33
3BTG811792-3032 / A Page 1 Functional Description PID01 - Closed Loop Controller Version 5.2-0

Functional Description - PID01

Embed Size (px)

Citation preview

Page 1: Functional Description - PID01

3BTG811792-3032 / A Page 1

Functional Description

PID01 - Closed Loop Controller Version 5.2-0

Page 2: Functional Description - PID01

3BTG811792-3032 / A Page 2

NOTICE

The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document.

In no event shall ABB be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, nor shall ABB be liable for incidental or consequential damages arising from use of any software or hardware described in this document.

This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party nor used for any unauthorized purpose.

The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.

TRADEMARKS

Copyright © 2012 ABB

All rights reserved.

Release: February 2012

Document number: 3BTG811792-3032

Page 3: Functional Description - PID01

3BTG811792-3032 / A Page 3

Table of Contents

Section 1 - Introduction .................................................................................. 5

General ......................................................................................................................... 5

Section 2 - Function Block & Data Types ..................................................... 7

Function Block............................................................................................................. 7 Data Types ................................................................................................................... 9

PID01_InPar ..................................................................................................................... 9 PID01_OutPar .................................................................................................................. 9 PID01_Opr ...................................................................................................................... 10

Permission ................................................................................................................. 11

Section 3 - Function ...................................................................................... 13

Control Modes ........................................................................................................... 13 Balance Mode ................................................................................................................ 13 Manual Mode ................................................................................................................. 13 Auto Mode...................................................................................................................... 13 E1 and E2 Mode ............................................................................................................. 14 E3 Mode ......................................................................................................................... 14

Control Algorithm ...................................................................................................... 14 Control Deviation .......................................................................................................... 14 Transfer Function .......................................................................................................... 15 Reverse Action .............................................................................................................. 15 Feed Forward ................................................................................................................. 16 External Feedback ......................................................................................................... 16

Range ......................................................................................................................... 16 Setpoint Limitation .................................................................................................... 16 Output Limitation....................................................................................................... 17 Ramp Function .......................................................................................................... 17 Tracking ..................................................................................................................... 17 Alarm Limits ............................................................................................................... 18 Interlocks ................................................................................................................... 18 External Control......................................................................................................... 19 Gain Scheduling ........................................................................................................ 19 Simulation .................................................................................................................. 19 Interaction Window ................................................................................................... 19 Text Configuration ..................................................................................................... 22

Section 3 - Operator Function...................................................................... 25

Process Display ......................................................................................................... 25 Faceplate .................................................................................................................... 26

Aspect Link .................................................................................................................... 26 Reduced Faceplate and Faceplate ............................................................................... 26

Page 4: Functional Description - PID01

3BTG811792-3032 / A Page 4

Extended Faceplate ....................................................................................................... 27 Interlock Display ........................................................................................................ 31 Object Display............................................................................................................ 31 Object Trend Display ................................................................................................. 32 Alarm & Event ............................................................................................................ 32

Alarm & Event List ........................................................................................................ 32 Alarm Message .............................................................................................................. 32 Event Message .............................................................................................................. 32

Page 5: Functional Description - PID01

3BTG811792-3032 / A Page 5

Section 1 - Introduction

General PID01 is a functional unit for closed loop process control analog input in ControlIT, to be

operated from 800xA System. A PID01 normally performs a complete function independently.

PID01 has the following functions and properties: Different control modes, set by operator or by control logic Bumpless change between different control modes Controllable change rate of setpoint & output Setpoint & output limitation Setpoint tracking High & low limits supervision Interlocks function P, PI, PD or PID control algorithm External control parameters which can be used for gain scheduling Feed forward Alarm & Event detection and handling

Page 6: Functional Description - PID01

3BTG811792-3032 / A Page 6

Page 7: Functional Description - PID01

3BTG811792-3032 / A Page 7

Section 2 - Function Block & Data Types

Function Block Name Data Type Attributes

Direction

FD Port

Initial value Description

Name string coldretain in yes 'PID01' Object name Description string coldretain in yes 'Descr' Object description Enable bool coldretain in yes true Enable object TrackA dint coldretain in yes 1 Selection of tracking reference TrackB dint coldretain in yes 1 Selection of how to track TrackC dint coldretain in yes 0 Selection of tracking reference for

external setpoint RevAct dint coldretain in yes 1 Reverse control action Deriv dint coldretain in yes 0 Selection of derivation FeedFwd real retain in yes Added output value for feedforward MV real retain in yes Measured Value AIErr dword retain in yes 16#C0 MV status Speed1 real coldretain in yes 2.0 Max setpoint change rate in Auto mode

(unit/s) Speed4 real coldretain in yes 20.0 Max output change rate (unit/s) ManEnbl bool coldretain in yes true Enable Man mode AutoEnbl bool coldretain in yes true Enable Auto mode E1Enbl bool coldretain in yes Enable E1 mode E2Enbl bool coldretain in yes Enable E2 mode E3Enbl bool coldretain in yes Enable E3 mode ExtRef1 real retain in yes External reference setpoint in E1 mode ExtRef2 real retain in yes External reference setpoint in E2 mode ExtRef3 real retain in yes External reference setpoint in E3 mode Speed2 real coldretain in yes 2.0 Max setpoint change rate in E1 mode

(unit/s) Speed3 real coldretain in yes 2.0 Max setpoint change rate in E2 mode

(unit/s) SeqE1 bool retain in yes Order mode to E1 SeqE2 bool retain in yes Order mode to E2 SeqE3 bool retain in yes Order mode to E3 Local bool retain in yes Order mode to Local BalIn bool retain in yes Order mode to Balance SeqMan bool retain in yes Order mode to Man SeqAuto bool retain in yes Order mode to Auto BalRef real coldretain in yes 0.0 Balance Reference Clamp bool retain in yes Order mode to Clamp ClampRef real coldretain in yes 0.0 Clamp Reference EOLim bool retain in yes Enable external output limit EOLL real coldretain in yes 0.0 External Output Low Limit EOHL real coldretain in yes 100.0 External Output High Limit IB1 bool retain in yes true Process Interlock 1 IB2 bool retain in yes true Process Interlock 2 IB3 bool retain in yes true Process Interlock 3 IB4 bool retain in yes true Process Interlock 4 IB1Ref real coldretain in yes 0.0 Reference for Process Interlock 1

Page 8: Functional Description - PID01

3BTG811792-3032 / A Page 8

Name Data Type Attributes Directi

on FD

Port Initial value Description

IB2Ref real coldretain in yes 0.0 Reference for Process Interlock 2 IB3Ref real coldretain in yes 0.0 Reference for Process Interlock 3 IB4Ref real coldretain in yes 0.0 Reference for Process Interlock 4 ActPos real retain in yes Actuator position AlcBlk bool retain in yes Block alarm AlarmAck bool retain in yes Acknowledge alarm ExtResetFB real retain in yes External reset feedback ExtResetFBEn bool retain in yes Enable external reset feedback ExtCtrl Ext_Control by_ref in yes External control MVAlarms Alarm4Limit by_ref in yes MV alarm configuration DevAlarms Alarm2Limit by_ref in yes Deviation alarm configuration InPar PID01_InPar by_ref in yes In Parameter EventName string coldretain in yes '||PID01_' Event name AutoSP real retain out yes Auto setpoint WSP real retain out yes Working setpoint Dev real retain out yes Deviation OutP real retain out yes Output Sim bool retain out yes Simulation mode Bal bool retain out yes Balance mode Man bool retain out yes Man mode ManFd bool retain out yes Man Forced mode Auto bool retain out yes Auto mode E1 bool retain out yes E1 mode E2 bool retain out yes E2 mode E3 bool retain out yes E3 mode BalOut bool retain out yes Balance Out OutEqLL bool retain out yes Output less than or equal to Low Limit OutEqHL bool retain out yes Output greater than or equal to High Limit SpEqLL bool retain out yes SP less than or equal to Low Limit SpEqHL bool retain out yes SP greater than or equal to High Limit MV_GT_H2 bool retain out yes MV greater than or equal to High High

Limit (H2) MV_GT_H1 bool retain out yes MV greater than or equal to High Limit

(H1) MV_LT_L1 bool retain out yes MV less than or equal to Low Limit (L1) MV_LT_L2 bool retain out yes MV less than or equal to Low Low Limit

(L2) Dev_GT_H bool retain out yes Deviation greater than or equal to High

Limit Dev_LT_L bool retain out yes Deviation less than or equal to Low Limit OLimErr bool retain out yes Output Low Limit is greater than Output

High Limit NoInt bool retain out yes No Interlocks Err bool retain out yes Error ExtParOut Ctrl_Data by_ref out yes Control data for supervisory control OutPar PID01_OutPar by_ref out yes Out Parameter Opr PID01_Opr by_ref out yes Operator order

Page 9: Functional Description - PID01

3BTG811792-3032 / A Page 9

Data Types PID01_InPar

PID01_InPar data type contains all configuration parameter available in PID01. Configuration can be entered by writing value to this structured data type and connecting it to input InPar of PID01 function block.

Name Data Type Attributes Initial value

ISP value Description

Class dint coldretain 500 AE class Severity dint coldretain 1000 AE severity MVRange RangeReal coldretain MV Range OUTRange RangeReal coldretain OUT Range SPLimit RangeLimit coldretain SP limit OUTLimit RangeLimit coldretain OUT limit InitMode dint coldretain 5 Init mode (5 = Man ; 6 = Auto ; 7 = E1 ; 8

= E2 ; 9 = E3) ManFdBlk bool coldretain false Block operator order Man Forced mode SeqManEvBlk bool coldretain true Block event for SeqMan SeqAutoEvBlk bool coldretain true Block event for SeqAuto SeqE1EvBlk bool coldretain true Block event for SeqE1 SeqE2EvBlk bool coldretain true Block event for SeqE2 SeqE3EvBlk bool coldretain true Block event for SeqE3 AlcBlkEvBlk bool coldretain true Block event for AlcBlk EOLimEvBlk bool coldretain true Block event for EOLim LocalEvBlk bool coldretain true Block event for Local BalInEvBlk bool coldretain true Block event for BalIn ClampEvBlk bool coldretain true Block event for Clamp IB1 IBInParType3 coldretain Configuration for IB1 IB2 IBInParType3 coldretain Configuration for IB2 IB3 IBInParType3 coldretain Configuration for IB3 IB4 IBInParType3 coldretain Configuration for IB4 ErrCtrl bool coldretain No error at overflow AEConfigAIErr dint coldretain 1 AE configuration for AI Error AlarmDelay time coldretain 0s Alarm Delay ShowActPos bool coldretain false Show actuator position IntBlk bool coldretain false Block integral action DerBlk bool coldretain true Block derivative action OUTIncDec real coldretain 2.0 Increase/Decrease step of output (In

percentage of range) SPIncDec real coldretain 1.0 Increase/Decrease step of setpoint (In

percentage of range) Gain real coldretain 0.5 Gain TI real coldretain 15 Integration Time TD real coldretain 0.0 Derivative Time TF real coldretain 0.0 Filter Time Beta real coldretain 1.0 Beta Factor TIDeadB real coldretain 0.0 Integration Deadband HystType bool coldretain false Hysterisis type (0 = Unit, 1 = Percent)

PID01_OutPar PID01_OutPar data type contains all information on the object which not available on the

output parameter of the function block.

Page 10: Functional Description - PID01

3BTG811792-3032 / A Page 10

Name Data Type Attributes Initial value

ISP value Description

AlarmBlk bool retain Alarm blocked IntlkBlk bool retain Interlock blocked IntlkBlkActive bool retain Interlock blocked active EnOverrideAll bool retain Override All button enabled Mode dint retain Active mode NormalMode bool retain Normal mode (Active mode = Init mode) AIErr bool retain MV error Forced bool retain MV forced IB1Ind bool retain IB1 interlocked IB2Ind bool retain IB2 interlocked IB3Ind bool retain IB3 interlocked IB4Ind bool retain IB4 interlocked MVH2 real retain Active High High MV alarm limit MVH1 real retain Active High MV alarm limit MVL1 real retain Active Low MV alarm limit MVL2 real retain Active Low Low MV alarm limit DevH real retain Active High Deviation alarm limit DevL real retain Active Low Deviation alarm limit ALB_H2 bool retain High High MV alarm blocked ALB_H1 bool retain High MV alarm blocked ALB_L1 bool retain Low MV alarm blocked ALB_L2 bool retain Low Low MV alarm blocked ALB_DevH bool retain High Deviation alarm blocked ALB_DevL bool retain Low Deviation alarm blocked AU_MVH2 bool retain UnAcknowledge alarm for MV > H2 AU_MVH1 bool retain UnAcknowledge alarm for MV > H1 AU_MVL1 bool retain UnAcknowledge alarm for MV < L1 AU_MVL2 bool retain UnAcknowledge alarm for MV < L2 AU_DevH bool retain UnAcknowledge alarm for Dev > H AU_DevL bool retain UnAcknowledge alarm for Dev < L AU_AIErr bool retain UnAcknowledge alarm for AI Error Direction bool retain Direction (0 = direct ; 1 = reverse) HWStatus HwStatus retain Hardware status SubStatus dint retain Hardware substatus IOStatus dint retain Hardware I/O status quality MV real retain MV indication

PID01_Opr PID01_Opr data type contains all operator order.

Name Data Type Attributes Initial value

ISP value Description

BlockAlarm bool retain Operator block alarms ALB_H2 bool retain Operator block alarm limit H2 ALB_H1 bool retain Operator block alarm limit H1 ALB_L1 bool retain Operator block alarm limit L1 ALB_L2 bool retain Operator block alarm limit L2 ALB_DevH bool retain Operator block alarm deviation H ALB_DevL bool retain Operator block alarm deviation L ManFd bool retain Operator order Manual Forced mode Man bool retain Operator order Manual mode Auto bool retain Operator order Auto mode E1 bool retain Operator order E1 mode E2 bool retain Operator order E2 mode

Page 11: Functional Description - PID01

3BTG811792-3032 / A Page 11

Name Data Type Attributes Initial value

ISP value Description

E3 bool retain Operator order E3 mode Incr real retain Operator order Increase SP command Decr real retain Operator order Decrease SP command OverrideAll bool retain Operator override all interlocks IB1Override bool retain Operator override IB1 interlock IB2Override bool retain Operator override IB2 interlock IB3Override bool retain Operator override IB3 interlock IB4Override bool retain Operator override IB4 interlock AutoSP real coldretain 0.0 Operator enter Auto Setpoint ManOUT real coldretain 0.0 Operator enter Man OUT EnableSim bool retain Enable simulated running feedback

Permission All variables in PID01_InPar data type are set with Configure permission in 800xA system. All

variables in PID01_Opr data type are set with Operate permission.

The variable permission can be configured according to the plant requirement. This can be done by adding Property Attribute Override aspect for the object in Control Structure or for the object type in Object Type Structure.

Page 12: Functional Description - PID01

3BTG811792-3032 / A Page 12

Page 13: Functional Description - PID01

3BTG811792-3032 / A Page 13

Section 3 - Function

Control Modes There are six different control modes are available in priority order: Balance, Man, Auto, E1,

E2 and E3. Active mode is indicated on the faceplate and object display. These modes can also be blocked individually from operator access. When in one particular mode, control from other location is blocked. Balance Mode

In Balance mode, the control output follows the input parameter BalRef. Balance mode can be activated by setting the input parameter Local or BalIn of the function

block. When activated by input parameter Local, an indication BaLo is presented in graphic elements and faceplate. When activated by input parameter BalIn, an indication Bal is presented instead. Manual Mode

Manual mode is the default init mode of the PID01. Manual mode can be activated as long as Local and BalIn is not active.

In this mode, operator directly sets the control output from the faceplate’s dialog entry window. Manual mode can be activated from the Man button on the faceplate or with a rising edge pulse to the input SeqMan of the function block. An indication M or Man is presented on the graphic elements and faceplate. To enable Man button on the faceplate, the input parameter ManEnbl must set to True.

When an AI error occurs in input parameter AIErr, control mode will be switch to Manual mode. As long as the AI error exist, it’s not possible to switch to other control mode with lower priority such as Auto, E1, E2 or E3 mode.

Another condition in Manual mode is called Manual Forced. In this condition, the interlock is overridden. Operator can sets the control output from the faceplate’s dialog entry window even if an interlock is active. Manual Forced is activated from the MFd button on the faceplate. An indication MFd is presented on the graphic elements and faceplate.

Manual mode can also be activated by the setting the input parameter Clamp of the function block. The output will follow the input parameter ClampRef. An indication MCp is presented on the graphic elements and faceplate. During this condition, the output value set by operator is ignored. Auto Mode

In this mode, operator directly sets the setpoint from the faceplate’s dialog entry window.

As long as Local, BalIn and Clamp is not active, Auto can be activated from the Auto button on the faceplate or with a rising edge pulse to the input SeqAuto of the function block. An

Page 14: Functional Description - PID01

3BTG811792-3032 / A Page 14

indication of A or Auto is presented on the graphic elements and faceplate. To enable Auto button on the faceplate, the input parameter AutoEnbl must set to True. E1 and E2 Mode

In this mode, the setpoint is controlled by the input parameter ExtRef1 in E1 mode and ExtRef2 in E2 mode.

As long as Local, BalIn and Clamp is not active, E1 or E2 mode can be activated from the E1 or E2 button on the faceplate or with a rising edge pulse to the input SeqE1 or SeqE2 of the function block. An indication of E1 or E2 is presented on the graphic elements and faceplate. To enable E1 or E2 button on the faceplate, the input parameter E1Enbl or E2Enbl must set to True. E3 Mode

In this mode, the output is controlled by the input parameter ExtRef3.

As long as Local, BalIn and Clamp is not active, E3 mode can be activated from the E3 button on the faceplate or with a rising edge pulse to the input SeqE3 of the function block. An indication of E3 is presented on the graphic elements and faceplate. To enable E3 button on the faceplate, the input parameter E3Enbl must set to True.

The table below describes the control mode activation and priority of PID01. Signal Balance Manual Auto E1 E2 E3 Input Local (1) BaLo - - - - - Input BalIn (1) Bal - - - - - Input Clamp (1) - MCp - - - - Operator ManForced (2) - MFd - - - - Input AIErr - M - - - - Operator Man - M - - - - Input SeqMan (3) - M - - - Operator Auto - - A - - - Input SeqAuto (3) - - A - - - Operator E1 - - - E1 - - Input SeqE1 (3) - - - E1 - - Operator E2 - - - - E2 - Input SeqE2 (3) - - - - E2 - Operator E3 - - - - - E3 Input SeqE3 (3) - - - - - E3

1. On leaving Balance or Manual Clamped, Manual mode is always obtained, unless other signal commands another mode. 2. The mode MFd is temporarily left while a command signal with higher priority is active. The mode is not left finally, until the operator

gives a command for another mode. All other commands of lower priority are blocked. 3. The arrow indicates that only a rising edge signal will trigger the mode change.

Control Algorithm The algorithm consists of a controller with optional P, PI, PD or PID characteristics. The

different parameters can be set from the faceplate or by control logic. Control Deviation

Control deviation is the difference between the working setpoint and measured value from the process. Control deviation is calculated with the following equation:

Page 15: Functional Description - PID01

3BTG811792-3032 / A Page 15

Dev = (MV - WSP) * (OUTmax - OUTmin) / (MVmax - MVmin) where: Dev = control deviation MV = measured value (internally limited to the range of the MV signal) WSP = working setpoint

Transfer Function

The transfer function for a PID controller consists of the sum of the different transfer functions for PI-controller and derivation.

TFsTDs

TsMVWSPGainsG

111)(

where: Gain = gain constant * (OUTmax - OUTmin) / (MVmax - MVmin) TI = integration time constant TD = derivation time constant TF = filter time constant

= beta factor (setpoint factor)

The PID algorithm in the function block performs the following tests:

If TI < Ts, then TI = Ts

If Abs(Dev) < IntegralDeadband, then no integration change.

If TD and TF 2 x Ts, then TD and TF = 2 x Ts where: Ts = the sampling time for the controller.

The beta factor appearing in the P part makes the formula differs from the most common form of a PID controller (in which case the beta factor has the fixed value = 1, the P part thus operating on the deviation Dev). The inclusion of beta factor allows the loop to be made faster without causing big overshoots at setpoint changes. To get an ordinary P or PD controller without a reduced beta factor, then beta factor should be set to 1.

The beta factor allows two-degree-of-freedom control in the PID controller. This means that the response to a setpoint step of a certain size differs from a disturbance step in the measured value of the same size. Using a value of beta factor less than one can be used to avoid excessive overshoot in the setpoint step response (controller is slower for setpoint changes compared to measurement disturbances). But this factor can also be used to increase the setpoint gain (thereby speeding up the setpoint step response) in cases where the controller proportional gain has to be kept low due to a high disturbance level (i.e. measurement noise). Reverse Action

The input RevAct defines the selection of function in term of PI and D control. 0 = Direct action in PI and D 1 = Reverse action in PI and D 2 = Direct action in PI and Reverse action in D 3 = Reverse action in PI and Direct action in D

Page 16: Functional Description - PID01

3BTG811792-3032 / A Page 16

Feed Forward

In automatic modes, the output of the controller is generated by the control algorithm and added with the value of the input parameter FeedFwd. The result is checked against high and low limits and rate limit. External Feedback

The purpose of external feedback is to set up an arrangement of 2 or more PID controllers which share a common output but have different process values and setpoints. As there’s only one output which has effect over the process, some selection logic must be added to decide which PID controller acts the output. Normally this will be a minimum selector, although any other selector or more complicated logic may be used. For this logic to work the actual output must be informed to all PID controllers so that the output of the PID controllers that don’t have control over the process don’t saturate. This control scheme is called overrun control.

Range Range parameter can be set from interaction window. Measured value and control output have

their own parameter. It includes Min, Max, Decimal / Fraction and Unit. The setpoint range is always the same as measured value range.

Setpoint Limitation The value from ExtRef1 / ExtRef2 when in E1 / E2 mode or operator input when in Auto mode

is limited to upper limit H and lower limit L before passed to the output WSP.

Setpoint limit can be entered from interaction window or extended faceplate. When limitation is not necessary, the Max and Min of MV shall be used as the upper and lower limit.

For upper limit, the value of SpEqHL will be set when WSP H. It will be reset when the WSP is lower than the setpoint limit. For lower limit, the value of SpEqLL will be set when WSP L. It will be reset when the WSP is greater than the setpoint limit.

Page 17: Functional Description - PID01

3BTG811792-3032 / A Page 17

Output Limitation The control output value is normally limited to the Max and Min of the output signal, but it’s

possible to define upper limit H and lower limit L within the signal range.

Internal output limit can be entered from interaction window or extended faceplate. It can also be set externally in logic via input parameter EOHL and EOLL. The activation of input parameter EOLim determines whether external limit or internal limit is applied to the output limitation.

The upper limit can be set equal to the lower limit, but lower limit cannot be set greater than the upper limit. Otherwise, limitation error will be activated in output parameter OLimErr.

For upper limit, the value of OutEqHL will be set when OutP H. It will be reset when the OutP is lower than the output limit. For lower limit, the value of OutEqLL will be set when OutP L. It will be reset when the OutP is greater than the output limit.

Ramp Function Ramp function is introduced into the signal path to determine the maximum permitted rate of

change of certain signal. The maximum permitted rate of changed is determine by the input parameter Speed(x) and is specified in unit per second.

Speed1 determines the maximum setpoint change rate in Auto mode. Speed2 and Speed3 determine the maximum change rate for ExtRef1 in E1 mode and ExtRef2 in E2 mode respectively. Speed4 determines the maximum output change rate in Manual, Clamp or E3 mode.

Tracking The tracking functions are intended to eliminate abrupt changes of the setpoint on return to the

different control modes. Tracking functions are available for both Auto mode and external mode and are activated during mode transfers.

Tracking selection for Auto mode is configured using input parameter Track_A and Track_B. Track_A Track_B Description

X 0 No tracking

1 1 The working setpoint is tracking MV when not in Auto mode. The working setpoint is ramped to AutoSP on return to Auto mode

2 1 The working setpoint is tracking ExtRef1 when in E1 mode or ExtRef2 when in E2 mode. The working setpoint is ramped to AutoSP on return to Auto mode

1 2 The working setpoint and AutoSP is tracking MV when not in Auto mode. The AutoSP will stays at current value on return to Auto mode

2 2 The working setpoint and AutoSP is tracking ExtRef1 when in E1 mode or ExtRef2 when in E2 mode. The AutoSP will stays at current value on return to Auto mode

Tracking selection for external mode is configured using input parameter Track_C. Track_C Description

0 No tracking (default value)

1 The external setpoint ExtRef1 and ExtRef2 is tracking MV when not in E1 and E2 mode. The internal setpoint is ramped to ExtRef1 or ExtRef2 on return to E1 or E2 mode

Page 18: Functional Description - PID01

3BTG811792-3032 / A Page 18

Track_C Description

2 The external setpoint ExtRef1 and ExtRef2 is tracking WSP when not in E1 and E2 mode. The internal setpoint is ramped to ExtRef1 or ExtRef2 on return to E1 or E2 mode

Alarm Limits PID01 monitor the measured value MV and compared it with two upper (H1 and H2) and two

lower (L1 and L2) alarm limits. When determining the MV alarm limits, it is recommended to follow the rule: H2 > H1 > L1 > L2. Alarm limit can be entered from interaction window or extended faceplate.

It’s possible to select whether the hysteresis is in unit or in percentage. If percentage is selected, then actual hysteresis used internally is calculated by multiplying the percentage against the signal range.

For upper alarm limit, the value of MV_GT_H1 and MV_GT_H2 will be set when MV > H1 and MV > H2 respectively. It will be reset when the MV is lower than the alarm limit minus the respective hysteresis. For lower alarm limit, the value of MV_LT_L1 and MV_LT_L2 will be set when MV < L1 and MV < L2 respectively. It will be reset when the MV is greater than the alarm limit plus the respective hysteresis.

PID01 also monitor the deviation value Dev and compared it with upper H and lower L alarm limits. Alarm limit can be entered from interaction window or extended faceplate.

For upper alarm limit, the value of Dev_GT_H will be set when Dev > H. It will be reset when the Dev is lower than the alarm limit minus the hysteresis. For lower alarm limit, the value of Dev_LT_L will be set when Dev < L. It will be reset when the Dev is greater than the alarm limit plus the hysteresis.

The value of MV_GT_H2, MV_GT_H1, MV_LT_L1, MV_LT_L2, Dev_GT_H and Dev_LT_L will always be monitored even if the alarm and event is not activated (AEConfig set to 0).

All alarm limits can be blocked altogether or individually. Alarm blocking can be done from faceplate or from function block using AlcBlk or MVAlarms or DevAlarms.

Interlocks The PID01A control can be interlocked by signals from the process or control logic. Interlocks

are active when the value is False. There are 4 process interlocks available: IB1 - IB4. All can be configured to accept blocking by the operator.

When interlock is active, the control output will be set to a value defined in the IB1Ref - IB4Ref. If the active interlock is at the IB1, the output will be set based on value in IB1Ref. The same condition applies to IB2, IB3 and IB4. Interlock supervision is performed in the priority order IB1, IB2, IB3 and IB4.

These interlocks do not change the current control mode, but can be overridden by Manual Forced, when selected by the operator. If the control mode is Manual when the interlock is released, the output will stay at the interlock-value.

Page 19: Functional Description - PID01

3BTG811792-3032 / A Page 19

External Control Alarm limit and control parameter can be controlled externally by logic using the input

parameter ExtCtrl. When external control is enabled, alarm limit or control parameter will take the value from the external control. When it is released, the alarm limit or control parameter will take value set in the function block.

Internal data of PID01 can be accessed for other purposes using output parameter ExtParOut.

Gain Scheduling Gain scheduling can be accomplished by using GainSched function block. The output

parameter ExtCtrl in GainSched function block shall be connected to input parameter ExtCtrl in PID01.

Simulation The function block support internal simulation. Simulation can be activated by enabling the

simulation button in Interaction Window or by setting the Opr.EnableSim to True using the bulk tool. The simulation will be reset when cold download is performed.

Object in simulation mode will be indicated with a frame on the graphic elements. The default color is flashing yellow as defined by ppSimulation in Pulp & Paper Library Colors aspect. It also indicates Sim next to the mode indication in faceplate.

Measured value will be filtered by 2s from the output OutP. The measured value will be simulated based on the MV range defined in the PID01 and the control direction.

Interaction Window Interaction Window is used to configure the object’s parameter in the Control Builder. It is only

accessible when Control Builder is in Online mode by right clicking the function block.

The main Interaction Window shows the name and description of the function block. The buttons are link to open the sub-window.

Page 20: Functional Description - PID01

3BTG811792-3032 / A Page 20

1. General Par Name and Description can be entered from interaction window or from the function block

parameters directly. After performing Name Uploader, these values will be used as Object Name and Description and shown in faceplate.

Class defines the process section or area in which alarms are grouped. By utilizing Class, the alarms can be filtered. Valid values are 1 - 9999. Severity defines the alarm priority for general alarms. Valid values are 1 - 1000 where 1000 is the highest priority.

2. Order & Event Block, Init Mode Order Block is used to prevent operator from giving an order of certain activity. The faceplate

button will be dimmed if order block is activated (set to 1).

Event Block is used to block the event message generated due to changes in value from logic connection. To enable event for selected message, press the button to set the value to 0. The text message for each event is stored in the AE Translator aspect. List of events for all operator activity is managed in 800xA system with Audit Trail functionality.

Init Mode defines the initial mode of the object when cold download is performed. By default, the init mode for PID01 is Manual mode.

3. Interlock Setting When Block Event is disabled (set to 0), changes in value of the interlock will generate an

event message. The text message for each event is stored in the AE Translator aspect.

Page 21: Functional Description - PID01

3BTG811792-3032 / A Page 21

Enabling the Opr Block (set to 1) will give operator the possibility to override the interlock(s) from faceplate.

4. Unit & Range Unit & Range covers minimum and maximum range, unit and decimal number for MV/SP and

Output.

Limit Control defines the percentage value of changes for SP (in Auto mode) and Output (in Man mode) when faceplate button Dec or Inc is pressed. It also defines the High and Low Limit of SP and Output operator can enter from faceplate when in Auto and Manual mode respectively.

Enabling Show Actuator Position will show the actuator value in the faceplate.

5. Alarm Setting Four MV alarm limits can be configured, two high limits and two low limits. Each alarm limit

has its own configuration and can be defined individually. AE Config can be set in 3 different ways: 0 = No Alarm or Event will be generated 1 = Alarm and Event will be generated 2 = Only Event will be generated

If AE Config is set to 1, alarm will be generated if the limit stays active longer than alarm delay time. Otherwise, alarm will not be generated.

When MV Alarm Hysteresis in Percentage (%) is activated (set to 1), the hysteresis will be in percentage and calculated against the range.

Page 22: Functional Description - PID01

3BTG811792-3032 / A Page 22

Similarly, there are two Deviation alarm limits, high limit and low limit. Note that the deviation limit is in percentage.

6. Parameters It covers the tuning parameter when external control is not used.

Text Configuration Text Configuration aspect is used to define the text properties of the object, such as modes,

interlocks and info texts. It is accessible in the Control Structure. The length of the each text should not exceed more than 50 characters, except for modes name which is limited to 10 characters only.

Page 23: Functional Description - PID01

3BTG811792-3032 / A Page 23

Page 24: Functional Description - PID01

3BTG811792-3032 / A Page 24

Page 25: Functional Description - PID01

3BTG811792-3032 / A Page 25

Section 3 - Operator Function

Process Display PID01 has the following graphic elements which can be inserted into graphic displays.

Page 26: Functional Description - PID01

3BTG811792-3032 / A Page 26

The following display shows the presentation in graphic elements under different states.

Faceplate Aspect Link

Icon Aspect View

Operator Note

Interlocks Display

Object Display

Object Trend Display

Reduced Faceplate and Faceplate

Reduced Faceplate and Faceplate give basic information about the object. Size and contents have been optimized to cover most of the normal process operator action. Process values presented in bargraph are available in Faceplate.

Reduce Faceplate is the default view.

Page 27: Functional Description - PID01

3BTG811792-3032 / A Page 27

Reduced Faceplate Faceplate

Extended Faceplate

The extended faceplate gives more detailed information about the object. Additional information about the object is available in tabs.

1. Control 2

This tab show the remote SP which will be used if control mode is changed to E1, E2 or E3 mode.

Page 28: Functional Description - PID01

3BTG811792-3032 / A Page 28

2. T Curve

Trim Curve is used to present value in the last 4 minutes period. It contains 3 traces: MV (for Measured Value), WSP (for SP) and Out (for Output).

3. Limits 1

MV and Deviation alarm limit, hysteresis and alarm delay can be defined in this tab. Alarm limit will be visible if configured as alarm & event (indicated with AE) or event only (indicated with E). If alarm is blocked, then it will be indicated with B.

When alarm limit is active, a red square indication is shown in front of the limit. Alarm will be generated if the limit stays active for more than the alarm delay time. It will be indicated with the blinking red square indication as long as not acknowledged.

User with Tune permission can change the alarm limits, while hysteresis and alarm delay can be adjusted by user with Configure permission. Input field for alarm limit will be disabled if the external control for the respective limit is active. If MV Alarm Hyst in Percentage (%) is checked, then hysteresis entered is calculated as percentage of the range.

Page 29: Functional Description - PID01

3BTG811792-3032 / A Page 29

4. Limits 2 Setpoint and output limit can be defined in this tab. When limit is active, a yellow square

indication is shown in front of the limit. User with Tune permission can change the output limits. Input field for limit will be disabled if the external limitation is active.

5. Parameters

Tuning parameter for PID01 can be configured here. User with Tune permission can adjust these values. Direction can only be set from function block. Input field will be enabled or disabled depending on the controller type. Input field for limit will be disabled if the external limitation is active.

6. Block

Checkbox Override Interlock will override all blockable interlocks. It is enabled when at least one interlock is configured blockable.

Operator can block each MV/Dev alarm limit individually or all alarms by ticking on the checkbox. Checkbox Block All Alarms is enabled when at least one of MV/Dev limits or signal fault is configured as alarm. Checkbox for blocking individual MV/Dev alarm limit is enabled when the respective MV/Dev limit is configured as alarm. It will be disabled when external control for the respective MV/Dev limit is activated.

Un-ticking checkbox Enable Object will bring the object to Out Of Service mode.

Page 30: Functional Description - PID01

3BTG811792-3032 / A Page 30

7. Status

Status of the IO Signal of MV is shown in this tab. It also shows the type of the device where the IO Signal is connected to.

8. Tracking

Tracking configuration for the setpoint is shown in this tab.

9. Info

Relevant information about the object can be entered here.

Page 31: Functional Description - PID01

3BTG811792-3032 / A Page 31

Interlock Display Interlock Display shows the actual status of all interlocks. Operator can override individual

interlock or all interlocks which is blockable. Blockable, Block Event and Interlock Texts are set with Configure permission.

When interlock is active, a yellow square indication will be shown in front of the interlock. When operator blocks an interlock, a BX text indication will be shown. If the interlock is active, it will be in red color. Otherwise it will be in yellow color.

Object Display Object Display can be used to get the complete overview of the object. It has detailed

information of the MV value and range, setpoint value and range, output value and range, alarm limit, ratio and output limitation, parameters and available control modes.

Page 32: Functional Description - PID01

3BTG811792-3032 / A Page 32

Object Trend Display Values stored can be presented graphically in the form of curves in Object Trend Display

aspect. By default, PID01 presents 3 traces: MV, WSP and OutP. It uses the trend template PP Library Control Object Trend in Library Structure.

Alarm & Event Alarm & Event List

All alarm & event list aspect is configured to follow the templates defined in PP Library Alarm & Event List Configurations in Library Structure.

Alarm Message The Message Description is hardcoded in the function block and cannot be modified. The

Condition text is stored in the AE Translator aspect in Object Type Structure and support NLS functionality.

Resource Id Condition Message Description AIErr AI Error Alarm DevH Dev > H Alarm DevL Dev < L Alarm MVH1 MV > H1 Alarm MVH2 MV > H2 Alarm MVL1 MV < L1 Alarm MVL2 MV < L2 Alarm

Event Message The Message Description is stored in the AE Translator aspect in Object Type Structure and

support NLS functionality. Resource Id Message Description

AlarmAck Alarm acknowledged by program

Page 33: Functional Description - PID01

3BTG811792-3032 / A Page 33

Resource Id Message Description AlcBlk Alarm blocked by program BalInOff BalIn Off BalInOn BalIn On ClampOff Clamp Off ClampOn Clamp On EOLimOff EOLim Off EOLimOn EOLim On IB1Off IB1 Off IB1On IB1 On IB2Off IB2 Off IB2On IB2 On IB3Off IB3 Off IB3On IB3 On IB4Off IB4 Off IB4On IB4 On LocalOff Local Off LocalOn Local On SeqAuto SeqAuto SeqE1 SeqE1 SeqE2 SeqE2 SeqE3 SeqE3 SeqMan SeqMan