FP5000
Refer to www.eatonelectrical.com for the latest information on this constantly evolving product
FP5000 Product Overview• Microprocessor design
combines protection, metering and control into a single compact package
• Flexible configuration and programmable logic control for custom applications
• Easy navigation keys and menu structure make it simple and safe to use
• Meets ANSI, UL and CUL standards
FP5000 Product Overview
• User Interface– Latching cover and Password protection for
security– 4 x 20 character vacuum fluorescent display for
improved readability– 18 status LED’s for trip, alarm, breaker status and
display mode indication• Battery backed up trip LED for target indication even
if station is dead
– Direct access to monitoring, view settings, logs and status/control screens
– Breaker open/close buttons can provide direct breaker control when enabled
FP5000 Product Overview
• Hardware– Advanced 32 bit Microprocessor design– Compact drawout case design for easy
installation and removal– Four currents inputs (1A or 5A)
• Measured three phase and ground currents• Calculated residual ground current
– Four voltage inputs• Three phase plus fourth auxiliary voltage
measurement
FP5000 Product Overview
• Hardware– 8 optically isolated contact inputs– 5 trip rated “a” contact outputs
• 2 outputs with circuit continuity monitoring
– 2 form c alarm contacts• One is for relay healthy alarm
– C-H Zone Interlocking Circuitry– Inputs and outputs are user configurable
FP5000 Protection Features
• Three phase and ground overcurrent (50P-1, 50P-2, 50P-3, 51P and 50R-1, 50R-2,50R-3,51R, 50X-1,50X-2,50X-3,51X)– Measured (X) and calculated (R) ground currents
• Negative sequence overcurrent (46-1, 46-2)• Three phase over and under voltage
protection (27M-1, 59M-1, 27M-2, 59M-2)• Single phase over and under voltage
protection (27A-1, 27A-2, 59A-1, 59A-2)• Over and under frequency protection (81U-1,
81U-2, 81O-1, 81O-2)
FP5000 Protection Features
• Negative sequence over voltage protection (47-1,47-2)
• Breaker failure (50BF)– Internal Breaker Failure Initiation– External Breaker failure Initiation
• Apparent and Displacement Power factor (55A,55D)
• Four setting groups available
FP5000 Protection Features
• Zone Interlocking– Faster fault clearing times with better
zone coordination – Stuck breaker (breaker failure)
accelerated remote fault clearing – Phase and ground selectable– Extended range up to 1000’ – Works with DT3000
•Zone Interlocking•Fault @ Location 2•Relay @ CB2 sees fault & sends interlocking signal to upstream devices at CB1•Upstream devices continues to operate on normal set time for remote backup protection•CB2 fast trips to interrupt fault•If CB2 fails to interrupt fault in 10 cycles remote clearing of CB1 occurs
•Fault @ Location 1•Relay @ CB2 does not see the fault - no signal is sent to relay @ CB1•Relay @ CB1 sees fault but does not receive interlocking signal - Fast Trips
Zone 1
Zone 2
CB1
Fault 2
FP5000 Protection Features
CB2
Fault 1
FP-5000 Metering Features
• RMS Load Values– Currents - Ia, Ib, Ic, IX, IR, I Average– Voltages - LL, LN, VX, LL Average, LN Average– System Power - Watts, vars, VA– Power Factor, Frequency– % THD Voltage and Current– Magnitude THD Voltage and Currents
• Current accuracy ±0.5% or ±0.025 A• Voltage accuracy ±0.5% or ±0.02 V• Power accuracy ±1.5% worse case
FP5000 Metering Features
• Fundamental phasor measurements– Magnitude and phase angle of
voltages and currents– Magnitude and phase angle of
positive, negative and zero sequence voltages and currents
– Percent voltage unbalance and phase rotation (%V2/V1)
– Percent current unbalance and phase rotation (%I2/I1)
FP-5000 Metering Features
• Energy Measurements– System Watt Hours - Forward, Reverse, Net– System var Hours - Forward, Reverse, Net– System VA Hours– Start Date & Time for Energy Accumulation
• Minimum & maximum values– Phase and Ground Currents – Voltages - LL and LN– System Power– Frequency– Power Factor– time and date stamp
FP-5000 Monitoring Features
• Relay self-diagnostics and Relay Healthy Alarm Output (failsafe operation)– Memory and setting checks– Calibration and A/D monitoring– Power supply monitoring– Watchdog timer
• Trip circuit monitoring and alarming• Close circuit monitoring and alarming
FP-5000 Monitoring Features
• Circuit breaker monitoring and Alarming– Breaker open/close state and indication– Operation counter and alarm– Breaker wear alarm (accumulated
interrupted current per phase) – 52 auxiliary contact monitoring with 52a
and 52b contact inputs connected– Sluggish breaker operation monitoring– Loss of Vacuum monitoring– Stuck breaker (breaker failure)
FP-5000 Logic & Control Features
• Breaker open and close logic with front panel open/close control
• Power factor monitoring and cap bank switching control
• Output contact logic gate control• Overcurrent blocking gates• Multiple setting group selection
and control• Main-tie-main transfer schemes
FP-5000 Logic & Control Features
• Programmable logic control function– Six programmable logic gates
• AND OR, NAND, NOR• 4 programmable inputs
– Six programmable timers• Pick up time delay• Drop out time delay
– Two Latching logic gates– Use internal or external signals
Cin1Cin2Cin3Cin4Cin5Cin6Cin7Cin8
Zin
Input Data Store:CinState - Cin1-8, ZinCinBkr - 52a, 52b, BFIRemOpen, RemClose
PROT Data Store:Pickup FlagsTrip Flags
TRIP1TRIP2K3K4K5ALM1ALM2Zout
Breaker Data Store:Bkr StateBkr OperationsBkr Accum I
System Alarm Flags
TRIP1, TRIP2 Monitor In
Open/Close Bkr PB
Comm Open/Close Bkr
COUT Data Store:Relay StatesComm Trip / Alarm IndicatorsLED States
Comm Logic Flags
CIN
Block50z#(9)
IN1IN2IN3IN4
Timer Gate(6)
On Delay
Off Delay
IN
LogicGate(6)
Latch(2)
COUT
BKR
PROT
COMM
MNTR
LOGIC
Logic Data Store:LOGIC_BlkState
LOGIC
Block51z(3)
DIRRECL
CNTRL Data Store:RecloseFlagsSync FlagsDirectionFlags
Logic Data Store:LOGIC_LGxStateLOGIC_TGxStateLOGIC_OGxState
LOGIC_LGxState, LOGIC_TGxState
LOGIC_OGxState
Direction
Recl
LOGIC_LGxState,LOGIC_TGxState
IN1IN2IN3IN4
IN1IN2IN3IN4
S et
Reset
LG1 - LG6
Q1 - Q2
TG1 - TG6
OutputGate(7)
IN1IN2IN3IN4
OG1 - OG7
Disarm
Reset
RelayTest
FP-5000 Data Logging Features
• Event log records 100 events with date and time stamp ( 1 ms resolution)– Event Types
• General – Control power on/off– Breaker open/close– Reset demand, min/max, energy– Change settings
• Trip, alarm, pickup, dropout• Input / output state change• Self-test warning
FP-5000 Data Logging Features
• Trip log records last 16 trips– Date & time stamp (1 ms resolution)– Fault type, status – Trip counter, event number, osc buffer– Time to trip (51 elements)– Phase currents & voltages (rms. and phasor)– Frequency– I/O and logic states
FP-5000 Data Logging Features
• History log records accumulated values– Number of operating hours– Number of trips– Number of breaker operations– Accumulated interrupted amps per phase– Times powered up– Number of setting changes– Date and time stamp of last reset
FP-5000 Data Logging Features
• Data logger– 1024 records in 128 blocks– Each block: timestamp & 8 records– Log 8 quantities in each record
• Default configuration logs currents & voltages• Select from V, I, Power, PF, Freq, %THD, Demand,
Contact inputs/outputs
– Select logging interval from 1 s to 1 hour– Select continuous or single pass logging– Trigger: auto, Cin, Logic, PB, Comm.
FP-5000 Data Logging Features
• Waveform Capture– 256 cycles of data storage– Select Trigger: Pickup, Trip, Cin, dV/dI, Logic,
PB, Comm. – Number of pre-trigger cycles is configurable– Stored Parameters– 32 samples per cycle: 4 Currents, 4 Voltages – Once a cycle:
• rms and phasor Voltages & Currents• Frequency, Fault Type• Input & Output States• Pickup, Trip, Alarm, & Logic States