First Revision No. 226-NFPA 2-2013 [ Global Input ] With this revision cycle, NFPA 2 is the primary source for hydrogen fueling applications. NFPA 52 no longer contains requirements for compressed or liquified hydrogen fueling. All extract tags in Chapters 10 and 11 and associated annex material for NFPA 52 should be removed. Also delete all of the bracketed text, as NFPA 2 is now the primary source for this material. Extract tags for Chapter 3, definitions, have been reviewed on a case-by-case basis. Submitter Information Verification Submitter Full Name: Susan Bershad Organization: National Fire Protection Assoc Street Address: City: State: Zip: Submittal Date: Fri Jun 28 10:45:34 EDT 2013 Committee Statement Committee Statement: With this revision cycle, NFPA 2 is the primary source for fueling applications. NFPA 52 no longer contains requirements for compressed or liquified hydrogen fueling. All extract tags in Chapters 10 and 11 for NFPA 52 should be removed. Also delete all of the bracketed text, as NFPA 2 is now the primary source for this material. Extract tags for Chapter 3, definitions, have been reviewed on a case-by-case basis. Response Message: National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... 1 of 491 1/30/2014 9:30 AM

First Revision No. 226-NFPA 2-2013 [ Global Input ] · ANSI A13.1, Scheme for Identification of Piping Systems,1996 2007 . ... ANSI Z535.1, Safety Color Code, 2006. ANSI Z535.2, Environmental

  • Upload
    lamtram

  • View
    220

  • Download
    5

Embed Size (px)

Citation preview

First Revision No. 226-NFPA 2-2013 [ Global Input ]

With this revision cycle, NFPA 2 is the primary source for hydrogen fueling applications. NFPA 52no longer contains requirements for compressed or liquified hydrogen fueling. All extract tags inChapters 10 and 11 and associated annex material for NFPA 52 should be removed. Also delete allof the bracketed text, as NFPA 2 is now the primary source for this material. Extract tags forChapter 3, definitions, have been reviewed on a case-by-case basis.

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 10:45:34 EDT 2013

Committee Statement

CommitteeStatement:

With this revision cycle, NFPA 2 is the primary source for fueling applications. NFPA 52 no longercontains requirements for compressed or liquified hydrogen fueling. All extract tags in Chapters 10and 11 for NFPA 52 should be removed. Also delete all of the bracketed text, as NFPA 2 is now theprimary source for this material. Extract tags for Chapter 3, definitions, have been reviewed on acase-by-case basis.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

1 of 491 1/30/2014 9:30 AM

First Revision No. 524-NFPA 2-2013 [ Global Input ]

Drop all extract tags from NFPA 55 in Chapter 13, Hydrogen Generation. This material will no longerbe in NFPA 55. NFPA 2 will have primacy for this material in the 2016 edition. The only exception tothis will be in A.13.2.1, which should still have the 55 extract tag.

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 18 08:47:17 EST 2013

Committee Statement

CommitteeStatement:

NFPA 2 to have primacy for this material in the 2016 edition. This material is being deletedfrom NFPA 55.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

2 of 491 1/30/2014 9:30 AM

First Revision No. 164-NFPA 2-2013 [ Section No. 2.3.1 ]

2.3.1 AIHA Publications.

American Industrial Hygiene Association, 2700 Prosperity Avenue, Suite 250, Fairfax, VA 22031-4319.

AIHA Z9.5, Laboratory Ventilation, 2003 2012 .

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 07:56:16 EDT 2013

Committee Statement

Committee Statement: Updated to current edition

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

3 of 491 1/30/2014 9:30 AM

First Revision No. 165-NFPA 2-2013 [ Section No. 2.3.2 ]

2.3.2 ANSI Publications.

American National Standards Institute, Inc., 25 West 43rd Street, 4th Floor, New York, NY 10036.

ANSI A13.1, Scheme for Identification of Piping Systems,1996 2007 .

ANSI/IAS NGV 4.4 Breakaway Devices for Dispensing Systems, 1999 Edition.

ANSI C2, National Electrical Safety Code, 2007 2012 .

ANSI/CSA FC 1, American National Standard for Fuel Cell Power Systems,2004 2012 .

ANSI/CSA FC 3, American National Standard/CSA American Standard for Portable Fuel Cell PowerSystems, 2004 .

ANSI Z535.1, Safety Color Code, 2006.

ANSI Z535.2, Environmental and Facility Safety Signs, 2007 2011 .

ANSI Z535.3, Criteria for Safety Symbols, 2007 2011 .

ANSI Z535.4, Product Safety Signs and Labels, 2007 2011 .

ANSI Z9.5, Laboratory Ventilation, 2003 2011 .

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 08:02:45 EDT 2013

Committee Statement

Committee Statement: Updated to current editions

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

4 of 491 1/30/2014 9:30 AM

First Revision No. 6-NFPA 2-2013 [ Section No. 2.3.3 ]

2.3.3 ASME Publications.

American Society of Mechanical Engineers, Three Two Park Avenue, New York, NY 10016-5990.

ASME A13.1, Scheme for the Identification of Piping Systems, 2007.

ASME B31.3, Process Piping, 2006 2012 .

ASME B31.12, Hydrogen Piping and Pipelines , 2011.

ASME Boiler and Pressure Vessel Code, Section VIII, 2004 2013 .

ASME International, Boiler and Pressure Vessel Code, “Rules for the Construction of Unfired PressureVessels,” Section VIII, 2007 2013 .

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jun 04 10:36:10 EDT 2013

Committee Statement

CommitteeStatement:

Add references to B31 Code for Pressure Piping and B31.12 Hydrogen Piping andPipelines, 2011

Response Message:

Public Input No. 87-NFPA 2-2012 [Section No. 2.3.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

5 of 491 1/30/2014 9:30 AM

First Revision No. 166-NFPA 2-2013 [ Section No. 2.3.4 ]

2.3.4 ASTM Publications.

American Society for Testing and Materials, 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959.

ASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials, 2009 2013 .

ASTM E 681-01, Code Test Method for Concentration Limits of Flammability of Chemicals (Vapors andGases) , 2004.

ASTM E 1529, Determining Effects of Large Hydrocarbon Pool Fire on Structural Members andAssemblies, 2006 2010 .

ASTM E 1591, Standard Guide for Data for Fire Models, 2013 .

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 08:07:16 EDT 2013

Committee Statement

Committee Statement: Updated to current editions.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

6 of 491 1/30/2014 9:30 AM

First Revision No. 167-NFPA 2-2013 [ Section No. 2.3.5 ]

2.3.5 CGA Publications.

Compressed Gas Association, 4221 Walney Road, 5th Floor 14501 George Carter Way, Suite 103,Chantilly, VA 20151-2923.

CGA C-7, Guide to the Preparation of Precautionary Labeling and Marking of Compressed GasContainers, 2004 2011 .

CGA G-4.1, Cleaning Equipment for Oxygen Service , 2009.

CGA G-5.5, Hydrogen Vent Systems, 2004 2007 .

CGA P-1, Safe Handling of Compressed Gases in Containers, 2008.

CGA P-23, Standard for Categorizing Gas Mixtures Containing Flammable and NonflammableComponents , 2008.

CGA S-1.1, Pressure Relief Device Standards — Part 1 — Cylinders for Compressed Gases, 2011 .

CGA S-1.2, Pressure Relief Device Standards — Part 2 — Cargo and Portable Tanks for CompressedGases, 2009.

CGA S-1.3, Pressure Relief Device Standards — Part 3 — Stationary Storage Containers for CompressedGases, 2008.

CGA H-1, Service Conditions for Portable, Reversible Hydride Systems, 2004.

CGA H-2, Guidelines for The Classification and Labeling of Hydrogen Storage Systems with HydrogenAbsorbed in Reversible Metal Hydrides, 2004.

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 08:10:11 EDT 2013

Committee Statement

Committee Statement: Updated to current editions.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

7 of 491 1/30/2014 9:30 AM

First Revision No. 168-NFPA 2-2013 [ Section No. 2.3.7 ]

2.3.7 ICC Publications.

International Code Council, 5203 Leesburg Pike, Suite 600, Falls Church, VA 22041.

IFC 5303.16, International Fire Code , Compressed Gases, 2012.

IFGC, International Fuel Gas Code (IFGC) , 2006 2012 .

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 08:21:46 EDT 2013

Committee Statement

Committee Statement: Updated to current editions.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

8 of 491 1/30/2014 9:30 AM

First Revision No. 169-NFPA 2-2013 [ Section No. 2.3.8 ]

2.3.8 IAPMO Publications.

International Association of Plumbing and Mechanical Officials, 5001 E. Philadelphia Street, Ontario, CA91761.

Uniform Mechanical Code , 2003 edition.

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 08:22:17 EDT 2013

Committee Statement

Committee Statement: Updated to current editions.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

9 of 491 1/30/2014 9:30 AM

First Revision No. 7-NFPA 2-2013 [ Section No. 2.3.9 ]

2.3.9 ISO Publications.

International Organization for Codeization Publications, 1 rue de Varembé, Case Postale 56, CH-1211Geneve 20, Switzerland.

ISO 10156, Gases and gas mixtures — Determination of Fire Potential and Oxidizing Ability for theSelection of Cylinder Valve Outlets , 1996.

ISO 10298, Determination of Toxicity of a Gas or Gas Mixture , 1995.

ISO/DIS 22734–1, Hydrogen generators using water electrolysis process — Part 1: Industrial andcommercial applications .

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jun 04 10:47:11 EDT 2013

Committee Statement

Committee Statement: Electrolysis standards are released and referenced by proposals/annex text in Chapter 13

Response Message:

Public Input No. 88-NFPA 2-2012 [Section No. 2.3.9]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

10 of 491 1/30/2014 9:30 AM

First Revision No. 170-NFPA 2-2013 [ Section No. 2.3.10 ]

2.3.10 NSF Publication.

National Sanitation Foundation International, 789 North Dixboro Road, P.O. Box 130140, Ann Arbor, MI48113-1040.

NSF/ANSI 49, Class II (Laminar Flow) Biosafety Cabinetry , 2007.

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 08:51:50 EDT 2013

Committee Statement

Committee Statement: Updated to current editions.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

11 of 491 1/30/2014 9:30 AM

First Revision No. 171-NFPA 2-2013 [ Section No. 2.3.11 ]

2.3.8 SAE Publications.

Society of Automotive Engineers, 400 Commonwealth Drive, Warrendale, PA 15096, www.SAE.org.

SAE J2600, Compressed Hydrogen Surface Refueling Connection Devices, 2002 2012 .

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 08:52:31 EDT 2013

Committee Statement

Committee Statement: Updated to current editions.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

12 of 491 1/30/2014 9:30 AM

First Revision No. 470-NFPA 2-2013 [ Section No. 2.4 ]

2.4 References for Extracts in Mandatory Sections.

NFPA 1, Fire Code, 2009 2012 edition.

NFPA 13, Standard for the Installation of Sprinkler Systems, 2010 2013 edition.

NFPA 30, Flammable and Combustible Liquids Code, 2008 2012 edition.

NFPA 30A, Code for Motor Fuel Dispensing Facilities and Repair Garages, 2008 2012 edition.

NFPA 45, Standard on Fire Protection for Laboratories Using Chemicals, 2011 edition.

NFPA 52, Vehicular Gaseous Fuel Systems Code, 2010 2013 edition.

NFPA 54, National Fuel Gas Code, 2009 2012 edition.

NFPA 55, Compressed Gases and Cryogenic Fluids Code, 2010 2013 edition.

NFPA 58, Liquefied Petroleum Gas Code, 2011 2014 edition.

NFPA 70®, National Electrical Code®, 2011 2014 edition.

NFPA 80, Standard for Fire Doors and Other Opening Protectives, 2010 2013 edition.

NFPA 86, Standard for Ovens and Furnaces, 2011 edition.

NFPA 88A, Standard for Parking Structures, 2011 edition.

NFPA 88B, Standard for Repair Garages, 1997 edition.

NFPA 91, Standard for Exhaust Systems for Air Conveying of Vapors, Gases, Mists, and NoncombustibleParticulate Solids, 2010 edition.

NFPA 99, Standard for Health Care Facilities, 2005 edition.

NFPA NFPA 101®, Life Safety Code®, 2009 2012 edition.

NFPA 220, Standard on Types of Building Construction, 2009 2012 edition.

NFPA 318, Standard for the Protection of Semiconductor Fabrication Facilities, 2009 2012 edition.

NFPA 400, Hazardous Materials Code, 2010 2013 edition.

NFPA 801, Standard for Fire Protection for Facilities Handling Radioactive Materials, 2008 2013 edition.

NFPA 820, Standard for Fire Protection in Wastewater Treatment and Collection Facilities, 2008 2012edition.

NFPA 853, Standard for the Installation of Stationary Fuel Cell Power Systems, 2010 edition.

NFPA 914, Code for Fire Protection of Historic Structures, 2010 edition.

NFPA 921, Guide for Fire and Explosion Investigations, 2011 2014 edition.

NFPA 1925, Standard on Marine Fire-Fighting Vessels, 2008 edition.

NFPA 5000®, Building Construction and Safety Code®, 2009 2012 edition.

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

13 of 491 1/30/2014 9:30 AM

Submittal Date: Wed Aug 28 13:44:22 EDT 2013

Committee Statement

Committee Statement: Update of editions of NFPA documents for extracted text.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

14 of 491 1/30/2014 9:30 AM

First Revision No. 124-NFPA 2-2013 [ New Section after 3.2 ]

3.3.58* Defueling.

The controlled discharge of hydrogen from motor vehicle fuel storage tanks systems according to thevehicle manufacturer’s instructions, utilizing a nozzle or port supplied by the vehicle or test systemmanufacturer and equipment that has been listed and labeled, or approved for the intended use.

Supplemental Information

File Name Description

A_3.3.x_FR_124_SB.docx

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 07 08:44:58 EDT 2013

Committee Statement

CommitteeStatement:

A defueling system is required at the H2 fueling station to support the testing of dispenser functionsat commissioning and during periodic inspections.

All of the dispenser test procedures to establish Weights and Measures accuracy, and SAE J-2601,CSA HGV-4.3, or equivalent fueling protocol validation require a provision for a connection to beavailable for qualified personnel to connect dispenser test devices to a permanently mounted ventstack at each fuel dispensing station. (note: in the absence of a permanent vent system, test systemoperators may establish a temporary vent stack system)

This submittal is partially based on the work of the NFPA-2 Task Group on Chapter 17 and 19. Theproponent found and Task Group agreed that defueling requirements are needed for both fuelingstations (this proposal) and at repair garages. The Task Group felt it necessary to create a definitionfor “defueling” to clarify how and when repair work may require the use of defueling systems. Thisnew definition proposed by the chapter 19 TF has been revised to further clarify the definition ofdefueling as applicable at both repair garages and at fueling stations.

Note to NFPA-2 TC: the defueling system requirements for stations are slightly different from thedefueling requirements in Chapter 19.

ResponseMessage:

Public Input No. 67-NFPA 2-2012 [New Section after 3.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

15 of 491 1/30/2014 9:30 AM

   A.3.3.x  Defueling.  Defueling of the vehicle storage system can be used for some vehicle maintenance procedures.    Defueling systems can also be used at fueling stations to allow for the safe discharge of hydrogen from vehicle fuel tank test systems during dispenser calibration, certification, and periodic validation procedures. The dispensers at a fueling station are typically commissioned, validated, certified and periodically tested by conducting test fills of H2 vehicle storage tanks.  After a test fill, the test tank system can be vented safely using a vent system installed at the fueling station.  

Formatted: Font: Bold

Formatted: Font: Bold

First Revision No. 173-NFPA 2-2013 [ Section No. 3.3.6.1 ]

3.3.6.1 Control Area.

A designated area, either indoors or outdoors building or portion of a building or outdoor area , withinwhich hazardous materials are allowed to be stored, dispensed, used, or handled, or dispensed inquantities not exceeding the maximum allowable quantity quantities (MAQ). [1 400 ,2009 2013 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 08:56:01 EDT 2013

Committee Statement

Committee Statement: Updated extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

16 of 491 1/30/2014 9:30 AM

First Revision No. 175-NFPA 2-2013 [ New Section after 3.3.6.5 ]

3.3.6.6* Use Area.

A location inside or outside of a building or structure where the material placed into use is situated.[ 55 , 2013]

Supplemental Information

File Name Description

A_3_3_6_6_FR_175_SB_Comment.docx

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 09:06:00 EDT 2013

Committee Statement

Committee Statement: Updated extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

17 of 491 1/30/2014 9:30 AM

A.3.3.6.6 Use Area.

Piping systems are used to transport gas (and liquids) from a point of storage to the actual point of use where the gas is deployed. Piping alone does not create a condition of “use” where the material is being consumed or otherwise released from a closed pipe system. On the other hand, piping that connects to “process equipment,” which is acting to raise or lower the energy in the system, or that either consumes or releases the material must be viewed as “active,” and as a result the material is viewed as being “placed into action” at the point of delivery or connection to the process equipment. [55, 2013]

First Revision No. 176-NFPA 2-2013 [ Section No. 3.3.6.5 ]

3.3.6.5 Outdoor Area.

An area that is either outside the confines of a building, or an area sheltered from the elements byoverhead cover, that is protected from weather exposure by an exterior wall that obstructs not more than25 percent of the building boundary not an indoor area . [1 55 ,2009 2013 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 09:06:21 EDT 2013

Committee Statement

Committee Statement: Updated extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

18 of 491 1/30/2014 9:30 AM

First Revision No. 179-NFPA 2-2013 [ Section No. 3.3.13.1 ]

3.3.13.1 Detached Building.

A separate single-story building, that is separated from other structures or uses as required by this codefor a freestanding structure without a basement or crawl space, used exclusively for the storage or use ofhazardous materials and located an approved distance from other structures . [ 5000, 2009] [ 55, 2013]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 09:08:51 EDT 2013

Committee Statement

Committee Statement: Updated extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

19 of 491 1/30/2014 9:30 AM

First Revision No. 180-NFPA 2-2013 [ Section No. 3.3.22.1 ]

3.3.22.1* Gas Cabinet.

A fully enclosed, noncombustible enclosure used to provide an isolated environment for compressed gascylinders in storage or use. [ 5000, 2009] [ 55, 2013]

Supplemental Information

File Name Description

A.3.3.22.1_FR_180_.docx

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 09:18:46 EDT 2013

Committee Statement

Committee Statement: Updated extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

20 of 491 1/30/2014 9:30 AM

A.3.3.22.1 Gas Cabinet.

Doors and access ports for exchanging cylinders and accessing pressure-regulating controls are permitted to be included. [55, 2013][5000, 2012]

 

First Revision No. 9-NFPA 2-2013 [ New Section after 3.3.22.2 ]

3.3.23 Canopy.

A permanent structure or architectural projection of rigid construction over which a covering is attachedthat provides weather protection, identity, or decoration.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jun 04 11:40:35 EDT 2013

Committee Statement

CommitteeStatement:

This input provides a definition for the term "canopy". This is used in Chapter 10 in a separatepublic input that adds requirements relevent to canopies for refueling with GH2.

ResponseMessage:

Public Input No. 105-NFPA 2-2013 [New Section after 3.3.22.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

21 of 491 1/30/2014 9:30 AM

First Revision No. 471-NFPA 2-2013 [ Section No. 3.3.25 ]

3.3.26 Cargo Transport [ Vehicle] .

A mobile unit designed to transport GH2, or LH2. [ 52, 2010]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 30 10:14:54 EDT 2013

Committee Statement

Committee Statement: Removed extract tag since definition is not found in the current edition of NFPA 52.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

22 of 491 1/30/2014 9:30 AM

First Revision No. 181-NFPA 2-2013 [ New Section after 3.3.37.1 ]

3.3.38.2 Fire Code.

The fire prevention code adopted by the jurisdiction. [ 55 , 2013]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 09:27:19 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

23 of 491 1/30/2014 9:30 AM

First Revision No. 182-NFPA 2-2013 [ Section No. 3.3.38.1 ]

3.3.39.1 Limited- Combustible Material . [-].

Refers to a building construction material not complying with the definition of noncombustible that, in theform in which it is used, has a potential heat value not exceeding 3500 Btu/lb (8141 kJ/kg), where testedin accordance with NFPA 259 and includes either (1) materials having a structural base ofnoncombustible material, with a surfacing not exceeding a thickness of 1 ⁄8 (3.2 mm) that has a flamespread index not greater than 50, or (2) materials, in the form and thickness used having neither a flamespread index greater than 25 nor evidence of continued progressive combustion, and of such compositionthat surfaces that would be exposed by cutting through the material on any plane would have neither aflame spread index greater than 25 nor evidence of continued progressive combustion, when tested inaccordance with ANSI/UL 723 or ASTM E 84. [ 220, 2009] See 4.15.2 .

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 09:28:33 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

24 of 491 1/30/2014 9:30 AM

First Revision No. 183-NFPA 2-2013 [ Section No. 3.3.45 ]

3.3.46 Compressor.

A mechanical device used for increasing to increase the pressure and the resultant density of a gasthrough the act of compression . [853 55 ,2011 2013 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 09:30:47 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

25 of 491 1/30/2014 9:30 AM

First Revision No. 196-NFPA 2-2013 [ Section No. 3.3.46.2 ]

3.3.47.2 Fuel Supply Container.

A container mounted on a vehicle to store [-] LH2, or GH2 as the fuel supply to the vehicle. [ 52, 2010]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 09:49:15 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

26 of 491 1/30/2014 9:30 AM

First Revision No. 184-NFPA 2-2013 [ Section No. 3.3.54.1 ]

3.3.55.1 Flammable Cryogenic Fluid.

A cryogenic fluid that is flammable forms flammable mixtures in air when in its vapor state. [ 55 , 2013]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 09:32:21 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

27 of 491 1/30/2014 9:30 AM

First Revision No. 1-NFPA 2-2013 [ Section No. 3.3.77.3 ]

3.3.79.3 Residential GH2 Fueling Facility (RFF-GH2).

An assembly with a capacity not exceeding 18 scf/min (0.5 scm/min) of GH2, that generates and

compresses hydrogen and that can be used for fueling a vehicle at a home or residence. [ 52, 2010]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon May 27 12:33:05 EDT 2013

Committee Statement

CommitteeStatement:

Extract tag has been dropped since the definition for hydrogen only and should not beextracted from NFPA 52

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

28 of 491 1/30/2014 9:30 AM

First Revision No. 126-NFPA 2-2013 [ Section No. 3.3.99 ]

3.3.101 Repair Garages.

3.3.101.1* Major Repair Garage.

Hydrogen Fuel Cell Vehicle. A building or portions of a building where for major repairs, such as engineoverhauls, painting, body and fender work work on the hydrogen storage system, the fuel cell system, thepropulsion system , and repairs that require venting defueling of the motor vehicle fuel tank areperformed on motor vehicles, including associated floor space used for offices, parking, orshowrooms hydrogen fuel cell vehicle, and maintenance or repairs that require open-flame cutting orwelding . [ 30A, 2008]

3.3.101.2* Minor Repair Garages .

Buildings and structures used for service and repair operations in connection with self-propelled GH2 andLH2 fueled vehicles (including, but not limited to, passenger automobiles, buses, trucks and tractors).

Hydrogen Fuel Cell Vehicle. A building or portions of a building not used for work required to beperformed in a major repair garage, such as lubrication, inspection, and minor automotive maintenancework, fluid changes (e.g., brake fluid, air conditioning refrigerants), brake system repairs, tire rotation,and similar routine maintenance work.

Supplemental Information

File Name Description

A_3_3_x_FR_126_SB.docx

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 07 09:21:19 EDT 2013

Committee Statement

CommitteeStatement:

Committee generated first revision. This incorporates PI # 89 into the correct location in thedefinition chapter. We have deleted definitions for terms that that are no longer used in NFPA 2.This FR also resolves PI #60.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

29 of 491 1/30/2014 9:30 AM

 

A.3.3.X.1 Major Repair Garage.

The propulsion system on a hydrogen fuel cell vehicle includes the high voltage (>12 volts) battery, the high voltage electrical system and the high voltage electric motor(s) used to propel the vehicle.

A.3.3.X.2 Minor Repair Garage.

Work on the components of a hydrogen fuel cell vehicle that are similar or identical to conventional liquid fueled vehicles (gasoline or diesel fuel) such as wheel, tires, brakes, shock absorbers, and so forth, does not present any unique fire hazard; therefore, no additional fire safety requirements beyond those in place for conventional liquid vehicles are warranted.

 

First Revision No. 197-NFPA 2-2013 [ Section No. 3.3.100.1 ]

3.3.102.1* Compressed Gas.

A material, or mixture of materials, that (1) is a gas at 68°F (20°C) or less at an absolute pressure of 14.7psia psi (101.3 kPa) of pressure , and (2) has a boiling point of 68°F (20°C) or less at an absolutepressure of 14.7 psia psi (101.3 kPa) and that is either liquefied, nonliquefied, or in solution, exceptthose gases that have no other health or physical hazard properties are not considered to be compressedgases until the pressure in the packaging exceeds 41 psia (282.5 an absolute pressure of 40.6 psi (280kPa) at 68°F (20°C). [ 5000, 2009] [ 55, 2013]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 09:50:03 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

30 of 491 1/30/2014 9:30 AM

First Revision No. 2-NFPA 2-2013 [ Section No. 3.3.116 ]

3.3.118 Hydrogen Generator.

A packaged or factory- matched hydrogen gas generation device that (a 1 ) uses electrochemicalreactions to electrolyze water to produce hydrogen and oxygen gas (electrolyzer) and (b 2 ) convertshydrocarbon fuel to a hydrogen-rich stream of composition and conditions suitable for the type of device(e.g., fuel cells) using the hydrogen (reformer). [ 52, 2010]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon May 27 12:35:54 EDT 2013

Committee Statement

CommitteeStatement:

Extract tag has been dropped since the term has been deleted from NFPA 52. Hydrogen-specific terminology.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

31 of 491 1/30/2014 9:30 AM

First Revision No. 185-NFPA 2-2013 [ Section No. 3.3.139.2 ]

3.3.141.2 Noncombustible Material.

A material that, in the form in which it is used and under the conditions anticipated, will not ignite, burn,support combustion, or release flammable vapors, when subjected to fire or heat. Materials that arereported as passing ASTM E 136, Standard Test Method for Behavior of Materials in a Vertical TubeFurnace at 750 Degrees C, shall be considered noncombustible materials. [ 5000, 2009]

See 4.15.1 .

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 09:34:38 EDT 2013

Committee Statement

Committee Statement: Update of extract text.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

32 of 491 1/30/2014 9:30 AM

First Revision No. 149-NFPA 2-2013 [ New Section after 3.3.144 ]

3.3.147 Mechanical Connection.

A non-welded or brazed connection.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jun 17 15:16:29 EDT 2013

Committee Statement

CommitteeStatement:

The committee added this text to address PI #175. This FR puts the definition in theappropriate place in the chapter.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

33 of 491 1/30/2014 9:30 AM

First Revision No. 199-NFPA 2-2013 [ Section No. 3.3.150 ]

3.3.153* Mobile [Refueler Refueling ].

A The use of a DOT-approved vehicle or mobile equipment on site with tank(s) and/or pump(s) thatdispenses engine fuel directly to vehicles, storage vessels/cylinders, or secondary refueling equipment, .[ 52, 2010] [ 52, 2013]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 09:53:20 EDT 2013

Committee Statement

Committee Statement: Update of extract text.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

34 of 491 1/30/2014 9:30 AM

First Revision No. 10-NFPA 2-2013 [ Section No. 3.3.156 ]

3.3.159* Nonbulk Hydrogen Compressed Gas.

Gaseous hydrogen (GH2) packaged in cylinders, containers, or tanks with a contained volume not

exceeding 400 5000 scf (6600 141.6 cm Nm 3) each at NTP that are either not interconnected bymanifolds or piping systems or that when interconnected have an aggregate contained volume of less

than 400 5000 scf (6600 141.6 cm Nm 3).

Supplemental Information

File Name Description

A.3.3.156_FR_10_.docx

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jun 04 12:48:36 EDT 2013

Committee Statement

CommitteeStatement:

Bulk GH2 systems are defined as those that exceed 5000 scf, therefore, non-bulk hydrogensystems are those that are below the threshold for bulk. The use of cubic centimeters to reflect ametric conversion from standard cubic feet is of little to no value. The 2011 Edition of NFPA 2incorrectly converts a quantity of 400 scf to 6600 cubic centimeters. If the quantity of 5000 scf wereto be correctly shown in cubic centimeters the value would be 141,584,232 cubic centimeters. Theuse of Normal Cubic Meters is advised.

This change has been submitted on behalf of the Extracts Task Group to coordinate with a revisionto the threshold for bulk GH2 as extracted from NFPA 55. At the non-bulk definition is not an extractdefinition the proposed change had to be submitted outside of the extract package.

ResponseMessage:

Public Input No. 53-NFPA 2-2012 [Section No. 3.3.156]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

35 of 491 1/30/2014 9:30 AM

  

A.3.3.156 Nonbulk Hydrogen Compressed Gas. Nonbulk GH2 includes individual cylinders, containers, or tanks of compressed hydrogen gas typically found in storage with the valves shut and protective caps in place. A nonbulk GH2 system can include interconnected cylinders, containers, or tanks that have been manifolded or connected for use, providing the aggregate volume of individual systems does not exceed 400 ft3 (6600 cm3) 5000 scf (141.6 Nm3).  

Formatted: Font: Bold

First Revision No. 186-NFPA 2-2013 [ New Section after 3.3.160 ]

3.3.164 Normal Cubic Meter (Nm 3 ) of Gas.

A cubic meter of gas at an absolute pressure of 14.7 psi (101.3 kPa) and a temperature of 70 ° F

(21 ° C). [ 55, 2013]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 09:36:08 EDT 2013

Committee Statement

Committee Statement: Update of extract text.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

36 of 491 1/30/2014 9:30 AM

First Revision No. 11-NFPA 2-2013 [ New Section after 3.3.190 ]

3.3.195 Purging.

A method used to free the internal volume of a piping system of unwanted contents that results in theexisting contents being removed or replaced. [ 55 , 2013]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jun 04 12:54:45 EDT 2013

Committee Statement

CommitteeStatement:

The definition for purging is companion to a separate PI addressing technical requirements to beadded to Chapters 7 and 8. It is further explained by the following:

A new standard to address the cleaning and purging of flammable gas piping systems was issued asNFPA 56PS (PS is a Provisional Standard) in 2012. Piping systems included in NFPA 2 wereexcepted from the requirements of NFPA 56PS. A Tentative Interim Amendment (TIA) establishingrequirements for the cleaning and purging of all gas piping systems, including flammable gas pipingsystems under the purview of NFPA 55 was accepted by the Standards Council and published onOctober 30, 2012 (SC 12-10-5/TIA Log #1073) effective November 19, 2012. A copy of the completetext is available on the NFPA website available at: www.nfpa.org/55. The TIA was submitted by andaccepted by NFPA’s IMG_AAA Technical Committee.

The TIA is designated as tentative as it will be included as public input and available for discussion bythe IMG TC during the Annual 2015 code revision cycle with a closing date of July 8, 2013.

The entire text of the TIA could be added to NFPA 2 to coordinate NFPA 2 with NFPA 55; however,given the fact that the TIA will be subject to additional public input in this code cycle it is felt thatreferencing NFPA 55 is sufficient as a means to address the subject during the public input phase forNFPA 2. Changes that may occur during the public input phase of NFPA 55 will be available to theNFPA 2 TC during the public comment phase.

ResponseMessage:

Public Input No. 63-NFPA 2-2012 [New Section after 3.3.190]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

37 of 491 1/30/2014 9:30 AM

First Revision No. 187-NFPA 2-2013 [ New Section after 3.3.210.2 ]

3.3.216 Special Provisions.

Controls required when the maximum allowable quantity in the control area is exceeded. [ 55, 2013]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 09:37:38 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

38 of 491 1/30/2014 9:30 AM

First Revision No. 427-NFPA 2-2013 [ Section No. 3.3.219 ]

3.3.225 System.

3.3.225.1 Automatic Fire Detection System.

A fire detection system that senses the presence of fire, smoke, or heat and activates a [firesuppression] system [and/]or an automatic alarm system. [ 853, 2010]

3.3.225.2* Bulk Oxygen System.

An assembly of equipment, such as oxygen storage containers, pressure regulators, pressure reliefdevices, vaporizers, manifolds, and interconnecting piping, that has a storage capacity of more than

3 20,000 ft 3 (scf) scf (566 N m3) of oxygen, including unconnected reserves on hand at the site, andthat terminates at the source valve. [ 55, 2010] [ 55, 2013]

3.3.225.3 Compressed Gas System.

An assembly of equipment designed to contain, distribute, or transport compressed gases. [ 318, 2012]

3.3.225.4 Duct System.

A continuous passageway for the transmission of air that, in addition to ducts, includes duct fittings,dampers, fans, and accessory air-managing equipment and appliances. [ 853, 2010]

3.3.225.5* Engineered and Field-Constructed Fuel Cell Power System.

A fuel cell power system that is not preassembled or does not have factory-matched components. [ 853,2010]

3.3.225.6 Exhaust System.

An air-conveying system for moving materials from a source to a point of discharge. [ 91, 2010]

3.3.225.7* Fuel Cell Power System.

A generator system that converts the chemical energy of reactants (a fuel and oxidant) by anelectrochemical process to electric energy (direct current or alternating current electricity) and thermalenergy. [ 853, 2010]

3.3.225.8 Gas Detection System.

One or more sensors capable of detecting [hydrogen] at specified concentrations and activating alarmsand safety systems. [ 52, 2013]

3.3.225.9* Gaseous Hydrogen (GH 2 ) System.

An assembly of equipment that consists of, but is not limited to, storage containers, pressure regulators,pressure relief devices, compressors, manifolds, and piping.

3.3.225.10* Bulk Hydrogen Compressed Gas System.

A GH 2 system with a storage capacity of more than 5000 scf (141.6 Nm 3 ) of compressed hydrogen

gas, and that terminates at the source valve.

3.3.225.11 Hydrogen Generation System.

A packaged, factory matched, or site constructed hydrogen gas generation appliance or system such as(a) an electrolyzer that uses electrochemical reactions to electrolyze water to produce hydrogen andoxygen gas; (b) a reformer that converts hydrocarbon fuel to a hydrogen-rich stream of composition andconditions suitable for the type of device using the hydrogen; or (c) a gasifier that converts coal to ahydrogen-rich stream of composition and conditions suitable for a type of device using the hydrogen. Itdoes not include hydrogen generated as a by-product of a waste treatment process. [ 55, 2013]

3.3.225.12 Hydrogen Storage System.

That portion of a closed system used for retention of hydrogen gas or liquid upstream of the sourcevalve.

3.3.225.13 Hydrogen Use System.

Placing hydrogen into action through the use of piping, pressure or control systems downstream of thesource valve.

3.3.225.14 Interactive System.

A fuel cell [power] system that operates in parallel with and may deliver power to an electrical productionand distribution network. For the purpose of this definition, an energy storage subsystem of a fuel cell[power] system, such as a battery, is not another electrical production source. [ 70: 692.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

39 of 491 1/30/2014 9:30 AM

3.3.225.15* Liquefied Hydrogen (LH 2 ) System.

An assembly of equipment that consists of, but is not limited to, storage containers, pressure regulators,pressure relief devices, vaporizers, liquid pumps, compressors, manifolds, and piping.

3.3.225.16* Bulk Liquefied Hydrogen (LH 2 ) System.

An LH 2 system with a storage capacity of more than 39.7 gal (150 L) of liquefied hydrogen that

terminates at the source valve

3.3.225.17 Metal Hydride Storage System.

A closed system consisting of a group of components assembled as a package to contain metal–hydrogen compounds for which there exists an equilibrium condition where the hydrogen-absorbingmetal alloy(s), hydrogen gas, and the metal–hydrogen compound(s) coexist and where only hydrogengas is released from the system in normal use. [ 55, 2013]

3.3.225.18 Micro Fuel Cell Power System.

A micro fuel cell power unit and associated fuel cartridges that is wearable or that is easily carried byhand.

3.3.225.19* Piping System.

Interconnected piping consisting of mechanical components suitable for joining or assembly intopressure-tight fluid-containing system. Components include pipe, tubing, fittings, flanges, bolting, valves,and devices such as expansion joints, flexible joints, pressure hoses, in-line portions of instruments, andwetted components other than individual pieces or stages of equipment. [ 55, 2013]

3.3.225.20* Pre-Engineered and Matched Modular Components Fuel Cell Power System.

A fuel cell power system that has components that are assembled in a factory in separate modules,such as the fuel cell [power system] stack, reformer, and inverter. [ 853, 2010]

3.3.225.21 Prepackaged, Self-Contained Fuel Cell Power System.

A fuel cell power system that is designed as one unit, assembled in a factory, and shipped to site.[ 853 , 2010]

3.3.225.22 Sprinkler System.

A system that consists of an integrated network of piping designed in accordance with fire protectionengineering standards that includes a water supply source, a water control valve, a waterflow alarm,and a drain and is commonly activated by heat from a fire, discharging water over the fire area..Theportion of the sprinkler system above ground is a network of specially sized or hydraulically designedpiping installed in a building, structure, or area, generally overhead, and to which sprinklers are attachedin a systematic pattern. The system is commonly activated by heat from a fire and discharges waterover the fire area. [ 13, 2013]

3.3.225.23 Treatment System.

An assembly of equipment capable of processing a hazardous gas and reducing the gas concentrationto a predetermined level at the point of discharge from the system to the atmosphere. [ 55, 2013]

3.3.225.2 Detection System.

3.3.225.2.1 Automatic Fire Detection System.

A fire detection system that senses the presence of fire, smoke, or heat and activates a [firesuppression] system [and/]or an automatic alarm system. [ 853, 2010]

3.3.225.2.2 Gas Detection System.

One or more sensors capable of detecting hydrogen at specified concentrations and activating alarmsand safety systems. [ 52, 2010]

3.3.225.3 Duct System.

A continuous passageway for the transmission of air that, in addition to ducts, includes duct fittings,dampers, fans, and accessory air-managing equipment and appliances. [ 853, 2010]

3.3.225.4 Exhaust System.

An air-conveying system for moving materials from a source to a point of discharge. [ 91, 2010]

3.3.225.5* Fuel Cell Power System.

A generator system that converts the chemical energy of reactants (a fuel and oxidant) by anelectrochemical process to electric energy (direct current or alternating current electricity) and thermalenergy. [ 853, 2010]

3.3.225.5.1* Engineered and Field-Constructed Fuel Cell Power System.

A fuel cell power system that is not preassembled or does not have factory-matched components. [ 853,2010]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

40 of 491 1/30/2014 9:30 AM

3.3.225.5.2 Micro Fuel Cell Power System.

A micro fuel cell power unit and associated fuel cartridges that is wearable or that is easily carried byhand.

3.3.225.5.3* Pre-Engineered and Matched Modular Components Fuel Cell Power System.

A fuel cell power system that has components that are assembled in a factory in separate modules,such as the fuel cell [power system] stack, reformer, and inverter. [ 853, 2010]

3.3.225.5.4 Prepackaged, Self-Contained Fuel Cell Power System.

A fuel cell power system that is designed as one unit, assembled in a factory, and shipped to site. [ 853,2010]

3.3.225.6 Gas System.

3.3.225.6.1 Compressed Gas System.

An assembly of equipment designed to contain, distribute, or transport compressed gases. [ 318, 2009]

3.3.225.6.1.1* Bulk Hydrogen Compressed Gas System.

An assembly of equipment that consists of, but is not limited to, storage containers, pressure regulators,pressure relief devices, compressors, manifolds, and piping, with a storage capacity of more than 400

ft 3 (scf) (11 m 3 ) of compressed hydrogen gas, including unconnected reserves on hand at the site,and that terminates at the source valve. [ 55, 2010]

3.3.225.7 Hydrogen Gas System.

3.3.225.7.1* Bulk Liquefied Hydrogen Gas System.

An assembly of equipment that consists of, but is not limited to, storage containers, pressure regulators,pressure relief devices, vaporizers, liquid pumps, compressors, manifolds, and piping, with a storagecapacity of more than 39.7 gal (150 L) of liquefied hydrogen, including unconnected reserves on hand atthe site, and that terminates at the source valve. [ 55, 2010]

3.3.225.8 Hydrogen Generation System.

A packaged, factory matched, or site constructed hydrogen gas generation appliance or system such as(a) an electrolyzer that uses electrochemical reactions to electrolyze water to produce hydrogen andoxygen gas; (b) a reformer that converts hydrocarbon fuel to a hydrogen-rich stream of composition andconditions suitable for the type of device using the hydrogen; or (c) a gasifier that converts coal to ahydrogen-rich stream of composition and conditions suitable for a type of device using the hydrogen. Itdoes not include hydrogen generated as a by-product of a waste treatment process. [ 55, 2010]

3.3.225.9 Hydrogen System.

3.3.225.9.1* Gaseous Hydrogen System.

A system in which hydrogen is delivered, stored, and discharged in the gaseous form to a pipingsystem. The gaseous hydrogen system terminates at the point where hydrogen at service pressure firstenters the distribution piping. [ 55, 2010]

3.3.225.9.2* Liquefied Hydrogen System.

A system into which liquefied hydrogen is delivered and stored and from which it is discharged in theliquid or gaseous form to a piping system. The system originates at the storage container fill connectionand terminates at the point where hydrogen at service pressure first enters the supply line. [ 55, 2010][ 55, 2013]

3.3.225.10 Hydrogen Use System.

Placing hydrogen into action through the use of piping, pressure or control systems downstream of thesource valve.

3.3.225.11 Interactive System.

A fuel cell [power] system that operates in parallel with and may deliver power to an electrical productionand distribution network. For the purpose of this definition, an energy storage subsystem of a fuel cell[power] system, such as a battery, is not another electrical production source. [ 70: 692.2]

3.3.225.12 LH 2 System.

An assembly of equipment designed to contain, distribute, or transport LH 2 .

3.3.225.13* Piping System.

Interconnected piping consisting of mechanical components suitable for joining or assembly intopressure-tight fluid-containing system. Components include pipe, tubing, fittings, flanges, bolting, valves,and devices such as expansion joints, flexible joints, pressure hoses, in-line portions of instruments, andwetted components other than individual pieces or stages of equipment. [ 55, 2010]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

41 of 491 1/30/2014 9:30 AM

3.3.225.14 Sprinkler System.

For fire protection purposes, an integrated system of underground and overhead piping designed inaccordance with fire protection engineering standards. The installation includes at least one automaticwater supply that supplies one or more systems. The portion of the sprinkler system above ground is anetwork of specially sized or hydraulically designed piping installed in a building, structure, or area,generally overhead, and to which sprinklers are attached in a systematic pattern. Each system has acontrol valve located in the system riser or its supply piping. Each sprinkler system includes a device foractuating an alarm when the system is in operation. The system is usually activated by heat from a fireand discharges water over the fire area. [ 13, 2010]

3.3.225.15 Storage System.

3.3.225.15.1 Hydrogen Storage System.

That portion of a closed system used for retention of hydrogen gas or liquid upstream of the sourcevalve.

3.3.225.15.2 Metal Hydride Storage System.

A closed system consisting of a group of components assembled as a package to contain metal–hydrogen compounds for which there exists an equilibrium condition where the hydrogen-absorbingmetal alloy(s), hydrogen gas, and the metal–hydrogen compound(s) coexist and where only hydrogengas is released from the system in normal use. [ 55, 2010] [ 55, 2013]

3.3.225.16 Treatment System.

An assembly of equipment capable of processing a hazardous gas and reducing the gas concentrationto a predetermined level at the point of discharge from the system to the atmosphere. [ 55, 2010]

Supplemental Information

File Name Description

3_3_219_FR_427_-SB.docx

A.3.3.219_FR_427_.docx

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 12:07:01 EDT 2013

Committee Statement

CommitteeStatement:

Committee Generated First Revision. Committee rewrote and substantially revised this sectionto update definitions and reorganize the section.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

42 of 491 1/30/2014 9:30 AM

3.3.219 System. 3.3.219. 2.1 Automatic Fire Detection System. A fire detection system that senses the presence of fire, smoke, or heat and activates a [fire suppression] system [and/]or an automatic alarm system. [853, 2010] 3.3.219.12* Bulk Oxygen System. An assembly of equipment, such as oxygen storage containers, pressure regulators, pressure relief devices, vaporizers, manifolds, and interconnecting piping, that has a storage capacity of more than 320,000 ft3 (scf) (566N m3) of oxygen , including unconnected reserves on hand at the site, and that terminates at the source valve. [55, 20130]

3.3.219.6.13 Compressed Gas System.

An assembly of equipment designed to contain, distribute, or transport compressed gases. [318, 20092012]

3.3.219.3 4 Duct System. A continuous passageway for the transmission of air that, in addition to ducts, includes duct fittings, dampers, fans, and accessor air-managing equipment and appliances. [853, 2010] 3.3.219.5.15* Engineered and Field-Constructed Fuel Cell Power System. A fuel cell power system that is not preassembled or does not have factory-matched components. [853, 2010] 3.3.219.4 6 Exhaust System. An air-conveying system for moving materials from a source to a point of discharge. [91, 2010] 3.3.219.57* Fuel Cell Power System. A generator system that converts at the chemical energy of reactants (a fuel and oxidant) by an electrochemical process to electric energy (direct current or alternating current electricity) and thermal energy. [853, 2010] 3.3.219.2.28 Gas Detection System. One or more sensors capable of detecting [hydrogen] at specified concentrations and activating alarms and safety systems. [52, 20130] 3.3.219.9.1 * Gaseous Hydrogen (GH2) System. An assembly of equipment that consists of, but is not limited to, storage containers, pressure regulators, pressure relief devices, compressors, manifolds, and piping that terminates at the source valve. [55, 2010]

3.3.219.6.19.1* Bulk Hydrogen Compressed Gas System.

An assembly of equipment that consists of, but is not limited to, storage containers, pressure regulators, pressure relief devices, compressors, manifolds, and piping,A GH2 system with a

storage capacity of more than 400 ft3 (5000scf) (141.6 Nm3) of compressed hydrogen gas and that terminates at the source valve. [55, 2010]

3.3.219.8 10 Hydrogen Generation System.

A packaged, factory matched, or site constructed hydrogen gas generation appliance or system such as (a) an electrolyzer that uses electrochemical reactions to electrolyze water to produce hydrogen and oxygen gas; (b) a reformer that converts hydrocarbon fuel to a hydrogen-rich stream of composition and conditions suitable for the type of device using the hydrogen; or (c) a gasifier that converts coal to a hydrogen-rich stream of composition and conditions suitable for a type of device using the hydrogen. It does not include hydrogen generated as a by-product of a waste treatment process. [55, 20130]

3.3.219.15.1 1 Hydrogen Storage System.

That portion of a closed system used for retention of hydrogen gas or liquid upstream of the source valve.

3.3.219.120 Hydrogen Use System.

Placing hydrogen into action through the use of piping, pressure, or control systems downstream of the source valve.

3.3.219.131 Interactive System.

A fuel cell [power] system that operates in parallel with and may deliver power to an electrical production and distribution network. For the purpose of this definition, an energy storage subsystem of a fuel cell [power] system, such as a battery, is not another electrical production source. [70:692.2]

3.3.219.9.214* Liquefied Hydrogen (LH2) System.

A system into which liquefied hydrogen is delivered and stored and from which it is diescharged in the liquid or gaseous form to a piping sytem. The system originates at the storage container fill connection and terminates at the point where hydrogen at service pressure first enters the supply line. [55, 2010]An assembly of equipment that consists of, but is not limited to, storage containers, pressure regulators, pressure relief devices, vaporizers, liquid pumps, compressors, manifolds, and piping.

3.3.219.14.1 Bulk Liquefied Hydrogen (LH2) System.

An LH2 system with a storage capacity of more than 39.7 gal (150 L) of liquefied hydrogen that terminates at the source valve.

3.3.219.15.2 5 Metal Hydride Storage System.

Formatted: div19, Adjust space between Latin and Asiantext, Adjust space between Asian text and numbers

Formatted: Font: Not Bold

A closed system consisting of a group of components assembled as a package to contain metal–hydrogen compounds for which there exists an equilibrium condition where the hydrogen-absorbing metal alloy(s), hydrogen gas, and the metal–hydrogen compound(s) coexist and where only hydrogen gas is released from the system in normal use. [55, 20130]

3.3.219.5.216 Micro Fuel Cell Power System.

A micro fuel cell power unit and associated fuel cartridges that is wearable or that is easily carried by hand.

3.3.219.1317* Piping System. Interconnected piping consisting of mechanical components suitable for joining or assembly into pressure-tight fluid-containing system. Components include pipe, tubing, fittings, flanges, bolting, valves, and devices such expansion joints, flexible joints, pressure hoses, in-line portions of instruments, and wetted components other than individual pieces or stages of equipment. [55, 20130] 3.3.219.5.318* Pre-Engineered and Matched Modular Components Fuel Cell Power System. A fuel cell power system that has components that are assembled in a factory in separate modules, such as the fuel cell [power system] stack, reformer, and inverter. [853, 2010] 3.3.219.5.419 Prepackaged, Self-Contained Fuel Cell Power System. A fuel cell power system that is designed as one unit, assembled in a factory, and shipped to site. [853, 2010] 3.3.219.14 20 Sprinkler System. For fire protection purposes,A system that consists of an integrated network system of underground and overhead piping designed in accordance with fire protection engineering standards that includes a water supply source, a water control valve, a waterflow alarm, and a drain and is commonly activated by heat from a fire, discharging water over the fire area. The installation includes at least one automatic water supply that supplies one or more systems. The portion of the sprinkler system above ground is a network of specially sized or hydraulically designed piping installed in a building, structure, or area, generally overhead, and to which sprinklers are attached in a systematic pattern. Each system has a control valve located in the system riser or its supply piping. Each sprinklwer system includyes a device for actuating an alarm when the system is in operation. The system is usually commonly activated by heat from a fire and discharges water over the fire area. [13, 20130] 3.3.219.16 21 Treatment System. An assembly of equipment capable of processing a hazardous gas and reducing the gas concentration to a predetermined level at the point of discharge from the system to the atmosphere. [55, 20130]

3.3.219.1* Bulk Oxygen System. An assembly of equipment, such as oxygen storage containers, pressure regulators, pressure relief devices, vaporizers, manifolds, and interconnecting piping, that has a storage capacity of more than 320,000 ft3 (scf) (566 m3) of oxygen, including unconnected reserves on hand at the site, and that terminates at the source valve. [55, 2010] 3.3.219.2 Detection System. 3.3.219.2.2 Gas Detection System. One or more sensors capable of detecting hydrogen at specified concentrations and activating alarms and safety systems. [52, 2010] 3.3.219.3 Duct System. A continuous passageway for the transmission of air that, in addition to ducts, includes duct fittings, dampers, fans, and accessory air-managing equipment and appliances. [853, 2010] 3.3.219.4 Exhaust System. An air-conveying system for moving materials from a source to a point of discharge. [91, 2010] 3.3.219.5* Fuel Cell Power System. A generator system that converts the chemical energy of reactants (a fuel and oxidant) by an electrochemical process to electric energy (direct current or alternating current electricity) and thermal energy. [853, 2010] 3.3.219.5.1* Engineered and Field-Constructed Fuel Cell Power System. A fuel cell power system that is not preassembled or does not have factory-matched components. [853, 2010] 3.3.219.5.2 Micro Fuel Cell Power System. A micro fuel cell power unit and associated fuel cartridges that is wearable or that is easily carried by hand. 3.3.219.5.3* Pre-Engineered and Matched Modular Components Fuel Cell Power System. A fuel cell power system that has components that are assembled in a factory in separate modules, such as the fuel cell [power system] stack, reformer, and inverter. [853, 2010] 3.3.219.5.4 Prepackaged, Self-Contained Fuel Cell Power System. A fuel cell power system that is designed as one unit, assembled in a factory, and shipped to site. [853, 2010]

3.3.219.6 Gas System.

3.3.219.6.1 Compressed Gas System. An assembly of equipment designed to contain, distribute, or transport compressed gases. [318, 2012]

3.3.219.6.1.1* Bulk Hydrogen Compressed Gas System. An assembly of equipment that consists of, but is not limited to, storage containers, pressure regulators, pressure relief devices, compressors, manifolds, and piping, with a storage capacity of more than 5,000 scf (141.6 Nm3) of compressed hydrogen gas that terminates at the source valve. [55, 2013]

3.3.219.7 Hydrogen Gas System.

3.3.219.7.1* Bulk Liquefied Hydrogen System. An assembly of equipment that consists of, but is not limited to, storage containers, pressure regulators, pressure relief devices, vaporizers, liquid pumps, compressors, manifolds, and piping, with a storage capacity of more than 39.7 gal (150 L) of liquefied hydrogen that terminates at the source valve. [55, 2013]

3.3.219.8 Hydrogen Generation System. A packaged, factory matched, or site constructed hydrogen gas generation appliance or system such as (a) an electrolyzer that uses electrochemical reactions to electrolyze water to produce hydrogen and oxygen gas; (b) a reformer that converts hydrocarbon fuel to a hydrogen-rich stream of composition and conditions suitable for the type of device using the hydrogen; or (c) a gasifier that converts coal to a hydrogen-rich stream of composition and conditions suitable for a type of device using the hydrogen. It does not include hydrogen generated as a by-product of a waste treatment process. [55, 2013]

3.3.219.9 Hydrogen System.

3.3.219.9.1* Gaseous Hydrogen (GH2) System. A system in which hydrogen is delivered, stored, and discharged in the gaseous form to a piping system. The gaseous hydrogen system terminates at the point where hydrogen at service pressure first enters the distribution piping. [55, 2013]

3.3.219.9.2* Liquefied Hydrogen (LH2) System. A system into which liquefied hydrogen is delivered and stored and from which it is discharged in the liquid or gaseous form to a piping system. The system originates at the storage container fill connection and terminates at the point where hydrogen at service pressure first enters the supply line.

3.3.219.10 Hydrogen Use System. Placing hydrogen into action through the use of piping, pressure or control systems downstream of the source valve.

3.3.219.11 Interactive System. A fuel cell [power] system that operates in parallel with and may deliver power to an electrical production and distribution network. For the purpose of this definition, an energy storage subsystem of a fuel cell [power] system, such as a battery, is not another electrical production source. [70:692.2]

3.3.219.12 LH2 System. An assembly of equipment designed to contain, distribute, or transport LH2. 3.3.219.13* Piping System. Interconnected piping consisting of mechanical components suitable for joining or assembly into pressure-tight fluid-containing system. Components include pipe, tubing, fittings, flanges, bolting, valves, and devices such as expansion joints, flexible joints, pressure hoses, in-line portions of instruments, and wetted components other than individual pieces or stages of equipment. [55, 2010] 3.3.219.14 Sprinkler System. For fire protection purposes, an integrated system of underground and overhead piping designed in accordance with fire protection engineering standards. The installation includes at least one automatic water supply that supplies one or more systems. The portion of the sprinkler system above ground is a network of specially sized or hydraulically designed piping installed in a building, structure, or area, generally overhead, and to which

sprinklers are attached in a systematic pattern. Each system has a control valve located in the system riser or its supply piping. Each sprinkler system includes a device for actuating an alarm when the system is in operation. The system is usually activated by heat from a fire and discharges water over the fire area. [13, 2010] 3.3.219.15 Storage System. 3.3.219.15.1 Hydrogen Storage System. That portion of a closed system used for retention of hydrogen gas or liquid upstream of the source valve. 3.3.219.15.2 Metal Hydride Storage System. A closed system consisting of a group of components assembled as a package to contain metal–hydrogen compounds for which there exists an equilibrium condition where the hydrogen-absorbing metal alloy(s), hydrogen gas, and the metal–hydrogen compound(s) coexist and where only hydrogen gas is released from the system in normal use. [55, 2010] 3.3.219.16 Treatment System. An assembly of equipment capable of processing a hazardous gas and reducing the gas concentration to a predetermined level at the point of discharge from the system to the atmosphere. [55, 2010]  

1  

A.3.3.219.1 2 Bulk Oxygen System. The bulk oxygen system terminates at the source valve, which is commonly the point where oxygen at service pressure first enters the supply line or a pieceof equipment that utilizes the oxygen gas or liquid. The oxygen containers are either stationary or movable, and the oxygen is stored as a compressed gas or cryogenic fluid. Bulk oxygen systems can be used to supply gas in either its compressed gaseous or liquefied form. Systems that may be used to supply both gaseous and liquid forms are referred to as hybrid systems. The following bulk oxygen systems are typical of those in use: (1) When the primary supply of the gas as stored is from a compressed gaseous source that is used in the compressed and gaseous form, the bulk oxygen system is said to be a bulk compressed oxygen gas system. (2) When the primary supply of the gas as stored is in a liquid form and the system is designed to transfer only liquid, the system is said to be a bulk liquefied oxygen system. (3) When the primary supply of the gas as stored is in a liquid form and the system is designed to transfer or store the gas in a compressed gaseous form, with or without a feature that may also allow the subsequent transfer and use of liquid, the bulk oxygen system is said to be a hybrid bulk oxygen system. For the purpose of the application of the code, a hybrid system is viewed as a bulk liquefied oxygen system. [55, 2013] A.3.3.219.5.15 Engineered and Field-Constructed Fuel Cell Power System. The power system is engineered and designed for the assembly of various components from various sources and is installed on site. (See Figure A.3.3.219.5 7 for a schematic of a typical fuel cell power system.) [853, 2010] A.3.3.219.5 7 Fuel Cell Power System. The system is composed of all or some of the systems shown in Figure A.3.3.219.57. [853, 2010] Figure A.3.3.219.5 7 Typical Fuel Cell Power System. [853:Figure B.1] A.3.3.219.9.1 Gaseous Hydrogen (GH2) System. The gaseous hydrogen system terminates at the point where hydrogen at service pressure first enters the distribution piping. [55, 2010] A.3.3.219. 6.19.1 Bulk Hydrogen Compressed Gas System. The bulk system terminates at the source valve [commonly referred to as] the point where the gas supply, at service pressure, first enters the supply line, or at a piece of equipment that utilizes the hydrogen gas, such as a hydrogen dispenser. The containers are either stationary or movable, and the source gas for the system is stored as a compressed gas.

Formatted: Font: Bold

2  

Bulk hydrogen compressed gas systems can include a bulk storage source, transfer piping and manifold system, compression system, and other components. The gaseous source can include a tube trailer, tube bank, or other high pressure storage vessels used to serve the piping system that transports hydrogen to the end user. Compressors can be installed downstream of the storage supply to boost the pressure of the source gas, and intermediate high pressure storage might be present. This is done where the end use requires hydrogen at a pressure higher than that of the bulk supply. In these instances, there may be intermediate storage vessels used to store the gas at elevated pressures. It is not uncommon for the bulk supply as delivered to be furnished at nominal gauge pressure of 3000 psi (20,684 kPa), and the intermediate high pressure storage to be stored at gauge pressures up to 15,000 psi (103,421 kPa). See Figure A.3.3.219.6.19.1(a) through Figure A.3.3.219.6.19.1(f). [55, 20130] Figure A.3.3.219.6.19.1(a) Symbol Legend for Figure A.3.3.263.10.2(b) through Figure A.3.3.263.10.2.1(f). [55:Figure 3.3.1293.2(a)] Figure A.3.3.219.6.19.1(b) Typical Tube Trailer. [55:Figure A.3.3.1293.2(b)] Figure A.3.3.219.6.19.1(c) Typical Bulk Compressed Gaseous Storage System. [55:Figure A.3.3.1293.2(c)] Figure A.3.3.219.6.19.1(d) Typical Tube Trailer Discharge Stanchion and Pressure Control Manifold. [55:Figure A.3.3.1293.2(d)] Figure A.3.3.219.6.19.1(e) Typical Chemical Energy Storage Module (CESM). [55:Figure A.3.3.1293.2(e)] Figure A.3.3.219.6.19.1(f) Typical Compressor Module. [55:Figure A.3.3.1293.2(f)] A.3.3.219.9.214 Liquefied Hydrogen (LH2) System. The system originates at the storage container fill connection and terminates at the point where hydrogen at service pressure first enters the supply line. [55, 2010] A.3.3.219.173 Piping System. Equipment such as a compressor or an intermediate storage vessel should be considered individual pieces of equipment. The equipment is not piping within the context of the definition of a piping system. [55, 20130] A.3.3.219.5.318 Pre-Engineered and Matched Modular Components Fuel Cell Power System. The modules are matched to be installed in the field. [853, 2010]  

Formatted: Font: Bold

Formatted: Font: Bold

Formatted: Font: Bold

First Revision No. 194-NFPA 2-2013 [ New Section after 3.3.228 ]

3.3.234 Unpierced Wall.

A wall that is allowed to have pipes or conduits passing through it, or openable windows, glazed withsafety glass or wired glass, set in it, but such openings are sealed to prevent the flow of air betweenadjacent rooms. [ 55, 2013]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 09:46:00 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

43 of 491 1/30/2014 9:30 AM

First Revision No. 195-NFPA 2-2013 [ Section No. 3.3.236 ]

3.3.243 Ventilation.

3.3.243.1 Fixed Natural Ventilation.

The movement of air into and out of a space through permanent openings that are arranged in such away that the required ventilation cannot be reduced by operating windows, doors, louvers, or similardevices. [ 55 , 2013]

3.3.243.2 Mechanical Ventilation.

The flow of air or gas created by a fan, blower, or other mechanical means that will push or induce the gasstream through a ventilation system. [853, 2010]

3.3.243.3 Natural Ventilation.

The flow of air or gases created by the difference in the pressures or gas densities between the outsideand inside of a vent, room, or space. [853, 2010]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 09:47:02 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

44 of 491 1/30/2014 9:30 AM

First Revision No. 22-NFPA 2-2013 [ Section No. 4.1.5 ]

4.1.5

The requirements of Sections 4.5 through 4.1.5 shall be part of the prescriptive requirements of thiscode.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 09:00:40 EDT 2013

Committee Statement

CommitteeStatement:

The section states “The requirements of Sections 4.5 through 4.1.5 shall be part of the prescriptiverequirements of this code.” The statement does not make sense chronologically. Additionally, onewould think that the intent of this statement is already implied in the administrative requirements ofthe code.

ResponseMessage:

Public Input No. 7-NFPA 2-2012 [Section No. 4.1.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

45 of 491 1/30/2014 9:30 AM

First Revision No. 472-NFPA 2-2013 [ Section No. 4.4.1.1 ]

4.4.1.1

A prescriptive-based option shall be in accordance with Chapters 1 through 4 and Chapters 6 through 20of this code [ as applicable] . [ 1: 4.3.1.1]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 30 10:29:55 EDT 2013

Committee Statement

CommitteeStatement:

Extract tag is removed since the chapter references for NFPA 2 are different than those in theoriginally extracted text from NFPA 1.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

46 of 491 1/30/2014 9:30 AM

First Revision No. 23-NFPA 2-2013 [ Section No. 4.6.2 ]

4.6.2

The plan shall be available for inspection by the AHJ upon reasonable notice and shall include thefollowing information:

[ 55: 4.2.1.2]

(1) The type of emergency equipment available and its location [ 55: 4.2.1.2(1)]

(2) A brief description of any testing or maintenance programs for the available emergency equipment[ 55: 4.2.1.2(2)]

(3) An indication that hazard identification labeling is provided for each storage area [ 55: 4.2.1.2(3)]

(4) The location of posted emergency procedures [ 55: 4.2.1.2(4)]

(5) A material safety data sheet (MSDS) or equivalent for [ GH2 or LH2] stored or used on the site

[ 55: 4.2.1.2(5)]

(6) A list of personnel who are designated and trained to be liaison personnel for the fire department andwho are responsible for the following: [ 55: 4.2.1.2(6)]

(a) Aiding the emergency responders in pre-emergency planning [ 55: 4.2.1.2(6)(a)]

(b) Identifying the location of the [ GH2 and LH2] stored or used [ 55: 4.2.1.2(6)(b)]

(c) Accessing MSDSs [ 55: 4.2.1.2(5)(c)]

(d) Knowing the site emergency procedures [ 55: 4.2.1.2(6)(d)]

(7) A list of the types and quantities of [ GH2 and LH2] found within the facility [ 55: 4.2.1.2(7)]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 09:04:45 EDT 2013

Committee Statement

CommitteeStatement:

The Emergency Plan should be readily available at all times. If a facility operator cannotimmediately (quickly) obtain a copy of their emergency plan for an AHJ to inspect, then it is likelythat it would not be readily available in an emergency for facility first responders or publicemergency responders.

ResponseMessage:

Public Input No. 8-NFPA 2-2012 [Section No. 4.6.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

47 of 491 1/30/2014 9:30 AM

First Revision No. 201-NFPA 2-2013 [ Section No. 4.7 ]

4.7 Facility Closure.

4.7.1

Where required by the AHJ, no facility storing hazardous materials listed in 1.1.1 of NFPA 400 shallclose or abandon an entire storage facility without notifying the AHJ at least 30 days prior to thescheduled closing. [ 400: 1.9.1]

4.7.2

The AHJ shall be permitted to reduce the 30-day period specified in 4.7.1 where there are specialcircumstances requiring such reduction. [ 400: 1.9.2]

4.7.3 Facilities Out of Service.

4.7.3.1 Temporarily Out-of-Service Facilities.

Facilities that are temporarily out of service shall continue to maintain a permit and be monitored andinspected. [ 400: 1.9.3.1]

4.7.3.2 Permanently Out-of-Service Facilities.

Facilities for which a permit is not kept current or that are not monitored and inspected on a regularbasis shall be deemed to be permanently out of service and shall be closed in accordance with 4.7.4 .[ 400: 1.9.3.2]

4.7.4 Temporarily Out-of-Service Facilities.

Facilities that are temporarily out of service shall continue to maintain a permit and be monitored andinspected. [ 1: 60.1.5.3.2]

4.7.5 Permanently Out-of-Service Facilities.

Facilities for which a permit is not kept current or that are not monitored and inspected on a regularbasis shall be deemed to be permanently out of service and shall be closed in accordance with 4.7.3 .[ 1: 60.1.5.3.3]

4.7.4 Closure Plan.

4.7.4.1

The Where required by the AHJ, the permit holder or applicant shall submit a plan to the fire departmentto terminate storage, dispensing, handling, or use of [GH2 or LH2] at least 30 days prior to facility closure.

[400 1 :60.1.5.3.3.1 1.9.4.1 ]

4.7.4.2

The plan shall demonstrate that [GH2 or LH2] that was stored, dispensed, handled, or used in the facility

has been transported, disposed of, or reused in a manner that eliminates the need for further maintenanceand any threat to public health and safety. [1 400 :60.1.5.3.3.2 1.9.4.2 ]

4.7.4.3

The plan shall be submitted with a permit application for facility closure in accordance with Section 4.5.[55:4.3.3.3]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 10:03:05 EDT 2013

Committee Statement

Committee Statement: Update of extract material

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

48 of 491 1/30/2014 9:30 AM

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

49 of 491 1/30/2014 9:30 AM

First Revision No. 463-NFPA 2-2013 [ Section No. 4.9 ]

4.9 Management Plan and Hazardous Materials Documentation.

4.9.1 Hazardous Materials Management Plan.

When Where required by the AHJ, permit applications shall include a hazardous materials managementplan (HMMP) shall be submitted to the AHJ [including addressing the GH 2 or LH 2 present] .

[1 55 :60.1.6.1 4.5.1 ]

4.9.1.1 Contents .

The HMMP shall comply with the requirements of the [adopted] fire code [ 55: 4.5.1.1] include anemergency response training plan and facility site plan designating the following: [ 1: 60.1.6.1.1]

Storage and use areas [ 1: 60.1.6.1.1(1)]

Maximum amount of each [hazardous] material stored or used in each area [ 1: 60.1.6.1.1(2)]

Range of container sizes [ 1: 60.1.6.1.1(3)]

Product-conveying piping containing liquids or gases, other than utility-owned fuel gas lines andlow-pressure fuel gas lines [ 1: 60.1.6.1.1(4)]

Locations of emergency isolation and mitigation valves and devices [ 1: 60.1.6.1.1(5)]

ON and OFF positions of valves for valves that are of the self-indicating type [ 1: 60.1.6.1.1(6)]

Storage plan that is legible and drawn approximately to scale showing the intended storagearrangement, including the location and dimensions of aisles, with separate distribution systemspermitted to be shown on separate pages [ 1: 60.1.6.1.1(7)]

4.9.1.2 Location.

The location of the HMMP shall be posted adjacent to permits when an HMMP is provided.[ 1: 60.1.6.1.2]

4.9.2 Hazardous Materials Inventory Statement.

When required by the AHJ, permit applications shall include a hazardous materials inventory statement(HMIS) [addressing the GH2 or LH2 present] shall be completed and submitted to the AHJ .

[1 400 :60.1.6.2 1.12.1 ]

4.9.3 Material Safety Data Sheets.

Material safety data sheets (MSDS) shall be readily available on the premises for [GH2 or LH2]. When

approved, MSDSs shall be permitted to be retrievable by electronic access. [1:60.1.7 2 ]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 02 14:36:35 EDT 2013

Committee Statement

Committee Statement: Update of extract text.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

50 of 491 1/30/2014 9:30 AM

First Revision No. 464-NFPA 2-2013 [ Section No. 4.10 ]

4.10 Release of GH2 or LH2.

4.10.1* Prohibited Releases.

[GH2 or LH2] shall not be released into a sewer, storm drain, ditch, drainage canal, lake, river, or tidal

waterway; upon the ground, sidewalk, street, or highway unless such release is permitted by the following:[1 400 :60.1.8.1 6.1.3.1 ]

(1) Federal, state, or local governing regulations [ 1 400 :60.1.8.1 6.1.3.1 (1)]

(2) Permits of the jurisdictional air quality management board [ 1 400 :60.1.8.1 6.1.3.1 (2)]

(3) National Pollutant Discharge Elimination System Permit [ 1 400 :60.1.8.1 6.1.3.1 (3)]

(4) Waste discharge requirements established by the jurisdictional water quality control board [1 400 :60.1.8.1 6.1.3.1 (4)]

(5) Local sewer Sewer pretreatment requirements for publicly owned treatment works [1 400 :60.1.8.1 6.1.3.1 (5)]

(6) Pressure relief devices and vents designed as part of a system

4.10.2 Control and Mitigation of Unauthorized Discharge Release s.

Provisions shall be made for controlling and mitigating unauthorized discharge release s. [1 400 :60.1.8.2 6.1.3.2 ]

4.10.3* Records of Unauthorized Discharge Release s.

Accurate records of the unauthorized discharge releases of [GH2 or LH2] shall be kept by the permittee. [

1 400 :60.1.8. 6.1.3. 3]

4.10.4 Notification of Unauthorized Discharge Release s.

The fire department shall be notified immediately or in accordance with approved emergency procedureswhen an unauthorized discharge release becomes reportable under state, federal, or local regulations. [1 400 :60.1.8. 6.1.3. 4]

4.10.5 Container Failure.

When an unauthorized discharge release due to primary container failure is discovered, the involvedprimary container shall be repaired or removed from service. [ 1 400 :60.1.8. 6.1.3. 5]

4.10.6 Responsibility for Cleanup of Unauthorized Discharge Release s.

4.10.6.1

The person, firm, or corporation responsible for an unauthorized discharge release shall institute andcomplete all actions necessary to remedy the effects of such unauthorized discharge release , whethersudden or gradual, at no cost to the AHJ. [ 1 400 :60.1.8. 6.1.3. 6 7 .1]

4.10.6.2

When deemed necessary by the AHJ, cleanup of an unauthorized discharge release shall be permitted tobe initiated by the fire department or by an authorized individual or firm, and costs associated with suchcleanup shall be borne by the owner, operator, or other person responsible for the unauthorizeddischarge release . [1: 400: 60.1.8. 6.1.3. 6 7 .2]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 02 14:56:57 EDT 2013

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

51 of 491 1/30/2014 9:30 AM

Committee Statement

Committee Statement: Update of extracted text

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

52 of 491 1/30/2014 9:30 AM

First Revision No. 214-NFPA 2-2013 [ Section No. 4.11 ]

4.11* Personnel Training.

Persons in areas where [GH 2 or LH 2 ] are stored, dispensed, handled, or used shall be trained in the

hazards of the materials employed and actions required by the emergency plan. The level of training tobe conducted shall be consistent with the responsibilities of the persons to be trained in accordance with4.11.1 through 4.11.4 . [ 400: 6.1.4]

4.11.1 Awareness.

Persons engaged in the handling and storage of GH 2 , and LH 2 shall be trained in the hazards and

properties of these materials.

The training provided for persons designated in Section 4.11 shall include awareness training inaccordance with 4.11.1 through 4.11.3 . [ 400: 6.1.4.1]

4.11.1.1 Completion.

Initial training shall be completed prior to beginning work in the work area. [ 400: 6.1.4.1.1]

4.11.1.2 Hazard Communications.

Training shall be provided prior to beginning work in the work area to enable personnel to recognize andidentify [GH 2 or LH 2 ] stored, dispensed, handled, or used on site and where to find hazard safety

information pertaining to the materials employed. [ 400: 6.1.4.1.2]

4.11.1.3 Emergency Plan.

Training shall be provided prior to beginning work in the work area to enable personnel to implement theemergency plan. [ 400: 6.1.4.1.3]

4.11.2 Operations Personnel.

Persons responsible for the operation of areas in which [GH 2 or LH 2 ] is stored, dispensed, handled,

or used shall be familiar with the chemical nature of the materials and the appropriate mitigating actionsnecessary in the event of fire, leak, or spill. [ 1: 60.1.9]

Persons engaged in storing, using, or handling [GH 2 or LH 2 ] shall be designated as operations

personnel and shall be trained in accordance with 4.11.1 and 4.11.2.1 through 4.11.3.2 .[ 400: 6.1.4.2]

4.11.2.1 Physical and Health Hazard Properties.

Operations personnel shall be trained in the chemical nature of the materials, including their physicalhazards and the symptoms of acute or chronic exposure as provided by the Material Safety Data Sheet(MSDS) furnished by the manufacturer or other authoritative sources. [ 400: 6.1.4.2.1]

4.11.2.2 Dispensing, Using, and Processing.

Operations personnel shall be trained in the specific safeguards applicable to the dispensing,processing, or use of the materials and the equipment employed. [ 400: 6.1.4.2.2]

4.11.2.3 Storage.

Operations personnel shall be trained in the application of storage arrangements and site-specificlimitations on storage for the materials employed. [ 400: 6.1.4.2.3]

4.11.2.4 Transport (Handling).

Operations personnel involved in materials handling shall be trained in the requirements for on-sitetransport of the materials employed. [ 400: 6.1.4.2.4]

4.11.2.5 Actions in an Emergency.

Operations personnel shall be trained in the necessary actions to take in the event of an emergency,including the operation and activation of emergency controls prior to evacuations. [ 400: 6.1.4.2.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

53 of 491 1/30/2014 9:30 AM

4.11.2.6 Changes.

Training shall be provided whenever a new hazardous material is introduced into the work area thatpresents a new physical or health hazard, or when new information is obtained pertaining to physical orhealth hazards of an existing hazardous material that has not been included in previous training, andwhen there are changes in one of the following:

(1) Equipment

(2) Operations

(3) Hazardous Materials

[ 400: 6.1.4.2.6]

4.11.3 Emergency Response Liaison. [400:6.1.4.3]

4.11.3.1

Responsible persons shall be designated and trained to be emergency response (ER) liaisonpersonnel. [ 400: 6.1.4.3.1]

4.11.3.2

Emergency response liaison personnel shall do the following:

(1) Aid emergency responders in pre-planning responses to emergencies

(2) Identify locations where [GH 2 or LH 2 ] are located

(3) Have access to material safety data sheets

(4) Be knowledgeable in the site emergency response procedures

[ 400: 6.1.4.3.2]

4.11.4* Emergency Responders.

Emergency responders shall be trained to be competent in the actions to be taken in an emergencyevent. [ 400: 6.1.4.4]

4.11.4.1* Emergency Response Team Leader.

Persons acting as ER team leaders shall be trained under the Incident Command System concept orequivalent. [ 400: 6.1.4.4.1]

4.11.4.2 Response to Incipient Events.

Responses to incidental releases of [GH 2 or LH 2 ] where the material can be absorbed, neutralized,

or otherwise controlled at the time of release by employees in the immediate release area, or bymaintenance personnel, shall not be considered emergency responses as defined with the scope ofthis code. [ 400: 6.1.4.4.2]

4.11.4.3* On-Site Emergency Response Team.

When an on-site emergency response team is provided, emergency responders shall be trained inaccordance with the requirements of the specific site emergency plan or as required by federal, state,or local governmental agencies.[ 400: 6.1.4.4.3]

4.11.4.4 Training Mandated by other Agencies.

Training required by federal, state, or local regulations that is required based on the quantity or type of[GH 2 or LH 2 ] stored, dispensed, handled, or used shall be conducted in accordance with the

requirements of and under the jurisdiction of the governing agency. [ 400: 6.1.4.5]

4.11.4.5 Documentation.

Training shall be documented and made available to the AHJ upon written request. [ 400: 6.1.4.6]

Supplemental Information

File Name Description

A.4.11_subsections_FR_214_.docx

Submitter Information Verification

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

54 of 491 1/30/2014 9:30 AM

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 10:20:49 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

55 of 491 1/30/2014 9:30 AM

A.4.11

The hazard potential of a facility is not dependent on any single factor. Physical size, number of employees, and the quantity and the nature of the hazardous materials are important considerations. The level of training can vary with the complexity of the facility under consideration. [400:A.6.1.4]

A.4.11.4

Emergency responders can include on-site personnel that have been designated and trained to respond to emergencies, persons from the public sector such as fire department personnel, or persons from the private sector that can be contracted or otherwise engaged to perform emergency response duties. (See Annex I , Emergency Response Guideline in NFPA 400, Hazardous Materials Code, for additional information.). [400:A.6.1.4.4]

A.4.11.4.1

OSHA describes an Incident Command System as a standardized on-scene incident management concept designed specifically to allow responders to adopt an integrated organizational structure equal to the complexity and demands of any single incident or multiple incidents without being hindered by jurisdictional boundaries. [400:A.6.1.4.4.1]

A.4.11.4.2

Responses to releases of hazardous materials where there is no potential safety or health hazard such as fire, explosion, or chemical exposure are not considered emergency responses as defined within the context of this code. [400:A.6.1.4.4.2]

A.4.11.4.3

Emergency response training will vary depending on the level of emergency response required and by the requirements of the governmental agency. [400:A.6.1.4.4.3]

 

Formatted: Font: Italic

Formatted: Font: Italic

First Revision No. 465-NFPA 2-2013 [ Section No. 4.12 ]

4.12 Ignition Source Controls.

4.12.1 Smoking.

Smoking shall be prohibited in the following locations: [1 400 :60.1.11.1 6.1.5.1 ]

(1) Within 25 ft (7.6 m) of outdoor storage or dispensing areas areas, dispensing areas, or open useareas. [1 400 :60.1.11.1 6.1.5.1 (1)]

(2) In rooms or areas where [GH2 or LH2] is are stored, or dispensed, or used in open systems in

amounts requiring a permit in accordance with Section 4.5 [1 400 :60.1.11.1 6.1.5.1(2) (2 ) ]

4.12.2 Open Flames and High-Temperature Devices.

Open flames and high-temperature devices shall not be used in a manner that creates a hazardouscondition. [1 400 :60.1.11.2 6.1.5.2 ]

4.12.3 Energy-Consuming Equipment.

Energy-consuming equipment with the potential to serve as a source of ignition shall be listed orapproved for use with [ GH2 or LH2] .[ 400: 6.1.5.3]

4.12.4 Powered Industrial Trucks.

Powered industrial trucks shall be operated and maintained in accordance with NFPA 50 . [ 1: 10.18]

4.12.5 Laboratories.

Equipment in laboratories shall be in accordance with Chapter 16.

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Aug 02 15:39:54 EDT 2013

Committee Statement

Committee Statement: Update of extract text.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

56 of 491 1/30/2014 9:30 AM

First Revision No. 466-NFPA 2-2013 [ Section No. 4.13 ]

4.13 Signs.

4.13.1 General.

4.13.1.1 Design and Construction.

Signs shall be durable, and the size, color, and lettering of signs shall be in accordance with nationallyrecognized standards. [1 400 :60.1.13.1.1 6.1.8.1.1 ]

4.13.1.2 Language.

Signs shall be in English as the primary language or in symbols allowed by this code.[ 1: [ 400: 60.1.13. 6.1.8. 1.2]

4.13.1.3 Maintenance.

Signs shall not be obscured or removed meet the following criteria: [ 400: 6.1.8.1.3] .

(1) They shall not be obscured. [ 400: 6.1.8.1.3(1)]

(2) They shall be maintained in a legible condition. [ 400: 6.1.8.1.3(2)]

(3) They shall not be removed, unless for replacement. [ 400: 6.1.8.1.3(3)]

[ 1: 60.1.13. 1.3]

4.13.2 Hazard Identification Signs.

4.13.2.1

Visible hazard identification signs in accordance with NFPA 704, Standard System for the Identificationof the Hazards of Materials for Emergency Response , shall be placed on at the following locations ,except where the AHJ has received a hazardous materials management plan and a hazardous materialsinventory statement in accordance with 4.9.1 through 4.9.2 and has determined that omission of suchsigns is consistent with safety: [ 1: [ 400: 60.1.13. 6.1.8. 2.1]

(1) S On s tationary aboveground tanks [ 1: [ 400: 60.1.13. 6.1.8. 2.1(1)]

(2) S On s tationary aboveground containers [ 1: [ 400: 60.1.13. 6.1.8. 2.1(2)]

(3) At entrances to locations where hazardous materials are stored, dispensed, used, or handled inquantities requiring a permit [ 1: [ 400: 60.1.13. 6.1.8. 2.1(3)]

(4)

4.13.2.2 Identification of Containers, Cartons, and Packages.

Individual containers, cartons, or packages shall be conspicuously marked or labeled in accordance withnationally recognized [codes and] standards. [1:60.1.13. 6.1.8. 2.2]

4.13.2.3 Identification of Gas Rooms and Cabinets.

Rooms or cabinets containing compressed gases shall be conspicuously labeled as follows:COMPRESSED GAS

[ 1: 60.1.13.2.3] [ 55: 4.10.2.3]

4.13.3 No Smoking Signs.

Signs prohibiting smoking shall be provided for an entire site, building, or in the following locations Where“no smoking” is not applicable to an entire site or building, signs shall be provided as follows :[ 1: [ 400: 60.1.13. 6.1.8. 3]

(1) In rooms or areas where [GH2 or LH2] is stored or dispensed or used in open systems in amounts

requiring a permit in accordance with Section 4.5 1.8 of NFPA 400 [ 1: [ 400: 60.1.13. 6.1.8. 3(1)]

(2) Within 25 ft (7.6 m) of outdoor storage [or] , dispensing, or open-use areas[ 1: [ 400: 60.1.13. 6.1.8. 3(2)]

In areas containing [GH 2 or LH 2 ] [ 1: 60.1.13. 3(3)]

Submitter Information Verification

* At other entrances and locations designated by the AHJ [ 1: [ 400: 60.1.13. 6.1.8. 2.1(4)]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

57 of 491 1/30/2014 9:30 AM

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Aug 05 07:44:32 EDT 2013

Committee Statement

Committee Statement: Update of extract text.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

58 of 491 1/30/2014 9:30 AM

First Revision No. 467-NFPA 2-2013 [ Section No. 4.14.1 [Excluding any Sub-Sections] ]

When Where required, guard posts in accordance with 4.14.1.2 or other approved means shall beprovided to protect against physical damage in accordance with Section 4.1.5 .

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Aug 05 08:04:17 EDT 2013

Committee Statement

CommitteeStatement:

4.1.5 contains no requirements for guard posts or other protective measures, these are allfound in 4.14.

Response Message:

Public Input No. 9-NFPA 2-2012 [Section No. 4.14.1 [Excluding any Sub-Sections]]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

59 of 491 1/30/2014 9:30 AM

First Revision No. 223-NFPA 2-2013 [ Section No. 4.14.1.1 ]

4.14.1.1

Guard posts or other approved means shall be provided to protect the following areas where subject tovehicular damage: [1 400 :60.1.15.1 6.1.9.1 ]

(1)

(2) Dispensing areas Storage areas containing tanks or portable containers except where the exposingvehicles are powered industrial trucks used for transporting the [GH 2 or

LH 2 ] [ 1: 60.1.15.1 [ 400: 6.1.9.1 (2)]

(3) Use areas [ 1: 60.1.15.1 [ 400: 6.1.9.1 (3)]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 10:39:04 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

* Storage tanks and connected piping, valves, and fittings [1 400 :60.1.15.1 6.1.9.1 (1)]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

60 of 491 1/30/2014 9:30 AM

First Revision No. 224-NFPA 2-2013 [ New Section after 4.14.1.2 ]

4.15* Building Construction Materials.

4.15.1* Noncombustible Material.

A material that complies with any of the following shall be considered a noncombustible material:[ 101 : 4.6.13.1]

(1)

(2) A material that is reported as passing ASTM E 136, Standard Test Method for Behavior ofMaterials in a Vertical Tube Furnace at 750 Degrees C , shall be considered a noncombustiblematerial. [ 101 : 4.6.13.1(2)]

(3) A material that is reported as complying with the pass/fail criteria of ASTM E 136 when tested inaccordance with the test method and procedure in ASTM E 2652, Standard Test Method forBehavior of Materials in a Tube Furnace with a Cone-shaped Airflow Stabilizer, at 750 DegreesC , shall be considered a noncombustible material. [ 101 : 4.6.13.1(3)]

4.15.2* Limited-Combustible Material.

A material shall be considered a limited-combustible material where all the conditions of 4.15.2.1 and4.15.2.2 , and the conditions of either 4.15.2.3 or 4.15.2.4 are met. [ 101 : 4.6.14]

4.15.2.1

The material shall not comply with the requirements for a noncombustible material, in accordance with4.15.1 . [ 101 : 4.6.14.1]

4.15.2.2

The material, in the form which it is used, shall exhibit a potential heat value not exceeding 3500 Btu/lb(8141 kJ/kg), where tested in accordance with NFPA 259 . [ 101 : 4.6.14.2]

4.15.2.3

The material shall have a structural base of a noncombustible material with a surfacing not exceeding athickness of 1 ⁄8 in. (3.2 mm) where the surfacing exhibits a flame spread index not greater than 50when tested in accordance with ASTM E 84, Standard Test Method for Surface Burning Characteristicsof Building Materials , or ANSI/UL 723, Standard for Test for Surface Burning Characteristics ofBuilding Materials . [ 101 : 4.6.14.3]

4.15.2.4

The material shall have composed of materials that, in the form and thickness used, neither exhibit aflame spread index greater than 25 nor evidence of continued progressive combustion when tested inaccordance with ASTM E 84 or ANSI/UL 723, and are of such composition that all surfaces that wouldbe exposed by cutting through the material on any plane with neither exhibit a flame spread indexgreater than 25 nor evidence of continued progressive combustion when tested in accordance withASTM E 84 or ANSI/UL 723. [ 101 : 4.6.14.4]

4.15.2.5

Where the term limited-combustible is used in this code, it shall also include the termnoncombustible . [ 101 : 4.6.14.5]

Supplemental Information

File Name Description

A.4.15_FR_224_.docx

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

* A material that, in the form in which it is used and under the condition anticipated, will not ignite,burn, support combustion, or release flammable vapors, when subjected to fire or heat.[ 101 : 4.6.13.1(1)]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

61 of 491 1/30/2014 9:30 AM

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 10:42:18 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

62 of 491 1/30/2014 9:30 AM

A.4.15

The term materials used throughout this section applies to building construction materials and not to hazardous materials, compressed gases, or cryogenic fluids. [55:A.4.12]

A.4.15.1

The provisions of 4.15.1 do not require inherently noncombustible materials to be tested in order to be classified as noncombustible materials. [101:A.4.6.13]

A.4.15.1(1)

Examples of such materials include steel, concrete, masonry, and glass. [101:A.4.6.13.1(1)]

A.4.15.2 Materials subject to increase in combustibility or flame spread index beyond the limits herein established through the effects of age, moisture, or other atmospheric condition are considered combustible. (See NFPA 259, Standard Test Method for Potential Heat of Building Materials, and NFPA 220, Standard on Types of Building Construction.) [101:A.4.6.14]

Formatted: Indent: Left: 0"

Formatted: Font: Not Bold

Formatted: Font: Not Bold

Formatted: Font: Not Bold, Italic

Formatted: Font: Not Bold

Formatted: Font: Not Bold

Formatted: Font: Not Bold

Formatted: Font: Not Bold

Formatted: Font: Italic

Formatted: Font: Not Bold

Formatted: Font: Not Bold

Formatted: Font: Italic

Formatted: Font: Not Bold

Formatted: Font: Italic

Formatted: Font: Italic

Formatted: Font: Italic

Formatted: Font: Italic

Formatted: Font: Italic

First Revision No. 225-NFPA 2-2013 [ Section No. 4.14.1.2 ]

4.14.1.2

Where guard posts are installed, the posts shall meet the following criteria: [ 400: [ 1: 60.1.15. 6.1.9. 2]

(1) They shall be constructed of steel not less than 4 in. (102 mm) in diameter and concrete filled.[ 400: [ 1: 60.1.15. 6.1.9. 2(1)]

(2) They shall be spaced not more than 4 ft (1.2 m) between posts on center.[ 400: [ 1: 60.1.15. 6.1.9. 2(2)]

(3) They shall be set not less than 3 ft (0.9 m) deep in a concrete footing of not less than a 15 in. (380mm) diameter. [ 400: [ 1: 60.1.15. 6.1.9. 2(3)]

(4) They shall be set with the top of the posts not less than 3 ft (0.9 m) above ground.[ 400: [ 1: 60.1.15. 6.1.9. 2(4)]

(5) They shall be located not less than 5 ft (1.5 m) from the tank. [ 400: [ 1: 60.1.15. 6.1.9. 2(5)]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 10:43:05 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

63 of 491 1/30/2014 9:30 AM

First Revision No. 228-NFPA 2-2013 [ Section No. 5.1.2 ]

5.1.2 Goals and Objectives.

The performance-based design shall meet the goals and objectives of Section 4.2 this Code inaccordance with the assumptions of Section 4.3. [ 1: 5.1.2]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 11:05:43 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

64 of 491 1/30/2014 9:30 AM

First Revision No. 25-NFPA 2-2013 [ Section No. 5.3.5 ]

5.3.5 Equivalency.

Equivalent designs for the features covered in the retained prescriptive requirements mandated by 5.3.1through 5.3.4 shall be addressed in accordance with the equivalency provisions of Section 1.4 5 . [1:5.3.5]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 10:03:43 EDT 2013

Committee Statement

Committee Statement: Section 1.4 relates to retroactivity, 1.5 is the correct reference.

Response Message:

Public Input No. 10-NFPA 2-2012 [Section No. 5.3.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

65 of 491 1/30/2014 9:30 AM

First Revision No. 229-NFPA 2-2013 [ Section No. 6.1.1.4 ]

6.1.1.4 Quantities Less than or Equal to the MAQ.

Building-related controls in Indoor control areas with [GH2 or LH2] stored or used within an indoor control

area in quantities less than or equal to those shown in Table 6.4.1.1 shall be in accordance with 6.4.1.5and Sections 6.1 6.7, 6.8, 6.12 , 6.16, and 6.17. [55:6.2.3 4 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 11:06:50 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

66 of 491 1/30/2014 9:30 AM

First Revision No. 230-NFPA 2-2013 [ Section No. 6.3.1 ]

6.3.1 Construction Requirements.

Control areas shall be separated from each other by not less than a 1-hour fire-resistive occupancyseparation as required by the [adopted] building code. [ 55: 6.2.1] 's fire barriers in accordance with theadopted building code.

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 11:09:07 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

67 of 491 1/30/2014 9:30 AM

First Revision No. 231-NFPA 2-2013 [ New Section after 6.3.2 ]

6.3.3

Where only one control area is present in a building, no special construction provisions shall berequired.

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 11:11:17 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

68 of 491 1/30/2014 9:30 AM

First Revision No. 232-NFPA 2-2013 [ Section No. 6.3.2 ]

6.3.2 Number of Control Areas .

The maximum number of control areas in buildings or portions of buildings shall not exceed that allowedby the [adopted] building code. [ 55: 6.2.2] within a building shall be in accordance with the adoptedbuilding code.

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 11:11:40 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

69 of 491 1/30/2014 9:30 AM

First Revision No. 482-NFPA 2-2013 [ Section No. 6.4.1.1 ]

6.4.1.1 Threshold Exceedences.

Where the quantities of [GH2 or LH2] stored or used within an indoor control area exceed those shown in

Table 6.4.1.1, the area shall meet the requirements for [the occupancy classification] in accordance withthe [adopted] building code, based on the requirements of 6.4.2. [55:6.3.1.1]

Table 6.4.1.1 Maximum Allowable Quantity of Hydrogen per Control Area (Quantity Thresholds RequiringSpecial Provisions)

Unsprinklered Areas Sprinklered Areas

Material

No Gas Cabinet, GasRoom, or Exhausted

Enclosure

Gas Cabinet, GasRoom, or

ExhaustedEnclosure

No Gas Cabinet, GasRoom, or Exhausted

Enclosure

Gas Cabinet, GasRoom, or

ExhaustedEnclosure

[ LH2] * 0 gal (0 L) 45 gal (170 L) † 45 gal (170 L) 45 gal (170 L) †

[ GH2] *1000 ft3 (28 m3) 2000 ft3 (56 m3) 2000 ft3 (56 m3) 4000 ft3 (112 m3)

Note: The maximum quantity indicated is the aggregate quantity of materials in storage and usecombined.

†A gas cabinet or exhausted enclosure is required. Pressure relief devices or stationary or portablecontainers shall be vented directly outdoors or to an exhaust hood. (See 8.1.4.6.)

*This material is extracted from rows 2 and 3 of Table 6.3.1.1 of NFPA 55 , Compressed Gases andCryogenic Fluids Code .

Supplemental Information

File Name Description

2_Table_6_4_1_1.docx

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 04 14:15:03 EDT 2013

Committee Statement

Committee Statement: Update of extract material. Moved footnote to the correct location on the Table.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

70 of 491 1/30/2014 9:30 AM

Table 6.4.1.1 Maximum Allowable Quantity of Hydrogen per Control Area (Quantity Thresholds Requiring Special Provisions)

Unsprinklered Areas Sprinklered Areas

Material

No Gas Cabinet, Gas Room, or

Exhausted Enclosure

Gas Cabinet, Gas Room, or Exhausted Enclosure

No Gas Cabinet, Gas Room, or

Exhausted Enclosure

Gas Cabinet, Gas Room, or

Exhausted Enclosure

[LH2]* 0 gal (0 L) 45 gal (170 L) † 45 gal (170 L) 45 gal (170 L)

[GH2]* 1000 ft3 (28 m3) 2000 ft3 (56 m3) 2000 ft3 (56 m3) 4000 ft3 (112 m3)

Note: The maximum quantity indicated is the aggregate quantity of materials in storage and use combined.

†A gas cabinet or exhausted enclosure is required. Pressure relief devices or stationary or portable containers shall be vented directly outdoors or to an exhaust hood. (See 8.1.4.6.)

*This material is extracted from Table 6.3.1.1 of the 2013 edition of NFPA 55, Compressed Gases and Cryogenic Fluids Code.

First Revision No. 233-NFPA 2-2013 [ Section No. 6.4.1.5.2 ]

6.4.1.5.1.1

Cylinders, containers, or tanks not exceeding 250 scf (7.1 Nm 3 ) content at normal temperature andpressure (NTP) and used for maintenance purposes, patient care, or operation of equipment shall bepermitted. [ 55: 6.3.1.6.2]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 11:15:06 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

71 of 491 1/30/2014 9:30 AM

First Revision No. 234-NFPA 2-2013 [ Section No. 6.4.1.5.3 ]

6.4.1.5.1.2

Piping systems used to supply GH 2 in accordance with 7.3.1.2.1 shall be permitted.

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 11:17:36 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

72 of 491 1/30/2014 9:30 AM

First Revision No. 4-NFPA 2-2013 [ Section No. 6.4.2 ]

6.4.2 Classification of Occupancy.

The [ occupancy classification] required shall be based on the hazard class of the material involved asindicated in 6.4.2.1. [ 55: 6.3.2]

6.4.2.1 Occupancy Classification.

Occupancies used for the storage or use of [ GH2 or LH2] in quantities that exceed the quantity

thresholds for gases requiring special provisions shall be classified [ in accordance with the adoptedbuilding code] . [ 55: 6.3.2.2]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon May 27 13:10:05 EDT 2013

Committee Statement

CommitteeStatement:

Extract tags have been dropped since the text does not match 55 with the addition of theadopted building code designation.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

73 of 491 1/30/2014 9:30 AM

First Revision No. 235-NFPA 2-2013 [ Section No. 6.5 ]

6.5 Gas Rooms.

Where a gas room is used to increase the threshold quantity for a gas requiring special provisions orwhere otherwise required by the material or application specific requirements of Chapters 10 through18 , the room shall meet the requirements of 6.5.1 through 6.5.5 . [ 55: 6.4]

6.5.1 Pressure Control.

Gas rooms shall operate at a negative pressure in relationship to the surrounding area. [55:6.4.1]

6.5.2 Exhaust Ventilation.

Gas rooms shall be provided with an exhaust ventilation system. [55:6.4.2]

6.5.3 Construction.

Gas rooms shall be constructed in accordance with the [adopted] building code. [55:6.4.3]

6.5.4 Separation.

Gas rooms shall be separated from other occupancies by a minimum of 1-hour fire resistance. [55:6.4.4]

6.5.5 Limitation on Contents.

6.5.5.1

The function of compressed gas rooms shall be limited to storage and use of compressed gases andassociated equipment and supplies. [55:6.4.5]

6.5.5.2

When Where GH2 or LH2 is stored and used in gas rooms it shall comply with 6.5.5.1.

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 11:19:26 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

74 of 491 1/30/2014 9:30 AM

First Revision No. 236-NFPA 2-2013 [ Section No. 6.6.1.2 ]

6.6.1.2

For such storage or use areas to be regulated as outdoor storage or use, compliance with conditionsin Weather protected areas constructed in accordance with 6.6.1.4 and 6.6.2 shall be required regulatedas outdoor storage or use area. . [55:6.5 6 .2.2]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 11:21:06 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

75 of 491 1/30/2014 9:30 AM

First Revision No. 237-NFPA 2-2013 [ Section No. 6.6.1.3 ]

6.6.1.3

Where storage or use areas are provided with weather protection that does not comply with theseconditions, the storage or use area shall be regulated as an indoor storage or use area.[ 55: 6.5.2.3] Weather protected areas that are not constructed in accordance with 6.6.1.4 shall beregulated as indoor storage or use. [ 55: 6.6.2.1]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 11:22:05 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

76 of 491 1/30/2014 9:30 AM

First Revision No. 238-NFPA 2-2013 [ Section No. 6.6.1.4 ]

6.6.1.4

Supports and walls shall not obstruct more than one side or more than 25 percent of the perimeter of thestorage or use area. [ 55: 6.5.3] Buildings or structures used for weather protection shall be inaccordance with the following: [ 55 :6.6.3]

(1) The building or structure shall be constructed of noncombustible materials. [ 55 :6.6.3(1)]

(2) Walls shall not obstruct more than one side of the structure. [ 55 :6.6.3(2)]

(3) Walls shall be permitted to obstruct portions of multiple sides of the structure, provided that theobstructed area does not exceed 25 percent of the structure’s perimeter area. [ 55 :6.6.3(3)]

(4) The building or structure shall be limited to a maximum area of 1500 ft 2 (140 m 2 ), with increasesin area allowed by the building code based on occupancy and type of construction. [ 55 :6.6.3(4)]

(5) The distance from the structure constructed as weather protection to buildings, lot lines, publicways or means of egress to a public way shall not be less than the distance required for an outsidehazardous material storage or use area without weather protection based on the hazardclassification of the materials contained. [ 55 :6.6.3(5)]

(6) Reductions in the separation distance shall be permitted based on the use of fire barrier wallswhere permitted for specific materials in accordance with the requirements of Chapters 7 and 8 .[ 55 :6.6.3(6)]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 11:23:37 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

77 of 491 1/30/2014 9:30 AM

First Revision No. 239-NFPA 2-2013 [ Section No. 6.6.2 ]

6.6.2 Structure Separation Distances.

6.6.2.1

The distance from the structure and the structural supports to buildings, lot lines, public ways or meansof egress to a public way shall not be less than the distance required for an outside hazardous materialstorage or use area without weather protection. [ 55: 6.5.4.1]

6.6.2.2

Where the weather protection structure is constructed of noncombustible materials, reductions in theseparation distance shall be permitted based on the use of fire barrier walls where permitted for specificmaterials in accordance with the requirements of Chapters 7 and 8 . [ 55: 6.5.4.2]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 11:24:45 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

78 of 491 1/30/2014 9:30 AM

First Revision No. 479-NFPA 2-2013 [ Section No. 6.7 [Excluding any Sub-Sections] ]

Electrical wiring and equipment shall be in accordance with Section 6.7 and NFPA 70, National ElectricalCode . [55:6.6 7 ]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 04 10:06:06 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

79 of 491 1/30/2014 9:30 AM

First Revision No. 273-NFPA 2-2013 [ Sections 6.7.1.1, 6.7.1.2 ]

6.7.1.1

Where the following systems are required by this code for the storage or use of [GH2 or LH2] that exceed

the quantity thresholds for gases requiring special provisions, such systems shall be connected to astandby power system in accordance with NFPA 70, National Electrical Code: [55:6.6.1.1 7.1.1 ]

(1) Mechanical ventilation [55:6.6.1.1 7.1.1 (1)]

(2) Treatment systems [55:6.6.1.1 7.1.1 (2)]

(3) Temperature controls [55:6.6.1.1 7.1.1 (3)]

(4) Alarms [55:6.6.1.1 7.1.1 (4)]

(5) Detection systems [55:6.6.1.1 7.1.1 (5)]

(6) Other electrically operated systems [55:6.6.1.1 7.1.1 (6)]

6.7.1.2

The requirements of 6.7.1.1 shall not apply where emergency power is provided in accordance with6.7.2 , and NFPA 70, National Electrical Code . [55:6.6 7 .1.2]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 12:21:11 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

80 of 491 1/30/2014 9:30 AM

First Revision No. 274-NFPA 2-2013 [ Section No. 6.7.2 ]

6.7.2 Emergency Power.

When emergency power is required, the system shall meet the requirements for a Protection Level 2system in accordance with NFPA 110, Standard for Emergency and Standby Power Systems .[55:6.6 7 .2]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 12:23:39 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

81 of 491 1/30/2014 9:30 AM

First Revision No. 275-NFPA 2-2013 [ Section No. 6.8 ]

6.8* Employee Alarm System.

Where required by government regulations, an employee alarm system shall be provided to allow warningfor necessary emergency action as called for in the emergency action plan required by 4.6.1 4.6.1.1 , orfor reaction time for safe egress of employees from the workplace or the immediate work area, or both.[55:6.7 8 ]

Supplemental Information

File Name Description

A.6.8_FR_275_.docx

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 12:24:03 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

82 of 491 1/30/2014 9:30 AM

A.6.8

Under the requirements of 29 CFR 1910.38 established by OSHA regulations, employers must establish an employee alarm system that complies with 29 CFR 1910.165. The requirements of 29 CFR 1910.165 for the employee alarm system include, but are not limited to, systems that are capable of being perceived above ambient noise or light levels by all employees in the affected portions of the workplace. Tactile devices [can] be used to alert those employees who would not otherwise be able to recognize the audible or visual alarm. The alarm system can be electrically powered or powered by pneumatic or other means. State, local, or other governmental regulations [can] also establish requirements for employee alarm systems. [55: A.6.87]

First Revision No. 245-NFPA 2-2013 [ Section No. 6.10.1 ]

6.10.1 Sprinkler System Design.

When sprinkler protection is provided required , the area in which [GH2 or LH2] is stored or used shall be

protected with a sprinkler system designed to be not less than that required by NFPA 13, Standard forthe Installation of Sprinkler Systems , for Extra Hazard Group 1. with a minimum design area of 2500

ft 2 (232.25 m 2 ). [55:6.9 10 .2.2]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 11:28:11 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

83 of 491 1/30/2014 9:30 AM

First Revision No. 246-NFPA 2-2013 [ Section No. 6.13 ]

6.13* Lighting.

Approved lighting by natural or artificial means shall be provided [for the storage areas] for areas ofstorage or use . [55:6.10 11 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 11:28:50 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

84 of 491 1/30/2014 9:30 AM

First Revision No. 247-NFPA 2-2013 [ Section No. 6.14.1 ]

6.14.1 GH2.

Spill control, drainage, and secondary containment shall not be required for [GH2]. [55:6.12 13 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 11:32:21 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

85 of 491 1/30/2014 9:30 AM

First Revision No. 276-NFPA 2-2013 [ Sections 6.15.1, 6.15.2 ]

6.15.1

Shelves used for the storage of cylinders, containers, and tanks shall be of noncombustible constructionand designed to support the weight of the materials stored. [55:6.13 14 .1]

6.15.2

In seismically active areas, shelves and containers shall be secured from overturning. [55:6.13 14 .2]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 12:27:07 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

86 of 491 1/30/2014 9:30 AM

First Revision No. 250-NFPA 2-2013 [ Section No. 6.16 ]

6.16* Vent Pipe Termination.

Hydrogen venting systems serving pressure relief devices discharging hydrodgen to the atmosphereshall be in accordance with CGA G-5.5, Hydrogen Vent Systems. [55:10.2.2 3 ]

Supplemental Information

File Name Description

A.6.16_FR_250_.docx

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 11:35:22 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

87 of 491 1/30/2014 9:30 AM

A.6.16

The termination point for piped vent systems serving cylinders, containers, tanks, and gas systems used for the purpose of operational or emergency venting [should] be located to prevent impingement exposure on the system served and to minimize the effects of high temperature thermal radiation or the effects of contact with the gas from the escaping plume to the supply system, personnel, adjacent structures, and ignition sources. [55:6.154]

 

First Revision No. 251-NFPA 2-2013 [ Section No. 6.17 [Excluding any Sub-Sections] ]

Indoor storage and use areas and storage buildings for [GH2 and LH2] shall be provided with mechanical

exhaust ventilation or fixed natural ventilation, where natural ventilation can be is shown to be acceptablefor [GH2 or LH2]. [55:6.15 16 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 11:36:27 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

88 of 491 1/30/2014 9:30 AM

First Revision No. 252-NFPA 2-2013 [ Section No. 6.17.1 ]

6.17.1 Ventilation Rate. Mechanical Exhaust Ventilation.

Mechanical exhaust or fixed natural ventilation shall be at a rate of not less than 1 scf/min/ft 2 (0.3048

Nm 3 /min/m 2 ) of floor area over the area of storage or use. [ 55: 6.16.3.2]

6.17.1.1 Mechanical Ventilation Rate.

Mechanical ventilation shall be at a rate of not less than 1 ft 3 /min/ft 2 (0.3048 m 3 /min/m 2 ) of floorarea over the area of storage or use. [ 55: 6. 15 .3]

6.17.1.2 Continuous Operation.

Systems shall operate continuously unless an alternate design is approved by the AHJ. [ 55: 6.15.4]

6.17.1.3 Shutoff Controls.

Where powered ventilation is provided, a manual shutoff switch shall be provided outside of the room ina position adjacent to the principal access door to the room or in an approved location. [ 55: 6.15.5]

6.17.1.4 Manual Shutoff Switch.

The switch shall be the break-glass or equivalent type and shall be labeled as follows:

WARNING:

VENTILATION SYSTEM EMERGENCY SHUTOFF

[ 55: 6.15.6]

6.17.1.5 Inlets to the Exhaust System.

6.17.1.5.1

The exhaust ventilation system design shall take into account the density of the potential gasesreleased. [ 55: 6.15.7.1]

6.17.1.5.2

For gases that are lighter than air, exhaust shall be taken from a point within 12 in. (304.8 mm) of theceiling. [ 55: 6.15.7.3]

6.17.1.5.3*

For gases that are heavier than air, exhaust shall be taken from a point within 12 in. (304.8 mm) of thefloor. [ 55: 6.15.7.2]

6.17.1.2 Floor Level Exhaust.

The location of both the exhaust and inlet air openings shall be designed to provide air movementacross all portions of the floor or room to prevent the accumulation of vapors. [ 55: 6.15.8]

6.17.1.7 Recirculation of Exhaust.

Exhaust ventilation shall not be recirculated within the room or building [-]. [ 55: 6.15.9]

6.17.1.8 Ventilation Discharge.

Ventilation systems shall discharge a minimum of 50 ft (15 m) from intakes of air-handling systems,air-conditioning equipment, and air compressors. [ 55: 6.15.10]

6.17.1.9 Air Intakes.

Storage and use of [GH 2 or LH 2 ] shall be located not less than 50 ft (15 m) from air intakes.

[ 55: 6.15.11]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 11:37:25 EDT 2013

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

89 of 491 1/30/2014 9:30 AM

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

90 of 491 1/30/2014 9:30 AM

First Revision No. 26-NFPA 2-2013 [ Section No. 6.17.2 ]

6.17.3 Natural Ventilation. (Reserved)

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 10:40:34 EDT 2013

Committee Statement

CommitteeStatement:

The reserved section section is no longer needed. Specific criteria for natural ventilation will beextracted to NFPA 2 as a result of the change to NFPA 55-2013, Section 6.16.3.2.

ResponseMessage:

Public Input No. 46-NFPA 2-2012 [Section No. 6.17.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

91 of 491 1/30/2014 9:30 AM

First Revision No. 277-NFPA 2-2013 [ Section No. 6.18 ]

6.18 Gas Cabinets.

Where a gas cabinet is required, is used to provide separation of gas hazards, or is used to increase thethreshold quantity for a gas requiring special provisions, the gas cabinet shall be in accordance with therequirements of 6.18.1 through 6.18.4. [55:6.16 17 ]

6.18.1 Construction.

6.18.1.1 Materials of Construction.

The gas cabinet shall be constructed of not less than 0.097 in. (2.46 mm) (12 gauge) steel.[55:6.16 17 .1.1]

6.18.1.2 Access to Controls.

The gas cabinet shall be provided with self-closing limited access ports or noncombustible windows togive access to equipment controls. [55:6.16 17 .1.2]

6.18.1.3 Self-Closing Doors.

The gas cabinet shall be provided with self-closing doors. [55:6.16 17 .1.3]

6.18.2 Ventilation Requirements.

The gas cabinet shall be provided with an exhaust ventilation system designed to operate at a negativepressure relative to the surrounding area. [55:6.16 17 .2.1]

6.18.3 Quantity Limits.

Gas cabinets shall contain not more than three cylinders, containers, cylinders, or tanks. [55:6.16 17 .4]

6.18.4 Separation of Incompatibles.

Incompatible gases, as defined by Table 7.2.1.1, shall be stored or used within separate gas cabinets.[55:6.16 17 .5]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 12:29:57 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

92 of 491 1/30/2014 9:30 AM

First Revision No. 278-NFPA 2-2013 [ Section No. 6.19 ]

6.19 Exhausted Enclosures.

6.19.1 Ventilation Requirements.

Where an exhausted enclosure is required or used to increase the threshold quantity for a gas requiringspecial provisions, the exhausted enclosure shall be provided with an exhaust ventilation system designedto operate at a negative pressure in relationship to the surrounding area. [55:6.17 18 .1]

6.19.2 Separation of Incompatible Gases within Enclosures.

6.19.2.1

Cylinders, containers, and tanks within enclosures shall be separated in accordance with Table 7.2.1.1.[55:6.17 18 .1.2]

6.19.2.2

Incompatible gases, as defined by Table 7.2.1.1, shall be stored or used within separate exhaustedenclosures. [55:6.17 18 .2]

6.19.3 Fire Protection.

Exhausted enclosures shall be internally sprinklered. [55:6.17 18 .1.3]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 12:31:57 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

93 of 491 1/30/2014 9:30 AM

First Revision No. 279-NFPA 2-2013 [ Section No. 6.20 ]

6.20* Source Valve.

Bulk gas systems shall be provided with a source valve. [55:6.18 19 ]

6.20.1

The source valve shall be marked. [55:6.18 19 .1]

6.20.2

The source valve shall be designated on the design drawings for the installation. [55:6.18 19 .2]

Supplemental Information

File Name Description

A.6.20_FR_279_.docx

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 12:33:14 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

94 of 491 1/30/2014 9:30 AM

A.6.20

Figure A.6.20 shows three possible locations of the source valve. [55:A.6.1819]

FIGURE A.6.20 Three Examples of Source Valve Locations. [55:A.6.1819]  

****INSERT FIGURE HERE****

 

First Revision No. 130-NFPA 2-2013 [ New Section after 6.20.2 ]

6.21 Cleaning and Purging of Piping Systems.

6.21.1 General.

6.21.1.1

[Hydrogen] systems shall be cleaned and purged in accordance with the requirements of Section 6.21when one or more of the following conditions exist:

(1) When the system is installed and prior to being placed into service.

(2) When there is a change in service.

(3)

(4)

[ 55: 7.1.19.1.1]

6.21.1.2

Cleaning and purging of the internal surfaces of [hydrogen] systems shall be conducted by qualifiedindividuals trained in cleaning and purging operations and procedures, including the recognition ofpotential hazards associated with cleaning and purging. [ 55: 7.1.19.1.2]

6.21.1.3*

A written cleaning or purging procedure shall be provided to establish the requirements for the cleaningand purging operations to be conducted. [ 55: 7.1.19.1.3]

6.21.1.3.1*

An independent or third party review of the written procedure shall be conducted after the procedure hasbeen written and shall:

(1) Evaluate hazards, errors, and malfunctions related to each step in the procedure.

(2) Review the measures prescribed in the procedure for applicability.

(3) Make recommendations for additional hazard mitigation measures if deemed to be necessary.

[ 55: 7.1.19.1.3.1]

6.21.1.3.2

The completed written procedure shall be:

(1) Maintained on site by the facility owner/operator

(2) Provided to operating personnel engaged in cleaning or purging operations

(3) Made available to the AHJ upon request

[ 55: 7.1.19.1.3.2]

6.21.1.3.3

Where generic cleaning or purging procedures have been established, a job specific operatingprocedure shall not be required. [ 55: 7.1.19.1.3.3]

6.21.1.3.4

Generic procedures shall be reviewed when originally published or when the procedure or operation ischanged. [ 55: 7.1.19.1.3.4]

6.21.1.4

Written procedures to manage a change to process materials, technology, equipment, procedures, andfacilities shall be established and implemented. [ 654: 4.3]

* When there are alterations or repair of the system, involving the replacement of parts or additionto the piping system and prior to returning the system to service.

* Where specified by the design standards or written procedures.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

95 of 491 1/30/2014 9:30 AM

6.21.1.4.1

The management-of-change procedures shall ensure that the following topics are addressed prior toany change:

(1) The technical basis for the proposed change

(2) The safety and health implications

(3) Whether the change is permanent or temporary

(4) Modifications to the cleaning and purging procedures

(5) Employee training requirements

(6) Authorization requirements for the proposed change

[ 56: 4.6.1]

6.21.1.4.2*

Implementation of the management-of-change procedures shall not be required for replacements-in-kind. [ 56: 4.6.2]

6.21.1.4.3

The written cleaning and purging procedure, as required by 6.21.1.3 , shall be updated to incorporatethe change. [ 56: 4.6.3]

6.21.1.5

Prior to cleaning or purging [in, hydrogen] piping systems shall be inspected and tested to determinethat the installation including the materials of construction, and method of fabrication, comply with therequirements of the design standard used and the intended application for which the system wasdesigned. [ 55: 7.1.19.1.5]

6.21.1.5.1

Inspection and testing of piping systems shall not be required to remove a system from service.[ 55: 7.1.19.1.5.1]

6.21.1.5.2*

Personnel in the affected area(s), as determined by the cleaning or purging procedure, shall beinformed of the hazards associated with the operational activity and notified prior to the initiation of anysuch activity. [ 55: 7.1.19.1.5.3]

Supplemental Information

File Name Description

A_6_x_1_1_FR_130_SB.docx

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 07 10:06:20 EDT 2013

Committee Statement

CommitteeStatement:

Committee generated first revision. TC added this text to address PI #64 and #66. TC feels thisshould not simple reference 55, but extract from appropriate sources. Since this addresses bothLH2 and GH2, this should be in the general chapter.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

96 of 491 1/30/2014 9:30 AM

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

97 of 491 1/30/2014 9:30 AM

  

A.6.x.1.1(c)

The replacement of parts in a system to repair leaks, the addition of gaskets, and similar routine maintenance is not intended to establish the need for cleaning of the entire piping system. Conversely, when a piping system is extended, or when the system needs to be rendered safe for maintenance purposes, purging the system [out of service] before disassembly will likely be required as will internal cleaning if new piping or materials of construction are introduced. [55: A.7.1.19.1.1(c)]

A.6.x.1.1(d)

Cleaning and purging of [hydrogen] systems can be conducted as individual functions, i.e., just cleaning or just purging, or in combination as required to satisfy the requirements of the procedures. [55:A.7.1.19.1.1(d)]

A.6.x.1.3

It is not intended that a new written procedure be required each time the activity occurs within a facility. [55:A.7.1.19.1.3]. Guidance on considerations for the written procedure is outlined in Section 4.3 of NFPA 56, Standard for Fire and Explosion Prevention During Cleaning and Purging of Flammable Gas Piping Systems.

A.6.x.1.3.1

The review of the written procedures should not be performed solely by the same person or persons responsible for developing the procedures. It can be performed by an independent person or group within the company or department or by a third-party consultant. [55: A.7.1.19.1.3.1]

A.6.x.1.4.2

Replacement-in-kind refers to a situation in which a piece of equipment is replaced with equipment of the same design and service. [56:A.4.5.2]

A.6.x.1.5.2

The notification is given to warn personnel that such procedures are about to occur so that they will be out of zones potentially affected by the cleaning or purging procedure. The intended notification is to be commensurate with the operation to be conducted and the timing of the notification should be relevant to the activity conducted so that personnel in the area can respond in a timely manner. Notification could consist of sounding of an audible and/or visible alarm, or it could consist of an announcement over a public address system, private network, radio, or similar and reliable means of electronic transmission.

Verbal notification can be used in operations where the piping system is limited to the area occupied by those that will be conducting the cleaning or purging procedures and related operating personnel. These areas are frequently found in occupancies where the gas used to charge the piping system is supplied from portable containers, as well as those areas where the piping system is primarily located in the occupied work area. [55:A.7.1.19.1.5.3]

 

First Revision No. 268-NFPA 2-2013 [ Section No. 7.1.3 ]

7.1.3 Listed and Approved Hydrogen Equipment.

Listed and approved hydrogen generating and consuming equipment shall be in accordance with thelisting requirements and manufacturers’ instructions. [55:7.1.3.1 7.1.4.1 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 11:55:12 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

98 of 491 1/30/2014 9:30 AM

First Revision No. 280-NFPA 2-2013 [ Sections 7.1.4.1.1, 7.1.4.1.2, 7.1.4.1.3, 7.1.4.1.4 ]

7.1.4.1.1

The storage and use of metal hydride storage systems shall be in accordance with 7.1.4.[55:7.1.4.1.1 7.1.5.1.1 ]

7.1.4.1.2 Metal Hydride Systems Storing or Supplying GH2.

Those portions of the system that are used as a means to store or supply GH2 shall also comply with

Sections 7.2 or 7.3 as applicable. [55:7.1.4.1.2 7.1.5.1.2 ]

7.1.4.1.3 Classification.

The hazard classification of the metal hydride storage system shall be based on the GH2 stored without

regard to the metal hydride content. [ 55: 7.1.5.1.3]

7.1.4.1.4* Listed or Approved Systems.

Metal hydride storage systems shall be listed or approved for the application and designed in a mannerthat prevents the addition or removal of the metal hydride by other than the original equipmentmanufacturer. [55:7.1.4.1.4 7.1.5.1.4 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 12:35:18 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

99 of 491 1/30/2014 9:30 AM

First Revision No. 271-NFPA 2-2013 [ Section No. 7.1.4.1.5 ]

7.1.4.1.5 Design and Construction of Containers.

[GH2] cylinders, containers, cylinders, and tanks used for metal hydride storage systems shall be

designed and constructed in accordance with 7.1.5.1. [55:7.1.4.1.5 7.1.5.1.5 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 11:56:17 EDT 2013

Committee Statement

Committee Statement: Update or extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

100 of 491 1/30/2014 9:30 AM

First Revision No. 281-NFPA 2-2013 [ Sections 7.1.4.1.6, 7.1.4.1.7, 7.1.4.1.8, 7.1.4.1.9 ]

7.1.4.1.6 Service Life and Inspection of Containers.

Metal hydride storage system cylinders, containers, or and tanks shall be inspected, tested, andrequalified for service at not less than 5-year intervals. [55:7.1.4.1.6 7.1.5.1.6 ]

7.1.4.1.7 Marking and Labeling.

Marking and labeling of cylinders, containers, tanks, and systems shall be in accordance with 7.1.5 andthe requirements in 7.1.4.1.7.1 through 7.1.4.1.7.4. [55:7.1.4.1.7 7.1.5.1.7 ]

7.1.4.1.7.1 System Marking.

Metal hydride storage systems shall be marked with the following: [55:7.1.4.1.7.1 7.1.5.1.7.1 ]

(1) Manufacturer’s name [55:7.1.4.1.7.1(1) 7.1.5.1.7.1(1) ]

(2) Service life indicating the last date the system can be used [55:7.1.4.1.7.1(2) 7.1.5.1.7.1(2) ]

(3) Unique A unique code or serial number specific to the unit [55:7.1.4.1.7.1(3) 7.1.5.1.7.1(3) ]

(4) System name or product code that identifies the system by the type of chemistry used in the system[55:7.1.4.1.7.1(4) 7.1.5.1.7.1(4) ]

(5) Emergency contact name, telephone number, or other contact information[55:7.1.4.1.7.1(5) 7.1.5.1.7.1(5) ]

(6) Limitations on refilling of containers to include rated charging pressure and capacity[55:7.1.4.1.7.1(6) 7.1.5.1.7.1(6) ]

7.1.4.1.7.2 Valve Marking.

Metal hydride storage system valves shall be marked with the following: [55:7.1.4.1.7.2 7.1.5.1.7.2 ]

(1) Manufacturer’s name [55:7.1.4.1.7.2(1) 7.1.5.1.7.2(1) ]

(2) Service life indicating the last date the valve can be used [55:7.1.4.1.7.2(2) 7.1.5.1.7.2(2) ]

(3) Metal hydride service in which the valve can be used or a product code that is traceable to thisinformation [55:7.1.4.1.7.2(3) 7.1.5.1.7.2(3) ]

7.1.4.1.7.3 Pressure Relief Device Marking.

Metal hydride storage system pressure relief devices shall be marked with the following:[ 55: 7.1.5.1.7.3]

(1) Manufacturer’s name [ 55: 7.1.5.1.7.3(1)]

(2) Metal hydride service in which the device can be used or a product code that is traceable to thisinformation [ 55: 7.1.5.1.7.3(2)]

(3) Activation parameters to include temperature, pressure, or both [ 55: 7.1.5.1.7.3(3)]

(A)

Metal hydride storage system pressure relief devices shall be marked with the following:[ 55: 7.1.5.1.7.3]

Manufacturer’s name [ 55: 7.1.5.1.7.3(1)]

Metal hydride service in which the device can be used or a product code that is traceable to thisinformation [ 55: 7.1.5.1.7.3(2)]

Activation parameters to include temperature, pressure, or both [ 55: 7.1.5.1.7.3(3)]

(A)

The required markings for pressure relief devices that are integral components of valves used oncylinders, containers, and tanks shall be allowed to be placed on the valve.[55:7.1.4.1.7.3(A) 7.1.5.1.7.3(A) ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

101 of 491 1/30/2014 9:30 AM

7.1.4.1.7.4 Pressure Vessel Markings.

Cylinders, containers, and tanks used in metal hydride storage systems shall be marked with thefollowing: [55:7.1.4.1.7.4 7.1.5.1.7.4 ]

(1) Manufacturer’s name [55:7.1.4.1.7.4(1) 7.1.5.1.7.4(1) ]

(2) Design specification to which the vessel was manufactured [55:7.1.4.1.7.4(2) 7.1.5.1.7.4(2) ]

(3) Authorized body approving the design and initial inspection and test of the vessel[55:7.1.4.1.7.4(3) 7.1.5.1.7.4(3) ]

(4) Manufacturer’s original test date [55:7.1.4.1.7.4(4) 7.1.5.1.7.4(4) ]

(5) Unique serial number for the vessel [55:7.1.4.1.7.4(5) 7.1.5.1.7.4(5) ]

(6) Service life identifying the last date the vessel can be used [55:7.1.4.1.7.4(6) 7.1.5.1.7.4(6) ]

(7) System name or product code that identifies the system by the type of chemistry used in the system[55:7.1.4.1.7.4(7) 7.1.5.1.7.4(7) ]

7.1.4.1.8 Temperature Extremes.

Metal hydride storage systems, whether full or partially full, shall not be exposed to artificially created hightemperatures exceeding 125°F (52°C) or subambient (low) temperatures unless designed for use underthe exposed conditions. [55:7.1.4.1.8 7.1.5.1.8 ]

7.1.4.1.9 Falling Objects.

Metal hydride storage systems shall not be placed in areas where they are capable of being damaged byfalling objects. [55:7.1.4.1.9 7.1.5.1.9 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 12:36:35 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

102 of 491 1/30/2014 9:30 AM

First Revision No. 282-NFPA 2-2013 [ Section No. 7.1.4.1.10 [Excluding any

Sub-Sections] ]

The refilling of listed or approved metal hydride storage systems shall be in accordance with the listingrequirements and manufacturers’ instructions. [55:7.1.4.1.11 7.1.5.1.11 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 12:39:23 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

103 of 491 1/30/2014 9:30 AM

First Revision No. 283-NFPA 2-2013 [ Section No. 7.1.4.1.10.1 ]

7.1.4.1.10.1 Industrial Trucks.

The refilling of metal hydride storage systems serving powered industrial trucks shall be in accordancewith NFPA 52 , Vehicular Fuel Systems Code the requirements of Chapter 10 . [ 55: 7.1.5.1.11.1]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 12:39:57 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

104 of 491 1/30/2014 9:30 AM

First Revision No. 284-NFPA 2-2013 [ Section No. 7.1.4.1.10.2 ]

7.1.4.1.10.2 Hydrogen Purity.

The purity of [GH2] used for the purpose of refilling containers shall be in accordance with the listing and

the manufacturers’ instructions. [55:7.1.4.1.11.2 7.1.5.1.11.2 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 12:40:44 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

105 of 491 1/30/2014 9:30 AM

First Revision No. 285-NFPA 2-2013 [ Section No. 7.1.4.1.11 ]

7.1.4.1.11 Electrical.

Electrical components for metal hydride storage systems shall be designed, constructed, and installed inaccordance with NFPA 70, National Electrical Code . [55:7.1.4.1.12 7.1.5.1.12 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 12:41:21 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

106 of 491 1/30/2014 9:30 AM

First Revision No. 286-NFPA 2-2013 [ Section No. 7.1.4.2 ]

7.1.4.2 Portable Containers or Systems.

7.1.4.2.1 Securing Containers.

Containers, cylinders, Cylinders, containers, and tanks shall be secured in accordance with 7.1.7.4.[55:7.1.4.2.1 7.1.5.2.1 ]

7.1.4.2.1.1 Use on Mobile Equipment.

Where a metal hydride storage system is used on mobile equipment, the equipment shall be designed torestrain cylinders, containers, cylinders, or tanks from dislodgement, slipping, or rotating when theequipment is in motion. [55:7.1.4.2.1.1 7.1.5.2.1.1 ]

7.1.4.2.1.2 Motorized Equipment.

(A)

Metal hydride storage systems used on motorized equipment shall be installed in a manner that protectsvalves, pressure regulators, fittings, and controls against accidental impact. [55:7.1.4.2.1.2 7.1.5.2.1.2 ]

(B)

Metal hydride storage systems, including cylinders, containers, tanks, and fittings, shall not extend beyondthe platform of the mobile equipment. [55:7.1.4.2.1.2(A) 7.1.5.2.1.2(A) ]

7.1.4.2.2 Valves.

Valves on cylinders, containers, cylinders, and tanks shall remain closed except when containers areconnected to closed systems and ready for use. [55:7.1.4.2.2 7.1.5.2.2 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 12:41:48 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

107 of 491 1/30/2014 9:30 AM

First Revision No. 287-NFPA 2-2013 [ Section No. 7.1.5 ]

7.1.5 Containers, Cylinders, Cylinders, Containers, and Tanks.

7.1.5.1 Design and Construction.

Containers, cylinders, Cylinders, containers, and tanks shall be designed, fabricated, tested, and marked(stamped) in accordance with regulations of DOT, Transport Canada (TC) Transportation of DangerousGoods Regulations, or the ASME Boiler and Pressure Vessel Code, “Rules for the Construction of UnfiredPressure Vessels,” Section VIII. [55:7.1.5.1 7.1.6.1 ]

7.1.5.2 Defective Containers, Cylinders, Cylinders, Containers, and Tanks.

7.1.5.2.1

Defective cylinders, containers, cylinders, and tanks shall be returned to the supplier.[55:7.1.5.2.1 7.1.6.2.1 ]

7.1.5.2.2

Suppliers shall either repair the cylinders, containers, cylinders, and tanks, remove them from service, ordispose of them in an approved manner. [55:7.1.5.2.2 7.1.6.2.2 ]

7.1.5.3 Supports.

Stationary cylinders, containers, and tanks shall be provided with engineered supports of noncombustiblematerial on noncombustible foundations. [55:7.1.5.3 7.1.6.3 ]

7.1.5.4 Containers, Cylinders, Cylinders, Containers, and Tanks Containing Residual Gas.

[GH2] cylinders, containers, cylinders, and tanks containing residual product shall be treated as full

except when being examined, serviced, or refilled by a gas manufacturer, authorized cylinder requalifier,or distributor. [55:7.1.5.4 7.1.6.4 ]

7.1.5.5 Pressure-Relief Devices.

7.1.5.5.1

When required by 7.1.5.5.2, pressure relief devices shall be provided to protect containers and systemscontaining [GH2] from rupture in the event of overpressure from thermal exposure. [55:7.1.5.5.1 7.1.6.5.1 ]

7.1.5.5.2

Pressure relief devices to protect containers shall be designed and provided in accordance with CGAS-1.1, Pressure Relief Device Standards— Part 1 — Cylinders for Compressed Gases, for cylinders; CGAS-1.2, Pressure Relief Device Standards— Part 2 — Cargo and Portable Tanks for Compressed Gases,for portable tanks; and CGA S-1.3, Pressure Relief Device Standards — Part 3 — Stationary StorageContainers for Compressed Gases, for stationary tanks or in accordance with applicable equivalentrequirements in the country of use. [55:7.1.5.5.2 7.1.6.5.2 ]

7.1.5.5.3

Pressure relief devices shall be sized in accordance with the specifications to which the container wasfabricated. [55:7.1.5.5.3 7.1.6.5.3 ]

7.1.5.5.4

The pressure relief device shall have the capacity to prevent the maximum design pressure of thecontainer or system from being exceeded. [55:7.1.5.5.4 7.1.6.5.4 ]

7.1.5.5.5

Pressure relief devices shall be arranged to discharge unobstructed to the open air in such a manner as toprevent any impingement of escaping gas upon the container, adjacent structures, or personnel. This

requirement shall not apply to DOT specification containers having an internal volume of 2.0 ft3 (0.057

m3) or less. [55:7.1.5.5.5 7.1.6.5.5 ]

7.1.5.5.6

Pressure relief devices or vent piping shall be designed or located so that moisture cannot collect andfreeze in a manner that would interfere with operation of the device. [55:7.1.5.5.6 7.1.6.5.6 ]

Submitter Information Verification

Submitter Full Name: James Grimard

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

108 of 491 1/30/2014 9:30 AM

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 12:43:01 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

109 of 491 1/30/2014 9:30 AM

First Revision No. 288-NFPA 2-2013 [ Section No. 7.1.6.1 ]

7.1.6.1 Containers.

Individual [GH2] cylinders, containers, cylinders, and tanks shall be marked or labeled in accordance with

DOT requirements or those of the applicable regulatory agency. [55:7.1.7.1 7.1.8.1 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 12:49:16 EDT 2013

Committee Statement

Committee Statement: Update of extracted text.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

110 of 491 1/30/2014 9:30 AM

First Revision No. 289-NFPA 2-2013 [ Section No. 7.1.6.2 ]

7.1.6.2 Label Maintenance.

The labels applied by the gas manufacturer to identify the liquefied or nonliquified [GH2] cylinder contents

shall not be altered or removed by the user. [55:7.1.7.2 7.1.8.2 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 12:49:51 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

111 of 491 1/30/2014 9:30 AM

First Revision No. 290-NFPA 2-2013 [ Section No. 7.1.6.3 ]

7.1.6.3 Stationary GH2Containers, Cylinders, Cylinders, Containers, and Tanks.

7.1.6.3.1

Stationary [GH2] cylinders, containers, cylinders, and tanks shall be marked in accordance with NFPA

704, Standard System for the Identification of the Hazards of Materials for Emergency Response .[55:7.1.7.3.1 7.1.8.3.1 ]

7.1.6.3.2

Markings shall be visible from any direction of approach. [55:7.1.7.3.2 7.1.8.3.2 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 12:50:28 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

112 of 491 1/30/2014 9:30 AM

First Revision No. 291-NFPA 2-2013 [ Section No. 7.1.6.4 ]

7.1.6.4 Piping Systems.

7.1.6.4.1

Except as provided in 7.1.6.4.2, piping systems shall be marked in accordance with ASME A13.1,Scheme for the Identification of Piping Systems, or other applicable approved [codes and] standards asfollows: [55:7.1.7.4.1 7.1.8.4.1 ]

(1) Marking shall include the name of the gas and a direction-of-flow arrow. [55:7.1.7.4.1(1) 7.1.8.4.1(1) ]

(2) Piping that is used to convey more than one gas at various times shall be marked to provide clearidentification and warning of the hazard. [55:7.1.7.4.1(2) 7.1.8.4.1(2) ]

(3) Markings for piping systems shall be provided at the following locations: [55:7.1.7.4.1(3) 7.1.8.4.1(3) ]

(a) At each critical process control valve [55:7.1.7.4.1(3)(a) 7.1.8.4.1(3)(a) ]

(b) At wall, floor, or ceiling penetrations [55:7.1.7.4.1(3)(b) 7.1.8.4.1(3)(b) ]

(c) At each change of direction [55:7.1.7.4.1(3)(c) 7.1.8.4.1(3)(c) ]

(d) At a minimum of every 20 ft (6.1 m) or fraction thereof throughout the piping run[55:7.1.7.4.1(3)(d) 7.1.8.4.1(3)(d) ]

7.1.6.4.2

Piping within gas manufacturing plants, gas processing plants, refineries, and similar occupancies shall bemarked in an approved manner. [55:7.1.7.4.2 7.1.8.4.2 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 12:51:46 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

113 of 491 1/30/2014 9:30 AM

First Revision No. 292-NFPA 2-2013 [ Section No. 7.1.7.1 ]

7.1.7.1 General.

[GH2] cylinders, containers, cylinders, tanks, and systems shall be secured against accidental

dislodgement and against access by unauthorized personnel. [55:7.1.8.1 7.1.9.1 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 12:52:30 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

114 of 491 1/30/2014 9:30 AM

First Revision No. 293-NFPA 2-2013 [ New Section after 7.1.7.2 ]

7.1.7.2.1

Administrative controls shall be allowed to be used to control access to individual storage, use, andhandling areas located in secure facilities not accessible by the general public. [ 55: 7.1.9.2.1]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 12:53:09 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

115 of 491 1/30/2014 9:30 AM

First Revision No. 294-NFPA 2-2013 [ Section No. 7.1.7.2 ]

7.1.7.2* Security of Areas.

Storage, use, and handling areas shall be secured against unauthorized entry. [55:7.1.8.2 7.1.9.2 ]

7.1.7.2.1

Administrative controls shall be allowed to be used to control access to individual storage, use, andhandling areas located in secure facilities not accessible by the general public. [ 55: 7.1.9.2.1]

Supplemental Information

File Name Description

A.7.1.7.2.docx

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 12:53:59 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

116 of 491 1/30/2014 9:30 AM

A.7.1.7.2 The goal of this requirement is to prevent unauthorized personnel or those unfamiliar with gas storage systems from tampering with the equipment as well as to prevent the inadvertent or unauthorized removal or use of compressed gases from storage areas. Where the compressed gases are located in an area open to the general public, a common practice is to fence and lock the storage or use area, with access restricted to supplier and use personnel. When the storage or use area is located within the user’s secure area and is not accessible by the general public, it is not always necessary to fence or otherwise secure the individual gas storage or use areas. Personnel access patterns may still mandate that the system be fenced, as determined by the supplier and the user. [55:A.7.1.9.2]

 

First Revision No. 295-NFPA 2-2013 [ Section No. 7.1.7.3.1 ]

7.1.7.3.1

[GH2] cylinders, containers, cylinders, tanks, and systems that could be exposed to physical damage

shall be protected. [55:7.1.8.3.1 7.1.9.3.1 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 12:56:19 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

117 of 491 1/30/2014 9:30 AM

First Revision No. 296-NFPA 2-2013 [ Section No. 7.1.7.3.2 ]

7.1.7.3.2

Guard posts or other means shall be provided to protect [GH2] cylinders, containers, cylinders, tanks,

and systems indoors and outdoors from vehicular damage. (See Section 4.14.) [55:7.1.8.3.2 7.1.9.3.2 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 12:56:56 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

118 of 491 1/30/2014 9:30 AM

First Revision No. 297-NFPA 2-2013 [ Section No. 7.1.7.4 ]

7.1.7.4 Securing GH2Containers, Cylinders, Cylinders, Containers, and Tanks.

[GH2] cylinders, containers, cylinders, and tanks in use or in storage shall be secured to prevent them

from falling or being knocked over by corralling them and securing them to a cart, framework, or fixedobject by use of a restraint, unless otherwise permitted by 7.1.7.4.1 and 7.1.7.4.2. [55:7.1.8.4 7.1.9.4 ]

7.1.7.4.1

[GH2] cylinders, containers, cylinders, and tanks in the process of examination, servicing, and refilling

shall not be required to be secured. [55:7.1.8.4.1 7.1.9.4.1 ]

7.1.7.4.2

At cylinder-filling plants, authorized cylinder requalifier’s facilities, and distributors’ warehouses, thenesting of cylinders shall be permitted as a means to secure cylinders. [55:7.1.8.4.2 7.1.9.4.2 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 12:57:37 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

119 of 491 1/30/2014 9:30 AM

First Revision No. 301-NFPA 2-2013 [ Section No. 7.1.8.1 ]

7.1.8.1* General.

[GH2] cylinder, container, cylinder, and tank valves shall be protected from physical damage by means of

protective caps, collars, or similar devices. [55:7.1.9.1 7.1.10.1 ]

7.1.8.1.1

Valve protection of individual valves shall not be required to be installed on individual cylinders,containers, or tanks installed on tube trailers or similar transportable bulk gas systems equipped withmanifolds that are provided with a means of physical protection that will protect the valves from physicaldamage when the equipment is in use. Protective systems required by DOT for over the road transportshall provide an acceptable means of protection. [ 55: 7.1.10.1.1]

7.1.8.1.1.1

Valve protection of individual valves shall not be required to be installed on individual cylinders,containers, or tanks that comprise bulk or non-bulk gas systems where the containers are stationary, orportable equipped with manifolds, that are provided with physical protection in accordance with4.1.4 and 7.1.7.3 or other approved means. Protective systems required by DOT for over the roadtransport shall provide an acceptable means of protection. [ 55: 7.1.10.1.1.1]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:02:33 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

120 of 491 1/30/2014 9:30 AM

First Revision No. 302-NFPA 2-2013 [ Section No. 7.1.8.2 ]

7.1.8.2 Valve-Protective Caps.

Where [GH2] cylinders, containers, cylinders, and tanks are designed to accept valve-protective caps,

the user shall keep such caps on the [GH2] cylinders, containers, cylinders, and tanks at all times, except

when empty, being processed, or connected for use. [55:7.1.9.2 7.1.10.2 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:03:20 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

121 of 491 1/30/2014 9:30 AM

First Revision No. 303-NFPA 2-2013 [ Section No. 7.1.9.1 [Excluding any Sub-Sections] ]

[GH2] cylinders, containers, cylinders, tanks, and systems in storage or use shall be separated from

materials and conditions that present exposure hazards to or from each other. [55:7.1.10.1.1 7.1.11.1.1 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:05:27 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

122 of 491 1/30/2014 9:30 AM

First Revision No. 304-NFPA 2-2013 [ Section No. 7.1.9.1.1 [Excluding any

Sub-Sections] ]

Combustible waste, vegetation, and similar materials shall be kept a minimum of 10 ft (3.1 m) from [GH2]

cylinders, containers, cylinders, tanks, and systems. [55:7.1.10.3 7.1.11.3 ]

Supplemental Information

File Name Description

A.7.1.9.1.1.docx

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:06:01 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

123 of 491 1/30/2014 9:30 AM

A.7.1.9.1.1 Figure A.7.1.9.1.1 is a schematic showing the separation distances required by 7.1.9.1.1. [55: A.7.1.110.2]

****INSERT FIGURE HERE****

FIGURE A.7.1.9.1.1 Separation of Gas Cylinders by Hazard. [55: A.7.1.110.2]

Clearance is required from combustible materials to minimize the effects of exposure fires to the materials stored or used. The requirement to separate the materials from vegetation should not be interpreted to mean that the area is maintained free of all vegetation. In some settings, gas systems are located on grounds that are maintained with formal landscaping. Some judgment must be exercised to determine whether the vegetation poses what might be viewed as an exposure hazard to the materials stored. Cut lawns, formal landscaping, and similar vegetation does not ordinarily present a hazard and should be allowed. On the other hand, tall dried grass or weeds and vegetation that fringes on the border of an urban-wildland interface might be viewed as a hazard. [55: A.7.1.110.3]

 

First Revision No. 305-NFPA 2-2013 [ Sections 7.1.9.1.1.1, 7.1.9.1.1.2 ]

7.1.9.1.1.1

A noncombustible partition without openings or penetrations and extending not less than 18 in. (457 mm)above and to the sides of the storage area shall be permitted in lieu of the minimum distance.[55:7.1.10.3.1 7.1.11.3.1 ]

7.1.9.1.1.2

The noncombustible partition shall either be an independent structure or the exterior wall of the buildingadjacent to the storage area. [55:7.1.10.3.2 7.1.11.3.2 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:06:57 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

124 of 491 1/30/2014 9:30 AM

First Revision No. 306-NFPA 2-2013 [ Sections 7.1.9.1.2, 7.1.9.1.3 ]

7.1.9.1.2 Ledges, Platforms, and Elevators.

[GH2] cylinders, containers, cylinders, and tanks shall not be placed near elevators, unprotected platform

ledges, or other areas where [GH2] cylinders, containers, cylinders, or tanks could fall distances

exceeding one-half the height of the cylinder, container, cylinder, or tank. [55:7.1.10.4 7.1.11.4 ]

7.1.9.1.3* Temperature Extremes.

[GH2] cylinders, containers, cylinders, and tanks, whether full or partially full, shall not be exposed to

temperatures exceeding 125°F (52°C) or subambient (low) temperatures unless designed for use undersuch exposure. [55:7.1.10.5 7.1.11.5 ]

7.1.9.1.3.1

Compressed gas cylinders, containers, and tanks that have not been designed for use under elevatedtemperature conditions shall not be exposed to direct sunlight outdoors where ambient temperaturesexceed 125°F (52°C). The use of a weather protected structure or shaded environment for storage oruse shall be permitted as a means to protect against direct exposure to sunlight. [ 55: 7.1.11.5.1]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:07:46 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

125 of 491 1/30/2014 9:30 AM

First Revision No. 129-NFPA 2-2013 [ New Section after 7.1.9.1.3 ]

7.1.9.1.3.1

Compressed gas cylinders, containers, and tanks that have not been designed for use under elevatedtemperature conditions shall not be exposed to direct sunlight outdoors where ambient temperaturesexceed 125°F (52°C). The use of a weather protected structure or shaded environment for storage oruse shall be permitted as a means to protect against direct exposure to sunlight. [ 55: 7.1.11.5.1]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 07 09:59:10 EDT 2013

Committee Statement

CommitteeStatement:

The proposed addition to chapter 7 was missed when extract text was updated. NFPA 55 hasrevised requirements relative to temperature effects by including the proposed text under a newSection 7.1.11.5.1. The following reason was considered when the item was deliberated during theROP phase of NFPA 55.

" The filling density for compressed gases is related to temperature and pressure. Filling densitiesand pressures are generally determined at 130°F. The 125°F (52°C) limitation provides a margin ofsafety to users of gaseous materials. When ambient temperatures exceed 125°F, and containers areexposed to direct sunlight, it is possible to exceed the 130°F threshold temperature limit internallycausing containers to become over-pressurized and leak, pressure relief valves to release, or in thecase of liquefied gas to expand to a point where the container may be subject to extreme hydraulicoverpressure. In areas where ambient temperatures are expected to exceed 125°F containers storedor used out of doors should be under weather protection, moved inside to a cooler environment orotherwise provided with shade to avoid direct contact with the rays of the sun."

ResponseMessage:

Public Input No. 94-NFPA 2-2013 [New Section after 7.1.9.1.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

126 of 491 1/30/2014 9:30 AM

First Revision No. 307-NFPA 2-2013 [ Sections 7.1.9.1.4, 7.1.9.1.5, 7.1.9.1.6, 7.1.9.1.7 ]

7.1.9.1.4 Falling Objects.

[GH2] cylinders, containers, cylinders, and tanks shall not be placed in areas where they are capable of

being damaged by falling objects. [55:7.1.10.6 7.1.11.6 ]

7.1.9.1.5 Heating.

[GH2] cylinders, containers, cylinders, and tanks, whether full or partially full, shall not be heated by

devices that could raise the surface temperature of the cylinder, container, cylinder, or tank to above125°F (52°C). [55:7.1.10.7 7.1.11.7 ]

7.1.9.1.5.1 Electrically Powered Heating Devices.

Electrical heating devices shall be in accordance with NFPA 70, National Electrical Code .[55:7.1.10.7.1 7.1.11.7.1 ]

7.1.9.1.5.2 Fail-Safe Design.

Devices designed to maintain individual [GH2] cylinders, containers, cylinders, or tanks at constant

temperature shall be designed to be fail-safe. [55:7.1.10.7.2 7.1.11.7.2 ]

7.1.9.1.6 Sources of Ignition.

Open flames and high-temperature devices shall not be used in a manner that creates a hazardouscondition. [55:7.1.10.8 7.1.11.8 ]

7.1.9.1.7 Exposure to Chemicals.

[GH2] cylinders, containers, cylinders, and tanks shall not be exposed to corrosive chemicals or fumes

that could damage cylinders, containers, cylinders, tanks, or valve-protective caps. [55:7.1.10.9 7.1.11.9 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:08:56 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

127 of 491 1/30/2014 9:30 AM

First Revision No. 309-NFPA 2-2013 [ Section No. 7.1.9.1.8 ]

7.1.9.1.8 Exposure to Electrical Circuits.

[GH2] containers, cylinders, and tanks shall not be placed where they could become a part of an electrical

circuit. [55:7.1.10.10 7.1.11.10 ]

7.1.9.1.8.1*

Electrical devices mounted on [GH 2 ] piping, cylinders, containers, or tanks shall be installed,

grounded, and bonded in accordance with the methods specified in NFPA 70 . [ 55: 7.1.11.10.1]

Supplemental Information

File Name Description

A.7.1.9.1.8.1_FR-309_.docx

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:11:17 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

128 of 491 1/30/2014 9:30 AM

A.7.1.9.1.8 Electrical devices can include pressure transducers, signal transmitters, shutoff controls, and similar devices. Some of these devices may be nonincendive and suitable for use in hazardous areas. Flammability of gases is not the only concern with respect to electrical circuits, because piping serving systems in use can act as conductors of electrical energy, exposing unrelated portions of the system to electrical hazards if improperly installed. [55: A.7.1.11.10.1]

 

First Revision No. 310-NFPA 2-2013 [ Sections 7.1.10, 7.1.11, 7.1.12, 7.1.13, 7.1.14 ]

7.1.10 Service and Repair.

Service, repair, modification, or removal of valves, pressure relief devices, or other [GH2] cylinder,

container, cylinder, or tank appurtenances shall be performed by trained personnel and with thepermission of the container owner. [55:7.1.11 7.1.12 ]

7.1.11 Unauthorized Use.

[GH2] cylinders, containers, cylinders, and tanks shall not be used for any purpose other than to serve as

a vessel for containing the product for which it was designed. [55:7.1.12 7.1.13 ]

7.1.12 Cylinders, Containers, Cylinders, and Tanks Exposed to Fire.

[GH2] cylinders, containers, cylinders, and tanks exposed to fire shall not be used or shipped while full or

partially full until they are requalified in accordance with the pressure vessel code under which they weremanufactured. [55:7.1.13 7.1.14 ]

7.1.13 Leaks, Damage, or Corrosion.

7.1.13.1* Removal From Service.

Leaking, damaged, or corroded [GH2] cylinders, containers, cylinders, and tanks shall be removed from

service. [55:7.1.14.1 7.1.15.1 ]

7.1.13.2 Replacement and Repair.

Leaking, damaged, or corroded [GH2] systems shall be replaced or repaired. [55:7.1.14.2 7.1.15.2 ]

7.1.13.3* Handling of Cylinders, Containers, Cylinders, and Tanks Removed from Service.

[GH2] cylinders, containers, cylinders, and tanks that have been removed from service shall be handled

in an approved manner. [55:7.1.14.3 7.1.15.3 ]

7.1.14 Surfaces.

7.1.14.1

To prevent bottom corrosion, cylinders, containers, cylinders, and tanks shall be protected from directcontact with soil or surfaces where water might accumulate. [55:7.1.15.1 7.1.16.1 ]

7.1.14.2

Surfaces shall be graded to prevent accumulation of water. [55:7.1.15.2 7.1.16.2 ]

Supplemental Information

File Name Description

A.7.1.13.3_FR_310_.docx

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:13:28 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

129 of 491 1/30/2014 9:30 AM

A.7.1.13.3

The gas supplier should be consulted for advice under these circumstances. [55: A.7.1.1415.3]  

First Revision No. 28-NFPA 2-2013 [ Section No. 7.1.15.2 ]

7.1.15.2 Aboveground Piping. (Reserved)

Piping, tubing, valves, and fittings shall be in accordance with 7.3.1.2.1 .

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 11:06:19 EDT 2013

Committee Statement

CommitteeStatement:

The proposed public input is provided to address those sections designated as reserved in the 2011Edition of the code is a product of a combined effort assigned to the members of the technicalcommittee and a task group designated as the Reserved Sections Task Group.

The term reserved is normally used by a technical committee to recognize that the committee thatdeveloped the material has an awareness that there is a need in the subject area identified, but didnot feel that there was time available during the initial document development process or that therewas a need for additional justification to create requirements on the subject for any number ofreasons, including: 1) a lack of existing data, 2) a limited amount of applied practices in the field, or3) an inability to reach consensus.

The proposed change addresses the need to provide general requirements for piping systems.

ResponseMessage:

Public Input No. 50-NFPA 2-2012 [Section No. 7.1.15.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

130 of 491 1/30/2014 9:30 AM

First Revision No. 311-NFPA 2-2013 [ Sections 7.1.15.3.1, 7.1.15.3.2 ]

7.1.15.3.1

Underground piping shall be of welded construction without valves, unwelded mechanical joints, orconnections installed underground. [55:7.1.17.1 7.1.18.1 ]

7.1.15.3.1.1

Valves or connections located in boxes or enclosures shall be permitted to be installed undergroundwhen where such boxes or enclosures are accessible from above ground and where the valves orconnections contained are isolated from direct contact with earth or fill. [55:7.1.17.1.1 7.1.18.1.1 ]

7.1.15.3.1.2

Valve boxes or enclosures installed in areas subject to vehicular traffic shall be constructed to resistuniformly distributed and concentrated live loads in accordance with the [adopted] building code for areasdesignated as vehicular driveways and yards, subject to trucking. [55:7.1.17.1.1.1 7.1.18.1.1.1 ]

7.1.15.3.1.3*

Piping installed in trench systems located below grade where the trench is open to above shall not beconsidered to be underground. [55:7.1.17.1.2 7.1.18.1.2 ]

7.1.15.3.2 Contact with Earth.

7.1.15.3.2.1

Gas piping in contact with earth or other material that could corrode the piping shall be protected againstcorrosion in an approved manner. [55:7.1.17.2 7.1.18.2 ]

7.1.15.3.2.2

When cathodic protection is provided, it shall be in accordance with 7.1.18. [55:7.1.17.2.1 7.1.18.2.1 ]

Supplemental Information

File Name Description

A.7.1.15.3.1.3_FR_311_.docx

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:16:16 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

131 of 491 1/30/2014 9:30 AM

A.7.1.15.3.1.3

Underground piping systems are those systems that are buried and in contact with earth fill or similar materials. Piping located in open-top or grated-top trenches is not considered to be underground although it may be below grade. [55: A.7.1.1718.1.2]

 

First Revision No. 312-NFPA 2-2013 [ Section No. 7.1.15.3.7 ]

7.1.15.3.7

In areas not subject to vehicle traffic, the pipe trench shall be deep enough to permit a cover of at least 12in. (300 mm) of well-compacted backfill material. [55:7.1.17.7 7.1.18.7 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:17:08 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

132 of 491 1/30/2014 9:30 AM

First Revision No. 313-NFPA 2-2013 [ Section No. 7.1.18 [Excluding any Sub-Sections] ]

Where required, cathodic protection shall be in accordance with 7.1.18. [55:7.1.6 7.1.7 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:18:07 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

133 of 491 1/30/2014 9:30 AM

First Revision No. 314-NFPA 2-2013 [ Sections 7.1.18.1, 7.1.18.2 ]

7.1.18.1 Operation.

Where installed, cathodic protection systems shall be operated and maintained to continuously providecorrosion protection. [55:7.1.6.1 7.1.7.1 ]

7.1.18.2 Inspection.

Container systems equipped with cathodic protection shall be inspected for [proper] operation by acathodic protection tester. The frequency of inspection shall be determined by the designer of the cathodicprotection system. [55:7.1.6.2 7.1.7.2 ]

7.1.18.2.1

The cathodic protection tester shall be certified as being qualified by the National Association of CorrosionEngineers, International (NACE). [55:7.1.6.2.1 7.1.7.2.1] ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:18:46 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

134 of 491 1/30/2014 9:30 AM

First Revision No. 315-NFPA 2-2013 [ New Section after 7.1.18.3 ]

7.1.18.3.1

The design limits of the cathodic protection system shall be available to the AHJ upon request.[ 55: 7.1.7.3.1]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:20:40 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

135 of 491 1/30/2014 9:30 AM

First Revision No. 316-NFPA 2-2013 [ Section No. 7.1.18.3 [Excluding any Sub-Sections]

]

Systems equipped with impressed current cathodic protection systems shall be inspected in accordancewith the requirements of the design and 7.1.18.2. The design limits shall be available to the AHJ uponrequest. [55:7.1.6.3 7.1.7.3 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:21:19 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

136 of 491 1/30/2014 9:30 AM

First Revision No. 317-NFPA 2-2013 [ Section No. 7.1.18.3.1 ]

7.1.18.3.2

The system owner shall maintain the following records to demonstrate that the cathodic protection is inconformance with the requirements of the design: [55:7.1.6.3.1 7.1.7.3.2 ]

(1) The results of inspections of the system [55:7.1.6.3.1(1) 7.1.7.3.2(1) ]

(2) The results of testing that has been completed [55:7.1.6.3.1(2) 7.1.7.3.2(2) ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:21:56 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

137 of 491 1/30/2014 9:30 AM

First Revision No. 318-NFPA 2-2013 [ Section No. 7.1.18.4 ]

7.1.18.4 Corrosion Expert.

Repairs, maintenance, or replacement of a cathodic protection system shall be under the supervision of acorrosion expert certified by NACE. [55:7.1.6.4 7.1.7.4 ]

7.1.18.4.1

The corrosion expert shall be certified by NACE as a senior corrosion technologist, a cathodic protectionspecialist, or a corrosion specialist or shall be a registered engineer with registration in a field that includeseducation and experience in corrosion control. [55:7.1.6.4.1 7.1.7.4.1 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:23:27 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

138 of 491 1/30/2014 9:30 AM

First Revision No. 319-NFPA 2-2013 [ Section No. 7.1.19 ]

7.1.19 Transfer.

Transfer of [GH2] between cylinders, containers, cylinders, and tanks shall be performed by qualified

personnel using equipment and operating procedures in accordance with CGA P-1, Safe Handling ofCompressed Gases in Containers. [55:7.3.1.9]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:23:55 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

139 of 491 1/30/2014 9:30 AM

First Revision No. 468-NFPA 2-2013 [ New Section after 7.1.20 ]

7.1.21 Equipment Enclosures.

7.1.21.1

Equipment enclosures shall be in accordance with 7.1.21.1.1 through 7.1.21.1.13 .

7.1.21.1.1

Hydrogen storage vessels within equipment enclosures shall be equipped with automatic emergencyshutoff valves to isolate the source of hydrogen from the delivery piping system.

7.1.21.1.1.1

Automatic shutoff control valves service the storage system shall be located within the samecompartment in which the storage vessels are located.

7.1.21.1.2

Hydrogen piping entering an enclosure compartment from any other compartment or an external sourceshall be equipped with an automatic shutoff control valve to stop the entry of hydrogen into thecompartment.

7.1.21.1.3

Enclosures or compartments within enclosures that contain hydrogen storage, generation, or otherhydrogen containing equipment not limited to compressors, hydrogen piping , or valves shall beequipped with hydrogen detection and fire detection systems.

7.1.21.1.3.1

Detection of hydrogen above 25 percent of the LFL shall be indicated on the local alarm indicationsystem.

7.1.21.1.3.2

Detection of hydrogen above 50 percent of the LFL shall result in activation of the emergency shutdowndevice ( ESD ) system, shutdown of compression equipment, and isolation of hydrogen storagevessels, isolation of hydrogen sources outside the module , and shall be indicated on the local alarmindication system(s).

7.1.21.1.3.3

All compartments containing hydrogen shall be equipped with fire detection devices that, whenactuated, shall result in activation of the ESD system, shutdown of compression equipment, isolation ofhydrogen storage vessels, isolation of hydrogen sources outside the module, and shall be indicated onthe alarm indication system(s).

7.1.21.1.4

Enclosures or compartments within enclosures with hydrogen containing equipment such as storage,compressors or valves shall be provided with mechanical or natural ventilation systems meeting therequirements of 7.1.17.1 and 7.1.17.2 .

7.1.21.1.5

Enclosure compartments equipped with hydrogen compressors, storage, or piping systems shall beequipped with explosion control systems in accordance with 6.9.2 .

7.1.21.1.5.1

Explosion vents shall not be discharged from one compartment to another within an equipmentenclosure.

7.1.21.1.5.2

The discharge from explosion vents shall be to an unoccupied space located on the property on whichthe equipment enclosure is installed.

7.1.21.1.6 Electrical Equipment.

7.1.21.1.6.1

Electrical equipment within enclosure compartments that contain hydrogen storage, generation, or otherhydrogen-containing equipment not limited to compressors, hydrogen piping, or valves shall beclassified in accordance with NFPA 70 .

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

140 of 491 1/30/2014 9:30 AM

7.1.21.1.6.2

Electrical equipment within enclosure compartments need not be classified where the compartmentmeets the following requirements:

(1) Compartments are sealed to prevent migration of hydrogen from adjacent compartments.

(2) Interconnecting conduits and penetrations are sealed in accordance with NFPA 70 .

(3) Ventilation intakes, where present, draw air from outside the classified area, no more than 18 in.(0.45 m) above grade level, and are designed to prevent the ingress of hydrogen releases fromadjacent equipment.

7.1.21.1.6.3

Enclosures or compartments within enclosures that contain unclassified electrical equipment shall beequipped with a hydrogen detection system in accordance with 7.1.21.1.3 where such compartment islocated within 15 ft (4.6 m) of a gaseous hydrogen storage system or 25 ft (7.6 m) of a liquid hydrogenstorage system.

7.1.21.1.7

Hydrogen shall not be vented within the equipment enclosure or to compartments within an equipmentenclosure.

7.1.21.1.7.1

Pressure relief devices and valves discharging to the atmosphere shall be vented in accordance withSection 7.1.5.5.5 .

7.1.21.1.8 Emergency Shutdown System.

7.1.21.1.8.1

When activated, the emergency shutdown system shall close all automatic shutoff control valves onpiping into and from the equipment enclosures and equipment compartments containing hydrogenequipment.

7.1.21.1.8.2

Equipment enclosures containing hydrogen equipment that are interconnected shall be provided with acommon emergency shutdown system.

7.1.21.1.8.3

A manual emergency shutdown device (ESD) shall be located on the exterior of each equipmentenclosure that is interconnected to the hydrogen system.

(A)

ESD(s) shall be identified by means of a sign located at the exterior of the equipment enclosure.

7.1.21.1.8.4

A remote emergency shutdown shall be located not less than 25 ft (7.6 m) and not more than 100 ft (30m) from equipment enclosures equipped with individual ESDs.

7.1.21.1.9

Equipment enclosures and enclosure compartments that contain a source of asphyxiating gas shall beequipped with an oxygen deficiency alarm system to alert personnel to the presence of an oxygen-deficient atmosphere.

7.1.21.1.9.1

An oxygen deficiency system is not required if the asphyxiating gas is flammable and if the enclosure orcompartment is equipped with a flammable gas detector.

7.1.21.1.10

Exterior doors service equipment enclosures shall be provided with locks or latches.

7.1.21.1.10.1

Locks or latches, if provided, shall not require the use of a key, a tool, or special knowledge or effort forthe operation from the egress side.

7.1.21.1.10.2

Locks or latches shall not be required for doors to equipment enclosures that are secured with anapproved perimeter fence or wall with access limited to authorized personnel.

7.1.21.1.11

Exits from equipment enclosures and equipment compartments for service personnel shall be inaccordance with Section 7.11 of NFPA 101 .

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

141 of 491 1/30/2014 9:30 AM

7.1.21.1.11.1

Not fewer than two means of egress shall be provided from each equipment enclosure or equipmentcompartment, unless all of the following criteria are met:

(1) Undivided equipment enclosures or equipment compartments do not exceed 200 ft 2 (18.6 m 2 ).

(2) Undivided equipment enclosures or equipment compartments have an occupant load notexceeding three persons.

(3) Equipment enclosures or equipment compartments have a travel distance to the room's orcompartment's exit door(s) not exceeding 25 ft (7620 mm).

(A)

Where two means of egress are required, the means of egress path shall connect the two means ofegress.

7.1.21.1.11.2

The means of egress shall:

(1) Be a minimum of 28 in. (710 mm) clear width

(2) Have a minimum headroom of not less than 6 ft, 8 in. (2030 mm) along the entire designatedmeans of egress path

7.1.21.1.11.3

Compliance with exit requirements from equipment enclosures and equipment compartments shall notbe required for enclosures that require operation or maintenance-related work to be performed from theexterior of the enclosure.

7.1.21.1.11.4

Entry into equipment enclosures or equipment compartments for the purpose of equipment replacementshall require that all hydrogen piping and equipment be depressurized and systems renderednonoperational before entry to the space is permitted.

7.1.21.1.11.5

Where not possible to provide internal access and egress, provision shall be made to:

(1) Perform maintenance work from the exterior of the enclosure

(2) Depressurize equipment prior to performing maintenance

7.1.21.1.12

Enclosures shall be installed and affixed to secure foundations constructed in accordance with therequirements of the adopted building code.

7.1.21.1.13 Location for Equipment Enclosures.

7.1.21.1.13.1

Equipment enclosures containing nonbulk hydrogen systems shall be located in accordance with7.2.3.3 .

7.1.21.1.13.2

Equipment enclosures containing bulk hydrogen compressed gas systems shall be located inaccordance with 7.3.2 .

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

142 of 491 1/30/2014 9:30 AM

Submittal Date: Mon Aug 05 10:20:24 EDT 2013

Committee Statement

CommitteeStatement:

Prefabricated enclosures such as shipping containers are being used widely to package hydrogencompression and storage equipment. These are used for both fueling stations and industrialsystems. There are a number of potential hazards that need to be addressed for these enclosures.These include personnel access, explosion control, safety equipment, shutdown devices, siting,electrical classification, etc. There is some confusion as to whether they should be considered“indoor” locations, “detached buildings”, or simply part of an outdoor equipment installation.

A definition should also be provided when an agreed upon description and scope is finalized forthese units.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

143 of 491 1/30/2014 9:30 AM

First Revision No. 320-NFPA 2-2013 [ Section No. 7.1.21.1 [Excluding any Sub-Sections]

]

Accessible manual or automatic emergency shutoff valves shall be provided to shut off the flow of GH2 in

case of emergency. [ 55: 7.3.1.11.1]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:24:39 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

144 of 491 1/30/2014 9:30 AM

First Revision No. 321-NFPA 2-2013 [ Section No. 7.1.21.1.1 ]

7.1.22.1.1*

Emergency Manual emergency shutoff valves or the device that activates an automatic emergencyshutoff valve on a bulk source or piping systems serving the bulk supply shall be identified by means of asign. [ 55: 7.3.1.11.1.1]

Supplemental Information

File Name Description

A.7.1.21.1.1.docx

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:25:11 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

145 of 491 1/30/2014 9:30 AM

A.7.1.21.1.1 In operations where an automatic emergency shutoff valve is activated by a control system that is operated from a remote station or by remote station software, the software system should be designed to provide a visual indication of the emergency shutdown control system. The visual emergency shutdown function should be able to be identified by trained operators and recognizable to emergency response personnel. [55: A.7.3.1.11.1.1]

 

First Revision No. 322-NFPA 2-2013 [ Section No. 7.1.21.2 ]

7.1.22.2

Emergency shutoffs shall be located at the point of use and at the tank, cylinder, or bulk source [ , and atthe point where the system piping enters the building] . [55:7.3.1.11.2]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:25:40 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

146 of 491 1/30/2014 9:30 AM

First Revision No. 29-NFPA 2-2013 [ Section No. 7.1.22.1 [Excluding any Sub-Sections] ]

Where [GH2] [-] is carried in pressurized piping above a gauge pressure of 15 psi (103 kPa), an approved

means of either leak detection and with automatic emergency shutoff or excess flow control shall beprovided. [55:7.3.1.12.1] [-]

Supplemental Information

File Name Description

A.7.1.22.1.docx

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 11:26:42 EDT 2013

Committee Statement

CommitteeStatement:

To avoid confusion the requirement should clarify that the emergency shutoff is processed bythe equipment automatically rather than relying on an operator's action.

Note that since this is a change from the original text extracted from NFPA 55, we have droppedthe extract tag.

ResponseMessage:

Public Input No. 52-NFPA 2-2012 [Section No. 7.1.22.1 [Excluding any Sub-Sections]]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

147 of 491 1/30/2014 9:30 AM

A.7.1.22.1 An approved means of leak detection and emergency shutoff is one way of meeting the requirements for excess flow control. [55:7.3.1.12.1]

 

First Revision No. 323-NFPA 2-2013 [ Section No. 7.1.22.1.2 ]

7.1.23.1.2 Excess Flow Control Location with Bulk Storage.

Where the piping originates from a bulk source, the excess flow control shall be located at the bulk sourceat the point immediately downstream of the source valve . [55:7.3.1.12.1.2]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:27:31 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

148 of 491 1/30/2014 9:30 AM

First Revision No. 324-NFPA 2-2013 [ Section No. 7.1.22.1.4 ]

7.1.23.1.4 Location Exemptions.

The requirements of 7.1.23.1 shall not apply to the following: [ 55: 7.3.1.12.4]

(1) Piping for inlet connections designed to prevent backflow [ 55: 7.3.1.12.4(1)]

(2) Piping for pressure-relief devices pressure relief devices [ 55: 7.3.1.12.4(2)]

(3) Systems containing 400 430 scf (12.7 m Nm 3) or less of [GH2] [55:7.3.1.12.4(3) ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:28:16 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

149 of 491 1/30/2014 9:30 AM

First Revision No. 325-NFPA 2-2013 [ Section No. 7.1.23 ]

7.1.24 Ignition Source Control.

Ignition sources in areas containing [GH2] shall be in accordance with 7.1.24. [55:7.6.3 7.6.4 ]

7.1.24.1 Static Producing Equipment.

Static producing equipment located in [GH2] areas shall be grounded. [55:7.6.3.1 7.6.4.1 ]

7.1.24.2 No Smoking or Open Flame.

Signs shall be posted in areas containing [GH2] stating that smoking or the use of open flame, or both, is

prohibited within 25 ft (7.6 m) of the storage or use area perimeter. [55:7.6.3.2 7.6.4.2 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:29:34 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

150 of 491 1/30/2014 9:30 AM

First Revision No. 30-NFPA 2-2013 [ Section No. 7.2.1 ]

7.2.1 Nonbulk GH2 General. (Reserved)

7.2.1.1* Incompatible Materials.

[GH2] cylinders, containers, cylinders, and tanks shall be separated in accordance with Table 7.2.1.1.

[55:7.1.10.2 7.1.11.2 ]

Table 7.2.1.1 Separation of Gas Cylinders, Containers, and Tanks by Hazard Class [from Nonbulk GH 2Cylinders, Containers, Tanks, and Systems]

GH 2a

Gas Category ft m

Toxic or highly toxic 20 6.1

Pyrophoric 20 6.1

Flammable — —

Oxidizing 20 6.1

Corrosive 20 6.1

Unstable reactive Class 2, Class 3, or Class 4 20 6.1

Other gas NR NR

NR: No separation required.

[ 55: 7.1.11.2]

a Extract of flammable gas column from Table 7.1.11.2 of NFPA 55 .

7.2.1.1.1

Bulk GH2 systems in outdoor storage or use shall be separated from other compressed gases in

accordance with Table 7.3.2.3.1.1(A)(a) or Table 7.3.2.3.1.1(A)(b).

Table 7.2.1.1.1 Separation of Gas Cylinders, Containers, and Tanks by Hazard Class [from NonbulkGH 2 Cylinders, Containers, Tanks, and Systems]

GH 2a

Gas Category ft m

Toxic or highly toxic 20 6.1

Pyrophoric 20 6.1

Flammable — —

Oxidizing 20 6.1

Corrosive 20 6.1

Unstable reactive Class 2, Class 3, or Class 4 20 6.1

Other gas NR NR

NR: No separation required.

[ 55: 7.1.11.2]

a Extract of flammable gas column from Table 7.1.11.2 of NFPA 55 .

7.2.1.1.2

Subparagraph 7.2.1.1.1 shall not apply to [GH 2 ] contained within closed piping systems.[ 55: 7.1.11.2.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

151 of 491 1/30/2014 9:30 AM

7.2.1.1.3

The distances shown in Table 7.2.1.1 shall be permitted to be reduced without limit [when GH2] cylinders,

tanks, and containers, and tanks are separated by a barrier of noncombustible construction that has a fireresistance rating of at least 0.5 hour and interrupts the line of sight between the containers.[55:7.1.10.2.1 7.1.11.2.2 ]

7.2.1.1.4

The 20 ft (6.1 m) distance shall be permitted to be reduced to 5 ft (1.5 m) where one of the gases isenclosed in a gas cabinet or without limit where both gases are enclosed in gas cabinets.[55:7.1.10.2.2 7.1.11.2.3 ]

7.2.1.1.5

Cylinders without pressure-relief devices shall not be stored without separation from flammable andpyrophoric gases with pressure-relief devices. [55:7.1.10.2.3 7.1.11.2.4 ]

7.2.1.1.6

Spatial separation shall not be required between cylinders deemed to be incompatible that in gasproduction facilities where cylinders are connected to manifolds for the purposes of filling and , analysisof compressed gases, or manufacturing procedures, assuming the prescribed controls for themanufacture of gas mixtures are in place. [55:7.1.10.2.4 7.1.11.2.5 ]

Supplemental Information

File Name Description

FR_30_Material.1375716958788.docx

A.7.2.1.1_FR_30_.docx

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 11:34:15 EDT 2013

Committee Statement

CommitteeStatement:

The proposed public input is provided to address those sections designated as reserved in the 2011Edition of the code is a product of a combined effort assigned to the members of the technicalcommittee and a task group designated as the Reserved Sections Task Group.

The term reserved is normally used by a technical committee to recognize that the committee thatdeveloped the material has an awareness that there is a need in the subject area identified, but didnot feel that there was time available during the initial document development process or that therewas a need for additional justification to create requirements on the subject for any number ofreasons, including: 1) a lack of existing data, 2) a limited amount of applied practices in the field, or3) an inability to reach consensus.

For this section, the "reserved" designation is not needed. The section is a title for generalrequirements in addition to those provided in 7.1. This approach is consistent with Section 7.2.2.1.

ResponseMessage:

Public Input No. 49-NFPA 2-2012 [Section No. 7.2.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

152 of 491 1/30/2014 9:30 AM

7.2.1 Nonbulk GH2 General. (Reserved)

7.2.1.1 Incompatible Materials. [GH2] cylinders, containers, cylinders, and tanks shall be separated in accordance with Table 7.2.1.1.1. [55:7.1.1011.2]

7.2.1.1.1 Bulk GH2 systems in outdoor storage or use shall be separated from other compressed gases in accordance with Table 7.3.2.3.1.2(a) or Table 7.3.2.3.1.2(b).

Table 7.2.1.1.1 Separation of Gas Cylinders, Containers, Cylinders, and Tanks by Hazard Class [from Nonbulk GH2 Cylinders, Containers, Tanks, and Systems]

GH2a

Gas Category ft m

Toxic or highly toxic 20 6.1

Pyrophoric 20 6.1

Flammable — —

Oxidizing 20 6.1

Corrosive 20 6.1

Unstable reactive Class 2, Class 3, or Class 4 20 6.1

Other gas NR NR

NR: No separation required.

[55:7.1.1011.2]

aExtract of flammable gas column from Table 7.1.10.2 of NFPA 55, Compressed Gases and Cryogenic Fluids Code.

7.2.1.1.2 Subparagraph 7.2.1.1 shall not apply to [GH2] contained within closed piping systems. [55:7.1.11.2.1]

7.2.1.1.23 The distances shown in Table 7.2.1.1.1 shall be permitted to be reduced without limit [when GH2] cylinders, containers, and tanks, and containers are separated by a barrier of noncombustible construction that has a fire resistance rating of at least 0.5 hour and interrupts the line of sight between the containers. [55:7.1.1011.2.12]

7.2.1.1.34 The 20 ft (6.1 m) distance shall be permitted to be reduced to 5 ft (1.5 m) where one of the gases is enclosed in a gas cabinet or without limit where both gases are enclosed in gas cabinets. [55:7.1.1011.2.23]

7.2.1.1.45 Cylinders without pressure relief devices shall not be stored without separation from flammable and pyrophoric gases with pressure relief devices. [55:7.1.1011.2.34]

7.2.1.1.56 Spatial separation shall not be required between cylinders deemed to be incompatible in gas production facilities where cylinders are that are connected to manifolds for

the purposes of filling, analysis of compressed gases, or and manufacturing procedures, assuming the prescribed controls for the manufacture of gas mixtures are in place. [55:7.1.1011.2.45]

A.7.2.1.1

Figure A.7.2.1.1 is a schematic showing the separation distances required by 7.2.1.1. [55:A.7.1.11.2]

FIGURE A.7.2.1.1 Separation of Gas Cylinders by Hazard. [55:A.7.1.11.2]  

****INSERT FIGURE HERE****  

 

Formatted: Font: Bold

Formatted: Font: Bold

Formatted: Font: Bold

First Revision No. 326-NFPA 2-2013 [ New Section after 7.2.2.2.1 ]

7.2.2.2.2 Indoor Hydrogen System Location.

7.2.2.2.2.1

Hydrogen systems of less than 3500 scf (142 Nm 3 ) and greater than the MAQ, where located insidebuildings, shall be in accordance with the following: [ 55: 7.6.3.1]

(1) In a ventilated area in accordance with the provisions of Section 6.17 [ 55: 7.6.3.1(1)]

(2) Separated from incompatible materials in accordance with the provisions of 7.2.1.1[ 55: 7.6.3.1(2)]

(3) A distance of 25 ft (7.6 m) from open flames and other sources of ignition [ 55: 7.6.3.1(3)]

(4) A distance of 50 ft (15 m) from intakes of ventilation, air-conditioning equipment, and aircompressors located in the same room or area as the hydrogen system [ 55: 7.6.3.1(4)]

(a) The distance shall be permitted to be reduced to 10 ft (3.1 m) where the room or area inwhich the hydrogen system is installed is protected by a listed detection system as perArticle 500.7(K) of NFPA 70 and the detection system shall shut down the fuel supply inthe event of a leak that results in a concentration that exceeds 25 percent of the LFL.[ 55: 7.6.3.1(4)(a)]

(b) Emergency shutoff valves shall be provided in accordance with 7.1.21 . [ 55: 7.6.3.1(4)(b)]

(5) A distance of 50 ft (15 m) from other flammable gas storage [ 55: 7.6.3.1(5)]

(6) Protected against damage in accordance with the provisions of 7.1.7.3 [ 55: 7.6.3.1(6)]

7.2.2.2.2.2 Systems Installed in One Room.

(A)

More than one system of 3500 scf (99 Nm 3 ) or less shall be permitted to be installed in the same roomor area, provided the systems are separated by at least 50 ft (15 m) or a full-height fire-resistive partitionhaving a minimum fire resistance rating of 2 hours is located between the systems. [ 55: 7.6.3.2.1]

(B)

The separation distance between multiple systems of 3500 scf (99 Nm 3 ) or less shall be permitted tobe reduced to 25 ft (7.6 m) in buildings where the space between storage areas is free of combustiblematerials and protected with a sprinkler system designed for Extra Hazard, Group 1 in accordance withthe requirements of Section 6.10 . [ 55: 7.6.3.2.2]

(C)

The required separation distance between individual portable systems in the process of being filled orserviced in facilities associated with the manufacture or distribution of hydrogen and its mixtures shallnot be limited by 7.2.2.2.2.2(A) or 7.2.2.2.2.2(B) when such facilities are provided with ProtectionLevel 2 controls and the applicable requirements of Chapters 1 through 7 . [ 55: 7.6.3.2.3]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:37:42 EDT 2013

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

153 of 491 1/30/2014 9:30 AM

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

154 of 491 1/30/2014 9:30 AM

First Revision No. 327-NFPA 2-2013 [ Section No. 7.2.2.3.2.1(A) ]

(A)*

Where a protective structure fire barrier is used to protect [GH2] systems, the system shall terminate

downstream of the source valve. [55:7.6.2.1.1 7.5.2.1.1 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:39:26 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

155 of 491 1/30/2014 9:30 AM

First Revision No. 328-NFPA 2-2013 [ Section No. 7.2.2.3.2.1(B) ]

(B)

The fire barrier wall shall be either an independent structure or the exterior wall of the building adjacent tothe storage or use area. [55:7.6.2.1.2 7.5.2.1.2 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:40:06 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

156 of 491 1/30/2014 9:30 AM

First Revision No. 329-NFPA 2-2013 [ Sections 7.2.4.2, 7.2.4.3 ]

7.2.4.2 Carts and Trucks.

7.2.4.2.1

Cylinders, C c ontainers, cylinders, and tanks shall be moved using an approved method. [55:7.3.3.2.1]

7.2.4.2.2

Where cylinders, containers, cylinders, or tanks are moved by hand cart, hand truck, or other mobiledevice, such carts, trucks, or devices shall be designed for the secure movement of cylinders, containers,cylinders , or tanks. [55:7.3.3.2.2]

7.2.4.3 Lifting Devices.

Ropes, chains, or slings shall not be used to suspend [GH2] cylinders, containers, cylinders, and tanks

unless provisions at time of manufacture have been made on the cylinder, container, cylinder, or tank forappropriate lifting attachments, such as lugs. [55:7.3.3.3]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:42:59 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

157 of 491 1/30/2014 9:30 AM

First Revision No. 330-NFPA 2-2013 [ Section No. 7.3.1.1 ]

7.3.1.1 Applicability.

The storage, use, and handling of bulk [bulk GH2] systems shall be in accordance with the applicable

provisions of Chapters 1 through 6, as applicable, and Section 7.3. [55:10.1]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:44:30 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

158 of 491 1/30/2014 9:30 AM

First Revision No. 331-NFPA 2-2013 [ Section No. 7.3.1.2.1 ]

7.3.1.2.1*

Piping, tubing, valves, and fittings shall be designed and installed in accordance with ASME B31.12,Hydrogen Piping and Pipelines , 7.1.15.1 and Sections 704.1.2.3, 704.1.2.4, and 704.1.2.5 of the ICCInternational Fuel Gas Code (IFGC). Cast-iron pipe, valves, and fittings shall not be used.[55:10.2.1 10.2.2 ]

Supplemental Information

File Name Description

A_7_3_1_2_1_FR_331_SB.docx

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:46:47 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

159 of 491 1/30/2014 9:30 AM

A.7.3.1.2.1

Any reference to listed or approved equipment in the noted sections of the IFGC is within the context of the ANSI/ASME B31.3, Process Piping, standard and describes a material or component thatwhich conforms to the specifications integral to ANSI/ASME B31.3. [55: A.10.2.21]

 

First Revision No. 332-NFPA 2-2013 [ Section No. 7.3.1.2.2 ]

7.3.1.2.2 Pressure Relief Devices GH 2 Venting Systems .

Hydrogen-venting systems serving pressure relief devices discharging [GH 2 ] to the atmosphere shall

be in accordance with CGA G-5.5, Hydrogen Vent Systems. [55:10.2.2 10.2.3 ]

7.3.1.2.2.1

Venting from the relief vents from the hydrogen supply piping serving listed fuel cell power systems shallbe permitted to be discharged into an enclosure integral to the fuel cell system where the concentration ofhydrogen is diluted below 25 percent of the lower flammable limit (LFL) at the outlet of the enclosure.[55:10.2.2.1 10.2.3.1 ]

7.3.1.2.2.2

The hydrogen supply piping system shall be designed to isolate the source of hydrogen from the reliefvent in the event of loss of dilution ventilation or power. [55:10.2.2.2 10.2.3.1.1 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:47:45 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

160 of 491 1/30/2014 9:30 AM

First Revision No. 333-NFPA 2-2013 [ Sections 7.3.1.2.3.1, 7.3.1.2.3.2 ]

7.3.1.2.3.1

In addition to the requirements of 7.1.15.1, brazing materials used for joints in piping and tubing systemsshall have a melting point above 1000°F (538°C). [55:10.2.3.1 10.2.2.2 ]

7.3.1.2.3.2

Underground piping systems shall be in accordance with 7.1.15.3. [55:10.2.3.2 10.2.2.3 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:49:46 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

161 of 491 1/30/2014 9:30 AM

First Revision No. 334-NFPA 2-2013 [ Section No. 7.3.1.2.4.1 ]

7.3.1.2.4.1

Valves, gauges, regulators, and other accessories used for bulk hydrogen compressed gas systems shallbe specified for hydrogen service by the manufacturer or the hydrogen supplier. [55:10.2.4.1]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:50:37 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

162 of 491 1/30/2014 9:30 AM

First Revision No. 335-NFPA 2-2013 [ Section No. 7.3.1.2.4.2 ]

7.3.1.2.4.2

Storage containers, piping, valves, regulating equipment, and other accessories appurtenances servingbulk hydrogen compressed gas systems shall be accessible and shall be protected against physicaldamage and tampering. [55:10.2.4.1.1]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:51:19 EDT 2013

Committee Statement

Committee Statement: Update to extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

163 of 491 1/30/2014 9:30 AM

First Revision No. 336-NFPA 2-2013 [ Section No. 7.3.1.2.4.3 ]

7.3.1.2.4.3

Cabinets or enclosures containing hydrogen control or operating equipment shall be ventilated tominimize prevent the accumulation of hydrogen. [55:10.2.4.2]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:52:00 EDT 2013

Committee Statement

Committee Statement: Update to extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

164 of 491 1/30/2014 9:30 AM

First Revision No. 487-NFPA 2-2013 [ Section No. 7.3.1.2.4.4 ]

7.3.1.2.4.4

Mobile hydrogen supply units used as part of a bulk hydrogen compressed gas system shall be securedto prevent movement. [55:10.2.4.3]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Sep 06 09:12:41 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

165 of 491 1/30/2014 9:30 AM

First Revision No. 337-NFPA 2-2013 [ Section No. 7.3.1.2.4.5 ]

7.3.1.2.4.5

Mobile hydrogen supply units shall be electrically bonded to the storage system before hydrogen isdischarged from the supply unit. [55:10.2.4.4 10.2.5.1 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:54:06 EDT 2013

Committee Statement

Committee Statement: Update to extract text.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

166 of 491 1/30/2014 9:30 AM

First Revision No. 338-NFPA 2-2013 [ Sections 7.3.1.2.5.1, 7.3.1.2.5.2 ]

7.3.1.2.5.1

Hazard identification signs shall be provided in accordance with 4.13.2. [55:10.2.5.1 10.2.1.1 ]

7.3.1.2.5.2

In addition, the area in which a hydrogen system is located shall be permanently placarded as follows:

WARNING: HYDROGEN — FLAMMABLE GAS — NO SMOKING — NO OPEN FLAMES

[55:10.2.5.2 10.2.1.2 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:54:46 EDT 2013

Committee Statement

Committee Statement: Update to extract text.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

167 of 491 1/30/2014 9:30 AM

First Revision No. 339-NFPA 2-2013 [ Section No. 7.3.1.2.6 ]

7.3.1.2.6 Bonding and Grounding.

The [GH 2 ] bulk hydrogen compressed gas system shall be electrically bonded and grounded.

[55:10.2.6 10.2.5 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:55:33 EDT 2013

Committee Statement

Committee Statement: Update to extract text

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

168 of 491 1/30/2014 9:30 AM

First Revision No. 340-NFPA 2-2013 [ Section No. 7.3.1.2.7.1 ]

7.3.1.2.7.1

Prior to acceptance and initial operation, all piping installations shall be inspected and pressure tested inaccordance with ASME B31.12, Hydrogen Piping and Pipelines and ICC International Fuel Gas Code(IFGC), Section 705. [55:10.5.1 10.2.2.1 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:56:13 EDT 2013

Committee Statement

Committee Statement: Update to extract text

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

169 of 491 1/30/2014 9:30 AM

First Revision No. 342-NFPA 2-2013 [ Section No. 7.3.1.2.7.2(A) ]

(A)

For installations that require any operation of equipment by the user, the user shall be instructed in theoperation of the equipment and emergency shutdown procedures. [55:10.5.2.1 10.2.7.1.1 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 13:59:58 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

170 of 491 1/30/2014 9:30 AM

First Revision No. 343-NFPA 2-2013 [ Section No. 7.3.1.2.7.2(B) ]

(B)

Instructions shall be maintained at the operating site at a location acceptable to the AHJ authority havingjurisdiction . [55:10.5.2.2 10.2.7.1.2 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 14:00:34 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

171 of 491 1/30/2014 9:30 AM

First Revision No. 344-NFPA 2-2013 [ Section No. 7.3.1.2.8 ]

7.3.1.2.8 Maintenance.

Maintenance shall be performed annually by a qualified representative of the equipment owner. Themaintenance shall include inspection for physical damage, leak tightness, ground system integrity, ventsystem operation, equipment identification, warning signs, operator information and training records,scheduled maintenance and retest records, alarm operation, and other safety-related features. Scheduledmaintenance and retest activities shall be formally documented and records shall be maintained aminimum of 3 years. [ 55: 10.5.3]

7.3.1.2.8.1

Maintenance shall be performed annually by a qualified representative of the equipment owner.[ 55: 10.2.7.2.1]

7.3.1.2.8.2

The maintenance shall include inspection for physical damage, leak tightness, ground system integrity,vent system operation, equipment identification, warning signs, operator information and trainingrecords, scheduled maintenance and retest records, alarm operation, and other safety-related features.[ 55: 10.2.7.2.2]

7.3.1.2.8.3

Scheduled maintenance and retest activities shall be formally documented and records shall bemaintained a minimum of 3 years. [ 55: 10.2.7.2.3]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 14:01:38 EDT 2013

Committee Statement

Committee Statement: Update extract materail

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

172 of 491 1/30/2014 9:30 AM

First Revision No. 345-NFPA 2-2013 [ Section No. 7.3.2.1.2 ]

7.3.2.1.2

Systems within 50 ft (15 m) of aboveground storage of all classes of flammable and combustible liquidsshall be located on ground higher than such storage, except where dikes, diversion curbs, grading, orseparating solid walls are used to prevent accumulation of these liquids under the system.[ 55: 10.3.1.2]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 14:04:03 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

173 of 491 1/30/2014 9:30 AM

First Revision No. 346-NFPA 2-2013 [ Section No. 7.3.2.1.3 [Excluding any

Sub-Sections] ]

Compression and gas processing equipment integral to bulk hydrogen compressed gas storage systemsshall be designed for use with GH2 and for maximum pressures and temperatures to which it can be

subjected under normal operating conditions. [55:10.8 10.2.6 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 14:04:41 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

174 of 491 1/30/2014 9:30 AM

First Revision No. 347-NFPA 2-2013 [ Sections 7.3.2.1.3.1, 7.3.2.1.3.2, 7.3.2.1.3.3 ]

7.3.2.1.2.1

Compression and gas processing equipment shall have pressure relief devices that limit each stagepressure to the maximum allowable working pressure for the compression cylinder and piping associatedwith that stage of compression. [55:10.8.1 10.2.6.1 ]

7.3.2.1.2.2

Where GH2 compression equipment is operated unattended, it shall be equipped with a high discharge

and a low suction pressure automatic shutdown control. [55:10.8.2 10.2.6.2 ]

7.3.2.1.2.3

Control circuits that automatically shut down shall remain down until manually activated or reset after asafe shutdown is performed. [55:10.8.3 10.2.6.3 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 14:05:42 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

175 of 491 1/30/2014 9:30 AM

First Revision No. 348-NFPA 2-2013 [ Section No. 7.3.2.1.4.1(A) ]

(A)

Valves shall be installed such that each compressor can is able to be isolated for maintenance.[55:10.8.4.1.1 10.2.6.4.1.1 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 14:06:42 EDT 2013

Committee Statement

Committee Statement: Update of extracted material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

176 of 491 1/30/2014 9:30 AM

First Revision No. 349-NFPA 2-2013 [ Section No. 7.3.2.1.4.1(B) ]

(B)

The discharge line shall be equipped with a check valve to prevent the backflow of gas from high-pressuresources located downstream of the compressor. [55:10.8.4.1.2 10.2.6.4.1.2 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 14:07:23 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

177 of 491 1/30/2014 9:30 AM

First Revision No. 350-NFPA 2-2013 [ Sections 7.3.2.1.4.2(A), 7.3.2.1.4.2(B) ]

(A)

Foundations used for supporting equipment shall be designed and constructed to prevent frost heaving.[55:10.8.4.2.1 10.2.6.5.1 ]

(B)

The structural aspects of such foundations shall be designed and constructed in accordance with theprovisions of the [adopted] building code. [55:10.8.4.2.2 10.2.6.5.2 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 14:09:44 EDT 2013

Committee Statement

Committee Statement: Update of extracted material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

178 of 491 1/30/2014 9:30 AM

First Revision No. 351-NFPA 2-2013 [ Section No. 7.3.2.1.4.3 ]

7.3.2.1.3.3 Emergency Shutdown.

When an emergency shutdown system is required, activation of the emergency shutdown system shallshut down operation of all compressors serving a single bulk gas installation. [55:10.8.4.3 10.2.6.6 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 14:10:23 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

179 of 491 1/30/2014 9:30 AM

First Revision No. 353-NFPA 2-2013 [ Section No. 7.3.2.1.4.4 ]

7.3.2.1.3.4 Relief Valves.

(A)

Each compressor shall be provided with a vent or relief device that will prevent overpressurizing of thecompressor under normal or upset conditions. [55:10.8.4.4.1 10.2.6.7.1 ]

(B)

Pressure relief devices used to serve pumps or compression equipment shall be connected to a vent pipesystem in accordance with 7.3.1.2.2. [55:10.8.4.4.2 10.2.6.7.2 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 14:12:25 EDT 2013

Committee Statement

Committee Statement: Update to extracted material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

180 of 491 1/30/2014 9:30 AM

First Revision No. 355-NFPA 2-2013 [ Sections 7.3.2.1.4.5, 7.3.2.1.4.6 ]

7.3.2.1.3.5 Pressure Monitoring.

The pressure on the compressor discharge shall be monitored by a control system. [55:10.8.4.5 10.2.6.8 ]

(A)

Discharge pressures in excess of the equipment design pressures shall cause the compressor to shutdown. [ 55: 10.2.6.8.1]

7.3.2.1.3.6 Protection.

Transfer piping and compressors shall be protected from vehicular damage. [55:10.8.4.6 10.2.6.9 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 14:14:58 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

181 of 491 1/30/2014 9:30 AM

First Revision No. 356-NFPA 2-2013 [ Section No. 7.3.2.1.5 ]

7.3.2.1.5 Clearance to Combustibles.

Clearance to combustibles shall be in accordance with the requirements of 7.1.9.1.1 . [ 55: 10.5.4]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 14:17:45 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

182 of 491 1/30/2014 9:30 AM

First Revision No. 357-NFPA 2-2013 [ Section No. 7.3.2.1.6 ]

7.3.2.1.4* Fire Protection.

Fire protection shall be in accordance with the requirements of Section 6.10. [55:10.6 10.6.1.2 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 14:22:44 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

183 of 491 1/30/2014 9:30 AM

First Revision No. 31-NFPA 2-2013 [ Section No. 7.3.2.1.7 ]

7.3.2.1.5 Installation in Vaults Above and Below Ground. (Reserved)

Generation, compression, storage and dispensing equipment for compressed gases shall be allowed tobe located in either abovegrade or belowgrade vaults in accordance with IFC 5303.16.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 11:47:19 EDT 2013

Committee Statement

CommitteeStatement:

The proposed public input is provided to address those sections designated as reserved in the 2011Edition of the code is a product of a combined effort assigned to the members of the technicalcommittee and a task group designated as the Reserved Sections Task Group.

The term reserved is normally used by a technical committee to recognize that the committee thatdeveloped the material has an awareness that there is a need in the subject area identified, but didnot feel that there was time available during the initial document development process or that therewas a need for additional justification to create requirements on the subject for any number ofreasons, including: 1) a lack of existing data, 2) a limited amount of applied practices in the field, or3) an inability to reach consensus.

Incorporating a reference to the IFC will help prescriptive requirements to this section.

ResponseMessage:

Public Input No. 51-NFPA 2-2012 [Section No. 7.3.2.1.7]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

184 of 491 1/30/2014 9:30 AM

First Revision No. 358-NFPA 2-2013 [ Section No. 7.3.2.2.1 ]

7.3.2.2.1

The location of hydrogen bulk [GH 2 ] systems shall be in accordance with Table 7.3.2.2.1.

[55:10.3.2.1 10.6.1.1 ].

Table 7.3.2.2.1 Location of [GH2] Systems

Quantity of Hydrogen

Location ≤MAQ

>MAQ to<3500 scf (<99

m 3 )

≥3500 5000 scf to <15,000 scf

(≥99 142 N m3 to <425 N m3)

≥15,000 scf (≥425

N m3)

In a detached building A A A A

In a gas room, inaccordance with Section6.4

A A ADetached building

required

Not in a gas room A A* A* NANA Detached

building required

A: Allowed. NA: Not allowed.

[ * These locations shall meet the requirements of 7.3.2.2.4.]

[55: Table 10.3.2 6.1 .1]

Supplemental Information

File Name Description

FR_358_Material.docx

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 07:22:21 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

185 of 491 1/30/2014 9:30 AM

7.3.2.2.1 The location of bulk [GH2] hydrogen systems shall be in accordance with Table 7.3.2.2.1. [55:10.3.26.1.1].

Table 7.3.2.2.1 Location of [GH2] Systems

Quantity of Hydrogen

Location

≥3500 5000 scf to <15,000 scf (≥99 142

m3 to <425 m3) ≥15,000 scf (≥425

m3)

In a detached building A A

In a gas room, in accordance with Section 6.4

A Detached building required

Not in a gas room A*NA NADetached building required

A: Allowed. NA: Not allowed.

[ * These locations shall meet the requirements of 7.3.2.2.4.]

[55: Table 10.3.26.1.1]

First Revision No. 359-NFPA 2-2013 [ Section No. 7.3.2.2.2 ]

7.3.2.2.2 Detached Buildings.

7.3.2.2.2.1

Detached buildings shall be constructed of noncombustible or limited-combustible materials in accordancewith the requirements of Section 6.5. [55:10.4.4.1 10.6.2.1 ]

7.3.2.2.2.2

Ventilation shall be provided in accordance with the requirements of Section 6.17. [55:10.4.4.2 10.6.2.2 ]

(A)

Outlet openings shall be located at the high point of the room in exterior walls or roof.[55:10.4.4.2.1 10.6.2.2.1 ]

(B)

Inlet and outlet openings shall each have a minimum total area of 1 ft2/1000 ft3 (1 m2/305 m3) of roomvolume. [55:10.4.4.2.2 10.6.2.2.2 ]

(C)

Discharge from outlet openings shall be directed or conducted to the atmosphere.[55:10.4.4.2.3 10.6.2.2.3 ]

7.3.2.2.2.3*

Explosion control shall be provided in accordance with the requirements of Section 6.9.[55:10.4.4.3 10.6.2.3 ]

7.3.2.2.2.4

Electrical equipment shall be in accordance with Article 501 of NFPA 70, National Electrical Code , forClass I, Division 2 locations. [55:10.4.4.4 10.6.2.4 ]

7.3.2.2.2.5

Heating, if provided, shall be by steam, hot water, or other indirect means except that electrical heatingshall be permitted to be used if in compliance with 7.3.2.2.2.4. [55:10.4.4.5 10.6.2.5 ]

Supplemental Information

File Name Description

A.7.3.2.2.2.3_FR_359_.docx

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 07:24:03 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

186 of 491 1/30/2014 9:30 AM

A.7.3.2.2.2.3

For guidance in these construction techniques, see NFPA 68, Standard on Explosion Protection by Deflagration Venting. [55:A.10.6.24.4.3]

 

First Revision No. 360-NFPA 2-2013 [ Section No. 7.3.2.2.3 ]

7.3.2.2.3 Hydrogen Gas Rooms.

7.3.2.2.3.1

Floors, walls, and ceilings shall be constructed of noncombustible or limited-combustible materials inaccordance with the requirements of the [adopted] building code. [55:10.4.5.1 10.6.3.1 ]

(A)

Interior walls or partitions shall have a fire resistance rating of not less than 2 hours, shall be continuousfrom floor to ceiling, and shall be anchored to resist movement. [55:10.4.5.1.1 10.6.3.1.1 ]

(B)

Not less than 25 percent of the perimeter wall shall be an exterior wall. [55:10.4.5.1.2 10.6.3.1.2 ]

(C)

Openings to other parts of the building shall not be permitted. [55:10.4.5.1.3 10.6.3.1.3 ]

(D)

Windows and doors shall be in exterior walls only. [55:10.4.5.1.4 10.6.3.1.4 ]

7.3.2.2.3.2

Ventilation shall be as provided in 6.17. [55:10.4.5.2 10.6.3.2 ]

7.3.2.2.3.3

Explosion control shall be provided in accordance with the requirements of Section 6.9.[55:10.4.5.3 10.6.3.3 ]

7.3.2.2.3.4

There shall be no sources of ignition from open flames, electrical equipment, or heating equipment.[55:10.4.5.4 10.6.3.4 ]

7.3.2.2.3.5*

Electrical equipment shall be in accordance with Article 501 of NFPA 70, National Electrical Code , forClass I, Division 2 locations. [55:10.4.5.5 10.6.3.5 ]

7.3.2.2.3.6

Heating, if provided, shall be by steam, hot water, or indirect means except that electrical heating shall bepermitted to be used if in compliance with 7.3.2.2.3.5. [55:10.4.5.6 10.6.3.6 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 07:25:18 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

187 of 491 1/30/2014 9:30 AM

First Revision No. 361-NFPA 2-2013 [ Section No. 7.3.2.2.4 ]

7.3.2.2.4 Indoor Hydrogen System Location.

7.3.2.2.4.1

Hydrogen systems of less than 3500 scf (99 m 3 ) and greater than the MAQ, where located insidebuildings, shall be located in the building so that the system will be as follows: [ 55: 10.4.6.1]

In a ventilated area in accordance with the provisions of Section 6.17 [ 55: 10.4.6.1(1)]

Separated from incompatible materials in accordance with the provisions of 7.2.1.1[ 55: 10.4.6.1(2)]

A distance of 25 ft (7.6 m) from open flames and other sources of ignition [ 55: 10.4.6.1(3)]

A distance of 50 ft (15 m) from intakes of ventilation, air-conditioning equipment, and aircompressors [ 55: 10.4.6.1(4)]

The distance shall be permitted to be reduced to 10 ft (3.1 m) where the room or area isprotected by a listed detection system as per Article 500.7(K) of NFPA 70 , NationalElectrical Code , and the detection system shall shut down the fuel supply in the event of aleak that results in a concentration that exceeds 25 percent of the LFL. [ 55: 10.4.6.1(4)(a)]

Isolation valves used to isolate the fuel supply shall be of a fail-safe design.[ 55: 10.4.6.1(4)(b)]

A distance of 50 ft (15 m) from other flammable gas storage [ 55: 10.4.6.1(5)]

Protected against damage in accordance with the provisions of 7.1.7.3 [ 55: 10.4.6.1(6)]

7.3.2.2.4.2 Systems Installed in One Room.

(A)

More than one system of 3500 scf (99 m 3 ) or less shall be permitted to be installed in the same roomor area, provided the systems are separated by at least 50 ft (15 m) or a full-height fire-resistive partitionhaving a minimum fire resistance rating of 2 hours is located between the systems. [ 55: 10.4.6.2.1]

(B)

The separation distance between multiple systems of 3500 scf (99 m 3 ) or less shall be permitted to bereduced to 25 ft (7.6 m) in buildings where the space between storage areas is free of combustiblematerials and protected with a sprinkler system designed for Extra Hazard, Group 1 in accordance withthe requirements of Section 6.10 . [ 55: 10.4.6.2.2]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 07:26:30 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

188 of 491 1/30/2014 9:30 AM

First Revision No. 362-NFPA 2-2013 [ Section No. 7.3.2.3.1.1 ]

7.3.2.3.1.1 Minimum Distance for Aboveground Locations.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

189 of 491 1/30/2014 9:30 AM

(A)*

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

190 of 491 1/30/2014 9:30 AM

The minimum distance from a [GH2] system [of indicated capacity] located outdoors to specified

exposures shall be in accordance with Table 7.3.2.3.1.1(A)(a) or Table 7.3.2.3.1.1(A)(b) . (See also AnnexI.) [55:10.3.2.2.1 10.3.2.1 ]

(1) Maximum Internal Diameter of Interconnecting Piping. The maximum internal diameter of thepiping system used for interconnecting piping between the shutoff valve on any single storagecontainer to the point of connection to the system source valve shall not exceed be required to be inaccordance with the values shown in Table 7.3.2.3.1.1(A)(a)and when in accordance with Table7.3.2.3.1.1(A)(b). for the pressure range indicated, except as shown in 7.3.2.3.1.1 (A)(1)(b) or7.3.2.3.1.1 (A)(1)(c). [55:10.3.2.2.1.1 10.3.2.2 ]

Shutoff Valves on the Source of Supply. When shutoff valves are not connected directly tothe source of supply, all interconnecting piping between the source connection and pointsdownstream shall be included in the determination of internal diameter for the piping system.[ 55: 10.3.2.2.1.1.(A)]

(a)

The separation distance for piping systems with internal diameters less than those specified inTable 7.3.2.3.1.2(a) and Table 7.3.2.3.1.2(b) for the pressure range selected shall beallowed to be reduced with tabular distances determined based on the use of equations inTable 7.3.2.3.1.2(c) . [ 55: 10.3.2.2.1.1(C)]

(b) Separation distances determined based on the use of Table 7.3.2.3.1.1(b) Table7.3.2.3.1.1(A)(a) or Table 7.3.2.3.1.1(A)(c) shall be subject to review and approval by the AHJ.[55:10.3.2.2.1.1(D) 10.3.2.2.2 ]

(c)

(d)

Table 7.3.2.3.1.1(A)(a) Minimum Distance (D) from Outdoor [GH 2 ] Systems to Exposures — Typical

Maximum Pipe Size

Pressure> 15 to ≤250 psig

> 250 to ≤3000 psig

> 3000 to ≤7500 psig

> 7500 to ≤15000 psig

Internal Pipe Diameter (ID)>103.4 to ≤1724 kPa

>1724 to ≤20,684 kPa

>20,684 to ≤51,711 kPa

>51,711 to ≤103,421 kPa

d mmd =

52.5 mm

d =18.97 mm

d =7.31 mm

d =7.16 mm

Exposures Group 1 m ft m ft m ft m ft

(a) Lot lines 12 40 14 46 9 29 10 34

(b) Air intakes (HVAC, compressors, other)

(c) Operable openings in buildings andstructures

(d) Ignition sources such as open flames andwelding

* Alternative Internal Diameters. The separation distance for piping systems with internaldiameters greater other than those specified in Table 7.3.2.3.1.1(A)(a) for the pressure rangeselected shall be permitted with tabular distances determined based on the use of theequations in Table 7.3.2.3.1.1(A)(b) or Table 7.3.2.3.1.1(A)(c)and or .. [55:10.3.2.2.1.1(B) 10.3.2.1.1 ]

* Determination of Internal Diameter. The internal diameter of the piping system shall bedetermined by the diameter of the piping serving that portion of a storage array with content

greater than 400 5000 scf (11.3 m 3 141.6 N m m3 ). The piping system size used in the

application of Table 7.3.2.3.1.2(a) Table 7.3.2.3.1.1(b) Table 7.3.2.3.1.1(A)(b) or Table7.3.2.3.1.1(c) Table 7.3.2.3.1.1(A)(c) and Table 7.3.2.3.1.2(b) shall be determined based onthat portion of the system with the greatest maximum internal diameter.[55:10.3.2.2.1.1(E) 10.3.2.2.1 ]

* Determination of System Pressure. The system pressure shall be determined by themaximum operating pressure of the storage array with content greater than 400 5000 scf

(11.3 141.6 N m3), irrespective of those portions of the system elevated to a higher pressure.[55:10.3.2.2.1.1(F) 10.3.2.3 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

191 of 491 1/30/2014 9:30 AM

Pressure> 15 to ≤250 psig

> 250 to ≤3000 psig

> 3000 to ≤7500 psig

> 7500 to ≤15000 psig

Internal Pipe Diameter (ID)>103.4 to ≤1724 kPa

>1724 to ≤20,684 kPa

>20,684 to ≤51,711 kPa

>51,711 to ≤103,421 kPa

d mmd =

52.5 mm

d =18.97 mm

d =7.31 mm

d =7.16 mm

[ 55: Table 10.3.2.1(a)]

Table 7.3.2.3.1.1(A)(b) Minimum Distance (D) from Outdoor [GH 2 ] Systems to Exposures by Maximum

Pipe Size with Pressures >15 to ≤3000 psig

Pressure

>15 to ≤250 psig

>103.4 to ≤1724 kPa

>250 to ≤3000 psig >17.24 to ≤20,684kPa

Exposures*† Exposures*†

Internal PipeDiameter (ID)

Group 1 Group 2 Group 3 Group 1 Group 2 Group 3

D = 0.231dD =

0.12584d −0.47126

D = 0.096d D = 0.738dD =

0.43616d −0.91791

D = 0.307d

ID(in.)

d(mm) m ft m ft m ft m ft m ft m ft

0.2 5.1 1 4 0 1 0 2 4 12 1 4 2 5

0.3 7.6 2 6 0 2 1 2 6 18 2 8 2 8

0.4 10.2 2 8 1 3 1 3 7 25 4 12 3 10

0.5 12.7 3 10 1 4 1 4 9 31 5 15 4 13

0.6 15.2 4 12 1 5 1 5 11 37 6 19 5 15

0.7 17.8 4 13 2 6 2 6 13 43 7 22 5 18

0.8 20.3 5 15 2 7 2 6 15 49 8 26 6 20

0.9 22.9 5 17 2 8 2 7 17 55 9 30 7 23

1.0 25.4 6 19 3 9 2 8 19 62 10 33 8 26

1.1 27.9 6 21 3 10 3 9 21 68 11 37 9 28

1.2 30.5 7 23 3 11 3 10 22 74 12 41 9 31

1.3 33 8 25 4 12 3 10 24 80 13 44 10 33

1.4 35.6 8 27 4 13 3 11 26 86 15 48 11 36

1.5 38.1 9 29 4 14 4 12 28 92 16 52 12 38

1.6 40.6 9 31 5 15 4 13 30 98 17 55 12 41

1.7 43.2 10 33 5 16 4 14 32 105 18 59 13 43

1.8 45.7 11 35 5 17 4 14 34 111 19 62 14 46

1.9 48.3 11 37 6 18 5 15 36 117 20 66 15 49

2.0 50.8 12 39 6 19 5 16 37 123 21 70 16 51

2.1 53.3 12 40 6 20 5 17 39 129 22 73 16 54

Note: Linear interpolation of internal pipe diameters and distances between table entries is allowed.

*For a list of exposures in each exposure group see Column 1 of Table 7.3.2.3.1.1(A)(a).

†When calculating the minimum separation distance (D) using the formulas indicated, based on theexposure group and pressure indicated, the internal pipe diameter (d) is entered in millimeters (mm). Thecalculated distance (D) is expressed in units of measure in meters (m). To convert distance (D) to units ofmeasure in feet, multiply the value of (D) in meters by 3.2808 and round to the nearest whole foot.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

192 of 491 1/30/2014 9:30 AM

[ 55: Table 10.3.2.1(b)]

Table 7.3.2.3.1.1(A)(c) Minimum Distance (D) from Outdoor [GH 2 ] Systems to Exposures by Maximum

Pipe Size with Pressures >3000 to ≤15,000 psig

Pressure

>3000 to ≤7500 psig >20,684 to ≤51,711kPa

>7500 to ≤15,000 psig >51,711 to≤103,421 kPa

Exposures*† Exposures*†

Internal PipeDiameter (ID)

Group 1 Group 2 Group 3 Group 1 Group 2 Group 3

ID(in.)

d(mm)

D = 1.105dD = 0.68311d− 1.3123 D = 0.459d D = 1.448d D = 1.448d D = 0.602d

m ft m ft m ft m ft m ft m ft

0.2 5.1 6 18 2 7 2 8 7 24 3 10 3 10

0.3 7.6 8 28 4 13 3 11 11 36 5 18 5 15

0.4 10.2 11 37 6 18 5 15 15 48 8 25 6 20

0.5 12.7 14 46 7 24 6 19 18 60 10 33 8 25

0.6 15.2 17 55 9 30 7 23 22 72 12 41 9 30

0.7 17.8 20 64 11 36 8 27 26 84 15 49 11 35

0.8 20.3 22 74 13 41 9 31 29 97 17 56 12 40

0.9 22.9 25 83 14 47 10 34 33 109 20 64 14 45

1.0 25.4 28 92 16 53 12 38 37 121 22 72 15 50

1.1 27.9 31 101 18 58 13 42 40 133 24 80 17 55

1.2 30.5 34 111 20 64 14 46 44 145 27 87 18 60

1.3 33.0 36 120 21 70 15 50 48 157 29 95 20 65

1.4 35.6 39 129 23 75 16 54 51 169 31 103 21 70

1.5 38.1 42 138 25 81 17 57 55 181 34 111 23 75

1.6 40.6 45 147 26 87 19 61 59 193 36 118 24 80

1.7 43.2 48 157 28 92 20 65 63 205 38 126 26 85

1.8 45.7 51 166 30 98 21 69 66 217 41 134 28 90

1.9 48.3 53 175 32 104 22 73 70 229 43 142 29 95

2.0 50.8 56 184 33 110 23 77 74 241 46 149 31 100

Note: Linear interpolation of internal pipe diameters and distances between table entries is allowed.

*For a list of exposures in each exposure group see Column 1 of Table 7.3.2.3.1.1(A)(a).

†When calculating the minimum separation distance (D) using the formulas indicated, based on theexposure group and pressure indicated, the internal pipe diameter (d) is entered in millimeters (mm). Thecalculated distance (D) is expressed in units of measure in meters (m). To convert distance (D) to units ofmeasure in feet, multiply the value of (D) in meters by 3.2808 and round to the nearest whole foot.

[ 55: Table 10.3.2.1(c)]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

193 of 491 1/30/2014 9:30 AM

(B)*

Except for distances to lot lines, operable building openings, air intakes, and overhead utilities, thedistances in Table 7.3.2.3.1.2(a) and Table 7.3.2.3.1.2(b) shall not apply where fire barrier wallshaving a minimum fire resistance rating of 2 hours are located between the system and the exposure.[ 55: 10.3.2.2.2]

The fire barrier wall shall be without openings or penetrations. [ 55: 8.7.2.1.1]

Penetrations of the fire barrier wall by conduit or piping shall be permitted provided that thepenetration is protected with a firestop system in accordance with the [adopted] buildingcode. [ 55: 8.7.2.1.1.1]

(C)*

The distances in (1), (2), (4), and (10) [inclusive] in Table 7.3.2.3.1.2(a) and Table 7.3.2.3.1.2(b) shallbe permitted to be reduced by one-half where fire barrier walls having a minimum fire resistance ratingof 2 hours are located between the system and the exposure. [ 55: 10.3.2.2.3]

(D)

When fire barrier walls of three sides are used, the walls shall be in accordance with 8.3.2.4.5.1(D) .[ 55: 10.3.2.2.4]

(E)

Unloading connections on delivery equipment shall not be positioned closer to any of the exposurescited in Table 7.3.2.3.1.2(a) and Table 7.3.2.3.1.2(b) than the distances given for the storage system.[ 55: 10.3.2.3]

7.3.2.3.1.2* Reduction of Distance by Mitigation Means.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

194 of 491 1/30/2014 9:30 AM

(A)*

Except for distances to air intakes, the distances to Group 1 and 2 exposures shown in Table7.3.2.3.1.1(A)(a) and Table 7.3.2.3.1.1(A)(b) and Table 7.3.2.3.1.1(A)(c) shall be permitted to bereduced by one-half and shall not apply to Group 3 exposures where fire barrier walls are locatedbetween the system and the exposure and constructed in accordance with the following:[ 55: 10.3.2.4.1]

(1) The fire barrier wall shall be without openings or penetrations. [ 55: 8.7.3.2.1]

(a) Penetrations of the fire barrier wall by conduit or piping shall be permitted provided that thepenetration is protected with a firestop system in accordance with the [adopted] buildingcode. [ 55: 8.7.3.2.1.1]

(2) Fire barrier walls shall have a minimum fire resistance rating of not less than 2 hours.[ 55: 10.3.2.4.1(1)]

(3) The fire barrier wall shall interrupt the line of sight between the bulk hydrogen compressed gassystem and the exposure. [ 55: 10.3.2.4.1(2)]

(4) The configuration of the fire barrier shall allow natural ventilation to prevent the accumulation ofhazardous gas concentrations. [ 55: 10.3.2.4.1(3)]

(5) The number of fire barrier walls used to separate individual systems shall be limited to three.[ 55: 10.3.2.4.1(4)]

(6) The fire barrier wall shall not have more than two sides at 90 degrees (1.57 rad) directions or notmore than three sides with connecting angles of 135 degrees (2.36 rad). [ 55: 10.3.2.4.1(5)]

(a) The connecting angles between fire barrier walls shall be permitted to be reduced to lessthan 135 degrees (2.3 rad) for installations consisting of three walls when in accordancewith 8.3.2.3.1.5(E) . [ 55: 10.3.2.4.1(5)(a)]

(7) Fire barrier walls shall be designed and constructed as a structure in accordance with therequirements of the building code without exceeding the specified allowable stresses for thematerials of construction utilized. Structures shall be designed to resist the overturning effectscaused by lateral forces due to wind, soil, flood, and seismic events. [ 55: 10.3.2.4.1(6)]

(8) Where clearance is required between bulk hydrogen compressed gas system and the barrier wallfor the performance of service or maintenance-related activities, a minimum horizontal clearanceof 5 ft (1.5 m) shall be provided between the structure and the system. [ 55: 10.3.2.4.1(7)]

(9) The fire barrier wall shall be either an independent structure or the exterior wall of the buildingadjacent to the storage or use area when the exterior building wall meets the requirements for firebarrier walls. [ 55: 10.3.2.4.1(8)]

(10) The minimum wall height shall be not less than 8 ft (2.1 m). [ 55: 10.3.2.4.1(9)]

(11) The minimum wall length shall project not less than 5 ft (1.5 m) horizontally beyond the mostremote point of the system or the exposure. [ 55: 10.3.2.4.1(10)]

(B)* Active Means.

Active control systems that mitigate the rise of system leaks and failures shall be permitted to be usedas a means to reduce separation distances where approved by the AHJ under the authority as grantedby Section 1.5 . [ 55: 10.3.2.4.2]

Supplemental Information

File Name Description

A.7.3.2.3.1.1_A_FR_362_.docx

A.7.3.2.3.1.2_A_FR_362_.docx

A.7.3.2.3.1.2_B_FR_362_.docx

Submitter Information Verification

Submitter Full Name: James Grimard

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

195 of 491 1/30/2014 9:30 AM

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 07:27:32 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

196 of 491 1/30/2014 9:30 AM

A.7.3.2.3.1.1(A)

Conversions for distance between inch-pound and SI units of measure cannot be consistently performed using typical mathematical conversion factors. The majority of separation distances shown in the SI table have been determined by the application of a risk-informed approach substantiated by statistical evaluation and modeling based on validated models for both ignited and unignited release of hydrogen gas. Where distance has been determined to allow for access or for correlation with the electrical code, the distances were not established through the use of models. Tabular distances in the inch-pound table have been determined by first converting SI units into inch-pound units and then rounding the distance to the nearest 5 ft for ease of application by code enforcers and users. A similar rounding technique has not been applied in the tabular distances shown in the SI table.

The exposures integral to Table 7.3.2.3.1.1(a), Table 7.3.2.3.1.1(b), and Table 7.3.2.3.1.1(c), have been arranged into groups based on similar risks. The thresholds are applicable to the exposures identified in each group, as follows: [55:A.10.3.2.1]

(1) Group 1 Exposures. The distances specified are those required to reduce the radiant heat flux level to 500 Btu/hr*ft2 (1577 W/m2) at the property line or the distance to a point in the unignited hydrogen jet where the hydrogen content is reduced to a 4 percent mole fraction (volume fraction) of hydrogen, whichever is greater. In all cases the distance required to achieve a 4 percent mole fraction was the greater distance and used to establish the requirements. [55:A.10.3.2.1(1)]

(2) Group 2 Exposures. The distances specified are those required to reduce the radiant heat flux level to 1500 Btu/hr*ft2 (4732 W/m2) for persons exposed a maximum of 3 minutes. [55:A.10.3.2.1(2)]

(3) Group 3 Exposures. The distances specified are those required to reduce the radiant heat flux level to 6340 Btu/hr*ft2 (20,000 W/m2) or the visible flame length for combustible materials, or a radiant heat flux level of 8000 Btu/hr*ft2 (25,237 W/m2) or the visible flame length for noncombustible equipment. In both cases the visible flame length was used to establish the requirements. [55:A.10.3.2.1(3)]

 

Formatted: Font: Italic

Formatted: Superscript

Formatted: Superscript

Formatted: Font: Italic

Formatted: Superscript

Formatted: Superscript

Formatted: Font: Bold

Formatted: Font: Italic

Formatted: Superscript

Formatted: Superscript

Formatted: Superscript

Formatted: Superscript

A.7.3.2.3.1.2(A)

As stated by Sandia National Laboratories researchers Houf, Schefer, and Evans in “Evaluation of Barrier Walls for Mitigation of Unintended Releases of Hydrogen,” the purposed of the Sandia study was to extend the available database on barrier walls as a hazard mitigation strategy and to provide technical data for risk-informed decisions in hydrogen codes and standards regarding barrier wall design and implementation. Additional analysis by Sandia (LaChance, Phillips, and Houf) in a paper titled “Risk Associated with the Use of Barriers in Hydrogen Refueling Stations” provided insights on the effectiveness of various barrier designs in terms of the following: [55:A.10.3.2.4.1]

(1) Deflecting jet flames [55:A.10.3.2.4.1(1)]

(2) Reducing the extent of the flammable cloud resulting from an unignited release [55: A.10.3.2.4.1(2)]

(3) Reducing the magnitude of the radiative heat flux produced by a jet flame from an ignited release. [55:A.10.3.2.4.1(3)]

(4) Minimizing the amount of ignition overpressure produced from the barrier confinement [55: A.10.3.2.4.1(4)]

Houf, Schefer, and Evans have determined that for the conditions investigated, 2000 psi (13.79 MPa) source pressure and a ⅛ in. (3.175 mm) diameter round leak, the barrier configurations studied were found to (1) reduce horizontal jet flame impingement hazard by deflecting the jet flame, (2) reduce radiation hazard distances for horizontal jet flames, and (3) reduce horizontal unignited jet flammability hazard distances. For the one-wall vertical barrier and the three-wall barrier configurations examined in the tests, the simulations of the peak overpressure hazard from ignition were found to be approximately 5.8 psi (40 kPa) on the release side of the barrier and approximately 0.72 psi to 0.44 psi (5 kPa to 3 kPa) on the downstream side of the barrier. Although an overpressure can be expected due to latent ignition of a flammable cloud, the overpressure can be expected to be limited to a localized area. Special designs for overpressure in addition to the structural loads imposed by the building code have not been required. [55: A.10.3.2.4.1]

The function of the fire barrier wall is to protect the exposure from the system and the converse. The code assumes that other factors will enter into locating any material or structure in proximity to the bulk hydrogen compressed gas system. For example, if a property or lot line is involved opposite the hydrogen installation, the proximity of a building to be constructed on the lot line is regulated by the building code based on the type and occupancy of the structure to be constructed. [55:A.10.3.2.4.1]

 

Formatted: Font: Bold

Formatted: Font: Bold

Formatted: Font: Bold

A.7.3.2.3.1.2(B)

To determine the acceptability of technologies, processes, products, facilities, materials, and uses attending the design, operation or use of such systems, the AHJ is authorized to require the owner or agent to provide, without charge to the jurisdiction, a technical opinion and report. The model fire prevention codes provide the authority for the AHJ to seek technical assistance from independent third parties with expertise in the matter to be reviewed at the submitter’s expense. The AHJ is authorized to require design submittals to be prepared by, and bear the stamp of, a registered design professional or professional engineer. [55:A.10.3.2.4.2]

Active means of control could include a means to detect leakage or fire coupled with automatic system shutdown, such as gas or flame detection. The use of gas or flame detection should consider, but is not limited to, the following: [55:A.10.3.2.4.2]

(1) Gas Detection. To utilize gas detection as a means of control, the gas sensor would be placed at a point between the bulk hydrogen compressed gas system and the exposure. Gas detection systems may be limited in their ability to detect the presence of hydrogen in the open. They are most effective if the sensor is located within an enclosed space such as an equipment enclosure. If used, gas detection systems should be either listed or approved. [55:A.10.3.2.4.2(1)]

(2) Flame Detection. Flame detection systems may include combination UV/IR detection systems and be installed in accordance with the requirements of NFPA 72, National Fire Alarm and Signaling Code. [55:A.10.3.2.4.2(2)]

Ultraviolet flame detectors typically use a vacuum photodiode Geiger–Muller tube to detect the ultraviolet radiation that is produced by a flame. The photodiode allows a burst of current to flow for each ultraviolet photon that hits the active area of the tube. When the number of current bursts per unit time reaches a predetermined level, the detector initiates an alarm. [72:A.17.8.2]

A single wavelength infrared flame detector uses one of several different photocell types to detect the infrared emissions in a single wavelength band that are produced by a flame. These detectors generally include provisions to minimize alarms from commonly occurring infrared sources such as incandescent lighting or sunlight. An ultraviolet/infrared (UV/IR) flame detector senses ultraviolet radiation with a vacuum photodiode tube and a selected wavelength of infrared radiation with a photocell and uses the combined signal to indicate a fire. These detectors need exposure to both types of radiation before an alarm signal can be initiated. A multiple wavelength infrared (IR/IR) flame detector senses radiation at two or more narrow bands of wavelengths in the infrared spectrum. These detectors electronically compare the emissions between the bands and initiate a signal where the relationship between the two bands indicates a fire. [72:A.17.8.2]

 

Formatted: Font: Not Bold, Italic

Formatted: Font: Not Bold, Italic

Formatted: Font: Not Bold

Formatted: Font: Italic

Formatted: Font: Bold

Formatted: Font: Bold

First Revision No. 363-NFPA 2-2013 [ New Section after 7.3.2.3.1.2 ]

7.3.2.3.1.4

Bulk hydrogen compressed gas systems shall be allowed to integrate or co-locate other nonliquefiedflammable gas systems as a component of the hydrogen gas system without separation, where theoutput of the system is designed to deliver a product in which the gases are mixed or blended fordelivery into the user’s system. [ 55: 10.3.2.6]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 07:43:05 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

197 of 491 1/30/2014 9:30 AM

First Revision No. 364-NFPA 2-2013 [ New Section after 7.3.2.3.1.2 ]

7.3.2.3.1.5 Electrical Equipment. 

Electrical wiring and equipment shall be in accordance with Table 7.3.2.3.1.5 . [ 55: 10.3.1.2]

Table 7.3.2.3.1.5 Electrical Area Classification

Location Classification Extent of Classified Area

Storage equipment excludingthe piping system downstreamof the source valve Class I, Division 2

Between 0 ft (0 m) and 15 ft(4.6 m)

Supplemental Information

File Name Description

Table_7.3.2.3.1.5_FR_364_.docx

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 07:43:44 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

198 of 491 1/30/2014 9:30 AM

Table 10.3.1.2 Electrical Area Classification

Location Classification Extent of Classified Area

Storage equipment excluding the piping system downstream of the source valve

Class I, Division 2 Between 0 ft (0 m) and 15 ft (4.6 m)

First Revision No. 365-NFPA 2-2013 [ Section No. 7.3.2.3.1.2 ]

7.3.2.3.1.3 Design Requirements at Outdoor Locations. Required Separation Distance for All Systems.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

199 of 491 1/30/2014 9:30 AM

Separation distances shall be required for bulk hydrogen compressed gas systems independent ofsystem pressure or internal diameter of piping systems in accordance with Table 7.3.2.3.1.1(A)(a) ,Table 7.3.2.3.1.1(A)(b) , or Table 7.3.2.3.1.1(A)(c) . [ 55: 10.3.2.5]

Table 7.3.2.3.1.3(a) Minimum Distance from Outdoor [GH2] Systems to Exposures (U.S. Units)

Exposure

>15 to≤250 psi2.067 in.

ID (ft)

>250 to≤3000 psi0.747 in.

ID (ft)

>3000 to≤7500 psi0.312 in.

ID (ft)

>7500 to≤15000 psi0.282 in. ID

(ft)

(1) Lot lines greater of a or b 40 45 30 35

(2)Exposed persons other than those involved in

servicing of the system. c 20 25 15 15

(3) Buildings and structures

Combustible construction d 15 20 10 15

Noncombustible non-fire-rated construction e 15 20 10 15

Fire-rated construction with a fire resistance

rating of not less than 2 hours f 5 5 5 5

(4)Openings in buildings of fire-rated ornon-fire-rated construction (doors, windows,and penetrations)

Openable a

 Fire-rated or non-fire-rated 40 45 30 35

Unopenable c

 Fire-rated or non fire-rated 15 20 10 15

(5) Air intakes (HVAC, compressors, other) a 40 45 30 35

(6)Fire barrier walls or structures used to shield

the bulk system from exposures f 5 5 5 5

(7) Unclassified electrical equipment g 15 15 15 15

(8)

Utilities (overhead) including electric power,building services, or hazardous materials

piping d15 20 10 15

(9)Ignition sources such as open flames and

welding a 40 45 30 35 ft

(10) Parked cars c 20 25 15 15 ft

(11)Flammable gas storage systems includingother hydrogen systems above ground.

Nonbulk 15 20 10 15

Bulk h 15 15 15 15

(12)

Aboveground vents or exposed piping andcomponents of flammable gas storage systemsincluding other hydrogen systems below

ground c

Gaseous or Cryogenic 15 20 10 15

(13)Hazardous materials (other than flammable

gases) storage below ground c

Physical hazard materials or Health hazardmaterials

15 20 10 15

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

200 of 491 1/30/2014 9:30 AM

Exposure

>15 to≤250 psi2.067 in.

ID (ft)

>250 to≤3000 psi0.747 in.

ID (ft)

>3000 to≤7500 psi0.312 in.

ID (ft)

>7500 to≤15000 psi0.282 in. ID

(ft)

Note: All pressures are gauge pressures.

a Unignited jet concentration decay distance to 4 percent mole fraction (volume fraction) hydrogen.

b D rad – radiation heat flux level of 500 Btu/hr·ft 2 .

c D rad for heat flux level of 1500 Btu/hr·ft 2 exposure to employees for a maximum of 3 minutes.

d The greater of D rad for combustible heat flux level of 6340 Btu/hr·ft 2 or the visible flame length.

e The greater of D rad for noncombustible equipment heat flux level of 8000 Btu/hr ft 2 or the visible

flame length.

f The minimum clearance between the structure and the system required for access for service-relatedactivities.

g Equipment classified as meeting Class I, Division 2, Group B requirements of NFPA 70 , NationalElectrical Code , when the area is in accordance with NFPA 497 , Recommended Practice for theClassification of Flammable Liquids, Gases, or Vapors and of Hazardous (Classified) Locations forElectrical Installations in Chemical Process Areas .

h Bulk hydrogen storage systems are allowed to integrate (co-locate) other nonliquefied flammable gassystems when the output of the system is designed to deliver a product in which the gases are mixed orblended for delivery into the user’s system. The separation distance indicated requires a minimumseparation between gaseous and liquid systems integrated into a single system where the liquid sourceis vaporized, compressed, and stored in the gaseous state.

[ 55: Table 10.3.2.2.1(a)]

Table 7.3.2.3.1.3(b) Minimum Distance from Outdoor [GH2] Systems to Exposures (SI Units)

Exposure

>103.4 to≤172.4 kPa52.50 mm

ID (m)

>1724 to≤20,684

kPa 18.97mm ID (m)

>20,684 ≤ to51,711 kPa7.92 mm ID

(m)

>51,711 to≤103,421

kPa 7.16 mmID (m)

(1) Lot lines greater of a or b 12.2 13.8 9.2 10.7

(2)Exposed persons other than those

involved in servicing of the system c 6.1 7.7 4.6 4.6

(3) Buildings and structures

Combustible construction d 4.6 6.1 3.1 4.6

Noncombustible non-fire-rated

construction e 4.6 6.1 3.1 4.6

Fire-rated construction with a fireresistance rating of not less than 2

hours f1.6 1.6 1.6 1.6

(4)Openings in buildings of fire-rated ornon-fire-rated construction (doors,windows, and penetrations)

Openable d

 Fire-rated or non-fire-rated 12.2 13.8 9.2 10.7

Unopenable c

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

201 of 491 1/30/2014 9:30 AM

Exposure

>103.4 to≤172.4 kPa52.50 mm

ID (m)

>1724 to≤20,684

kPa 18.97mm ID (m)

>20,684 ≤ to51,711 kPa7.92 mm ID

(m)

>51,711 to≤103,421

kPa 7.16 mmID (m)

 Fire-rated or non-fire-rated 4.6 6.1 3.1 4.6

(5) Air intakes (HVAC, compressors, other) a 12.2 13.8 9.2 10.7

(6)Fire barrier walls or structures used to

shield the bulk system from exposures f 1.6 1.6 1.6 1.6

(7) Unclassified electrical equipment g 4.6 4.6 4.6 4.6

(8)

Utilities (overhead), including electricpower, building services, or hazardous

materials piping d4.6 6.1 3.1 4.6

(9)Ignition sources such as open flames and

welding a 12.2 13.8 9.2 10.7

(10) Parked cars c 6.1 7.7 4.6 4.6

(11)Flammable gas storage systems,including other hydrogen systems aboveground

Nonbulk 4.6 6.1 3.1 4.6

Bulk h 4.6 4.6 4.6 4.6

(12)

Aboveground vents or exposed pipingand components of flammable gasstorage systems including other

hydrogen systems, below ground. d

Gaseous or cryogenic 4.6 6.1 3.1 4.6

(13)

Hazardous materials (other thanflammable gases) storage below

ground d

Physical hazard materials or healthhazard materials

4.6 6.1 3.1 4.6

(14)Hazardous materials storage (other than

flammable gases) above ground d

Physical hazard materials or healthhazard materials

4.6 6.1 3.1 4.6

(15)

Ordinary combustibles, includingfast-burning solids such as ordinarylumber, excelsior, paper, or combustiblewaste and vegetation other than that

found in maintained landscaped areas d

4.6 6.1 3.1 4.6

(16)Heavy timber, coal, or other slow-burning

combustible solids d 4.6 6.1 3.1 4.6

Note: All pressures are gauge pressures.

a Unignited jet concentration decay distance to 4 percent mole fraction (volume fraction) hydrogen.

b D rad – radiation heat flux level of 1577 W/m 2 .

e The greater of D rad for non-combustible equipment heat flux level of 25,237 W/m 2 or the visible

flame length.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

202 of 491 1/30/2014 9:30 AM

d The greater of D rad for combustible heat flux level of 20,000 W/m 2 or the visible flame length.

c D rad for heat flux level of 4732 W/m 2 exposure to employees for a maximum of 3 minutes.

f The minimum clearance between the structure and the system required for access for service relatedactivities.

g Equipment classified as meeting Class I, Division 2, Group B requirements of NFPA 70 , NationalElectrical Code when the area is in accordance with NFPA 497 , Recommended Practice for theClassification of Flammable Liquids, Gases, or Vapors and of Hazardous (Classified) Locations forElectrical Installations in Chemical Process Areas .

h Bulk hydrogen storage systems are allowed to integrate (co-locate) other nonliquefied flammable gassystems when the output of the system is designed to deliver a product in which the gases are mixed orblended for delivery into the user’s system. The separation distance indicated requires a minimumseparation between gaseous and liquid systems integrated into a single system where the liquid sourceis vaporized, compressed, and stored in the gaseous state.

[ 55: Table 10.3.2.2.1(b)]

Table 7.3.2.3.1.3(c) Separation Distance Based on Alternative Pipe or Tube Internal Diameters

Notes *>15 to ≤250 psi (>103.4 to

≤1724 kPa)>250 to ≤3000 psi (>1724 to

≤ 20,684 kPa)>3000 to ≤7500 psi (>20,684 ≤

51,711 kPa) (>

(a) D a = 0.23179d 0.99931 D a = 0.73903d 0.99962 D a = 1.1062d 0.99959 D

(b)

D b = 0.091137d 1.1303 +

e -0.084081d (0.087694d 0.72681

- 0.091137d 1.1303 )

D b = 0.36599d 1.1152 +

e -0.10771d (0.1885d 1.2531

-

0.36599d 1.1152 )

D b = 0.60173d 1.1063 +

e -0.36516d (-0.00002521d 5.6078

- 0.60173d 1.1063 )

D b

e -0.403

(c)

D c = 0.075952d 1.1022 +

e -0.087589d (0.076814d 0.83088

- 0.075952d 1.1022 )

D c = 0.2889d 1.092 +

e -0.10392d (0.18705d 1.1795

- 0.2889d 1.092 )

D c = 0.45889d 1.0887 +

e -0.46723d (-0.000027772d 5.8841

- 0.45889d 1.0887 )

D

e -0.524

(d) D d = 0.096359d 0.99928 D d = 0.3072d 0.99962 D d = 0.45967d 0.99971 D d

(e) D e = 0.096359d 0.99928 D e = 0.3072d 0.99962 D e = 0.45967d 0.99971 D e

Notes:

(1) Use of this table assumes a leak diameter of 3 percent of the pipe flow area or internal diameterwhere d = inside diameter (ID) of pipe or tube expressed in millimeters (mm), and D a,b,c,d, or e =

separation distance in meters (m).

(2) All pressures are gauge pressures.

* Notes are from Table 10.3.2.2.1(a) and Table 10.3.2.2.1(b) as follows:

 (a) Unignited jet concentration decay distance to 4 percent mole fraction (volume fraction) hydrogen

 (b) D rad - radiation heat flux level of 500 Btu/hr·ft 2 (1577 W/m 2 )

 (c) D rad for heat flux level of 1500 Btu/hr·ft 2 (4732 W/m 2 ) exposure to employees for a maximum

of 3 minutes

 (d) The greater of D rad for combustible heat flux level of 6340 Btu/hr·ft 2 (20,000 W/m 2 ) or the

visible flame length

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

203 of 491 1/30/2014 9:30 AM

 (e) The greater of D rad for noncombustible equipment heat flux level of 8000 Btu/hr·ft 2 (25,237

W/m 2 ) or the visible flame length

[ 55: 10.3.2.2.1.1(B)]

Table 7.3.2.3.1.3(d) Electrical Area Classification

Location Classification Extent of Classified Area

Storage equipment excluding the piping systemdownstream of the source valve

Class I, Division2

Between 0 ft (0 m) and 15ft (4.6 m)

[ 55: Table 10.4.1.2]

(A)

Where overhead cover is provided, it shall be in accordance with the provisions of Section 6.6 .[ 55: 10.4.1.1] Unloading connections on delivery equipment shall not be positioned closer to any of theexposures cited in Table 7.3.2.3.1.1(A)(a) , Table 7.3.2.3.1.1(A)(b) , or Table 7.3.2.3.1.1(A)(c) than thedistances given for the storage system. [ 55: 10.3.2.5.1]

(B)

Electrical wiring and equipment shall be in accordance with Table 7.3.2.3.1.2(d) . [ 55: 10.4.1.2] Theminimum separation distance between gaseous and liquid systems integrated into a single system wherethe liquid source is vaporized, compressed, and stored in the gaseous state shall be 15 ft (4.6 m).[ 55: 10.3.2.5.2]

(C)

Vehicular protection shall be provided in accordance with 4.1.5 . [ 55: 10.4.1.3] Systems within 50 ft (15m) of aboveground storage of all classes of flammable and combustible liquids shall be located on groundhigher than such storage, except where dikes, diversion curbs, grading, or separating solid walls are usedto prevent accumulation of the liquids under the system. [ 55: 10.3.2.5.3]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 07:44:59 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

204 of 491 1/30/2014 9:30 AM

First Revision No. 366-NFPA 2-2013 [ Section No. 7.3.2.4 [Excluding any Sub-Sections] ]

[GH 2 ] Bulk hydrogen compressed gas systems installed underground where [GH2] containers are to be

buried in contact with earth or fill shall be in accordance with 7.3.2.4. [55:10.4.2 10.4.1 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 09:23:15 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

205 of 491 1/30/2014 9:30 AM

First Revision No. 367-NFPA 2-2013 [ Section No. 7.3.2.4.1 ]

7.3.2.4.1 Container Design.

Pressure [GH2] containers installed underground using burial methods shall be of seamless construction

in accordance with Part UF or Appendix 22 of the ASME Boiler and Pressure Vessel Code, Section VIII,Division 1. [55:10.4.2.1 10.4.1.1 ]

7.3.2.4.1.1*

[GH2] containers shall be designed to include cyclic pressure life calculations using fracture mechanics

methods. [55:10.4.2.1.1 10.4.1.1.1 ]

7.3.2.4.1.2 GH2 Container Examination.

(A)

[GH2] containers shall be examined for internal and external surface flaws and inclusions before burial, or

at the time of manufacture. [55:10.4.2.1.2.1 10.4.1.1.2.1 ]

(B)

[GH2] containers with flaws or inclusions exceeding the lesser of 5 percent of the wall thickness or 0.12 in.

(3 mm) shall not be used. [55:10.4.2.1.2.2 10.4.1.1.2.2 ]

7.3.2.4.1.3 Composite Containers. (Reserved)

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 09:25:50 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

206 of 491 1/30/2014 9:30 AM

First Revision No. 368-NFPA 2-2013 [ Sections 7.3.2.4.2, 7.3.2.4.3 ]

7.3.2.4.2 Corrosion Protection.

[GH2] containers and underground piping shall be protected from corrosion in accordance with 7.1.9.1.7,

7.1.14, [and] 7.1.15.3 as applicable. [55:10.4.2.2 10.4.1.3 ]

7.3.2.4.3* Outlet Connections.

7.3.2.4.3.1

Threaded [GH2] container outlet connections shall be designed with primary and secondary seals that

shall be tested for functionality. [55:10.4.2.3.1 10.4.1.4.1 ]

7.3.2.4.3.2

The seal design shall include a method of detecting a leak in the primary seal. [55:10.4.2.3.2 10.4.1.4.2 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 09:27:58 EDT 2013

Committee Statement

Committee Statement: Revision of extract text

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

207 of 491 1/30/2014 9:30 AM

First Revision No. 369-NFPA 2-2013 [ Section No. 7.3.2.4.4.1 ]

7.3.2.4.4.1

Joints in the piping system shall be butt welded installed and 100 percent inspected using nondestructivetesting (NDT) methods in accordance with the requirements of ANSI/ ASME B31.3 12 , ProcessPiping Hydrogen Piping and Pipelines , or other approved standards. [55:10.4.2.4.1 10.4.1.5.1 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 09:30:26 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

208 of 491 1/30/2014 9:30 AM

First Revision No. 370-NFPA 2-2013 [ Section No. 7.3.2.4.4.2 ]

7.3.2.4.4.2

Valves, controls, safety devices, and instrumentation shall be above ground and accessible to authorizedpersonnel. [55:10.4.2.4.2 10.4.1.5.2 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 09:32:00 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

209 of 491 1/30/2014 9:30 AM

First Revision No. 371-NFPA 2-2013 [ Section No. 7.3.2.4.5 [Excluding any

Sub-Sections] ]

[GH2] containers shall be located in accordance with 7.3.2.4.5.1 through 7.3.2.4.5.6 7.3.2.4.5.6 .

[55:10.4.2.5 10.4.1.6 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 09:38:03 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

210 of 491 1/30/2014 9:30 AM

First Revision No. 373-NFPA 2-2013 [ Sections 7.3.2.4.5.1, 7.3.2.4.5.2, 7.3.2.4.5.3,

7.3.2.4.5.4... ]

7.3.2.4.5.1

Underground [GH2] containers shall not be located beneath buildings. [55:10.4.2.5.1 10.4.1.6.1 ]

7.3.2.4.5.2

[GH2] containers and associated equipment shall be located with respect to foundations and supports of

other structures such that the loads carried by such structures cannot be transmitted to the tank.[55:10.4.2.5.2 10.4.1.6.2 ]

7.3.2.4.5.3 GH 2 Container Separation Distances.

The distance from any part of the [GH 2 ] container to the nearest wall of a basement, pit, cellar, or lot

line shall not be less than 10 ft (3.1 m). [ 55: 10.4.1.6.3]

(A)

The distance from any part of the [GH 2 ] container to the nearest wall of a basement, pit, cellar, or lot

line shall not be less than 10 ft (3.1 m). [ 55: 10.4.1.6.3]

(B)

A structure or foundation of a structure on the same property shall not be erected or constructed within10 ft (3.1 m) of any point on the container surface, unless the footings extend to the bottom of thecontainer or the container’s foundation. [ 55: 10.4.1.6.4]

7.3.2.4.5.5

A minimum distance of 1 ft (0.3 m), shell to shell, shall be maintained between adjacent undergroundcontainers. [55:10.4.2.5.4 10.4.1.6.5 ]

7.3.2.4.5.6*

A minimum distance of 3 ft (0.9 m) shall be maintained between [GH2] containers and buried utilities.

[55:10.4.2.5.5 10.4.1.6.6 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 09:42:04 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

211 of 491 1/30/2014 9:30 AM

First Revision No. 374-NFPA 2-2013 [ Section No. 7.3.2.4.6 ]

7.3.2.4.6 Foundations.

Underground [GH2] containers shall be set on foundations constructed in accordance with the adopted

building code, and surrounded with not less than 6 in. (152 mm) of noncorrosive inert material.[55:10.4.2.6 10.4.1.7 ]

7.3.2.4.6.1

The concrete shall extend a minimum of 1 ft (0.3 m) horizontally beyond the footprint of the tank in alldirections. [ 55: 10.4.1.7.1]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 09:46:45 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

212 of 491 1/30/2014 9:30 AM

First Revision No. 375-NFPA 2-2013 [ Section No. 7.3.2.4.7.1 ]

7.3.2.4.7.1

Containers shall be buried such that the top of the container is covered with a minimum of 1 ft (0.3 m) ofearth and with concrete a minimum of 4 in. (101 mm) thick placed over the earthen cover.[55:10.4.2.7.1 10.4.1.8 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 09:48:10 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

213 of 491 1/30/2014 9:30 AM

First Revision No. 376-NFPA 2-2013 [ Section No. 7.3.2.4.7.2 ]

7.3.2.4.7.2

The concrete shall extend a minimum of 1 ft (0.3 m) horizontally beyond the footprint of the tank in alldirections. [ 55: 10.4.2.7.2]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 09:48:56 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

214 of 491 1/30/2014 9:30 AM

First Revision No. 377-NFPA 2-2013 [ Sections 7.3.2.4.8, 7.3.2.4.9, 7.3.2.4.10, 7.3.2.4.11 ]

7.3.2.4.8* Anchorage and Security.

[GH2] containers installed underground in flood hazard areas shall be anchored to prevent flotation,

collapse, or lateral movement resulting from hydrostatic loads, including the effects of buoyancy, duringconditions of the design flood. [55:10.4.2.8 10.4.1.9 ]

7.3.2.4.9 Venting of Underground GH2 Containers.

Vent pipes for underground [GH2] containers shall be in accordance with 7.3.1.2.1.

[55:10.4.2.9 10.4.1.10 ]

7.3.2.4.10 Overfill Protection and Prevention Systems.

An approved means or method shall be provided to prevent the overfilling of the storage containers.[55:10.4.2.10 10.4.1.11 ]

7.3.2.4.11 Physical Protection.

Piping and control equipment ancillary to underground containers that is located above ground shall beprotected from physical damage in accordance with 7.1.7.3. [55:10.4.2.11 10.4.1.12 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 09:51:16 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

215 of 491 1/30/2014 9:30 AM

First Revision No. 378-NFPA 2-2013 [ Section No. 7.3.4.2.1 ]

7.3.4.2.1

Personnel conducting transfer operations from the bulk transport vehicle shall be trained. [ 52: 9.14.13]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 09:54:12 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

216 of 491 1/30/2014 9:30 AM

First Revision No. 379-NFPA 2-2013 [ Section No. 7.3.4.2.2 ]

7.3.4.2.2

Unloading connections on delivery equipment shall not be positioned closer to any of the exposures citedin Table 7.3.2.3.1.1(A)(a)or , Table 7.3.2.3.1.1(A)(b)or Table 7.3.2.3.1.1(c) Table 7.3.2.3.1.1(A)(c) thanthe distances given for the bulk GH 2 compressed gas storage system. [55:10.7.1 10.2.8.2 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 09:55:26 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

217 of 491 1/30/2014 9:30 AM

First Revision No. 380-NFPA 2-2013 [ Section No. 7.3.4.2.3 ]

7.3.4.2.3

During transfer of hydrogen from cargo vehicles to the bulk GH 2 compressed gas storage system , the

hand or emergency brake of the vehicle shall be set, and chock blocks shall be used to prevent rolling ofthe vehicle from moving . [55:10.7.2 10.2.8.3 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 09:56:15 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

218 of 491 1/30/2014 9:30 AM

First Revision No. 381-NFPA 2-2013 [ Sections 7.3.4.2.4, 7.3.4.2.5, 7.3.4.2.6, 7.3.4.2.7,

7.3.4.... ]

7.3.4.2.4

Cargo vehicles equipped with air-brake interlock in front of the unloading connection to protect againstdrive-away aways shall be engaged such that the interlock is activated. [55:10.7.3 10.2.8.4 ]

7.3.4.2.5

Mobile hydrogen supply units shall be electrically bonded to the bulk hydrogen gas storage system beforehydrogen is discharged from the supply unit. [55:10.7.4 10.2.8.5 ]

7.3.4.2.6 Transfer System Depressurization.

7.3.4.2.6.1

The transfer systems shall be capable of depressurizing to facilitate disconnection.[55:10.7.5.1 10.2.8.6.1 ]

7.3.4.2.6.2

Bleed connections shall be connected to a hydrogen venting system in accordance with 7.3.1.2.2.[55:10.7.5.2 10.2.8.6.2 ]

7.3.4.2.7

Where required, check valves on delivery systems shall be in accordance with 7.1.15.1.2.[55:10.7.6 10.2.8.7 ]

7.3.4.2.8

Prohibitions on smoking or the use of open flame shall be in accordance with 7.1.24.2.[55:10.7.7 10.2.8.8 ]

7.3.4.2.9

An emergency shutoff valve shall be provided in accordance with 7.1.22. [55:10.7.8 10.2.8.9 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 09:57:13 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

219 of 491 1/30/2014 9:30 AM

First Revision No. 451-NFPA 2-2013 [ Section No. 8.1.3.1 ]

8.1.3.1 Piping Systems.

Piping, tubing, fittings, and related components shall be designed, fabricated, and tested in accordancewith the requirements of ANSI/ ASME B31.3 12 , Process Piping Hydrogen Piping and Pipelines , or otherapproved standards and shall be in accordance with 8.1.3.1.1. [ 55: 8.14.1.4.2]

8.1.3.1.1 Piping and Appurtenances.

8.1.3.1.1.1

Piping systems shall be designed for the use intended through the full range of pressure and temperatureto which they will be subjected. [55:8.14.2.1]

8.1.3.1.1.2

Piping or tubing used at operating temperatures below -20°F (-29°C) shall be fabricated from materialsmeeting the impact test requirements of ASME B31.12, Hydrogen Piping and Pipelines , when tested atthe minimum operating temperature to which the piping will be exposed to in service. [ 55: 11.2.3.2]

8.1.3.1.1.3

Piping systems shall be designed and constructed to allow for expansion, contraction, vibration,settlement, and fire exposure. [55:8.14.2.2]

8.1.3.1.2 Joints.

Joints in piping and tubing shall be permitted to be made by welding or brazing, or by use of flanged,threaded, socket, slip, or compression fittings. [ 55: 8.14.3] in accordance with the requirements of ASMEB31.12, Hydrogen Piping and Pipelines . [ 55: 11.2.3.3]

8.1.3.1.2.1

Brazing materials, where used, shall have a melting point above 1000°F (538°C). [ 11: 2.3.4]

8.1.3.1.3 Valves and Accessory Equipment.

Valves and accessory equipment shall be acceptable for the intended use at the temperatures of theapplication and shall be designed and constructed to withstand the maximum pressure at the minimumtemperature to which they will be subjected. [55:8.14.4]

8.1.3.1.4 Shutoff Valves on Containers.

Shutoff valves shall be provided on all container connections, except for pressure relief devices.[55:8.14.5]

8.1.3.1.4.1

Shutoff valves for containers with multiple pressure relief devices shall be permitted in accordance with8.1.4.7. [55:8.14.5.1]

8.1.3.1.4.2

Shutoff valves shall be accessible and located as close as practical to the container. [55:8.14.5.2]

8.1.3.1.5 Shutoff Valves on Piping.

8.1.3.1.5.1

Shutoff valves shall be installed in piping containing [LH2] where needed to limit the volume of liquid

discharged in the event of piping or equipment failure. [55:8.14.6.1]

8.1.3.1.5.2*

Pressure relief valves shall be installed where liquid [ or cold gas] can be trapped between shutoff valvesin the piping system. (See 8.1.4 .) [55:8.14.6.2]

8.1.3.1.6 Physical Protection and Support.

8.1.3.1.6.1

Aboveground piping systems shall be supported and protected from physical damage. [55:8.14.7.1]

8.1.3.1.6.2

Piping passing through walls shall be protected from mechanical damage. [55:8.14.7.2]

8.1.3.1.7 Corrosion Protection.

8.1.3.1.7.1

Aboveground piping that is subject to corrosion shall be protected against corrosion. [55:8.14.8.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

220 of 491 1/30/2014 9:30 AM

8.1.3.1.7.2

Belowground piping shall be protected against corrosion. [55:8.14.8.2]

8.1.3.1.8 Cathodic Protection.

Where required, cathodic protection shall be in accordance with 8.1.3.1.8. [55:8.14.9]

8.1.3.1.8.1 Operation.

Where installed, cathodic protection systems shall be operated and maintained to continuously providecorrosion protection. [55:8.14.9.1]

8.1.3.1.8.2 Inspection.

(A)

Container systems equipped with cathodic protection shall be inspected for proper the intended operationby a cathodic protection tester. [55:8.14.9.2.1]

(B)

The cathodic protection tester shall be certified as being qualified by the National Association of CorrosionEngineers, International (NACE). [55:8.14.9.2.2]

8.1.3.1.8.3 Impressed Current Systems.

(A)

Systems equipped with impressed current cathodic protection systems shall be inspected in accordancewith the requirements of the design and 8.1.3.1.8.2. [55:8.14.9.3.1]

(B)

The design limits shall be available to the AHJ upon request. [55:8.14.9.3.2]

(C)

The system owner shall maintain the following records to demonstrate that the cathodic protection is inconformance with the requirements of the design: [55:8.14.9.3.3]

(1) The results of inspections of the system [55:8.14.9.3.3(1)]

(2) The results of testing that has been completed [55:8.14.9.3.3(2)]

8.1.3.1.8.4 Corrosion Expert.

(A)

Repairs, maintenance, or replacement of a cathodic protection system shall be under the supervision of acorrosion expert certified by NACE. [55:8.14.9.4]

(B)

The corrosion expert shall be certified by NACE as a senior corrosion technologist, a cathodic protectionspecialist, or a corrosion specialist or shall be a registered engineer with registration in a field that includeseducation and experience in corrosion control. [55:8.14.9.4.1]

8.1.3.1.9 Testing.

8.1.3.1.9.1

Piping systems shall be tested and proved free of leaks after installation as required by the [ codes and]standards to which they are designed and constructed. [55:8.14.10.1]

8.1.3.1.9.2

Test pressures shall not be less than 150 percent of the maximum allowable working pressure whenhydraulic testing is conducted or 110 percent when testing is conducted pneumatically. [55:8.14.10.2]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 02 11:38:06 EDT 2013

Committee Statement

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

221 of 491 1/30/2014 9:30 AM

CommitteeStatement:

The previous references to ASME B31.3 were taken from chapter 8 of NFPA 55, which hasrequirements for all cryogenic systems. Chapter 11 of NFPA 55 has the material-specificrequirements for liquid hydrogen systems and refers to ASME B31.12 for hydrogen piping. Somesections from NFPA 55 have been extracted because they provide more specific details for hydrogenpiping (e.g, low temperature impact requirements and brazing material high temperaturerequirements). The extract tag was removed from 8.1.3.1 because the wording as modified does notexist in NFPA 55 but is an accurate and complete requirement for liquid hydrogen piping.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

222 of 491 1/30/2014 9:30 AM

First Revision No. 383-NFPA 2-2013 [ Section No. 8.1.4.1 ]

8.1.4.1 General.

8.1.4.1.1

Pressure relief devices shall be provided to protect containers and systems containing [LH2] from rupture

in the event of overpressure. [55:8.2.5 4 .1.1]

8.1.4.1.2

Pressure relief devices shall be designed in accordance with CGA S-1.1, Pressure Relief DeviceStandards — Part 1 — Cylinders for Compressed Gases, and CGA S-1.2, Pressure Relief DeviceStandards — Part 2 — Cargo and Portable Tanks for Compressed Gases, for portable tanks; and CGAS-1.3, Pressure Relief Device Codes Standards — Part 3 — Stationary Storage Containers forCompressed Gases, for stationary tanks. [55:8.2.5 4 .1.2]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 10:12:57 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

223 of 491 1/30/2014 9:30 AM

First Revision No. 384-NFPA 2-2013 [ Section No. 8.1.4.2 [Excluding any Sub-Sections] ]

Portable containers that are open to the atmosphere and are designed to contain [LH2] at atmospheric

pressure shall not be required to be equipped with pressure relief devices. [55:8.2.5 4 .2]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 10:13:45 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

224 of 491 1/30/2014 9:30 AM

First Revision No. 385-NFPA 2-2013 [ Sections 8.1.4.3, 8.1.4.4 ]

8.1.4.3 Equipment Other Than Containers.

Heat exchangers, vaporizers, insulation casings surrounding containers, vessels, and coaxial pipingsystems in which [LH2] could be trapped due to leakage from the primary container shall be provided with

a pressure relief device. [55:8.2.5 4 .3]

8.1.4.4 Sizing.

8.1.4.4.1

Pressure relief devices shall be sized in accordance with the specifications to which the container wasfabricated. [55:8.2.5 4 .4.1]

8.1.4.4.2

The pressure relief device shall have the capacity to prevent the maximum design pressure of thecontainer or system from being exceeded. [55:8.2.5 4 .4.2]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 10:15:07 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

225 of 491 1/30/2014 9:30 AM

First Revision No. 387-NFPA 2-2013 [ Section No. 8.1.4.5 [Excluding any Sub-Sections] ]

Pressure relief devices shall be located such that they are accessible for inspection and repair.[55:8.2.5 4 .5]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 10:17:05 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

226 of 491 1/30/2014 9:30 AM

First Revision No. 386-NFPA 2-2013 [ Section No. 8.1.4.5.1 ]

8.1.4.5.1*

ASME pressure relief valves shall be sealed to prevent adjustment made to be tamper resistant in orderto prevent adjusting of the set pressure by other than authorized personnel. [55:8.2.5 4 .5.1]

Supplemental Information

File Name Description

A.8.1.4.5.1_FR_386_.docx

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 10:16:13 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

227 of 491 1/30/2014 9:30 AM

A.8.1.4.5.1

Pressure relief valves are typically are spring-loaded valves where the relief pressure is set by adjustment of a spring. Valves should be sealed made to be tamper resistant in order to prevent adjustment by other than authorized personnel typically found at a retest facility. An ASME pressure relief valve is designed to comply with the requirements of the ASME Boiler and Pressure Vessel Code and typically is equipped with a wire and lead seal to prevent resist tampering. [55:A.8.2.54.5.1]

 

First Revision No. 388-NFPA 2-2013 [ Section No. 8.1.4.5.2 ]

8.1.4.5.2

Non-ASME pressure relief valves shall not be field adjusted. [55:8.2.5 4 .5.2]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 10:18:16 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

228 of 491 1/30/2014 9:30 AM

First Revision No. 389-NFPA 2-2013 [ Section No. 8.1.4.6 ]

8.1.4.6 Arrangement.

8.1.4.6.1 Pressure Relief Devices.

Pressure relief devices shall be arranged to discharge unobstructed to the open air in such a manner as toprevent impingement of escaping gas on personnel, containers, equipment, and adjacent structures or itsentrance into enclosed spaces. [55:8.2.5 4 .6.1]

8.1.4.6.2 Portable Containers with Volume Less than 2.0 ft scf 3 (0.057 N m3).

8.1.4.6.2.1

The arrangement of the discharge from pressure relief devices from DOT-specified containers with an

internal water volume of 2.0 ft scf 3 (0.057 N m3) or less shall be incorporated in the design of thecontainer. [55:8.2.5 4 .6.2.1]

8.1.4.6.2.2

Additional safeguards regarding placement or arrangement shall not be required. [55:8.2.5 4 .6.2.2]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 10:19:09 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

229 of 491 1/30/2014 9:30 AM

First Revision No. 390-NFPA 2-2013 [ Sections 8.1.4.7, 8.1.4.8 ]

8.1.4.7 Shutoffs Between Pressure Relief Devices and Containers.

8.1.4.7.1 General.

Shutoff valves installed between pressure relief devices and containers shall be in accordance with8.1.4.7. [55:8.2.5 4 .7.1]

8.1.4.7.2 Location.

Shutoff valves shall not be installed between pressure relief devices and containers unless the valves ortheir use meet the requirements of 8.1.4.7.2.1 or 8.1.4.7.2.2. [55:8.2.5 4 .7.2]

8.1.4.7.2.1 Security.

Shutoff valves shall be of a locking type locked in the open position , and their use shall be limited toservice-related work performed by the supplier under the requirements of the ASME Boiler and PressureVessel Code. [55:8.2.5 4 .7.2.1]

8.1.4.7.2.2 Multiple Pressure-Relief Devices.

Shutoff valves controlling multiple pressure relief devices on a container shall be installed so that eitherthe type of valve installed or the arrangement provides the full required flow through the minimum numberof required relief devices at all times. [55:8.2.5 4 .7.2.2]

8.1.4.8 Temperature Limits.

Pressure relief devices shall not be subjected to [LH2] fluid temperatures except when operating.

[55:8.2.5 4 .8]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 10:23:52 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

230 of 491 1/30/2014 9:30 AM

First Revision No. 480-NFPA 2-2013 [ Section No. 8.1.6.1 [Excluding any Sub-Sections] ]

[LH2] containers and systems shall be marked in accordance with nationally recognized codes standards

and in accordance with 8.1.6. [55:8.4.1]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 04 11:23:04 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

231 of 491 1/30/2014 9:30 AM

First Revision No. 391-NFPA 2-2013 [ Section No. 8.1.6.3.2 ]

8.1.6.3.2

The nameplate shall be marked in accordance with nationally recognized codes standards . [55:8.4.3.2]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 10:25:41 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

232 of 491 1/30/2014 9:30 AM

First Revision No. 393-NFPA 2-2013 [ Section No. 8.1.7.2 ]

8.1.7.2* Security of Areas.

Areas used for the storage of containers and systems shall be secured against unauthorized entry Userstorage sites shall be fenced or otherwise secured and posted to prevent entry by unauthorizedpersonnel . [55:8.6.2 11.4.1.4 ]

8.1.7.2.1

Administrative controls shall be allowed to be used to control access to individual storage, use, andhandling areas located in secure facilities not accessible by the general public. [ 55 :11.4.1.4.1]

Supplemental Information

File Name Description

FR_393_Annex_Material.docx

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 10:27:28 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

233 of 491 1/30/2014 9:30 AM

 FR 393 Annex Material  

A.8.1.7.2 The basis of this requirement is to prevent unauthorized personnel or those unfamiliar with gas storage systems from tampering with the equipment. Where LH2 is located in an area open to the general public, a common practice is to fence and lock the storage or use area, with access restricted to supplier and user personnel. When the storage or use is located within the user’s secure area and is not accessible by the general public, a common practice is to fence and lock the storage or use area, with access restricted to supplier and user personnel. When the storage or use is located within the user’s secure area and is not accessible by the general public, it is not always necessary to fence or otherwise secure individual gas storage or use areas. Personnel access patterns may still mandate that the system be fenced, as determined by the supplier and the user. [55: A.11.4.1.4]

 

First Revision No. 32-NFPA 2-2013 [ Section No. 8.1.8 ]

8.1.8 Surfaces Beneath Containers. Separation from Hazardous Conditions.

The surface of the area on which stationary containers are placed, including the surface of the arealocated below the point at which connections are made for the purpose of filling such containers, shallbe compatible with the [LH 2 ] in the container. [ 55: 8.7.2.3]

8.1.8.1 General.

[LH 2 ] containers and systems in storage or use shall be separated from materials and conditions that

present exposure hazards to or from each other in accordance with 8.1.8 . [ 55: 8.7.1]

8.1.8.1.1* Surfaces Beneath Containers.

The surface of the area on which stationary containers are placed, including the surface of the arealocated below the point at which connections are made for the purpose of filling such containers, shallbe compatible with the [LH 2 ] in the container. [ 55: 8.7.2.3]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 12:37:21 EDT 2013

Committee Statement

CommitteeStatement:

Section 8.1.8 doesn't really cover the subject of "Separation from Hazardous Conditions". It onlyhas one actual requirement 8.1.8.1.1, which can go in the Design requirements (as 8.1.3.1) and therest of the section 8.1.8 can be deleted. The actual requirements of the source section onSeparation from Hazardous Conditions (55:8.7) have been extracted into other sections of Chapter8 in NFPA 2.

ResponseMessage:

Public Input No. 71-NFPA 2-2012 [Section No. 8.1.8]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

234 of 491 1/30/2014 9:30 AM

First Revision No. 394-NFPA 2-2013 [ New Section after 8.1.10.1.2 ]

8.1.10.1.3

Containers that have previously been used for [LH 2 ] and have been removed from service shall be

purged with an inert gas to remove residual [LH 2 ] and stored with all valves closed and the valve

outlets plugged. [ 55: 8.9.1.3]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 10:28:25 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

235 of 491 1/30/2014 9:30 AM

First Revision No. 33-NFPA 2-2013 [ Section No. 8.2.2.2.1 ]

8.2.2.2.1 Installation.

Stationary c C ontainers stored indoors shall be installed in accordance with Sections 8.1 and 8.2.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 12:56:26 EDT 2013

Committee Statement

CommitteeStatement:

As currently worded, the requirements for indoor storage of portable LH2 containers are notaddressed. The same requirements should apply for portable and stationary containers.

ResponseMessage:

Public Input No. 72-NFPA 2-2012 [Section No. 8.2.2.2.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

236 of 491 1/30/2014 9:30 AM

First Revision No. 34-NFPA 2-2013 [ Section No. 8.2.2.2.2 ]

8.2.2.2.2 Stationary Containers.

Stationary containers shall be in accordance with 8.1.2 . [ 55: 8.13.1.2]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 13:00:54 EDT 2013

Committee Statement

CommitteeStatement:

The same requirement (8.1.2) should apply for portable containers. Othewrwsie if they aredifferent, we should call them out.

ResponseMessage:

Public Input No. 73-NFPA 2-2012 [Section No. 8.2.2.2.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

237 of 491 1/30/2014 9:30 AM

First Revision No. 481-NFPA 2-2013 [ Section No. 8.2.2.2.5 ]

8.2.2.2.4 Installation of LH2 Inside Buildings Other Than Detached Buildings and Gas Rooms.

Portable LH2 containers of [39.7 gal (150 L) or less capacity] where housed inside buildings, not located

in a gas room, and exposed to other occupancies shall comply with the following minimum requirements:[55:11.3.3]

(1) Containers shall be located 20 ft (6.1 m) from all classes of flammable or combustible liquids andcombustible materials such as excelsior or paper. [55:11.3.3(1)]

(2) Containers shall be located 25 ft (7.6 m) from ordinary electrical equipment and other sources ofignition, including process or analytical equipment. (See 8.1.8 .) [55:11.3.3(2)]

(3) Containers shall be located 50 ft (15 m) from intakes for ventilation, air-conditioning equipment, orcompressors. [55:11.3.3(3)]

(4) Containers shall be located 50 ft (15 m) from the storage or use of other flammable gases or thestorage or use of incompatible gases. [55:11.3.3(4)]

(5) Containers shall be protected against physical damage in accordance with the requirements of8.1.7.5. [55:11.3.3(5)]

(6) Containers shall be secured in accordance with the requirements of 8.1.7.3. [55:11.3.3(6)]

(7) Welding or cutting operations and smoking shall be prohibited while hydrogen is in the room, andsigns shall be provided as required by 4.13.3. [55:11.3.3(7)]

(8) Ventilation shall be provided in accordance with the requirements of Section 6.17. [55:11.3.3(8)]

(9) Pressure-relief devices on stationary or portable containers shall be vented directly outdoors or to anexhaust hood. (See 8.1.4.6) [55:11.3.3(9)]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 04 11:32:52 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

238 of 491 1/30/2014 9:30 AM

First Revision No. 395-NFPA 2-2013 [ Section No. 8.2.2.3.1.2 ]

8.2.2.3.1.2 Enclosed Courts.

[-] containers shall not be installed within [outdoor] enclosed courts. [ 55: 8.13.2.7.1]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 10:30:40 EDT 2013

Committee Statement

Committee Statement: Update of extract material. Definition and associated annex material to be deleted.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

239 of 491 1/30/2014 9:30 AM

First Revision No. 396-NFPA 2-2013 [ Section No. 8.2.2.3.4 ]

8.2.2.3.4 Separation Distance to Exposures .

The outdoor use of [LH 2 ] shall be located from lot lines, public streets, public alleys, public ways, or

buildings not associated with the manufacture or distribution of [GH 2 ] Non -bulk portable containers of

liquefied hydrogen shall be separated from exposure hazards in accordance with Table 8.2.2.3.4.[55:7.6.2 8.7.3.1 ]

Table 8.2.2.3.4 Distance to Exposures for Non-Bulk Liquefied Hydrogen [LH2]a, b, c

MaximumAmount per

Storage Area(gal)

MinimumDistanceBetweenStorage

Areas (ft)

MinimumDistance toLot Lines of

PropertyThat Can BeBuilt Upon

(ft)

MinimumDistance to

PublicStreets,Public

Alleys orPublic

Ways (ft)

Minimum Distance to Buildings on theSame Property

Less than2-Hour

Construction2-Hour

Construction4-Hour

Construction

[0–39.7] 5 5 5 5 0 0

[39.8–186.9] 10 10 10 10 5 0

[187–448.7] 10 15 15 20 5 0

[448.8–747.8] 10 20 20 20 5 0

[>747.8] 20 25 25 20 5 0

For SI units: 1 ft = 304.8 305 mm 3 = 0.02832 305 m 3 .

Notes:

[ (a) For requirements on minimum distance to air intakes, see 8.2.2.3.4.2.]

[ (b) For requirements on minimum distance to building openings including exits, see 8.2.2.3.4.3.]

(c) The minimum required distances shall not apply when fire barriers without openings or penetrationshaving a minimum fire resistive rating of 2 hours interrupt the line of sight between the storage and theexposure. The When 8.2.2.3.4.1 is used as a means of distance reduction, the configuration of the firebarriers shall should be designed to allow natural ventilation to prevent the accumulation of hazardousgas concentrations.

[55: Table 7.6.2 8.7.3.1 ]

8.2.2.3.4.1 Fire Barriers.

A 2-hour fire barrier wall shall be permitted in lieu of the distances specified by Table 8.2.2.3.4 when inaccordance with the provisions of 8.2.2.3.4.1(A) through 8.2.2.3.4.1(E). [55:8.7.3.1 2 ]

(A)

The fire barrier wall shall be without openings or penetrations. [55:8.7.3.1 2 .1]

(B)

Penetrations of the fire barrier wall by conduit or piping shall be permitted provided that the penetration isprotected with a firestop system in accordance with the building code. [55:8.7.3.1 2 .1.1]

(C)

The fire barrier wall shall be either an independent structure or the exterior wall of the building adjacent tothe storage system. [55:8.7.3.1 2 .2]

(D)

The fire barrier wall shall be located not less than 5 ft (1.5 m) from any exposure. [55:8.7.3.1 2 .3]

(E)

The fire barrier wall shall not have more than two sides at approximately 90 degree (1.57 rad) directions ornot more than three sides with connecting angles of approximately 135 degrees (2.36 rad).[55:8.7.3.1 2 .4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

240 of 491 1/30/2014 9:30 AM

8.2.2.3.4.2 Air Intakes.

Storage and use of [LH2] shall not be located within 50 ft (15.2 m) of air intakes. [55:7.6.2.4]

8.2.2.3.4.3 Building Openings.

Storage and use of [LH2] outside of buildings shall also be separated from building openings by 25 ft (7.6

m). Fire barriers shall be permitted to be used as a means to separate storage areas from openings or ameans of egress used to access the public way. [55:7.6.2.5]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 10:32:26 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

241 of 491 1/30/2014 9:30 AM

First Revision No. 397-NFPA 2-2013 [ Section No. 8.2.2.3.6 ]

8.2.2.3.6 Physical Protection.

8.2.2.3.6.1

[LH2] cylinders, containers, cylinders, tanks, and systems that could be exposed to physical damage

shall be protected. [55:8.13.2.3]

8.2.2.3.6.2

Guard posts or other means shall be provided to protect [LH2] cylinders, containers, cylinders, tanks, and

systems indoors and outdoors from vehicular damage. (See Section 4.14). [55:8.13.2.3.1]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 10:38:06 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

242 of 491 1/30/2014 9:30 AM

First Revision No. 398-NFPA 2-2013 [ Section No. 8.2.2.3.9.3 ]

8.2.2.3.9.3

The provisions of 8.2.2.3.9.2 shall be permitted to be altered or waived where the authority havingjurisdiction determines that the container does not constitute a hazard after consideration of specialfeatures such as the following: [55:8.13.2.6.3]

(1) Crushed rock utilized as a heat sink [55:8.13.2.6.3(1)]

(2) Topographical conditions [55:8.13.2.6.3(2)]

(3) Nature of occupancy [55:8.13.2.6.3(3)]

(4) Proximity to structures on the same or adjacent property [55:8.13.2.6.3(4)]

(5) Capacity and construction of containers and character of fluids to be stored [LH 2 ] [55:8.13.2.6.3(5)]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 10:41:25 EDT 2013

Committee Statement

Committee Statement: Update of extract materials.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

243 of 491 1/30/2014 9:30 AM

First Revision No. 399-NFPA 2-2013 [ Section No. 8.2.3.1.1.3 ]

8.2.3.1.1.3 Inspection.

(A)

[LH2] storage systems shall be inspected annually and maintained by a qualified representative of the

equipment owner as required by the material-specific requirements of Chapter 8 . [55:8.14.1.3.1]

(A)

The interval between inspections [-] shall be based on nationally recognized good practices orstandards. [ 55: 8.14.1.3.1.1]

(B)

A record of the inspection shall be prepared and provided to the user or the authority having jurisdictionupon request. [55:8.14.1.3.2]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 10:44:41 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

244 of 491 1/30/2014 9:30 AM

First Revision No. 400-NFPA 2-2013 [ Section No. 8.2.3.1.3 ]

8.2.3.1.3 Joints.

Joints in piping and tubing shall be permitted to be made by welding or brazing, or by use of flanged,threaded, socket, slip, or compression fittings in accordance with the requirements of ANSI/ASME B31.3,Process Piping , or other approved standards . [55:8.14.3]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 10:46:43 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

245 of 491 1/30/2014 9:30 AM

First Revision No. 401-NFPA 2-2013 [ Section No. 8.2.3.1.6.2 ]

8.2.3.1.6.2

Pressure relief valves shall be installed where liquid or cold gas can be trapped between shutoff valves inthe piping system. (See 8.1.4 .) [55:8.14.6.2]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 10:50:13 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

246 of 491 1/30/2014 9:30 AM

First Revision No. 484-NFPA 2-2013 [ Section No. 8.2.3.1.9.3(C) ]

(C)

The system owner shall maintain the following records to demonstrate that the cathodic protection is inconformance with the requirements of the design: [55:8.14.9.3.3]

(1) The results of inspections of the system [55:8.14.9.3.3(1)]

(2) The results of testing that has been completed [55:8.14.9.3.3(2)]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 04 16:12:19 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

247 of 491 1/30/2014 9:30 AM

First Revision No. 402-NFPA 2-2013 [ Section No. 8.2.3.1.10.1 ]

8.2.3.1.10.1

Piping systems shall be tested and proven free of leaks after installation as required by the codes andstandards to which they are designed and constructed. [55:8.14.10.1]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 10:51:20 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

248 of 491 1/30/2014 9:30 AM

First Revision No. 403-NFPA 2-2013 [ Section No. 8.2.3.2.1.1 ]

8.2.3.2.1.1 General.

Filling and dispensing of [LH 2 ] shall be in accordance with 8.3.3.1.4 A qualified person shall be in

attendance at all times cryogenic fluid is transferred from mobile supply units to a storage system. .[55:8.14.11.3.1 1.2 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 10:52:23 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

249 of 491 1/30/2014 9:30 AM

First Revision No. 35-NFPA 2-2013 [ Section No. 8.2.3.3 ]

8.2.3.3 Outdoor Use. (Reserved)

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 13:06:55 EDT 2013

Committee Statement

Committee Statement: Section should be marked as reserved since it has no content

Response Message:

Public Input No. 106-NFPA 2-2013 [Section No. 8.2.3.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

250 of 491 1/30/2014 9:30 AM

First Revision No. 404-NFPA 2-2013 [ Section No. 8.2.4.1 ]

8.2.4.1 Applicability. Nonbulk LH 2

Handling of [LH2] containers shall be in accordance with 8.2.4. [55:8.14.11.4.1]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 10:53:27 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

251 of 491 1/30/2014 9:30 AM

First Revision No. 36-NFPA 2-2013 [ Section No. 8.3.1.2.1.2 ]

8.3.1.2.1.2

Containers shall be marked in accordance with the provisions of 8.1.6 and as follows:

LIQUEFIED HYDROGEN — FLAMMABLE GAS

[ 55: 11.2.1.2]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 13:13:16 EDT 2013

Committee Statement

CommitteeStatement:

This container marking requirement is misplaced. It is not related to the heading "fire protectionof structural supports". It should be moved to a new section 8.1.6.1.3.1

ResponseMessage:

Public Input No. 74-NFPA 2-2012 [Section No. 8.3.1.2.1.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

252 of 491 1/30/2014 9:30 AM

First Revision No. 405-NFPA 2-2013 [ Sections 8.3.1.2.3.1, 8.3.1.2.3.2, 8.3.1.2.3.3 ]

8.3.1.2.3.1

Piping and tubing shall be in accordance with the requirements of ANSI/ ASME B31.3 12 ,Process Hydrogen Piping and Pipelines . [55:11.2.3.1]

8.3.1.2.3.2

Piping or tubing used at operating temperatures below -20°F (-29°C) shall be fabricated from materialsmeeting the impact test requirements of Chapter III of ANSI/ ASME B31.3 12 , Process Hydrogen Pipingand Pipelines , when tested at the minimum operating temperature to which the piping will be exposedwhen in service. [55:11.2.3.2]

8.3.1.2.3.3

Joints in piping and tubing shall be in accordance with the requirements of ANSI/ ASME B31.3 12 ,Process Hydrogen Piping and Pipelines . [55:11.2.3.3]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 10:54:58 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

253 of 491 1/30/2014 9:30 AM

First Revision No. 485-NFPA 2-2013 [ Section No. 8.3.1.2.3.4 ]

8.3.1.2.3.4

Brazing materials, when where used, shall have a melting point above 1000°F (538°C). [55:11.2.3.4]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 04 16:15:23 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

254 of 491 1/30/2014 9:30 AM

First Revision No. 406-NFPA 2-2013 [ Section No. 8.3.1.2.4.1 ]

8.3.1.2.4.1

Installation of bulk LH2 systems shall be supervised by personnel knowledgeable about the applicable

codes and the construction and use of the system to be installed. [55:11.2.4.1]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 10:56:41 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

255 of 491 1/30/2014 9:30 AM

First Revision No. 407-NFPA 2-2013 [ Section No. 8.3.1.2.4.2(B) ]

(B)

Containers exceeding 2000 gal (7570 L) capacity shall be provided with an automatic emergency shutoffvalve. [55:11.2.4.2.2]

(1) The automatic shutoff valve shall be operated by a remotely located, manually activated shutdowncontrol. [55:11.2.4.2.2.1]

(2) The shutoff valve shall be connected to the primary container by means of welded connectionswithout the use of flanges or other appurtenances except that a manual shutoff valve equipped withwelded connections is allowed to be installed immediately upstream of the automatic shutoff valve toallow for maintenance of the automatic valve. [55:11.2.4.2.2.2]

(3) Connections downstream of the shutoff valve shall be in accordance with ANSI/ASME B31.3,Process Piping ASME B31.12 Hydrogen Piping and Pipelines . [55:11.2.4.2.2.3]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 10:57:23 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

256 of 491 1/30/2014 9:30 AM

First Revision No. 408-NFPA 2-2013 [ Section No. 8.3.1.2.6 [Excluding any

Sub-Sections] ]

Electrical wiring and equipment shall be in accordance with Table 8.3.1.2.6 and NFPA 70, NationalElectrical Code . [55:11.2.6]

Table 8.3.1.2.6 Electrical Area Classification

Location Division Extent of Classified Area

Points where connections to the hydrogen system areregularly made and disconnected The bulk liquefiedhydrogen system fill connection, pressure relief vent outlets,or other points on the system where hydrogen is vented tothe atmosphere under the designed operating conditions

1

Within 3 ft (1 m) of the system fillconnection, system pressurerelief vent outlets or, other pointsof release when the system isoperating as designed

Storage equipment excluding the piping system downstreamof the source valve.

2

Between 3 ft (1 m) and 25 ft (4.6m) from system pressure reliefvent outlets or, other points ofrelease when the system isoperating as designed

[55: Table 11.2.6]

Supplemental Information

File Name Description

FR_408_Material.docx

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 10:58:27 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

257 of 491 1/30/2014 9:30 AM

8.3.1.2.6 Electrical Systems. Electrical wiring and equipment shall be in accordance with Table 8.3.1.2.6 and NFPA 70, National Electrical Code. [55:11.2.6]

Table 8.3.1.2.6 Electrical Area Classification

Location Division Extent of Classified Area

Points where connections to the hydrogen system are regularly made and disconnectedThe liquefied bulk hydrogen system fill connection, pressure relief vent outlets, or other points on the system where hydrogen is vented to the atmosphere under the designed operating conditions

1 Within 3 ft (1 m) of the system fill connection, system pressure relief vent outlets or, other points of release when the system is operating as designed

Storage equipment excluding the piping system downstream of the source valve.

2 Between 3 ft (1 m) and 25 ft (7.6 4.6 m) from system pressure relief vent outlets or, other points of release when the system is operating as designed

[55: Table 11.2.6]

First Revision No. 409-NFPA 2-2013 [ Section No. 8.3.1.2.8.5 ]

8.3.1.2.8.5* Pressure Monitoring.

The p P ressure on each the pump and or compressor discharge shall be monitored by the controlsystem. [55:11.2.8.5]

(A)

Discharge pressures in excess of the equipment design pressures shall cause the pump or compressorto shut down. [ 55: 11.2.8.5.1]

Supplemental Information

File Name Description

A_8_3_1_2_8_5_FR_409_SB.docx

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 11:00:26 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

258 of 491 1/30/2014 9:30 AM

A.8.3.1.2.8.5

Liquid hydrogen supply systems typically store the liquid, a cryogenic fluid, in storage tanks with maximum allowable working pressures (MAWP) that range from 150 psig to 250 psig. The majority of tanks area limited to 150 psig MAWP. Liquid hydrogen is piped from the tank to a vaporizer that serves as a heat exchanger and to convert the fluid from the liquid to the gaseous state in order to provide a supply of gaseous hydrogen to the user. The gaseous hydrogen supply pressure for such systems is limited to a maximum pressure below that of the storage tank MAWP.. Additional details on system arrangement and piping systems can be found in CGA H-5, Installation Standards for Bulk Hydrogen Supply Systems. [55:A.11.2.8.5]

When gaseous or liquid hydrogen is required to be supplied at pressures higher than the storage tank MAWP, either pumps or compressors are added to the system to raise the delivered pressure. Pumps are used for delivering hydrogen in the liquid state, while compressors deliver hydrogen in the gaseous state. Additional details on system arrangement and piping systems can be found in CGA H-5, Installation Standards for Bulk Hydrogen Supply Systems. [55: A.11.2.8.5]

 

Formatted: Font: Italic

Formatted: Font: Italic

First Revision No. 37-NFPA 2-2013 [ Section No. 8.3.1.2.9.1 ]

8.3.1.2.9.1

The ESD system shall be operated by a remotely located manually activated shutdown control locatednot less than 15 feet (4.5 m) from the source of supply (1) a local manually activated shutdown controllocated near the source and accessible to the operator and (2) by a remote manually activated shutdowncontrol located in an accessible area at least 25 ft (8 m) from the source . [ 55: 11.2.9.1]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 13:38:23 EDT 2013

Committee Statement

CommitteeStatement:

15 ft from the source is not "remote" in the sense of protecting an operator or responder from injuryduring an LH2 release. At this distance, the operator or responders might have to run into harm'sway in order to activate the ESD. "Remote" is a relative term, I proposed 75 ft (23 m) based on therequirement for separation distance from bulk sources to public assembly in Table in Table8.3.2.4.5.1.

ResponseMessage:

Public Input No. 108-NFPA 2-2013 [Section No. 8.3.1.2.9.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

259 of 491 1/30/2014 9:30 AM

First Revision No. 410-NFPA 2-2013 [ Section No. 8.3.2.1.4.4 ]

8.3.2.1.4.4 Concrete Containers.

(A)

Concrete containers shall be built in accordance with the [adopted] building code. [ 55: 8.2.3.1]

(B)

Barrier materials and membranes used in connection with concrete, but not functioning structurally, shallbe materials prescribed by nationally recognized standards. [ 55: 8.2.3.2]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 11:01:44 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

260 of 491 1/30/2014 9:30 AM

First Revision No. 411-NFPA 2-2013 [ Section No. 8.3.2.1.4.5 ]

8.3.2.1.4.4 Foundations and Supports.

Stationary tanks shall be provided with concrete or masonry foundations or structural steel supports onfirm concrete or masonry foundations, and the requirements of 8.3.2.1.4.4(A) through 8.3.2.1.4.4(E) alsoshall apply. [55:8.2.4 3 ]

(A)

Excessive Loads. Stationary tanks shall be supported to prevent the concentration of excessive loads onthe supporting portion of the shell. [55:8.2.4 3 .1]

(B)

Expansion and Contraction. Foundations for horizontal containers shall be constructed to accommodateexpansion and contraction of the container [55:8.2.3.2]

(C)*

Support of Ancilliary Equipment.

(1) Foundations shall be provided to support the weight of the vaporizers or heat exchangers.[55:8.2.4 3 .3.1]

(2) Foundations shall be designed to withstand soil and frost conditions as well as the anticipatedseismic, snow, wind, and hydrostatic loading under operating conditions. [55:8.2.4 3 .3.2]

(D)

Temperature Effects. Where drainage systems, terrain, or surfaces beneath stationary tanks arearranged in a manner that can subject stationary tank foundations or supports to temperatures below–130°F (–90°C), the foundations or supports shall be constructed of materials that are capable ofwithstanding the low-temperature effects of [LH2] spillage. [55:8.2.4 3 .4]

(E)

Corrosion Protection. Portions of stationary tanks in contact with foundations or saddles shall be paintedto protect against corrosion. [55:8.2.4 3 .5]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 11:02:38 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

261 of 491 1/30/2014 9:30 AM

First Revision No. 412-NFPA 2-2013 [ Section No. 8.3.2.2.1.4 ]

8.3.2.2.1.4 Specific Locations.

The location of bulk LH2 storage systems , as determined by the [maximum total quantity of LH2], shall

be in accordance with Table 8.3.2.2.1.4. [55:11.3.2.1]

Table 8.3.2.2.1.4 Location of [LH2] Systems

Quantity of Hydrogen

Location MAQ

>MAQ to 300 gal(>170.32 L to 1135.5

L)

>300 to 600 gal(>1135.5 L to 2271

L)>600 gal(>2271 L)

Outdoors A A A A

In a detached building A A A NA

In a gas room A A NA NA

Inside a building (not in a gas room ordetached building) and exposed to otheroccupancies

A NA NA NA

MAQ: Maximum allowable quantity. A: Allowed. NA: Not allowed.

[55: Table 11.3.2.1]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 11:05:48 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

262 of 491 1/30/2014 9:30 AM

First Revision No. 486-NFPA 2-2013 [ Section No. 8.3.2.2.2.2(C) ]

(C)

Both the inlet and outlet vent openings shall have a minimum total area of 1 ft 2 /1000 scf ft 3 (1 m2/300

N m3) of room volume. [55:11.4.4.2.3]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 04 16:27:39 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

263 of 491 1/30/2014 9:30 AM

First Revision No. 38-NFPA 2-2013 [ New Section after 8.3.2.2.3.1 ]

8.3.2.2.3.2

Explosion control shall be provided in accordance with the requirements of Section 6.9 . [ 55: 11.4.4.1.2]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 14:20:25 EDT 2013

Committee Statement

CommitteeStatement:

This is added as a clarification that explosion control is needed for gas rooms containing bulkLH2 (same as is done in the previous section for detached buildings (see 8.3.2.2.2.1 (B))

ResponseMessage:

Public Input No. 109-NFPA 2-2013 [New Section after 8.3.2.2.3.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

264 of 491 1/30/2014 9:30 AM

First Revision No. 413-NFPA 2-2013 [ Section No. 8.3.2.2.4 ]

8.3.2.2.4 Installation of LH 2 Inside Buildings Other Than Detached Buildings and Gas Rooms.

Portable LH 2 containers, where housed inside buildings not located in a gas room and exposed to

other occupancies, shall comply with the following minimum requirements:

Containers shall be located 20 ft (6.1 m) from all classes of flammable or combustible liquids andcombustible materials such as excelsior or paper. [ 55: 11.3.3(1)]

Containers shall be located 50 ft (15 m) from storage or use of other flammable gases or storageor use of incompatible gases. [ 55: 11.3.3(4)]

Containers shall be protected against physical damage in accordance with the requirements of8.1.7.5 . [ 55: 11.3.3(5)]

Containers shall be secured in accordance with the requirements of 8.1.7.3 . [ 55: 11.3.3(6)]

Welding or cutting operations and smoking shall be prohibited while hydrogen is in the room, andsigns shall be provided as required by 4.14.3. [See also 4.13 .] [ 55: 11.3.3(7)]

Ventilation shall be provided in accordance with the requirements of Section 6.17 .[ 55: 11.3.3(8)]

Pressure relief devices on stationary or portable containers shall be vented directly outdoors or toan exhaust hood. ( See 8.1.4.6 ) [ 55: 11.3.3(9)]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 11:07:12 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

265 of 491 1/30/2014 9:30 AM

First Revision No. 414-NFPA 2-2013 [ Section No. 8.3.2.4 ]

8.3.2.3.1 Aboveground Tanks.

8.3.2.3.1.1 Access.

(A)

Stationary containers shall be located to provide access by mobile supply equipment and authorizedpersonnel. [ 55: 8.13.2.2]

(B)

Where exit access is provided to serve areas in which equipment is installed, the minimum width shallbe not less than 28 in. (710 mm). [ 55: 8.13.2.2.1]

8.3.2.3.1.2 Physical Protection.

(A)

[LH 2 ] cylinders, containers, tanks, and systems that could be exposed to physical damage shall be

protected. [ 55: 8.13.2.3]

(B)

Guard posts or other means shall be provided to protect [LH 2 ] cylinders, containers, tanks, and

systems indoors and outdoors from vehicular damage. (See Section 4.14 .) [ 55: 8.13.2.3.1]

8.3.2.3.1.3* Areas Subject to Flooding.

Stationary containers located in flood hazard areas shall be anchored to prevent flotation duringconditions of the design flood as designated by the [adopted] building code. [ 55: 8.13.2.5]

(A) Elevated Tanks.

Structures supporting elevated tanks and tanks that are supported at a level above that designated inthe design flood shall be anchored to resist lateral shifting due to flood and other hydrostatic effects.[ 55: 8.13.2.5.1]

8.3.2.3.1.4 Drainage.

(A)

The area surrounding stationary and portable containers shall be provided with a means to preventaccidental discharge of fluids from endangering personnel, containers, equipment, and adjacentstructures and from entering enclosed spaces in accordance with [the adopted fire prevention code].[ 55: 8.13.2.6.1]

(B)

The stationary container shall not be placed where spilled or discharged [LH 2 ] will be retained around

the container. [ 55: 8.13.2.6.2]

(C)

The provisions of 8.3.2.3.1.4(B) shall be permitted to be altered or waived where the authority havingjurisdiction determines that the container does not constitute a hazard after consideration of specialfeatures such as the following: [ 55: 8.13.2.6.3]

(1) Crushed rock utilized as a heat sink [ 55: 8.13.2.6.3(1)]

(2) Topographical conditions [ 55: 8.13.2.6.3(2)]

(3) Nature of occupancy [ 55: 8.13.2.6.3(3)]

(4) Proximity to structures on the same or adjacent property [ 55: 8.13.2.6.3(4)]

(5) Capacity and construction of containers and character of fluids to be stored [ 55: 8.13.2.6.3(5)]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

266 of 491 1/30/2014 9:30 AM

(D) Grade.

The grade for a distance of not less than 50 ft (15.2 m) from where cryogenic fluid storage or deliverysystems are installed shall be higher than the grade on which flammable or combustible liquids arestored or used. [ 55: 8.13.2.6.4]

(1) Drainage Control.

(a) Where the grade differential between the storage or delivery system and the flammable orcombustible liquids storage or use area is not in accordance with 8.3.2.3.1.4(D) , diversioncurbs or other means of drainage control shall be used to divert the flow of flammable orcombustible liquids away from the [LH 2 ]. [ 55: 8.13.2.6.4.1(A)]

(b) The means of drainage control shall prevent the flow of flammable or combustible liquid to adistance not less than 50 ft (15.2 m) from all parts of the delivery system.[ 55: 8.13.2.6.4.1(B)]

8.3.2.3.1.5 Design Considerations at Specific Locations.

(A) Outdoor Locations.

Roadways and yard surfaces located below [LH 2 ] piping as well as areas located under the fill

connections and delivery vehicles’ uninsulated hydrogen piping from which liquid air is able to drip shallbe constructed of noncombustible materials. [ 55: 11.4.1.1]

(1) Asphalt and bitumastic paving shall be assumed to be combustible. [ 55: 11.4.1.1.1]

(2) Expansion joints and fillers used in the construction of concrete slabs shall be of noncombustiblematerials. [ 55: 11.4.1.1.2]

(B)

Weather protection shall be constructed in accordance with the requirements of the adopted buildingcode.

(C)

Lighting shall be provided for nighttime transfer operation, and supplemental lighting shall be providedwhere required by 8.1.13 . [ 55: 11.4.1.3]

(D) Enclosed Courts.

Stationary containers shall not be installed within enclosed courts. [ 55: 8.13.2.7.1]

(E)* Open Courts

Stationary containers shall be sited so that they are open to the surrounding environment except thatencroachment by building walls of unlimited height shall be permitted when in accordance with thedistances specified by Table 8.3.2.3.1.6(A) . [ 55: 8.13.2.7.2]

(1)

(2) The required distance between the exterior walls of the building forming the court and thecontainer shall be determined independently without regard to fire barrier walls used to allowencroachment by fire exposure hazards. [ 55: 8.13.2.7.2.2]

(F) Fenced Areas.

(1)

8.3.2.3.1.6 Siting Locations.

* Where exterior building walls encroach on the system to form a court, the system shall belocated at a distance not less than the height of the wall from at least two court walls.[ 55: 8.13.2.7.2.1]

* User storage sites shall be fenced or otherwise secured and posted to prevent entry byunauthorized personnel. [ 55: 11.4.1.4]

(a) Administrative controls shall be allowed to be used to control access to individual storage,use, and handling areas located in secure facilities not accessible by the general public.[ 55: 11.4.1.4.1]

(b) At least two means of egress shall be provided from any fenced area. [ 55: 11.4.1.4.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

267 of 491 1/30/2014 9:30 AM

(A)*

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

268 of 491 1/30/2014 9:30 AM

The minimum distance from [LH 2 ] systems of indicated capacity shall be in accordance with Table

8.3.2.3.1.6(A) . [ 55: 11.3.2.2]

Table 8.3.2.3.1.6(A) Minimum Distance from Bulk Liquefied Hydrogen[LH 2 ] Systems to Exposures

Total Bulk Liquefied Hydrogen [LH 2 ] Storage

39.7 gal to3500 gal

150 L to13,250 L

3501 galto 15,000gal

13,251 L to56,781 L

15,001 galto 75,000gal

56,782 Lto283,906 L

Type of Exposure ft m ft m ft m

Group 1

1. Lot lines25 7.6 50 15 75 23

2. Air intakes [heating,ventilating, or airconditioning equipment(HVAC, compressors, other]

75 23 75 23 75 23

3. Wall openings

Operable openings inbuildings and structures

75 23 75 23 75 23

4. Ignition sources such asopen flames and welding

50 15 50 15 50 15

Group 2

5. Places of publicassembly

75 23 75 23 75 23

Group 3

6. Building or structure

(a) Buildings constructed ofnoncombustible or limited-combustible materials

(1) Sprinklered building orstructure or unsprinkleredbuilding or structure havingnoncombustible contents

5 a 1.5 5 a 1.5 5 a 1.5

(2) Unsprinklered buildingor structure withcombustible contents

(i) Adjacent wall(s) with fireresistance rating less than3 hours

25 7.6 50 15 75 23

(ii) Adjacent wall(s) with fireresistance rating of 3 hours

or greater b5 1.5 5 1.5 5 1.5

(b) Buildings of combustibleconstruction

(1) Sprinklered building orstructure

50 15 50 15 50 15

(2) Unsprinklered buildingor structure

50 15 75 23 100 30.5

7. Flammable gas storageor systems (other thanhydrogen) above or below

50 15 75 23 75 23

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

269 of 491 1/30/2014 9:30 AM

a Portions of wall less than 10 ft (3.1 m) (measured horizontally) from any part of a system must have afire resistance rating of not less than 1 hour.

b Exclusive of windows and doors.

c The separation distances for Class IIIB combustible liquids shall be permitted to be reduced to 15 ft(4.6 m).

[ 55: Table 11.3.2.2]

(1) The distances in 1, 6, 7, 9, 10, and 11 in Table 8.3.2.3.1.6(A) shall be permitted to be reduced bytwo-thirds, but not to less than 5 ft (1.5 m), for insulated portions of the system. [ 55: 11.3.2.2.1]

(2)

(B)

Unloading connections on delivery equipment shall not be positioned closer to any of the exposurescited in Table 8.3.2.3.1.6(A) than the distances given for the storage system. [ 55: 11.3.2.3]

(C)

The minimum distance of container fill connections from parked vehicles shall be 25 ft (7.6 m).[ 55: 11.3.2.4]

* Fire Barrier Walls. The distances in 1, 6, 7, 9, 10 and 11 in Table 8.3.2.3.1.6(A) shall bepermitted to be reduced by the use of fire barrier walls having a fire resistance rating of not lessthan 2 hours when constructed in accordance with 8.3.2.3.1.6(A) . [ 55: 11.3.2.2.2]

(a) The fire barrier or the insulated [LH 2 ] tank shall interrupt the line of sight between

uninsulated portions of the [LH 2 ] storage system and the exposure. [ 55: 11.3.2.2.3]

(b) The fire barrier wall shall not have more than two sides at 90 degree (1.57 rad) directions,or not more than three sides with connecting angles of not less than 135 degrees (2.36rad). [ 55: 11.3.2.2.4]

i.

(c)

(d) The fire barrier wall shall be without openings or penetrations. [ 55: 8.7.2.1.1]

i. Penetrations of the fire barrier wall by conduit or piping shall be permitted providedthat the penetration is protected with a fire stop system in accordance with the[adopted] building code. [ 55: 8.7.2.1.1.1]

(e) The fire barrier wall shall be either an independent structure or the exterior wall of thebuilding adjacent to the storage system. [ 55: 8.7.2.1.2]

(f) The fire barrier wall shall not be located less than 5 ft (1.5 m) from any exposure.[ 55: 8.7.2.1.3]

(g) Where the requirement of 8.3.2.3.1.6(A)(2)(b) is met, the bulk system shall be a minimumdistance of 1 ft (0.3 m) from the fire barrier wall. [ 55: 8.7.2.1.5]

* The connecting angles between fire barrier walls shall be permitted to be reduced toless than 135 degrees (2.36 rad) for installations consisting of three walls when inaccordance with 8.3.2.3.1.5(E) . [ 55 :11.3.2.2.4.1]

* When fire barrier walls of three sides are used, piping and control systems servingstationary tanks shall be located at the open side of the enclosure created by the barrierwalls to provide access for filling and ventilation. [ 55: 11.3.2.2.4.2]

i. Vertical tanks shall be located at a distance not less than one tank diameter from theenclosing walls. [ 55: 11.3.2.2.4.2(A)]

ii. Where horizontal tanks are used, the distance to any enclosing wall shall be not lessthan one-half the length of the tank. [ 55: 11.3.2.2.4.2(B)]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

270 of 491 1/30/2014 9:30 AM

(D)

Fire department access to outdoor storage areas where bulk systems are installed shall be providedand maintained in accordance with [the adopted fire code]. [ 55: 11.3.2.5]

8.3.2.3.1.7 Underground Tanks.

Underground tanks for the storage of [LH 2 ] shall be in accordance with this subsection. [ 55: 11.4.3]

(A) Construction.

Storage tanks for liquid hydrogen shall be designed and constructed in accordance with Section VIII ofASME Boiler and Pressure Vessel Code and shall be vacuum-jacketed in accordance with8.3.2.3.1.7(A)(1) . [ 55: 11.4.3.1]

(1) Vacuum Jacket Construction.

(a) The vacuum jacket shall be designed and constructed in accordance with Section VIII ofASME Boiler and Pressure Vessel Code and shall be designed to withstand theanticipated loading, including loading from vehicular traffic, where applicable.[ 55: 11.4.3.1.1.1]

(b) Portions of the vacuum jacket installed below grade shall be designed to withstandanticipated soil, hydrostatic, and seismic loading. [ 55: 11.4.3.1.1.2]

(c) The vacuum jacket shall be constructed of stainless steel or other approved corrosion-resistant material. [ 55: 11.4.3.1.1.2(A)]

(d) Corrosion Protection. The vacuum jacket shall be protected by an engineered cathodicprotection system. A cathodic protection system maintenance schedule shall be providedand reconciled by the owner/operator. Exposed components shall be inspected at leasttwice a year. [ 55: 11.4.3.1.1.2(B)]

(B) Location.

Tanks shall be located in accordance with 8.3.2.3.1.7(B)(1) through 8.3.2.3.1.7(B)(4) . [ 55: 11.4.3.2]

(1) Underground storage tanks shall not be located beneath buildings. [ 55: 11.4.3.2.1]

(2) Tanks and associated equipment shall be located with respect to foundations and supports ofother structures such that the loads carried by such structures cannot be transmitted to the tank.[ 55: 11.4.3.2.2]

(3) The distance from any part of the tank to the nearest wall of a basement, pit, cellar, or lot line shallnot be less than 10 ft (3.1 m). [ 55: 11.4.3.2.3]

(4) A minimum distance of 1 ft (0.3 m), shell to shell, shall be maintained between adjacentunderground tanks. [ 55: 11.4.3.2.4]

(C) Depth, Cover, and Fill.

(1) The tank shall be buried such that the top of the vacuum jacket is covered with a minimum of 1 ft(0.3 m) of earth and with concrete a minimum of 4 in. (101 mm) thick placed over the earthencover. [ 55: 11.4.3.3.1]

(2) The concrete shall extend a minimum of 1 ft (0.3 m) horizontally beyond the footprint of the tank inall directions. [ 55: 11.4.3.3.2]

(3) Underground tanks shall be set on foundations constructed in accordance with the [adopted]building code and surrounded with not less than 6 in. (152 mm) of noncorrosive inert material.[ 55: 11.4.3.3.3]

(4) The vertical extension of the vacuum jacket required for service connections shall be allowed toextend above grade. [ 55: 11.4.3.3.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

271 of 491 1/30/2014 9:30 AM

(D) Anchorage and Security.

Tanks and systems shall be secured against accidental dislodgment due to seismic events or flooding.[ 55: 11.4.3.4]

(1)

(E) Venting of Underground Tanks.

Vent pipes for underground storage tanks shall be in accordance with 8.3.1.2.2.2 . [ 55: 11.4.3.5]

(F) Underground LH 2 Piping.

(1) Underground [LH 2 ] piping shall be vacuum-jacketed. [ 55: 11.4.3.6.1]

(2) Unjacketed piping shall not be buried and shall exit the tank annular space above grade.[ 55: 11.4.3.6.2]

(G) Overfill Protection and Prevention Systems.

An approved means or method shall be provided to prevent the overfilling of storage tanks.[ 55: 11.4.3.7]

(H) Vacuum Level Monitoring.

An approved monitoring method shall be provided to indicate vacuum degradation within the vacuumjacket(s). [ 55: 11.4.3.8]

(I) Physical Protection.

Piping and control equipment ancillary to the underground tank located above ground shall be protectedfrom physical damage in accordance with 8.1.7.5 . [ 55: 11.4.3.9]

(J) Tanks Not in Service.

(1)

(2) Corrosion protection shall be maintained in operation. [ 55: 11.4.3.10.1]

Supplemental Information

File Name Description

A_8_3_2_3_1_3_FR_414_SB.docx

Table_8.3.2.3.1.6_A_FR_414.docx

Table_8.3.2.3.1.6_extracted_from_NFPA_55.docx

A.8.3.2.3.1.7_FR_414.docx

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 11:34:07 EDT 2013

Committee Statement

* Areas Subject to Flooding. Stationary containers located in flood hazard areas shall beanchored to prevent flotation during conditions of the design flood as designated by the [adopted]building code. [ 55: 8.13.2.5]

(a) Underground Tanks. Underground tanks in flood hazard areas shall be anchored to preventflotation, collapse, or lateral movement resulting from hydrostatic loads, including the effectsof buoyancy, during conditions of the design flood. [ 55: 8.13.2.5.2]

* Tanks not in service shall be maintained in accordance with 8.3.2.3.1.7(J)(2) . [ 55: 11.4.3.10]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

272 of 491 1/30/2014 9:30 AM

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

273 of 491 1/30/2014 9:30 AM

   

A.8.3.2. 3.1.34.3

Flood hazard areas typically are identified on either (1) the special flood hazard area shown on the flood insurance rate map or (2) the area subject to flooding during the design flood and shown on a jurisdiction’s flood hazard map or otherwise legally designated. [55:A.8.13.2.5]

A.8.3.2. 3.1.5

See A.8.2.2.3.1.3.

A.8.3.2. 3.1.5(E)(1)

See A.8.2.2.3.1.3(A).

A.8.3.2. 3.1.5(F)(1)

The basis of this requirement is to prevent unauthorized personnel or those unfamiliar with gas storage systems from tampering with the equipment. Where LH2 is located in an area open to the general public, a common practice is to fence and lock the storage or use area, with access restricted to supplier and user personnel. When the storage or use is located within the user’s secure area and is not accessible by the general public, a common practice is to fence and lock the storage or use area, with access restricted to supplier and user personnel. When the storage or use is located within the user’s secure area and is not accessible by the general public, it is not always necessary to fence or otherwise secure individual gas storage or use areas. Personnel access patterns may still mandate that the system be fenced, as determined by the supplier and the user. [55:A.11.4.1.4]

A.8.3.2.4.5.13.1.6(A)

Table 8.3.2.3.1.6(A)8.3.2.4.5.1 has been split into two tables, with one representing distances to exposure in inch-pound units of measure and the other representing distance to exposure in SI units of measure. At the present time, mathematical rounding of distances in a manner similar to that used in the formulation of Table 7.3.2.3.1.21(a) and Table 7.3.2.3.1.21(b) have has not been applied, and the use of conventional conversion factors between the tables remains relevant with Table 8.3.2.3.1.6(A)8.3.2.4.5.1 accordingly.

The Occupational Safety and Health Administration (OSHA) established requirements for hydrogen systems reproduced in Figure A. 8.3.2.3.1.6(A)8.3.2.4.5.1 from 29 CFR 1910.103. The tabular distances in Annex I reflect those values published in the July 1, 2006 edition of the CFR. The criteria established in Table I.2(a) and Table I.2(b) are based on the 1969 edition of NFPA 50A, Standard for Gaseous Hydrogen Systems at Consumer Sites, which superseded the 1963 edition. Subsequent editions were adopted in 1973, 1978, 1984, 1989, 1994, and 1999. In 2003, the document was integrated into NFPA 55, Compressed Gases and Cryogenic Fluids Code, because the committee believed that one standard covering storage and use of all compressed gases and cryogenic fluids was needed. NFPA 55 was revised in 2005 as the requirements for compressed gases and cryogenic fluids were broadened. [55:A.11.3.2.2]

Throughout those eight revision cycles, the distances were subject to revision as the technology in the use of hydrogen advanced. However, the distances listed in the OSHA tables remain

Formatted: Tab stops: 0.64", Left

Commented [b1]: SL: Delete? This text does not appear in A.11.4.1.4, NFPA 55. Yes, delete

Commented [b2]: SL: Should be ‘has’? Yes.

based on the 1969 data. It is important to recognize that the OSHA tables represent the current statutory requirements. While the tables might be accurate, it should be recognized that the OSHA tables in some cases lack clarity, and in other cases hazards recognized by the ongoing evolution of the separation tables have not been acknowledged. [55:A.11.3.2.2]

For an example of clarity, consider row 1, “Building or structure,” of the tableTable 11.3.2.2 [in NFPA 55]. The OSHA table refers to buildings by construction types, including wood frame, heavy timber, ordinary, and fire resistive. The current construction types are now designated as Types I through V with variations to address the elements of construction, including the supporting structure as well as the construction of the roof and exterior walls. Although one can guess as to the original intent, there is no clear correlation between the construction types designated in the OSHA tables and the types in either NFPA 220, Standard on Types of Building Construction, or the building code. [55: A.11.3.2.2]

Other examples where hazards are not addressed include the fact that there are no prescribed distances for separation from property lines, public sidewalks, and parked vehicles. A close comparison between the OSHA table and the distance tables found in the 2005 edition of NFPA 55 reveals a number of discrepancies. As the 2010 edition of NFPA 55 was being developed, a collective effort was undertaken by a joint task group established between the NFPA Industrial and Medical Gases Committee and the NFPA Hydrogen Technology Committee. The scope of the Hydrogen Technology Committee’s work was to review and verify the separation distances for exposures integral to the distance tables found in NFPA 55. Research on separation distances funded by the U.S. Department of Energy (DOE) and undertaken by Sandia National Laboratories in 2007 focused on the effects of fire and potential explosion due to an inadvertent release of hydrogen. The initial work had as its focus the use of hydrogen as an alternative vehicle fuel; however, the data produced present the case for separation based on radiant heat flux from hydrogen jet flames and flammability envelopes from unintended releases of hydrogen. The work was based on modeling that was then validated against Sandia National Laboratories and SRI International experiments. [55: A.11.3.2.2]

As the work continued, it became apparent to the group that a risk-informed approach to separation distance could be developed. At that juncture, the committee developed consequence-based tables for separation as well as a set of risk-informed tables. The consequence-based tables present the hazard without regard to probability or frequency. However, there are variables that have not previously been considered in the evolution of the tabular distances. [55: A.11.3.2.2]

On the other hand, the risk-informed tables consider the cumulative frequency of accidents and the distance required to prevent an undesired consequence across a spectrum of varying pressures. [55: A.11.3.2.2]

Additionally, the fundamental requirements of NFPA 55 prescribe a minimum set of engineering controls and construction features. As the work evolved, it became clear that with mitigation methodology, an unintended release could be minimized or eliminated. The developmental work was focused on using a scientific method to obtain separation distances to verify or revise the tabular distances accordingly. [55: A.11.3.2.2]

The OSHA tables are provided to inform the code user of the minimum requirements as they currently exist under 29 CFR and the federal OSHA program. It is incumbent on the installers

and the property owners to recognize the limitations of OSHA based on the precedent requirements established with the use of the 1969 edition of NFPA 50A., Standard for Gaseous Hydrogen at Consumer Sites. The use of alternative approaches to distance as now embodied within the body of the code is subject to approval on a location-by-location basis. The typical AHJ has traditionally been the fire official who might not be the only official that exercises regulatory control for installations of this nature. [55: A.11.3.2.2]

FIGURE A. 8.3.2.3.1.6(A)8.3.2.4.5.1 OSHA Table H-4. Table 8.3.2.3.1.6(A) Item 1. Lot lines. Lot lines (property lines) are those property lines between parcels and should not be construed to be the imaginary property lines that are drawn for the purposes of protecting the exterior walls of multiple buildings placed on the same lot or parcel. Railroad easements that are not accessible to the public other than by raid l travel can be used as a means of spatial separation with the required separation being measured between the hydrogen system and the nearest railroad track. It should be noted that in these cases, the

Formatted: Left

Formatted: Font: Not Bold

Formatted: Font: Italic

addition or relocation of track may result in an encroachment that will necessitate relocation of the hydrogen system at the system user’s expense. [55:A.11.3.2.2] Where the property on the other side of a property line is determined to be unbuildable or unoccupiable due to natural features including, but not limited to, waterways, terrain, wetlands, or similar features encroachment by the hydrogen system on the property line can be acceptable with the approval of the authority having jurisdiction. Should the property that is encroached upon become buildable or otherwise occupiable, the hydrogen system location should be reevaluated by the system user and the AHJ notified of the results. [55:A.11.3.2.2]

A.8.3.2.4.5.13.1.6(BA)(2)

See NFPA 259, Standard Test Method for Potential Heat of Building Materials. Separation distances to exposures in Figure A.8.3.2.4.5.13.1.6(A) should be measured in a direct line of sight or horizontally in the shortest path along the outside of buildings. The 5 ft (1.5 m) distance in Table 8.3.2. 3.1.6(A)4.5.1 facilitates maintenance and enhances ventilation. [55: A.11.3.2.2.2]

A.8.3.2.3.1.6(A)(2)(b)(i)

The separation distances shown in Figure A.8.3.2.3.1.6(A)(2)(b)(i) are required to provide for ventilation in order to avoid creating a confined space. [-] Hydrogen [-] can require greater separation distances based on the type of construction or the related exposure. For example, wall number 3 shown in Figure A.8.3.2.3.1.6(A)(2)(b)(i) could be an exterior building wall [-]. Refer to Table 8.3.2.3.1.6(A) for specific details regarding building walls, wall openings, air intakes, and similar conditions. [55:A.8.13.2.7.2.1]

****INSERT FIGURE HERE****

FIGURE A.8.3.2.3.1.6(A)(2)(b)(i) Bulk Cryogenic System Located in a Courtyard. [55:Figure A.8.13.2.7.2.1]

A.8.3.2.4.5.1(D)(23.1.6(A)(2)(c))

Figure A.8.3.2.3.1.6(A)(2)(c)(i) A.8.3.2.4.5.1(D)(2)(a) and Figure A.8.3.2.3.1.6(A)(2)(c)(ii)A.8.3.2.4.5.1(D)(2)(b) illustrate wall enclosures for a hydrogen storage system. The geometry of the three-sided enclosure should not contain any hydrogen release that would be enough to create a significant hazard. [55: A.11.3.2.2.4.21]

****INSERT FIGURE HERE****

FIGURE A.8.3.2.3.1.6(A)(2)(c)(i)A.8.3.2.4.5.1(D)(2)(a) Schematic of Three-Sided Fire Barrier Wall Enclosure for a Vertical Hydrogen Storage System. [55: Figure A.11.3.2.2.4

.2.1(a)]

****INSERT FIGURE HERE****

Formatted: Font: Bold

Formatted: Font: Not Bold

Formatted: Font: Bold

Formatted: Font: Not Bold

Formatted: Font: (Default) Times New Roman

Formatted: Font: (Default) serif, Bold

FIGURE A.8.3.2.3.1.6(A)(2)(c)(ii)A.8.3.2.4.5.1(D)(2)(b) Schematic of Three-Sided Fire Barrier Wall Enclosure for a Horizontal Hydrogen Storage System. [55: Figure

A.11.3.2.2.4. 21(b)]

Formatted: Font: (Default) serif, Bold

Table 8.3.2.3.1.6(A) Item 1. Lot lines. Lot lines (property lines) are those property lines between parcels and should not be construed to be the imaginary property lines that are drawn for the purposes of protecting the exterior walls of multiple buildings placed on the same lot or parcel. Railroad easements that are not accessible to the public other than by raid travel can be used as a means of spatial separation with the required separation being measured between the hydrogen system and the nearest railroad track. It should be noted that in these cases, the addition or relocation of track may result in an encroachment that will necessitate relocation of the hydrogen system at the system user’s expense. [55:A.11.3.2.2.2] Where the property on the other side of a property line is determine to be unbuildable or unoccupiable due to natural features including, but not limited to, waterways, terrain, wetlands, or similar features encroachment by the hydrogen system on the property line can be acceptable with the approval of the authority having jurisdiction. Should the property that is encroached upon become buildable or otherwise occupiable, the hydrogen system location should be reevaluated by the system user and the AHJ notified of the results. [55:A.11.3.2.2.2]

 

FIGURE A.8.3.2.3.1.6(A)(2)(b)(i) Bulk Cryogenic System Located in a Courtyard. [55:Figure A.8.13.2.7.2.1]

A.8.3.2.3.1.6(A)(2)(c) Figure A.8.3.2.3.1.6(A)(2)(c)(i) and Figure A.8.3.2.3.1.6(A)(2)(c)(ii) illustrate wall enclosures for a hydrogen storage system. The geometry of the three-sided enclosure should not contain any hydrogen release that would be enough to create a significant hazard. [55: A.11.3.2.2.4.2]

Table 8.3.2.4.5.18.3.2.3.1.6(A) Minimum Distance from Bulk Liquefied Hydrogen[LH2] Systems to Exposures

Total Bulk Liquefied Hydrogen[LH2] Storage

39.7 gal to 3500

gal 150 L to 13,250 L

3501 gal to 15,000

gal

13,251 L to 56,781

L

15,001 gal to 75,000

gal

56,782 L to

283,906 L

Type of Exposure ft m ft m ft m Group 1

1.* 11. Public ways, railroads, and property Lot lines

25

7.6

50

15

75

23 32. Air compressor intakes or inlets for (heating air-conditioning or ventilating or air conditioning equipment (HVAC, compressors, other)

75 23 75 23 75 23

23. Wall openings (a) Operable openings in buildings and structures

75 23 75 23 75 23

94. Ignition sources such as open Open flames and welding

50 15 50 15 50 15

Group 2 105. Places of public assembly 75 23 75 23 75 23

Group 3 16. Building or structure (a) Wall(s) adjacent to systemBuildings constructed of noncombustible or limited-combustible materials

(1) Sprinklered building or structure or unsprinklered building or structure having noncombustible contents

5a 1.5 5a 1.5 5a 1.5

(2) Unsprinklered building or structure with combustible contents

(i) Adjacent wall(s) with fire resistance rating less than 3 hours

25 7.6 50 15 75 23

(ii) Adjacent wall(s) with fire

resistance rating of 3 hours or greaterb 5 1.5 5 1.5 5 1.5

(b) Wall(s) adjacent to system constructed of combustible materialsBuildings of combustible construction

(1) Sprinklered building or structure 50 15 50 15 50 15 (2) Unsprinklered building or structure 50 15 75 23 100 30.5 67. Flammable gas storage or systems other than hydrogen above or below ground

50 15 75 23 75 23

58. Between stationary liquefied hydrogen containers

5 1.5 5 1.5 5 1.5

49. All classes of flammable and combustible liquids (above ground and

vent or fill openings if below ground)c

50 15 75 23 100 30.5

710. Hazardous materials storage or systems including Lliquid oxygen storage and other oxidizers, above or below ground

75 23 75 23 75 23

811. Heavy timber, coal, or other slow-burning Ccombustible solids

50 15 75 23 100 30.5

212. Wall openings (b) InoperableUnopenable openings in buildings and structures

25 7.6 50 15 50 15

1213. Inlet to underground sewers 5 1.5 5 1.5 5 1.5 1314. Encroachment by Utilities overhead, including electric power, linesbuilding services or hazardous materials piping systems

(a) Horizontal distance from the vertical plane below the nearest overhead wire of an electric trolley, train, or bus line

50 15 50 15 50 15

(b) Horizontal distance from the vertical plane below the nearest overhead electrical wire

25 7.5 25 7.5 25 7.5

(c) Piping containing other hazardous materials

15 4.6 15 4.6 15 4.6

a Portions of wall less than 10 ft (3.1 m) (measured horizontally) from any part of a system shall have a fire resistance rating of not less than 1 hour.

b Exclusive of windows and doors.

c The separation distances for Class IIIB combustible liquids shall be permitted to be reduced to 15 ft (4.6 m).

[55: Table 11.3.2.2]

A.8.3.2.5.4.1(A)3.1.7(D)(1)(a)

Flood hazard areas typically are identified on either (1) the special flood hazard area shown on the flood insurance rate map or (2) the area subject to flooding during the design flood and shown on a jurisdiction’s flood hazard map or otherwise legally designated. [55:A.8.13.2.5]

A.8.3.2. 3.1.7(J)(1)5.10.1

Users should notify suppliers where a tank is to be left in place but not refilled for an extended period of time. The supplier can inert the tank or otherwise prepare the tank for ultimate removal.

 

First Revision No. 417-NFPA 2-2013 [ Section No. 8.3.3.1.5.1 ]

8.3.3.1.5.1

[LH2] storage systems shall be inspected annually and maintained by a qualified representative of the

equipment owner as required by the material-specific requirements of Chapter 8 . [55:8.14.1.3.1]

(A)

The interval between inspections [-] shall be based on nationally recognized good practices orstandards. [ 55: 8.14.1.3.1.1]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 11:40:29 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

274 of 491 1/30/2014 9:30 AM

First Revision No. 418-NFPA 2-2013 [ Section No. 8.3.3.3 ]

8.3.3.3 Outdoor Use. (Reserved)

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 11:41:25 EDT 2013

Committee Statement

Committee Statement: Update extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

275 of 491 1/30/2014 9:30 AM

First Revision No. 419-NFPA 2-2013 [ Section No. 8.3.4.1 ]

8.3.4.1 Applicability. Bulk LH 2 Systems.

Handling of [LH2] containers shall be in accordance with 8.3.4. [55:8.14.11.4.1]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 11:42:17 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

276 of 491 1/30/2014 9:30 AM

First Revision No. 519-NFPA 2-2013 [ Section No. 8.3.4.4.1 ]

8.3.4.4.1

Pressurized containers shall be closed while being transported. [55:8.14.11.4.4.1]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Sep 09 12:42:18 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

277 of 491 1/30/2014 9:30 AM

First Revision No. 420-NFPA 2-2013 [ Section No. 8.3.4.5.1 ]

8.3.4.5.1

Personnel conducting transfer operations from the bulk transport vehicle shall be trained. [ 52: 9.14.13]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 11:43:09 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

278 of 491 1/30/2014 9:30 AM

First Revision No. 421-NFPA 2-2013 [ Section No. 8.3.4.5.2 ]

8.3.4.5.2

Unloading connections on delivery equipment shall not be positioned closer to any of the exposures citedin Table 8.3.2.4.5.1 Table 8.3.2.3.1.6(A) than the distances given for the storage system. [55:11.5.1]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 11:44:17 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

279 of 491 1/30/2014 9:30 AM

First Revision No. 422-NFPA 2-2013 [ Section No. 8.3.4.5.3 ]

8.3.4.5.3

Prior to connection, a cargo transport vehicle’s wheels shall be rendered immobile. [ 52: 14.4.7]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 11:45:30 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

280 of 491 1/30/2014 9:30 AM

First Revision No. 423-NFPA 2-2013 [ Sections 8.3.4.5.7, 8.3.4.5.8, 8.3.4.5.9 ]

8.3.4.5.7

The cargo transport vehicle’s engine shall be shut off while the transfer hose or piping is being connectedor disconnected. If required for LH2 trailer pumping transfer, the engine pump drive motor shall be

permitted to be started and used during the liquid transfer operations. [ 52: 14.4.8]

8.3.4.5.8

When transfers are made into fueling facility containers, the LH2 shall be transferred at a pressure that

shall not overpressurize the receiving tank. [ 52: 14.4.1]

8.3.4.5.9

The transfer piping shall be equipped with a check valve to prevent backflow from the container beingfilled to the transport vehicle. [ 52: 14.4.2]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 11:46:41 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

281 of 491 1/30/2014 9:30 AM

First Revision No. 39-NFPA 2-2013 [ Section No. 8.3.4.5.10 ]

8.3.4.5.10*

When the tank to be filled or the attendant transfer equipment is located in an area below grade, controlsshall be provided and visible to the operator to prevent overfilling of the tank. The controls shall beprovided in the unloading area and as a minimum shall include a liquid level indicator, pressure indicator,and a full trycock.

When the tank to be filled is directly buried or installed in an inaccessible, sealed, and corrosion-resistantarea that does not create a confined space as defined by applicable occupational safety and healthregulations, the following shall apply:

(1) Controls shall be provided and visible to the operator to prevent overfilling of the tank

(2) The controls shall be provided in the unloading area and as a minimum shall include a liquid levelindicator, pressure indicator, and a fill termination device

Supplemental Information

File Name Description

A_8_3_4_5_10_FR39_2_SB.docx

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 14:34:29 EDT 2013

Committee Statement

CommitteeStatement:

"Below grade" tanks are not defined or addressed by the code. Perhaps this requirement wasmeant for underground tanks.

ResponseMessage:

Public Input No. 112-NFPA 2-2013 [Section No. 8.3.4.5.10]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

282 of 491 1/30/2014 9:30 AM

A.8.3.4.5.10 

Liquid tanks, when buried underground, should meet the following provisions: 

(1)  Liquid hydrogen tanks and associated piping are installed with considerations for physical damage 

prevention, corrosion protection, and proper layout of piping runs. 

(2)  Manually operated valves, controls, PRDs, and instrumentation are located above ground, outdoors, 

and accessible to authorized personnel.  Manually operated valves, controls, and instrumentation for 

filling and routine operations should be readily available to mobile supply equipment at ground level. 

(3)  Remotely operated emergency shutoff valves can be located below grade to allow for product 

isolation.  These valves should be in a corrosion‐resistant area that is accessible from ground level and 

does not create a confined space. 

 

First Revision No. 424-NFPA 2-2013 [ Section No. 8.3.4.5.13 ]

8.3.4.5.13

Sources of ignition shall not be permitted in the unloading area while transfer is in progress. [ 52: 14.4.5]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 11:47:33 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

283 of 491 1/30/2014 9:30 AM

First Revision No. 426-NFPA 2-2013 [ Section No. 8.3.4.6 ]

8.3.4.6 Overfilling Filling Controls .

Controls A pressure gauge and full trycock valve shall be provided to prevent overfilling and shall bevisible from the delivery point to allow the delivery operator to monitor the internal pressure and liquidlevel of stationary containers during filling operations . [55:8.14.11.3.4 5 ]

8.3.4.6.1

When the containers being filled are remote from the delivery point and pressure gauges or full trycockvalves are not visible, redundant gauges and valves shall be installed at the filling connection.[ 55: 8.14.11.3.5.1]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 11:49:01 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

284 of 491 1/30/2014 9:30 AM

First Revision No. 42-NFPA 2-2013 [ New Section after 10.1.1 ]

10.1.1.1

Hydrogen dispensing systems for vehicular fueling shall comply with Chapter 10 .

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 15:48:33 EDT 2013

Committee Statement

CommitteeStatement:

Define the start of the hydrogen dispensing system. Help answer the question: what is coveredby chapter 10 and what is covered in other chapters?

ResponseMessage:

Public Input No. 183-NFPA 2-2013 [New Section after 10.1.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

285 of 491 1/30/2014 9:30 AM

First Revision No. 44-NFPA 2-2013 [ New Section after 10.1.1.2.2 ]

10.1.1.3

Hydrogen generation systems shall be designed in accordance with Chapter 13 .

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 16:06:27 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal - Hydrogen generation is covered in chapter 13. Also hydrogengeneration is related to the bulk hydrogen storage rather than dispensing of fuel (out of scope forchapter 10)

ResponseMessage:

Public Input No. 129-NFPA 2-2013 [New Section after 10.1.1.2.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

286 of 491 1/30/2014 9:30 AM

First Revision No. 45-NFPA 2-2013 [ Section No. 10.2.1.1 ]

10.2.1.1

Dispensing and storage facilities shall be certified as meeting the requirements of this code by qualifiedengineer(s) with expertise and competence in the design, fabrication, and construction of hydrogencontainers, piping systems, site fire protection, gaseous detection, emergency shutdown provisions,isolation, drainage, site spacing, fire protection equipment, operating procedures, worker protection, andother components of the facility. [ 52: 9.2.2]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 16:07:12 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal - Storage is out of scope for chapter 10. Storage iscovered in chapter 7.

Response Message:

Public Input No. 130-NFPA 2-2013 [Section No. 10.2.1.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

287 of 491 1/30/2014 9:30 AM

First Revision No. 46-NFPA 2-2013 [ Section No. 10.2.1.2 ]

10.2.1.2*

A hazard analysis shall be conducted on every hydrogen fueling system installation by a qualifiedengineer(s) with proven expertise in hydrogen fueling systems, installations, and hazard analysistechniques installations . [ 52: 9.2.3]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 16:17:38 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal - Add qualification, editorial change to list of qualificationrequirements.

Response Message:

Public Input No. 131-NFPA 2-2013 [Section No. 10.2.1.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

288 of 491 1/30/2014 9:30 AM

First Revision No. 47-NFPA 2-2013 [ Section No. 10.2.1.3 ]

10.2.1.3

The hazard analysis shall include the following fire protection measures: fire protection and suppressionsystems, detection systems, and ventilation. [ 52: 9.2.3.1]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 16:20:37 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal –

Unnecessary requirements on the hazard analysis also an incomplete list.

Acceptance of previous comment (10.2.1.2) addresses the need for a qualified individual toperform the hazard analysis.

ResponseMessage:

Public Input No. 132-NFPA 2-2013 [Section No. 10.2.1.3]

Public Input No. 225-NFPA 2-2013 [Section No. 10.2.1.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

289 of 491 1/30/2014 9:30 AM

First Revision No. 48-NFPA 2-2013 [ Section No. 10.2.1.4 ]

10.2.1.4

The hazard analysis shall include consideration of potential failures in hoses, nozzles, dispensingequipment, as well as failures for maintenance and service. [ 52: 9.2.3.2]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 16:22:59 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal -

Unnecessary requirements on the hazard analysis also an incomplete list.

Acceptance of previous comment (10.2.1.2) addresses the need for a qualified individual toperform the hazard analysis.

ResponseMessage:

Public Input No. 133-NFPA 2-2013 [Section No. 10.2.1.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

290 of 491 1/30/2014 9:30 AM

First Revision No. 49-NFPA 2-2013 [ Section No. 10.3.1.1 ]

10.3.1.1* System Component Qualifications.

The following systems and system components shall be listed or approved: [ 52: 5.2.1]

(1) Pressure relief devices, including pressure relief valves [ 52: 5.2.1(1)]

(2) Pressure gauges [ 52: 5.2.1(2)]

(3) Pressure regulators [ 52: 5.2.1(3)]

(4) Valves [ 52: 5.2.1(4)]

(5) Hose and hose connections [ 52: 5.2.1(5)]

(6) Vehicle fueling connections (nozzle) [ 52: 5.2.1(6)]

Metal hydride storage [ 52: 5.2.1(7)]

(7) Electrical equipment used with GH2 systems [ 52: 5.2.1(8)]

(8) Gas detection equipment and alarms [ 52: 5.2.1(9)]

Hydrogen generators [ 52: 5.2.1(10)]

(9) Hydrogen dispensers [ 52: 5.2.1(11)]

(10) Pressure switches [ 52: 5.2.1(12)]

(11) Flow meters [ 52: 5.2.1(13)]

(12) Breakaway devices Composite storage (reserved)

(13) Dispenser enclosure

Supplemental Information

File Name Description

FR_49_Annex_Material.docx

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 16:30:44 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal -

-Remove metal hydride and composite storage as these are not current, nor future practices forthe dispensing system. This chapter does not address on-board storage of the vehicles.

-Remove hydrogen generators as these are out of scope for the chapter (covered in chapt 13)

-Add breakaway devices to the list of components

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

291 of 491 1/30/2014 9:30 AM

ResponseMessage:

Public Input No. 135-NFPA 2-2013 [Section No. 10.3.1.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

292 of 491 1/30/2014 9:30 AM

FR 49 Annex Material

A.10.3.1.1

Dispensers may be listed and certified to meet the requirements of ANSI/CSA HGV 4.1.

First Revision No. 50-NFPA 2-2013 [ Section No. 10.3.1.3 ]

10.3.1.3* Design and Construction of Cylinders, Containers, Cylinders, and Tanks.

10.3.1.3.1

Cylinders, Containers containers , cylinders, and tanks shall be fabricated of materials compatible withhydrogen service. [ 52: 5.3.1.2] , installed, and maintained in accordance with Chapters 6 , 7 , and 8 ofthis document.

10.3.1.3.2

Containers, cylinders, and tanks shall be designed for GH 2 service and shall be permanently marked

“Hydrogen” by the manufacturer. [ 52: 5.3.1.3]

10.3.1.3.3

Containers, cylinders, and tanks manufactured prior to the effective date of this code shall be permittedto be used in GH 2 service if designated for GH 2 service by the container manufacturer or if approved

by the AHJ. [ 52: 5.3.1.4]

10.3.1.3.4 Composite Container Cylinders and Tanks. (Reserved)

10.3.1.3.5 ASME Containers, Cylinders, and Tanks.

10.3.1.3.5.1

Welding or brazing for the repair or alteration of an ASME pressure vessel shall comply with thedocuments under which the pressure vessel was fabricated. [ 52: 5.3.4.3]

(A)

Other welding or brazing shall be permitted only on saddle plates, lugs, or brackets attached to thepressure vessel by the pressure vessel manufacturer. [ 52: 5.3.4.3.1]

(B)

The exchange or interchange of pressure vessel appurtenances intended for the same purpose shallnot be considered a repair or alteration. [ 52: 5.3.4.3.2]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 16:47:34 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal - Eliminate special provisions for containers, cylinders andtanks as that equipment is covered in chapter 6 and 7.

ResponseMessage:

Public Input No. 160-NFPA 2-2013 [Section No. 10.3.1.3]

Public Input No. 185-NFPA 2-2013 [Section No. 10.3.1.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

293 of 491 1/30/2014 9:30 AM

First Revision No. 51-NFPA 2-2013 [ Section No. 10.3.1.4.2.1 ]

10.3.1.4.2.1

Pressure Hydrogen dispensing system pressure relief devices shall be in accordance with 7.1.5.5 .[ 52: 9.6.1] set to no greater than 138 percent of the service pressure of the vehicle.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 16:54:54 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal - Reference to section 7.1.5.5 requires that the pressure relief tobe set at the service pressure which is contradictory to the allowance of a 125% overfill, and thecommon practice of setting the pressure relief to 10% above the control pressure.

ResponseMessage:

Public Input No. 166-NFPA 2-2013 [Section No. 10.3.1.4.2.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

294 of 491 1/30/2014 9:30 AM

First Revision No. 52-NFPA 2-2013 [ Section No. 10.3.1.4.2.2 ]

10.3.1.4.2.2

Pressure relief devices shall be so arranged that they discharge in accordance with Section 6.16 and7.1.5.5.5 . [ 52: 9.6.1.1]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 16:55:41 EDT 2013

Committee Statement

Committee Statement: Fueling Working Group Proposal - Redundant with 10.3.1.4.2.1.

Response Message:

Public Input No. 167-NFPA 2-2013 [Section No. 10.3.1.4.2.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

295 of 491 1/30/2014 9:30 AM

First Revision No. 53-NFPA 2-2013 [ New Section after 10.3.1.4.2.4 ]

10.3.1.4.2.4*

Pressure relief devices installed on hydrogen dispensers shall exceed the full flow capacity of thedispenser supply.

Supplemental Information

File Name Description

FR_53_Annex_Material.docx

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 17:03:08 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal - Pressure relief devices must be sized for the flow of thedispenser since there is not a specific storage volume which they are protecting.

ResponseMessage:

Public Input No. 163-NFPA 2-2013 [New Section after 10.3.1.4.2.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

296 of 491 1/30/2014 9:30 AM

  

FR   53 Annex Material  

A.10.3.1.4.2.X The full flow capacity of the dispenser is intended to represent the maximum flow rate of gas possible. This determination could be made by identifying the smallest flow restriction in the dispenser, then assuring the flow capacity of the relief device exceeds that value.  

First Revision No. 54-NFPA 2-2013 [ New Section after 10.3.1.4.2.4 ]

10.3.1.4.2.5

A relief device is not required on a hydrogen dispenser if there are equivalent means of protecting foroverpressure upstream of the dispenser.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 17:04:47 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal - Overpressure protection is feasible without the use of apressure relief device, in some installations this overpressure may be preferable due toconstraints or other safety concerns from venting hydrogen.

ResponseMessage:

Public Input No. 165-NFPA 2-2013 [New Section after 10.3.1.4.2.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

297 of 491 1/30/2014 9:30 AM

First Revision No. 55-NFPA 2-2013 [ Section No. 10.3.1.5.2 ]

10.3.1.5.2

A gauge shall have an opening not to exceed 0.055 in. (1.4 mm) (No. 54 drill size) at the inletconnection. [ 52: 5.6.2]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 17:05:52 EDT 2013

Committee Statement

Committee Statement: Editorial, clarification of the intent of the paragraph.

What is the diameter requirement based on? Why is it specific to pressure gauges?

Response Message:

Public Input No. 189-NFPA 2-2013 [Section No. 10.3.1.5.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

298 of 491 1/30/2014 9:30 AM

First Revision No. 56-NFPA 2-2013 [ New Section after 10.3.1.5.3 ]

10.3.1.5.3

Pressure gauges shall be constructed such that the gauge will protect personnel under overpressureconditions (e.g., blow-out back or secondary containment and release).

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 17:12:45 EDT 2013

Committee Statement

CommitteeStatement:

Add requirement to protect personnel by use of commonly practiced engineering hazardcontrols.

Response Message:

Public Input No. 190-NFPA 2-2013 [New Section after 10.3.1.5.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

299 of 491 1/30/2014 9:30 AM

First Revision No. 133-NFPA 2-2013 [ Section No. 10.3.1.5.3 ]

10.3.1.5.2 Installation of Pressure Gauges on Dispensing Systems.

Gauges or other suitable readout devices shall be installed to indicate compression discharge pressure,storage pressure, and dispenser discharge pressure. [ 52: 9.8] dispenser discharge pressure.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 07 10:29:40 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal - Unless compressor is installed in the dispenser then thecompressor discharge and storage pressure is not necessary for the dispenser (may benecessary for dispenser performance but not safety).

ResponseMessage:

Public Input No. 168-NFPA 2-2013 [Section No. 10.3.1.5.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

300 of 491 1/30/2014 9:30 AM

First Revision No. 57-NFPA 2-2013 [ Section No. 10.3.1.6.3.1 ]

10.3.1.6.3.1

Regulators Components shall be designed, installed, or protected so that their operation is not affectedby freezing rain, sleet, snow, ice, mud, insects, or debris. [ 52: 9.7.1]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 17:15:35 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal - Add text to general section however this should be evaluatedagainst previous recommendations for environmental conditions. Perhaps a general section isrequired for the "Installation and Testing" Section. Regardless all component, not just regulatorsshould be similarly designed, installed or protected.

ResponseMessage:

Public Input No. 169-NFPA 2-2013 [Section No. 10.3.1.6.3.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

301 of 491 1/30/2014 9:30 AM

First Revision No. 58-NFPA 2-2013 [ Section No. 10.3.1.6.4 ]

10.3.1.6.4

The regulator protection in 10.3.1.6.3.1 shall be permitted to be integral with the regulator. [ 52: 9.7.2]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 17:16:57 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal – This is a design requirement not a installation or testingrequirement.

Response Message:

Public Input No. 170-NFPA 2-2013 [Section No. 10.3.1.6.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

302 of 491 1/30/2014 9:30 AM

First Revision No. 59-NFPA 2-2013 [ Section No. 10.3.1.7.1.1 ]

10.3.1.7.1.1

Pipe Wetted piping , tubing, fittings, gaskets, and packing material shall be compatible with thefuel hydrogen under service conditions. [ 52: 5.8.1.1]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 17:18:48 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal – Make change and global public input for change from“fuel” to “hydrogen”.

Response Message:

Public Input No. 171-NFPA 2-2013 [Section No. 10.3.1.7.1.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

303 of 491 1/30/2014 9:30 AM

First Revision No. 60-NFPA 2-2013 [ Section No. 10.3.1.7.6.2 ]

10.3.1.7.6.2

Exterior piping shall be either buried, laid in a trench, or installed above ground and shall be supportedand protected against mechanical damage. [ 52: 9.9.1.1] protected against mechanical damage.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 17:22:58 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal – Eliminate additional text as it doesn’t add anyrequirements, could only cause confusion of required approach.

ResponseMessage:

Public Input No. 172-NFPA 2-2013 [Section No. 10.3.1.7.6.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

304 of 491 1/30/2014 9:30 AM

First Revision No. 61-NFPA 2-2013 [ Section No. 10.3.1.7.6.3 ]

10.3.1.7.6.3

Manifolds connecting fuel containers shall be fabricated to minimize vibration and shall be installed in aprotected location or shielded to prevent damage from unsecured objects. [ 52: 9.9.1.4.1.1]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 17:23:52 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal – There are no manifold fuel containers in the current dispenserunder consideration, see previous comments on speculative code concepts – only causesopportunity for misinterpretation.

ResponseMessage:

Public Input No. 173-NFPA 2-2013 [Section No. 10.3.1.7.6.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

305 of 491 1/30/2014 9:30 AM

First Revision No. 62-NFPA 2-2013 [ Section No. 10.3.1.7.6.6 ]

10.3.1.7.6.5*

Threaded pipe and fittings Mechanical connections in hydrogen piping shall not be used underground.[ 52: 9.9.1.4.1.4] buried.

Supplemental Information

File Name Description

FR_62_Annex_Material.docx

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 17:27:40 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal – Mechanical connections shall not used for buried piping.Add definition to Section 3 for mechanical connection.

ResponseMessage:

Public Input No. 174-NFPA 2-2013 [Section No. 10.3.1.7.6.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

306 of 491 1/30/2014 9:30 AM

  

FR  62 Annex Material  A.10.3.1.7.6.8 Mechanical joints can be disassembled and include flanged, threaded, or equivalent joints, including crimped connections. Welded joints do not need to be in an accessible location.  

First Revision No. 63-NFPA 2-2013 [ Sections 10.3.1.7.6.8, 10.3.1.7.6.9 ]

10.3.1.7.6.7

Joints or connections shall be located in an accessible location. [ 52: 9.9.1.4.4] Mechanical joints shall belocated in an accessible location.

10.3.1.7.6.8

The number of joints shall be minimized and placed in a location considering personnel safety.[ 52: 9.9.1.4.5]

Supplemental Information

File Name Description

A.10.3.1.7.6.8_FR_63_.docx

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 17:43:39 EDT 2013

Committee Statement

CommitteeStatement:

Welded joints offer a high degree of reliability and are acceptable in in acessible areas. Weldedjoints do not need regular inspection and are not considered to be high propbability leak points andshould be allowed inside locations that are not acessible. In addition, the quantity of joints shouldbe minimized but this restriction shuld not be placed on welded joints.

ResponseMessage:

Public Input No. 103-NFPA 2-2013 [Sections 10.3.1.7.6.8, 10.3.1.7.6.9]

Public Input No. 176-NFPA 2-2013 [Sections 10.3.1.7.6.8, 10.3.1.7.6.9]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

307 of 491 1/30/2014 9:30 AM

  

 A.10.3.1.7.6.8 Mechanical joints can be disassembled and include flanged, threaded, or equivalent joints, including crimped connections. Welded joints do not need to be in an accessible location.  

First Revision No. 64-NFPA 2-2013 [ Section No. 10.3.1.8.5 ]

10.3.1.8.5

The use of hose in an installation a hydrogen dispensing system shall be limited to the following:[ 52: 9.9.3] to vehicle fueling hose.

Vehicle fueling hose [ 52: 9.9.3(1)]

Inlet connection to compression equipment [ 52: 9.9.3(2)]

Section of hose not exceeding 36 in. (910 mm) in length in a pipeline to provide flexibility wherenecessary. [ 52: 9.9.3(3)]

10.3.1.8.5.1

Where necessary to provide flexibility in hydrogen piping, sections of hose not exceeding 36 in. (910mm) in length shall be permitted.

10.3.1.8.5.2

Each section shall be installed so installed that it is protected against mechanical damage and is readilyvisible accessible for inspection. [ 52: 9.9.3.1]

10.3.1.8.5.3

The individual component and manufacturer’s identification shall be retained in each section andthroughout the system. [ 52: 9.9.3.2]

10.3.1.8.5.4

The hose shall be approved or listed for hydrogen service. [ 52: 9.9.4]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 05 17:55:30 EDT 2013

Committee Statement

CommitteeStatement:

Bullet #3 should be eliminated for safety reasons. Bullet #2 may be applicable for compressionequipment located at the bulk storage but that is not in the scope of chapter 10, compressionequipment in the dispenser is not a common practice. Leave only bullet #1 which is the commonapplication of hoses and the integrity of the hose is checked prior to each fill to ensure safety inbullet #1.

ResponseMessage:

Public Input No. 178-NFPA 2-2013 [Section No. 10.3.1.8.5.1]

Public Input No. 179-NFPA 2-2013 [Section No. 10.3.1.8.5.2]

Public Input No. 191-NFPA 2-2013 [Section No. 10.3.1.8.5]

Public Input No. 192-NFPA 2-2013 [Section No. 10.3.1.8.5.3]

Public Input No. 226-NFPA 2-2013 [Section No. 10.3.1.8.5 [Excluding any Sub-Sections]]

Public Input No. 227-NFPA 2-2013 [Section No. 10.3.1.8.5.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

308 of 491 1/30/2014 9:30 AM

First Revision No. 65-NFPA 2-2013 [ Section No. 10.3.1.9.1 ]

10.3.1.9.1

Valves, valve packing, and gaskets shall be designed or selected for the fuel over the full range ofpressures and temperatures to which they can be subjected under any operating conditions. [ 52: 5.9.1] All system components shall be listed or approved for the hydrogen service pressures,internal and external temperatures, and operating environment of the hydrogen dispensing system.

10.3.1.9.1.1

Shutoff valves shall have a rated service pressure not less than the rated service pressure of the entiresystem and shall be designed with a minimum safety factor of 3. [ 52: 5.9.1.1]

10.3.1.9.1.2

Leakage shall not occur when tested in accordance with the requirements of ANSI/ASME B31.3 B31.12 ,Process Piping Hydrogen Piping and Pipelines , either pneumatically or hydrostatically. The test pressureshall be not less than 110 percent of the rated service pressure when tested pneumatically, using an inertgas as the medium, nor less than 150 percent of the rated service pressure when tested hydrostatically.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 08:04:13 EDT 2013

Committee Statement

CommitteeStatement:

The entire dispenser system should be listed or approved, not just specific components. Thecurrent standard is a patchwork of “listed or approved” statements. If the intent is to be explicit inthe general section and redundant in component section, then the committee should place the‘listed or approved’ requirement in each component section rather than specific ones.

ResponseMessage:

Public Input No. 180-NFPA 2-2013 [Section No. 10.3.1.9.1]

Public Input No. 193-NFPA 2-2013 [Section No. 10.3.1.9.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

309 of 491 1/30/2014 9:30 AM

First Revision No. 66-NFPA 2-2013 [ Section No. 10.3.1.9.3 ]

10.3.1.9.3

The manufacturer shall stamp or otherwise permanently mark the valve body to indicate the serviceratings.

10.3.1.9.3.1

Container valves incorporating integral pressure relief devices complying with 7.1.5.5 shall not requireadditional marking. [ 52: 5.9.3]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 08:21:27 EDT 2013

Committee Statement

CommitteeStatement:

Permanent marking is part of the listing requirement. We need to transition this language fromassuming non-listed components to assuming listed components and ensure that any languagethat would otherwise overlap (such as this statement) overlaps in such a way as to prevent conflictbetween the code and the listing standard.

ResponseMessage:

Public Input No. 194-NFPA 2-2013 [Section No. 10.3.1.9.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

310 of 491 1/30/2014 9:30 AM

First Revision No. 67-NFPA 2-2013 [ Section No. 10.3.1.10.1 ]

10.3.1.10.1*

Piping, tubing and hose, and hose assemblies Hydrogen dispensing systems shall be leak tested afterassembly final installation to prove them free from leaks at a pressure equal to at least the normal servicepressure of that portion of the system. [ 52: 9.10.1]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 08:27:43 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal - If the intent of this section was to require a leak test afterinstallation rather than after assembly (in the field vs. at the factory) then the text should reflectthat fact.

ResponseMessage:

Public Input No. 137-NFPA 2-2013 [Section No. 10.3.1.10.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

311 of 491 1/30/2014 9:30 AM

First Revision No. 68-NFPA 2-2013 [ New Section after 10.3.1.10.3 ]

10.3.1.10.3.1

This leak test shall be conducted following any maintenance that involves breaking a connection or, at aminimum, annually.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 08:38:46 EDT 2013

Committee Statement

Committee Statement: Fueling Working Group Proposal - Add periodic leak test as a system requirement.

Response Message:

Public Input No. 136-NFPA 2-2013 [New Section after 10.3.1.10.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

312 of 491 1/30/2014 9:30 AM

First Revision No. 69-NFPA 2-2013 [ Section No. 10.3.1.10.5 [Excluding any

Sub-Sections] ]

Pressure relief valves shall be tested at least every 3 5 years. [ 52: 9.10.2]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 08:43:11 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal - The current text contradicts itself, requiring 3 years in10.3.1.10.5 then referencing CGA S1.3 and stating 5 years. The testing requirement should be nodifferent than current industrial gas industry practice, 5 year interval.

ResponseMessage:

Public Input No. 138-NFPA 2-2013 [Section No. 10.3.1.10.5 [Excluding any Sub-Sections]]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

313 of 491 1/30/2014 9:30 AM

First Revision No. 70-NFPA 2-2013 [ Section No. 10.3.1.10.6 ]

10.3.1.10.6

At fueling stations, gas used for calibration and testing shall be vented to a vent pipe in accordance withSection 6.16 . [ 52: 9.9.5]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 08:47:16 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal - Is this guidance for maintenance personnel so that they don'tshortcut the existing infrastructure and vent test gas by breaking fittings or other unconventionalmeans? If so then change the language, otherwise do we need this if we already have the guidanceof chapter 6. If test gas is inert does it need to go to vent stack? If vent gas is flammable isn't itrequired to go to a vent stack per chapter 6?

ResponseMessage:

Public Input No. 139-NFPA 2-2013 [Section No. 10.3.1.10.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

314 of 491 1/30/2014 9:30 AM

First Revision No. 71-NFPA 2-2013 [ Section No. 10.3.1.11.1 ]

10.3.1.11.1

Containers and their appurtenances, piping systems, compression equipment, controls, and detectiondevices Hydrogen dispensing systems shall be maintained in operating condition and according tomanufacturer’s instructions. [ 52: 9.16.1] accordance with the manufacturers' instructions.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 08:51:00 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal - Remove other equipment terms, use the general term forthe dispensing system as used throughout the chapter.

ResponseMessage:

Public Input No. 140-NFPA 2-2013 [Section No. 10.3.1.11.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

315 of 491 1/30/2014 9:30 AM

First Revision No. 72-NFPA 2-2013 [ Section No. 10.3.1.11.2 ]

10.3.1.11.2 Hose Assemblies Assembly Maintenance .

10.3.1.11.2.1

Hoses, nozzles, and breakaways shall be examined according to the manufacturers’ recommendations orat least monthly and shall be maintained in accordance with the manufacturers’ instructions.[ 52: 9.16.2.1]

10.3.1.11.2.2

Hose shall be tested for leaks per according to the manufacturer’s requirements. , and any unsafel L eakage or surface cracks shall be reason for rejection and replacement. [ 52: 9.16.2.2]

10.3.1.11.2.3

Testing shall be carried out using an inert gas as the test medium or where this is not practical, withhydrogen using suitable precautions. . [ 52: 9.16.2.3]

(A)

Where this is not possible, the hose assembly shall be completely isolated from the system and testedwith the flammable gas normally within the system, or with air and then purged with an inert gas.[ 52: 9.16.2.3.1]

(B)

In the case of hydrogen, testing shall be carried out with helium or a helium inert gas blend (10 percentby volume or greater) as the test gas, or if this is not possible, with hydrogen using suitable precautions.[ 52: 9.16.2.3.2]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 08:59:35 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal - Need to distinguish from previous sectoins on Design andInstallation.

Perhaps a good global guidance for committee - the Design, Installation and Maintenance sectionsthat are specific to components should contain those words (either Design, Installation orMaintenance) in their respective titles (make searching easier and avoids confusion on intendedportion of system life to which the requirement pertains.

ResponseMessage:

Public Input No. 141-NFPA 2-2013 [Section No. 10.3.1.11.2]

Public Input No. 142-NFPA 2-2013 [Section No. 10.3.1.11.2.2]

Public Input No. 229-NFPA 2-2013 [Section No. 10.3.1.11.2.3]

Public Input No. 228-NFPA 2-2013 [Section No. 10.3.1.11.2.3(A)]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

316 of 491 1/30/2014 9:30 AM

First Revision No. 73-NFPA 2-2013 [ Sections 10.3.1.11.3, 10.3.1.11.4, 10.3.1.11.5 ]

10.3.1.11.3 Maintenance, Modification, and Calibration Documentation.

The station operator shall maintain a maintenance log in good condition and accessible to theinspector. [ 52: 9.16.2.4]

10.3.1.11.3.1

The hydrogen dispensing system operator (station owner, contractor, station operator, etc.) shalldevelop a management of change (MOC) system to ensure system modifications are documented andany necessary revisions to system documents are identified and marked completed (system documentscan include hazard analysis, site plans, emergency procedures, first responder pre-plans, etc.)

10.3.1.11.3.2

Each hydrogen dispensing system shall indicate the last maintenance date and date of the nextscheduled maintenance.

10.3.1.11.3.3

If testing is required, each hydrogen dispensing system shall indicate the last test date and the date ofthe next scheduled test.

10.3.1.11.3.4

If calibration is required, each hydrogen dispensing system shall indicate expiration date of the currentcalibration.

(A)

The calibration indicator shall be readily visible to the hydrogen dispensing system user and shall notobscure other display functions of the dispenser.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 09:10:49 EDT 2013

Committee Statement

CommitteeStatement:

Remove the “log” and “sticker” requirements are buried in the Hose Assembly (10.3.1.11) and FireProtection (10.3.1.19) sections.

Create a new section in the general section, applicable to all dispenser with a consistentdocumentation requirement. Include management of change rather than ‘simple log’ documentation.Include the indication of maintenance and calibration. Separate maintenance from calibration ascalibration is not required for all dispensers. Consider requirement of calibration for dispensing tothe public section.

Combined general requirements in this section. Also addresses PI #199.

ResponseMessage:

Public Input No. 196-NFPA 2-2013 [Sections 10.3.1.11.3, 10.3.1.11.4, 10.3.1.11.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

317 of 491 1/30/2014 9:30 AM

First Revision No. 74-NFPA 2-2013 [ Section No. 10.3.1.11.6 ]

10.3.1.11.4*

Controllers on fuel stations hydrogen dispensing systems shall be designed to verify the integrity of thefuel hose, breakaway, nozzle, and receptacle by pressurizing these components to at least the vehicleback pressure and checking monitoring pressure drop decay over a period of at least 5 seconds prior tothe start of fueling. [ 52: 9.16.2.6]

Supplemental Information

File Name Description

FR_74_Annex_Material.docx

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 09:13:55 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal - Change term to pressure decay to more appropriatelydescribe the measurement.

ResponseMessage:

Public Input No. 143-NFPA 2-2013 [Section No. 10.3.1.11.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

318 of 491 1/30/2014 9:30 AM

FR 74 Annex Material

A.10.3.1.11.6 In addition to the initial integrity check at the beginning of the fueling event, additional integrity checks have been effective at finding leaks that develop during the fueling process. NFPA 2 – 2011 required this integrity check at 3000 psig increments. Specifying the pressures at which these tests occur will result in greater standardization and consistency of the fueling process. The leak tests should occur within 5% of the specified pressure values. For example, the 85% fill point check may occur between 80% and 90% of the service pressure

 

First Revision No. 76-NFPA 2-2013 [ Section No. 10.3.1.11.7 ]

10.3.1.11.5

The integrity check shall then be repeated at 3000 psi (20.7 MPa) increments up to the final fill pressure.[ 52: 9.16.2.7] Hydrogen dispensing integrity checks shall be as follows :

(1) Hydrogen fueling events of 350 bar shall have an integrity check repeated at 85 percent of thedispenser nozzle service pressure by stopping flow and checking the pressure decay over a periodof 5 seconds.

(2) Hydrogen fueling events of 700 bar shall have an integrity check repeated at 45 percent and 85percent of the dispenser nozzle service pressure by stopping flow and checking the pressure decayover a period of at least 5 seconds.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 09:25:40 EDT 2013

Committee Statement

Committee Statement: See PI#212 for substantiation.

Response Message:

Public Input No. 239-NFPA 2-2013 [Section No. 10.3.1.11.7]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

319 of 491 1/30/2014 9:30 AM

First Revision No. 77-NFPA 2-2013 [ Section No. 10.3.1.11.8 ]

10.3.1.11.8

Pressure relief valves shall be maintained in operating condition. [ 52: 9.16.3]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 09:52:41 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal - Covered by general requirement that all equipment bemaintained in operating condition (section 10.3.1.11.1)

ResponseMessage:

Public Input No. 144-NFPA 2-2013 [Section No. 10.3.1.11.8]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

320 of 491 1/30/2014 9:30 AM

First Revision No. 79-NFPA 2-2013 [ Section No. 10.3.1.12 ]

10.3.1.12 Equipment Security and Vehicle Protection.

Compression, processing, generation, storage, and Hydrogen dispensing equipment systems shall beprotected to prevent damage from vehicles and to minimize physical damage and vandalism.[ 52: 9.2.5.2]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 09:55:25 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal - Replace list with comprehensive equipment definition. Moveto general equipment section rather than specific component requirement.

ResponseMessage:

Public Input No. 145-NFPA 2-2013 [Section No. 10.3.1.12]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

321 of 491 1/30/2014 9:30 AM

First Revision No. 80-NFPA 2-2013 [ Section No. 10.3.1.13 ]

10.3.1.13 Compression and Gas Processing Systems.

Engine-driven compressor installations shall conform, where applicable, to NFPA 37 , Standard for theInstallation and Use of Stationary Combustion Engines and Gas Turbines . [ 52: 9.2.11]

10.3.1.13.1

Where hydrogen is used as a fuel in an engine-driven compressor installation, the engine shall complywith 10.3.2 . For purposes of electrical classification, the engine shall be considered a source ofignition. [ 52: 9.2.12]

10.3.1.13.2

Gas processing equipment including compression and hydrogen generation equipment, in processeswhere liquid is present, shall have means to prevent liquid carryover to the storage system. [ 52: 9.2.13]

10.3.1.13.3

A self-closing valve shall be provided on the inlet of the compressor that shuts off the gas supply to thecompressor when one of the following occurs: [ 52: 9.11.9]

An emergency shutdown device is activated. [ 52: 9.11.9(1)]

A power failure occurs. [ 52: 9.11.9(2)]

The power to the compressor is switched to the OFF position. [ 52: 9.11.9(3)]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 09:56:59 EDT 2013

Committee Statement

CommitteeStatement:

If the scope of this chapter is dispensers (starting at the source valve from the bulk storage) thenis this sectoin relevant?

One might argue that some installer might try to put a compressor in the dispenser. True, but if thatisn't practiced today. Are we going to speculatively write code? If speculating, on this code isprudent are there other 'near term' gaseous dispenser technologies that we should considerincluding?

If not, then we should delete this whole section which is my recommendation.

ResponseMessage:

Public Input No. 186-NFPA 2-2013 [Section No. 10.3.1.13]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

322 of 491 1/30/2014 9:30 AM

First Revision No. 81-NFPA 2-2013 [ Section No. 10.3.1.14.1 ]

10.3.1.13.1

A vehicle hydrogen container shall not be charged in excess of the service pressure that is stamped onthe container and displayed on a label near the filling connection when compensated for differences intemperature from 59°F (15°C). [ 52: 9.14.1]

10.3.1.13.1.1

A vehicle fuel hydrogen container shall not be subjected to pressure in excess of 125 percent of itsmarked service pressure.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 09:59:54 EDT 2013

Committee Statement

CommitteeStatement:

The proposed text combines section 10.3.14.1 and 10.3.14.3 which both limit the temperaturecompensated pressure to the service pressure labeled on the tank. Having both sections wasredundant and confusing.

This public input is supported by the following organization:

The Fuel Cell and Hydrogen Energy Association (FCHEA) is the trade association for the fuel celland hydrogen energy industry, and is dedicated to the commercialization of fuel cells and hydrogenenergy technologies. FCHEA represents the full global supply chain, including universities,government laboratories and agencies, trade associations, fuel cell materials, components andsystems manufacturers, hydrogen producers and fuel distributors, utilities and other end users.

ResponseMessage:

Public Input No. 217-NFPA 2-2013 [Section No. 10.3.1.14.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

323 of 491 1/30/2014 9:30 AM

First Revision No. 82-NFPA 2-2013 [ Section No. 10.3.1.14.2 ]

10.3.1.14.2

System design shall take into account the possibility of pressure and/or temperature communicationbetween dispenser and vehicle, although this communication is not required. [ 52: 9.14.1.2]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 10:07:32 EDT 2013

Committee Statement

Committee Statement: Fueling Working Group Proposal - Delete section, requirement is vague and unclear.

Response Message:

Public Input No. 149-NFPA 2-2013 [Section No. 10.3.1.14.2]

Public Input No. 214-NFPA 2-2013 [Section No. 10.3.1.14.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

324 of 491 1/30/2014 9:30 AM

First Revision No. 83-NFPA 2-2013 [ Section No. 10.3.1.14.3 ]

10.3.1.14.3

A fuel supply container shall not have a settled pressure above the service pressure that is stamped onthe container and displayed on a label near the filling connection, corrected for the ambient temperatureat the time of filling. [ 52: 9.14.2]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 10:10:59 EDT 2013

Committee Statement

CommitteeStatement:

The proposed text combines section 10.3.14.1 and 10.3.14.3 which both limit the temperaturecompensated pressure to the service pressure labeled on the tank. Having both sections wasredundant and confusing.

This public input is supported by the following organization:

The Fuel Cell and Hydrogen Energy Association (FCHEA) is the trade association for the fuel celland hydrogen energy industry, and is dedicated to the commercialization of fuel cells and hydrogenenergy technologies. FCHEA represents the full global supply chain, including universities,government laboratories and agencies, trade associations, fuel cell materials, components andsystems manufacturers, hydrogen producers and fuel distributors, utilities and other end users.

ResponseMessage:

Public Input No. 218-NFPA 2-2013 [Section No. 10.3.1.14.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

325 of 491 1/30/2014 9:30 AM

First Revision No. 84-NFPA 2-2013 [ Section No. 10.3.1.14.11 ]

10.3.1.13.9

A warning sign with the words “STOP MOTOR, NO SMOKING, NO CELL PHONES , FLAMMABLE GAS,HYDROGEN HAS NO ODOR ” shall be posted at dispensing station and compressor areas eachdispensor . [ 52: 9.14.12]

10.3.1.13.9.1

The lettering on the sign shall be large enough to be visible and legible from each point of transfer.

If the hydrogen is not odorized, the wording “HYDROGEN GAS DOES NOT HAVE A DISTINCTIVEODOR” shall be added to the warning sign. [ 52: 9.14.12.1]

10.3.1.14.11.2

The location of signs shall be determined by local conditions. [ 52: 9.14.12.2]

10.3.1.14.11.3

The lettering on the sign shall be large enough to be visible and legible from each point of transfer.[ 52: 9.14.12.3]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 10:11:45 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal - Combine phrases into one required sign. There isn't anyodorized hysrogen, nor are there near-term plans for odorants.

ResponseMessage:

Public Input No. 147-NFPA 2-2013 [Section No. 10.3.1.14.11]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

326 of 491 1/30/2014 9:30 AM

First Revision No. 85-NFPA 2-2013 [ Section No. 10.3.1.14.12 ]

10.3.1.13.10

Control Pneumatic gas supply systems for control devices shall be installed so that internal or externalicing does not cause vehicle or fueling station malfunction. [ 52: 9.2.7] designed to prevent internal andexternal freezing. Fuel gas controls shall be installed to prevent external freezing.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 10:23:28 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal - Reword the paragraph to represent the icing concernsrelative to standards of practice.

ResponseMessage:

Public Input No. 148-NFPA 2-2013 [Section No. 10.3.1.14.12]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

327 of 491 1/30/2014 9:30 AM

First Revision No. 86-NFPA 2-2013 [ New Section after 10.3.1.14.13.1 ]

10.3.1.13.12

A means shall be provided to bring the system to a safe condition in the event of failure of the hydrogendispensing system logic controller.

10.3.1.13.12.1

The means of protection shall stop the dispensing of hydrogen if the dispenser pressure or dispenserfuel temperature deviate from the operating parameters.

10.3.1.13.13

The dispenser gas temperature shall be measured as close to the hose breakaway as possible andshall not be less than −40°F (−40°C).

10.3.1.13.14

A dispenser shall only dispense hydrogen when the ambient temperature is between −40°F (−40°C) and122°F (50°C).

10.3.1.13.15*

The flowrate of a hydrogen dispenser for light duty vehicles shall not exceed 0.1323 lb (60 g) ofhydrogen per second.

10.3.1.13.15.1

The limit of 0.1323 lb (60 g) per second does not include transient excursions due to valve actuation.

10.3.1.13.16

The dispenser shall not exceed the service pressure, temperature, or maximum fuel density of thecontainer over the range of dispenser operating conditions.

Supplemental Information

File Name Description

A_10_3_1_14_AA_FR_86_SB.docx

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 10:27:50 EDT 2013

Committee Statement

CommitteeStatement:

This will increase the safety and reliability of the dispensing process by providing a “watchdog”controller to monitor the function of the primary controller.

ResponseMessage:

Public Input No. 215-NFPA 2-2013 [New Section after 10.3.1.14.13.1]

Public Input No. 219-NFPA 2-2013 [New Section after 10.3.1.14.13.1]

Public Input No. 220-NFPA 2-2013 [New Section after 10.3.1.14.13.1]

Public Input No. 222-NFPA 2-2013 [New Section after 10.3.1.14.13.1]

Public Input No. 230-NFPA 2-2013 [New Section after 10.3.1.14.13.1]

Public Input No. 238-NFPA 2-2013 [New Section after 10.3.1.14.13.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

328 of 491 1/30/2014 9:30 AM

 A.10.3.1.14.AA   The limit of 0.1323 lb (60 g) per second was not intended to include short, transient excursions that occur prior to the start of filling due to opening and closing of valves.  

Commented [b1]: Final section number still to come.  Ok 

First Revision No. 87-NFPA 2-2013 [ Section No. 10.3.1.16.1 [Excluding any

Sub-Sections] ]

Fixed electrical equipment and wiring within areas specified in Table 10.3.1.15.1 shall comply with Table10.3.1.15.1 and shall be installed in accordance with NFPA 70, National Electrical Code . [ 52: 9.12.1]

Table 10.3.1.15.1 Electrical Installations

LocationDivisionor Zone Extent of Classified Area

Area containing compression and ancillaryequipment

2 Up to 15 ft (4.6 m) from equipment

Outdoor dispensing equipment enclosureinterior

1Up to support mechanism or connection to theground

Outdoor dispensing equipment enclosureexterior Outdoor dispenser enclosure -exterior and interior

2 Up to 5 ft (1.5 m) from dispenser

Indoor dispensing equipment dispenserenclosure — exterior and interior

1 2Up to support mechanism or connection to theground 15 ft (4.6 m) from the point of transferin accordance with 10.3.3.2.2.3

Indoor dispensing equipment enclosure —exterior

215 ft (4.6 m) from the point of transfer inaccordance with 10.3.3.2.2.3

Outdoor discharge from relief valves or vents 1 5 ft (1.5 m) from source

Outdoor discharge from relief valves or vents 2 15 ft (4.6 m) from source

Discharge from relief valves within 15degrees of the line of discharge

1 15 ft (4.6 m) from source

Exception: Electrical equipment on internal combustion engines installed in accordance with NFPA 37 ,Standard for the Installation and Use of Stationary Combustion Engines and Gas Turbines .[ 52: 9.12.1]

Supplemental Information

File Name Description

10.3.1.16.1_FR_87_Material.docx

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 11:12:13 EDT 2013

Committee Statement

CommitteeStatement:

The interior of the cabinet should be a Division 2 location by definition since hydrogen wouldnot normally be present and would only occur in the event of a leak.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

329 of 491 1/30/2014 9:30 AM

Public Input No. 18-NFPA 2-2012 [Section No. 10.3.1.16.1 [Excluding any Sub-Sections]]

Public Input No. 150-NFPA 2-2013 [Section No. 10.3.1.16.1]

Public Input No. 236-NFPA 2-2013 [Section No. 10.3.1.16.1 [Excluding any Sub-Sections]]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

330 of 491 1/30/2014 9:30 AM

10.3.1.16.1 Fixed electrical equipment and wiring within areas specified in Table 10.3.1.16.1 shall comply with Table 10.3.1.16.1 and shall be installed in accordance with NFPA 70, National Electrical Code.

Table 10.3.1.16.1 Electrical Installations

Location Division or Zone Extent of Classified Area

Area containing compression and ancillary equipment 2 Up to 15 ft (4.6 m) from equipment

Outdoor dispensing equipment enclosure interior 1 Up to support mechanism or connection to the ground

Outdoor dispensing equipment enclosure exterior Outdoor dispenser enclosure - exterior and interior

2 Up to 5 ft (1.5 m) from dispenser

Indoor dispensing equipment dispenser enclosure — exterior and interior

1 2 Up to support mechanism or connection to the ground 15 ft (4.6m) from the point of transfer in accordance with 10.3.3.2.2.3

Indoor dispensing equipment enclosure — exterior 2 15 ft (4.6 m) from the point of transfer in accordance with 10.3.3.2.2.3

Outdoor discharge from relief valves or vents 1 5 ft (1.5 m) from source

Outdoor discharge from relief valves or vents 2 15 ft (4.6 m) from source

Discharge from relief valves within 15 degrees of the line of discharge

1 15 ft (4.6 m) from source

First Revision No. 88-NFPA 2-2013 [ Section No. 10.3.1.16.2.1 ]

10.3.1.15.2.1

Modifications shall be signed off approved by a qualified engineer with expertise in fire safety andgaseous fuels. [ 52: 9.12.2.1]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 11:25:36 EDT 2013

Committee Statement

Committee Statement: Fueling Working Group Proposal - Change term to more commonly used term.

Response Message:

Public Input No. 151-NFPA 2-2013 [Section No. 10.3.1.16.2.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

331 of 491 1/30/2014 9:30 AM

First Revision No. 89-NFPA 2-2013 [ Section No. 10.3.1.17.3 ]

10.3.1.16.3

A vehicle fueling pad shall be provided in the area where vehicles are to be refueled. [ 52: 9.13.3] Vehiclefueling areas shall be constructed with a length and width to accommodate the types of vehicles to befueled.

10.3.1.21.3.1

The pad shall be constructed with a length and width to accommodate the types of vehicles to befueled . [ 52: 9.13.3.1]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 11:30:28 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal - The term "fueling pad" is poorly defined; the word "area" shouldbe used in this "general" section for all dispensing applications. A vehicle "pad" should be used inlater chapters which are more specific to the environment of use, eg., outdoor public fueling.

ResponseMessage:

Public Input No. 153-NFPA 2-2013 [Section No. 10.3.1.17.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

332 of 491 1/30/2014 9:30 AM

First Revision No. 90-NFPA 2-2013 [ Section No. 10.3.1.17.4 ]

10.3.2.3.1.3*

The vehicle fueling pad shall be of concrete or a material having a resistivity not exceeding 1 megohmas determined by an approved method unless the vehicle is grounded by other means, such as agrounding cable.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 12:31:41 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal - Move this requirement to the outdoor public fueling section asthis requirement is inappropriate for many other fueling applications. Keep the appendix noteattached to this statement.

ResponseMessage:

Public Input No. 154-NFPA 2-2013 [Section No. 10.3.1.17.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

333 of 491 1/30/2014 9:30 AM

First Revision No. 91-NFPA 2-2013 [ Section No. 10.3.1.18.3 ]

10.3.1.17.3

Where excess-flow check valves are used, the closing flow shall be greater than the design flowmaximum system design flow rate and less than the flow rating of the piping system that results from acomplete line failure between the excess-flow valve and the equipment downstream of the excess-flowcheck valve. [ 52: 9.11.3]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 12:33:57 EDT 2013

Committee Statement

Committee Statement: Fueling Working Group Proposal – Editorial.

Response Message:

Public Input No. 155-NFPA 2-2013 [Section No. 10.3.1.18.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

334 of 491 1/30/2014 9:30 AM

First Revision No. 92-NFPA 2-2013 [ Section No. 10.3.1.18.6 ]

10.3.1.17.6

A breakaway device that causes hydrogen gas flow to stop shall be installed between the connection ofthe hose to the dispenser and the filling nozzle. Where a separate vent hose is used, the vent hoseconnection also shall be equipped with a breakaway device. [ 52: 9.11.6]

10.3.1.17.6.1

Such a devices shall be arranged to separate using a force not greater than 150 lb (68 kg) when appliedin any direction that the vehicle would move. [ 52: 9.11.6.1]

10.3.1.17.6.2

Breakaway devices shall be compatible with ANSI/IAS NGV 4.4, Breakaway Devices for DispensingSystems . [ 52: 9.11.6.2]

All other connections shall not prevent the operation of the gas flow breakaway devices.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 12:36:05 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal – There is no explicit requirement for a breakaway on the venthose. The standard of practice is to use a breakaway coupling however such a device is not asafety requirement.

ResponseMessage:

Public Input No. 157-NFPA 2-2013 [Section No. 10.3.1.18.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

335 of 491 1/30/2014 9:30 AM

First Revision No. 93-NFPA 2-2013 [ New Section after 10.3.1.18.7 ]

10.3.1.17.8

The emergency shutdown system shall include an automatic emergency shutoff valve at the hydrogenstorage and supply system.

10.3.1.17.8.1

When supplying an indoor dispenser, a redundant automatic emergency shutoff shall be installed wherethe hydrogen piping enters the building.

(A)

This valve shall be located outside.

(B)

This valve shall shut when the dispensing area gas detection system actuates.

10.3.1.17.8.2

The automatic emergency shutdown valve(s) shall close when an emergency shutdown is activated.

10.3.1.17.8.3

This valve shall be fail closed.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 12:54:01 EDT 2013

Committee Statement

CommitteeStatement:

In the event of an emergency and activation of the emergency shutdown system, this valve willautomatically close and isolate the hydrogen storage limiting the hydrogen release. It will failclosed upon loss of signal to the valve.

Risk studies have shown that the probability of a single valve failing/leaking in this critical safetyservice requires a redundant valve.

ResponseMessage:

Public Input No. 231-NFPA 2-2013 [New Section after 10.3.1.18.7]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

336 of 491 1/30/2014 9:30 AM

First Revision No. 94-NFPA 2-2013 [ Section No. 10.3.1.19.1 ]

10.3.1.18.1

Dispensing equipment shall be provided with hydrogen gas detectors de tection , leak detection, andflame detectors such that fire and gas can be detected at any point on the equipment.[52: 9.2.14 ] detection at the fueling area.

10.3.1.18.1.1

These detectors The detection systems shall be maintained and calibrated in accordance with Chapter6 the manufacturer's instructions on at least an annual basis or earlier if required by the manufacturer.[ 52: 9.2.14.1]

10.3.1.18.1.2

The station owner or operator shall maintain a record of detector maintenance and calibration in goodcondition and accessible to the inspector. [ 52: 9.2.14.2]

10.3.1.18.1.3

A sticker at least 6 in. 2 (39 cm 2 ) shall be affixed on the dispenser indicating the date of the nextscheduled maintenance and calibration. [ 52: 9.2.14.3]

Activation of the detection systems shall automatically stop dispensing and activate the automaticemergency shutoff valve. Reactivation of the dispenser requires a manual restart following the provisionsof this chapter.

10.3.1.18.1.4

Dispenser enclosure shall be designed to prevent the accumulation of flammable gas within theenclosure.

10.3.1.19 Canopies Used to Support Gaseous Hydrogen Systems.

Canopies that are used to shelter dispensing operations where flammable compressed gases arelocated on the roof of the canopy shall be in accordance with the following:

(1) The canopy shall meet or exceed Type I construction requirements of the adopted building code.

(2) Operations located under canopies shall be limited to refueling only.

(3) The canopy shall be constructed in a manner that prevents the accumulation of hydrogen gas.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 13:06:21 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal – The addition of the "or" conjunction allows flexibility of thedesign without reducing the requirement of detection of all failures on any point of the system. Theaddition of the "during transfer operation" explicitly states that these requirements are onlynecessary during the dispenser operation.

ResponseMessage:

Public Input No. 102-NFPA 2-2013 [New Section after 10.3.1.19.1.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

337 of 491 1/30/2014 9:30 AM

Public Input No. 134-NFPA 2-2013 [New Section after 10.3.1.19.1.3]

Public Input No. 158-NFPA 2-2013 [Section No. 10.3.1.19.1]

Public Input No. 159-NFPA 2-2013 [New Section after 10.3.1.19.1.3]

Public Input No. 188-NFPA 2-2013 [Section No. 10.3.1.19.1]

Public Input No. 197-NFPA 2-2013 [Section No. 10.3.1.19.1.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

338 of 491 1/30/2014 9:30 AM

First Revision No. 95-NFPA 2-2013 [ Section No. 10.3.2.1.2 ]

10.3.2.1.2 Qualified Operator.

Dispensing operations shall be performed by an operator who has been qualified by training to performthe functions necessary in the filling operation as described by the manufacturer’s operatinginstructions. [ 52: 9.4.1]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 14:26:18 EDT 2013

Committee Statement

CommitteeStatement:

The language in NFPA 2 requires that anyone performing dispensing operations must have training.However, dispensers and vehicles are currently designed to be used by the public without a qualifiedoperator or training. There are currently eight public stations where Hydrogen Vehicle customers fueltheir own vehicles. Two of the eight are installed at self-service motor fuel dispensing facilities, withone more to open in the early calendar year 2013. Many more of these stations will be built in thecoming years, and will be operated by public drivers who lease or purchase Hydrogen Vehicles, asdescribed in the California Fuel Cell Partnership Road Map document (http://cafcp.org/resources/print-materials).

The proposed text aligns NFPA 2 with NPFA 30A which has Operating Requirements for Motor FuelDispensing Facilities. NFPA 30A also includes requirements for operating instructions which willprovide enough information for the user to operate the dispenser.

This proposal is supported by the following organization:

The Fuel Cell and Hydrogen Energy Association (FCHEA) is the trade association for the fuel celland hydrogen energy industry, and is dedicated to the commercialization of fuel cells and hydrogenenergy technologies. FCHEA represents the full global supply chain, including universities,government laboratories and agencies, trade associations, fuel cell materials, components andsystems manufacturers, hydrogen producers and fuel distributors, utilities and other end users.

ResponseMessage:

Public Input No. 216-NFPA 2-2013 [Section No. 10.3.2.1.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

339 of 491 1/30/2014 9:30 AM

First Revision No. 97-NFPA 2-2013 [ Section No. 10.3.2.2.1 ]

10.3.3.2.1.3 General.

10.3.3.2.1.3.1 Dispensing.

Fuel dispensing indoors shall be in accordance with 10.3.3.2 .

10.3.3.2.1.3.2 Deflagration Venting.

When used, deflagration (explosion) venting shall be provided in exterior walls and roofs only.

10.3.3.2.1.3.3

Vents shall be permitted to consist of any one or any combination of the following:

(1) Walls of light material

(2) Lightly fastened hatch covers

(3) Lightly fastened, outward opening doors in exterior walls

(4) Lightly fastened walls or roofs

(5) Other methods in accordance with NFPA 69

10.3.3.2.1.3.4

Where applicable, snow loads shall be included in the calculations of the building venting system.

10.3.3.2.1.3.5 Rooms Within Buildings.

Rooms within or attached to other buildings shall be constructed of noncombustible or limited-combustible materials.

Exception: Window glazing shall be permitted to be plastic.

(A)

Interior walls or partitions shall be continuous from floor to ceiling, shall be anchored, and shall have afire resistance rating of at least 2 hours.

(B)

At least one wall shall be an exterior wall.

(C)

Explosion venting shall be provided in accordance with 10.3.3.2.1.3.2 and 10.3.3.2.1.3.3 .

(D)

Access to the room shall be from outside the primary structure.

(E)

If access to the room from outside the primary structure is not possible, access from within the primarystructure shall be permitted where such access is made through a vapor-sealing, self-closing fire doorhaving the appropriate rating for the location where installed.

10.3.3.2.1.3.6 Ventilation.

(A)

Indoor locations shall be ventilated utilizing air supply inlets and exhaust outlets arranged to provideuniform air movement to the extent practical.

(B)

Inlets shall be uniformly arranged on exterior walls near floor level.

(C)

Outlets shall be located in exterior walls at the high point of the room or in the roof.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

340 of 491 1/30/2014 9:30 AM

(D) Room Ventilation.

(1) Ventilation shall be by a continuous mechanical ventilation system or by a mechanical ventilationsystem activated by a continuously monitoring hydrogen detection system where a gasconcentration of not more than one-quarter of the lower flammable limit is present.

(2) In either case in 10.3.3.2.1.3.6 (D)(1), the system shall immediately shut down the fueling systemin the event of detection of an alarm condition or failure of the ventilation system, the detectionsystem, or of the controls.

(E)

The ventilation rate shall be at least 1 ft 3 /min/ft 2 (0.3 m 3 /min/m 2 ) of room area, but no less than 1

ft 3 /min/12 ft 3 (0.03 m 3 /min/0.34 m 3 ) of room volume.

(F)

A ventilation system for a room within or attached to another building shall be separate from anyventilation system for the other building.

10.3.3.2.1.3.7

Where installed, a gas detection system shall be equipped to sound a latched alarm and visuallyindicate when a maximum of one-quarter of the lower flammable limit is reached.

(A)

The gas detection system shall be certified by a qualified engineer with expertise in fire safety andgaseous detection.

10.3.3.2.1.3.8

The gas detection system shall function during system maintenance operations.

10.3.3.2.1.3.9

Reactivation of the fueling system shall be by manual restart and shall be conducted by trainedpersonnel.

10.3.3.2.1.3.10

Buildings and rooms used for compression other than that integral to the bulk storage system, gasprocessing, and dispensing shall be classified in accordance with Table 10.3.1.15.1 for installations ofelectrical equipment.

10.3.3.2.1.3.11

Nonelectrical sources of ignition, other than electrical installations as permitted by Table 10.3.1.15.1 ,shall not be permitted.

10.3.3.2.1.3.12 Warning Signs.

(A)

Access doors shall have warning signs with the words “WARNING — NO SMOKING — FLAMMABLEGAS.” “Non-odorized Gas.”

(B)

The wording shall be in plainly legible, bright red letters not less than 1 in. (25 mm) high on a whitebackground.

10.3.3.2.1.3.13 Construction of Indoor Areas.

Walls, ceilings, and floors within 15 feet (4.6 m) of the dispenser shall be constructed as fire barriershaving a fire resistance rating not less than 2 hours.

(A)

Openings. Opening protectives shall be provided for wall openings in accordance with therequirements of the adopted building code.

(B)

Penetrations. Through-penetrations and membrane penetrations of fire resistance rated constructionshall be protected in accordance with the requirements of the adopted building code.

(C)

Roof-Ceiling Assemblies. The fire-resistive protection of a roof-ceiling assembly required by10.3.3.2.1.3.13 shall not be required where every part of the roof-ceiling assembly is 20 ft (6.1 m) ormore above any floor immediately below.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

341 of 491 1/30/2014 9:30 AM

(D)

Floors. Floors in dispensing areas constructed of noncombustible or limited-combustible materialsshall not be required to comply with 10.3.3.2.1.3.13 .

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 14:33:40 EDT 2013

Committee Statement

CommitteeStatement:

Move all Indoor Public Fueling to 10.3.3.2 Indoor Nonpublic Fueling

Public does not currently fuel indoors, nor does this chapter provide sufficient guidance toconducting public fueling indoors. Return this section to “Reserved” status for future code revisioncycles to include language.

ResponseMessage:

Public Input No. 202-NFPA 2-2013 [Section No. 10.3.2.2.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

342 of 491 1/30/2014 9:30 AM

First Revision No. 98-NFPA 2-2013 [ New Section after 10.3.3.1.1 ]

10.3.3.1.1

The maximum refueling rate shall be limited to not more than 1.1 lb/min (0.5 kg/min) or 211 ft 3 /min (6

m 3 /min).

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 14:43:43 EDT 2013

Committee Statement

CommitteeStatement:

Define “normal” fueling rate maximum (when fueling is not fast-fill).

Move fast fill maximum from ‘ventilation’ section to the top of the indoor nonpublic fast fillfueling section (10.3.3.2.2)

ResponseMessage:

Public Input No. 203-NFPA 2-2013 [New Section after 10.3.3.1.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

343 of 491 1/30/2014 9:30 AM

First Revision No. 96-NFPA 2-2013 [ Section No. 10.3.3.1.1 ]

10.3.3.1.1 Qualified Operator.

Dispensing operations shall be performed by an operator who has been qualified by training to performthe functions necessary in the filling operation as described by the manufacturer’s operatinginstructions. [ 52: 9.4.1]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 14:32:20 EDT 2013

Committee Statement

Committee Statement: See PI 216.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

344 of 491 1/30/2014 9:30 AM

First Revision No. 99-NFPA 2-2013 [ Section No. 10.3.3.2.2.2 ]

10.3.3.2.2.2 Ventilation.

Ventilation shall be in accordance with 10.3.2.2.1.6 . [ 52 :9.4.3.1]

Table 10.3.3.2.2.2 Minimum Room Volume Based on Maximum Fueling Event

Maximum Fuel Quantity per Dispensing Event Minimum Room Volume

lb kg ft 3 m 3

Up to 1.8 Up to 0.8 40,000 1,000

1.8 to 3.7 >0.8 to 1.7 70,000 2,000

3.7 to 5.5 >1.7 to 2.5 100,000 3,000

5.5 to 7.3 >2.5 to 3.3 140,000 4,000

7.3 to 9.3 >3.3 to 4.2 180,000 5,000

[ 52 :Table 9.4.3.2.1]

(A)

Ventilation shall be in accordance with 10.3.3.2.1.3.6 .

(B)

The ventilation system of 10.3.3.2.1.3.6 shall not be required in industrial and storage occupancies whenthe room or area in which dispensing occurs is in accordance with 10.3.3.2.2.2(A) through10.3.3.2.2.2(H) the following: [ 52 :9.4.3.2]

(1) The minimum volume of the room in which a dispenser is installed shall be not less than 180,000

ft 3 ( 5000 m 3 ) , and the maximum quantity of fuel to be dispensed per fueling event shall belimited to 9.2 lb ( 4.2 kg ) .

(2) The dispenser shall be equipped with an automatic shutoff control to shut down the source of fuelwhen the maximum fuel quantity per dispensing event is reached or when the vehicle has beenfueled to capacity, whichever is less.

(a) The shutoff control shall be tested at installation and annually thereafter.

(b) Failure of the controller shall shut down the dispensing system.

(3) When multiple dispensers are installed in a room, the minimum room volume shall be incrementallyincreased for each additional dispenser.

(4) The height of the ceiling of the room where dispensing occurs shall be not less than 25 ft (8 m).

(5) The maximum refueling rate shall be limited to not more than 2.2 lb/min (1 kg/min), and the flowlimiting device shall be installed outdoors.

(6) All potential leak points between the dispenser cabinet and the refueling nozzle shall be monitoredby the dispenser in accordance with 10.3.1.11.4 and 10.3.1.11.5 . Activation of the monitoringsystem shall shut down the dispensing system.

(7) The fueling hose shall be limited to a maximum length of 25 ft (7.6 m) and shall be protected frommechanical damage, from abrasion, and from being driven over by a vehicle.

(a) Transfer systems shall be capable of depressurizing the nozzle through the dispenser ventline to facilitate disconnection.

(8) The dispensing area shall be inspected annually and certified in accordance with 10.1.1.1 .

(C)*

The minimum volume of the room in which a dispenser is installed shall be not less than t hat specifiedby Table 10.3.3.2.2.2 and the maximum quantity of fuel to be dispensed per fueling event shall belimited to an amount not greater than that established by the minimum room volume. [ 52 :9.4.3.2.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

345 of 491 1/30/2014 9:30 AM

(D)

The dispenser shall be equipped with an automatic shutoff control to shut down the source of fuel whenthe maximum fuel quantity per dispensing event is reached or when the vehicle has been fueled tocapacity, whichever, is less. [ 52: 9.4.3.2.2]

In no case shall the amount of fuel being delivered exceed the maximum quantity per dispensingevent as shown in Table 10.3.3.2.2.2 . [ 52 :9.4.3.2.2.1]

The shut off control shall be tested at installation and annually thereafter. [ 52 :9.4.3.2.2.2]

A sticker indicating that the required testing has occurred shall be affixed to the dispenser inaccordance with 10.3.1.19.1.3 and shall also indicate the next test date. [ 52 :9.4.3.2.2.2(A)]

Failure of the controller shall shutdown the dispensing system. [ 52 :9.4.3.2.2.2(B)]

(E)*

When multiple dispensers are installed in a room, the minimum room volume shall be incrementallyincreased for each additional dispenser. [ 52 :9.4.3.2.3]

(F)

The height of the ceiling of the room, where dispensing occurs, shall be not less than 25 feet (8 m).[ 52 :9.4.3.2.4]

(G)

The maximum refueling rate shall be limited to not more than 4.4 lb/min ( 2 kg/min) or 845 ft 3 /min

(24 m 3 /min). [ 52 :9.4.3.2.5]

(H)

All potential leak points between the dispenser cabinet and the refueling nozzle shall be monitored bythe dispenser in accordance with 10.3.1.11.4 and 10.3.1.11.5 . Activation of the monitoring systemshall shut down the dispensing system. [ 52 :9.4.3.2.6]

(I)

The fueling hose shall be limited to a maximum length of 25 ft (7.6 m) and shall be protected frommechanical damage, from abrasion and from being driven over by a vehicle. [ 52 :9.4.3.2.7]

Transfer systems shall be capable of depressurizing the nozzle through the dispenser vent line tofacilitate disconnection. [ 52 :9.4.3.2.7.1]

(J)

The dispensing area shall be inspected annually and certified in accordance with 10.2.1.1.1.[ 52 :9.4.3.2.8]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 15:01:30 EDT 2013

Committee Statement

CommitteeStatement:

Remove the “log” and “sticker” requirements are buried in the Hose Assembly (10.3.1.11) and FireProtection (10.3.1.19) sections.

Create a new section in the general section, applicable to all dispenser with a consistentdocumentation requirement. Include management of change rather than ‘simple log’ documentation.Include the indication of maintenance and calibration. Separate maintenance from calibration as

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

346 of 491 1/30/2014 9:30 AM

calibration is not required for all dispensers. Consider requirement of calibration for dispensing tothe public section.

ResponseMessage:

Public Input No. 198-NFPA 2-2013 [Section No. 10.3.3.2.2.2]

Public Input No. 204-NFPA 2-2013 [Section No. 10.3.3.2.2.2(F)]

Public Input No. 233-NFPA 2-2013 [Section No. 10.3.3.2.2.2]

Public Input No. 234-NFPA 2-2013 [Section No. 10.3.3.2.2.2(F)]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

347 of 491 1/30/2014 9:30 AM

First Revision No. 100-NFPA 2-2013 [ Section No. 10.3.3.2.2.7(E) ]

(E) Gas Detection System.

The dispenser enclosure or housing shall be equipped with a gas detection system, which that shallactuate when a maximum of 25 percent of the lower flammable limit (LFL) is detected (1 percent H2 in

air). [ 52 :9.4.7.4]

(1) Actuation of the gas detection system shall shut down the dispenser, stop the flow of gas into theroom, and start or continue to run the ventilation system [ when mechanical ventilation systems arerequired] . [ 52 :9.4.7.4.1]

(2) Actuation of the gas detection system shall sound a local alarm and provide visual indication when amaximum of 25 percent of the lower flammable limit (LFL) is detected (1 percent H2 in air).

[ 52 :9.4.7.4.2]

(3) The gas detection system shall function remain functional during maintenance operations on theventilation system. [ 52 :9.4.7.4.3]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 15:12:45 EDT 2013

Committee Statement

CommitteeStatement:

Believe the intent is to have the gas detection system to be operational during maintenancein the event of a leak.

ResponseMessage:

Public Input No. 235-NFPA 2-2013 [Section No. 10.3.3.2.2.7(E)]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

348 of 491 1/30/2014 9:30 AM

First Revision No. 101-NFPA 2-2013 [ Section No. 10.3.3.2.2.7(I) ]

(I) Ignition Source Control.

The owner/operator shall not allow hot work/ open flames within 15 ft (4.6 m) of the refueling locationunless the dispenser is shut down, depressurized, and purged with an inert gas . [ 52 :9.4.8]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 15:16:43 EDT 2013

Committee Statement

CommitteeStatement:

Fueling Working Group Proposal – Added text to explicitly require the use of inert gas forpurge prior to hot work.

ResponseMessage:

Public Input No. 181-NFPA 2-2013 [Section No. 10.3.3.2.2.7(I)]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

349 of 491 1/30/2014 9:30 AM

First Revision No. 103-NFPA 2-2013 [ Section No. 11.2.1 ]

11.2.1 Competent Design and Fabrication.

Designers, fabricators, and constructors of LH 2 fueling facilities shall be competent in the design,

fabrication, and construction of LH 2 containers, cryogenic equipment, loading and unloading systems,

fire protection equipment, hydrogen detection, and other components of the facility.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 15:24:26 EDT 2013

Committee Statement

CommitteeStatement:

Technical Committee has deleted this section since it is unenforceable and is not within thescope of NFPA 2.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

350 of 491 1/30/2014 9:30 AM

First Revision No. 102-NFPA 2-2013 [ Section No. 11.2.2 ]

11.2.2 Supervision.

Supervision shall be provided for the fabrication, construction, and acceptance tests of facilitycomponents to the extent necessary to ensure that facilities are structurally sound, suitable for theservice, and otherwise in compliance with this code.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 15:23:22 EDT 2013

Committee Statement

CommitteeStatement:

Requirement calls for “supervision” of construction in a very general sense and is not easilyenforceable. Additionally there is no similar requirement for the construction of GH2 fuelingfacilities.

ResponseMessage:

Public Input No. 11-NFPA 2-2012 [Section No. 11.2.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

351 of 491 1/30/2014 9:30 AM

First Revision No. 200-NFPA 2-2013 [ Chapter 12 ]

Chapter 12 Hydrogen Fuel Cell Power Systems

12.1 Scope.

This chapter shall apply to the design, construction, and installation of fuel cell power systems.

12.1.1 Application.

The requirements of this chapter shall apply to stationary and portable and micro fuel cell powergeneration systems of any capacity .

12.1.1.1

The storage, use, and handling of hydrogen in any quantity shall also comply with the requirements ofChapters 1 through 4 and the applicable requirements of Chapters 5 through 8.

12.1.1.2

Chapters 4 and 6 through 8 contain fundamental requirements that shall apply to all hydrogen systems.

12.1.1.2.1

The use-specific requirements of this chapter for hydrogen fuel cell power systems shall apply.

12.1.1.2.2

Where there is a conflict between a fundamental requirement and a use-specific requirement, theuse-specific requirement shall apply.

12.2* General.

12.2.1* Requirements. Listed and Approved Equipment.

A fuel cell power system(s) and associated equipment, components, and controls shall be meet thefollowing requirements:

It shall be protected against [tampering] by unauthorized persons commensurate with the locationand installation environment. Fire department access shall be provided. [ 853: 5.1.1(4)]

It shall be sited [or placed] so the power system and equipment do not affect required buildingexits during normal operations or fire emergencies. [ 853: 5.1.1(6)]

It shall be located or protected to prevent physical damage. [ 853: 5.1.1(10)]

12.2.1.1

Where demonstrated by an engineering analysis that the prescriptive requirements in this section areunnecessary to achieve an equivalent level of safety, approved alternatives shall be permitted.[ 853: 5.1.2]

Listed and approved hydrogen fuel cell equipment shall be installed in accordance with the listingrequirements and manufacturers’ instructions.

12.2.1.2

Such equipment shall not be required to meet the requirements of Chapter 7 . [ 55: 12.3.1.2]

12.3 Specific Requirements.

12.3.1 Stationary Fuel Cells.

12.3.1.1 General. [853:4.1]

12.3.1.1.1 Prepackaged, Self-Contained, Fuel Cell Power Systems. [853:4.2]

12.3.1.1.1.1

Prepackaged, self-contained [stationary] fuel cell power systems shall be designed, tested, and listed inaccordance with ANSI CSA FC.1, American National Standard for Fuel Cell Power Systems. [853:4.2.1]

12.3.1.1.1.2

Prepackaged, self-contained [stationary] fuel cell power systems outside the scope of ANSI CSA FC.1,American National Standard for Fuel Cell Power Systems, shall meet the provisions of 12.3.1.1.2[853:4.2.2]

* It shall be located [and used] outside potentially hazardous atmospheres as defined by Article500 or Article 505 of NFPA 70 , National Electrical Code , unless listed and approved for thespecific application. [ 853: 5.1.1(5)]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

352 of 491 1/30/2014 9:30 AM

12.3.1.1.2 Pre-Engineered Fuel Cell Power Systems. [ 853: 4.3]

[ 853: 4.3]

12.3.1.1.2.1

Pre-engineered fuel cell power systems and matched modular components shall be designed and testedto meet the intent of ANSI CSA FC.1, American National Standard for Fuel Cell Power Systems.[853:4.3.1]

12.3.1.1.2.2

Proprietary equipment or materials for which no generally recognized codes or standards exist shall beevaluated based on data from operational experience in the same or comparable service or test recordscovering the performance of the equipment or materials. [853:4.3.2]

12.3.1.1.3 Engineered and Field-Constructed Fuel Cell Power Systems. [ 853: 4.4]

[ 853: 4.4]

12.3.1.1.3.1

Documentation for engineered and field-constructed fuel cell power systems shall be provided. [853:4.4.1]

12.3.1.1.3.2

Documentation shall include a fire risk evaluation prepared by a registered engineer or third partyacceptable to the authority having jurisdiction. [853:4.4.2]

12.3.1.1.4 Fuel Cell Power Systems 47 Btu/sec (50 kW or Less).

Fuel cell power systems that use hydrogen shall be installed in accordance with the manufacturer'sinstructions and Chapter 6. [ 853: 9.3.7]

12.3.1.1.4 Siting for Fuel Cell Power Systems.

12.3.1.1.4.1 Siting.

A fuel cell power system(s) and associated equipment, components, and controls shall be sited andinstalled in accordance with the manufacturer's instructions and meet the following requirements:[ 853: 5.1.1]

It shall be placed on a firm foundation that is capable of supporting the equipment or components.[ 853: 5.1.1(1)]

It shall be located so the foundation of, and access to, associated components and the fuel cellpower system are above the base flood elevation. [ 853: 5.1.1(3)]

It shall be located so the power system(s) and components of a matched modular or field-engineered fuel cell power system and their respective vent or exhaust terminations are separatedfrom doors, windows, outdoor air intakes, and other openings into a building. [ 853: 5.1.1(7)]

It shall be located in a manner that allows service, maintenance, and emergency access.[ 853: 5.1.1(8)]

It shall be located [1.5 m (5 ft)] away from combustible materials, hazardous chemicals, high-piledstock, and other exposures to fire hazards. [ 853: 5.1.1(9)]

It shall be located such that a fire or failure of one of the systems does not present an exposurehazard to adjacent fuel cell power systems. [ 853: 5.1.1(11)]

12.3.1.1.5.2

Fuel cell power systems shall not be located in areas that are used or are likely to be used forcombustible, flammable, or hazardous materials storage. [ 853: 5.2.5]

12.3.1.1.5.3

Fire protection for systems and areas under construction shall comply with NFPA 241 , Standard forSafeguarding Construction, Alteration, and Demolition Operations . [ 853: 5.1.3]

12.3.1.1.6 Electrical Equipment and Components.

[ 853: 8.1.3]

12.3.1.1.6.1

All electrical connections and wiring to the power system(s) or components of matched modular or field-engineered fuel cell power systems shall be in accordance with NFPA 70 , National Electrical Code .[ 853: 5.5.1]

12.3.1.1.6.2

The installation requirements of fuel cell power systems shall be in accordance with Article 692 ofNFPA 70 , National Electrical Code .

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

353 of 491 1/30/2014 9:30 AM

12.3.1.1.6.3

The area classification around outlets from processes or compartments that contain fuel-bearingcomponents shall be in accordance with Article 500 or Article 505 of NFPA 70 , National ElectricalCode . [ 853: 5.2.3.2]

12.3.1.1.6.4

All transformers shall be installed in accordance with NFPA 70 , National Electrical Code .[ 853: 8.1.3.2]

12.3.1.1.6.5

Oil-filled transformers that have at least 500 gal (1892 L) capacity shall be protected by one of thefollowing: [ 853: 8.1.3.3]

A minimum spatial separation of 25 ft (7.6 m) between each transformer containment area andother structures [ 853: 8.1.3.3(1)]

A 2-hour-rated fire barrier between adjacent noncombustible or limited combustible structures,transformers, or switchgear that extend 1 ft (30.5 cm) above the transformer or structure and 2 ft(61 cm) beyond the sides [ 853: 8.1.3.3(2)]

An automatic deluge water spray system designed in accordance with NFPA 15 , Standard for

Water Spray Fixed Systems for Fire Protection , to provide a minimum density of 0.25 gpm/ft 2

(10.2 L/min·m 2 ) over all surfaces of the transformer [ 853: 8.1.3.3(3)]

12.3.1.1.7 Fire Protection.

12.3.1.1.7.1 Site Fire Protection.

Sites that have flammable or combustible liquid fuel storage shall have fire hydrants provided inaccordance with NFPA 30 , Flammable and Combustible Liquids Code , and NFPA 24 , Standard forthe Installation of Private Fire Service Mains and Their Appurtenances . [ 853: 8.1.1.1]

12.3.1.1.7.2

The hydrants specified in 12.3.1.1.7.1 shall have a water supply of at least 250 gpm (946 L/min) for 2hours. [ 853: 8.1.1.2]

12.3.1.1.7.3

Fuel cell power systems that do not have flammable or combustible liquid fuel storage and are locatedoutside buildings that have yard or city hydrant protection shall be considered to have required siteprotection. [ 853: 8.1.1.3]

12.3.1.1.7.4

If fuel cell power systems are sited at locations that do not have hydrant protection, power systems shallbe protected in accordance with a fire risk evaluation. [ 853: 8.1.1.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

354 of 491 1/30/2014 9:30 AM

12.3.1.1.8 Fire Prevention and Emergency Planning.

A written fire prevention and emergency plan shall be provided and shall include the following,commensurate with the size and location of the fuel cell power system: [ 853: 8.2]

Written information on fire prevention procedures, plant emergency alarms, and egressprocedures [ 853: 8.2(1)]

Requirements to conduct and document inspections and to identify and address needed remedialactions to correct conditions that increase fire hazards [ 853: 8.2(2)]

Written description of the general housekeeping practices and the control of transientcombustibles [ 853: 8.2(3)]

Written procedures for the handling and storage of flammable and combustible liquids and gases[ 853: 8.2(4)]

Written procedures for the control of potential ignition sources [ 853: 8.2(5)]

A written procedure that addresses impairments to fire protection systems and other materials,systems, or equipment that affect the level of fire hazards associated with the installation and thatalso addresses at least identification of equipment not available for service, personnel to benotified, and required enhancement of fire surveillance [ 853: 8.2(6)]

Requirements needed to complete a fire report, including an investigation and notification ofcorrective action to be taken [ 853: 8.2(7)]

Listing of frequency and requirements for periodic inspection, testing, and maintenance of the fuelcell power system emergency systems [ 853: 8.2(8)]

Signage prohibiting smoking and nonprocess ignition services within protective enclosures andsignage that designates areas where smoking is permitted [ 853: 8.2(9)]

Posting of the location of the operating instructions and the location of the emergency controls[ 853: 8.2(10)]

Requirements for the availability of portable flammable gas detectors at the service entrance to thefuel cell power system installations [ 853: 8.2(11)]

Signage providing instructions on the types of fire-suppressing materials that are prohibited andwhere they are prohibited [ 853: 8.2(12)]

Standard color or distinctive marking on all fuel piping and components, with marking inaccordance with ANSI A13.1, Scheme for Identification of Piping Systems [ 853: 8.2(13)]

Written fire emergency plan that includes the following: [ 853: 8.2(14)]

Response to fire alarms and fire system supervisory alarms and notification of personnelidentified in the plan [ 853: 8.2(14)(a)]

Evacuation of employees and visitors not directly involved in fire-fighting activities for the firearea [ 853: 8.2(14)(b)]

Coordination with security forces or other designated personnel to admit public firedepartment and control traffic and personnel [ 853: 8.2(14)(c)]

Fire extinguishment activities and identification of fire water application concerns onoperating equipment [ 853: 8.2(14)(d)]

Periodic drills to verify viability of the plan [ 853: 8.2(14)(e)]

Operator activities during fire emergencies [ 853: 8.2(14)(f)]

12.3.1.2 Indoor Installation of Fuel Cell Power Systems.

12.3.1.2.1 General.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

355 of 491 1/30/2014 9:30 AM

12.3.1.2.1.1

All fuel cell power systems shall be provided with a source of ventilation, exhaust, and makeup air inaccordance with 12.3.1.2 , with the exception of the following: [ 853: 7.1.1]

Listed prepackaged or pre-engineered and matched modular fuel cell power systems that have asealed, direct ventilation and exhaust system that is installed in accordance with the terms of thelisting and manufacturer's installation instructions [853: 7.1.1(2)]

12.3.1.2.1.2

A direct-vented fuel cell power system operating at negative pressure with respect to the room shall notrequire additional mechanical exhaust from the room or area. [ 853: 9.4.1]

12.3.1.2.1.3

Where the total abnormal gas emission or concentration from the fuel cell power system is nontoxic andcannot attain 25 percent of LFL under normal room or area ventilation, the fuel cell power system shallnot be required to supply additional ventilation and exhaust. [ 853: 9.4.2]

12.3.1.2.2 Room Construction.

A fuel cell power system and its associated components that are not located in areas designed forindustrial uses shall be located in a room that meets the conditions of 12.3.1.2.2.1 through12.3.1.2.2.3 . [ 853: 5.3]

12.3.1.2.2.1

The room shall be separated from the remainder of the building by floor, wall, and ceiling constructionthat has at least a 1-hour fire resistance rating in accordance with NFPA 251 , Standard Methods ofTests of Fire Resistance of Building Construction and Materials . [ 853: 5.3.1]

(A)

Electrical and piping penetrations and joints associated with the room shall be sealed with approvedmaterials that have a 1-hour fire resistance rating. [ 853: 5.3.2]

12.3.1.2.2.2

Openings between the room and other occupied spaces shall be protected by fire doors and dampers.[ 853: 5.3.3]

(A)

Fire doors shall be installed in accordance with NFPA 80 , Standard for Fire Doors and Other OpeningProtectives , and shall have a minimum fire resistance rating equivalent to that of the barrier.[ 853: 5.3.4]

(B)

Fire dampers shall be installed in accordance with NFPA 80 , Standard for Fire Doors and OtherOpening Protectives .

12.3.1.2.2.3

Each room shall be provided with egress in accordance with [the adopted building code]. [ 853: 5.3.6]

12.3.1.2.2.4

Fuel cell power systems located inside buildings shall be protected in accordance with 12.3.1.2.9 and12.4.1.1.3.4 . [ 853: 8.1.1.5]

12.3.1.2.2.5

Transformers installed in compartments, in modules, or in rooms that contain fuel cell power systemsshall be the dry type. [ 853: 8.1.3.1]

12.3.1.2.2.6

Fuel cell power systems [47 Btu/sec (50 kW) or less] supplied with a hydrogen fuel supply not

exceeding a total of 400 scf (11.33 m 3 ) shall not be required to have fire-rated separation.[ 853: 9.3.7.1]

12.3.1.2.3 Control Rooms and Distributed Integrated Controls Equipment.

If a separate room or building is provided for a fuel cell power system's monitoring and control, the roomor building shall be constructed in accordance with the [adopted] building code. [ 853: 8.1.4]

12.3.1.2.4 Ventilation and Exhaust.

12.3.1.2.4.1*

The ventilation and exhaust system shall be designed to provide a negative or neutral pressure in theroom, with respect to the building. [ 853: 7.1.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

356 of 491 1/30/2014 9:30 AM

12.3.1.2.4.2

The air intake and exhaust system shall meet the requirements specified in 12.3.1.2.5 , 12.3.1.2.6and 12.3.1.1.5.1 . [ 853: 7.1.3]

12.3.1.2.4.3

If mechanical ventilation is required, a control interlock shall be provided to shut down the unit upon lossof ventilation. [ 853: 7.1.4]

12.3.1.2.5 Ventilation Air.

[ 853: 7.2]

12.3.1.2.5.1

A separate mechanical ventilation system shall be provided for the area where a fuel cell power systemis located. [ 853: 7.2.1]

12.3.1.2.5.2

If it can be verified, natural ventilation shall be permitted to provide all required ventilation and makeupair. [ 853: 7.2.2]

12.3.1.2.5.3

The inlet air vent shall be designed to prevent foreign matter from entering. [ 853: 7.2.3]

12.3.1.2.6 Exhaust Systems.

[ 853: 7.3]

12.3.1.2.6.1

An exhaust system shall be provided for the area where a fuel cell power system is located.[ 853: 7.3.1]

12.3.1.2.6.2

The exhaust system shall be designed such that all emissions are exhausted to a safe location.[ 853: 7.3.2]

12.3.1.2.6.3

The exhaust rate from the room shall not be less than 1 cfm/ft 2 (0.3 m 3 /min · m 2 ) of floor area and

not less than 150 cfm (45 m 3 /min). [ 853: 7.3.3]

12.3.1.2.6.4

If mechanical exhaust is required, a control interlock shall be provided to shut down the unit upon loss ofexhaust. [ 853: 7.3.4]

12.3.1.2.6.5

The exhaust outlet shall be located as specified in 12.3.1.3.1.3 . [853: 7.3.5 ]

12.3.1.2.6.6

The exhaust system materials [for fuel cell power systems] shall be compatible with the exhaust gas andany resulting condensate. [ 853: 9.3.5]

12.3.1.2.7 Process Purging and Venting.

[ 853: 7.4]

12.3.1.2.7.1

Pressure tanks and piping intended to be purged, pressure regulators, relief valves, and other potentialsources of combustible gas shall be vented to the outside of the building, terminating at least 15 ft (4.6m) from air intakes, windows, doors, or other building openings. [ 853: 7.4.1]

12.3.1.2.7.2

The vent shall be designed to prevent entry of water or foreign objects. [ 853: 7.4.2]

12.3.1.2.8 Fire Protection.

12.3.1.2.8.1* Fuel Cell Fire Protection and Detection.

Fuel cell [power] systems designed and constructed in accordance with 12.3.1.1.3 shall be providedwith an automatic fire detection and alarm system in accordance with NFPA 72 , National Fire Alarmand Signaling Code . [ 853: 8.1.2]

12.3.1.2.8.2

The requirements of 12.3.1.1.7 shall not apply to [47 Btu/sec (50 kW)] or smaller systems except asmodified in 12.3.1.2.8.3 and 12.3.1.2.9.2 . [ 853: 9.5]

12.3.1.2.8.3

Fuel cell power systems that meet the requirements of 12.3.1.1.1 or 12.3.1.1.2 shall not require awritten fire prevention and emergency plan. [ 853: 9.5.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

357 of 491 1/30/2014 9:30 AM

12.3.1.2.9 Gas Detection System.

Combustible gas detector(s) shall be installed in the fuel cell power system enclosure, the exhaustsystem, or the room that encloses the fuel cell power system installation.[ 853: 8.1.5.4]

12.3.1.2.9.1

A combustible gas detector that meets the requirements of 12.3.1.2.9 shall be provided for all indooror separately enclosed gas compressors. [ 853: 8.1.5.5]

12.3.1.2.9.2

Combustible gas detection shall be installed in accordance with 12.3.1.2.9 [-]. [ 853: 9.5.1]

12.3.1.2.9.3

When gaseous or liquefied hydrogen is piped into the room or area from outside, hydrogen detector(s)shall be installed in accordance with 12.3.1.2.9.4 . [ 853: 8.1.5.6]

12.3.1.2.9.4

The following criteria for combustible gas detection systems, including detection specific to hydrogen,shall be met: [ 853: 8.1.5.7]

The location of the detection device(s) shall be based on leakage sources and fuel type.[ 853: 8.1.5.7(1)]

The combustible gas detection system shall be arranged to alarm at 25 percent of the lowerflammable limit (LFL) and be interlocked to shut down the power system fuel supply at 60 percentLFL. [ 853: 8.1.5.7(2)]

12.3.1.2.10 Limit Controls.

Indoor use of fuel cell power systems [47 Btu/sec (50 kW) or less] that operate without ventilation airfrom the outside shall be provided with limit controls that will not permit room ambient oxygen levels todrop below 18 percent unless it can be demonstrated by other means that the oxygen level will not dropbelow 18 percent. [ 853: 9.3.4]

12.3.1.3 Outdoor Installations of Fuel Cell Power Systems.

12.3.1.3.1 General.

12.3.1.3.1.1 Siting.

A fuel cell power system(s) and associated equipment, components, and controls shall be sited andinstalled in accordance with the manufacturer's instructions and meet the following requirements:[ 853: 5.1.1]

(A)

It shall be anchored, located, and protected so that the system and equipment will not be adverselyaffected by rain, snow, ice, freezing temperatures, wind, seismic events, and lightning. [ 853: 5.1.1(2)]

(B)

For outdoor installations, a fuel cell power system and related components shall be designed andconstructed for outdoor installation. [ 853: 5.2.1]

12.3.1.3.1.2

Air intakes to a fuel cell power system shall be located so the plant is not adversely affected by otherexhausts, gases, or contaminants. [ 853: 5.2.2]

12.3.1.3.1.3

The exhaust outlet(s) from process areas or areas that contain fuel-bearing components of a fuel cellpower system shall be located at least 15 ft (4.6 m) from heating, ventilating, and air-conditioning(HVAC) air intakes, windows, doors, and other openings into buildings. [ 853: 5.2.3]

(A)

The exhaust outlets of the [fuel cell power system] shall be located at least 10 ft (3 m) from HVAC airintakes, windows, doors, and other openings into buildings. [853: 9.2.1 ]

(B)

The exhaust outlet(s) shall not be directed onto walkways or other paths of travel for pedestrians.[ 853: 9.2.2]

12.3.1.3.1.4

Security barriers, fences, landscaping, and other enclosures shall not affect the required air flow into orexhaust out of the fuel cell power system and its components. [ 853: 5.2.4]

12.3.1.3.2 Rooftop Installation. [ 853: 5.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

358 of 491 1/30/2014 9:30 AM

12.3.1.3.2.1

Fuel cell power systems and components located on rooftops shall be installed in accordance with12.3.1.1.5.2 , 12.3.1.3.1.1(B) , and 12.3.1.3.1.2 through 12.3.1.3.1.5. [ 853: 5.4.1]

12.3.1.3.2.2

The roofing material under and within 12 in. (30.5 cm) horizontally from a fuel cell power system orcomponent shall be noncombustible or shall have a Class A rating. [ 853: 5.4.2]

12.3.1.2 Siting and Installation.

12.3.1.2.1 Siting.

Stationary fuel cell power system(s) and associated equipment, components, and controls shall be sitedand installed in accordance with NFPA 853, Standard for the Installation of Stationary Fuel Cell PowerSystems .

12.3.2 Portable Fuel Cells.

12.3.2.1 General.

12.3.2.1.1*

Prepackaged, self-contained portable fuel cell power systems shall be designed, tested, and listed inaccordance with ANSI/CSA FC 3, American National Standard / CSA American Standard for PortableFuel Cell Power Systems, or IEC 6228-1, Portable Fuel Cell Power Systems, Safety.

12.3.2.2 Indoor Portable Fuel Cells. (Reserved)

12.3.2.3 Outdoor Portable Fuel Cells. (Reserved)

12.3.3 Micro Fuel Cells Power Systems.

12.3.3.1 General.

12.3.3.1.1 Listed or Approved Systems.

Prepackaged, self-contained micro fuel cell power systems shall be listed or approved for the application.

12.3.3.2 Indoor Micro Fuel Cells. (Reserved)

12.3.3.3 Outdoor Micro Fuel Cells. (Reserved)

12.4 Storage.

12.4.1 Requirements for Hydrogen Storage Systems Serving Stationary Fuel Cell Installations.

12.4.1.1

Storage systems serving stationary fuel cell power systems shall be in accordance with NFPA 853 .

12.4.1.1 General.

12.4.1.1.1

The installation and location of fuel cell power system fuel supplies, associated fuel piping, andcomponents and their connection to a stationary fuel cell power system shall be in accordance with12.4.1 . [ 853: 6.1.1]

12.4.1.1.2

All gaseous fuel piping outside the fuel cell power system shall be marked or identified in accordancewith ANSI A13.1, Scheme for Identification of Piping Gases . [ 853: 6.1.2]

12.4.1.1.3 Hydrogen Fuel Systems and Storage.

12.4.1.1.3.1 Gaseous Hydrogen Storage.

The design, location, and installation of gaseous hydrogen storage shall be [in accordance] with[Chapters 6 and 7 ]. [ 853: 6.4.1]

12.4.1.1.3.2 Liquid Hydrogen Storage.

The design, location, and installation of liquid hydrogen storage shall [be in accordance] with [Chapters6 and 8 ]. [ 853: 6.4.2].

12.4.1.1.3.3 Hydrogen Piping.

Hydrogen piping, valves, and fittings from the hydrogen storage system to the fuel cell power systemshall [be in accordance with] ASME/ANSI B31.3, Process Piping , and 12.4.1.1.3.3 and 12.4.1.2 .[ 853: 6.4.3]

(A)

Piping, valves, regulators, or other equipment shall be located so that they are not subject to physicaldamage or otherwise be protected against physical damage. [ 853: 6.4.3.5]

(B)

Areas classified as Class I, Division 2 due to hydrogen piping shall be provided with ventilation to theoutdoors. [ 853: 6.4.3.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

359 of 491 1/30/2014 9:30 AM

(C)

Hydrogen containers and associated piping shall be electrically grounded and bonded in accordancewith NFPA 70 . [ 853: 6.4.3.7]

12.4.1.1.3.4 Shutdown of Fuel Supply.

When an automatic fire suppression system is provided, it shall be interconnected to shut off the fuelsupply when the suppression system is activated. [ 853: 8.1.5.3]

(A)

The location of the manual fuel shutoff valve required by Chapter 6 shall be marked at the location ofthe primary disconnecting means of the building or supplied circuits. [ 853: 5.5.3]

(B)*

An accessible manual shutoff valve shall be located in the hydrogen piping to the fuel cell power systemwithin 6 ft (1.8 m) of the storage container. [ 853: 6.4.3.1]

(C)*

The hydrogen supply piping to the fuel cell power system shall be provided with a second accessiblemanual shutoff valve that is located within 1.8 m (6 ft) of the power system, unless the power system isenclosed by a room with a 1-hour fire resistance rating as described in 12.3.1.2.2.1 through12.3.1.2.2.4 . [ 853: 6.4.3.2]

(D)

If the hydrogen storage is within 6 ft (1.8 m) of a fuel cell power system, the valve described in12.4.1.1.3.4(B) shall be considered to meet this requirement. [ 853: 6.4.3.2]

(E)

Fuel gas connections to the power system(s) or components of a matched modular or field engineeredfuel cell power system shall be in accordance with 12.4.1 . [ 853: 5.5.2]

(F)

If the power system is enclosed by a room with a 1-hour fire resistance rating, [an accessible shutoff]valve shall be located outside the room. [ 853: 6.4.3.3]

12.4.1.2 Indoor Storage.

For indoor installation of a power system, where the fuel supply is stored outdoors, an automatic shutoffvalve interlocked with gas detection shall be located outside the building that houses the power systemin accordance with 12.4.1.1.3.4 . [ 853: 6.4.3.4]

12.4.1.3 Outdoor Storage. (Reserved)

12.4.2 Requirements for Hydrogen Storage Systems Serving Portable Fuel Cell Power Systems.

12.4.2.1 General.

12.4.2.1.1 Fuel Cell Cartridges.

12.4.2.1.1.1 Listed or Approved Devices.

Fuel cell cartridges shall be listed or approved for the application.

12.4.2.1.1.2

Fuel cell cartridge refilling equipment shall be listed or approved for the application, and refill shall be inaccordance with the manufacturer’s published instructions and the listing.

12.4.2.2 Indoor Storage. (Reserved)

12.4.2.3 Outdoor Storage. (Reserved)

12.4.3 Requirements for Hydrogen Storage Systems Serving Micro Fuel Cell Power Systems.

12.4.3.1 General.

12.4.3.1.1 Fuel Cell Cartridges.

12.4.3.1.1.1 Listed or Approved Devices.

Fuel cell cartridges shall be listed or approved for the application.

12.4.3.1.1.2

Fuel cell cartridge refilling equipment shall be listed or approved for the application, and refill shall be inaccordance with the manufacturer’s published instructions and the listing.

12.4.3.2 Indoor Storage. (Reserved)

12.4.3.3 Outdoor Storage. (Reserved)

Supplemental Information

File Name Description

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

360 of 491 1/30/2014 9:30 AM

NFPA_2_-_Chapter_12_Hydrogen_Fuel_Cell_Power_Systems_-_revised_for_committee_input.1372428713887_1_.docx

A_12_2_FR_200_SB.docx

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 28 10:01:18 EDT 2013

Committee Statement

CommitteeStatement:

The Technical Committee has revised this entire chapter. This is in response to the followingpublic input received on this chapter. - PI -209, 20,21,22, 23. See attached word file for thechapter and annex text.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

361 of 491 1/30/2014 9:30 AM

Chapter 12 Hydrogen Fuel Cell Power Systems 12.1 Scope. This chapter shall apply to the design, construction, and installation of fuel cell power systems. 12.1.1 Application. The requirements of this chapter shall apply to stationary, and portable, and micro fuel cell power generation systems of any capacity. 12.1.1.1 The storage, use, and handling of hydrogen in any quantity shall also comply with the requirements of Chapters 1 through 4 and the applicable requirements of Chapters 5 through 8. 12.1.1.2 Chapters 4 and 6 through 8 contain fundamental requirements that shall apply to all hydrogen systems. 12.1.1.2.1 The use-specific requirements of this chapter for hydrogen fuel cell power systems shall apply. 12.1.1.2.2 Where there is a conflict between a fundamental requirement and a use-specific requirement, the use-specific requirement shall apply. 12.2* General. 12.2.1* Listed and Approved Equipment. 12.2.1.1 Listed and approved hydrogen fuel cell equipment shall be [installed] in accordance with the listing requirements and manufacturers’ instructions. 13.2.1.2 Such equipment shall not be required to meet the requirements of Chapter 7. [55:12.3.1.2]Requirements. A fuel cell power system(s) and associated equipment, components, and controls shall be meet the following requirements: (1) It shall be protected against [tampering] by unauthorized persons commensurate with the location and installation environment. Fire department access shall be provided. [853:5.1.1(4)] (2)*It shall be located [and used] outside potentially hazardous atmospheres as defined by Article 500 or Article 505 of NFPA 70, National Electrical Code, unless listed and approved for the specific application. [853:5.1.1(5)] (3) It shall be sited [or placed] so the power system and equipment do not affect required building exits during normal operations or fire emergencies. [853:5.1.1(6)] (4) It shall be located or protected to prevent physical damage. [853:5.1.1(10)] 12.2.1.1* Where demonstrated by an engineering analysis that the prescriptive requirements in this section are unnecessary to achieve an equivalent level of safety, approved alternatives shall be permitted. [853:5.1.2] 12.3 Specific Requirements. 12.3.1 Stationary Fuel Cells. 12.3.1.1 General. [853:4.1] 12.3.1.1.1 Prepackaged, Self-Contained, Fuel Cell Power Systems. [853:4.2] 12.3.1.1.1.1 Prepackaged, self-contained [stationary] fuel cell power systems shall be designed, tested, and listed in accordance with ANSI CSA FC.1, American National Standard for Fuel Cell Power Systems. [853:4.2.1] 12.3.1.1.1.2 Prepackaged, self-contained [stationary] fuel cell power systems outside the scope of ANSI CSA FC.1, American National Standard for Fuel Cell Power Systems, shall meet the provisions of 12.3.1.1.2 [853:4.2.2] 12.3.1.1.2 Pre-Engineered Fuel Cell Power Systems. [853:4.3] 12.3.1.1.2.1 Pre-engineered fuel cell power systems and matched modular components shall be designed and tested to meet the intent of ANSI CSA FC.1, American National Standard for Fuel Cell Power Systems. [853:4.3.1]

Commented [SG1]: Borrowed language from Chapter 13. 

12.3.1.1.2.2 Proprietary equipment or materials for which no generally recognized codes or standards exist shall be evaluated based on data from operational experience in the same or comparable service or test records covering the performance of the equipment or materials. [853:4.3.2] 12.3.1.1.3 Engineered and Field-Constructed Fuel Cell Power Systems. [853:4.4] 12.3.1.1.3.1 Documentation for engineered and field-constructed fuel cell power systems shall be provided. [853:4.4.1] 12.3.1.1.3.2 Documentation shall include a fire risk evaluation prepared by a registered engineer or third party acceptable to the authority having jurisdiction. [853:4.4.2] 12.3.1.1.4 Fuel Cell Power Systems 47 Btu/sec (50 kW or Less). Fuel cell power systems that use hydrogen shall be installed in accordance with the manufacturer’s instructions and Chapter 6. [853:9.3.7] 12.3.1.1.52 Siting for Fuel Cell Power Systemsand Installation. 12.3.1.1.52.1 Siting. A Stationary fuel cell power system(s) and associated equipment, components, and controls shall be sited and installed in accordance with the manufacturer’s instructions andmeet the following requirements: [853:5.1.1]NFPA 853, Standard for the Installation of Stationary Fuel Cell Power Systems.

(1) It shall be placed on a firm foundation that is capable of supporting the equipment or components. [853:5.1.1(1)] (2) It shall be located so the foundation of, and access to, associated components and the fuel cell power system are above the base flood elevation. [853:5.1.1(3)] (3) It shall be located so the power system(s) and components of a matched modular or field-engineered fuel cell power system and their respective vent or exhaust terminations are separated from doors, windows, outdoor air intakes, and other openings into a building. [853:5.1.1(7)] (4) It shall be located in a manner that allows service, maintenance, and emergency access. [853:5.1.1(8)] (5) It shall be located [1.5 m (5 ft)] away from combustible materials, hazardous chemicals, high-piled stock, and other exposures to fire hazards. [853:5.1.1(9)] (6) It shall be located such that a fire or failure of one of the systems does not present an exposure hazard to adjacent fuel cell power systems. [853:5.1.1(11)]

12.3.1.1.5.2 Fuel cell power systems shall not be located in areas that are used or are likely to be used for combustible, flammable, or hazardous materials storage. [853:5.2.5] 12.3.1.1.5.3 Fire protection for systems and areas under construction shall comply with NFPA241, Standard for Safeguarding Construction, Alteration, and Demolition Operations. [853:5.1.3]

Commented [SG2]: 853 references 55 

Commented [SG3]: Except for Chapter 4 that is extracted above NFPA 853 addresses installation so this seemed the best place to reference it. 

12.3.1.1.6 Electrical Equipment and Components. [853:8.1.3] 12.3.1.1.6.1 All electrical connections and wiring to the power system(s) or components of matched modular or field engineered fuel cell power systems shall be in accordance with NFPA 70, National Electrical Code. [853:5.5.1] 12.3.1.1.6.2 The installation requirements of fuel cell power systems shall be in accordance with Article 692 of NFPA 70, National Electrical Code. 12.3.1.1.6.3 The area classification around outlets from processes or compartments that contain fuel-bearing components shall be in accordance with Article 500 or Article 505 of NFPA 70, National Electrical Code. [853:5.2.3.2] 12.3.1.1.6.4 All transformers shall be installed in accordance with NFPA 70, National Electrical Code. [853:8.1.3.2] 12.3.1.1.6.5 Oil-filled transformers that have at least 500 gal (1892 L) capacity shall be protected by one of the following: [853:8.1.3.3]

(1) A minimum spatial separation of 25 ft (7.6 m) between each transformer containment area and other structures [853:8.1.3.3(1)] (2) A 2-hour-rated fire barrier between adjacent noncombustible or limited combustible structures, transformers, or switchgear that extend 1 ft (30.5 cm) above the transformer or structure and 2 ft (61 cm) beyond the sides [853:8.1.3.3(2)] (3) An automatic deluge water spray system designed in accordance with NFPA 15, Standard for Water Spray Fixed Systems for Fire Protection, to provide a minimum density of 0.25 gpm/ft2 (10.2 L/min·m2) over all surfaces of the transformer [853:8.1.3.3(3)]

12.3.1.1.7 Fire Protection. 12.3.1.1.7.1 Site Fire Protection. Sites that have flammable or combustible liquid fuel storage shall have fire hydrants provided in accordance with NFPA 30, Flammable and Combustible Liquids Code, and NFPA 24, Standard for the Installation of Private Fire Service Mains and Their Appurtenances. [853:8.1.1.1] 12.3.1.1.7.2 The hydrants specified in 12.3.1.1.7.1 shall have a water supply of at least 250 gpm (946 L/min) for 2 hours. [853:8.1.1.2] 12.3.1.1.7.3 Fuel cell power systems that do not have flammable or combustible liquid fuel storage and are located outside buildings that have yard or city hydrant protection shall be considered to have required site protection. [853:8.1.1.3] 12.3.1.1.7.4 If fuel cell power systems are sited at locations that do not have hydrant protection, power systems shall be protected in accordance with a fire risk evaluation. [853:8.1.1.4]

Commented [SG4]: Reference to [853: 5.5.1.1] was omitted. 

12.3.1.1.8 Fire Prevention and Emergency Planning. A written fire prevention and emergency plan shall be provided and shall include the following, commensurate with the size and location of the fuel cell power system: [853:8.2]

(1) Written information on fire prevention procedures, plant emergency alarms, and egress procedures [853:8.2(1)] (2) Requirements to conduct and document inspections and to identify and address needed remedial actions to correct conditions that increase fire hazards [853:8.2(2)] (3) Written description of the general housekeeping practices and the control of transient combustibles [853:8.2(3)] (4) Written procedures for the handling and storage of flammable and combustible liquids and gases [853:8.2(4)] (5) Written procedures for the control of potential ignition sources [853:8.2(5)] (6) A written procedure that addresses impairments to fire protection systems and other materials, systems, or equipment that affect the level of fire hazards associated with the installation and that also addresses at least identification of equipment not available for service, personnel to be notified, and required enhancement of fire surveillance [853:8.2(6)] (7) Requirements needed to complete a fire report, including an investigation and notification of corrective action to be taken [853:8.2(7)] (8) Listing of frequency and requirements for periodic inspection, testing, and maintenance of the fuel cell power system emergency systems [853:8.2(8)] (9) Signage prohibiting smoking and nonprocess ignition services within protective enclosures and signage that designates areas where smoking is permitted [853:8.2(9)] (10) Posting of the location of the operating instructions and the location of the emergency controls [853:8.2(10)] (11) Requirements for the availability of portable flammable gas detectors at the service entrance to the fuel cell power system installations [853:8.2(11)]

(12) Signage providing instructions on the types of fire suppressing materials that are prohibited and where they are prohibited [853:8.2(12)] (13) Standard color or distinctive marking on all fuel piping and components, with marking in accordance with ANSI A13.1, Scheme for Identification of Piping Systems [853:8.2(13)] (14) Written fire emergency plan that includes the following: [853:8.2(14)]

(a) Response to fire alarms and fire system supervisory alarms and notification of personnel identified in the plan [853:8.2(14)(a)] (b) Evacuation of employees and visitors not directly involved in fire-fighting activities for the fire area [853:8.2(14)(b)] (c) Coordination with security forces or other designated personnel to admit public fire department and control traffic and personnel [853:8.2(14)(c)] (d) Fire extinguishment activities and identification of fire water application concerns on operating equipment [853:8.2(14)(d)] (e) Periodic drills to verify viability of the plan [853:8.2(14)(e)] (f) Operator activities during fire emergencies [853:8.2(14)(f)]

12.3.1.2 Indoor Installation of Fuel Cell Power Systems. 12.3.1.2.1 General. 12.3.1.2.1.1 All fuel cell power systems shall be provided with a source of ventilation, exhaust, and makeup air in accordance with 12.3.1.2, with the exception of the following: [853:7.1.1]

(1) Listed prepackaged or pre-engineered and matched modular fuel cell power systems that have a sealed, direct ventilation and exhaust system that is installed in accordance with the terms of the listing and manufacturer’s installation instructions [853:7.1.1(2)]

12.3.1.2.1.2 A direct-vented fuel cell power system operating at negative pressure with respect to the room shall not require additional mechanical exhaust from the room or area. [853:9.4.1] 12.3.1.2.1.3 Where the total abnormal gas emission or concentration from the fuel cell power system is nontoxic and cannot attain 25 percent of LFL under normal room or area ventilation, the fuel cell power system shall not be required to supply additional ventilation and exhaust. [853:9.4.2] 12.3.1.2.2 Room Construction. A fuel cell power system and its associated components that are not located in areas designed for industrial uses shall be located in a room that meets the conditions of 12.3.1.2.2.1 through 12.3.1.2.2.3. [853:5.3] 12.3.1.2.2.1 The room shall be separated from the remainder of the building by floor, wall, and ceiling construction that has at least a 1-hour fire resistance rating in accordance with NFPA 251, Standard Methods of Tests of Fire Resistance of Building Construction and Materials. [853:5.3.1]

(A) Electrical and piping penetrations and joints associated with the room shall be sealed with approved materials that have a 1-hour fire resistance rating. [853:5.3.2]

12.3.1.2.2.2 Openings between the room and other occupied spaces shall be protected by fire doors and dampers. [853:5.3.3]

(A) Fire doors shall be installed in accordance with NFPA 80, Standard for Fire Doors and Other Opening Protectives, and shall have a minimum fire resistance rating equivalent to that of the barrier. [853:5.3.4] (B) Fire dampers shall be installed in accordance with NFPA 80, Standard for Fire Doors and Other Opening Protectives.

12.3.1.2.2.3 Each room shall be provided with egress in accordance with [the adopted building code]. [853:5.3.6] 12.3.1.2.2.4 Fuel cell power systems located inside buildings shall be protected in accordance with 12.3.1.2.9 and 12.4.1.1.3.4. [853:8.1.1.5] 12.3.1.2.2.5 Transformers installed in compartments, in modules, or in rooms that contain fuel cell power systems shall be the dry type. [853:8.1.3.1] 12.3.1.2.2.6 Fuel cell power systems [47 Btu/sec (50 kW) or less] supplied with a hydrogen fuel supply not exceeding a total of 400 scf (11.33 m3) shall not be required to have fire rated separation. [853:9.3.7.1] 12.3.1.2.3 Control Rooms and Distributed Integrated Controls Equipment. If a separate room or building is provided for a fuel cell power system’s monitoring and control, the room or building shall be constructed in accordance with the [adopted] building code. [853:8.1.4]

Commented [SG5]: This was extracted incorrectly.  Reference to [853:5.3.5] was omitted and text should have been: 5.3.5 Fire dampers shall be installed in accordance with NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems. 

12.3.1.2.4 Ventilation and Exhaust. 12.3.1.2.4.1* The ventilation and exhaust system shall be designed to provide a negative or neutral pressure in the room, with respect to the building. [853:7.1.2] 12.3.1.2.4.2 The air intake and exhaust system shall meet the requirements specified in 12.3.1.2.5, 12.3.1.2.6 and 12.3.1.1.5.1. [853:7.1.3] 12.3.1.2.4.3 If mechanical ventilation is required, a control interlock shall be provided to shut down the unit upon loss of ventilation. [853:7.1.4] 12.3.1.2.5 Ventilation Air. [853:7.2] 12.3.1.2.5.1 Aseparate mechanical ventilation system shall be provided for the area where a fuel cell power system is located. [853:7.2.1] 12.3.1.2.5.2 If it can be verified, natural ventilation shall be permitted to provide all required ventilation and makeup air. [853:7.2.2] 12.3.1.2.5.3 The inlet air vent shall be designed to prevent foreign matter from entering. [853:7.2.3] 12.3.1.2.6 Exhaust Systems. [853:7.3] 12.3.1.2.6.1 An exhaust system shall be provided for the area where a fuel cell power system is located. [853:7.3.1] 12.3.1.2.6.2 The exhaust system shall be designed such that all emissions are exhausted to a safe location. [853:7.3.2] 12.3.1.2.6.3 The exhaust rate from the room shall not be less than 1 cfm/ft2 (0.3 m3/min · m2) of floor area and not less than 150 cfm (45 m3/min). [853:7.3.3] 12.3.1.2.6.4 If mechanical exhaust is required, a control interlock shall be provided to shut down the unit upon loss of exhaust. [853:7.3.4] 12.3.1.2.6.5 The exhaust outlet shall be located as specified in 12.3.1.3.1.3. [853:7.3.5] 12.3.1.2.6.6 The exhaust system materials [for fuel cell power systems] shall be compatible with the exhaust gas and any resulting condensate. [853:9.3.5] 12.3.1.2.7 Process Purging and Venting. [853:7.4] 12.3.1.2.7.1 Pressure tanks and piping intended to be purged, pressure regulators, relief valves, and other potential sources of combustible gas shall be vented to the outside of the building, terminating at least 15 ft (4.6 m) from air intakes, windows, doors, or other building openings. [853:7.4.1] 12.3.1.2.7.2 The vent shall be designed to prevent entry of water or foreign objects. [853:7.4.2] 12.3.1.2.8 Fire Protection. 12.3.1.2.8.1* Fuel Cell Fire Protection and Detection. Fuel cell [power] systems designed and constructed in accordance with 12.3.1.1.3 shall be provided with an automatic fire detection and alarm system in accordance with NFPA 72, National Fire Alarm and Signaling Code. [853:8.1.2] 12.3.1.2.8.2 The requirements of 12.3.1.1.7 shall not apply to [47 Btu/sec (50 kW)] or smaller systems except as modified in 12.3.1.2.8.3 and 12.3.1.2.9.2. [853:9.5] 12.3.1.2.8.3 Fuel cell power systems that meet the requirements of 12.3.1.1.1 or 12.3.1.1.2 shall not require a written fire prevention and emergency plan. [853:9.5.2]

12.3.1.2.9 Gas Detection System. Combustible gas detector(s) shall be installed in the fuel cell power system enclosure, the exhaust system, or the room that encloses the fuel cell power system installation.[853:8.1.5.4] 12.3.1.2.9.1 A combustible gas detector that meets the requirements of 12.3.1.2.9 shall be provided for all indoor or separately enclosed gas compressors. [853:8.1.5.5] 12.3.1.2.9.2 Combustible gas detection shall be installed in accordance with 12.3.1.2.9 [-]. [853:9.5.1] 12.3.1.2.9.3 When gaseous or liquefied hydrogen is piped into the room or area from outside, hydrogen detector(s) shall be installed in accordance with 12.3.1.2.9.4. [853:8.1.5.6] 12.3.1.2.9.4 The following criteria for combustible gas detection systems, including detection specific to hydrogen, shall be met: [853:8.1.5.7]

(1) The location of the detection device(s) shall be based on leakage sources and fuel type. [853:8.1.5.7(1)] (2) The combustible gas detection system shall be arranged to alarm at 25 percent of the lower flammable limit (LFL) and be interlocked to shut down the power system fuel supply at 60 percent LFL. [853:8.1.5.7(2)]

12.3.1.2.10 Limit Controls. Indoor use of fuel cell power systems [47 Btu/sec (50 kW) or less] that operate without ventilation air from the outside shall be provided with limit controls that will not permit room ambient oxygen levels to drop below 18 percent unless it can be demonstrated by other means that the oxygen level will not drop below 18 percent. [853:9.3.4] 12.3.1.3 Outdoor Installations of Fuel Cell Power Systems. 12.3.1.3.1 General. 12.3.1.3.1.1 Siting. A fuel cell power system(s) and associated equipment, components, and controls shall be sited and installed in accordance with the manufacturer’s instructions and meet the following requirements: [853:5.1.1]

(A) It shall be anchored, located, and protected so that the system and equipment will not be adversely affected by rain, snow, ice, freezing temperatures, wind, seismic events, and lightning. [853:5.1.1(2)] (B) For outdoor installations, a fuel cell power system and related components shall be designed and constructed for outdoor installation. [853:5.2.1]

12.3.1.3.1.2 Air intakes to a fuel cell power system shall be located so the plant is not adversely affected by other exhausts, gases, or contaminants. [853:5.2.2] 12.3.1.3.1.3 The exhaust outlet(s) from process areas or areas that contain fuel-bearing components of a fuel cell power system shall be located at least 15 ft (4.6 m) from heating, ventilating, and air-conditioning (HVAC) air intakes, windows, doors, and other openings into buildings. [853:5.2.3]

(A) The exhaust outlets of the [fuel cell power system] shall be located at least 10 ft (3 m) from HVAC air intakes, windows, doors, and other openings into buildings. [853:9.2.1] (B) The exhaust outlet(s) shall not be directed onto walkways or other paths of travel for pedestrians. [853:9.2.2]

12.3.1.3.1.4 Security barriers, fences, landscaping, and other enclosures shall not affect the required air flow into or exhaust out of the fuel cell power system and its components. [853:5.2.4] 12.3.1.3.2 Rooftop Installation. [853:5.4] 12.3.1.3.2.1 Fuel cell power systems and components located on rooftops shall be installed in accordance with 12.3.1.1.5.2, 12.3.1.3.1.1(B), and 12.3.1.3.1.2 through 12.3.1.3.1.5. [853:5.4.1] 12.3.1.3.2.2 The roofing material under and within 12 in. (30.5 cm) horizontally from a fuel cell power system or component shall be noncombustible or shall have a Class A rating. [853:5.4.2]

12.3.2 Portable Fuel Cells. 12.3.2.1 General. 12.3.2.1.1* Prepackaged, self-contained portable fuel cell power systems shall be designed, tested, and listed in accordance with ANSI/CSA FC 3, American National Standard / CSA American Standard for Portable Fuel Cell Power Systems, or IEC 6228-1, Portable Fuel Cell Power Systems, Safety. 12.3.2.2 Indoor Portable Fuel Cells. (Reserved) 12.3.2.3 Outdoor Portable Fuel Cells. (Reserved) 12.3.3 Micro Fuel Cells Power Systems. 12.3.3.1 General. 12.3.3.1.1 Listed or Approved Systems. Prepackaged, self-contained micro fuel cell power systems shall be listed or approved for the application. 12.3.3.2 Indoor Micro Fuel Cells. (Reserved) 12.3.3.3 Outdoor Micro Fuel Cells. (Reserved) 12.4 Storage. 12.4.1 Requirements for Hydrogen Storage Systems Serving Stationary Fuel Cell Installations. 12.4.1.1 General. 12.4.1.1.1 The installation and location ofStorage systems serving stationary fuel cell power systems fuel supplies, associated fuel piping, and components and their connection to a stationary fuel cell power system shall be in accordance with NFPA 853, Standard for the Installation of Stationary Fuel Cell Power Systems. 12.4.1. [853:6.1.1] 12.4.1.1.2 All gaseous fuel piping outside the fuel cell power system shall be marked or identified in accordance with ANSI A13.1, Scheme for Identification of Piping Gases. [853:6.1.2] 12.4.1.1.3 Hydrogen Fuel Systems and Storage. 12.4.1.1.3.1 Gaseous Hydrogen Storage. The design, location, and installation of gaseous hydrogen storage shall be [in accordance] with [Chapters 6 and 7]. [853:6.4.1] 12.4.1.1.3.2 Liquid Hydrogen Storage. The design, location, and installation of liquid hydrogen storage shall [be in accordance] with [Chapters 6 and 8]. [853:6.4.2]. 12.4.1.1.3.3 Hydrogen Piping. Hydrogen piping, valves, and fittings from the hydrogen storage system to the fuel cell power system shall [be in accordance with] ASME/ANSI B31.3, Process Piping, and 12.4.1.1.3.3 and 12.4.1.2. [853:6.4.3]

(A) Piping, valves, regulators, or other equipment shall be located so that they are not subject to physical damage or otherwise be protected against physical damage. [853:6.4.3.5] (B) Areas classified as Class I, Division 2 due to hydrogen piping shall be provided with ventilation to the outdoors. [853:6.4.3.6] (C) Hydrogen containers and associated piping shall be electrically grounded and bonded in accordance with NFPA 70. [853:6.4.3.7]

Commented [SG6]: This isn’t really necessary but the requirement for standardized chapter organization forces it. 

Commented [SG7]: 853 reference 55 

Commented [SG8]: 853 reference 55 

12.4.1.1.3.4 Shutdown of Fuel Supply. When an automatic fire suppression system is provided, it shall be interconnected to shut off the fuel supply when the suppression system is activated. [853:8.1.5.3]

(A) The location of the manual fuel shutoff valve required by Chapter 6 shall be marked at the location of the primary disconnecting means of the building or supplied circuits. [853:5.5.3] (B)* An accessible manual shutoff valve shall be located in the hydrogen piping to the fuel cell power system within 6 ft (1.8 m) of the storage container. [853:6.4.3.1] (C)* The hydrogen supply piping to the fuel cell power system shall be provided with a second accessible manual shutoff valve that is located within 1.8 m (6 ft) of the power system, unless the power system is enclosed by a room with a 1-hour fire resistance rating as described in 12.3.1.2.2.1 through 12.3.1.2.2.4. [853:6.4.3.2] (D) If the hydrogen storage is within 6 ft (1.8 m) of a fuel cell power system, the valve described in 12.4.1.1.3.4(B) shall be considered to meet this requirement. [853:6.4.3.2] (E) Fuel gas connections to the power system(s) or components of a matched modular or field engineered fuel cell power system shall be in accordance with 12.4.1. [853:5.5.2] (F) If the power system is enclosed by a room with a 1-hour fire resistance rating, [an accessible shutoff] valve shall be located outside the room. [853:6.4.3.3]

12.4.1.2 Indoor Storage. For indoor installation of a power system, where the fuel supply is stored outdoors, an automatic shutoff valve interlocked with gas detection shall be located outside the building that houses the power system in accordance with 12.4.1.1.3.4. [853:6.4.3.4]

12.4.1.3 Outdoor Storage. (Reserved) 12.4.2 Requirements for Hydrogen Storage Systems Serving Portable Fuel Cell Power Systems. 12.4.2.1 General. 12.4.2.1.1 Fuel Cell Cartridges. 12.4.2.1.1.1 Listed or Approved Devices. Fuel cell cartridges shall be listed or approved for the application. 12.4.2.1.1.2 Fuel cell cartridge refilling equipment shall be listed or approved for the application, and refill shall be in accordance with the manufacturer’s published instructions and the listing. 12.4.2.2 Indoor Storage. (Reserved) 12.4.2.3 Outdoor Storage. (Reserved) 12.4.3 Requirements for Hydrogen Storage Systems Serving Micro Fuel Cell Power Systems. 12.4.3.1 General. 12.4.3.1.1 Fuel Cell Cartridges. 12.4.3.1.1.1 Listed or Approved Devices. Fuel cell cartridges shall be listed or approved for the application. 12.4.3.1.1.2 Fuel cell cartridge refilling equipment shall be listed or approved for the application, and refill shall be in accordance with the manufacturer’s published instructions and the listing. 12.4.3.2 Indoor Storage. (Reserved) 12.4.3.3 Outdoor Storage. (Reserved)

 

A.12.2 Fuel cell technology is evolving at a rapid rate, and codes and standards criteria are needed to help acceptance of the new technology. Currently, there is only one standard for testing stationary fuel cell power systems, which is ANSI CSA FC.1, American National Standard for Fuel Cell Power Systems. ANSI CSA FC.1 applies to a specific size fuel cell power system that is prepackaged and assembled as one complete unit. The constraints of ANSI CSA FC.1 limit the ability to test and list larger power plants or power systems that use fuels other than natural gas or LP-Gas or that are not prepackaged and self-contained. [853: A.4.1] NFPA 853 provides additional guidance for acceptance of power system installations that are not within the scope of ANSI CSA FC.1, commensurate with the need to protect life safety and property and the need of the adoption agencies to be able to uniformly evaluate power system installations outside the scope of available equipment standards. [853:A.4.1] A.12.2.1 The equipment referenced is intended to include fuel cell [power system] applications, generation of hydrogen from portable or transportable hydrogen generation equipment, batteries, and similar devices and equipment that utilize hydrogen for the purpose of power generation. It does not include hydrogen production facilities intended to produce hydrogen used for distribution or repackaging operations operated by gas producers, distributors, and repackagers. [55:A.12.3.1] A.12.2.1.1 The siting of a fuel cell power system depends on many variables relating to the unit size, fuel, and failure mode. [853: A.5.1.2] A.12.2.1(2) For additional information on hazardous atmospheres, see NFPA497, Recommended Practice for the Classification of Flammable Liquids, Gases, or Vapors and of Hazardous (Classified) Locations for Electrical Installations in Chemical Process Areas [853: A.5.1.1(5)] A.12.3.1.2.4.1 The ventilation and exhaust system design should consider the manufacturer’s air requirements for the fuel cell power system(s) and any additional equipment that is located within the space. [853: A.7.1.2] A.12.3.1.2.8.1 Units meeting ANSI CSA FC.1, American National Standard for Fuel Cell Power Systems, requirements have internal devices to monitor for overheating, and smoke and combustible gas releases, interlocked to shut down the fuel cell by isolating the fuel supply. The fire detection and alarm for engineered and field-constructed fuel cell power systems should provide for these internal hazards as well as hazards outside the fuel cell. If a fire alarm system is provided for the site or facility where a prepackaged and pre-engineered fuel cell is installed, the process monitors interlocked to shut down the fuel cell should be monitored by the fire alarm system. [853: A.8.1.2]

A.12.3.2.1.1 ANSI/CSA FC 3, American National Standard / CSA American Standard for Portable Fuel Cell Power Systems, applies to ac- and dc-type portable fuel cell power systems, with a rated output voltage not exceeding 600 volts, for commercial, industrial, and residential indoor and outdoor use in nonhazardous locations, in accordance with NFPA 70, National Electrical Code. ANSI CSA FC3 does not apply to portable fuel cell power systems that are permanently connected (stationary) to either fuel or electric supply, designed to export power to a grid, replacement fuel cell power units for appliances, or fuel cell systems for propulsion. Additional guidance pertaining to portable fuel cell power systems is provided by IEC 62282-5-1, Portable Fuel Cell Power Systems, Safety. A.12.4.1.1.3.4(B) The shutoff valve should be in a location that is identified and easily accessed by authorized personnel such that the valve can be operated in the event of a pending emergency. A cylinder valve on unmanifolded cylinder storage installations meets the intent of 12.4.1.1.3.4(B). [853:A.6.4.3.1] A.12.4.1.1.3.4(C) The shutoff valve should be outside the storage containment area in a location that is identified and easily accessed by authorized personnel such that the valve can be operated in the event of a pending emergency. An inlet shut off valve on the fuel cell system meets the intent of 12.4.1.1.3.4(C).[853:A.6.4.3.2]  

Commented [SG1]: Reference to [853:A.6.4.3.1] was omitted. 

Commented [SG2]: Reference to [853:A.6.4.3.2] was omitted. 

First Revision No. 520-NFPA 2-2013 [ Section No. 13.1.1.3 ]

13.1.1.1.1

Systems that generate hydrogen in excess of the quantity indicated in 13.1.1 shall be constructed,installed, and operated in accordance with nationally recognized standards.

Submitter Information Verification

Submitter Full Name: Patrick Foley

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 15 14:26:04 EST 2013

Committee Statement

CommitteeStatement:

Move 13.1.1.3 to 13.1.1.1.1. The text remains the same with the exception that the referenceto 55:12.3.2.2.1 is deleted.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

362 of 491 1/30/2014 9:30 AM

First Revision No. 521-NFPA 2-2013 [ Section No. 13.2.1 ]

13.2.1* Listed and or Approved Equipment.

13.2.1.1

Listed and or approved hydrogen-generating equipment shall be [installed] installed in accordance withthe listing requirements and manufacturers’ instructions. [ 55: 12.3.1.1]

13.2.1.1.1

Such equipment shall not be required to meet the requirements of Chapter 6 , Chapter 7 , and the restof this chapter.

13.2.1.2

Such equipment shall not be required to meet the requirements of Chapter 7 . [ 55: 12.3.1.2]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 15 15:12:59 EST 2013

Committee Statement

CommitteeStatement:

The “and” statement in “Listed and approved” indicates that this section applies only to equipmentthat is both “certified” by an NRTL and acceptable to the AHJ (see the NFPA Glossary of Terms).

Believe that the original intent was to address equipment that was either “certified” or acceptable tothe AHJ. Renumbered 13.2.1.2 to 13.2.1.1.1 for clarity - indicates that (only) listed or approvedequipment is exempt.

Added Chapter 6 and the remainder of Chapter 13 to “exemptions” for Listed or approvedequipment. Chapter 6 is primarily extract from Chapter 6 of NFPA 55, “Building-Related Controls”,and doesn’t apply to hydrogen generators. This is not clear in Chapter 6 so including here makes itclear.

Listing or approving equipment includes the installation and operation, etc. (or the relatedinstructions) so, there is no need to apply the rest of Chapter 13.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

363 of 491 1/30/2014 9:30 AM

First Revision No. 104-NFPA 2-2013 [ New Section after 13.2.2 ]

13.2.2.1* Interconnecting Hydrogen Piping.

Hydrogen piping, valves, and fittings from the hydrogen generation equipment to other equipmentincluding hydrogen storage systems shall conform to the appropriate section of ASME B31, Code forPressure Piping .

Supplemental Information

File Name Description

A_13_2_2_1_FR_104_SB.docx

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 16:11:11 EDT 2013

Committee Statement

CommitteeStatement:

Installers will benefit from direction addressing various purities of hydrogen when interconnectinghydrogen generators and downstream equipment. Some hydrogen generators, ex. reformers orgasifiers, may produce a gas mixture that is less than 95% hydrogen or above the temperature limitsof ASME B31.12, Hydrogen Piping and Pipelines. In these cases another section of ASME B31 maybe more appropriate, such as B31.3.

ResponseMessage:

Public Input No. 86-NFPA 2-2012 [New Section after 13.2.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

364 of 491 1/30/2014 9:30 AM

  A.13.2.2.1   Some hydrogen generators (e.g., reformers or gasifiers) can produce a gas mixture that is less than 95  percent hydrogen or above the temperature limits of ASME B31.12, Hydrogen Piping and Pipelines.  In such cases, another section of ASME B31 might be more appropriate.   

Formatted: Font: Italic

First Revision No. 483-NFPA 2-2013 [ Section No. 13.2.4 ]

13.2.4 Siting.

Hydrogen generation system(s) shall be installed in accordance with Chapters 1 through 8 [ as well as thefollowing criteria] : [ 55 :12.3.2.4]

(1) The system shall be placed on a firm foundation that is capable of supporting the equipment orcomponents as in accordance with ASCE-7. [ 55 :12.3.2.4(1)]

(2) The system shall be anchored, located, and protected so that the system and equipment will not beadversely affected by rain, snow, ice, freezing temperatures, wind, seismic events, and lightning.[ 55 :12.3.2.4(2)]

(3)

(4) The system shall be located outside potentially hazardous areas defined by NFPA 70, NationalElectrical Code , Article 500 unless listed and approved for such areas. [ 55: 12.3.2.4(4)]

(5) Vent terminations from hydrogen generation systems shall be in accordance with Section 6.16.[ 55: 12.3.2.4(5)]

(6) Setbacks of hydrogen generation system equipment from exposures shall be in accordance withTable 7.3.2.3.1.1(A)(a) or Table 7.3.2.3.1.1(A)(b) . [ 55: 12.3.2.4(6)]

A hydrogen generation system and associated hydrogen storage not exceeding a total of 400 scf

(11.33 Nm 3 ) shall not be required to have fire-rated separation.

(7) All safety-related controls shall comply with NFPA 79, Electrical Standard for Industrial Machinery .[ 55: 12.3.2.4(8)]

Supplemental Information

File Name Description

Word_file_for_revisions_to_FR_483.docx

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Sep 04 15:41:50 EDT 2013

Committee Statement

CommitteeStatement:

Committee generated first revision - dropped extract tags from 55. Deleted requirements in13.2.4 (7). Hydrogen generators typically do not store any hydrogen. Not clear what fire-ratedseparation is required/exempted.

ResponseMessage:

* The system shall be protected against access by unauthorized persons commensurate with thelocation and installation environment. Fire department access shall be provided. [ 55 :12.3.2.4(3)]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

365 of 491 1/30/2014 9:30 AM

13.2.4 Siting. Hydrogen generation system(s) shall be installed in accordance with Chapters 1 through 8 [as well as the following criteria]as follows: [55:12.3.2.4]

(1) The system shall be placed on a firm foundation that is capable of supporting the equipment or components as in accordance with ASCE-7. [55:12.3.2.4(1)]

(2) The system shall be anchored, located, and protected so that the system and equipment will not be adversely affected by rain, snow, ice, freezing temperatures, wind, seismic events, and lightning. [55:12.3.2.4(2)]

(3)* The system shall be protected against access by unauthorized persons commensurate with the location and installation environment. Fire department access shall be provided. [55:12.3.2.4(3)]

(4) The system shall be located outside potentially hazardous areas defined by NFPA 70, National Electrical Code, Article 500 unless listed and approved for such areas. [55:12.3.2.4(4)]

(5) Vent terminations from hydrogen generation systems shall be in accordance with Section 6.16. [55:12.3.2.4(5)]

(6) Setbacks of hydrogen generation system equipment from exposures shall be in accordance with Table 7.3.2.3.1.2(a) or Table 7.3.2.3.1.2(b).

(7) A hydrogen generation system and associated hydrogen storage not exceeding a total of 400 scf (11.33 m3) shall not be required to have fire-rated separation. [55:12.3.2.4(7)]

(8) All safety-related controls shall comply with NFPA 79, Electrical Standard for Industrial Machinery. [55:12.3.2.4(8)]

 

First Revision No. 522-NFPA 2-2013 [ Section No. 13.2.5 ]

13.2.5 Indoor Installations.

A hydrogen generation system installed indoors shall be located in a ventilated area in accordance withthe provisions of Section 6.17 . 7.3.2.2.4 . [ 55: 12.3.2.6]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 15 16:23:51 EST 2013

Committee Statement

CommitteeStatement:

Section 13.2.5 was a general section that required all hydrogen generators being installed indoorsto be installed as if they were buld GH2 systems storage by referring to 7.3.2.2.4. Hydrogengenerators (generally) contain much less than 5000 scf and are exempt from Section 7.3 (see also13.2.4).

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

366 of 491 1/30/2014 9:30 AM

First Revision No. 526-NFPA 2-2013 [ Section No. 13.2.6 ]

13.2.6 Outdoor and Rooftop Installations.

[ 55: 12.3.2.5]

13.2.6.1

For outdoor or rooftop installations, a hydrogen generation system and related components shall bedesigned and constructed for outdoor installation. [ 55: 12.3.2.5.1]

13.2.6.1.1

Hydrogen reformers or gasifiers shall not be installed on rooftops or in penthouse areas of occupiedstructures. [ 55: 12.3.2.5.1.1]

13.2.6.1.2

The installation of listed or approved reformers or gasifiers shall be allowed provided the listing orapproval is specific to rooftop installations. [ 55: 12.3.2.5.1.2]

13.2.6.2

The area classification around hydrogen generation system outlets that exhaust flammable gas inconcentrations greater than 25 percent LFL shall be in accordance with Article 500 or 505 of NFPA 70,National Electrical Code . [ 55: 12.3.2.5.2]

13.2.6.3

For units installed on rooftops, the roofing material under and within 12 in. (305 mm) horizontally of a[ hydrogen generation system] or component thereof shall be noncombustible or shall have a Class Arating as in accordance with [ the adopted building code] . [ 55: 12.3.2.5.3]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 18 09:15:22 EST 2013

Committee Statement

CommitteeStatement:

Placing hydrogen equipment higher than other equipment takes advantage of hydrogen’s naturalbuoyancy and placing it on the roof reduces the likelihood hydrogen will collect somewhere andform a flammable atmosphere. It seems like rooftop installation should be encouraged notprohibited.

Note: NFPA 54 allows gas appliances including heating systems for whole buildings to be locatedon the roof or in the attic. Hydrogen reformers are essentially gas appliances and should beallowed also.

Note: Left requirements for gasifiers because they may use carbonaceous materials, such as coalor petroleum, for fuel (according to NFPA Glossary of Terms) and these can be heavier than air.

Clarify that requirement only applies to components of the hydrogen generation system – not allcomponents.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

367 of 491 1/30/2014 9:30 AM

First Revision No. 106-NFPA 2-2013 [ New Section after 13.3.1.1.1 ]

13.3.1.1.1 Siting and Interconnecting.

Siting and interconnection of water electrolyzers shall be in accordance with the applicable requirementsof Section 13.2 as modified or appended by this section.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 16:19:17 EDT 2013

Committee Statement

CommitteeStatement:

New header and text to direct the reader this section modifies section 13.2, and applies thetemplate approach of the NFPA 2 TG

ResponseMessage:

Public Input No. 41-NFPA 2-2012 [New Section after 13.3.1.1.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

368 of 491 1/30/2014 9:30 AM

First Revision No. 105-NFPA 2-2013 [ Section No. 13.3.1.1.1 ]

13.3.1.1.2* Product Standards.

Electrolyzers shall be tested and approved in accordance with ISO/DIS 22734-1, Hydrogen generatorsusing water electrolysis process — Part 1: Industrial and commercial applications . [ 55: 12.3.2.7.1]

Water electrolyzers shall be listed or approved for their use.

Supplemental Information

File Name Description

FR_105_Annex_Material.docx

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 16:16:47 EDT 2013

Committee Statement

CommitteeStatement:

UL and CSA are to coordinate with CSA to produce nationalized electrolyzer product standards asUL/CSA 22734-1 and UL/CSA 22734-2. This is the path outline by UL2264 technical grouppreviously. Specific commercial and residential electrolyzer product listing standards ISO 22734-1,Hydrogen generators using water electrolysis process — Part 1: Industrial and commercialapplications, and ISO 22734-2, Hydrogen generators using water electrolysis process — Part 2:Residential Applications are already in use. Small electrolyzers have been specifically listed toUL/CSA 61010 for laboratory and other uses.

This is an alternative proposal not reviewed by Ch 13 TG

Retaining informative text in the Annex helps guide the AHJ.

ResponseMessage:

Public Input No. 1-NFPA 2-2012 [Section No. 13.3.1.1.1]

Public Input No. 42-NFPA 2-2012 [Section No. 13.3.1.1.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

369 of 491 1/30/2014 9:30 AM

 FR 105 Annex Material  A.13.3.1.1.2    Listing standards for water electrolyzers are available.  A commercial electrolyzer product listing standard already in use is ISO 22734‐1, Hydrogen generators using water electrolysis process — Part 1: Industrial and commercial applications.   A companion residential use electrolysis product listing standard, ISO 22734‐2, Hydrogen generators using water electrolysis process — Part 2: Residential Applications, is also available.  UL and CSA are working to bring forth nationalized versions as UL/CSA 22734‐1 and UL/CSA 22734‐2.  Small electrolyzers have been specifically listed to UL/CSA 61010 for laboratory and other uses.  

First Revision No. 108-NFPA 2-2013 [ New Section after 13.3.1.1.2 ]

13.3.1.2 Ventilation for Indoor Electrolyzers.

If mechanical ventilation is required, a control interlock shall be provided to shut down the electrolyzerupon loss of ventilation.

13.3.1.3

If oxygen is released within the electrolyzer room, sufficient ventilation shall be provided to preventoxygen-enriched atmospheres above 23.5 percent oxygen.

13.3.1.4

Ventilation for indoor electrolyzers shall be in accordance with manufacturer's installation instructionsand with one of the following:

(1) In accordance with Section 6.17 .

(2) Use of constant ventilation sufficient to maintain an average H2 gas concentration within the roombelow 25 percent LFL based on the maximum anticipated hydrogen leak as determined by themanufacturer's installation instructions.

(3) Use of a hydrogen detection system, using GH2 detection equipment per Section 6.12 , thatinitiates ventilation per Section 6.17 at a detected level of 10 percent LFL.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 16:26:09 EDT 2013

Committee Statement

CommitteeStatement:

Water based equipment is very likely to freeze in cold climates if area ventilation is per section 6.17.The code can anticipate this with provision of alternate methods to address thermal limitations ofinstalling water based electrolysis equipment in freezing environments.

One alternate method is to provide sufficient ventilation to assure <25% LFL based on the equipmentdesign and anticipated leak

Another alternate method is to use an approved flammable gas detector to trigger dilution/ventilationsystems similar to that allowed by the electrolyzer listing standard. The source of the hydrogen, theelectrolyzer, is power interlocked so as to stop any additional hydrogen production in the event of aleak. This approach is anticipated by NFPA30A section 7.4.7 for service garages, where a flammablegas detector will turn on ventilation and turn off heaters. However, turning off heaters as prescribed inNFPA30A section 7.4.7 will result in freezing and further damage to the water electrolyzer. Therefore,new code language is proposed instead.

A control interlock between mechanical ventilation loss and hydrogen generation as extracted from55:12.3.2.8.5.4 remains appropriate.

Cogeneration of oxygen is unique to water electrolysis; therefore new code language directingsufficient ventilation for indoor release of oxygen to prevent creation of an enriched atmospheregreater than 23.5% (per OSHA) is proposed.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

370 of 491 1/30/2014 9:30 AM

Annex material providing one appropriate standard for H2 detectors is proposed.

ResponseMessage:

Public Input No. 84-NFPA 2-2012 [New Section after 13.3.1.1.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

371 of 491 1/30/2014 9:30 AM

First Revision No. 107-NFPA 2-2013 [ Section No. 13.3.1.1.2 ]

13.3.1.1.3 Hazardous Material Containment.

With the exception of gaseous hydrogen, electrolyzers that contain or utilize hazardous materials asdefined by [ the adopted building code] shall be designed and installed to contain such materials inaccordance with [ the adopted building code] . [ 55: 12.3.2.7.2]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 16:21:08 EDT 2013

Committee Statement

Committee Statement: Add title to describe paragraph, renumber.

Accepted by Ch 13 TG

Response Message:

Public Input No. 43-NFPA 2-2012 [Section No. 13.3.1.1.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

372 of 491 1/30/2014 9:30 AM

First Revision No. 113-NFPA 2-2013 [ Section No. 13.3.1.2 ]

13.3.1.5 Indoor Installations of Electrolyzers. (Reserved)

13.3.1.5.1* Residential.

Electrolyzers listed or approved for residential occupancies compliant with the GH 2 content limit of

6.4.1.5.1.1 shall be permitted.

Supplemental Information

File Name Description

A.13.3.1.5.1_FR_113_.docx

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 16:56:22 EDT 2013

Committee Statement

CommitteeStatement:

Deleted "reserved" marker as we have added text. Note that this FR includes response to PI-44

Residential electrolysis appliances are beginning to be deployed for energy storage and for H2fueling.

Section 6.4.1.5.1 only allows industrial and storage occupancies, while 6.4.1.5.2 allows for‘operation of equipment’ for any use as long as the H2 content is below 250 cubic feet

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

373 of 491 1/30/2014 9:30 AM

FR 109 Annex Material

A 13.3.1.2.1  Listing standards for residential use electrolyzers, such as ISO22734‐2, allow manufacturers to list electrolyzers for residential applications such as energy conversion and vehicle fueling.  Limiting GH2 content to 250 scf GH2 per 6.4.1.5.2 aligns with non‐industrial use 

First Revision No. 527-NFPA 2-2013 [ Section No. 13.3.2 ]

13.3.2 Catalytic Reforming–Based Hydrogen Generation Systems.

[ 55: 12.3.2.8]

13.3.2.1 General.

13.3.2.1.1 Siting and Interconnecting.

Siting and interconnection of catalytic reformer–type hydrogen generation systems shall be in accordancewith 13.2.4 through 13.2.6 as modified or appended by this section. [ 55: 12.3.2.8.1]

13.3.2.1.1.1

Hydrogen piping, valves, and fittings from the catalytic reforming–based hydrogen generation equipmentto hydrogen storage system shall conform to ASME/ANSI B31.3, Process Piping. [ 55: 12.3.2.8.4.2]

13.3.2.1.1.2

The output of the catalytic reformer systems, which typically contain s significant quantities of carbonmonoxide and other toxic substances, shall be controlled. [ 55: 12.3.2.8.4.9]

(A)

The output from the final element of conditioning equipment shall be handled as hydrogen gas unlessresidual toxic content remains that would exceed applicable OSHA exposure limits in the event of aleak, in which case the requirements of 13.3.2.1.1.2 shall apply. [ 55: 12.3.2.8.4.9(A)]

(B)

Materials for outlet interface piping shall be selected based on both the temperature and the chemicalcomposition of the gas. [ 55: 12.3.2.8.4.9(B)]

13.3.2.1.1.3

Pressurized portions of process exhaust system piping shall be in accordance with ASME B31.3,Process Piping. ASME B31.12, Hydrogen Piping and Guidelines [ 55: 12.3.2.8.5.1]

13.3.2.1.2 Fire Protection for Catalytic Reforming–Based Hydrogen Generation Systems.

The fire protection requirements of NFPA 853 shall apply, in addition to the following:[ 55: 12.3.2.8.6] A

(1) When a catalytic reformer-based hydrogen generation system is installed indoors, a carbonmonoxide detector shall be installed in the catalytic reformer system enclosure, the cabinet exhaustsystem, or the room that encloses the installation.[ 55: 12.3.2.8.6(1)]

(2) Where installed in a room containing a catalytic reformer system, the location of the detector shall beapproved.[ 55: 12.3.2.8.6(2)]

13.3.2.1.3 Fire Protection for Catalytic Reforming–Based Hydrogen Generation Systems.

The fire protection requirements of NFPA 853 shall apply, in addition to the following: [ 55: 12.3.2.8.6]

A carbon monoxide detector shall be installed in the catalytic reformer system enclosure, thecabinet exhaust system, or the room that encloses the installation. [ 55: 12.3.2.8.6(1)]

Where installed in a room containing a catalytic reformer system, the location of the detector shallbe approved. [ 55: 12.3.2.8.6(2)]

13.3.2.2 Indoor Installations of Reformers.

13.3.2.2.1

A catalytic reformer–type hydrogen generation system and its associated components that are not locatedin areas designed for industrial uses shall be located in a room that meets the conditions of 13.3.2.2.1.1through 13.3.2.2.1.6. [ 55: 12.3.2.8.3.1]

13.3.2.2.1.1

The room shall be separated from the remainder of the building by floor, wall, and ceiling construction thathas at least a 1-hour fire resistance rating in accordance with NFPA 251 ASME E119 , Standard Methodsof Tests of Fire Resistance of Building Construction and Materials Standard Test Methods for Fire Tests ofBuilding Construction and Materials or UL 263, Fire Tests of Building Construction and Materials .[ 55: 12.3.2.8.3.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

374 of 491 1/30/2014 9:30 AM

13.3.2.2.1.2

Electrical and piping penetrations and joints associated with the room shall be sealed with approvedmaterials that have a 1-hour fire resistance rating. [ 55: 12.3.2.8.3.4]

13.3.2.2.1.3

Openings between the room and other occupied spaces shall be protected by fire doors and dampers.[ 55: 12.3.2.8.3.5]

13.3.2.2.1.4

Fire doors shall be installed in accordance with NFPA 80, Standard for Fire Doors and Other OpeningProtectives , and shall have a minimum fire resistance rating equivalent to that of the barrier.[ 55: 12.3.2.8.3.6]

13.3.2.2.1.5

Fire dampers shall be installed in accordance with NFPA 90A, Standard for the Installation ofAir-Conditioning and Ventilating Systems . [ 55: 12.3.2.8.3.7]

13.3.2.2.1.6

Each room shall be provided with egress in accordance with NFPA 101 , Life Safety Code the adoptedbuilding code . [ 55: 12.3.2.8.3.8]

13.3.2.2.2 Ventilation.

Clearances from combustible construction and other combustible materials shall be in accordance withmanufacturer's instructions, NFPA 31, NFPA 54, or NFPA 58.

13.3.2.2.2.1

[-] Catalytic reforming–based hydrogen generation systems shall be provided with a source ofventilation, exhaust, and makeup air in accordance with this chapter. [ 55: 12.3.2.8.5.2]

13.3.2.2.2.2

The ventilation and exhaust system shall be designed to provide a negative or neutral pressure in theroom, with respect to the building. [ 55: 12.3.2.8.5.3]

13.3.2.2.2.3

If mechanical ventilation is required, a control interlock shall be provided to shut down the unit upon lossof ventilation. [ 55: 12.3.2.8.5.4]

13.3.2.2.2.4 Ventilation Air.

(A)

A separate mechanical ventilation system shall be provided for the area where a catalyticreforming–based hydrogen generation system’s power system is located. [ 55: 12.3.2.8.5.5(A)]

(B)

If it can be verified, natural ventilation shall be permitted to provide all required ventilation and makeupair. [ 55: 12.3.2.8.5.5(B)]

(C)

The inlet air vent shall be designed to prevent foreign matter from entering. [ 55: 12.3.2.8.5.5(C)]

13.3.2.2.2.5 Exhaust Systems.

As required by the manufacturer’s instructions and the product listing, a process exhaust system shallbe installed to carry combustion and reforming process by-products such that all emissions areexhausted to an approved location. [ 55: 12.3.2.8.5.6]

(A)

The area containing [catalytic reformer exhaust exit] shall be located such that HVAC air intakes,windows, doors, and other openings into buildings cannot be exposed to the following:[ 55: 12.3.2.8.3.2(1)]

Hazardous atmospheres [ 55: 12.3.2.8.3.2(1)]

Toxic gases in excess of applicable OSHA exposure limits [ 55: 12.3.2.8.3.2(2)]

13.3.2.2.3

Indoor use of catalytic reforming systems that operate without ventilation air from the outside shall beprovided with limit controls that will not permit room ambient oxygen levels to drop below 18 percentunless it can be demonstrated by other means that the oxygen level will not drop below 18 percent.

13.3.2.2.4

The exhaust system materials shall be compatible with the exhaust gas and any resulting condensate.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

375 of 491 1/30/2014 9:30 AM

13.3.2.2.5

Catalytic reforming systems using a flammable liquid as a fuel shall be located outside unless they meetthe requirements for indoor installations in Chapters 1 through 7 or meet all of the followingrequirements:

(1) The catalytic reforming system enclosure plus the connected indoor liquid fuel piping shall contain

less than 5 gal (0.019 m 3 ) of liquid fuel during all modes of operation, standby, and shutdown.

(2) The bulk fuel storage shall be located outside.

(3) The indoor fuel piping shall be of solid pipe or tube or all-welded, soldered, or brazed constructionup through the catalytic reforming enclosure.

(4) The catalytic reforming system shall be equipped with leakage detection and automatic isolation ofthe indoor fuel piping from the outdoor bulk fuel supply upon detection of fuel leakage using pumpstoppage, valve closure, or other appropriate means as determined by the manufacturer.

(5) Outdoor bulk fuel storage located at an elevation above the catalytic reforming system shall beequipped with an automatic isolation valve at the tank.

13.3.2.2.6

Catalytic reforming systems that store hydrogen shall be installed in accordance with the manufacturer'sinstructions and Chapter 7 .

13.3.2.2.7 Ventilation.

13.3.2.2.7.1

Catalytic reforming–based hydrogen generation systems shall be provided with a source of ventilation,in accordance with this chapter.

13.3.2.2.7.2

If mechanical ventilation is required, a control interlock shall be provided to shut down the unit upon lossof ventilation.

13.3.2.2.7.3 Ventilation Air.

(A)

If mechanical ventilation is required, a separate mechanical ventilation system shall be provided for thearea where the catalytic reforming–based hydrogen generation system power is located.

(B)

If natural ventilation is available, it shall be permitted to provide all required ventilation.

(C)

The air inlets shall be designed to prevent foreign matter from entering.

13.3.2.2.11* Process Purging and Venting.

Process purging and vents shall conform to the following: [ 55: 12.3.2.8.5.7]

Pressure equipment and piping intended to be purged, pressure regulators, relief valves, andother potential sources of combustible gas shall be vented to the outside of the building.[ 55: 12.3.2.8.5.7(1)]

The vent shall be designed to prevent entry of water or foreign objects. [ 55: 12.3.2.8.5.7(2)]

The vent gas shall be directed so as not create additional hazards to the building openings, suchas windows, doors, or HVAC intakes. [ 55: 12.3.2.8.5.7(3)]

13.3.2.2.8 Combustible Gas Detection.

13.3.2.2.8.1

Combustible When required, combustible gas detection shall be installed in accordance with12.3.1.2.9 8.1.5.4 through 8.1.5.8 of NFPA 853 , except where the fuel gas system is listed for indoor useand the fuel is odorized. [ 55: 12.3.2.8.8.1]

13.3.2.2.12.2

Listed catalytic reformer systems in scope to 13.3.2.4.2 shall not require a written fire prevention andemergency plan. [ 55: 12.3.2.8.8.2]

13.3.2.3 Outdoor and Rooftop Installations of Reformers.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

376 of 491 1/30/2014 9:30 AM

13.3.2.3.1

The area containing the catalytic reformer system and associated conditioning equipment shall be locatedsuch that HVAC air intakes, windows, doors, and other openings into buildings cannot be exposed to thefollowing: [ 55: 12.3.2.8.2.1]

(1) Hazardous atmospheres [ 55: 12.3.2.8.2.1(1)]

(2) Toxic gases in excess of applicable OSHA exposure limits [ 55: 12.3.2.8.2.1(2)]

13.3.2.3.2 Exhaust Outlets.

(A)

The exhaust outlet(s) from process areas or areas that contain fuel-bearing components of a catalyticreforming systems shall be located at least 15 m (50 ft) from HVAC air intakes, windows, doors, and otheropenings into buildings, . or in accordance with 7.3.2.3 . [ 55: 12.3.2.8.2.2(A)]

(B)

The exhaust outlet(s) Hydrogen generation system ventilation outlets that exhaust flammable gas inconcentration exceeding 25 percent of the lower LEL shall not be directed onto walkways or other pathsof travel for pedestrians. [ 55: 12.3.2.8.2.2(B)]

(C)

Reformer burner exhausts shall be located and installed in accordance with Chapter 12 of NFPA 54.

13.3.2.3.3

Process air Air intakes to a hydrogen generation system shall be located so the plant is not adverselyaffected by other exhausts, gases, or contaminants. [ 55: 12.3.2.8.2.3]

13.3.2.3.4

Security barriers, fences, landscaping, and other enclosures shall not affect the required process air flowinto the hydrogen generation system and its components. [ 55: 12.3.2.8.2.4]

13.3.2.4 Small Catalytic Reforming– Based Hydrogen Generation Systems.

13.3.2.4.1 General.

Subsection 13.3.2.4 identifies additional requirements and or modifications to 13.3.2 for small catalyticreforming hydrogen generation systems with hydrogen generation capacity of less than 9 lb/hr (4 kg/hr).

13.3.2.4.2 Indoor Installations of Small Reformers.

13.3.2.4.2.1

Clearances from combustible construction and other combustible materials shall be in accordance withmanufacturer’s instructions; NFPA 31 , Standard for the Installation of Oil-Burning Equipment ; NFPA54 , National Fuel Gas Code ; or NFPA 58 , Liquefied Petroleum Gas Code . [ 55: 12.3.2.8.7.3(A)]

13.3.2.4.2.2

Indoor use of catalytic reforming systems that operate without ventilation air from the outside shall beprovided with limit controls that will not permit room ambient oxygen levels to drop below 18 percentunless it can be demonstrated by other means that the oxygen level will not drop below 18 percent.[ 55: 12.3.2.8.7.3(B)]

13.3.2.4.2.3

The exhaust system materials shall be compatible with the exhaust gas and any resulting condensate.[ 55: 12.3.2.8.7.3(C)]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

377 of 491 1/30/2014 9:30 AM

13.3.2.4.2.4

Catalytic reforming systems using a flammable liquid as a fuel shall be located outside unless they meetthe requirements for indoor installations in Chapters 1 through 7 or meet all of the followingrequirements: [ 55: 12.3.2.8.7.3(D)]

The catalytic reforming system enclosure plus the connected indoor liquid fuel piping shall contain

less than 5 gal (0.019 m 3 ) of liquid fuel during all modes of operation, standby, and shutdown.[ 55: 12.3.2.8.7.3(D)(1)]

The bulk fuel storage shall be located outside. [ 55: 12.3.2.8.7.3(D)(2)]

The indoor fuel piping shall be of solid pipe or tube or all-welded, soldered, or brazed constructionup through the catalytic reforming enclosure. [ 55: 12.3.2.8.7.3(D)(3)]

The catalytic reforming system shall be equipped with leakage detection and automatic isolation ofthe indoor fuel piping from the outdoor bulk fuel supply upon detection of fuel leakage using pumpstoppage, valve closure, or other appropriate means as determined by the manufacturer.[ 55: 12.3.2.8.7(D)(4)]

Outdoor bulk fuel storage located at an elevation above the [catalytic reforming system] shall beequipped with an automatic isolation valve at the tank. [ 55: 12.3.2.8.7(D)(5)]

13.3.2.4.2.5

Catalytic reforming systems that store hydrogen shall be installed in accordance with the manufacturer’sinstructions and Chapter 7 . [ 55: 12.3.2.8.7.3(E)]

13.3.2.4.2.6

The requirements of 13.3.2.1.2 shall not apply to 8.8 lb/hr (4 kg/hr) or smaller systems except asmodified herein. [ 55: 12.3.2.8.7.3(F)]

13.3.2.4.3 Outdoor Installations of Small Reformers.

13.3.2.4.3.1

The exhaust outlets of the system shall be located at least 50 ft (15 m) from HVAC air intakes, windows,doors, and other openings into buildings. [ 55: 12.3.2.8.7.2(A)]

13.3.2.4.3.2

The exhaust outlet(s) shall not be directed onto walkways or other paths of travel for pedestrians.[ 55: 12.3.2.8.7.2(B)]

Supplemental Information

File Name Description

Justification_for_FR_527_Section_13.3.2.docx

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 18 12:05:09 EST 2013

Committee Statement

CommitteeStatement:

Committee generated first revision. NFPA 2 is the primary document for this material. Seeattachment for substantiation for this section.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

378 of 491 1/30/2014 9:30 AM

13.3.2.1.1 12.3.2.8.1 Chapter 7does not apply; see 13.2.4. Looks like we changed the references to this chapter – is “as modified or appended by this section” still required?

13.3.2.1.1.1 12.3.2.8.4.2 ASME B31.12 is specific to hydrogen piping. 13.3.2.1.1.2 12.3.2.8.4.9 Meaning of “output” is not clear; typically would think of the product (hydrogen) but could be

exhaust, etc., too. Changes to 13.3.2.3.2 address concerns of this section. 13.3.2.1.1.2(A) 12.3.2.8.4.9(A) See 13.3.2.1.1.2. 13.3.2.1.1.2(B) 12.3.2.8.4.9(B) See 13.3.2.1.1.2. 13.3.2.1.1.3 12.3.2.8.5.1 “Process exhaust” is understood to mean reformer burner exhaust; this is addressed in the

changes to13.3.2.3.2. 13.3.2.1.2(1) 12.3.2.8.6 (1) Section implies but does not clearly state that it applies when the reformer based hydrogen

generator is installed indoors (“…the room that encloses the installation.”) 13.3.2.2.2 12.3.2.8.7.3(A) The requirements in 13.3.2.4.2 are not specific to “small” indoor reformers and seem

applicable to all indoor reformers so, moved them to 13.3.2.2.2 – 13.3.2.2.6. 13.3.2.2.3 12.3.2.8.7.3(B) See 13.3.2.2.2. 13.3.2.2.4 12.3.2.8.7.3(C) See 13.3.2.2.2. 13.3.2.2.5 12.3.2.8.7.3(D) See 13.3.2.2.2. 13.3.2.2.5(1) 12.3.2.8.7.3(D)(1) See 13.3.2.2.2. 13.3.2.2.5(2) 12.3.2.8.7.3(D)(2) See 13.3.2.2.2. 13.3.2.2.5(3) 12.3.2.8.7.3(D)(3) See 13.3.2.2.2. 13.3.2.2.5(4) 12.3.2.8.7.3(D)(4) See 13.3.2.2.2. 13.3.2.2.5(5) 12.3.2.8.7.3(D)(5) See 13.3.2.2.2. NOTE: Is this really needed? Why elevated?? 13.3.2.2.6 12.3.2.8.7.3(E) See 13.3.2.2.2. 13.3.2.2.7.1 (was 13.3.2.2.2.1)

12.3.2.8.5.2 This is redundant and somewhat confusing. Ventilation and exhaust are addressed in other sections and “make up air” is not defined.

13.3.2.2.2.2 12.3.2.8.5.3 The intent of this requirement is not clear; perhaps it is out of place. At first the subject appears to be the dilution system (ventilation and exhaust) for the reformer based hydrogen generator but then it refers to the pressure in the room with respect to the building. (Source text, 12.3.2.8.5.3 of NFPA 55, was not in the indoor section so, this was even more confusing. )

If the intent was to address the dilution system of enclosed reformer based hydrogen generator (assuming it used dilution instead of other protection techniques, ex. intrinsic safety), then the only requirement is that there be adequate air flow; it does not matter if the pressure inside is positive or negative (especially if the generator is outdoors). This was discussed at length at the ISO 22734 committee meetings and the consensus was that direction of the pressure did not matter. NFPA 497 only requires air flow for dilution to “declassify” a zone. And, Chapter 8 of NFPA 496 requires pressurizing (positive pressure) an enclosure that contains an internal source of flammable gas. Negative pressure may be the most common approach but it is not the only useful one. If the intent was to address ventilation in a room containing a reformer based hydrogen generator, this requirement needs to be clarified.

Note: Even indoors negative pressure may not be the only solution. If the room the generator is in is completely sealed from the rest of the building, it doesn’t matter if the pressure is positive or negative especially if the hydrogen generator has its own separate air intakes and exhaust outside the building and is maintaining a negative pressure inside its enclosure and duct work.

13.3.2.2.7.4(A) (was 13.3.2.2.2.4(A))

12.3.2.8.5.5 (A) Mechanical ventilation may or may not be required – natural ventilation may be adequate (see 13.3.2.2.7.4(B) (was 13.3.2.2.2.4(B))) or other protection means may be used. This requirement only applies if mechanical ventilation is required.

“Power system” appears to be a left over from a “cut and paste”.

13.3.2.2.7.4(B) (was 13.3.2.2.2.4(B))

12.3.2.8.5.5 (B) Requirement is for “adequate” natural ventilation – see NFPA 497 and IEC 60079-10.

13.3.2.2.7.4(C) (was 13.3.2.2.2.4(C))

12.3.2.8.5.5 (C) Vents are typically exits or exhausts not inlets – see NFPA Glossary of Terms.

13.3.2.2.5 (original)

12.3.2.8.5.6

Exhausts are addressed in 13.3.2.3.2. And, Listed equipment (including exhausts) is already required to be installed in accordance with the Listing and manufacturer’s instruction per the Listing and 13.2.1.1.

13.3.2.2.5(A) (original)

12.3.2.8.3.2 This requirement is for gasifiers not reformers and is addressed in 13.3.3 (and its subsections).

13.3.2.2.5(A)(1) (original) 

12.3.2.8.3.2(1) See 13.3.2.2.5(A).

13.3.2.2.5(A)(2) (original) 

12.3.2.8.3.2(2) See 13.3.2.2.5(A).

13.3.2.2.3 (original)

12.3.2.8.5.7 Waste gases and venting include purged gases and are already addressed in 13.2.4 (5) and 13.3.2.3.2.

13.3.2.2.3(1) (original)

12.3.2.8.5.7(1) See 13.3.2.2.3 (original).

13.3.2.2.3(2) (original)

12.3.2.8.5.7(2) See 13.3.2.2.3 (original).

13.3.2.2.3(3) (original)

12.3.2.8.5.7(3) See 13.3.2.2.3 (original).

13.3.2.2.8.1 (was 13.3.2.2.4.1)

12.3.2.8.8.1 Combustible gas detectors are not always required. Since they tend to give a false sense of safety, they should only be installed when required. (They rarely get installed / located correctly and are very susceptible to drift and effects from the environment and require frequent calibration that is often neglected. In addition very few have circuitry that meets the requirement for the level of Functional Safety that should be applied.)

13.3.2.2.4.2 12.3.2.8.8.2 See 13.3.2.2.8.1. 13.3.2.3.2(A) 12.3.2.8.2.2 (A) If the concentration of flammable gas in the exhaust is less than 25% LFL, the exhaust is not

hazardous and there is no need for separation distances. If the exhaust is hazardous the requirements should be consistent with sections of this code, ex. Chapter 7. Rather than specify individual distances for operable and unopenable doors, windows, etc. and risk this section getting out of synch with the rest of the code again in the future, it’s more efficient to refer to 7.3.2.3.

Note: The original separation distance of 50 feet was greater than the worst case in Table 7.3.2.3.1.2(a). And, a reformer that is exhausting a flammable mixture of hydrogen is not performing very well and is probably not operating correctly. Enclosure ventilation exhausts are covered elsewhere and will be below 25% LFL or classified in accordance with NFPA 70 (see 13.2.6.2). So, there should be little if any hazard from hydrogen in the exhaust. There may be hazards from CO and possible other gases in the reformer exhaust but these are the same as other natural gas appliances. NFPA 54 only requires that chimneys be a certain height above buildings; the “worst” case is 10 feet higher than any portion of any building within 25 feet. My original thought was that Section 13.3.2.3.2be deleted. My next though was to change 13.3.2.3.2 to refer to Chapter 12 of NFPA 54. At a minimum it should be changed so that the required distance is ≤ Table 7.3.2.3.1.2(a). The final recommendation is a combination of these. Note: Referring to the concentration of flammable gas helps address the concern about what exhausts were intended to be addressed. It wasn’t clear if the original requirement was meant to apply to enclosure ventilation exhausts, vent stacks, etc. or just to the exhaust of reformer section of the hydrogen generator. With the new wording it doesn’t matter – they are all addressed and the manufacturer (or AHJ) only has to be concerned with the hazardous ones.

13.3.2.3.2(B) 12.3.2.8.2.2 (B) See 13.3.2.3.2 (A) above. 13.3.2.3.2(C) n/a See 13.3.2.3.2 (A) above. 13.3.2.3.3 12.3.2.8.2.3 “Process” air intakes implies only intakes for air being used in the reformer and might be

interpreted to not apply to ventilation, dilution, or air intakes that also should not be affected by exhausts, etc.

13.3.2.3.4 12.3.2.8.2.4 See 13.3.2.3.3 above. 13.3.2.4.1 12.3.2.8.7.1 FOR DISCUSSION:

NFPA 55 had no definition for “small” reformer based hydrogen generators. The smallest “size” in the rest of NFPA 55 that seemed appropriate was the MAQ of flammable gas for a control area (1000 scf in a closed system according to Table 6.3.1.1).

13.3.2.4.2.1 12.3.2.8.7.3(A) The requirements in 13.3.2.4.2 are not specific to “small” indoor reformers and seem applicable to all indoor reformers so, moved them to 13.3.2.2.2 – 13.3.2.2.6.

13.3.2.4.2.2 12.3.2.8.7.3(B) See 13.3.2.4.2.1. 13.3.2.4.2.3 12.3.2.8.7.3(C) See 13.3.2.4.2.1.

13.3.2.4.2.4 12.3.2.8.7.3(D) See 13.3.2.4.2.1. 13.3.2.4.2.4(1) 12.3.2.8.7.3(D)(1) See 13.3.2.4.2.1. 13.3.2.4.2.4(2) 12.3.2.8.7.3(D)(2) See 13.3.2.4.2.1. 13.3.2.4.2.4(3) 12.3.2.8.7.3(D)(3) See 13.3.2.4.2.1. 13.3.2.4.2.4(4) 12.3.2.8.7.3(D)(4) See 13.3.2.4.2.1. 13.3.2.4.2.4(5) 12.3.2.8.7.3(D)(5) See 13.3.2.4.2.1. 13.3.2.4.2.5 12.3.2.8.7.3 (E) See 13.2.4 re: Chapter 7.

Explanation from submittal to NFPA 55: Chapter 10 addresses Bulk Hydrogen Compressed Gas Systems. Section 10.1.1 specifically states that Chapter 10 does not apply to systems with total hydrogen content of less than 5000 scf. Hydrogen generators (generally) contain much less than 5000 scf and are exempt from Chapter 10.

13.3.2.4.2.6 12.3.2.8.7.3 (F) See 13.3.2.1.2. Didn’t make sense in NFPA 55: The fire protection requirements of Chapter 10 are for storage not hydrogen generators. Since Chapter 10 does not apply an exemption is not needed. May be OK in NFPA 2.

13.3.2.4.3.1 12.3.2.8.7.2(A) This is the same as for “large” reformer based hydrogen generators and does not need to be repeated here. See also the changes to 13.3.2.2.2 – 13.3.2.2.6 and 13.3.2.4.2.1 - 13.3.2.4.2.4(5).

13.3.2.4.3.2 12.3.2.8.7.2(B) See 13.3.2.4.3.1.

 

First Revision No. 111-NFPA 2-2013 [ Section No. 13.4.1 ]

13.4.1 Requirements for Hydrogen Storage Systems Serving Electrolyzer Installations. (Reserved)

The requirements of this section addressing hydrogen storage systems serving electrolyzer installationsare supplemental to those specified by Section 13.2 and 13.3.1 .

13.4.1.1

In residential applications, the electrolyzer installation shall be in accordance with the equipment listingand the manufacturer's instructions.

13.4.1.2

Hydrogen piping, valves, and fittings from the electrolyzer to the hydrogen storage system shall be inaccordance with ASME B31.12, Hydrogen Piping and Pipelines .

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 16:48:44 EDT 2013

Committee Statement

CommitteeStatement:

This previously reserved section proposes supplemental code language to allow residential use ofstorage in accordance with section 13.2 and 13.3.1, requiring listed electrolyzers with manufacturer'sinstructions.

Piping between the electrolyzer and storage contains high purity hydrogen, so ASME B31.12 is theappropriate piping standard to apply.

The proposed public input is provided to address those sections designated as reserved in the 2011Edition of the code is a product of a combined effort assigned to the members of the technicalcommittee and a task group designated as the Reserved Sections Task Group.

The term reserved is normally used by a technical committee to recognize that the committee thatdeveloped the material has an awareness that there is a need in the subject area identified, but didnot feel that there was time available during the initial document development process or that therewas a need for additional justification to create requirements on the subject for any number ofreasons, including: 1) a lack of existing data, 2) a limited amount of applied practices in the field, or 3)an inability to reach consensus.

During the development of the first edition of NFPA 2 a template approach was used to structure eachof the fundamental, occupancy or use specific Chapters where text may have been extracted fromexisting source documents where a condition raised by the outline was not addressed by the sourcedocument. In these instances the term reserved was used to bring the matter to the attention of thecommittee so that future consideration would be given to the development of requirements. Forexample, in Chapter 10, Section 10.3.1.3.4 was reserved to establish requirements for the use of“Composite Containers, Cylinders and Tanks” as it was recognized that although such tanks areencountered in practice, and requirements for their use are unspecified at this time. The reserveddesignation for this subject keeps attention on the issue until such time as consensus is reached bythe committee on the need, the content, or input from members of the public at large.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

379 of 491 1/30/2014 9:30 AM

ResponseMessage:

Public Input No. 85-NFPA 2-2012 [Section No. 13.4.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

380 of 491 1/30/2014 9:30 AM

First Revision No. 528-NFPA 2-2013 [ Section No. 13.4.2 ]

13.4.2 Requirements for Hydrogen Storage Systems Serving Reformer Installations.

13.4.2.1 General.

13.4.2.1.1

An accessible shutoff valve shall be located in the fuel piping to the catalytic reforming–based hydrogengeneration system’s power system within 6 ft (1.8 m) of the storage container. [ 55: 12.3.2.8.4.3]

13.4.2.1.2

The fuel piping to the catalytic reforming–based hydrogen generation system’s power system shall beprovided with a second accessible shutoff valve that is located within 6 ft (1.8 m) of the power system,unless the power system is enclosed by a room with a 1-hour fire resistance rating. [ 55: 12.3.2.8.4.4]

13.4.2.1.3

If the power system is enclosed by a room with a 1-hour fire resistance rating, the shutoff valve shall belocated outside the room. [ 55: 12.3.2.8.4.5]

13.4.2.1.4

Piping, valves, regulators, or other equipment shall be located so that it is not subject to physicaldamage or shall otherwise be protected against physical damage. [ 55: 12.3.2.8.4.7]

13.4.2.1.5

Backflow prevention shall be provided to preclude inducing external atmospheres into the catalyticreforming systems. [ 55: 12.3.2.8.4.8]

13.4.2.2 Indoor Storage. (Reserved)

13.4.2.3 Outdoor Storage.

13.4.2.3.1 Outdoor Storage Supplying an Indoor Reformer Installation.

(A)

For indoor installation of a reforming system, where the fuel supply is stored outdoors, an automaticshutoff valve interlocked with gas detection shall be located outside the building that houses the powersystem. [ 55: 12.3.2.8.4.6(A)]

(B)

The valve and the detector shall be installed such that the valve will close upon detection of aconcentration of greater than 25 percent LFL.[ 55: 12.3.2.8.4.6(B)]

Supplemental Information

File Name Description

Justification_for_FR_528_Section_13.4.2.docx

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 18 15:29:49 EST 2013

Committee Statement

Committee Statement: See attached file for substantiation for FR

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

381 of 491 1/30/2014 9:30 AM

13.4.2.1.1 12.3.2.8.4.3 Shut off valves for reformers using natural gas, etc. are addressed in NFPA 54, etc. and these are referenced in 13.3.2.2.2 and 13.3.2.3.2. Note: NFPA 2 may need a more general reference to NFPA 54 for reformers.

13.4.2.1.2 12.3.2.8.4.4 See 13.4.2.1.1 above. 13.4.2.1.3 12.3.2.8.4.5 See 13.4.2.1.1 above. 13.4.2.1.4  12.3.2.8.4.7 “Other equipment” is too vague – could mean any equipment. Added word “related” to try to

keep it to piping related components. See also 13.4.2.1.5.

13.4.2.1.5  12.3.2.8.4.8 FOR DISCUSSION:

Just move to Installation section and make whole Storage section reserved (or delete). 

13.4.2.3.1 n/a See 13.4.2.3.1(A). 13.4.2.3.1(A) 12.3.2.8.4.6(A) Indoor installation of reformer based generators is already addressed in 13.3.2.2. And, these

requirements do not belong in the “Piping” section, 12.3.2.8.4. (The last comment was based on the NFPA 55 draft – may not apply to NFPA 2.)

 

First Revision No. 529-NFPA 2-2013 [ Section No. 13.4.3 ]

13.4.3 Requirements for Hydrogen Storage Systems Serving Gasifier Installations. (Reserved)

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 18 15:33:46 EST 2013

Committee Statement

Committee Statement: See info for FR 528

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

382 of 491 1/30/2014 9:30 AM

First Revision No. 115-NFPA 2-2013 [ Section No. 14.1 [Excluding any Sub-Sections] ]

This chapter shall apply to equipment that uses hydrogen as a process gas or as a combustion fuelsource for combustion fuel to provide heat used for the processing of materials and related equipment. .

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 17:06:10 EDT 2013

Committee Statement

Committee Statement: Improved clarity of the chapter scope, text similar to that found in NFPA 86:1.1

Response Message:

Public Input No. 55-NFPA 2-2012 [Section No. 14.1 [Excluding any Sub-Sections]]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

383 of 491 1/30/2014 9:30 AM

First Revision No. 116-NFPA 2-2013 [ Section No. 14.1.1 [Excluding any Sub-Sections] ]

The requirements of this chapter shall apply to the use of GH2 as part of a manufacturing process using

thermal spraying or as a fuel in heating applications. This chapter shall apply to new installations and toalterations or extensions to existing equipment. The storage, use, and handling of GH2 in any quantity

shall also comply with the requirements of Chapters 1 through 4 and the applicable requirements ofChapters 5 through 8.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 17:09:30 EDT 2013

Committee Statement

CommitteeStatement:

Assure modifications to existing equipment are completed in compliance with this Code, textsimilar to that found in NFPA 86:1.3.1

ResponseMessage:

Public Input No. 56-NFPA 2-2012 [Section No. 14.1.1 [Excluding any Sub-Sections]]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

384 of 491 1/30/2014 9:30 AM

First Revision No. 153-NFPA 2-2013 [ Section No. 14.3.2 ]

14.3.2 Heating Applications. [Reserved]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jun 18 15:18:08 EDT 2013

Committee Statement

Committee Statement: See PI #57 for changes to the reserved section for this chapter.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

385 of 491 1/30/2014 9:30 AM

First Revision No. 117-NFPA 2-2013 [ Section No. 16.3.2 ]

16.3.2 Indoor Dispensing Use .

16.3.2.1 Laboratory Ventilating Systems and Hood Requirements.

16.3.2.1.1* General.

16.3.2.1.1.1

This chapter shall apply to laboratory exhaust systems, including chemical fume hoods, special localexhaust devices, and other systems for exhausting air from laboratory work areas in which [GH2 or LH2]

are released. [45:8.1.1]

16.3.2.1.1.2

This chapter shall apply to laboratory air supply systems and shall provide requirements for identification,inspection, and maintenance of laboratory ventilation systems and hoods. [45:8.1.2]

16.3.2.1.2 Basic Requirements.

16.3.2.1.2.1*

Laboratory ventilation systems shall be designed to ensure that fire hazards and risks are minimized.[45:8.2.1]

16.3.2.1.2.2*

Laboratory units and laboratory hoods in which [GH2 or LH2] are present shall be continuously ventilated

under normal operating conditions. [45:8.2.2]

16.3.2.1.2.3*

Chemical fume hoods shall not be relied upon to provide explosion (blast) protection unless specificallydesigned to do so. (See also G.5.4 and G.5.5 for further information on explosion-resistant hoods andshields.) [45:8.2.3]

16.3.2.1.2.4

Exhaust and supply systems shall be designed to prevent a pressure differential that would impede egressor ingress when either system fails or during a fire or emergency scenario. This design includes reducedoperational modes or shutdown of either the supply or exhaust ventilation systems. [45:8.2.5]

16.3.2.1.2.5

The release of [GH2] into the laboratory shall be controlled by enclosure(s) or captured to prevent any

flammable concentrations of vapors from reaching any source of ignition. [45:8.2.6]

16.3.2.1.3 Supply Systems.

16.3.2.1.3.1

Laboratory ventilation systems shall be designed to ensure that [GH2] originating from the laboratory shall

not be recirculated. [45:8.3.1]

16.3.2.1.3.2*

The location and configuration of fresh air intakes shall be chosen so as to avoid drawing in [GH2] or

products of combustion coming either from the laboratory building itself or from other structures anddevices. [45:8.3.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

386 of 491 1/30/2014 9:30 AM

16.3.2.1.3.3

The air pressure in the laboratory work areas shall be negative with respect to corridors andnon-laboratory areas of the laboratory unit except in the following instances: [45:8.3.3]

(1) Where operations such as those requiring clean rooms preclude a negative pressure relative tosurrounding areas, alternate means shall be provided to prevent escape of the atmosphere in thelaboratory work area or unit to the surrounding spaces. [45:8.3.3(1)]

(2) The desired static pressure level with respect to corridors and non-laboratory areas shall bepermitted to undergo momentary variations as the ventilation system components respond to dooropenings, changes in chemical fume hood sash positions, and other activities that can for a shortterm affect the static pressure level and its negative relationship. [45:8.3.3(2)]

(3) Laboratory work areas located within a designated electrically classified hazardous area with apositive air pressure system as described in NFPA 496,Standard for Purged and PressurizedEnclosures for Electrical Equipment , Chapter 7, Pressurized Control Rooms, shall be permitted tobe positive with respect to adjacent corridors. [45:8.3.3(3)]

16.3.2.1.3.4*

The location of air supply diffusion devices shall be chosen so as to avoid air currents that wouldadversely affect the performance of chemical fume hoods, exhaust systems, and fire detection orextinguishing systems. (See 16.2.3.1, 16.2.3.2, and 16.3.2.1.8.1.) [45:8.3.4]

16.3.2.1.4 Exhaust Air Discharge.

16.3.2.1.4.1*

Air exhausted from chemical fume hoods and other special local exhaust systems shall not berecirculated. (See also 16.3.2.1.3.1.) [45:8.4.1]

16.3.2.1.4.2* Energy Conservation Devices.

(A)

If energy conservation devices are used, they shall be designed in accordance with 16.3.2.1.3.1 through16.3.2.1.3.3. [45:8.4.2.1]

(B)

Devices that could result in recirculation of exhaust air or exhausted contaminants shall not be usedunless designed in accordance with Section 4:10.1, “Nonlaboratory Air,” and Section 4:10.2, “GeneralRoom Exhaust,” of ANSI/AIHA Z9.5, Laboratory Ventilation. [45:8.4.2.2]

16.3.2.1.4.3

Air exhausted from laboratory work areas shall not pass unducted through other areas. [45:8.4.3]

16.3.2.1.4.4*

Air from laboratory units and laboratory work areas in which [GH2] is present shall be continuously

discharged through duct systems maintained at a negative pressure relative to the pressure of normallyoccupied areas of the building. [45:8.4.4]

16.3.2.1.4.5

Positive pressure portions of the lab hood exhaust systems (e.g., fans, coils, flexible connections, andductwork) located within the laboratory building shall be sealed airtight or located in a continuouslymechanically ventilated room. [45:8.4.5]

16.3.2.1.4.6

Chemical fume hood face velocities and exhaust volumes shall be sufficient to contain [GH2] generated

within the hood and exhaust them outside of the laboratory building. [45:8.4.6]

16.3.2.1.4.7*

The hood shall provide containment of the possible hazards and protection for personnel at all times when[GH2 is] present in the hood. [45:8.4.7]

16.3.2.1.4.8

Special local exhaust systems, such as snorkels or “elephant trunks,” shall have sufficient capturevelocities to entrain the [GH2] being released. [45:8.4.8]

16.3.2.1.4.9*

Canopy hoods shall not be used in lieu of chemical fume hoods. [45:8.4.9]

16.3.2.1.4.10

Laminar flow cabinets shall not be used in lieu of chemical fume hoods. [45:8.4.11]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

387 of 491 1/30/2014 9:30 AM

16.3.2.1.4.11*

Air exhausted from chemical fume hoods and special exhaust systems shall be discharged above the roofat a location, height, and velocity sufficient to prevent re-entry of chemicals and to prevent exposures topersonnel. [45:8.4.12]

16.3.2.1.5 Duct Construction for Hoods and Local Exhaust Systems.

16.3.2.1.5.1*

Ducts from chemical fume hoods and from local exhaust systems shall be constructed entirely ofnoncombustible materials except in the following cases:

(1) Flexible ducts of combustible construction shall be permitted to be used for special local exhaustsystems within a laboratory work area. (See 16.3.2.1.5.2.)

(2) Combustible ducts shall be permitted to be used if enclosed in a shaft of noncombustible or limited-combustible construction where they pass through non-laboratory areas or through laboratory unitsother than the one they serve. (See 16.3.2.1.5.2.)

(3) Combustible ducts shall be permitted to be used if all areas through which they pass are protectedwith an approved automatic fire extinguishing system, as described in 16.2.3. (See 16.3.2.1.5.2.)[45:8.5.1]

16.3.2.1.5.2

Combustible ducts or duct linings shall have a flame spread index of 25 or less when tested in accordancewith ASTM E 84 Standard Test Method for Surface Burning Characteristics of Building Materials , orANSI/UL 723, . T Standard for Test for Surface Burning Characteristics of Building Materials . Testspecimens shall be of the minimum thickness used in the construction of the duct or duct lining. [45:8.5.2]

16.3.2.1.5.3

Ducts shall be of adequate strength and rigidity to meet the conditions of service and installationrequirements and shall be protected against mechanical damage. [45:8.5.5]

16.3.2.1.5.4

Materials used for vibration isolation connectors shall comply with 16.3.2.1.5.2. [45:8.5.6]

16.3.2.1.5.5

Controls and dampers, where required for balancing or control of the exhaust system, shall be of a typethat, in event of failure, will fail open to ensure continuous draft. (See 16.3.2.1.9.3 through 16.3.2.1.9.5.)[45:8.5.8]

16.3.2.1.5.6

Hand holes, where installed for damper, sprinkler, or fusible link inspection or resetting and for residueclean-out purposes, shall be equipped with tight-fitting covers provided with substantial fasteners.[45:8.5.9]

16.3.2.1.5.7 Manifolding of Chemical Fume Hood and Ducts.

(A)

Exhaust ducts from each laboratory unit shall be separately ducted to a point outside the building, to amechanical room, or to a shaft. [ 45: 8.5.10.1]

(B)

Penetrations through fire-rated floor/ceiling, floor, and wall assemblies shall be protected in accordancewith NFPA 101 , Life Safety Code the adopted building code . [ 45: 5.1.5]

(C)

Connection to a common chemical fume hood exhaust duct system shall be permitted to occur within abuilding only in any of the following locations: [45:8.5.10.2]

(1) Mechanical room not greater than 10,000 ft2 (930 m2) protected with sprinklers and having 2– hourfire resistant walls [ 45: 8.5.10.2(1)]

(2) Shaft protected in accordance with the chapter for protection of vertical openings of NFPA 101, LifeSafety Code [45:8.5.10.2(2)]

(3) A point outside the building [45:8.5.10.2(3)]

(D)

Exhaust ducts from chemical fume hoods and other exhaust systems within the same laboratory unit shallbe permitted to be combined within that laboratory unit. (See 16.3.2.1.4.1.) [45:8.5.10.3]

16.3.2.1.6 Exhausters (Fans), Controls, Velocities, and Discharge.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

388 of 491 1/30/2014 9:30 AM

16.3.2.1.6.1

Fans shall be selected to meet requirements for fire, explosion, and corrosion. [45:8.7.1]

16.3.2.1.6.2

Fans conveying both corrosive and flammable or combustible materials shall be permitted to be lined withor constructed of corrosion-resistant materials having a flame spread index of 25 or less when tested inaccordance with ASTM E 84, Standard Test Method for Surface Burning Characteristics of BuildingMaterials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials.[45:8.7.2]

16.3.2.1.6.3

Fans shall be located and arranged so as to afford ready access for repairs, cleaning, inspection, andmaintenance. [45:8.7.3]

16.3.2.1.6.4*

Where [GH2 is] passed through the fans, the rotating element shall be of nonferrous or spark-resistant

construction; alternatively, the casing shall be constructed of or lined with such material. [45:8.7.4]

(A)

Nonferrous or spark-resistant materials shall have a flame spread index of 25 or less when tested inaccordance with ASTM E 84, Standard Test Method for Surface Burning Characteristics of BuildingMaterials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials.[45:8.7.4.2]

16.3.2.1.6.5

Motors and their controls shall be located outside the location where [GH2 is] generated or conveyed,

unless specifically approved for that location and use. [45:8.7.5]

16.3.2.1.6.6*

Fans shall be marked with an arrow or other means to indicate direction of rotation and with the location ofchemical fume hoods and exhaust systems served. [45:8.7.6]

16.3.2.1.7 Chemical Fume Hood Construction.

(See also 16.3.2.1.2.2) [45:8.8]

16.3.2.1.7.1 Chemical Fume Hood Interiors.

(A)*

Materials of construction used for the interiors of new chemical fume hoods or for the modification of theinteriors of existing chemical fume hoods shall have a flame spread index of 25 or less when tested inaccordance with ASTM E 84, Standard Test Method for Surface Burning Characteristics of BuildingMaterials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials,unless the interior of the hood is provided with automatic fire protection in accordance with 16.3.2.1.9.2.[45:8.8.1.1]

(B)*

Baffles shall be constructed so that they are unable to be adjusted to materially restrict the volume of airexhausted through the chemical fume hood. [45:8.8.1.2]

(C)*

Chemical fume hoods shall be provided with a means of preventing overflow of a spill of 0.5 gal (2 L) ofliquid. [45:8.8.1.3]

16.3.2.1.7.2* Chemical Fume Hood Sash Glazing.

The sash, if provided, shall be glazed with material that will provide protection to the operator against thehazards associated with the use of the hood. (See also Annex G.) [45:8.8.2]

16.3.2.1.7.3* Chemical Fume Hood Sash Closure.

(A)

Chemical fume hood sashes shall be kept closed whenever possible. [45:8.8.3.1]

(B)

When a fume hood is unattended, its sash shall remain fully closed. [45:8.8.3.2]

16.3.2.1.7.4* Electrical Devices.

(A)

In installations where services and controls are within the hood, additional electrical disconnects shall belocated within 50 ft (15 m) of the hood and shall be accessible and clearly marked. [45:8.8.4.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

389 of 491 1/30/2014 9:30 AM

(B)

If electrical receptacles are located external to the hood, no additional electrical disconnect shall berequired. [45:8.8.4.2]

16.3.2.1.7.5 Other Hood Services.

(A)

For new installations or modifications of existing installations, controls for chemical fume hood services(gas, air, water, etc.) shall be located external to the hood and within easy reach. [45:8.8.5.1]

(B)

In existing installations where service controls are within the hood, additional shutoffs shall be locatedwithin 50 ft (15 m) of the hood and shall be accessible and clearly marked. [45:8.8.5.2]

16.3.2.1.7.6 Auxiliary Air.

For auxiliary air hoods, auxiliary air shall be introduced exterior to the hood face in such a manner that theairflow does not compromise the protection provided by the hood and so that an imbalance of auxiliary airto exhaust air will not pressurize the hood interior. [45:8.8.6]

16.3.2.1.7.7 Measuring Device for Hood Airflow.

(A)

A measuring device for hood airflow shall be provided on each chemical fume hood. [45:8.8.7]

(B)

The measuring device for hood airflow shall be a permanently installed device. [45:8.8.7.1]

(C)

The measuring device for hood airflow shall provide constant indication to the hood user of adequate orinadequate hood airflow. [45:8.8.7.2]

16.3.2.1.8 Chemical Fume Hood Location.

16.3.2.1.8.1*

Chemical fume hoods shall be located in areas of minimum air turbulence. [45:8.9.1]

16.3.2.1.8.2

Chemical fume hoods shall not be located adjacent to a single means of access to an exit or to high-trafficareas. [45:8.9.2]

16.3.2.1.8.3*

Work stations not directly related to the chemical fume hood activity shall not be located directly in front ofchemical fume hood openings. [45:8.9.3]

16.3.2.1.9 Chemical Fume Hood Fire Protection.

16.3.2.1.9.1

Automatic fire protection systems shall not be required in chemical fume hoods or exhaust systems exceptin the following cases: [45:8.10.1]

(1) If a hazard assessment shows that an automatic extinguishing system is required for the chemicalfume hood, then the applicable automatic fire protection system standard shall be followed.[45:8.10.1(2)]

16.3.2.1.9.2

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

390 of 491 1/30/2014 9:30 AM

Automatic fire protection systems, where provided, shall comply with the following standards, asapplicable:

(1) NFPA 11, Standard for Low-, Medium-, and High-Expansion Foam

(2) NFPA 12, Standard on Carbon Dioxide Extinguishing Systems

(3) NFPA 12A, Standard on Halon 1301 Fire Extinguishing Systems

(4) NFPA 13, Standard for the Installation of Sprinkler Systems

(5) NFPA 15, Standard for Water Spray Fixed Systems for Fire Protection

(6) NFPA 17, Standard for Dry Chemical Extinguishing Systems

(7) NFPA 17A, Standard for Wet Chemical Extinguishing Systems

(8) NFPA 69, Standard on Explosion Prevention Systems

(9) NFPA 750, Standard on Water Mist Fire Protection Systems

(10)

[ 45: 8.10.2]

(A)

The fire extinguishing system shall be suitable to extinguish fires within the chemical fume hood under theanticipated conditions of use. [45:8.10.2.1]

16.3.2.1.9.3

The design and installation of ducts from chemical fume hoods shall be in accordance with NFPA 91,Standard for Exhaust Systems for Air Conveying of Vapors, Gases, Mists, and NoncombustibleParticulate Solids , except that specific requirements in NFPA 45 shall take precedence. [45:8.10.3]

(A)*

Automatic fire dampers shall not be used in chemical fume hood exhaust systems. [45:8.10.3.1]

16.3.2.1.9.4

Fire detection and alarm systems shall not be interlocked to automatically shut down chemical fume hoodexhaust fans. [45:8.10.4]

16.3.2.1.9.5

Proper door operation for egress shall be maintained when the supply system shuts down and the labexhaust system operates, creating a pressure differential. [45:8.10.5]

16.3.2.1.9.6

Chemical fume hoods equipped with control systems that vary the hood exhaust airflow as the sashopening varies and/or in conjunction with whether the laboratory room is in use (occupied or unoccupied)shall be equipped with a user-accessible means to attain maximum exhaust hood airflow regardless ofsash position when necessary or desirable to ensure containment and removal of a potential hazard withinthe hood. [45:8.10.6]

16.3.2.1.9.7*

Chemical fume hoods shall be installed in a manner that prevents fire or smoke from a fire in the chemicalfume hood from spreading into the voids above the ceiling. [45:8.10.7]

16.3.2.1.10 Identification of Chemical Fume Hood Systems.

16.3.2.1.10.1*

Special-use chemical fume hoods and special-use local exhaust systems shall be identified to indicatetheir intended use. [45:8.12.1]

16.3.2.1.10.2

A sign containing the following information from the last inspection shall be affixed to each hood, or aproperly maintained log of all hoods providing the following information shall be maintained:

(1) Inspection interval

(2) Last inspection date

(3) Average face velocity

(4) Location of fan that serves hood

(5) Inspector’s name

[ 45: 8.12.2]

* NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

391 of 491 1/30/2014 9:30 AM

16.3.2.1.11 Inspection, Testing, and Maintenance.

16.3.2.1.11.1*

When installed or modified and at least annually thereafter, chemical fume hoods, chemical fume hoodexhaust systems, and laboratory special exhaust systems shall be inspected and tested as applicable, asfollows:

(1) Visual inspection of the physical condition of the hood interior, sash, and ductwork

(2) Measuring device for hood airflow

(3) Low airflow and loss-of-airflow alarms at each alarm location

(4) Face velocity

(5) Verification of inward airflow over the entire hood face

(6) Changes in work area conditions that might affect hood performance

[ 45: 8.13.1]

16.3.2.1.11.2

Deficiencies in hood performance shall be corrected, or one of the following shall apply:

(1) The activity within the hood shall be restricted to the capability of the hood.

(2) The hood shall not be used. [45:8.13.2]

16.3.2.1.11.3

Chemical fume hood face velocity profile or hood exhaust air quantity shall be checked after anyadjustment to the ventilation system balance. [45:8.13.3]

16.3.2.1.11.4 Detectors and Alarms.

Air system flow detectors, if installed, shall be inspected and tested annually. [45:8.13.4.1]

16.3.2.1.11.5 Fans and Motors.

(A)*

Air supply and exhaust fans, motors, and components shall be inspected at least annually. [45:8.13.5.1]

(B)

Where airflow detectors are not provided or airflow-rate tests are not made, fan belts shall be inspectedquarterly; double sheaves and belts shall be permitted to be inspected semiannually. [45:8.13.5.2]

(C)

Frayed or broken belts shall be replaced promptly. [45:8.13.5.3]

16.3.2.2 Laboratory Operations and Apparatus.

16.3.2.2.1 Operations.

16.3.2.2.1.1* Hazards of Chemicals and Chemical Reactions.

(A)

Before laboratory tests or chemical reactions are begun, evaluations shall be made for hazards that canbe encountered or generated during the course of the work. [45:12.1.1.1]

(B)

Evaluations shall include the hazards associated with the properties and the reactivity of the materialsused and any intermediate and end products that can be formed, hazards associated with the operation ofthe equipment at the operating conditions, and hazards associated with the proposed reactions — forexample, oxidation and polymerization. [See also 16.3.2.2.1.1(D).] [45:12.1.1.2]

(C)

Regular reviews of laboratory operations and procedures shall be conducted with special attention givento any change in materials, operations, or personnel. [45:12.1.1.3]

(D)*

Where reactions are being performed to synthesize materials, the hazard characteristics of which havenot yet been determined by test, precautions shall be employed to control the highest possible hazardbased on a known hazard of similar material. [45:12.1.1.4]

(E)

Where use of a new material might present a severe explosion potential, initial experiments or tests shallbe conducted in an enclosure that is designed to protect people and property from potential explosiondamage. (See 16.2.4.) [45:12.1.1.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

392 of 491 1/30/2014 9:30 AM

(F)

Unattended or automatic laboratory operations involving hazardous chemicals shall be provided withregular surveillance for abnormal conditions. [45:12.1.1.6]

(1) Unattended operations shall be provided with override control and automatic shutdown to preventsystem failure that can result in fire or explosion. [45:12.1.2.4]

(2) Electrically heated constant temperature baths shall be equipped with over-temperature shutoffswitches in addition to normal temperature controls, if overheating could result in a fire or anexplosion. [45:12.2.4.1]

16.3.2.2.1.2 Other Operations.

(A)

Other laboratory operations, such as reactions at temperatures and pressures either above or belowambient conditions, shall be conducted in a manner that minimizes hazards. [45:12.1.6.1]

(B)

Shielding shall be used whenever there is a reasonable probability of explosion or vigorous chemicalreaction and associated hazards during charging, sampling, venting, and discharge of products. (See16.2.4 and 16.3.2.2.2.3.) [45:12.1.6.2]

(C)

Glass apparatus containing gas or vapors under vacuum or above ambient pressure shall be shielded,wrapped with tape, or otherwise protected from shattering (such as engineering controls or by apparatusdesign) during use. [45:12.1.6.3]

(D)*

Quantities of reactants shall be limited and procedures shall be developed to control or isolate vigorous orexothermic reactions. [45:12.1.6.4]

(E)

[GH2] evolved during drying operations shall be condensed, trapped, or vented to avoid ignition.

[45:12.1.6.5]

16.3.2.2.2 Apparatus.

16.3.2.2.2.1 General.

(A)

Apparatus shall be installed in compliance with applicable requirements of NFPA standards, includingNFPA 70, National Electrical Code . [45:12.2.1.1]

(B)

Operating controls shall be accessible under normal and emergency conditions. [45:12.2.1.2]

16.3.2.2.2.2 Heating Equipment.

(A)

All unattended electrical heating equipment shall be equipped with a manual reset over-temperatureshutoff switch, in addition to normal temperature controls, if overheating could result in a fire or explosion.[45:12.2.3.1]

(B)

Heating equipment with circulation fans or water cooling shall be equipped with an interlock arranged todisconnect current to the heating elements if the fan fails or the water supply is interrupted. [45:12.2.3.2]

(C)

Burners, induction heaters, ovens, furnaces, and other heat-producing equipment shall be located a safedistance from areas where temperature-sensitive and flammable materials and [GH2] are handled.

[45:12.2.3.3]

(D)

Oven and furnace installations shall comply with NFPA 86, Standard for Ovens and Furnaces .[45:12.2.3.4]

16.3.2.2.2.3 Pressure Equipment.

(A)*

Equipment used at pressures above 15 psi (103 kPa gauge) shall be designed and constructed byqualified individuals for use at the expected temperature, pressure, and other operating conditionsaffecting safety. [45:12.2.5.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

393 of 491 1/30/2014 9:30 AM

(B)

Pressure equipment shall be fitted with a pressure relief device, such as a rupture disc or a relief valve.The pressure relief device shall be vented to a safe location. [45:12.2.5.2]

(C)

Equipment operated at pressures above 15 psi (103 kPa gauge), such as autoclaves, steam sterilizers,reactors, and calorimeters, shall be operated and maintained according to manufacturers’ instructions, thedesign limitations of the equipment, and applicable codes and regulations. [45:12.2.5.3]

(1) Such equipment shall be inspected on a regular basis. [45:12.2.5.3.1]

(2) Any significant change in the condition of the equipment, such as corrosion, cracks, distortion, scaleformation, or general chemical attack, or any weakening of the closure, or any inability of theequipment to maintain pressure, shall be documented and removed from service immediately andshall not be returned to service until approved by a qualified person. [45:12.2.5.3.2]

(D)

Any pressure equipment that has been found to be degraded shall be derated or discarded, whichever isappropriate. [45:12.2.5.4]

16.3.2.2.2.4 Analytical Instruments.

(A)

Analytical instruments, such as infrared, ultraviolet, atomic absorption, x-ray, mass spectrometers,chromatographs, and thermal analyzers, shall be installed in accordance with the manufacturers’instructions and applicable standards and codes. [45:12.2.6.1]

(B)

Analytical instruments shall be operated in accordance with manufacturers’ instructions or approvedrecommended operating procedures. [45:12.2.6.2]

(C)

Hazards to personnel from high voltage, vapors or fumes, radiation, flames, flashbacks, and explosionsshall be minimized. [45:12.2.6.3]

16.3.2.3 Hazard Identification.

16.3.2.3.1* Exhaust Systems.

Exhaust systems used for the removal of hazardous materials shall be identified to warn personnel of thepossible hazards. [45:13.2]

16.3.2.3.2 Identification Systems.

Graphic systems used to identify hazards shall comply with ANSI Z535.1, Safety Color Code; ANSIZ535.2, Environmental and Facility Safety Signs; ANSI Z535.3, Criteria for Safety Symbols; and ANSIZ535.4, Product Safety Signs and Labels; or other approved graphic systems. [45:13.4]

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 17:14:47 EDT 2013

Committee Statement

CommitteeStatement:

The section title is changed to be consistent with 16.3 and the templated approach usedthroughout the document.

ResponseMessage:

Public Input No. 47-NFPA 2-2012 [Section No. 16.3.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

394 of 491 1/30/2014 9:30 AM

First Revision No. 119-NFPA 2-2013 [ Chapter 17 ]

Chapter 17 Parking Garages (Reserved)

17.1 Scope.

This chapter shall apply to open and enclosed parking garages used to store self-propelled vehiclespowered by GH 2 or LH 2 . This chapter shall also apply to storage of self-propelled vehicles powered

by GH 2 or LH 2 within the residential garages of one- and two-family dwellings.

17.1.1 Application.

This chapter shall apply to buildings and parking structures that store self-propelled vehicles powered byGH 2 or LH 2 . This chapter does not apply to dispensing of GH 2 or LH 2 or to storage or use of

GH 2 or LH 2 in parking garages.

17.1.2

Storage or use of GH 2 or LH 2 other than within the fuel and propulsion systems of vehicles being

stored shall not be allowed unless specifically approved by the AHJ.

17.2* Parking Garages.

17.2.1

The storage of self-propelled vehicles powered by GH 2 or LH 2 in parking garages or residential

garages associated with one- or two-family dwellings shall be subject to the same requirementsapplicable to vehicles powered by traditional fuels.

Supplemental Information

File Name Description

FR_119_Annex_Material.docx

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 17:38:23 EDT 2013

Committee Statement

CommitteeStatement:

This public input provides content for the ParkingGarages chapter where none previously existed.This text was developed jointly by the NFPA Task Group on Parking Garages. Essentially, this textrecognizes the fact (proved by fire testing) that fuel cell electric vehicles (FCEVs) pose no greaterhazard to fire spread than do vehicles fueled by conventional liquid fuels (i.e. gasoline and dieselfuel). By simply referring to the existing content of fire and building codes for the requirementsrelative to parking garages this chapter assures the reader that no additional requirements arewarranted for a parking garage (existing or new) if FCEVs are parked within.

The conclusion that FCEVs have similar fire spread characteristics to regular vehicles issubstantiated by the following report: THE SPREAD OF FIRE FROM ADJOINING VEHICLES TO AHYDROGEN FUEL CELL VEHICLE byTamura,Y.1, Takabayashi, M.1 ,Takeuchi,M.1 and Mitsuishi,H.1 1 FC-EV Research Division, Japan Automobile Research Institute, 1328-23,Takaheta, Osaka ,Shirosato, Ibaraki , 311-4316, Japan. A PDF version of this report has been attached.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

395 of 491 1/30/2014 9:30 AM

ResponseMessage:

Public Input No. 25-NFPA 2-2012 [Chapter 17]

Public Input No. 100-NFPA 2-2013 [Chapter 17]

Public Input No. 124-NFPA 2-2013 [Chapter 17]

Public Input No. 125-NFPA 2-2013 [Chapter 17]

Public Input No. 126-NFPA 2-2013 [Chapter 17]

Public Input No. 127-NFPA 2-2013 [Chapter 17]

Public Input No. 211-NFPA 2-2013 [New Section after 16.4.3.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

396 of 491 1/30/2014 9:30 AM

 FR 119 Annex Material  

A.17.2 The requirements for indoor parking of vehicles are located within the building and fire prevention codes adopted within a jurisdiction.

The fire hazard presented by self-propelled vehicles powered by GH2 or LH2 is sufficiently similar to those presented by vehicles fueled by liquid gasoline or diesel fuel that no additional requirements are warranted. Studies (add reference to paper 153) and fire tests performed have concluded that the combustible components common to all types of automobiles can cause a vehicle fire to spread from one parked vehicle to an adjacent one but that the presence or release of hydrogen (such as through activation of a thermal pressure relief device) is not a major cause of fire spread.

 

First Revision No. 120-NFPA 2-2013 [ Chapter 18 ]

Chapter 18 Road Tunnels (Reserved)

18.1

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 17:41:58 EDT 2013

Committee Statement

Committee Statement: This chapter has no content and should be deleted.

Response Message:

Public Input No. 121-NFPA 2-2013 [Chapter 18]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

397 of 491 1/30/2014 9:30 AM

First Revision No. 121-NFPA 2-2013 [ Chapter 19 ]

Chapter 18 Repair Garage (Reserved)

18.1 Scope

This chapter shall apply to buildings and structures used for service and repair operations in connectionwith self-propelled vehicles (including, but not limited to, passenger automobiles, buses, trucks andtractors) in which GH 2 or LH 2 is used.

18.2 Applicability.

This chapter shall apply to service and repair operations in connection with self-propelled vehiclespowered by GH 2 or LH 2 . The storage, use, and handling of GH 2 or LH 2 in any quantity shall

comply with the requirements of Chapters 1 through 4 and the applicable requirements of Chapters 5through 8 . Dispensing of GH 2 or LH 2 shall comply with Chapters 10 and 11 .

18.2.1

Major repair facilities that also repair flammable and combustible liquid vehicles shall also meet therequirements of NFPA 30A .

18.2.2

In major repair garages where CNG-fueled vehicles, LNG-fueled vehicles, or LP-Gas–fueled vehiclesare also repaired all applicable requirements of NFPA 52 or NFPA 58 , whichever is applicable, shallbe met.

18.3 General.

18.3.1 Motor Vehicle Repair Areas.

Repairing of motor vehicles shall be restricted to areas specifically provided for such purposes.[ 30A: 9.7.1]

18.3.1.1

The discharge or defueling of hydrogen from fuel supply containers shall be required for the purpose offuel storage system modification or repair or when welding or open flame activities occur within 18 in.(0.45 m) of the vehicle fuel supply container. Defueling shall be in accordance with Section 18.7 .

18.3.1.2

Other than for those repairs listed in 18.3.1.1 , repairs that would be required to be performed in amajor repair garage shall be permitted to be performed in a minor repair garage if the vehicle is

defueled in accordance with Section 18.5 to less than 250 scf (7.1 Nm 3 )and the fuel supply containeris sealed.

18.3.2 Automatic Sprinkler Systems.

Automatic sprinkler systems shall be provided in accordance with the building code and the fire codeadopted by the AHJ.

18.3.3 Gas Detection System.

Repair garages shall be provided with an approved hydrogen gas detection system such that gas canbe detected where vehicle hydrogen fuel storage systems are serviced or indoor defueling occurs.

18.3.3.1

The detection system shall be maintained and calibrated in accordance with the manufacturer'sinstructions on at least an annual basis , or more often, if required by the manufacturer.

18.3.3.2

The repair garage operator shall maintain a record of detection system maintenance and calibration ingood condition and accessible to an inspector.

18.3.3.3

The hydrogen detection system shall be designed to activate when the level of hydrogen exceeds 25percent of the lower flammable limit.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

398 of 491 1/30/2014 9:30 AM

18.3.3.4 Location.

System shall provide coverage of the fuel cell vehicle service area. The hydrogen detection system shallhave sensors in the following locations:

(1) At inlets to hazardous exhaust systems

(2) At high points in service bays with natural ventilation near vents

(3) At the inlets to mechanical ventilation systems; where hydrogen vehicle fuel systems are servicedor defueled.

18.3.3.5

Activation of hydrogen detection system shall result in all of the following:

(1) Initiation of distinct audible and visual alarm signals in the repair garage

(2) Deactivation of heating systems located in the repair garage

(3) Activation of the hazardous exhaust system, unless the hazardous exhaust system is incontinuous operation

18.3.3.6

Failure of the hydrogen detection system shall result in the deactivation of the heating system andactivation of the hazardous exhaust system and shall cause a trouble signal to sound in an approvedlocation.

18.3.3.7

The circuits of the detection system required by 18.3.3.6 shall be monitored for integrity in accordancewith, NFPA 72 .

18.4 Hazardous Exhaust System.

In major repair garages, or where indoor defueling occurs exhaust duct openings shall be located sothat they effectively remove hydrogen accumulation at ceiling level from all parts of the room.

18.4.1

Hazardous exhaust system should be designed per the mechanical code adopted by the AHJ.

18.5 Heat-Producing Appliances.

18.5.1

Heat-producing appliances shall be installed to meet the requirements of NFPA 31 , NFPA 54 , NFPA82 , NFPA 90A , and NFPA 211 , as applicable, except as hereinafter specifically provided. [ 30A: 7.6.9]

18.5.2

Heat-producing appliances shall be of an approved type. Solid - fuel stoves, improvised furnaces,salamanders, or space heaters shall not be permitted in major repair garages or where indoor refuelingoccurs.

18.5.3

Heat-producing appliances in major repair garages shall be permitted to be installed in a special roomthat is separated from the repair area by walls that are constructed to prevent the transmission ofhydrogen, that have a fire resistance rating of at least 1 hour, and that have no openings in the wallsthat lead to a classified area. Specific small openings through the wall, such as for piping and electricalconduit, shall be permitted, provided the gaps and voids are filled with a fire-resistant material to resisttransmission of hydrogen. All air for combustion purposes shall be taken from outside the building.

18.5.4

Heat-producing appliances using gas or oil fuel shall be permitted to be installed in a major repairgarage provided the combustion chamber is at least 18 in. (455 mm) below the ceiling.

18.5.5

In major repairs garages, open-flame heaters or heating equipment with exposed surfaces having atemperature in excess of 750°F (399°C) shall not be permitted in areas subject to ignit i bleconcentrations of gas.

18.5.6

Electrical heat-producing appliances shall meet the requirements of Chapter 6 .

18.6 Welding and Open-Flame Operations.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

399 of 491 1/30/2014 9:30 AM

18.6.1

Operations involving open flame or electric arcs, including fusion gas and electric welding, shall berestricted to areas specifically provided for such purposes. Cutting and welding and related fireprevention precautions shall be in accordance with the requirements of NFPA 51B . [ 30A: 9.7.2.1]

18.6.2

Electric arc welding generators or transformers shall conform to NFPA 70 . Gas fusion weldingapparatus and storage of compressed gas cylinders shall be in accordance with the provisions of NFPA51 . [ 30A: 9.7.2.2]

18.6.3

The grounded side of an electric welding circuit shall be attached to the part being welded.[ 30A: 9.7.2.3]

18.6.4

Gas fusion welding equipment shall be periodically inspected for worn or injured hoses and defective ordamaged valves, gauges, and reducing devices. [ 30A: 9.7.2.5]

18.7 Defueling Systems.

18.7.1 Methods of Discharge.

The discharge of hydrogen from motor vehicle fuel storage tanks shall be accomplished through anapproved method of atmospheric venting in accordance with 18.7.1 through 18.7.6 .

18.7.2 Defueling Equipment Required at Vehicle Maintenance and Repair Facilities.

Major repair garages shall have equipment to defuel vehicle fuel supply containers. Equipment used fordefueling shall be listed and labeled for the intended use.

18.7.3 Manufacturer Equipment Required.

Equipment supplied by the vehicle manufacturer shall be used to connect the vehicle fuel supplycontainers to be defueled to the defueling system.

18.7.4 Isolated Use.

The defueling shall not be connected to another venting system used for any other purpose.

18.7.5

Defueling systems shall discharge to a safe location in accordance with the requirements of CGA-G-5.5,Hydrogen Vent Systems .

18.7.6 Grounding and Bonding.

The defueling system shall include a method of grounding and bonding and operator instructions tofacilitate safe use. The defueling nozzle of the vehicle storage tank system shall be bonded with thedefueling system prior to the commencement of discharge or defueling operations.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 17:44:07 EDT 2013

Committee Statement

CommitteeStatement:

This submittal is the work of the NFPA 2 Task Group on Chapter 17 and 19.

New Definitions: Task Group felt it necessary to create definitions for minor and major repairgarages to differentiate between the types of garages and necessary differences between them.Also, defining “defueling” was felt necessary to clarify under what conditions the proposed submittalwas written. The Task Group wanted to allow most repair work to be performed in a minor repairgarage without altering status of vehicle.

Defueling: The Task Group felt that if a vehicle was defueled outside it could be worked on in a

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

400 of 491 1/30/2014 9:30 AM

minor facility or a major garage without concern or need for gas detection or ventilation unless thefuel container was being serviced or if welding or hot work was being conducted near the vehiclefuel storage vessel. Defueling to 250 scf is the threshold allowed and this is 1/8 of the 2000 scfMAQ, and roughly equivalent to the contents a large compressed gas bottle.

Gas Detection: NFPA 30A requires gas detection systems, however, the Task Group felt the locationand distribution of these systems should only be required in major repair garages where vehicle fuelstorage systems are serviced or indoor defueling occurs.

Detector Location: Proper location of a hydrogen detection system is crucial to detecting a hydrogenlead. If a leak is detected it is imperative that personnel in the area where hydrogen is or may belocated are made aware (audible/visual alarm). Also, deactivating heating and activating exhaust areintended for public safety.

The addition of sections 19.4 is extracted from NFPA 30A, changing the clearance for the appliancefrom floor mounting to ceiling mounting.

ResponseMessage:

Public Input No. 120-NFPA 2-2013 [Chapter 19]

Public Input No. 206-NFPA 2-2013 [Chapter 19]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

401 of 491 1/30/2014 9:30 AM

First Revision No. 122-NFPA 2-2013 [ Chapter 20 ]

Chapter 20 Fuel Blends (Reserved) DELETED

20.1

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 06 18:09:12 EDT 2013

Committee Statement

Committee Statement: This chapter has no content.

Response Message:

Public Input No. 122-NFPA 2-2013 [Chapter 20]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

402 of 491 1/30/2014 9:30 AM

First Revision No. 453-NFPA 2-2013 [ Section No. A.2.3.6 ]

A.2.3.6

Applicable equivalent regulations apply in the country of use. [55: A.2.3.5 6 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 02 11:58:54 EDT 2013

Committee Statement

Committee Statement: Update of extracted annex material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

403 of 491 1/30/2014 9:30 AM

First Revision No. 488-NFPA 2-2013 [ Section No. A.3.3.22.1 ]

A.3.3.22.1 Gas Cabinet.

Doors and access ports for exchanging cylinders and accessing pressure-regulating controls arepermitted to be included as part of a gas cabinet . [ 5000, 2009] [ 55, 2013]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Sep 06 10:49:14 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

404 of 491 1/30/2014 9:30 AM

First Revision No. 489-NFPA 2-2013 [ Section No. A.3.3.36 ]

A.3.3.37 Class C Furnace.

Class C ovens and furnaces are those in which there is a potential hazard due to a flammable or otherspecial atmosphere being used for treatment of material in process. This type of furnace uses any type ofheating system and includes a special atmosphere supply system(s). Also included in the Class Cclassification are integral quench furnaces and molten salt bath furnaces. [86, 2011]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Sep 06 10:51:50 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

405 of 491 1/30/2014 9:30 AM

First Revision No. 490-NFPA 2-2013 [ Section No. A.3.3.56 ]

A.3.3.57 Cylinder Pack.

Six-packs and twelve-packs are terms used to further define cylinder packs with a specific number ofcylinders. The characteristic internal water volume of individual cylinders in a cylinder pack ranges from

1.52 scf ft 3 to 1.76 ft scf 3 (43 L to 50 L) or a water capacity of 95 lb to 110 lb (43 kg to 50 kg). [ 55,2010] [ 55, 2013]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Sep 06 11:02:09 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

406 of 491 1/30/2014 9:30 AM

First Revision No. 443-NFPA 2-2013 [ Section No. A.3.3.105 ]

A.3.3.105 Gas Room.

Gas rooms must be constructed and utilized in accordance with Section 6.5 . [ 55, 2010]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 02 10:45:00 EDT 2013

Committee Statement

Committee Statement: Update of extracted annex material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

407 of 491 1/30/2014 9:30 AM

First Revision No. 444-NFPA 2-2013 [ Section No. A.3.3.124 ]

A.3.3.126 ISO Module.

The characteristic internal water volume of individual tubular cylinders is 43 ft 3 scf (1218 L) or a watercapacity of 2686 lb (1218 kg). The frame of an ISO container module and its corner castings are speciallydesigned and dimensioned to be used in multimodal transportation service on container ships, specialhighway chassis, and container-on-flatcar railroad equipment. [ 55, 2010] [ 55, 2013]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 02 10:46:50 EDT 2013

Committee Statement

Committee Statement: Update of extracted annex material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

408 of 491 1/30/2014 9:30 AM

First Revision No. 445-NFPA 2-2013 [ Section No. A.3.3.226 ]

A.3.3.232 Tube Trailer.

The characteristic internal water volume of individual tubular cylinders ranges from 43 ft 3 scf to 93

ft 3 scf (1218 L to 2632 L) or a water capacity of 2686 lb to 5803 lb (1218 kg to 2632 kg). [ 55, 2010][ 55, 2013]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 02 10:48:44 EDT 2013

Committee Statement

Committee Statement: Update of extracted annex material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

409 of 491 1/30/2014 9:30 AM

First Revision No. 447-NFPA 2-2013 [ Section No. A.6.7 ]

A.6.7

Electrical and electronic equipment and wiring for use in hazardous locations as defined in Article 500 ofNFPA 70, National Electrical Code , should meet the requirements of Articles 500 and 501 of NFPA 70,National Electrical Code . Note that Article 505 also details requirements for this equipment and wiring inhazardous locations and uses a zone classification method rather than the division method of Article 500.[55: A.6.6 7 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 02 11:01:32 EDT 2013

Committee Statement

Committee Statement: Update of extracted annex material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

410 of 491 1/30/2014 9:30 AM

First Revision No. 446-NFPA 2-2013 [ Section No. A.6.9 ]

A.6.9

NFPA 68 , Standard on Explosion Protection by Deflagration Venting , provides more information on thissubject. [ 55: A.6.8]

Annex K, Hydrogen Explosion Control , contains additional non- mandatory guidance relative to preventionand mitigation of hydrogen explosions.

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 02 10:55:34 EDT 2013

Committee Statement

Committee Statement: Update of extracted annex material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

411 of 491 1/30/2014 9:30 AM

First Revision No. 448-NFPA 2-2013 [ Section No. A.6.9.3 ]

A.6.9.3

The intent of this section is to require a water-based fire extinguishing system to keep vessels containingcompressed gases cool in the event of an exposure fire, thereby minimizing the likelihood of a release andassociated consequences. Accordingly, alternative fire extinguishing systems, such as dry-chemical orgaseous agent systems, should not be substituted. [55:A.6.9 10 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 02 11:02:32 EDT 2013

Committee Statement

Committee Statement: Update of extracted annex material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

412 of 491 1/30/2014 9:30 AM

First Revision No. 140-NFPA 2-2013 [ New Section after A.6.9.4 ]

A.6.12

Global FR-140 Hide Deleted

See Annex L for guidance on hydrogen gas detectors.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 07 11:06:40 EDT 2013

Committee Statement

CommitteeStatement:

Committee generated first revision. Added reference to new annex on hydrogendetectors.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

413 of 491 1/30/2014 9:30 AM

First Revision No. 491-NFPA 2-2013 [ Section No. A.6.16 ]

A.6.16

The termination point for piped vent systems serving cylinders, containers, tanks, and gas systems usedfor the purpose of operational or emergency venting [should] be located to prevent impingement exposureon the system served and to minimize the effects of high temperature thermal radiation or the effects ofcontact with the gas from the escaping plume to the supply system, personnel, adjacent structures, andignition sources. [55:6.14 15 ]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Sep 06 14:53:12 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

414 of 491 1/30/2014 9:30 AM

First Revision No. 493-NFPA 2-2013 [ Section No. A.6.20 ]

A.6.20

Figure A.6.20 shows three possible locations of the source valve. [55: A.6.18 19 ]

Figure A.6.20 Three Examples of Source Valve Locations. [55: A.6.18 19 ]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Sep 06 15:02:26 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

415 of 491 1/30/2014 9:30 AM

First Revision No. 449-NFPA 2-2013 [ Section No. A.7.1.2 ]

A.7.1.2

The [ GH2] system equipment referenced is intended to include fuel cell [ power system] applications,

generation of hydrogen from portable or transportable hydrogen-generation equipment, batteries, andsimilar devices and equipment that utilize hydrogen for the purpose of power generation. It does notinclude hydrogen production facilities intended to produce hydrogen used for distribution or repackagingoperations operated by gas producers, distributors, and repackagers. [ 55: A.7.1.4]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 02 11:08:36 EDT 2013

Committee Statement

Committee Statement: Update of extracted annex material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

416 of 491 1/30/2014 9:30 AM

First Revision No. 450-NFPA 2-2013 [ Section No. A.7.1.4 ]

A.7.1.4

Numerous metal hydrides are currently being tested for gaseous hydrogen storage applications. Whilecertain Class D extinguishing agents have been effective on some metal hydride materials, they have notbeen tested on the wide range of hydrides. It is crucial to understand any adverse chemical reactionsbetween the hydride and the agent prior to using the fire suppressant. Additionally, it is important tounderstand the application should be limited to small incipient stage fires. Larger fires would require theuse of personal protective equipment in the application of the extinguishing agent. [55: A.7.1.4 5 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 02 11:09:34 EDT 2013

Committee Statement

Committee Statement: Update of extracted annex material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

417 of 491 1/30/2014 9:30 AM

First Revision No. 494-NFPA 2-2013 [ Section No. A.7.1.9.1.3 ]

A.7.1.9.1.3

Clearance is required from combustible materials to minimize the effects of exposure fires to the materialsstored or used. The requirement to separate the materials from vegetation should not be interpreted tomean that the area is maintained free of all vegetation. In some settings, gas systems are located ongrounds that are maintained with formal landscaping. Some judgment must be exercised to determinewhether the vegetation poses what might be viewed as an exposure hazard to the materials stored. Cutlawns, formal landscaping, and similar vegetation does not ordinarily present a hazard and should beallowed. On the other hand, tall dried grass or weeds and vegetation that fringes on the border of anurban-wildland interface might be viewed as a hazard. [55: A.7.1.10 11 .3]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Sep 06 15:06:13 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

418 of 491 1/30/2014 9:30 AM

First Revision No. 495-NFPA 2-2013 [ Sections A.7.1.13.3, A.7.1.15.3.1.3 ]

A.7.1.13.3

The gas supplier should be consulted for advice under these circumstances. [55:A.7.1.14 15 .3]

A.7.1.15.3.1.3

Underground piping systems are those systems that are buried and in contact with earth fill or similarmaterials. Piping located in open-top or grated-top trenches is not considered to be underground althoughit may be below grade. [55:A.7.1.17 18 .1.2]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Sep 06 15:13:49 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

419 of 491 1/30/2014 9:30 AM

First Revision No. 496-NFPA 2-2013 [ Section No. A.7.3.1.2.1 ]

A.7.3.1.2.1

Any reference to listed or approved equipment in the noted sections of the IFGC is within the context ofthe ANSI/ASME B31.3, Process Piping, standard and describes a material or component which thatconforms to the specifications integral to ANSI/ASME B31.3. [55:A.10.2.1 2 ]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Sep 06 15:15:39 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

420 of 491 1/30/2014 9:30 AM

First Revision No. 452-NFPA 2-2013 [ Section No. A.7.3.2.1.6 ]

A.7.3.2.1.4

Hydrogen fires should not be extinguished until the supply of hydrogen has been shut off because of thedanger of re-ignition or explosion. In the event of fire, large quantities of water should be sprayed onadjacent equipment to cool the equipment and prevent involvement in the fire. Combination fog and solidstream nozzles are preferred, to permit widest adaptability in fire control. Small hydrogen fires can beextinguished with dry chemical extinguishers or with carbon dioxide, nitrogen, and steam. Re-ignition canoccur if a heated surface adjacent to the flame is not cooled with water or other means. [55:A.10.6.1.2 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 02 11:56:19 EDT 2013

Committee Statement

Committee Statement: Update of extracted annex material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

421 of 491 1/30/2014 9:30 AM

First Revision No. 497-NFPA 2-2013 [ Section No. A.7.3.2.2.2.3 ]

A.7.3.2.2.2.3

For guidance in these construction techniques, see NFPA 68, Standard on Explosion Protection byDeflagration Venting . [55: A.10.4.4 6.2 .3]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Sep 06 15:16:50 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

422 of 491 1/30/2014 9:30 AM

First Revision No. 498-NFPA 2-2013 [ Section No. A.7.3.2.3.1.1(A) ]

A.7.3.2.3.1.1(A)

Conversions for distance between inch-pound and SI units of measure cannot be consistently performedusing typical mathematical conversion factors. The majority of separation distances shown in the SI tablehave been determined by the application of a risk-informed approach substantiated by statisticalevaluation and modeling based on validated models for both ignited and unignited release of hydrogengas. Where distance has been determined to allow for access or for correlation with the electrical code,the distances were not established through the use of models. Tabular distances in the inch-pound tablehave been determined by first converting SI units into inch-pound units and then rounding the distance tothe nearest 5 ft for ease of application by code enforcers and users. A similar rounding technique has notbeen applied in the tabular distances shown in the SI table.

The exposures integral to Table 7.3.2.3.1.1(A)(a) , Exposure Group 1(a) Table 7.3.2.3.1.1(A)(b) , andTable 7.3.2.3.1.1(A)(c) have been arranged into groups based on similar risks. The thresholds areapplicable to the exposures identified in each group, as follows: [ 55: A.10.3.2.1]

(1)  Group 1 Exposures. The distances specified are those required to reduce the radiant heat flux

level to 500 Btu/hr / ft 2 (1577 W/m 2 ) at the property line or the distance to a point in the unignitedhydrogen jet where the hydrogen content is reduced to a 4 percent mole fraction (volume fraction) ofhydrogen, whichever is greater. In all cases the distance required to achieve a 4 percent mole fractionwas the greater distance and used to establish the requirements. [ 55: A.10.3.2.1]

(2)  Group 2 Exposures. The distances specified are those required to reduce the radiant heat flux

level to 1500 Btu/hr / ft 2 (4732 W/m 2 ) for persons exposed a maximum of 3 minutes. [ 55: A.10.3.2.1]

(3)  Group 3 Exposures. The distances specified are those required to reduce the radiant heat flux

level to 6340 Btu/hr / ft 2 (20,000 W/m 2 ) or the visible flame length for combustible materials, or a

radiant heat flux level of 8000 Btu/hr / ft 2 (25,237 W/m 2 ) or the visible flame length for noncombustibleequipment. In both cases the visible flame length was used to establish the requirements.[ 55: A.10.3.2.1]

Table 7.3.2.3.1.1(A)(a) Exposure Group 1(a). Lot lines (property lines) are those property lines betweenparcels and should not be construed to be the imaginary property lines that are drawn for the purposes ofprotecting the exterior walls of multiple buildings placed on the same lot or parcel. Railroad easementsthat are not accessible to the public other than by rail travel can be used as a means of spatialseparation, with the required separation being measured between the hydrogen system and the nearestrailroad track. It should be noted that in these cases, the addition or relocation of track may result in anencroachment that will necessitate relocation of the hydrogen system at the system user’s expense.[ 55: A.10.3.2.1]

Where the property on the other side of a property line is determined to be unbuildable or unoccupiabledue to natural features including, but not limited to, waterways, terrain, wetlands, or similar featuresencroachment by the hydrogen system on the property line can be acceptable with the approval of theauthority having jurisdiction. Should the property that is encroached upon become buildable or otherwiseoccupiable, the hydrogen system location should be reevaluated by the system user and the AHJ notifiedof the results. [ 55: A.10.3.2.1]

Table 7.3.2.3.1.1(A)(a) Exposure Group 2(a). The exposed persons of concern are non-work-relatedpersons or members of the public who are not involved with servicing the system, because thesepersons typically are neither trained nor knowledgeable in the operation of the system, but are on thepremises. By comparison, service personnel or those involved with servicing the system are trained andengaged in activities related to the system operation including, but not limited to, inspecting, monitoringsystem inventory, delivering product, maintenance, or similar functions. Administrative controls,engineering controls, or construction features are typically used to restrict persons other than servicepersonnel from being within the zone of potential exposure. The permit holder is responsible formanaging and administering the controls to restrict access. Examples of such controls could includepainted lines or signs or physical barriers such as a fence. [ 55: A.10.3.2.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

423 of 491 1/30/2014 9:30 AM

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Sep 06 15:32:42 EDT 2013

Committee Statement

Committee Statement: Updated extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

424 of 491 1/30/2014 9:30 AM

First Revision No. 499-NFPA 2-2013 [ Section No. A.7.3.2.3.1.1(A)(1)(b) ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

425 of 491 1/30/2014 9:30 AM

A.7.3.2.3.1.1(A)(1)(b)

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

426 of 491 1/30/2014 9:30 AM

[Table 7.3.2.1.1(A)(1)(b)]

The following is a sample calculation for separation distances using 1 ⁄4 in. ID tubing at gauge pressureof 250 – 3000 psi. [ 55: A.10.3.2.2.1.1(B)]

Determine internal diameter (ID) where ID = OD - (2 × wall thickness); wall thickness = 0.049 in.(known); outside diameter (OD) = 0.250 in.:

ID = d = 0.250 - (2 × 0.049) or 0.152 in. = 3.86 mm

To use the equations in Table 7.3.2.3.1.2(c) the ID values (the value of d in the equation) to beused must be expressed in millimeters. [ 55: A.10.3.2.2.1.1(B)]

Next, determine separation distance(s). The separations distances D a , D b , etc. are

calculated in meters to two significant places after the decimal. To convert meters to feet, multiplymeters by 3.281 and round off to the nearest 5 ft. [ 55: A.10.3.2.2.1.1(B)]

For example, assuming the 250—3000 psi pressure range (second column), calculations forseparation distance for the Table 7.3.2.3.1.2(c) footnotes (a) through (e) are as follows:

Where:

D a, b, c, d, e = calculated separation distance for D a , D b , etc.

e = 2.71828 ..., the base of natural logarithms

Then:

D a = 0.74 d 0.99962

D a = 0.74(3.86 0.99962 )

D a = 0.74(3.858) = 2.85 m = 9.4 ft → 10 ft

D b = 0.37 d 1.1152 + e -0.10771d (0.19 d 1.2531 - 0.37 d 1.1152 )

D b = 0.37(3.86 1.1152 ) + e -(0.10771)(3.86) [(0.19)(3.86 1.2531 ) - (0.37)(3.86 1.1152 )]

D b = 0.37(4.51) + e -0.4158 [(0.19)(5.43) - (0.37)(4.51)]

D b = 1.67 + 0.66(1.03 - 1.67)

D b = 1.67 - 0.42

D b = 1.25 m = 4.1 ft → 5 ft

D c = 0.29 d 1.092 + e -0.10392d (0.19 d 1.1795 - 0.29 d 1.092 )

D c = 0.29(3.86 1.092 ) + e -(0.10392)(3.86) [(0.19)(3.86 1.1795 ) - (0.29)(3.86 1.092 )]

D c = 0.29(4.37) + e -0.4011 [(0.19)(4.92) - (0.29)(4.37)]

D c = 1.27 + 0.67(0.94 - 1.27)

D c = 1.27 - 0.22

D c = 1.05 m = 3.45 ft → 5 ft

D d = 0.31 d 0.99962

D d = 0.31(3.86 0.99962 )

D d = 0.31(3.84) = 1.19 m = 3.9 ft → 5 ft

D e = 0.31 d 0.99962

D e = 0.31(3.86 0.99962 )

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

427 of 491 1/30/2014 9:30 AM

D e = 0.31(3.84) = 1.19 m = 3.9 ft → 5 ft [ 55: A.10.3.2.2.1.1(B)]

The subscript, e.g., D, a, b, c, d and e relate to notes (a) through (e), respectively, in Table

7.3.2.3.1(b). To convert the distance in meters to feet multiply by 3.2808. The resultant distance in feetis then rounded off to the nearest 5 foot dimension. For example, a distance of 5.2 ft would be roundeddown to 5 ft. A distance of 7.6 ft would be rounded up to 10 ft. [ 55: A.10.3.2.2.1.1(B)]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Sep 06 15:36:54 EDT 2013

Committee Statement

Committee Statement: Update of extract text.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

428 of 491 1/30/2014 9:30 AM

First Revision No. 500-NFPA 2-2013 [ Section No. A.7.3.2.3.1.1(A)(1)(e) ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

429 of 491 1/30/2014 9:30 AM

A.7.3.2.3.1.1(A)(1)(c)

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

430 of 491 1/30/2014 9:30 AM

Systems that employ compressors downstream of a bulk supply typically operate at higher pressures thanthat of the bulk supply. As a result, the diameter of the piping system may can vary with the pressure. Theuse of a higher pressure rating or variation of internal diameters is not warranted unless there is a storage

component with a hydrogen content that exceeds 400 5000 scf (11.3 141.6 N m3) located downstream ofthe primary storage source and upstream of the source valve. The volume of gas contained within thepiping system is not included in determining the quantity in storage. [55: A.10.3.2.2.1.1(E) ]

For example, a 3000 psi (20,684 kPa) storage system that supplies a 6000 psi (41,369 kPa) compressor

that directly feeds a process with less than 400 5000 scf (11.3 141.6 N m3) of intervening storage at apressure of 6000 psi (41,369 kPa) or less is considered a 3000 psi (20,684 kPa) system. Conversely, asystem where the primary storage of 3000 psi (20,684 kPa) might supply a compressor that in turn

delivers hydrogen to intermediate storage with a quantity of greater than 400 5000 scf (11.3 141.6 N m3).(Note: Pressures given are gauge pressures.) The piping serving the intermediate storage system from apoint of discharge on the compressor can have an internal diameter of less than that serving the primarystorage system upstream of the compressor. Accordingly, each portion of the system must be analyzedwith respect to the tabular distances. See the typical piping and instrumentation drawings ( P&IDs) shownin Figure A.3.3.225.10(a) through Figure A.3.3.225.10(f) for additional information in this regard. [55:A.10.3.2.2.1.1(E) ]

The use of Table 7.3.2.3.1.1(A)(c) is based on the maximum internal diameter of the piping system overthe range of pressures specified. In practice, it is common to maintain a consistent size of pipingthroughout the system; however, there might be cases where the ID of the piping system varies. In suchcases, the piping with the largest internal diameter in the system is used to establish the system pipe sizefor the purposes of using the table, regardless of the length of the piping. It is not uncommon for portionsof the system equipped with pressure gauges, pressure transducers, or other instrumentation to be servedby small-diameter piping systems. However, the maximum internal diameter of the piping system willcontrol the establishment of distance for the exposures indicated. [55: A.10.3.2.2.1.1(E) ]

Pipe sizes are typically expressed in nominal terms as illustrated in Table A.7.3.2.3.1.1(A)(1)(e) . This iscompared with tubing in which the outside diameter (OD) is expressed in exact terms. Designerscommonly use pipe schedule to specify the wall thickness for a given material based on the designconditions. Typical pipe sizes found in commerce include those shown in Table A.7.3.2.3.1.1(A)(1)(e) .

Table A.7.3.2.3.1.1(A)(1)(e) Typical Pipe Sizes

Nominal Pipe Size (in.) O.D. (in.)

Pipe Schedules — Wall Thickness (in.)

40 80 XH XXH

1 ⁄4 0.540 0.088 0.119 0.119 —3 ⁄8 0.675 0.091 0.126 0.126 —1 ⁄2 0.840 0.109 0.147 0.147 0.294

¾ 1.050 0.113 0.154 0.154 0.308

1 1.315 0.133 0.179 0.179 0.358

1 1 ⁄4 1.660 0.140 0.191 0.191 0.382

1 1 ⁄2 1.900 0.145 0.200 0.200 0.400

2 2.375 0.154 0.218 0.218 0.436

2 1 ⁄2 2.875 0.203 0.276 0.276 0.552

3 3.500 0.216 0.300 0.300 0.600

3 1 ⁄2 4.000 0.226 0.318 0.318 0.636

4 4.500 0.237 0.337 0.337 0.674

XH = extra heavy; XXH = extra extra heavy.

Note: Standard pipe schedule or pipe size as listed by ANSI/ASME B36.10, Welded and SeamlessWrought Steel Pipe, and API Spec 5L, Specifications for Line Pipe .

[ 55: Table A.10.3.2.2.1.1(E)]

To determine internal diameter (ID) of a selected pipe size multiply by 2 the wall thickness for theselected schedule and subtract from the outside diameter (OD):

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

431 of 491 1/30/2014 9:30 AM

ID = OD - (2 × wall thickness)

For example, for 2 in. schedule 40 pipe:

Wall thickness = 0.154 in.; OD = 2.375 in.

Then:

ID = 2.375 - (2 × 0.154) = 2.067 in.

[ 55: A.10.3.2.2.1.1(E)]

When tubing is used in lieu of pipe, the OD of the tubing is designated in inches (e.g., 1 ⁄4 , 3 ⁄8 , 1 / 2 ,

1, 1 1 ⁄4 , 1 1 ⁄2 , 2), and the tubing is manufactured to those specific dimensions. Tube wall thickness isdetermined by the designer based on the working pressure and materials of construction. The calculationof internal diameter is the same as that used for conventional pipe:

ID = OD - (2 × wall thickness)

For example, for 1 ⁄4 in. OD tubing, if the wall thickness is 0.049 in., and the OD is 0.250 in.

then:

ID = 0.250 - (2 × 0.049) = 0.152 in.

[ 55: A.10.3.2.2.1.1(E)]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Sep 06 16:45:51 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

432 of 491 1/30/2014 9:30 AM

First Revision No. 501-NFPA 2-2013 [ Section No. A.8.1.4.5.1 ]

A.8.1.4.5.1

Pressure relief valves are typically are spring-loaded valves where the relief pressure is set byadjustment of a spring. Valves should be sealed made to be tamper resistant in order to preventadjustment by other than authorized personnel typically found at a retest facility. An ASME pressure reliefvalve is designed to comply with the requirements of the ASME Boiler and Pressure Vessel Code andtypically is equipped with a wire and lead seal to prevent resist tampering. [55:A.8.2.5 4 .5.1]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Fri Sep 06 16:52:20 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

433 of 491 1/30/2014 9:30 AM

First Revision No. 455-NFPA 2-2013 [ Section No. A.8.3.1.2.3.6 ]

A.8.3.1.2.3.6

Air can be condensed when it contacts containers or piping containing cryogenic fluids. When thisoccurs, the concentration of oxygen in the condensed air increases, thereby increasing the likelihood ofignition of organic [or inorganic] material. [ 45: A.11.4.1.2]

Like other cryogenic liquids, liquid hydrogen is susceptible to heat leak. Adding heat to the fluid liquid,reduces the net positive suction head (NPSH) to the pump and can reduce the level of sub-cooling or cancause the fluid to flash to vapor. Sub-cooled liquid is the ideal state for pumping liquid hydrogen. As thefluid saturates, the ability to pump decreases. The liquid suction and gas return piping to and from thepump typically is vacuum-jacketed piping. Vacuum-jacketed piping is most commonly used when liquid isto be transferred, because it avoids the potential condensation of air and oxygen enrichment that canoccur in piping systems that are insulated with convention materials. In some cases the liquid may betransferred using uninsulated piping systems . Such systems must be designed in a way that condensedair does not present a contact hazard to personnel or otherwise create a potential flammability hazarddue to material contact and the presence of oxygen contained in the condensate. [ 55: A.11.2.3.6]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 02 13:43:50 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

434 of 491 1/30/2014 9:30 AM

First Revision No. 143-NFPA 2-2013 [ New Section after A.10.3.2.2.1.10 ]

A.10.3.3.2.2

A generic dispenser piping and instrumentation diagram with NFPA 2 references is provided to help theuser to apply the requirements. See Figure A.10.3.3.2.2 .

Figure A.10.3.3.2.2 Indoor Nonpublic Fast-Fill Dispenser P & ID.

Supplemental Information

File Name Description

2FCfA-10-3-3-2-2.jpg

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 07 11:16:48 EDT 2013

Committee Statement

CommitteeStatement:

Provide a generic system P&ID for the indoor nonpublic fast filling hydrogen dispensingsystem.

Response Message:

Public Input No. 182-NFPA 2-2013 [New Section after A.10.3.2.2.1.10]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

435 of 491 1/30/2014 9:30 AM

First Revision No. 454-NFPA 2-2013 [ Section No. A.13.3.3.1.2 ]

A.13.3.3.1.2

Global FR-524 Hide Deleted

There are two considerations unique to gasification: [ 55: A.12.3.2.9.2]

(1) Gasifiers typically operate in excess of 2600°F 1425°C ( 1425°C 2600°F ). Gas delivery temperatureis a strict function of the amount of cooling provided by the system. [ 55: A.12.3.2.9.2(1)]

(2) The output of the gasifier typically contains significant quantities of carbon monoxide, hydrogensulfide, and other toxic substances. [ 55: A.12.3.2.9.2(2)]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 02 12:35:59 EDT 2013

Committee Statement

Committee Statement: Update of extracted annex material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

436 of 491 1/30/2014 9:30 AM

First Revision No. 503-NFPA 2-2013 [ Section No. B.1.4 ]

B.1.4 Installations.

B.1.4.1

Installations Buildings permitted for construction after the adoption of this code shall comply with theprovisions stated herein for new buildings . [1:1.3.6.1]

B.1.4.2

Installations Buildings in existence or permitted for construction prior to the adoption of this code shallcomply with the provisions stated herein or as approved by the AHJ referenced for existing buildings .[1:1.3.6.2]

B.1.4.3

Repairs, renovations, alterations, and additions to existing hydrogen installations shall conform with NFPA2 and the adopted building code. [ 1: 1.3.6.3]

B.1.4.4

Newly introduced equipment, materials, and operations regulated by this code shall comply with therequirements for new construction or processes. [1:1.3.6.4]

B.1.4.5 Severability.

If any provision of this code or the application thereof to any person or circumstance is held invalid, theremainder of the code and the application of such provision to other persons or circumstances shall not beaffected thereby. [1:1.3.7]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Sep 09 08:53:32 EDT 2013

Committee Statement

Committee Statement: Update of extracted text.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

437 of 491 1/30/2014 9:30 AM

First Revision No. 504-NFPA 2-2013 [ Section No. B.2.7 ]

B.2.7 Tests.

B.2.7.1

Whenever there is insufficient evidence of compliance with the requirements of this code Code isinsufficient or evidence that any material or method of construction does not conform to the requirementsof this code Code , or to substantiate claims for alternative construction systems, materials, or methods ofconstruction, the AHJ shall be permitted to require tests for proof of compliance to be made by anapproved agency at the expense of the owner or his/her agent. [1:1.4.7.1]

B.2.7.2

Test methods shall be as specified by this code Code for the material in question. If there are notappropriate test methods are not specified in this code Code , the AHJ is authorized to accept anapplicable test procedure from another recognized source. [1:1.4.7.2]

B.2.7.3

Copies of the results of all such tests shall be retained in accordance with Section B.7. [1:1.4.7.3]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Sep 09 09:08:35 EDT 2013

Committee Statement

Committee Statement: Update of extracted material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

438 of 491 1/30/2014 9:30 AM

First Revision No. 505-NFPA 2-2013 [ Section No. B.5.2 ]

B.5.2 Minimum Qualifications to Enforce this Code.

The AHJ shall adopt establish minimum qualifications for all persons assigned the responsibility ofadministering and enforcing this code. [1:1.7.2]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Sep 09 09:11:46 EDT 2013

Committee Statement

Committee Statement: Update of extracted material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

439 of 491 1/30/2014 9:30 AM

First Revision No. 506-NFPA 2-2013 [ Section No. B.5.3 ]

B.5.3 Interpretations.

Such interpretations, rules, and regulations shall be in conformance with the intent and purpose of thiscode and shall be available to the public during normal business hours. [ 1: 1.7.3.1]

B.5.3.1

The AHJ is authorized to render interpretations of this Code and to make and enforce rules andsupplemental regulations in order to carry out the application and intent of its provisions. [ 1: 1.7.3.1]

B.5.3.2

Such interpretations, rules, and regulations shall be in conformance with the intent and purpose of thisCode and shall be available to the public during normal business hours. [ 1: 1.7.3.2]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Sep 09 09:18:29 EDT 2013

Committee Statement

Committee Statement: Update of extracted material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

440 of 491 1/30/2014 9:30 AM

First Revision No. 507-NFPA 2-2013 [ Section No. B.5.6.5 ]

B.5.6.5

As used in B.5.6.4, emergency means circumstances that the AHJ knows, or has reason to believe, existand that can constitute immediate danger to life and property . [1:1.7.6.5]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Sep 09 09:27:31 EDT 2013

Committee Statement

Committee Statement: Update of extracted material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

441 of 491 1/30/2014 9:30 AM

First Revision No. 428-NFPA 2-2013 [ Section No. B.5.11 ]

B.5.11 Plans and Specifications.

The AHJ shall have the authority to require plans and specifications to ensure compliance with applicablecodes and standards. [ 1: 1.7.11]

B.5.11.1

The AHJ shall have the authority to require plans and specifications to ensure compliance withapplicable codes and standards. [ 1: 1.7.11 .1 ]

B.5.11.2

Plans shall be submitted to the AHJ prior to construction unless otherwise permitted by B.5.11.4 .[ 1: 1.7.11.2]

B.5.11.3

The construction documents for each phase shall be complete in themselves, so that review andinspection can properly be made. Preliminary plans of the to t al building shall be submitted with theconstruction documents, and with sufficient detail, so that proper evaluation can be made. Areas anditems not included in the phase to be permitted shall be shown as not included. [ 5000: 1.7.6.3.3.3]

B.5.11.4

The AHJ is authorized to exempt detached one- and two-family dwellings and accessory structures fromthe submittal of plans. [ 1: 1.7.11.4]

B.5.11.5

Plans shall be submitted to the AHJ prior to the change of occupancy of any existing building.[ 1: 1.7.11.5]

B.5.11.6

Plans shall be submitted to the AHJ prior to the alteration of the means of egress or fire protectionsystems of any existing building. [ 1: 1.7.11.6]

B.5.11.7

Plans shall be submitted to the AHJ for other conditions as deemed necessary by the AHJ to determinecompliance with the applicable codes and standards. [ 1: 1.7.11.7]

B.5.11.8

The AHJ shall be authorized to require permits for conditions listed in B.5.11.2 , B.5.11.5 , andB.5.11.6 , unless otherwise permitted by B.5.11.9 . [1:1.7.11.8]

B.5.11.9

The AHJ is authorized to exempt detached one- and two-family dwellings and accessory structures fromthe permit requirement of B.5.11.8 . [ 1: 1.7.11.9]

B.5.11.10

No construction work shall proceed until the AHJ has reviewed the plans for compliance with theapplicable codes and standards and the applicable permits have been issued. [ 1: 1.7.11.10]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 12:43:41 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

442 of 491 1/30/2014 9:30 AM

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

443 of 491 1/30/2014 9:30 AM

First Revision No. 508-NFPA 2-2013 [ Section No. B.5.13 ]

B.5.13 Certificate of Occupancy.

When If the adopted building code requires a certificate of occupancy, the certificate of occupancy shallnot be issued until approved by the AHJ for the adopted fire code enforcement. [ 1: 1.7.13]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Sep 09 09:30:14 EDT 2013

Committee Statement

CommitteeStatement:

Remove extract tag to allow the use of the term "adopted" as it pertains to the buildingcode

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

444 of 491 1/30/2014 9:30 AM

First Revision No. 429-NFPA 2-2013 [ Section No. B.5.14 ]

B.5.14 Stop Work or Evacuation Order .

The AHJ shall have the authority to order an operation, construction, or use stopped when any of thefollowing conditions exists: 1: 1.7.14]

(1)

(2) Work is being done contrary to provision of this code. [ 1: 1.7.14(1)]

(3) Work is occurring without a permit required by B.5.12 . [ 1: 1.7.14(2)]

(4) An imminent danger has been created. [ 1: 1.7.14(3)]

[

B.5.14.1

The AHJ shall have the authority to order an operation or use stopped and the immediate evacuation ofany occupied building or area when such building or area has hazardous conditions that presentimminent danger. [ 1: 1.7.14.1]

B.5.14.2

Whenever any work is being done contrary to provisions of this code, the AHJ is hereby authorized toorder such work stopped. [ 1: 1.7.14.2]

B.5.14.3

Such work shall immediately stop until authorized by the AHJ to proceed. [ 1: 1.7.14.3]

B.5.15 Imminent Dangers and Evacuation.

B.5.15.1

When, in the opinion of the AHJ, an imminent danger exists, the AHJ shall be authorized to orderoccupants to vacate, or temporarily close for use or occupancy, a building, the right-of-way, sidewalks,streets, or adjacent buildings or nearby areas. [ 1: 1.7.15.1]

B.5.15.2

The AHJ shall be authorized to employ the necessary resources to perform the required work in order tomitigate the imminent danger. [ 1: 1.7.15.2]

B.5.15.3

Costs incurred by the AHJ in performance of emergency work shall be the responsibility of the propertyowner or other responsible party creating such imminent danger. [ 1: 1.7.15.3]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 12:44:39 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

445 of 491 1/30/2014 9:30 AM

First Revision No. 430-NFPA 2-2013 [ Section No. B.6 ]

B.6 Fire Code Board of Appeals.

B.6.1 Establishment of Fire Code Board of Appeals.

A Board of Appeals shall be established to rule on matters relating to the fire code and its enforcement.[ 1: 1.10.1]

B.6.1.1 Membership.

A Board of Appeals shall be established consisting of members and alternate members who shall beappointed by the appointing official of the jurisdiction by reason of education, experience, and knowledgeand are deemed to be competent to sit in judgment on matters concerning this code and its enforcement.[ 1: 1.10.1.1]

B.6.1.1.1

The members of the Board of Appeals shall be appointed by the governing body of the jurisdiction.[ 1: 1.10.1.1.1]

B.6.1.1.2

The Board of Appeals shall consist of five or seven principal members and one ex officio memberrepresentative of the AHJ. Each principal member shall be permitted to have an alternate with similarexperience to serve in his or her stead when necessary. [ 1: 1.10.1.1.2]

B.6.1.1.3

Members and alternate members shall be appointed based on their education, experience, andknowledge. [ 1: 1.10.1.1.3]

B.6.1.1.4

Members and alternates shall be appointed to a 3-year term. [ 1: 1.10.1.1.4]

B.6.1.1.5

Members and alternates shall be composed of individuals experienced in the following fields orprofessions: [ 1: 1.10.1.1.5]

(1) Engineering or architectural design [ 1: 1.10.1.1.5(1)]

(2) General contracting [ 1: 1.10.1.1.5(2)]

(3) Fire protection contracting [ 1: 1.10.1.1.5(3)]

(4) Fire department operations or fire code enforcement [ 1: 1.10.1.1.5(4)]

(5) Building code enforcement [ 1: 1.10.1.1.5(5)]

(6) Legal [ 1: 1.10.1.1.5(6)]

(7) General public [ 1: 1.10.1.1.5(7)]

B.6.1.1.5.1

Members and alternates shall not be employees, agents, or officers of the jurisdiction. [ 1: 1.10.1.1.5.1]

B.6.1.1.5.2

Members and alternates shall be residents of the jurisdiction. [ 1: 1.10.1.1.5.2]

B.6.1.1.5.3

No more than one member shall represent the same field or provision listed inB.6.1.1.5 [ 1: 1.10.1.1.5.3]

B.6.1.1.6

The representative of the AHJ shall be an ex officio member and shall be entitled to participate in alldiscussions. The ex officio member shall not be entitled to a vote. [ 1: 1.10.1.1.6]

B.6.1.1.7

No member of the Board of Appeals shall sit in judgment on any case in which the member holds adirect or indirect property or financial interest in the case. [ 1: 1.10.1.1.7]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

446 of 491 1/30/2014 9:30 AM

B.6.1.1.8

The board shall select one of its members to serve as chair and one member to serve as vice chair.[ 1: 1.10.1.1.8]

B.6.1.2

No more than one of said members or their alternates shall be engaged in the same business,profession, or line of endeavor. [ 1: 1.10.1.2]

B.6.1.3

The members shall serve for a term of three years, except for the initial appointees who shall serve asfollows: two for a term of one year, two for a term of two years, and three for a term of three years.[ 1: 1.10.1.3]

B.6.1.4

All members and any alternate members shall be appointed and shall serve in accordance with theterms and conditions of the AHJ. [ 1: 1.10.1.4]

B.6.2 Rules and Procedures of the Board of Appeals.

The Board of Appeals shall have the authority to establish rules and regulations for conducting itsbusiness and shall render all decisions and findings in writing to the AHJ, with a copy to the appellant thatare consistent with the provisions of this code . [1:1.10.2]

B.6.3 Conflicts of Interest Authority of the Board of Appeals .

B.6.3.1

Board of Appeals members shall not be officers, agents, or employees of the jurisdiction The Board ofAppeals shall provide for the reasonable interpretation of the provisions of this code and issue rulings onappeals of the decisions of the AHJ . [1:1.10.3.1]

B.6.3.2

No member of the Board of Appeals shall sit in judgment on any case in which the member, personally, isdirectly interested The ruling of the Board of Appeals shall be consistent with the letter of the code orwhen involving issues of clarity, ensuring that the intent of the code is met with due consideration forpublic safety and fire fighter safety. . [1:1.10.3.2]

B.6.3.3

The Board of Appeals shall have the authority to grant alternatives or modifications through proceduresoutlined in Section B.2 of the code. [ 1: 1.10.3.3]

B.6.3.4

The Board of Appeals shall not have the authority to waive the requirements of the code. [ 1: 1.10.3.4]

B.6.3.5

The Board of Appeals decisions shall not be precedent setting. [ 1: 1.10.3.5]

B.6.4 Duties of Board of Appeals Means of Appeals .

B.6.4.1

The Board of Appeals shall provide for reasonable interpretation of the provisions of this Code and ruleon appeals from decisions of the AHJ Any person with standing shall be permitted to appeal a decision ofthe AHJ to the Board of Appeals when it is claimed that any one or more of the following conditions exist:[ 1 :1.10.4.1]

(1) The true intent of the code has been incorrectly interpreted. [ 1: 1.10.4.1(1)]

(2) The provisions of the code do not fully apply. [ 1: 1.10.4.1(2)]

(3) A decision is unreasonable or arbitrary as it applies to alternatives or new materials.[ 1: 1.10.4.1(3)]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

447 of 491 1/30/2014 9:30 AM

B.6.4.2

The ruling of the Board of Appeals shall ensure that the intent of the Code is complied with and publicsafety is secured. An appeal shall be submitted to the AHJ in writing within 30 calendar days ofnotification of violation. The appeal shall outline all of the following: [ 1: 1.10.4.2]

(1) The code provision(s) from which relief is sought [ 1: 1.10.4.2(1)]

(2) A statement indicating which provisions of B.6.4.1 apply [ 1: 1.10.4.2(2)]

(3) Justification as to the applicability of the provision(s) cited in B.6.4.1 [ 1: 1.10.4.2(3)]

(4) A requested remedy [ 1: 1.10.4.2(4)]

(5) Justification for the requested remedy stating specifically how the code is complied with, publicsafety is secured, and fire fighter safety is secured [ 1: 1.10.4.2(5)]

B.6.4.3

The Board of Appeals shall be permitted to grant alternatives or modifications through the proceduresoutlined in Section B.2 of this code Documentation supporting an appeal shall be submitted to the AHJat least 7 calendar days prior to the Board of Appeals hearing . [1:1.10.4.3]

B.6.4.3.1

No additional information should be submitted to review by the Board of Appeals without the informationsubmitted to the AHJ for their review prior to the hearing date. Additional information submitted after thefiling of the appeal to the Board and AHJ should be made available to the Board and AHJ in a timeframethat permits adequate review before the hearing date. [ 1: A.1.10.4.3]

B.6.4.4

The Board of Appeals shall not have the authority to waive the requirements of this code. [ 1: 1.10.4.4]

B.6.5 Meetings of Board of Appeals and Records .

B.6.5.1

The Board of Appeals shall meet whenever directed by the appointing authority to interpret the provisionsof this code and to consider and rule on any properly filed appeal from a decision of the AHJ, giving atleast five days’ notice of hearing, but in no case shall it fail to meet on an appeal within 30 calendar daysof the filing of notice of appeal Meetings of the Board of Appeals shall be held at the call of the chair, atsuch other times as the board determines, and within 30 calendar days of the filing of a notice of appeal .[1:1.10.5.1]

B.6.5.2

All of the meetings of hearings before the Board of Appeals shall be open to the public. [1:1.10.5.2]

B.6.5.3

The Board of Appeals shall keep minutes of its proceedings showing the vote of each member on everyquestion or, if the member is absent or fails to vote, these actions shall be recorded. [ 1: 1.10.5.3]

B.6.5.4

The Board of Appeals shall keep records of its examinations and other official actions. [ 1: 1.10.5.4]

B.6.5.5

Minutes and records of the Board of Appeals shall be public record. [ 1: 1.10.5.5]

B.6.5.6

A quorum shall consist of not less than 5 members or alternates. [ 1: 1.10.5.6]

B.6.5.7

In varying the application of any provision of this code, or in modifying an order of the AHJ, a two-thirdsvote of the quorum shall be required. [ 1: 1.10.5.7]

B.6.6 Quorum Decisions .

Two-thirds, but not less than four members, of the Board of Appeals shall constitute a quorum. Invarying the application of any provision of this code, or in modifying an order of the AHJ, a majority voteshall be required. [ 1: 1.10.6]

B.6.6.1

Every decision of the Board of Appeals shall be entered in the minutes of the board meeting.[ 1: 1.10.6.1]

B.6.6.2

A decision of the Board of Appeals to modify an order of the AHJ shall be in writing and shall specify themanner in which such modification is made, the conditions upon which it is made, the reasons therefore,and justification linked to specific code sections. [ 1: 1.10.6.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

448 of 491 1/30/2014 9:30 AM

B.6.6.3

Every decision shall be promptly filed in the office of the AHJ and shall be open for public inspection.[ 1: 1.10.6.3]

B.6.6.4

A certified copy shall be sent by mail or delivered in person to the appellant, and a copy shall be publiclyposted in the office of the AHJ for 2 weeks after filing. [ 1: 1.10.6.4]

B.6.6.5

The decision of the Board of Appeals shall be final, subject to such remedy as any aggrieved partymight have through legal, equity, or other avenues of appeal or petition. [ 1: 1.10.6.5]

B.6.6.6

If a decision of the Board of Appeals reverses or modifies a refusal, order, or disallowance of the AHJ,or varies the application of any provision of this code, the AHJ shall take action immediately inaccordance with such decision. [ 1: 1.10.6.6]

B.6.7 Meetings and Records.

B.6.7.1

Meetings of the Board of Appeals shall be held at the call of the chair and at such other times as theboard determines. [ 1: 1.10.7.1]

B.6.7.2

All hearings before the Board of Appeals shall be open to the public. [ 1: 1.10.7.2]

B.6.7.3

The Board of Appeals shall keep minutes of its proceedings showing the vote of each member on everyquestion, or if the member is absent or fails to vote, indicating such actions. [ 1: 1.10.7.3]

B.6.7.4

Minutes and records of the Board of Appeals shall be public record. [ 1: 1.10.7.5]

B.6.8 Procedures.

The Board of Appeals shall establish rules and regulations for its own procedures consistent with theprovisions of this code. [ 1: 1.10.8]

B.6.9 Means of Appeals.

B.6.9.1

Any person shall be permitted to appeal a decision of the AHJ to the Board of Appeals when it isclaimed that any one or more of the following conditions exist:

The true intent of the codes or ordinances described in this code has been incorrectly interpreted.

The provisions of the codes or ordinances do not fully apply.

A decision is unreasonable or arbitrary as it applies to alternatives or new materials. [ 1: 1.10.9.1]

B.6.9.2

An appeal shall be submitted to the AHJ in writing within 30 calendar days of notification of violationoutlining the code provision from which relief is sought and the remedy proposed. [ 1: 1.10.9.2]

B.6.9.3

All documentation supporting an appeal shall be submitted to the AHJ. [ 1: 1.10.9.3]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 12:46:39 EDT 2013

Committee Statement

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

449 of 491 1/30/2014 9:30 AM

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

450 of 491 1/30/2014 9:30 AM

First Revision No. 431-NFPA 2-2013 [ New Section after B.8.2 ]

B.8.3 Conditions of Approval.

B.8.3.1

Any conditions of the initial approval by the AHJ of a use, occupancy, permit, or construction shallremain with the use, occupancy, permit, or construction unless modified by the AHJ. [ 1: 1.12.3.1]

B.8.3.2

The AHJ shall be permitted to require conditions of approval be memorialized via recording in the publicrecords, as part of the plat, permit, or other method as approved by the AHJ. [ 1: 1.12.3.2]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 12:50:17 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

451 of 491 1/30/2014 9:30 AM

First Revision No. 432-NFPA 2-2013 [ Sections B.8.4, B.8.5 ]

B.8.4 Approvals by Other Authorities Having Jurisdiction.

B.8.4.1

The AHJ shall have the authority to require evidence to show that other regulatory agencies havingjurisdiction over the design, construction, alteration, repair, equipment, maintenance, process, andrelocation of structures have issued appropriate approvals. [1:1.12.3.1 1.12.4.1 ]

B.8.4.2

The AHJ shall not be held responsible for enforcement of the regulations of such other regulatoryagencies unless specifically mandated to enforce those agencies’ regulations. [1:1.12.3.2 1.12.4.2 ]

B.8.5 Misrepresentation.

B.8.5.1

Any attempt to misrepresent or otherwise deliberately or knowingly design; install; service; maintain;operate; sell; represent for sale; falsify records, reports, or applications; or other related activity in violationof the requirements prescribed by this code shall be a violation of this code. [1:1.12.4.1 1.12.5.1 ]

B.8.5.2

Such violations shall be cause for immediate suspension or revocation of any related approvals,certificates, or permits issued by this jurisdiction. [1:1.12.4.2 1.12.5.2 ]

B.8.5.3

Such violations shall be subject to any other criminal or civil penalties as available by the laws of thisjurisdiction. [1:1.12.4.3 1.12.5.3 ]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 12:51:18 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

452 of 491 1/30/2014 9:30 AM

First Revision No. 433-NFPA 2-2013 [ Section No. B.8.6 ]

B.8.6 Permits.

A permit shall be predicated upon compliance with the requirements of this code and shall constitutewritten authority issued by the AHJ to maintain, store, use, or handle materials, or to conduct processesthat could produce conditions hazardous to life or property, or to install equipment used in connection withsuch activities. [ 1: 1.12.5.1]

B.8.6.1

A permit shall be predicated upon compliance with the requirements of this code and shall constitutewritten authority issued by the AHJ to maintain, store, use, or handle materials, or to conduct processesthat could produce conditions hazardous to life or property, or to install equipment used in connection withsuch activities. [ 1: 1.12. 5 6 .1]

B.8.6.2

Any permit issued under this code shall not take the place of any other approval, certificate, license, orpermit required by other regulations or laws of this jurisdiction. [ 1: 1.12.6.2]

B.8.6.3

Where additional permits, approvals, certificates, or licenses are required by other agencies, approvalshall be obtained from those other agencies. [ 1: 1.12.6.3]

B.8.6.4

The AHJ shall have the authority to require an inspection prior to the issuance of a permit. [ 1: 1.12.6.4]

B.8.6.5

A permit issued under this code shall continue until revoked or for the period of time designated on thepermit. [ 1: 1.12.6.5]

B.8.6.6

The permit shall be issued to one person or business only and for the location or purpose described in thepermit. [ 1: 1.12.6.6]

B.8.6.7

Any change that affects any of the conditions of the permit shall require a new or amended permit.[ 1: 1.12.6.7]

B.8.6.8

The AHJ shall have the authority to grant an extension of the permit time period upon presentation by thepermittee of a satisfactory reason for failure to start or complete the work or activity authorized by thepermit. [ 1: 1.12.6.8]

B.8.6.9

A copy of the permit shall be posted or otherwise readily accessible at each place of operation and shallbe subject to inspection as specified by the AHJ. [ 1: 1.12.6.9]

B.8.6.10

Any activity authorized by any permit issued under this code shall be conducted by the permittee or thepermittee’s agents or employees in compliance with all requirements of this code applicable thereto andin accordance with the approved plans and specifications. [ 1: 1.12.6.10]

B.8.6.11

No permit issued under this code shall be interpreted to justify a violation of any provision of this code orany other applicable law or regulation. [ 1: 1.12.6.11]

B.8.6.12

Any addition or alteration of approved plans or specifications shall be approved in advance by the AHJ,as evidenced by the issuance of a new or amended permit. [ 1: 1.12.6.12]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

453 of 491 1/30/2014 9:30 AM

B.8.6.13

Permits shall be issued by the AHJ and shall indicate the following: [ 1: 1.12.6.13]

(1) Operation, activities, or construction for which the permit is issued [ 1: 1.12.6.13(1)]

(2) Address or location where the operation, activity, or construction is to be conducted[ 1: 1.12.6.13(2)]

(3) Name, address, and phone number of the permittee [ 1: 1.12.6.13(3)]

(4) Permit number [ 1: 1.12.6.13(4)]

(5) Period of validity of the permit [ 1: 1.12.6.13(5)]

(6) Inspection requirements [ 1: 1.12.6.13(6)]

(7) Name of the agency authorizing the permit (AHJ) [ 1: 1.12.6.13(7)]

(8) Date of issuance [ 1: 1.12.6.13(8)]

(9) Permit conditions as determined by the AHJ [ 1: 1.12.6.13(9)]

B.8.6.14

Any application for, or acceptance of, any permit requested or issued pursuant to this code shallconstitute agreement and consent by the person making the application or accepting the permit to allowthe AHJ to enter the premises at any reasonable time to conduct such inspections as required by thiscode. [ 1: 1.12.6.14]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 12:54:42 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

454 of 491 1/30/2014 9:30 AM

First Revision No. 434-NFPA 2-2013 [ Section No. B.8.7 ]

B.8.7 Revocation or Suspension of Permits.

Where additional permits, approvals, certificates, or licenses are required by other agencies, approvalshall be obtained from those other agencies. [ 1: 1.12.5.3]

B.8.7.1

The AHJ shall be permitted to revoke or suspend a permit or approval issued if any violation of this codeis found upon inspection or in case any false statements or misrepresentations have been submitted inthe application or plans on which the permit or approval was based. [ 1: 1.12.7.1]

B.8.7.2

Revocation or suspension shall be constituted when the permittee is duly notified by the AHJ.[ 1: 1.12.7.2]

B.8.7.3

Any person who engages in any business, operation, or occupation, or uses any premises, after thepermit issued therefore has been suspended or revoked pursuant to the provisions of this code, andbefore such suspended permit has been reinstated or a new permit issued, shall be in violation of thiscode. [ 1: 1.12.7.3]

B.8.7.4

Permits shall be required when the amount of GH 2 exceeds 200 ft 3 (5.7 m 3 ) or LH 2 exceeds 1

gal (3.8 L) inside a building , or 60 gal (230 L) outside of a building.

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 12:56:46 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

455 of 491 1/30/2014 9:30 AM

First Revision No. 510-NFPA 2-2013 [ Sections B.8.8, B.8.9, B.8.10, B.8.11, B.8.12,

B.8.13, B.8.... ]

B.8.8

The AHJ shall have the authority to require an inspection prior to the issuance of a permit.[1:1.12.5.4 1.12.6.4 ]

B.8.9

A permit issued under this code shall continue until revoked or for the period of time designated on thepermit. [1:1.12.5.5 1.12.6.5 ]

B.8.10

The permit shall be issued to one person or business only and for the location or purpose described in thepermit. [1:1.12.5.6 1.12.6.6 ]

B.8.11

Any change that affects any of the conditions of the permit shall require a new or amended permit.[1:1.12.5.7 1.12.6.7 ]

B.8.12

The AHJ shall have the authority to grant an extension of the permit time period upon presentation by thepermittee of a satisfactory reason for failure to start or complete the work or activity authorized by thepermit. [1:1.12.5.8 1.12.6.8 ]

B.8.13

A copy of the permit shall be posted or otherwise readily accessible at each place of operation and shallbe subject to inspection as specified by the AHJ. [1:1.12.5.9 1.12.6.9 ]

B.8.14

Any activity authorized by any permit issued under this code shall be conducted by the permittee or thepermittee’s agents or employees in compliance with all requirements of this code applicable thereto and inaccordance with the approved plans and specifications. [1:1.12.5.10 1.12.6.10 ]

B.8.15

No permit issued under this code shall be interpreted to justify a violation of any provision of this code orany other applicable law or regulation. [1:1.12.5.11 1.12.6.11 ]

B.8.16

Any addition or alteration of approved plans or specifications shall be approved in advance by the AHJ, asevidenced by the issuance of a new or amended permit. [1:1.12.5.12 1.12.6.12 ]

B.8.17

Permits shall be issued by the AHJ and shall bear the name and signature of the AHJ or that of the AHJ’sdesignated representative. In addition, the permit shall indicate the following:

(1) Operation, or activities, or construction for which the permit is issued

(2) Address or location where the operation or activity is to be conducted

(3) Name, and address, and phone number of the permittee

(4) Permit number and date of issuance

(5) Period of validity of the permit

(6) Inspection requirements and other permit conditions [1:1.12.5.13]

(7) Name of the agency authorizing the permit (AHJ)

(8) Date of issuance

(9) Permit conditions as determined by the AHJ

[ 1: 1.12.6.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

456 of 491 1/30/2014 9:30 AM

B.8.18

Any application for, or acceptance of, any permit requested or issued pursuant to this code shall constituteagreement and consent by the person making the application or accepting the permit to allow the AHJ toenter the premises at any reasonable time to conduct such inspections as required by this code.[1:1.12.5.14 1.12.6.14 ]

B.8.19 Revocation or Suspension of Permits.

B.8.19.1

The AHJ shall be permitted to revoke or suspend a permit or approval issued if any violation of this codeis found upon inspection or in case any false statements or misrepresentations have been submitted inthe application or plans on which the permit or approval was based. [1:1.12.6.1 1.12.7.1 ]

B.8.19.2

Revocation or suspension shall be constituted when the permittee is duly notified by the AHJ.[1:1.12.6.2 1.12.7.2 ]

B.8.19.3

Any person who engages in any business, operation, or occupation, or uses any premises, after thepermit issued therefore has been suspended or revoked pursuant to the provisions of this code, andbefore such suspended permit has been reinstated or a new permit issued, shall be in violation of thiscode. [1:1.12.6.3 1.12.7.3 ]

B.8.19.4

Permits shall be required when the amount of GH2 exceeds 200 ft3 (5.7 m3) or LH2 exceeds 1 gal (3.8 L)

inside a building, or 60 gal (230 L) outside of a building.

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Sep 09 09:41:39 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

457 of 491 1/30/2014 9:30 AM

First Revision No. 511-NFPA 2-2013 [ Section No. B.10.3 ]

B.10.3

The AHJ shall be authorized to require design submittals to bear the stamp of a registered designprofessional engineer . [1:1.15.3]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Sep 09 09:51:39 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

458 of 491 1/30/2014 9:30 AM

First Revision No. 435-NFPA 2-2013 [ Section No. B.11 ]

B.11 Notice of Violations and Penalties.

B.11.1 Where Required.

Whenever the AHJ determines violations of this code, a written notice shall be issued to confirm suchfindings. [1:1.16.1]

B.11.2 Serving Notice of Violation .

B.11.2.1

Any order or notice of violation issued pursuant to this code shall be served upon the owner, operator,occupant, registered agent, or other person responsible for the condition or violation, either by personalservice, by mail, or by delivering the same to, and leaving it with, some person of responsibility upon thepremises. by one of the following means: [1:1.16.2.1]

(1) Personal service [ 1: 1.16.2.1(1)]

(2) Mail to last known address of the owner, operator, or registered agent [ 1: 1.16.2.1(2)]

B.11.2.2

For unattended or abandoned locations, a copy of such order or notice of violation shall be posted on thepremises in a conspicuous place at or near the entrance to such premises, and the order or notice shallbe mailed by registered or certified mail, with return receipt requested, to the last known address of theowner, occupant, or both or publication in a newspaper of general circulation wherein the subject premiseis located. disseminated in accordance with one of the following: [ 1: 1.16.2.2]

(1) Mailed to the last known address of the owner, occupant, or registered agent [ 1: 1.16.2.2(1)]

(2) Published in a newspaper of general circulation wherein the property in violation is located[ 1: 1.16.2.2(2)]

B.11.2.3

Any person who mutilates, destroys, or removes posted orders or notices without the authorization of theAHJ shall be subject to the penalties established by the jurisdiction Refusal of an owner, occupant,operator, or other person responsible for the violation to accept the violation notice shall not be cause toinvalidate the violation or the notice of violation. When acceptance of a notice of violation is refused, validnotice shall have deemed to have been served under this section provided the methods of service inB.11.2.1 1.16.2.1 or B.11.2.2 1.16.2.2 have been followed . [1:1.16.3 1.16.2.3 ]

B.11.2.4

Any person who fails to comply with the provisions of this code or who fails to carry out an order madepursuant of this code or violates any condition attached to a permit, approval, or certificate shall besubject to the penalties established by the jurisdiction. [ 1: 1.16.4]

B.11.2.5

Failure to comply with the time limits of an abatement notice or other corrective notice issued by theAHJ shall result in each day that such violation continues being regarded as a new and separateoffense. [ 1: 1.16.5]

B.11.3 Destruction or Removal of Notice.

The mutilation, destruction, or removal of a posted order or violation notice without authorization by theAHJ shall be a separate violation of this code and punishable by the penalties established by the AHJ.[ 1: 1.16.3]

B.11.4 Penalties.

B.11.4.1

Any person who fails to comply with the provisions of this code, fails to carry out an order madepursuant to this code, or violates any condition attached to a permit, approval, or certificate shall besubject to the penalties established by the AHJ. [ 1: 1.16.4.1]

B.11.4.2

Where the AHJ establishes a separate penalty schedule, violations of this code shall be subject to a$250.00 penalty. [ 1: 1.16.4.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

459 of 491 1/30/2014 9:30 AM

B.11.4.3

Failure to comply with the time limits of an order or notice of violation issued by the AHJ shall result ineach day that the violation continues being regarded as a separate offense and shall be subject to aseparate penalty. [ 1: 1.16.4.3]

B.11.4.4

A separate notice of violation shall not be required to be served each day for a violation to be deemed aseparate offense. [ 1: 1.16.4.4]

B.11.4.5 Abatement.

Where a violation creates an imminent danger, the AHJ is authorized to abate such hazard inaccordance with B.5.15 . [ 1: 1.16.5]

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 12:58:00 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

460 of 491 1/30/2014 9:30 AM

First Revision No. 512-NFPA 2-2013 [ Section No. D.2 ]

D.2 Physical Properties.

Liquefied hydrogen is transparent, odorless, and neither corrosive, toxic nor noticeably reactive. Theboiling point at atmospheric pressure is -423°F (-253°C). [With a specific gravity of 0.07], it is only onefourteenth (1/14) as heavy as water.Liquified In converting liquefied hydrogen converted to gaseoushydrogen at standard conditions, it expands approximately 850 times. [55: C.2]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Sep 09 09:57:58 EDT 2013

Committee Statement

Committee Statement: Update of extracted material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

461 of 491 1/30/2014 9:30 AM

First Revision No. 513-NFPA 2-2013 [ Section No. F.4 ]

F.4 Periodic Checklist.

The following maintenance checklist should be completed at intervals based on the recommendations ofthe manufacturer and the requirements of the process:

(1) Test the interlock sequence of all safety equipment. If possible, the interlocks should be made to failmanually, verifying that the related equipment operates as specified by the manufacturer.

(2) Test the safety shutoff valves for tightness of closure as specified by the manufacturer.

(3) Test the main fuel manual valves for operation.

(4) Test the pressure switches for proper operation.

(5) Visually inspect electrical switches, contacts, or controls for signs of arcing or contamination.

(6) Test instruments for proper response to thermocouple failure.

(7) Verify the results of a timed purge procedure, if used.

(8) Clean the air blower filters.

(9) Clean the water, gas compressor, and pump strainers.

(10) Clean the fire-check screens and valve seats and test for freedom of valve movement.

(11) Inspect burners and pilots; if necessary, clean them.

(12) Check orifice plates, air–gas mixers, flow indicators, meters, gauges, and pressure indicators; ifnecessary, clean or repair them.

(13) Check the ignition cables and transformers.

(14) Check the operation of modulating controls.

(15) Check the interior of the equipment, ductwork, and ventilation systems for cleanliness and flowrestrictions.

(16) Test pressure-relief valves; if necessary, clean or replace them .

(17) Inspect air, water, fuel, and impulse piping for leaks.

(18) Inspect radiant tubes and heat exchanger tubes for leakage; if necessary, repair them if necessary .

(19) Lubricate the instrumentation, valve motors, valves, blowers, compressors, pumps, and othercomponents.

(20) Test instrumentation in accordance with manufacturers' recommendations.

(21) Test flame safeguard units.

[86: G.4]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Sep 09 10:05:36 EDT 2013

Committee Statement

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

462 of 491 1/30/2014 9:30 AM

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

463 of 491 1/30/2014 9:30 AM

First Revision No. 514-NFPA 2-2013 [ Section No. G.5.6 [Excluding any Sub-Sections] ]

Peak pressure and impulse loadings resulting from deflagrations (not detonations) can be significantlyreduced by adequate explosion venting. (See NFPA 68, Standard on Explosion Protection by DeflagrationVenting for information on calculating required vent areas .) [45: C.5.6]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Sep 09 10:16:36 EDT 2013

Committee Statement

Committee Statement: Update of extracted material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

464 of 491 1/30/2014 9:30 AM

First Revision No. 515-NFPA 2-2013 [ Section No. H.20 ]

H.20 Asphyxiation.

Possibly the greatest hazard to a user of compressed gases — and especially users of cryogenic fluids —is asphyxiation. Remember, that except for oxygen and for air ( with at least 19.5 percent oxygen) , ALLGAS IS AN ASPHYXIANT. Vent gas only into safe and properly ventilated locations outside of the buildingor fume hood. EXPOSURE TO AN ATMOSPHERE THAT HAS 12 PERCENT OR LESS OXYGEN WILLBRING ABOUT UNCONSCIOUSNESS WITHOUT WARNING AND SO QUICKLY THAT THEINDIVIDUALS CANNOT HELP OR PROTECT THEMSELVES. [45: F.20]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Sep 09 10:22:01 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

465 of 491 1/30/2014 9:30 AM

First Revision No. 441-NFPA 2-2013 [ Chapter I ]

Annex I Design Standard References

This annex is not a part of the requirements of this NFPA document but is included for informationalpurposes only. This annex is extracted from NFPA 55, Compressed Gases and Cryogenic Fluids Code ,Annex G.

I.1 Introduction.

The Occupational Safety and Health Administration (OSHA) establishes requirements for hydrogensystems in 29 CFR 1910.103. The tabular distances reflect those values published in the July 1, 2006,edition of the CFR. The criteria established in OSHA’s tables of distances are based on the 1969 edition ofNFPA 50A, which superseded the 1963 edition. Subsequent editions were adopted in 1973, 1978, 1984,1989, 1994, and 1999. In 2003, the document was integrated into NFPA 55 because the committeebelieved that one standard covering storage and use of all compressed gases and cryogenic fluids wasneeded. NFPA 55 was revised in 2005 because the requirements for compressed gases and cryogenicfluids were broadened. [55: G.1]

Throughout the eight revision cycles of NFPA 55, the tabular distances were revised as the technology inthe use of hydrogen advanced. However, the tabular distances listed in the OSHA tables remain based onthe 1969 data. It is important to recognize that the OSHA tables represent the current statutoryrequirements. While the OSHA tables may, in fact, be accurate, it should also be recognized that theOSHA tables in some cases lack clarity and that, in other cases, hazards recognized by the ongoingevolution of the separation tables have not been acknowledged. [55: G.1]

For an example of lack of clarity, consider row 1 of Table I.2(a) (Building or structure). The OSHA tablerefers to buildings by construction types, including wood frame, heavy timber, ordinary, and fire resistive.Current construction types are now designated as Types I through V, with variations to address theelements of construction, including the supporting structure as well as the construction of the roof andexterior walls. Although one can guess as to the original intent, there is no clear correlation between theconstruction types designated in the OSHA tables and current editions of either NFPA 220, Standard onTypes of Building Construction , or NFPA 5000, Building Construction and Safety Code . [55: G.1]

Other examples where clarity is needed include rows 3, 4, and 5, which specify separation distance fromflammable liquids, raising the question as to whether combustible liquids should be considered or ignored.Examples of hazards not addressed include the fact that there are no prescribed distances for separationfrom property lines, public sidewalks, and parked vehicles. A close comparison between the OSHA tablesand the distance tables found in the 2005 edition of NFPA 55 reveals a number of discrepancies. [55: G.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

466 of 491 1/30/2014 9:30 AM

I.2 OSHA Tables.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

467 of 491 1/30/2014 9:30 AM

The OSHA tables [Table I.2(a) and Table I.2(b)] are provided to inform the code user of the minimumrequirements as they currently exist under 29 CFR and the federal OSHA program. It is incumbent oninstallers and property owners to recognize the limitations of OSHA based on the precedent requirementsestablished with the use of the 1969 edition of NFPA 50A. The use of alternative approaches to distanceas now embodied within the body of the code is subject to approval on a location-by-location basis. Thetypical AHJ traditionally has been a fire official, but that person might not be the only official who exercisesregulatory control for installations of this nature. [55: G.2]

The evaluation of separation distances for bulk gaseous hydrogen systems was the subject of study of ajoint task group that comprised members of NFPA’s Hydrogen Technology Technical Committee and theIndustrial and Medical Gases Technical Committee. The task of the group was to examine the exposuredistances published in Table 10.3.2.2.1 of the 2005 edition of NFPA 55 for the purpose of validation orrevision based on a scientific approach that could be substantiated either through testing or throughgenerally accepted scientific means. [55:G.2 H.1 ]

The determination of separation distance was initially approached through the use of aconsequence-based approach in which the consequences of a release of hydrogen from a systemresulted either in ignition and its attendant jet flame or in an envelope of unignited gas, which was subjectto dispersion. In each instance, the effects of a release on a receptor were considered within the contextof hazard scenarios developed in the performance approach foundational to determining the designscenarios outlined in the performance-based option integral to NFPA 1, Fire Code .[1] [55:G.2 H.1 ]

Table I.2(a) OSHA Table: Minimum Distance from Liquefied Hydrogen Systems to Exposure

Size of Hydrogen System

<3,000 scf

(85 N m3)

3,000 to 15,000 scf (85

N m3 to 425 N m3)

>15,000 scf

(425 N m3)

Type of Outdoor Exposure ft m ft m ft m

1. Building or structure

Wood frame construction1 10 3.1 25 7.6 50 15.2

Heavy timber, noncombustible, or ordinary

construction1 0 0 10 3.1 25 7.6

Fire resistive construction1 0 0 0 0 0 0

2. Wall openings

Not above any part of a system 10 3.1 10 3.1 10 3.1

Above any part of a system 25 7.6 25 7.6 25 7.6

3. Flammable liquids above ground

0–1000 gal (3785 L) 10 3.1 25 7.6 25 7.6

In excess of 1000 gal (3785 L) 25 7.6 50 15.2 50 15.2

4. Flammable liquids below ground —0–1000 gal (3785 L)

Tank 10 3.1 10 3.1 10 3.1

Vent of fill opening of tank 25 7.6 25 7.6 25 7.6

5. Flammable liquids below ground, inexcess of 1000 gal (3785 L)

Tank 20 6.1 20 6.1 20 6.1

Vent of fill opening of tank 25 7.6 25 7.6 25 7.6

6. Flammable gas storage, either highpressure or low pressure

0–15,000 scf (425 N m3) capacity 10 3.1 25 7.6 25 7.6

In excess of 15,000 scf (425 N m3) capacity 25 7.6 50 15.2 50 15.2

7. Oxygen storage

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

468 of 491 1/30/2014 9:30 AM

Size of Hydrogen System

<3,000 scf

(85 N m3)

3,000 to 15,000 scf (85

N m3 to 425 N m3)

>15,000 scf

(425 N m3)

Type of Outdoor Exposure ft m ft m ft m

1 Refer to NFPA 220, Standard on Types of Building Construction , for definitions of various types ofconstruction (1969).

2 But not less than one-half the height of adjacent side wall of the structure.

3 In congested areas such as offices, lunchrooms, locker rooms, time-clock areas.

4 Refer to NFPA 51., Standard for the Design and Installation of Oxygen – Fuel Gas Systems forWelding, Cutting , and Allied Processes (1969).

5 Refer to NFPA 566, Bulk Oxygen Systems at Consumer Sites .

[55: Table G.2(a)]

Table I.2(b) OSHA Table: Minimum Distance (Feet) from Liquefied Hydrogen Systems to Exposure1,2

Liquefied Hydrogen Storage

39.63–3,500 gal(150–13,249 L)

3,501–15,000 gal(13,249–56,780 L)

15,001–30,000 gal(56,780–113,559 L)

Type of Outdoor Exposure ft m ft m ft m

1. Fire resistive building and fire

walls3 5 1.5 5 1.5 5 1.5

2. Noncombustible building3 25 7.6 50 15.2 75 22.9

3. Other buildings3 50 15.2 75 22.9 100 30.5

4. Wall openings, air-compressorintakes, inlets for air-conditioning orventilating equipment

75 22.9 75 22.9 75 22.9

5. Flammable liquids (above groundand vent or fill openings if belowground) (See 513 and 514)

50 15.2 75 22.9 100 30.5

6. Between stationary liquidhydrogen containers

5 1.5 5 1.5 5 1.5

7. Flammable gas storage 50 15.2 75 22.9 100 30.5

8. Liquid oxygen storage and otheroxiders (See 513 and 514)

100 30.5 100 30.5 100 30.5

9. Combustible solids 50 15.2 75 22.9 100 30.5

10. Open flames, smoking andwelding

50 15.2 50 15.2 50 15.2

11. Air compressor intakes or inletsto ventilating or air-conditioningequipment

50 15.2 50 15.2 50 15.2

12. Concentrations of people4 75 22.9 75 22.9 75 22.9

1The distances in Nos. 2, 3, 5, 7, 9, and 12 may be reduced where protective structures such as fire wallsequal to the top of the container, to safeguard the liquefied hydrogen storage system, are located betweenthe liquefied hydrogen installation and the exposure.

2Where protective structures are provided, ventilation and confinement of product should be considered.The 5 ft (1.5 m) distance in Nos. 1 and 6 facilitates maintenance and enhances ventilation.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

469 of 491 1/30/2014 9:30 AM

3Refer to NFPA 220, Standard on Types of Building Construction , for definitions of various types ofconstruction (1969).

4In congested areas such as offices, lunchrooms, locker rooms, time-clock areas.

[55: Table G.2(b)]

Notes for each of the rows found in Table 10.3.2.2.1(a) and Table 10.3.2.2.1(b) [of NFPA 55] have beendeveloped to inform the user of the rationale considered for each of the exposures listed in Table I.2(c)and Table I.2(d) . Table I.2(c) is cross-referenced to Table 10.3.2.2.1(a) and Table 10.3.2.2.1(b) [of NFPA55] by row number. [55:G.2 H.1 ]

Notes are provided to indicate the specific rationale considered for each of the exposures listed. Thenotes are then cross-referenced to specific hazard scenarios further defined in Table I.2(d). Theperformance criteria and design scenarios have been extracted from NFPA 1 as indicated in the extractsprovided. In the event alternative materials or methods are to be employed when bulk systems areinstalled, code users should be aware of the specific hazard scenarios attendant to each exposure.[55:G.2 H.1 ]

Studies by Houf and Schefer of Sandia National Laboratories predicted the radiative heat flux at variousdistances resulting from the ignition of turbulent jet releases of hydrogen from systems at variouspressures. In addition, the concentrations of an unignited hydrogen jet in the surrounding air and theenvelope of locations where the concentration falls below the lower flammability limit for hydrogen weredetermined.[2] Understanding the consequences of release in terms of thermal flux or the boundaries ofthe unignited cloud could then be used to determine distances that were believed to be appropriate basedon the consequence of a release. The consequence approach is referred to as a deterministic approachbecause distances are determined based on consequence alone. Another consequence-based approach,found in a project sponsored by NFPA’s Fire Research Foundation, to determine appropriate separationdistances for certain installations of bulk gaseous hydrogen systems was also reviewed by the task group,and comparisons were made to the existing requirements in the 2005 edition of NFPA 55. [3] [55:G.2 H.1 ]

As the group evaluated the impact of the deterministic tables, it became apparent that the probability ofoccurrence of events could have a bearing on determining a reasonable level of safety. NFPA 55addresses the installation of bulk hydrogen systems used for any application. Whether the installation is toserve an industrial use or an emerging technology that uses hydrogen as an alternative fuel, theinstallation standards have a common basis in which the safety of the user, employees, and members ofthe public is of concern. Recent work undertaken by the U.S. Department of Energy to develop a scientificbasis for control of this material has resulted in substantial technological advancement in the safetyaspects involved in the use of hydrogen as an alternative fuel. Whether the material is used as a vehiclefuel or in classic industrial processes, the hazards of a bulk installation are similar. It was also recognizedthat use as an alternative fuel would have the impact of increasing the number of installations such thatthere would be broader exposure to the public at large. [55:G.2 H.1 ]

Table I.2(c) Hazard Scenario

Row ExposureHazard Scenario

Rationale*

1 Lot lines 1, 2, 3, 4, 5

2 Exposed persons other than those involved in servicing of the system 4

3 Buildings and structures

Combustible construction

Noncombustible non-fire-rated construction

Fire-rated construction with fire resistance rating of not less than 2 hours

2

4 Openings in buildings of fire-rated or non-fire-rated construction (doors,windows, penetrations)

Openable

Fire-rated or non fire-rated

Unopenable

Fire-rated or non fire-rated

1, 2

5 Air intakes (HVAC, compressors, other) 1

6 Fire barrier walls or structures used to shield bulk system from exposures 2, 4

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

470 of 491 1/30/2014 9:30 AM

Row ExposureHazard Scenario

Rationale*

7 Unclassified electrical equipment 2, 5

8 Utilities (overhead), including electric power, building services, hazardousmaterials piping

2, 10

9 Ignition sources such as open flames and welding 3, 5

10 Parked cars 4

11 Flammable gas storage systems, including other hydrogen systems aboveground

Nonbulk Bulk

2

12 Aboveground vents or exposed piping and components of flammable gasstorage systems, including other hydrogen systems below ground

Gaseous or cryogenic

6, 7

13 Hazardous materials (other than flammable gases) storage below ground

Physical hazard materials or health hazard materials

6, 7

14 Hazardous materials storage (other than flammable gases) above ground

Physical hazard materials or health hazard materials

8, 9

15 Ordinary combustibles, including fast-burning solids such as ordinary lumber,excelsior, paper, combustible waste, vegetation other than that found inmaintained landscaped areas

2

16 Heavy timber, coal, other slow-burning combustible solids 2

*See Table I.2(d)for explanation of notes.

[55: Table G.2 H.1 (c a )]

The work of the task group integrated the efforts of Sandia National Laboratories’ risk and reliabilitydepartment. LaChance, in a paper discussing the use of risk in determining acceptable separationdistances, explains the focus of ongoing work to provide a defensible analysis strategy for risk andconsequence assessment of unintended releases from hydrogen systems, generally referred to as ascientific basis for the establishment of separation distances, and describes the work in pertinent part asfollows: [55:G.2 H.1 ]

As part of the U.S. Department of Energy Hydrogen, Fuel Cells & Infrastructure Technologies Program,Sandia National Laboratories is developing the technical basis for assessing the safety of hydrogen-basedsystems for use in the development/modification of relevant codes and standards. The project impactsmost areas of hydrogen utilization, including bulk transportation and distribution, storage, production andutilization. Sandia is developing benchmark experiments and a defensible analysis strategy for risk andconsequence assessment of unintended releases from hydrogen systems. This work includesexperimentation and modeling to understand the fluid mechanics and dispersion of hydrogen for differentrelease scenarios, including investigations of hydrogen combustion and subsequent heat transfer fromhydrogen flames. The resulting technical information is incorporated into engineering models that areused for assessment of different hydrogen release scenarios and for input into quantitative riskassessments (QRA) of hydrogen facilities. [55:G.2 H.1 ]

The QRAs are used to identify and quantify scenarios for the unintended release of hydrogen, identify thesignificant risk contributors at different types of hydrogen facilities, and to identify potential accidentprevention and mitigation strategies to reduce the risk to acceptable levels. The results of the QRAs areone input into a risk-informed codes and standards development process that can also include otherconsiderations by the code and standard developers. Examples of these other considerations can includethe results of deterministic analyses of selected accidents scenarios, the need for defense-in-depth forcertain safety features (e.g., overpressure protection), the use of safety margins for high-pressurecomponents, and requirements identified from the actual occurrences at hydrogen facilities. [4][55:G.2 H.1 ]

To evaluate risk, the history of leakage data from high pressure compressed gas systems was needed.Hydrogen-specific leak data were provided by one of the major suppliers through the use of a 5-yeardocumented collection of leak data from both industrial and fueling uses. These data were augmentedwith data from other sources after being reviewed for applicability, and representative values wereselected. The source documents considered in augmentation of hydrogen-specific data included the

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

471 of 491 1/30/2014 9:30 AM

following publications: [ 55: G.2]

(1) “Determination of Safety Distances,” European Industrial Gases Association, IGC Doc 75/07/E, 2007

(2) A. W. Cox, F. P. Lees, and M. L. Ang, “Classification of Hazardous Locations,” Institution of ChemicalEngineers, May 2003

(3) C. H. Blanton and S. A. Eide, “Savannah River Site Generic Data Base Development,” WSRC-TR-93-262, Westinghouse Savannah River Company, June 30, 1993

(4) J. Spouge, “New Generic Leak Frequencies for Process Equipment,” Process Safety Progress (Vol.24, No. 4), December 2005 [ 55: G.2]

Table I.2(d) Hazard Scenario Rationale Notes to Table I.2(c)

NoteNumber

Statement Performance Criteria Hazardous Materials Design Scenario

1

Gas release andsubsequententrainment oraccumulation by thereceptor

Explosion Conditions.The facility design shallprovide an acceptable levelof safety for occupants andfor individuals immediatelyadjacent to the propertyfrom the effects ofunintentional detonation ordeflagration. [1:5.2.2.2]

Hazardous Materials Design Scenario 1.Hazardous Materials Design Scenario 1involves an unauthorized release of hazardousmaterials from a single control area. Thisdesign scenario shall address the concernregarding the spread of hazardous conditionsfrom the point of release. [1:5.4.4.1]

2

Fire spread to orfrom adjacentequipment orstructure

Property Protection. Thefacility design shall limit theeffects of all requireddesign scenarios fromcausing an unacceptablelevel of property damage.[1:5.2.2.4]

Hazardous Materials Design Scenario 2.Hazardous Materials Design Scenario 2involves an exposure fire on a location wherehazardous materials are stored, used,handled, or dispensed. This design scenarioshall address the concern regarding how a firein a facility affects the safe storage, handling,or use of hazardous materials. [1:5.4.4.2]

3

Gas explosionhazard on site oraffecting adjacentproperty

Explosion Conditions.The facility design shallprovide an acceptable levelof safety for occupants andfor individuals immediatelyadjacent to the propertyfrom the effects ofunintentional detonation ordeflagration. [1:5.2.2.2]

Hazardous Materials Design Scenario 1.Hazardous Materials Design Scenario 1involves an unauthorized release of hazardousmaterials from a single control area. Thisdesign scenario shall address the concernregarding the spread of hazardous conditionsfrom the point of release. [1:5.4.4.1]

4

Threat of injuries onsite or adjacentproperty

Hazardous MaterialsExposure. The facilitydesign shall provide anacceptable level of safetyfor occupants and forindividuals immediatelyadjacent to the propertyfrom the effects of anunauthorized release ofhazardous materials or theunintentional reaction ofhazardous materials.[1:5.2.2.3]

Hazardous Materials Design Scenario 2.Hazardous Materials Design Scenario 2involves an exposure fire on a location wherehazardous materials are stored, used,handled, or dispensed. This design scenarioshall address the concern regarding how a firein a facility affects the safe storage, handling,or use of hazardous materials. [1:5.4.4.2]Hazardous Materials Design Scenario 4.Hazardous Materials Design Scenario 4involves an unauthorized discharge with eachprotection system independently renderedineffective. This set of design hazardousmaterials scenarios shall address concernregarding each protection system or protectionfeature, considered individually, beingunreliable or becoming unavailable.[1:5.4.4.4.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

472 of 491 1/30/2014 9:30 AM

NoteNumber

Statement Performance Criteria Hazardous Materials Design Scenario

5

Ignition of anunignitedrelease/ventedhydrogen

Explosion Conditions.The facility design shallprovide an acceptable levelof safety for occupants andfor individuals immediatelyadjacent to the propertyfrom the effects ofunintentional detonation ordeflagration. [1:5.2.2.2]

Hazardous Materials Design Scenario 1.Hazardous Materials Design Scenario 1involves an unauthorized release of hazardousmaterials from a single control area. Thisdesign scenario shall address the concernregarding the spread of hazardous conditionsfrom the point of release. [1:5.4.4.1]

6Damage to exposedcomponents ofundergroundsystem that areexposed aboveground

Property Protection. Thefacility design shall limit theeffects of all requireddesign scenarios fromcausing an unacceptablelevel of property damage.[1:5.2.2.4]

Hazardous Materials Design Scenario 1.Hazardous Materials Design Scenario 1involves an unauthorized release of hazardousmaterials from a single control area. Thisdesign scenario shall address the concernregarding the spread of hazardous conditionsfrom the point of release. [1:5.4.4.1]

7

Damage toabovegroundsystem due tofunction ofexplosion controlsystem used to ventunderground vaultor structure

Property Protection. Thefacility design shall limit theeffects of all requireddesign scenarios fromcausing an unacceptablelevel of property damage.[1:5.2.2.4]

Explosion Conditions.The facility design shallprovide an acceptable levelof safety for occupants andfor individuals immediatelyadjacent to the propertyfrom the effects ofunintentional detonation ordeflagration. [1:5.2.2.2]

Hazardous Materials Design Scenario 3.Hazardous Materials Design Scenario 3involves the application of an external factor tothe hazardous material that is likely to result ina fire, explosion, toxic release, or other unsafecondition. This design scenario shall addressthe concern regarding the initiation of ahazardous materials event by the applicationof heat, shock, impact, or water onto ahazardous material being stored, used,handled, or dispensed in the facility. [1:5.4.4.3]

8

Fire or explosion inother hazardousmaterials resultingin release ofhydrogen

Hazardous MaterialsExposure. The facilitydesign shall provide anacceptable level of safetyfor occupants and forindividuals immediatelyadjacent to the propertyfrom the effects of anunauthorized release ofhazardous materials or theunintentional reaction ofhazardous materials.[1:5.2.2.3]

Hazardous Materials Design Scenario 3.Hazardous Materials Design Scenario 3involves the application of an external factor tothe hazardous material that is likely to result ina fire, explosion, toxic release, or other unsafecondition. This design scenario shall addressthe concern regarding the initiation of ahazardous materials event by the applicationof heat, shock, impact, or water onto ahazardous material being stored, used,handled, or dispensed in the facility. [1:5.4.4.3]

9

Fire or explosion inhydrogen systemresulting in releaseof other hazardousmaterials

Hazardous MaterialsExposure. The facilitydesign shall provide anacceptable level of safetyfor occupants and forindividuals immediatelyadjacent to the propertyfrom the effects of anunauthorized release ofhazardous materials or theunintentional reaction ofhazardous materials.

Hazardous Materials Design Scenario 2.Hazardous Materials Design Scenario 2involves an exposure fire on a location wherehazardous materials are stored, used,handled, or dispensed. This design scenarioshall address the concern regarding how a firein a facility affects the safe storage, handling,or use of hazardous materials. [1:5.4.4.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

473 of 491 1/30/2014 9:30 AM

NoteNumber

Statement Performance Criteria Hazardous Materials Design Scenario

[1:5.2.2.3]

10

Failure ofequipment exposinghydrogen system toelectrical hazard,physical, or healthhazard; failure ofsystem exposingutilities to failure

Property Protection. Thefacility design shall limit theeffects of all requireddesign scenarios fromcausing an unacceptablelevel of property damage.[1:5.2.2.4]

Public Welfare. Forfacilities that serve a publicwelfare role as defined in4.1.5 of NFPA 1, the facilitydesign shall limit theeffects of all requireddesign scenarios fromcausing an unacceptableinterruption of the facility'smission. [1:5.2.2.5]

Hazardous Materials Design Scenario 3.Hazardous Materials Design Scenario 3involves the application of an external factor tothe hazardous material that is likely to result ina fire, explosion, toxic release, or other unsafecondition. This design scenario shall addressthe concern regarding the initiation of ahazardous materials event by the applicationof heat, shock, impact, or water onto ahazardous material being stored, used,handled, or dispensed in the facility. [1:5.4.4.3]

A hierarchy was developed that gave hydrogen-specific data the highest priority, followed by non-gas-specific data where available for high pressure components. Piping and instrumentation drawings (P&IDs)were then prepared to define a standard bulk supply system in terms of modules that might be found inthe typical system. The P&IDs can be found in A.3.3.225.10. The P&IDs were reviewed by suppliers andthe typical nature verified. [55:G.2 H.1 ]

Frequency and size of leaks encountered were evaluated across a number of systems, including bothindustrial and fueling operations. The leak/failure data were then applied to “typical” fitting counts(components) integral to each of the modules identified in the P&IDs for each of the components. Thefailure data were based on the most recent 5-year history for high pressure systems. Hydrogen-specificdata were provided by Compressed Gas Association (CGA) representatives. These data were augmentedby failure data from other resources obtained by researchers from Sandia National Laboratories andcombined to quantify a probability for failure on a component-by-component basis [hoses (pigtails),valves, elbows, tees, pipe, gauges, etc.]. The analysis resulted in a probability for failure being developedfor each component, which could then be wrapped into failures expected across the spectrum of thevarious modules included in the array of P&IDs developed. [55:G.2 H.1 ]

A Bayesian approach to the determination of probability was used in the analysis of data by researchersat Sandia National Laboratories. The technical approach and supporting details can be found in thearticles listed in Annex E and informational articles found in M.2. The advantage of the Bayesianapproach is that it can combine data from different sources to include uncertainty. This approach iscontrary to what has been done in other sources. For example, judgment can be used as a means todetermine risk; however, that method does not provide for uncertainty. Such methods are qualitative atbest. By comparison, the use of specific leak data results in a quantitative approach. [55:G.2 H.1 ]

The tables developed for inclusion in Chapter 7 are said to be risk informed, not risk based, the differencebeing that integral to the risk tables is a series of decisions based on the applicability of various factors.For example, with respect to thermal flux, one could use a series of exposures from no harm to fatality,and those exposures could then be taken from the point of various receptors (workers, people on theproperty where the installation is located, people off the property, etc.). One of the primary decisions madeby the group was that in the final analysis the risk presented for the typical GH2 installation (either

industrial or fueling applications) should present no greater risk to the public in terms of fatalities or injuriesthan does an existing gasoline service station. The average frequency of a fatality or injury associatedwith the operation of a single gasoline station has been reported to be approximately 2E-5/yr and 7E-4/yr,respectively. [5] Other key decisions of the group included the parameters given in Sections I.3 throughI.6. [55:G.2 H.1 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

474 of 491 1/30/2014 9:30 AM

I.3 Lower Flammable Limit — 4 Percent H2 by Volume.

In scenarios where the concern is that a plume of unignited GH2 from a release may reach an ignition

source, the separation distance was determined using a computational fluid dynamics (CFD) model todetermine the distance required to reduce the GH2 concentration to 4 percent by volume. A concentration

of 4 percent hydrogen in air has been shown to be the lower bounds of an ignitible mixture under idealconditions for burning. As such, 4 percent is the established lower flammable limit for hydrogen mixturesin air. In other situations, such as the design of flammable gas detection systems, target concentrations of2 percent, or 1 percent GH2 by volume, are commonly used to provide a factor of safety and account for

uncertainties in the configuration that can affect the detection system. This fact could lead one to concludethat 1 percent or 2 percent should be used as the basis for establishing a separation distance as well.However, the inherent uncertainties associated with detection systems, such as room configuration,ventilation rates, and so forth, that drive conservatism in the design of a hydrogen detection system do notexist in the case of this CFD model, and therefore no additional reduction of the conservative 4 percentvalue is warranted. [55:G.3 H.2 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

475 of 491 1/30/2014 9:30 AM

I.4 Use of 3 Percent of Internal Pipe Diameter (ID) as Leak Size.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

476 of 491 1/30/2014 9:30 AM

The development of separation distances for hydrogen facilities can be determined in several ways. Aconservative approach is to use the worst possible accidents in terms of consequences. Such accidentscan be of very low frequency such that they likely would never occur. Although this approach boundsseparation distances, the resulting distances are generally prohibitive. The current separation distancesdo not reflect this approach. An alternative deterministic approach that is often utilized by standardsdevelopment organizations (SDOs) and allowed under some regulations is to select accident scenariosthat are more probable but do not provide bounding consequences. In this approach, expert opinion isgenerally used to select the accidents used as the basis for the prescribed separation distances. Althoughanecdotal experience often forms the basis for the selection of the accidents, the frequency of accidentscan also be used as a selection criterion. [55:G.4 H.3 ]

A detailed description of the process used and the results achieved are provided in a technical articleincluded in Annex E.[6] This process follows guidance by the Fire Protection Research Foundationpublished in March 2007 that encourages NPFA Technical Committees to use risk concepts in theirdecision-making process.[7] A risk-informed process, as opposed to a risk-based process, utilizes riskinsights obtained from quantitative risk assessments (QRAs) combined with other considerations toestablish code requirements. The QRAs are used to identify and quantify scenarios for the unintendedrelease of hydrogen, identify the significant risk contributors at different types of hydrogen facilities, and toidentify potential accident prevention and mitigation strategies to reduce the risk to acceptable levels.[55:G.4 H.3 ]

The risk-informed approach included two considerations: the frequency of hydrogen system leakage andthe risk from leakage events. Unfortunately, hydrogen component leakage data are very limited. PastQRAs of hydrogen facilities have thus been forced to utilize leakage rates based on data fromnon-hydrogen facilities. The European Industrial Gas Association (EIGA) [8], for example, assessed thefrequencies presented in five different sources and then used values that were deemed appropriate for theassessment rather than performing any further analysis. [55:G.4 H.3 ]

Rather than selecting a value from different generic sources, a different approach was utilized in thisassessment. Data from different sources were collected and combined using Bayesian statistics. [9] Thisapproach has three major advantages over the approach utilized by EIGA and other QRA guidancedocuments. First, it allows for the generation of leakage rates for different amounts of leakage. Second, itgenerates uncertainty distributions for the leakage rates that can be propagated through the QRA modelsto establish the uncertainty in the risk results. Finally, it provides a means for incorporating limitedhydrogen-specific leakage data to establish estimates for leakage rates for hydrogen components. Limitedhydrogen-specific leakage data were obtained through the efforts of the CGA for use in the Bayesiananalysis. [55:G.4 H.3 ]

Component leak frequencies as a function of leak size were generated for several hydrogen components.The hydrogen-specific leakage rates were used to estimate the leakage frequency for four examplesystems used as the basis for the risk evaluation used in the study. The cumulative probability for differentleak sizes was then calculated to determine what range of leaks represents the most likely leak sizes. Theresults of this analysis indicated that leaks less than 0.1 percent of the component flow areas represent 95percent of the leakage frequency for the example systems. Leak areas less than 10 percent of the flowarea are estimated to result in 99 percent of the leaks that could occur based on the results of theanalysis. [55:G.4 H.3 ]

The risks resulting from different size leaks were also evaluated for four standard gas storageconfigurations. The risk evaluations indicate that the use of 0.1 percent of the component flow area as thebasis for determining separation distances results in risk estimates that significantly exceed the 2 ×

10-5/yr risk guideline selected by the NFPA separation distance working group, particularly for the 7500psig and 15,000 psig systems. On the other hand, use of a leak size equal to between 1 percent and 10percent of the component flow area results in risk estimates that are reasonably close to the risk guideline.The fact that the risk estimates are a factor of 2 higher than the risk guideline for the 7500 psig and 15,000psig example systems was weighed against the uncertainties in the QRA models, most of which result inconservative risk estimates. [55:G.4 H.3 ]

Based on the results of both the system leakage frequency evaluation and the associated riskassessment, a diameter of 3 percent of the flow area corresponding to the largest internal pipedownstream of the highest pressure source in the system is used in the model. The use of a 3 percentleak area results in capturing an estimated 98 percent of the leaks that have been determined to beprobable based on detailed analysis of the typical systems employed. Typical systems to includecomponents have been established in the form of P&IDs and incorporated into the work so that the basisfor the statistical determinations reached can be documented. [55:G.4 H.3 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

477 of 491 1/30/2014 9:30 AM

I.5 Selected Heat Flux Values.

The values for heat flux used in development of the separation distance tables are as follows:[55:G.5 H.4 ]

(1) 1,577 W/m2 (500 Btu/hr-ft2)

(2) 4,732 W/m2 (1,500 Btu/hr-ft2)

(3) 20,000 W/m2 (6,340 Btu/hr-ft2)

(4) 25,237 W/m2 (8,000 Btu/hr-ft2)

[ 55: H.4]

The basis for using each value is as follows:

(1) 1,577 W/m2 (500 Btu/hr-ft2) is used as the “no harm” value. This heat flux is defined by API 521,Recommended Practice, Guide for Relieving Depressuring Systems, as the heat flux threshold towhich personnel with appropriate clothing can be continuously exposed. [10] This value is slightlyless than what the Society of Fire Protection Engineers determined to be the “no harm” heat flux

threshold (540 Btu/hr-ft2), that is, the maximum heat flux to which people can be exposed forprolonged periods of time without experiencing pain. [11] [55:G.5 H.4 ]

(2) 4,732 W/m2 (1,500 Btu/hr-ft2) is defined by API 521 as the heat flux threshold in areas whereemergency actions lasting several minutes may be required by personnel without shielding but withappropriate clothing. [10] It is also defined by the International Fire Code as the threshold forexposure to employees for a maximum of 3 minutes. [12] [ 55: G.5] [ 55: H.4]

(3) 20,000 W/m2 (6,340 Btu/hr-ft2) is generally considered the minimum heat flux for the nonpilotedignition of combustible materials, such as wood. [13] [ 55: H.4]

(4) 25,237 W/m2 (8,000 Btu/hr-ft2) is the threshold heat flux imposed by the International Fire Code fornoncombustible materials. [12] [55:G.5 H.4 ]

I.6 Pressure as a Controlling Parameter in Lieu of Volume.

The traditional approach of using volume as a determinant in the establishment of distance was revised infavor of using pressure as the determinate factor. The work of Houf and Schefer demonstrated that theflame radiation heat flux and flame length varied with the pressure of gas released across a given orifice.[2] In cases where the high pressure leak of hydrogen was unignited, a turbulent jet is formed and thearea of the flammable envelope can be calculated. [55:G.6 H.5 ]

Peak flows were used as a means to determine acceptable distances, and comparisons were made tocontents. It was determined that once the threshold for a bulk supply had been exceeded, gas pressure,not volume, was the determining factor in establishing the radiant flux or the unignited jet concentration.Detailed analysis over a series of tank pressures of 18.25 bar (250 psig), 207.85 bar (3000 psig), 518.11bar (7500 psig), and 1035.21 bar (15,000 psig) over a range of leak diameters were examined.[55:G.6 H.5 ]

Transient effects varying the quantity and pressure decay over time were ruled out as controllingparameters. Volume was then considered to be at its worst case, which assumed that pressure wasconstant due to the volume contained. This is especially true for large systems typically encountered incommercial applications. Small systems using small-diameter tubing are accounted for by the use oftables that allow the user to calculate the benefit from the use of small-diameter systems. [55:G.6 H.5 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

478 of 491 1/30/2014 9:30 AM

I.7 References.

[55:G.7 H.6 ]

(1) NFPA 1, Fire Code, 2009 edition, National Fire Protection Association, Quincy, MA, Chapter 5.

(2) W. Houf and R. Schefer, “Predicting Radiative Heat Fluxes and Flammability Envelopes fromUnintended Releases of Hydrogen,” International Journal of HydrogenEnergy, Elsevier Publishing,2007, Vol. 32, pp. 136–151.

(3) J. Floyd, Siting Requirements for Hydrogen Supplies Serving Fuel Cells in Non-CombustibleEnclosures, Hughes Associates, Inc., 3610 Commerce Drive, Suite 817, Baltimore, MD 21227, HAIProject #3250-000, November 30, 2006.

(4) J. LaChance, Risk-Informed Separation Distances for Hydrogen Refueling Stations, Risk andReliability Department, Sandia National Laboratories, Albuquerque, NM, May 2007. (Sandia is amultiprogram laboratory operated by Sandia Corporation, a Lockheed Martin Company, for theUnited States Department of Energy’s National Nuclear Security Administration under ContractDEAC04-94-AL85000.)

(5) Ibid, p. 11, reference to Fires in or at Service Stations and Motor Vehicle Repair and Paint Shops,NFPA, April 2002.

(6) J. LaChance, W. Houf, B. Middleton (all of Sandia National Laboratories), and L. Fluer (of Fluer, Inc.),“Analyses to Support Development of Risk-Informed Separation Distances for NFPA HydrogenCodes and Standards,” SAND 2009-0874, Sandia National Laboratories, Albuquerque, NM 87185,and Livermore, CA 94550, March 2009.

(7) S. E Rose, S. Flamberg, and F. Leverenz, “Guidance Document for Incorporating Risk Concepts intoNFPA Codes and Standards,” Fire Protection Research Foundation, March 2007.

(8) “Determination of Safety Distances,” European Industrial Gases Association, IGC Doc. 75/07/E,2007.

(9) C. L. Atwood, J. L. LaChance, H. F. Martz, D. J. Anderson, M. Englehardt, D. Whitehead, and T.Wheeler, “Handbook of Parameter Estimation for Probabilistic Risk Assessment,” NUREG/CR-6823,U.S. Nuclear Regulatory Commission, Washington, D.C., 2003.

(10) API Recommended Practice 521, Guide for Pressure Relieving and Depressuring Systems, 4thedition, March 1997, API Publishing Services, 1220 L. St. N.W., Washington, DC 20005, Table 8, p.41.

(11) “Predicting 1st and 2nd Degree Skin Burns from Thermal Radiation,” SFPE Engineering Guide,Society of Fire Protection Engineers, Bethesda, MD 20814, March 2000, p. 8.

(12) ICC, International Fire Code™, 2006 edition, International Code Council, 4051 West FlossmoorRoad, Country Club Hills, IL 60478-5795, Table 2209.5.4.3.6(1), p. 210.

(13) V. Babrauskas, “Ignition of Wood: A Review of the State of the Art,” Interflam 2001, InterscienceCommunications Ltd., London, 2001, pp. 71–88.

[55:G.7 H.6 ]

Supplemental Information

File Name Description

Table_I.2_a_FR_441_.docx

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

479 of 491 1/30/2014 9:30 AM

Submittal Date: Mon Jul 01 13:12:54 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

480 of 491 1/30/2014 9:30 AM

Table I.2(a) OSHA Table: Minimum Distance from Liquefied Hydrogen Systems to Exposure

Size of Hydrogen System

<3,000 scf (85

Nm3)

3,000 to 15,000 scf (85 Nm3 to

425 Nm3) >15,000 scf (425 Nm3)

Type of Outdoor Exposure ft m ft m ft m

1. Building or structure

Wood frame construction1 10 3.1 25 7.6 50 15.2

Heavy timber, noncombustible, or ordinary construction1

0 0 10 3.1 25 7.6

Fire resistive construction1 0 0 0 0 0 0

2. Wall openings

Not above any part of a system 10 3.1 10 3.1 10 3.1

Above any part of a system 25 7.6 25 7.6 25 7.6

3. Flammable liquids above ground

0–1000 gal (3785 L) 10 3.1 25 7.6 25 7.6

In excess of 1000 gal (3785 L) 25 7.6 50 15.2 50 15.2

4. Flammable liquids below ground — 0–1000 gal (3785 L)

Tank 10 3.1 10 3.1 10 3.1

Vent of fill opening of tank 25 7.6 25 7.6 25 7.6

5. Flammable liquids below ground, in excess of 1000 gal (3785 L)

Tank 20 6.1 20 6.1 20 6.1

Vent of fill opening of tank 25 7.6 25 7.6 25 7.6

6. Flammable gas storage, either high pressure or low pressure

0–15,000 scf (425 Nm3) capacity 10 3.1 25 7.6 25 7.6

In excess of 15,000 scf (425 Nm3) capacity 25 7.6 50 15.2 50 15.2

7. Oxygen storage

12,000 scf (340 Nm3) or less4 —

More than 12,000 scf (340 Nm3)5 —

8. Fast-burning solids such as ordinary lumber, excelsior, paper

50 15.2 50 15.2 50 15.2

9. Slow-burning solids such as heavy timber, coal

25 7.6 25 7.6 25 7.6

10. Open flames and welding 25 7.6 25 7.6 252 7.62

11. Air compressor intakes or inlets to ventilating or air-conditioning equipment

50 15.2 50 15.2 50 15.2

12. Concentration of people3 25 7.6 50 15.2 50 15.2

First Revision No. 516-NFPA 2-2013 [ Section No. J.2 ]

J.2 Electrical Design Standards for Vacuum Furnace Manufacturers.

The following is a list of electrical associations and codes, parts of which are used whose publications canbe used as a guide for safe installation and application of electrical equipment and installation:

(1) National Fire Protection Association (NFPA), publisher of NFPA 70, National Electrical Code

(2) National Electrical Manufacturer’s Association (NEMA)

(3) Joint Industrial Council (JIC)

(4) Electronic Industries Association (EIA)

(5) Canadian Standards Association (CSA)

(6) FM Global

[86: L.2]

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Sep 09 10:39:39 EDT 2013

Committee Statement

Committee Statement: Update of extract material

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

481 of 491 1/30/2014 9:30 AM

First Revision No. 147-NFPA 2-2013 [ Section No. K.2.2.4 ]

K.2.2.4 Deflagration Venting.

Hydrogen deflagration venting for limiting explosion damage should be in accord accordance with therequirements in Section 6.9 of this standard and with NFPA 68, Standard on Explosion Protection byDeflagration Venting .

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 07 11:38:07 EDT 2013

Committee Statement

Committee Statement: Editorial. Text revised to correct typo.

Response Message:

Public Input No. 118-NFPA 2-2013 [Section No. K.2.2.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

482 of 491 1/30/2014 9:30 AM

First Revision No. 148-NFPA 2-2013 [ Section No. K.2.2.5.3 [Excluding any

Sub-Sections] ]

The following factors should be considered in the design of an a deflagration venting system:

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 07 11:38:39 EDT 2013

Committee Statement

Committee Statement: Editorial.

Response Message:

Public Input No. 119-NFPA 2-2013 [Section No. K.2.2.5.3 [Excluding any Sub-Sections]]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

483 of 491 1/30/2014 9:30 AM

First Revision No. 469-NFPA 2-2013 [ New Section after K.4 ]

Annex L Hydrogen Detection Systems

L.1 General.

The purpose of gas detectors is to detect an unintended release of hydrogen and send a signal toactivate an alarm or other safety systems and measures (e.g., ventilation systems, system shutdown)and a device for recording the gas concentration. Hydrogen detectors can be configured to havemultiple alarm levels, for example, a low-level alarm that activates an audible signal and increasesventilation and a high-level alarm that initiates a system shutdown and signals first responders of apotential emergency situation. Alarm levels should be some set fraction of the hydrogen lowerflammable limit, which in air is 4 vol%.

L.2 Types of Gas Detectors that Effectively Detect Hydrogen.

The following types of gas detectors (often called sensing elements in the detector or simply sensor) aremost effective for detecting hydrogen:

(1) Thermal conductivity (TC) sensors

(2) Combustible gas (CGS) sensors

(3) Electrochemical (EC) sensors

(4) Metal oxide (MOX) sensors

(5) Sensing elements based on palladium thin films (PTF)

L.2.1

Hydrogen detectors based on the sensing elements listed in Section L.2 are commercially available.These sensing elements are used in many detector models, many of which have been optimized todetect gases other than hydrogen. Therefore, it is necessary to review and verify manufacturerspecifications on detector performance to verify the detector’s ability to respond to hydrogen. Therelative merits and general performance characteristics of the hydrogen sensing elements listed inSection L.2 were reviewed and summarized by Buttner et al. [1]. Deployed sensors should beinstrumented with the necessary control circuitry and user interface. The user interface can includedisplays, electrical output signals providing hydrogen concentration, and alarm interfaces. Criticalsensor performance parameters and specifications that can be relevant to specific applications include,but are not limited to, the following:

(1) Linear Range. The sensor dynamic range is the concentration range in which the change in thesensor response is proportional to the change in analyte concentration. The sensor should respond upto the lower flammable limit of hydrogen (4 vol% in air). It is recommended that the sensor linear rangeextend beyond the LFL to a hydrogen concentration of 10 vol%.

(2) Alarm Thresholds. Facility monitors should have alarm set points at 25 percent of hydrogen LFL, or1 vol% hydrogen, with lower alarm thresholds at 10 percent of the LFL (0.4 vol% hydrogen) or lower forcritical applications.

(3) Lower Detection Limit (LDL). The smallest signal above background noise that the sensor canreliably detect and which is frequently calculated as three times the standard deviation of thebackground signal. The LDL of the deployed sensor should be at least 25 percent of the lowest alarmthreshold.

(4) Selectivity. Hydrogen fueling stations will be co-deployed with conventional fueling operations. TheCGS and MOX sensor platforms will respond to both hydrogen and to petroleum products and naturalgas, although the relative sensitivity to hydrogen versus interferent (i.e., “cross-sensitivity”) vapor variessignificantly among model types. A review of manufacturers’ specifications and in-house testing (ortesting to a contract laboratory) is recommended to verify appropriate detector selectivity.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

484 of 491 1/30/2014 9:30 AM

L.2.2

Furthermore, the impact of fluctuations in ambient environmental conditions such as temperature (T),relative humidity (RH), and barometric pressure (P) on the sensor should be considered. Temperaturescan range from −40˚ F to +104˚ F (−40˚C to +40˚C) depending on prevailing weather conditions.Temperature extremes are more likely encountered with outdoor deployment. Sensors should becompatible with prevailing weather conditions. Electrochemical sensors typically do not perform wellbelow 32˚F (0˚C). Although many detectors can be affected by pressure changes, local barometricpressure does not generally fluctuate significantly. However, detectors calibrated in one location (e.g., atsea level with 1 bar barometric pressure) might not be accurate at the deployment site (e.g., elevateddeployments such as Denver). Although most detectors are not significantly affected by moderatefluctuations of RH, operation at extreme RH (less than 10 percent or greater than 90 percent) canadversely affect detector performance. Electrochemical sensors can degrade at low RH. The calibrationcurve of many MOX sensors is affected by RH extremes.

Detailed discussions on recommended sensor performance parameters and correspondingspecifications for a range of hydrogen applications can be found in Buttner et al. [2].

L.3 Location of Gas Detectors to Effectively Detect Hydrogen.

The following should be considered to effectively locate gas detectors where they are most likely todetect an unintended hydrogen release:

(1) Hydrogen buoyancy, which dictates that sensors should be placed above any potential releasepoint.

(2) A gas detector mounting on the ceiling should be avoided because of elevated temperatures at theceiling. Gas detectors should be mounted a foot or more below the ceiling—possibly using thewall.

(3) The gas detector should be mounted facing the potential release point. However, considerationsshould be given to the effect ventilation would have on air flow and how this alteration of air flowmight impact the direction or orientation of the release point.

(4) The gas detector should be effectively downwind of any potential air flow.

(5) Hydrogen gas detectors should not be located in any structural entrapments.

(6) Hydrogen gas detectors can also be mounted on a wall close to but above the hydrogendispensing system.

L.4 Number of Gas Detectors to Effectively Detect Hydrogen.

In assessing the number of gas detectors required to detect a hydrogen release, the following should beconsidered:

(1) A minimum of one gas detector should be deployed per dispenser.

(2) If a canopy is used to protect the dispensing operation, the gas detector should be placed directlyabove the dispenser.

(3) Additional gas detectors can be placed along the length of the canopy to increase the probabilityof detecting a release.

L.5 Referenced Publications.

[1]. Buttner, W., et al., “An overview of hydrogen safety sensors and requirements,” InternationalJournal of Hydrogen Energy , 36, 2011.

[2]. Buttner, W., et al., “Summary and Findings from the NREL/DOE Hydrogen Sensor Workshop,”NREL Technical Report Number: NREL/TP-5600-55645, July 2012. http://www.nrel.gov/docs/fy12osti/55645.pdf

Submitter Information Verification

Submitter Full Name: Susan Bershad

Organization: National Fire Protection Assoc

Street Address:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

485 of 491 1/30/2014 9:30 AM

City:

State:

Zip:

Submittal Date: Tue Aug 27 08:41:39 EDT 2013

Committee Statement

Committee Statement: New Annex Material on Hydrogen Gas Detectors

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

486 of 491 1/30/2014 9:30 AM

First Revision No. 436-NFPA 2-2013 [ Section No. L.1.2.4 ]

M.1.2.4 ASME Publications.

American Society of Mechanical Engineers, Three Two Park Avenue, New York, NY 10016-5990.

ASME Boiler and Pressure Vessel Code, Section VIII, “Rules for Construction of Pressure Vessels,”Division 1, 2007 2013 .

ASME B31.1, Power Piping, 2007 2012 .

ANSI/ ASME B31.3, Process Piping, 2006 2012 .

ASME B31.12, Hydrogen piping and pipelines: ASME Code for Pressure Piping, B31, 2008.

Note: ASME Publications: B31.12-2008 Hydrogen piping and pipelines: ASME Code for Pressure Piping,B31 is a use specific document for hydrogen service. A Section Committee was formed by the B31Standards Committee to address gaps that existed between piping and pipeline codes and standards, andhydrogen infrastructure applications. The first edition of the B31.12 code applies to design, construction,operation, and maintenance requirements for piping, pipeline, and distribution in hydrogen service. ASMEB31.12 includes information specific to hydrogen service by either reference or incorporation of applicableparts of B31.3, B31.1, B31.8, B31.8S, and Section VIII, Division 3 of the ASME Boiler and PressureVessel Code. Many materials included in B31.3 have been omitted from B31.12 tables due to theirunsuitability for hydrogen service.

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 13:04:20 EDT 2013

Committee Statement

Committee Statement: Updated of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

487 of 491 1/30/2014 9:30 AM

First Revision No. 437-NFPA 2-2013 [ Section No. L.1.2.5 ]

M.1.2.5 ASTM Publications.

ASTM International, 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959.

ASTM D5, Standard Test Method for Penetration of Bituminous Materials , 2006.

ASTM D 92, Standard Test Method for Flash and Fire Points by Cleveland Open Cup , 2005.

ASTM D 323, Standard Method of Test for Vapor Pressure of Petroleum Products (Reid Method) , 2006.

ASTM E 1472, Standard Guide for Documenting Computer Software for Fire Models, 2008 .

ASTM E 2079, Standard Test Method for Limiting Oxygen (Oxidant) Concentration for Gases and Vapors,2008 .

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 13:05:19 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

488 of 491 1/30/2014 9:30 AM

First Revision No. 438-NFPA 2-2013 [ Section No. L.1.2.6 ]

M.1.2.6 CGA Publications.

Compressed Gas Association, 4221 Walney Road, 5th Floor 14501 George Carter Way, Suite 103, ,Chantilly, VA 20151-2923.

CGA Pamphlet P-1, Safe Handling of Compressed Gases in Containers, 8th edition, 2006 2008 .

CGA/ANSI V-1, Standard for Compressed Gas Cylinder Valve Outlet and Inlet Connections, 7th edition,2005.

CGA G-4.4 , Industrial Practices for Gaseous Oxygen Transmission and Distribution Piping Systems ,2003.

CGA H-5, Handbook of Compressed Gases, Installation Standards for Bulk Hydrogen Supply

Systems, 4 th 2008 Edition.

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 13:06:52 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

489 of 491 1/30/2014 9:30 AM

First Revision No. 146-NFPA 2-2013 [ Section No. L.1.2.7 ]

L.1.2.7 UL Publications.

Underwriters Laboratories, Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

UL 429, Electrically Operated Valves, 2009.

Submitter Information Verification

Submitter Full Name: [ Not Specified ]

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 07 11:36:13 EDT 2013

Committee Statement

CommitteeStatement:

Add ANSI approval designation to ANSI/UL 429. ANSI/UL 2085 should be added as aninformational reference. It is referenced within the various documents that were used as extractsources such as NFPA 1 and NFPA 30.

ResponseMessage:

Public Input No. 27-NFPA 2-2012 [Section No. L.1.2.7]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

490 of 491 1/30/2014 9:30 AM

First Revision No. 440-NFPA 2-2013 [ Section No. L.2.2 ]

M.2.2 CGA Publications.

Compressed Gas Association, 4221 Walney Road, 5 th Floor 14501 George Carter Way, Suite 103 ,Chantilly, VA 20151-2923.

CGA G-6.1, Standard for Insulated Liquid Carbon Dioxide Systems at Consumer Sites, 2005 2013 .

CGA G-6.5, Standard for Small, Stationary, Insulated Carbon Dioxide Supply Systems, 2001 2007 .

CGA G-6.7, Safe Handling of Liquid Carbon Dioxide Containers That Have Lost Pressure2009 .

CGA H.1, Conditions for Portable, Reversible Hydride Systems,2004 2011 .

CGA H-2, Guidelines for the Classification and Labeling of Hydrogen Storage Systems with HydrogenAbsorbed in Reversible Metal Hydrides, 2004.

Submitter Information Verification

Submitter Full Name: James Grimard

Organization: NFPA

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jul 01 13:09:34 EDT 2013

Committee Statement

Committee Statement: Update of extract material.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

491 of 491 1/30/2014 9:30 AM