Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 Issue Date: 6/21/2013 FNM-2127 Panel Installation Manual

FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Hochiki America FNM-2127 Panel Installation Manual

HA3529-0M, Revision E02.00 Issue Date: 6/21/2013

FNM-2127 Panel Installation Manual

Page 2: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

Underwriters Laboratories (UL)

File number (S 8485)

Fire Alarm Equipment

Hochiki America

The FNM-2127 Panel is suitable as follows:

• Local Signaling Unit

• Non-Releasing for FNM-2127 Panels.

• Types of signaling services are automatic fire alarm and manual fire alarm

• Style 4, 6 or 7 for Signaling Line Circuits

• Style Y for Notification Appliance Circuits

• Style Y For Notification Appliance Circuits

• Proprietary (P) Protected Premises Unit (PPU), Remote Station (RS) Protected Premises Unit (PPU)

NFPA

Hochiki America

Install this product in accordance with NFPA 13, NFPA 72 and NEC 70 and all local codes.

Short Circuit Isolator Modules protect SLC loop devices from single-loop-shorts. SLC loops must be wired with Short Circuit Isolator Modules to comply with NFPA 72, Class A Style 7. SLC loop connections must include closed nippling and conduit nippling to maintain compliance with individual enclosures under NFPA 72, Class A, Style 7 requirements. Closed nippling encloses individual devices on SLC loops and conduit nippling encloses wiring between these individual enclosures. For Class A, Style 6 compliance, the Short Circuit Isolator Modules may be located at strategic locations based on the discretion of the designer or installer.

Install SLC detectors with spacing as specified in section 90.19 of UL 864, 9th edition where units employing the multiple detector operation shall include guidelines for installing of a minimum of two detectors in each protected space and to reduce the detector installation spacing to 0.7 times the linear spacing in accordance with National Fire Alarm Code, NFPA 72. Also reference 55.3.1 and 55.3.2 of UL 864, 9th edition for these detector spacing requirements.

All field wiring should be installed using fire rated cables according to the NFPA 72. Riser conductors shall be installed in accordance with the survivability from attack by fire requirements in National Fire Alarm Code, NFPA 72, Sections 6.8.6.3, and 6.9.4. Riser conductors shall employ either a 2 hour rated cable system, or meet requirements approved by the AHJ, or installation of the Supervised Output Module using NFPA Style 7 configuration.”

FM Global Technologies LLC (FM APPROVALS)

Hochiki America

Hochiki America

All references to marine usage are based upon Certificate of Approval of the United States Coast Guard. The system must be installed and configured in accordance with subpart 161.002 and Subchapter J of Title 46 of the U.S. Code of Federal Regulations and with the 1993 or later version of NFPA 72. This is in addition to any other requirements specific to the vessel and its route. Only those components listed on the approved component list may be used.

United States Coast Guard Approval

Page 3: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

Hochiki is a registered trademark of Hochiki America. All other product or service names are the property of their respective owners.

Copyright © 2013 by Hochiki America. All rights reserved.

Page 4: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Contents

i

Section 1Introduction

Using This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Related Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Document Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Part Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Writing styles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

If You Need Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Contacting HA Tech Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 RMA Returns Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Warranty Returns . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Advanced Replacements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Product Return Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Section 2Overview

Points and Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Zone Capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Hardware Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Notification Appliance Circuit (NAC) Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Panel Controls and Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Left-Panel-Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Right-Panel Controls and indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Lower-Control-Pad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Settings and Resets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Terminal Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Internal Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Section 3Installation

General Installation Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Separation of Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Determining System Current Draw . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Power Supply and Standby-Battery Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Operating Constraints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

Page 5: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Contents

ii

Mounting the FNM-2127 Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Marking the Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Anchoring the Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Feeding Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Replacing Cabinet Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Connecting Power and Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Standby-Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Before Wiring and Operating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 AC Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Installing SLC Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Installing the Laird Ferrite . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Detector Spacing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Connecting Class A Loops . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Connecting Class B Loops . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Output Modules Controlling Notification Appliances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Silencing Notification Appliances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 NAC Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Installing NAC Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Connecting NAC Devices and the Laird Ferrite . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Connecting Auxiliary 24 VDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Relay Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Testing the Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Confirming a Successful Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Testing the Panel Lamps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Trouble-Silence Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Test Zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Event Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Loop Data Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

Page 6: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Contents

iii

Section 4Fascia Menu

Access Level 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Disablements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 View Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Test Zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Set System Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Sensor Maintenance Early Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Events and Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

Access Level 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 Fascia Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

Alarm Silence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 Re-Sound Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 Fire Drill . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 Programmable Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

Section 5Maintenance and Repair

Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Inspecting Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Replacing Standby-Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

Replacing Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 10 Amp Battery Fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 3 Amp Power-Supply Fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58 Removing Cabinet Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

Page 7: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Contents

iv

Appendix ASpecifications

Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 Standby and Alarm Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 Earth Fault Indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 SLC Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 SLC Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 Programmable Relay Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 NAC Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 RS485 Serial Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 NET Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 24 V OUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Auxiliary 24 VDC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 AC Line Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

Operating Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 Physical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

Appendix BEquipment List FNM-2127 Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 Loop Devices and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 Notification Appliances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71

Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 Configuring NAC Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 Regulated NAC Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 Special Application NAC Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73 Maximum Line Impedance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73

Compatible Device Models for Auxiliary 24V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

Page 8: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Contents

v

Appendix CCalculations

Current-Loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 Example of Total Load Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76

The Standby-Battery Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 Battery Rating Equation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 Tabulating Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78

NAC Wiring Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 Sample Lmax Calculation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

Appendix DDoor Label

Appendix EOperating Instructions

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

Page 9: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Contents

vi

This page intentionally left blank.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

Page 10: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Introduction 1

Section 1Introduction

Notice to users, installers, authorities having jurisdiction, and other involved parties. This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864 9th Edition, certain programming features or options must be limited to specific values or not used at all as indicated below.

Reference Appendix B, “Equipment List” for the specific models described in this table.

Program Feature or Option Permitted in UL 864 ?(Y / N)

Possible Settings Settings Permitted In UL 864

AC Fail Delay Yes 0 - 24 hours 1 - 3 hours

Alarm Verification Yes 5 - 60 seconds 60 second

Disable Buzzer Yes Enable / Disable Enable

Disable Ground Trouble Yes Enable / Disable Enable

Set Buzzer Silence Access Level Yes 1 or 2 2

NAC Output Delay Stage 1 No 0 - 5 minutes 0 minutes

NAC Output Delay Stage 2 No 0 - 5 minutes 0 minutes

Photoelectric Smoke Sensor Delay No 0 seconds 0 seconds

Dual Relay Module Delay Yes two delays of up to 10 minutes

0 seconds

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

1 of 90

jcohen
Sticky Note
Unmarked set by jcohen
Page 11: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Introduction 1

This manual describes 2 loop marine models of the FNM-2127 Panel. These models contain the Loop Expansion Module and support Hochiki loop protocol. Cabinet colors of the FNM-2127 Panel are provided in red or charcoal.

This section describes:

• Using This Manual• Related Documentation• Document Conventions• If You Need Help• Contacting Hochiki America For Repair

The figure below illustrates the FNM-2127 Panel: Figure 1-1 FNM-2127 Panel

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

2 of 90

Page 12: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Introduction 1

Using This ManualThe following sections provide instructions for installing, testing and troubleshooting the FNM-2127 Panel:

Document ConventionsThis document contains conventions for part numbers and writing style.

Part NumbersPart numbers are provided in Section 1, Appendix B and Appendix D of this manual. Refer to Appendix D, Door Label for a diagram summary of this manual.

Reference Appendix B, Equipment List for a complete list of part numbers required for completing this installation.

Writing stylesBefore you begin using the FNM-2127 Panel, familiarize yourself with the stylistic conventions used in this manual:

Section 1 Introduction provides document conventions, the technical help-line, repair and return information.

Section 2

Section 3

Overview provides a summary features of the FNM-2127 Panel.

Installation describes how to setup, install and test the FNM-2127 Panel.

Section 4 Fascia Menu describes how to operate the FNM-2127 Panel from its fascia.

Section 5 Maintenance and Repair describes how to maintain and repair the FNM-2127 Panel.

Appendix A Specifications provides characteristics of the FNM-2127 Panel.

Appendix B Equipment List provides model numbers for FNM-2127 Panels, loop devices, accessories, replacement parts and compatible Notification Appliances.

Appendix C Calculations provides calculations for determining load capacity, battery rating, and wiring length of the FNM-2127 Panel.

Appendix D Front Door Label is a copy of the FNM-2127 Panel front door label.

Appendix E Operating Instructions provides an overview of FNM-2127 Panel status and controlinstructions.

Italic type Denotes a displayed variable, a variable that you must type, or is used for emphasis.

Courier font Indicates text displayed on a computer screen.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

3 of 90

Page 13: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Introduction 1

If You Need HelpIf you need technical support contact Hochiki America at (800) 845 - 6692 or email [email protected]. Technical support is available Monday through Friday, 7:00 AM to 5:00 PM, Pacific Standard Time.

Contacting Hochiki America Tech SupportOn-site technicians familiar with the product issue should contact Tech Support and include the:• Product part number• Purchase order or Hochiki America order number• Product serial number• Current function of the product• Expected function of the product• Installation of the product

RMA Returns RequiredA Return Material Authorization (RMA) must be assigned to all products returning to Hochiki America. Tech Support will assign an RMA to a returning product after recording information collected from the on-site technician. Hochiki America cannot not accept product-returns that do not include an accompanying RMA number.

An RMA number is assigned when:

• A product issue is acknowledged by a Hochiki America Tech Support representative• A product was damaged during shipping• An incorrect product was shipped• An order was placed using an incorrect part number *• An order was placed using an incorrect part quantity *• An order is no longer required ** Restocking fees may apply.

Warranty ReturnsTech Support can replace a defective product when the original purchase is within the warranty period defined in the sales contract. Check your sales-contract for more information or contact your sales representative about the warranty period described in your sales-contract.

Warranty products that have been placed in service will be repaired or replaced by Hochiki America. Warranty products that have not been placed in service will be returned to Hochiki America stock and an equivalent credit will be provided to the contractor.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

4 of 90

Page 14: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Introduction 1

Advanced ReplacementsSuspect-products that fail to operate in the field can be replaced quickly using the advanced replacement process. The advanced replacement process is available to all contractors who maintain an acceptable line of credit with HA.

Initiate the advanced replacement process by requesting an RMA number from a HA Tech Support representative. Advanced replacements can be shipped to your location when the suspect-product is covered under warranty and when a replacement product is in stock. All advanced replacement products are shipped UPS ground.

Expedited ReplacementsAdvanced replacements can be expedited at the request of the contractor. Shipping costs associated with this process are the responsibility of the contractor.

Returning ProductsProducts returning to HA using the advanced replacement process must be received 30 days from the RMA issue-date. Contractors can be billed for returning products received following this 30 day period.

Product TestingProducts returned to HA are tested to confirm operating failures experienced in the field. If the returned-product is found to be functional, contractors must absorb expenses for:• Shipping of the advanced replacement product• Return-shipping of the original product• Cost of the advanced replacement product

Product Return AddressProminently display the RMA number on all packages sent to Hochiki America for return. Ship all return products to: Attention: RMA # _____________Hochiki America7051 Village Drive, Suite 100Buena park, CA 90621

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

5 of 90

Page 15: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Introduction 1

This page intentionally left blank.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

6 of 90

Page 16: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Overview 2

Section 2Overview

Models of the FNM-2127 Panel operate Signaling Line Circuits (SLC) using Hochiki protocol. Standard models of the FNM-2127 Panel contain two SLC loops and support networking through the use of the eNet. The eNet provides a secure communication architecture for networking the FNM-2127 Panel and the FNM-LCD-S. The FNM-LCD-S is an Annunciator (Repeater) that can be networked to the FNM-2127 Panel in single or multiple connections.

Configure the FNM-2127 Panel using the soft-keys of the fascia or use Loop Explorer for a complete range of programming features. The Loop Explorer application is a control panel configuration utility for programming SLC devices, notification appliances, initiation devices and networking.

Programming with the fascia soft-keys of the FNM-2127 provides limited functionality. Hochiki America recommends configuring the FNM-2127 Panel with Loop Explorer for a complete range of programming features.

Points and AddressesPoints and addresses are fundamental to the operation of FNM-2127 Panel monitoring and reporting. Devices are identified as points when connected to the FNM-2127 Panel. Each FNM-2127 Panel supports a maximum of 127 points per loop plus subpoints on any module or 254 points per loop when utilizing subpoints. The FNM-2127 Panel supports a maximum of 800 devices per panel.

All FNM-2127 Panels support a point and subpoint maximum of 762 addresses per panel.

Zone CapabilityZones are groups containing combinations of control panel input, output and addressable loop devices.

Hardware FeaturesThe figure below illustrates hardware features of the FNM-2127 Panel: Figure 2-1Hardware Features

E E

P2R

P2TL2RL2T

P1R

P1TL1RL1T

AlarmSilence

Panel SounderSilence

LampTest Reset Fire Drill

ProgrammableFunction

Enable AccessRe-SoundAlarm

FireAC Power On

Pre-Alarm

On Test

More Events

GeneralDisablement

General Trouble

Power Trouble

Supervisory

NAC Trouble

MoreFire Events

MoreEvents

EnterExit

24V OUT AUX 24V

+ -+ - NC C NO

TROUBLE

NC C NO

FIRE

NC C NO

SUPERVISORYNAC 1 NAC2

+ - + -

NET OUT NET IN

+ - + -

COMMS

+ -

SLC1 OUT SLC1 IN

+ - + -

AC POWERL N E

BatteryConnection

+ -

JP1

PCPC / Dialer Reset Watchdog

OperatedContrastWatchdog

Reset

SLC2 OUT SLC2 IN

+ - + -

1

2

3

4 ?

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37

38 39 40 41

Panel SounderSilenced

Delay Active

C

A

B

Key Description

A Grounding Block

B Fascia

C Batteries

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

7 of 90

Page 17: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Overview 2

Notification Appliance Circuit (NAC) OutputsNAC outputs of the FNM-2127 Panel are programmable and can be operated in regulated or special application mode.Reference Appendix A, Specifications for constraints and operating levels of these NAC output modes.

Panel Controls and IndicatorsThe figure below illustrates controls and indicators of the FNM-2127 Panel: Figure 2-2Controls and Indicators

Key Description Key Description

A Terminal connections F AC power connections

B Left-panel-indicators G Settings and controls

C Lower-control-pad H Right-panel-controls and indicators

D PC connection I LCD Display

E Battery connection J JP1 connection

E E

P2RP2TL2RL2T

P1RP1TL1RL1T

AlarmSilence

Panel SounderSilence

LampTest Reset Fire Drill

ProgrammableFunction

Enable AccessRe-SoundAlarm

FireAC Power On

Pre-Alarm

On Test

More Events

General Disablement

General Trouble

Power Trouble

Supervisory

NAC Trouble

More Fire Events

More Events

EnterExit

24V OUT AUX 24V

+ -+ - NC C NO

TROUBLE

NC C NO

FIRE

NC C NO

SUPERVISORYNAC 1 NAC2

+ - + -

NET OUT NET IN

+ - + -

COMMS

+ -

SLC1 OUT SLC1 IN

+ - + -

AC POWERL N E

BatteryConnection

+ -

JP1

PCPC / Dialer Reset Watchdog

OperatedContrastWatchdog

Reset

SLC2 OUT SLC2 IN

+ - + -

1

2

3

4 ?

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37

38 39 40 41 A

B

C

D

E F

G

H

I

J

Panel Sounder Silenced

Delay Active

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

8 of 90

Page 18: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Overview 2

Left-Panel-IndicatorsThe figure below illustrates left-panel-indicators:

Figure 2-3Left-Panel-Indicators

FireAC Power On

Pre-Alarm

On Test

Panel Sounder Silenced

Delay Active

More Events

PointBypassed

General Trouble

Power Trouble

Supervisory

NAC Trouble

A

B

CD

E

F

GH

IJ

K

L

Key LED Indicator Color

A Fire, NAC Output State- Flashing = NACs Activated- ON Continuous = NACs silenced- OFF = Panel and NACs Reset

Red

B AC Power On Green

C Pre Alarm Yellow

D On Test Yellow

E Panel Sounder Silence Yellow

F Delay Active Yellow

G More Events Yellow

H Point Bypassed Yellow

I General Trouble Yellow

J Power Trouble Yellow

K Supervisory Yellow

L NAC Trouble Yellow

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

9 of 90

Page 19: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Overview 2

Right-Panel Controls and indicatorsThe figure below illustrates right-panel controls and indicators:

Figure 2-4Right-Panel-Indicators

MoreFire Events

MoreEvents

EnterExit

1

2

3

4 ?

A

B

C

D

E

F

G

H

I

Key Name Description

A Keypad number one Navigates menu selections up.

B Keypad number four Navigates menu selections to the left.

C Keypad number three Navigates menu selections down.

D Exit Cancels the current menu selection.

E More Fire Events Displays the number of alarms present on the FNM-2127 Panel and overrides the display provided by menu navigation.

F Keypad number two Navigates menu selections to the right.

G Keypad question mark Provides a “help screen” for the current menu display and also displays status. For example, recommendations aredisplayed during alarm or fault conditions. If a menu function is accessed then help relating to that function will be displayed.

H Enter Enables the menu selection.

I More Events Displays the number of events present and overrides menu navigation. Provides event status for Fire, Pre-Alarm, Trouble, Disablements and Other.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

10 of 90

Page 20: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Overview 2

Lower-Control-PadThe figure below illustrates the lower-control-pad:

Figure 2-5Lower-Control-Pad

Key Name Description

A Re-Sound Alarm Re-sounds the alarm when sounders are silenced using the Alarm Silencebutton.

B Alarm Silence Silences NACs connected to the FNM-2127 Panel after receiving authorization through Access Level 2.

C Panel Sounder Silence

Silences the internal buzzer of the FNM-2127 Panel. No other sounder outputs are affected by this operation.

D Lamp Test Tests fascia indicators and the internal buzzer by illuminating all LEDs while darkening the fascia display and sounding the buzzer.

E Reset Resets latching inputs such as fire and pre-alarm events after receiving authorization through Access Level 2. Fault events are non-latching inputs and cannot be cleared by the Reset button. Non-latching inputs are cleared when faults are cleared.

F Fire Drill Provides a fire drill for the FNM-2127 Panel after receiving authorization through Access Level 2. During the drill:

• The “On Test” LED illuminates continuously• The “Fire” LED blinks• The internal buzzer sounds intermittently• The display provides the message,

“FIRE DRILL:FIRE DRILL ZONE 00*

To stop the fire drill:1 Press 4 to display the “SET ACCESS LEVEL 2 MENU”.2 Provide Access Level 2 authorization.3 Press Reset or Fire Drill on the lower-control-pad.

G Programmable Function

Activates inputs, outputs or actions defined in the configuration by the installer.

H Enable Access This feature places the menu of the FNM-2127 Panel in ACCESS LEVEL 2. Insert the key in the lock and turn it to the right to obtain ACCESS LEVEL 2.

AlarmSilence

Panel SounderSilence

LampTest Reset Fire Drill

ProgrammableFunction

Enable AccessRe-SoundAlarm

B C D E F GA H

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

11 of 90

Page 21: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Overview 2

Settings and ResetsThe figure below illustrates settings and resets of the FNM-2127 Panel: Figure 2-6Settings and Resets

Terminal ConnectionsThe figure below illustrates terminal connections of the FNM-2127 Panel: Figure 2-7Terminal Connections

The table below describes terminal designations of the FNM-2127 Panel:

Designation Terminal Description

E, E 1 and 2 Earth ground

24V OUT 11 and 12 Terminal connections for the 24 volt output

AUX 24V 13 and 14 Terminal connections for the auxiliary 24 volt output

Key Name Description

A Reset Restores operation by restarting processors in the FNM-2127 Panel. Press Reset after a firmware upgrade to re-initialize processors in the panel.

B Watchdog Operated Illuminates when the processor of the FNM-2127 Panel stops running or re-boots.

C Watchdog Reset Turns off the Watchdog Operated LED by resetting it.

D Contrast Trim pot adjustment for increasing or decreasing the contrast of the LCD.

Reset WatchdogOperated

ContrastWatchdogReset

A B C D

24V OUT AUX 24V

+ -+ - NC C NO

TROUBLE

NC C NO

FIRE

NC C NO

SUPERVISORYNAC 1 NAC2

+ - + -

NET OUT NET IN

+ - + -

COMMS

+ -

SLC1 IN SLC1 OUT

+ - + -

SLC2 OUT SLC2 IN

+ - + -

5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37

38 39 40 41

E E

1 2

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

12 of 90

Page 22: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Overview 2

Internal Power SupplyThe internal power supply of the FNM-2127 Panel meets UL 864, 9th edition and provides a 5.25 Amp, off-line switch-mode power-source for operating Fire Alarm Control Panel (FACP) functions as well as charging the standby batteries.

The 5.25 Amp power supply can operate at 120 or 240 VAC. A jumper connection is provided on the power supply to switch between these operating voltages. Connecting the jumper provides 120 VAC operation and removing it provides 240 VAC operation.

Reference Appendix C, Calculations to determine load current limitations of the 5.25 Amp power supply

Features of the power supply include:

Designation Terminal Description

NAC1 15 and 16 Terminal connections for the NAC 1 circuit.

NAC2 17 and 18 Terminal connections for the NAC 2 circuit.

SLC1 IN 19 and 20 Terminal connections for the “IN” of SLC loop 1.

SLC1 OUT 21 and 22 Terminal connections for the “OUT” of SLC loop 1.

TROUBLE 23, 24 and 25 Trouble relay contacts

FIRE 26, 27 and 28 Fire relay contacts

SUPERVISORY 29, 30 and 31 Supervisory relay contacts

NET OUT 32 and 33 Terminal connections for the 'OUT' of the networking card

NET IN 34 and 35 Terminal connections for the 'IN' of the networking card

COMMS 36 and 37 Terminal connections for RS485 serial communication

SLC2 OUT 38 and 39 Terminal connections for the “OUT” of SLC loop 2.

SLC2 IN 40 and 41 Terminal connections for the “IN” of SLC loop 2.

Battery-backup Provides battery power to the load when the AC input of the power supply falls below the rated level. The voltage at the load remains within the specified range during these switching-transitions.

Battery-boost Boosts voltage when the battery voltage drops due to a low-battery condition.

Short-circuit protection Provides a shut down on the load side of the power supply when the load-current exceeds the maximum level.

Automatic-retry Restores output to the load when operating conditions return to nominal levels. This feature restores voltage levels at the load following conditions such as over-current and battery depletion.

Status The AC input to the power supply is supervised by the FNM-2127 Panel. The control panel provides an LED status display for normal and fault conditions. Normal conditions occur when the power supply is operating in an acceptable range. Fault conditions occur when the power supply is not operating in an acceptable range.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

13 of 90

Page 23: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Overview 2

This page intentionally left blank.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

14 of 90

Page 24: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

Section 3Installation

This section provides instructions for connecting cables, mounting and testing the FNM-2127 Panel for installation.

General Installation ChecklistTo complete the installation:

1 Create a plan of the fire alarm system and checklist for installing the FNM-2127 Panel.

2 Determine the current draw of the fire alarm system.

3 Determine the battery capacity of the FNM-2127 Panel.

4 Remove the FNM-2127 Panel from its packaging and check its contents.

5 Remove the standy-batteries from the base of the cabinet.

6 Mark the location for anchoring the cabinet to the premises-wall.

7 Anchor the cabinet of the FNM-2127 Panel to the premises-wall.

8 Thread cabling into the cabinet and secure it.

9 Place standby-batteries in the base of the empty-cabinet.

10 Attach the cabinet-door and the fascia to the cabinet.

11 Connect the standby-batteries to the terminal-connection on the fascia.

12 Connect all cabling.

13 Apply power to the FNM-2127 Panel from the AC source.

14 Configure the FNM-2127 Panel.

15 Test the FNM-2127 Panel installation.

CAUTION!Maintain extreme care when anchoring the cabinet and its contents to the premises wall. Electronic components within the FNM-2127 Panel are vulnerable to physical damage from shock and vibration. Remove the cabinet-door and fascia from the cabinet when installations cannot guarantee vigilant care during the wall-anchoring process.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

15 of 90

Page 25: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

Before You BeginBefore you begin the installation, take a few minutes to review the installation information, gather the required items, and complete the tasks listed below to make the installation as quick and easy as possible.

Separation of CircuitsWhen the product design is such that the product requires or permits power limited circuit conductors to occupy the same enclosure as non-power limited conductors, specific wire routing configurations must be detailed that ensure a minimum ¼ inch spacing be maintained between the different circuit type conductors.

Reference UL86412.3.1.

Determining System Current Draw Determine the current draw of the fire alarm system for alarm and standby conditions. Use these maximum current values to obtain the battery capacity of the fire alarm system as well as to confirm the operating constraints of the system.

1 Create a plan and checklist before beginning the installation process. Planning can reduce the number of problems that can occur during installation.

2 Select a mounting site for the FNM-2127 Panel that is suitable for its operating environment. The site chosen for mounting the FNM-2127 Panel should be clean and dry and not subject to shock or vibration. Ensure that the FNM-2127 Panel environment is free from wire ends, knockout discs and any other debris.

3 Acquire the following items that are not included with the FNM-2127 Panel, but may be required for theinstallation:

Item Quantity Description

MountingHardware

1 The mounting hardware that secures the FNM-2127 Panel to the premises-wall is not provided in the FNM-2127 Panel packaging.

Ground Strap 1 A ground strap is required for handling FNM-2127 Panel circuit boards. The ground strap is not provided in packaging of the FNM-2127 Panel.

CAUTION!

The FNM-2127 Panel installation must be performed by qualified personnel. Electronic components within the FNM-2127 Panel are vulnerable to damage from electrostatic discharge. Ground straps must be worn by installers before handling circuit boards of this device to prevent damage from electrostatic discharge.

CAUTION!Disconnect power before removing circuit boards from this device. Circuit boards can be damaged if removed from this device while receiving power. Never insert or remove circuit boards while in a power condition.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

16 of 90

Page 26: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

Power Supply and Standby-Battery CapacityPerform the installation after confirming that the load current of the system is below the operating capacity of the FACP power supply and within the functional range of the standby-batteries.

Reference Appendix C, Calculations to generate operating limits of the FACP system.

Operating ConstraintsInstallation of the FACP must include the operating constraints of the system to maintain continuous signal monitoring and reporting. Operating constraints are based on the current-driving capability of the FNM-2127 Panel outputs and the external loading caused by devices and cabling. External loads connected to the FNM-2127 Panel outputs must be chosen within the driving limits of each output.

The loading placed on these outputs can be caused by individual or multiple combinations of signaling line circuits, notification appliances and initiating devices. Cabling is also an external loading property on the FNM-2127 Panel outputs. Select cabling size and length based on the type of circuit connected to the output of the FNM-2127 Panel.

Reference Appendix A, Specifications and Appendix C, Calculations to determine specific operating constraints for devices and cabling connected to the FNM-2127 Panel.

Mounting the FNM-2127 Panel Select a mounting location that provides adequate room for opening the door of the FNM-2127 Panel. Provide a minimum of 1” clearance beyond the door-edge when anchoring the FNM-2127 Panel. Figure 3-1Door Clearance Recommendation

Marking the LocationMark hole locations on the premises-wall for mounting the FNM-2127 Panel. Figure 3-2Hole Marking Requirements

1"

24.5"

12.25"

16.50"

Ø0.25"

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

17 of 90

Page 27: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

Hochiki America

Anchoring the CabinetDrill holes in the premises-wall to anchor the empty FNM-2127 Panel cabinet using mounting-hardware to secure it.

Feeding CableRemove knockout tabs from the cabinet to feed cabling for AC power, 24 VDC, SLC devices, initiation devices and notification appliances.

Separate high and low voltage wiring in the enclosure with a minimum gap of 0.25". Reference UL 864 12.3.1.

To feed cabling into the cabinet:

Replacing Cabinet ComponentsReplace cabinet components of the FNM-2127 Panel to prepare for wiring the terminal-connector for AC power.

To prepare for wiring the terminal-connector for AC power:

1 Remove the top-left and top-right knockout tabs from the cabinet.

Figure 3-3Removing Knockout Tabs

2 Feed the AC power-cable into the top-left-hole provided from the knockout-tab.

3 Feed cables for 24 VDC, SLC devices, initiation devices and notification appliances into the top-right-hole. Remove additional knockout-holes directly adjacent to this knockout-hole, to provide more cabling space as required.

1 Remove debris from the base of the cabinet that may have accumulated during the anchoring process.

2 Replace the fascia on the cabinet-hinges and insert the hinge-pins to secure it.

3 Replace the cabinet-door on the cabinet-hinges and insert the hinge-pins to secure it.

1

2

3

4

Key Description

1 Remove this tab to feed the AC power-cable.

2 Remove this tab to feed cables for device communication.

3 Top-rear of the FNM-2127 Panel.

4 Top-front of the FNM-2127 Panel. fascia door flange shown.

CAUTION!Avoid routing SLC cabling through the same conduit as AC lines.

FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

18 of 90

Page 28: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

Connecting Power and Devices This section describes connecting power and devices to the FNM-2127 Panel.

Standby-BatteriesThe FNM-2127 Panel requires two batteries for FACP standby operation. The standby-batteries must be of a type that provides 12 VDC, 12 Amp Hour (AH) and rechargeable Sealed Lead Acid (SLA). Reference Appendix B, “Equipment List” for part numbering designations of the standby-batteries and Section 5, “Maintenance and Repair” for replacement requirements of the standby-batteries.

To install standby-batteries:

1 Place two 12 VDC batteries in the base of the FNM-2127 Panel cabinet that conform to the battery capacity values determined from Appendix C, Calculations.

2 Wire the batteries in series using the Battery Leads and Jumper Kit FN-BLJ.

3 Remove the battery-terminal-connector from the terminal-socket on the FNM-2127 Panel.

4 Orient the terminal-connector with the screw-heads facing up.

Figure 3-4Orienting the AC Terminal-Connector

E E

P2RP2TL2RL2T

P1RP1TL1RL1T

AlarmSilence

Panel SounderSilence

LampTest Reset Fire Drill

ProgrammableFunction

Enable AccessRe-SoundAlarm

FireAC Power On

Pre-Alarm

On Test

More Events

General Disablement

General Trouble

Power Trouble

Supervisory

NAC Trouble

More Fire Events

More Events

EnterExit

24V OUT AUX 24V

+ -+ - NC C NO

TROUBLE

NC C NO

FIRE

NC C NO

SUPERVISORYNAC 1 NAC2

+ - + -

NET OUT NET IN

+ - + -

COMMS

+ -

SLC1 OUT SLC1 IN

+ - + -

BatteryConnection

+ -

JP1

PCPC / Dialer Reset Watchdog

OperatedContrastWatchdog

Reset

SLC2 OUT SLC2 IN

+ - + -

1

2

3

4 ?

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37

38 39 40 41

Panel Sounder Silenced

Delay Active

AC POWERL N E

Battery Connection

+ -

Terminal-connector installed on front-panel of FNM-2127 Panel

Terminal-connector removed from FNM-2127 Panel and rotated with screw-heads facing up

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

19 of 90

Page 29: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

5 Connect wires from the standby-batteries to the battery-terminal-connector.

Figure 3-5Wiring the Terminal Connector

6 Insert the terminal-connector in the Battery Connection port on the fascia of the FNM-2127 Panel.

Figure 3-6Installing the Standby-Batteries

Black

Red

Terminal-connector above shown with screw-heads facing up.

+

E E

P2RP2TL2RL2T

P1RP1TL1RL1T

AlarmSilence

Panel SounderSilence

LampTest Reset Fire Drill

ProgrammableFunction

Enable AccessRe-SoundAlarm

FireAC Power On

Pre-Alarm

On Test

More Events

General Disablement

General Trouble

Power Trouble

Supervisory

NAC Trouble

More Fire Events

More Events

EnterExit

24V OUTAUX 24V

+ -+ - NC C NO

TROUBLE

NC C NO

FIRE

NC C NO

SUPERVISORYNAC 1 NAC2

+ - + -

NET OUT NET IN

+ - + -

COMMS

+ -

SLC1 OUT SLC1 IN

+ - + -

BatteryConnection

+ -

JP1

PCPC / Dialer Reset Watchdog

OperatedContrastWatchdog

Reset

SLC2 OUT SLC2 IN

+ - + -

1

2

3

4 ?

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37

38 39 40 41

Panel Sounder Silenced

Delay Active

AC POWERL N E

10 Amp battery fuse

The series battery connection provides 24 VDC at the Battery Connection terminals.

Battery Connection

+ -

BlackRed

Installed terminal-connector shown on the fascia of FNM-2127 Panel

Battery Kit, FN-BLJ contains battery leads, jumper and fuse assembly Fuse assembly FN-FUS-BAT contains a 32 V, 10 A fuse with red cabling.

Standby-batteries are 12 VDC, 12 AH and rechargeable SLA

Positive battery leadred cable

Negative battery lead black cable

Jumper-cable -

Battery 1 12 AH

Battery 2 12 AH

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

20 of 90

Page 30: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

Before Wiring and OperatingThe 5.25 Amp power supply of the FNM-2127 Panel provides settings for voltage inputs of 120 VAC or 240 VAC. Check these input settings prior to wiring and operating the control panel.

Make certain that the power supply is set for 240 VAC before operating at 240 VAC. Failure to make this check will cause permanent damage to the power supply when the input setting is 120 VAC and applied voltage is 240 VAC.

Remove jumper J1 from the circuit-board of the power supply to provide 240 VAC operation. Connect jumper J1 to the circuit-board to provide 120 VAC operation.

The figure below illustrates the location of jumper J1 on the circuit-board of the FNM-2127 Panel: Figure 3-7Circuit-Board Jumper J1

AC WiringConnect cabling from the power source to the terminal-connector for AC Power. The AC Power terminal-connector is located on the bottom-right of the FNM-2127 Panel.

Protect source connections to the AC Power terminal-connector with a 15 Amp fuse. Complete cabling to the AC Power terminal-connector using three insulated wires that are black, white and green.

Reference Appendix A, Specifications for the wire-gage requirements of these connections.

Remove jumper J1 before operating the FNM-2127 Panel at 240 VAC. Failure to remove jumper J1 before 240 VAC operation will cause severe and permanent damage to components of the FNM-2127 Panel.

WARNING!

WARNINGHIGHVOLTAGE

D1090 ISSUE 01

FUSE 5X20

REMOVE JUMPER J1 TOOPERATE THE POWERSUPPLY AT 240 VAC.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

21 of 90

Page 31: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

Wiring The Terminal-Connector

To wire the terminal-connector:

1 Remove the terminal-connector from the AC Power connection of the FNM-2127 Panel.

2 Orient the terminal-connector with the screw-heads facing up.

Figure 3-8Orienting the AC Terminal-Connector

4 Cut 3 feet of black wire and strip 1/4” of insulation from one end.

5 With the screw-terminals of the connector facing up, insert the stripped end of the black-wire in the right-side of the terminal-connector. Reference figure 3-9 for orientation of the black-wire in the terminal-connector.

6 Tighten the right-terminal-screw so that the black-wire is secure in the terminal-connector.

7 Cut 3 feet of white-wire and strip 1/4” of insulation from one end.

8 With the screw-terminals of the connector facing up, insert the stripped end of the white-wire in the center of the terminal-connector.Reference figure 3-9 for orientation of the white-wire in the terminal-connector.

9 Tighten the center-screw of the terminal-connector so that the white-wire is secure.

10 Cut 3 feet of green-wire and strip 1/4” of insulation from one end.

E E

P2RP2TL2RL2T

P1RP1TL1RL1T

AlarmSilence

Panel SounderSilence

LampTest Reset Fire Drill

ProgrammableFunction

Enable AccessRe-SoundAlarm

FireAC Power On

Pre-Alarm

On Test

More Events

General Disablement

General Trouble

Power Trouble

Supervisory

NAC Trouble

More Fire Events

More Events

EnterExit

24V OUT AUX 24V

+ -+ - NC C NO

TROUBLE

NC C NO

FIRE

NC C NO

SUPERVISORYNAC 1 NAC2

+ - + -

NET OUT NET IN

+ - + -

COMMS

+ -

SLC1 OUT SLC1 IN

+ - + -

BatteryConnection

+ -

JP1

PCPC / Dialer Reset Watchdog

OperatedContrastWatchdog

Reset

SLC2 OUT SLC2 IN

+ - + -

1

2

3

4 ?

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37

38 39 40 41

Panel Sounder Silenced

Delay Active

AC POWERL N E

AC POWERL N E

Terminal-connector connected to front-panel

Terminal-connector removed from front-panel and rotated with screw-heads facing up

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

22 of 90

Page 32: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

Installing the Ferrite and AC WiringTo install the ferrite and wire AC:

Connecting PowerTo complete the wiring process for AC and standby-battery power:

11 With the screw-terminals of the connector facing up, insert the stripped end of the green-wire in the left-side of the terminal-connector.Reference figure 3-9 for orientation of the green-wire in the terminal-connector.

Figure 3-9Wiring the Terminal-Connector

12 Connect the green-wire to the ground-stud of the cabinet.

1 Slide the white and black wires of the terminal-connector through Laird Ferrite P/N 28B1020-100.

2 Secure the ferrite at both ends with wire ties.

3 Connect the white and black wires of the terminal-connector to the Neutral and Line of the AC main.

Figure 3-10Installing the Ferrite and AC Wiring

1 Insert the battery terminal-connector in the Battery Connection socket on the fascia of the FNM-2127 Panel.

2

3

4

5

Insert the AC terminal-connector in the AC Power socket on the fascia of the FNM-2127 Panel.

Connect cabling for serial data and DC power.

Connect initiating devices, notification appliances and signalling circuits.

Test the installation following these connections. Reference “Testing the Installation” in this section.

Green

BlackWhite

The terminal-connector is shown rotated with screw-heads facing up and is shipped pre-wired from the factory.

G N LWhite Wire

Green Wire

Black Wire

Ferrite

15 Amp Branch Circuit of AC Main

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

23 of 90

Page 33: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

Installing SLC DevicesThis section describes installation requirements of SLC devices and the Laird ferrite. SLC devices described in this section include detectors, addressable notification appliances and output modules.

Installing the Laird FerriteA Laird ferrite must be installed on SLC wiring to filter the signal path from the FNM-2127 Panel to SLC devices. Position the Laird ferrite in the cabinet of the FNM-2127 Panel to provide optimum filtering of the signal path.

To install the Laird ferrite on SLC wiring:

1 Connect wiring and Zero-Ohm-Shorting-Jumpers to the SLC terminals.

2 Feed the wiring from the SLC terminals through the Laird ferrite three-times to create two-loops of wiring around the Laird ferrite.

3 Feed SLC wiring from the Laird ferrite through the nearest cabinet-exit-hole.

4 Position the Laird ferrite within 1.0” of the cabinet-exit-hole and secure it at both ends with wire-ties.

5 Connect SLC devices to the SLC wiring exiting the FNM-2127 Panel.

6 Maintain the limit for maximum wire length of the SLC circuit.

7 Dress and secure SLC wiring in the cabinet.

8 Repeat this procedure for remaining SLC wiring.

Figure 3-11Connecting SLC Devices and the Laird Ferrite

19 20 21 22

SLC1 IN SLC1 OUT

+ -+ -

Laird Ferrite P/N 28B1020-100 must be installed on all SLC wiring with two loops and within 1.0" of the nearest cabinet-exit-hole.

Zero-Ohm shorting-jumpers must be used on loop terminals, specify P/N S2026.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

24 of 90

Page 34: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

Detector SpacingInstall SLC detectors with spacing as specified in section 90.19 of UL 864, 9th edition where units employing the multiple detector operation shall include guidelines for installing of a minimum of two detectors in each protected space and to reduce the detector installation spacing to 0.7 times the linear spacing in accordance with National Fire Alarm Code, NFPA 72. Also reference 55.3.1 and 55.3.2 of UL 864, 9th edition for these detector spacing requirements.

Connecting Class A LoopsThe FNM-2127 Panel provides Class A loop connections at SLC 1 terminals 19 through 22. A second Class A loop connection is at SLC 2 terminals 38 through 41.

Terminate unused loops of the FNM-2127 Panel with zero-ohm shorting-jumpers. Connect zero-ohm shorting-jumpers on the FNM-2127 Panel from OUT (-) to IN (-) and OUT (+) to IN (+).

The FNM-2127 Panel provides a trouble signal when unused loops are not terminated. SLC loops of the FNM-2127 Panel are supervised. SLC loops must be wired with Short Circuit Isolator Modules to comply with NFPA 72, Class A Style 7. Short Circuit Isolator Modules protect SLC loop devices from single-loop-shorts.

During an SLC loop short-circuit:• The closest Short Circuit Isolator Modules to the short-circuit activate and respond by lighting their LED.• Devices between the Short Circuit Isolator Modules are isolated and inoperative.• Other devices on the SLC loop remain operational.• The FNM-2127 Panel indicates a trouble condition.

To install Class A, Style 6 and Style 7 SLC loops: • Do not use T-taps on Class A SLC loops.

T-taps are not permitted for use on Class A SLC loops.

• Do not permit outgoing loops and return-side loops to share the same conduit or cable.Feed outgoing and return-side loops separately.

Reference NFPA 72 for additional Class A requirements.

NFPA 72, Style 7

Connect wiring in compliance with NFPA 72, Class A, Style 7 requirements. For Class A, style 7 compliance, each device must be wired in a Closed Nipple with two surrounding Short Circuit Isolator Modules. The two Short Circuit Isolator Modules and the addressable device are enclosed individually or are shared in a common enclosure. If they are enclosed individually, the individual enclosures must be joined by “closed-nippling”.

When using Class A, Style 7 wiring, the Short Circuit Isolator Module must be installed before and after each addressable device on the SLC loop. Conduit must enclose wiring of the first and last Short Circuit Isolator Module on the SLC loop.

Isolator Modules shall be connected less than five feet from loop-terminal-connections of the FNM-2127 Panel to maintain compliance with Class A, Style 7 requirements. Closed Nipple devices share a common enclosure and include single housings or raceways.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

25 of 90

Page 35: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

Common Enclosure

The figure below illustrates the “common enclosure” type of Closed Nipple connection containing two short circuit isolator modules and a sensor:

Figure 3-12Common Enclosure

Individual Enclosures

SLC loop connections must include closed nippling and conduit nippling to maintain compliance with individual enclosures under NFPA 72, Class A, Style 7 requirements. Closed nippling encloses individual devices on SLC loops and conduit nippling encloses wiring between these individual enclosures.

The figure below illustrates the use of closed nippling and conduit nippling on an SLC loop of the FNM-2127 Panel:

Figure 3-13Individual Enclosure

SHORT CIRCUIT ISOLATORS

SENSOR

COMMON ENCLOSURE

Reference manufacturer specifications for Short Circuit Isolator Module and Sensor connections.

SHORT CIRCUIT ISOLATORS INDIVIDUAL ENCLOSURE

SENSOR

CONDUIT

Reference manufacturer specifications for Short Circuit Isolator Module and Sensor connections.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

26 of 90

Page 36: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

The figure below illustrates a Class A, Style 7 wiring example using three closed nipple enclosures on SLC Loop 1:

Figure 3-14 Class A, Style 7 Wiring Example

Reference manufacturer specifications for Short Circuit Isolator Module and Sensor connections.

Connect Short Circuit Isolator Modules less than five feet from the loop terminals of the FNM-2127 Panel to maintain compliance with Class A, style 7 requirements.

NFPA 72, Style 6

For Class A, Style 6 compliance, the Short Circuit Isolator Modules may be located at strategic locations based on the discretion of the designer or installer.

Connecting Class B LoopsThe FNM-2127 Panel provides Class B loop connections at SLC 1 terminals 19 through 22. Install Loop Expansion Module, VF1054-00 to provide a second Class B loop at SLC 2 terminals 38 through 41.

Terminate used and unused SLC loops with zero-ohm shorting-jumpers. Connect zero-ohm shorting-jumpers from OUT (-) to IN (-) and OUT (+) to IN (+). The FNM-2127 Panel provides a trouble signal when unused loops are not terminated. SLC loops of the FNM-2127 Panel are supervised.

CLOSED NIPPLE CIRCUIT CONTAINING TWO SHORT CIRCUIT ISOLATORS AND A SENSOR.

19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37

38 39 40 41

SUPERVISED 10K END-OF-LINE-RESISTOR, P/N S2030

TROUBLE

NC C NO

FIRE

NC C NO NC C NO

SUPERVISORY+ -+ -

NET OUT NET IN COMMS

+ -SLC1 IN SLC1 OUT

+ -+ -

SLC2 OUT SLC2 IN

+ -+ -

ZONE 1 ZONE 2 ZONE 3

15 16 17 18

NAC 1 NAC 2

+ -+ -

CABLE LENGTH OF THE CLOSED-NIPPLE CIRCUIT MUST NOT EXCEED 5 FEET FROM THE PANEL TO THE FIRST SHORT-CIRCUIT ISOLATOR-MODULE

CONNECT SHORT-CIRCUIT ISOLATOR-MODULES TO LOOPS CONTAINING CLOSED-NIPPLE CIRCUITS

INSTALL CONDUIT FROM THE PANEL TO THE FIRST SHORT-CIRCUIT ISOLATOR-MODULE ON LOOPSCONTAINING CLOSED-NIPPLE CIRCUITS

ZERO-OHM SHORTING-JUMPERS MUST BE USED ON UNUSED LOOP TERMINALS, SPECIFY P/N S2026

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

27 of 90

Page 37: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

The figure below illustrates Class B, Style 4 connections on SLC 1 of the FNM-2127 Panel: Figure 3-15Class B, Style 4 Connections

Reference manufacturer specifications for Short Circuit Isolator Module and Sensor connections. The Loop termination jumpers shown are provided in Resistor Kit (8) Zero Ohm. End Of Line Resistors (EOLRs) are used on Class B and not used on Class A, style 6 or 7 SLC loops.

Output Modules Controlling Notification AppliancesNot more than one notification zone shall be affected by a fault condition when installing output modules on SLC loops for controlling notification appliances. Install devices on an SLC loop of the FNM-2127 Panel containing one of the following methods to meet this requirement:• Perform an SLC loop installation that does not contain output devices.• Perform an SLC loop installation where output devices are in one zone.• Perform a Class A, Style 7 SLC loop installation where output devices are in different zones.• Perform a Class A SLC loop installation with output devices in separate zones, short-circuit-isolators on

SLC Loops and output devices on SLC loops with separate notification zones.

Reference “Connecting Class A Loops” for example-circuits containing these features.

Section 51.4.3 of UL 864, 9th edition specifies that a single break, single ground, or wire-to-wire fault on the installation conductors of a signaling line circuit for use with addressable notification appliances or modules shall not effect operation of more than one notification zone.

19 20 21 22 23 24 25 26 27 28 29 30 31 15 16 17 18 32 33 34 35 36 37

38 39 40 41

TROUBLE

NC C NO

FIRE

NC C NO NC C NO

SUPERVISORYNAC 1 NAC 2

+ -+ - + -+ -NET OUT NET IN COMMS

+ -SLC1 IN SLC1 OUT

+ -+ -

SLC2 OUT SLC2 IN

+ -+ -

ZERO-OHM SHORTING-JUMPERS MUST BE USED ON UNUSED LOOP TERMINALS, SPECIFY P/N S2026

SUPERVISED 10 K END-OF-LINE-RESISTOR, P/N S2030

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

28 of 90

Page 38: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

Silencing Notification AppliancesNotification Appliance (NA) silencing on the FNM-2127 Panel meets exception 1, item 33.3.4. of UL 864, 9th edition. Individual NA zones can be re-sounded by addressable loops on the FNM-2127 Panel after receiving the global silence command for multiple NA zones.

Exception 1 states,“When a system is intended to provide signaling service to two or more physically separated buildings or zones, re-energizing of the notification appliance circuits only on a zone basis meets the intent of the requirement.”

NAC Synchronization NAC 1 and 2 outputs on the FNM-2127 Panel can be connected for dual-output synchronization. These NAC outputs cannot be utilized for cross-panel synchronization.

Synchronized device connections on multiple FNM-2127 Panels require special conditions when installing audible and visual Notification Appliances:

Installing NAC DevicesThis section describes the installation requirements of NAC devices and the Laird ferrite.

Connect NAC 1 devices to terminals 15 and 16 and NAC 2 devices to terminals 17 and 18. NAC 1 and NAC 2 can be operated simultaneously provided current loading on each output is within FNM-2127 Panel specifications. NAC 1 and NAC 2 are supervised.

Reference Appendix A, “Specifications” for operating limits of these NAC outputs.

Audible Devices

The installation of synchronized-audible notification appliances on one control panel shall not be installed in hearing range of another control panel operating synchronized-audible notification appliances. NAC outputs on the FNM-2127 Panel are synchronized however these outputs cannot be synchronized with other control panels operating synchronized-audible notification appliances.

Visual Devices The installation of synchronized-visual notification appliances on one control panel shall not be installed in the line-of-sight of another control panel operating synchronized-visual notification appliances. NAC outputs on the FNM-2127 Panel are synchronized however these outputs cannot be synchronized with other control panels operating synchronized-visual notification appliances.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

29 of 90

Page 39: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

The figure above illustrates an example of Class B, Style Y Notification Appliances on NAC 1.

Connecting NAC Devices and the Laird FerriteA Laird ferrite must be installed on NAC wiring to filter the signal path from the FNM-2127 Panel to NAC devices. Position the Laird ferrite in the cabinet of the FNM-2127 Panel to provide optimum filtering of the signal path.

To install the Laird ferrite on NAC wiring:

1 Connect wiring to the NAC terminals.

2 Feed the wiring from the NAC terminals through the Laird ferrite two-times to create one-loop of wiring around the Laird ferrite.

3 Feed NAC wiring from the Laird ferrite through the nearest cabinet-exit-hole.

4 Position the Laird ferrite within 1.0” of the cabinet-exit-hole and secure it at both ends with wire-ties.

5 Connect NAC devices and the End Of Line Resistor (EOLR) to the NAC wiring exiting the FNM-2127 Panel.

6 Maintain the limit for maximum wire length of the NAC circuit.

7 Connect End-Of-Line-Resistors to the terminals of unused NAC outputs.

8 Dress and secure NAC wiring in the cabinet.

9 Repeat this procedure for remaining NAC wiring.

Figure 3-11Connecting NAC devices and the Laird Ferrite

15 16 17 18

NAC 1 NAC 2

+ -+ -NAC 1 NAC 2

+ -+ -

Supervised 10 K End-Of-Line-Resistor

-

+

-

+

-

+

Laird Ferrite P/N 28B1020-100 must be installed on all NAC wiring with one loop and within 1.0" of the nearest cabinet-exit-hole.

Class B Style-Y Notification Appliance Circuit containing three strobes andan end of line device, EOLD.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

30 of 90

Page 40: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

Connecting Auxiliary 24 VDC The 24 V OUT and AUX 24 V power-source can be used to operate expansion-boards or low-current auxiliary-devices. Devices connected to these terminals must not draw current in excess of 360 mA on each of these outputs. Connect circuits to terminals 11 and 12 for the 24 V OUT power-source. Connect circuits to terminals 13 and 14 for the AUX 24 V power-source.

Provide cabling connections to these outputs using wire with a 3 volt maximum line loss.

Maintain these connections using the wire gages defined in Appendix A, Specifications.

Reference Appendix B, “Equipment List” for the list of devices authorized for these outputs.

Relay ContactsConfigurable dry Form C relays are located on the FNM-2127 Panel for providing contact-actuation. The relays can be operated from default parameters or configured for specific functions in Loop Explorer.

Relay contacts of the FNM-2127 Panel include:

The figure below illustrates an example circuit using the normally-open contacts of the trouble relay:

Figure 3-12Trouble Relay Example

The adjacent figure illustrates a trouble-condition caused by the absence of end-of-line resistors and end-of-line-devices on terminals of the FNM-2127 Panel.

Trouble The default operation of this relay is set to perform a Trouble output. Configurable settings are provided for Delay, Alarm Silence, Zone and Location Text. Default settings for these attributes are disabled from operating.

Fire The default operation of this relay is set to perform a General Alarm and Emergency output. Configurable settings are provided for Delay, Alarm Silence, Zone and Location Text.Default settings for these attributes are disabled from operating.

Supervisory The default operation of this relay is set to perform a Supervisory Alarm output and the Alarm Silence button is enabled for operating. Configurable settings are provided for Delay, Zone and Location Text. Default settings for these attributes are disabled from operating.

24V OUTAUX 24V

+ -+ - NC C NO

TROUBLE

NC C NO

FIRE

NC C NO

SUPERVISORYNAC 1 NAC2

+ - + -

SLC1 OUT SLC1 IN

+ - + -

11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31

TROUBLE LAMP

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

31 of 90

Page 41: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

Hochiki America

Testing the InstallationPerform the following before testing the FNM-2127 Panel:

Confirming a Successful InstallationThe FNM-2127 Panel installation is successful when it completes the following sequence of fascia displays:

The fascia displays shown are intended for reference only.

Panel initialization

1 Connect loops, sounder circuits, inputs and outputs to the control panel.

2 Confirm that correct connections exist between the batteries and the power supply.

3 Apply AC power to the FNM-2127 Panel.

4 Verify that the panel display illuminates.

5 Perform an AUTO LEARN and confirm that the Fascia Menu does not contain errors.

AUTO LEARN is a feature of the FNM-2127 Panel for testing the health of external devices and connections. Operate AUTO LEARN through Access Level 3 of the fascia menu. External devices receive default configuration settings during the AUTO LEARN sequence and circuit connections are tested for opens, shorts and ground fault conditions.

6 Test the FNM-2127 Panel lamps.

1 Panel Initialization Tests internal hardware and firmware responsible for operating loop devices.

2 Loop Initialization

3 Normal-Standby

Configures the FNM-2127 Panel to existing loop conditions.

Displays the Normal Standby after a successful boot process.

CAUTION!

The FNM-2127 Panel buzzer may activate following AUTO LEARN. Buzzer activation indicates that an installation error condition exists. Disable the buzzer, determine the cause of the alarm and then rectify the installation problem.

FireAC Power On

Pre- Alarm

On Test

More Events

Point Bypassed

General Trouble

Power Trouble

Supervisory

NAC Trouble

Panel Sounder Silenced

Delay Active

INITIALIZING PANEL

PLEASE WAIT...

ProgrammableFunction

Enable AccessAlarmSilence

Panel SounderSilence

LampTest Reset Fire Drill

Re- SoundAlarm

1

2

3

4 ?

More Events

More Fire Events

EnterExit

FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

32 of 90

Page 42: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

Loop Initialization

Normal-Standby

Testing the Panel Lamps

1 Press the lamp test button to light the fascia lamps.

2 Verify that all fascia lamps are lit.

Contact the help desk if fascia lamps do not light. Reference Section 2, “Overview” for a description of Lamp Test operation.

FireAC Power On

Pre-Alarm

On Test

More Events

General Trouble

Power Trouble

Supervisory

NAC Trouble

Panel Sounder Silenced

Delay Active

ProgrammableFunction

Enable AccessAlarmSilence

Panel SounderSilence

LampTest Reset Fire Drill

Re-SoundAlarm

1

2

3

4 ?

More Events

More Fire Events

EnterExit

Point Bypassed

INITIALIZING LOOPS PLEASE WAIT

LOOP NUM. DEVICES INIT. PROCESS 1 0 100%2 0 100%

FireAC Power On

Pre-Alarm

On Test

More Events

Point Bypassed

General Trouble

Power Trouble

Supervisory

NAC Trouble

Panel Sounder Silenced

Delay Active

ProgrammableFunction

Enable AccessAlarmSilence

Panel SounderSilence

LampTest Reset Fire Drill

Re-SoundAlarm

1

2

3

4 ?

More Events

More Fire Events

EnterExit

11:08 Monday 09 January 2012

AUTO CONFIGURED PANEL

USE ARROW KEYS TO ENABLE PANEL

PRESS ? FOR HELP

Initializations performed during the booting process are complete when the Normal Standby condition displays. The Normal Standby condition indicates that the FNM-2127 Panel is operating properly and that the installation was successful.

FireAC Power On

Pre-Alarm

On Test

More Events

Point Bypassed

General Trouble

Power Trouble

Supervisory

NAC Trouble

Panel Sounder Silenced

Delay Active

ProgrammableFunction

Enable AccessAlarmSilence

Panel SounderSilence

LampTest Reset Fire Drill

Re-SoundAlarm

1

2

3

4 ?

More Events

More Fire Events

EnterExit

11:08 Monday 09 January 2012

AUTO CONFIGURED PANEL

USE ARROW KEYS TO ENABLE PANEL

PRESS ? FOR HELP

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

33 of 90

Page 43: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

Trouble-Silence TestThis test checks the silencing operation of the FNM-2127 Panel during a trouble condition.

To perform the Trouble-Silence Test:

1 Confirm that the FNM-2127 Panel is in the Normal-Standby mode before performing this test.The Normal-Standby mode is shown below:

The first line of the message format contains the time, day and date. The second line of the format contains a default or user defined message.

2 Press any numeric arrow-button on the right-control-panel or turn the enable key-switch to the right to display “SET ACCESS LEVEL 2 MENU” on the LCD.

3 Provide Access Level 2 authorization and then press Enter on the right-control-panel.

4 Remove the black-lead from the negative terminal of the standby-battery in the FNM-2127 Panel.

The following conditions occur on the fascia of the FNM-2127 Panel:• The General Trouble LED flashes yellow.

• The Power Trouble LED flashes yellow.

• The internal sounder annunciates.

• The LCD display provides the following message to identify this condition:

In the example display above the trouble condition is identified by * TROUBLE * and “TBL=0002”. TBL=0002 indicates that two trouble conditions exist. The first trouble condition, “Low battery voltage” is displayed above. The second trouble condition, “battery disconnected” is displayed in the

MORE EVENTS menu.

11:08 Monday 09 January 2012AUTO CONFIGURED PANEL

USE ARROW KEYS TO ENABLE PANELPRESS ? FOR HELP

ALM=000 TBL=0002 SUP=000 OOS=000 REL=00

* TROUBLE *

NODE=1 PANEL NAME

Low battery voltage

More Events

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

34 of 90

Page 44: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

5 Identify the second trouble condition on the FNM-2127 Panel.

To display the second trouble condition on the FNM-2127 Panel: Press More Events on the fascia of the FNM-2127 Panel.Press 3 on the central-key-pad to scroll down to “MORE TROUBLE”. Press 2 on the central-key-pad to display “battery disconnected”.

6 Silence the sounder on the FNM-2127 Panel.

Press the Panel Sounder Silence button on the fascia to silence the internal alarm of the FNM-2127 Panel. The following conditions occur on the fascia of the FNM-2127 Panel: • The General Trouble LED flashes yellow.

• The Power Trouble LED flashes yellow.

• The internal sounder does not annunciate.

• The LCD display provides the following message to identify this condition:

7 Re-connect the black-lead to the negative terminal of the standby-battery in the FNM-2127 Panel.

The LCD display provides the following message to identify the return to the normal-standby condition:

MORE TROUBLE 001/002

* TROUBLE *

NODE=1 PANEL NAME

Battery disconnected

Use UP/DOWN arrow keys to scroll events

ALM=000 TBL=0002 SUP=000 OOS=000 REL=00

* TROUBLE *

NODE=1 PANEL NAME

Low battery voltage

More Events

11:08 Monday 09 January 2012AUTO CONFIGURED PANEL

USE ARROW KEYS TO ENABLE PANELPRESS ? FOR HELP

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

35 of 90

Page 45: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

Troubleshooting This section describes how to troubleshoot using the Fascia Menu of the FNM-2127 Panel.Perform troubleshooting techniques on the FNM-2127 Panel when messages on the fascia are not consistent with those described in “Confirming a Successful Installation”. Options on the Fascia Menu include:

Test ZonesThe TEST ZONES menu tests NAC, panel and loop outputs. Options for this menu feature are described below:

Reference Section 4, “Fascia Menu” for more information about Test Zones.

Test Zones reverts to the MAIN MENU after 25 seconds when there is no navigation activity on the fascia display.

To troubleshoot using the TEST ZONES menu feature:

Test Zones Tests zones 1 to 500 including local NACs, panel outputs and loop outputs.

Event Log Provides event log view function as well as an event log clear function.

Loop Data Test Tests devices connected to FNM-2127 Panel loops.

Test Zones Default = 1 Sets the test for zones 1 to 500.

Local NACs Default = On Tests NACs of the FNM-2127 Panel. Audible and visual notification circuits activate for 3-second durations during this test.

Loop Outputs Default = Off Tests loop driven outputs other than the loop sounders.

1 Press 3 on the upper-control-pad to display the SET ACCESS LEVEL 2 MENU.

SET ACCESS LEVEL 2 MENU

Enter Access Level 2 Password

Use numbered arrow keys

*****

Access will automatically expire after

120 seconds if no key is pressed.

ENTER TO PROCECEED – EXIT TO QUIT

2 Type the five digit code in the password field and press Enter.The default password is 22222.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

36 of 90

Page 46: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

3 Press 3 on the upper-control-pad to display the MAIN MENU.

MAIN MENU – V07.0007A

>DISABLEMENTS

VIEW DeviceS

TEST ZONES

SET SYSTEM TIME

SENSOR MAINTENANCE EARLY WARNING

ACCESS LEVEL 3

4 Press 3 on the upper-control-pad to navigate down to TEST ZONES.

MAIN MENU – V07.0007A

DISABLEMENTS

VIEW DeviceS

>TEST ZONES

SET SYSTEM TIME

SENSOR MAINTENANCE EARLY WARNING

ACCESS LEVEL 3

5 Press 2 on the upper-control-pad to select TEST ZONES.

TEST ZONES MENU

>TEST ZONE: 01 – (NORMAL)

Use Up/Down arrow keys to select.

Press > to proceed. Press < to go back.

6 Press 1 on the upper-control-pad to select a TEST ZONE from 1 to 500.

7 Press 2 on the upper-control-pad to select the TEST ZONE option for LOCAL NAC: - ON.

TEST ZONE: 1

>LOCAL NAC: - ON

Use Up/Down arrow keys to select.

Press > to proceed. Press < to go back.

8 Press 1 on the upper-control-pad to set LOCAL NAC: - OFF.

9 Press 2 on the upper-control-pad to select the TEST ZONE option for PANEL OUTPUTS: -OFF.

TEST ZONE: 1

>PANEL OUTPUTS: - OFF

Use Up/Down arrow keys to select.

Press > to proceed. Press < to go back.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

37 of 90

Page 47: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

10 Press 1 on the upper-control-pad to set PANEL OUTPUTS: - ON.

11 Press 2 on the upper-control-pad to select the TEST ZONE option for Loop OUTPUTS: - OFF.

TEST ZONE: 1

>Loop OUTPUTS: - OFF

Use Up/Down arrow keys to select.

Press > to proceed. Press < to go back.

12 Press 1 on the upper-control-pad to set Loop OUTPUTS: - ON.

13 Press 2 on the upper-control-pad to display the test mode for the TEST ZONE:

START TEST MODE ?

TEST ZONE: 1

Test Mode will expire after 15 minutes if zone is idle.

Press ENTER to start Test Mode.

Press EXIT to quit.

Press < to go back.

14 Press ENTER on the upper-control-pad to begin the test or press EXIT to quit.Test mode runs for 15 minutes.

During the test:• The “On Test” LED illuminates continuously• The More events LED illuminates continuously• The General Trouble LED blinks.• The internal buzzer sounds intermittentlyThe fascia display provides the following message:

ZONES IN Alarm=000 TRBL=0001 DISAB=0000

* TROUBLE *

NODE=1 AUTOLEARN

Test mode

More Events

15 Press ENTER (again) to cancel the test.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

38 of 90

Page 48: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

Event LogAll FACP system activities are displayed in the event log. Operators of the FNM-2127 Panel can use the event log to trouble-shoot system problems or confirm conditions such as Fire Drills.

Reference Section 4, “Fascia Menu” for more information about Event Log.

Displaying the Event Log

To display the Event Log:

1 Press 3 on the upper-control-pad to display the SET ACCESS LEVEL 2 MENU.

SET ACCESS LEVEL 2 MENU

Enter Access Level 2 Password

Use numbered arrow keys

*****

Access will automatically expire after

120 seconds if no key is pressed.

ENTER TO PROCECEED – EXIT TO QUIT

2 Type the five digit code in the password field and press Enter.The default password is 22222.

3 Press 3 on the upper-control-pad to display the MAIN MENU.

MAIN MENU – V07.0007A

>DISABLEMENTS

VIEW DeviceS

TEST ZONES

SET SYSTEM TIME

SENSOR MAINTENANCE EARLY WARNING

ACCESS LEVEL 3

4 Press 1 on the upper-control-pad to navigate to ACCESS LEVEL 3.

MAIN MENU – V07.0007A

DISABLEMENTS

VIEW DeviceS

TEST ZONES

SET SYSTEM TIME

SENSOR MAINTENANCE EARLY WARNING

>ACCESS LEVEL 3

5 Press 2 on the upper-control-pad to display the SET ACCESS LEVEL 3 MENU:

SET ACCESS LEVEL 3 MENU

Enter Access Level 3 Password

Use numbered arrow keys

*****

ENTER TO PROCEED – EXIT TO QUIT

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

39 of 90

Page 49: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

6 Type the five digit code in the password field and press Enter.The default password is 33333.

ACCESS LEVEL 3 MENU

>EDIT CONFIGURATION

SET TIMES

VIEW PRINT EVENT LOG

PRINT CONFIGURATION

SYSTEM DISABLEMENTS

Loop DATA TEST

7 Press 3 on the upper-control-pad and navigate to EVENT LOG.

ACCESS LEVEL 3 MENU

EDIT CONFIGURATION

SET TIMES

>VIEW PRINT EVENT LOG

PRINT CONFIGURATION

SYSTEM DISABLEMENTS

Loop DATA TEST

8 Press 2 on the upper-control-pad to display the VIEW/CLEAR EVENT LOG MENU.

VIEW/CLEAR EVENT LOG MENU

>View Event Log

Print Event Log

Clear Event Log

View Archived Event Log

Clear Archived Event Log

9 Press 2 on the upper-control-pad to display the View Event Log.

SELECT EVENT TYPES TO VIEW

>FIRE- 0

PRE-Alarm- 1

TROUBLE- 0

DISABLEMENT- 0

OTHER EVENTS- 0

ALL EVENTS- 0

10 Press 3 on the upper-control-pad to scroll down the list of event types.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

40 of 90

Page 50: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

Clearing the Event Log

The Clear Event Log feature removes the event log from FNM-2127 Panel memory.

To clear the event log:

11 Press 2 on the upper-control-pad to display the event type.Event logs are not displayed when events are shown with zeros in “SELECT EVENT TYPES TO VIEW”. An example of a pre-alarm condition is shown below:

VIEW PRE-Alarm EVENTS 001/016

*PRE-Alarm: HEAT SENSOR ZONE 02 *

ADR=011.00 Loop=2 ND=1 AUTOLEARN

TIME 10:35 02/18/2004

Pre-Alarm

Use UP/DOWN arrow keys to scroll events

12 Press 4 on the upper-control-pad to go back or press Exit to quit.

1 Press 3 on the upper-control-pad to display the SET ACCESS LEVEL 2 MENU.

SET ACCESS LEVEL 2 MENU

Enter Access Level 2 Password

Use numbered arrow keys

*****

Access will automatically expire after

120 seconds if no key is pressed.

ENTER TO PROCECEED – EXIT TO QUIT

2 Type the five digit code in the password field and press Enter.The default password is 22222.

3 Press 3 on the upper-control-pad to display the MAIN MENU.

MAIN MENU – V07.0007A

>DISABLEMENTS

VIEW DeviceS

TEST ZONES

SET SYSTEM TIME

SENSOR MAINTENANCE EARLY WARNING

ACCESS LEVEL 3

4 Press 1 on the upper-control-pad to navigate to ACCESS LEVEL 3.

MAIN MENU – V07.0007A

DISABLEMENTS

VIEW DeviceS

TEST ZONES

SET SYSTEM TIME

SENSOR MAINTENANCE EARLY WARNING

>ACCESS LEVEL 3

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

41 of 90

Page 51: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

5 Press 2 on the upper-control-pad to display the SET ACCESS LEVEL 3 MENU:

SET ACCESS LEVEL 3 MENU

Enter Access Level 3 Password

Use numbered arrow keys

*****

ENTER TO PROCEED – EXIT TO QUIT

6 Type the five digit code in the password field and press Enter.The default password is 33333.

ACCESS LEVEL 3 MENU

>EDIT CONFIGURATION

SET TIMES

EVENT LOG

SYSTEM DISABLEMENTS

Loop DATA TEST

7 Press 3 on the upper-control-pad and navigate to EVENT LOG.

ACCESS LEVEL 3 MENU

EDIT CONFIGURATION

SET TIMES

>EVENT LOG

SYSTEM DISABLEMENTS

Loop DATA TEST

8 Press 2 on the upper-control-pad to display the VIEW/CLEAR EVENT LOG MENU.

VIEW/CLEAR EVENT LOG MENU

>View Event Log

Clear Event Log

9 Press 3 on the upper-control-pad to scroll down to Clear Event Log.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

42 of 90

Page 52: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

Loop Data TestThe Loop Data Test feature tests loop devices connected on the FNM-2127 Panel. Reference

Section 4, “Fascia Menu” for more information about the Loop Data Test feature. To

perform the Loop Data Test:

10 Press 2 on the upper-control-pad to display the CLEAR EVENT LOG MENU.

CLEAR EVENT LOG MENU

Event Log has 1 entries

Press ENTER to clear Event Log.

Press EXIT to quit.

Press < to go back.

11 Press ENTER to clear the Event log.

CLEAR EVENT LOG MENU

Event Log has 0 entries

Press ENTER to clear Event Log.

Press EXIT to quit.

Press < to go back.

12 Press EXIT to quit or press 4 to go back.

1 Press 3 on the upper-control-pad to display the SET ACCESS LEVEL 2 MENU.

SET ACCESS LEVEL 2 MENU

Enter Access Level 2 Password

Use numbered arrow keys

*****

Access will automatically expire after

120 seconds if no key is pressed.

ENTER TO PROCECEED – EXIT TO QUIT

2 Type the five digit code in the password field and press Enter.The default password is 22222.

3 Press 3 on the upper-control-pad to display the MAIN MENU.

MAIN MENU – V07.0007A

>DISABLEMENTS

VIEW DeviceS

TEST ZONES

SET SYSTEM TIME

SENSOR MAINTENANCE EARLY WARNING

ACCESS LEVEL 3

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

43 of 90

Page 53: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

4 Press 1 on the upper-control-pad to navigate to ACCESS LEVEL 3.

MAIN MENU – V07.0007A

DISABLEMENTS

VIEW DeviceS

TEST ZONES

SET SYSTEM TIME

SENSOR MAINTENANCE EARLY WARNING

>ACCESS LEVEL 3

5 Press 2 on the upper-control-pad to display the SET ACCESS LEVEL 3 MENU:

SET ACCESS LEVEL 3 MENU

Enter Access Level 3 Password

Use numbered arrow keys

****

ENTER TO PROCEED - EXIT TO QUIT

6 Type the five digit code in the password field and press Enter.The default password is 33333.

ACCESS LEVEL 3 MENU

>EDIT CONFIGURATION

SET TIMES

EVENT LOG

SYSTEM DISABLEMENTS

Loop DATA TEST

7 Press 1 on the upper-control-pad scroll up to Loop DATA TEST.

ACCESS LEVEL 3 MENU

EDIT CONFIGURATION

SET TIMES

EVENT LOG

SYSTEM DISABLEMENTS

>Loop DATA TEST

8 Press 2 on the upper-control-pad to display the Loop DATA TEST.

Loop DATA TEST

>SELECT Loop 1

SET TIMES

9 Press 2 on the upper-control-pad to START TEST.

Loop DATA TEST

>START TEST

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

44 of 90

Page 54: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

10 Press 2 on the upper-control-pad to begin the test.

Loop DATA TEST (Loop: 1)

Start Date: 12/10/2009 10:37:00

Good Readings: 0100800

Bad Readings: 0000000

Current Date: 12/10/2009 10:58:13

The test example above indicates that the loop test was started 12/10/2009 at 10:37. It also reveals that over one-hundred-thousand test readings have been recorded since the beginning of the test.

11 Press 4 on the upper-control-pad to back out of the Loop DATA TEST screen.

Loop DATA TEST

>VIEW DATA

CANCEL TEST

12 Press 3 on the upper-control-pad to scroll down to CANCEL TEST.

13 Press 2 on the upper-control-pad to display the window for stopping the test.

Loop DATA TEST

PLEASE PRESS ENTER TO STOP TEST

14 Press ENTER to cancel the loop test.

Loop DATA TEST

>SELECT Loop 1

15 Press EXIT to return to the main menu.

11:12 Thursday December 10 2009

AUTO CONFIGURED PANEL

USE ARROW KEYS TO ENABLE PANEL

PRESS ? FOR HELP

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

45 of 90

Page 55: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Installation 3

This page intentionally left blank.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

46 of 90

Page 56: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Front-Panel Menu 4

Section 4Fascia Menu

This section describes the operation of the Fascia Menu on the FNM-2127 Panel. Navigate the menu using the upper-control-pad of the FNM-2127 Panel.

The FNM-2127 Panel provides navigation of the Fascia Menu for Access Level 2 and Access Level 3. Access Level 2 controls fascia-buttons and menu settings. Access Level 3 controls FNM-2127 Panel system settings. To operate the Fascia Menu of the FNM-2127 Panel:

The Fascia Menu display returns to the Main Menu when navigation activity stops for more than 25 seconds.

1 Confirm that the display of the Fascia Menu does not contain errors after performing AUTO LEARN.AUTO LEARN is a feature of the FNM-2127 Panel for testing the health of external devices and connections. Operate AUTO LEARN through Access Level 3 of the fascia menu. External devices receive default configuration settings during the AUTO LEARN sequence and circuit connections are tested for opens, shorts and ground fault conditions.

Reference “Section 3, Troubleshooting” if error messages are displayed on the fascia following the AUTO LEARN process.

2 Press 3 on the upper-control-pad to display the SET ACCESS LEVEL 2 MENU.

3 Type the five digit code in the password field and press Enter.The default password is 22222.

4 Press 3 on the upper-control-pad to display the MAIN MENU.

5 Press 3 on the upper-control-pad to navigate to LOCAL MENU.

6 Press 2 on the upper-control-pad to select LOCAL MENU and display MAIN MENU.

7 Press 1 on the upper-control-pad to navigate to ACCESS LEVEL 3.

8 Press 2 on the upper-control-pad to select ACCESS LEVEL 3 and display SET ACCESS LEVEL 3 MENU.

9 Type the five digit code in the password field and press Enter.The default password is 33333.

10 Press 1 to navigate to ACCESS LEVEL 3 MENU.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

47 of 90

Page 57: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Front-Panel Menu 4

Access Level 2Access Level 2 provides functions for:• Disablements• View Devices• Test Zones• Set System Time• Sensor Maintenance Early Warning• Access Level 3

DisablementsThe Disablements Menu provides an option for viewing and restoring disabled features as well as settingtimed or un-timed disablements for loops, zones, addresses, audible devices and panel I/O:

The timed function provides a disablement-duration of 30 minutes to 24 hours and stops the disablement when the duration-time expires. The un-timed function provides an infinite disablement that stops when “cleared” on the menu.

Disable Loops

The DISABLE Loops function disables loop-devices from reporting fire signals to the FNM-2127 Panel. This function does not disable loop-devices from reporting trouble and supervisory signals to the FNM-2127 Panel.

Disable Zones

All detection devices, including manual pull stations, are disabled in the selected zone. When a device is disabled, the FNM-2127 Panel ignores the analog value reported by the device. All other faults for the device such as missing device, double address, internal fault, type changed and bad data are still reported by the FNM-2127 Panel.

MAIN MENU - V07.0007A

>DISABLEMENTS

VIEW DeviceS

TEST ZONES

SET SYSTEM TIME

SENSOR MAINTENANCE EARLY WARNING

ACCESS LEVEL 3

DISABLEMENTS MENU

>DISABLE Loops

DISABLE ZONES

DISABLE ADDRESSES

DISABLE AUDIBLE DeviceS

DISABLE PANEL I/O

VIEW & RESTORE DISABLED FEATURES

CAUTION!

The DISABLE Loops function does not isolate the FNM-2127 Panel from SLC connections. Disconnect SLC connections to the FNM-2127 Panel when troubleshooting or when performing wiring changes.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

48 of 90

Page 58: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Front-Panel Menu 4

Disable Addresses

Any loop device can be disabled using this menu option. Sub-addresses may be individually disabled when using devices with more than one input or output.

When a device is disabled, the FNM-2127 Panel ignores the analog value reported by the device. All other faults for the device such as missing device, double address, internal fault, type changed and bad data are still reported by the FNM-2127 Panel.

Disable Audible Devices

This menu option disables all audible device outputs connected to the control panel. An audible device output is defined as any output that has been set to respond to Silence and Evacuate panel commands. Audible device outputs may be directly wired to NAC 1 and NAC 2 or loop driven devices. The NAC Trouble indicator will be illuminated, as well as the Point Bypassed Indicator.

Disable Panel I/O

This menu option disables or enables panel input and output functions. Timed disabling can be set to occur between 30 minutes to 24 hours. Un-timed disabling can be set to occur indefinitely.

Panel Inputs

Panel Outputs

Programmable Default = Enabled Disables or enables the fascia Programmable Function button.

Fire Drill Default = Enabled Disables or enables the fascia Fire Drill button.

NAC 1 Default = Enabled Disables or enables NAC 1 on Terminal X1 of the Main Board. To set these parameters using the FNM-2127 Panel Fascia Menu: 1 Select ACCESS LEVEL 22 Select ACCESS LEVEL 33 Select EDIT CONFIGURATION4 Select EDIT PANEL I/O5 Select EDIT PANEL OUTPUTS6 Scroll through the options for NAC CIRCUIT 1

NAC 2 Default = Enabled Disables or enables NAC 2 on Terminal X1 of the Main Board. To set these parameters using the Front Panel Menu of the FNM-2127 Panel: 1 Select ACCESS LEVEL 22 Select ACCESS LEVEL 33 Select EDIT CONFIGURATION4 Select EDIT PANEL I/O5 Select EDIT PANEL OUTPUTS6 Scroll through the options for NAC CIRCUIT 2

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

49 of 90

Page 59: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Front-Panel Menu 4

View & Restore Disabled Features

To cancel disablements, scroll through the menu options and toggle disablements to the normal condition. Another way to cancel disablements is to use the View / Restore Disablements option to scroll through active disablements and individually enable each disablement by pressing the Enter button.

View DevicesThis menu option is used by experienced personnel to investigate system status and may help in fault finding.The View Devices option displays addresses connected to each detection circuit. For each address & sub-address, the LCD status display provides the device type, zone and location text. Analog devices are displayed in the menu with indicators representing the connected device. Digital input devices such as the points of manual pull stations and switch monitor units are displayed as Normal or Activated. Output devices are displayed as either Off, Intermittent or Continuous.Status conditions are displayed in the Devices By Loop or View Devices By Zone area of the menu.

Test ZonesEach zone may be individually put into a Test Mode condition.

Test Zone (1 – 500)

When test mode is selected, devices in the zone may be tested and the FNM-2127 Panel will automatically reset after 3 seconds. When a zone is put into test mode, the user is prompted to select a number of test mode options. These options are retained for each zone, but may be changed at any time.

Local NAC On – Off (Default = On)

When set to the ON position, all NAC outputs will sound for the duration of the fire event. The NACs will be silenced when the panel automatically resets.

NAC devices may not activate within the three second fire period on systems operating high numbers of loop-powered NAC devices. Loop confirmation of these NAC devices may be intermittent under these conditions.

Loop Outputs On – Off (Default = Off)

When selected in the ON position, all loop driven outputs other than the loop NAC outputs will operate in accordance with their standard configuration.

Start Test Mode?

Initiate zone testing using this screen after setting parameters in Test Zone (1 – 500), Local NAC On – Off, Panel Outputs On – Off and Loop Outputs On – Off.The screen display is:

A 15 minute timer begins decrementing when a zone is set in test mode. The test will automatically stop after the timer stops. The timer automatically resets to 15 minutes whenever a device is activated in the zone test.

Test Mode will expire after 15 minutes

if zone is idle.

Press ENTER to start Test Mode.

Press EXIT to quit.

Press < to go back,

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

50 of 90

Page 60: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Front-Panel Menu 4

Include Pull Stations Yes – No (Default = No)

When selected to the ON position, all manual pull stations will also be included in the Test Mode for the zone. The normal use of this facility is to set the Include Pull Stations to No and test all smoke detection devices in the zone. At this stage, all manual pull stations will still operate and will take the panel out of test mode. When all devices in the zone have been tested, then the zone is put into test, including manual pull stations.

All manual pull stations can then be tested and will operate the test mode when a zone (or zones) has been set to test mode, then a 15 minute timer is started. This timer will decrement and after 15 minutes the zone will be automatically taken out of test mode. Whenever a device is activated in the zone in test, the timer will automatically be reset to 15 minutes.

Set System TimeThis menu option sets the panel date and time. Set the system time to log events in the event log.

The FNM-2127 Panel automatically compensates for daylight saving time.

Sensor Maintenance Early Warning This option provides contamination status for Loop 1 and 2.

Events and Status This section describes events and the status of the fascia display while operating the FNM-2127 Panel. The following events are described: • Fire Event• Trouble Event• Pre Alarm Event

Fire Event

In the event of a fire, the red FIRE lamp and the appropriate Fire Zone indicator flash (if connected). Details of the fire activation (address and location text) display on the fascia.Fire warning NACs sound throughout the building and the panel fire relay contact energizes. The panel buzzer pulses, but can be silenced by pressing the Silence Buzzer button.

To silence fire NACs, press any of the menu navigation buttons and enter the Access 2 password then press the Enter button. Panel controls will be enabled and will remain enabled for one minute after pressing the last key. Pressing the Alarm Silence button will silence the NACs. The NACs can be started again by pressing the Re-Sound Alarm button. The system can be reset by pressing the Reset button.

Press the More Events button on the fascia to display the status of more than two fire events.

The maximum Fire event delay setting shall be less than 10 seconds.

Trouble Event

If there is a fault on the system, the yellow General Trouble indicator will flash and there may be other fault LED indications which identify the nature of the fault. The Fault Contact and Fault Routing outputs will energize and the panel buzzer will sound continuously.Details of the fault will be provided on the fascia display. The panel buzzer can be silenced at any time by pressing the Silence Buzzer button.Press the More Events button on the fascia to display the status of more than two fire events.

The maximum Trouble event delay setting shall be less than 120 seconds.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

51 of 90

Page 61: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Front-Panel Menu 4

Pre-alarm Event

Sensors or inputs can generate a pre-alarm. A pre-alarm is used to warn of a slow change in the analog level of detection devices. A smoldering fire can be an example of a condition that can cause a pre alarm event.

When a pre-alarm is generated, the control panel will illuminate the pre-alarm LED and will sound the internal buzzer continuously. The address and location of the source of the pre-alarm will be indicated in the LCD status display.

The source of the pre-alarm input should be investigated. The panel buzzer can be silenced at any time by pressing the Silence Buzzer button.

Press the More Events button on the fascia to display the status of more than two fire events.

The maximum Pre-Alarm event delay setting shall be less than 60 seconds.

Access Level 3Access Level 3 of the FNM-2127 Panel provides menu settings for: • Edit Configuration• Set Times• View Event Log• System Disablements• Loop Data Test

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

52 of 90

Page 62: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Front-Panel Menu 4

Figure 4-1 illustrates a menu map describing menu commands for navigating Access Level 3:

Figure 4-1Access Level 3 Menu

Edit Configuration

Edit Supplier Name

Edit General Alarm Mode

Common Ring Mode

Edit I/O

Zonal Ring Mode

Edit Panel Inputs

Edit Device Attributes

Add/Delete Device

Auto Learn

Edit Panel I/O

Edit Default Pattern

Edit Panel Outputs

Edit Alarm Verification

Edit AC Fail Report Delay

Edit Network Class

Add Communicator

Edit Remote I/O

Set Remote Configuration

Add Dialer

Set Times

Set Calibration Time

Set Day/Night Times

Set Sounder Time-Out

Loop Data Test

Select Loop 1

Select Loop 2

View Event Log

View Archived Event Log

Print Event Log

Clear Event Log

Clear Archived Event Log

View Event Log

Print Configuration

Print By Loop - All Loops

Print By Loop - Select Loop

Print By Zone - All Zones

Print By Zone - Select Zone

System Disablements

Set Buzzer Silenced Access Level

Disable printer

Disable Buzzer

Disable Ground Trouble

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

53 of 90

Page 63: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Front-Panel Menu 4

Fascia ControlsAccess Level 2 operates the following fascia button-controls: • Alarm Silence• Re-sound Alarm• Reset• Fire Drill• Programmable FunctionObtain Access level 2 with the menu-password or with the Enable Access key.

Reference “Section 2, Overview” for a summary of these controls and “Appendix E, Operating Instructions” for detailed functional descriptions.

Alarm SilenceThe Alarm Silence button silences the internal buzzer as well as sounders connected to the FNM-2127 Panel.

Press the Panel Sounder Silence button to silence the internal buzzer without silencing sounders connected to the control panel.

Re-Sound AlarmThe Re-Sound Alarm button re-sounds the alarm following a silence condition initiated by the Panel Sounder Silence or Alarm Silence command.

ResetThe Reset button clears latching inputs on the control panel. Latching inputs remain active after correcting the cause of the input event. Perform a reset to clear latching inputs on the control panel caused by supervisory, trouble, pre-alarm and fire signals.

Non-latching inputs do not require reset. Non-latching inputs clear after correcting the cause of the input condition.

Fire Drill The Fire drill button initiates a fire drill on the control panel. Cancel the fire drill by pressing the Fire Drill button while in Access Level 2.

Programmable FunctionThe Programmable Function button is disabled as a default condition, but can be configured to perform specific functions while in Access Level 3or Loop Explorer. Operate the Programmable Function button in Access Level 2 of the FNM-2127 Panel menu.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

54 of 90

Page 64: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Maintenance and Repair 5

Section 5Maintenance and Repair

This section provides procedures to maintain and repair the FNM-2127 Panel.

Reference Appendix B, “Equipment List” for component-part-numbers described in this section.

MaintenancePerform the following procedures to maintain operation of the FNM-2127 Panel.

Inspecting Batteries Inspect the standby-batteries annually to determine the connection integrity to the power supply and to confirm the voltage capacity available for operating the FNM-2127 Panel during power failures.

Replacing Standby-BatteriesReplace standby-batteries when the service period reaches 3 to 5 years. Specify replacement batteries that are sealed-lead-acid and that are UL recognized.

Removing the Standby-Batteries

To remove the existing standby-batteries:

1 Disconnect the jumper-cable connection between Battery 1 and Battery 2.

2 Disconnect the red-cable from the positive Terminal of Battery 1.

3 Disconnect the black-cable from the negative Terminal of Battery 2.

4 Remove Battery 1 and Battery 2 from the bottom of the FNM-2127 Panel cabinet.

5 Re-cycle Battery 1 and Battery 2 according to the manufacturer procedures provided in the packaging of the batteries.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

55 of 90

Page 65: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Maintenance and Repair 5

Installing the Standby-Batteries

To install the replacement standby-batteries:

Reference Section 3, Installation for more information describing the standby battery installation process.

The figure below illustrates the connection required for installing replacement standby-batteries in the FNM-2127 Panel:Figure 5-1Installing Standby-Batteries

The series connection illustrated above provides the 24 volt standby voltage required by the FNM-2127 Panel. Do not connect the two batteries in parallel. A parallel connection will not provide the 24 volts required for operating the FNM-2127 Panel in a standby condition.

1 Place standby-batteries at the bottom of the FNM-2127 Panel cabinet.

2 Connect the black-cable to the negative terminal of Battery 2.

3 Connect the red-cable to the positive terminal of Battery 1.

4 Connect the jumper-cable from the negative terminal of Battery 1 to the positive terminal of Battery 2.

5 Mark a “placed into service date” on Battery 1 and Battery 2.

E E

P2RP2TL2RL2T

P1RP1TL1RL1T

AlarmSilence

Panel SounderSilence

LampTest Reset Fire Drill

ProgrammableFunction

Enable AccessRe-SoundAlarm

FireAC Power On

Pre-Alarm

On Test

More Events

General Disablement

General Trouble

Power Trouble

Supervisory

NAC Trouble

More Fire Events

More Events

EnterExit

24V OUTAUX 24V

+ -+ - NC C NO

TROUBLE

NC C NO

FIRE

NC C NO

SUPERVISORYNAC 1 NAC2

+ - + -

NET OUT NET IN

+ - + -

COMMS

+ -

SLC1 OUT SLC1 IN

+ - + -

BatteryConnection

+ -

JP1

PCPC / Dialer Reset Watchdog

OperatedContrastWatchdog

Reset

SLC2 OUT SLC2 IN

+ - + -

1

2

3

4 ?

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37

38 39 40 41

Panel Sounder Silenced

Delay Active

E E

P2R

P2T

L2RL2T

P1R

P1T

L1RL1T

AlarmSilence

Panel SounderSilence

LampTest Reset Fire Drill

ProgrammableFunction

Enable AccessRe-SoundAlarm

FireAC Power On

Pre-Alarm

On Test

More Events

GeneralDisablement

General Trouble

Power Trouble

Supervisory

NAC Trouble

MoreFire Events

MoreEvents

EnterExit

24V OUT AUX 24V

+ -+ - NC C NO

TROUBLE

NC C NO

FIRE

NC C NO

SUPERVISORYNAC 1 NAC2

+ - + -

NET OUT NET IN

+ - + -

COMMS

+ -

SLC1 OUT SLC1 IN

+ - + -

AC POWERL N E

BatteryConnection

+ -

JP1

PCPC / Dialer Reset Watchdog

OperatedContrastWatchdog

Reset

SLC2 OUT SLC2 IN

+ - + -

1

2

3

4 ?

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37

38 39 40 41

Panel SounderSilenced

Delay Active

AC POWERL N E

+ -

Standby-batteries are 12 VDC, 12 AH and rechargeable SLA

10 Amp battery fuse

Battery 1

Kit FN-BLJ contains battery-leads, jumper and fuse assembly Fuse assembly FN-FUS-BAT contains a 32 V fuse rated @ 10 A with red cabling.

Negative battery-lead (black cable)

Positive battery-lead(red cable)

Jumper-lead

Battery 2

HA3529-0M, Revision E02.00Hochiki America FNM-2127 Panel Installation Manual

56 of 90

Page 66: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Maintenance and Repair 5

Replacing FusesA 10 Amp battery fuse and a 3 Amp power-supply fuse are provided to protect the FNM-2127 Panel against circuit overloads. During the life of the product it may be necessary to replace one or both of the fuses to restore operation to the FNM-2127 Panel.

Replace a fuse only after replacing the components responsible for causing the fuse failure. Fuse failure is not a condition caused by the fuse. Diagnose and replace components in the fuse-circuit before replacing the fuse and operating the FNM-2127 Panel.

10 Amp Battery FuseReplace the 10 Amp battery-fuse by removing the fuse, the battery wiring and the standby-batteries. Specify kit 92160 to replace the red-cable containing the 10 Amp fuse or specify battery-lead-kit 92151 to replace the red-cable containing the 10 Amp fuse, the jumper-cable and the black-cable.

Replace the 3 Amp Power-Supply Fuse by removing it from the housing contained on the circuit board of the power supply. Install the replacement fuse in the housing and then test the power supply to determine that it operates.

Removing the 10 Amp Battery-Fuse

To remove the fuse:

Installing the 10 Amp Battery-Fuse

To install the new 10 Amp Battery-Fuse:

1 Remove the battery-connector from the Battery Connection on the fascia of the FNM-2127 Panel.

2 Disconnect the jumper-cable connection between Battery 1 and Battery 2.

3 Disconnect the red-cable from the positive terminal of Battery 1.

4 Disconnect the black-cable from the negative terminal of Battery 2.

5 Dispose the battery-leads described in steps 1 through 3 above.

1 Connect the jumper-lead from the negative terminal of Battery 1 to the positive terminal of Battery 2.

2 Connect the red-cable to the positive terminal of Battery 1.

3 Connect the black-lead to the negative terminal of Battery 2.

4 Connect the battery-connector to the Battery Connection on the fascia of the FNM-2127 Panel.

5 Determine that trouble conditions are not reported by the FNM-2127 Panel following the fuse replacement. This step confirms that the installation was performed correctly.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

57 of 90

Page 67: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Maintenance and Repair 5

3 Amp Power-Supply FuseThe 3 Amp fuse located on the circuit board of the power supply. Remove this fuse and install a replacement by following the procedures described below.Removing the FuseTo remove the fuse:

The figure below illustrates the location of the 3 Amp fuse on the power supply of the Main Board.Figure 5-23 Amp Fuse Location

Installing the Replacement Fuse

To install the replacement fuse:

1 Turn off AC power to the control panel at the source.

2 Remove the AC Power terminal-connector from the connection at the lower-front of the control panel.

3 Locate the housing containing the 3 Amp fuse.

4 Remove the upper-half of the fuse-housing with long-nose-pliers.

5 Remove the fuse from the upper-half of the fuse-housing.

1 Insert the fuse in the upper-housing.

2 Center the position of the fuse in the upper-housing.

3 Press the upper-housing on the lower-housing until the halves snap together.

4 Restore AC power to the power supply.

5 Verify that the FNM-2127 Panel completes the booting process to confirm that the Power Supply is operating correctly.

WARNING!

This is a high voltage circuit area. An electrical shock hazard exists in this area when the control panel is operating. Do not remove the fuse while the control panel is powered. Disconnect AC power at the source before attempting to remove the 3 Amp fuse.

WARNINGHIGHVOLTAGE

D1090 ISSUE 01

FUSE 5X20

FUSE 5X20

HA3529-0M,Revision E02.00 Hochiki America FNM-2127 Panel Installation Manual

58 of 90

Page 68: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Maintenance and Repair 5

Removing Cabinet ComponentsRemove cabinet components of the FNM-2127 Panel to prepare for the mounting process. To prepare the FNM-2127 Panel for mounting:

1 Turn the key in the cabinet-door-lock to the right to unlock and open the cabinet-door of the FNM-2127 Panel.

Figure 4-3Unlocking and Opening The Cabinet-Door

2 Remove the upper and lower hinge-pins to remove the cabinet-door.

Figure 4-4Removing Upper and Lower Hinge-Pins

AlarmSilence

Panel SounderSilence

LampTest Reset Fire Drill

ProgrammableFunction

Enable AccessRe- SoundAlarm

FireAC Power On

Pre- Alarm

On Test

Delay Active

AC Power On

More Events

General Disablement

General Trouble

Power Trouble

Supervisory

NAC Trouble

More Fire Events

More Events

EnterExit

1

2

3

4 ?

Cabinet-door-lock

To remove hinge-pins from the cabinet:

1 Pull the head of the upper-hinge-pin away from the hinge-assembly using needle-nose-pliers.

2 Brace the top-corner of the cabinet-door to maintain alignment with the lower-hinge.

3 Pull the head of the lower-hinge-pin away from the hinge-assembly using needle-nose-pliers.

E E

P2RP2TL2RL2T

P1RP1TL1RL1T

AlarmSilence

Panel SounderSilence

LampTest Reset Fire Drill

ProgrammableFunction

Enable AccessRe-SoundAlarm

FireAC Power On

Pre-Alarm

On Test

More Events

GeneralDisablement

General Trouble

Power Trouble

Supervisory

NAC Trouble

MoreFire Events

MoreEvents

EnterExit

24V OUT AUX 24V

+ -+ - NC C NO

TROUBLE

NC C NO

FIRE

NC C NO

SUPERVISORYNAC 1 NAC2

+ - + -

NET OUT NET IN

+ - + -

COMMS

+ -

SLC1 OUT SLC1 IN

+ - + -

AC POWERL N E

BatteryConnection

+ -

JP1

PCPC / Dialer Reset Watchdog

OperatedContrastWatchdog

Reset

SLC2 OUT SLC2 IN

+ - + -

1

2

3

4 ?

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37

38 39 40 41

Panel SounderSilenced

Delay Active

Pull the hinge-pin in the direction of the arrow to remove it from the upper-cabinet-hinge

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

59 of 90

Page 69: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Maintenance and Repair 5

3 Remove the cabinet-door from the FNM-2127 Panel.

Figure 4-5Removing the Cabinet-Door

4 Remove the terminal-connector from the AC Power socket.

Figure 4-6Removing the AC Power Connector

E E

P2RP

2TL2RL2T

P1RP

1TL1RL1T

AlarmSilence

Panel SounderSilence

LampTest Reset Fire Drill

ProgrammableFunction

Enable AccessRe-SoundAlarm

FireAC Power On

Pre-Alarm

On Test

More Events

GeneralDisablement

General Trouble

Power Trouble

Supervisory

NAC Trouble

MoreFire Events

MoreEvents

Exit

24V OUT AUX 24V

+ -+ - NC C NO

TROUBLE

NC C NO

FIRE

NC C NO

SUPERVISORYNAC 1 NAC2

+ - + -

NET OUT NET IN

+ - + -

COMMS

+ -

SLC1 OUT SLC1 IN

+ - + -

AC POWERBattery

Connection

+ -

JP1

PCPC / Dialer Reset Watchdog

OperatedContrastWatchdog

Reset

SLC2 OUT SLC2 IN

+ - + -

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37

Panel SounderSilenced

Delay Active

E E

P2RP2TL2RL2T

P1RP1TL1RL1T

AlarmSilence

Panel SounderSilence

LampTest Reset Fire Drill

ProgrammableFunction

Enable AccessRe-SoundAlarm

FireAC Power On

Pre-Alarm

On Test

More Events

GeneralDisablement

General Trouble

Power Trouble

Supervisory

NAC Trouble

More MoreEvents

Exit

24V OUT AUX 24V

+ -+ - NC C NO

TROUBLE

NC C NO

FIRE

NC C NO

SUPERVISORYNAC 1 NAC2

+ - + -

NET OUT NET IN

+ - + -

COMMS

+ -

SLC1 OUT SLC1 IN

+ - + -

BatteryConnection

+ -

JP1

PCPC / Dialer Reset Watchdog

OperatedContrastWatchdog

Reset

SLC2 OUT SLC2 IN

+ - + -

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37

Panel SounderSilenced

Delay Active

AC POWERL N E

AC power terminal-connector containing a ground-wire. Do not remove this connection.

The AC power terminal-connector remains in the cabinet during the mounting process. Disconnect it from the control panel and place it on the bottom of the cabinet. Cover the terminal-connector to prevent debris from contaminating it during the mounting process.

The AC power terminal-connector contains a ground-wire that terminates on the cabinet-wall. The ground-wire is secured to the cabinet-wall with a lock-washer and nut combination. Do not remove the this connection during the installation process.

HA3529-0M, Revision E02.00Hochiki America FNM-2127 Panel Installation Manual

60 of 90

Page 70: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Maintenance and Repair 5

5 Remove the retaining screw from the fascia of the FNM-2127 Panel cabinet.

Figure 4-7Retaining Screw

6 Open the fascia of the FNM-2127 Panel cabinet.

7 Remove the hinge-pins from the fascia.

Figure 4-8Removing the Fascia

E E

P2RP2TL2RL2T

P1RP1TL1RL1T

AlarmSilence

Panel SounderSilence

LampTest Reset Fire Drill

ProgrammableFunction

Enable AccessRe-SoundAlarm

FireAC Power On

Pre-Alarm

On Test

More Events

GeneralDisablement

General Trouble

Power Trouble

Supervisory

NAC Trouble

MoreFire Events

MoreEvents

EnterExit

24V OUT AUX 24V

+ -+ - NC C NO

TROUBLE

NC C NO

FIRE

NC C NO

SUPERVISORYNAC 1 NAC2

+ - + -

NET OUT NET IN

+ - + -

COMMS

+ -

SLC1 OUT SLC1 IN

+ - + -

JP1

PCPC / Dialer Reset Watchdog

OperatedContrastWatchdog

Reset

SLC2 OUT SLC2 IN

+ - + -

1

2

3

4 ?

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37

38 39 40 41

Panel SounderSilenced

Delay Active

BatteryConnection

+ -AC POWERL N E

Remove retainingscrew to openfront-panel

E E

P2RP

2TL2RL2T

P1RP

1TL1RL1T

AlarmSilence

Panel SounderSilence

LampTest Reset Fire Drill

ProgrammableFunction

Enable AccessRe-SoundAlarm

FireAC Power On

Pre-Alarm

On Test

More Events

GeneralDisablement

General Trouble

Power Trouble

Supervisory

NAC Trouble

MoreFire Events

MoreEvents

EnterExit

24V OUT AUX 24V

+ -+ - NC C NO

TROUBLE

NC C NO

FIRE

NC C NO

SUPERVISORYNAC 1 NAC2

+ - + -

NET OUT NET IN

+ - + -

COMMS

+ -

SLC1 OUT SLC1 IN

+ - + -

AC POWERL N E

BatteryConnection

+ -

JP1

PCPC / Dialer Reset Watchdog

OperatedContrastWatchdog

Reset

SLC2 OUT SLC2 IN

+ - + -

1

2

3

4 ?

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37

38 39 40 41

Panel SounderSilenced

Delay Active

To remove hinge-pins from the fascia:

Place the fascia button-side-down on a clean, dry and uncluttered-surface. Do not place the fascia down on the component side.

1 Pull the head of the upper-hinge-pin away from the hinge-assembly using needle-nose-pliers.

2 Brace the top-corner of the fascia to maintain alignment with the lower-hinge.

3 Pull the head of the lower-hinge-pin away from the hinge-assembly using needle-nose-pliers.

4 Remove the fascia from the cabinet.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

61 of 90

Page 71: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Maintenance and Repair 5

This page intentionally left blank.

HA3529-0M, Revision E02.00Hochiki America FNM-2127 Panel Installation Manual

62 of 90

Page 72: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Specifications A

Appendix ASpecifications

This appendix provides electrical and environmental specifications for the FNM-2127 Panel.

Electrical The electrical specifications provided for Standby and Alarm Current are typical values.

Standby and Alarm Current

Earth Fault IndicationA ground fault indication occurs on the FNM-2127 Panel when a minimum of 30K Ohms exists between earth-ground and either DC RTN or +24 VDC of the power-supply.

SLC Ratings

Loops Standby Alarm (mA) Description

1 160 mA @ 120 VAC 220 mA @ 120 VAC Line current for standby and alarm when battery current is less than 30 mA.

200 mA @ 24 VDC 220 mA @ 24 VDC Battery current for standby and alarm when a power failure condition occurs on the AC line.

2 200 mA @ 120 VAC 250 mA @ 120 VAC Line current for standby and alarm when battery current is less than 30 mA.

270 mA @ 24 VDC 290 mA @ 24 VDC Battery current for standby and alarm when a power failure condition occurs on the AC line.

Terminal Connection Rating

19 Loop 1 (+ IN) 32 VDC @ 250 mA

20 Loop 1 (- IN)

21 Loop 1 (+ OUT) 32 VDC @ 250 mA

22 Loop 1 (- OUT)

38 Loop 2 (+ OUT) 32 VDC @ 250 mA

39 Loop 2 (- OUT)

40 Loop 2 (+ IN) 32 VDC @ 250 mA

41 Loop 2 (- IN)

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

63 of 90

Page 73: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Specifications A

SLC CablingThe FNM-2127 Panel requires the following wire gage and length when connecting Class A and B SLC loops:

Programmable Relay Contacts

NAC Outputs

Reference Appendix B, “Equipment List” for NAC devices that are authorized for use with the FNM-2127 Panel.

NAC outputs of the FNM-2127 Panel can be operated in regulated or special application modes.

Wire Gage Wire Length

18 AWG, Shielded-Stranded 1950 Feet

16 AWG, Shielded-Stranded 3100 Feet

14 AWG, Shielded-Stranded 5,000 Feet

Terminal Connection Rating

23 Trouble (NC), Not Supervised 30 VDC @ 1A

24 Trouble (C), Not Supervised 30 VDC @ 1A

25 Trouble (NO), Not Supervised 30 VDC @ 1A

26 Fire (NC), Not Supervised 30 VDC @ 1A

27 Fire (C), Not Supervised 30 VDC @ 1A

28 Fire (NO), Not Supervised 30 VDC @ 1A

29 Supervisory (NC), Not Supervised 30 VDC @ 1A

30 Supervisory (C) Not Supervised 30 VDC @ 1A

31 Supervisory (NO) Not Supervised 30 VDC @ 1A

Terminal Connection Rating

15 NAC 1 (+) Regulated: 24 VDC @ 1.6 A continuous DC or 900 mA pulsed DCSpecial Application: 24 VDC @ 2.3 A continuous with the combined current of NAC 1 and NAC 2 not to exceed 3.1 A

16 NAC 1 (-)

17 NAC 2 (+) Regulated: 24 VDC @ 1.6 A continuous DC or 900 mA pulsed DCSpecial Application: 24 VDC @ 2.3 A continuous with the combined current of NAC 1 and NAC 2 not to exceed 3.1 A

18 NAC 2 (-)

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

64 of 90

Page 74: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Specifications A

Regulated Outputs

NAC outputs of the FNM-2127 Panel operate in a regulated mode when conforming to specific levels of continuous or pulsed DC. NAC outputs meet requirements for regulated levels when the output current does not exceed the constraints described below:

Continuous CurrentContinuous DC currents cannot exceed 1.6 A from either NAC output when operating in a regulated output mode:Regulated continuous DC output = 1.6 A NAC 1 + 1.6 A NAC 2 = 3.2 A total

Pulsed CurrentPulsed DC currents cannot exceed 900 mA from either NAC output when operating in a regulated output mode:Regulated pulsed DC output = 900 mA NAC 1 + 900 mA NAC 2 = 1.8 A total

SynchronizationSynchronize the regulated output of NAC 1 and NAC 2 using UL listed and compatible synchronization modules. Connect End-Of-Line-Device 92158 to the output of each Synchronization Module installed.

Reference Appendix B, Equipment List for more information about NAC synchronization on the FNM-2127 Panel.

Special Application Output

NAC outputs of the FNM-2127 Panel operate in a special application mode when conforming to specific levels of continuous DC. NAC outputs meet requirements for special application levels when the output current does not exceed the 2.3 A of NAC 1 or NAC 2 with the combined current of NAC 1 and NAC 2 not to exceed 3.1 A.

SynchronizationThe FNM-2127 Panel provides internal device synchronization between the outputs of NAC 1 and NAC 2 when operating NAC devices from Gentex or Wheelock.External synchronization modules must not be used on the NAC outputs when operating in the special application mode. Reference Appendix B, Equipment List for more information about NAC synchronization on theFNM-2127 Panel.

RS485 Serial Bus

NET Terminals

Terminal Connection Rating

36 COMMS (+) (+) Data 3.3 VDC @ 30 mA

37 COMMS (-) (-) Data

Terminal Connection Rating

32 NET OUT (+) (+) Data 3.3 VDC @ 30 mA

33 NET OUT (-) (-) Data

34 NET IN (+) (+) Data 3.3 VDC @ 30 mA

35 NET IN (-) (-) Data

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

65 of 90

Page 75: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Specifications A

24 V OUT

The 24 V OUT connection is a common output and provides a regulated 24 VDC output.

Auxiliary 24 VDC

The AUX 24 VDC connection is a common output and provides a regulated 24 VDC output.

AC Line Connection

Power Supply

The specifications above pertain to terminations of the standby-battery at the Battery Connection of the FNM-2127 Panel.

Terminal Connection Rating

11 24 V OUT (+) Regulated 24 VDC @ 360 mA

12 24 V OUT (-)

Terminal Connection Rating

13 AUX 24V (+) Regulated 24 VDC @ 360 mA

14 AUX 24V (-)

Terminal Description Voltage Current

L AC line 120 VAC, 50/60Hz

240 VAC, 50/60Hz

2.1 A

1.1 A

N AC neutral

G Earth ground

Fuse 3A, 250VAC, SLOW-BLOW, 5 x 20mm

Input (Supervised) 120 or 240 VAC 50/60Hz

Output Voltage 24 VDC Regulated

Output Current 0 - 5.25 Amps (1.25 A reserved for battery charger)

Charge Current Fast charge: 1.25 A Trickle charge: 1.25 A (voltage limited)

Battery-Charging Type Two 12 VDC, 12 AH, SLA standby batteries wired in series

Transfer Voltage 120 VAC transfer @ 75 VAC240 VAC transfer @ 160 VAC

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

66 of 90

Page 76: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Specifications A

Hochiki America

CablingThe following specifications identify the range of acceptable wire gages for field wiring, battery and power connections:

Field Wiring

Designation Terminal Wire Range Description

E, E 1 and 2 12 - 14 AWG, Shielded-Stranded Earth ground

24V OUT 11 and 12 12 - 14 AWG, Shielded-Stranded Terminal connections for the 24 volt output

AUX 24V 13 and 14 12 - 14 AWG, Shielded-Stranded Terminal connections for the auxiliary 24 volt output

NAC1 15 and 16 12 - 14 AWG, Shielded-Stranded Terminal connections for the NAC 1circuit.

NAC2 17 and 18 12 - 14 AWG, Shielded-Stranded Terminal connections for the NAC 2 circuit.

SLC1 IN 19 and 20 12 - 14 AWG, Shielded-Stranded Terminal connections for the “IN” of SLC loop 1.

SLC1 OUT 21 and 22 12 - 14 AWG, Shielded-Stranded Terminal connections for the “OUT” of SLC loop 1.

TROUBLE 23, 24 and 25 12 - 14 AWG, Shielded-Stranded Normally closed (NC) and normally open (NO) contacts of the trouble circuit.

FIRE 26, 27 and 28 12 - 14 AWG, Shielded-Stranded Normally closed (NC) and normally open (NO) contacts of the fire circuit.

SUPERVISORY 29, 30 and 31 12 - 14 AWG, Shielded-Stranded Normally closed (NC) and normally open (NO) contacts of the supervisory circuit.

NET OUT 32 and 33 12 - 14 AWG, Shielded-Stranded Not used

NET IN 34 and 35 12 - 14 AWG, Shielded-Stranded Not used

COMMS 36 and 37 12 - 14 AWG, Shielded-Stranded Terminal connections for RS485 serial communication

SLC2 OUT 38 and 39 12 - 14 AWG, Shielded-Stranded Terminal connections for the “OUT” of SLC loop 2.

SLC2 IN 40 and 41 12 - 14 AWG, Shielded-Stranded Terminal connections for the “IN” of SLC loop 2.

FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

67 of 90

Page 77: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Specifications A

Battery and Power

Cabling Construction

Operating Environment

Physical Specifications

Designation Terminal Wire Range Description

Battery Connection

+ 12 - 14 AWG Positive connection for the Standby-batteries

- 12 - 14 AWG Negative connection for the Standby-batteries

AC Power L 12 - 14 AWG Line connection

N 12 - 14 AWG Neutral connection

E 12 - 14 AWG Ground connection

Material All field wiring should be installed using fire rated cables according to the NFPA.

Cross Sectional Size The cross sectional size of the SLC cables should be determined based on length and the number of devices in use. Connect SLC cabling using a minimum of 1mm cross sectional area.

Low Temperature 32 +/- 3oF (0 +/- 2oC) Dry indoor use only

High Temperature 120+/- 3oF (49 +/- 2oC) Dry indoor use only

Relative Humidity 93% +/- 2% @ 90 +/- 3oF (32 +/- 2oC)

This device functions in an atmosphere of relative humidity up to 93 percent, non-condensing.

Dimensions 18.50”H X 14”W X 4.25”D

Mounting 0.25” Maximum screw diameter

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

68 of 90

Page 78: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Equipment list B

Appendix BEquipment List

This appendix lists models and supporting equipment of the FNM-2127 Panel.

FNM-2127 PanelThe following models are provided for the FNM-2127 Panel:

Loop Devices and AccessoriesThe following models are loop devices and accessories for use with the FNM-2127 Panel:

( 1 ) May not be used in "locations requiring an exceptional degree of protection" as defined in 46 CFR 110.15-1 to be a location exposed to weather, seas, splashing, pressure-directed liquids, or similar moisture conditions.

( 2 ) May be used in "locations requiring an exceptional degree of protection" as defined in 46 CFR 110.15-1 to be a location exposed to weather, seas, splashing, pressure-directed liquids, or similar moisture conditions.

Model Description

FNM-2127-R 2 Loop, No Communication, Loop Expansion, Red, Marine ( 1 )

FNM-2127-C 2 Loop, No Communication, Loop Expansion, Charcoal, Marine ( 1 )

Models Description

FNM-ALK-V Detector, Photoelectric, Smoke ( 2 )

FNM-ACA-V Detector, Photoelectric, Smoke and Heat, Multi-Criteria ( 2 )

FNM-NSA-4 Base, Analog, 4 Inch ( 2 )

FNM-NSA-6 Base, Analog, 6 Inch ( 2 )

FNM-AMS-KL-LP1M

FNM-FRCME-M Input Module, Single ( 2 )

FNM-DIMM Input Module, Dual ( 1 )

FNMN-FRCMA Input Module, Single ( 1 )

FNM-R2ML Relay Module, Dual ( 1 )

Pull Station Addressable Manual ( 2 )

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

69 of 90

Page 79: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Equipment list B

Replacement PartsThe following models are replacement parts for use with the FNM-2127 Panel:

Models Description

FNM-1127-SLC Loop Expansion Module

FNM-2127-BO Main Board Without Integrated Dialer

FNM-KEY Panel Key Lock Set

FNM-PBS Panel Bonding Strap

FNM-PGB Panel Grounding Block

FNM-STO Panel Standoff Kit

FNM-FUS Panel Main AC Input Fuse

FNM-TRIM-R Trim Ring for the FNM-2127 Panel, Red

FNM-TRIM-C Trim Ring for the FNM-2127 Panel, Charcoal

PS-12120 Standby-Battery, 12 Volt, 12 AH, Rechargeable SLA, Two Per Cabinet, PS12120 ( 1 )

FN-BLJ Battery Leads & Jumper

HA3529-0M FNM-2127 Panel Installation Manual

HA3534-0M FNM-2127 Panel Door Label

HA3535-0M Operating Instructions

S2028-6 Resistor Kit (6) 10K Ohm

S2028 EOL Resistor 10K

28B1020-100 Laird Ferrite

S2026 Resistor Kit (8) Zero Ohm

S2030 EOLD for Synchronization Module outputs only

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

70 of 90

Page 80: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Equipment list B

( 1 ) May not be used in "locations requiring an exceptional degree of protection" as defined in 46 CFR 110.15-1 to be a location exposed to weather, seas, splashing, pressure-directed liquids, or similar moisture conditions.

( 2 ) May be used in "locations requiring an exceptional degree of protection" as defined in 46 CFR 110.15-1 to be a location exposed to weather, seas, splashing, pressure-directed liquids, or similar moisture conditions.

Notification Appliances Notification Appliances furnished in this manual operate with the FNM-2127 Panel in a special application or regulated mode. The FNM-2127 Panel supports the simultaneous operation of regulated and special application outputs between NAC 1 and NAC 2.

The FNM-2127 Panel does not support the simultaneous operation of regulated and special application outputs on the same NAC channel.

The FNM-2127 Panel supports regulated and special application outputs when operating Gentex NAC devices without synchronization modules. Gentex synchronization protocol is provided by the FNM-2127 Panel. Synchronization modules are not required when operating Gentex NAC devices with Gentex synchronization protocol on NAC 1 or NAC 2 of the FNM-2127 Panel.

SynchronizationNAC channels 1 and 2 of the FNM-2127 Panel provide single and dual circuit synchronization. Single circuit synchronization provides synchronized NAC outputs on one channel of the FNM-2127 Panel. Dual circuit synchronization provides synchronized NAC outputs on two channels of the FNM-2127 Panel.

NAC synchronization can be performed on individual FNM-2127 Panels.

NAC synchronization cannot be performed on between multiple FNM-2127 Panels.

Models Description

FNM-LCD-S-R FNM-LCD-S Serial Annunciator (Repeater), Red ( 1 )

FNM-LCD-S-C FNM-LCD-S Serial Annunciator (Repeater), Charcoal ( 1 )

VF1173-40

HA3510-0M FNM-LCD-S Installation Manual, Annunciator (Repeater)

Fuse Assembly

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

71 of 90

Page 81: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Equipment list B

Configuring NAC OutputsSettings are provided in Loop Explorer for controlling NAC outputs of the FNM-2127 Panel. Selections are available in this utility for providing outputs with synchronization or various forms of constant power. Settings are also provided to allow the Alarm Silence button to operate on the fascia in various modes.

NAC channels of the FNM-2127 Panel can be configured as independent outputs as long as the same manufacturer types are used when operating synchronized outputs.

Strobe operations are disabled as default functions on the FNM-2127 Panel. Settings are available to enable the operation of sounders and strobes when operating NAC channels in the constant power mode.

Review the settings described below to configure each NAC output for operation:

Regulated NAC OutputsNAC outputs of the FNM-2127 Panel operate in a regulated mode when conforming to specific levels of continuous or pulsed DC. NAC outputs meet requirements for regulated levels when the output current does not exceed the constraints described below:

Regulated Continuous Output Current

Continuous DC currents cannot exceed 1.6 A from either NAC output when operating in a regulated output mode:

Regulated continuous DC output = 1.6 A NAC 1 + 1.6 A NAC 2 = 3.2 A total

Regulated Pulsed Output Current

Pulsed DC currents cannot exceed 900 mA from either NAC output when operating in a regulated output mode:

Regulated pulsed DC output = 900 mA NAC 1 + 900 mA NAC 2 = 1.8 A total

Reference Appendix A, Specifications for operating NAC outputs in the regulated mode.

Output Options General Alarm and Emergency are selected as default conditions. Alternative output options for this field include Auxiliary Output, Pre Alarm Output, Supervisory Alarm and Trouble Output. Do not select the General Alarm option if the NAC channel is to be controlled by cause and effect programming.

Strobe Strobe Output is not selected for operation as a default condition. Selecting this field allows the user to define which synchronization protocol to be used.

NAC Aux 24 DC When the Strobe option above is not selected, Off is selected as the default operating condition. Options for this output are continuous constant power, door holder continuous power and resettable constant power. Continuous constant power provides a voltage output identical to Aux 24 VDC. Door holder continuous power drops out during fire alarm conditions or when an AC fail event occurs. Resettable constant power drops out between four and five seconds after the reset of the control panel.

Alarm Silence Each NAC circuit is configurable in reaction to the Alarm Silence button on the fascia of the FNM-2127 Panel. Edit properties of the NAC channel in Loop Explorer. Select the box for Silencing if NAC silencing is required on this channel. If Internal Synchronization Protocols are in use, an option is also available to Silence the strobe.Failure to check the Strobe Silence box will cause horns to be silenced with continued operation of the strobe.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

72 of 90

Page 82: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Equipment list B

Special Application NAC OutputsNAC outputs of the FNM-2127 Panel operate in a special application mode when conforming to specific levels of continuous DC. Outputs meet these requirements when NAC currents do not exceed the 2.3 A of NAC 1 or NAC 2 with the combined current of NAC 1 and NAC 2 not to exceed 3.1 A.

Reference Appendix A, Specifications for operating NAC outputs in the special application mode.

Synchronization

The FNM-2127 Panel provides internal device synchronization between the outputs of NAC 1 and NAC 2 when operating NAC devices from Gentex.

External synchronization modules must not be used on the NAC outputs when operating in the special application mode.

NAC devices from Gentex do not require external synchronization modules when operating in the special application mode. The FNM-2127 Panel contains an internal synchronization feature that supports these NAC devices.

Hochiki America Multiple Listed Gentex NAC Devices

The following Hochiki America NAC modes are multiple-listed with Gentex and are compatible for use on the special application outputs of NAC 1 and NAC 2 when these outputs are configured for “Gentex” synchronization protocol:

Maximum Line ImpedanceReference Section 1-D, Notification Appliance Circuit (NAC) for calculations of maximum line impedance.

Compatible Device Models for Auxiliary 24V

Power connections of this device must be terminated at the 24 volt terminals of the 24V OUT or AUX 24V on the FNM-2127 Panel.

( 1 ) May not be used in "locations requiring an exceptional degree of protection" as defined in 46 CFR 110.15-1 to be a location exposed to weather, seas, splashing, pressure-directed liquids, or similar moisture conditions.

( 2 ) May be used in "locations requiring an exceptional degree of protection" as defined in 46 CFR 110.15-1 to be a location exposed to weather, seas, splashing, pressure-directed liquids, or similar moisture conditions.

Hochiki America Models

Description Gentex Models Gentex Part Numbers

WHEC24-75WR Sounder, Weather Proof, Horn/ Strobe, 24 VDC ( 2 )

WGEC24-75WR 904-1217-002

WHES24-75WR Sounder, Weather Proof, Strobe, 24 VDC ( 2 ) WGES24-75WR 904-1219-002

Hochiki America Model

Description

FNM-LCD-S-R FNM-LCD-S, Annunciator, Repeater, Remote Display, Red, Marine ( 1 )

FNM-LCD-S-C FNM-LCD-S, Annunciator, Repeater, Remote Display, Charcoal, Marine ( 1 )

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

73 of 90

Page 83: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Equipment list B

This page intentionally left blank.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

74 of 90

Page 84: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Calculations C

Appendix CCalculations

This section describes current-loading, the standby-battery rating and the NAC wiring length.

Current-Loading Current-loading of the FNM-2127 Panel is limited to the capacity of the 5.25 Amp power supply. FACP installers must determine the loading placed on the power supply and standby-batteries by adding the sumof device-loads to the no-load-alarm current of the FNM-2127 Panel. The result obtained from this calculation must be below 4 Amps of the 5.25 Amp power supply and within the 12 AH range of the standby-batteries so that the FNM-2127 Panel can operate.

The power supply of the FNM-2127 Panel is rated at 5.25 Amps where 1.25 Amps is reserved for charging the standby-batteries and 4 Amps is reserved for operating the control panel and external loads. The 5.25 Amp reserve of the 5.25 Amp power supply is the maximum current capacity of the FNM-2127 Panel. The control panel will not function properly if the operating constant of 4 Amps is exceeded.

Current limits are provided in Appendix A, “Specifications” for each of the circuit-connections on the FNM-2127 Panel. Installers must identify the current-draw of each device on the circuit-connection and then compare the sum of these device-currents with the current limit provided for each of the circuit-connections. The total of device-currents must be below the limits provided in Appendix A, “Specifications” for each circuit-connection.

The calculation of total-current-loading must include the sum of device-loads on each of the FNM-2127 Panel circuits.

Circuits to be included in this calculation for total-current-loading are:• Panel standby and alarm currents

• SLC Loops

• NAC Outputs

• 24V OUT

• AUX 24V

The current limits provided in Appendix A, “Specifications” are maximums for each of the circuit-connections on the FNM-2127 Panel. These levels are not intended to be summed together to determine the total-current available from the FNM-2127 Panel. Refer to these levels only when determining the limit of device-loading on each circuit.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

75 of 90

Page 85: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Calculations C

Example of Total Load Current

The following example demonstrates the process for determining the total load-current of the FNM-2127 Panel:

1 Identify the current-draw of each device on the circuit-connection.

2 Add the device-currents together in each circuit-connection.

3 Compare the sum of the device-currents with the current-limit of each circuit-connection to verify that the summed level is below the current-limit value.

4 Add the device-load-currents together that were obtained for each of the circuit-connections:

5 Add the Total Device Load to the no-load-alarm current of the FNM-2127 Panel to obtain the

Total-Load-Current.

Total Device Load + FNM-2127 Panel No-Load = Total-Load-Current

1.875 A + 200 mA = 2.075 A

6 Verify that the current level is below 4 Amps:

This example demonstrates that device-loading of the circuit does not exceed the 4 Amp capacity of the

FNM-2127 Panel, where 1.25 A of the 5.25 A power supply is reserved for battery charging.

5.25 A - 1.25 A = 4 Amp load capacity of the FNM-2127 Panel

Circuit-Connection Current Limit Device Load Current

SLC Loop 1 250 mA 150 mA

SLC Loop 2 250 mA 50 mA

24V OUT 360 mA 0

AUX 24V 360 mA 0

NAC Channel 1 Regulated Output

1.6 A continuous DC or 900 mA pulse DC

750 mA continuous DC

NAC Channel 2Special Application Output

Single NAC output 2.3 A continuous with combined NAC outputs not to exceed 3.1 A continuous

925 mA continuous DC

Total Device Load 1.875 A

Total Load Current: 2.075 A

2.075 A < 4 A

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

76 of 90

Page 86: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Calculations C

The Standby-Battery RatingThis section provides calculations for confirming that the 12 AH standby-battery rating is within the operating range of the FACP system.

Battery Rating Equation

The equation below describes the process for determining the Amp-Hour Rating of the standby-batteries:

To determine the battery Amp-Hour-Rating:

Complete the worksheets on the following pages to tabulate the total-current-load of the FACP system and to confirm that the minimum Amp-Hour-Rating for the standby-batteries is 12 AH.

1 Record standby and alarm currents of devices.

2 Record the standby and alarm currents of NAC Devices.

3 Record the standby and alarm currents of Auxiliary Devices.

4 Total the standby and alarm currents of SLC 1, SLC 2, NAC 1, NAC 2, AUX 24V and 24V OUT.

5 Calculate the Total Standby Amp Hours.

6 Calculate the Total Alarm Amp Hours.

7 Determine Total Amp-Hours by adding the Total Standby Amp Hours with the Total Alarm Amp Hours.

8 Determine the minimum Amp-Hour-Rating for the battery by multiplying the Total Amp-Hours with the Derating Factor (1.20).

9 Select a battery with a rating equal to or greater than the minimum Amp-Hour-Rating determined in step 8.

Battery Rating = ( Battery Derating Factor ) x [ ( Standby Amp Hours ) + ( Alarm Amp Hours ) ]

Or

Battery Rating = ( Battery Derating Factor ) x [ ( 24 Hours x Standby-Current ) + ( 5 Minutes x alarm current)]

Where the Battery Derating Factor = 1.2 and 5 minutes = 5 / 60 minutes = 1/12 = .0833 hours.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

77 of 90

Page 87: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Calculations C

Tabulating Data

Category Instruction Standby-Current Alarm-Current

1 Devices Enter the total standby and alarm current for Devices.

Amps Amps

2 NAC Devices Enter the total standby and alarm current for NAC Devices.

Amps Amps

3 Auxiliary Devices Enter the total standby and alarm current for Auxiliary Devices.

Amps Amps

4 Total Standby and Alarm Current

Total the Standby Current of steps 1, 2 and 3. Total the Alarm Current of steps 1, 2 and 3.

Amps Amps

5 Total Standby Time Enter a Total Standby Time of 24 or 60 hours.

Hours

6 Total Standby Amp-Hours Multiply the Total Standby Time of step 5 by the Total Standby Current of step 4.

AH

7 Total Alarm Time Enter a Total Alarm Time in hours, where 5 minutes = .083 hours and 15 minutes = .25 hours.

Hours

8 Total Alarm Amp Hours Multiply the Total Alarm Time in step 7 with the Total Alarm Current of step 4.

AH

9 Total Amp-Hours Add the Total Alarm Amp Hours of step 8 with the Total Standby Amp Hours of step 6.

AH

10 Derating factor The Derating Factor is 1.20. 1.20

11 Minimum Battery Amp-Hour Rating

Multiply the Derating Factor of step 10 (1.20) by the Total Amp-Hours of step 9. The Amp-Hour-Rating of the battery selected must be equal to or greater than the minimum Amp-Hour-Rating obtained in this step. Note: The maximum battery size is 12 AH.

AH

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

78 of 90

Page 88: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Calculations C

NAC Wiring LengthDetermine the maximum wire length that can safely operate Notification Appliances under worst case conditions.To determine the maximum wire length under worst case conditions:

Sample Lmax CalculationDetermine the maximum wire length (Lmax) for three Notification Appliances on NAC channel 1 where,• The manufacturer data sheet for the strobe indicates that the minimum operating-voltage (Vopmin) is 16 VDC.

• The manufacturer data sheet for the strobe indicates that the maximum current-draw (Istrobe) is 209mA DC.

• The circuit connection is provided with 18 AWG shielded-stranded copper-wire.

• The EOLD in the circuit is 10K Ohms.

To determine the maximum wire length (Lmax) of this circuit:

1 Identify the minimum operating-voltage (Vopmin) of Notification Appliances on the NAC channel.

2 Calculate the maximum current of the circuit (Imax).

3 Identify the wire-resistance-per-foot of the circuit (Rwire).

4 Calculate the maximum wire length (Lmax) of the circuit.

1 Identify the minimum operating-voltage (Vopmin) of the strobe from the manufacturer data sheet. From the manufacturer data sheet:

2 Calculate the total current of the parallel devices in the circuit (Itotal)where,

[ Itotal = Istrobe_1 + Istrobe_2 + Istrobe_3 + (Vopmin / EOLD) ]

= [ ( .209 + .209 + .209 + 16 / 10K ) ] A

= ( .627 + .0016 ) A

Vopmin = 16 VDC

Itotal = .6286 A

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

79 of 90

Page 89: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Calculations C

3 Identify the maximum resistance of the wire gage used in the circuit (Rwiremax) when using 18 AWG copper.An 18 AWG shielded-stranded copper-wire is 6.385 Ohms at 1000FT using the Resistance Table below:

4 The calculation for the minimum output voltage of the NAC is:

Voutmin = Vpanel X 85%

= 24 VDC X 85%

5 The calculation for voltage-drop across the length of the wire is:

Vdrop = Voutmin - Vopmin

= 20.4 VDC - 16 VDC

6 The calculation for maximum wire length of this circuit is:

Lmax = 1/2 ( Vdrop / Imax ) / Rwire

where,

= 1/2 [ ( 4.4 / .6286 ) / ( .006385 Ohms / FT ) ]

Gage Resistance / 1000Ft @ 68F Rwire

18 AWG 6.385 Ohms 0.006385 Ohms / FT

16 AWG 4.016 Ohms 0.004016 Ohms / FT

14 AWG 2.525 Ohms 0.002525 Ohms / FT

Voutmin = 20.4 VDC

Vdrop = 4.4 VDC

Lmax = 548 FT

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

80 of 90

Page 90: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Calculations C

The figure below illustrates an example circuit for determining maximum wire length where values are provided for minimum operating-voltage of the NAC channel output (Vopmin), maximum current of the circuit (Imax), wire-resistance-per-foot of the circuit (Rwire) and maximum current-draw of the strobe (Istrobe):

Figure C-1Example Circuit For Determining Maximum Wire Length

19 20 21 2215 16 17 18

NAC 1 NAC 2

+ -+ -SLC1 IN SLC1 OUT

+ -+ -

ZERO-OHM SHORTING-JUMPERS MUST BE USED ON UNUSED SLC LOOPS. SPECIFY P/N S2026

19 20 21 22 23 24 25 15 16 17 18

TROUBLE

NC C NO

NAC 1 NAC 2

+ -+ -SLC1 IN SLC1 OUT

+ -+ -

S202810KEOLR

Vopmin

Lmax = 548 FT

++++

.209 A

Istrobe

.209 A

Istrobe

.209 A

Istrobe

-

+

-

+

-

+

-

+

Voutmin MEASURED ACROSS TERMINALS OF NAC 1

EXAMPLE CIRCUIT IDENTIFIES WIRE LENGTH FOR TWO CONDUCTOR CABLE

SUPERVISED END-OF-LINE-RESISTOR, S2028

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

81 of 90

Page 91: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Calculations C

This page intentionally left blank.

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

82 of 90

Page 92: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Door Label - Appendix D

83 of 90

E E

Alar

mS

ilenc

eP

anel

S

ound

erS

ilenc

eLa

mp Test

Res

etFi

re D

rill

Pro

gram

ma

ble F

unct

ion

Ena

ble

Acc

ess

Re A

l-S

arm

ound

Fire

AC P

ower

On

Pre

-A

larm

On

Test

Mor

e E

vent

s

DG

isen

erab

lale

m

ent

Gen

eral

Tr

oubl

e

Pow

er T

roub

le

Sup

ervi

sory

NA

C

Trou

ble

Mo

re

Fire

Eve

nts

Mor

e E

vent

s

Ent

erEx

it

24V

OUT

AU

X 2

4V

+

- +

-

NC

C

N

O

TROU

BLE

NC

C

N

O

FIRE

NC

C

N

O

SUPE

RVISO

RYN

AC

1

NA

C2

+

-

+

-

NE

T O

UT

NE

T IN

+

- +

-

CO

MM

S

+

-

SLC

1 O

UT

SLC

1 IN

+

- +

-

Bat

ter

yC

onne

cti

on+

-

JP1

PCP

C /

Dia

ler

Res

etW

Oat

per

c athd

oged

Con

trast

Wat

Rec s

ehdo t g

SLC

2 O

UT

SLC

2 IN

+

- +

-

1

2

3

4?

1 2

3

4 5

6

7

8 9

10

11 1

2 13

14

1

5 1

6 17

18

1

9 2

0 21

22

23 2

4 25

26

27 2

8

29

30

31

32

33

34

35

36

37

38 3

9 40

41

PS

ilean

elnc

S

edou

nder

Del

ay

Act

ive

ACL

PO

N

W

E ER

Zero

-Ohm

Sho

rting

-Jum

pers

Mus

t B

e U

sed

On

Unu

sed

Loop

Te

rmin

als,

Spe

cify

P/N

S20

26.

2 6 2

7 28

29

30

31

3

2 3

3 34

35

3

6 37

38 3

9 40

41

E E

24V

OU

T A

UX

24V

N

AC 1

N

AC 2

+

- +

-+

-

+ -

+

- +

-S

LC1

IN S

LC1

OU

T

NC

C

NO TRO

UBL

E

+

- +

-NC

C

NO

FIR

E

NC

C

N

O

+

- +

-

SU

PE

RV

ISO

RY

N

ET

OU

T N

ET

IN

CO

MM

S

SLC

2 O

UT

SLC

2 IN

1

2

3

4

5

6

7

8

9

10

11 1

2 1

3 14

15

16

17 1

8

19 2

0 2

1 22

23

24 2

5

Neg

ativ

e B

atte

ry

Lead

, Bla

ck

Cab

le

Pos

itive

B

atte

ry

Lead

, Red

C

able

The

Term

inal

-Con

nect

or F

or

AC

Pow

er C

onta

ins

A G

roun

d C

onne

ctio

n To

The

Cab

inet

-W

all O

f The

FN

M-2

127

Pane

l. D

o N

ot R

emov

e Th

is C

onne

ctio

n W

hen

Inst

allin

g Fa

cilit

y G

roun

ding

. Con

nect

Fac

ility

G

roun

ding

To

The

Cab

inet

.

10 A

mp

Bat

tery

Fu

se+

Zone

2

Zone

3

Zone

1

Sta

ndby

Bat

terie

s A

re A

M

inim

um O

f 12

VD

C, 1

2 A

H A

nd R

echa

rgea

ble

SLA

Cab

le L

engt

h O

f Th

e C

lose

d-N

ippl

e C

ircui

t M

ust N

ot E

xcee

d 5

Feet

Fro

m T

he P

anel

To

The

Firs

t Sho

rt-C

ircui

t Iso

lato

r-Mod

ule

Bat

tery

2PS

-121

20

-

Bat

tery

1 PS

-121

20

Jum

per -

C

able

The

Ser

ies

Bat

tery

C

onne

ctio

n P

rovi

des

24 V

DC

A

t Th

e B

atte

ry

Con

nect

ion

Te

rmin

als.

AC

P

OW

ER

L

N

E

Bla

ck

Bat

tery

C

onne

ctio

n+

-

Bla

ckR

ed

Supe

rvis

ed E

nd-O

f-Lin

e-R

esis

tor,

10K

Ohm

S20

28

Req

uire

d O

n R

egul

ated

O

utpu

ts W

ithou

t Sy

nchr

oniz

atio

n M

odul

es A

nd

Spec

ial A

pplic

atio

n O

utpu

ts

Clo

sed

Nip

ple

Circ

uit C

onta

inin

g Tw

o Sh

ort

Circ

uit I

sola

tors

And

A S

enso

r. R

efer

ence

Cla

ss

A, S

tyle

7.

Inst

all C

ondu

it Fr

om T

he P

anel

To

The

Firs

t Sh

ort-C

ircui

t Iso

lato

r-Mod

ule

On

Loop

s C

onta

inin

g C

lose

d-N

ippl

e C

ircui

ts

Whi

te G

ree

n

A AG

ENC

Ygen

Lc

y Li

ISTs

t IiN

G

ng

Req R

EQU

Iuir R

emEM

ents

ENTS

INST

ALL

ATI

ON

R

EQU

IREM

ENTS

PATE

NT

PEN

DIN

GW

Wa A

Rr

n Ni IN

ngG

!

Wiri

ng D

iagr

am fo

r The

FN

M-2

127

Pane

l For

Indo

or D

ry U

se O

nly

Inst

alla

tion

Req

uire

men

ts

Ala

rm T

ime-

Lim

it

This

uni

t inc

lude

s an

opt

iona

l ala

rm v

erific

atio

n fe

atur

e th

at w

ill re

sultin

a d

elay

of t

he

syst

emal

arm

sig

nal f

rom

the

indi

cate

d ci

rcui

ts.

The

tota

ldel

ay ti

me

(con

trol p

lus

smok

e de

tect

ors)

sha

ll not

exc

eed

60 s

econ

ds. N

o ot

her

smok

e de

tect

or s

hall b

e co

nnec

ted

to th

ese

circ

uits

unle

ss a

ppro

ved

by th

e lo

cal a

utho

rity

havi

ng ju

risdi

ctio

n.* Z

ones

(s)_

____

____

____

____

____

____

____

___

*Whe

re a

larm

ver

ificat

ion

is u

sed

conf

irmat

ion

per

oid

shal

l be

a m

inim

um

of 6

0 se

cond

s.St

andb

y A

nd A

larm

C

urre

nt

Loop

s S

tand

by

Alar

m

Des

crip

tion

1 16

0 m

A @

12

0 VA

C

220

mA

@

120

VAC

Li

ne c

urre

nt

for

stan

dby

and

alar

m

whe

n ba

ttery

cu

rrent

is

less

than

30

mA.

20

0 m

A @

24

DC

22

0 m

A @

24

VD

C

Batte

ry c

urre

nt f

or

stan

dby

and

alar

m

whe

n a

pow

er

failu

re

cond

ition

occu

rs

on

the

AC li

ne.

2 20

0 m

A @

12

0 VA

C

250

mA

@

120

VAC

Li

ne c

urre

nt

for

stan

dby

and

alar

m

whe

n ba

ttery

cu

rrent

is

less

than

30

mA.

27

0 m

A @

24

DC

29

0 m

A @

24

VD

C

Batte

ry c

urre

nt f

or

stan

dby

and

alar

m

whe

n a

pow

er

failu

re

cond

ition

occu

rs

on

the

AC li

ne.

SLC

Lo

ops

Term

inal

C

onne

ctio

n R

atin

g

19

LOO

P 1

(+

IN)

32 V

DC

@ 2

50

mA

20

LOO

P 1

(-

IN)

32 V

DC

@ 2

50

mA

21

LOO

P 1

(+

OU

T)

32 V

DC

@ 2

50

mA

22

LOO

P 1

(-

OU

T)

32 V

DC

@ 2

50

mA

38

LOO

P 2

(+

OU

T)

32 V

DC

@ 2

50

mA

39

LOO

P 2

(-

OU

T)

32 V

DC

@ 2

50

mA

40

LOO

P 2

(+

IN)

32 V

DC

@ 2

50

mA

41

LOO

P 2

(-

IN)

32 V

DC

@ 2

50

mA

SLC

Dev

ice

Wiri

ng

Leng

thM

ust N

ot

Exce

ed:

5000

Fee

t For

14

AWG

3100

Fee

t For

16

AWG

1950

Fee

t For

18

AWG

All

Con

nect

ions

For

Fie

ld

Wiri

ng A

re 1

2 –

14 A

WG

All

Con

nect

ions

For

Bat

tery

A

nd P

ower

12

– 14

AW

G

Wire

G

age

Gro

und

Faul

t In

dica

tion

A G

roun

d Fa

ult I

ndic

atio

n O

ccur

s O

n M

odel

s O

f The

FN

M-2

127

Pane

l Whe

n A

Min

imum

OF

30K

Ohm

s Ex

ists

B

etw

een

Eart

h-G

roun

d A

nd

Eith

er D

C R

TN o

r+2

4 D

C O

f The

Pow

er-S

uppl

y.Po

wer

Lim

ited

Circ

uits

All

Circ

uits

Are

Pow

er

Lim

ited

Exce

pt A

C A

nd B

atte

ry

Inpu

ts

24V

OU

T an

d A

UX

24V

Term

inal

D

escr

iptio

n R

atin

g

11

24V

OU

T ( +

) 24

VD

C @

360

m

A 12

24

V O

UT

( - )

13

AUX

24V

( + )

24 V

DC

@ 3

60

mA

14

AUX

24V

( - )

Conn

ectio

ns a

t the

term

inal

s of

24V

OU

T an

d AU

X 24

V pr

ovid

e se

para

tely

fuse

d, re

gula

ted

outp

uts.

Alar

m T

ime-

Lim

it Cu

t-Out

Is

____

____

.

Pow

er

Supp

ly

Fuse

3A

, 250

VA

C, S

low

-Blo

w, 5

x

20m

m

Inpu

t (S

uper

vise

d)

120

or 2

40 V

AC

50/6

0Hz

Out

put

Volta

ge

24 V

DC

R

egul

ated

O

utpu

t C

urre

nt

0 - 4

AM

PS

Cha

rge

Cur

rent

Fa

st C

harg

e: 1

.25

A

Tric

kle

Cha

rge:

1.2

5 A

Volta

ge

Lim

ited

Bat

tery

-Typ

e Tw

o Se

ries

12 V

DC

SLA

Sta

ndby

Ba

tterie

s Tr

ansf

er

Volta

ge

120

VAC

Tra

nsfe

r @ 7

5 VA

C

240

VAC

Tra

nsfe

r @ 1

60

VAC

Labe

l Par

t Num

ber:

HA

3534

-0M

, Rev

isio

n E

03.0

0 D

ate:

05/

28/2

014

Rel

ay

Con

tact

s Pr

ogra

mm

abl

e Te

rmin

al

Relay

R

atin

g

23

TRO

UB

LE

(NC

) N

ot S

uper

vise

d

30VD

C @

1A

, 1P

F 24

TR

OU

BLE

(C

) N

ot

Supe

rvis

ed

25

TRO

UB

LE

(NO

) N

ot

Supe

rvis

ed

26

FIR

E 1

(NC

) N

ot

Supe

rvis

ed

30VD

C @

1A

, 1P

F 27

FI

RE

1 (C

) N

ot

Supe

rvis

ed

28

FIR

E 1

(NO

) N

ot

Supe

rvis

ed

29

SUPE

RVI

SOR

Y (N

C)

Not

Su

perv

ised

30

VDC

@ 1

A,

1PF

30

SUPE

RVI

SOR

Y (C

) N

ot

Supe

rvis

ed

31

SUPE

RVI

SOR

Y (N

O)

Not

Su

perv

ised

NET

Te

rmin

als

Term

inal

D

escr

iptio

n R

atin

g

32

NET

IN

( + )

Not U

sed

33

NE

T IN

( -

) 34

N

ET O

UT

( + )

Not

Use

d 35

N

ET O

UT

( - )

Wire

Le

ngth

AC

Lin

e C

onne

ctio

n Te

rmin

al

Des

crip

tion

Volta

ge

Curre

nt

L AC

Lin

e 11

0 to

120

VAC

@ 5

0/60

H

z 22

0 to

240

VAC

@ 5

0/60

H

z

2.1

A

1.1

A

N

AC N

eutra

l

E Ea

rth G

roun

d NA

C

Out

puts

Pr

ogra

mm

abl

e Te

rmin

al

Des

crip

tion

Rat

ing

15

NAC

1 ( +

) 24

VD

C R

egul

ated

@ 1

.6 A

Con

tinuo

us

DC

o

r

24 V

DC

Reg

ulat

ed @

900

mA

Pul

sed

DC

o

r 24

VD

C S

peci

al A

pplic

atio

n @

2.3

A

16

NAC

1 ( -

)

17

NAC

2 ( +

) 24

VD

C R

egul

ated

@ 1

.6 A

Con

tinuo

us

DC

o

r

24 V

DC

Reg

ulat

ed @

900

mA

Pul

sed

DC

o

r

24 V

DC

Spe

cial

App

licat

ion

@ 2

.3

A

18

NAC

2 ( -

)

RS4

85 S

eria

l B

us

Term

inal

D

escr

iptio

n R

atin

g

36

CO

MM

S (+

) ( +

) D

ata

3.3

VDC

@ 3

0 m

A 37

C

OM

MS

(-)

( - )

Dat

a 3.

3 VD

C @

30

mA

Inst

all m

odel

s of

the

FNM

-212

7 P

anel

in

Acc

orda

nce

with

the

FNM

-212

7 P

anel

In

stal

latio

n M

anua

l, H

A35

29-0

M, R

ev.

E03

.00.

NFP

A

The

FNM

-212

7 Pa

nel I

s Su

itabl

e As

Fo

llow

s:

Lo

cal S

igna

ling

Uni

t

Type

s O

f Sig

nalin

g Se

rvic

es A

re A

utom

atic

Fire

Al

arm

And

Man

ual F

ire A

larm

Styl

e 4,

6 o

r 7 F

or S

igna

ling

Line

C

ircui

ts

St

yle

Y Fo

r Not

ificat

ion

Appl

ianc

e C

ircui

ts

Pr

oprie

tary

(P) P

rote

cted

Pre

mis

es U

nit (

PPU

), R

emot

e St

atio

n (R

S)

Prot

ecte

d P

rem

ises

Uni

t (PP

U) A

nd C

entra

l Sta

tion

(CS)

Pro

tect

ed

Prem

ises

Uni

t (PP

U) P

rovi

de N

on-R

elea

sing

On

FNM

-212

7 M

odel

s

FCC

Th

is D

evic

e C

ompl

ies

With

Par

t 15

Of T

he F

CC

R

ules

. O

pera

tion

Is S

ubje

ct T

o Th

e Fo

llow

ing

Two

Con

ditio

ns:

(1)

This

Dev

ice

May

Not

Cau

se H

arm

ful

Inte

rfere

nce

And

(2

) Th

is D

evic

e M

ust A

ccep

t Any

Inte

rfere

nce

Rec

eive

d,

Incl

udin

g In

terfe

renc

e Th

at M

ay C

ause

Und

esire

d O

pera

tion.

Com

mun

icat

ion

Dev

ices

R

S485

D

evic

es

Mod

el

Num

ber

Annu

ncia

tor

FNM

-LC

D-S

-X

Net

wor

k In

terfa

ce

FNM

-N

IC

NA

C S

ynch

roni

zatio

n M

odul

es

Man

ufac

ture

r M

anuf

actu

rer

Mod

el

VES

Mod

el

Air P

rodu

cts

M

IB-S

DR

T-SM

/T

VF49

94-0

0

Gen

tex

Sy

nchr

oniz

atio

n Mod

ule

Not

R

equi

red

Sync

hron

izat

ion M

odul

e N

ot

Req

uire

d N

AC D

evic

es c

ompa

tible

with

the

sync

hron

izat

ion

mod

ules

abo

ve

are

com

patib

le fo

r ope

ratio

n w

ith th

e H

ochi

ki F

NM

-212

7 Pa

nel.

Gen

tex

sync

hron

izat

ion

prot

ocol

is p

rovi

ded

by th

e FN

M-2

127

Pane

l. Sy

nchr

oniz

atio

n m

odul

es a

re n

ot re

quire

d w

hen

oper

atin

g G

ente

x N

AC d

evic

es w

ithG

ente

x sy

nchr

oniz

atio

n pr

otoc

ol o

n N

AC1

or N

AC 2

of t

he F

NM

-212

7 Pa

nel.

NAC

out

puts

can

ope

rate

in re

gula

ted

or s

peci

al a

pplic

atio

n m

ode.

R

egul

ated

Mod

e D

o N

ot c

onne

ct N

AC d

evic

es a

nd s

ynch

roni

zatio

n m

odul

es fr

om d

iffer

ent m

anuf

actu

rers

. Ins

talla

tions

m

ust c

onta

in N

AC d

evic

es a

nd s

ynch

roni

zatio

n m

odul

es fr

om o

ne m

anuf

actu

rer.

Sync

hron

izat

ion

mod

ule

outp

uts

from

Air

Prod

ucts

requ

ire th

e us

e of

EO

LD S

2030

whe

n op

erat

ing

in re

gula

ted

mod

e. R

egul

ated

N

AC o

utpu

ts fr

om G

ente

x de

vice

s re

quire

the

use

of th

e 10

K O

hm E

OLR

, S20

28 w

hen

oper

atin

g w

ithou

t sy

nchr

oniz

atio

n m

odul

es.

Reg

ulat

ed c

ontin

uous

DC

out

put =

1.6

A N

AC 1

+ 1

.6 A

NAC

2 =

3.2

A T

otal

R

egul

ated

pul

sed

DC

out

put =

900

mA

NAC

1 +

900

mA

NAC

2 =

1.8

A

Tota

l Sp

ecia

l App

licat

ion

Mod

e C

onne

ct N

AC c

ircui

ts u

sing

dev

ices

from

eith

er G

ente

x or

Air

Prod

ucts

. Do

Not

con

nect

dev

ices

from

G

ente

x an

d Ai

r Pro

duct

s on

the

sam

e N

AC c

ircui

t. N

AC in

stal

latio

ns m

ust c

onta

in d

evic

es fr

om o

ne

man

ufac

ture

r. Th

is fi

re c

ontro

l pan

el p

rovi

des

NAC

syn

chro

niza

tion

whe

n op

erat

ing

in s

peci

al a

pplic

atio

n m

ode.

Syn

chro

niza

tion

mod

ules

mus

t not

be

used

on

NAC

out

puts

whe

n op

erat

ing

in th

e sp

ecia

l ap

plic

atio

n m

ode.

Spe

cial

app

licat

ion

NAC

out

puts

requ

ire th

e us

e of

the

10K

Ohm

EO

LR, S

2028

. Th

e m

axim

um ra

ted

spec

ial a

pplic

atio

n ou

tput

= 2

.3 A

NAC

1 O

R 2

.3 A

NAC

2 w

ith th

e co

mbi

ned

curre

nt

of N

AC 1

and

NAC

2 n

ot to

exc

eed

3.1

A.Sy

nchr

oniz

ed N

AC o

utpu

ts o

pera

te o

n in

divi

dual

con

trol p

anel

s on

ly. N

AC s

ynch

roni

zatio

n ca

nnot

be

perfo

rmed

bet

wee

n co

ntro

l pan

els.

Page 93: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Door Label - Appendix D

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

84 of 90

This page intentionally left blank.

Page 94: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Operating Instructions - Appendix E

Hochiki America FNM-2127 Panel Installation Manual

HA3529-0M, Revision E02.00

85 of 90

1

2

3

4?

Mo

re

Eve

nt

s

Mo

re

Fire

Ev

ents

En

ter

Exi

tF GA B C D E H I

Key

N

ame

Des

crip

tion

Ope

ratio

n A

R

e-So

und

Alar

m

Re-

soun

ds a

larm

of

cont

rol

pane

l aft

er th

e co

nditi

on is

si

lenc

ed b

y th

e Pa

nel

Soun

der

Sile

nce

butt

on. R

e-so

unds

N

AC

ala

rms

sile

nced

by

the

Ala

rm S

ilenc

e bu

tton.

1 Pr

ess

3 to

dis

play

“S

ET

ACCE

SS L

EVEL

2

MEN

U”.

2 Pr

ovid

e A

cces

s Le

vel 2

au

thor

izat

ion.

3

Pres

s En

ter

4

Pres

s th

e R

e-So

und

Ala

rm

butt

on.

B

A

larm

Si

lenc

e Si

lenc

es N

AC

s. A

lso

sile

nces

th

e bu

zzer

of t

he c

ontr

ol

pane

l du

ring

Fir

e D

rill

test

s,

trou

bles

an

d al

arm

s.

1 Pr

ess

3 to

dis

play

“S

ET

ACCE

SS L

EVEL

2

MEN

U”.

2 Pr

ovid

e A

cces

s Le

vel 2

au

thor

izat

ion.

3

Pres

s En

ter

4

Pres

s th

e A

larm

Si

lenc

e bu

tto

n.

C

Pan

el S

ound

er

Sile

nce

Mut

es th

e bu

zzer

of t

he

cont

rol

pane

l onl

y.

Pres

s th

e Pa

nel

Soun

der

Sile

nce

butt

on.

D

L

amp

Test

Te

sts

LEDs

of t

he

cont

rol

pane

l. A

lso

test

s th

e LC

D

disp

lay

and

the

inte

rnal

bu

zzer

.

Pres

s th

e La

mp

Test

bu

tton

to

illum

inat

e al

l LED

s, d

arke

n th

e fr

ont-

pane

l dis

play

and

so

und

the

buzz

er o

f the

con

trol

pa

nel.

E

Res

et

Res

ets

latc

hing

inpu

ts

such

as

fire

and

pre-

alar

m

even

ts.

1 Pr

ess

3 to

dis

play

“S

ET

ACCE

SS L

EVEL

2

MEN

U”.

2 Pr

ovid

e A

cces

s Le

vel 2

au

thor

izat

ion.

3

Pres

s En

ter

4

Pres

s th

e R

eset

bu

tton

. F

Fi

re D

rill

Prov

ides

a p

anel

Fire

D

rill.

Th

e Fi

re D

rill

butt

on c

an

also

be

con

figur

ed to

per

form

ot

her

func

tion

s.

1 Pr

ess

3 to

dis

play

“S

ET

ACCE

SS L

EVEL

2

MEN

U”.

2 Pr

ovid

e A

cces

s Le

vel 2

au

thor

izat

ion.

3

Pres

s En

ter.

4

Pres

s th

e Fi

re D

rill

butt

on.

To s

top

the

fire

drill

: 1

Pres

s 4

to d

ispl

ay

the “S

ET A

CCES

S LE

VEL

2 MEN

U”

. 2

Prov

ide

Acc

ess

Leve

l 2

auth

oriz

atio

n.

3 Pr

ess

Res

et o

r Fir

e D

rill.

G

P

rogr

amm

able

Fu

nctio

n Th

e Pr

ogra

mm

able

Fu

nctio

n bu

tton

can

be

conf

igur

ed to

pe

rfor

m o

ther

fu

nctio

ns.

Req

uire

s A

CC

ESS

LEVE

L 3

to

conf

igur

e th

e bu

tton

.

Fir

e AC P

ower

O

n

Pre

-A

larm

On

Te

st

Mor

e Ev

ents

Gen

eral

D

isab

lem

ent G

ener

al

Tro

ub

leP

ower

Tr

oubl

e

Su

per

viso

ry NA

C

Trou

ble

Pan

el

Sou

nd

er S

ilen

ced D

elay

A

ctiv

e

A B C D E F

G H I J K L

CO

NTA

CT:

N

AM

E: AD

DRES

S: C

ITY

: STA

TE: ZI

P:

TELE

PHO

NE:

THE

FOLL

OW

ING

CO

ND

ITIO

NS

OC

CU

R A

FTER

PR

ESSI

NG

TH

E “

PAN

EL S

OU

ND

ER S

ILEN

CE”

BU

TTO

N T

O S

ILEN

CE

A

TRO

UB

LE:

TH

E G

ENER

AL T

RO

UBL

E LE

D F

LASH

ES

YELL

OW

.

THE

POW

ER T

RO

UBL

E LE

D F

LASH

ES

YELL

OW

.

THE

INTE

RN

AL S

OU

ND

ER D

OES

NO

T AN

NU

NC

IATE

.TH

E LC

D D

ISPL

AY P

RO

VID

ES A

MES

SAG

E TO

ID

ENTI

FY T

HE

TRO

UB

LE C

ON

DIT

ION

. IN

STRU

CTIO

N PL

ACEM

ENT

FRAM

E TH

ESE

INST

RUCT

IONS

AND

PLA

CE T

HEM

ADJ

ACEN

T TO

THE

CO

NTRO

L UN

IT F

OR

READ

Y RE

FERE

NCE.

STA

ND

BY

BA

TTER

IES

AR

E SE

ALE

D-

REC

HA

RG

EAB

LE A

ND

PR

OVI

DE

FAC

P R

ECO

VER

Y IN

TH

E EV

ENT

OF

POW

ER

FAIL

UR

E. IN

SPEC

T ST

AN

DB

Y B

ATT

ERIE

S A

ND

CO

NN

ECTI

ON

S A

NN

UA

LLY.

REP

LAC

E ST

AN

DB

Y B

ATT

ERIE

S EV

ERY

3 TO

5 Y

EAR

S.

CO

NN

ECT

STA

ND

BY

BA

TTER

IES

IN S

ERIE

S.

DO

NO

T C

ON

NEC

T ST

AN

DB

Y B

ATT

ERIE

S IN

PA

RA

LLEL

.

Prog

ram

mab

leFu

ncti

on

Enab

le

Acce

ssAl

armSi

len

ce

Pan

el

Soun

der

Sile

nce

Lam

pTes t

Res

et

Fire

D

rill

Re-

Soun

dA

lar

m

AB

CD

EF

G

Key

LE

D

Col

or

LED

Li

t A

Fi

re

Red

A

n al

arm

or

fire

drill

con

ditio

n ex

ists

. The

sta

tus

cond

ition

is p

rovi

ded

on th

e LC

D d

ispl

ay.

Thec

ontr

ol p

anel

buz

zer

soun

ds

inte

rmitt

ently

. O

utpu

t rel

ays

are

activ

ated

.

Flas

hing

= N

AC

sa

ctiv

ated

O

n C

ontin

uous

= N

AC

s si

lenc

ed

OFF

= P

anel

and

NA

Cs

rese

t B

A

C P

ower

O

n G

reen

A

C p

ower

is

on.

C

Pre-

Ala

rm

Yello

w

A p

re-a

larm

con

ditio

n ex

ists

. Pr

e-al

arm

st

atus

is

prov

ided

on

theL

CD d

ispl

ay.

The

buzz

er

on

the

cont

rol

pane

l so

unds

co

ntin

uous

ly.

D

On

Test

Ye

llow

A

test

is in

pr

ogre

ss.

E

Pan

el

Sou

nder

Si

lenc

ed

Yello

w

The

Pane

l Sou

nder

Sile

nce

butt

on w

as

depr

esse

d. N

AC

out

puts

are

not

aff

ecte

d.

F

Del

ay

Act

ive

Yello

w

War

ning

sou

nder

s ha

ve b

een

dela

yed

duri

ng

a fir

e co

nditi

on.

Pres

s th

e A

larm

Sile

nce

butt

on

to m

ute

or e

xten

d th

e de

lay

to a

se

cond

sta

ge d

elay

. G

M

ore

Even

ts

Yello

w

A n

on-f

ire

alar

m e

vent

exi

sts

whi

ch

may

be

acce

ssed

by

the

'Mor

e Ev

ents

' bu

tton

sH

Po

int

Byp

asse

d Ye

llow

LC

D m

enu

optio

ns h

ave

been

use

d to

dis

able

de

vice

s.

I

Gen

eral

Tr

oubl

e Ye

llow

A

Gen

eral

Tro

uble

con

ditio

n ex

ists

whe

n fla

shin

g. T

he G

ener

al T

roub

le c

ondi

tion

is a

lso

iden

tifie

d by

oth

er li

t LED

s. S

tatu

s is

pro

vide

d on

th

e LC

D di

spla

y. T

he b

uzze

r on

the

cont

rol

pane

l sou

nds

cont

inuo

usly

. J

Po

wer

Tr

oubl

e Ye

llow

A

Pow

er T

roub

le e

xist

s. S

tatu

s is

pro

vide

d on

th

e LC

D d

ispl

ay. T

he b

uzze

r on

the

cont

rol

pane

l sou

nds

cont

inuo

usly

. K

Su

perv

isor

y A

larm

Ye

llow

St

atus

is p

rovi

ded

on th

e LC

D di

spla

y. T

he

buzz

er o

n th

e co

ntro

l pan

el s

ound

s co

ntin

uous

ly.

L

NA

C

Trou

ble

Yello

w

A N

AC

Tro

uble

exi

sts

on o

ne o

r bo

th o

f th

e N

AC

out

puts

. Con

nect

ions

at

this

loca

tion

are

faul

ty o

r dis

able

d.

RE

PLA

CIN

G T

HE

3 A

MP

PO

WE

R-

SU

PP

LY F

US

E

TO R

EMO

VE T

HE

FUSE

: 1

TU

RN

OFF

120

VA

C P

OW

ER

TO

TH

E C

ON

TRO

L P

AN

EL.

2

LO

CA

TE T

HE

3 A

MP

FU

SE

ON

TH

E M

AIN

CIR

CU

IT

BO

AR

D O

F TH

E C

ON

TRO

L PA

NEL

.

3

GEN

TLY

INSE

RT

A SM

ALL-

FLAT

-BLA

DE

SCR

EW D

RIV

ER

INTO

TH

E SL

OT

OF

THE

FUSE

-HO

USI

NG

.

4

SLID

E TH

E LE

NG

TH O

F TH

E SC

REW

DR

IVER

INTO

TH

E SL

OT

OF

THE

FUS

E-H

OU

SIN

G U

NTI

L TH

E U

PP

ER

-HA

LF

DIS

LOD

GE

S F

RO

M T

HE

LO

WER

-HAL

F O

F TH

E H

OU

SIN

G.

5

REM

OVE

TH

E FU

SE F

RO

M T

HE

UPP

ER-H

ALF

OF

THE

FUSE

-HO

USI

NG

.

TO IN

STA

LL T

HE

NEW

FU

SE:

1 IN

SE

RT

THE

FU

SE

IN T

HE

UP

PE

R-

HO

US

ING

. 2

CE

NTE

R T

HE

PO

SIT

ION

OF

THE

FU

SE

IN T

HE

UP

PE

R-

HO

US

ING

. 3

PRES

S TH

E U

PPER

-HO

USI

NG

ON

TH

E LO

WER

-HO

USI

NG

U

NTI

L TH

E H

ALVE

S SN

AP T

OG

ETH

ER.

4 R

ES

TOR

E 1

20 V

AC

PO

WE

R T

O T

HE

CO

NTR

OL

PA

NE

L.

5 C

HEC

K C

ON

TRO

L PA

NEL

OPE

RAT

ION

FO

LLO

WIN

G T

HIS

PR

OC

EDU

RE

TO C

ON

FIR

MTH

AT F

USE

REP

LAC

EMEN

T R

ESTO

RED

FU

NC

TIO

NAL

ITY.

Key

N

ame

Des

crip

tion

Ope

ratio

n A

1 N

avig

ates

men

u se

lect

ions

up

. Pr

ess

1 to

nav

igat

e m

enu

sele

ctio

ns u

p.

B

4

Nav

igat

es m

enu

sele

ctio

ns

left

. Pr

ess

4 to

nav

igat

e m

enu

sele

ctio

ns

left.

C

? Pr

ovid

es a

“he

lp s

cree

n” f

or

the

curr

ent m

enu

disp

lay

and

also

dis

play

s st

atus

.

Pres

s ?

to p

rovi

de s

tatu

s of

th

e c

ontr

ol p

anel

on

the

LCD

di

spla

y.

D

3

Nav

igat

es m

enu

sele

ctio

ns d

own.

Pr

ess

3 na

viga

te m

enu

sele

ctio

ns d

own.

E

2

Nav

igat

es m

enu

sele

ctio

ns ri

ght.

Pr

ess

2 to

nav

igat

e m

enu

sele

ctio

ns ri

ght.

F Ex

it C

ance

ls th

e cu

rren

t m

enu

sele

ctio

n an

d re

turn

s to

th

e

mai

n m

enu.

Pres

s Ex

it to

can

cel t

he c

urre

nt

men

u se

lect

ion

and

retu

rn to

the

mai

n m

enu.

G

Ente

r En

able

s th

e m

enu

sele

ctio

n.

Pres

s En

ter t

o en

able

the

men

u se

lect

ion.

H

Mor

e Fi

re E

vent

s D

ispl

ays

the

num

ber o

f al

arm

s pr

esen

t and

ove

rrid

es th

e di

spla

y pr

ovid

ed b

y m

enu

navi

gatio

n. P

rovi

des

even

t st

atus

forfi

res.

1 Pr

ess

the

Mor

e Fi

re E

vent

s bu

tton.

2

Rea

d ev

ent o

n LC

D.

3 Pr

ess

3 to

scr

oll t

hrou

gh

even

ts. 4

Pr

ess

2 to

dis

play

ev

ent.

5 Pr

ess

3 to

scr

oll t

hrou

gh

even

ts.

I M

ore

Even

ts

Dis

play

s th

e nu

mbe

r of e

vent

s an

d ov

errid

es m

enu

navi

gatio

n. P

rovi

des

even

t st

atus

forn

on-fi

re a

larm

ev

ents

.

1 Pr

ess

the

Mor

e Ev

ents

bu

tton.

2

Rea

d ev

ent o

n LC

D.

3 Pr

ess

3 to

scr

oll t

hrou

gh

even

ts. 4

Pr

ess

2 to

dis

play

ev

ent.

5 Pr

ess

3 to

scr

oll t

hrou

gh

even

ts.

REP

LAC

ING

TH

E 10

AM

P B

ATT

ERY

FUSE

TO

REM

OVE

TH

E FU

SE:

1 D

ISC

ON

NEC

T TH

E JU

MPE

R-C

ABLE

BET

WEE

N B

ATTE

RY

1 AN

D B

ATTE

RY

2.

2 D

ISC

ON

NEC

T TH

E R

ED-C

ABLE

FR

OM

TH

E PO

SITI

VE

TER

MIN

AL O

F BA

TTER

Y 2.

3 D

ISC

ON

NE

CT

THE

BLA

CK

-CA

BLE

FR

OM

TH

E N

EG

ATI

VE

TE

RM

INA

L O

F B

ATT

ER

Y 1

.

4 D

ISPO

SE T

HE

CAB

LES

DES

CR

IBED

IN T

HE

STEP

S AB

OVE

. 5

RE

MO

VE

B

ATT

ER

Y

1 A

ND

B

ATT

ER

Y

2 FR

OM

TH

E

BO

TTO

M

OF

THE

CAB

INET

AN

D

RE-

CYC

LE

THEM

AC

CO

RD

ING

TO

MAN

UFA

CTU

RER

GU

IDE

LIN

ES

.

TO IN

STA

LL T

HE

NEW

FU

SE:

1 M

OU

NT

THE

RE

PLA

CE

ME

NT

BA

TTE

RIE

S IN

TH

E

BA

SE

OF

THE

CO

NTR

OL

PAN

EL C

ABIN

ET.

2 C

ON

NEC

T TH

E R

EPLA

CEM

ENT

JUM

PER

-CAB

LE F

RO

M T

HE

NEG

ATIV

E TE

RM

INAL

OF

BATT

ERY

1 TO

TH

E PO

SITI

VE

TER

MIN

AL O

F B

ATT

ER

Y 2

.

3 C

ON

NEC

T TH

E BL

ACK-

WIR

E O

F TH

E R

EPLA

CEM

ENT

BATT

ERY-

CAB

LE T

O T

HE

NEG

ATIV

E TE

RM

INAL

OF

BATT

ERY

2.

4 C

ON

NE

CT

THE

RE

D-W

IRE

OF

THE

RE

PLA

CE

ME

NT

BA

TTE

RY

-CA

BLE

TO

TH

E P

OS

ITIV

E T

ER

MIN

AL

OF

BA

TTE

RY

1.

5 D

ETE

RM

INE

TH

AT

TRO

UB

LE C

ON

DIT

ION

S A

RE

NO

T R

EP

OR

TED

BY

TH

E C

ON

TRO

L PA

NEL

FO

LLO

WIN

G T

HE

FUSE

REP

LAC

EMEN

T. OPE

RA

TIN

G

CH

AR

AC

TER

ISTI

CS

N

OR

MA

L-ST

AN

DB

Y TH

E FO

LLO

WIN

G F

ORM

AT A

PPEA

RS O

N TH

E

FRO

NT-

PAN

EL-D

ISPL

AY

WH

EN O

PER

ATI

NG

WIT

HO

UT

TRO

UB

LES

OR

ALA

RMS:

TIME, DAY, DATE

DEFAULT OR USER DEFINED

MESSAGE

USE ARROW KEYS TO ENABLE

PANEL PRESS ? FOR

HELP

LED

In

dica

tors

C

ontr

ols

Mai

nten

ance

And

R

epai

r

Ope

ratin

g In

stru

ctio

ns F

or T

he F

NM

-212

7 Fi

re A

larm

C

ontr

ol P

anel

PA

TEN

T P

EN

DIN

G

IN T

HE E

VENT

OF

TRO

UBLE

Ref

eren

ce

Mat

eria

lTR

OU

BLE

-SI

LEN

CE

Inst

all T

his

Con

trol

Pan

el In

Acc

orda

nce

With

The

FN

M-2

127

Pane

l Ins

talla

tion

Man

ual,

HA

3539

-0M

, Rev

. E0

2.XX

Par

t Num

ber:

HA

3535

-0M

, Rev

isio

n E

02.02

DA

TE: M

ay 2

014

Ope

ratin

g In

stru

ctio

ns

Page 95: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Index

Index

Contacting HA for Repair 4 contamination status 51 Control Unit Board 63 Current Draw Worksheet 75

Ddaylight saving time 51Denotes a displayed variable 3Details of the fire activation 51Detector Sensitivity 28Detector Spacing 24Determining Battery Capacity 16device-loading 75Disable 49Disable Addresses 49Disable Loops 48Disable Panel I/O 49Disable Zones 48Disablements Menu 48Disables or enables NAC 1 49Disables or enables NAC 2 49Disables or enables the front panel Programmable Func-tion button 49Disables or enables the front-panel Fire Drill button 49disconnected-battery and low-battery indicators 55Displaying the Event Log 39Displays after a successful boot 32Displays the number of alarms present 10Displays the number of events present 10Document Conventions 3

Eelectrostatic discharge 16Enables the menu selection 10Enter 10EVENT LOG 36Event Log 39event log 36event log clear 36Events and Status 51Exit 10expansion boards 31

Numerics5.25 Amp Power Supply 13

AAccess Level 2 47Access Level 3 52Access Level 3 controls 47Activates inputs, outputs or actions 11additional requirements 25addressable device 25Alarm Silence 11Alarm Silence button 11anchor the empty cabinet 18Anchoring 18Audible Devices 29Automatic-retry 13Auxiliary 24 VDC 81

BBattery Cabinet 31battery disconnected 34Battery-backup 13Battery-boost 13battery-lead-kit 57before beginning the installation process 16

CCabling 67cancel disablements 50Cancels the current menu selection 10 circuit overloads 57Class A, Style 6 25Class A, Style 6 compliance 27Class B connections 28Class B, Style Y Notification Appliances 30 clearance beyond the door 17Clearing the Event Log 41Closed Nipple 25Closed Nipple devices 26closed-nippling 25common enclosure 25Compatible Devices for Auxiliary 24V 73 Configures the FNM-2127 Panel 32 Confirming a Successful Installation 32 Connect Class B loops 27Connecting 24VDC Devices 25 Connecting Batteries 31Connecting Class A Loops 31

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

86 of 90

Page 96: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Index

Ffield-programmable software 1Fire 31Fire Drill 11, 49Fire Event 51Fire warning NACs 51Fire Zone indicator 51front panel lamps 33Front-Panel MenuDisablements 48Events and Status 51Sensor Maintenance Early Warning 51Set System Time 51Test Zones 50Fuse failure 57

GGeneral Trouble indicator 51ground strap 16Ground straps 16

Hheart-beat 55help screen 10

Iif front panel lamps do not light 33If You Need Helptechnical assistance contact 4Indicates text displayed on a computer screen 3Initiate zone testing 50Input Delay Settings 24Inspecting Batteries 55InstallationBefore you begin 16Confirming a Successful Installation 32Connecting Class B Loops 27Connecting the Power Supply and Batteries 17Event Log 39Loop Data Test 43NFPA 72, Style 6 27NFPA 72, Style 7 25TEST ZONES 36Testing the Panel Lamps 33Wiring AC Power and TELCO 18Installation Procedures 25

installing audible and visual Notification Appliances 29Installing SLC Devices 24Installing the 10 Amp Battery-Fuse 57Installing the 3 Amp Power Supply Fuse 58Installing the Standby-Batteries 55Introduction 1

Kknockout tabs 18

LLamp Test 11lamp test button 33LCD status display 52Local NAC On – Off 50Logon 15, 47LOOP DATA TEST 36Loop Initialization 32Loop Outputs On – Off 50Low battery voltage 34low current auxiliary devices 31

Mmaintain and repair 55Maintenance 55Marking the Location 17maximum current draw 79maximum line loss 31maximum Pre-Alarm event delay 52maximum resistance 80maximum Trouble event delay 51maximum wire length 79minimum operating-voltage 79monitoring and reporting 7More Events 10More Fire Events 10Mounting Hardware 16mounting site 16Mutes the internal buzzer 11

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

87 of 90

Page 97: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Index

NNAC Circuit 1 49NAC Circuit 2 49NAC Trouble indicator 49navigate down to TEST ZONES 37Navigate the menu 47Navigates menu selections down 10Navigates menu selections to the left 10Navigates menu selections to the right 10Navigates menu selections up 10NFPA 72, Class A, Style 7 requirements 25non-latching inputs 11Non-latching inputs are cleared 11normally-open contact 31Normal-Standby 32Notification Appliance (NA) 29

OOperating Environment 68Overview 7Panel Controls and Indicators 8

Ppanel buzzer 51Panel Initialization 32Panel Outputs On – Off 50Panel Sounder Silence 11Part Numbers 3Appendix B 3Part numbersAppendix B 3Appendix D 3Physical Specifications 68Planning 16Points and addresses 7points per loop 7points per panel 7polarized and suppressed circuits 31Power-Supply 13power-supply fuse 57Pre-alarm Event 52Preparation 15, 47Preparing for Mounting 18Programmable 49Programmable Function 11protect SLC loop devices 25Provides a fire drill test 11

Qqualified personnel 16

Rraceways 25Re Sound Alarm 11red FIRE lamp 51Related Documentation 3Relay 31Relay Contacts 31Relay contacts 31removes the event log 41Removing Knockout Tabs 18Removing the 10 Amp Battery-Fuse 57Removing the 3 Amp Power Supply Fuse 58Removing the Door 60Removing the Standby-Batteries 55replacement standby-batteries 56Replacing Fuses 57Replacing Standby-Batteries 55Reset 11Reset button 11Resets latching inputs 11

SSelecting Standby-Batteries 17Sensor Maintenance Early Warning 51sets the panel date and time 51Short Circuit Isolator Modules 25Short-circuit protection 13Silence the sounder 35Silences NACs connected to the 11silencing operation 34single housings 25SLC 63SLC detectors 25SLC loop 25SLC loop installation 28Specifying Wire Size 25Standard for Control Units and Accessories for Fire Alarm Systems 1Status 13Sub-addresses 49sum of device-loads 75Supervisory 31

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

88 of 90

Page 98: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

89 of 90

Index

Ttermination jumpers 28test example 45Test Mode condition 50TEST ZONES 36Testing the Installation 18, 25Tests front panel indicators and the internal buzzer 11 Tests internal hardware and firmware 32Tests loop driven outputs 36Tests NACs of the FNM-2127 Panel 36Timed disabling 49To cancel disablements 50To complete the installation 15to comply with NFPA 72, Class A, Style 6 or Style 7 25 toggle disablements 50total-current 75Trouble 31trouble condition 34Trouble Event 51trouble signal 25, 27Troubleshooting 36Trouble-Silence Test 34

Uupper control pad 36used for emphasis 3Using This Manual 3

Vvariable that you must type 3View / Restore Disablements option 50View & Restore Disabled Features 50View Devices 50Visual Devices 29voltage reversing outputs 31

Wwire length maximums 64Writing styles 3

Zzero-ohm shorting-jumpers 25, 27

Page 99: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

Index

Hochiki America FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

90 of 90

This page intentionally left blank.

Page 100: FNM-2127 Panel Installation Manual - Hochiki America … · FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00 2 of 90 This manual describes 2 loop marine models of the

FNM-2127 Panel Installation Manual HA3529-0M, Revision E02.00

90