John D. O'Toole Vice President S
Consolidated Edison Company of New York, Inc. 4 Irving Place, New York, NY 10003 Telephone (212) 460-2533
May 4, 1982
Re: Indian Point Unit No. 2 Docket No. 50-247
-\.
Director of Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Washington, D. C. 20555 4
ATTN: Mr. Steven A. Varga, Chief Operating Reactors Branch No. Division of Licensing
Dear Mr. Varga:
Attached is our response to your letter of request for additional information.
February 25, 1982 regarding a
Should you or your staff have any questions, please contact us.
Very truly yours,
Attachments
/1;
8205110389 820504 PDR ADOCK 05000247 P PDR
ATTACHMENT A
Environmental Qualification of Safety Related Electrical Equipment
Response To February 25, 1982 NRC Request For Additional Information
TMI Action Plan Requirements
April 1982
Consolidated Edison Company of New York, Inc. Indian Point Unit No. 2
Docket No. 50-247 Facility Operating License No. DPR-26
ATTACHM-ENT A
The paragraph numbers below correspond to paragraph numbers in the enclosure to the NRC letter from Mr. Steven A. Varga to Mr. John D. O'Toole dated February 25, 1982
Ia.) Identification of all TMI Action Plan equipment installed to date in a harsh environment is included in Attachment B.
lb.) The equipment tables use a format consistent with our original submittal of May 9, 1980 and our updated submittal of October 31, 1980. We have retained this format in order to expedite our response to your request. Nevertheless, the subcategory headings under the Equipment Type Column provide correlation to some of the TMI Action Plan sections.
lc.) Indian Point Unit No. 2 was advanced into the SEP Group for its environmental qualification review and, therefore, the 79-01B format and the SCEW sheets did not apply to our original submittals. Nevertheless, our September 4, 1981 submittal which forwarded our 90 Day Response to the Staff SER did include SCEW sheets for those items that were addressed at that time.
ld.) The bulk of the TMI equipment installations in harsh evironments, particularly containment, were installed during our extended outage from October 1980 through May 1981. For most of those items, the projects were initiated prior to the May 1980 Commission Order on environmental qualification. Where possible, items were upgraded to 1974 qualification, if they did not extend that outage. Individual line items in the Attachment B tables are footnoted appropriately if they are IEEE 323 (1971) qualification items.
2.) Individual qualification reports have-not been provided because of their tremendous volume. These reports are contained in our auditable environmental qualification files at our Corporate Office and are available for review by the NRC Staff.
3.) Con Edison had made references to Standard Owners' Group positions and has requested extensions of implementation dates with respect to the NUREG-0737 technical areas in our original submittal of February 26, 1981 and updated submittals of May 12, 1981 and July 1, 1981. Additional extensions have been requested in our submittals of December 30, 1981, February 4, 1982 and April 16, 1982.
4.) The dose calculations according to the guidelines are extremely conservative and include large margins to account for uncertainties. The normal operating exposures are included in these calculations. These normal exposures are at least two orders of magnitude below the accident exposures and are therefore insignificant for the purposes of qualification testing. With regard to equipment near the sump, no new
now equipment near the sump has been identified in this
submittal. Equipment identified in our original May 9, 1980
submittal and our September 4, 1981 submittal near the sump has
been previously reviewed.
5.) Information concerning radiation environments outside containment
has been provided in our original May 9, 1980 submittal and
updated in our September 4, 1981 submittal. This information has been summarized in the introduction to Attachment B.
ATTACHMENT B
Environmental Qualification of Electrical Equipment
TMI Action Plan Equipment
April 1982
Consolidated Edison Company of New York, Inc. Indian Point Unit No. 2
Docket No. 50-247 Facility Operating License No. DPR-26
ATTAC1LMENT B
This Attachment summarizes the results of an investigation conducted to
review the environmental qualification levels for electrical equipment
installed prior to this date at Indian Point Unit No. 2 in response to
TMI "Lessons Learned" and the TMI Action Plan (NUREG-0737). The
investigation was initiated in response to environmental qualification
requirements appearing in NUREG-0737 as well as NRC's I&E Bulletin 79-01B
as applied to Indian Point 2.
The scope of systems and components listed for investigation was
determined using previously derived levels of inside and outside
containment environmental conditions that could occur as the result of
postulated events consisting of Loss of Coolant Accident (LOCA) or a High
Energy Line Break (HELB). Inside and outside containment service
conditions were specified in the May 9, 1980 and subsequently modified in
the September 4, 1981 submittals to NRC in order to conform to the
requirements specified in the May 21, 1981 NRC Staff Safety Evaluation
Report. The applicable service conditions are summarized below:
Containment Accident Conditions (C)
Maximum Pressure: 40.6 psig
Saturation Temperature: 287°F
Humidity: 100%
Radiation: 2 x 108 rads
Chemical Spray: 2000 ppm boric acid spray with 40% NaOH to
result in pH 10.0
Pipng eneraton reaAccident Conditions (PP)
Maximum Pressure:; Ambient
Saturation Temperature: Ambient
Humidity: Ambient
Radiation: 3.6x10 rads
Chemical Spray: None
Aux. Feed Pump Room Accident Conditions (AP)
Maximum Pressure:
Saturation Temperature:
Humidity:
Radiation:
Chemical Spray:
0.9 psig
215 0 F
100%
Negligible
None
A list of T141 related components installed at Indian Point 2 has been
developed and reviewed to identify equipment that would be exposed to
severe environmental conditions following a postulated accident. This
listing, complete with the service conditions and the qualification data
associated with each component, is included herein. Equipment located
in areas outside the containment considered to be mild environments due
to no change in service conditions following the postulated LOCA or HELB
were excluded from this listing.
Electrical cables in the pipe penetration area, outside containment, a re
still undergoing review for environmental qualification. As soon as this
review is completed, we will submit a table to update this report.
Piping Penetration Area
PARAMETER ABREVIATIONS
Temp Temperature in degrees fahrenheit
Press Pressure in pounds per square inch gauge
R H Relative Humidity in percent
Chem Containment Chemical Spray
Rad Integrated Radiation Dose
Sub Submerged
LOCATION ABREVIATIONS
C Inside containment
PP Pipe penetration area outside of and adjacent
to containment
AP Auxiliary feedwater pump room
QUALIFICATION DATA ABREVIATIONS
Spec Specifications
Qual Qualifications
Ref Reference
NA Not applicable
P Separate Methodology of Qualification
S Sequential Methodology of Qualification
Amb Ambient
Table 1 (1 of 3) INDIAN POINT 2
TMI EQUIPMENT QUALIFICATION FOR HARSH ENVIRONMENT
Time Environmental Qual. Equipment Type Loc. Needed Parameter Spec. Qual. Method Ref. Note
Valve Motor Operators:
Primary Coolant Sample P.P. 30 day Temp Amb NA S (1) Line Valves MOV 5153, Press Amb NA 5154, 956 E&F RH Amb NA Limitorque SMB-000 Chem No NA H-Insulation Rad 3.6x10 6 2x10 8
Sub No NA
RCS Sample Line Valves C 30 day Temp 287 300 5 (1) MOV 955 A&B Press 40.6 70
.Limitorque SMB-000 RH 100 100 H-Insulation Chem YES YES
Rad 2xlO 8 2x10 8
Sub No NA
RCS Sample Line to P.P. 30 day Temp Amb NA (1) Booster Pump Valves Press Amb NA MOV 4396, 4397 RH Amb NA Limitorque SMB-000 Chem No NA H-Insulation Rad 3.6xi0 6 2xlO 8
Sub No NA
Flush Water to RCS P.P. 30 day Temp Amb NA (1) Sample Line Valves Press Amb NA MOV 4394, 4395 RH Amb NA Limitorque SMB-O00 Chem No NA H-Insulation Rad 3.6x10 6 2xlO 8
Sub No NA
Table 1 (2 of 3) INDIAN POINT 2
TMI EQUIPMENT QUALIFICATION FOR HARSH ENVIRONMENT
Time Environmental Qual. Equipment Type Loc. Needed Parameter Spec. Qual. Method Ref. Note
Valve Motor Operators (Contt d):
RHR Loop Sample Line P.P. 30 day Temp Ainb. NA S() Valves MOV-958, 959 Press Anab. NA Limitorque SMB-000 RH Amb. NA H-Insulation Chem No NA
Rad 3.6xi0 6 2x10 8
Sub No NA
Recirculation Pump P.P. 30 day Temp Amb. NA S() Discharge Sample Line Press Amb. NA Valves RH Amb. NA MOV-990A & B Chem No NA Limitorque SMB-000 Rad 3.6xi0 6 2x10 8
H - Insulation Sub No NA
RHR Miniflow Line P.P. 30 day Temp Arab. NA (1) Valves MOV 1870, 743 Press Amb. NA LimitorquE SMB-000 RH Amb. NA H - Insulation Chem No NA
Rad 3.6x10 6 2x10 8
Sub No NA
Seal Water Return Valve P.P. 30 day Temp Anb. NA (1) MOV 222 Press Amb. NA Limitorque SMB-O00 RH Amb. NA H - Insulation Chem No NA
Rad 3.6x10 6 2x10 8
Sub No NA
CVCS Charging Line P.P. 30 day Temp Amb. NA (1) Valves Press Amb. NA MOV-205, RH Amb. NA 226, 227 Chem No NA Limitorque Rad 3.6xi0 6 2x10 8
H - Insulation Sub No NA
Table 1 (3 of 3)
INDIA1 POINT 2 TMI EQUIPMENT QUALIFICATION
FOR HARSH ENVIRONMENT
Eauioment Type Loc.Time
Needed
Environmental
Parameter Spec. Oual.Qual. Method Ref. Notes
Valve 'Motor Operators
RC Pump Seal Water
Supply Valves
MOV 4925 thru 4928, 250 A thru D
Limitorque SMB-00 &
SMB-000
H - insulation
Sample Injection
to Containment Sump
MOV 4399, 5132
Limitorque SMB-000
H - Insulation
Safety Injection
Pump
Discharge Valves
MOV 850 A&B
Limitorque SMB-000 H - Insulation
Containment Spray
System
Header: Valves
MOV-869 A&B
Limitorque SHB-000
H - Insulation
(Cont'd):
P.P.
P.P.
P. P.
P.P.
30 day
30 day
30 day
30 day
0
Temp Press
RH Chem
Rad
Sub
Temp
Press
RH Chem
Rad
Sub
Temp
Press
RH
Chem
Rad
Sub
Temp
Press
RH
Chem
Rad
Sub
Amb. Amb. Amb • No 3. 6xl0
6
No
Amb An b Amb No 3. 6x10 6
No
Amb Amb Amb No 3.6x10
6
No
Amb Amb Amb No 3.6xlO
6
No
NA
NA
NA NA
2xlO8
NA
NA
NA
NA
NA
2x108
NA
NA
NA
NA
NA
2xl08
NA
NA
NA NA
NA
2x10 8
NA
Equipment Type
Table 2 (1 of 2) INDIAN POINT 2
TMI EQUIPMENT QUALIFICATION FOR HARSH ENVIRONMENT
Time Environmental Qual. Equipment Type Loc. Needed Parameter Spec. Qual. Method Ref. Note
Solenoid Valves:
Nitrogen Seal Valves P.P. 30 day Temp Amb NA S (2) (3) SOV 3500, 3506 thru Press Amb NA 3510 RH Amb NA Valcor V-52600 Series Chem No NA
Rad 3.6x10 6 2x10 8
Sub No NA
Isolation Valve Seal P.P. 30 day Temp Amb NA 5 (2) (3) Water Systemn Press Amb NA SOV 3501 thru 3505, RH Amb NA 3511 thru 3517 Chem No NA Valcor V-52600 Series Rad 3.6x10 6 2x10 8
Sub No NA
Post Accident Liquid P.P. 30 day Temp Amb NA 5 (2) (3) Sample Line Press Amb NA SOV 3426 thru 3431 RH Amb NA Valcor V-52600 Series Chem No NA
Rad 3.6xi0 6 2x10 8
Sub No NA
Containment Hydrogen P.P. 30 day Temp Amb NA 5 (2) (3) Monitor Valves Press Amb NA SOV 5018 thru 5025 RH Anb NA Valcor V-52600 Series Chem No NA
Rad 3.6x10 6 2x10 8
Sub No NA
Nitrogen Supply Valves P.P. 30 day Temp Amb. NA 5 (2) (3) to Reactor Coolant Press Amb. NA Drain Tank RH Amb. NA SOV 3416, 3417 Chem No NA Valcor V-52600 Series Rad 3x10 6 2x10 8
Sub No NA
Table 2 (2 of 2)
INDIAN POINT 2 TMI EQUIPMENT QUALIFICATION
FOR HARSH ENVIRONMENT
Time Environmental Qual.
Equipment Type Loc. Needed Parameter Spec. Qual. Method Ref. Note
Solenoid Valves (Cont'd):
Nitrogen Supply to P.P. 30 day Temp Amb NA S (2)(3)
Pressurizer Relief Tank Press Amb NA
Valves SOV 3418, 3419 RH Amb NA
Valcor V-52600 Series Chem No NA Rad 3"6xi0 6 2xi0 8
Sub No NA
Post Accident Con- P.P 30 day Temp Amb NA S (2)(3)
tainment Vent System Press Amb NA
SOV EW-I, EW-2 RH Amb NA
ASCO NP Series Chem No Na Rad 3.6xi0 6 2xlO 8
Sub No NA
Relief and Safety C 30 day Temp 287 346 5 (4)(5)
Valves PCV 455C, 456 Press 40.6 110 ASCO-NP Series RH 100 100
Chem YES YES Rad 2x10 8 2xlO 8
Sub No NA
Post Accident Con- P.P. 30 day Temp Amb NA S (4)(5)
tainment Vent System Press Amb NA
SOV E-l, E-lA, E-2, RH Amb NA E-3, E-5 Chem No NA ASCO-NP Series Rad 3.6xi0 6 2x10 8
Sub No NA
Table 3 (1 of 1)INDIAN POINT 2
TMI EQUIPMENT QUALIFICATION FOR HARSH ENVIRONMENT
Equipment Type Loc.Time Needed
Environmental Parameter Spec. Oual.
Qual. Method
TransmItters:
AFWS Flow FT-1200,1201,
1202,1203 Rosemount 1153 HA5
Containment Pressure PT 3300 & 3301 Rosemount 1153 CA
Containment Water Level LT 3300 thru 3302 Barton 764 (Lot 4)
RCS & Wide Range Pressure for Saturation Meter PT 402 & 403 Barton 764 (Lot 4)
Reactor Vessel Level LT 1311 1312
1321 1322 Barton 752 (L;)t 4)
30 days
30 daysP. P.
30 days
30 days
P.P. 30 days
Temp
Press
RH
Chem
Rad
Sub
Temp
Press
RH
Chem
Rad
Sub
Temp
Press
RH
Chem
Rad
Sub
Temp
Press
RH
Chem
Rad
Sub
Temp
Press RH
Chem
Rad Sub
215 0.9 100 No Neglible No
Amb Amb Amb No 3.6x10
6
No
287 40.6 100 YES 1.4x10
7
No
287 40.6 100 YES -52xi0
7
No
Amb Amb Amb No 3. 6x10
6
No
350 120 100 NA 4.4x10
7
NA
NA NA NA NA 2x10
8
NA
380 89.7 100 YES 5x10
7
NA
380 89.7 100 YES 5x10
7
NA
NA NA NA NA 5x10
7
NA
(6) (a)(b)
(6) (a)
(7) (c)(e)
(7) (c)
(7) (c)
Ref. NoteRef. Note
Table 4 (1 of 1) INDIAN POINT 2
TMI EQUIPMENT QUALIFICATION FOR HARSH ENVIRONMENT
Time Environmental Qual. Equipment Type Loc. Needed Parameter Spec. Qual. Method Ref. Note
Limit Switches:
Relief and Safety Valves C 30 days Temp 287 340 S (8) PCV 455C, 456 Press 40.6 70 NAMCO EA 180 RH 100 100
Chem YES YES Rad 2x10 8 2x10 8
Sub No NA
Table 5 (1 of 1)INDIAN POINT 2
TMI EQUIPMENT QUALIFICATION FOR HARSH ENVIRONMENT
Equipment Type Loe .Time Needed
Environmental Parameter SneC.
Terminal Blocks:
Westinghouse Terminal Blocks 542247 (805432)
C/P.P. 30 days Temp
Press RH Chem Rad
Sub
287 40.6 100 YES 107
No
(9)(10) (a)(b) (11)
YES
2x107
Oual.Qual.
Parameter Sr~e.Method Re. otRp . N t
Table 6 (1 of 1)INDIAN POINT 2
TMI EQUIPMENT QUALIFICATION
FOR HARSH ENVIRONMENT
Equipment Type Loc.Time
Needed
Environmental Parameter Spec. Oual.
Qual. Method Ref. Nnt-e
Containment High Range Radiation Monitor:
High Range Detector R25 & R26
Victoreen 877-1
Cable/Connector Assembly 878-1 Victoreen
30 days
30 days
Temp Press RH
Chem Rad
Sub
Temp
Press RH
Chem Rad Sub
287 40.6 100 YES 2xlO8
No
287 40.6 100 YES 2x10
8
357 133 100 YES 2xlO 8
(12)
(12) (d)
Oual. Method Ref. Note
Table 7 (1 of 1)INDIAN POINT 2
TMI EQUIPMENT QUALIFICATION FOR HARSH ENVIRONMENT
Equipment Type Loc.Time
NeededEnvironmental
Pararmtpr n .
Safety Valve Flow Monitor System:
Acoustic Sensors
Accelerometers
FE 3106, 3107,3108
TEC 1414 System Endevco 2273 AMl
Preamplifier
TEC 1414 System
Charge Converters
Model 501
Valve Flow Monitor
Cable Assembly TEC 2273-Cl
30 days
30 days
30 days
Temp
Press
RH Chem
Rad
Sub
Temp
Press RH
Chem
Rad
Sub
Temp
Press
RH
Chem
Rad
Sub
287 40.6 100 YES 2xl0 8
No
287 40.6 100 YES 2x10
8
No
287 40.6 100 YES 2x1 08
No
400 60 100 YES 2x10 8
NA
(1-3)
(13) (d)
(13) (d)
Qual.
Table 8 (I of 1)INDIAN POINT 2
TMI EQUIPMENT QUALIFICATION FOR HARSH ENVIRONMENT
Equipment Type Loc.Time Needed
Environmental Parameter SParameter S Method Ref Nnt-
Resistance Temp. Dectectors-
Reactor Vessel Level TE 1313,1314,1317,1318
1319,1324,1323,1327 1328,1329
NIMCO Model #S8809S8810
ICC Saturation Meter
TE 401 thru 404, 413,423,433,443
Rosemount 176 JA
30 days
Dec. Onal."I
Qual. M~thnd
R~f
30 days
Temp
Press RH Ch em Rad Sub
Temp
Press RH
Chem Rad Sub
(d)287 40.6 100 YES
2xlO 8
No
287 40.6 100 YES 2xiO
8
(d)
Table 9 (1 of 1)
INDIAN POINT 2TMI EQUIPMENT QUALIFICATION
FOR HARSH ENVIRONMENT
F,.tiinrn"M Type Loc.Time Needed
Environmental
Parameter SiDec. Qual.Qual. Method Ref. Note
Electro-Pneumatic
Transducers
Post Accident Con
tainment Vent System
Valves E-1, E-lA, E-2,
E-3, E-5
Fischer Governor 546
P.P. 30 days Temp
Press
RH
Chem
Rad
Sub
Amb Amb Amb No 3. 6x10 6
No
(d)
0
uipment Type pec -
Table 10 (1 of 1)INDIAN POINT 2
TMI EQUIPMENT QUALIFICATION FOR HARSH ENVIRONMENT
Equipment 'type Loc.Time Needed
Environmental Parameter Snec.Parameter Soec. Method I? - f TT +
Cable:
2/C #16, 4/C #16 Silicone Rubber
Dielectric Harbour Industry
1/C #12, 1/C #10 7/C #12 XLPE /NEO The Rockbestos Co.
Firewall III
30 days
30 days
Temp
Press RH Chem
Rad
Sub
Temp
Press RH
Chem
Rad
Sub
287 40.6 100 YES 2x10 8
No
287 40.6 100 YES 2xlO8
No
(d)
340 113 100 YES 2x10 8
NA
(14)
Splices:
Heat Shrinkable In-Line Splices Raychem Type WCSF-N
30 days Temp Press
RH
Chem Rad
Sub
287 40.6 100 YES 2xlO
8
No
314 66 100 YES 2x10 8
NA
(15)
Oul].Qual. M~thnd = _ eo
References
i.* Limitorque Corporation, Nuclear Power Station Qualification
Type Test Report, Limitorque Valve Actuators for PWR Service,
Project #600456, December 9, 1975.
2.* Valcor Engineering Corporation, Qualification Test Report for
IEEE Class lE Solenoid Valves, QR 52600-5940-2, July 11, 1979.
3. Valcor Engineering Corporation, Letter, Quality Assurance
Report QR 52600-5940-2, B. Quail to S. Nadipuram, August
26, 1981.
4. Automatic Switch Co., ASCO Qualification Specification AQS
21678, Revision "B" February 15, 1978.
5. Automatic Switch Co., ASCO Qualification Specification AQS
21678/TR Rev. "A" July 1979.
6. Rosemount Inc. Qualification Test Report for Rosemount
Pressure Transmitters Model 1153 Series A Report No. 3788
7.* Westinghouse Corp. WCAP - 9885 Qualification Testing of ITT/
BARTON Transmitters, Production Lot No. 2, April 1981.
8.* ACME-Cleveland Development Company, Test Plan Qualification
of Series EA-180 and EA-740 Switches, August 31, 1977.
9.* US NRC letter: Summary of Meeting held February 1, 1978 con
cerning Yankee Rowe terminal boards. A. Burger to Yankee
Atomic Electric Co.
l0.* Rochester Gas & Electric Co. Minutes of meeting, Nuclear Safety
Audit & Review Board. January 31, 1978.
ll.* Franklin Institute Report F-C4911-l Qualification Tests of
Terminal Blocks in a Simulated Loss of Coolant Accident En
vironment, January 1979.
12. Victoreen Inc. Qualification Type Test Data Report For Class
IE Victoreen High Range Containment Radiation Area Monitor
System, June 19, 1981.
I
References (Cont'd)
13. Technology for Energy Corporation, Final Test Report No. 517-TR-03: Revision 2, December, 1981.
14. Rockbestos Co., Qualification of Firewall III Class IE Electric Cables. Report QR #1806, RevisedMay 1, 1981.
15. Wyle Laboratories, Environmental Qualification Test Report of Raychem WCSF-N Nuclear In-Line Cable Splice Assemblies. No. 58442-1, May 15, 1981.
Qualification report previously identified in Con Edison' May 9, 1980 submittal or its October 31, 1980 update, and already reviewed by Franklin Research Institute.
~. E~
Notes
a) Manufacturer of this component ha~s successfully completed qualification to IEEE 323-1971 Standards. The 1971 qualification level for these components is acceptable on the basis that alternative 1974 qualified equipment were unobtainable within the deadline to meet TI4I lesson learned schedules.
b) Qualification data for these components was included in the May 9, 1980 Con Edison letter from William J. Cahill, Jr. to Steven A. Varga.
c) Qualification tests for these components are being conducted to meet the particular sequence requirements of IEEE 323-1974 Standards. These units are identical to Lot 2 units that have successfully passed environmental qualification in accordance with IEEE 323-1971.
d) These components will either be qualified by testing or replaced with qualified equipment. Qualification by testing or replacement will be achieved by the second refueling outage after March 31, 1982.
(e) Qualification data for these components was included in the September 4, 1981 Con Edison letter from John D. O'Toole to Steven A. Varga.
I