transfer experiments are being conducted on short (36
in. long) CFT stub columns. The specimens are 12 x 12 in. in cross-section with different b/t ratios (32, or 48).
The parameters considered in the heat transfer experiments are: Gypsum plaster thickness (0.25 and 0.50 in.) Concrete strength f’c (5 ksi and high strength 10 ksi), and Presence of reinforcement bars.
Twelve CFT short stubs were tested by subjecting them to elevated temperatures simulating fire loading. For now, the surface of the gypsum plaster was controlled to follow the ASTM E119 T-t curve.
The heating was applied using ceramic fiber radiant heaters. These heaters integrate high temperature iron-chrome-aluminum (ICA) heating element wire with ceramic fiber insulation, and can provide surface temperatures up to 1200oC when placed close (250 mm) to them. They can controlled to follow specified T-t or heat flux-time curves
using Watlow F4 PID controllers with communications.
HEAT TRANSFER EXPERIMENTS
Test setup and thermocouple layout. Since this is only a heat
transfer experiment, there are no loads acting on the CFT
Thermocouple locations
3ft
6”
6”
6”
2”
2”
2”
2” 1”
2”4”
3” 2”
Heated Area
Concrete pedestal
CFT stub
Heating equipment
EXPERIMENTAL RESULTS
Experimental results indicate that the heating system does
an excellent job of subjecting the gypsum surface to the T-t
curve
0
100
200
300
400
500
600
700
800
900
1000
1100
0 50 100 150 200
Time (min)
Tem
pe
ratu
re (
C)
Gypsum surface specified Gypsum
surface measured
Steel surfaces measured
CFT 12 x 12 x 3/8 in. A500 Gr.-B, f’c=5 ksi, Gypsum thickness = 0.5 in.
EXPERIMENTAL RESULTS The experimental results included T-t curves measured at
various locations (steel surfaces, concrete depths) in the
section. A 3D finite element model was built to perform the heat
transfer analysis. The results from the heat transfer analysis
are compared
COMPARISON OF EXPERIMENTAL RESULT WITH RESULTS FROM HEAT TRANSFER MODEL
0
50
100
150
200
250
300
350
400
450
0.00 25.00 50.00 75.00 100.00 125.00 150.00 175.00 200.00Time (min)
Tem
per
atu
re (
c)
ABAQUS 4 in conc. 4in S2 ABAQUS 3 in conc. 3 in S1 conc. 2 in S1
conc. 2 in S3 conc. 2 in S4 ABAQUS 2in conc. 1 in S3 ABAQUS 1 in
COMPARISON OF EXPERIMENTAL RESULT WITH RESULTS FROM HEAT TRANSFER MODEL
0
50
100
150
200
250
300
350
400
450
0 25 50 75 100 125 150 175 200TIME (MIN)
TE
MP
ER
AT
UR
E (
C)
steel exp. 1 steel exp 2 steel exp. 3steel exp. 4 abaqus steel temp
EXPERIMENTAL RESULTS
Similar results and comparisons were obtained for the
twelve short CFT specimens. The experimental results are
being used to calibrate the nonlinear heat transfer analysis
models – work in progress.
HEATERS IN ACTION
HEATERS IN ACTION
EXPERIMENTAL INVESTIGATIONS
In Phase II, the CFT beam-column specimen is tested by: Applying axial load (15-30% of Po) The axial load is maintained constant over the remaining of the
test. The axial loading and hydraulic setup can accommodate
movement while maintaining constant axial force. The heating is applied to the segment close to the base of the
CFT specimens. The heating is applied using four ceramic fiber
radiant heaters that are position around the base segment. The base of the CFT specimens is protected using gypsum
plaster that is embedded in metal lath. This is the procedure we
used for our experiments The heaters are controlled to subject the gypsum surface to the
ASTM E119 T-t curve for now. After two hours of heating, the CFT beam-column is pushed
laterally at the top. This causes maximum bending and failure
of the heated segment of the base
EXPERIMENTAL INVESTIGATIONS
TEST SETUP
H o l l o w C o r e J a c k
A x i a l L o a d i n g B e a m
A x i a l T e n s i o n R o d
H y d r a u l i c R a m D i r e c t i o n
C l e v i s
S t e e l B a s e P l a t e
C o n c r e t e B l o c k
CFT
CFT
AXIAL LOADING
LATERAL LOADING
P
H
Column BASE
EXPERIMENTAL INVESTIGATIONS
HEATERS
PID Controllers
Heater in Action
EXPERIMENTAL INVESTIGATIONS
STATIC PUSHOVER
End of test. Lateral displacement = 8 in.
Local buckling failure
Local buckling failure
SENSOR DISTRIBUTION
How to measure deformations at very high temperatures? Close-range photogrammetry combined with digital image
processing techniques. This method has been used recently for
medical and microstructure investigation type application. High precision digital camera – looking at a target that is on the
specimen. The camera and data acquisition acquire images and
used digital image processing to compute the x, y, and z
movement of the target point. Accuracy can be as high as 0.001 in. depending on the view
area (1 in.), lighting condition, etc. Much lower resolutions are
possible as sub-pixelation is employed by the software. We are using 8 digital cameras to track and measure the
deformations of the heated failure segment at the base of
the column. The average curvature and rotation over the segment is
calculated using these measurements
* *
* *
1ft
1ft
1ft
1ft
1ft
Lateral Displacement
Camera Sensor Locations
Rotation-meter location
Vertical Displacement
SENSOR DISTRIBUTION
EXPERIMENTAL RESULTS
CFT 10 x 10 x ¼ in. A500 Gr.-B steel (46 ksi), 5.0 ksi
concrete Fire protection with ¼ in. of gypsum Axial load = 15% Po
2 hours of ASTM E119 heating (steel surface T=550oC)Lateral Force vs. Displacement at Top
0
10
20
30
40
50
60
0 1 2 3 4 5 6 7 8
Displacement (inch)
For
ce (
kip)
Ambient
Heated
EXPERIMENTAL RESULTS
Comparing M--T behavior of the 10 in. CFTs. Curvature
obtained from photogrammetric measurementsMoment - Curvature Relationship
y = 472762x
R2 = 0.8529
y = 147691x - 65.599
R2 = 0.9534
0
50
100
150
200
250
300
350
0 0.001 0.002 0.003 0.004 0.005 0.006 0.007 0.008 0.009
Curvature (1/inch)
Mo
me
nt
(kip
-ft)
TEST MATRIX
Test matrix includes fourteen total CFT specimens that will
be tested at ambient and heated temperatures Parameters being considered:
Size of column (b) = 250 and 300 mm. Tube width-to-thickness (b/t) ratio = 32, 48 Axial load level (P=15% or 30% Po) Fire protection thickness (0.25 and 0.50 in.) Some repeat specimens
Experiments are ongoing – Complete by Summer 06. Validation of analytical models using experimental results –
Complete by Fall 06. Determined the fundamental force-deformation-temperature
behavior of composite beam-columns
FINDINGS
A unique experimental approach was developed to
determine the fundamental behavior of composite CFT
beam-columns This approach builds upon years of experimental research,
the PIs expertise, and the requirements of the problem The heating approach works well for the application we
tested The close-range photogrammetry measurements work well
for measuring deformations at elevated temperatures The experimental data needs to be improved with higher
rates of cycling.
Where do we go from here?
R9.1 – Develop and validate analytical tools, guidelines, and
test methods necessary to evaluate the fire performance of
the structure as a whole system.
In this research we focused on developing an analytical
approach and unique experimental approach that can be
used to predict the fundamental force-deformation-
temperature behavior of members.
Analytical fiber beam-column elements can be calibrated to
the experimental and analytical data developed using the
approach outlined. Then, the validated beam-column
elements can be used while predicting the fire performance
of structures as whole system