51
7 7 Description Multi-conductor Cable, two, three or four flexible soft copper conductors polyolefin insulated, twisted and external PVC Rubber jacket Construction Conductor Flexible soft copper conductor, Class K stranded Insulation Polyolefin (75° C) Jacket Flame retardant Polyvinyl Chloride with content of rubber Characteristics Operating Temperature 75° C. Operating Voltage 600 V. Applications Hard Service Cord for equipment and portable tools, special for factories, scenes and display cabinets. Open wiring installation, in portable extensions with terminals. By being of common use, it can be used like portable cord, control and power cable. Easy handling and flexibility in reduced spaces. Specifications CENTELSA ST-C Cables are manufactured under the following standards: UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and Flexible Cords UL 62, NTC-2356 Flexible Cord and Fixture Wire. CENTELSA Specifications for ST-C Cables Type ST-C Cables Extra Hard Service Thermoplastic Insulated, C: Common Use

Flexible cords

Embed Size (px)

DESCRIPTION

Flexible cords

Citation preview

Page 1: Flexible cords

77

Description

Multi-conductor Cable, two, three or four flexible soft copper conductorspolyolefin insulated, twisted and external PVC Rubber jacket

Construction

ConductorFlexible soft copper conductor, Class K stranded

InsulationPolyolefin (75° C)

JacketFlame retardant Polyvinyl Chloride with content of rubber

Characteristics

Operating Temperature75° C.Operating Voltage600 V.

Applications

Hard Service Cord for equipment and portable tools, special for factories, scenes anddisplay cabinets. Open wiring installation, in portable extensions with terminals.

By being of common use, it can be used like portable cord, control and power cable.Easy handling and flexibility in reduced spaces.

Specifications

CENTELSA ST-C Cables are manufactured under the following standards:

UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and FlexibleCordsUL 62, NTC-2356 Flexible Cord and Fixture Wire.CENTELSA Specifications for ST-C Cables

Type ST-C CablesExtra Hard Service Thermoplastic Insulated, C: Common Use

Page 2: Flexible cords

8

Certifications

CENTELSA ST-C Flexible cords are certified by:CIDET (Colombia). Cert. No. 02005, according to RETIE (Colombian TechnicalCode of Electrical Installations) requirements

ColorsConductors identification: 2, black-white; 3, black-white-green; 4, black-white-red-green. Black colored Jacket.

PackagingWood Reels. Reel lengths between 500 m and 2500 m.

Note: Other configurations, sizes, colors and length not specified hereinare available upon request.

Page 3: Flexible cords

9

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity.2. Ampacities based on 75°C conductor temperature, and Section 400 of NEC (NTC 2050) and 30°C ambient temperature.3. Two current carrying conductors.4. Three current carrying conductors.5. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Flexible Cord Type ST-C 600V, 60oC (International System Unit)Extra Hard Service Thermoplastic Insulated, C: Common Use

Standards: UL 62, NTC 2356 and CENTELSA specifications for ST-C cables

0.64

0.76

0.76

0.76

0.76

0.76

1.14

1.52

1.52

1.52

0.254

0.254

0.254

0.254

0.254

0.254

0.254

0.254

0.254

0.254

10

16

26

41

65

104

168

266

420

665

0.51

0.81

1.32

2.08

3.29

5.27

8.51

13.48

21.28

33.70

0.97

1.23

1.51

1.98

2.52

3.21

3.66

4.77

6.00

7.56

6.266.627.237.267.708.437.828.309.118.769.32

10.249.84

10.4812.3212.0012.7414.7815.2516.1918.7720.0521.2823.3323.2924.7127.0826.4128.0730.85

0.760.760.760.760.760.760.760.760.760.760.760.760.760.761.141.141.141.521.521.522.032.032.032.032.412.412.412.412.412.41

35.435.435.422.122.122.113.613.613.68.638.638.635.455.455.453.403.403.402.112.112.111.331.331.33

0.8430.8430.8430.5320.5320.532

2

10

13

18

25

30

40

55

70

95

50597069829986

104127113139171152190255231288382380476630635790976902

11331407125416002003

-

7

10

15

20

25

35

45

60

80

20

18

16

14

12

10

8

6

4

2

234234234234234234234234234234

STRANDSSIZEAWG STRAND

DIAMETER(mm)

SECTION(mm2)

INSULATIONTHICKNESS

(mm)

JACKETTHICKNESS

(mm)

OVERALLDIAMETER

(mm)

DCRESISTANCE

AT 20°C 1(ohm/km)

APPROX.TOTAL

WEIGHT(kg/km)

AMPACITY 2

(A) 3AMPACITY 2

(A) 4DIAMETER

(mm)

COPPER CONDUCTORCONDUCTORS

No.

Page 4: Flexible cords

10

Notas: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity.2. Ampacities based on 75°C conductor temperature, and Section 400 of NEC (NTC 2050) and 30°C ambient temperature.3. Two current carrying conductors.4. Three current carrying conductors.5. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

25

30

30

30

30

30

45

60

60

60

10.0

10.0

10.0

10.0

10.0

10.0

10.0

10.0

10.0

10.0

10

16

26

41

65

104

168

266

420

665

1.00

1.60

2.60

4.10

6.50

10.40

16.80

26.60

42.00

66.50

38

48

59

78

99

126

144

188

236

298

246261284286303332308327359345367403387413485472502582600637739789838919917973

1066104011051215

303030303030303030303030303045454560606080808080959595959595

10.810.810.86.746.746.744.154.154.152.632.632.631.661.661.661.041.041.04

0.6420.6420.6420.4060.4060.4060.2570.2570.2570.1620.1620.162

2

10

13

18

25

30

40

55

70

95

3339474655675870857693

115102128172155194256256320423427531656606761945843

10751346

-

7

10

15

20

25

35

45

60

80

20

18

16

14

12

10

8

6

4

2

234234234234234234234234234234

Flexible Cord Type ST-C 600V, 60oCExtra Hard Service Thermoplastic Insulated, C: Common Use

Standards: UL 62, NTC 2356 and CENTELSA specifications for ST-C cables

STRANDDIAMETER

(mils)

STRANDSSIZEAWG SECTION

(kcmil)

INSULATIONTHICKNESS

(mils)

JACKETTHICKNESS

(mils)

OVERALLDIAMETER

(mils)

DCRESISTANCE

AT 20°C 1(ohm/kft)

APPROX.TOTAL

WEIGHT(lb/kft)

AMPACITY 2

(A) 3AMPACITY 2

(A) 4DIAMETER

(mils)

COPPER CONDUCTORCONDUCTORS

No.

Page 5: Flexible cords

11

Description

Multi-conductor Cable, two, three or four flexible soft copper conductors polyvinylchloride (PVC) insulated, twisted and external PVC jacket

Construction

ConductorFlexible soft copper conductor, Class K stranded

InsulationFlame Retardant Polyvinyl chloride (PVC 60° C)

JacketFlame Retardant Polyvinyl chloride (PVC 60° C)

Characteristics

Operating Temperature60° C.Operating Voltage600 V.

Applications

Hard Service Cord for equipment and portable tools, special for factories, scenes anddisplay cabinets. Open wiring installation, in portable extensions with terminals.

Specifications

CENTELSA ST Cables are manufactured under the following standards:UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and FlexibleCordsUL 62, NTC-2356 Flexible Cord and Fixture Wire.

Certifications

CENTELSA ST Flexible cords are certified by UL, File E203934

Flexible Cords Type STExtra Hard Service Thermoplastic Insulated

Page 6: Flexible cords

12

ColorsConductors identification: 2, black-white; 3, black-white-green; 4, black-white-red-green. Black colored Jacket.

Note: Other configurations, sizes, colors and length not specified hereinare available upon request.

Page 7: Flexible cords

13

Flexible Cords Type ST 600V, 60oC (International System Unit)Extra Hard Service Thermoplastic Insulated

Standard: UL 62, NTC-2356 Flexible Cord and Fixture Wire.

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity.2. Ampacities based on 60°C conductor temperature, and Section 400 of NEC (NTC 2050) and 30°C ambient temperature.3. Two current carrying conductors.4. Three current carrying conductors.5. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

1.14

1.14

1.14

1.52

1.52

1.52

1.52

0.254

0.254

0.254

0.254

0.254

0.254

0.254

41

65

104

168

266

420

665

2.08

3.29

5.27

8.51

13.48

21.28

33.70

1.98

2.52

3.21

3.66

4.12

6.72

8.58

12.9113.5814.7114.7715.5316.8016.1517.0218.4719.4020.4523.0121.1022.2324.9027.0928.6231.9631.5933.4137.15

2.032.032.032.412.412.412.412.412.412.792.793.183.183.183.563.563.563.943.943.944.32

8.638.638.635.455.455.453.403.403.402.112.112.111.331.331.33

0.8430.8430.8430.5320.5320.532

18

25

30

40

55

70

95

210244290283331394357425512535644818692851

1082108813271674154118992388

15

20

25

35

45

60

80

14

12

10

8

6

4

2

234234234234234234234

STRANDSSIZEAWG STRAND

DIAMETER(mm)

SECTION(mm2)

INSULATIONTHICKNESS

(mm)

JACKETTHICKNESS

(mm)

OVERALLDIAMETER

(mm)

DCRESISTANCE

AT 20°C 1(ohm/km)

APPROX.TOTAL

WEIGHT(kg/km)

AMPACITY 2

(A) 3AMPACITY 2

(A) 4DIAMETER

(mm)

COPPER CONDUCTORCONDUCTORS

No.

Page 8: Flexible cords

14

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity.2. Ampacities based on 60°C conductor temperature, and Section 400 of NEC (NTC 2050) and 30°C ambient temperature.3. Two current carrying conductors.4.Three current carrying conductors.5. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

45

45

45

60

60

60

60

10.0

10.0

10.0

10.0

10.0

10.0

10.0

41

65

104

168

266

420

665

4.10

6.50

10.40

16.80

26.60

42.00

66.50

78

99

126

144

162

265

338

508535579582611661636670727764805906831875980

106611271258124413151463

808080959595959595

110110125125125140140140155155155170

2.632.632.631.661.661.661.041.041.04

0.6420.6420.6420.4060.4060.4060.2570.2570.2570.1620.1620.162

18

25

30

40

55

70

95

141164195190222265240286344359433550465572727731892

1125103612771605

15

20

25

35

45

60

80

14

12

10

8

6

4

2

234234234234234234234

Flexible Cords Type ST 600V, 60oCExtra Hard Service Thermoplastic Insulated

Standard: UL 62, NTC-2356 Flexible Cord and Fixture Wire.

STRANDDIAMETER

(mils)

STRANDSSIZEAWG SECTION

(kcmil)

INSULATIONTHICKNESS

(mils)

JACKETTHICKNESS

(mils)

OVERALLDIAMETER

(mils)

DCRESISTANCE

AT 20°C 1(ohm/kft)

APPROX.TOTAL

WEIGHT(lb/kft)

AMPACITY 2

(A) 3AMPACITY 2

(A) 4DIAMETER

(mils)

COPPER CONDUCTORCONDUCTORS

No.

Page 9: Flexible cords

15

Description

Multi-conductor Cable, two, three or four flexible soft copper conductors polyvinylchloride (PVC) insulated, twisted and external PVC jacket

Construction

ConductorFlexible soft copper conductor, Class K stranded

InsulationFlame Retardant Polyvinyl chloride (PVC 60° C)JacketFlame Retardant Polyvinyl chloride (PVC 60° C)

Characteristics

Operating Temperature60° C.Operating Voltage300 V.

Applications

Junior Hard Service Cord for industrial, commercial and residential equipment. Openwiring installation, in portable extensions with terminals.

Specifications

CENTELSA SJT Cables are manufactured under the following standards:UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and FlexibleCordsUL 62, NTC-2356 Flexible Cord and Fixture Wire.

Flexible Cords Type SJTJunior Hard Service Thermoplastic Insulated

Page 10: Flexible cords

16

Certifications

CENTELSA SJT Flexible cords are certified by UL, File E203934

ColorsConductors identification: 2, black-white; 3, black-white-green; 4, black-white-red-green. Black colored Jacket.

Note: Other configurations, sizes, colors and length not specified hereinare available upon request.

Page 11: Flexible cords

17

Flexible Cords Type SJT 600V, 60oC (International System Unit)Junior Hard Service Thermoplastic Insulated

Standard: UL 62, NTC-2356 Flexible Cord and Fixture Wire.

Flexible Cords Type SJT 600V, 60oCJunior Hard Service Thermoplastic Insulated

Standard: UL 62, NTC-2356 Flexible Cord and Fixture Wire.

0.76

0.76

0.76

0.76

1.14

0.254

0.254

0.254

0.254

0.254

16

26

41

65

104

0.81

1.32

2.08

3.29

5.27

1.23

1.51

1.98

2.52

3.21

7.267.708.437.828.309.118.769.32

10.2410.6211.2612.3214.3515.2216.67

0.760.760.760.760.760.760.760.760.761.141.141.141.521.521.52

22.122.122.113.613.613.68.638.638.635.455.455.453.403.403.40

10

13

18

25

30

69829986

104127113139171169208255298363445

7

10

15

20

25

18

16

14

12

10

234234234234234

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity.2. Ampacities based on 60°C conductor temperature, and Section 400 of NEC (NTC 2050) and 30°C ambient temperature.3. Two current carrying conductors.4. Three current carrying conductors.5. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity.2. Ampacities based on 60°C conductor temperature, and Section 400 of NEC (NTC 2050) and 30°C ambient temperature.3. Two current carrying conductors.4. Three current carrying conductors.5. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

30

30

30

30

45

10.0

10.0

10.0

10.0

10.0

16

26

41

65

104

1.60

2.60

4.10

6.50

10.40

48

59

78

99

126

286303332308327359345367403418443485565599656

303030303030303030454545606060

6.746.746.744.154.154.152.632.632.631.661.661.661.041.041.04

10

13

18

25

30

4655675870857693

115114140172200244299

7

10

15

20

25

18

16

14

12

10

234234234234234

STRANDSSIZEAWG STRAND

DIAMETER(mm)

SECTION(mm2)

INSULATIONTHICKNESS

(mm)

JACKETTHICKNESS

(mm)

OVERALLDIAMETER

(mm)

DCRESISTANCE

AT 20°C 1(ohm/km)

APPROX.TOTAL

WEIGHT(kg/km)

AMPACITY 2

(A) 3AMPACITY 2

(A) 4DIAMETER

(mm)

COPPER CONDUCTORCONDUCTORS

No.

STRANDDIAMETER

(mils)

STRANDSSIZEAWG SECTION

(kcmil)

INSULATIONTHICKNESS

(mils)

JACKETTHICKNESS

(mils)

OVERALLDIAMETER

(mils)

DCRESISTANCE

AT 20°C 1(ohm/kft)

APPROX.TOTAL

WEIGHT(lb/kft)

AMPACITY 2

(A) 3AMPACITY 2

(A) 4DIAMETER

(mils)

COPPER CONDUCTORCONDUCTORS

No.

Page 12: Flexible cords

18

Description

Multi-conductor Cable, two, three or four flexible soft copper conductorspolyvinyl chloride (PVC) insulated, twisted and external PVC jacket

Construction

ConductorFlexible soft copper conductor, Class M stranded

InsulationFlame Retardant Polyvinyl chloride (PVC 60° C)JacketFlame Retardant Polyvinyl chloride (PVC 60° C)

Characteristics

Operating Temperature60° C.Operating Voltage300 V.

Applications

Service Cord, vacuum cleaner cord computers and similar equipments.Open wiring installation, in portable extensions with terminals.

Specifications

CENTELSA SVT Cables are manufactured under the followingstandards:UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables andFlexible CordsUL 62, NTC-2356 Flexible Cord and Fixture Wire.

Flexible Cords Type SVTService Vacuum-cleaner cord, Thermoplastic Insulated

Page 13: Flexible cords

19

Certifications

CENTELSA SVT Flexible cords are certified by UL, File E203934

ColorsConductors identification: 2, black-white; 3, black-white-green; 4, black-white-red-green. Black colored Jacket.

Note: Other configurations, sizes, colors and length not specified herein are availableupon request.

Page 14: Flexible cords

Flexible Cord Type SVT 300V 60°C (International System Unit)Service Vacuum-cleaner cord, Thermoplastic Insulated

Standard: UL 62, NTC-ICONTEC 2356. Flexible and Fixture Wire

0.38

0.38

0.160

0.160

41

65

0.82

1.31

1.166.766.001.486.766.00

5.605.916.436.246.607.20

0.760.760.760.760.760.76

22.122.122.113.613.613.6

10

13

465668627694

7

10

18

16

234234

Notes: 1. Fourth conductor is used as grounding conductor.2. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity.3. Ampacities based on 60°C conductor temperature, and Section 400 of NEC (NTC 2050) and 30°C ambient temperature.4. Two current carrying conductors.5. Three current carrying conductors.6. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Flexible Cord Type SVT 300V 60°CService Vacuum-cleaner cord, Thermoplastic Insulated

Standard: UL 62, NTC-ICONTEC 2356. Flexible and Fixture Wire

15

15

6.3

6.3

41

65

1.63

2.58

46

58

220233253246260284

303030303030

6.746.746.744.154.154.15

10

13

313846415163

7

10

18

16

234234

Notes: 1. Fourth conductor is used as grounding conductor.2. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity.3. Ampacities based on 60°C conductor temperature, and Section 400 of NEC (NTC 2050) and 30°C ambient temperature.4. Two current carrying conductors.5. Three current carrying conductors.6. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

20

STRANDSSIZEAWG STRAND

DIAMETER(mm)

SECTION(mm2)

INSULATIONTHICKNESS

(mm)

JACKETTHICKNESS

(mm)

OVERALLDIAMETER

(mm)

DCRESISTANCE

AT 20°C 1(ohm/km)

APPROX.TOTAL

WEIGHT(kg/km)

AMPACITY 2

(A) 3AMPACITY 2

(A) 4DIAMETER

(mm)

COPPER CONDUCTORCONDUCTORS

No.

STRANDDIAMETER

(mils)

STRANDSSIZEAWG SECTION

(kcmil)

INSULATIONTHICKNESS

(mils)

JACKETTHICKNESS

(mils)

OVERALLDIAMETER

(mils)

DCRESISTANCE

AT 20°C 1(ohm/kft)

APPROX.TOTAL

WEIGHT(lb/kft)

AMPACITY 2

(A) 3AMPACITY 2

(A) 4DIAMETER

(mils)

COPPER CONDUCTORCONDUCTORS

No.

Page 15: Flexible cords

21

Description

Two copper flexible copper conductor, paralleled and PVC insulated.

Construction

Flexible soft copper conductor, Class K stranded

InsulationFlame Retardant Polyvinyl chloride (PVC 60° C)Integral insulation with separation membrane, and polarization ridges in oneconductor.

Characteristics

Operating Temperature60° C.Operating Voltage300 V. (600V optional)

Applications

Service Cord, for portable electrical devices. Open wiring installation, in portableextensions with terminals.

Specifications

CENTELSA SPT Cables are manufactured under the following standards:UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and FlexibleCordsUL 62, NTC-2356 Flexible Cord and Fixture Wire.CENTELSA Specifications for SPT-C Cables

Certifications

CENTELSA SPT-C Paralleled cords are certified by:CIDET (Colombia). Cert. No. 02004, according to RETIE (Colombian Technical Codeof Electrical Installations) requirements

Parallel Cord Type SPT-CParallel Cord, Thermoplastic Insulated

Page 16: Flexible cords

ColorsWhite, grey brown and black. Optional with red strip at one conductorfor polarization indication.

Packaging100 m spools covered with plastic thermo pack, in corrugated carton boxes.

Note: Other configurations, sizes, colors and length not specified hereinare available upon request.

22

Page 17: Flexible cords

23

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity.2. Ampacities based on 60°C conductor temperature, and Section 400 of NEC (NTC 2050) and 30°C ambient temperature.3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Paralleled Cord Type SPT-C 300V, 60°C (International System Unit)Parallel Cord, Thermoplastic Insulated

Standards: UL 62, NTC 2356 and CENTELSA specifications for SPT-C cables

Paralleled Cord Type SPT-C 300V, 60°C)Parallel Cord, Thermoplastic Insulated

Standards: UL 62, NTC 2356 and CENTELSA specifications for SPT-C cables

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity.2. Ampacities based on 60°C conductor temperature, and Section 400 of NEC (NTC 2050) and 30°C ambient temperature.3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

10.010.010.010.010.010.0

71016264165

0.701.001.602.604.106.50

303848597899

202025252525

91219263856

15.110.66.614.072.581.63

XXXXXX

-2

10131825

222222

XXXXXX

222018161412

7382

102113131153

147163204226263305

STRANDSSIZEAWG STRAND

DIAMETER(mm)

SECTION(mm2)

INSULATIONTHICKNESS

(mm)

EXTERNALDIMENSIONS

(mm)

APPROX.TOTAL

WEIGHT(kg/km)

DCRESISTANCE

AT 20°C 1

(ohm/km)

AMPACITY 2

(A)DIAMETER

(mm)

COPPER CONDUCTOR

0.2540.2540.2540.2540.2540.254

71016264165

0.350.510.811.322.083.29

0.760.971.231.511.982.52

0.510.510.640.640.640.64

141728395784

49.634.721.713.38.465.34

XXXXXX

-2

10131825

222222

XXXXXX

222018161412

1.862.072.592.873.343.88

3.724.145.175.736.677.75

STRANDSSIZEAWG STRAND

DIAMETER(mils)

SECTION(kcmil)

INSULATIONTHICKNESS

(mils)

EXTERNALDIMENSIONS

(mils)

APPROX.TOTAL

WEIGHT(lb/kft)

DCRESISTANCE

AT 20°C 1

(ohm/kft)

AMPACITY 2

(A)DIAMETER

(mils)

COPPER CONDUCTOR

Page 18: Flexible cords

24

Description

Two copper flexible copper conductor, paralleled and PVC insulated.

ConductorFlexible soft copper conductor, Class M stranded for SPT-1 and SPT-2Flexible soft copper conductor, Class K stranded for SPT-3

InsulationFlame Retardant Polyvinyl chloride (PVC 60° C)Integral insulation with separation membrane, and polarization ridgesin one conductor.

Characteristics

Operating Temperature60° C.Operating Voltage300 V.

Applications

SPT-1: Portable lamps feeders, fans, radios, clocks, householdappliances and office equipment.SPT-2: Same as above, stereo and video devicesSPT-3: Freezers, coolers, air conditioning equipment, dish washingmachines, waste disposers and office equipment.

Specifications

CENTELSA SPT-1, SPT-2 and SPT-3 Paralleled Cords are manufacturedunder the following standards:UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables andFlexible Cords

Paralleled CordType SPT-1 SPT-2 SPT-3Parallel Cord, Thermoplastic Insulated

Page 19: Flexible cords

25

UL 62, NTC-2356 Flexible Cord and Fixture Wire.

ColorsWhite, grey, brown and black.

Packaging100 m spools covered with plastic thermo pack, in corrugated carton boxes.

Note: Other configurations, sizes, colors and length not specified herein are availableupon request.

Page 20: Flexible cords

26

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity.2. Ampacities based on 60°C conductor temperature, and Section 400 of NEC (NTC 2050) and 30°C ambient temperature.3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Paralleled Cords Type SPT-1 SPT-2 SPT-3 300V, 60°CParallel Cord, Thermoplastic Insulated

Standard: UL 62, NTC 2356. Flexible and Fixture Wire

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity.2. Ampacities based on 60°C conductor temperature, and Section 400 of NEC (NTC 2050) and 30°C ambient temperature.3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Paralleled Cords Type SPT-1 SPT-2 SPT-3 300V, 60°C(International System Unit)Parallel Cord, Thermoplastic Insulated

Standard: UL 62, NTC 2356. Flexible and Fixture Wire

0.1600.1600.1600.1600.2540.2540.2540.2540.254

2641416516264165

104

0.520.820.821.310.811.322.083.295.27

0.921.161.161.481.231.511.982.523.21

0.760.761.141.141.521.522.032.412.79

172436505168

115177268

33.621.321.313.521.713.38.465.343.34

XXXXXXXXX

21010131013182530

222222222

XXXXXXXXX

201818161816141210

2.522.763.533.854.394.676.167.488.96

4.635.116.787.428.499.05

11.0112.8715.04

SPT-1

SPT-2

SPT-3

6.36.36.36.3

10.010.010.010.010.0

2641416516264165

104

1.031.631.632.581.602.604.106.50

10.40

3646465848597899

126

3030454560608095

110

12162433354677

119180

10.36.506.504.106.614.072.581.631.02

XXXXXXXXX

21010131013182530

222222222

XXXXXXXXX

201818161816141210

99109139152173184243295353

182201267292334356434507592

SPT-1

SPT-2

SPT-3

STRANDSSIZEAWG STRAND

DIAMETER(mm)

SECTION(mm2)

INSULATIONTHICKNESS

(mm)

EXTERNALDIMENSIONS

(mm)

APPROX.TOTAL

WEIGHT(kg/km)

DCRESISTANCE

AT 20°C 1

(ohm/km)

AMPACITY 2

(A)DIAMETER

(mm)

COPPER CONDUCTOR

STRANDSSIZEAWG STRAND

DIAMETER(mils)

SECTION(kcmil)

INSULATIONTHICKNESS

(mils)

EXTERNALDIMENSIONS

(mils)

APPROX.TOTAL

WEIGHT(lb/kft)

DCRESISTANCE

AT 20°C 1

(ohm/kft)

AMPACITY 2

(A)DIAMETER

(mils)

COPPER CONDUCTOR

TYPE

TYPE

Page 21: Flexible cords

27

Description

Soft copper flexible conductor PVC insulated.

Construction

ConductorFlexible soft copper conductor, Class K stranded

InsulationFlame Retardant Polyvinyl chloride (PVC 60° C)

Characteristics

Operation Temperature60° C.Operating Voltage600 V.

Applications

Internal equipment wiring, boards, in ducts or raceways.Also used in low voltage automotive wiring.

Specifications

CENTELSA TFF and TWK Cables are manufactured under the followingstandards:UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and FlexibleCordsUL 62, NTC-2356 Flexible Cord and Fixture Wire, for TFFUL 83, NTC-1332 Thermoplastic insulated Wires and Cables, for TWK

ColorsBlack, white, red, green, yellow, blue.

Cables Type TFF and TWKThermoplastic Insulation, Flexible Fixture WireThermoplastic Insulation, Suitable for Wet Locations, Class K Stranding

Page 22: Flexible cords

Packaging100 m spools covered with plastic thermo pack, in corrugated carton boxes.

Note: Other configurations, sizes, colors and length not specified hereinare available upon request.

28

Page 23: Flexible cords

Cables Type TFF and TWK 600V, 60°C (International System Units)Thermoplastic Insulation, Flexible Fixture WireThermoplastic Insulation, Suitable for Wet Locations, Class K Stranding

Standard: UL 62, NTC 2356. Flexible and Fixture Wire, for TFFUL 83, NTC-1332 Thermoplastic insulated Wires and Cables, for TWK

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity.2. Ampacities based on 60°C conductor temperature, and Section 400 of NEC (NTC 2050) and 30°C ambient temperature.3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Cables Type TFF and TWK 600V, 60°CThermoplastic Insulation, Flexible Fixture WireThermoplastic Insulation, Suitable for Wet Locations, Class K Stranding

Standard: UL 62, NTC 2356. Flexible and Fixture Wire, for TFFUL 83, NTC-1332 Thermoplastic insulated Wires and Cables, for TWK

Notes: 1. Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity.2. Ampacities based on 60°C conductor temperature, and Section 400 of NEC (NTC 2050) and 30°C ambient temperature.3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

0.2540.2540.2540.2540.2540.2540.254

16264165

104168266

0.811.322.083.295.278.51

13.48

1.231.511.982.523.213.664.12

0.760.760.760.760.761.141.52

1520294263

104164

21.713.38.465.343.342.071.30

10131825304055

1816141210

86

2.833.113.584.124.816.047.28

TFF

TWK

STRANDSSIZEAWG

STRANDDIAMETER

(mm)

SECTION(mm2)

INSULATIONTHICKNESS

(mm)

DIAMETEROVER

INSULATION(mm)

APPROX.TOTAL

WEIGHT(kg/km)

DCRESISTANCE

AT 20°C 1

(ohm/km)

AMPACITY 2

(A)CONDUCTOR

DIAMETER(mm)

TYPE

10.010.010.010.010.010.010.0

16264165

104168266

1.602.604.106.50

10.4016.8026.60

48597899

126144162

30303030304560

101420284270

110

6.614.072.581.631.02

0.6300.398

10131825304055

1816141210

86

111122141162189238287

TFF

TWK

29

STRANDSSIZEAWG

STRANDDIAMETER

(mils)

SECTION(kcmil)

INSULATIONTHICKNESS

(mils)

DIAMETEROVER

INSULATION(mils)

APPROX.TOTAL

WEIGHT(lb/kft)

DCRESISTANCE

AT 20°C 1

(ohm/kft)

AMPACITY 2

(A)CONDUCTOR

DIAMETER(mils)

TYPE

Page 24: Flexible cords

30

Description

Soft copper conductor, PVC insulated and with a Nylon covering

Construction

ConductorFlexible soft copper conductor, Class K stranded

InsulationPolyvinyl Chloride (PVC 90° C), flame retardant

JacketAbrasion resistant Nylon

Characteristics

Operating Temperature90°C.

Operating Voltage600 V.

Applications

TFFN cables and wires are used generally in internal equipment and boardwiring. Installation: in ducts tubing and boards.

Special for locations with abrasive environment, oil, grease, gasoline andother chemical agents contaminated ambient. Its reduced diameter permitsan optimum utilization of ducts or sites where is installed.

Standards

CENTELSA TFFN wires and cables are manufactured under the followingstandards:

UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables andFlexible CordsUL 62, NTC-2356 Flexible Cord and Fixture Wire

Cables Type TFFNThermoplastic Insulation, Flexible Fixture Wire, Nylon Jacket

Page 25: Flexible cords

31

ColorsBlack, white, red, yellow, blue.

Packaging100 m spools covered with plastic thermo pack, in corrugated carton boxes.

Note: Other configurations, sizes, colors and length not specified herein are availableupon request.

Page 26: Flexible cords

32

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity.2. Ampacities based on 60°C conductor temperature, and Section 400 of NEC (NTC 2050) and 30°C ambient temperature.3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Cable Type TFFN 600V (International System Units)Thermoplastic Insulation, Fixture Wire, Nylon Jacket (90° C)

Standard: UL 62, NTC-2356. Flexible Cord and Fixture Wire.

0.380.38

0.2540.254

1626

0.811.32

1.231.51

0.100.10

2.062.36

1117

21.413.4

2.292.59

68

1816

STRANDSSIZEAWG

STRANDDIAMETER

(mm)

SECTION(mm2)

INSULATIONTHICKNESS

(mm)

JACKETTHICKNESS

(mm)

DIAMETEROVER

JACKET(mm)

DCRESISTANCE

AT 20°C 1(ohm/km)

APPROX.TOTAL

WEIGHT(kg/km)

AMPACITY 2

(A)CONDUCTOR

DIAMETER(mm)

DIAMETEROVER

INSULATION(mm)

Cable Type TFFN 600V, 90°CThermoplastic Insulation, Fixture Wire, Nylon Jacket

Standard: UL 62, NTC-2356. Flexible Cord and Fixture Wire.

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity.2. Ampacities based on 60°C conductor temperature, and Section 400 of NEC (NTC 2050) and 30°C ambient temperature.3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

1515

10.010.0

1626

1.602.60

4859

44

8193

811

6.514.10

90102

68

1816

STRANDSSIZEAWG

STRANDDIAMETER

(mils)

SECTION(kcmil)

INSULATIONTHICKNESS

(mils)

JACKETTHICKNESS

(mils)

DIAMETEROVER

JACKET(mm)

DCRESISTANCE

AT 20°C 1(ohm/kft)

APPROX.TOTAL

WEIGHT(lb/kft)

AMPACITY 2

(A)CONDUCTOR

DIAMETER(mils)

DIAMETEROVER

INSULATION(mils)

Page 27: Flexible cords

33

Description

Soft copper flexible conductor PVC insulated.

Construction

ConductorFlexible soft copper conductor, Class K stranded

InsulationFlame Retardant Polyvinyl chloride (PVC 105° C)

Characteristics

Operating Temperature105° C.

Operating Voltage600 V.

Applications

Lighting connections and high temperature applications.

Specifications

CENTELSA LIGHTING Cables are manufactured under the following standards:UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and FlexibleCordsUL 83, NTC-1332 Thermoplastic insulated Wires and CablesUL 62, NTC-2356 Flexible Cord and Fixture Wire (Sizes 20 to 16 AWG)CENTELSA Specifications for LIGHTING Cables

ColorsBlack, white, red, yellow, blue.

Lighting Cables

Page 28: Flexible cords

34

Packaging100 m spools covered with plastic thermo pack, in corrugated carton boxes.

Note: Other configurations, sizes, colors and length not specified herein areavailable upon request.

Page 29: Flexible cords

35

Lighting Cables 105°C (International System Units)

Standard: UL 62, NTC 2356. Flexible and Fixture WireUL 83, NTC-1332 Thermoplastic insulated Wires and CablesCENTELSA Specifications for LIGHTING Cables

Lighting Cables 105°C

Standard: UL 62, NTC 2356. Flexible and Fixture WireUL 83, NTC-1332 Thermoplastic insulated Wires and CablesCENTELSA Specifications for LIGHTING Cables

0.760.760.760.760.760.761.141.52

0.2540.2540.2540.2540.2540.2540.2540.254

1016264165

104168266

0.510.811.322.083.295.278.51

13.48

0.971.231.511.982.523.213.664.12

2.232.492.773.243.784.475.526.58

34.721.713.38.465.343.342.071.30

9131826395996

152

201816141210

86

STRANDSSIZEAWG

STRANDDIAMETER

(mm)

SECTION(mm2)

INSULATIONTHICKNESS

(mm)

DIAMETEROVER

INSULATION(mm)

DCRESISTANCE

AT 20°C 1(ohm/km)

APPROX.TOTAL

WEIGHT(kg/km)

CONDUCTORDIAMETER

(mm)

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity.2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

3030303030304560

10.010.010.010.010.010.010.010.0

1016264165

104168266

1.001.602.604.106.50

10.4016.8026.60

3848597899

126144162

8898

109128149176217259

10.66.64.1

2.581.631.020.630.40

68

1218264065

102

201816141210

86

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity.2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

STRANDSSIZEAWG

STRANDDIAMETER

(mils)

SECTION(kcmil)

INSULATIONTHICKNESS

(mils)

DIAMETEROVER

INSULATION(mils)

DCRESISTANCE

AT 20°C 1(ohm/kft)

APPROX.TOTAL

WEIGHT(lb/kft)

CONDUCTORDIAMETER

(mils)

Page 30: Flexible cords

36

Description

Soft copper flexible conductor XLPE insulated.

Construction

ConductorFlexible soft copper conductor, Class K stranded

InsulationFlame retardant Black Cross Linked Polyethylene (XLPE 125°C)

Characteristics

Operating Temperature125° C.

Applications

Used generally in internal equipment and board wiring. Installation in ductsor raceways. High temperature applications. Also used in automotive lowvoltage wiring. Insulation resistant to abrasion, gasoline, oil, solvents andchemical agents.

Specifications

CENTELSA XGW Cables are manufactured under the followingstandards:UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables andFlexible CordsCENTELSA Specifications for XGW Cables

Cables Type XGWCross (X) Linked Polyethylene Insulated 125°C, General Purpose Wire

Page 31: Flexible cords

37

Packaging100 m spools covered with plastic thermo pack, in corrugated carton boxes.

Note: Other configurations, sizes, colors and length not specified herein are availableupon request.

Page 32: Flexible cords

Cables Type XGW 600V, 125°C (International System Units)Cross (X) Linked Polyethylene Insulated 125°C, General Purpose Wire

Standard: CENTELSA Specifications for XGW Cables

Cables Type XGW 600V, 125°CCross (X) Linked Polyethylene Insulated 125°C, General Purpose Wire

Standard: CENTELSA Specifications for XGW Cables

0.740.760.810.890.941.041.09

0.2540.2540.2540.2540.2540.2540.254

1016264165

104168

0.510.811.322.083.295.278.51

0.971.231.511.982.523.213.66

2.192.492.853.444.064.915.42

34.721.713.38.465.343.342.07

9131828416495

201816141210

8

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity.2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

29303235374143

10.010.010.010.010.010.010.0

1016264165

104168

1.001.602.604.106.50

10.4016.80

3848597899

126144

8495

110133157191211

10.66.614.072.581.631.02

0.630

68

1219284364

201816141210

8

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity.2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

38

STRANDSSIZEAWG

STRANDDIAMETER

(mm)

SECTION(mm2)

INSULATIONTHICKNESS

(mm)

DIAMETEROVER

INSULATION(mm)

DCRESISTANCE

AT 20°C 1(ohm/km)

APPROX.TOTAL

WEIGHT(kg/km)

CONDUCTORDIAMETER

(mm)

STRANDSSIZEAWG

STRANDDIAMETER

(mils)

SECTION(kcmil)

INSULATIONTHICKNESS

(mils)

DIAMETEROVER

INSULATION(mils)

DCRESISTANCE

AT 20°C 1(ohm/kft)

APPROX.TOTAL

WEIGHT(lb/kft)

CONDUCTORDIAMETER

(mils)

Page 33: Flexible cords

39

Description

Soft tinned copper flexible conductor Thermoset Elastomer insulated.

Construction

ConductorFlexible tinned soft copper conductor, Class K stranded

InsulationBlack Thermoset Elastomer Flame retardant (XLPE 150°C)

Characteristics

Operating Temperature150° C.

Applications

Used generally in internal equipment and board wiring. Installation in ductsor raceways, transit zones, high temperature applications. Also used inautomotive low voltage wiring.Flexible insulation, low smoke emissions, non halogenated, lead free andexcellent thermal stability.

Specifications

CENTELSA HTS-C Cables are manufactured under the followingstandards:UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables andFlexible CordsCENTELSA Specifications for HTS-C Cables

Cables Type HTS-CHeavy Duty Thermoset Elastomer (Synthetic Rubber) Insulated 150°C, C: Common use

Page 34: Flexible cords

Packaging100 m spools covered with plastic thermo pack, in corrugated carton boxes.

Note: Other configurations, sizes, colors and length not specified herein areavailable upon request.

40

Page 35: Flexible cords

41

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity.2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Cables Type HTS-C 600V, 150°CHeavy Duty Thermoset Elastomer (Synthetic Rubber) Insulated 150°C, C: Common use

Standard: CENTELSA Specifications for HTS-C Cables

0.730.790.820.900.901.101.191.271.291.291.291.291.541.54

0.2540.2540.2540.2540.2540.2540.2540.2540.2540.2540.2540.2540.2540.254

16264165

104168266420665836

1064132316662107

0.811.322.083.295.278.51

13.4821.2833.7042.3653.9167.0484.42

106.76

1.231.511.982.523.213.664.126.728.589.77

11.1012.4714.1015.97

2.773.173.704.425.115.946.609.36

11.2612.4513.7815.1517.3019.17

22.613.9

8.85.63.52.11.40.90.50.40.30.30.20.2

1420294465

101151239365451564691878

1094

1816141210

86421

1/02/03/04/0

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity.2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

2931323636434750515151516161

10.010.010.010.010.010.010.010.010.010.010.010.010.010.0

16264165

104168266420665836

1064132316662107

1.602.604.106.50

10.4016.8026.6042.0066.5083.60

106.40132.30166.60210.70

48597899

126144162265338385437491555629

109125146174201234260369443490543596681755

6.94.232.681.691.060.650.410.260.160.130.100.080.060.05

91420304468

102161245303379464590735

1816141210

86421

1/02/03/04/0

Cables Type HTS-C 600V, 150°C (International System Unit)Heavy Duty Thermoset Elastomer (Synthetic Rubber) Insulated 150°C, C: Common use

Standard: CENTELSA Specifications for HTS-C Cables

STRANDSSIZEAWG

STRANDDIAMETER

(mm)

SECTION(mm2)

INSULATIONTHICKNESS

(mm)

DIAMETEROVER

INSULATION(mm)

DCRESISTANCE

AT 20°C 1(ohm/km)

APPROX.TOTAL

WEIGHT(kg/km)

CONDUCTORDIAMETER

(mm)

STRANDSSIZEAWG

STRANDDIAMETER

(mils)

SECTION(kcmil)

INSULATIONTHICKNESS

(mils)

DIAMETEROVER

INSULATION(mils)

DCRESISTANCE

AT 20°C 1(ohm/kft)

APPROX.TOTAL

WEIGHT(lb/kft)

CONDUCTORDIAMETER

(mils)

Page 36: Flexible cords

42

Description

Soft copper flexible conductor PVC insulated.

Construction

ConductorFlexible soft copper conductor, Class K stranded

InsulationFlame Retardant Polyvinyl chloride (PVC 75° C)

Characteristics

Operating Temperature75° C.

Operating Voltage50 V.

Applications

Low voltage automotive wiring. Insulation resistant to abrasion gasolineand oil.

Specifications

CENTELSA GPT Cables are manufactured under the followingstandards:UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables andFlexible CordsSAE J1128 NTC-1116 Primary Low Voltage Cables

ColorsBlack, white, red, yellow, blue, brown, orange grey and violet.

Automotive CablesType GPTGeneral Purpose Thermoplastic Insulated

Page 37: Flexible cords

43

Packaging100 m spools covered with plastic thermo pack, in corrugated carton boxes.

Note: Other configurations, sizes, colors and length not specified herein are availableupon request.

Page 38: Flexible cords

44

Automotive Cables Type GPT 50V, 75°C(International System Units)General Purpose Thermoplastic Insulated

Standard: SAE J1128 NTC-1116, Primary Low Voltage Cables

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity.2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Automotive Cables Type GPT 50V, 75°CGeneral Purpose Thermoplastic Insulated

Standard: SAE J1128 NTC-1116, Primary Low Voltage Cables

0.580.580.580.580.580.660.790.94

0.2540.2540.2540.2540.2540.2540.2540.254

71016264165

104168

0.350.510.811.322.083.295.278.51

0.760.971.231.511.982.523.213.66

1.761.972.232.512.983.624.515.20

49.634.721.713.38.465.343.342.07

68

111624385993

22201816141210

8

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity.2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

2323232323263137

10.010.010.010.010.010.010.010.0

71016264165

104168

0.701.001.602.604.106.50

10.4016.80

303848597899

126144

69788899

117143178205

15.110.66.614.072.581.631.02

0.630

458

1116254062

22201816141210

8

STRANDSSIZEAWG

STRANDDIAMETER

(mm)

SECTION(mm2)

INSULATIONTHICKNESS

(mm)

DIAMETEROVER

INSULATION(mm)

DCRESISTANCE

AT 20°C 1(ohm/km)

APPROX.TOTAL

WEIGHT(kg/km)

CONDUCTORDIAMETER

(mm)

STRANDSSIZEAWG

STRANDDIAMETER

(mils)

SECTION(kcmil)

INSULATIONTHICKNESS

(mils)

DIAMETEROVER

INSULATION(mils)

DCRESISTANCE

AT 20°C 1(ohm/kft)

APPROX.TOTAL

WEIGHT(lb/kft)

CONDUCTORDIAMETER

(mils)

Page 39: Flexible cords

45

Description

Soft copper flexible conductor PVC insulated.

Construction

ConductorFlexible soft copper conductor, Class K stranded

InsulationFlame Retardant Polyvinyl chloride (PVC 75° C)

Characteristics

Operating Temperature75° C.

Operating Voltage50 V.

Applications

Low voltage automotive wiring where the reduced diameter offers an optimumutilization of site in which is installed. Insulation resistant to abrasion gasolineand oil.

Specifications

CENTELSA TWP Cables are manufactured under the following standards:UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and FlexibleCordsSAE J1128 NTC-1116 Primary Low Voltage Cables

ColorsBlack, white, red, yellow, blue, brown, orange grey and violet.

Automotive CablesType TWPThin Wall, Thermo Plastic Insulated

Page 40: Flexible cords

Packaging100 m spools covered with plastic thermo pack, in corrugated carton boxes.

Note: Other configurations, sizes, colors and length not specified herein areavailable upon request.

46

Page 41: Flexible cords

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity.2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Automotive Cable Type TWP 50V, 75°CThin Wall, ThermoPlastic Insulated

Standard: SAE J1128 NTC-1116, Primary Low Voltage Cables

0.400.400.400.400.400.450.500.55

0.2540.2540.2540.2540.2540.2540.2540.254

71016264165

104168

0.350.510.811.322.083.295.278.51

0.760.971.231.511.982.523.213.66

1.441.651.912.192.663.324.074.58

49.634.721.713.38.465.343.342.07

57

101522355586

22201816141210

8

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity.2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

1616161616182022

10.010.010.010.010.010.010.010.0

71016264165

104168

0.701.001.602.604.106.50

10.4016.80

303848597899

126144

55637384

103127157178

15.110.66.614.072.581.631.02

0.630

347

1015243758

22201816141210

8

Automotive Cable Type TWP 50V, 75°C(Internacional System Units)Thin Wall, ThermoPlastic Insulated

Standard: SAE J1128 NTC-1116, Primary Low Voltage Cables

47

STRANDSSIZEAWG

STRANDDIAMETER

(mm)

SECTION(mm2)

INSULATIONTHICKNESS

(mm)

DIAMETEROVER

INSULATION(mm)

DCRESISTANCE

AT 20°C 1(ohm/km)

APPROX.TOTAL

WEIGHT(kg/km)

CONDUCTORDIAMETER

(mm)

STRANDSSIZEAWG

STRANDDIAMETER

(mils)

SECTION(kcmil)

INSULATIONTHICKNESS

(mils)

DIAMETEROVER

INSULATION(mils)

DCRESISTANCE

AT 20°C 1(ohm/kft)

APPROX.TOTAL

WEIGHT(lb/kft)

CONDUCTORDIAMETER

(mils)

Page 42: Flexible cords

48

Description

Soft copper flexible conductor PVC insulated.

Construction

ConductorFlexible soft copper conductor, Class K stranded

InsulationFlame Retardant Polyvinyl chloride (PVC 75° C)

Characteristics

Operating Temperature75° C.

Operating Voltage50 V.

Applications

SGT cables are used to connect the system of engine Start-up. Insulationis resistant to abrasion, gasoline, oil, solvents and chemical agents.

Specifications

CENTELSA SGT Cables are manufactured under the following standards:UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables andFlexible CordsSAE J1127 NTC-1955 Battery Cables

Starter or Ground, General Purpose Thermoplastic Insulated

Automotive Cables Type SGT.Battery Cable

Page 43: Flexible cords

49

PackagingWood reels or spools upon request.

Note: Other configurations, sizes, colors and length not specified herein areavailable upon request.

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity.2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Automotive Cables Type SGT 50V, 75°CStarter or Ground, General Purpose Thermoplastic Insulated

Standard: SAE J1127 NTC-1955. Battery Cables

1.521.651.651.651.651.651.981.98

0.2540.2540.2540.2540.2540.2540.2540.254

266420665836

1064132316662107

13.4821.2833.7042.3653.9167.0484.42

106.76

4.126.728.589.77

11.1012.4714.1015.97

6.589.40

11.2612.4513.7815.1517.3019.17

1.300.8260.5220.4150.3260.2620.2080.165

152243368454568697886

1105

6421

1/02/03/04/0

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity.2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

6065656565657878

10.010.010.010.010.010.010.010.0

266420665836

1064132316662107

26.6042.0066.5083.60

106.40132.30166.60210.70

162265338385437491555629

259370443490543596681755

0.3980.2520.1590.127

0.09940.08000.06350.0502

102163247305382469595742

6421

1/02/03/04/0

Automotive Cables Type SGT 50V, 75°C (International System Unit)Starter or Ground, General Purpose Thermoplastic Insulated

Standard: SAE J1127 NTC-1955. Battery Cables

STRANDSSIZEAWG

STRANDDIAMETER

(mm)

SECTION(mm2)

INSULATIONTHICKNESS

(mm)

DIAMETEROVER

INSULATION(mm)

DCRESISTANCE

AT 20°C 1(ohm/km)

APPROX.TOTAL

WEIGHT(kg/km)

CONDUCTORDIAMETER

(mm)

STRANDSSIZEAWG

STRANDDIAMETER

(mils)

SECTION(kcmil)

INSULATIONTHICKNESS

(mils)

DIAMETEROVER

INSULATION(mils)

DCRESISTANCE

AT 20°C 1(ohm/kft)

APPROX.TOTAL

WEIGHT(lb/kft)

CONDUCTORDIAMETER

(mils)

Page 44: Flexible cords

50

Description

Soft copper flexible conductor XLPE insulated.

Construction

ConductorFlexible soft copper conductor, Class K stranded

InsulationFlame retardant Cross Linked Polyethylene (XLPE 125°C)

Characteristics

Operating Temperature125° C.

Operating Voltage50 V.

Applications

Low voltage automotive, special for vane motor. Applications whereheavy duty requires more than GPT cables. Insulation resistant toabrasion gasoline and oil.

Specifications

CENTELSA SXL Cables are manufactured under the following standards:UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables andFlexible CordsSAE J1128 NTC-1116 Primary Low Voltage Cables

ColorsBlack, red, orange

Automotive CablesType SXLSpecial Purpose, Cross (X) Linked Polyethylene Insulated

Page 45: Flexible cords

51

Packaging100 m spools covered with plastic thermo pack, in corrugated carton boxes.

Note: Other configurations, sizes, colors and length not specified herein areavailable upon request.

Page 46: Flexible cords

52

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity.2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Automotive Cables Type SXL 50V, 75°CSpecial Purpose, Cross (X) Linked Polyethylene Insulated

Standard: SAE J1128 NTC-1116, Primary Low Voltage Cables

0.740.760.810.890.941.041.09

0.2540.2540.2540.2540.2540.2540.254

1016264165

104168

0.510.811.322.083.295.278.51

0.971.231.511.982.523.213.66

2.192.492.853.444.064.915.42

34.721.713.38.465.343.342.07

9131828416495

201816141210

8

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity.2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

29303235374143

10.010.010.010.010.010.010.0

1016264165

104168

1.001.602.604.106.50

10.4016.80

3848597899

126144

8495

110133157191211

10.66.614.072.581.631.02

0.630

68

1219284364

201816141210

8

Automotive Cables Type SXL 50V, 75°C(International System Unit)Special Purpose, Cross (X) Linked Polyethylene Insulated

Standard: SAE J1128 NTC-1116, Primary Low Voltage Cables

STRANDSSIZEAWG

STRANDDIAMETER

(mm)

SECTION(mm2)

INSULATIONTHICKNESS

(mm)

DIAMETEROVER

INSULATION(mm)

DCRESISTANCE

AT 20°C 1(ohm/km)

APPROX.TOTAL

WEIGHT(kg/km)

CONDUCTORDIAMETER

(mm)

STRANDSSIZEAWG

STRANDDIAMETER

(mils)

SECTION(kcmil)

INSULATIONTHICKNESS

(mils)

DIAMETEROVER

INSULATION(mils)

DCRESISTANCE

AT 20°C 1(ohm/kft)

APPROX.TOTAL

WEIGHT(lb/kft)

CONDUCTORDIAMETER

(mils)

Page 47: Flexible cords

53

Description

Soft copper flexible conductor Silicon Rubber insulated.

Construction

ConductorFlexible soft copper conductor, Class K stranded

InsulationSilicon Rubber natural color (Beige)

Characteristics

Operation Temperature200° C.Operating Voltage600 V.

Applications

High temperature applications like motors wiring, internal wiring of luminaries,ballast, dryers, ovens, freezers, coolersExcellent insulation performance at high temperatures

Specifications

CENTELSA SF Cables are manufactured under the following standards:UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and FlexibleCordsUL 62, NTC-2356 Flexible Cord and Fixture Wire

Silicon Cables Type SFSilicon Insulated Flexible

Page 48: Flexible cords

54

Packaging100 m spools covered with plastic thermo pack, in corrugated carton boxes.

Note: Other configurations, sizes, colors and length not specified hereinare available upon request.

Silicon Cable Type SF 600V, 200°CSilicon Insulated Flexible

Standard: UL 62, NTC-2356. Flexible and Fixture Wire

3030303030

10.010.010.010.010.0

16264165

104

1.602.604.106.50

10.40

48597899

126

111122141162189

6.614.072.581.631.02

913182740

1816141210

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity.2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

Silicon Cable Type SF 600V, 200°C(International System Unit)Silicon Insulated Flexible

Standard: UL 62, NTC-2356. Flexible and Fixture Wire

0.760.760.760.760.76

0.2540.2540.2540.2540.254

16264165

104

0.811.322.083.295.27

1.231.511.982.523.21

2.833.113.584.124.81

21.713.38.465.343.34

1319274060

1816141210

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity.2. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

STRANDSSIZEAWG

STRANDDIAMETER

(mm)

SECTION(mm2)

INSULATIONTHICKNESS

(mm)

DIAMETEROVER

INSULATION(mm)

DCRESISTANCE

AT 20°C 1(ohm/km)

APPROX.TOTAL

WEIGHT(kg/km)

CONDUCTORDIAMETER

(mm)

STRANDSSIZEAWG

STRANDDIAMETER

(mils)

SECTION(kcmil)

INSULATIONTHICKNESS

(mils)

DIAMETEROVER

INSULATION(mils)

DCRESISTANCE

AT 20°C 1(ohm/kft)

APPROX.TOTAL

WEIGHT(lb/kft)

CONDUCTORDIAMETER

(mils)

Page 49: Flexible cords

55

Description

Soft copper flexible conductor with Elastomer Thermoplastic insulation

Construction

ConductorFlexible soft copper conductor, Class K stranded

InsulationFlame Retardant Black Elastomer Thermoplastic i(TPR 105°C)

Characteristics

Operation Temperature105° C.Operating Voltage600 V.

Applications

Extra hard service Cable, flexible and resistant to heavy-duty, for electricwelding equipments.Insulation: Rough handling, abrasion and spark welding resistant.

Specifications

CENTELSA SF Cables are manufactured under the following standards:UL 1581, NTC-3203 Reference Standard for Electrical Wires, Cables and FlexibleCordsUL 62, NTC-2356 Flexible Cord and Fixture Wire

Welding Cable

Page 50: Flexible cords

Packaging100 m spools covered with plastic thermo pack, in corrugated carton boxes.

Note: Other configurations, sizes, colors and length not specified hereinare available upon request.

56

Page 51: Flexible cords

Notes: 1. DC Resistance calculated based on a 17.241 ohm-mm2/km copper resistivity.2. Ampacity based on 5 minutes working cycles and 80% Load Factor.3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

WELDING Cable 600V, 105oC

Standard: BS 638. Arc welding power coerces equipment and accessories.CENTELSA Specifications for HTS-C Cables

0.2540.2540.2540.2540.2540.2540.2540.2540.2540.2540.254

266420665836

1064132316662107249929893458

13.4821.2833.7042.3653.9167.0484.42

106.76126.63151.45175.22

4.126.728.589.77

11.1012.4714.1015.9717.4019.0220.61

2.002.002.002.202.402.402.602.802.803.003.20

168258389487616756947

1189139016581933

1.300.8260.5220.4150.3260.2620.2080.1650.1390.1160.100

125170232270318369431505566639705

6421

1/02/03/04/0

250300350

8.2810.8812.7414.3116.0417.4119.4621.7323.1625.2027.21

Welding Cable 600V, 105oC (International System Units)

Standard: BS 638. Arc welding power coerces equipment and accessories.CENTELSA Specifications for HTS-C Cables

Notes: 1. DC Resistance calculated based on a 10.371 ohm-cmil/ft copper resistivity.2. Ampacity based on 5 minutes working cycles and 80% Load Factor.3. Values herein indicated are approximated and are subject to normal manufacturing tolerances.

10.010.010.010.010.010.010.010.010.010.010.0

266420665836

1064132316662107249929893458

26.6042.0066.5083.60

106.40132.30166.60210.70249.90298.90345.81

162265338385437491555629685749811

797979879494

102110110118126

113174261327414508636799934

11141299

0.3980.2520.1590.127

0.09940.08000.06350.05020.04230.03540.0306

125170232270318369431505566639705

6421

1/02/03/04/0

250300350

326428502563631685766856912992

1071

57

STRANDSSIZEAWG

STRANDDIAMETER

(mm)

SECTION(mm2)

INSULATIONTHICKNESS

(mm)

DIAMETEROVER

INSULATION(mm)

DCRESISTANCE

AT 20°C 1(ohm/km)

APPROX.TOTAL

WEIGHT(kg/km)

CONDUCTORDIAMETER

(mm)

STRANDSSIZEAWG

STRANDDIAMETER

(mils)

SECTION(kcmil)

INSULATIONTHICKNESS

(mils)

DIAMETEROVER

INSULATION(mils)

DCRESISTANCE

AT 20°C 1(ohm/kft)

APPROX.TOTAL

WEIGHT(lb/kft)

CONDUCTORDIAMETER

(mils)

AMPACITY 2(A)