FUGRO TECHNICAL SERVICES LIMITED Room 723 - 726, 7/F, Block B, Profit Industrial Building, Tel : (852)-24508238 1 – 15 Kwai Fung Crescent, Kwai Fong, Fax : (852)-24508032 Hong Kong. Email : [email protected]

Report No.: 0102/19/ED/0207

The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval from the Company.

A Fugro Group Company

1 | P a g e

Table of Contents

1. Introduction ..................................................................................................................................... 2 2. Site Description ............................................................................................................................... 2 3. Measurement Requirement ............................................................................................................. 2 3.1 Measurement Equipment ................................................................................................................ 3 3.2 Measurement Location .................................................................................................................... 3 4. Result .......................................................................................................................................... 4 5. Conclusion ...................................................................................................................................... 4 Appendix Appendix A Endorsed Test Report Appendix B Calibration Certificate of the Equipment Appendix C Certificate of Accreditation Appendix D Measurement Photos

Page 3: FUGRO TECHNICAL SERVICES LIMITED Quality Report 19101… · Hong Kong. Email : mcl@fugro.com Report No.: 0102/19/ED/0207 The copyright of this document is owned by Fugro Technical

FUGRO TECHNICAL SERVICES LIMITED Room 723 - 726, 7/F, Block B, Profit Industrial Building, Tel : (852)-24508238 1 – 15 Kwai Fung Crescent, Kwai Fong, Fax : (852)-24508032 Hong Kong. Email : [email protected]

Report No.: 0102/19/ED/0207

The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval from the Company.

A Fugro Group Company

2 | P a g e

1. Introduction

This measurement report is prepared by Fugro Technical Services Limited (FTS). It includes the assessment criteria, measurement methodology and results.

2. Site Description

The project site is located along Campus Circuit East in the Chinese University of Hong Kong. The building consists of 3 blocks – Wing A, Wing B and Wing C. It is under major renovation and the work is being conducted in two phases. Wing A and Wing B will be conducted in first phase and Wing C will be conducted in the second phase. The general layout plan of the project site is shown in Figure 2.1.

3. Measurement Requirement

The requirements as stipulated in A Guide on Indoor Air Quality Certification Scheme for Offices and Public Places [2019] will be used as reference in this project. The measurements were conducted by an IAQ Certificate Issuing Body (CIB) in representative locations after building completion. The Certificate of Accreditation is shown in Appendix C. The measuring parameters are listed in Table 3.1.

Wing A

Wing B

Wing C

Page 4: FUGRO TECHNICAL SERVICES LIMITED Quality Report 19101… · Hong Kong. Email : mcl@fugro.com Report No.: 0102/19/ED/0207 The copyright of this document is owned by Fugro Technical

FUGRO TECHNICAL SERVICES LIMITED Room 723 - 726, 7/F, Block B, Profit Industrial Building, Tel : (852)-24508238 1 – 15 Kwai Fung Crescent, Kwai Fong, Fax : (852)-24508032 Hong Kong. Email : [email protected]

Report No.: 0102/19/ED/0207

The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval from the Company.

A Fugro Group Company

3 | P a g e

Table 3.1 Monitoring Parameters and Criteria

Parameters Unit 8-hour average

Excellent Class Good Class

Total Volatile Organic Compounds (TVOC)

μg/m3 < 200 < 600

ppbv < 87 < 261

Formaldehyde (HCHO) μg/m3 < 30 < 100

ppbv < 24 < 81

The methodology listed in “A Guide on Indoor Air Quality Certification Scheme for Offices and Public Places [2019]” (The Guide) shall be followed.

3.1 Measurement Equipment

The technical information of measuring equipment is listed in Table 3.2. Calibration certificates of the measurement equipment are shown in Appendix B. Table 3.2 Measurement Equipment for IAQ

Parameters Model of equipment Serial Number Calibration Date

TVOC ppbRAE 3000 – PGM-7340 594-911965; 594-913809;

13/08/2018; 16/05/2019;

HCHO Riken Keiki FP-31 8Z3050134; 8Z3050139;

20/06/2019; 20/06/2019

3.2 Measurement Location

Total 10 number of indoor primary locations were designated for the IAQ measurements. All measurement locations are marked in Table 3.4.

Table 3.4 Measurement Locations

Location ID Floor Room

1 9/F A905

2 8/F B812

3 8/F A810

4 6/F A601

5 6/F B619

6 5/F A509

7 7/F A702

8 4/F A411

9 3/F A311

10 2/F 202

Page 5: FUGRO TECHNICAL SERVICES LIMITED Quality Report 19101… · Hong Kong. Email : mcl@fugro.com Report No.: 0102/19/ED/0207 The copyright of this document is owned by Fugro Technical

FUGRO TECHNICAL SERVICES LIMITED Room 723 - 726, 7/F, Block B, Profit Industrial Building, Tel : (852)-24508238 1 – 15 Kwai Fung Crescent, Kwai Fong, Fax : (852)-24508032 Hong Kong. Email : [email protected]

Report No.: 0102/19/ED/0207

The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval from the Company.

A Fugro Group Company

4 | P a g e

4. Result Measurements were conducted on 2nd and 3rd October 2019. Measurement photo records can be found in Appendix D. Table 4.1 Result Summary

Location ID

Location Measurement Date TVOC HCHO Compliance

(Yes/No) ppbv ppbv

1 A905

02/10/19

87 40 Yes

2 B812 46 64 Yes

3 A810 125 36 Yes

4 A601 94 28 Yes

5 B619 120 36 Yes

6 A509 71 49 Yes

7 A702

03/10/19

34 51 Yes

8 A411 <20 50 Yes

9 A311 52 50 Yes

10 202 <20 38 Yes

IAQ Good Class Criteria - <261 <81 -

5. Conclusion

Measurement results show that the indoor sources of TVOC and HCHO at 10 locations meet the standard of Good Class criteria in A Guide on Indoor Air Quality Certification Scheme for Offices and Public Places [2019].

Page 6: FUGRO TECHNICAL SERVICES LIMITED Quality Report 19101… · Hong Kong. Email : mcl@fugro.com Report No.: 0102/19/ED/0207 The copyright of this document is owned by Fugro Technical

FUGRO TECHNICAL SERVICES LIMITED Room 723 - 726, 7/F, Block B, Profit Industrial Building, Tel : (852)-24508238 1 – 15 Kwai Fung Crescent, Kwai Fong, Fax : (852)-24508032 Hong Kong. Email : [email protected]

Report No.: 0102/19/ED/0207

The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval from the Company.

A Fugro Group Company

APPENDIX A

Endorsed Test Report

Page 7: FUGRO TECHNICAL SERVICES LIMITED Quality Report 19101… · Hong Kong. Email : mcl@fugro.com Report No.: 0102/19/ED/0207 The copyright of this document is owned by Fugro Technical

FUGRO TECHNICAL SERVICES LIMITED Fugro Development Centre, 5 Lok Yi Street, Tai Lam Tel : (852)-24508233 Tuen Mun, NT Fax : (852)-24506138 Hong Kong. Email : [email protected]

Report No.: 0102/19/ED/0207

The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval from the Company.

A Fugro Group Company

Test Report on Analysis of Air Client : The Chinese University of Hong Kong

Project : VOC and Formaldehyde Measurement for Jockey Club Postgraduate

Hall 1

Sample Description : 10 samples of air

Test Required : 1. Total Volatile Organic Compounds (TVOC) 2. Formaldehyde (HCHO)

Date of in-situ sampling : 02/10/19 – 03/10/19

Test Method Used

Parameters Methodology Model of equipment Sampling Period

TVOC Measured by a real-time TVOC monitor with photo-ionization detector

ppbRAE 3000 – PGM-7340 Four half-an-hour time slot

evenly distributed within the 8-hour sampling period

HCHO Measured by real-time monitor with Photoelectric photometry method

Riken Keiki FP-31

Equipment Used

Parameters Model of equipment Serial Number Calibration Date

TVOC ppbRAE 3000 – PGM-7340 594-911965; 594-913809;

13/08/2018; 16/05/2019;

HCHO Riken Keiki FP-31 8Z3050134; 8Z3050139;

20/06/2019; 20/06/2019

Note: This report refers only to the sample(s) tested.

Page 8: FUGRO TECHNICAL SERVICES LIMITED Quality Report 19101… · Hong Kong. Email : mcl@fugro.com Report No.: 0102/19/ED/0207 The copyright of this document is owned by Fugro Technical
Page 9: FUGRO TECHNICAL SERVICES LIMITED Quality Report 19101… · Hong Kong. Email : mcl@fugro.com Report No.: 0102/19/ED/0207 The copyright of this document is owned by Fugro Technical

FUGRO TECHNICAL SERVICES LIMITED Room 723 - 726, 7/F, Block B, Profit Industrial Building, Tel : (852)-24508238 1 – 15 Kwai Fung Crescent, Kwai Fong, Fax : (852)-24508032 Hong Kong. Email : [email protected]

Report No.: 0102/19/ED/0207

The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval from the Company.

A Fugro Group Company

APPENDIX B

Calibration Certificates of Equipment

Page 10: FUGRO TECHNICAL SERVICES LIMITED Quality Report 19101… · Hong Kong. Email : mcl@fugro.com Report No.: 0102/19/ED/0207 The copyright of this document is owned by Fugro Technical
Page 11: FUGRO TECHNICAL SERVICES LIMITED Quality Report 19101… · Hong Kong. Email : mcl@fugro.com Report No.: 0102/19/ED/0207 The copyright of this document is owned by Fugro Technical
Page 12: FUGRO TECHNICAL SERVICES LIMITED Quality Report 19101… · Hong Kong. Email : mcl@fugro.com Report No.: 0102/19/ED/0207 The copyright of this document is owned by Fugro Technical
Page 13: FUGRO TECHNICAL SERVICES LIMITED Quality Report 19101… · Hong Kong. Email : mcl@fugro.com Report No.: 0102/19/ED/0207 The copyright of this document is owned by Fugro Technical
Page 14: FUGRO TECHNICAL SERVICES LIMITED Quality Report 19101… · Hong Kong. Email : mcl@fugro.com Report No.: 0102/19/ED/0207 The copyright of this document is owned by Fugro Technical

FUGRO TECHNICAL SERVICES LIMITED Room 723 - 726, 7/F, Block B, Profit Industrial Building, Tel : (852)-24508238 1 – 15 Kwai Fung Crescent, Kwai Fong, Fax : (852)-24508032 Hong Kong. Email : [email protected]

Report No.: 0102/19/ED/0207

The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval from the Company.

A Fugro Group Company

APPENDIX C

Certificate of Accreditation

Page 15: FUGRO TECHNICAL SERVICES LIMITED Quality Report 19101… · Hong Kong. Email : mcl@fugro.com Report No.: 0102/19/ED/0207 The copyright of this document is owned by Fugro Technical
Page 16: FUGRO TECHNICAL SERVICES LIMITED Quality Report 19101… · Hong Kong. Email : mcl@fugro.com Report No.: 0102/19/ED/0207 The copyright of this document is owned by Fugro Technical

FUGRO TECHNICAL SERVICES LIMITED Room 723 - 726, 7/F, Block B, Profit Industrial Building, Tel : (852)-24508238 1 – 15 Kwai Fung Crescent, Kwai Fong, Fax : (852)-24508032 Hong Kong. Email : [email protected]

Report No.: 0102/19/ED/0207

The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval from the Company.

A Fugro Group Company

APPENDIX D

Measurement Photo Record

Page 17: FUGRO TECHNICAL SERVICES LIMITED Quality Report 19101… · Hong Kong. Email : mcl@fugro.com Report No.: 0102/19/ED/0207 The copyright of this document is owned by Fugro Technical

FUGRO TECHNICAL SERVICES LIMITED Room 723 - 726, 7/F, Block B, Profit Industrial Building, Tel : (852)-24508238 1 – 15 Kwai Fung Crescent, Kwai Fong, Fax : (852)-24508032 Hong Kong. Email : [email protected]

Report No.: 0102/19/ED/0207

The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval from the Company.

A Fugro Group Company

Room A905 Room B812

Room A810 Room A601

Room B619 Room A509

Page 18: FUGRO TECHNICAL SERVICES LIMITED Quality Report 19101… · Hong Kong. Email : mcl@fugro.com Report No.: 0102/19/ED/0207 The copyright of this document is owned by Fugro Technical

FUGRO TECHNICAL SERVICES LIMITED Room 723 - 726, 7/F, Block B, Profit Industrial Building, Tel : (852)-24508238 1 – 15 Kwai Fung Crescent, Kwai Fong, Fax : (852)-24508032 Hong Kong. Email : [email protected]

Report No.: 0102/19/ED/0207

The copyright of this document is owned by Fugro Technical Services Ltd. It may not be reproduced except with prior written approval from the Company.

A Fugro Group Company

Room A702 Room A411

Room A311 Room 202