22
cculation and chlorination process cont Jar test and Chlorine demand test

Flocculation and chlorination process control Jar test and Chlorine demand test

Embed Size (px)

Citation preview

Page 1: Flocculation and chlorination process control Jar test and Chlorine demand test

Flocculation and chlorination process controlJar test and Chlorine demand test

Page 2: Flocculation and chlorination process control Jar test and Chlorine demand test

Flocculation and chlorination controlWATSAN M15 ERUWATSAN M15 ERU 2

Contents

1. Chemicals and preparation of solutions

2. Flocculation control: Jar test

3. Chlorination control: Chlorine demand test

4. Jar test practical procedure

Page 3: Flocculation and chlorination process control Jar test and Chlorine demand test

Flocculation and chlorination controlWATSAN M15 ERUWATSAN M15 ERU 3

1.Chemicals and preparation of solutions

Page 4: Flocculation and chlorination process control Jar test and Chlorine demand test

Flocculation and chlorination controlWATSAN M15 ERUWATSAN M15 ERU 4

Aluminium Sulphate mother solution

1 % = 10 g Aluminium Sulphate / litre clean water = 10.000 mg/litre

Dissolve 10 g. in a small volume of water and pour the solution into 1 litre of clean water.

If a scale is not available, prepare the mother solution by using a “spoon” as a

measurement unit ≈ 1 spoon / litre clean water

Chlorine mother solution (Using Calcium Hypochlorite HTH 70%)

1 % chlorine = 14 g HTH/litre clean water = 10.000 mg Cl2/litre

1. Chemicals and preparation of solutions1. Chemicals and preparation of solutions

Page 5: Flocculation and chlorination process control Jar test and Chlorine demand test

Flocculation and chlorination controlWATSAN M15 ERUWATSAN M15 ERU 5

2. Flocculation control: Jar test

Page 6: Flocculation and chlorination process control Jar test and Chlorine demand test

Flocculation and chlorination controlWATSAN M15 ERUWATSAN M15 ERU 6

2. Flocculation control. Jar test2. Flocculation control. Jar test

Laboratory

Page 7: Flocculation and chlorination process control Jar test and Chlorine demand test

Flocculation and chlorination controlWATSAN M15 ERUWATSAN M15 ERU 7

Process• Material: 6 bottles/jars with 1 litre of raw water each

1 jar with mother solution (MS) Turbidity meter (final turbidity < 5 NTU)

Syringe to measure volumes Watch

Wand

• Add MS (2 ml, 4 ml, 6 ml, 8 ml, 10 ml, 12 ml) in the raw water bottles• Stir for about 10 min. and leave the solution to settle for 30 min.• Choose the right jar

Dosage calculation for a 30.000 litre tank of raw water

Example: [6 ml (MS) (1 %) / 1000 ml] x [10 g Al /1litre (MS)] x 30.000 litres = 1.800 g Al [6 ml (MS) /1000 ml] x [1spoon /1litre (MS)] x 30.000 litres = 180 spoons Al

Dosage implementation (manually or with dosage pumps)

2. Flocculation control. Jar test2. Flocculation control. Jar test

Page 8: Flocculation and chlorination process control Jar test and Chlorine demand test

Flocculation and chlorination controlWATSAN M15 ERUWATSAN M15 ERU 8

2. Flocculation control. Jar test2. Flocculation control. Jar test

Watch out for choosing the right dosage. Aluminium excess.

Page 9: Flocculation and chlorination process control Jar test and Chlorine demand test

Flocculation and chlorination controlWATSAN M15 ERUWATSAN M15 ERU 9

3. Chlorination control: Chlorine demand control

Page 10: Flocculation and chlorination process control Jar test and Chlorine demand test

Flocculation and chlorination controlWATSAN M15 ERUWATSAN M15 ERU 10

Process• Material: 6 marked buckets with 10 litres of clean raw water (flocculated)

1 jar with mother solution (MS) Chlorine tester (Final optimum chlorine = 0,5 mg /l aprox.)

Syringe to measure volumes Watch

• Add MS (1,0 ml, 1,5 ml, 2,0 ml, 2,5 ml, 3,0 ml and 4,0 ml) in the raw water buckets• Stir for about 10 min. and leave the solution to settle for 30 min.• Choose the right bucket

Dosage calculation for a 30.000 litre tank of raw water

Example: [2,0 ml (MS) (1 %) /10.000 ml] x [14 g Cl2 /1litre (MS)] x 30.000 litres = 284 g Cl2

Dosage implementation (manually or with dosage pumps) Handle with caution

3. Chlorination control. Chlorine demand test3. Chlorination control. Chlorine demand test

Page 11: Flocculation and chlorination process control Jar test and Chlorine demand test

Flocculation and chlorination controlWATSAN M15 ERUWATSAN M15 ERU 11

4. Jar test practical procedure

Page 12: Flocculation and chlorination process control Jar test and Chlorine demand test

Flocculation and chlorination controlWATSAN M15 ERUWATSAN M15 ERU 12

4. Jar test practical procedure4. Jar test practical procedure

1. Aim

To establish the quantity of Aluminium Sulphate needed to decrease the turbidity of a certain volume of raw water bellow a given value, generally 5 NTU.

2. Applications - Mass water treatment. - Pretreatmet of raw water with high turbidity (specialized water).

3. Importance High turbidity implies an increase in chlorine consumption in the treatment process. It also leads to more frequent maintenance, particularly filters, to shorter lifespan of equipment and to upsetting taste and appearance for consumers.

Excess of aluminium is toxic.

Page 13: Flocculation and chlorination process control Jar test and Chlorine demand test

Flocculation and chlorination controlWATSAN M15 ERUWATSAN M15 ERU 13

4. Jar test practical procedure4. Jar test practical procedure

4. Materials

• Clean water• Aluminium sulphate• 7 jars• 1 spoon• 6 litres of raw water• 1 watch

Page 14: Flocculation and chlorination process control Jar test and Chlorine demand test

Flocculation and chlorination controlWATSAN M15 ERUWATSAN M15 ERU 14

4. Jar test practical procedure4. Jar test practical procedure 5. Procedure

Pour 1 litre of clean water into a jar and 1 litre of the raw water sample in each of the other 6 jars.

Fill a spoon with Aluminium Sulphate (10 g.)

Page 15: Flocculation and chlorination process control Jar test and Chlorine demand test

Flocculation and chlorination controlWATSAN M15 ERUWATSAN M15 ERU 15

5. Procedure

Pour the Aluminium Sulphate in the jar with clean water.

Vigorously stir until the complete dissolution of the chemical.

4. Jar test practical procedure4. Jar test practical procedure

Page 16: Flocculation and chlorination process control Jar test and Chlorine demand test

Flocculation and chlorination controlWATSAN M15 ERUWATSAN M15 ERU 16

5. Procedure

The solution is named mother

solution (MS) 1%.

Using a syringe, growing quantities of mother solution 1% will be taken.

4. Jar test practical procedure4. Jar test practical procedure

Page 17: Flocculation and chlorination process control Jar test and Chlorine demand test

Flocculation and chlorination controlWATSAN M15 ERUWATSAN M15 ERU 17

4. Jar test practical procedure4. Jar test practical procedure

5. Procedure

Pour 1 ml. of MS to the first jar

2 ml to the second jar

4 ml to the third jar, 8 ml to the fourth, 16 ml to the fifth so that each jar duplicates the

concentration of the preceding. It is also possible to use different quantities.

Page 18: Flocculation and chlorination process control Jar test and Chlorine demand test

Flocculation and chlorination controlWATSAN M15 ERUWATSAN M15 ERU 18

4. Jar test practical procedure4. Jar test practical procedure

5. Procedure

Stir vigorously to favour coagulation.

Stir very slowly in the same direction for 10 min.

Let it settle for 30 min.

Page 19: Flocculation and chlorination process control Jar test and Chlorine demand test

Flocculation and chlorination controlWATSAN M15 ERUWATSAN M15 ERU 19

4. Jar test practical procedure4. Jar test practical procedure

5. Procedure

When 30 minutes or the time agreed has expired we will observe a colour gradient.

We will not select the clearest, but the jar where less mother solution was added among those sufficiently clear.

Page 20: Flocculation and chlorination process control Jar test and Chlorine demand test

Flocculation and chlorination controlWATSAN M15 ERUWATSAN M15 ERU 20

4. Jar test practical procedure4. Jar test practical procedure

5. Procedure

If none of the jars comes up with clear water, after checking the turbidity as explained bellow, we shall repeat all the process although adding 24, 34, 46, 60 and 76 ml. Only after checking again that a cleaner source is still not available.

If all are sufficiently clear, we shall repeat all the process with smaller amounts 0.1, 0.2, 0.5, 0.75 y 1 ml. Only after checking again that the source still does not meet turbidity requirements without any treatment.

Page 21: Flocculation and chlorination process control Jar test and Chlorine demand test

Flocculation and chlorination controlWATSAN M15 ERUWATSAN M15 ERU 21

4. Jar test practical procedure4. Jar test practical procedure

5. Procedure

Check that turbidity is below 5 NTU or 20 NTU, by pouring very carefully the sample into a measuring column (turbidity meter). Avoid the dissolution of solids settle at the bottom of the jar.

Page 22: Flocculation and chlorination process control Jar test and Chlorine demand test

Flocculation and chlorination controlWATSAN M15 ERUWATSAN M15 ERU 22

Thank you……….Thank you……….