Pneumatic Actuated with Local Reset Deluge Valve Deluge Systems ADVANTAGES CHARACTERISTICS The FDV is a Fire Protection control valve for Deluge fire sprinkler systems, designed for installations in hazardous environments. The FDV-DP0 Deluge system is actuated pneumatically and resets locally. When the pneumatic dry pilot detection line is exposed to flame heat, its automatic fire sprinklers shatter-open, while venting the air pressure from the FDV-DP0’s actuator, commanding the deluge valve to open. The Deluge system incorporates an emergency valve, bypassing the fire detection systems for manual operation. Designed for vertical or horizontal installation, a globe pattern, line pressure operated FDV-DP0 valve features a direct elastomeric diaphragm seal. It has no balancing spring or internal metallic wet components in the valve body. The hydrodynamic pattern design, ensures high flow rates with minimum head loss. Only three parts: body, diaphragm & cover plate. No wet metal spring inside the control chamber Full bore unobstructed Simple manual reset of the valve to standby position without draining or opening the valve itself, neither closing OS&Y or other valves in the system Open fail safe valve, maintained in stand-by closed position Low maintenance cost: the valve is serviced in-line with only one replaceable part which is long life elastomeric diaphragm Conforms with inspection, testing and maintenance standard of water-based fire protection systems, NFPA 25 Hydro-dynamic pattern design ensures high flowrates with minimum head loss The valve trips open automatically upon a gradual release of water pressure from its control chamber. The trip is actuated by Dry Pilot Line’s pneumatic pressure release due to its exposure to flame heat Soft closing upon pressurization of the valve’s control chamber, by line pressure or other independent water source, prevents surges FDV - DP0 Fire Protection MARKETS TECHNICAL DATA Commercial Residential 21 The FDV-DP0 resets to stand-by close position by pressurizing the Dry Pilot Line and manually operating the PSA device. FLUID: Water, Brackish water, Sea water, Foam SIZE RANGE: 40mm to 250mm (1½’’ to 10”) AVAILABLE CONNECTIONS ENDS: Flange*Flange, Groove*Groove, Flange*Groove, Groove*Flange, Thread*Thread PRESSURE NOMINAL: 250 psi (17.2 bar) Marine APPROVALS P.O.G. Industry

Fire Protection Deluge Systems Pneumatic Actuated with ... Deluge... · Pneumatic Actuated with Local Reset Deluge Valve Deluge Systems ADVANTAGES ... The FDV-DP0 resets to stand-by

  • Upload
    lamcong

  • View
    292

  • Download
    4

Embed Size (px)

Citation preview

Pneumatic Actuated with Local Reset Deluge Valve

Deluge Systems

ADVANTAGES

CHARACTERISTICS

The FDV is a Fire Protection control valve for Deluge fire sprinkler systems, designed for installations in hazardous environments. The FDV-DP0 Deluge system is actuated pneumatically and resets locally. When the pneumatic dry pilot detection line is exposed to flame heat, its automatic fire sprinklers shatter-open, while venting the air pressure from the FDV-DP0’s actuator, commanding the deluge valve to open.The Deluge system incorporates an emergency valve, bypassing the fire detection systems for manual operation.Designed for vertical or horizontal installation, a globe pattern, line pressure operated FDV-DP0 valve features a direct elastomeric diaphragm seal. It has no balancing spring or internal metallic wet components in the valve body. The hydrodynamic pattern design, ensures high flow rates with minimum head loss.

Only three parts: body, diaphragm & cover plate. No wet metal spring inside the control chamber Full bore unobstructedSimple manual reset of the valve to standby position without draining or opening the valve itself, neither closing OS&Y or other valves in the systemOpen fail safe valve, maintained in stand-by closed positionLow maintenance cost: the valve is serviced in-line with only one replaceable part which is long life elastomeric diaphragm Conforms with inspection, testing and maintenance standard of water-based fire protection systems, NFPA 25

Hydro-dynamic pattern design ensures high flowrates with minimum head lossThe valve trips open automatically upon a gradual release of water pressure from its control chamber. The trip is actuated by Dry Pilot Line’s pneumatic pressure release due to its exposure to flame heatSoft closing upon pressurization of the valve’s control chamber, by line pressure or other independent water source, prevents surges

••

FDV - DP0Fire

Pro

tect

ion

M A R K E T S

T E C H N I C A L D ATA

Commercial Residential

21

The FDV-DP0 resets to stand-by close position by pressurizing the Dry Pilot Line and manually operating the PSA device.

FLUID:Water, Brackish water, Sea water, Foam SIZE RANGE:40mm to 250mm (1½’’ to 10”)AVAILABLE CONNECTIONS ENDS:Flange*Flange, Groove*Groove, Flange*Groove, Groove*Flange,Thread*ThreadPRESSURE NOMINAL:250 psi (17.2 bar)

Marine

A P P R O VA L S

P.O.G. Industry

Schematic drawing

OPERATION

SET positionPressurized water in the valve’s control chamber (DL) is trapped by the closed PSA (PA), the closed PA-PTC actuator (PC) and by the closed emergency valve (EU), maintaining the FDV Deluge valve (DL) closed.

FIRE situationWhen some of the Dry Pilot detection line’s automatic fire sprinklers are subjected to flames heat and shatter-open, the pilot detection line depressurizes the PA-PTC control chamber. The PA-PTC (PC) opens and drains the deluge valve’s control chamber.The FDV deluge valve opens and admits water to the spray sprinklers line.

RESET positionSystem reset requires the replacement of all the Dry Pilot detection Line’s shattered-open automatic fire sprinklers.The detection line is then pressurizing together with the PA-PTC actuator, to reset it to closed position.The PSA (PS) push button should be pressed to enable the control chamber filling, closing the FDV deluge valve.

Set position Fire position

Fire

Pro

tect

ion

TALI

S FP

RAN

GE

22

BF - Butterfly valveDL - FDV Deluge valveAL - Acoustic & Electric alarmsTS - Trim supply valve

SR - “Y” strainerCV - Check valvePS - PSA – Pressure Supply ArrestorMA - MADV – Man/Auto Drain Valve

TV - Alarm test valveEU - Emergency Manual UnitPC - PA-PTC – PneumaticActuator-Pressure to Close

Fire

Pro

tect

ion

23

FDV - DP0Typical installation

MD

PC

PS

CVSRTV

TS

AL

DL

EU

BF

BF - Butterfly valveDL - FDV Deluge valveAL - Acoustic & Electric alarmsTS - Trim supply valve

SR - “Y” strainerCV - Check valvePS - PSA – Pressure Supply ArrestorMA - MADV – Man/Auto Drain Valve

TV - Alarm test valveEU - Emergency Manual UnitPC - PA-PTC – PneumaticActuator-Pressure to Close

Fire

Pro

tect

ion

TALI

S FP

RAN

GE

24

Dimensions Table

Vertical

A 314 384 300 11.8 327 12.9268 231 220

630.8 296 11.7

94 84 2.5 61 2.4

12.4 15.210.5 93.7 3.38.8 12.84.6 2.66.5 76.740.7

7.968

224 325 462 18.2 580 22.8117 66 -164 180 230 9 254 1017018.5

20030.8

3952447340040

20624047.7

30266.2

11.9146

335105.8

13.2233.3

15.59.62.915.81.68.19.5

105.2

BCDEFG

Kg/lb

Size1 1/2” 2” 3”

mm mm mm mm mmInch Inch Inch Inch Inch

4” 6” 8”

Size1 1/2” 2” 3”

mm mm mm mm mmInch Inch Inch Inch Inch

4” 6” 8”

Horizontal

A 314 381 420 16.5 398189 201 240

-9.5 268

- 31 - -

12.4 157.4 7.9- 1.2

8.8 12.85 1.9

6.5 78.242

9.468

224 325 462 18.2 580127 47 - - -164 180 231 9 25720919

23930.8

395215-

40013

20727847.7

34166.4

13.4146.5

374105.7

15.710.5

-228

-10.214.7

223.2

15.68.5-

15.80.58.510.9105.2

BCDEFG

Kg/lb

PIPING & TUBING:

Stainless Steel 316

Copper/Brass

Cupro-Nickel

Monel®

FITTINGS:

Stainless Steel 316

Brass

Super Duplex

Cupro-Nickel

Monel®

ACCESSORIES:

Brass Nickel plated

Nickel Aluminium bronze

Stainless steel CF8M

Monel®

Cupro-Nickel

TRIM

BODY & COVER

Ductile iron

Cast Steel WCB

Stainless Steel CF8

Stainless Steel CF8M

Nickel Aluminum Bronze

ELASTOMERS:

NBR, 3 layer reinforced natural rubber

EPDM, 3 layer reinforced

COATING:

Rilsan Polyamide based (Nylon 11)

Polyester based EPC

High built Epoxy FBE

Vitreous Enamel (internal only)

MAIN VALVE:

Factory Standard

Working Media

Ambiental conditions

Min/Max operating flow

Min/Max operating pressure

Energize to Open/Close valve

Pneumatic working pressure

System installation orientation

Additional accessories needed

PLEASE SPECIFY

For more detailed technical information, please refer to chapter Engineering Data.