HYDRAULIC CALCULATION:
Al Maha Sofitel Hotel (B+GF+24)
HYDRAULIC CALCULATION:Building
: Al Maha Sofitel Hotel (B+G+24)Level
: 1st Basement FloorRoom
: Qtel RoomSystem
: FM 200 Fire Extinguishing System Protection and hydraulic calculations for Qtel Room is in accordance with NFPA 2001 (2004 Edition)
Amount of Clean Agent Required to Achieve Design ConcentrationW = (V / S) x (C / (100-C)) NFPA 2001, 5.5.1 Total Flooding Qty. Equation (3.1)Where:
W
= weight of clean agent, (kg)
V
= net volume of hazard, (m)
S
= specific volume of the superheated agent vapour at 1 atmosphere and the
temperature, T (m/kg)
C
= agent design concentration (volume percent)T
= minimum anticipated temperature of the protected volume (C)
Design Data:
Volume of Hazard
: 196m
Extinguishing Agent
: HFC-227ea
Design Concentration
: 7%
Design Temperature
: 20C
Specific Volume of the Superheated: 0.1376 m/kg (NFPA 2001, Table A.5.5.1(k)
Agent Vapour at Design Temp and 1 Atm. Thus:
W= (V / S) x (C / (100-C))
= (196 / 0.1376) x (7 / (100-7))
W= 107 kg Fire Fighting