Hochiki America Corporation 7051 Village Drive, Suite 100 Buena Park, CA 90621-2268 Phone: 714/522-2246 Fax: 714/522-2268 Technical Support: 800/845-6692 or [email protected] 03/2010 Find latest revision at www.hochiki.com F0087 DESCRIPTION Specifications subject to change without notice. FireNET Plus 1127 - ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL The FireNET™ Plus 1127 series control panel is an analog addressable fire alarm panel with build options containing 1 or 2 SLC loops, a Digital Alarm Communicator/ Transmitter (DACT), and an RS-485 bus for network communication. Each SLC loop supports 127 devices of any combination (sensors or modules), and 127 analog sounder bases, for a possible total of 254 points per loop. Communication between devices is accomplished by use of standard cable (shielded or twisted pair is not required). Each panel includes a 4-amp power supply and has 2 on- board NAC circuits. The RS-485 bus provides communication to the panel network while another RS-485 bus provides communication for peripheral devices. The RS-232 interface allows the convenience of programming via a PC. The system will support a variety of Hochiki devices; photo, ion and heat sensors, which contain a unique, patented sensor design incorporating automatic drift compensation and day/night sensitivity modes. Additional devices include contact monitors, relay controllers, supervised auxiliary output and short circuit isolator modules. In addition, interfaces to conventional detection systems can be established by using a conventional zone- monitoring module. The Loop Explorer Windows® Software interface provides the installer with fingertip access to installation programming and diagnostic tools. An Auto Learn feature offers the convenience for quick start applications. Add to this a reputation for high quality and dedicated service which makes this an exceptional product both in performance and value. STANDARD FEATURES Continued on back. UL 864, Local Signaling Unit. Types: Automatic, manual, waterflow, sprinkler supervisory, Remote Station and Central Station Service (DACT) Non-coded signaling. NFPA 70, 72 &13 Compliant Analog design using Hochiki’s advanced DCP protocol for fast communication Up to 127 sensors & modules, plus 127 analog sounder bases, for a total of 254 points possible per loop Uses standard wire, no-shielded or twisted pair required on SLC loops Integrated digital alarm communicator (DACT) with Contact ID and SIA reporting formats Programmable sensitivity levels by device Alarm Verification feature Automatic daily calibration & drift compensation routine Large 8-line x 40-character LCD display (320 char.) 1 or 2 loop (option) RS-485 bus for panel network (option) Built-in RS-232 interface for programming via a PC 3 on board programmable Form C relays rated at 1 amp at 30VDC 2 auxiliary power outputs, each rated 360mA at 24 VDC Loop Explorer Windows® configuration utility Auto-learn feature 500 network wide software zones Network Capability of up to 64 panels (option) Built in help and alarm information screens 2 on-board Class B (style Y) NAC circuits rated at 2.3 amps each (Special Application) and 1.6 amps each (Regulated continuous) Gentex, System Sensor, Wheelock, and Amseco NAC sync protocol built-in Automatic day/night sensitivity modes Fire Drill test function Walk Test function Powerful & versatile Cause & Effect wizard including: *Cause & Effect action *Disable function configuration *Test mode configuration 3038713 PRODUCT LISTINGS 7165-0410:180 California State Fire Marshal S6468

FIRENET Plus 03-2010 - centauruae.comcentauruae.com/hochiki/Fire Alaram Control Panel.pdf · The RS-485 bus provides ... DH-98A Analog Addressable Duct Detector Unit ... Color Red

Embed Size (px)

Citation preview

Hochiki America Corporation7051 Village Drive, Suite 100 Buena Park, CA 90621-2268Phone: 714/522-2246 Fax: 714/522-2268Technical Support: 800/845-6692 or [email protected] 03/2010

Find latest revision at www.hochiki.com

F0087

DESCRIPTION

Specifications subject to change without notice.

FireNET Plus 1127 - ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL™

The FireNET™ Plus 1127 series control panel is ananalog addressable fire alarm panel with build optionscontaining 1 or 2 SLC loops, a Digital AlarmCommunicator/ Transmitter (DACT), and an RS-485bus for network communication. Each SLC loopsupports 127 devices of any combination (sensors ormodules), and 127 analog sounder bases, for apossible total of 254 points per loop. Communicationbetween devices is accomplished by use of standardcable (shielded or twisted pair is not required). Eachpanel includes a 4-amp power supply and has 2 on-board NAC circuits. The RS-485 bus providescommunication to the panel network while anotherRS-485 bus provides communication for peripheraldevices. The RS-232 interface allows the convenienceof programming via a PC. The system will support avariety of Hochiki devices; photo, ion and heatsensors, which contain a unique, patented sensordesign incorporating automatic drift compensation andday/night sensitivity modes. Additional devicesinclude contact monitors, relay controllers, supervisedauxiliary output and short circuit isolator modules. Inaddition, interfaces to conventional detection systemscan be established by using a conventional zone-monitoring module. The Loop Explorer Windows®Software interface provides the installer with fingertipaccess to installation programming and diagnostictools. An Auto Learn feature offers the conveniencefor quick start applications. Add to this a reputationfor high quality and dedicated service which makesthis an exceptional product both in performance andvalue.

STANDARD FEATURES

Continued on back.

UL 864, Local Signaling Unit.Types: Automatic, manual,waterflow, sprinkler supervisory,Remote Station and CentralStation Service (DACT)Non-coded signaling.NFPA 70, 72 &13 Compliant

• Analog design using Hochiki’s advanced DCPprotocol for fast communication

• Up to 127 sensors & modules, plus 127 analog sounderbases, for a total of 254 points possible per loop

• Uses standard wire, no-shielded or twisted pair requiredon SLC loops

• Integrated digital alarm communicator (DACT) withContact ID and SIA reporting formats

• Programmable sensitivity levels by device• Alarm Verification feature• Automatic daily calibration & drift compensation routine• Large 8-line x 40-character LCD display (320 char.)• 1 or 2 loop (option)• RS-485 bus for panel network (option)• Built-in RS-232 interface for programming via a PC• 3 on board programmable Form C relays rated at 1 amp

at 30VDC• 2 auxiliary power outputs, each rated 360mA at 24 VDC• Loop Explorer Windows® configuration utility• Auto-learn feature• 500 network wide software zones• Network Capability of up to 64 panels (option)• Built in help and alarm information screens• 2 on-board Class B (style Y) NAC circuits rated at 2.3

amps each (Special Application) and 1.6 amps each(Regulated continuous)

• Gentex, System Sensor, Wheelock, and Amseco NACsync protocol built-in

• Automatic day/night sensitivity modes• Fire Drill test function• Walk Test function• Powerful & versatile Cause & Effect wizard including:

*Cause & Effect action*Disable function configuration*Test mode configuration

3038713

PRODUCT LISTINGS

7165-0410:180

CaliforniaState FireMarshal

S6468

Specifications subject to change without notice.Hochiki America Corporation FireNET Plus ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL

MODEL DESCRIPTION

CONTROL PANEL EXPANDERSFNP-1127-SLC SLC One Loop Expansion CardFN-4127-NIC Network Interface CardFN-4127-IO 16 Channel Input/Output Board

ANNUNCIATOR

FN-LCD-S Serial LCD AnnunciatorFNP-LED Graphix Display

SLC LOOP DEVICESALG-V, ALK-V Analog Addressable Photoelectric SensorAIE-EA Analog Addressable Ionization SensorATG-EA Analog Addressable Heat SensorNSA-6 Six inch Sensor BaseNSA-4 Four inch Sensor BaseASB Analog Sounder BaseDH-98A Analog Addressable Duct Detector UnitDH-98AR Analog Addressable Duct Detector Unit (with relays)MS-RA, MS-RA/R,MS-KA/R Remote Test Station for DH98ARFRCME-S Contact Monitoring Module (mini w/terminal blocks)FRCME-P Contact Monitoring Module (mini w/pigtail leads)FRCME-4 Contact Monitoring Module (with faceplate/indicating LED)FRCMA, FRCMA-I Class A Contact Monitoring Module (FRCMA-I has Built-in SCI)DIMM Dual Input Monitor Module (with faceplate/indicating LED)CZM Conventional Zone ModuleR2M Dual Relay ModuleR2ML/H Series Dual Relay Module (R2ML-I & R2MH-I has Built-in SCI)SOM Supervised Output ModuleSOM-A, SOM-AI Class A Supervised Output Module (SOM-AI has Built-in SCI)SCI Short Circuit Isolator Module

AMS Series Addressable Manual Pull StationACCESSORIES

TCH-B100 Hand Held Programmer (portable device addresser)FN-ACC Battery/Accessory Enclosure (houses up to 33AH size batteries)FNP-ETR Enclosure Trim Ring for Panel Flush Mount

SLC COMPATIBLE DEVICES & SYSTEM ACCESSORIES

SPECIFICATIONSPrimary AC 120VAC @ 2.1 Amps 50/60hz or 220VAC @ 1.1Amps 50/60hzOutput DC 24VDC @ 5.25 AmpsPower Supply 4 Amp integratedCharger Current 1.5 Amps max.Dimensions 14.5" W x 19" H x 3.5" DWeight 20 lbs. (without batteries)Color Red (optional charcoal)Material ABS/steel enclosureDisplay 8 line x 40 character LCD (320 characters total)Network Dual RS485 ports (64 panels max.)Zones 500 network wide software zones per systemSLC loops 1 or 2 (class A, "style 6 or 7" or class B, "style 4")Devices per loop 127 sensors & modules, plus 127 analog sounder bases, 254 totalAddresses per panel 800 addresses+sub-addresses max. per panelNAC Outputs (2) class B, 2.3 Amps (special application)

1.6 Amps Regulated (continuous)Relay Outputs (3) Form C 1 Amp @ 30VDCAux. Power 2 outputs, 360mA @ 24VDC eachPC Port / Printer RS232DACT Formats Contact ID and SIA

Hochiki America Corporation7051 Village Drive, Suite 100 Buena Park, CA 90621-2268Phone: 714/522-2246 Fax: 714/522-2268Technical Support: 800/845-6692 or [email protected] 07/2009

Find latest revision at www.hochiki.com

F0093

Specifications subject to change without notice.

DESCRIPTION

This alternate build of the FireNET™ 4127 control panelis equipped with a Plexiglass window to meet therequirements of major cities including the City ofDenver. Access level 2 is enabled as soon as the outerdoor of the enclosure is opened (CAT 30 Key).The FireNET™ 4127 control panel is an analog addres-sable fire alarm panel containing 2 or 4 SLC loops witheach loop supporting 127 devices of any combination(sensors or modules), and 127 analog sounder bases,for a possible total of 254 points. Communicationbetween devices is transferred through standard cable(shielded or twisted pair is not required). Each panelincludes a 5.25 amp power supply and has 4 on boardNAC circuits. An RS-485 bus provides communication tothe panel network, while the RS-232 interface allows theconvenience of programming via a PC. The system willsupport a variety of Hochiki devices: photo, ion and heatsensors, which contain a unique, patented sensordesign incorporating automatic drift compensation andday/night sensitivity mode. Additional devices includecontact monitors, relay controllers, supervised auxiliaryoutput and short circuit isolator modules. In addition,interfaces to conventional detection systems can beestablished by using a conventional zone-monitoringmodule. The Loop Explorer Windows® Softwareinterface provides the installer with fingertip access toinstallation programming and diagnostic tools. AnAuto-learn feature offers the convenience for quick startapplications. Add to this a reputation for high quality anddedicated service makes this an exceptional productboth in performance and value.

• UL 864 9th edition Listed• Analog design using Hochiki’s advanced DCP

protocol for fast and robust communication• Up to 127 sensors & modules, plus 127 analog sounder

bases, for a total of 254 points possible per loop• Uses standard wire, no shielded or twisted pair required on

SLC loops• Supports Class B (style 4) and Class A (style 6 or 7) SLC

loops• 4 on board Class B (style Y) NAC circuits rated at 2.5 Amps

each• Programmable sensitivity levels per device & automatic day/

night sensitivity modes• Automatic daily calibration & drift compensation routine• Large 8-line x 40-character LCD display (320 char.)• 2 or 4 loop versions (800 addresses/sub-addr. max.)• Dual RS-485 bus for panel network• 2 built-in RS-232 interfaces for programming via a PC and

serial printer interface• 5 on board programmable Form C relays rated at 1 amp at

30VDC (Fire1, Fire2, trouble, supervisory, aux.)• 500mA of auxiliary power available rated at 24 VDC• Loop Explorer Windows® configuration utility• 500 network wide software zones• Network Capability of up to 64 panels• RS485 slave bus for expansion - up to 32 FN-4127-IO

boards or up to 15 FN-LCD-S serial annunciators and up to17 FN-4127-IO boards

• Auto-learn feature• Built in help and alarm information screens• Fire Drill test function• Walk Test function• Alarm Verification feature• FireNET is UL listed for Central Station Service, Remote

Station Service and Proprietary Service• Operates on 120VAC or 240VAC input voltage• Powerful & versatile Cause & Effect programming (up to 500

maximum, network wide) including:*Cause & Effect action*Disable function configuration*Test mode configuration

STANDARD FEATURES

Continued on back.

™FireNET 4127 - ANALOG ADDRESSABLE FIRE ALARM CONTROL PANELWITH PLEXIGLASS WINDOW

UL 864, Local Signaling Unit.Types: Automatic, manual, waterflow,sprinkler supervisory, AuxiliaryService(local energy), and CentralStation Service, Remote StationService and Proprietary Service(DACT) Non-coded signaling.NFPA 70, 72 &13 Compliant

PRODUCT LISTINGS

7165-0410:159

CaliforniaState FireMarshal

S8255

Specifications subject to change without notice.Hochiki America Corporation FireNET ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL

SPECIFICATIONSPrimary AC 120VAC @ 2.1 Amps 60hz or 220VAC @ 1.1Amps 60hzOutput DC 24VDC @ 5.25 Amps (4 Amps availble for system power)Power Supply 5.25 Amps integratedCharger Current 1.5 Amps max.Dimensions 14.5" W x 24" H x 5" DWeight 31 lbs. (without batteries)Color Red (optional charcoal)Material ABS/steel enclosureDisplay 8 line x 40 character LCD (320 characters total)Network Dual RS485 ports (64 panels max.)Zones 500 network wide software zones per systemSLC loops 2 or 4 (class A, "style 6 or 7" or class B, "style 4")Devices per loop 127 sensors & modules, plus 127 analog sounder bases, 254 totalAddresses per panel (800 addresses+sub-addresses max. per panel)NAC Outputs (4) 2.5 Amps @ 24VDC (class B)Relay Outputs (5) Form C 1 Amp @ 30VDCVoltage Outputs (3) 500mA @ 24VDCAux. Power 500mA @ 24VDCAux. Inputs (8) digital pull downsPC Port RS232Printer Port RS232

MODEL DESCRIPTIONCONTROL PANEL EXPANDERS

FN-4127-SLC Dual SLC Loop Expansion CardFN-4127-NIC Network Interface CardFN-4127-IO 16 Channel Input/Output BoardFN-DAC Digital Alarm CommunicatorFN-CTM City-Tie Module (Local Energy Type)

ANNUNCIATORSFN-LCD-N Network LCD AnnunciatorFN-LCD-S Serial LCD Annunciator

SLC LOOP DEVICESALG-V Analog Addressable Photoelectric SensorALK-V & ALK-V2 Analog Addressable Photoelectric SensorAIE-EA Analog Addressable Ionization SensorATG-EA Analog Addressable Heat SensorNSA-6 Six inch Sensor BaseNSA-4 Four inch Sensor BaseASB Analog Sounder BaseDH-98A Analog Addressable Duct Detector UnitDH-98AR Analog Addressable Duct Detector Unit (with relays)MS-RA, MS-RA/R,MS-KA/R Remote Test Station for DH98A & DH98ARFRCME-S Contact Monitoring Module (mini w/terminal blocks)FRCME-P Contact Monitoring Module (mini w/pigtail leads)FRCME-4 Contact Monitoring Module (with faceplate/indicating LED)DIMM Dual Input Monitor Module (with faceplate/indicating LED)CZM Conventional Zone ModuleR2M Dual Relay ModuleSOM Supervised Output ModuleSOM-A, SOM-AI Class A Supervised Output Module With SCI or Without SCISCI Short Circuit Isolator ModuleAMS Series Addressable Manual Pull Station

ACCESSORIESTCH-B100 Hand Held Programmer (portable device addresser)FN-ACC Battery/Accessory Enclosure (houses up to 33AH size batteries)FN-ETR Enclosure Trim Ring for Panel Flush Mount

SLC COMPATIBLE DEVICES & SYSTEM ACCESSORIES

MODEL DESCRIPTIONFN-2127-DDW FACP (2 Loop/5.25 Amps)FN-2127-DDWN FACP (2 Loop/5.25 Amps) (w/Network)FN-4127-DDW FACP (4 Loop/5.25 Amps)FN-4127-DDWN FACP (4 Loop/5.25 Amps) (w/Network)

FireNET ORDERING MODELS

Hochiki America Corporation7051 Village Drive, Suite 100 Buena Park, CA 90621-2268Phone: 714/522-2246 Fax: 714/522-2268Technical Support: 800/845-6692 or [email protected] 06/2009

Find latest revision at www.hochiki.com

F0068

Specifications subject to change without notice.

™FireNET 4127 - ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL

DESCRIPTION

The FireNET™ 4127 control panel is an analog addres-sable fire alarm panel containing 2 or 4 SLC loops witheach loop supporting 127 devices of any combination(sensors or modules), and 127 analog sounder bases,for a possible total of 254 points. Communicationbetween devices is transferred through standard cable(shielded or twisted pair is not required). Each panelincludes a 5.25 amp power supply and has 4 on boardNAC circuits. An RS-485 bus provides communication tothe panel network, while the RS-232 interface allows theconvenience of programming via a PC. The system willsupport a variety of Hochiki devices: photo, ion and heatsensors, which contain a unique, patented sensordesign incorporating automatic drift compensation andday/night sensitivity mode. Additional devices includecontact monitors, relay controllers, supervised auxiliaryoutput and short circuit isolator modules. In addition,interfaces to conventional detection systems can beestablished by using a conventional zone-monitoringmodule. The Loop Explorer Windows® Softwareinterface provides the installer with fingertip access toinstallation programming and diagnostic tools. AnAuto-learn feature offers the convenience for quick startapplications. Add to this a reputation for high quality anddedicated service makes this an exceptional productboth in performance and value.

STANDARD FEATURES• UL 864 9th edition Listed• Analog design using Hochiki’s advanced DCP

protocol for fast and robust communication• Up to 127 sensors & modules, plus 127 analog sounder

bases, for a total of 254 points possible per loop• Uses standard wire, no shielded or twisted pair required on

SLC loops• Supports Class B (style 4) and Class A (style 6 or 7) SLC

loops• 4 on board Class B (style Y) NAC circuits rated at 2.5 Amps

each• Programmable sensitivity levels per device & automatic day/

night sensitivity modes• Automatic daily calibration & drift compensation routine• Large 8-line x 40-character LCD display (320 char.)• 2 or 4 loop versions (800 addresses/sub-addr. max.)• Dual RS-485 bus for panel network• 2 built-in RS-232 interfaces for programming via a PC and

serial printer interface• 5 on board programmable Form C relays rated at 1 amp at

30VDC (Fire1, Fire2, trouble, supervisory, aux.)• 500mA of auxiliary power available rated at 24 VDC• Loop Explorer Windows® configuration utility• 500 network wide software zones• Network Capability of up to 64 panels• RS485 slave bus for expansion - up to 32 FN-4127-IO

boards or up to 15 FN-LCD-S serial annunciators and up to17 FN-4127-IO boards

• Auto-learn feature• Built in help and alarm information screens• Fire Drill test function• Walk Test function• Alarm Verification feature• FireNET is UL listed for Central Station Service, Remote

Station Service and Proprietary Service• Operates on 120VAC or 240VAC input voltage• Powerful & versatile Cause & Effect programming (up to 500

maximum, network wide) including:*Cause & Effect action*Disable function configuration*Test mode configuration

UL 864, Local Signaling Unit.Types: Automatic, manual, waterflow,sprinkler supervisory, AuxiliaryService(local energy), and CentralStation Service, Remote StationService and Proprietary Service(DACT) Non-coded signaling.NFPA 70, 72 &13 Compliant

PRODUCT LISTINGS

7165-0410:159

CaliforniaState FireMarshal

S8255

Continued on back.

Specifications subject to change without notice.Hochiki America Corporation FireNET ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL

SPECIFICATIONSPrimary AC 120VAC @ 2.1 Amps 60hz or 220VAC @ 1.1Amps 50hzOutput DC 24VDC @ 5.25 Amps (4 Amps availble for system power)Power Supply 5.25 Amps integratedCharger Current 1.5 Amps max.Dimensions 14.5" W x 24" H x 5" DWeight 31 lbs. (without batteries)Color Red (optional charcoal)Material ABS/steel enclosureDisplay 8 line x 40 character LCD (320 characters total)Network Dual RS485 ports (64 panels max.)Zones 500 network wide software zones per systemSLC loops 2 or 4 (class A, "style 6 or 7" or class B, "style 4")Devices per loop 127 sensors & modules, plus 127 analog sounder bases, 254 totalAddresses per panel (800 addresses+sub-addresses max. per panel)NAC Outputs (4) 2.5 Amps @ 24VDC (class B)Relay Outputs (5) Form C 1 Amp @ 30VDCVoltage Outputs (3) 500mA @ 24VDCAux. Power 500mA @ 24VDCAux. Inputs (8) digital pull downsPC Port RS232Printer Port RS232

MODEL DESCRIPTIONFN-2127 FACP (2 Loop/5.25 Amps)FN-2127N FACP (2 Loop/5.25 Amps) (w/Network)FN-4127 FACP (4 Loop/5.25 Amps)FN-4127N FACP (4 Loop/5.25 Amps) (w/Network)

FireNET ORDERING MODELS

MODEL DESCRIPTIONCONTROL PANEL EXPANDERS

FN-4127-SLC Dual SLC Loop Expansion CardFN-4127-NIC Network Interface CardFN-4127-IO 16 Channel Input/Output BoardFN-DAC Digital Alarm CommunicatorFN-CTM City-Tie Module (Local Energy Type)

ANNUNCIATORSFN-LCD-N Network LCD AnnunciatorFN-LCD-S Serial LCD Annunciator

SLC LOOP DEVICESALG-V Analog Addressable Photoelectric SensorALK-V & ALK-V2 Analog Addressable Photoelectric SensorAIE-EA Analog Addressable Ionization SensorATG-EA Analog Addressable Heat SensorNSA-6 Six inch Sensor BaseNSA-4 Four inch Sensor BaseASB Analog Sounder BaseDH-98A Analog Addressable Duct Detector UnitDH-98AR Analog Addressable Duct Detector Unit (with relays)MS-RA, MS-RA/R,MS-KA/R Remote Test Station for DH98A & DH98ARFRCME-S Contact Monitoring Module (mini w/terminal blocks)FRCME-P Contact Monitoring Module (mini w/pigtail leads)FRCME-4 Contact Monitoring Module (with faceplate/indicating LED)DIMM Dual Input Monitor Module (with faceplate/indicating LED)CZM Conventional Zone ModuleR2M Dual Relay ModuleSOM Supervised Output ModuleSOM-A, SOM-AI Class A Supervised Output Module With SCI or Without SCISCI Short Circuit Isolator ModuleAMS Series Addressable Manual Pull Station

ACCESSORIESTCH-B100 Hand Held Programmer (portable device addresser)FN-ACC Battery/Accessory Enclosure (houses up to 33AH size batteries)FN-ETR Enclosure Trim Ring for Panel Flush Mount

SLC COMPATIBLE DEVICES & SYSTEM ACCESSORIES

Hochiki America Corporation7051 Village Drive, Suite 100 Buena Park, CA 90621-2268Phone: 714/522-2246 Fax: 714/522-2268Technical Support: 800/845-6692 or [email protected] 06/2009

Find latest revision at www.hochiki.com

F0071

FN-LCD-N - LCD NETWORK ANNUNCIATOR

DESCRIPTION

Continued on back.

• UL 864 9th edition Listed• 320 character liquid crystal display (8 line x 40

character)• LED indicators for Fire, Supervisory Alarm, Pre-

Alarm, Fire Output Active, Power On, On Test, PanelSounder Silenced, Delay Active, More Events, PointBypassed, General Trouble, Power Trouble, SystemTrouble & NAC Trouble

• Dual RS485 ports for primary fire network• RS485 slave bus for expansion - up to 32 FN-4127-IO

boards or up to 15 FN-LCD-S serial annunciators andup to17 FN-4127-IO boards

• 2 built-in RS-232 interfaces for programming via a PCand serial printer interface

• 4 on board programmable Form C relays rated at 1Amp at 30VDC (Fire, Supervisory, Trouble &Auxiliary)

• Same controls as the FireNET fire panel (Reset,Panel Sounder Silence, Lamp Test, Alarm Silence,Re-sound Alarm, Fire Drill, Programmable Function,More Events, More Fire Events, Enter & Exit)

• Local piezo sounder for event notification• Supports user codes & firefighter key to enable

access & controls• Powered by FireNET Aux 24VDC or UL fire listed

Aux. 24VDC supply• Available in red or charcoal, and can be surface or

flush mounted (using trim ring)• True network annunciator, any or all panels can be

routed to the FN-LCD-N. In addition, each eventcategory can be individually routed to the FN-LCD-N

• Up to (64) FireNET panels & FN-LCD-N's can benetworked together in any combination

• 500mA of auxiliary power available rated at 24VDC• Auto-learn feature• Built-in help & alarm information screens• Fire drill function• Each FN-LCD-N is completely independent• The FN-LCD-N can be configured to remote reset,

silence, resound, any or all panels on the network inany combination

The FN-LCD-N type LCD network annunciator isdesigned to be used with the FireNET analogaddressable system. It allows for remote access,monitoring & control of the FireNET system throughoutthe building.The FN-LCD-N is a true network annunciator that canaccess, monitor & control any or all FireNET panels inthe network. Each FN-LCD-N is completelyindependent. The highly intuitive user interface and320 character LCD display of the FN-LCD-N is exactlythe same as the FireNET panel. In addition to routingany panel in the network to the FN-LCD-N, every eventcategory within each panel can also be individuallyrouted, as well as routing of all remote control functions(reset, alarm silence, re-sound alarm) from individualpanels. The FN-LCD-N supports the same RS485expansion port as the FireNET panel, allowing forFireNET expansion boards and accessories to beconnected to the network annunciator.The FN-LCD-N also has (4) output relays for fire,supervisory, trouble & auxiliary. The relays areprogrammable (except supervisory).Security is established by the use of a password orfirefighters enable key. Designed to be aestheticallypleasing, the FN-LCD-N is available in charcoal greyor red and can be surface or flush mounted using astandard trim ring kit.

STANDARD FEATURES

Specifications subject to change without notice.

PRODUCT LISTINGS

UL 864, NFPA 70 & 72:Signaling Device

S8255 Vol. 2 7120-0410:165

CaliforniaState FireMarshal

Specifications subject to change without notice.Hochiki America Corporation FN-LCD-N

WIRING DIAGRAM

SPECIFICATIONSInput DC 24VDC @ 270mA Max. ( + Aux. Power Load)Aux. Output DC 24VDC @ 500mADimensions 14.5" W x 10" H x 3.3" DWeight 9.4 lbsColor Red (optional charcoal)Material ABS/steel enclosureDisplay 8 line x 40 character LCD (320 characters total)Network Dual RS485 ports (64 nodes max.)Relay Outputs (4) Form C 1amp@30VDCPC Port RS232Printer Port RS232Expansion Port RS485 (for optional expansion boards)

ENGINEERING SPECIFICATION

The contractor shall furnish and install where indicated on the plans, the network annunciator model FN-LCD-N.The FN-LCD-N shall connect to the FireNET fire alarm control panel (FACP) network. The network annunciatorshall be capable of annunciating on its 320 character display and local buzzer, the condition of any FireNET FACPor network annunciator on the network. Up to 64 FN-LCD-N network annunciators or FireNET FACP's may beconnected together on the network. The FN-LCD-N shall be UL listed, and have surface or flush mount capability.

Hochiki America Corporation7051 Village Drive, Suite 100 Buena Park, CA 90621-2268Phone: 714/522-2246 Fax: 714/522-2268Technical Support: 800/845-6692 or [email protected] 09/2007

Find latest revision at www.hochiki.com

F0070

FN-LCD-S - SERIAL LCD ANNUNCIATOR

Specifications subject to change without notice.

DESCRIPTION

The FN-LCD-S serial annunciator provides aconvenient and cost effective remote annunciatorsolution. Up to 15 FN-LCD-S annunciators can beconnected to the slave RS-485 port of the FireNETcontrol panel or network annunciator. The FN-LCD-S’slarge 320 character display and navigation buttons area complete mimic of the FireNET control paneldisplay. The use of a common interface allows theuser to easily operate the FN-LCD-S as if he wereoperating the FireNET control panel directly.

Security is established by the use of a password orfirefighters enable key. Designed to be aestheticallypleasing, the FN-LCD-S is available in charcoal greyor red enclosures. The FN-LCD-S can be surface orflush mounted without the need for a trim ring.

Continued on back.

Current Draw Standby: 20mA @ 24VDC Alarm: 110mA @ 24VDCDimensionsFN-LCD-S 10.88" W x 8.00" H x 1.38" DBack Box 10.38" W x 7.38" H x 1.25" DWeight 3.5 lbs

Color Red (optional charcoal)

Material ABS/steel enclosure

Display 8 line x 40 character LCD(320 characters total)

Network RS485 port

SPECIFICATIONS

STANDARD FEATURES

• UL 864 9th edition Listed

• Large 320 character liquid crystal display (8 linex 40 character) allows viewing of system status

• LED indicators for Fire, Supervisory Alarm, Pre-Alarm, Fire Output Active, AC Power On, OnTest, Panel Sounder Silenced, Delay Active,More Events, Point Bypassed, General Trouble,Power Trouble, System Trouble & NAC Trouble

• Same controls as the FireNET fire panel (Reset,Panel Sounder Silence, Lamp Test, AlarmSilence, Re-sound Alarm, Fire Drill, Program-mable Function, More Events, More Fire Events,Enter & Exit)

• Up to 15 FN-LCD-S serial annunicators may beconnected to a FireNET control panel or networkannunciator

• Resides on the FireNET slave RS-485 line• Local piezo sounder for event notification

• Supports user codes & firefighter key to enableaccess & controls

• Powered by FireNET Aux 24VDC or UL fire listedAux. 24VDC supply

• Available in red or charcoal, and can be surfaceor flush mounted

• Built-in help & alarm information screens

• Fire drill function

PRODUCT LISTINGS

UL 864, NFPA 70 & 72:Signaling Device

S8255 Vol. 2 7120-0410:165

CaliforniaState FireMarshal

Specifications subject to change without notice.Hochiki America Corporation FN-LCD-S

To next serial

FN-LCD-S or other

RS485 Buss

Device

7. PR2

8. PR3

COMMS

l +

AUX24X l

+

NETWORKIN l

+

NETWORKOUT l

+

ADDITIONALI/O BOARDS

+l+l

1 2 3 4

ON K S

15

22

RO

@

+l+l

ADDRESS COMM20V +24VRESET W / DOG RESET

FIT JUMPERFOR END OF LINECOMM1 COMM2

COMMSACTIVE

COMM1

DIP Switch used to set the FN-LCD-S address

between 1 -15

Not Used

RS485 End-of-line jumper . Put jumper in place when FN-LCD-S is the last device on the RS485 buss “I/O Comm”.

Not Used

( + )

( - )

( + )

( - ) 24 VDC

RS-485

FireNET Control Panel(section)

To AUX 24VDC of control panel (as shown) or to UL 864/1481 listed AUX 24VDC Power Supply

ResetSwitch

WIRING DIAGRAM

ENGINEERING SPECIFICATION

The contractor shall furnish and install where indicated on the plans, the serial remote annunciator modelFN-LCD-S. The FN-LCD-S shall connect to the FireNET fire alarm control panel (FACP) or networkannunciator (FN-LCD-N) RS485 slave bus. The serial remote annunciator shall annunciate on its 320character display and local buzzer, the condition of its master FireNET FACP. Up to 15 FN-LCD-S serialannunciators may be connected together on a single RS-485 FireNET slave bus. The FN-LCD-S shall beUL listed and compatible with the Hochiki FireNET control panel, and have surface or flush mountcapability.

Hochiki America Corporation7051 Village Drive, Suite 100 Buena Park, CA 90621-2268Phone: 714/522-2246 Fax: 714/522-2268Technical Support: 800/845-6692 or [email protected] 03/2010

Find latest revision at www.hochiki.com

F0102

Specifications subject to change without notice.

FNP-LED - GRAPHIX LED DISPLAY

Continued on back.

STANDARD FEATURES

• Available in Red and Charcoal Gray• Up to 504 LED's can be controlled with FireNET Plus

Panel• Available in 3 different size enclosures• LED's comes in 3 different colors: Red, Green, or Yellow• FNP-LED can be easily upgraded onsite with minimal

cost and effort

DESCRIPTION

The FNP-LED system uses flexible, optic light guidesto illuminate areas on a floor plan, laid over a highresolution grid. This unique system dispensescompletely with wiring and enables indicators to bemoved, removed or added onsite without the need forany wiring. All indicators can be configured to operateupon any event type and at point, zone or group levelvia the powerful and intuitive Loop Explorerconfiguartion tool. FNP-LED can be supplied with orwithout optional LED's and controls. Optional LED'sindicate Power On, Fire, Trouble and Disablementsand optional controls are for Alarm Silence, BuzzerSilence, Lamp Test, and Reset. Housed in anattractive, slimline enclosure to match FireNET PlusFire Alarm Panels. High quality, full color floor plansprovide a clear and geographical indication of eventactivation, which enables fast identification of the FireAlarm source.

3038713

PRODUCT LISTINGS

7120-0410:181

CaliforniaState FireMarshal

S5694

Operating Voltage 21- 30VDC

Maximum Current 360mA

Wire Size 12AWG to 22AWG

Communication Method RS485

Max. Wiring Distance 3900ft. (1200m)

Avalible Dimensions AM2: 14.50"W x 12.25"H x 3.50"D

AM3: 14.50"W x 18.90"H x 4.25"D

AM4: 14.50"W x 24.25"H x 4.25"D

Color Red or Charcoal

Material ABS/Steel Enclosure

Max. LED's AM2: 24 LED's

AM3: 56 LED's

AM4: 88 LED's

Operation Temperature 20°F (-6°C) to 120°F (49°C)

Cabinet Lock Type CAT 30 Key

SPECIFICATIONS

Specifications subject to change without notice.Hochiki America Corporation FNP-LED Graphix Display

Standby Current

Red LED Driver Board Contains 8 LED's = 13mA

Red LED Expansion Board Contains 16 LED's = 13mA

Green LED Expansion Board Contains 16 LED's = 13mA

Yellow LED Expansion Board Contains 16 LED's = 13mA

Alarm Current

Red LED Driver Board Contains 8 LED's = 45mA

Red LED Expansion Board Contains 16 LED's = 45mA

Green LED Expansion Board Contains 16 LED's = 45mA

Yellow LED Expansion Board Contains 16 LED's = 45mA

CURRENT RATINGS