8
PRODUCT DESCRIPTION The Series 7C7 Air Maintenance/Compressor assembly consists of a riser-mounted compressor, Series 757P Air Maintenance Device and flexible hoses for installation. It is designed to ensure the valve system can achieve operational air pressure within 30 minutes of discharge, in accordance with NFPA 13 requirements (7.2.6.2.2). The Series 757P Air Maintenance Device is UL Listed and FM Approved. The Series 7C7 Assembly is available with 1/6, 1/3 and horsepower compressors depending upon the system requirements. For FireLock NXT™ Series 768 Dry Valves, Series 769 Deluge and Preaction Valves, Series 764 Alternate Valves. Note: The Series 7C7 Air Maintenance/Compressor Assembly is designed for systems that do not require an accelerator to achieve the required system pressure performance. If an accelerator is required, a tank-mounted compressor with a regulated air maintenance device should be used. COMPRESSOR CAPACITIES The engineer/system designer is responsible for sizing the compressor so that the entire system is charged to the required air pressure within NFPA guidelines (30 minutes). DO NOT oversize the compressor to provide more airflow. An oversized compressor will slow down or possibly prevent valve operation. Hp Nominal AC Voltage/Hz (+/- 10%) Pressure psi/Bar Time Minutes Capacity WITH AutoVent gallons/m 3 Capacity WITHOUT AutoVent gallons/m 3 Amp Draw 1/6 110/60 18 30 175 275 2.1 Amps 1.2 0.7 1.1 1/3 110/60 18 30 375 525 4.4 Amps 1.2 1.4 2.0 1/3 220/50 18 30 160 235 1.2 0.6 0.9 1/3 220/50 18 60 450 660 1.2 1.7 2.5 1/3 220/60 18 30 370 400 1.5 1.2 1.4 1/2 110/50 18 30 660 670 6.6 Amps 1.2 2.5 2.5 1/2 110/60 18 30 780 830 3.1 1.2 3.0 3/4 220/50 18 30 600 675 3.8 Amps 1.2 2.3 2.5 3/4 220/60 18 30 700 775 2.9 1.2 2.7 3/4 220/50 18 60 1200 1350 5.0 1.2 4.5 3/4 220/60 18 60 1375 1525 5.8 1.2 5.2 NOTE: Refer to the charts on the following pages for minimum required fill capacities to 13 psi/0.9 Bar. Low air alarms will clear at 13 psi/0.9 Bar. In addition, these charts contain higher capacities to 18 psi/1.2 Bar that are not shown in the table above. 30.22_1 Air Maintenance/ Compressor Assembly SERIES 7C7 30.22 FIRE PROTECTION PRODUCTS – DEVICES JOB/OWNER CONTRACTOR ENGINEER System No. ______________________________ Submitted By ____________________________ Spec Sect _______________ Para ___________ Location ________________________________ Date ___________________________________ Approved _______________________________ Date ___________________________________ www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2013 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_G SERIES 7C7

FIRE PROTECTION PRODUCTS – DEVICES 30.22 Air Maintenance

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

PRODUCT DESCRIPTION The Series 7C7 Air Maintenance/Compressor assembly consists of a riser-mounted compressor, Series 757P Air Maintenance Device and flexible hoses for installation. It is designed to ensure the valve system can achieve operational air pressure within 30 minutes of discharge, in accordance with NFPA 13 requirements (7.2.6.2.2).

The Series 757P Air Maintenance Device is UL Listed and FM Approved.

The Series 7C7 Assembly is available with 1/6, 1/3 and 1/2 horsepower compressors depending upon the system requirements.

For FireLock NXT™ Series 768 Dry Valves, Series 769 Deluge and Preaction Valves, Series 764 Alternate Valves.

Note: The Series 7C7 Air Maintenance/Compressor Assembly is designed for systems that do not require an accelerator to achieve the required system pressure performance. If an accelerator is required, a tank-mounted compressor with a regulated air maintenance device should be used.

COMPRESSOR CAPACITIES

The engineer/system designer is responsible for sizing the compressor so that the entire system is charged to the required air pressure within NFPA guidelines (30 minutes). DO NOT oversize the compressor to provide more airflow. An oversized compressor will slow down or possibly prevent valve operation.

Hp

Nominal AC

Voltage/Hz (+/- 10%)

Pressurepsi/Bar

TimeMinutes

CapacityWITH

AutoVentgallons/m3

CapacityWITHOUTAutoVent

gallons/m3AmpDraw

1/6 110/6018 30 175 275 2.1 Amps1.2 0.7 1.1

1/3 110/6018 30 375 525

4.4 Amps

1.2 1.4 2.0

1/3 220/5018 30 160 2351.2 0.6 0.9

1/3 220/5018 60 450 6601.2 1.7 2.5

1/3 220/6018

30370 400

1.51.2 1.4

1/2 110/5018 30 660 670

6.6 Amps1.2 2.5 2.5

1/2 110/6018

30780 830

3.11.2 3.0

3/4 220/5018 30 600 675

3.8 Amps

1.2 2.3 2.5

3/4 220/6018

30700 775

2.91.2 2.7

3/4 220/5018

601200 1350

5.01.2 4.5

3/4 220/6018

601375 1525

5.81.2 5.2

NOTE: Refer to the charts on the following pages for minimum requiredfill capacities to 13 psi/0.9 Bar. Low air alarms will clear at 13 psi/0.9 Bar. Inaddition, these charts contain higher capacities to 18 psi/1.2 Bar that are notshown in the table above.

30.22_1

Air Maintenance/ Compressor AssemblySERIES 7C7

30.22FIRE PROTECTION PRODUCTS – DEVICES

JOB/OWNER CONTRACTOR ENGINEER

System No. ______________________________ Submitted By ____________________________ Spec Sect _______________ Para ___________

Location ________________________________ Date ___________________________________ Approved _______________________________

Date ___________________________________

www.victaulic.comVICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2013 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

REV_G

SERIES 7C7

ASSEMBLY DIMENSIONS

Series 7C7 - 1/3HP Compressor

Pipe Size A B C D

1 1/2” 14.53 5.00 6.55 15.382” 14.78 5.00 6.55 15.38

2 1/2” & 76.1 15.04 5.00 6.55 15.383” 15.36 5.00 6.55 15.384” 15.88 5.00 6.55 15.38

6” & 165.5 16.98 5.00 6.55 15.388” 18.02 5.00 6.55 15.38

Series 7C7 - 1/3HP Compressor Series 7C7 - 1/6HP Compressor

Series 7C7 - 1/6HP Compressor

Pipe Size A B C D

1 1/2” 14.53 4.60 6.55 15.382” 14.78 4.60 6.55 15.38

2 1/2” & 76.1 15.04 4.60 6.55 15.383” 15.36 4.60 6.55 15.384” 15.88 4.60 6.55 15.38

6” & 165.5 16.98 4.60 6.55 15.388” 18.02 4.60 6.55 15.38

A

B

C

D

A

B

C

DD

A

B

C

Series 7C7 - 1/2HP Compressor

Pipe Size A B C D

1 1/2” 14.5 4.8 6.55 15.542” 14.77 4.8 6.55 15.54

2 1/2” & 76.1 15.03 4.8 6.55 15.543” 15.36 4.8 6.55 15.544” 15.94 4.8 6.55 15.54

6” & 165.5 16.98 4.8 6.55 15.548” 18.01 4.8 6.55 15.54

Series 7C7 - 1/2HP Compressor

30.22

30.22_2

FIRE PROTECTION PRODUCTS – DEVICES

Air Maintenance/ Compressor Assembly

www.victaulic.comVICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2013 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

REV_G

SERIES 7C7

ASSEMBLY PERFORMANCE (1/2 HP Compressor) - For use with FireLock NXT Series 768 Dry, Series 764 Alternate wet/dry and 769 Deluge and Preaction systems.

18 psi

13 psi

System Size (gallons)

Tim

e (m

inut

es)

Estimated Time to Reach Various Pressures -Series 7C7 with 1/2-hp (110 VAC, 50 Hz) Compressor and Auto Vent

0

5

10

15

20

25

30

35

40

50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000

45

50

18 psi

13 psi

System Size (gallons)

Tim

e (m

inut

es)

Estimated Time to Reach Various Pressures -Series 7C7 with 1/2-hp (110 VAC, 60-Hz) Compressor and Auto Vent

0

5

10

15

20

25

30

35

40

50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200

0

10

20

30

40

50 18 psi

13 psi

System Size (gallons)

Tim

e (m

inut

es)

Estimated Time to Reach Various Pressures -Series 7C7 with 1/2-hp (110 VAC, 50 Hz) Compressor and No Auto Vent

50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100

0

10

20

30

40

50

18 psi

13 psi

System Size (gallons)

Tim

e (m

inut

es)

Estimated Time to Reach Various Pressures -Series 7C7 with 1/2-hp (110 VAC, 60 Hz) Compressor and No Auto Vent

25 75 125 175 225 275 325 375 425 475 525 575 625 675 725 775 825 875 925 975 1025 1075 1125 1175 1225

30.22

30.22_3

FIRE PROTECTION PRODUCTS – DEVICES

Air Maintenance/ Compressor Assembly

www.victaulic.comVICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2013 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

REV_G

SERIES 7C7

ASSEMBLY PERFORMANCE (1/3 HP Compressor) - For use with FireLock NXT Series 768 Dry, Series 764 Alternate wet/dry and 769 Deluge and Preaction systems.

0

10

20

30

40

50

60

System Size (cubic meters)

Tim

e (m

inut

es)

0.6 1.0 1.4 1.80.2 2.2 2.6 3.0

1.2 Bar 0.9 Bar

Estimated Time to Reach Various Pressures - 220-volt OptionSeries 7C7 with 1/3-hp (220-240 VAC, 50-Hz) Compressor and Auto Vent

0

10

20

30

40

50

60

System Size (cubic meters)

Tim

e (m

inut

es)

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0 2.2 2.4 2.6 2.8

1.2 Bar

0.9 Bar

Estimated Time to Reach Various Pressures - 220-volt OptionSeries 7C7 with 1/3-hp (220-240 VAC, 60-Hz) Compressor and Auto Vent

0

10

20

30

40

50

60

70

Estimated Time to Reach Various Pressures - 220-volt OptionSeries 7C7 with 1/3-hp (220 - 240 VAC, 50 Hz) Compressor and No AutoVent

Tim

e (m

inut

es)

System Size/Volume (cubic meters)

0 0.5 1.0 1.5 2.0 2.5 3.0

1.2 Bar

0.9 Bar

0

10

20

30

40

50

60

Estimated Time to Reach Various Pressures - 220-volt OptionSeries 7C7 with 1/3-hp (220 - 240 VAC, 60 Hz) Compressor and No Auto Vent

0 0.5 1.0 1.5 2.0 2.5 3.0

Tim

e (m

inut

es)

System Size/Volume (cubic meters)

1.2 Bar

0.9 Bar

0

10

20

30

40

50

60

System Size (Gallons)

Tim

e (M

inut

es)

50 100 150 200 250 300 350 400 450 500 550 600 650 700 750

Estimated Time to Reach Various Pressures - Series 7C7 with 1/3-hp (110 VAC) Compressor and Auto Vent

13 psi

18 psi

50 100 150 200 250 300 350 400 450 500 550 600 650 700 7500

10

20

3018 psi 13 psi

Estimated Time to Reach Various Pressures -Series 7C7 with 1/3-hp (110 VAC) Compressor and No Auto Vent

System Size (gallons)

Tim

e (m

inut

es)

NOTE: Refer to the following page for charts reflecting the 220-volt 1/3-hp option.

30.22

30.22_4

FIRE PROTECTION PRODUCTS – DEVICES

Air Maintenance/ Compressor Assembly

www.victaulic.comVICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2013 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

REV_G

SERIES 7C7

0

10

20

30

40

50

60

70

System Size (Gallons)

Tim

e (M

inut

es)

50 100 150 200 250 300 350 400

Estimated Time to Reach Various Pressures - Series 7C7 with 1/6-hp (110 VAC) Compressor and Auto Vent

13 psi

18 psi

50 100 150 200 250 300 350 4000

10

20

3018 psi 13 psi

Estimated Time to Reach Various Pressures -Series 7C7 with 1/6-hp (110 VAC) Compressor and No AutoVent

System Size (gallons)

Tim

e (m

inut

es)

ASSEMBLY PERFORMANCE (1/6 HP Compressor) - For use with FireLock NXT Series 768 Dry, Series 764 Alternate wet/dry and 769 Deluge and Preaction systems.

30.22

30.22_5

FIRE PROTECTION PRODUCTS – DEVICES

Air Maintenance/ Compressor Assembly

www.victaulic.comVICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2013 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

REV_G

SERIES 7C7

ExPLODED VIEW DRAWING - SERIES 7C7 AIR MAINTENANCE COMPRESSOR ASSEMBLY WITH 1/2-HP COMPRESSOR

1

4

23

6

14 2

3

107

14

11

To ActuatorTrim

9

8

5

15

1925

24

18

16

17

12

13

20

21

22

26

Bill of MaterialsItem Qty. Description 1 1 Compressor 2 1 Mounting Bracket 3 1 Series 757P Air Maintenance Trim Assembly with Pressure Switch 4 1 Stainless Steel Braided Flex Hose (½-inch NPT Male x Female) 5 2 Split Hanger for ½-inch Pipe 6 2 Hose Clamp 7 1 Close Nipple (¼-inch NPT) 8 3 Close Nipple (½-inch NPT) 9 3 90° Female Elbow (½-inch NPT) 10 2 Hex-Head Bolt (3⁄8 - 16 x 5⁄8-inch Long) 11 4 Lock Washer (5⁄16 inch) 12 2 Lock Washer (3⁄8 inch) 13 4 Hex Nut (¼ - 20 UNC) 14 2 Straight Conduit Connector (½-inch) 15 1 Liquid-Tight Conduit (½ inch x 9½ inches Long) 16 1 14 AWG, 3-Strand Cable (25 inches Long) 17 3 #8 U-Style Wire Connector 18 1 Identi�cation Tag 19 1 Compressor Air Intake Filter 20 1 Nipple (½-inch NPT x 10 inches Long) 21 1 Nipple (½-inch NPT x 4½ inches Long) 22 1 Union (½-inch NPT) 23 1 Reducing Bell (½-inch NPT x ¼-inch NPT) 24 1 14 AWG Grounded Cord with Plug (5½ feet Long)* 25 1 Strain Relief Connector* 26 1 Identi�cation Label*

* NOTE: Items 24 - 26 apply only to the CSA version

Exaggerated for Clarity

30.22

30.22_6

FIRE PROTECTION PRODUCTS – DEVICES

Air Maintenance/ Compressor Assembly

www.victaulic.comVICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2013 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

REV_G

SERIES 7C7

ExPLODED VIEW DRAWING - SERIES 7C7 AIR MAINTENANCE COMPRESSOR ASSEMBLY WITH 1/6-HP COMPRESSOR

1

4

7

5

6

11

13

2

3

8

19

10

To ActuatorTrim

16

9

512

14

1517 18

20

21

22

23

2425

26

Bill of MaterialsItem Qty. Description 1 1 Compressor 2 1 Mounting Bracket 3 1 Series 757P Air Maintenance Trim Assembly with Pressure Switch 4 1 Stainless Steel Braided Flex Hose (½-inch NPT Male x Female) 5 2 Split Hanger for ½-inch Pipe 6 2 Hose Clamp 7 3 90° Female Elbow (½-inch NPT) 8 1 Close Nipple (¼-inch NPT) 9 2 Close Nipple (½-inch NPT) 10 2 Hex-Head Bolt (3⁄8 - 16 x 5⁄8-inch Long) 11 3 Hex-Head Bolt (#10 - 32 x ½-inch Long) 12 2 Lock Washer (3⁄8 inch) 13 3 Lock Washer (#10) 14 1 Identi�cation Tag 15 1 Straight Connector, Flexible Cord 16 1 Connector, Flexible Cord 17 1 Liquid-Tight Conduit (½ inch x 11½ inches Long) 18 3 #8 U-Style Wire Connector 19 1 Reducing Bell (½-inch NPT x ¼-inch NPT) 20 1 Nipple (½-inch NPT x 1½ inches Long) 21 1 Nipple (½-inch NPT x 9 inches Long) 22 1 Union (½-inch NPT) 23 1 Nipple (½-inch NPT x 5 inches Long) 24 1 Identi�cation Label* 25 1 Strain Relief Connector* 26 1 14 AWG Grounded Cord with Plug (5½ feet Long)*

* NOTE: Items 24 - 26 apply only to the CSA versionExaggerated for Clarity

ExPLODED VIEW DRAWING - SERIES 7C7 AIR MAINTENANCE COMPRESSOR ASSEMBLY WITH 1/3-HP COMPRESSOR

1

4

25

6

23

2

3

7

To ActuatorTrim

9

8

5

10

11

12

13

14

15

16

17

1819 20 21

22

24

26

27

Bill of MaterialsItem Qty. Description 1 1 Compressor 2 1 Mounting Bracket 3 1 Series 757P Air Maintenance Trim Assembly with Pressure Switch 4 1 Stainless Steel Braided Flex Hose (½-inch NPT Male x Female) 5 2 Split Hanger for ½-inch Pipe 6 2 Hose Clamp 7 1 Close Nipple (¼-inch NPT) 8 2 Close Nipple (½-inch NPT) 9 3 90° Female Elbow (½-inch NPT) 10 4 Hex-Head Bolt (5⁄16 - 18 x ¾-inch Long) 11 2 Hex-Head Bolt (3⁄8 - 16 x 5⁄8-inch Long) 12 4 Lock Washer (5⁄16 inch) 13 2 Lock Washer (3⁄8 inch) 14 4 Hex Nut (5⁄16 - 18) 15 2 Straight Conduit Connector (½ inch) 16 1 Liquid-Tight Conduit (½ inch x 9½ inches Long) 17 2 14 AWG, 3-Strand Cable (25 inches Long) 18 3 #8 U-Style Wire Connector 19 1 Identi�cation Tag 20 1 Reducing Bell (½-inch NPT x ¼-inch NPT) 21 1 Nipple (½-inch NPT x 1½ inches Long) 22 1 Nipple (½-inch NPT x 5½ inches Long) 23 1 Nipple (½-inch NPT x 9½ inches Long) 24 1 Union (½-inch NPT) 25 1 14 AWG Grounded Cord with Plug (5½ feet Long)* 26 1 Strain Relief Connector* 27 1 Identi�cation Label*

* NOTE: Items 25 - 27 apply only to the CSA versionExaggerated for Clarity

30.22

30.22_7

FIRE PROTECTION PRODUCTS – DEVICES

Air Maintenance/ Compressor Assembly

www.victaulic.comVICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2013 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

REV_G

SERIES 7C7

WARNING

�•� This�product�must�be�installed�by�an�experienced,�trained�installer,�in�accordance�with�the�instructions�provided�with�each�valve.�These� instructions contain important information.

Failure�to�follow�these�instructions�may�result�in�serious�personal�injury,�property�damage,�or�valve�leakage.

If�you�need�additional�copies�of�this�product�literature�or�the�valve��installation�instructions,�or�if�you�have�any�questions�about�the�safe�installation�and�use�of�this�device,�contact�Victaulic�Company,�P.O.�Box�31,�Easton,�PA�18044-0031�USA,�Telephone:�001-610-559-3300.

WARNING

WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details.

This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations.

NOTE

ELECTRICAL INFORMATION

DANGER•� Only�qualified�electricians�should�connect�

incoming�power�to�the�Series�7C7�Air�Maintenance/Compressor Assembly.

•� To�reduce�the�risk�of�electric�shock,�check�the�electrical�source�for�proper�grounding.

Failure�to�follow�these�instructions�could�result�in�death�or�serious�personal�injury.

Ground Connection

ELECTRICAL CONNECTION

LINE LOAD LINELOAD

L1 L2

L 1 T 1 T 2 L 2

T 1 T 2

MOTOR

INCOMING POWER SUPPLY(REFERENCE COMPRESSOR

DATA PLATE)

NOTE: NEMA 1 Enclosure - intended only for indoor use

Only qualified electricians should make the connection to the incoming power supply. All wiring shall be completed in accordance with requirements of the local authority having jurisdiction and any applicable electrical codes.

30.22

Air Maintenance/ Compressor Assembly

30.22FIRE PROTECTION PRODUCTS – DEVICES

For complete contact information, visit www.victaulic.com30.22����4847�REV G UPDATED 02/2013VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2013 VICTAULIC COMPANY. ALL RIGHTS RESERVED.

SERIES 7C7