MV network management - Easergy range Flite 116-SA Technical data sheet Radio fault passage indicator for overhead networks 2008 b Remote monitoring of overhead lines (currents, faults, voltage losses, etc.) b Detects both short-circuits and low current earth faults b Highly visible 360° red flashing light b Easy installation (spring grips) b Remote setting PE41017 Application: fast location of faulty circuits The location of a fault along an overhead MV network by mean of optical fault passage indicators is time-consuming (traffic jam, hard to access network sections, long outgoing feeders). A solution is to use (in addition) our remotely indicated Flite 116-SA fault passage detector. The payback is quick because the outage time being decreased, the reduction of non-distributed energy is important, and the quality is improved. Principal Each of the Flite 116-SA clipped onto the MV line communicates via a low power licence-free radio with a G200 RTU mounted on the pole. The G200 RTU is able to manage the communication with up to 9 Flite 116-SA (3 MV lines) and transmits information to the SCADA using open protocols such as DNP3 or IEC 870-5-101/104. Communication with G200 RTU b Frequency: 918 MHz or others upon local standard, licence-free. Frequency spread spectrum used to avoid radio interferences b Secured protocol: enabling message correction and repetition b Maximum distance: 100m b Capacity: up to 9 Flite 116-SA (the number of Flite 116-SA monitored by G200 affects the autonomy of the Flite 116-SA lithium battery). Fault detection (same characteristics as Flite 110-SA) b Self-adaptation: Flite 116-SA adjusts to the network voltage and frequency b Configuration: Flite 116-SA is remote configured from the G200 at the pole bottom b Fault types: Flite 116-SA detects and transmits earth fault (di/dt algorythm), short circuits and voltage loss b Inrush current filter: when the line is energized, a time delay filters inrush current due to transformers magnetization b Transient faults: Flite 116-SA detects and transmits transient fault (a fault is considered as “transient” when the upstream protection device eliminates the fault during its reclosing cycle) b Fault confirmation: faults are confirmed by the loss of voltage after the upstream protection device has tripped b Reset: permanent fault indication is automatically cleared when voltage returns to the MV line or following a time delay. Operation b Instantaneous MV line fault reporting: v Instantaneous transmission to the G200 RTU of the fault detection (earth or phase to phase) or the voltage drop b Periodic event reporting: v Continuous recording of the current values, updating of RTU local archives (average, min, max) v MV line status v Flite 116-SA battery status b Communication to SCADA: v Data transmission v Remote parameter settings. G200 GF PE41016

Flite 116 SA

Embed Size (px)

DESCRIPTION

FPI

Citation preview

MV network management - Easergy rangeFlite 116-SATechnical data sheetRadio fault passage indicatorfor overhead networks2008b Remote monitoring of overhead lines (currents, faults, voltage losses, etc.)b Detects both short-circuits and low current earth faultsb Highly visible 360 red fashing lightb Easy installation (spring grips)b Remote settingPE41017Application: fast location of faulty circuitsThe location of a fault along an overhead MV network by mean of optical fault passage indicators is time-consuming (traffc jam, hard to access network sections, long outgoing feeders).A solution is to use (in addition) our remotely indicated Flite 116-SA fault passage detector. The payback is quick because the outage time being decreased, the reduction of non-distributed energy is important, and the quality is improved.PrincipalEach of the Flite 116-SA clipped onto the MV line communicates via a low power licence-free radio with a G200 RTU mounted on the pole. The G200 RTU is able to manage the communication with up to 9 Flite 116-SA (3 MV lines) and transmits information to the SCADA using open protocols such as DNP3 or IEC 870-5-101/104.Communication with G200 RTUb Frequency: 918 MHz or others upon local standard, licence-free. Frequency spread spectrum used to avoid radio interferencesb Secured protocol: enabling message correction and repetitionb Maximum distance: 100m b Capacity: up to 9 Flite 116-SA (the number of Flite 116-SA monitored by G200 affects the autonomy of the Flite 116-SA lithium battery).Fault detection (same characteristics as Flite 110-SA)b Self-adaptation: Flite 116-SA adjusts to the network voltage and frequencyb Confguration: Flite 116-SA is remote confgured from the G200 at the pole bottomb Fault types: Flite 116-SA detects and transmits earth fault (di/dt algorythm), short circuits and voltage lossb Inrush current flter: when the line is energized, a time delay flters inrush current due to transformers magnetizationb Transient faults: Flite 116-SA detects and transmits transient fault (a fault is considered as transient when the upstream protection device eliminates the fault during its reclosing cycle)b Fault confrmation: faults are confrmed by the loss of voltage after the upstream protection device has trippedb Reset: permanent fault indication is automatically cleared when voltage returns to the MV line or following a time delay. Operationb Instantaneous MV line fault reporting:v Instantaneous transmission to the G200 RTU of the fault detection (earth or phase to phase) or the voltage dropb Periodic event reporting:v Continuous recording of the current values, updating of RTU local archives (average, min, max)v MV line statusv Flite 116-SA battery statusb Communication to SCADA:v Data transmissionv Remote parameter settings.G200 GFPE41016ENMED305015EN 08-2008As standard, specifcations and designs change from time to time, please ask for confrmation of the information given in this publication.Publishing : Schneider Electric Industries SASProduction : Schneider Electric Industries SASPrinting : Imprimerie du Pont de Claix/JPF - Made in FranceThis document has been printed on ecological paperSchneider Electric Industries SAS89, boulevard Franklin RooseveltF-92505 Rueil-Malmaison CedexTl. : +33 (0)1 41 29 85 00www.schneider-electric.comwww.easergy.comART.806910 Schneider Electric Industries SAS - All rights reservedPE55564Installation with SICAME toolInstallation with shotgun hotstickG200 unit with solar panelPE55844PE55563Flite 116-SA characteristicsApplicationDistribution network voltage 7 kV to 69 kV ( 8 years with hourly transmissionEnvironmentOperating temperature 40C to + 70CStorage temperature 40C to + 85CHumidity < 95%Protection level IP 54 IK 7MechanicalDimensions 130 mm x 130 mmNet weight 540 gWind resistance Up to 150 km per hourStandardsShort-circuit withstand 25 kA/170 ms (ANSI 495)Vibrations and shocks test IEC 68-2-6 and 68-2-29EMI/EFI immunity IEC 801-3and FCC Part 15Salt spray and humidity tests IEC 68-2-11 and 68-2-30Description ReferencesFlite 116-SA Flite 116-SAInstallation tool with SICAME adapter 59953Installation tool with BOWTHORP adapter 5995412 meter telescopic hotstick (20 kV insulated) 59955