Fire extinguishing system - fire main 0725 The most common detainable items are (i) malfunctioning, (ii) leaking, (iii) blocked nozzles and (iv) missing servicing documentation. The fire main pipe system is intact and properly maintained, free from leakage or temporary patches. Fire hydrants and valves are in good condition. The fire main isolating valves are operable and indentified. Fire hose boxes contain all required equipment (fire hose, nozzle and spanner). Fire hose boxes are located as per Fire Control Plan and marked with IMO symbols. Fire hoses are periodically pressure tested with dates recorded. Hoses are free from leaks. Length of fire hoses as required. Responsible officer is assigned for maintenance and inspection. Records for testing and maintenance are readily available. Approved by ............................................

Fire extinguishing system - 0725 fire main · PDF fileMain0740 fire pump The most common detainable items are (i) ... Fire extinguishers – portable 0730 Recorded deficiencies include

Embed Size (px)

Citation preview

Fire extinguishing system -fire main0725

The most common detainable items are (i) malfunctioning, (ii)leaking, (iii) blocked nozzles and (iv) missing servicingdocumentation.

The fire main pipe system is intact and properly maintained,free from leakage or temporary patches.

Fire hydrants and valves are in good condition.

The fire main isolating valves are operable and indentified.

Fire hose boxes contain all required equipment (fire hose,nozzle and spanner).

Fire hose boxes are located as per Fire Control Plan and markedwith IMO symbols.

Fire hoses are periodically pressure tested with dates recorded.

Hoses are free from leaks.

Length of fire hoses as required.

Responsible officer is assigned for maintenance and inspection.

Records for testing and maintenance are readily available.

Approved by ............................................

Main fire pump0740

The most common detainable items are (i) malfunction, (ii)insufficient pressure and (iii) corrosion of the pump.

Tested and confirmed to be in good working condition. Numberof pumps as required.

Power supply correct.

Pipe connection flanges are in good condition and free fromleaks.

Pressure gauges are in good working condition.

Start/Stop from different locations as per Fire Control Plan (asapplicable).

Delivery water pressure (outlet) is sufficient as per regulations.

Working performance test is carried out.

Maintenance, test and training records are available.

Records showing drills, training and instructions of responsiblepersonnel are readily available.

Responsible officer is assigned for maintenance and inspection.

Approved by ............................................

Means of control(opening/closure of skylight,pump and machinery spaces)

0741

The most common detainable item is malfuction of quick closingvalves for fuel system. Below checklist covers measures toisolate/secure machinery spaces.

Local and remote closing mechanisms are well maintained andin good working condition.

Operating control points are clearly marked/identified and crewis familiar with their location.

For manually operated systems, means must be provided forstopping fuel oil unit and transfer pumps.

Locking and hold-back (as applicable) arrangements are ingood condition.

Responsible officer is assigned for maintenance and inspection.

Periodically inspected and maintained as per plannedmaintenance system.

In case of malfunction, repaired or renewed immediately.

Crew is familiar with operating procedures.

Approved by ............................................

Fire extinguishing system -gas system0725

Recorded deficiencies are related mostly to hydrotesting ofcylinders and flexible hoses.

Annual Inspection by competent technician.

All flexible hoses are properly attached.

System is ready for immediate use

Control valves marked.

Cylinders hydro tested according to Flag Administration'srequirements.

Responsible officer assigned for inspection.

Records and certificates of inspection readily available.

Approved by ............................................

Fire doors0714

The most common detainable items are (i) malfunctioning doors,(ii) damaged doors or (iii) defective closing devices.

Free from unauthorized hold-back arrangements.

Free from obstructions.

Closing and latching mechanism working properly.

General good condition of structural parts (frames and doors).

Responsible officer is assigned for maintenance and inspection.

Records of inspection and maintenance available.

Approved by ............................................

Personal equipment0735

Recorded deficiencies include (i) unacceptable condition offacemasks and (ii) insufficient pressure in the airbottles.

Fireman outfits are in good condition and type approved.

Fire fighting outfits are appropriately sized to fit designatedcrew.

Breathing apparatus (BA) sets are in good condition.

All air bottles are fully charged (including all spares).

Low pressure alarm on BA operating correctly.

Quantity of outfits and BA as per Fire Control Plan.

Torch and radio fully charged.

Equipment stowed in the appropriate fire station, ready for use.

Easy access without obstruction to the fire stations andequipment.

Crew are familiar and trained in the use of the equipment andrequired procedures.

Responsible officer is assigned for maintenance and inspection.

Records available showing periodical inspections andmaintenance as per manufacturer's recommendations.

Approved by ............................................

Fire extinguishers –portable0730

Recorded deficiencies include (i) not properly maintained and (ii)missing service report.

Placed in accordance with the Fire Control Plan, easy to access,free from obstructions and ready for use.

Extinguishers are in good condition, without corrosion and withsufficient pressure level.

All markings and labels are clearly visible and readable.

Spare charges/cartridges are available onboard as perrequirements.

Crew trained to operate and familiar with their location.

Onboard periodical inspections are carried out within due dates.Records are readily available for review.

Periodical inspection,as per flag state requirements, byauthorized service technician is carried out.

Responsible officer is assigned for maintenance and inspection.

Records of periodical inspections are readily available.

Approved by ............................................

Fire detection system0715

The most common detainable items are (i) panel in faultycondition, (ii) disconnected loops and detectors and (iii) back upbattery/power supply failure under black out condition.

The main control panel/unit is in good working condition.

The crew is familiar with and able to operate the system.

Local sensors at required positions.

All sensors are clean, unobstructed and in good workingcondition.

Operating procedures are available in the working language ofthe crew.

Overriding procedures are defined and there are NOunauthorized overriding or cancelling of alarms.

Responsible officer is assigned for maintenance and inspection.

Approved by ............................................

Fire dampers0743

The most common detainable item is malfunctioned or corrodeddampers.

Ventilation flaps and dampers moving freely with all parts inplace.

Crew familiar with operation of fire dampers.

Dampers/ducts preferably marked, indicating clearly whichspace the damper serves.

Operating handles and stoppers are in good working condition.

Responsible officer is assigned for maintenance and inspection.

Periodic maintenance and required tests of local and remoteoperation carried out.

Open/Close positions are properly marked.

Approved by ............................................

Fire extinguishers –portable0730

Recorded deficiencies include (i) not properly maintained and (ii)missing service report.

Placed in accordance with the Fire Control Plan, easy to access,free from obstructions and ready for use.

Extinguishers are in good condition, without corrosion and withsufficient pressure level.

All markings and labels are clearly visible and readable.

Spare charges/cartridges are available onboard as perrequirements.

Crew trained to operate and familiar with their location.

Onboard periodical inspections are carried out within due dates.Records are readily available for review.

Periodical inspection,as per flag state requirements, byauthorized service technician is carried out.

Responsible officer is assigned for maintenance and inspection.

Records of periodical inspections are readily available.

Approved by ............................................

Emergency fire pump0739

The most common detainable items are (i) malfunction, (ii)insufficient pressure and (iii) corrosion of the pump.

Pump in good working condition, tested and ready forimmediate use.

Pump is free from leakage (seawater, hydraulic oil etc.)

Delivery water pressure (outlet) is sufficient to operate 2 firehoses simultaneously.

Start/Stop from local and/or remote position clearly marked.

Operating instructions in the working language of the crew areposted at appropriate locations.

Records showing instructions,drills and training of responsiblepersonnel are readily available.

Responsible officer is assigned for maintenance and inspection.

Maintained as per manufacturer's recommendations withrecords readily available.

Approved by ............................................