36
Fans | Air Handling Units | Air Distribution | Fire Savety | Air Conditioning | Air Curtains and Heating Products | Tunnel Fans Forward-thinking live and work Ventilation systems for any type of Passiv houses

Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

Fans | Air Handling Units | Air Distribution | Fire Savety | Air Conditioning | Air Curtains and Heating Products | Tunnel Fans

Forward-thinking live and work Ventilation systems for any type of Passiv houses

Page 2: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

2 | Passiv house

Sustainable and innovativ for more quality of life! 4

The passiv house certified residential ventilation units from Systemair 7

SAVE VTC residential ventilation units 8

SAVE VTC 200 10

SAVE VTC 300 12

SAVE VTC 700 14

Genius - the intelligent central building services unit 16

Modular and adaptive: MAXK range 24

Flexible High-End solutions for exalted and upmost requirements! 28

Systemair duct systems 30

Diffusers from Systemair 32

Contents

Page 3: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

Passiv house | 3

You are designing sustainable solutions for your customers according to the Passive House standard.

We assist you!

With intelligent technical solutions, perfectly harmonized to requirements of modern buildings. Economical in invest. Energy efficient operation and flexible in use.

The Systemair SAVE range units and our modular units offers solutions for residential and commercial applications.

Discover these fresh ideas for yourcustomers.

Page 4: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

4 | Passiv house

Sustainable and innovativ for more quality of life!Modern complete solutions for a healthy climate!

Increasing energy costs influences future architecture. The goal is to build up energy efficient buildings. That means buildings which uses extremly less energy and preferably produced by themselves. Thus a combination of building and technical equipment. That is what Passive House stands for.

Systemair offers different efficient Products for solutions in residential and commercial buildings.

Almost every application can be designed with an indivi-dual ventilation system.

Passiv House certified products from Systemair fits for systems up to 15.000 m³/s (4.170 l/s).

The Passive House is not an energy standard but an integrated concept assuring the highest level of comfort. The exact definition is as follows:

“A Passive House is a building, for which thermal comfort (ISO 7730) can be achieved solely by post-heating or post-cooling of the fresh air mass, which is required to achieve sufficient indoor air quality conditions – without the need for additional recirculation of air.”

This is a purely functional definition which doesn‘t contain any numerical values and is valid for all climates. This definition shows that the Passive House is a fundamental concept and not a random standard. Thermal comfort is achieved to a maximum extent through passive measures (insulation, heat recovery, passive use of solar energy and internal heat sources).

The Passive House - definition!

Since 1974, Systemair has been taking care of a vitalresource. Today, the company is one of the global leaders in the field of ventilation technology and air conditioning.

A success story which started in Skinnskatteberg, Sweden which has revolutionised the world of ventilation with the invention of the in-line centrifugal fan.Since then, the company has continued to grow, and today it offers a complete range of standard-setting ventilation technologies. Whether it is the ventilation concept for a shopping mall, the controlled residential ventilation of a single-family home or the ventilation of tunnels and metro stations – Systemair experts are familiar with the conditions and have the necessary know-how. More than 4700 employees in more than 63 subsidiaries in over 47 countries ensure the necessary proximity to the customer.

Systemair

Page 5: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

Passiv house | 5

Fast course is the awareness that we have to economize with the earth‘s resources. This sometimes creates a conflict between the desire to provide energy for the ventilation system and the desire to save resources and protect the environment. Must it be so? No. Today energy-efficient solutions are available that create a good indoor climate. Systemair products are aligned by their sensible use of materials and the sophisticated production on the preservation of a healthy environment. The products are designed for the economical use of the energy available. ventilation products Systemair, that meet these requirements in particularly, are marked with „Green Ventilation“.

Heat recoveryIn regions with relatively low annual average temperature the ventilation system needs an efficient heat recovery, through which the heat contained in the exhaust air is transferred to the incoming air. With a good thermal wheel up to 90 % of the heat can be recovered. The new generation of fans drives helps to reduce energy consumption dramatically by up to 50 %. The new so-called EC motors are particularly suitable for applications with control; precisely here that energy savings are particularly large.

PressureThe required pressure in the system is affected by the channel system, as well as by the construction of the ventilation unit. Here it is sometimes possible to save up to one hundred Pascal.

Night CoolingIn warmer areas of the world, an energy saving can be achieved by supplying cooler air during the night into the rooms. Thereby the walls are cooled.

Quality LabelingHow can the right product for an optimal solution be found when so much alternatives are available? Most major suppliers are now ISO certified and sell products with CE marking.Systemair goes one step further and is working hard to ensure that the products are of a high standard and are recognized by different laboratories. For the ventilation units which may be the Eurovent certification or a local certification in each country. Across this is now the passive house - certification of some unit series. To achieve this, resources and expertise are required. Systemair has one of the most modern development centers in Europe, which is certified by AMCA.

The AMCA certified development center in Skinnskatteberg in Sweden was an investment of about EUR 700 000 and has one of the most modern test equipments in Europe. The „quiet room“ is a so called reverberation room with a background noise of less than 10 dB (A). During the measurement of air outlets it is detected by green laser light how the air of wall or ceiling mounted air outlets is distributing into the room. In the development laboratory is also an air chamber, that is cooling the air down to -20 °C. This uses Systemair all year for the development of heat recovery equipment. Apart from the development center in Skinnskatteberg in Sweden Systemair has also impressive test facilities in Germany and Denmark for fans and Air Handling Units.

Whether simple apartment ventilation, Combined House building services or non-residential ventilation to highly sophisticated solutions and dehumidification, adiabatic cooling - everything can be made by Systemair.

Give us a task - we prepare the solution.

Page 6: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

6 | Passiv house

Page 7: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

Passiv house | 7

The passiv house solutions from Systemair

Residential ventilation units for residential building

SAVE VTC 200 SAVE VTC 300 SAVE VTC 700

Energy efficiency classStandard unitStandard unit with accessories

Technical dataDesign up to living space m² 180 300 600Max. air volume at 120 Pa m³/h 260 410 860Max. sound level at 1 m distance dB(A) 46 43 54Efficiency heat recovery % 90 81 86Duct connections mm 125 160 250Widht mm 658 762 1170Height mm 822 857 1214Depth mm 593 616 860

It goes without saying that such a high-quality systemalso comes with high-quality service. As such, wemake ourselves available to you with our helpful adviceduring the planning and tendering process. Using thebuilding plans we determine your customers’ requiredair quantity. We then plan your entire ventilation system using our experience and the latest CAD programmes. This

way, you can be sure that your system and all of its components are optimally coordinated with the building. We also make it easy for you to put together your quotation:

Alongside the description of the individual items and detailed material lists, you receive all of the corresponding prices from us too.

Expert advice from the start

Page 8: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

8 | Passiv house

Bild eines EFH / Text von Klaus als Einleitung

SAVE VTC Residential ventilation units for a comfortable indoor climate!

Page 9: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

Passiv house | 9

Bild eines EFH / Text von Klaus als Einleitung

SAVE VTC

Residential ventilation unit in residential building

Page 10: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

10 | SAVE VTC

SAVE VTC 200The casing is built of sheet metal and well insulatedagainst condensation. The inner part of the case is madeof expanded polypropylene (EPP) and provides extremelygood insulation in terms of noise and heat losses. Allcomponents are easily removed for maintenance and service.The unit has built-in functions available for demandcontrol that gives effective and economical operation. Forinstance, CO2, presence or humidity sensor. It also hasbuilt-in functions for communication with building management systems like Modbus.

Technical dataArt. no. (R) 24802Art. no. (L) 24803Voltage V 230Frequency Hz 50Power rating per fan at the operation point

Wca. 2852.77 l/h at 80 Pa

Energy efficiency classStandard unitStandard unit with accessories*

AA+

SFP kW/m²/s < 1.0Fuse A 10Heating coil W -Filter, supply air G4 / F7**Filter, extract air G4Weight kg 42Connection (socket) DN 125

* Accessories see page 11.

** Available as accessories.

SFP = Specific Fan Power (kW/m³/s)

The SFP value stated applies to the complete unit.

Mid-frequency band, HzLwA dB(A) Tot 63 125 250 500 1k 2k 4k 8kExtract air 53 41 41 50 47 44 36 25 22Supply air 56 25 33 41 50 52 51 43 34Surrounding 46 22 31 34 41 41 38 28 20

The sound data table indicates the sound power level LwA, which shouldnot be confused with the sound pressure level LpA.(based on the operationpoint at 80 Pa).

0 0.02 0.04 0.06 0.080

50

100

150

200

250

300

[m³/s]

[Pa]

0 100 200[m³/h]

SFP 1

SFP 1,5

SFP 2

SFP 2,5

50 150 250

0 0.02 0.04 0.06 0.080

50

100

150

200

250

300

[m³/s]

[Pa]

0 100 200[m³/h]

SFP 1

SFP 1,5

SFP 2

SFP 2,5

50 150 250

• Up to 90% heat recovery efficiency• For approx. 180 m² living space• Automatic change to supper operation

(without heat recovery)• Demand control regulation• Start-up wizard for easy commissioning• Separate settings of supply and extract air flow• User friendly, integrated control panel CD 3 with

LCD-display• Modbus communication with RS-485• Integrated humidity sensor in extract for humidity

control.

Supply air Extract air

Performance data

Page 11: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

SAVE VTC | 11

A B C D E F G H ISAVE VTC 200 658 593 530 822 752 408 148 1.301 1.207

Dimensions in mm..

= supply air = extract air = exhaust air = outdoor air= Supply air = Outdoor air= Extract air= Exhaust air

A

ED

C

B

I

H109

100

109

125

125(3x)

F

GG

FB

A

ED

C

B

I

H109

100

109

125

125(3x)

F

GG

FB

EF Extract fanG4 Extract/Supply filterETS Extract air temp. sensorSF Supply fanSS Supply air temp. sensorOS Outdoor air sensorDB Bypass damperHE Heat exchangerRH Humidity sensor

Art. no.Control panel CD 4 210396Shutter damper EFD 125 311321CEC cable, 15 m VK-15 306594Silencer SCD 125/1.0 25563-way valve ZTR 15-0.4 9670Water heating battery VBC 125 5457Actuator 0-10V RVAZ4 9862Transformer 24V PSS48 204385Surface sensor TG-A 130 5159Duct sensor TG-K 360 4846Fast clamp FK 125 1608Electrical heating battery CB 125 5290Heating battery VTC200 209967

Accessories Energy efficiency class A+ Art. no.WirelessDiverting plug CE/CD 37367Cable CEC 208263Gateway Wireless RS485 25130CO2 Sensor Wireless* - 25126Humidity Sensor Wireless* - 25127

Cabel-boundCO2 Transmitter CO2RT-R-D 6993Raum-Hygrostat HU 30213

Accessories

Wireless accessories Art. no.Gateway Wireless RS485 25130Diverting plug CE/CD 37367Cable CEC 208263

CO2 Sensor Wireless - 25126Humidity Sensor Wireless - 25127Input Modul Wireless - 25128SmartDial (Funk-Bedieneinheit) - 25129

For wireless accessories the gateway is needed.

* At least one additional sensor is needed to achieve A+

Right-hand version

Dimensions

Right-hand versionScheme

Page 12: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

12 | SAVE VTC

SAVE VTC 300

Technical dataArt. no. (R) 2480Art. no. (L) 2481Voltage V 230Frequency Hz 50ower rating per fan at the operation point

Wca. 4383.33 l/s bei 80 Pa

Energy efficiency classStandard unitStandard unit with accessories*

AA

SFP kW/m³/s 1.03Fuse A 10Power rating, fan motor W 2 x 85Filter, supply air G4 / F7**Filter, extract air G4Weight kg 72Dimension (L x B x H) mm 762 x 616 x 857Connection (Socket) DN 160

* Accessories see page. 13.

** Available as accessories.SFP = Specific Fan Power (kW/m3/s)The SFP value stated applies to the complete unit.

SFP 2,5

SFP 1,2

SFP 1,5

SFP 2,0

0 0.03 0.06 0.09 0.12 0.150

50

100

150

200

250

300

350

400

[m³/s]

[Pa]

0 100 200 300 400 500[m³/h]

0 0.03 0.06 0.09 0.12 0.150

50

100

150

200

250

300

350

400

[m³/s]

[Pa]

0 100 200 300 400 500[m³/h]

• Up to 81% heat recovery efficiency• For approx. 300 m² living space• Automatic summer and defrost function

with/without preheating• Demand control regulation• Start-up wizard for easy commissioning• Separate settings of supply and extract air flow• User friendly, control panel CD 3 with LCD-display

integrated• Modbus communication via RS-485• Integrated humidity sensor in extract for humidity

control.

Supply air Extract airPerformance data

The unit is double skinned, fully insulated and with com-plete control functions, high efficiency counterflow heat exchanger and filters. Energy efficient fans with EC motors will reduce energy consumption for transportation of ven-tilation air by apx. 50 % compared to traditional AC mo-tors. Modern technology gives low SFP factor (Specific Fan Power). The unit will automatically alternate between nor-mal operation with heat recovery and summer operation without heat recovery. This solution will also automatically recover chilled indoor air (from cooling).

Mid-frequency band, HzLwA dB(A) Tot 63 125 250 500 1k 2k 4k 8kExtract air 63 46 50 57 56 54 57 49 40Supply air 52 43 40 50 42 42 40 27 22Surrounding 43 27 33 39 37 34 32 25 21

The sound data table indicates the sound power level LwA, which shouldnot be confused with the sound pressure level LpA.(based on the opera-tion point at 80 Pa).

Page 13: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

SAVE VTC | 13

Art. no.Control panel CD 4 210396 Shutter damper EFD 160 7122CEC cable, 15 m VK-15 306594Silencer SCD 160 25583-way valve ZTR15-0.4 9670Reheater, electr. VTC 300 R/L 2488/2489Water heating battery VBC 160 5458Actuator 0-10V RVAZ4 9862Transformer, 24V PSS48 204385Surface sensor TG-A 130 5159Duct sensor TG-K 360 4846

Accessories Energy efficiency class A Art. no.WirelessDiverting plug CE/CD 37367Cable CEC 208263Gateway Wireless RS485 25130CO2 Sensor Wireless* - 25126Humidity Sensor Wireless* - 25127

Cabel-boundCO2 Transmitter CO2RT-R-D 6993Raum-Hygrostat HU 30213

Dimensions

Wireless accessories Art. no.Gateway Wireless RS485 25130Diverting plug CE/CD 37367Cable CEC 208263

CO2 Sensor Wireless - 25126Humidity Sensor Wireless - 25127Input Modul Wireless - 25128SmartDial - 25129

For wireless accessories the gateway is needed.

* At least one additional sensor is needed to achieve A+

762*616553

802 85

7

758279

131 131

616

406

139

Ø160(4x)

1508

1332

139

421

762*616553

802 85

7

758279

131 131

616

406

139

Ø160(4x)

1508

1332

139

421

762*616553

802 85

7

758279

131 131

616

406

139

Ø160(4x)

1508

1332

139

421

= supply air = extract air = exhaust air = outdoor air= Supply air = Outdoor air= Extract air= Exhaust air

Right-hand version

EF Extract fanG4 Extract/Supply filterETS Extract air temp. sensorSF Supply fanSS Supply air temp. sensorOS Outdoor air sensorDB Bypass damperHE Heat exchangerRH Humidity sensor

AccessoriesRight-hand versionScheme

Page 14: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

14 | SAVE VTC

The unit is double skinned, fully insulated and with com-plete control functions, high efficiency counterflow heat exchanger and filters. Energy efficient fans with EC motors will reduce energy consumption for transportation of ven-tilation air by apx. 50 % compared to traditional AC mo-tors. Modern technology gives low SFP factor (Specific Fan Power). The unit will automatically alternate between nor-mal operation with heat recovery and summer operation without heat recovery. This solution will also automatically recover chilled indoor air (from cooling).

SAVE VTC 700

Technische DatenArt. no. (L) 2174Art. no. (R) 2173Voltage V 230Frequency Hz 50ower rating per fan at the operation point

Wca. 95194.44 l/s bei 80 Pa

Energy efficiency classStandard unitStandard unit with accessories*

AA+

SFP kW/m³/s 0,97Fuse A 10Power rating, fan motor W 2 x 168Filter, supply air G4 / F7**Filter, extract air G4Weight kg 150Dimension (L x B x H) mm 1170 x 860 x 1214Connection (Socket) DN 250

* Accessories see page. 15.

** Available as accessories.SFP = Specific Fan Power (kW/m3/s)The SFP value stated applies to the complete unit.

SFP 1,2

SFP 1,5

SFP 2,0

SFP 2,5

SFP 1,6

0 0.05 0.1 0.15 0.2 0.25 0.30

50

100

150

200

250

300

350

[m³/s]

[Pa]

0 200 400 600 800 1000[m³/h]

0 0.05 0.1 0.15 0.2 0.25 0.30

50

100

150

200

250

300

350

[m³/s]

[Pa]

0 200 400 600 800 1000[m³/h]

• Up to 86% hear recovery efficiency

• For approx. 600 m² living space

• Automatic summer and defrost function with/without preheating

• Demand control regulation

• Start-up wizard for easy commissioning

• Separate settings of supply and extract air flow

• User friendly, control panel CD 3 with LCD-display and 6 m connecting cable inclusive (enclosed)

• Modbus communication with RS-485• Integrated humidity sensor in extract for humidity

control.

Mid-frequency band, HzLwA dB(A) Tot 63 125 250 500 1k 2k 4k 8kExtract air 66 47 50 58 65 54 52 44 38Supply air 78 61 61 64 75 71 71 69 64Surrounding 54 37 39 43 52 45 44 39 35

The sound data table indicates the sound power level LwA, which should not be

confused with the sound pressure level LpA.(based on the operation point at 80 Pa).

Supply air Extract airPerformance data

Page 15: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

SAVE VTC | 15

1170

450

576

211

176

ø250(4x)

211

571

180

860780

1214

1088

1170

450

576

211

176

ø250(4x)

211

571

180

860780

1214

1088

EF Extract fanG4 Extract/Supply filterETS Extract air temp. sensorSF Supply fanSS Supply air temp. sensorOS Outdoor air sensorDB Bypass damperHE Heat exchangerRH Humidity sensor

Art. no.Control panel CD 4 210396Shutter damper EFD 250 6748CEC cable, 15 m VK-15 306594Silencer SCD 250 25613-way valve ZTR15-1.6 9673Reheater, electr. VTC 700 R/L 2738/2739Water heating battery VBC 250 5460Actuator 0-10V RVAZ4 9862Transformer, 24V PSS48 204385Surface sensor TG-A 130 5159Duct sensor TG-K 360 4846CO2 Transmitter CO2RT-R-D 6993

*400V power supply required

Accessories Energy efficiency class A+ Art. no.WirelessDiverting plug CE/CD 37367Cable CEC 208263Gateway Wireless RS485 25130CO2 Sensor Wireless* - 25126Humidity Sensor Wireless* - 25127

Cabel-boundCO2 Transmitter CO2RT-R-D 6993Raum-Hygrostat HU 30213

Wireless accessories Art. no.Gateway Wireless RS485 25130Diverting plug CE/CD 37367Cable CEC 208263

CO2 Sensor Wireless - 25126Humidity Sensor Wireless - 25127Input Modul Wireless - 25128SmartDial - 25129

For wireless accessories the gateway is needed.

* At least one additional sensor is needed to achieve A+

AccessoriesRight-hand versionScheme

DimensionsRight-hand version

= supply air = extract air = exhaust air = outdoor air= Supply air = Outdoor air= Extract air= Exhaust air

Page 16: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

16 | SAVE VTC

You make dreams a reality. We provide the efficient Air-Conditioning.

Genius – the intelligent central building services unitfor heating, cooling, ventilation and water heating.

Page 17: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

SAVE VTC | 17

Genius

Page 18: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

18 | Genius

Genius is the compact Central Building Services Unit which can do everything: ventilation, heating, cooling and hot water production.All Genius needs is a secondary air circuitin addition to the conventional ventilationducts. Thanks to the integrated air/air heatpump, a heating system using water becomesunnecessary.

Where Oil, Gas and water once came –we now do it all with Air. Air heating system from Systemair

KEY

Outdoor air Supply air Secondary air Extract air Exhaust air

Page 19: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

Genius | 19

Nowadays, whoever builds a new building or renovates an old one must fulfi l the European Directive Energy Performance of Buildings (EPBD). The result is often highly insulated, airtight building envelopes which require mechanical residential ventilation – for a healthy indoor climate and as little energy loss as possible. At the same time, thanks to today‘s improved standards for insulation, the heating energy required is less. For this reason, classical heating systems are generally overdi-mensioned for energy-effi cient houses. This is why we developed Genius. A central building services unit which with its integrated air-air heat pump is, on the one hand, able to ventilate effi ciently with heat recovery, and on the other hand is able to use the air for heating or coo-ling the rooms. But that‘s not all: thanks to an integra-ted air-water heat pump, even hot water production is included. That is to say, you only need one system. This saves a great deal of time in the planning phase, reduces investment costs and, what‘s more, needs less space. Convincing arguments for demanding customers. And promising prospects for you.

The idea of using air as a heat transfer medium andtransporting it from room to room through ducts has been around a long time. However, until now it was commonfor unpleasant smells and impurities to be transportedtoo. Thanks to Systemair‘s secondary air system, yourcustomers will only experience pure air quality, becausethe extract air system remains completely untouched.This ensures that the transmission of odours orsubstances is excluded. Furthermore, high-quality pollenand dust fi lters clean the air.The result: the very best air quality and a pleasant indoorclimate for your customers.

Poor Indoor Environment is History with the Genius unit

How the air heating system worksAt the heart of the system is the Genius combi-unit. It continually supplies the living and sleeping quarters with fresh, clean air, and transports the extract air to the exterior, via the kitchen, bathroom and WC. A rotary heat exchanger removes the heat from the extract air and, if necessary, uses it to preheat the cool supply air. Further-more, it ensures that the air is not too dry. In summer, the principle functions in reverse, so that the extract air cools the supply air and excessive ambient air humidity is removed.

Heating and cooling modesThe heating load is covered by an increase in the volu-metric flow. Here a fan draws air from the living area via a separate duct system (secondary air). A stepless controlled air-air heat pump heats this depending on the requirements and conveys it to the living and sleeping quarters. In summer, the heat pump works in reverse so that the dwelling is cooled.

Hot water productionAll the functions of Genius can be used individually or inparallel. This applies to hot water production as well. A150 litre tank is integrated for storing the drinking water.A heating rod is installed inside to ensure the systemfunctions perfectly, even if the outside temperatures areextremely low.

Page 20: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

20 | Genius

Increased comfort, decreased space requirement

Good to know!The individual Genius components for ventila-tion, the heat pump and hot water are installed in compact modules, which can simply be pushed into the housing or placed on top. This makes instal-lation and maintenance easier.

Ventilation module – WRG

Heat pump module – WP

Hot water module – WW

KEY

Genius

Hot water tank

Boiler

Air handling unit

Underfloor heating

Conventional system Genius air heating system

Page 21: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

Genius | 21

Supply air

Outdoor air

Exhaust air

Hot water module

Rotary heat exchanger with humidity recoveryg

Heating and cooling of the building via the ventilation system‘s supply air ducts.

Ventilation module

Extract airSecondary airOutdoor air

Heat pump module

·

·

With stepless controlled compressor for precise adjustment

Reversible air-air/air-water heat pump for heating/cooling/ hot water

·

·

Incl. control cabinet and 150 L hot water tank

Hot water production parallel to heating and cooling operation

·

·

Page 22: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

22 | Genius

Comfortable in all areas.Modules, control, functions

The functions in detail:

• 4 ventilation steps according to DIN 1946/6:• Ventilation for humidity protection• Reduced ventilation• Nominal ventilation• Intensive ventilation• Additional option to switch off

• Temperature control in the winter:• Setpoint adjustment based on external temperature• Temperature control of individual rooms• Fixed value• Setpoint = average setpoint temperature for the room• Setpoint = Reference room setpoint

• Temperature control in the summer:• Setpoint adjustment based on external temperature• Fixed value• Cooling can be deactivated

• Fireplace operation

• Legionella control program

• Fast charging hot water

• Emergency mode hot water

Modern technology requires contemporary, convenient operation. This is why we have designed Genius so that you and your customers can control the system easily with a PC and even via the Internet: as an expert via the service level and as an end user via the user level. This enables you and your customers to have permanent

access, even from outside, and an optimum overview of all functions and parameters. Control of individual rooms via a display is just as easy as controlling the system via an operating panel on the unit. The Systemair App permits you to control the system using your mobile phone.

• Emergency mode heating

• Adjustment of the maximum supply air temperature based on external temperature, alternatively manually

• Minimum supply air temperature

• Time programs:• Ventilation/heating/cooling• Hot water: automatic, individual• Decrease mode: setpoint temperature, ventilation stage• Holiday mode

• Filter monitoring

• Passive night-time cooling, individually adjustable

• Chart function: recording of conditions/parameters

• Electric reheating elements (PTCs):• Temperature control of individual rooms• Emergency operation• Start delay• Can be switched off

Page 23: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

Genius | 23

Electrical dataVoltage V 230Frequency Hz 50Max. compressor power consumption W max 1800

Max. fan power consumptionVentilation module W je 80

Max. fan power consumptionHeat pump module W 170

Storage charging pump power consumption W 6–28

VentilationAir flow (normal mode) m3/h 190

Max. air flow heating/cooling(incl. secondary air) m3/h 600

Outdoor air heat recovery % bis 85Outdoor air filter class F7Extract air filter class G4Secondary air filter class G4

Dimensions/weightsWidth mm 865Height mm 2070Depth mm 750Ventilation modul weight kg 75Heat pump modul weight kg 60Basic Modul/hot water unit weight kg 170Total weight when empty kg 305Total weight when full kg 460

OtherRefrigerant R410ARefrigerant fill quantity kg 1,2Tank volume l 150Expansion tank l 6Hot water safety valve bar 6

ConnectionsCold water 1" AGHot water 1" AGCirculation 1" AG

Condensate mm DN 40 hose connection (5 pcs)

Safety valve 3/4" Outdoor air ventilation mm DN 160Outdoor air heat pump mm DN 250Extract air mm DN 160Supply air mm DN 200Secondary air mm DN 200Exhaust air ventilation/Heat pump mm DN 250

Performance dataMax. heating capacity kW 6Max. cooling capacity kW 4PTC element output W je 500Heating rod output WW kW 3

Setpoint airflowHeat pump

m3/h%

125 60

190 60

Temperature outdoor air °C -3 10 10Temperature extract air °C 21 21 21Temperature supply air °C 41.8 43.4 44

Heat recovery efficiencytotal unit (fictitious) % 253 399 391

Performance rating (COP)total unit 6.39 5.99 6.52

Volume related electr.compressor capacity W/(m3/h) 4.63 4.52 4.69

Volume related electr.ventilation capacity W/(m3/h) 0.73 1.11 1.25

Electrical efficiency 5.9 5.44 5.97

0 50 100 150 200 250 300 350

Volume flow [m³/h]

0

50

100

150

200

250

300

350

400

450

500

Pres

sure

[Pa]

Supply airExtract airMin. pressure reserveV min.V max.Step 2Step 1

Air flow/pressure diagram

Technical data

Page 24: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

24 | MAXK

Modular and adaptive: MAXK range

Page 25: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

MAXK | 25

If residential buildings with central units or non-residential buildings with basic requirements the flexible MAXK units are the ideal solution.

Suitable for indoor and outdoor installation. Heating, Cooling, Ventilation and Heat Recovery on a base of a modular unit. Guaranteed efficiency as a certified PH component. Possible to chose different combinations of thermal insulation and factor for thermal brigdes.

• modular and flexible

• delivery in single parts or partly mounted

• with or without control

• assembly and commissioning by Servicepartners

Page 26: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

26 | MAXK

Certified Passive House appliances series MAXKfor air quantities of 600 - 6200 m3/h, HR, eff up to 89 % in multi-family houses, offices, restaurants, kindergartens and schools for indoor and outdoor installation in passive and low-energy house standard.

The MAXK air handling units with heat recovery consists of a counter flow plate heat exchanger with integrated bypass (Plattenmaterial aus korrosionsbeständiger Alumi-niumlegierung), supply- and exhaust air fan with EC motor and backwarts curved radial impeller, outdoor- and extract air filter and four flexible connectors.

Casing made from zink-coated steel plate, double-walled, insulated; wall thickness: 50 mm

Accessories: damper, heating register, cooling register and silencer.

MAXK

• For indoor and outdoor installation.• If crowed conditions for bring in the air handling unit to

the installation location it´s possible to deliver the unit fragmented respectively partially screwed

• Optionally with complete control system available• The only internationally certified manufacturer of mo-

dular air handling units.

Dimensions

A

B

C

A

MAXK A B C *MAXK-I3 2000 DC 3290 800 1664MAXK I3 3000 DC 3450 1120 1664MAXK I3 4000 DC 3550 1600 1664MAXK I3 5000 DC 3650 1900 1664MAXK I3 6000 DC 3650 2280 1664MAXK-I3 7000 DC 3750 2600 1664

* incl. 100 mm base frame(dimensions in mm)

Side view (control side)

Top view

Page 27: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

MAXK | 27

MAXK-I3 2000 DC 3000 DC 4000 DC 5000 DC 6000 DC 7000 DCMax. volume flow – non-residential buildings m³/h 1400 2200 3200 4200 5200 6200

At an external pressure of * Pa 243 271 294 316 328 360

Max. volume flow – residential buildings m³/h 1600 Also suited for the application in residential buildings.

At an external pressure of * Pa 216 Also suited for the application in residential buildings.

Effective heat recovery rate % 84 84 84 84 84 84

Electric power consumption Wh/m3 0.39 0.45 0.45 0.45 0.45 0.43

Heat exchanger type counter-flow plate heat exchangerFan motor Direct current (EC technology)Max. power consumption of one fan W 423 1000 1400 1850 2730 2730

Voltage V 200 ... 277 380 ... 480 200 ... 277 380 ... 480 380 ... 480 380 ... 480

Phase ~ 1 3 1 3 3 3Frequency Hz 50/60 50/60 50/60 50/60 50/60 50/60Filter outdoor air F7 / extract air M6Integrated bypass existingDuct connection (W x H) mm 656 x 638 976 x 638 1456 x 638 1756 x 638 2136 x 638 2456 x 638Total weight kg 770 830 1100 1300 1550 1610

Technical data

* Definition of the external pressure according to test regulations: the central device will only be considered as a unit of heat exchanger and fans. The filters (outdoor air F7, extract air min. G4) as well as possibly used supplementary heating registers and/or frost protection pre-heating registers are part of the external pressing.

Page 28: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

28 | Menerga Adconair

Flexible High-End solutions from 1.000 to 15.000 m³/h for exalted and upmost requirements

Page 29: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

Menerga Adconair | 29

Every building is different and especially commercial applications gives special requirements to the design. Regardless if schools, office buildings, discounter, shops, sports halls and spa´s the Systemair company Menerga offers units with lots of special technical features and thanks to the sophisticated controls we can fulfill individual needs. This variety of possibilities is unique for certified units and a good opportunity to make you building to something special.

Just for strapped customers this high-class technology is a great chance to save costs.

Inform yourself about the units Adconair 76 and Resolair 64 on our company Menerga homepage: www.menerga.de

Page 30: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

30 | Duct systems

Systemair duct systemsVery flexible

Spiral seam pipe or plastic pipe system

Systemair offers spiral seam pipes in round and oval versions (flat duct) and Systemair-FLEX+, ISO+, OVAL+ plastic pipes. All inner sides are smooth and therefore aerodynamical and easy to clean.

Dimensioning of duct systems

The dimensioning of the ducts for the ventilation system is made according to the requirements of the unit (calculation of the required supply air according to DIN 1946-6) and according to the situation in the building. Flow engineering and acoustic properties have first priorities. The duct installation has to be coordinated early enough with other disciplines on site. The duct size depends on the air volume. To avoid high pressure losses and unwanted noise, we recommend an air velocity of max. 3 m/s in the main duct. When round, rectangular or oval ducts are used, the air velocity is lower at the same pressure loss in the duct. Different diameters must not be proportional installed. The pressure differences between the longest and the shortest sections have to be reduced to guarantee the previously defined air flow for all air outlets.

SystemairFLEX+ the flexible plastic pipe

The FLEX+ pipe is made of physiologically and toxicologically safe PE with no recycling materials. Thus, it is neutral in odour, free of halogens, emission-free, antistatic and antibacterial. Easy and time saving installation by a click system. Hermetically sealed connections ensure an absolutely air tight system without further sealing work. Therefore, it works economically and hygienically because no air can leak and no other substances can enter from outside. Deliverable sizes: DN 50, 63, 75, 90.

Systemair OVAL+ air distribution system with click system

The OVAL+ is made from a physiologically harmless and non-toxic plastic that does not contain any recycled additives. This makes it odourless and free of halogen and emissions, as well as antistatic and antibacterial. The smooth inside walls improve aerodynamics. The system can also be stood on and is easy to integrate in flooring thanks to its low height. The click system makes assembly quick and easy.Available sizes: 133 x 52mm, 45m³/h at 3m/s.

Systemair ISO+ a perfect combination of heat and sound insulation

Outer sheath made of polyethylene with high density (HDPE); inner sheath made of polyolefin with closed cell structure. Flexible fast clamp made of EPDM. The special design of the pipes provides thermical and acoustic insulation. This pipe should be preferably used as a connection between unit and facade (outdoor and extract air) and in unheated areas. Available nominal widths (inner diameter): DN 125 and DN 180.

Page 31: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

Duct systems | 31

Flat duct

Flat ducts are made of galvanized steel sheet. The ele-ments are made of stainless steel and are connected by a plug-in system. Fixing and sealing is made by cold shrink tape.Available sizes:

• System 100 (129 x 52); length 3 m• System 151 (208 x 52); length 3 m

Spiral seam pipe with telescopic pipe

For duct systems with spiral seam pipes, Systemair uses folded spiral seam pipes with a length of 1.2 m as well as telescopic pipes. The elements are equipped with rubberlip seals. The length of the telescopic pipe can be freely adjusted. The most important advantage of this duct system is that it can be installed without cutting or trimming work. This saves installation time and makes maintenance and cleaning easier. All joints have to be fixed by sheet metal screws and also sealed with tape.

Pipe kit available

Ventilation systems from Systemair are individually planned for each building. The air volume is calculated according to DIN 1946-6, the unit is accordingly specified and the duct system is planned inclusive silencers, insulation, outlets and mounting material. The duct system is assembled and delivered according to the material list of the planning.

ISO+

FLEX+

Spiral seam pipes

Flat duct

OVAL+

Page 32: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

32 | Air distribution products

Installation informationWhen dimensioning for ventilation by diffusion, the most important consideration is to ensure that the air velocity in the occupied zone will not be too high, as this will be experienced as a draught.Experience has shown that the introduction of the air from the top is (ceiling or wall below the ceiling) the most convenient. Blowing supply air horizontally from the ceiling works excellently for most rooms. If the supply air is above ambient temperature and also used

to heat the premises, practical experiments have shown that this works well in rooms with ceiling heights of no more than 3.5 metres. This assumes that the maximum temperature difference is 10-15°C.Wall diffusers that produce a conical/flat stream should have a max. distance of 30 cm to the ceiling, that the Co-anda effect will work. Radial wall diffusers should have a shielding at the bottom, that the stream does not touch the occupied zone, causing draught.

Diffusers from SystemairDesign meets function

Blowing supply air horizontally from a ceiling diffuser.Induction of the surrounding air into the air stream.

VentilationResidential ventilation works with very small amounts of air on the principle of mixing ventilation. Fresh air is mixed with the room air. The particle control (dust, smells, etc.) takes place through the effect of dilution. The flow energy in the air stream is reduced by the fact that surrounding air from the room is “aspirated” and mixed with the air stream (Induction).

The air movements caused by the air stream very soon mix all the air in the room thoroughly. Impurities in the air are not only attenuated but also evenly distributed. The temperatures in the different parts of the room are also evened out.

Systemair offers a wide range of high quality diffusers. In this catalogue we have compiled a choice of the most favoured and most used diffusers in residential ventilation.

Page 33: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

Air distribution products | 33

Different kind of air streams

radial

flat

conical

If the diffusers are near the floor, the danger of obstacles in the air stream causing the air velocity being disturbed is very high. The result is, that the mixing and induction is not ensured any more. Also the air distribution differs with changing temperatures, as well as the perception of air quality. If the diffusers are too small, they cause draught, as the blow directly into the occupied zone. If they are too big, the air stream is too slow, so that the penetration of fresh into the room is not enough.

Extract valves should alway be placed in or near the ceiling, because the warm and moistured air always rises to the top and should be extracted there. The placing in the room is unimportant, as the extract air is not directed.

Tellerventile

BOR-S BOREA

PLUTO FAV

Page 34: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

34 | Systemair

Skinnskatteberg, Sweden: Head office of the Systemair group, distribution center and largest production facility with one of Europe’s most advanced R&D-centers. Production of fans and accessories, compact air handling units, air curtains and heating products.

Windischbuch, Germany: Production facility for fans and modular air hand-ling units, specialized on engineered products (e.g. tunnel and jet fans). Distribution center.

Mülheim an der Ruhr, Germany:Menerga-Systemair, is a leading European

producer of air handling units for swimming pool halls and comfort ventilation with extra high efficiency.

Langenfeld, Germany: Production of air curtains.

Hässleholm, Sweden: VEAB manufactures heating products for ventilation systems, mobile and stationary fan heaters and dehumidifiers.

Ukmerge, Lithuania:Modern production facility for air handling units with focus on energy recovery.

Maribor, Slovenia: Production of high temperature fans and air handling units.

Aarhus, Denmark: Production of modular air handling units.

Dal, Eidsvoll, Norway: Production of air handling units for the Norwegian market.

Bratislava, Slovakia: Production and modern R+D center for air distribution products and fire and smoke dampers.

Systemair production facilities worldwide:

Systemair Worldwide

Page 35: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

Systemair | 35

Kuala Lumpur, Malaysia

Skinnskatteberg, Sweden Hässleholm, Sweden

Ukmerge, Lithuania

Bratislava, Slovakia Maribor, Slovenia

Madrid, Spain

Hasselager, DenmarkDal, Eidsvoll, Norway

New Delhi, India

Hyderabad, India

Milano, ItalyIstanbul, Turkey

Windischbuch, Germany

Waalwijk, NiederlandeLangenfeld, GermanyMülheim an der Ruhr, Germany

Tillières-sur-Avre, France

Wujiang, China

Save energy, lower running cost!Our label "Green Ventilation" features products with a high energy saving potential. All products labelled with "Green Ventilation" combine energy economy with energy efficiency.

Quality:Systemair is certified in accordance with ISO 9001; ISO 14001 and ATEX. Our research and development laboratories are one of the most modern in Europe; measurements are made in accordance with international standards like AMCA and ISO.

Kansas City, USA

Bouctouche, Canada Tillsonburg, Canada

Sao Paulo, Brasil

Madrid, Spain: Production of air handling units and box fans.

Milan, Italy: Production of chillers and heat pumps.

Waalwijk, Netherlands:Production of air handling units, also for marine applications.

Tillières-sur-Avre, France: Production of air conditioning products.

Istanbul, Turkey:Systemair-HSK is Turkey‘s leading manufacturer of air handling units.

Bouctouche, Canada: Production of fans and air handling units for the North American market.

Tillsonburg, Canada: In Tillsonburg we develop, engineer, service and manufacture school classroom ventilation equipment for the American market.

Kansas City, USA: Production of fans for the US market.

Sao Paulo, Brazil:Production of air handling units.

Kuala Lumpur, Malaysia :Production of fans for the Asian market.

Hyderabad, India: Production if air distribution products.

New Delhi, India: The factories in New Delhi and Noida manufacture grilles and diffusers.

Wujiang, China:Production of air handling units for the Asian market.

Page 36: Forward-thinking live and work€¦ · Forward-thinking live and work Ventilation systems for any type of Passiv houses. 2 | Passiv house ... wheel up to 90 % of the heat can be recovered

www.systemair.com

Syst

emai

r Gm

bH ·

Mär

z 20

16