    03 AUTOMATION

    FIRE DETECTION UNITITDAC-14P-4

    Fire detection system is one of the most important marine systems, since its functionality is directly connected with thesafety of people and equipment. As such, it must provide reliable notification of f ire and warn the responsible persons, inorder to prevent fire spreading and potential catastrophic consequences.

    Inelteh's fire detection unit ITDAC-14P-4 features:

    conventional fire detection system4 fire detection linesautomatic and/or manual alarm output activationseparate and independent outputs for crew and passengersoutputs 24V DC - fire bells can be directly connected

    type approved by Croatian Register of Shipping

    OUTPUT CONTACTfor VENTILATIONBLOCKING

    MANUAL CALL

    POINTS

    IN CASE OF FIRE

    BREAK GLASS

    IN CASE OF FIRE

    BREAK GLASS

    SMOKE

    DETECTORS

    HEAT

    DETECTORS

    FIRE DETECTION UNIT

    ITDAC-14P-4

    OUTPUT FOR BELLS IN CREW'S AREA

    OUTPUT FOR BELLS IN PASSENGERS' AREAPOWER SUPPLY: 24V DC

    24V DC

    24V DC

    4 lines

    LINE FAILURE

    POWER

    FAILURE

    ALARM OUTPUT

    ACTIVATED

    POWER

    TEST

    ITDAC-14P-4FIRE DETECTION UNITRIJEKA - CROATIA

    ALARMCREW

    ALARMPASSENGERS

    LINE 4

    LINE 3

    LINE 2

    LINE 1

    All dimensions are in mm.

    FIRE DETECTION UNIT ITDAC-14P-4

    power supply: 24V DC (18-32V DC) current consumption (without bells ): 200mA max. number of smoke and heat detectors in single line: 17 max. number of manual call points in single line is unlimited power failure signalization: LED + buzzer; built-in battery with automatic charging

    output contact for ventilation blocking: Voltage-free contact 5A/250V AC, activated as long as one of f ire detectors is in alarm state and/or whenalarm output is manually activated

    alarm output for crew: output 24V DC 1A max; activation: automatically (after 2 min if alarm isn't accepted) and/or manually alarm output for passengers: 24V DC 1A max; activation: manually flush (IP22, weight: 0.9kg) or bulkhead (IP54, weight: 7kg) mounting

    ENGINEERING FOR ELECTRONIC EQUIPMENT AND SYSTEMS

    144

    300

    320

    144

    300

    260

    DEPTH IS 107mm.

    138

    138 CONSOLE

    CUT-OUT

    30

    1658

    7xPG13.5+1xPG16

  • 8/11/2019 fire dec

    2/2

    OPTICAL SMOKE DETECTOR

    BELL CEADEL 165

    power supply: 8.5-33V DC quick and reliable detection of smoke on the light scatter principle performs well in detecting black and white smoke with LED indication bulkhead mounting or wall mounting (on box with cable glands)

    approved for use in marine environment by GL, DNV, BV, LR, ABS, CCS IP protection: according to EN 54-7:2000

    MANUAL CALL POINT

    conventional, with voltage-free contact and resistor elementtest-key for alarm simulation construction: ABS spare glass (on request) bulkhead mounting for indoor (IP42) or outdoor (IP66) use weight: 0.36kg (IP42 version) or 0.46kg (IP 66 version)

    power supply: 24V DC current consumption: 0.3A sound pressure: 98dB / 1m IP protection: IP66 weight: 1.6kg

    for applications where smoke detectors are unsuitable in environments that are dirty or smoky under normal conditions for temperature 65C or for temperature 80C (kitchen) power supply: 8.5-33V DC quick and reliable sensing of air temperature, using single thermis tor with LED indication bulkhead mounting or wall mounting (on box with cable glands) approved for use in marine environment by GL, DNV, BV, LR, ABS, CCS IP protection: according to EN 54-7:2000

    HEAT DETECTOR

    2xPG13.5

    O6

    220

    204

    120

    82

    for wall mounting

    DEPTH: 132; WEIGHT: 0.7kg

    All dimensions are in mm.

    6.5

    13

    91

    DEPTH: 76

    IN CASE OF FIRE

    BREAK GLASS

    110 (for IP66)

    110(forIP66)

    87 (for IP42)

    87(forIP42)

    2xPG13.5

    DEPTH: 53 (for IP42)

    or 65 (for IP66)

    O100

    72

    O5

    52

    for bulkhead mounting

    WEIGHT: 0.14kg

    Optical smoke and heatdetectors, dimensions:

    Ljubljanska cesta 7, HR-51000 Rijeka / Croatia / tel. ++385 51 274 536 / fax 712 122 / [email protected] / www.inelteh.hr

    O168