Areas of application for Fire Resistant Cables:

Authorized Local Distributor

Hospitals

Metros & Underground Tunnels Airports

HotelsHigh Rise Buildings

Previous Page | Next Page

Page 2: Fr single core

Core Identification

Green/Yellow Blue Red

Brown Black Grey White

Application- Essential safety circuits where the cable is laid in metal conduit or on metal trays

- Use in emergency lighting and fire alarm system

- Where situation demands single core cable meeting fire resistance test for special application.

Construction1. Copper conductor: Plain annealed stranded class 2 conductor to

BS EN 60228

2. Primary Insulation: Mica Glass tape

3. Secondary Insulation: Extruded XL-LSF compound

Technical data for Ducab Fire Resistant Single Core Cables with stranded copper conductors 600 / 1000 V

Current rating based on installation "enclosed in conduit on a wall or in trunking" in line with BS 7671 (IEE Wiring Regulations) Laying condition: 30°C ambient temperature & 90°C operating temperature. For other ambient temperatures appropriate rating factors should be applied.

Nominal conductor

area

Approximateoverall

Diameter

Approximatecable weight

Maximum conductor

resistance at 20°C

Current rating(1ø AC)

Current rating(3ø AC)

Voltage drop(1ø AC)

Voltage drop(3ø AC)

mm² mm kg/km Ohm/km Amp Amp mV/A/m mV/A/m

1.5

2.5

4

6

10

16

25

35

50

70

95

120

150

185

240

300

400

500

630

3.5

4.1

4.7

5.2

6.5

7.4

9.4

10.5

11.9

13.6

15.5

17.0

18.9

21.0

23.6

26.5

29.3

32.7

36.7

26

38

54

74

120

180

280

370

500

695

955

1180

1450

1820

2370

2965

3735

4800

6085

12.1

7.41

4.61

3.08

1.83

1.15

0.727

0.524

0.387

0.268

0.193

0.153

0.124

0.0991

0.0754

0.0601

0.047

0.0366

0.0283

23

31

42

54

75

100

133

164

198

253

306

354

393

449

528

603

683

783

900

20

28

37

48

66

88

117

144

175

222

269

312

342

384

450

514

584

666

764

31

19

12

7.9

4.7

2.9

1.9

1.35

1.05

0.75

0.58

0.48

0.43

0.37

0.33

0.31

0.29

0.28

0.27

27

16

10

6.8

4

2.5

1.65

1.15

0.9

0.65

0.5

0.42

0.37

0.32

0.29

0.27

0.25

0.24

0.23

- Fire Resistance: C-W-Z test as per BS 6387 for small sizes and IEC 60331-21 for large sizes which cannot fit in a conduit.

- Acid gas emission: Less than 0.5 % when tested to IEC 60754 & BS EN 50267

- Low smoke emission: As per IEC 61034 & BS EN 50268

- Ducab – FR SC cables comply to IEC 60331-21 fire test at increased temperature of 950°C, which is higher than that specified by the standard.

Technical Data Introduction Performance Characteristics is Fire Resistant Single Core cable with approval from Loss Prevention

Certification Board, UK for the use in emergency safety circuits to maintain circuit integrity

under fire conditions.

These cables are certified by LPCB as fire resistant on the basis of successful fire resistance

tests carried out in their laboratory. For smaller sizes which can fit in a conduit, C-W-Z tests of

BS 6387 are carried out whereas for large size cables a fire resistance test as per IEC 60331-21

is carried out at an enhanced temperature of 950°C. The applied voltage during the fire testing

is based on the 600/1000 volts system.

The cables are designed for laying in metallic conduit or in cable trunking

where electrical circuit integrity under fire circumstances is of paramount importance. These

cables are designed with special materials which ensure very low smoke and zero halogen in

the event of a fire. The low smoke generation gives better visibility in a fire situation aiding the

rescue operation and enabling the EXIT path to be seen clearly for escape. As there is no

halogen or acidic gas emission during burning of the cable, the sensitive equipments in the

surrounding areas are not affected adversely.

These cables employ primary insulation of Mica Glass fire resistant tape along with the

secondary insulation of Cross Linked Low Smoke and Fume (XL-LSF) material. This cable has

an operating temperature of 90°C. The cable is suitable for installation in accordance with BS

7671 – IEE wiring regulations.

Ducab’s Quality Management System is certified to ISO 9001 by BASEC.

BS 6387 fire testing in progress at Ducab

(Other colours as per request)

Temperature Rating FactorsAmbient Temperature in °C 25 30 35 40 45 50 55 60

Rating factor 1.02 1.00 0.96 0.91 0.87 0.82 0.76 0.71

Correction Factors for GroupingNumber of circuits 2 3 4 5 6 7 8 9

Rating factor 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50

Previous Page | Next Page Previous Page | Next Page Previous Page | Next Page

Page 3: Fr single core

Core Identification

Green/Yellow Blue Red

Brown Black Grey White

Application- Essential safety circuits where the cable is laid in metal conduit or on metal trays

- Use in emergency lighting and fire alarm system

- Where situation demands single core cable meeting fire resistance test for special application.

Construction1. Copper conductor: Plain annealed stranded class 2 conductor to

BS EN 60228

2. Primary Insulation: Mica Glass tape

3. Secondary Insulation: Extruded XL-LSF compound

Technical data for Ducab Fire Resistant Single Core Cables with stranded copper conductors 600 / 1000 V

Current rating based on installation "enclosed in conduit on a wall or in trunking" in line with BS 7671 (IEE Wiring Regulations) Laying condition: 30°C ambient temperature & 90°C operating temperature. For other ambient temperatures appropriate rating factors should be applied.

Nominal conductor

area

Approximateoverall

Diameter

Approximatecable weight

Maximum conductor

resistance at 20°C

Current rating(1ø AC)

Current rating(3ø AC)

Voltage drop(1ø AC)

Voltage drop(3ø AC)

mm² mm kg/km Ohm/km Amp Amp mV/A/m mV/A/m

1.5

2.5

4

6

10

16

25

35

50

70

95

120

150

185

240

300

400

500

630

3.5

4.1

4.7

5.2

6.5

7.4

9.4

10.5

11.9

13.6

15.5

17.0

18.9

21.0

23.6

26.5

29.3

32.7

36.7

26

38

54

74

120

180

280

370

500

695

955

1180

1450

1820

2370

2965

3735

4800

6085

12.1

7.41

4.61

3.08

1.83

1.15

0.727

0.524

0.387

0.268

0.193

0.153

0.124

0.0991

0.0754

0.0601

0.047

0.0366

0.0283

23

31

42

54

75

100

133

164

198

253

306

354

393

449

528

603

683

783

900

20

28

37

48

66

88

117

144

175

222

269

312

342

384

450

514

584

666

764

31

19

12

7.9

4.7

2.9

1.9

1.35

1.05

0.75

0.58

0.48

0.43

0.37

0.33

0.31

0.29

0.28

0.27

27

16

10

6.8

4

2.5

1.65

1.15

0.9

0.65

0.5

0.42

0.37

0.32

0.29

0.27

0.25

0.24

0.23

- Fire Resistance: C-W-Z test as per BS 6387 for small sizes and IEC 60331-21 for large sizes which cannot fit in a conduit.

- Acid gas emission: Less than 0.5 % when tested to IEC 60754 & BS EN 50267

- Low smoke emission: As per IEC 61034 & BS EN 50268

- Ducab – FR SC cables comply to IEC 60331-21 fire test at increased temperature of 950°C, which is higher than that specified by the standard.

Technical Data Introduction Performance Characteristics is Fire Resistant Single Core cable with approval from Loss Prevention

Certification Board, UK for the use in emergency safety circuits to maintain circuit integrity

under fire conditions.

These cables are certified by LPCB as fire resistant on the basis of successful fire resistance

tests carried out in their laboratory. For smaller sizes which can fit in a conduit, C-W-Z tests of

BS 6387 are carried out whereas for large size cables a fire resistance test as per IEC 60331-21

is carried out at an enhanced temperature of 950°C. The applied voltage during the fire testing

is based on the 600/1000 volts system.

The cables are designed for laying in metallic conduit or in cable trunking

where electrical circuit integrity under fire circumstances is of paramount importance. These

cables are designed with special materials which ensure very low smoke and zero halogen in

the event of a fire. The low smoke generation gives better visibility in a fire situation aiding the

rescue operation and enabling the EXIT path to be seen clearly for escape. As there is no

halogen or acidic gas emission during burning of the cable, the sensitive equipments in the

surrounding areas are not affected adversely.

These cables employ primary insulation of Mica Glass fire resistant tape along with the

secondary insulation of Cross Linked Low Smoke and Fume (XL-LSF) material. This cable has

an operating temperature of 90°C. The cable is suitable for installation in accordance with BS

7671 – IEE wiring regulations.

Ducab’s Quality Management System is certified to ISO 9001 by BASEC.

BS 6387 fire testing in progress at Ducab

(Other colours as per request)

Temperature Rating FactorsAmbient Temperature in °C 25 30 35 40 45 50 55 60

Rating factor 1.02 1.00 0.96 0.91 0.87 0.82 0.76 0.71

Correction Factors for GroupingNumber of circuits 2 3 4 5 6 7 8 9

Rating factor 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50

Previous Page | Next Page Previous Page | Next Page Previous Page | Next Page

Page 4: Fr single core

Core Identification

Green/Yellow Blue Red

Brown Black Grey White

Application- Essential safety circuits where the cable is laid in metal conduit or on metal trays

- Use in emergency lighting and fire alarm system

- Where situation demands single core cable meeting fire resistance test for special application.

Construction1. Copper conductor: Plain annealed stranded class 2 conductor to

BS EN 60228

2. Primary Insulation: Mica Glass tape

3. Secondary Insulation: Extruded XL-LSF compound

Technical data for Ducab Fire Resistant Single Core Cables with stranded copper conductors 600 / 1000 V

Current rating based on installation "enclosed in conduit on a wall or in trunking" in line with BS 7671 (IEE Wiring Regulations) Laying condition: 30°C ambient temperature & 90°C operating temperature. For other ambient temperatures appropriate rating factors should be applied.

Nominal conductor

area

Approximateoverall

Diameter

Approximatecable weight

Maximum conductor

resistance at 20°C

Current rating(1ø AC)

Current rating(3ø AC)

Voltage drop(1ø AC)

Voltage drop(3ø AC)

mm² mm kg/km Ohm/km Amp Amp mV/A/m mV/A/m

1.5

2.5

4

6

10

16

25

35

50

70

95

120

150

185

240

300

400

500

630

3.5

4.1

4.7

5.2

6.5

7.4

9.4

10.5

11.9

13.6

15.5

17.0

18.9

21.0

23.6

26.5

29.3

32.7

36.7

26

38

54

74

120

180

280

370

500

695

955

1180

1450

1820

2370

2965

3735

4800

6085

12.1

7.41

4.61

3.08

1.83

1.15

0.727

0.524

0.387

0.268

0.193

0.153

0.124

0.0991

0.0754

0.0601

0.047

0.0366

0.0283

23

31

42

54

75

100

133

164

198

253

306

354

393

449

528

603

683

783

900

20

28

37

48

66

88

117

144

175

222

269

312

342

384

450

514

584

666

764

31

19

12

7.9

4.7

2.9

1.9

1.35

1.05

0.75

0.58

0.48

0.43

0.37

0.33

0.31

0.29

0.28

0.27

27

16

10

6.8

4

2.5

1.65

1.15

0.9

0.65

0.5

0.42

0.37

0.32

0.29

0.27

0.25

0.24

0.23

- Fire Resistance: C-W-Z test as per BS 6387 for small sizes and IEC 60331-21 for large sizes which cannot fit in a conduit.

- Acid gas emission: Less than 0.5 % when tested to IEC 60754 & BS EN 50267

- Low smoke emission: As per IEC 61034 & BS EN 50268

- Ducab – FR SC cables comply to IEC 60331-21 fire test at increased temperature of 950°C, which is higher than that specified by the standard.

Technical Data Introduction Performance Characteristics is Fire Resistant Single Core cable with approval from Loss Prevention

Certification Board, UK for the use in emergency safety circuits to maintain circuit integrity

under fire conditions.

These cables are certified by LPCB as fire resistant on the basis of successful fire resistance

tests carried out in their laboratory. For smaller sizes which can fit in a conduit, C-W-Z tests of

BS 6387 are carried out whereas for large size cables a fire resistance test as per IEC 60331-21

is carried out at an enhanced temperature of 950°C. The applied voltage during the fire testing

is based on the 600/1000 volts system.

The cables are designed for laying in metallic conduit or in cable trunking

where electrical circuit integrity under fire circumstances is of paramount importance. These

cables are designed with special materials which ensure very low smoke and zero halogen in

the event of a fire. The low smoke generation gives better visibility in a fire situation aiding the

rescue operation and enabling the EXIT path to be seen clearly for escape. As there is no

halogen or acidic gas emission during burning of the cable, the sensitive equipments in the

surrounding areas are not affected adversely.

These cables employ primary insulation of Mica Glass fire resistant tape along with the

secondary insulation of Cross Linked Low Smoke and Fume (XL-LSF) material. This cable has

an operating temperature of 90°C. The cable is suitable for installation in accordance with BS

7671 – IEE wiring regulations.

Ducab’s Quality Management System is certified to ISO 9001 by BASEC.

BS 6387 fire testing in progress at Ducab

(Other colours as per request)

Temperature Rating FactorsAmbient Temperature in °C 25 30 35 40 45 50 55 60

Rating factor 1.02 1.00 0.96 0.91 0.87 0.82 0.76 0.71

Correction Factors for GroupingNumber of circuits 2 3 4 5 6 7 8 9

Rating factor 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50

Previous Page | Next Page Previous Page | Next Page Previous Page | Next Page

Page 5: Fr single core

Areas of application for Fire Resistant Cables:

Authorized Local Distributor

Hospitals

Metros & Underground Tunnels Airports

HotelsHigh Rise Buildings

Previous Page | Next Page

Page 6: Fr single core

Areas of application for Fire Resistant Cables:

Authorized Local Distributor

Hospitals

Metros & Underground Tunnels Airports

HotelsHigh Rise Buildings

Previous Page | Next Page