International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013 London Tel: 0208 527 9669 London Fax: 0208 531 0936 Website: www.ileweb.co.uk Leicester Tel: 0116 269 0900 Leicester Fax: 0116 269 0939 Email: [email protected] We reserve the right to alter without giving prior notice technical data dimensions and weights described in this manual INTERNATIONAL LIFT EQUIPMENT LTD FUJI FRENIC INVERTER USER GUIDE FM 40432

FUJI FRENIC INVERTER - International Lift Equipment Ltd WEBSITE MANUALS/FUJI FRENIC... · International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013

Embed Size (px)

Citation preview

Page 1: FUJI FRENIC INVERTER - International Lift Equipment Ltd WEBSITE MANUALS/FUJI FRENIC... · International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013

International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3

Page 1 25/03/2013

London Tel: 0208 527 9669 London Fax: 0208 531 0936 Website: www.ileweb.co.uk

Leicester Tel: 0116 269 0900 Leicester Fax: 0116 269 0939

Email: [email protected]

We reserve the right to alter without giving prior notice technical data dimensions and weights described in this manual

INTERNATIONAL LIFT EQUIPMENT LTD

FUJI FRENIC INVERTER USER GUIDE

FM 40432

Page 2: FUJI FRENIC INVERTER - International Lift Equipment Ltd WEBSITE MANUALS/FUJI FRENIC... · International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013

International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3

Page 2 25/03/2013

London Tel: 0208 527 9669 London Fax: 0208 531 0936 Website: www.ileweb.co.uk

Leicester Tel: 0116 269 0900 Leicester Fax: 0116 269 0939

Email: [email protected]

We reserve the right to alter without giving prior notice technical data dimensions and weights described in this manual

Contents

Drive overview ................................................................................................................................... 4  Keypad operation ............................................................................................................................. 5  Keypad operation ............................................................................................................................. 6  

Keypad menus ......................................................................................................................... 6  0 QUICK SET ........................................................................................................................ 6  1 DATA SET .......................................................................................................................... 6  2 DATA CHECK .................................................................................................................... 6  3 OPR MNTR (OPERATION MONITOR) ............................................................................ 6  4 I/O CHECK ........................................................................................................................ 7  5 MAINTENANC (MAINTENANCE) .................................................................................... 7  6 ALM INF (ALARM INFORMATION) ................................................................................ 7  7 ALM CAUSE (ALARM CAUSE) ........................................................................................ 7  8 DATA COPY ....................................................................................................................... 7  9 LOAD FCTR (LOAD FACTOR) ......................................................................................... 7  

Example of parameter setting ......................................................................................................... 8  Encoder connections ....................................................................................................................... 9  

Standard (Built-in) input connection for 12V/15V incremental encoder ............................. 9  Option card OPC-LM1-PR for synchronous motors ................................................................. 9  Option card OPC-LM1-PS1 for synchronous motors .............................................................. 10  

Getting running for the first time and auto tuning ...................................................................... 12  Open loop operation ............................................................................................................... 12  Closed loop operation ............................................................................................................. 12  Gearless machines (permanent magnet) ............................................................................. 13  Final setting prior to running for the first time. ........................................................................ 14  

Setting speeds, acceleration, deceleration and jerks for High speed ..................................... 14  S curve for high speed (HS on Skycom Solo, HS or DTS on Skycom) .................................... 14  

Setting speeds, acceleration, deceleration and jerks for medium speed .............................. 15  S curve for medium speed (MS1 on Skycom) ........................................................................ 15  

Setting speeds, acceleration, deceleration and jerks for reduced power mode .................. 15  S curve for reduced power mode (RPR on Skycom / Skycom Solo) .................................. 15  

Inspection speed ............................................................................................................................. 16  Performance related settings ........................................................................................................ 17  

Brake lift / release timers ........................................................................................................... 17  Critical settings for open loop .................................................................................................. 17  

No load current (parameter P06) .................................................................................. 17  Slip frequency (parameter P12) .................................................................................... 17  Slip compensation gains (parameter P09 for driving, P10 for braking) ................ 18  

Gains (closed loop and Gearless) ........................................................................................... 18  Anti roll back parameters (gearless only) ............................................................................... 18  

Brake Checking Signal for UCM Compliance (EN81-1 + A3) ..................................................... 19  Introduction ................................................................................................................................ 19  Description of the function and parameters ......................................................................... 19  Function Behavior ...................................................................................................................... 20  Brake feedback is abnormal at starting ................................................................................. 20  

Brake feedback is abnormal at stopping ....................................................................... 21  Brake feedback is abnormal during travel (with BBE trip) ............................................. 21  

Page 3: FUJI FRENIC INVERTER - International Lift Equipment Ltd WEBSITE MANUALS/FUJI FRENIC... · International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013

International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3

Page 3 25/03/2013

London Tel: 0208 527 9669 London Fax: 0208 531 0936 Website: www.ileweb.co.uk

Leicester Tel: 0116 269 0900 Leicester Fax: 0116 269 0939

Email: [email protected]

We reserve the right to alter without giving prior notice technical data dimensions and weights described in this manual

Brake feedback is abnormal during travel (no BBE trip) ............................................... 22  Brake feedback is abnormal when the lift is stationary ................................................. 22  Test of BRKE1 Function at start .......................................................................................... 23  Test of BRKE1 function during travel ................................................................................. 24  Test of BRKE2 Function at start .......................................................................................... 25  Test of BRKE2 function during travel ................................................................................. 26  

Fault codes and their meanings .................................................................................................... 27  bbe Reset procedure ............................................................................................................... 28  

Document History ............................................................................................................................ 28  

Page 4: FUJI FRENIC INVERTER - International Lift Equipment Ltd WEBSITE MANUALS/FUJI FRENIC... · International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013

International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3

Page 4 25/03/2013

London Tel: 0208 527 9669 London Fax: 0208 531 0936 Website: www.ileweb.co.uk

Leicester Tel: 0116 269 0900 Leicester Fax: 0116 269 0939

Email: [email protected]

We reserve the right to alter without giving prior notice technical data dimensions and weights described in this manual

Drive overview  FUJI FRENIC – Lift series inverters is specially designed for operation of induction and permanent magnet synchronous motors used in lift applications. Also induction motors without encoder (open loop) can be controlled obtaining good performance and high positioning accuracy at stop.

The main characteristics of FUJI FRENIC Lift are:

ü Compact dimensions with high output power ü Rescue operation possible with Battery or UPS with indication of recommended

direction ü Short floor operation with distance based control ü 200% overload for 10 Seconds ü Incremental encoder input (12V or 15V / Open Collector) ü Optional cards for different encoder types (EnDat 2.1, SinCos...) ü Pole tuning and Auto tuning without removing the ropes ü Multifunctional, detachable keypad ü Braking transistor is integrated in all capacities ü Operation of Induction motor without encoder (open loop) ü Different S curves and accel/decel profiles for all speed inputs (medium and reduced

power speeds) ü High switching frequency for reduced motor noise (15Khz standard)

Conformity to European standards The CE marking on Fuji Electric products indicates that they comply with the essential requirements of the Electromagnetic Compatibility (EMC) Directive 89/336/EEC issued by the Council of the European Communities and the Low Voltage Directive 73/23/EEC. Inverters with built-in EMC filter that bear a CE marking are in conformity with EMC directives. Inverters having no built-in EMC filter can be in conformity with EMC directives if an optional EMC compliant filter is connected to them. General purpose inverters are subject to the regulations set forth by the Low Voltage Directive in the EU. Fuji Electric declares the inverters bearing a CE marking are compliant with the Low Voltage Directive. FRENIC Lift inverters are in accordance with the regulations of following council directives and their amendments:

EMC Directive 2004/108/EC (Electromagnetic Compatibility) Low Voltage Directive 2006/95/EC (LVD)

For assessment of conformity the following relevant standards have been taken into consideration: EN61800-3:2004 EN50178:1997

 The  FRENIC-­‐Lift  inverters  are  categorized  as  category  C2  according  to  EN61800-­‐3:2004.  When  you  use  these  products  in  

the  domestic  environment,  you  may  need  to  take  appropriate  countermeasures  to  reduce  or  eliminate  any  noise  emitted  from  these  products.  

Page 5: FUJI FRENIC INVERTER - International Lift Equipment Ltd WEBSITE MANUALS/FUJI FRENIC... · International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013

International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3

Page 5 25/03/2013

London Tel: 0208 527 9669 London Fax: 0208 531 0936 Website: www.ileweb.co.uk

Leicester Tel: 0116 269 0900 Leicester Fax: 0116 269 0939

Email: [email protected]

We reserve the right to alter without giving prior notice technical data dimensions and weights described in this manual

Keypad operation

To operate, commission and Set up FRENIC Lift inverter there are two possibilities: using inverter keypad or PC. For operation using a PC it is necessary to use the dedicated software Lift Loader. This software is free of charge and can be downloaded from our website www.ileweb.co.uk (a USB to RS485 converter is required) The keypad is connected to the inverter through the RJ-45 connector. This connection is also used for the connection with the PC or the lift controller using DCP 3 protocol  

Figure 12: Overview of keypad

Keys explanation:

LED-display shows the operation values, for example Set point frequency, actual frequency or alarm codes.

Displays the actual used multipliers and/or units used in the LED-display. The actual units will be indicated by a line below the unit’s indicator.

LCD-display for showing different information, like operation status, functions values. The lowest line shoes information regarding keypad operation.

a) Shows the actual operation status like FWD=UP, REV=DOWN or Stop = Standstill.

b) Shows the actual operation mode Terminal operation = REM or via DCP=COMM

Keys: With these keys displayed values can be set or function values can be changed. Status Led shows inverter status.

Use this key to change between operation and programming mode.

Use this key to move the cursor to the right in programming mode

In Alarm mode: Alarm reset In Programming mode: leave the parameter changing in the settings

In Programming mode: Function selection inside the menu or change the function value In Programming mode: Scroll to the next parameter

In Programming mode: Parameter edit or saving In Operation mode: for choosing the displayed value (and units)

These 3 keys may not be used in lift application. In local mode with these keys the motor can be started and/or stopped.

Change between Remote (Terminal control) and Local (keypad operation)

Page 6: FUJI FRENIC INVERTER - International Lift Equipment Ltd WEBSITE MANUALS/FUJI FRENIC... · International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013

International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3

Page 6 25/03/2013

London Tel: 0208 527 9669 London Fax: 0208 531 0936 Website: www.ileweb.co.uk

Leicester Tel: 0116 269 0900 Leicester Fax: 0116 269 0939

Email: [email protected]

We reserve the right to alter without giving prior notice technical data dimensions and weights described in this manual

Keypad operation  

Keypad menus The complete menu list can be accessed by pressing the PRG key. The LCD display shows the 4 first menus from the complete list.

 Figure 1: Complete menus list Detailed  menus  description  

0 QUICK SET This menu contains all of the parameters required for set up and commissioning of the Frenic inverter specific to ILE installations. The parameters in this menu will allow all the motor data to be set, all autotune functions and all S curve settings. After selecting a parameter it can be checked and/or changed (edited) if needed by pressing key.

 1 DATA SET This menu is used for accessing all parameters. It displays the function codes list and describes the function of that code. Every function has a number and name assigned. After selecting a function it can be checked and/or changed (edited) if needed by pressing  key.  

2 DATA CHECK Also using this menu parameters can be changed. In this menu only function codes and parameter values are shown (without the names) and the set values can be directly read. Parameter values changed from default are indicated by a star on the right side of the parameter number. By pressing key the selected function can be changed.

Figure 2: DATA CHECK menu.

3 OPR MNTR (OPERATION MONITOR) In this menu different operating values can be shown in the LCD display. There are 4 different screens showing 4 lines each, for example output frequency, output current, output voltage and calculated torque.

 0. QUICK  SET  1. DATA  SET  2. DATA  CHECK  3. OPR  MNTR  4. I/O  CHECK  5. MAINTENANCE  6. ALM  INF  7. ALM  CAUSE  8. DATA  COPY  9. LOAD  FCTR  

00,00 P01        4        P02*  11kW          P03      20A        P04          0  

Function changed and saved

Page 7: FUJI FRENIC INVERTER - International Lift Equipment Ltd WEBSITE MANUALS/FUJI FRENIC... · International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013

International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3

Page 7 25/03/2013

London Tel: 0208 527 9669 London Fax: 0208 531 0936 Website: www.ileweb.co.uk

Leicester Tel: 0116 269 0900 Leicester Fax: 0116 269 0939

Email: [email protected]

We reserve the right to alter without giving prior notice technical data dimensions and weights described in this manual

4 I/O CHECK Used for checking the I/O status and if FRENIC Lift is receiving the correct control signals from the ILE controller and the output signals are being issued correctly. Input and output signals are displayed in different screens.

Figure 3: Example with digital inputs displayed. In this Example ¢X2 and ¢FWD inputs are active.

5 MAINTENANC (MAINTENANCE) Shows the inverter condition: runtime, main capacitors capacitance, firmware version.

6 ALM INF (ALARM INFORMATION) In this menu the alarm memory is shown. After the selection of an alarm by pressing key the most relevant information of each alarm is shown.

7 ALM CAUSE (ALARM CAUSE) In this menu the possible alarm causes are shown. After the selection of an alarm by pressing key a possible cause of this alarm is shown.

8 DATA COPY With this menu the complete inverter parameter set can be saved to the keypad and transfered from one inverter to another. This may be helpful to set up different installations with the same motor and same characteristics. Be aware that function protection (F00) is no copied. Motor data and communication set are copied only between inverters of same range.

9 LOAD FCTR (LOAD FACTOR) In this menu the maximum current, the average current and the average braking torque during a preset measuring time can be measured in the real application.

00,00 TRM ¢X2 £X6 ¢FWD £X3 £X7 £REV £X4 £X8 £X1 £X5 £EN

Page 8: FUJI FRENIC INVERTER - International Lift Equipment Ltd WEBSITE MANUALS/FUJI FRENIC... · International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013

International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3

Page 8 25/03/2013

London Tel: 0208 527 9669 London Fax: 0208 531 0936 Website: www.ileweb.co.uk

Leicester Tel: 0116 269 0900 Leicester Fax: 0116 269 0939

Email: [email protected]

We reserve the right to alter without giving prior notice technical data dimensions and weights described in this manual

Example of parameter setting

Figure 4: LCD display of the first 4 menus after pressing PRG key

Figure 5: Menu selection (in this figure maintenance menu is selected)

Figure 6: Selection of Menu 1 Figure 7: Function code selection. In this figure P03 Rated current from the P Group (Motor functions)

Figure 8: To edit (go inside) the function

Figure 9: Changing the value of P03 (motor rated current), in this example to 12.

After changing the value using the arrow keys, it can be saved by pressing key. Exiting a parameter without saving is possible by pressing the key.

00,00 P01 M-POLES        P02  M-­‐CAP  �  P03  M-­‐Ir        P04  M-­‐TUN  

00,00 �1.  DATA  SET        2.  DATA  CHECK        3.  OPR  MNTR        4.  I/O  CHECK  

00,00 �1.DATA SET        2.DATA  CHECK        3.OPR  MNTR        4.I/O  CHECK  

00,00 P03 M-Ir  

12  A  0.00~500.00  

00,00 2. DATA CHECK      3.  OPR  MNTR      4.  I/O  CHECK  �  5.  MAINTENANC  

00,00 P03 M-Ir  

12  A  0.00~500.00  

Actual  value  

Setting  range  

Page 9: FUJI FRENIC INVERTER - International Lift Equipment Ltd WEBSITE MANUALS/FUJI FRENIC... · International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013

International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3

Page 9 25/03/2013

London Tel: 0208 527 9669 London Fax: 0208 531 0936 Website: www.ileweb.co.uk

Leicester Tel: 0116 269 0900 Leicester Fax: 0116 269 0939

Email: [email protected]

We reserve the right to alter without giving prior notice technical data dimensions and weights described in this manual

Encoder connections  

 Standard (Built-in) input connection for 12V/15V incremental encoder The FRENIC Lift control board includes an interface for the connection of an encoder for applications with induction motors. The connection is via screw terminals. The output supply voltage is 12 or 15VDC and is compatible with standard HTL 10-30VDC encoders. Pulse resolution from 360 to 6000 can be set using function L02. Supply voltage The supply voltage of the encoder can be selected by setting the slide switch SW5 located on the inverter control board. The default setting is 12V, which can be used for standard encoders with supply voltages from 10 to 30 VDC.

FRENIC Lift

Built-inHTL - Interface

Maxim

um 20m

cable length

PO PA PB PZCM

Incremental Encoder

HTL

Term6

PBOPAO

Term1

Output encoder signalOpen collector output-max. 27VDC, 50mA-ON level: 2V or less

Common terminal CMto be connected to the

lift controller (shaft copy)

Figure 10: Connection using HTL encoder interface $ The encoder cable must always be shielded. The shield must be connected at

the inverter and the encoder end using the ground terminal or dedicated terminal.

Option card OPC-LM1-PR for synchronous motors

ü For permanent magnet synchronous motors ü For encoder Heidenhain Type ERN1387 or ERN487 or compatible ü Output signal: 2048 Sin/Cos pulses (periods) per revolution ü Operating supply voltage: 5VDC±5% (maximum current is 300 mA) ü Absolute signal: 1 Sin/Cos signal with 1 Period/turn

Page 10: FUJI FRENIC INVERTER - International Lift Equipment Ltd WEBSITE MANUALS/FUJI FRENIC... · International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013

International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3

Page 10 25/03/2013

London Tel: 0208 527 9669 London Fax: 0208 531 0936 Website: www.ileweb.co.uk

Leicester Tel: 0116 269 0900 Leicester Fax: 0116 269 0939

Email: [email protected]

We reserve the right to alter without giving prior notice technical data dimensions and weights described in this manual

FRENIC Lift

OPC-LM1-PR

Maxim

um cable length 20m

PO PO PA+ PA- PB+ PB- PC+ PC- PD+ PD-

Heidenhain ERN1387

FPA FPBCMCM CMM

aximum

cable length 5m

CM

Output encoder signalOpen collector output-max. 27VDC, 50mA-ON level: 2V or less

to be connected to the lift controller (shaft copy)

Figure 11: Connection option card OPC-LM1-PR

Table 1: Connection description of terminals for OPC-LM1-PR Terminal description

in the option card Signal name from

Heidenhain Description

P0 Up und Up Sensor Supply voltage 5V, connection of Up Sensor mandatory for cable length >10m

CM 0V (Up) und 0V Sensor Common 0 V for the power supply PA+ A+ A phase PA- A- A phase inverted PB+ B+ B phase PB- B- B phase inverted PC+ C+ C phase (Absolute signal) PC-- C- C phase inverted (Absolute signal) PD+ D+ D phase (Absolute signal) PD- D- D phase inverted (Absolute signal)

$ Prior to the commissioning, the encoder resolution (pulses per revolution) has

to be set using parameter L02. $ For synchronous motors it is also necessary to set the encoder type in function

L01.    

Option card OPC-LM1-PS1 for synchronous motors

ü For permanent magnet synchronous motors ü For encoder Heidenhain Type ECN1313 or ECN413 or ECN113 ü Output signal: 2048 Sin/Cos pulses (periods) per revolution ü Operating voltage: 5VDC±5%; 300mA ü Data connection: EnDat 2.1

Page 11: FUJI FRENIC INVERTER - International Lift Equipment Ltd WEBSITE MANUALS/FUJI FRENIC... · International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013

International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3

Page 11 25/03/2013

London Tel: 0208 527 9669 London Fax: 0208 531 0936 Website: www.ileweb.co.uk

Leicester Tel: 0116 269 0900 Leicester Fax: 0116 269 0939

Email: [email protected]

We reserve the right to alter without giving prior notice technical data dimensions and weights described in this manual

FRENIC Lift

OPC-LM1-PS1

Maxim

um cable length 20m

PO PO PA+ PA- PB+ PB- CK+ CK- DT+ DT-

Heidenhain ECN1313Endat2.1

FPA FPBCMCM CMM

aximum

cable length 5m

CM

Output encoder signalOpen collector output-max. 27VDC, 50mA-ON level: 2V or less

to be connected to the lift controller (shaft copy)

Figure 12: OPC-LM1-PS1 option card connection

Table 2: Connection description of terminals for OPC-LM1-PS1 Terminal name in the option card

Signal name from Heidenhain

Description

P0 Up and Up Sensor Supply voltage 5V, connection of Up Sensor mandatory for cable length >10m

CM 0V (Up) and 0V Sensor Common 0 V for the power supply PA+ A+ A signal PA- A- A signal inverted PB+ B+ A signal PB- B- A signal inverted CK+ Clock+ Clock signal for serial communication CK- Clock- Clock signal inverted for serial communication DT+ DATA+ Data line for communication of the absolute

information DT- DATA- Data line inverted for communication of the absolute

information

$ Prior to the commissioning, the encoder resolution (pulses per revolution) has to be set using parameter L02. $ For synchronous motors it is also necessary to set the encoder type in function

L01.

Page 12: FUJI FRENIC INVERTER - International Lift Equipment Ltd WEBSITE MANUALS/FUJI FRENIC... · International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013

International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3

Page 12 25/03/2013

London Tel: 0208 527 9669 London Fax: 0208 531 0936 Website: www.ileweb.co.uk

Leicester Tel: 0116 269 0900 Leicester Fax: 0116 269 0939

Email: [email protected]

We reserve the right to alter without giving prior notice technical data dimensions and weights described in this manual

Getting running for the first time and auto tuning

Open loop operation Before running for the first time the site motor parameters have to be checked and adjusted to suit. It is recommended that an autotune is then performed. The auto tune is non rotating so the ropes can be left on. The lift should be on inspection, should be ready to run i.e. all emergency stops, car doors and landing locks made. Check the motor data parameters in table 3 are set correctly in menu 0 (quick set)  

Table 3: Parameters to be set prior to auto tuning Parameter Description Default value New setting

P01 Number of motor poles 4 4=1500 rpm 6=1000rpm P02 Motor capacity (KW) As per drive size Set as motor data plate P03 Motor rated Current

(Amps) As per drive size Set as motor data plate

F04 Motor speed (RPM) 1500 Set as motor data plate F05 Motor Voltage (Volts) 380 Set as motor data plate

$If you wish to switch to open loop so you can run the lift before the motor encoder is fitted set parameter F42 to 2 (torque vector control)  Once the motor parameters are set carry out the following procedure.

ü Make sure the motor is correctly connected

ü Set parameter P04 to 3 and press

ü Give the drive a run command by pressing test up or test down. MC & MC1 will

come in and there will be an audible motor noise

ü Once the tune is complete release the test direction

         

 

  Closed loop operation For closed loop installations the set up procedure is the same as for open loop, it is also recommended that an autotune is performed before the first travel. The auto tune procedure is carried out the same as for an open loop application. The motor data needs to be set as in table 3, but the additional parameter in table 4 also has to set and checked.  

Table  4:  Parameters  to  be  set  prior  to  auto  tuning  on  closed  loop  Parameter Description Default value New setting

L02 Encoder resolution (PPR) 2048 As per encoder data plate

 Once  the  motor  parameters  are  set  carry  out  the  auto  tune  as  open  loop  (see  section  above).    

Page 13: FUJI FRENIC INVERTER - International Lift Equipment Ltd WEBSITE MANUALS/FUJI FRENIC... · International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013

International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3

Page 13 25/03/2013

London Tel: 0208 527 9669 London Fax: 0208 531 0936 Website: www.ileweb.co.uk

Leicester Tel: 0116 269 0900 Leicester Fax: 0116 269 0939

Email: [email protected]

We reserve the right to alter without giving prior notice technical data dimensions and weights described in this manual

n

n

VLI

⋅= 33,405

     

Gearless machines (permanent magnet) For gearless applications the procedure for auto tuning is the same as for the open and closed loop applications above. Once an auto tune is completed a second tune is required for finding the offset of the poles in relation to the permanent magnets, this is known as a pole tune. After carrying out the auto tune set the additional parameter in table 5 below.  

Table 5: Parameters to be set prior to carrying out a pole tune Parameter Description Default value New setting

L05 Current loop controller 1.5 As per following formula

 L=Motor inductance (minimum value between Ld and Lq)

[mH] Vn=Motor rated voltage [V] (F05)

In=Motor rated current [A] (P03) The pole tune can now be carried out as follows. This tune checks for wiring abnormalities so it is important that the motor phasing is correct

ü Make sure the motor is correctly connected i.e U-U, V-V, W-W

ü Set parameter L03 to 1 and press

ü Give the drive a run command by pressing test up or test down. MC & MC1 will

come in and there will be an audible motor noise and the screen should show

“executing” this tune lasts approximately 4 seconds

ü Once the tune is complete “executing” disappears from the screen release the

test direction

$ If  “ER7”  appears  whilst  tuning  it  may  be  because  the  motor  has  surface  mounted  magnets  or  the  motor  wiring   is   incorrect.  To  check  motor  wiring   is  correct  rotate  the  motor  a  quarter  of  a  turn  and  make  a  note  of  the  value  in  parameter  L04  carry  out  another  tune  (as  above  procedure)  if  the  value  of  L04  is  more  than  15°  different  from  the  previous  value  the  motor  wiring  is  incorrect.  If  the  value  is  less  than  15°  out  the  motor  wiring  is  correct  but  the  motor  may  have  surface  mounted  magnets.  If  so  set  L03  to  4  and  tune  again.  If  “ER7”  still  appears  contact  the  ILE  technical  support  department.  

Page 14: FUJI FRENIC INVERTER - International Lift Equipment Ltd WEBSITE MANUALS/FUJI FRENIC... · International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013

International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3

Page 14 25/03/2013

London Tel: 0208 527 9669 London Fax: 0208 531 0936 Website: www.ileweb.co.uk

Leicester Tel: 0116 269 0900 Leicester Fax: 0116 269 0939

Email: [email protected]

We reserve the right to alter without giving prior notice technical data dimensions and weights described in this manual

Final setting prior to running for the first time. The parameters in table 6 have to be worked out and set so the inverter knows how far the lift will travel for 1 revolution of the motor. It needs this information so the speed references and distance based short floor operation work correctly.  

Table 6: Parameters set before running for the first time Parameter Description Default value New setting

F03 Motor RPM at full lift speed 1500 See formula below

 To work out the above parameter use the formula below.  

𝐹03 =19.1×𝑉×𝑅𝐷×𝑃

 

 (R=ROPING RATIO (1 FOR 1:1; 2 FOR 2:1); V=LIFT SPEED IN M/S; D=SHEAVE DIAMETER IN METERS; P= GEAR RATIO e.g. IF THE GEAR RATIO IS 53:2 DIVIDE 2 BY 53 AND INSERT THE RESULT INTO THE FORMULA)

 Setting speeds, acceleration, deceleration and jerks for High speed

S curve for high speed (HS on Skycom Solo, HS or DTS on Skycom)

Figure 13: High speed S curve showing parameters.

High speed

Speed

High speed

ONFWD

SS1

SS2

ON

ON

SS4 ON

Zero speedcommand

High speedcommand

Creep speedcommand

Zero speedcommand

Creep speed

Zero speedL19: S-curve setting 1

E14: Acceleration/deceleration time 7Time

L26: S-curve setting 8 L28: S-curvesetting 10

L28: S-curve setting 10

E12: Acceleration/deceleration time 5

E13: Acceleration/deceleration time 6

L25: S-curve setting 7L24: S-curve setting 6

From the diagram above we can see the parameters for tuning the high speed S curve the parameters are listed below in table 7

Table 7: High speed parameter settings Parameter Description Default value New setting

C07 Creep (level) speed 4Hz, 6m/min, 150RPM Site specific C11 High speed 50Hz, 60 m/min, 1500RPM Site specific L19 Jerk 1 20% Site specific E12 Acceleration rate 1.8 seconds Site specific L24 Jerk 2 20% Site specific L25 Jerk 3 20% Site specific E13 Deceleration rate 1.8 seconds Site specific L26 Jerk 4 20% Site specific L28 Jerk 56 20% Site specific E14 Decel from creep to zero speed 1 .8 seconds Site specific

The parameters in the above table are all of the speed and comfort settings for a high speed run. All speeds on Geared machines will be set so the units are in Hertz, if it is a gearless application we will set the units as meters/minutes to work these back to meters/second divide by 60.

Page 15: FUJI FRENIC INVERTER - International Lift Equipment Ltd WEBSITE MANUALS/FUJI FRENIC... · International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013

International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3

Page 15 25/03/2013

London Tel: 0208 527 9669 London Fax: 0208 531 0936 Website: www.ileweb.co.uk

Leicester Tel: 0116 269 0900 Leicester Fax: 0116 269 0939

Email: [email protected]

We reserve the right to alter without giving prior notice technical data dimensions and weights described in this manual

 All acceleration / deceleration units are in seconds the bigger the figure the softer the accel / decel. All jerks units are percentages of the S curve you are on, the higher the figure the softer the jerk.  

Setting speeds, acceleration, deceleration and jerks for medium speed

S curve for medium speed (MS1 on Skycom) Figure 14: Medium speed S curve showing parameters.

  From the diagram above we can see the parameters for tuning the high speed S curve the parameters are listed below in table 8

Speed

Time

Manual speed (Middle)

ONFWD

SS1

SS2

ON

SS4

ON

Zero speedcommand

Manual speed(Middle) command

Creep speedcommand

Zero speedcommand

Creep speed

Zero speed

Manualspeed (Middle)

L19: S-curve setting 1

E14: Acceleration/deceleration time 7

L26: S-curve setting 8 L28: S-curvesetting 10

L28: S-curve setting 10

E11: Acceleration/deceleration time 4E10: Acceleration/deceleration time 3

L22: S-curve setting 4 L23: S-curve setting 5

 

Table 8: Medium speed parameter settings Parameter Description Default value New setting

C07 Creep (level) speed 4Hz, 6m/min, 150RPM Site specific C10 Medium speed 50Hz, 60 m/min, 1500RPM Site specific L19 Jerk 1 20% Site specific E10 Acceleration rate 1.8 seconds Site specific L22 Jerk 2 20% Site specific L23 Jerk 3 20% Site specific E11 Deceleration rate 1.8 seconds Site specific L26 Jerk 4 20% Site specific L28 Jerk 56 20% Site specific E14 Decel from creep to zero speed 1 .8 seconds Site specific

The parameters in the above table are all of the speed and comfort settings for a high speed run. All speeds on Geared machines will be set so the units are in Hertz, if it is a gearless application we will set the units as meters/minutes to work these back to meters/second divide by 60. All acceleration / deceleration units are in seconds the bigger the figure the softer the accel / decel. All jerks units are percentages of the S curve you are on, the higher the figure the softer the jerk.

Setting speeds, acceleration, deceleration and jerks for reduced power mode S curve for reduced power mode (RPR on Skycom / Skycom Solo)

The Skycom can be parameterised to give an output which when on a non essential journey i.e. Homing and when in a group on no specific traffic pattern, the lift can run at a reduced acceleration, high speed and deceleration rate thus saving energy. The drive parameters for this speed input are as below.  

   

Page 16: FUJI FRENIC INVERTER - International Lift Equipment Ltd WEBSITE MANUALS/FUJI FRENIC... · International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013

International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3

Page 16 25/03/2013

London Tel: 0208 527 9669 London Fax: 0208 531 0936 Website: www.ileweb.co.uk

Leicester Tel: 0116 269 0900 Leicester Fax: 0116 269 0939

Email: [email protected]

We reserve the right to alter without giving prior notice technical data dimensions and weights described in this manual

   

Figure 14: Medium speed S curve showing parameters.

Manual speed (Low)

Time

Speed

ONFWD

SS1

SS2

ON

SS4 ON

ON

Zero speedcommand

Manual speed (Low)command

Creep speedcommand

Zero speedcommand

Creep speed

Zero speed

Manualspeed (Low)

L19: S-curve setting 1

E14: Acceleration/deceleration time 7

L26: S-curve setting 8

F07: Acceleration/deceleration time 1

L20: S-curve setting 2L21: S-curve setting 3

L28: S-curvesetting 10

L28: S-curve setting 10

F08: Acceleration/deceleration time 2

From the diagram above we can see the parameters for tuning the high speed S curve the parameters are listed below in table 9

Table 9 : Reduced power mode speed parameter settings Parameter Description Default value New setting

C07 Creep (level) speed 4Hz, 6m/min, 150RPM Site specific C09 Reduced power speed 50Hz, 60 m/min, 1500RPM Site specific L19 Jerk 1 20% Site specific F07 Acceleration rate 1.8 seconds Site specific L20 Jerk 2 20% Site specific L21 Jerk 3 20% Site specific F08 Deceleration rate 1.8 seconds Site specific L26 Jerk 4 20% Site specific L28 Jerk 56 20% Site specific E14 Decel from creep to zero speed 1 .8 seconds Site specific

The parameters in the above table are all of the speed and comfort settings for a high speed run. All speeds on Geared machines will be set so the units are in Hertz, if it is a gearless application we will set the units as meters/minutes to work these back to meters/second divide by 60.  All acceleration / deceleration units are in seconds the bigger the figure the softer the accel / decel. All jerks units are percentages of the S curve you are on, the higher the figure the softer the jerk.

 Inspection speed

Inspection speed is set in our test department at 15Hz for geared machines or 10 meters/minute for gearless machines if the speed needs increasing or decreasing table 10 highlights the parameter.  

Table 10 : inspection speed parameter settings Parameter Description Default value New setting

C06 Inspection speed 15Hz, 10m/min Site specific

Page 17: FUJI FRENIC INVERTER - International Lift Equipment Ltd WEBSITE MANUALS/FUJI FRENIC... · International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013

International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3

Page 17 25/03/2013

London Tel: 0208 527 9669 London Fax: 0208 531 0936 Website: www.ileweb.co.uk

Leicester Tel: 0116 269 0900 Leicester Fax: 0116 269 0939

Email: [email protected]

We reserve the right to alter without giving prior notice technical data dimensions and weights described in this manual

Performance related settings Brake lift / release timers

The FRENIC inverter controls the lifting of the brake via a relay output (terminals Y5C & Y5A) this in turn drives the BKC contactor on the controller, which then switches the brake voltage. If the brake lifts or drops particularly fast or slow there may be issues with rollback, snatch or general ride discomfort at the start and stop of operation. Table 11 shows the parameters for controlling the brake.

Table 11: Brake parameter settings

Parameter Description Default value New setting L82 Brake lift time 0.2 seconds Site specific L83 Brake drop time 0.2 seconds Site specific

Critical settings for open loop

No load current (parameter P06) The no-load current (function P06) defines the value of the current of the motor when no load is applied to the motor (exciting current). Typical values of the no-load current range from 30 % of P03 up to 70 % of P03. In the majority of the cases the value measured by the auto-tuning procedure will be correct. In some cases the auto-tuning procedure cannot be finished correctly (due to unusual behaviour of the motor). In this later case the value of P03 must be set manually. To

calculate the no-load current you can use the formula ( )2

2F05*1.471000*P02

P03P06 ⎟⎟⎠

⎞⎜⎜⎝

⎛−=

If the value of P06 is too low you will find that the motor does not have enough torque. I the value is too high the motor oscillates (this oscillation will cause a vibration in the motor that is transmitted to the cabin).

Slip frequency (parameter P12) The slip frequency function defines the value of the slip frequency of the motor. It is the key function for good slip compensation by the inverter; this means that this function is very important in open loop control of induction motors for good floor levelling accuracy because it will ensure that the rotating frequency of the motor is the same regardless of the load condition of the motor. In the majority of the cases the value measured by the auto-tuning procedure will be correct. In some cases the auto-tuning procedure cannot be finished correctly (due to unusual behaviour of the motor). In this later case the value of P12 must be set manually. To set function P12 manually we can calculate it from the following formula:

7,0120

_))(_)(_(12 ××−

=PolesNorpmspeedRatedrpmspeedsSynchronouP

Page 18: FUJI FRENIC INVERTER - International Lift Equipment Ltd WEBSITE MANUALS/FUJI FRENIC... · International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013

International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3

Page 18 25/03/2013

London Tel: 0208 527 9669 London Fax: 0208 531 0936 Website: www.ileweb.co.uk

Leicester Tel: 0116 269 0900 Leicester Fax: 0116 269 0939

Email: [email protected]

We reserve the right to alter without giving prior notice technical data dimensions and weights described in this manual

Slip compensation gains (parameter P09 for driving, P10 for braking) The slip frequency can be also compensated in both driving and braking mode. The method for adjusting these values is as follows. You need to measure one floor level with car empty both going up and down:

- If the car speed going up is lower than the desired speed (the car doesn’t reach floor level) decrease the value of P10 by 10% (braking mode).

- If the cabin speed going down is higher than the desired speed (the car goes past floor level) decrease the value of P09 by 10% (driving mode).

Adjust these parameters until good floor levelling accuracy is achieved.      

Gains (closed loop and Gearless) The driving and braking gains of the FRENIC inverter may be adjusted to increase performance with respect to undershoot, overshoot, hunting during high speed and noise / vibration in the motor. The parameters are shown in table 12 below.

 Table 12: Gain parameter settings

Parameter Description Default value New setting L36 ASR P CONSTANT (high

speed) 10% Site specific

L37 ASR I CONSTANT (high speed)

0.02 Site specific

L38 ASR P CONSTANT (low speed)

10% Site specific

L39 ASR I CONSTANT (low speed) 0.02 Site specific L38 ASR P CONSTANT (low

speed) 10% Site specific

 The higher the percentage value the tighter the control of the motor will be, also the smaller the time constant the tighter the control will be. $All gain parameters should be adjusted in small increments, too high or low value can cause the motor to lose control of the load. Consult ILE’s Technical support department if you are unfamiliar with adjusting these parameters.

Anti roll back parameters (gearless only) The FRENIC inverter has an extra set of gain parameters for controlling high out of balance loads in gearless applications. Once enabled the time, P gain and I gain can be adjusted to eliminate any roll back. $Anti roll back parameters should only be enabled after the brake release and drop timers have been set and the gains adjusted (see section 12.1 and 12.2)  The parameters are shown in table 13 below.  

Table 13: Anti roll back parameters (ULC Compensation) Parameter Description Default value New setting

L65 ULC ENABLE 0 1 (to enable) L66 ULC ACTIVATION TIMER 1 Site specific L68 ULC ASR P CONSTANT 10 Site specific L69 ULC ASR I CONSTANT 0.5 Site specific L73 ULC ASR GAIN 5 Site specific

 

Page 19: FUJI FRENIC INVERTER - International Lift Equipment Ltd WEBSITE MANUALS/FUJI FRENIC... · International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013

International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3

Page 19 25/03/2013

London Tel: 0208 527 9669 London Fax: 0208 531 0936 Website: www.ileweb.co.uk

Leicester Tel: 0116 269 0900 Leicester Fax: 0116 269 0939

Email: [email protected]

We reserve the right to alter without giving prior notice technical data dimensions and weights described in this manual

Anti roll back is enabled by changing parameter L65 to 1 The time the anti roll back is enabled for is set using parameter L66 (this should not need to be more than default) The gains in parameters L68, 69 & 73 should then be adjusted until the roll back is adjusted out. $The default parameters set by ILE should eliminate any roll back, if you are unfamiliar with adjusting these parameters consult ILE’s Technical support department

Brake Checking Signal for UCM Compliance (EN81-1 + A3) Introduction

From January 2012 the lift standard EN 81-1:1998+A3:2009 has to be applied. A3 addendum is related to Unintended Car Movement (UCM). In case of electrical traction lifts, one possible solution to fulfill the new A3 addendum of the EN81-1 standard, is to use the two brakes certified according to this standard that are directly coupled to the driving sheave (gearless) and additionally monitor their status individually, by using one switch for each brake that detects the actual brake status (released or applied). If the detected brake status is not correct the operation of the lift must be prevented. The following section explains how to set the function, test the function and reset any alarms related to the UCM.

Description of the function and parameters The parameters related to the UCM function are shown below.

Parameter Description Default value New setting E06 Command Assignmet to

Input X6 25 111

E07 Command Assignmet to Input X7

25 112

H95 BBE Alarm Reset 0 See description H96 Check Brake Control 0 1 L84 Brake Control Check Time 0.00 2.00

This function is not active in factory default settings. It means that this function has to be activated. The parameter used to activate this function is H96. The functionality of H96 is explained below. H96 is set automatically during the wizard if the response to the “brake switches fitted and connected” question is yes.

a) When H96 = 0

Even BRKE1 and BRKE2 functions are correctly programmed (E06 set to 111 and E07 set to 112) and wired, monitoring function for UCM is not active.

b) When H96 = 1

Brake monitoring operation is performed by the BRKE1 and BRKE2 inputs according to UCM. When BRKE1 or BRKE2 status is not correct, the timer of brake check time (L84) starts. BBE alarm is generated when the BRKE1 or BRKE2 inputs remain in an incorrect condition during the brake check time (L84). During the lift travel, the alarm is not issued, the alarm is generated as soon as BRKS function is OFF and L84

Page 20: FUJI FRENIC INVERTER - International Lift Equipment Ltd WEBSITE MANUALS/FUJI FRENIC... · International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013

International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3

Page 20 25/03/2013

London Tel: 0208 527 9669 London Fax: 0208 531 0936 Website: www.ileweb.co.uk

Leicester Tel: 0116 269 0900 Leicester Fax: 0116 269 0939

Email: [email protected]

We reserve the right to alter without giving prior notice technical data dimensions and weights described in this manual

timer expires. For additional details, please refer to the function behavior diagram below.

Function Behavior In the following figures, each possible scenario using BRKE1 and BRKE2 functions are explained.

Brake feedback is abnormal at starting

ON

Speed

0

High speed

Creep speed

FWD

SS1

SS2

SS4

ON

ON

ON

Zero speedcommand

High speed command Creep speedcommand

Zero speedcommand

BRKE1

Brake1 Release

BRKS ON

Stop speed(F25)

H67

L82 L84 L83 L84

BRKE2

ALM

Brake2 Release

ON ON

ON

ON

L82 L84

ON

ON

Release

EN  (EN1,EN2) ON

Inverter trips  bbe.

Standard travelTravel with abnormal brake operation at starting

ON

 

 

Page 21: FUJI FRENIC INVERTER - International Lift Equipment Ltd WEBSITE MANUALS/FUJI FRENIC... · International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013

International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3

Page 21 25/03/2013

London Tel: 0208 527 9669 London Fax: 0208 531 0936 Website: www.ileweb.co.uk

Leicester Tel: 0116 269 0900 Leicester Fax: 0116 269 0939

Email: [email protected]

We reserve the right to alter without giving prior notice technical data dimensions and weights described in this manual

 

Brake  feedback  is  abnormal  at  stopping  

ON

Speed

0

High speed

Creep speed

FWD

SS1

SS2

SS4

ON

ON

ON

Zero speedcommand

High speed command Creep speedcommand

Zero speedcommand

BRKE1

Brake1 Release

BRKS ON

Stop speed(F25)

H67

L82 L84 L83 L84

BRKE2

ALM

Brake2 Release

ON

ON

ON

EN  (EN1,EN2) ON

Inverter trips  bbe.

Brake  feedback  is  abnormal  during  travel  (with  BBE  trip)  

ON

Speed

0

High speed

Creep speed

FWD

SS1

SS2

SS4

ON

ON

ON

Zero speedcommand

High speed command Creep speedcommand

Zero speedcommand

BRKE1

Brake1 Release

BRKS ON

Stop speed(F25)

H67

L82 L84 L83 L84

BRKE2

ALM

Brake2 Release

ON ON

ON

ON

EN  (EN1,EN2) ON

ON

L84

Alarm is internally generated.

Inverter trips  bbe.

Page 22: FUJI FRENIC INVERTER - International Lift Equipment Ltd WEBSITE MANUALS/FUJI FRENIC... · International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013

International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3

Page 22 25/03/2013

London Tel: 0208 527 9669 London Fax: 0208 531 0936 Website: www.ileweb.co.uk

Leicester Tel: 0116 269 0900 Leicester Fax: 0116 269 0939

Email: [email protected]

We reserve the right to alter without giving prior notice technical data dimensions and weights described in this manual

Brake  feedback  is  abnormal  during  travel  (no  BBE  trip)  

ON

Speed

0

High speed

Creep speed

FWD

SS1

SS2

SS4

ON

ON

ON

ON

Zero speedcommand

High speed command Creep speedcommand

Zero speedcommand

BRKE1

Brake1 Release

BRKS ON

Stop speed(F25)

H67

L82 L84 L83 L84

BRKE2

ALM

Brake2 Release

ON ON

ON

EN  (EN1,EN2) ON

Inverter doesn’t trip with bbe, because L84 timer is not expired.

ON

Release

L84 Inverter doesn’t trip  bbe.

Brake  feedback  is  abnormal  when  the  lift  is  stationary  

ON

Speed

0

FWD

SS1

SS2

SS4

BRKE1

Brake1 Release

BRKS

L84

BRKE2

ALM

Brake2 Release

ON

EN  (EN1,EN2)

Inverter trips bbe

ON

L84

ON

Inverter doesn’t trip with bbe, because L84 timer is not expired.

Page 23: FUJI FRENIC INVERTER - International Lift Equipment Ltd WEBSITE MANUALS/FUJI FRENIC... · International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013

International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3

Page 23 25/03/2013

London Tel: 0208 527 9669 London Fax: 0208 531 0936 Website: www.ileweb.co.uk

Leicester Tel: 0116 269 0900 Leicester Fax: 0116 269 0939

Email: [email protected]

We reserve the right to alter without giving prior notice technical data dimensions and weights described in this manual

Test  of  BRKE1  Function  at  start   To test the function follow the following flowcharts

Make a normal call demand on the lift by entering the call from

the CPU

As soon as the inverter is in RUN mode short

between +24V and BKS1 at X15 on the terminal

rail

L84 time is expired

Inverter trips bbE ?

BRKE1 function test at start

NO

YES

Function not properly working check all parameters set

correctly

Remove the short

Follow the reset procedure on page 28

of this manual

Function Testing is finished

Error is reset?

YES

NO

Page 24: FUJI FRENIC INVERTER - International Lift Equipment Ltd WEBSITE MANUALS/FUJI FRENIC... · International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013

International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3

Page 24 25/03/2013

London Tel: 0208 527 9669 London Fax: 0208 531 0936 Website: www.ileweb.co.uk

Leicester Tel: 0116 269 0900 Leicester Fax: 0116 269 0939

Email: [email protected]

We reserve the right to alter without giving prior notice technical data dimensions and weights described in this manual

Test  of  BRKE1  function  during  travel  

Make a normal Car call demand on the lift

using the CPU

During high speed Short between +24V and BKS1 on X15 of

the terminal rail

L84 time is expired

Inverter trips bbE ?

BRKE1 function test during travel

NO

YES

Function not working properly check all

parameters set correctly

Remove the short

Follow the Reset procedure on page 28

of this manual

Function testing finished

Error is reset?

YES

NO

Travel is finished

Page 25: FUJI FRENIC INVERTER - International Lift Equipment Ltd WEBSITE MANUALS/FUJI FRENIC... · International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013

International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3

Page 25 25/03/2013

London Tel: 0208 527 9669 London Fax: 0208 531 0936 Website: www.ileweb.co.uk

Leicester Tel: 0116 269 0900 Leicester Fax: 0116 269 0939

Email: [email protected]

We reserve the right to alter without giving prior notice technical data dimensions and weights described in this manual

Test  of  BRKE2  Function  at  start  

Make a normal call demand on the lift by entering the call from

the CPU

As soon as the inverter is in RUN mode short

between +24V and BKS2 at X15 on the terminal

rail

L84 time is expired

Inverter trips bbE ?

BRKE1 function test at start

NO

YES

Function not properly working check all parameters set

correctly

Remove the short

Follow the reset procedure on page 28

of this manual

Function Testing is finished

Error is reset?

YES

NO

Page 26: FUJI FRENIC INVERTER - International Lift Equipment Ltd WEBSITE MANUALS/FUJI FRENIC... · International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013

International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3

Page 26 25/03/2013

London Tel: 0208 527 9669 London Fax: 0208 531 0936 Website: www.ileweb.co.uk

Leicester Tel: 0116 269 0900 Leicester Fax: 0116 269 0939

Email: [email protected]

We reserve the right to alter without giving prior notice technical data dimensions and weights described in this manual

Test  of  BRKE2  function  during  travel  

Make a normal Car call demand on the lift

using the CPU

During high speed Short between +24V and BKS2 on X15 of

the terminal rail

L84 time is expired

Inverter trips bbE ?

BRKE1 function test during travel

NO

YES

Function not working properly check all

parameters set correctly

Remove the short

Follow the Reset procedure on page 28

of this manual

Function testing finished

Error is reset?

YES

NO

Travel is finished

 

Page 27: FUJI FRENIC INVERTER - International Lift Equipment Ltd WEBSITE MANUALS/FUJI FRENIC... · International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013

International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3

Page 27 25/03/2013

London Tel: 0208 527 9669 London Fax: 0208 531 0936 Website: www.ileweb.co.uk

Leicester Tel: 0116 269 0900 Leicester Fax: 0116 269 0939

Email: [email protected]

We reserve the right to alter without giving prior notice technical data dimensions and weights described in this manual

Fault codes and their meanings Table 14 is a list of all the event codes on the FRENIC inverter, if any events persist please consult ILE’s technical support department

Table 14: Fault codes

Alarm  message  Displayed   Description   Possible  causes  

OC  

Motor  overloaded:  OC1=  Overload  during  acceleration  OC2=  Overload  during  deceleration  OC3=  Overload  during  constant  speed  

Check  if  the  motor  is  connected  correctly  Check  motor  data  has  been  entered  correctly  Check  brake  operation    

OU  

Overvoltage  in  inverter  DC  link:  OU1=  Overvoltage  during  acceleration  OU2=  Overvoltage  during  deceleration  OU3=  Overvoltage  during  constant  speed  

Braking  is  resistor  not  connected  or  defective  Lift  not  balanced  correctly  Deceleration  time  too  short  Check  mains  connection  

LU   Under  voltage  in  inverter  DC  link  

Supply  voltage  too  low  Mains  supply  failure  Acceleration  too  fast  Load  too  high  Check  connection  of  the  input  signal  

Lin   Input  phase  loss   Check  mains  input  fuses  Check  input  connections  

OH1   Inverter  heat  sink  temperature  too  high   Inverter  fan  defective  Ambient  temperature  too  high  

OH2   External  Alarm   Not  used  in  ILE  controller  OH3   Ambient  temperature  around  inverter  too  high   Check  temperature  inside  controller  cabinet  OH4   Motor  over  temperature  detected   Not  used  in  ILE  controller  

PG   Encoder  error  Check  encoder  cable  Motor  not  rotating  (safety  gear  in)  Brake  did  not  lift  

OL1   Motor  overload  

Check  brake  Motor,  car  or  counterweight  safety  gear  in  Inverter  at  current  limit,  possibly  too  small  Check  functions  F10~F12  

OLU   Inverter  overload  

Over  temperature  in  IGBT  Failure  in  the  cooling  system  Switching  frequency  (function  F26)  too  high  Lift  load  too  high.  

Er1   Save  error   Data  has  been  lost  

Er2   Keypad  communication  error   Keypad  was  removed  while  inverter  in  was  running  

Er3   CPU  error   Failure  in  the  inverter  CPU  

Er4   Option  card  communication  error   Option  card  not  correctly  installed.  Check  cables  and  shield  connection.  

Er5   Option  card  error  Check  configuration  (switches  and  bridges  correct?)  Check  cables  and  shield  connection.  

Er6   Operation  error   Check  parameter  L80,  L82,  L83,  L84  If  gearless  carry  out  pole  tuning  

Er7   Error  during  auto  tuning  /  pole  tuning  Check  MC  contactors  are  not  open  Check  encoder  cable  Check  encoder  

Er8   RS485  Comms  error   High  noise  level  Check  connection  

ErE   Speed  error  

Check  brake  Check  safety  gear  is  not  in  Check  parameters  L90-­‐L92  Current  limiter  active  

Page 28: FUJI FRENIC INVERTER - International Lift Equipment Ltd WEBSITE MANUALS/FUJI FRENIC... · International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3 Page 1 25/03/2013

International Lift Equipment Ltd : Fuji Frenic Lift Manual REF: ILE-TS-FUJI v1.3

Page 28 25/03/2013

London Tel: 0208 527 9669 London Fax: 0208 531 0936 Website: www.ileweb.co.uk

Leicester Tel: 0116 269 0900 Leicester Fax: 0116 269 0939

Email: [email protected]

We reserve the right to alter without giving prior notice technical data dimensions and weights described in this manual

If  gearless  was  pole  tuning  successful  

ErH   Option  card  hardware  fault  Option  card  not  correctly  installed  Inverter  software  not  compatible  with  the  option  card  

OS   Motor  speed  greater  than    100

0332xFL(rpm)  

Check  encoder  resolution  parameter  L02  Check  parameter  F03,  P01,  L32  

bbE   Sub  code  11  BRKE1  signal  is  abnormal  Sub  code  12  BRKE2  signal  is  abnormal  

Check  status  of  the  brake  micros  1  or  2  Check  +24V  is  present  at  the  brake  switches  Check  L84  time  

bbe Reset procedure

Because UCM brake switch monitoring is a safety feature it has to be reset via the correct procedure. The event cannot be reset by cycling the inverter power.

• First clear the problem by checking the status of the brake switches, brake switch time (L84) and the supply to the brake switches.

• Go to parameter H95 and enter the value 111 followed by the FUNCTION DATA button

• Press RESET repeatedly until the bbe event is cleared. $NOTE: The bbe event will not clear if the fault that caused the issue in the first instance is not fixed.

Document History

Version Changes Date Author Checked Approved V1.0 Initial Version 31/9/11 J. Colquhoun R. Bierton J. Miller V1.1 Text updated 03/09/12 J. Colquhoun R. Bierton J. Miller

V1.2 UCM function added 20/10/12 J. Colquhoun R. Bierton J. Colquhoun

V1.3 UCM function ammended 15/07/13 J. Colquhoun C. Saunt J. Colquhoun