FLOOR CEILING ASSEMBLY DIRECT FIX TO WOOD I JOIST F4543.03 STC 63 IIC 56 CONSTRUCTION Metroflor Commonwealth Commercial Luxury Resilient Tile Hacker Industries, Inc. Firm-Fill Gypsum Concrete Hacker Industries, Inc. Firm-Fill SCM-250 Sound Control Mat Oriented Strand Board Sheathing Johns Manville R-13 Fiberglass Insulation Weyerhaeuser TrusJoist 360 TJI Joist RSIC-1 Installed @ 24"x48" Clark Dietrich 087F125-18 Furring Channel @ 24" O.C. 2 Layers Type C Gypsum Panel STC 63 Test Number F4543.03 IIC 56 ©2016 PAC International, LLC. All Rights Reserved. • (866) 774-2100 • Fax (866) 649-2710 RSIC® is a registered Trade Mark of PAC International, LLC. STC IIC

FLOOR CEILING ASSEMBLY - PAC International RSIC-1... · Metroflor Commonwealth Commercial Luxury Resilient Tile Hacker Industries, Inc. Firm-Fill Gypsum Concrete Hacker Industries,

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: FLOOR CEILING ASSEMBLY - PAC International RSIC-1... · Metroflor Commonwealth Commercial Luxury Resilient Tile Hacker Industries, Inc. Firm-Fill Gypsum Concrete Hacker Industries,

FLOOR CEILING ASSEMBLY

DIRECT FIX TO WOOD I JOIST

F4543.03 STC 63 IIC 56

CONSTRUCTIONMetroflor Commonwealth Commercial Luxury Resilient TileHacker Industries, Inc. Firm-Fill Gypsum ConcreteHacker Industries, Inc. Firm-Fill SCM-250 Sound Control MatOriented Strand Board SheathingJohns Manville R-13 Fiberglass InsulationWeyerhaeuser TrusJoist 360 TJI JoistRSIC-1 Installed @ 24"x48"Clark Dietrich 087F125-18 Furring Channel @ 24" O.C.2 Layers Type C Gypsum Panel

STC 63Test Number F4543.03 IIC 56

©2016 PAC International, LLC. All Rights Reserved. • (866) 774-2100 • Fax (866) 649-2710RSIC® is a registered Trade Mark of PAC International, LLC.

STC

IIC

Page 2: FLOOR CEILING ASSEMBLY - PAC International RSIC-1... · Metroflor Commonwealth Commercial Luxury Resilient Tile Hacker Industries, Inc. Firm-Fill Gypsum Concrete Hacker Industries,

130 Derry Courtaa

York, PA 17406aa

p. 717.764.7700

f. 717.764.4129www.archtest.com · www.intertek.com/building

Ceiling Isolation: 28 mm PAC International RSIC-1 Classic Isolation Clips

Ceiling Isolation: 22.3 mm ClarkDietrich 087F125-18 Furring/Hat Channel

Ceiling: 15.9 mm Type C Gypsum Panel

Ceiling: 15.9 mm Type C Gypsum Panel

Reference should be made to Intertek-ATI Report F4543.03-113-11 for complete test specimen

description. This page alone is not a complete report.

Subfloor Topping: 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand Gypsum Concrete

Subfloor Underlayment: 6.4 mm Hacker Industries, Inc. FIRM-FILL® SCM-250 Sound Control Mat

Subfloor: 18.8 mm Oriented Strand Board Sheathing

Insulation: 88.9 mm Johns Manville R-13 Fiberglass Insulation

Joist: 301.63 mm Weyerhaeuser TrusJoist® 360 TJI Joist

Test Specimen Identification:

Floor Topping: 3 mm Metroflor® Commonwealth Commercial Luxury Resilient Tile

Specimen Type: Weyerhauser TJI Assembly - 302 mm

Overall Size: 3023 mm by 3632 mm

STC 63

IIC 56

Series/Model: FIRM-FILL® Brand Gypsum Concrete and FIRM-FILL® SCM-250

Sound Control Mat - Metroflor® Commonwealth Commercial Luxury Resilient Tile

F4543.03-113-11-R2

ACOUSTICAL PERFORMANCE TEST REPORT

ASTM E 90 AND ASTM E 492

Rendered to

HACKER INDUSTRIES INC.

Page 3: FLOOR CEILING ASSEMBLY - PAC International RSIC-1... · Metroflor Commonwealth Commercial Luxury Resilient Tile Hacker Industries, Inc. Firm-Fill Gypsum Concrete Hacker Industries,

130 Derry Courtaa

York, PA 17406aa

p. 717.764.7700

f. 717.764.4129www.archtest.com · www.intertek.com/building

ASTM E 989-06 (2012), Classification for Determination of Impact Insulation Class (IIC)

ASTM E 2235-04 (2012) Standard Test Method for Determination of Decay Rates for Use in

Sound Insulation Test Methods

Test Procedure

All testing was conducted in the VT test chambers at Intertek-ATI located in York,

Pennsylvania. The microphones were calibrated before conducting the tests.

The airborne transmission loss test was conducted in accordance with the ASTM E 90 test

method using the single direction method. Two background noise sound pressure level and five

sound absorption measurements were conducted at each of five microphone positions. Four

sound pressure level measurements were made simultaneously in both rooms, at each of five

microphone positions.

Test Methods

The acoustical tests were conducted in accordance with the following standards. The equipment

listed in the attachments meets the requirements of the following standards.

ASTM E 90-09, Standard Test Method for Laboratory Measurement of Airborne Sound

Transmission Loss of Building Partitions

ASTM E 413-10, Classification for Rating Sound Insulation

ASTM E 492-09, Standard Test Method for Laboratory Measurement of Impact Sound

Transmission Through Floor-Ceiling Assemblies Using the Tapping Machine

Report Date 03/03/16

Revision Date 04/29/16

Project Scope

Architectural Testing, Inc., a subsidiary of Intertek (Intertek-ATI), was contracted to conduct

airborne sound transmission loss and impact sound transmission tests. The complete test data is

included as attachments to this report. The client provided the test specimen. The specimen was

constructed on the date of testing.

Newport Beach, California 92660

Report F4543.03-113-11

Test Date 02/04/16

Page 1 of 5

Acoustical Performance Test Report

HACKER INDUSTRIES INC.

1600 Newport Center Drive, Suite 275

F4543.03-113-11-R2

Page 4: FLOOR CEILING ASSEMBLY - PAC International RSIC-1... · Metroflor Commonwealth Commercial Luxury Resilient Tile Hacker Industries, Inc. Firm-Fill Gypsum Concrete Hacker Industries,

TJI Joist57.2 by 3023 301.6 Weyerhaeuser TrusJoist® 360 21.2 lin m 4.46 kg/m

Note: Fastened to perimeter frame on 610 mm centers

2962 by 584 88.9 Johns Manville R-13 10.98 m² 1.25 kg/m²

Note: Laid directly over furring/hat channels.

Oriented Strand

Board Sheathing

1219 by 2438 18.8 N/A 10.98 m² 10.25 kg/m²

Note: Fastened to joists with 76 mm by 3 mm framing nails on 203 mm centers along perimeter and

305 mm centers in the field.

Fiberglass Insulation

Sound Control Mat1219 by 3023 6.4

Hacker Industries, Inc. FIRM-

FILL® SCM-25010.98 m² 0.49 kg/m²

Note: Installed per manufacturer's specifications with seams overlapping and taped

Gypsum Concrete3632 by 3023 25.4

Hacker Industries, Inc. FIRM-

FILL® Brand10.98 m² 48.82 kg/m²

Note: The gypsum concrete was allowed to cure for a minimum of 14 days. The gypsum layer had a

closed cell foam perimeter isolation. The product name was specified by client.

Luxury Resilient

Tile

457.2 by 457.2 3.0Metroflor® Commonwealth

Commercial10.98 m² 5.22 kg/m²

Note: Adhered to the subfloor topping with Mannington MT-711 Pressure Sensitive Adhesive.

Adhesive was spread with a 1.6 mm U-notch trowl and allowed to cure to the manufacturer's

specifications.

Test Specimen Materials and Installation Details

MaterialDimensions

(mm)

Thickness

(mm)Manufacturer and Series Quantity

Average

Weight

Average Relative Humidity 51% Average Relative Humidity 68%

Test Calculations

The STC (Sound Transmission Class) and IIC (Impact Insulation Class) ratings were calculated

in accordance with ASTM E 413 and ASTM E 989, respectively.

Test Conditions

Source Room Receive Room

Average Temperature 24°C Average Temperature 17.3°C

Page 2 of 5

Test Procedure (Continued)

The impact sound transmission test was conducted in accordance with the ASTM E 492 test

method. Two background noise sound pressure level, two sound pressure level measurements

with the tapping machine operating at each position specified by ASTM E 492, and five sound

absorption measurements were conducted at each of five microphone positions.

The air temperature and relative humidity conditions were monitored and recorded during all

measurements.

F4543.03-113-11-R2

Page 5: FLOOR CEILING ASSEMBLY - PAC International RSIC-1... · Metroflor Commonwealth Commercial Luxury Resilient Tile Hacker Industries, Inc. Firm-Fill Gypsum Concrete Hacker Industries,

Comments

The total weight of the floor/ceiling assembly was 1096.3 kg. Intertek-ATI will store samples

of the test specimen for four years. A photograph of the test specimen is included in the

attachments. A drawing of the test specimen is included in the attachments.

Gypsum Panel1219 by 3023 15.9 Type C 10.98 m² 11.9 kg/m²

Note: Fastened to the furring channels on 305 mm centers with 41.3 mm Type S bugle head screws.

Seams and perimeter sealed with Pecora AC-20 FTR Acoustical Sealant.

Gypsum Panel1219 by 3023 15.9 Type C 10.98 m² 11.9 kg/m²

Note: Fastened to the furring channels on 305 mm centers with 25.4 mm Type S bugle head screws.

Furring/Hat Channel3658 by 76.2 22.3 ClarkDietrich 087F125-18 29.1 lin m 0.48 kg/m

Note: Installed into the PAC International RSIC-1 Classic, spaced 610 mm on center.

Isolation Clips76.9 by 35.6 28.0 PAC International RSIC-1 Classic 24 clips 0.06 kg/clip

Note: Fastened to joists in a 610 mm by 1220 mm traditional pattern.

F4543.03-113-11-R2

Page 3 of 5

Test Specimen Materials and Installation Details (Continued)

MaterialDimensions

(mm)

Thickness

(mm)Manufacturer and Series Quantity

Average

Weight

Page 6: FLOOR CEILING ASSEMBLY - PAC International RSIC-1... · Metroflor Commonwealth Commercial Luxury Resilient Tile Hacker Industries, Inc. Firm-Fill Gypsum Concrete Hacker Industries,

Technician II - Acoustical Testing Project Manager - Acoustical Testing

Attachments (7 Pages): This report is complete only when all attachments are included.

* Stated by Client/Manufacturer

N/A - Non Applicable

Intertek-ATI will service this report for the entire test record retention period. Test records,

such as detailed drawings, datasheets, representative samples of test specimens, or other

pertinent project documentation, will be retained by Intertek-ATI for the entire test record

retention period. The test record retention period ends four years after the test date.

This report does not constitute certification of this product nor an opinion or endorsement by

this laboratory. It is the exclusive property of the client so named herein and relates only to the

specimen tested. This report is intended to help in the client’s quality assurance program, but it

does not represent a continuous or exhaustive evaluation of the specimen tested or of other

products or materials that were not evaluated. The statements and data provided herein do not

constitute approval, disapproval, certification, or acceptance of performance or materials.

This report may not be reproduced, except in full, without the written approval of

Intertek-ATI.

FOR INTERTEK-ATI:

David M. Dacheux Jordan Strybos

F4543.03-113-11-R2

Page 4 of 5

Page 7: FLOOR CEILING ASSEMBLY - PAC International RSIC-1... · Metroflor Commonwealth Commercial Luxury Resilient Tile Hacker Industries, Inc. Firm-Fill Gypsum Concrete Hacker Industries,

This report produced from controlled document template ATI 00629(d), Revised 02/09/15.

R2 04/29/16 Page 3 Clip spacing installation note corrected

R0 03/03/16 N/A Original Report Issue

R1 03/10/16 All pagesJob extension number changed per

client's request

F4543.03-113-11-R2

Page 5 of 5

Revision Log

Revision Date Page(s) Description

Page 8: FLOOR CEILING ASSEMBLY - PAC International RSIC-1... · Metroflor Commonwealth Commercial Luxury Resilient Tile Hacker Industries, Inc. Firm-Fill Gypsum Concrete Hacker Industries,

Test Chambers

VT Receive Room Volume 157.31 m³

VT Source Room Volume 190 m³

Page 1 of 7

Tapping Machine Look Line s.r.l. EM50 (TM50) 65351 11/15

* The calibration frequency for this equipment is every two years per the manufacturer's recommendation.

Source Room Microphone Scantek 378B20 63741 04/15

Source Room Environmental

IndicatorComet T7510 63812 11/15

Source Room Microphone PCB Piezotronics 378B20 63740 04/15

Source Room Microphone PCB Piezotronics 378B20 63742 04/15

Source Room Microphone PCB Piezotronics 378B20 63738 04/15

Source Room Microphone PCB Piezotronics 378B20 63739 04/15

Receive Room Environmental

IndicatorComet T7510

63810

63811

10/15

10/15

Receive Room Microphone PCB Piezotronics 378B20 63746 05/15

Receive Room Microphone PCB Piezotronics 378B20 63747 05/15

Receive Room Microphone PCB Piezotronics 378B20 63744 05/15

Receive Room Microphone PCB Piezotronics 378B20 63745 05/15

Microphone Calibrator Norsonic 1251 Y002919 07/15

Receive Room Microphone Scantek 378B20 63748 05/15

Data Acquisition Unit National Instruments PXI-1033 63763 06/14 *

F4543.03-113-11-R2

Attachments

Instrumentation

Instrument Manufacturer Model ATI NumberDate of

Calibration

Page 9: FLOOR CEILING ASSEMBLY - PAC International RSIC-1... · Metroflor Commonwealth Commercial Luxury Resilient Tile Hacker Industries, Inc. Firm-Fill Gypsum Concrete Hacker Industries,

STC Rating (Sound Transmission Class)

Deficiencies (Sum of Deficiencies)

Notes: 1) Receive Room levels less than 5 dB above the Background levels are highlighted in yellow.

2) Specimen TL levels listed in red indicate the lower limit of the transmission loss.

3) Specimen TL levels listed in green indicate that there has been a filler wall correction applied

ATI 00614 Revised 02/09/15 Page 2 of 7

25

63

0.70 -

10000 11.0 30.8 92 10 79 0.40 -

8000 11.2 24.8 97 14 81

0.50 -

6300 9.8 18.3 98 18 78 0.70 -

5000 8.7 14.3 104 28 75

0.40 0

4000 9.4 12.2 104 31 73 0.40 0

3150 9.1 10.3 103 33 72

0.30 0

2500 10.0 9.6 102 35 69 0.30 0

2000 13.6 8.6 104 37 69

0.50 0

1600 20.0 7.8 104 38 69 0.40 0

1250 24.0 7.8 104 40 67

0.50 1

1000 24.6 7.7 104 44 64 0.40 2

800 23.9 7.8 105 44 64

0.30 1

630 24.7 7.9 106 44 65 0.50 0

500 26.6 8.1 104 45 62

0.60 4

400 22.1 8.5 104 48 59 0.50 3

315 24.0 10.4 106 52 55

1.20 3

250 27.5 11.4 104 52 53 1.00 3

200 25.5 10.4 105 57 50

1.10 3

160 30.2 8.2 108 65 45 2.00 5

125 35.9 9.7 106 64 44

4.40 -

100 40.2 11.9 106 66 41 1.90 -

80 55.6 17.2 108 67 41

-

63 48.3 25.8 101 61 38 3.20 -

(dB) Limit Deficiencies

50 51.0 24.5 101 64 35 4.80

SPL SPL SPL Confidence of

(Hz) (dB) (m²) (dB) (dB)

Technician David M. Dacheux

FreqBackground

AbsorptionSource Receive Specimen

TL

95% Number

Client Hacker Industries Inc.

Description 3 mm Metroflor® Commonwealth Commercial Luxury Resilient Tile, 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand Gypsum

Concrete, 6.4 mm Hacker Industries, Inc. FIRM-FILL® SCM-250 Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9

mm Johns Manville R-13 Fiberglass Insulation, 301.63 mm Weyerhaeuser TrusJoist® 360 TJI Joist, 28 mm PAC International RSIC-1

Classic Isolation Clips, 22.3 mm ClarkDietrich 087F125-18 Furring/Hat Channel, 15.9 mm Type C Gypsum Panel, 15.9 mm Type C

Gypsum Panel

Specimen Area 10.98 m²

F4543.03-113-11-R2

AIRBORNE SOUND TRANSMISSION LOSS

ASTM E 90

Test Date 02/04/16

Data File No. F4543.03

Page 10: FLOOR CEILING ASSEMBLY - PAC International RSIC-1... · Metroflor Commonwealth Commercial Luxury Resilient Tile Hacker Industries, Inc. Firm-Fill Gypsum Concrete Hacker Industries,

Specimen Area 10.98 m²

Technician David M. Dacheux

ATI 00614 Revised 02/09/15 Page 3 of 7

Data File No. F4543.03

Client Hacker Industries Inc.

Description 3 mm Metroflor® Commonwealth Commercial Luxury Resilient Tile, 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand Gypsum

Concrete, 6.4 mm Hacker Industries, Inc. FIRM-FILL® SCM-250 Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9

mm Johns Manville R-13 Fiberglass Insulation, 301.63 mm Weyerhaeuser TrusJoist® 360 TJI Joist, 28 mm PAC International RSIC-1

Classic Isolation Clips, 22.3 mm ClarkDietrich 087F125-18 Furring/Hat Channel, 15.9 mm Type C Gypsum Panel, 15.9 mm Type C

Gypsum Panel

F4543.03-113-11-R2

AIRBORNE SOUND TRANSMISSION LOSS

ASTM E 90

Test Date 02/04/16

0

10

20

30

40

50

60

70

80

90

100

63

125

250

500

100

0

200

0

400

0

800

0

Sou

nd

Tra

nsm

issi

on

Loss

(d

B)

Frequency (Hz)

Airborne Sound Transmission Loss

Specimen TL

Contour Curve

Page 11: FLOOR CEILING ASSEMBLY - PAC International RSIC-1... · Metroflor Commonwealth Commercial Luxury Resilient Tile Hacker Industries, Inc. Firm-Fill Gypsum Concrete Hacker Industries,

IIC Rating (Impact Insulation Class)

Deficiencies (Sum of Deficiencies)

56

28

Note: Receive Room levels less than 5 dB above the Background levels are highlighted in yellow.

ATI 00615 Revised 02/09/15 Page 4 of 7

10000 7.3 31.4 13 0.3 -

8000 7.7 24.9 14 0.5 -

6300 8.0 18.3 17 0.9 -

5000 7.0 14.5 24 0.7 -

4000 10.7 12.1 27 0.8 -

3150 6.3 10.3 31 0.3 0

2500 7.6 9.6 38 0.4 0

2000 12.8 8.6 43 0.4 1

1600 19.0 7.8 46 0.2 1

1250 21.0 7.8 52 0.3 4

1000 20.4 7.7 56 0.3 5

800 20.7 7.7 59 0.3 7

630 20.7 8.0 56 0.5 3

500 21.2 8.0 54 0.2 0

400 18.9 8.6 53 0.9 0

315 21.5 10.6 53 1.5 0

250 26.9 11.3 53 0.8 0

200 23.8 10.1 53 0.6 0

160 28.2 8.8 59 1.1 3

125 33.0 10.1 58 2.1 2

100 39.4 12.3 58 2.0 2

80 48.0 19.0 59 2.4 -

63 44.8 29.8 63 3.3 -

50 48.8 25.8 67 4.0 -

(Hz) (dB) (m²) (dB) Limit Deficiencies

Technician David M. Dacheux

Freq Background SPL AbsorptionNormalized Impact

SPL

95% Number

Confidence of

Client Hacker Industries Inc.

Description 3 mm Metroflor® Commonwealth Commercial Luxury Resilient Tile, 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand Gypsum

Concrete, 6.4 mm Hacker Industries, Inc. FIRM-FILL® SCM-250 Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9

mm Johns Manville R-13 Fiberglass Insulation, 301.63 mm Weyerhaeuser TrusJoist® 360 TJI Joist, 28 mm PAC International RSIC-1

Classic Isolation Clips, 22.3 mm ClarkDietrich 087F125-18 Furring/Hat Channel, 15.9 mm Type C Gypsum Panel, 15.9 mm Type C

Gypsum Panel

Specimen Area 10.98 m²

F4543.03-113-11-R2

IMPACT SOUND TRANSMISSION

ASTM E 492

Test Date 02/04/16

Data File No. F4543.03

Page 12: FLOOR CEILING ASSEMBLY - PAC International RSIC-1... · Metroflor Commonwealth Commercial Luxury Resilient Tile Hacker Industries, Inc. Firm-Fill Gypsum Concrete Hacker Industries,

Technician David M. Dacheux

ATI 00615 Revised 02/09/15 Page 5 of 7

Client Hacker Industries Inc.

Description 3 mm Metroflor® Commonwealth Commercial Luxury Resilient Tile, 25.4 mm Hacker Industries, Inc. FIRM-FILL® Brand Gypsum

Concrete, 6.4 mm Hacker Industries, Inc. FIRM-FILL® SCM-250 Sound Control Mat, 18.8 mm Oriented Strand Board Sheathing, 88.9

mm Johns Manville R-13 Fiberglass Insulation, 301.63 mm Weyerhaeuser TrusJoist® 360 TJI Joist, 28 mm PAC International RSIC-1

Classic Isolation Clips, 22.3 mm ClarkDietrich 087F125-18 Furring/Hat Channel, 15.9 mm Type C Gypsum Panel, 15.9 mm Type C

Gypsum Panel

Specimen Area 10.98 m²

F4543.03-113-11-R2

IMPACT SOUND TRANSMISSION

ASTM E 492

Test Date 02/04/16

Data File No. F4543.03

10

20

30

40

50

60

70

80

90

100

1100

10

20

30

40

50

60

70

80

90

100

63

125

250

500

100

0

200

0

400

0

800

0

Imp

act

In

sula

tion

Cla

ss (

IIC

)

So

un

d P

ress

ure

Lev

el (

dB

)

Frequency (Hz)

Impact Sound Transmission

Normalized Impact SPL

Contour Curve

Page 13: FLOOR CEILING ASSEMBLY - PAC International RSIC-1... · Metroflor Commonwealth Commercial Luxury Resilient Tile Hacker Industries, Inc. Firm-Fill Gypsum Concrete Hacker Industries,

Page 6 of 7

Close-Up of Test Specimen

F4543.03-113-11-R2

Photograph

Page 14: FLOOR CEILING ASSEMBLY - PAC International RSIC-1... · Metroflor Commonwealth Commercial Luxury Resilient Tile Hacker Industries, Inc. Firm-Fill Gypsum Concrete Hacker Industries,

Page 7 of 7

5-Insulation

6-Joist

7-Ceiling Isolation

8-Ceiling

1-Floor Topping

2-Subfloor Topping

3-Subfloor Underlayment

4-Subfloor

Drawing

F4543.03-113-11-R2